S&C Spec Sheet
S&C Spec Sheet
S&C Spec Sheet
Specifications
Switching unloaded or lightly loaded delta-connected Protection of single-phase lateral circuits fed by single-
or ungrounded-primary wye-wye connected three-phase conductor shielded cable where the load is line-to-
transformers or banks (or line-to-line connected single- ground connected.
phase transformers), rated 150 kVA or less three-phase,
or 50 kVA or less single-phase—or of any kVA rating Switching with Mini-Rupter
when combined with unloaded cables or lines—where S&C Manual PMH Pad-Mounted Gear features S&C Mini-
maximum system operating voltage exceeds 22 kV. Rupter Switches for three-pole live switching of three-
Single-pole switching should be performed only if phase circuits.
each phase is carrying 5% load or more, or if the trans- Complete ratings for Mini-Rupters as applied in S&C
former or bank is temporarily grounded at the Manual PMH Pad-Mounted Gear are shown in the table
primary neutral during switching. below. In addition to the load-dropping ratings shown,
Switching loaded or unloaded ungrounded-primary Mini-Rupter is capable of interrupting transformer magne-
wye-delta connected three-phase transformers or tizing currents associated with the applicable loads, as well
banks—alone or combined with unloaded cables or as line-charging and cable-charging currents typical for
lines—where maximum system operating voltage distribution systems of these voltage ratings. For applica-
exceeds 22 kV. Single-pole switching should be per- tions on systems rated higher than 7.2 kV and involving
formed only if each phase is carrying 5% load or more load current with high harmonic content (such as rectifier
and if the lighting-load phase is always switched open load currents), refer to the nearest S&C Sales Office. The
first (or switched closed last); or if the transformer or two-time duty-cycle fault-closing ratings shown for Mini-
bank is temporarily grounded at the primary neutral Rupters define the ability to close the Mini-Rupter twice
during switching. against a three-phase fault with asymmetrical current in at
least one phase equal to the rated value, with the switch
Recommended Voltage Ratings of remaining operable and able to carry and interrupt rated
Current-Limiting Fuses for Use in current.
S&C Pad-Mounted Gear WARRANTY QUALIFICATIONS: The standard war-
In general, current-limiting fuses should have a maximum ranty contained in seller’s standard conditions of sale (as
voltage rating equal to, but not greater than 140% of, the set forth in Price Sheet 150) does not apply to S&C Manual
system line-to-line voltage since, for most applications, the PMH Pad-Mounted Gear where fuse units, fuse-unit end fit-
fuses can be exposed to full system line-to-line voltage in tings, holders, refill units, or switch blades of other than
clearing faults. Although there may be economic or space- S&C manufacture are used in conjunction with S&C SML
saving incentives for using current-limiting fuses with volt- Mountings. Nor does it apply to S&C Manual PMH Pad-
age ratings “appropriate for system line-to-ground voltage” Mounted Gear where other than Fault Fiter Electronic
(i.e., fuses with a voltage rating lower than line-to-line volt- Power Fuses, S&C Switch Blades, or the current-limiting
age but greater than or equal to maximum system line-to- fuses listed on page 19 are used in conjunction with Fault
ground voltage), S&C can recommend such use only in the Fiter Electronic Power Fuse Mountings and S&C Hold-
following applications: ers designed therefor, or when current-limiting fuses are
Protection of single-phase transformers serving single- applied other than as set forth under “Recommended
phase loads, Voltage Ratings of Current-Limiting Fuses for Use in S&C
Protection of three-phase lateral circuits fed by single- Pad-Mounted Gear” on page 3.
conductor shielded cable (provided each transformer
on that lateral is individually fused so that the current-
limiting fuse serving the lateral will not be required to
clear secondary faults), or
One-Second
Nom. Max BIL Cont. Load-Splitting Peak
Load Short Time
(Parallel or Peak RMS, Sym. Withstand,
Dropping Withstand,
Loop Switching) Peak
RMS, Sym.
SML- 14.4 17.0 95 200Ef 200 600 600 14 000 350 55112R3 825
20 25 27 125 200Ef 200 600 600 12 500 540 55113R3 1150
SML- 14.4 17.0 95 200E 200 600 600 12 500 310 55312R3 825
PMH-5d 23
4Z 25 27 125 200E 200 600 600 12 500l 540l 55313R3 1150
Fault 14.4 17.0 95 200 200 600 600 14 000 350 55512R3 825
Fiter4 25 29 125 200 200 600 600 12 500 540 55513R3 1150
SML- 14.4 17.0 95 200Ef 200 600 600 14 000 350 55122R4 1475
20 25 27 125 200Ef 200 600 600 12 500 540 55123R3 1975
SML- 14.4 17.0 95 200E 200 600 600 12 500 310 55322R4 1475
PMH-6d 24
4Z 25 27 125 200E 200 600 600 12 500l 540l 55323R3 1975
Fault 14.4 17.0 95 200 200 600 600 14 000 350 55522R4 1475
Fiter4 25 29 125 200 200 600 600 12 500 540 55523R3 1975
1 Fuse components are to be ordered separately. Refer to pages 13 ratings as listed on page 19 apply when current-limiting fuses are used.
through 18. Consult appropriate current-limiting fuse manufacturer for complete fuse
ratings.
2 Compartment numbers appear in corners of each diagram.
j Available only when ultimate user is an electric utility.
3 The short-circuit ratings expressed in amperes, RMS, asymmetrical
are 1.6 times the symmetrical values listed. Fault-closing and/or momen- d Key interlocks (Catalog Number Suffix “-C3” or “-C4”) are required for
tary ratings of switches and bus, and fault-closing capabilities and inter- ultimate users other than electric utilities.
rupting ratings of fuses, equal or exceed these values. For complete f SMU-20 Fuse Units are available in ratings through 200K amperes as
live-switching (as well as momentary and one-second) ratings for Mini- well as 200E amperes.
Rupters and complete live-switching capabilities of Uni-Rupters as applied
in S&C Manual PMH Pad-Mounted Gear, refer to “Application Notes” on l Applicable to solidly grounded-neutral systems only, with fuses
page 2. connected by single-conductor, concentric-neutral-type cable to a trans-
former or transformers. Rating is 9,400 amperes, RMS, symmetrical (405
4 These models also accommodate selected current-limiting fuses in MVA) for all other applications.
S&C Holders; refer to page 19. Maximum voltage and maximum ampere
TABLE CONTINUED v
14.4 17.0 95 200Ef 200 600 600 14 000 350 55132R4 1400
SML-20
25 27 125 200Ef 200 600 600 12 500 540 55133R3 1875
14.4 17.0 95 200E 200 600 600 12 500 310 55332R4 1400
PMH-7d SML-4Z 25
25 27 125 200E 200 600 600 12 500l 540l 55333R3 1875
Fault 14.4 17.0 95 200 200 600 600 14 000 350 55532R4 1400
Fiter4 25 29 125 200 200 600 600 12 500 540 55533R3 1875
14.4 17.0 95 200Ef 200 600 600 14 000 350 55142R4 1350
SML-20
25 27 125 200Ef 200 600 600 12 500 540 55143R3 1900
14.4 17.0 95 200E 200 600 600 12 500 310 55342R4 1350
PMH-8j SML-4Z 26
25 27 125 200E 200 600 600 12 500l 540l 55343R3 1900
Fault 14.4 17.0 95 200 200 600 600 14 000 350 55542R4 1350
Fiter4 25 29 125 200 200 600 600 12 500 540 55543R3 1900
14.4 17.0 95 200Ef 200 600 600 14 000 350 55152R4 1550
SML-20
25 27 125 200Ef 200 600 600 12 500 540 55153R3 2050
14.4 17.0 95 200E 200 600 600 12 500 310 55352R4 1550
PMH-9d SML-4Z 27
25 27 125 200E 200 600 600 12 500l 540l 55353R3 2050
Fault 14.4 17.0 95 200 200 600 600 14 000 350 55552R4 1550
Fiter4 25 29 125 200 200 600 600 12 500 540 55553R3 2050
14.4 17.0 95 200Ef 200 600 600 14 000 350 55162R4 1625
SML-20
25 27 125 200Ef 200 600 600 12 500 540 55163R3 2175
14.4 17.0 95 200E 200 600 600 12 500 310 55362R4 1625
PMH-11d SML-4Z 29
25 27 125 200E 200 600 600 12 500l 540l 55363R3 2175
Fault 14.4 17.0 95 200 200 600 600 14 000 350 55562R4 1625
Fiter4 25 29 125 200 200 600 600 12 500 540 55563R3 2175
TABLE CONTINUED v
14.4 17.0 95 200Ef 200 600 600 14 000 350 55172R4 1450
SML-20
25 27 125 200Ef 200 600 600 12 500 540 55173R3 1950
14.4 17.0 95 200E 200 600 600 12 500 310 55372R4 1450
PMH-12d SML-4Z 30
25 27 125 200E 200 600 600 12 500l 540l 55373R3 1950
Fault 14.4 17.0 95 200 200 600 600 14 000 350 55572R4 1450
Fiter4 25 29 125 200 200 600 600 12 500 540 55573R3 1950
SML-20 14.4 17.0 95 200Ef 200 600 600 14 000 350 55212R4 1625
PMH-19d SML-4Z 14.4 17.0 95 200E 200 600 600 12 500 310 55412R4 1625 32
Fault
14.4 17.0 95 200 200 600 600 14 000 350 55612R4 1625
Fiter4
1 Fuse components are to be ordered separately. Refer to pages 13 ratings as listed on page 19 apply when current-limiting fuses are used.
through 18. Consult appropriate current-limiting fuse manufacturer for complete fuse
ratings.
2 Compartment numbers appear in corners of each diagram.
d Key interlocks (Catalog Number Suffix “-C3” or “-C4”) are required for
3 The short-circuit ratings expressed in amperes, RMS, asymmetrical
ultimate users other than electric utilities.
are 1.6 times the symmetrical values listed. Fault-closing and/or momen-
tary ratings of switches and bus, and fault-closing capabilities and j Available only when ultimate user is an electric utility.
interrupting ratings of fuses, equal or exceed these values. For complete f SMU-20 Fuse Units are available in ratings through 200K amperes as
live-switching (as well as momentary and one-second) ratings for Mini- well as 200E amperes.
Rupters and complete live-switching capabilities of Uni-Rupters as
applied in S&C Manual PMH Pad-Mounted Gear, refer to “Application l Applicable to solidly grounded-neutral systems only, with fuses con-
Notes” on page 2. nected by single-conductor, concentric-neutral-type cable to a transformer
or transformers. Rating is 9,400 amperes, RMS, symmetrical (405 MVA) for
4 These models also accommodate selected current-limiting fuses in all other applications.
S&C Holders; refer to page 19. Maximum voltage and maximum ampere
OPTIONAL FEATURES
Suffix to be
Added to
Item Pad-Mounted Applicable to Models
Gear
Catalog Number
Light Gray Outdoor Ultradur Finish instead of Olive Green -A2 All models
Equipment Green Outdoor Finish (Toronto Standard) instead of Olive Green -A3 All models
Seafoam Green Outdoor Finish instead of Olive Green -A4 All models
Special Color Outdoor Ultradur Finish instead of Olive Green -A5 All models
With Olive Green Outdoor Ultradur Finish -A10 All models
Stainless-Steel Enclosure1 With Light Gray Outdoor Ultradur Finish -A12 All models
With Special Color Outdoor Ultradur Finish -A15 All models
For use except when Catalog Number Suffix
Hexhead Actuator for use in lieu of -B1a" All models
“-F2” is specified
pentahead actuator on all Penta-Latch
Mechanisms For use when Catalog Number Suffix “-F2” is
-B2n" All models except PMH-4
also specified
Copper Bus2 and Copper Switch Terminals, Fuse Connector Adapters, and Bus Terminals -B5 All models
Used with standard aluminum bus -B6 15-kV models of PMH-6, -7, -8, -9,
Reinforced Bus
Used with optional copper bus -B7 -10, -11, 12, -13
Key Interlocks to prevent paralleling of switches in Compartments 1 and 23 -C1 PMH-6, -9, -10, -11, -13, -19
Key Interlocks to prevent opening fuse-compartment doors unless all switches (series tap
-C3h PMH-5, -6, -7, -9, -11, -12, -19
switch only in PMH-19) are locked open3
Key Interlocks. Combines functions of options “-C1” and “-C3” listed above3 -C4h PMH-6, -9, -11, -19
Located in Compartment 1 -E1 PMH-5, -6, -7, -8, -9, -11, -19
Fuse-Storage Feature for three spare fuse
Located in Compartment 2 -E2 PMH-6, -7, -9, -11, -12, -19
assemblies per compartment4
Located in Compartments 1 and 2 -E3 PMH-6, -7, -9, -11, -19
1 When this optional feature is specified, the entire exterior of the Fiter Electronic Power Fuse Holder, or one spare current-limiting fuse
enclosure is fabricated from 11-gauge Type 304 stainless steel. When holder can be accommodated in each compartment.
specifying optional hexhead actuators, provisions for fault indicators a Specify Catalog Number Suffix “-B11” for gear with stainless-steel
with viewing windows in doors, or base spacer, specify the correct suffix enclosure.
for use in gear with a stainless-steel enclosure.
" Not available if UL listing (Catalog Number Suffix “-X”) is specified.
2 Copper bus measures ¹⁄₄!" 2!.
3 When specifying, please furnish name of ultimate user, station, and n Specify Catalog Number Suffix “-B12” for gear with stainless-steel
location of gear. enclosure.
h Must be specified if end user is not an electric utility and/or if Canadian
4 Fuse assemblies (fuse holders or fuse units with end fittings) are not
included. For units equipped with Fault Fiter Electronic Power Fuse Standards Association listing (Catalog Number Suffix “-Z”) is specified.
Mountings, two spare Fault Fiter Interrupting Modules, one spare Fault
TABLE CONTINUED v
OPTIONAL FEATURES—Continued
Suffix to be
Added to
Pad-Mounted
Item Applicable to Models
Gear
Catalog
Number
Copper Ground Stud for each switch, fuse, or In fuse compartments4 -H2 All models except PMH-3, -10, -13
bus terminal and ground pad3 In switch and bus compartments -J2 All models except PMH-4
1 Where the National Electrical Safety Code (ANSI Standard C2) app- 4 Including bus-compartment terminals in Model PMH-4.
lies, this optional feature may be included to meet the requirements of a Specify Catalog Number Suffix “-F12” for gear with stainless-steel
Section 381G. enclosure.
2 Meets RUS’s requirements for “dead-front.” d Not available if Canadian Standards Association listing (Catalog
3 Diameters of copper ground studs are as follows: Number Suffix “-Z”) is specified.
Ground Stud Diameter (inches)
Switch ¹⁄₂
Fuse ⁷⁄₁₆
Bus Terminal ⁷⁄₁₆
Ground Pad ⁷⁄₁₆
TABLE CONTINUED v
OPTIONAL FEATURES—Continued
Suffix to be Added to
Item Pad-Mounted Gear Applicable to Models
Catalog Number
TABLE CONTINUED v
OPTIONAL FEATURES—Continued
Suffix to be Added to
Item Pad-Mounted Gear Applicable to Models
Catalog Number
Switch- and Bus-Terminal Adapters—for connection of two cables (through 750 kc mil)
per terminal2
-M1 All models
Note: Space limitations prevent use of these adapters where surge arresters are to be
installed
1 Wood products used in the packaging are either hardwood or certified 3 These devices extend below the base of the unit. Provide a cable pit or
by the wood supplier as being “heat treated (kiln dried) to a core temp- specify a base spacer that provides a 12-inch (305 mm) or greater increase
erature of 133°F (56° Celsius) for a minimum of 30 minutes.” in cable-termination height.
2 When Catalog Number Suffix “-M1” or “-M2” is specified, cable-termi- 4 Surge arresters are base-mounted only (without isolators).
nation options (Catalog Number Suffixes “-U2” and “-U3”) cannot be f Not applicable to 25-kV models.
accommodated. In addition, when Catalog Number Suffixes “-M1” and
“-M2” are both specified, only one cable guide is provided at each switch l Not applicable to 14.4-kV models.
terminal. a A supplemental label is provided for Catalog Number Suffixes “-N11”
and “-N12” indicating the voltage rating of the surge arresters furnished.
TABLE CONTINUED v
OPTIONAL FEATURES—Continued
Suffix to be Added to
Item Pad-Mounted Gear Applicable to Models
Catalog Number
UL Listing. Includes “UL Listed” symbol on ratings label and nameplate -Xg v All 14.4 kV models
Canadian Standards Association Listing. Includes viewing window with tamper-resistant PMH-6, -9
cover in switch compartment door(s), and hazard-alerting labels and nameplate per CSA -Zajhg
specification PMH-11, -13, -19
PMH-10
1 These provisions accommodate Ohio Brass Type PDV (metal oxide), v Not available if hexhead actuator for use in lieu of pentahead actua-
McGraw-Edison Type AZL19C (metal oxide), General Electric Tranquell® tor on all Penta-Latch Mechanisms (Catalog Number Suffix “-B1,” “-B2,”
(metal oxide), or McGraw-Edison Type ES (silicon carbide) distribution- “-B11,” or “-B12”) is specified.
class surge arresters. Surge arresters must be base-mounted only (with- a Key interlocks (Catalog Number Suffix “-C3” or “-C4”) must be speci-
out isolators). fied on gear with fuse compartment(s).
d These devices extend below the base of the unit. Provide a cable pit or j Not available if mounting provisions for fault indicator with viewing win-
specify a base spacer. dow in switch compartment door(s) (Catalog Number Suffix “-F2” or “-F12”)
f Not applicable to 25-kV models. is specified.
l Not applicable to 14.4-kV models. h Not available if inner barrier panels (Catalog Number Suffix “-G7) is
g UL Listing (Catalog Number Suffix “-X”) cannot be furnished if Cana- specified.
dian Standards Association Listing (Catalog Number Suffix “-Z”) is speci-
fied and vice versa.
End Fittings (including Silencer), for use with SMU-20 Fuse Units 3097
For a complete listing of available ampere ratings, speeds, and catalog numbers, refer to pages 14 and 15.
1 These fuse units are usable in SM-20, SMD-20, SML-20, and SME-20
Mountings.
For a complete listing of available ampere ratings, speeds, and catalog numbers, refer to page 16.
1 These fuse units are usable in SM-4, SM-4Z, SML-4Z, and SME-4Z
Mountings.
Interrupting Modules1
Rating
Control Modules1
For a complete listing of available types, TCC curve parameters, and catalog numbers, refer to pages 17 and 18.
Rating, Rating,
Catalog Number Catalog Number
Amperes Amperes
1E 702001
3K 702003
6K 702006 5E 612005
8K 702008 7E 612007
10K 702010 10E 612010
12K 702012 13E 612013
15K 702015 15E 612015 712015
20K 702020 20E 612020 712020
25K 702025 25E 612025 712025
30K 702030 30E 612030 712030
40K 702040 40E 612040 712040
50K 702050 50E 612050 712050 602050
65K 702065 65E 612065 712065 602065
80K 702080 80E 612080 712080 602080
100K 702100 100E 612100 712100 602100
140K 702140 125E 612125 712125 602125
200K 702200 150E 612150 712150 602150
175E 612175 712175 602175
200E 612200 712200 602200
1 These fuse units are equally suitable for use in SMD-20 Outdoor
Distribution Mountings; and also, for use with SME-20 Fuse-Unit End
Fittings listed in Specification Bulletin 665-31, “S&C Manual PME Pad-
Mounted Gear” and Specification Bulletin 666-31, “S&C Remote Super-
visory PME Pad-Mounted Gear.”
Rating, Rating,
Catalog Number Catalog Number
Amperes Amperes
1E 703001
3K 703003
6K 703006 5E 613005
8K 703008 7E 613007
10K 703010 10E 613010
12K 703012 13E 613013
15K 703015 15E 613015 713015
20K 703020 20E 613020 713020
25K 703025 25E 613025 713025
30K 703030 30E 613030 713030
40K 703040 40E 613040 713040
50K 703050 50E 613050 713050 603050
65K 703065 65E 613065 713065 603065
80K 703080 80E 613080 713080 603080
100K 703100 100E 613100 713100 603100
140K 703140 125E 613125 713125 603125
200K 703200 150E 613150 713150 603150
175E 613175 713175 603175
200E 613200 713200 603200
1 These fuse units are equally suitable for use in SMD-20 Outdoor 2 Also suitable for protection of single-phase-to-neutral circuits (lines or
Distribution Mountings; and also, for use with SME-20 Fuse-Unit End transformers) on 20/34.5 GrY-kV systems.
Fittings listed in Specification Bulletin 665-31, “S&C Manual PME Pad-
Mounted Gear” and Specification Bulletin 666-31, “S&C Remote Super-
visory PME Pad-Mounted Gear.”
1 122001R4 123001R4
2 122002R4 123002R4
S&C Std. S&C Slow S&C Coord. S&C Std. S&C Slow
Speed
TCC 153-4 TCC 119-4 TCC 179-4 TCC 153-4 TCC 119-4
3E 122005R4 123005R4
5E 122007R4 123007R4
7E 122010R4 123010R4
10E 122015R4 123015R4
13E 122020R4 123020R4
15E 122025R4 252025R4 123025R4 253025R4
20E 122030R4 252030R4 123030R4 253030R4
25E 122040R4 252040R4 123040R4 253040R4
30E 122050R4 252050R4 123050R4 253050R4
40E 122060R4 252060R4 123060R4 253060R4
50E 122075R4 252075R4 123075R4 253075R4
65E 122100R4 252100R4 123100R4 253100R4
80E 122125R4 252125R4 123125R4 253125R4
100E 122150R4 252150R4 123150R4 253150R4
125E 122200R4 252200R4 123200R4 253200R4
150E 122250R4 252250R4 123250R4 253250R4
175E 122275R4 252275R4 123275R4 253275R4
200E 122300R4 252300R4 123300R4 253300R4
210E 382210R4f
1 These refill units are also suitable for use with SME-4Z Holders listed f This S&C Coordinating Speed refill unit should be applied where the
in Specification Bulletin 665-31, “S&C Manual PME Pad-Mounted Gear” maximum continuous load current does not exceed 200 amperes and
and Specification Bulletin 666-31, “S&C Remote Supervisory PME Pad- where all fault currents below 1000 amperes will be cleared by another
Mounted Gear.” fuse.
2 Rated 14.4 kV nominal, for use in SM-4 Holders rated 14.4 kV when
applied in listed mountings rated 13.8 kV or in discontinued mountings
rated 14.4 kV.
1 This control module is applicable for protection of 15-kV and 25-kV the load side of Fault Fiter. If the maximum rated transformer kVA con-
class underground distribution subloops having the following parameters: nected is greater than the values listed above, or if the application involves
maximum available fault current—14,000 amperes, RMS, symmetrical at protection of circuits serving industrial, commercial, or institutional loads,
15 kV, 12,500 amperes, RMS, symmetrical at 25 kV; maximum rated contact your nearest S&C Sales Office.
transformer kVA connected for residential circuits—1200 kVA single- 2 Control modules rated 600 amperes continuous are also applicable for
phase, 3600 kVA three-phase at 15 kV, 2400 kVA single-phase, 7200 kVA use in mountings rated 200 amperes or 400 amperes continuous.
three-phase at 25 kV; with no capacitor banks or current-limiting fuses on
400 814040
500 814050
600 814060
700 814070
600
800 814080
1000 814100
1250 814125
1500 814150
1 Control modules rated 600 amperes continuous are also applicable for
use in mountings rated 200 amperes or 400 amperes continuous.
3000 8 7010-C40S1T3D8
1
6000 8 7010-C40S1T6D8
3000 8 7010-C40S2T3D8
2
6000 8 7010-C40S2T6D8
400
3000 8 7010-C40S3T3D8
3
6000 8 7010-C40S3T6D8
3000 8 7010-C40S4T3D8
4
6000 8 7010-C40S4T6D8
3000 8 7010-C60S1T3D8
1
6000 8 7010-C60S1T6D8
3000 8 7010-C60S2T3D8
2
6000 8 7010-C60S2T6D8
600
3000 8 7010-C60S3T3D8
3
6000 8 7010-C60S3T6D8
3000 8 7010-C60S4T3D8
4
6000 8 7010-C60S4T6D8
600
3000 8 7010-C80S1T3D8
1
6000 8 7010-C80S1T6D8
3000 8 7010-C80S2T3D8
2
6000 8 7010-C80S2T6D8
800
3000 8 7010-C80S3T3D8
3
6000 8 7010-C80S3T6D8
3000 8 7010-C80S4T3D8
4
6000 8 7010-C80S4T6D8
3000 8 7010-C110S1T3D8
1
6000 8 7010-C110S1T6D8
3000 8 7010-C110S2T3D8
2
6000 8 7010-C110S2T6D8
1100
3000 8 7010-C110S3T3D8
3
6000 8 7010-C110S3T6D8
3000 8 7010-C110S4T3D8
4
6000 8 7010-C110S4T6D8
1 Control modules rated 600 amperes continuous are also applicable for
use in mountings rated 200 amperes or 400 amperes continuous.
Current-Limiting Fuse1
For use in
PMH Models Requires
with Rating2 S&C Holder3
Nominal Voltage Manufacturer Type Catalog Number4
Max Amperes, Max Current,
Rating, kV
kV Amperes, RMS
1 Fuses must be furnished by others. 3 Holders for 14.4-kV PMH models are rated 14.4 kV nominal, 17.0 kV
2 Maximum voltage and current ratings listed apply to the complete maximum, 200 amperes maximum. Holders for 25-kV PMH models are
pad-mounted gear unit. Consult fuse manufacturer for complete fuse rated 25 kV nominal, 29 kV maximum, 200 amperes maximum.
ratings. 4 Includes adapters when required.
SWITCH BLADES1
Rating
Switch Blade, for use in lieu of SMU-20 14.4 17.0 200 5432
Fuse Unit in SML-20 Mounting 25 27 200 5433
Switch Blade, for use in lieu of SML-4Z 14.4 17.0 200 5442
Holder in SML-4 Mounting 25 27 200 5443
Switch Blade, for use in lieu of Fault Fiter 14.4 17.0 400 3222
Holder in Fault Fiter Mounting 25 29 200 3223R1
1 When switch blades are used in lieu of fuses, the Uni-Rupter associ- fault-closing ratings equal to those of S&C Power Fuses with Uni-Rupter
ated with these switches can carry and interrupt load currents up to and (refer to “Application Notes” on page 2). The momentary and one-second
including the emergency peak-load capabilities of the SML power fuses, ratings of the switches equal the short-circuit ratings of the pad-mounted
or up to 400 amperes at 14.4 kV and 200 amperes at 25 kV for Fault Fiter gear.
Electronic Power Fuses. Furthermore, the switches with Uni-Rupter have
ACCESSORIES
Item Catalog Number
Voltage Tester with audio and visual signals, includes voltage tester, batteries, adapter for shotgun clamp sticks, and
9931-072
storage case1
1 For ultimate users other than electric utilities, also specify a shotgun
clamp stick of the appropriate length.
CONNECTOR
Illustration Description Accommodating Connector Catalog Number
Bronze Body, Tin Plated, Two Galvanized No. 2 solid through 500 kc mil
4745
Steel Bolts, Two Belleville Washers stranded copper or aluminum
Model PMH-3
14.4 kV and 25 kV Nominal
6
(152)
1¹⁄₂ 1¹⁄₂
(38) (38)
2³⁄₄ 2³⁄₄
(70) (70)
kV,
A1l A2l B C D E1 E2 F G1 G2 G3 H M W
Nominal
9⁷⁄₈ 11¹⁄₈ 5¹⁄₈ 17 40³⁄₄ 12⁷⁄₈ 7¹⁄₂ 37³⁄₄ 6 9³⁄₄ 9³⁄₄ 44 34 34⁷⁄₈
14.4 (432) (152) (1118) (864)
(251) (283) (130) (1035) (327) (191) (959) (248) (248) (886)
14¹⁄₈ 15¹⁄₄ 7¹⁄₈ 42¹⁄₂ 59³⁄₄ 13³⁄₄ 9⁵⁄₈ 56³⁄₄ 7¹⁄₂ 10 12¹⁄₂ 55 42¹⁄₂ 43
25 (254) (1397) (1092)
(359) (387) (181) (1080) (1518) (349) (244) (1441) (191) (318) (1070)
Model PMH-4
14.4 kV and 25 kV Nominal
1¹⁄₂ 1¹⁄₂
(38) (38)
2³⁄₄ 2³⁄₄
(70) (70)
kV,
A1 A2# B C D E F G1 G2 H J K M W
Nominal
14.4 7 11¹⁄₈ 5¹⁄₈ 27¹⁄₂ 40³⁄₄ 7⁷⁄₈ 37³⁄₄ 9³⁄₄ 9³⁄₄ 44 10¹⁄₂ 9³⁄₄ 34 34⁷⁄₈
(178) (283) (130) (699) (1035) (200) (959) (248) (248) (1118) (267) (248) (864) (886)
25 11¹⁄₄ 15¹⁄₄ 7¹⁄₈ 42¹⁄₂ 59³⁄₄ 9⁵⁄₈ 56³⁄₄ 10 12¹⁄₂ 55 11¹⁄₂ 12¹⁄₂ 42¹⁄₂ 43
(286) (387) (181) (1080) (1518) (244) (1441) (254) (318) (1397) (292) (318) (1070) (1092)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.
Model PMH-5
14.4 kV and 25 kV Nominal
6
(152)
1¹⁄₂ 1¹⁄₂
(38) (38)
2³⁄₄ 2³⁄₄
(70) (70)
kV,
A1# A2 B C D E F G H J K M W
Nominal
25 14¹⁄₈ 11¹⁄₄ 7¹⁄₈ 51 68¹⁄₄ 13³⁄₄ 65¹⁄₄ 7¹⁄₂ 55 6⁵⁄₈ 12¹⁄₂ 42¹⁄₂, 43
(359) (286) (181) (1295) (1734) (349) (1657) (191) (1397) (168) (318) (1070) (1092)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.
Model PMH-6
14.4 kV and 25 kV Nominal
6 6
(152) (152)
1¹⁄₂
(38)
1¹⁄₂
(38)
2³⁄₄
(70)
2³⁄₄
(70)
kV,
A1# A2 B C D E F G H J K L M W
Nominal
25 14¹⁄₈ 11¹⁄₄ 7¹⁄₈ 62¹⁄₂ 79³⁄₄ 13³⁄₄ 76³⁄₄ 7¹⁄₂ 55 6 12¹⁄₂ 16¹⁄₂ 41¹⁄₂ 82
(359) (286) (181) (1588) (2026) (349) (1949) (191) (1397) (152) (318) (419) (1054) (2083)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.
Model PMH-7
14.4 kV and 25 kV Nominal
6
(152)
1¹⁄₂
(38)
1¹⁄₂
(38)
2³⁄₄
(70)
2³⁄₄
(70)
kV,
A1# A2 B C D E F G H J K L M W
Nominal
25 14¹⁄₈ 11¹⁄₄ 7¹⁄₈ 62¹⁄₂ 79³⁄₄ 13³⁄₄ 76³⁄₄ 7¹⁄₂ 55 6 12¹⁄₂ 16¹⁄₂ 41¹⁄₂ 82
(359) (286) (181) (1588) (2026) (349) (1949) (191) (1397) (152) (318) (419) (1054) (2083)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.
Model PMH-8
14.4 kV and 25 kV Nominal
6
(152)
1¹⁄₂
(38)
1¹⁄₂
(38)
2³⁄₄
(70)
2³⁄₄
(70)
kV,
A 1# A2 A3# B C D E1 E2 F G1 G2 H J K L M W
Nominal
14.4 9⁷⁄₈ 7 19 5¹⁄₈ 40 63³⁄₄ 12⁷⁄₈ 8³⁄₄ 60³⁄₄ 6 9¹⁄₄ 44 4³⁄₄ 9³⁄₄ 14³⁄₄ 34 67
(251) (178) (483) (130) (1016) (1619) (327) (222) (1543) (152) (235) (1118) (121) (248) (375) (864) (1702)
25 14¹⁄₈ 11¹⁄₄ 18³⁄₄ 7¹⁄₈ 62¹⁄₂ 79³⁄₄ 13³⁄₄ 8¹⁄₁₆ 76³⁄₄ 7¹⁄₂ 12¹⁄₂ 55 6 12¹⁄₂ 16¹⁄₂ 41¹⁄₂ 82
(359) (286) (476) (181) (1588) (2026) (349) (205) (1949) (191) (318) (1397) (152) (318) (419) (1054) (2083)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.
Model PMH-9
14.4 kV and 25 kV Nominal
6
6 (152)
(152)
1¹⁄₂
(38)
1¹⁄₂
(38)
2³⁄₄
(70)
2³⁄₄
(70)
kV,
A1# A2 B C D E F G H J K L M W
Nominal
25 14¹⁄₈ 11¹⁄₄ 7¹⁄₈ 62¹⁄₂ 79³⁄₄ 13³⁄₄ 76³⁄₄ 7¹⁄₂ 55 6 12¹⁄₂ 16¹⁄₂ 41¹⁄₂ 82
(359) (286) (181) (1588) (2026) (349) (1949) (191) (1397) (152) (318) (419) (1054) (2083)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.
Model PMH-10
14.4 kV and 25 kV Nominal
6 6
(152) (152)
1¹⁄₂
(38)
1¹⁄₂
(38)
2³⁄₄ 2³⁄₄
(70) (70)
kV,
A1# A2# B C D E F G H M W
Nominal
Model PMH-11
14.4 kV and 25 kV Nominal
6 6
(152) (152)
1¹⁄₂
(38)
1¹⁄₂
(38)
2³⁄₄ 2³⁄₄
(70) (70)
kV,
A1# A2 B C D E F G H J K L M W
Nominal
14.4 9⁷⁄₈ 7 15⁵⁄₈ 29¹⁄₂ 63³⁄₄ 12⁷⁄₈ 60³⁄₄ 6 44 4³⁄₄ 9³⁄₄ 14³⁄₄ 34 67
(251) (178) (397) (749) (1619) (327) (1543) (152) (1118) (121) (248) (375) (864) (1702)
25 14¹⁄₈ 11¹⁄₄ 7¹⁄₈ 62¹⁄₂ 79³⁄₄ 13³⁄₄ 76³⁄₄ 7¹⁄₂ 55 6 12¹⁄₂ 16¹⁄₂ 41¹⁄₂ 82
(359) (286) (181) (1588) (2026) (349) (1949) (191) (1397) (152) (318) (419) (1054) (2083)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.
Model PMH-12
14.4 kV and 25 kV Nominal
6
(152)
1¹⁄₂
(38)
1¹⁄₂
(38)
2³⁄₄
(70)
2³⁄₄
(70)
kV,
A1# A2 B C D E F G H J K L M W
Nominal
25 14¹⁄₈ 11¹⁄₄ 7¹⁄₈ 62¹⁄₂ 79³⁄₄ 13³⁄₄ 76³⁄₄ 7¹⁄₂ 55 6 12¹⁄₂ 16¹⁄₂ 41¹⁄₂ 82
(359) (286) (181) (1588) (2026) (349) (1949) (191) (1397) (152) (318) (419) (1054) (2083)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.
Model PMH-13
14.4 kV and 25 kV Nominal
6 6
(152) (152)
1¹⁄₂
(38)
1¹⁄₂
(38)
2³⁄₄
(70) 2³⁄₄
(70)
kV,
A 1# A 2# B C D E1 E2 F G1 G2 H M W
Nominal
25 14¹⁄₈ 18³⁄₄ 7¹⁄₈ 62¹⁄₂ 79³⁄₄ 13³⁄₄ 8¹⁄₁₆ 76³⁄₄ 7¹⁄₂ 12¹⁄₂ 55 41¹⁄₂ 82
(359) (476) (181) (1588) (2026) (349) (205) (1949) (191) (318) (1397) (1054) (2083)
# When Catalog Number Suffix “-M1,” “-U2,” or “-U3” is specified, cable-
termination locations will be slightly affected. Consult your nearest S&C
Sales Office for details.
Model PMH-19
14.4 kV Nominal
44
(1118)
6 6
(152) (152)
1¹⁄₂
1¹⁄₂ (38)
67 (1702) 60³⁄₄ (1543)
(38)
63³⁄₄ (1619)
7
(178)
15⁵⁄₈ (397)
2³⁄₄ 2³⁄₄
60³⁄₄ (70) (70) 29¹⁄₂ (749)
(1543)
9⁷⁄₈ (251)l
12⁷⁄₈ 6 6 6 6 12⁷⁄₈
(327) (152) (152) (152) (152) (327)