PS3 Serie
PS3 Serie
PS3 Serie
Alco Controls
Pressure Switch
D A T A S H E E T
The ALCO PS3 is a Pressure Switch with fixed switch-point
settings.
Features
• Maximum Operating Pressure up to 43 bar
• Test Pressure up to 48 bar
• Standard factory settings from stock in small volumes
• High and low pressure switches
• High temperature version with snubber for direct
compressor mounting (Range 6)
• Direct mounting reduces the number of joints and thus
avoiding potential leakage
• Precise setting and repeatability
• IP 65 protection if used with the new PS3-Nxx and PS3-
Lxx cables with plug (acc. EN 175301-803), no additional
gasket required (molded into plug)
• Customer specific versions in multipacks, minimum order
quantity 100 Stück
Options
• For direct mounting on a pressure connection (free
standing) or with a capillary tube
• Direct compressor head mounting with high temperature
PS3
bellows and snubber:
- reduces the number of joints
Standards
- avoids potential leakage
- saves high cost of flexible hose per Low Voltage Directive
• TÜV approved versions for high and low pressure
per PED Directive 97/23/EC, TÜV appr. versions only
• Micro-switch for narrow pressure differentials
• Gold plated contacts for low voltage/current applications Manufactured and tested to standards on our own
• Cables with plug PS3-Nxx/PS3-Lxx not included; to be responsibility
ordered separately (see page 8 for details)
Underwriter Laboratories
Introduction
PS3 are equipped with a SPDT snap action contact, switching
from 1-2 to 1-4 on rising pressure and from 1-4 to 1-2 on falling
pressure (see diagram). The PS3 is factory preset according to
customers specification and is not adjustable. Several models
are available:
PS3__35003_EN_R08.doc 1 / 10 09.08.2011
PS3
Alco Controls
Pressure Switch
D A T A S H E E T
Technical data
Pressure sensing element
Type of Max. medium Construction Material Snubber Pressure TÜV Function Possible
diaphragm temperature Ranges approval Code * Pressure Conn.
Standard + 70° C Single diaphragm Bronze no 1-5 No A,R A,K,L,S,U,X
temperature Double diaphragm Bronze no 1-5 Yes B,S,W A,K,L,S,U,X
High + 150° C Bellows Stainless yes 6 Yes B,S,W S,U,X
temperature steel 6 no A,R S,U,X
*) see page 7 for more details.
Maximum ambient temperature (°C)
Note: For high temperature applications, i. e. medium 70
temperatures between 70 °C and 150 °C, the maximum
ambient temperature must be derated as per drawing. 60
E.g.: on medium temperature 120 °C the ambient temperature
of 55 °C around the switch housing should not be exceeded. 50
40
30
70 80 90 100 110 120 130 140 150
Medium temperature (°C)
PS3__35003_EN_R08.doc 2 / 10 09.08.2011
PS3
Alco Controls
Pressure Switch
D A T A S H E E T
Selection
1. Preferred types
Type PCN Fixed setting Reset Max. temperature Leakage Pressure
(bar) test connection
pressure pressure
Cut-out Cut-in ambient connection (bar)
Low Pressure Controls / Pressure Limiter for low pressure protection PSL EN 12263
PS3-W1S 0 714 760 -0,3 1,2 7/16"-20 UNF
PS3-W1S 0 714 761 0,3 1,8 Auto + 70°C + 70°C 30 female thread with
PS3-W1S 0 714 762 2,0 3,5 Schrader opener
Pressure Limiter for high pressure protection PSH with snubber for direct compressor mounting EN 12263
PS3-W6S 0 715 831 14,0 10,0
PS3-W6S 0 715 556 21,0 16,0 7/16"-20 UNF
PS3-W6S 0 715 555 25,0 20,0 Auto + 70°C + 150°C 48 female thread with
PS3-W6S 0 715 567 29,0 23,0 Schrader opener
PS3-W6S 0 715 550 33,5 27,5 and snubber
PS3-W6S 0 715 553 40,0 33,0
Pressure Cut Out for high pressure protection PZH with snubber for direct compressor mounting EN 12263
PS3-B6S 0 715 568 19,2
PS3-B6S 0 715 564 22,7 appr. external 7/16"-20 UNF
PS3-B6S 0 715 563 27,3 5 bar manual + 70°C + 150°C 48 female thread with
PS3-B6S 0 715 569 29,5 below reset Schrader opener
PS3-B6S 0 715 560 36,0 cut-out and snubber
Delivery: small quantities, single package without plug (Cables with plug must be ordered separately, see page 8)
Switching points
The differential of factory set switch points can be adjusted Example
within the limits given in the charts on page 4 to 6. Use the 40
Notes:
1. Specify always upper and lower switching points for 0
PS3__35003_EN_R08.doc 3 / 10 09.08.2011
PS3
Alco Controls
Pressure Switch
D A T A S H E E T
Range 1 / A
6
4
Pressure (bar)
-1
0 1 2 3 4 5 6 7 8 9 10 11
Range 3 / C
16
14
12
10
Pressure (bar)
0
0 1 2 3 4 5 6 7 8 9 10 11
PS3__35003_EN_R08.doc 4 / 10 09.08.2011
PS3
Alco Controls
Pressure Switch
D A T A S H E E T
Range 4 / D
30
25
20
Pressure (bar)
15
10
0
0 1 2 3 4 5 6 7 8 9 10 11
Range 5 / E
30
25
20
Pressure (bar)
15
10
0
0 1 2 3 4 5 6 7 8 9 10 11
PS3__35003_EN_R08.doc 5 / 10 09.08.2011
PS3
Alco Controls
Pressure Switch
D A T A S H E E T
Range 6 / F
45
40
35
30
Pressure (bar)
25
20
15
10
0
0 1 2 3 4 5 6 7 8 9 10 11
Selection guide
Condenser
PS3-A6S
Receiver
PS3-B6S* Service Valve
PS3-W1S* PS3-W1S
PS3-W1U
Service Valve
Evaporator
*) Requires additional adapter such as: 1/8 or 1/4 NPT by 7/16-20 UNF flare male (see Other Accessories on page 8)
PS3__35003_EN_R08.doc 6 / 10 09.08.2011
PS3
Alco Controls
Pressure Switch
D A T A S H E E T
Selection Sheet
PS3__35003_EN_R08.doc 7 / 10 09.08.2011
PS3
Alco Controls
Pressure Switch
D A T A S H E E T
Accessories
Cables with Plug for PS3, gasket molded into plug (IP 65)
Type PCN No of leads Diameter Temperature Range Cable length
of leads °C mtr.
PS3-N15 804 580 1.5
PS3-N30 804 581 3 0.75 mm2 -25/+80 3.0
PS3-N60 804 582 6.0
PS3-L15 804 583 1.5
PS3-L30 804 584 3 0.75 mm2 -50/+80 3.0
PS3-L60 804 585 6.0
PS3-215 804 587 2 0.75 mm2 -25/+80 1.5
PS3-415 804 588 1.5
+ +
P P
- -
4 4
PS3-2xx PS3-2xx
br 1 br 1
2 bl 2 bl
+ +
P P
- -
4 bl 4 bl
PS3-4xx PS3-4xx
br 1 br 1
2 2
+ +
P P
- -
PS3 – Pins
1
4
2
PS3__35003_EN_R08.doc 8 / 10 09.08.2011
PS3
Alco Controls
Pressure Switch
D A T A S H E E T
Other Accessories
7/16”-20UNF 7/16”-20UNF
85
12 17.5 17.5 12 Ø4.2 13 13
5
23.5 33 SW 14 30 SW 14
10
10 23.5 13
Ø4.8 1/4”NPT 1/8”NPT
63.5
Angle bracket (H140-046.001) Adapter ¼”NPT-male -7/16”-20UNF- Adapter 1/8”NPT-male-7/16”-20UNF-
for two PS3 male (for compressor direct mounting) male (for compressor direct mounting)
PCN: 803 772 PCN: 800 315 PCN: 800 316
Dimensions
Dimensions Range 1…5, A…E, J…N, S…W (in mm)
22
PS3-Nxx PS3-Nxx
Reset
43
43
35
35
15
4.5 17.6
20
39
37
48 3
35
49
1000
80 80
Ø 6,0 Ø 1/4"
Ø 1/4"
A (Range 1-5) U X L
7/16”-20 UNFmale 80 mm solder connection Ø 6 mm 80 mm solder connection Ø ¼” 1 m cap tube Ø ¼” solder
conn.
PS3__35003_EN_R08.doc 9 / 10 09.08.2011
PS3
Alco Controls
Pressure Switch
D A T A S H E E T
Dimensions Range 6, F, O, X (in mm)
41 28 28 28
PS3-Nxx 22
43
35 43
80 80
20
Ø6 Ø ¼”
48 39
EMERSON is not to be held responsible for erroneous literature use by persons having the appropriate technical knowledge and skills,
regarding capacities, dimensions, applications, etc. stated herein. at their own discretion and risk. Our products are designed and adapted
Products, specifications and data in this literature are subject to change for fixed locations For mobile applications failures may occur. The
without notice. The information given herein is based on technical data suitability for this has to be assured from the plant manufacturer which
and tests which EMERSON believes to be reliable and which are in may include making appropriate tests.
compliance with technical knowledge of today. It is intended only for This document replaces all earlier versions.
Phone: Fax:
Emerson Electric GmbH & Co OHG Benelux +31 (0)77 324 0 234 +31 (0)77 324 0 235
ALCO CONTROLS Germany, Austria & Switzerland +49 (0)6109 6059 -0 +49 (0)6109 6059 40
France, Greece, Maghreb +33 (0)4 78 66 85 70 +33 (0)4 78 66 85 71
Postfach 1251
Italia +39 02 961 781 +39 02 961 788 888
Heerstraße 111
Spain & Portugal +34 93 41 23 752 +34 93 41 24 2
D-71332 Waiblingen UK & Ireland +44 (0) 1635 876 161 +44 (0) 1635 877 111
Germany Sweden, Denmark, Norway & Finland +49 (0)2408 929 0 +49 (0)2408 929 528
Phone ...49-7151-509-0 Eastern Europe & Turkey +49 (0)2408 929 0 +49 (0)2408 929 525
Fax ...49-7151-509-200 Poland +48 (0)22 458 9205 +48 (0)22 458 9255
Russia & Cis +7 495 981 9811 +7 495 981 9816
Balkan +385 (0) 1560 38 75 +385 (0) 1 560 3879
www.emersonclimate.eu
Romania +40 364 73 11 72 +40 364 73 12 98
Ukraine +38 44 4 92 99 24 +38 44 4 92 99 28
PS3__35003_EN_R08.doc 10 / 10 09.08.2011