Potter
Potter
Potter
Potter Electric Signal Company, LLC • St. Louis, MO 63042 USA• Cust Service: 866-956-1211 • Tech Support: 866-240-1870 • Canada: 888-882-1833 • www.pottersignal.com
METHOD 1: When using PS10-EX and control unit with retard, METHOD 2: When using the PS10-EX for local bell application or
connect the PS10-EX into alarm port piping on the input side of retard with a control that does not provide a retard feature, the PS10-EX
chamber and electrically connect PS10–EX to control unit that pro- must be installed on the alarm outlet side of the retard chamber of the
vides a retard to compensate for surges. Ensure that no shut off valves Wet Pipe Alarm Valve trim.
are present between the alarm check valve and the PS10-EX.
PS10-EXF
METHOD 1 METHOD 2 ALARM PRESSURE
SWITCH
PS10-EXF WATER PS10-EXF WATER WATER WATER
WATER PS10-EXF PS10-EXF
MOTOR MOTOR MOTOR MOTOR MOTOR
GONG GONG GONG GONG
GONG
CHECK
WET RBVS RETARD RBVS WET RBVS CHECK
WET RETARD
RBVS WET DRY VALVE R
SYSTEM SYSTEM RBVS DRY VALVE
ALARM
SYSTEM SYSTEM PIPE
ALARM PIPE
ALARM ALARM VALVE
CHECK CHECK RETARD VALVE
VALVE CHECK VALVE CHECK RETARD
VALVE VALVE
WATER WATER
WATER
OS & Y BY-PASS WATER OS & Y BY-PASS WATER
OS & Y BY-PASS WATER
VALVE VALVE BY-PASS VALVE VALVE
OS & Y VALVE VALVE BY-PASS OS & Y BY-PASS
VALVE OS & Y
VALVE VALVE VALVE VALVE
VALVE
DWG# 8880010-1
DWG# 8880010-1 DWG# 8880010-1
DWG# 8880010-1
The closing of any shutoff valves between the alarm check valve and the PS10-EX will render the PS10-EX inoperative. To comply with
the IBC, IFC, & NFPA-72 any such valve shall be electrically supervised with a supervisory switch such as Potter Model RBVS.
Dry System Supervisory Signal (Low/High air) Dry System Water Flow Alarm
Connect the PS10-EX to the Dry Pipe Valve Trim piping at the Connect the PS10-EX into the piping that extends from the
supervisory Air/Gas Dry Pipe Valve supply line connected to the DPV. intermediate chamber of the dry sprinkler valve. Install on the outlet
A Model BVL bleeder valve as supplied by Potter Electric Signal side of the in-line check valve of the piping. Insure that no shut off
St. Louis, MO. or equivalent shall be connected between the air line valves are present between the dry sprinkler valve and the PS10-EX.
and the device to provide a means of testing the operation of the
supervisory switch. (Low Air Only) To test the High setting the system Testing: Accomplished by opening the water by-pass test valve.
pressure must be increased in the alarm line to operate the switch.
DRY SYSTEM
DRY SYSTEM PS10-EXF
ALARM
PRESSURE WATER
PRESSURE SUPERVISORY SWITCH PRESSURE SUPERVISORY SWITCH SWITCH MOTOR
PS10-EXF PS10-EXF
GONG
DRY CHECK
AIR LINE SYSTEM RBVS
VALVE
AIR LINE SHUT-FF ALARM
SHUT-FF VALVE BLEEDER CHECK
TEST VALVE
VALVE BLEEDER CHECK VALVE
TEST VALVE BVL
CHECK VALVE
VALVE BVL WATER
BY-PASS
OS & Y
TEST
VALVE
VALVE
DWG# 1029-1
DWG# 1029-1
The closing of any shutoff valves between the alarm check valve and the PS10-EX will render the PS10-EX inoperative. To comply with
the IBC, IFC, & NFPA-72 any such valve shall be electrically supervised with a supervisory switch such as Potter Model RBVS.
Typical Electrical Connections
NG
MI
CO
IN
An uninsulated section of a single conductor should not be looped
around the terminal and serve as two separate connections. The wire
must be severed, thereby providing supervision of the connection in
NG the event that the wire becomes dislodged from under the terminal.
OI DWG# 923-3
TG
OU
Line-Black Load-Black
AC BREAKER
BELL
Neutral-White
TO FIRE
TO FIREALARM
ALARM PANEL
PANEL TO FIRE ALARM PANEL TO FIRE ALARM PANEL
DWG# 5924-1 DWG# 5924-3A
SEE NOTE 2
GROUND SCREW
NOTES:
1. THESE CONTACTS CLOSE ON A PRESSURE DECREASE
2. THESE CONTACTS CLOSE ON A PRESSURE INCREASE
1/2” NPT FEMALE CONDUIT
OPENING. TO MAINTAIN
TYPE “d” COMPONENT
FRONT VIEW PROTECTION USE AN EX
(SHOWN WITHOUT COVER) COMPONENT CONDUIT
SEALING DEVICE
REMOVE SCREW AND
RAISE COVER SLEEVE
FOR ACCESS TO PRESSURE
ADJUSTMENT KNOBS.
LOW PRESSURE REPLACE WHEN
ADJUSTMENT KNOB ADJUSTMENTS ARE
COMPLETE.
HIGH PRESSURE
ADJUSTMENT KNOB
Field Adjustments
Pressure Switch Termination
The operating point of the switches on the PS10-EX can be adjusted to
PRESSURE
INCREASE
N.C. any point between 27-137 kPA/.27-1.3 BAR/4-20 PSI by turning the
COM.
N.O.
adjustment knob(s) clockwise to raise the actuation point, and counter-
clockwise to lower the actuation point. The two switches operate
completely independently of one another, and each switch may be
COM. N.O. N.C.
adjusted to actuate at any point the system requires. Final adjustment
should be made with a pressure gauge.
DWG# 983-4Y
Note: Switches are shown in standby condition with no pressure Use of pipe joint cement may result in obstruction of the aperature
applied.
and loss of signal.
When this device is to be installed in an area that is classified as “HAZARDOUS”, the person responsible for safety in the area shall be
contacted to determine if the tools and operations required for the installation of the device and associated components are permitted in
the area. To reduce the risk of ignition of hazardous atmospheres, disconnect supply circuits before opening cover. Keep cover tight while
circuits are live.
The mating surfaces of the cover and housing are designed and machined to meet the hazardous location requirements of the applicable
listing agencies. These surfaces shall be protected from any damage and shall be clean and free of all foreign matter. No gasket or sealant
of any type is allowed on these surfaces. The use of any type of gasket, sealant, or damage to these surfaces will void the hazardous rating
of the device and can lead to explosion and death. These surfaces are not repairable and the cover is not replaceable. If any damage has
occurred to either surface or a gasket or sealant has been applied to either surface, the entire device must be immediately removed from
service and replaced. All foreign matter must be removed. If mating surfaces are damaged, do not place the device in service.
Important: When reinstalling the cover during installation or maintenance, wipe the mating cover and housing surfaces with a soft clean lint
free cloth. Carefully inspect the surfaces for any damage or foreign matter. Firmly push the cover on the housing to fully seat the mating
surfaces. Initially tighten each of the (3) cover screws evenly to 5 in-lbs (.56 n-m) to ensure that the cover is fully seated. Next, torque each
cover screw to a final torque of 50 in-lbs (5.7 n-m). Failure to follow these instructions may result in injury or death.
Engineer/Architect Specifications
Pressure type waterflow switches shall be a Model PS10-EX as Switches shall have a maximum service pressure rating of 17.2 BAR
manufactured by Potter Electric Signal Co. of St. Louis, Mo. and (250 PSI) and shall be factory adjusted to operate on pressure increase
shall be installed on the sprinkler systems as shown on the drawings at .41 ±.07 BAR (6 ±1 PSI). There shall be two (2) SPDT contacts
and/or specified herein. rated at 15.0 Amps at 125/250VAC and 2.0 Amps at 30VDC. The
switch housing shall be weather proof and oil resistant with a NEMA
Switches shall be provided with a 1/2" NPT male pressure connection 4,9 rating.
to be connected into the alarm check valve of a “wet” sprinkler
system or into the intermediate chamber of a “dry” pipe system and The unit shall be listed by Underwriters Laboratories, Inc. and CSFM
shall be actuated by any flow of water to or in excess of the discharge and approved by Factory Mutual. It shall be rated for use in hazardous
from one sprinkler head. locations classified as Class I, Div. 1 & 2, Groups B, C, D; Class
II, Div. 1 & 2, Groups E, F, G; Class III, Div. 1 & 2.