Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

S&C Spec Sheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 32

S&C Manual PMH Pad-Mounted Gear

Outdoor Distribution (14.4 kV and 25 kV)

Specifications

set of fuses where required to achieve published BIL rat-


Conditions of Sale ings. Additional barriers of fiberglass-reinforced polyester
STANDARD: Seller’s standard conditions of sale set forth separate front and rear compartments and isolate the tie
in Price Sheet 150 apply, except as modified under “WAR- bus (where furnished). Full-length steel barriers separate
RANTY QUALIFICATIONS” on page 3. adjoining compartments (where applicable).
These PMH models are provided with a Grappler† (S&C
SPECIAL TO THIS PRODUCT: fuse handling fitting), if applicable; an instruction manual
holder; and storage racks in the fuse-compartment doors
INCLUSIONS: S&C Manual PMH Pad-Mounted Gear fea- for spare S&C Fuse Units or Refill Units and for the Grap-
tures directly operable accessible components. Switches pler (storage for Fault Fiter Electronic Power Fuses or
and fuses are clearly visible. Manual PMH models contain current-limiting fuses cannot be provided in these racks).
600-ampere external handle-operated S&C Mini-Rupter® A folding switch-operating handle, secured inside the
Switches for three-pole live switching of three-phase switch-operating-hub pocket, is provided for each Mini-
source circuits, and 200-ampere hookstick-operated S&C Rupter Switch. Terminal pads can accommodate a variety
Power Fuses with Uni-Rupter† for single-pole live switch- of cable-terminating devices for cable sizes through 1000 kc
ing of single-phase or three-phase load circuits. (These mil for switch and bus terminals, 4/0 maximum for fuse
models offer a choice of S&C Power Fuses—Types SML-20 terminals. Each switch, fuse, and bus terminal is provided
and SML-4Z, or S&C Fault Fiter® Electronic Power Fuses. with a ground stud as is each ground pad.
Fault Fiter Electronic Power Fuse Mountings also accom- All terminal pads can accommodate a variety of cable-
modate a variety of single-barrel current-limiting fuses as terminating devices for cable sizes through 1000 kc mil for
listed on page 19.) switch terminals, 4/0 maximum for fuse terminals. The
Enclosures meet the requirements of ANSI C57.12.28 cable-terminating devices must be equipped either with an
(enclosure integrity). They are of free-standing, self-sup- offset spade-type compression terminal for bolting directly
porting construction—not for bolting directly to trans- to the terminal pad or with a rod-type compression termi-
formers—with provisions for cable entrance and exit nal for attachment to a connector of the type shown on
through the bottom. Access to medium voltage is con- page 20. For applications where additional height is desired
trolled by the S&C Penta-Latch® Mechanism. The Penta- for increased elevation of ungrounded parts above the
Latch Mechanism provides automatic door latching and mounting pad, and to facilitate cable pulling and makeup
permits padlocking only when the door is securely latched. of cable-terminating devices, particularly where no cable
The door can be opened only with a pentahead socket pit is used, base spacers are available as listed on page 10.
wrench or tool. While the interior of S&C Pad-Mounted Gear is pro-
The enclosure roof is undercoated with an insulating tected from direct exposure to the elements, it is inherently
“no-drip” compound. A resilient closed-cell gasket on the an outdoor environment—and requires selection and appli-
enclosure bottom flange protects the finish from being cation of cable-terminating devices accordingly. Termina-
scratched during installation and isolates it from the alka- tions must incorporate adequate leakage distance between
linity of a concrete foundation. Enclosures are protected the exposed conductor and the stress-relief cone across a
from corrosion by S&C’s olive green Ultradur® Finishing surface of nontracking material (or a surface rendered
System. nontracking by properly taping with a suitable material).
A dual-purpose front barrier of fiberglass-reinforced Furthermore, to maintain the rated BIL, the following mini-
polyester is provided for each switch and fuse. Where the mum clearances are required: 6 inches at 14.4 kV and
National Electric Safety Code (ANSI Standard C2) applies, 7¹⁄₂ inches at 25 kV from energized parts to electrical
these barriers meet the requirements of Section 381G. ground; 1 inch at 14.4 kV and 2¹⁄₄ inches at 25 kV from ener-
When the switch or fuse is in the open position, this barrier gized parts to fiberglass-reinforced polyester barriers;
can be inserted into the open gap to guard against inadver- ¹⁄₂ inch at 14.4 kV and 1¹⁄₄ inches at 25 kV from terminator
tent contact with live parts. Interphase and end barriers of skirts to fiberglass-reinforced polyester barriers.
the same material are provided with each switch and each

December 19, 2011© S&C Electric Company Specification Bulletin 662A-31


S&C Manual PMH Pad-Mounted Gear

Conditions of Sale—Continued Switching with Uni-Rupter


S&C Manual PMH Pad-Mounted Gear features fuses with
EXCLUSIONS: Three-phase units listed on pages 5 Uni-Rupter for single-pole live switching of single-phase or
through 7 do not include the items listed in the table of three-phase load circuits on distribution systems rated
optional features on pages 8 through 12, nor do they include 14.4 kV or 25 kV.
the connector, fuse components, switch blades, or acces- Complete ratings and capabilities of S&C Power Fuses
sories listed in the tables on pages 13 through 20. with Uni-Rupter as applied in S&C Manual PMH Pad-
Mounted Gear are shown in the table below. Uni-Rupter is
SPECIFICATION DEVIATIONS: Features or modifica- also capable of carrying and interrupting load currents up
tions other than those listed in the table of optional fea- to and including the emergency peak-load capabilities of
tures cannot be accommodated. Specifically, the following the associated SML power fuses. In addition to the load-
modifications or additions are not available except in cus- dropping capabilities shown, Uni-Rupter is capable of
tom-design gear or other standard models of S&C gear: interrupting transformer magnetizing currents associated
Relocation of components (switches and fuses). with the applicable loads, as well as line-charging and
Inclusion, in fuse compartments, of surge arresters or cable-charging currents typical for distribution systems of
porcelain cable-terminating devices. these voltage ratings. The duty-cycle fault-closing capabil-
ities shown for S&C Power Fuses with Uni-Rupter repre-
Separable insulated connectors (either 200 or 600 sent the fault-closing capabilities of the fuse with
ampere). Uni-Rupter when the fuse is closed with a purposeful thrust
Intermediate- or station-class surge arresters. without hesitation. Following the specified number of such
Mechanical interlocks. closings (two or three), Uni-Rupter will remain operable
and able to carry and interrupt rated current.
Certain minor departures from the optional features can
be accommodated. For example, the user may wish to use A Note on Single-Pole Switching
mounting provisions for different porcelain cable ter- In single-pole switching of ungrounded-primary three-
minators in a switch compartment and bus compartment. phase transformers or banks (or single-phase transformer
Such deviations can be accommodated by a “minor connected line-to-line), circuit connections or parameters
modification.” Contact the nearest S&C Sales Office for may, in some cases, produce excessive overvoltages. In
availability. particular, for the following applications above 22 kV,
APPLICATION NOTES: For application information as single-pole switching by any means—including Uni-
well as a guide to the selection of appropriate ampere Rupter—should be performed only under the conditions
ratings and speeds of S&C SML Power Fuses, and types stated in italics:
and TCC curve parameters of control modules for S&C
Fault Fiter Electronic Power Fuses, contact the nearest
S&C Sales Office.

RATINGS AND CAPABILITIES FOR S&C POWER FUSES WITH UNI-RUPTER


Voltage, kV Current, Amperes, RMS
Live Switching
Fuse Type Interr.
Nom. Max BIL Max Load Splitting Duty-Cycle
(Sym.) Load
(Parallel or Loop Fault-Closing
Dropping
Switching) RMS, Sym.
14.4 17.0 95 200E or 200K 14 000 200 200 14 000 a
SML-20
25 27 125 200E or 200K 12 500 200 200 12 500f
14.4 17.0 95 200E 12 500 200 200 12 500a
SML-4Z
25 27 125 200E 12 500! 200 200 12 500f
14.4 17.0 95 200 14 000 200 200 14 000 a
Fault Fiter
25 29 125 200 12 500 200 200 12 500f
! Applicable to solidly ground-neutral systems only, with fuses connected a Three-time duty-cycle fault-closing capability
by single-conductor, concentric-neutral-type cable to a transformer or f Two-time duty-cycle fault-closing capability
transformers. Rating is 9,400 amperes, RMS, symmetrical for all other
applications.

2 S&C Specification Bulletin 662A-31


S&C Manual PMH Pad-Mounted Gear

Switching unloaded or lightly loaded delta-connected Protection of single-phase lateral circuits fed by single-
or ungrounded-primary wye-wye connected three-phase conductor shielded cable where the load is line-to-
transformers or banks (or line-to-line connected single- ground connected.
phase transformers), rated 150 kVA or less three-phase,
or 50 kVA or less single-phase—or of any kVA rating Switching with Mini-Rupter
when combined with unloaded cables or lines—where S&C Manual PMH Pad-Mounted Gear features S&C Mini-
maximum system operating voltage exceeds 22 kV. Rupter Switches for three-pole live switching of three-
Single-pole switching should be performed only if phase circuits.
each phase is carrying 5% load or more, or if the trans- Complete ratings for Mini-Rupters as applied in S&C
former or bank is temporarily grounded at the Manual PMH Pad-Mounted Gear are shown in the table
primary neutral during switching. below. In addition to the load-dropping ratings shown,
Switching loaded or unloaded ungrounded-primary Mini-Rupter is capable of interrupting transformer magne-
wye-delta connected three-phase transformers or tizing currents associated with the applicable loads, as well
banks—alone or combined with unloaded cables or as line-charging and cable-charging currents typical for
lines—where maximum system operating voltage distribution systems of these voltage ratings. For applica-
exceeds 22 kV. Single-pole switching should be per- tions on systems rated higher than 7.2 kV and involving
formed only if each phase is carrying 5% load or more load current with high harmonic content (such as rectifier
and if the lighting-load phase is always switched open load currents), refer to the nearest S&C Sales Office. The
first (or switched closed last); or if the transformer or two-time duty-cycle fault-closing ratings shown for Mini-
bank is temporarily grounded at the primary neutral Rupters define the ability to close the Mini-Rupter twice
during switching. against a three-phase fault with asymmetrical current in at
least one phase equal to the rated value, with the switch
Recommended Voltage Ratings of remaining operable and able to carry and interrupt rated
Current-Limiting Fuses for Use in current.
S&C Pad-Mounted Gear WARRANTY QUALIFICATIONS: The standard war-
In general, current-limiting fuses should have a maximum ranty contained in seller’s standard conditions of sale (as
voltage rating equal to, but not greater than 140% of, the set forth in Price Sheet 150) does not apply to S&C Manual
system line-to-line voltage since, for most applications, the PMH Pad-Mounted Gear where fuse units, fuse-unit end fit-
fuses can be exposed to full system line-to-line voltage in tings, holders, refill units, or switch blades of other than
clearing faults. Although there may be economic or space- S&C manufacture are used in conjunction with S&C SML
saving incentives for using current-limiting fuses with volt- Mountings. Nor does it apply to S&C Manual PMH Pad-
age ratings “appropriate for system line-to-ground voltage” Mounted Gear where other than Fault Fiter Electronic
(i.e., fuses with a voltage rating lower than line-to-line volt- Power Fuses, S&C Switch Blades, or the current-limiting
age but greater than or equal to maximum system line-to- fuses listed on page 19 are used in conjunction with Fault
ground voltage), S&C can recommend such use only in the Fiter Electronic Power Fuse Mountings and S&C Hold-
following applications: ers designed therefor, or when current-limiting fuses are
Protection of single-phase transformers serving single- applied other than as set forth under “Recommended
phase loads, Voltage Ratings of Current-Limiting Fuses for Use in S&C
Protection of three-phase lateral circuits fed by single- Pad-Mounted Gear” on page 3.
conductor shielded cable (provided each transformer
on that lateral is individually fused so that the current-
limiting fuse serving the lateral will not be required to
clear secondary faults), or

S&C Specification Bulletin 662A-31 3


S&C Manual PMH Pad-Mounted Gear

b. For SML-4Z Power Fuses: Obtain the catalog number


How to Order of the holder and refill units from the tables on pages
1. Three-Phase Units (Pad-Mounted Gear) 13 and 16, taking care to match the voltage rating of
the holder to the refill units.
a. Obtain the catalog number of the desired unit from
the table on pages 5 through 7. c. For Fault Fiter Electronic Power Fuses: Obtain the
catalog number for the holders, the interrupting mod-
b. Add suffix designations (to the catalog number above)
ules, and the control modules from the tables on
to indicate the optional features desired, selected
pages 13, 17, and 18, taking care to match the voltage
from the table on pages 8 through 12.
rating of the holders, interrupting modules, and the
c. Obtain the catalog number of the connector, acces- control modules.
sories, and touch-up kit components from the tables
d. For switch blades: Obtain the catalog number for the
on page 20.
switch blades from the table on page 20.
2. Fuse Components and Switch Blades
3. Example
a. For SML-20 Power Fuses: Obtain the catalog number
The catalog number of a 14.4-kV manual Model PMH-9
of the end fittings and the fuse units from the tables
with SML-20 Mountings; optional cable guides for
on pages 13 through 15, taking care to match the volt-
switches and fuses; and 10-kV metal-oxide surge arrest-
age rating of the end fittings to the fuse units.
ers at all switch terminals is 55152R4-M2M3N7.

RATINGS FOR S&C MINI-RUPTER SWITCHES


Voltage, kV Current, Amperes
Live Switching Three-Time Duty-Cycle Fault-Closing Short-Circuit

One-Second
Nom. Max BIL Cont. Load-Splitting Peak
Load Short Time
(Parallel or Peak RMS, Sym. Withstand,
Dropping Withstand,
Loop Switching) Peak
RMS, Sym.

14.4 17.5 95 600 600 600 36 400 14 000 36 400 14 000

25 29 125 600 600 600 32 500 12 500 32 500 12 500

4 S&C Specification Bulletin 662A-31


S&C Manual PMH Pad-Mounted Gear

THREE-PHASE UNITS (Including mountings with Uni-Rupter—less fuse components1)


Ratings3
kV Amperes, RMS Short-Circuit
Page
Fuse with Reference
Connection Fuse Mini-Rupter MVA Catalog Net Wt.,
Model Uni-Rupter for
Diagram2 Type Amperes, 3-Phase Number Lbs.
Dimensional
Nom. Max BIL RMS, Sym. at Information
Load Load Sym. Rated
Max Cont.
Dropping Dropping Voltage

14.4 17.0 95 — — 600 600 14 000 350 55232R3 650


PMH-3 — 21
25 29 125 — — 600 600 12 500 540 55233R3 950

SML- 14.4 17.0 95 200Ef 200 — — 14 000 350 55102R3 525


20 25 27 125 200Ef 200 — — 12 500 540 55103R3 675

SML- 14.4 17.0 95 200E 200 — — 12 500 310 55302R3 525


PMH-4j 22
4Z 25 27 125 200E 200 — — 12 500l 540l 55303R3 675

Fault 14.4 17.0 95 200 200 — — 14 000 350 55502R3 525


Fiter4 25 29 125 200 200 — — 12 500 540 55503R3 675

SML- 14.4 17.0 95 200Ef 200 600 600 14 000 350 55112R3 825
20 25 27 125 200Ef 200 600 600 12 500 540 55113R3 1150

SML- 14.4 17.0 95 200E 200 600 600 12 500 310 55312R3 825
PMH-5d 23
4Z 25 27 125 200E 200 600 600 12 500l 540l 55313R3 1150

Fault 14.4 17.0 95 200 200 600 600 14 000 350 55512R3 825
Fiter4 25 29 125 200 200 600 600 12 500 540 55513R3 1150

SML- 14.4 17.0 95 200Ef 200 600 600 14 000 350 55122R4 1475
20 25 27 125 200Ef 200 600 600 12 500 540 55123R3 1975

SML- 14.4 17.0 95 200E 200 600 600 12 500 310 55322R4 1475
PMH-6d 24
4Z 25 27 125 200E 200 600 600 12 500l 540l 55323R3 1975

Fault 14.4 17.0 95 200 200 600 600 14 000 350 55522R4 1475
Fiter4 25 29 125 200 200 600 600 12 500 540 55523R3 1975

1 Fuse components are to be ordered separately. Refer to pages 13 ratings as listed on page 19 apply when current-limiting fuses are used.
through 18. Consult appropriate current-limiting fuse manufacturer for complete fuse
ratings.
2 Compartment numbers appear in corners of each diagram.
j Available only when ultimate user is an electric utility.
3 The short-circuit ratings expressed in amperes, RMS, asymmetrical
are 1.6 times the symmetrical values listed. Fault-closing and/or momen- d Key interlocks (Catalog Number Suffix “-C3” or “-C4”) are required for
tary ratings of switches and bus, and fault-closing capabilities and inter- ultimate users other than electric utilities.
rupting ratings of fuses, equal or exceed these values. For complete f SMU-20 Fuse Units are available in ratings through 200K amperes as
live-switching (as well as momentary and one-second) ratings for Mini- well as 200E amperes.
Rupters and complete live-switching capabilities of Uni-Rupters as applied
in S&C Manual PMH Pad-Mounted Gear, refer to “Application Notes” on l Applicable to solidly grounded-neutral systems only, with fuses
page 2. connected by single-conductor, concentric-neutral-type cable to a trans-
former or transformers. Rating is 9,400 amperes, RMS, symmetrical (405
4 These models also accommodate selected current-limiting fuses in MVA) for all other applications.
S&C Holders; refer to page 19. Maximum voltage and maximum ampere

TABLE CONTINUED v

S&C Specification Bulletin 662A-31 5


S&C Manual PMH Pad-Mounted Gear

THREE-PHASE UNITS (Including mountings with Uni-Rupter—less fuse components1)—Continued


Ratings3
Page
kV Amperes, RMS Short-Circuit Reference
for
Connection Fuse Fuse with MVA Catalog Net Wt.,
Model Mini-Rupter Dimen-
Diagram2 Type Uni-Rupter Amperes, 3-Phase Number Lbs.
sional
Nom. Max BIL RMS, Sym. at Informa-
Load Load Sym. Rated
Max Cont. tion
Dropping Dropping Voltage

14.4 17.0 95 200Ef 200 600 600 14 000 350 55132R4 1400
SML-20
25 27 125 200Ef 200 600 600 12 500 540 55133R3 1875

14.4 17.0 95 200E 200 600 600 12 500 310 55332R4 1400
PMH-7d SML-4Z 25
25 27 125 200E 200 600 600 12 500l 540l 55333R3 1875

Fault 14.4 17.0 95 200 200 600 600 14 000 350 55532R4 1400
Fiter4 25 29 125 200 200 600 600 12 500 540 55533R3 1875

14.4 17.0 95 200Ef 200 600 600 14 000 350 55142R4 1350
SML-20
25 27 125 200Ef 200 600 600 12 500 540 55143R3 1900

14.4 17.0 95 200E 200 600 600 12 500 310 55342R4 1350
PMH-8j SML-4Z 26
25 27 125 200E 200 600 600 12 500l 540l 55343R3 1900

Fault 14.4 17.0 95 200 200 600 600 14 000 350 55542R4 1350
Fiter4 25 29 125 200 200 600 600 12 500 540 55543R3 1900

14.4 17.0 95 200Ef 200 600 600 14 000 350 55152R4 1550
SML-20
25 27 125 200Ef 200 600 600 12 500 540 55153R3 2050

14.4 17.0 95 200E 200 600 600 12 500 310 55352R4 1550
PMH-9d SML-4Z 27
25 27 125 200E 200 600 600 12 500l 540l 55353R3 2050

Fault 14.4 17.0 95 200 200 600 600 14 000 350 55552R4 1550
Fiter4 25 29 125 200 200 600 600 12 500 540 55553R3 2050

14.4 17.0 95 — — 600 600 14 000 350 55242R4 1725


PMH-10 — 28
25 29 125 — — 600 600 12 500 540 55243R3 2275

14.4 17.0 95 200Ef 200 600 600 14 000 350 55162R4 1625
SML-20
25 27 125 200Ef 200 600 600 12 500 540 55163R3 2175

14.4 17.0 95 200E 200 600 600 12 500 310 55362R4 1625
PMH-11d SML-4Z 29
25 27 125 200E 200 600 600 12 500l 540l 55363R3 2175

Fault 14.4 17.0 95 200 200 600 600 14 000 350 55562R4 1625
Fiter4 25 29 125 200 200 600 600 12 500 540 55563R3 2175

TABLE CONTINUED v

6 S&C Specification Bulletin 662A-31


S&C Manual PMH Pad-Mounted Gear

THREE-PHASE UNITS (Including mountings with Uni-Rupter—less fuse components1)—Continued


Ratings3
Page
kV Amperes, RMS Short-Circuit Refer-
ence for
Connection Fuse Fuse with MVA Catalog Net Wt.,
Model Mini-Rupter Dimen-
Diagram2 Type Uni-Rupter Amperes, 3-Phase Number Lbs.
sional
Nom. Max BIL RMS, Sym. at Informa-
Load Load Sym. Rated
Max Cont. tion
Dropping Dropping Voltage

14.4 17.0 95 200Ef 200 600 600 14 000 350 55172R4 1450
SML-20
25 27 125 200Ef 200 600 600 12 500 540 55173R3 1950

14.4 17.0 95 200E 200 600 600 12 500 310 55372R4 1450
PMH-12d SML-4Z 30
25 27 125 200E 200 600 600 12 500l 540l 55373R3 1950

Fault 14.4 17.0 95 200 200 600 600 14 000 350 55572R4 1450
Fiter4 25 29 125 200 200 600 600 12 500 540 55573R3 1950

14.4 17.0 95 — — 600 600 14 000 350 55252R4 1525


PMH-13 — 31
25 29 125 — — 600 600 12 500 540 55253R3 2125

SML-20 14.4 17.0 95 200Ef 200 600 600 14 000 350 55212R4 1625

PMH-19d SML-4Z 14.4 17.0 95 200E 200 600 600 12 500 310 55412R4 1625 32

Fault
14.4 17.0 95 200 200 600 600 14 000 350 55612R4 1625
Fiter4

1 Fuse components are to be ordered separately. Refer to pages 13 ratings as listed on page 19 apply when current-limiting fuses are used.
through 18. Consult appropriate current-limiting fuse manufacturer for complete fuse
ratings.
2 Compartment numbers appear in corners of each diagram.
d Key interlocks (Catalog Number Suffix “-C3” or “-C4”) are required for
3 The short-circuit ratings expressed in amperes, RMS, asymmetrical
ultimate users other than electric utilities.
are 1.6 times the symmetrical values listed. Fault-closing and/or momen-
tary ratings of switches and bus, and fault-closing capabilities and j Available only when ultimate user is an electric utility.
interrupting ratings of fuses, equal or exceed these values. For complete f SMU-20 Fuse Units are available in ratings through 200K amperes as
live-switching (as well as momentary and one-second) ratings for Mini- well as 200E amperes.
Rupters and complete live-switching capabilities of Uni-Rupters as
applied in S&C Manual PMH Pad-Mounted Gear, refer to “Application l Applicable to solidly grounded-neutral systems only, with fuses con-
Notes” on page 2. nected by single-conductor, concentric-neutral-type cable to a transformer
or transformers. Rating is 9,400 amperes, RMS, symmetrical (405 MVA) for
4 These models also accommodate selected current-limiting fuses in all other applications.
S&C Holders; refer to page 19. Maximum voltage and maximum ampere

S&C Specification Bulletin 662A-31 7


S&C Manual PMH Pad-Mounted Gear

OPTIONAL FEATURES
Suffix to be
Added to
Item Pad-Mounted Applicable to Models
Gear
Catalog Number

Light Gray Outdoor Ultradur Finish instead of Olive Green -A2 All models
Equipment Green Outdoor Finish (Toronto Standard) instead of Olive Green -A3 All models
Seafoam Green Outdoor Finish instead of Olive Green -A4 All models
Special Color Outdoor Ultradur Finish instead of Olive Green -A5 All models
With Olive Green Outdoor Ultradur Finish -A10 All models
Stainless-Steel Enclosure1 With Light Gray Outdoor Ultradur Finish -A12 All models
With Special Color Outdoor Ultradur Finish -A15 All models
For use except when Catalog Number Suffix
Hexhead Actuator for use in lieu of -B1a" All models
“-F2” is specified
pentahead actuator on all Penta-Latch
Mechanisms For use when Catalog Number Suffix “-F2” is
-B2n" All models except PMH-4
also specified
Copper Bus2 and Copper Switch Terminals, Fuse Connector Adapters, and Bus Terminals -B5 All models
Used with standard aluminum bus -B6 15-kV models of PMH-6, -7, -8, -9,
Reinforced Bus
Used with optional copper bus -B7 -10, -11, 12, -13

Key Interlocks to prevent paralleling of switches in Compartments 1 and 23 -C1 PMH-6, -9, -10, -11, -13, -19
Key Interlocks to prevent opening fuse-compartment doors unless all switches (series tap
-C3h PMH-5, -6, -7, -9, -11, -12, -19
switch only in PMH-19) are locked open3
Key Interlocks. Combines functions of options “-C1” and “-C3” listed above3 -C4h PMH-6, -9, -11, -19
Located in Compartment 1 -E1 PMH-5, -6, -7, -8, -9, -11, -19
Fuse-Storage Feature for three spare fuse
Located in Compartment 2 -E2 PMH-6, -7, -9, -11, -12, -19
assemblies per compartment4
Located in Compartments 1 and 2 -E3 PMH-6, -7, -9, -11, -19

1 When this optional feature is specified, the entire exterior of the Fiter Electronic Power Fuse Holder, or one spare current-limiting fuse
enclosure is fabricated from 11-gauge Type 304 stainless steel. When holder can be accommodated in each compartment.
specifying optional hexhead actuators, provisions for fault indicators a Specify Catalog Number Suffix “-B11” for gear with stainless-steel
with viewing windows in doors, or base spacer, specify the correct suffix enclosure.
for use in gear with a stainless-steel enclosure.
" Not available if UL listing (Catalog Number Suffix “-X”) is specified.
2 Copper bus measures ¹⁄₄!" 2!.
3 When specifying, please furnish name of ultimate user, station, and n Specify Catalog Number Suffix “-B12” for gear with stainless-steel
location of gear. enclosure.
h Must be specified if end user is not an electric utility and/or if Canadian
4 Fuse assemblies (fuse holders or fuse units with end fittings) are not
included. For units equipped with Fault Fiter Electronic Power Fuse Standards Association listing (Catalog Number Suffix “-Z”) is specified.
Mountings, two spare Fault Fiter Interrupting Modules, one spare Fault

TABLE CONTINUED v

8 S&C Specification Bulletin 662A-31


S&C Manual PMH Pad-Mounted Gear

OPTIONAL FEATURES—Continued
Suffix to be
Added to
Pad-Mounted
Item Applicable to Models
Gear
Catalog
Number

Mounting Provisions for a Fault Indicator in


each switch compartment (except series tap Without viewing window in door -F1 All models except PMH-4
switch in PMH-19)
Note: Accommodates three-phase indicator With viewing window in door -F2ad All models except PMH-4
with single-phase sensors
Inner Barrier Panels—a panel inside the enclosure door for each compartment, secured by
-G7d All models
recessed pentahead bolt(s)12

Copper Ground Stud for each switch, fuse, or In fuse compartments4 -H2 All models except PMH-3, -10, -13
bus terminal and ground pad3 In switch and bus compartments -J2 All models except PMH-4

1 Where the National Electrical Safety Code (ANSI Standard C2) app- 4 Including bus-compartment terminals in Model PMH-4.
lies, this optional feature may be included to meet the requirements of a Specify Catalog Number Suffix “-F12” for gear with stainless-steel
Section 381G. enclosure.
2 Meets RUS’s requirements for “dead-front.” d Not available if Canadian Standards Association listing (Catalog
3 Diameters of copper ground studs are as follows: Number Suffix “-Z”) is specified.
Ground Stud Diameter (inches)
Switch ¹⁄₂
Fuse ⁷⁄₁₆
Bus Terminal ⁷⁄₁₆
Ground Pad ⁷⁄₁₆
TABLE CONTINUED v

S&C Specification Bulletin 662A-31 9


S&C Manual PMH Pad-Mounted Gear

OPTIONAL FEATURES—Continued
Suffix to be Added to
Item Pad-Mounted Gear Applicable to Models
Catalog Number

6 inches -K1 All models


12 inches -K2 All models
Carbon steel
18 inches -K3 All models
Base Spacer, compartmented to match 24 inches -K4 All models
enclosure, increases cable-termination
height 6 inches -K11 All models
12 inches -K12 All models
Stainless steel
18 inches -K13 All models
24 inches -K14 All models
6 inches -K7 All models
12 inches -K8 All models
Carbon steel
18 inches -K9 All models

Base Spacer, noncompartmented, 24 inches -K10 All models


increases cable-termination height 6 inches -K17 All models
12 inches -K18 All models
Stainless steel
18 inches -K19 All models
24 inches -K20 All models

TABLE CONTINUED v

10 S&C Specification Bulletin 662A-31


S&C Manual PMH Pad-Mounted Gear

OPTIONAL FEATURES—Continued
Suffix to be Added to
Item Pad-Mounted Gear Applicable to Models
Catalog Number

International Crating1 -L71 All models

Switch- and Bus-Terminal Adapters—for connection of two cables (through 750 kc mil)
per terminal2
-M1 All models
Note: Space limitations prevent use of these adapters where surge arresters are to be
installed

In switch and bus compartments. For


-M2 All models
conductor sizes No. 2 through 1000 kc mil

PMH-4, -5, -6, -11, -19


Cable Guides, one at each terminal23
In fuse compartments. For conductor sizes
-M3 PMH-7, -8, -9
No. 2 through 4/0
PMH-12

9 kV -N6f All models

10 kV -N7f All models


Polymer-Housed Metal-Oxide Surge
Arresters4, base-mounted, at switch
12 kV -N8 All models
terminals and bus terminals in Compart-
ments 1 and 2 (removed for shipment)
15 kV -N9 All models

18 kV -N10l All models except PMH-19

Metal-Oxide Surge Arresters,4 base- 3 kV -N11a All models


mounted, at switch terminals and bus
terminals in Compartments 1 and 2
(removed for shipment) 6 kV -N12a All models

1 Wood products used in the packaging are either hardwood or certified 3 These devices extend below the base of the unit. Provide a cable pit or
by the wood supplier as being “heat treated (kiln dried) to a core temp- specify a base spacer that provides a 12-inch (305 mm) or greater increase
erature of 133°F (56° Celsius) for a minimum of 30 minutes.” in cable-termination height.
2 When Catalog Number Suffix “-M1” or “-M2” is specified, cable-termi- 4 Surge arresters are base-mounted only (without isolators).
nation options (Catalog Number Suffixes “-U2” and “-U3”) cannot be f Not applicable to 25-kV models.
accommodated. In addition, when Catalog Number Suffixes “-M1” and
“-M2” are both specified, only one cable guide is provided at each switch l Not applicable to 14.4-kV models.
terminal. a A supplemental label is provided for Catalog Number Suffixes “-N11”
and “-N12” indicating the voltage rating of the surge arresters furnished.

TABLE CONTINUED v

S&C Specification Bulletin 662A-31 11


S&C Manual PMH Pad-Mounted Gear

OPTIONAL FEATURES—Continued
Suffix to be Added to
Item Pad-Mounted Gear Applicable to Models
Catalog Number

9 kV, 10 kV, or 9/10 kV -P1f All models

Mounting Provisions for Base-Mounted 12 kV -P3 All models


Surge Arresters1, at switch terminals and
bus terminals in Compartments 1 and 2 15 kV -P4 All models

18 kV -P5l All models except PMH-19

G&W PSC for No. 6 through 2/0d, or G&W


Mounting Provisions for Porcelain Cable PAT for No. 4 through 250 kc mil copper or -U2 All models
Terminators for single-conductor UD cable, aluminum cable
at all cable-connected switch terminals and
bus terminals G&W PAT for 3/0 through 750 kc mil copper
-U3 All models
or 500 kc mil aluminum cabled

UL Listing. Includes “UL Listed” symbol on ratings label and nameplate -Xg v All 14.4 kV models

PMH-3, -5, -7, -12

Canadian Standards Association Listing. Includes viewing window with tamper-resistant PMH-6, -9
cover in switch compartment door(s), and hazard-alerting labels and nameplate per CSA -Zajhg
specification PMH-11, -13, -19

PMH-10

1 These provisions accommodate Ohio Brass Type PDV (metal oxide), v Not available if hexhead actuator for use in lieu of pentahead actua-
McGraw-Edison Type AZL19C (metal oxide), General Electric Tranquell® tor on all Penta-Latch Mechanisms (Catalog Number Suffix “-B1,” “-B2,”
(metal oxide), or McGraw-Edison Type ES (silicon carbide) distribution- “-B11,” or “-B12”) is specified.
class surge arresters. Surge arresters must be base-mounted only (with- a Key interlocks (Catalog Number Suffix “-C3” or “-C4”) must be speci-
out isolators). fied on gear with fuse compartment(s).
d These devices extend below the base of the unit. Provide a cable pit or j Not available if mounting provisions for fault indicator with viewing win-
specify a base spacer. dow in switch compartment door(s) (Catalog Number Suffix “-F2” or “-F12”)
f Not applicable to 25-kV models. is specified.
l Not applicable to 14.4-kV models. h Not available if inner barrier panels (Catalog Number Suffix “-G7) is
g UL Listing (Catalog Number Suffix “-X”) cannot be furnished if Cana- specified.
dian Standards Association Listing (Catalog Number Suffix “-Z”) is speci-
fied and vice versa.

12 S&C Specification Bulletin 662A-31


S&C Manual PMH Pad-Mounted Gear

SML-20 POWER FUSE COMPONENTS


Fuse-Unit End Fittings
Item Catalog Number

End Fittings (including Silencer), for use with SMU-20 Fuse Units 3097

SMU-20® Fuse Units1


14.4 kV Nominal, 17.0 kV Max 25 kV Nominal, 27 kV Max

For a complete listing of available ampere ratings, speeds, and catalog numbers, refer to pages 14 and 15.

1 These fuse units are usable in SM-20, SMD-20, SML-20, and SME-20
Mountings.

SML-4Z POWER FUSE COMPONENTS


Holders
Rating

Item kV Amperes, Catalog Number

Nom. Max Max

14.4 17.0 200E 92352


Holder (including Silencer), for use with SM-4 Refill Units
25 27 200E 92353

SM-4® Refill Units1


14.4 kV Nominal, 17.0 kV Max 25 kV Nominal, 27 kV Max

For a complete listing of available ampere ratings, speeds, and catalog numbers, refer to page 16.

1 These fuse units are usable in SM-4, SM-4Z, SML-4Z, and SME-4Z
Mountings.

FAULT FITER ELECTRONIC POWER FUSE COMPONENTS


Holders
Rating

Item kV Amperes, Catalog Number

Nom. Max Cont.

13.8 17.0 400 99412R1


Holder, for use with Fault Fiter Electronic Power Fuses
25 29 200 99413R1

Interrupting Modules1
Rating

Item kV Amperes, Catalog Number

Nom. Max Cont.

13.8 17.0 600 802600R2


Interrupting Module, for use with Fault Fiter Electronic Power Fuses
25 29 600 803600R2

Control Modules1

For a complete listing of available types, TCC curve parameters, and catalog numbers, refer to pages 17 and 18.

1 Interrupting modules and control modules rated 600 amperes continu-


ous are also applicable for use in mountings rated 200 or 400 amperes
continuous.

S&C Specification Bulletin 662A-31 13


S&C Manual PMH Pad-Mounted Gear

SMU-20® FUSE UNITS (For use in SM-20 or SML-20 Mountings)1


14.4 kV Nominal, 17.0 kV Max

“K” Ratings “E” Ratings

Rating, Rating,
Catalog Number Catalog Number
Amperes Amperes

S&C “K” S&C Std.


Speed Speed
TCC 165-2 TCC 115-2

1E 702001

S&C Std. S&C Slow S&C Very Slow


Speed
TCC 153-2 TCC 119-2 TCC 176-2

3K 702003
6K 702006 5E 612005
8K 702008 7E 612007
10K 702010 10E 612010
12K 702012 13E 612013
15K 702015 15E 612015 712015
20K 702020 20E 612020 712020
25K 702025 25E 612025 712025
30K 702030 30E 612030 712030
40K 702040 40E 612040 712040
50K 702050 50E 612050 712050 602050
65K 702065 65E 612065 712065 602065
80K 702080 80E 612080 712080 602080
100K 702100 100E 612100 712100 602100
140K 702140 125E 612125 712125 602125
200K 702200 150E 612150 712150 602150
175E 612175 712175 602175
200E 612200 712200 602200

1 These fuse units are equally suitable for use in SMD-20 Outdoor
Distribution Mountings; and also, for use with SME-20 Fuse-Unit End
Fittings listed in Specification Bulletin 665-31, “S&C Manual PME Pad-
Mounted Gear” and Specification Bulletin 666-31, “S&C Remote Super-
visory PME Pad-Mounted Gear.”

14 S&C Specification Bulletin 662A-31


S&C Manual PMH Pad-Mounted Gear

SMU-20® FUSE UNITS (For use in SM-20 or SML-20 Mountings)1


25 kV Nominal, 27 kV Max2

“K” Ratings “E” Ratings

Rating, Rating,
Catalog Number Catalog Number
Amperes Amperes

S&C “K” S&C Std.


Speed Speed
TCC 165-2 TCC 115-2

1E 703001

S&C Std. S&C Slow S&C Very Slow


Speed
TCC 153-2 TCC 119-2 TCC 176-2

3K 703003
6K 703006 5E 613005
8K 703008 7E 613007
10K 703010 10E 613010
12K 703012 13E 613013
15K 703015 15E 613015 713015
20K 703020 20E 613020 713020
25K 703025 25E 613025 713025
30K 703030 30E 613030 713030
40K 703040 40E 613040 713040
50K 703050 50E 613050 713050 603050
65K 703065 65E 613065 713065 603065
80K 703080 80E 613080 713080 603080
100K 703100 100E 613100 713100 603100
140K 703140 125E 613125 713125 603125
200K 703200 150E 613150 713150 603150
175E 613175 713175 603175
200E 613200 713200 603200

1 These fuse units are equally suitable for use in SMD-20 Outdoor 2 Also suitable for protection of single-phase-to-neutral circuits (lines or
Distribution Mountings; and also, for use with SME-20 Fuse-Unit End transformers) on 20/34.5 GrY-kV systems.
Fittings listed in Specification Bulletin 665-31, “S&C Manual PME Pad-
Mounted Gear” and Specification Bulletin 666-31, “S&C Remote Super-
visory PME Pad-Mounted Gear.”

S&C Specification Bulletin 662A-31 15


S&C Manual PMH Pad-Mounted Gear

SM-4® REFILL UNITS (For use in SM-4 and SML-4 Holders)1

14.4 kV Nominal, 17.0 kV Max2 25 kV Nominal, 27 kV Max


Rating,
Amperes
Catalog Number Catalog Number

S&C Std. S&C Std.


Speed
TCC 115-4 TCC 115-4

1 122001R4 123001R4
2 122002R4 123002R4

S&C Std. S&C Slow S&C Coord. S&C Std. S&C Slow
Speed
TCC 153-4 TCC 119-4 TCC 179-4 TCC 153-4 TCC 119-4

3E 122005R4 123005R4
5E 122007R4 123007R4
7E 122010R4 123010R4
10E 122015R4 123015R4
13E 122020R4 123020R4
15E 122025R4 252025R4 123025R4 253025R4
20E 122030R4 252030R4 123030R4 253030R4
25E 122040R4 252040R4 123040R4 253040R4
30E 122050R4 252050R4 123050R4 253050R4
40E 122060R4 252060R4 123060R4 253060R4
50E 122075R4 252075R4 123075R4 253075R4
65E 122100R4 252100R4 123100R4 253100R4
80E 122125R4 252125R4 123125R4 253125R4
100E 122150R4 252150R4 123150R4 253150R4
125E 122200R4 252200R4 123200R4 253200R4
150E 122250R4 252250R4 123250R4 253250R4
175E 122275R4 252275R4 123275R4 253275R4
200E 122300R4 252300R4 123300R4 253300R4
210E 382210R4f

1 These refill units are also suitable for use with SME-4Z Holders listed f This S&C Coordinating Speed refill unit should be applied where the
in Specification Bulletin 665-31, “S&C Manual PME Pad-Mounted Gear” maximum continuous load current does not exceed 200 amperes and
and Specification Bulletin 666-31, “S&C Remote Supervisory PME Pad- where all fault currents below 1000 amperes will be cleared by another
Mounted Gear.” fuse.
2 Rated 14.4 kV nominal, for use in SM-4 Holders rated 14.4 kV when
applied in listed mountings rated 13.8 kV or in discontinued mountings
rated 14.4 kV.

16 S&C Specification Bulletin 662A-31


S&C Manual PMH Pad-Mounted Gear

FAULT FITER CONTROL MODULES—Underground Subloop1 Type (TCC No. 422-7)


TCC Curve Parameters
Continuous Current,
Instantaneous Catalog Number
Amperes, Max2 Minimum Pickup, Short-Time Pickup, Short-Time
Pickup,
Amperes, RMS Amperes, RMS Delay Band
Amperes, RMS

400 1300 2 3000 7020-C40P130S2T3


600
500 1300 1 3000 7020-C50P130S1T3

1 This control module is applicable for protection of 15-kV and 25-kV the load side of Fault Fiter. If the maximum rated transformer kVA con-
class underground distribution subloops having the following parameters: nected is greater than the values listed above, or if the application involves
maximum available fault current—14,000 amperes, RMS, symmetrical at protection of circuits serving industrial, commercial, or institutional loads,
15 kV, 12,500 amperes, RMS, symmetrical at 25 kV; maximum rated contact your nearest S&C Sales Office.
transformer kVA connected for residential circuits—1200 kVA single- 2 Control modules rated 600 amperes continuous are also applicable for
phase, 3600 kVA three-phase at 15 kV, 2400 kVA single-phase, 7200 kVA use in mountings rated 200 amperes or 400 amperes continuous.
three-phase at 25 kV; with no capacitor banks or current-limiting fuses on

FAULT FITER CONTROL MODULES—Inverse Curve Type (TCC No. 410-7)


Continuous Current, Minimum Pickup,
Catalog Number
Amperes, Max1 Amperes, RMS

400 814040
500 814050
600 814060
700 814070
600
800 814080
1000 814100
1250 814125
1500 814150

1 Control modules rated 600 amperes continuous are also applicable for
use in mountings rated 200 amperes or 400 amperes continuous.

S&C Specification Bulletin 662A-31 17


S&C Manual PMH Pad-Mounted Gear

FAULT FITER CONTROL MODULES—Time-Delayed Compound-Curve Type (TCC No. 421-7)


TCC Curve Parameters
Continuous Current,
High-Current High-Current Catalog Number
Amperes, Max1 Minimum Pickup, Short-Time
Pickup, Delay Band
Amperes, RMS Delay Band
Amperes, RMS Time Delay, ms

3000 8 7010-C40S1T3D8
1
6000 8 7010-C40S1T6D8

3000 8 7010-C40S2T3D8
2
6000 8 7010-C40S2T6D8
400
3000 8 7010-C40S3T3D8
3
6000 8 7010-C40S3T6D8

3000 8 7010-C40S4T3D8
4
6000 8 7010-C40S4T6D8

3000 8 7010-C60S1T3D8
1
6000 8 7010-C60S1T6D8

3000 8 7010-C60S2T3D8
2
6000 8 7010-C60S2T6D8
600
3000 8 7010-C60S3T3D8
3
6000 8 7010-C60S3T6D8

3000 8 7010-C60S4T3D8
4
6000 8 7010-C60S4T6D8
600
3000 8 7010-C80S1T3D8
1
6000 8 7010-C80S1T6D8

3000 8 7010-C80S2T3D8
2
6000 8 7010-C80S2T6D8
800
3000 8 7010-C80S3T3D8
3
6000 8 7010-C80S3T6D8

3000 8 7010-C80S4T3D8
4
6000 8 7010-C80S4T6D8

3000 8 7010-C110S1T3D8
1
6000 8 7010-C110S1T6D8

3000 8 7010-C110S2T3D8
2
6000 8 7010-C110S2T6D8
1100
3000 8 7010-C110S3T3D8
3
6000 8 7010-C110S3T6D8

3000 8 7010-C110S4T3D8
4
6000 8 7010-C110S4T6D8

1 Control modules rated 600 amperes continuous are also applicable for
use in mountings rated 200 amperes or 400 amperes continuous.

18 S&C Specification Bulletin 662A-31


S&C Manual PMH Pad-Mounted Gear

CURRENT-LIMITING FUSES ACCOMMODATED IN FAULT FITER MOUNTINGS

Current-Limiting Fuse1
For use in
PMH Models Requires
with Rating2 S&C Holder3
Nominal Voltage Manufacturer Type Catalog Number4
Max Amperes, Max Current,
Rating, kV
kV Amperes, RMS

Kearney B 8.3 30—112 3142-A1

8.3 6—100 3142-A3


8.3 40—100 3142-A1
Kearney Q 15.5 6—30 3142-A2
15.5 40—50 3142-A1
15.5 65—100 3142

8.3 1.5C—100C 3142-A3


8.3 50C—100C 3142-A1
Cooper McGraw-Edison NX®
15.5 1.5C—100C 3142-A2
14.4 15.5 50C—100C 3142

8.3 3—50 3142-A3


RTE® ELX
15.5 3—50 3142-A2

8.3 12—40 3142-A3


Combined 8.3 50—140 3142-A1
Technologies, Inc.
X Limiter™ 15.5 12—40 3142-A2
15.5 50—100 3142

8.3 3.5C—40C 3142-A3


Eaton Culter Hammer CX
15.5 4C—40C 3142-A2

15.5 30—100 3143R1-A1


Kearney B
22 25—65 3143R1-A1

15.5 6—30 3143R1-A3


Kearney Q
15.5 40—100 3143R1-A1

15.5 1.5C—100C 3143R1-A3


McGraw-Edison NX® 15.5 50C—100C 3143R1-A1
Cooper
23 6C—40C 3143R1-A3
25
15.5 3—50 3143R1-A3
RTE® ELX
23 3—40 3143R1-A3

Combined 15.5 12—100 3143R1-A3


Technologies, Inc. 15.5 50—100 3143R1-A1
X Limiter™ 23 12—40 3143R1-A3

Culter Hammer CX 15.5 4C—40C 3143R1-A3


Eaton
Culter Hammer CXN 15.5 45C—100C 3143R1-A1

1 Fuses must be furnished by others. 3 Holders for 14.4-kV PMH models are rated 14.4 kV nominal, 17.0 kV
2 Maximum voltage and current ratings listed apply to the complete maximum, 200 amperes maximum. Holders for 25-kV PMH models are
pad-mounted gear unit. Consult fuse manufacturer for complete fuse rated 25 kV nominal, 29 kV maximum, 200 amperes maximum.
ratings. 4 Includes adapters when required.

S&C Specification Bulletin 662A-31 19


S&C Manual PMH Pad-Mounted Gear

SWITCH BLADES1
Rating

Item kV Catalog Number


Amperes,
Cont.
Nom. Max

Switch Blade, for use in lieu of SMU-20 14.4 17.0 200 5432
Fuse Unit in SML-20 Mounting 25 27 200 5433

Switch Blade, for use in lieu of SML-4Z 14.4 17.0 200 5442
Holder in SML-4 Mounting 25 27 200 5443

Switch Blade, for use in lieu of Fault Fiter 14.4 17.0 400 3222
Holder in Fault Fiter Mounting 25 29 200 3223R1

1 When switch blades are used in lieu of fuses, the Uni-Rupter associ- fault-closing ratings equal to those of S&C Power Fuses with Uni-Rupter
ated with these switches can carry and interrupt load currents up to and (refer to “Application Notes” on page 2). The momentary and one-second
including the emergency peak-load capabilities of the SML power fuses, ratings of the switches equal the short-circuit ratings of the pad-mounted
or up to 400 amperes at 14.4 kV and 200 amperes at 25 kV for Fault Fiter gear.
Electronic Power Fuses. Furthermore, the switches with Uni-Rupter have

ACCESSORIES
Item Catalog Number

Grounding Jumpers, set of three, with eye-type clamps for


3# cable length 4210
installation with a standard shotgun clamp stick

6#-5¹⁄₂! length 9933-150


Shotgun Clamp Sticks for installation of grounding jumpers
and for use with voltage testers
8#-5¹⁄₂! length 9933-151

For grounding jumpers 9933-149

Storage Bag, heavy canvas 6#-6! length 9933-152


For shotgun clamp stick
8#-6! length 9933-153

Voltage Tester with audio and visual signals, includes voltage tester, batteries, adapter for shotgun clamp sticks, and
9931-072
storage case1

Pentahead Socket, for ¹⁄₂-inch drive 9931-074

1 For ultimate users other than electric utilities, also specify a shotgun
clamp stick of the appropriate length.

TOUCH-UP KIT COMPONENTS—Aerosol Coatings in 12-Ounce Cans


Item Catalog Number

S&C Light Gray Outdoor Finish 9999-080

S&C Olive Green (Munsell 7GY3.29/1.5) Outdoor Finish 9999-058

S&C Red-Oxide Primer 9999-061

CONNECTOR
Illustration Description Accommodating Connector Catalog Number

Bronze Body, Tin Plated, Two Galvanized No. 2 solid through 500 kc mil
4745
Steel Bolts, Two Belleville Washers stranded copper or aluminum

20 S&C Specification Bulletin 662A-31


S&C Manual PMH Pad-Mounted Gear

Model PMH-3
14.4 kV and 25 kV Nominal

Dimensions in inches (mm)

6
(152)

1¹⁄₂ 1¹⁄₂
(38) (38)

FOUR ⁵⁄₈ (16) DIA. ANCHOR


BOLTS—BY USER

1¹⁄₂ (38) MIN.

2³⁄₄ 2³⁄₄
(70) (70)

kV,
A1l A2l B C D E1 E2 F G1 G2 G3 H M W
Nominal
9⁷⁄₈ 11¹⁄₈ 5¹⁄₈ 17 40³⁄₄ 12⁷⁄₈ 7¹⁄₂ 37³⁄₄ 6 9³⁄₄ 9³⁄₄ 44 34 34⁷⁄₈
14.4 (432) (152) (1118) (864)
(251) (283) (130) (1035) (327) (191) (959) (248) (248) (886)
14¹⁄₈ 15¹⁄₄ 7¹⁄₈ 42¹⁄₂ 59³⁄₄ 13³⁄₄ 9⁵⁄₈ 56³⁄₄ 7¹⁄₂ 10 12¹⁄₂ 55 42¹⁄₂ 43
25 (254) (1397) (1092)
(359) (387) (181) (1080) (1518) (349) (244) (1441) (191) (318) (1070)

# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-


termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.

S&C Specification Bulletin 662A-31 21


S&C Manual PMH Pad-Mounted Gear

Model PMH-4
14.4 kV and 25 kV Nominal

Dimensions in inches (mm)

1¹⁄₂ 1¹⁄₂
(38) (38)

FOUR ⁵⁄₈ (16) DIA. ANCHOR


BOLTS—BY USER

1¹⁄₂ (38) MIN.

2³⁄₄ 2³⁄₄
(70) (70)

kV,
A1 A2# B C D E F G1 G2 H J K M W
Nominal

14.4 7 11¹⁄₈ 5¹⁄₈ 27¹⁄₂ 40³⁄₄ 7⁷⁄₈ 37³⁄₄ 9³⁄₄ 9³⁄₄ 44 10¹⁄₂ 9³⁄₄ 34 34⁷⁄₈
(178) (283) (130) (699) (1035) (200) (959) (248) (248) (1118) (267) (248) (864) (886)

25 11¹⁄₄ 15¹⁄₄ 7¹⁄₈ 42¹⁄₂ 59³⁄₄ 9⁵⁄₈ 56³⁄₄ 10 12¹⁄₂ 55 11¹⁄₂ 12¹⁄₂ 42¹⁄₂ 43
(286) (387) (181) (1080) (1518) (244) (1441) (254) (318) (1397) (292) (318) (1070) (1092)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.

22 S&C Specification Bulletin 662A-31


S&C Manual PMH Pad-Mounted Gear

Model PMH-5
14.4 kV and 25 kV Nominal

Dimensions in inches (mm)

6
(152)

1¹⁄₂ 1¹⁄₂
(38) (38)

FOUR ⁵⁄₈ (16) DIA. ANCHOR


BOLTS—BY USER

1¹⁄₂ (38) MIN.

2³⁄₄ 2³⁄₄
(70) (70)

kV,
A1# A2 B C D E F G H J K M W
Nominal

14.4 9⁷⁄₈ 7 5¹⁄₈ 31 54³⁄₄ 12⁷⁄₈ 51³⁄₄ 6 44 4⁷⁄₈ 9³⁄₄ 34 34⁷⁄₈


(251) (178) (130) (787) (1391) (327) (1314) (152) (1118) (124) (248) (864 (886)

25 14¹⁄₈ 11¹⁄₄ 7¹⁄₈ 51 68¹⁄₄ 13³⁄₄ 65¹⁄₄ 7¹⁄₂ 55 6⁵⁄₈ 12¹⁄₂ 42¹⁄₂, 43
(359) (286) (181) (1295) (1734) (349) (1657) (191) (1397) (168) (318) (1070) (1092)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.

S&C Specification Bulletin 662A-31 23


S&C Manual PMH Pad-Mounted Gear

Model PMH-6
14.4 kV and 25 kV Nominal

Dimensions in inches (mm)

6 6
(152) (152)

1¹⁄₂
(38)
1¹⁄₂
(38)

FOUR ⁵⁄₈ (16) DIA. ANCHOR


BOLTS—BY USER

1¹⁄₂ (38) MIN.

2³⁄₄
(70)

2³⁄₄
(70)

kV,
A1# A2 B C D E F G H J K L M W
Nominal

14.4 9⁷⁄₈ 7 5¹⁄₈ 40 63³⁄₄ 12⁷⁄₈ 60³⁄₄ 6 44 4³⁄₄ 9³⁄₄ 14³⁄₄ 34 67


(251) (178) (130) (1016) (1619) (327) (1543) (152) (1118) (121) (248) (375) (864) (1702)

25 14¹⁄₈ 11¹⁄₄ 7¹⁄₈ 62¹⁄₂ 79³⁄₄ 13³⁄₄ 76³⁄₄ 7¹⁄₂ 55 6 12¹⁄₂ 16¹⁄₂ 41¹⁄₂ 82
(359) (286) (181) (1588) (2026) (349) (1949) (191) (1397) (152) (318) (419) (1054) (2083)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.

24 S&C Specification Bulletin 662A-31


S&C Manual PMH Pad-Mounted Gear

Model PMH-7
14.4 kV and 25 kV Nominal

Dimensions in inches (mm)

6
(152)

1¹⁄₂
(38)
1¹⁄₂
(38)

FOUR ⁵⁄₈ (16) DIA. ANCHOR


BOLTS—BY USER

1¹⁄₂ (38) MIN.

2³⁄₄
(70)

2³⁄₄
(70)

kV,
A1# A2 B C D E F G H J K L M W
Nominal

14.4 9⁷⁄₈ 7 5¹⁄₈ 40 63³⁄₄ 12⁷⁄₈ 60³⁄₄ 6 44 4³⁄₄ 9³⁄₄ 14³⁄₄ 34 67


(251) (178) (130) (1016) (1619) (327) (1543) (152) (1118) (121) (248) (375) (864) (1702)

25 14¹⁄₈ 11¹⁄₄ 7¹⁄₈ 62¹⁄₂ 79³⁄₄ 13³⁄₄ 76³⁄₄ 7¹⁄₂ 55 6 12¹⁄₂ 16¹⁄₂ 41¹⁄₂ 82
(359) (286) (181) (1588) (2026) (349) (1949) (191) (1397) (152) (318) (419) (1054) (2083)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.

S&C Specification Bulletin 662A-31 25


S&C Manual PMH Pad-Mounted Gear

Model PMH-8
14.4 kV and 25 kV Nominal

Dimensions in inches (mm)

6
(152)

1¹⁄₂
(38)
1¹⁄₂
(38)

FOUR ⁵⁄₈ (16) DIA. ANCHOR


BOLTS—BY USER

1¹⁄₂ (38) MIN.

2³⁄₄
(70)

2³⁄₄
(70)

kV,
A 1# A2 A3# B C D E1 E2 F G1 G2 H J K L M W
Nominal

14.4 9⁷⁄₈ 7 19 5¹⁄₈ 40 63³⁄₄ 12⁷⁄₈ 8³⁄₄ 60³⁄₄ 6 9¹⁄₄ 44 4³⁄₄ 9³⁄₄ 14³⁄₄ 34 67
(251) (178) (483) (130) (1016) (1619) (327) (222) (1543) (152) (235) (1118) (121) (248) (375) (864) (1702)

25 14¹⁄₈ 11¹⁄₄ 18³⁄₄ 7¹⁄₈ 62¹⁄₂ 79³⁄₄ 13³⁄₄ 8¹⁄₁₆ 76³⁄₄ 7¹⁄₂ 12¹⁄₂ 55 6 12¹⁄₂ 16¹⁄₂ 41¹⁄₂ 82
(359) (286) (476) (181) (1588) (2026) (349) (205) (1949) (191) (318) (1397) (152) (318) (419) (1054) (2083)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.

26 S&C Specification Bulletin 662A-31


S&C Manual PMH Pad-Mounted Gear

Model PMH-9
14.4 kV and 25 kV Nominal

Dimensions in inches (mm)

6
6 (152)
(152)

1¹⁄₂
(38)
1¹⁄₂
(38)

FOUR ⁵⁄₈ (16) DIA. ANCHOR


BOLTS—BY USER

1¹⁄₂ (38) MIN.

2³⁄₄
(70)

2³⁄₄
(70)

kV,
A1# A2 B C D E F G H J K L M W
Nominal

14.4 9⁷⁄₈ 7 5¹⁄₈ 40 63³⁄₄ 12⁷⁄₈ 60³⁄₄ 6 44 4³⁄₄ 9³⁄₄ 14³⁄₄ 34 67


(251) (178) (130) (1016) (1619) (327) (1543) (152) (1118) (121) (248) (375) (864) (1702)

25 14¹⁄₈ 11¹⁄₄ 7¹⁄₈ 62¹⁄₂ 79³⁄₄ 13³⁄₄ 76³⁄₄ 7¹⁄₂ 55 6 12¹⁄₂ 16¹⁄₂ 41¹⁄₂ 82
(359) (286) (181) (1588) (2026) (349) (1949) (191) (1397) (152) (318) (419) (1054) (2083)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.

S&C Specification Bulletin 662A-31 27


S&C Manual PMH Pad-Mounted Gear

Model PMH-10
14.4 kV and 25 kV Nominal

Dimensions in inches (mm)

6 6
(152) (152)

1¹⁄₂
(38)
1¹⁄₂
(38)

FOUR ⁵⁄₈ (16) DIA. ANCHOR


BOLTS (4)—BY USER

1¹⁄₂ (38) MIN.

2³⁄₄ 2³⁄₄
(70) (70)

kV,
A1# A2# B C D E F G H M W
Nominal

14.4 9⁷⁄₈ 9¹⁄₈ 15⁵⁄₈ 29¹⁄₂ 63³⁄₄ 12⁷⁄₈ 60³⁄₄ 6 44 34 67


(251) (232) (397) (749) (1619) (327) (1543) (152) (1118) (864) (1702)

25 14¹⁄₈ 14¹⁄₈ 7¹⁄₈ 62¹⁄₂ 79³⁄₄ 13³⁄₄ 76³⁄₄ 7¹⁄₂ 55 41¹⁄₂ 82


(359) (359) (181) (1588) (2026) (349) (1949) (191) (1397) (1054) (2083)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.

28 S&C Specification Bulletin 662A-31


S&C Manual PMH Pad-Mounted Gear

Model PMH-11
14.4 kV and 25 kV Nominal

Dimensions in inches (mm)

6 6
(152) (152)

1¹⁄₂
(38)
1¹⁄₂
(38)

FOUR ⁵⁄₈ (16) DIA. ANCHOR


BOLTS—BY USER

1¹⁄₂ (38) MIN.

2³⁄₄ 2³⁄₄
(70) (70)

kV,
A1# A2 B C D E F G H J K L M W
Nominal

14.4 9⁷⁄₈ 7 15⁵⁄₈ 29¹⁄₂ 63³⁄₄ 12⁷⁄₈ 60³⁄₄ 6 44 4³⁄₄ 9³⁄₄ 14³⁄₄ 34 67
(251) (178) (397) (749) (1619) (327) (1543) (152) (1118) (121) (248) (375) (864) (1702)

25 14¹⁄₈ 11¹⁄₄ 7¹⁄₈ 62¹⁄₂ 79³⁄₄ 13³⁄₄ 76³⁄₄ 7¹⁄₂ 55 6 12¹⁄₂ 16¹⁄₂ 41¹⁄₂ 82
(359) (286) (181) (1588) (2026) (349) (1949) (191) (1397) (152) (318) (419) (1054) (2083)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.

S&C Specification Bulletin 662A-31 29


S&C Manual PMH Pad-Mounted Gear

Model PMH-12
14.4 kV and 25 kV Nominal

Dimensions in inches (mm)

6
(152)

1¹⁄₂
(38)
1¹⁄₂
(38)

FOUR ⁵⁄₈ (16) DIA. ANCHOR


BOLTS—BY USER

1¹⁄₂ (38) MIN.

2³⁄₄
(70)

2³⁄₄
(70)

kV,
A1# A2 B C D E F G H J K L M W
Nominal

14.4 9⁷⁄₈ 7 5¹⁄₈ 40 63³⁄₄ 12⁷⁄₈ 60³⁄₄ 6 44 4³⁄₄ 9³⁄₄ 14³⁄₄ 34 67


(251) (178) (130) (1016) (1619) (327) (1543) (152) (1118) (121) (248) (375) (864) (1702)

25 14¹⁄₈ 11¹⁄₄ 7¹⁄₈ 62¹⁄₂ 79³⁄₄ 13³⁄₄ 76³⁄₄ 7¹⁄₂ 55 6 12¹⁄₂ 16¹⁄₂ 41¹⁄₂ 82
(359) (286) (181) (1588) (2026) (349) (1949) (191) (1397) (152) (318) (419) (1054) (2083)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.

30 S&C Specification Bulletin 662A-31


S&C Manual PMH Pad-Mounted Gear

Model PMH-13
14.4 kV and 25 kV Nominal

Dimensions in inches (mm)

6 6
(152) (152)

1¹⁄₂
(38)
1¹⁄₂
(38)

FOUR ⁵⁄₈ (16) DIA. ANCHOR


BOLTS—BY USER

1¹⁄₂ (38) MIN.

2³⁄₄
(70) 2³⁄₄
(70)

kV,
A 1# A 2# B C D E1 E2 F G1 G2 H M W
Nominal

14.4 9⁷⁄₈ 19 15⁵⁄₈ 29¹⁄₂ 63³⁄₄ 12⁷⁄₈ 8³⁄₄ 60³⁄₄ 6 9¹⁄₄ 44 34 67


(251) (483) (397) (749) (1619) (327) (222) (1543) (152) (235) (1118) (864) (1702)

25 14¹⁄₈ 18³⁄₄ 7¹⁄₈ 62¹⁄₂ 79³⁄₄ 13³⁄₄ 8¹⁄₁₆ 76³⁄₄ 7¹⁄₂ 12¹⁄₂ 55 41¹⁄₂ 82
(359) (476) (181) (1588) (2026) (349) (205) (1949) (191) (318) (1397) (1054) (2083)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.

S&C Specification Bulletin 662A-31 31


S&C Manual PMH Pad-Mounted Gear

Model PMH-19
14.4 kV Nominal

Dimensions in inches (mm)

44
(1118)
6 6
(152) (152)

1¹⁄₂
1¹⁄₂ (38)
67 (1702) 60³⁄₄ (1543)
(38)
63³⁄₄ (1619)

FOUR ⁵⁄₈ (16) DIA. ANCHOR


BOLTS—BY USER

67 (1702) 1¹⁄₂ (38) MIN.

4³⁄₄ 9³⁄₄ 14³⁄₄


(121) (248) (375)

7
(178)
15⁵⁄₈ (397)

2³⁄₄ 2³⁄₄
60³⁄₄ (70) (70) 29¹⁄₂ (749)
(1543)

9⁷⁄₈ (251)l

12⁷⁄₈ 6 6 6 6 12⁷⁄₈
(327) (152) (152) (152) (152) (327)

34 (864) (103° DOOR OPENINGS)


Printed in U.S.A.

# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-


termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.

32 S&C Specification Bulletin 662A-31

You might also like