Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

G NET Catalogue1

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

G-NET

1 kVA-10 kVA

Rack & Tower UPS


G-NET 1 kVA-10 kVA
Rack & Tower UPS
The Gnet Rack &Tower series of UPS systems is a line of an advanced
true on line UPSs which provide clean, reliable and regulated AC power to
perfectly adapt to user needs.

The series ranges from 1-10 kVA


available both in rack and tower design.
The 6 -10 models adopt rack tower
design as standard 19" and 2 U design
when changed into a tower model . This
alternation is made by simply revolving
the unit and LCD display.

The G-Net is an advanced, true online Uninterruptible Power Supply (UPS) providing reliable, regulated and stable voltage to
any type of load, from computers and telecommunication systems to automated industrial control systems. The GNet UPS
is available in various models of up to 10 kVA.

Voltage surges, spikes and sags are inherent in commercial utility power. Over time, these irregularities shorten the life of
the equipment and components. The G-Net UPS continually eliminates power irregularities, thus helping extend the life of
your equipment, even through normal use when the input power is constant and continuous.

The G-Net 6 - 10 kVA is designed so that it can be deployed horizontally or vertically. When deployed horizontally, it fits in a
standard 19” rack, and is 2U in height.

When deployed vertically, the control screen can be physically rotated 90 degrees for easy use in either position.

Features Available models


• True on line sine design, pure sine wave output without • 1-3 kVA tower or rack
pollution.
• 6 kVA with external battery cabinet tower or rack
• Intelligent DCP/CPU design with 0.98 PFC.
• 10 kVA with external battery cabinet tower or rack
• Zero transfer time ensuring the reliability of the load
operation.

• Local and remote control capability with RS232 or USB


port compatible with SNMP.

• Self diagnosis and protection function.

• Peak value of current and short circuit protection design.


GNET TECHNICAL SPECIFICATIONS
GNET TECHNICAL SPECIFICATIONS 1kVA 2kVA 3kVA 6kVA 10kVA
Topology True on-line, double-conversion, VFI
Operation Continuous
INPUT
Voltage (nominal, Vac) 220, single-phase
Voltage range (Vac) 160 ~ 276
Current, max. (A) 7 12 16 31 50
Frequency (Hz) 50
Power factor (full load) 0.98
OUTPUT
Rated power (kVA / kW) 1 / 0.8 2 / 1.6 3 / 2.4 6 / 4.8 10 / 8
Frequency (Hz) 50
Frequency range (%) ±1 (battery mode)
Voltage (Vac) 220±1 %, single-phase
Current (A) 5.4 9.6 13 27 45
105 % ~ 130 % transfer to bypass after 1 minute
Overload
>130 % transfer to bypass after 1 sec, no output after 1 min.
Waveform Sinusoidal
THD (%) <2 for linear load
Load CF (max) 3:1
Power factor 0.8
BATTERIES (see also Battery pack specifications)
Type Sealed, lead acid, rechargeable, maintenance-free
GENERAL
Ambient temperature (°C) -10 to +40 (operating and storage)
Relative humidity (%) 95 max. (non-condensing)
Altitude (m) 1000 without derating (derating table below)
Cooling system Forced air (multi-fan with speed control)
LCD DISPLAY
Input Voltage, current
Output Voltage, frequency, current
Batteries Voltage
Log (events memory) Last 200 events
STANDARDS
Safety IEC 62040-1
EMC IEC 62040-2
Design IEC 62040-3
Low magnetic field radiation EMF as per ICNIRP
WEIGHTS AND DIMENSIONS FOR UPS, W/O EXTERNAL BATT. PACK FOR EXTENDED BACKUP
7.5 (12.5 with 29.5 (includes. 30.5 (includes
UPS weight (kg)
internal batts.) internal batts.) internal batts.)
UPS dimensions (H x W x D, mm) 218x145x402 350 x 193 x 450 350 x 193 x 450
WEIGHTS AND DIMENSIONS FOR 19” MODELS
9 (14.5 with
UPS wgt (kg) 11 12 18 19
internal batts.)
UPS dimensions (H x W x D, mm) 85 x 430 x 680

BATTERY PACK SPECIFICATIONS


MODEL NUMBER AND TYPE OF BATTERIES CABINET DIMENSIONS (HXWXD, MM) WEIGHT (KG)
72 V battery pack 6 x 12 V, 7 Ah 85 x 430 x 480 18
96 V battery pack 8 x 12 V, 7 Ah 85 x 430 x 480 22
192 V battery pack 16 x 12 V, 7 Ah 85 x 430 x 680 42

DERATING FACTORS
MODEL
Altitude (m) 1000 1500 2000 2500 3000 3500 4000 4500 5000
Derating factor 100 % 95 % 91 % 86 % 82 % 78 % 74 % 70 % 67 %

* All specifications are subject to change without notice.


GAMATRONIC ELECTRONIC INDUSTRIES LTD.
Headquarters and Factory
17 Hartom St. POB 45029, Jerusalem 91450, Israel
Tel: +972-2-5888222 Fax: +972-2-5828875
e-mail: info@gamatronic.co.il

Gamatronic UK Ltd.
15 Chester Road, Colmworth Business Park, Eaton Socon,
Cambridgeshire, PE19 8YT, United Kingdom Tel: +44
(0)1480 479889/ 472665 Fax: +44(0)1480 407865
info@gamatronic.net
www.gamatronic.com

November 2012