136 GMV-PD
136 GMV-PD
136 GMV-PD
Service Manual
(T1/R410A/50Hz)
3
GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF
PRODUCT
1
DC INVERTER MULTI VRF PRODUCT
PRODUCT
1 MODELS LIST
1.1 Outdoor Unit
Capacity
Units Power
Model Ref. Appearance
Series Cooling Heating Supply
(Btu/h) (Btu/h)
R410A 220-240V
GMV(L)-Pd100W/NaB-K 34120 37532
~50Hz
R410A 220-240V
GMV(L)-Pd120W/NaB-K 40944 47768
DC ~50Hz
Inverter
Multi VRF 220-240V
GMV(L)-Pd140W/NaB-K 47768 52545 R410A
~50Hz
R410A 220-240V
GMV(L)-Pd160W/NaB-K 54592 60051
~50Hz
Cooling Heating
Indoor :27℃(80.6℉)/19℃(66.2℉) Indoor: 20℃(68℉)/-
Outdoor: 35℃(95℉)/- Outdoor : 7℃(44.6℉)/6℃(42.8℉);
2
DC INVERTER MULTI VRF PRODUCT
GMV-R63P/Na-K 23884
21496
GMVL-R63P/Na-K /
GMV-R71P/Na-K 27296
24226
GMVL-R71P/Na-K /
GMV-R80P/Na-K 30026
27297
GMVL-R80P/Na-K /
GMV-R90P/Na-K 34120
30709
GMVL-R90P/Na-K /
GMV-R100P/Na-K 37532
34121
GMVL-R100P/Na-K /
GMV-R112P/Na-K 42650
38216
GMVL-R112P/Na-K /
GMV-R125P/Na-K 46060
42652
GMVL-R125P/Na-K /
GMV-R140P/Na-K 51180
47770
GMVL-R140P/Na-K /
Conversion Formula: Btu/h=kW×3412
3
DC INVERTER MULTI VRF PRODUCT
Capacity
Power
Model Cooling Heating Ref Appearance
Supply
(Btu/h) (Btu/h)
GMV-R22P/NaB-K 8530
7507
GMVL-R22P/NaB-K /
GMV-R28P/NaB-K 10918
9554
GMVL-R28P/NaB-K /
GMV-R36P/NaB-K 13648
12284
GMVL-R36P/NaB-K /
GMV-R45P/NaB-K 17060
15355
GMVL-R45P/NaB-K /
GMV-R56P/NaB-K 21496 220-240V
19108 R410A
GMVL-R56P/NaB-K / ~50Hz
GMV-R71P/NaB-K 27296
24226
GMVL-R71P/NaB-K /
GMV-R90P/NaB-K 34120
30709
GMVL-R90P/NaB-K /
GMV-R112P/NaB-K 42650
38216
GMVL-R112P/NaB-K /
GMV-R140P/NaB-K 51180
47770
GMVL-R140P/NaB-K /
GMV-R22PS/NaB-K 8530
7507
GMVL-R22PS/NaB-K /
GMV-R28PS/NaB-K 10918
9554
GMVL-R28PS/NaB-K /
GMV-R36PS/NaB-K 13648
12284
GMVL-R36PS/NaB-K /
GMV-R45PS/NaB-K 17060
15355
GMVL-R45PS/NaB-K /
GMV-R56PS/NaB-K 21496 220-240V
19108 R410A
GMVL-R56PS/NaB-K / ~50Hz
GMV-R71PS/NaB-K 27296
24226
GMVL-R71PS/NaB-K /
GMV-R90PS/NaB-K 34120
30709
GMVL-R90PS/NaB-K /
GMV-R112PS/NaB-K 42650
38216
GMVL-R112PS/NaB-K /
GMV-R140PS/NaB-K 51180
47770
GMVL-R140PS/NaB-K /
4
DC INVERTER MULTI VRF PRODUCT
GMV-R28T/NaA-K 10900
9550
GMVL-R28T/NaA-K /
GMV-R36T/NaA-K 13650
12280
GMVL-R36T/NaA-K /
GMV-R45T/NaA-K 17060
15360
GMVL-R45T/NaA-K /
GMV-R28T/Na-K 10900
9550
GMVL-R28T/Na-K /
GMV-R36T/Na-K 13650
12280
GMVL-R36T/Na-K /
GMV-R45T/Na-K 17060
15360
GMVL-R45T/Na-K /
GMV-R50T/Na-K 19790
17060
GMVL-R50T/Na-K /
GMV-R56T/Na-K 21500
19100
GMVL-R56T/Na-K /
GMV-R63T/Na-K 23880
21500
GMVL-R63T/Na-K /
GMV-R71T/Na-K 27300
24230
GMVL-R71T/Na-K /
GMV-R80T/Na-K 30030
27300
GMVL-R80T/Na-K /
GMV-R90T/Na-K 34120
30700
GMVL-R90T/Na-K /
GMV-R100T/Na-K 37532
34121
GMVL-R100T/Na-K /
GMV-R112T/Na-K 42650
38210
GMVL-R112T/Na-K /
5
DC INVERTER MULTI VRF PRODUCT
GMVL-R125T/Na-K /
GMV-R140T/Na-K 49470
47770
GMVL-R140T/Na-K /
GMV-R22Td/Na-K 8530
7506
GMVL-R22Td/Na-K /
GMV-R28Td/Na-K 10900
220-240V
9550 R410A ~50Hz
GMVL-R28Td/Na-K /
GMV-R36Td/Na-K 13650
12280
GMVL-R36Td/Na-K /
Capacity
Power
Model Cooling Heating Ref Appearance
Supply
(Btu/h) (Btu/h)
GMV-R22G/NaB-K 8530
7507
GMVL-R22G/NaB-K /
GMV-R28G/NaB-K 10919
9554
GMVL-R28G/NaB-K /
GMV-R36G/NaB-K 13649
12284
GMVL-R36G/NaB-K /
GMV-R45G/NaB-K 17061
15355
GMVL-R45G/NaB-K /
GMV-R50G/NaB-K 19790
17061
GMVL-R50G/NaB-K /
GMV-R56G/NaB-K 21496
19108
GMVL-R56G/NaB-K / 220-240V
R410A
GMV-R22G/NaC-K 8530 ~50Hz
7507
GMVL-R22G/NaC-K /
GMV-R28G/NaC-K 10919
9554
GMVL-R28G/NaC-K /
GMV-R36G/NaC-K 13649
12284
GMVL-R36G/NaC-K /
GMV-R45G/NaC-K 17061
15355
GMVL-R45G/NaC-K /
GMV-R71G/Na-K 27297
24226
GMVL-R71G/Na-K /
GMV-R80G/Na-K 30709
27297
GMVL-R80G/Na-K /
6
DC INVERTER MULTI VRF PRODUCT
GMV-R90Zd/Na-K 34121
30709
GMVL-R90Zd/Na-K /
GMV-R112Zd/Na-K 42652
38216
GMVL-R112Zd/Na-K /
GMV-R125Zd/Na-K 46064
42652
GMVL-R125Zd/Na-K /
Conversion Formula: Btu/h=kW×3412
Cooling Heating
7
DC INVERTER MULTI VRF PRODUCT
2 NOMENCLATURE
2.1 Nomenclature of outdoor unit
GMV □ L - Pd 120 W / Na B - K
1 2 3 4 5 6 7 8 9
Example: GMV-R22G/NaB-K. A wall mounted indoor unit of GREE, and the nominal cooling capacity is 2.2kw. It's the
second generation product, and it could connect the outdoor unit with digital scroll, the power supply is 220V-240V, 50Hz.
8
DC INVERTER MULTI VRF PRODUCT
3 FUNCTION
Auto Restart
Fan Operation Mode
LCD Remote Controller (Option)
Auto Swing Function
Ceiling Soiling Prevention
For
Comfortable Program Dry
Air Conditioning
High Fan Speed Mode
High Ceiling Application
Two Select Thermo Sensor
Hot Start
Timer Selector
Fresh Return air inlet Directly from The Unit
Drain Pump
Long Life Filter
Ultra-Long life Filter (Option)
For Easy
Construction and Mold Resistant Treatment for Filter
Maintenance
Filter Sign
Mold Resistant Drain Pan
Emergency Operation
Self Diagnoses Function
Set Back Time Clock
Double Remote Control
For Flexible
Group Control By 1 Remote Controller
Control
Control By External Command
Remote/Centralized Control
9
DC INVERTER MULTI VRF PRODUCT
4 PRODUCT DATA
4.1 Product data of outdoor
Model GMV(L)-Pd100W/NaB-K GMV(L)-Pd120W/NaB-K
kW 10.0 12.0
Cooling①
Btu/h 34120 40944
Capacity
kW 11.0 14.0
Heating②
Btu/h 37532 47768
Sound Pressure Level dB(A) 58 58
R410A Filling Amount kg 7.5 7.5
Power Supply V,Ph,Hz 220V-240V~,1Ph,50Hz 220V-240V~,1Ph,50Hz
Cooling kW 2.86 3.5
Power input
Heating kW 2.6 3.4
Cooling A 14.2 17.3
Rated current
Heating A 13.2 16.4
Compressor DC inverter dual-rotor type compressor×1
Moisture protection IP×4 IP×4
Climate Type T1 T1
mm φ15.9 φ15.9
Gas Pipe
Inch 5/8" 5/8"
mm φ9.52 φ9.52
Connection Pipes Liquid Pipe
Inch 3/8" 3/8"
Connection Method Flare Connection Flare Connection
Max. NO. of Indoor Unit 5 6
Power input kW 0.136 0.136
3
m /h 6000 6000
Fan Air Flow Rate
CFM 3538 3538
Step 3 3
Recommended
mm2×Number 6.0×3 6.0×3
Power Lines
Circuit breaker A 32 32
Dimensions of Installation mm 1650×590×1700 1650×590×1700
Width mm 950 950
Unit Dimensions Depth mm 340 340
Height mm 1250 1250
Width mm 1110 1110
Dimensions of
Depth mm 450 450
Package
Height mm 1280 1280
Weight(Net/Gross) kg 135/140 135/140
10
DC INVERTER MULTI VRF PRODUCT
kW 14.0 16.0
Cooling①
Btu/h 47768 54592
Capacity
kW 15.4 17.6
Heating②
Btu/h 52545 60051
Sound Pressure Level dB(A) 58 60
R410A Filling Amount kg 7.5 7.5
Power Supply V,Ph,Hz 220V-240V~,1Ph,50Hz 220V-240V~,1Ph,50Hz
Cooling kW 4.36 4.98
Power input
Heating kW 4.05 4.85
Cooling A 20.5 23.2
Rated current
Heating A 19.6 21.9
Compressor DC inverter dual-rotor type compressor×1
Moisture protection IP×4 IP×4
Climate Type T1 T1
mm φ15.9 φ19.05
Gas Pipe
Inch 5/8" 3/4"
mm φ9.52 φ9.52
Connection Pipes Liquid Pipe
Inch 3/8" 3/8"
Connection Method Flare Connection Flare Connection
Max. NO. of Indoor Unit 7 8
Power input kW 0.136 0.184
3
m /h 6000 6800
Fan Air Flow Rate
CFM 3538 4010
Step 3 3
2
Recommended Power Lines mm ×Number 10.0×3 10.0×3
Circuit breaker A 40 40
Dimensions of Installation mm 1650×590×1700 1650×590×1700
Width mm 950 950
Unit Dimensions Depth mm 340 340
Height mm 1250 1250
Width mm 1110 1110
Dimensions of
Depth mm 450 450
Package
Height mm 1280 1280
Weight(Net/Gross) kg 135/140 135/140
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling
only units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little
higher in actual operation.
11
DC INVERTER MULTI VRF PRODUCT
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling
only units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little
higher in actual operation.
12
DC INVERTER MULTI VRF PRODUCT
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling
only units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little
higher in actual operation.
13
DC INVERTER MULTI VRF PRODUCT
Drain Pipes
mm φ30×1.5 φ30×1.5 φ30×1.5
(External Dia. × Thickness)
Unit Dimensions
mm 980×736×266 980×736×266 1112×756×300
(W×D×H)
Package Dimensions
mm 1068×766×320 1068×766×320 1245×785×360
(W×D×H)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling
only units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little
higher in actual operation.
14
DC INVERTER MULTI VRF PRODUCT
Unit Dimensions
mm 1112×756×300 1112×756×300 1112×756×300
(W×D×H)
Package Dimensions
mm 1245×785×360 1245×785×360 1245×785×360
(W×D×H)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling
only units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little
higher in actual operation.
15
DC INVERTER MULTI VRF PRODUCT
Unit Dimensions
mm 1385×736×300 1385×736×300 1385×736×300
(W×D×H)
Package Dimensions
mm 1514×795×360 1514×795×360 1514×795×360
(W×D×H)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling
only units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little
higher in actual operation.
16
DC INVERTER MULTI VRF PRODUCT
Drain Pipes
mm φ30×1.5 φ30×1.5
(External Dia. × Thickness)
Unit Dimensions
mm 1385×736×300 1385×736×300
(W×D×H)
Package Dimensions
mm 1514×795×360 1514×795×360
(W×D×H)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling
only units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little
higher in actual operation
17
DC INVERTER MULTI VRF PRODUCT
Drain Pipes
(External Dia. × Thickness)
mm φ20×1.5 φ20×1.5 φ20×1.5
Unit Dimensions
mm 880×655×250 880×655×250 880×655×250
(W×D×H)
Package Dimensions
mm 1020×745×305 1020×745×305 1020×745×305
(W×D×H)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level is tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
18
DC INVERTER MULTI VRF PRODUCT
Drain Pipes
mm Φ30×1.5 Φ30×1.5 Φ30×1.5
(External Dia. × Thickness)
Unit Dimensions
mm 980×721×266 1155×756×300 1155×756×300
(W×D×H)
Package Dimensions
mm 1068×766×320 1245×785×360 1245×785×360
(W×D×H)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level is tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
19
DC INVERTER MULTI VRF PRODUCT
Drain Pipes
mm Φ30×1.5 Φ30×1.5 Φ30×1.5
(External Dia. × Thickness)
Unit Dimensions
mm 1425×736×300 1425×736×300 1425×736×300
(W×D×H)
Package Dimensions
mm 1514×785×360 1514×785×360 1514×785×360
(W×D×H)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level is tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher
in actual operation.
20
DC INVERTER MULTI VRF PRODUCT
Drain Pipes
(External Dia. × Thickness)
mm φ20×1.5 φ20×1.5 φ20×1.5
Unit Dimensions
mm 880×655×250 880×655×250 880×655×250
(W×D×H)
Package Dimensions
mm 1020×745×305 1020×745×305 1020×745×305
(W×D×H)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level is tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
21
DC INVERTER MULTI VRF PRODUCT
Drain Pipes
mm Φ30×1.5 Φ30×1.5 Φ30×1.5
(External Dia. × Thickness)
Unit Dimensions
mm 980×721×266 1155×756×300 1155×756×300
(W×D×H)
Package Dimensions
mm 1068×766×320 1245×785×360 1245×785×360
(W×D×H)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level is tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
22
DC INVERTER MULTI VRF PRODUCT
Drain Pipes
mm Φ30×1.5 Φ30×1.5 Φ30×1.5
(External Dia. × Thickness)
Unit Dimensions
mm 1425×736×300 1425×736×300 1425×736×300
(W×D×H)
Package Dimensions
mm 1514×785×360 1514×785×360 1514×785×360
(W×D×H)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level is tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher
in actual operation.
23
DC INVERTER MULTI VRF PRODUCT
4.2.2Cassete Type
Drain Pipes
mm Φ30×1.5
(External Dia. × Thickness)
Unit Dimensions
mm Main body:570×570×230 Panel:650×650×50
(W×D×H)
Package Dimensions
(W×D×H) mm Main body:848×728×310 Panel:730×670×102
Net Weight
kg 20/5
(Main body/Panel)
Gross Weight
kg 27/10
(Main body/Panel)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
24
DC INVERTER MULTI VRF PRODUCT
Drain Pipes
mm Φ30×1.5 Φ30×1.5 Φ30×1.5
(External Dia. × Thickness)
Unit Dimensions
mm Main body:840×840×190 Panel:950×950×60
(W×D×H)
Package Dimensions
mm Main body:960×960×257 Panel:1040×1025×115
(W×D×H)
Net Weight
kg 25/6.5
(Main body/Panel)
Gross Weight
kg 33/10
(Main body/Panel)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
25
DC INVERTER MULTI VRF PRODUCT
Drain Pipes
mm Φ30×1.5 Φ30×1.5 Φ30×1.5
(External Dia. × Thickness)
Main body:840×840
Unit Dimensions Main body:840×840×240
mm ×190
(W×D×H) Panel:950×950×60
Panel:950×950×60
Main body:960×960
Package Dimensions ×257 Main body:960×960×310
mm
(W×D×H) Panel:1040×1025× Panel:1040×1025×115
115
Net Weight
kg 25/6.5 30/6.5
(Main body/Panel)
Gross Weight
kg 33/10 38/10
(Main body/Panel)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
26
DC INVERTER MULTI VRF PRODUCT
Drain Pipes
mm Φ30×1.5 Φ30×1.5 Φ30×1.5
(External Dia. × Thickness)
Main body:840×
Unit Dimensions Main body:840×840×240
mm 840×320
(W×D×H) Panel:950×950×60
Panel:950×950×60
Main body:960×
Package Dimensions Main body:960×960×310 960×394
mm
(W×D×H) Panel:1040×1025×115 Panel:1040×1025
×115
Net Weight
kg 30/6.5 38/6.5
(Main body/Panel)
Gross Weight
kg 38/10 46/10
(Main body/Panel)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
27
DC INVERTER MULTI VRF PRODUCT
Drain Pipes
mm Φ30×1.5 Φ30×1.5
(External Dia. × Thickness)
Gross Weight
kg 46/10
(Main body/Panel)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
28
DC INVERTER MULTI VRF PRODUCT
Drain Pipes
mm Φ30×1.5 Φ30×1.5
(External Dia. × Thickness)
Net Weight
kg 38/6.5
(Main body/Panel)
Gross Weight
kg 46/10
(Main body/Panel)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
29
DC INVERTER MULTI VRF PRODUCT
Drain Pipes
mm Φ30×1.5 Φ30×1.5 Φ30×1.5
(External Dia. × Thickness)
Unit Dimensions
mm Main body:920×360×185 Panel:1180×430×30
(W×D×H)
Package Dimensions
mm Main body:1290×465×270 Panel:1260×505×110
(W×D×H)
Net Weight
kg 16/3
(Main body/Panel)
Gross Weight
kg 25/5
(Main body/Panel)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation
30
DC INVERTER MULTI VRF PRODUCT
Drain Pipes
mm Φ20×1.5 Φ20×1.5 Φ20×1.5
(External Dia. ×Thickness)
Unit Dimensions
mm 830×189×285 830×189×285 830×189×285
(W×D×H)
Package Dimensions
mm 995×394×268 995×394×268 995×394×268
(W×D×H)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
31
DC INVERTER MULTI VRF PRODUCT
Unit Dimensions
mm 830×189×285 1020×228×310 1020×228×310
(W×D×H)
Package Dimensions
mm 1006×385×265 1178×325×390 1178×325×390
(W×D×H)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
32
DC INVERTER MULTI VRF PRODUCT
Unit Dimensions
mm 770×190×250 770×190×250 830×189×285
(W×D×H)
Package Dimensions
mm 955×330×272 955×272×330 1006×395×295
(W×D×H)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
33
DC INVERTER MULTI VRF PRODUCT
Package Dimensions
mm 1006×395×295 1365×417×333 1365×417×333
(W×D×H)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
34
DC INVERTER MULTI VRF PRODUCT
Drain Pipes
(External Dia. × mm Φ17×1.75 Φ17×1.75 Φ17×1.75
Thickness)
Unit Dimensions
mm 840×238×695 840×238×695 840×238×695
(W×D×H)
Package Dimensions
mm 1035×295×805 1035×295×805 1035×295×805
(W×D×H)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
35
DC INVERTER MULTI VRF PRODUCT
Drain Pipes
mm Φ17×1.75 Φ17×1.75
(External Dia. × Thickness)
Unit Dimensions
mm 1300×188×600 1590×238×695
(W×D×H)
Package Dimensions
mm 1514×248×724 1714×330×830
(W×D×H)
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
36
DC INVERTER MULTI VRF PRODUCT
Unit Dimensions
mm 1590×238×695 1590×238×695
(W×D×H)
Package Dimensions
mm 1714×330×830 1714×330×830
(W×D×H)
Weight(Net/Gross) kg 44/53 44/53
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
Cooling 10℃(50℉)~48℃(118.4℉)
Heating -20℃(-4℉)~27℃(8℉)
37
DC INVERTER MULTI VRF PRODUCT
5 PIPING DIAGRAM
5.1 Cooling Only
Heat
Exchanger
with Axial
Receiver Flow Fan
extra condenser
High pressure
switch
Compressor
Accumulator
Stop valve
Electronic
Heat Exchanger with Centrifugal Fan Expansion
Valve
38
DC INVERTER MULTI VRF PRODUCT
Filter Filter
Heat exchanger
with axial flow fan
1-way valve
Receiver
Extra condenser
4-way valve
Compressor
Accumulator
Stop valve
39
GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF
CONTROL
40
DC INVERTER MULTI VRF CONTROL
CONTROL
1 OPERATION FLOWCHART
41
DC INVERTER MULTI VRF CONTROL
Cooling Operation
There Is Not
Guide Louver
There Is
In The Process Of
Yes
Preventing Restart Operation?
(3 Minutes)
No
Temperature No
Adjustment?
Fan Motor:Stop
Yes
Electronic Expansion Valve: Close
Electronic Expansion
Valve: Capacity Control
42
DC INVERTER MULTI VRF CONTROL
43
DC INVERTER MULTI VRF CONTROL
2 MAIN LOGIC
2.1 Control Function of Outdoor Unit
1) Compressor Capacity Output
It is defined that the full load capacity output of the compressor is 100%.
The compressor capacity output is calculated according to the required indoor load, which is
related to the following factors: whether the indoor unit is started, the set temperature, the indoor
ambient temperature, the outdoor ambient temperature, etc.
Calculation of capacity output of cooling compressor
j
∑ (q iON Ai )
Q= i =1
j
× 100%
∑q
i =1
i
∑ (q iON Ai + qiOFF × Bi )
Q= i =1
j
× 100%
∑q
i =1
i
f = Fmax × Q ,and when f is not 0,, the minimum is Fmin ,the maximum is Fmax
Among which:
Q is the calculated compressor capacity output;
f Actual run frequency of inverter compressor;
Fmax Maximum allowable run frequency of inverter compressor;
Fmin Minimum allowable run frequency of inverter compressor
qi Rated capacity of indoor unit
qiON Rated capacity of indoor unit in ON state
qiOFF Rated capacity of indoor unit in OFF state
Ai Setting temperature, correction of indoor and outdoor ambient temperature, %
Bi Capacity compensation under heating when indoor unit in OFF state, %;
44
DC INVERTER MULTI VRF CONTROL
frequency-reducing.
Before the first starting of compressor, you should keep it running for 3min at 60Hz, and then
switch to the target frequency. The dwell time is separately 5min and 5 min when the frequency
passes 75 Hz and 90 Hz. If high-pressure frequency-reducing and exhausting frequency-reducing
happens during the process, you should quit the initial action, and deal with according to their
separate frequency-reducing.
45
DC INVERTER MULTI VRF CONTROL
Inverter controller
4-way Valve Power the four-way valve if the high and low voltage
deviation is no less than 3kg/cm2G
Fan
Initialization
Outdoor unit EXV 350-step
Regulate according to
normal logic
4) Defrosting Function
◆ Defrosting Start Conditions
Keep heating (the four-way valve is under the heating position) for 50 minutes; when the intermediate sensor
temperature and outdoor ambient temperature retain the following curve figure for 120s,
46
DC INVERTER MULTI VRF CONTROL
Or the outdoor ambient temperature is below -6 ℃; and keeps heating (the four-way valve is under the heating
position) for 2 hours;
The action time for unit defrosting operation is shown as the following figure.
47
DC INVERTER MULTI VRF CONTROL
Heating timer
Defrosting mark
Defrosting timer
Compressor frequency
4-way Valve
High fan
Outdoor fan
Outdoor electronic
expansion valve
Indoor electronic
expansion valve T = <10 Minutes 30s
2 minute
30s
1 minute 1 minute 2 minute
4 minute
Defrosting preparation Defrosting process End of defrosting
If all the indoor units’ temperatures of a unit are up to temperature spot, then the capacity needs is o. the outdoor
unit will stop the compressor, and all the indoor electromagnetic expansion valve will be closed.
◆Indoor Fan Action
When the indoor unit is opened and the fan is not set at automatic fan speed, the indoor fan will unceasingly
48
DC INVERTER MULTI VRF CONTROL
Medium
中风档
Low
低风档
低风档
Low
室内环境温度
Indoor Ambient Temperature +1 +2 +3 +4
Indoor setting temperature
室内设定温度
Automatic
制冷自动风速 cooling fan speed
(菱格风) (Trendy)
Automatic fan speed switching will be detected every 30 seconds.
If the indoor fan is closed at first, the fan will be forced to run at high speed for 8s after start-up, then changed to
setting speed.
◆ Blowing Residual Cold Air Control
When the indoor unit is turned off, the fan will run for 0-60 seconds at the setting speed or automatic speed
When the capacity requirement of indoor unit is 0, the electronic expansion valve of indoor unit will be closed, and
then the fan will unceasingly run at the setting speed or automatic speed.
2) Dry Operation
When the units work under dry mode, the indoor fan could only work at low speed (no matter what speed is set). All
other actions are the same with cooling operation. Please refer to cooling operation.
Low
低风档
Indoor ambient
室内环境温度temperature -1 +1
Indoor setting temperature
室内设定温度
If the indoor fan is closed at first, the fan will be forced to run at high fan for 8s after start-up, then changed to
setting speed.
2) Heating Operation
◆ Heating Capacity
Outdoor unit will determine the compressor capacity output according to the capacity requirements of indoor unit.
Indoor unit will determine the opening of indoor electronic expansion valve by the control of outdoor unit, and the
electronic expansion valve should be set once for every 40 seconds.
◆ Temperature Control
Indoor unit will control the temperature by opening and closing of indoor electronic expansion valve (Shown as
the following figure):
When the indoor unit capacity requirement is 0, the electronic expansion valve should be closed;
When the indoor unit of capacity requirement is not 0, the electronic expansion valve should be open.
Expansion
膨胀阀ON valve ON
Expansion
膨胀阀OFF Valve OFF
◆ Fan Control
49
DC INVERTER MULTI VRF CONTROL
High
高风档
中风档
Medium
Low
低风档
高风档
High fan
中风档 fan
Medium
Low
低风档fan
室内环境温度 -3
Indoor ambient temperature -2 -1 +1 +2
Indoor
室内设定温度setting temperature
Automatic
制热自动风速 heating fan speed
(菱格风) (Trendy)
t / 。C
Tv-evaporatorTv蒸
High t evaporator
t蒸发器
高风档
Setting
设定风速 speed
Fan
风机关 OFF
8s
t/s
0 60s
t evaporator tReaching the valve value within one minute
蒸发器 一分钟内达到阀值
50
DC INVERTER MULTI VRF CONTROL
t
t / 。C t 蒸发器
evaporator
Tv-evaporatorTv蒸
高风档
High
Setting
设定风速 speed
风机关
Fan OFF
8s
t/s
0 60s
t evaporator Failing to reach the valve value within one minute
t蒸发器 一分钟内未达到阀值
Once the indoor unit started under heating operation, if the fan stops in any case (including starting up,
defrosting, fault, no capability needs), the anti cold air operation will keep before starting the fan for the next time.
Once the indoor fan is started, unless the fan stops, the anti cold air operation will not take effect even t evaporator
< T v-evaporator again.
Setting wind
设定风速speed
Low speed
低风档
Fan OFF
风机关
Tresidual heat
T余热
t/s
0
The corresponding residual heat removal period for different models in different situations is listed in the
following table.
The blowing period for residual heat in different situations T residual heat
(s)
Reaching the
Entering into Malfunction
Model Stop temperature
the defrosting stop
point
Duct Type Series 100 60-100 60 60
Wall Mounting
50 10-50 10 10
Type Series
Cassette Type Low wind,
60 20 20
Series non-stop
Special case: For the indoor units of cassette series, it will run at low fan speed when it reaches the temperature
point, and do not need to stop the fan.
Therefore, you should use the temperature compensation function under heating mode: to reflect the real
temperature of living space by reducing 2 degrees of the air inlet temperature. You may keep comfortable
temperature in the living space. Shown as the following figure:
51
DC INVERTER MULTI VRF CONTROL
Expansion valve ON
膨胀阀ON
Expansion
膨胀阀OFFValve OFF
Indoor ambient室内环境温度
temperature (air -1 +1
inlet temperature)
(回风口温度) Indoor Setting Temperature
室内设定温度
Temperature标准情况下的温度调节
regulation under standard conditions
膨胀阀ON
Expansion valve ON
Expansion
膨胀阀OFFValve OFF
Temperature具有温度补偿的温度调节
regulation with temperature compensation
4) Auto swing control
The indoor units of Wall mounting and cassette series have the swing function. By this function, you can increase
the indoor air convection and the uniformity of indoor temperature regulation.
◆Reset
The swing louver will sway once automatically when electrifying for the first time. It can make the swing louver
return to the initial positions, and ensure the accuracy of swing louver action.
◆Using Indoor Units’ Own Buttons for Start
When you use the indoor units’ own buttons for start, the automatic swing will work automatically. The swing louver
will swing back and forth between the max and min positions (there are different max and min positions according
to different modes)
◆ Use the Wired Controller or Remote Controller for controlling
When using the wired controller or remote controller for start, if you don’t set the automatic swing signal when
starting, the swing louver will stop at default location (The default locations are different according to different
modes). If the automatic swing signal has been set well when starting, the automatic swing will automatically work.
The swing louver will swing back and forth between the max and min positions (there are different max and min
positions according to different modes).
When the wired controller or remote controller sends an automatic swing signal, the automatic swing function
will be started, and the swing louver begins to swing from current position.
When the wired controller or remote controller sends a stopping swing signal, the automatic swing function will
be stopped, and the swing louver stops at current position.
◆ Others
When the indoor unit receives the shutdown signal, detecting the fault signal and defrosting signal unless the
auxiliary electric heating protection, no matter the swing louver are under any state, they will all stop at initial
position after the cessation of indoor fans.
When the indoor units detected the auxiliary electric heating protection, no matter the indoor units are under
any state, the automatic swing will work, and the indoor fans will run at high speed at the same time.
5) Controlling of drainage pump motor
Cassette indoor units have drainage pump device to discharge the condensation water which is produced during
cooling or drying.
◆ When the indoor unit is operating under cooling or dry mode, the water pump and compressor will start at the
same time.
◆ When powering off or cooling stop, drying stop or transfering to other modes, the water pump will be powered
off after five miuntes.
◆When water level is flooded for 8 second at any mode (include power-off), the water pump must be started at
once. The pump will not stop running untill the flooding signal disappears and it will stop running ten minutes after
52
DC INVERTER MULTI VRF CONTROL
Compressor
压缩机开 start
Compressor
压缩机关 stop Compressor
压缩机关 stop
Pump
水泵开 start Pump
水泵开start
Pump
Pump
水泵关stop stop
水泵关 Pump
水泵关 stop
5m 5m
t
Water full
Water full 水满信号有效
signal is valid
signal is
水满信号无效
invalid Water full signal is disappears
水满信号消除
Pump
水泵开start
8s
Pump
水泵关stop Pump
水泵关stop
10m
t
The parameter of TCompressor, TDefending frost, TFrosting temperature and TReset temperature will be different according to the model,
as shown:
TDefending frost TFrosting temperature TReset temperature
Model TCompressor (m)
(m) (℃) (℃)
Series of
cassete and 15 10 -4 15
duct type
Series of wall
mounted 6 3 0 10
type
7) Controling of indoor electronic expansion valve
◆ Reset control of indoor electronic expansion valve
When the indoor unit is energized, it will automatically carry out the electronic expansion valve reposition action,
to make the electronic expansion valve return the initial position, and ensure the accuracy of expansion valve’s
action.
◆ Controling of superheating degree in cooling mode
In the operation process of cooling and drying , to keep suitable superheating degree, the unit will control the jaw
opening of indoor electronic expansion valve according to the difference between entry temperature and setting
superheating value of indoor unit evaporator.It will be detected every 40 seconds. This process will stop when
powering off, stop after reaching temperature point and malfunction.
◆ Controlling of supercooling degree in heating mode
In the operation process of heating, to keep suitable supercooling degree, the unit will control the jaw opening of
indoor electronic expansion valve according to the difference between entry temperature and setting supercooling
value of indoor unit evaporator. It will be detected every 40 seconds. This process will stop when powering off, stop
after reaching temperature point and malfunction.
8) Controling of sensor test
◆ Ambient temp. sensor
When the ambient temperature is measured lower than -20℃ or higer than 100℃ for one minute continuously,
the ambient sensor error signal will be sent(error code: F0), and then indoor unit will stop for abnormity.
When the environment sensor is in trouble, the environment temperature is tested lower than -20℃ or higer
than 100℃ for one minute continuously, the ambient sensor error signal will disappear, and indoor unit will operate
as the former state.
◆ Evaporator temp sensor
When the evaporator temperature is measured lower than -30℃ or higer than 100℃ for one minute
continuously,the evaporator temp sensor error signal will be sent (error code: F0), and then indoor unit will stop for
abnormity.
53
DC INVERTER MULTI VRF CONTROL
When the evaporator temperature sensor is in trouble, the evaporator temperature is measured lower than -30℃
or higer than 100℃ for one minute continuously,, the evaporator temperature sensor error signal will disappear,
and the indoor unit will operate as the former state.
◆The measure times should not be accumulatived
感温包
Temperature
of sensor
温度
下限值
Lower limit value
故障产生
Error 故障产生
Error
producing producing
Error故障恢复
resume Error故障恢复
resume
感温包故
Sensor fault state
障状态
1m 1m 1m 1m <1m t
55
DC INVERTER MULTI VRF CONTROL
DIP switch 2(L/I)——Control mode; it includes wired control mode and remote control mode. Wired
control mode is that: control the running of indoor unit by wired controller, which is factory setting (dialing
the DIP switch to “ON” position); When the setting is wired control mode, “Memory mode setting” and
“Master/slave indoor unit setting” of S7 are invalid which can be directly set on the wired controller.
Remote control mode is that: control the running of indoor unit by remote controller; when the setting is
remote control mode, its functional code must be set in S7.
DIP switch 3(M/S)——Master/slave indoor unit setting; it is master/slave setting of indoor unit running
mode, which is mainly used for people’ priority requirements (such as leaders, patients, etc.). The factory
setting is master indoor unit( dialing the DIP switch to “ON” position). When settings of all indoor units are
slave indoor units, outdoor unit will run in the mode of firstly started slave indoor unit. If the mode of later
started slave indoor unit and mode of firstly started slave indoor unit conflict, the conflict modes error will
be warned by the system and later started indoor unit cannot run. In that case, the running of the unit is
decided by firstly started slave indoor unit.
56
DC INVERTER MULTI VRF CONTROL
When there is only one indoor unit that is set to be master indoor unit, in that case, no matter if the master
indoor unit is firstly started, the conflict mode error will be warned by slave indoor unit once the mode of
slave indoor unit and the mode of master indoor unit conflict (except for turnoff mode of master/slave
indoor unit). And the unit will firstly run at the mode of master indoor unit
When there are multi indoor units that are set to be master indoor units, the unit will run at the mode of
master indoor unit with min. address code. When the indoor unit with min. address code changes to the
running status from turnoff status, modes of other master indoor units or slave indoor unit should be in the
same mode with it, or the conflict mode error will be warned. Therefore, when there are multi master
indoor units, set the address code from high to low according to priority.
DIP switch 4(I/O)——Collection point setting of ambient temp.; the setting is mainly used when there is
high differential between temperatures of air conditioning area and return air of the unit. The setting is
valid only when there is receiver and includes collection points setting of temperatures of return air inlet e
and receiver head. The factory setting is the collection points setting of temperature of return air
inlet( dialing the DIP switch to the “ON” position.
DIP switch 5(L/H)——High-low static pressure setting of fan; it includes high static pressure setting of
fan and low static pressure setting of fan, which should be adjusted according to the project.
Cautions:
1).Code setting must be under off state of power.
2). There is 3-bit, 4-bit or 5-bit DIP switch. 4-bit or 5-bit DIP switch is only applicable to ducted type
unit(including GMV Multi VRF ducted type units and ducted type split)
3).;When the control setting is "L", the Master/slave and memory setting on the main board is invalid.
When the control setting is “I”, the code setting is valid.
4). The dial-up position shall be at ON which means 0 or at opposite position which means 1.
Dial-upswitch at middle position is prohibited.
5). After dialing up, please record address code of the unit (√).
57
DC INVERTER MULTI VRF CONTROL
Address DIP
Functional DIP Switch S1
Switch S7
58
DC INVERTER MULTI VRF CONTROL
AUTOFAN OPER
TEMP. button AUTO
Set temp. increases 1 c AIR
by pressing "+" and
decreases 1 c by pressing
"-" once. COOL
SWING HUMID LIGHT SAVE
DRY
Set temp. : 16 c~30 c TIMER FAN
Set temp. : 16 c~30 c ONOFF HR.
HEAT
Set temp. : 16 c~30 c
Set temp. : 16 c~30 c
ON/OFF button
MODE button Press the button to turn on
Press the button to change the unit. Press the button
the mode according to the once again to turn off the
following order unit and cancal the timer.
MODE ON/0FF
NOTE: The cooling only
units have no mode.
NOTE!
After every indoor unit received the turn off signal, the fan and electric inflate valve will
continue to work for 20-70mins to make use of the rest cool or rest heat, while for preparation for the
nest work. And this is normal phenomenon.
59
DC INVERTER MULTI VRF CONTROL
NOTE!
This type of remote control is a kind of general use remote control that is suitable for several
types (function) of air conditioner units. Please understand that the functions and buttons that are
not suitable for this air conditioner will not be introduced.
Liquid crystal displayer
It shows all set contents.
SWING FAN
SLEEP button
AUTOFAN Press the button to set SLEEP
OPER
mode, and stop when repressed.
AUTO
When the sleep mode is in the
AIR cool and dry mode, the set
temp. will increases 1~2℃
during the set time, then the
SWING HUMID LIGHT SAVE unit will operate according to
the temp.. When sleep mode is
TIMER
ONOFF HR. in the heat mode, the set temp.
decreases 1~2℃ during the set
time, then the unit will operate
according to the set temp..
SLEEP AIR
LIGHT HUMID
MODE ON/0FF
Temp./Timer button
When the unit is operating, increase 1℃
by pressing "+" button once, and
decrease 1℃ by pressing "-" button
once. The indoor temp. can be set in
the range of 16-30℃.
Press the "Timer OFF/TIMER ON"
button at operating/ stopping to set the
off/on time. Press "Timer OFF/TIMER
ON" once to increase 0.5 hour for the
set time. The Max.value of setting time
could be 24 hours,when repressed it
the setting time will be canceled.
Operation procedure
Normal procedure
1. Press ON/OFF button after connected with the power, then the unit is operating.
2. Press MODE button to choose the need operation mode.
3. Press FAN button to set the fan speed.
4. Press +/- button to set the need temp.
Selectable procedure
5. Press SLEEP mode to set the sleep state.
6. Press TIMER OFF button to set the set time.
Note: When the operating mode selected by the indoor unit is clash with the one selected by the
outdoor unit, the remote controller will display the operating clash after 5 seconds and the power
light will flicker, then the indoor unit turns off. At this time, the units will become normal after the
operating mode of the indoor unit is changed to cooperate with the outdoor unit. Cool mode can
cooperate with dry mode, and fan mode can cooperate with any mode.
60
DC INVERTER MULTI VRF CONTROL
61
DC INVERTER MULTI VRF CONTROL
4 WIRED CONTROLLER
4.1 Operation and Display View
Fig.4.1
Various Components of Wired controller
1 Operating mode display (Cool, Dry, Fan, Heat) 9 On/Off button
2 Sleep mode display 10 Timer button
3 Ambient temp.display /Malfunction display 11 Sleep button
4 Fan control display (automatic, high, media, low) 12 Swing display
5 Set Temp. display 13 Fan control button
6 Defrosting display 14 Temp./ Timer decrease button
7 Timer display 15 Temp./ Timer increase button
8 Signal receptor 16 Mode button
4.2 Dimension
21.5
54
42.5
85
60
85
62
DC INVERTER MULTI VRF CONTROL
4.3 Installation
1 2 3 4
Fig.4.3 Installation of wired controller
SN 1 2 3 4
Name Casing base, installed into the wall Controller Soleplate Screw M4X25 Controller Panel
63
DC INVERTER MULTI VRF CONTROL
Fig.1.1
Before using, the controller functions must be selected by the personnel who performance the installation with the
requirements of users. Please refer to Project Debugging Setting section for the details.
Note: If the controller is set to be region wired controller, the wired controller of the selected indoor unit must be
removed.
The region controller can be matched with long-distance monitor. As a region monitoring controller, its control is
subject to that of the long-distance monitor. In the same group, one of the region controllers can be used as region monitoring
controller and matches one or more region wired controller which replace(s) one or more wired controller, in which case, the
region monitoring controller can also monitor or control the region wired controller.
Fig.1.2 Sketch map to the relation among the region controller, region monitoring controller and region wired
controller
64
DC INVERTER MULTI VRF CONTROL
(Fig.5.2)
Instruction to functions of buttons (Table 5.1)
No. Name Function
A. Switch the control mode of inquiry/single/ central control.
FUNC
1 B. In central control status, give the central order by successively pressing FUNC
(FUNCTION)
button.
2 MODE Set cooling/heating/fan/dry mode for indoor unit
3 ▲ A. Inquiry status: cycle, increase or decrease No. of indoor units to easily inquire the
status of each indoor unit.
B. Single/Central control status: set running temp. of indoor unit, maximum is 30℃
4 ▼ and minimum is 16℃.
C. Timer setting status: increase or decrease the timer on/off time, maximum is 24hr
and minimum is 0.
A. Set the indoor fan speed of hi/mid/low/auto.
5 FAN
B. Successively press FAN button to set on/off swing.
A. Under single/central control mode, set on /off timer of selected indoor unit
6 TIMER B. Under inquiry status, inquire the timer setting of the indoor unit with current
address.
7 ON/OFF Set ON/OFF of the indoor unit.
Under single/central control, press MODE and ON/OFF buttons simultaneously to
2MODE and
Lock start/ stop the lock of operation to buttons of wired controller for selected indoor
7 ON/OFF
units.
2MODE and Under single/central control, press MODE and TIMER simultaneously to start/ stop
Shield mode
6 TIMER the shield of operation to MODE button of wired controller for selected indoor unit.
4 ▼and Shielding Under single/central control, press ▼ and TIMER simultaneously to start/ stop the
6 TIMER Temp. shield of operation to Temp button of wired controller for selected indoor unit.
7 ON/OFF and Shielding Under single/central control, press ON/OFF and TIMER simultaneously to start/ stop
6 TIMER ON/OFF the shield of operation to ON/OFF button of wired controller for selected indoor unit.
2 MODE and Memory
Refer to power-off memory function about the details.
3 ▲ mode
4 ▼and Selection A.Check the control mode of region monitoring controller / region wired controller
7 ON/OFF of function B.Set the control mode of region monitoring controller / region wired controller
Note:
1.The characters with gray back ground indicate buttons. Following part is the same to it.
2. The time of single press of the button is more than 3s, which means successively-press.
3. There isn‘t the function that the region wired controller shields other indoor wired controller.
65
DC INVERTER MULTI VRF CONTROL
(Fig.5.3)
5 Fan speed display Hi, mid, low or auto speed of indoor fan is displayed.
6 Swing Swing running of indoor unit is displayed.
7 Timer “TIMER ON/OFF” is displayed when setting timer or inquiring timer state.
Under inquiry state, No. of online indoor units are displayed and No. of selected
indoor unit will blink.
8 No. of indoor unit
Under single control state, only No. of selected indoor unit is displayed.
Under centralized state, No. of all online indoor units are displayed.
9 Room temp. “ROOMTEMP” is displayed for no malfunction, but isn’t for malfunction.
Centralized controller
A. Under inquiry state,” SHIELD” will be displayed when selected indoor unit is
shielded.
10 Shield B. Under control state,” SHIELD” will be displayed during setting or giving the
shield order.
Region wired controller:” SHIELD” will be displayed when selected units are
shielded during long-distance monitoring.
66
DC INVERTER MULTI VRF CONTROL
Note:
1. Contents in the double quotation marks indicate the display in LCD. Following part is the same to it.
2. Online indoor units to Mini Centralized Controller indicate that in a region. Following part is the same to it.
3. No signal control function for region wired controller, and “SINGLE” won’t be displayed either.
Before installation and connection, make sure the power supply is off. After installation and
connection, check the connection result again to prevent loose or short.
There are 4 connection lines (included in the 4-core twisted pair line) to the controller, from CN1 or the
upper and right CN2 to the upper they respectively are: Ground line (GND), communication line A (A),
communication line B(B) and power cord (+12 v).
Note:
During following connection of wirings, pay special attention to them to avoid malfunction to units for
67
DC INVERTER MULTI VRF CONTROL
electromagnetic interference.
1. Keep the signal lines or wirings (communication) of region controller or wired controller at least 20
cm from the power cords or connecting lines between indoors and outdoors to prevent abnormal
communication.
2. Shielding twisted pair line must be adopted as signal line or wiring (communication) once the unit
is installed in the place where there is serious electromagnetic interference.
6 CENTRALIZED CONTROLLER
6.1 Function
Main characteristics of Centralized Controller:
◆ A set of Centralized Controller can control 64 communication modules and can connect to as
much as 1024 indoor units. It can conduct individual control with any separated area or unified
control. It can monitor or control On/Off, Mode, Temperature setting and Timer On/Off of indoor
unit etc.
◆ It can realize the central, single or select control to all indoor units.
◆ It can organize several indoor units into groups as you desired and conduct unified
control—Group select control.
◆ Error contents are shown by codes. Corresponding communication module numbers of the indoor
units with error contents would blink for rapid inspection and repair (There is sound warning for a
few errors).
◆ Timer function. Every indoor unit can set Timer On/Off time by central, single or select control.
Both Timer On time and Timer Off time can be set at the same time, and it is available to set the
timer to which day among the 7 days from Sunday to Saturday works.
◆ Clock function displays in year, month, day, hour, minute and week, and the clock can be
manually adjusted.
◆ Indoor and outdoor units online auto detect, display and working state indication.
◆ Self-inspection function is remained.
◆ Centralized Controller and several communication modules formed communication net, the length
of communication wire of the net can be as long as 1km (without using communication repeaters).
3
17
16
15
4
14
13 12 11 10 9 8 7 6 5
(Fig.6.2)
68
DC INVERTER MULTI VRF CONTROL
This central control has Sequence On function, that enable conduction to sequence control
1 ALL ON to communication modular in interval of 2 seconds, communication modular controls
Sequence On of indoor units (to lower impact to power network).
This central control has Sequence Off function, that enable conduction of sequence control
2 ALL OFF to communication modular in interval of 2 seconds, communication module controls
Sequence Off of indoor units (to lower impact to power network).
It works as direction and adjusting under every operation function. Such as: When
LEFT/RIGHT checking, it can move to the required indoor unit or communication modular by using this
8
UP/DOWN button; when adjusting time, press LEFT (/RIGHT) to shift “Y/M/D” etc. and press UP
(/DOWN) to adjust value
Under control mode, press this button after setting state of indoor unit, control to indoor
9 CONTROL
unit would be conducted by corresponding control mode.
Press button under checking state to begin information check and set of grouped indoor
10 GROUP
unit, grouped information is for select control.
Shift display domain and indoor wired air condition control. DOMAIN corresponding to
13 INDOOR/DOMAIN display on line communication modular, INDOOR corresponding to display on line
indoor control.
Press this button during process of setting function to exit the already made function
14 CANCEL setting operation. Such as, if central control mode were selected, press CANCEL at this
time would back to control mode selecting state.
Begin control setting mode, and Central Control, Select Control and Single Control can be
selected.
CONTROL MODE Central Control: Control all indoor units under domain by present set state.
15 Single Control: Control present indoor unit by present set state.
Select Control: Control selected indoor unit by present set state, it also called
grouped control
16 SELECT Select required control or setting object; repress the button to the object is to cancel.
17 CONFIRM Confirm the operated operation is effective
69
DC INVERTER MULTI VRF CONTROL
(Fig.6.3.1)
Sketch for LCD part:
1 2 3 4 5
16 7
8
15 14 13 12 11 10 9
(Fig.6.3.2)
Pagination/displays Under select control mode, group no. that is present controlling is displayed;
1
present domain Under addresses setting state, present Soft Add is displayed.
Displays the soft address of communication module that the present checking or
2 Present unit no. controlling indoor unit is belonged as well as the address of indoor unit;
Format: Soft add—Indoor unit add
3 Error Displays when there is error at any indoor or outdoor unit.
4 Operation mode Displays every operation state mode of indoor unit
5 Speed display Displays High, Medium, Low and Auto speed of indoor unit
Under group control mode, it is displayed when checking grouping information;
6 Check
Under address setting mode, it is displayed when checking hard address.
Operation monitoring and When central control works in normal, operation monitoring displays; when control
7
controlling /monitoring signal is transmitted, operation monitoring and controlling is displayed.
8 Error code Displays when abnormal occur on operation state of present indoor unit.
9 System time Displays present time, format is Y, M, D, H, M and week.
10 Timer setting Timer On/Off on when Timer On/Off is set to present indoor unit
11 Pre-set temperature Displays value of pre-set temperature
12 Ambient temperature Displays value of ambient temperature of present indoor unit
13 Swing and Defrost Displays operation of swing at indoor unit and defrost at outdoor unit
70
DC INVERTER MULTI VRF CONTROL
15 Control mode Displays 3 control modes of Central, Single and Select controls
As shown in figure, the ”\” at A are parting lines for communication net. Left side of the “\” is the communication net
between central control and communication module while the right side is that between multi variable outdoor unit and
indoor units. The 2 nets are individual nets.
Before normal use of central control, do conduct addresses setting and adjusting to communication system by
installation personnel. Only after that can the central control offered to be used by user.
71
DC INVERTER MULTI VRF CONTROL
This office building has been installed with 2 sets of GMV units, as shown in the table below.
Quantity of
required Quantity of
Name Models communicati indoor Corresponding rooms of indoor units
on modules units
(pinboard)
Address of
Address of
Room communication
indoor unit
module
Office 1 1,2
GMV(L)-Pd160
Unit1 1(0) 12 Office 2 3,4
W/NaB-K
Office 3 5,6
01
Office 4 7,8
Office 5 9,10
Office 6 11,12
Address of
Address of
Room communication
indoor unit
module
Office 7 1,2
GMV-R620W4/ 02
Unit 2 2(2) 20 Office 8 3,4
D
Assembly
1,2,3,4
room 1
03
Assembly
5,6,7,8
room 2
72
DC INVERTER MULTI VRF CONTROL
73
DC INVERTER MULTI VRF CONTROL
3-core neilsbed
connects with indoor
unit or
communication
module.
Mark B: Outdoor Unit GMV(L)-R620W4/A can be connected with up to 32 indoor units by two pinboards ,either of
which can connect with up to 16 indoor units . What’s more, the quantity of communication modules used is the same as that
of pinboards.
In this project, pinboard 1 is connected with the communication module with address of 02 and indoor units (address
01~04)of office 7-8, corresponding with independent communication Net.2. Pinboard 2 is connected with communication
module of address 03 and indoor units (address 01~08)of office 1-2, corresponding with independent communication Net.3.
The outdoor figure is as follow:
74
DC INVERTER MULTI VRF CONTROL
Pinboard 2:
3-core neilsbed connects with indoor unit
or communication module and 4-core
neilsbed with outdoor unit
Pinboard 1:
3-core neilsbed connects
with indoor unit or
modules, and 4-core
neilsbed with outdoor unit
Mark C: Centralized controller cabinet is mainly used to put communication modules together. Refer to Section 3
Instruction to Installation Procedure of System about its figure and connection method of communication modules.
Mark D: Centralized Controller ZJ701. For the first use of it, address mapping setting must be made to specify
addresses of communication modules which should be controlled. In this project example there are 3 communication
modules with the address of 01, 02 and 03 which are displayed in the centralized controller correspondingly.
Mark S1, S2, and S3: Telephone 3-way triple adapters are used to connect communication modules with
communicating net of indoor and outdoor units. Refer to Section 3 Instruction to Installation Procedure of System for its
connection method.
Centralized control
1 Monitor room Installed indoors according to user’s conditions.
cabinet
Centralized
1 Monitor room Installed indoors
controller
75
DC INVERTER MULTI VRF CONTROL
Align the cutting terminals and terminals of communication line to COM1, as shown below:
76
DC INVERTER MULTI VRF CONTROL
And then weld the terminals of communication line to COM1 with the welding spots in the above figure
together by yellow wire to brown wire, as shown below:
At last, wrap the welding spots with insulating tape and test conduction performance of the three
communication lines, as shown below:
77
DC INVERTER MULTI VRF CONTROL
Insert the three crystal heads into the triple adopter and test conduction performance of them, as shown
below:
78
DC INVERTER MULTI VRF CONTROL
Note: The above figure is only for reference to relation among the equipments. The actual wiring is subject to the
above frame diagram of system
●Step 3: There are two methods of DIP address setting of communication module
Method 1: The address of each communication module has been fixed in the factory and marked on the label at the
back of it. It is unnecessary for users to set anything. In addition, the 3-digital DIP can not be dialed to OFF completely, as
shown below:
79
DC INVERTER MULTI VRF CONTROL
80
DC INVERTER MULTI VRF CONTROL
1 0 1 1 0 0 0 0 13 1 0 1 1 0 1 0 0 45
0 1 1 1 0 0 0 0 14 0 1 1 1 0 1 0 0 46
1 1 1 1 0 0 0 0 15 1 1 1 1 0 1 0 0 47
0 0 0 0 1 0 0 0 16 0 0 0 0 1 1 0 0 48
1 0 0 0 1 0 0 0 17 1 0 0 0 1 1 0 0 49
0 1 0 0 1 0 0 0 18 0 1 0 0 1 1 0 0 50
1 1 0 0 1 0 0 0 19 1 1 0 0 1 1 0 0 51
0 0 1 0 1 0 0 0 20 0 0 1 0 1 1 0 0 52
1 0 1 0 1 0 0 0 21 1 0 1 0 1 1 0 0 53
0 1 1 0 1 0 0 0 22 0 1 1 0 1 1 0 0 54
1 1 1 0 1 0 0 0 23 1 1 1 0 1 1 0 0 55
0 0 0 1 1 0 0 0 24 0 0 0 1 1 1 0 0 56
1 0 0 1 1 0 0 0 25 1 0 0 1 1 1 0 0 57
0 1 0 1 1 0 0 0 26 0 1 0 1 1 1 0 0 58
1 1 0 1 1 0 0 0 27 1 1 0 1 1 1 0 0 59
0 0 1 1 1 0 0 0 28 0 0 1 1 1 1 0 0 60
1 0 1 1 1 0 0 0 29 1 0 1 1 1 1 0 0 61
0 1 1 1 1 0 0 0 30 0 1 1 1 1 1 0 0 62
1 1 1 1 1 0 0 0 31 1 1 1 1 1 1 0 0 63
81
DC INVERTER MULTI VRF CONTROL
Display Present Unit No. 00-00 which means soft address 00-No. 00 indoor unit. (Soft address is the No.
displayed in 1-64 grid of LCD.
Press SYSTEM/DEBUG into system setting interface. After pressing UP, DOWN, LEFT and RIGHT buttons,
press CONFIRM button into the interface for selection between ADDRESS SETTING and INITIALIZE SETTING.
Then press UP or DOWN button to switch between them.
DC INVERTER MULTI VRF CONTROL
2. When ADDRESS SETTING is blinking, press SELECT button into address setting interface.
Hard address
Soft address
Press LEFT or RIGHT button to switch between SOFT and Hard ADDRESS settings, and UP or Down button
to adjust their values。After adjustment, press CONFIRM button to make the address values corresponding and
effective. If the cursor stops at hard address position (hard address is blinking), press CANCEL button to make the
setting value ineffective, in which case, the “- -”will be displayed.(Soft address is the No. displayed in 1-64 grid of
LCD and hard address is the actual one of communication module.)
In this example, the centralized controller controls 3 communication modules with the address of 01, 02 and 03
(i.e. hard address is 01,02 and 03).For convenient management, soft address will be set to the same as hard address, i.e.
“01 001”,“02 002”and “03 003”.
If communication is normal after setting, the centralized controller will display as the following figure:
Soft address
display 01,02 Press this button to
and 03 check indoor unit status
under corresponding
soft address.
I. 01,02 and 03 of soft address is displayed, which indicates normal communication of these 3
communication modules.
II. PRESENT UNIT NO. displays “01-08”, which indicates No. 08 indoor unit under 01 communication
module is being checked.
III. Press ROOM/REGION button to check other indoor units’ status under present communication module.
Indoor units’ status is automatically detected, without setting in centralized controller.
① If incorrect or non-connection of communication module, centralized controller and communication line of indoor
and outdoor units, the green indicator will be black all the time.
② It indicates connection problem between communication module and centralized controller that green indicator
blinks once every 2s.In this case, COM2 must be used to connect them.
③ It indicates connection problem of communication module and indoor and outdoor units that green indicator blinks
twice every 2s. In this case, COM1 must be used to connect them. Refer to Step 2, C for details.
84
DC INVERTER MULTI VRF CONTROL
7 MONITORING SOFTWARE
7.1 Function
As the development and improvement of manufacturing technology and in order to solve the problems of complex
distribution of the central AC in the buildings and difficult control and maintenance of them, an platform easy and reliable to
operate must be provided to the users for daily management and maintenance. So this long-distance monitoring system
combining electronic communication and computer technologies is developed to collect the running state of the units and to
monitor and control the units from a long distance. Its structure is as follow:
z the communication cable and heavy-current wire should be separated and the distance between them can not be below
15cm
z line A and line B of Bus 485 should respectively correspond with line A and line B.
DC INVERTER MULTI VRF CONTROL
2. Wiring Diagram
86
DC INVERTER MULTI VRF CONTROL
7.3 Hardware
1. Introduction to Main Devices
1.1 R232-R485 Optoelectronic Isolated Converter (standard parts)
1)Function Introduction:
z R232-R485 optoelectronic Isolated converter is used to convert the signal 232 of PC COM and signal of bus
485.
2)Dimension
Description L(mm) W(mm) H(mm)
3)Installation Dimension
DC INVERTER MULTI VRF CONTROL
4)Installation Criteria:
z It must be installed indoors to avoid knock, insolation or rainwater and is better to be put in the monitoring
room.
z This device must be the original one in the factory. Never self-buy the models for replacement.
z 220-V AC socket must be installed for independent power supply.
z Power supply specification: 12~30VDC 800mA
1.2 Optoelectronic Isolated Repeater(optional parts)
1)Function Introduction:
z Optoelectronic Isolated repeater is mainly used to collect increase of communication distance and nodes
when the quantity of communication modules is above 30 or communication distance is above 800m.Refer
to Project and Installation section for details.
z 2)Dimension
Description L(mm) W(mm) H(mm)
Optoelectronic Isolated Repeater 94 72 23
3)Installation Dimension
88
DC INVERTER MULTI VRF CONTROL
4)Installation Criteria:
z It must be installed indoors to avoid knock, insolation or rainwater and is better to be put in centralized control
cabinet
z This device must be the original one in the factory. Never self-buy the models for replacement.
z 220-V AC socket must be installed for independent power supply.
z 12~30VDC 800mA Power supply specification: 12~30VDC 800mA
1.3 Communication Module (standard parts)
1)Function Introduction
z Communication module is used for conversion and transfer of signal of PC and air conditioner during the
communication of them, making the role of communication controller. Refer to User Instruction to
Communication Module for details.
2)Dimension:
Description L(mm) W(mm) H(mm)
Communication module 150 102 30
89
DC INVERTER MULTI VRF CONTROL
3)Installation Dimension:
Hanging Hole 35 5
Power
z Use Instruction
Please check the user manual of communication module for details information.
5)Installation Criteria of Communication Module:
z Ensure the specification of power adapter to avoid malfunction or damage to the communication module.
z Ensure unique DIP address of each communication module in the project to avoid malfunction.
z Ensure communication cable connects with correct COM to avoid malfunction.
z The communication modules should be put in centralized control cabinet together to avoid direct sunlight or high
temperature and wet environment.
z Power transformer specification: input AC200V~50HZ and output DC9V~800mA
90
DC INVERTER MULTI VRF CONTROL
1)Function Instruction:
z It can put the communication modules together for convenient centralized management and reliable
operation.
2)Dimension:
z The following dimension is for reference. The cabinet is designed according to 10 communication modules
into. If more modules are needed, the cabinet should be designed once again. The internal structure should
accord to actual state.
The external dimension of the cabinet (Unit: mm)
3)Installation Criteria:
z The dimension of the cabinet should be designed according to quantity , arrangement and put position of the
communication modules before make of it.
z Independent power supply for each communication module is needed, so enough 220v AC sockets should be
installed in the cabinet.
z The communication cable and heavy-current wire should be separated for the distance above 15cm.
z The cabinet should be put indoors and locked to avoid insolation and rainwater or contact of non-manager.
1.5 3-way Phone Connector (user provided parts)
Note: Lines without 3-way telephone connector can be connected by welding and protected with insulating tape to
avoid oxidization and short circuit.
DC INVERTER MULTI VRF CONTROL
1)Function Instruction: Common 3-way phone connector is applied to connect 3 pieces of communication cable.
Dimension :
3-way connector 33 27 21
2)Installation Criteria:
z Avoid knock, insolation or rainwater.
z Ensure tightness of each bayonet without load.
z Perform conduction test after installation. Replace the ones of poor contact.
z The welding method is better than 3-way connector.
z After the connection of communication cables with 3-way connector, it must be fixed by insulating tape to
avoid loose and poor contact of crystal head.
92
GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF
INSTALLATION
93
DC INVERTER MULTI VRF INSTALLATION
INSTALLATION
1 PRECAUTIONS FOR INSTALLATION
1.1 Precautions for installation
Before installation, please ensure if the installing site, power ratings, possible operating range (pipe distance,
height difference between indoor and outdoor unit, power voltage) and installing space are correct and suitable.
The outdoor unit is general to all models according to its power.
To ensure correct installation, please make sure to read the Safety Considerations thoroughly before
starting the installation works.
The considerations stated below are classified into WARNING and CAUTION. Those that might
cause death or severe injury in case of wrong installation are identified in WARNING. However, those
that are stated in CAUTION may also cause severe accidents sometimes. Therefore, both of them
relate to important safety considerations and must be strictly followed.
After completing the installation and test run and confirming that all are normal, please introduce to the
client on how to use and repair the machine according to the Operating Instructions. Besides, please
deliver the considerations herein to the clients together with the Operating Instructions, and ask them to
keep properly.
WARNING!
The installation shall be performed by the vendor or professional dealer from which you buy the machine. If
you install by yourself, any improper installation might cause water leakage, electric shock or fire accident.
The installation shall be done correctly according to installation instructions. Improper installation may
cause water leakage, electric shock or fire.
To install a large air-conditioning system in a small room, please make sure to take measures to prevent
that the refrigerant will not exceed the limit concentration in case of leakage. For the measures to prevent
the refrigerant from exceeding the limit concentration, please consult your dealer. If no proper measures, it
might cause human suffocation in case of refrigerant leakage.
Please install at a position that is strong enough to support the weight of machine. If the installing position
is of low strength, the machine may drop down and thus cause human injury.
Please carry out installation in accordance with the rules for preventing the typhoon or earthquake. The
machine may tip over if the installation does not comply with the requirements.
The electrical cabling shall be carried out by qualified electricians in accordance with the Safety Code for
Electrical Equipment, relevant local rules and the installation instructions. Make sure to use the
special-purpose circuit. If the power circuit capacity is low or the construction is improper, it might cause
electric shock or fire accidents.
Please use suitable cables and connect them securely. Please fix the terminal joints securely. The terminal
connection shall not be affected due to any external force applied onto the cable. Improper connection and
fixing may cause heating and fire accidents.
Keep the cables in correct shape and prevent them from protruding upward. Please protect them securely
with repair board. Improper installation may cause heating and fire accidents.
When erecting or relocating the air conditioner, do not let any air enter into cooling circulation system
except the specified refrigerant. If any air is mixed, abnormal high pressure will occur in the cooling
circulation system, thus causing crack or human injury accidents.
During installation, please always use the attached parts or designated parts. Failure to use the designated
parts may cause water leakage, electric shock, fire or refrigerant leakage.
CAUTION:
Please earth securely. Do not connect the earth wires to gas pipe, water pipe, lightning rod or telephone
line. Improper earthling might cause electric shock.
Leakage circuit breaker must be installed at some place. No installation of leakage circuit breaker might
cause electric shock.
Do not install at a place where inflammable gas might leak. Gas leakage and despot around the machine
might cause fire accidents.
To ensure correct drainage of water, the drainage hose shall be installed according to the installation
instructions. Also the heat insulation shall be provided to avoid condensing.Improper installation of the pipe
might result in water leakage and lead to possible wetting of the articles in the room.
94
DC INVERTER MULTI VRF INSTALLATION
Installation
of
connection Welding 1. The copper tube must meet the specifications.
pipes 2. Ensure it is dry and clean inside the tube.
3. Make sure to charge nitrogen as required for protection
95
when welding the tubes.
4. Please keep to the welding process and ensure the
DC INVERTER MULTI VRF INSTALLATION
96
DC INVERTER MULTI VRF INSTALLATION
材料的选购
Material selection
现场安装位置审核
Inspection of site
installation position
安装室内机
Installation of indoor unit 安装连接管
Installation of 安装室外机
Installation of outdoor unit
connection pipes
焊接
Welding
安装远 连接 连接 安装
Installation Connection Connection Installation
of remote of of power of drainage Purge and make
Connection of
连接电源线
程监控 通讯线 电源线 排水管
control communica cables pipes 吹洗和保压检漏
leakage detection
power cables
tion wires under pressure
地址拨码
Address dial code
Thermal
保温 焊接
Welding
保温
Address dial code
insulation
连接室内机和室外机
Connection of indoor unit and outdoor unit 连接室内机和室外机
Connection of indoor unit and outdoor unit
Leakage detection
保压检漏
under pressure
室内机Test run of
indoor unit
试运行检查
抽真空
Vacuuming
风量
Air flow and noise
level inspection
噪音检查 追加制冷剂
Add refrigerant
打开阀门
Open the valve
机组调试
Commissioning of
complete unit
竣工图
As-built Drawing
交付使用说明书
Delivery of the Operating
Instructions
97
DC INVERTER MULTI VRF INSTALLATION
98
DC INVERTER MULTI VRF INSTALLATION
Unit:mm
Model A B C
99
DC INVERTER MULTI VRF INSTALLATION
或以上over
500
500
or
★Arranged on front and back
300(200)
300(200)
1500 or over
1500或以上 1500 or over
1500或以上 or over
或以上
600(500)
或以上
600(500)
or over
100 or over
100
DC INVERTER MULTI VRF INSTALLATION
500 or above
200 or above
500 or above
Bench
Bench
101
DC INVERTER MULTI VRF INSTALLATION
Note!
The air conditioner unit installed in the following place may have malfunction, if it is
unpreventable please contact the Nominated Repair Center Of Gree Electric Appliances, Inc. Of
Zhuhai.
①the place with greasy all around; ②the seashore place with salinity and alkali; ③the place with
vulcanized gas( such as vulcanized hot spring); ④the place with high frequency equipment ( such
as wireless equipment, electric welding machine and medical treatment equipment);⑤the place
with special environment.
102
DC INVERTER MULTI VRF INSTALLATION
Rear air
return vent
103
DC INVERTER MULTI VRF INSTALLATION
104
DC INVERTER MULTI VRF INSTALLATION
Fig.1
105
DC INVERTER MULTI VRF INSTALLATION
Fig.2
1、Look into from air outlet vent, the wiring is in the left of the unit.
2、The method of wind circle can be selected to bottom back wind or rear back wing according to the
installation circumstance of the reality.
型号 A B C D E F G H I J
GMV(L)-R45P/NaB-K GMV(L)-R45PS/NaB-K 932 430 738 892 980 721 738 125 203 266
GMV(L)-R56P/NaB-K、GMV(L)-R71P/NaB-K
1114 420 918 1074 1155 736 1010 207 207 300
GMV(L)-R56PS/NaB-K、GMV(L)-R71PS/NaB-K
GMV(L)-R90P/NaB-K、GMV(L)-R112P/NaB-K
GMV(L)-R90PS/NaB-K、GMV(L)-R112PS/NaB-K 1382 420 1155 1340 1425 736 1280 207 250 300
GMV(L)-R140P/NaB-K 、 GMV(L)-R140PS/NaB-K
106
DC INVERTER MULTI VRF INSTALLATION
Nut with
washer
Nut spring
pad
5 4 5 3
107
DC INVERTER MULTI VRF INSTALLATION
Ceiling hoisting
Return air
Back wind Supply air
Wind supply
Return air
Back wind
No. 1 2 3 4 5 6
Return air Ducted type Return air
Name Hoisting Supply air bent Air outlet
duct indoor unit inlet
Note:Fig.6 only shows the installation of back return air inlet.The bottom return air inlet can be
installed according to the back return air inlet. The supply air duct, which is rectangle or round, and
connected with the air inlet/outlet of the indoor unit, should keep open at least one. The round air
duct type should adopt round duct to transmit cold (hot) air to the room. The round air duct should
add a transitionary pipe, whose size should match with the size of supply air outlet of the unit. After
connecting the transitionary pipe, install the round air outlet connection pipe whose longest length
to each individual air outlet should not be over 10m. Ducted type indoor unit model 70 can share 3
trainsitional pipes, while model 100,120 can share 4. The transitional pipe, whose straight length is
200.Round air outlet connection pipe produced by our company, whose diameter is 200, can be
ordered separately as standard fittings. Model 50 and the model below it do not share the round air
vent. The following is the diagram for installation of round air duct.
Note:
1. The longest length of air duct means the general length of the supply air duct to the
farthest supply air outlet plus the general length of return air duct to the relative farthest
return air inlet.
2.To the unit with auxiliary heater, if the round air duct is need to connected, the straight
length of trainsitional air duct should not shorter than 200mm.
1
2
3
4
7
5 6
Number 1 2 3 4 5 6 7
Return air Ducted type Return air Transitionary Supply air Air outlet
Name Screw
duct indoor unit inlet pipe duct pipe
108
DC INVERTER MULTI VRF INSTALLATION
Note!
There will be lots of lampblack and dust sticked on the acentric, heat exchanger and water pump
in dining room and kitchen, which would reduce the capacity of heat exchanger, thus leading water
leakage and abnormal operation of the water pump. The following treatments should be taken
under this circumstance:
Ensure that the smoke trap above cooker has enough capacity to obviate lampblack to prevent the
indraft of the lampblack by the air conditioner.
Keep the air conditioner far from the kitchen so that the lampblack would not be drafted in by the
air conditioner.
Important notices:
To guarantee the good performance, the unit must be installed by professional personnel
according with this instruction.
Please contact the local authorized repair department of Gree before installation. Any malfunction
caused by the unit that is installed by unauthorized center would not be treated on time by the
inconvenience of the business contact.
109
DC INVERTER MULTI VRF INSTALLATION
GMV(L)-R140T/Na-K
GMV(L)-R125T/Na-K,GMV(L)-R112T/Na-K,GMV(L)-R100T/Na-K,GMV(L)-R90T/Na-K,GMV(L)-R8
0T/Na-K,GMV(L)-R71T/Na-K,GMV(L)-R63T/Na-K,GMV(L)-R56T/Na-K ,GMV(L)-R50T/Na-K,GMV
(L)-R45T/Na-K ,GMV(L)-R36T/Na-K,GMV(L)-R28T/Na-K
Hoisting screw(X4)
A
Package
Dimension Width (mm) Depth (mm) Height (mm)
Model
GMV(L)-R28T/Na-K 950 950 210
GMV(L)-R36T/Na-K 950 950 210
GMV(L)-R45T/Na-K 950 950 210
GMV(L)-R50T/Na-K 950 950 210
GMV(L)-R56T/Na-K 950 950 310
GMV(L)-R63T/Na-K 950 950 310
GMV(L)-R71T/Na-K 950 950 310
GMV(L)-R80T/Na-K 950 950 310
GMV(L)-R90T/Na-K 950 950 340
GMV(L)-R100T/Na-K 950 950 340
GMV(L)-R112T/Na-K 950 950 340
GMV(L)-R125T/Na-K 950 950 340
GMV(L)-R140T/Na-K 950 950 340
110
DC INVERTER MULTI VRF INSTALLATION
W a ll
s u rfa c e
>20
H
W a ll W a ll
s u rfa c e s u rfa c
≥ 1500
M odel H
G M V (L )-R 2 8 T /N a -K
≥ 1500 G M V (L )-R 3 6 T /N a -K 210
G M V (L )-R 4 5 T /N a -K
G M V (L )-R 5 0 T /N a -K
≥1800
G M V (L )-R 5 6 T /N a -K
G M V (L )-R 6 3 T /N a -K 260
G M V (L )-R 7 1 T /N a -K
G M V (L )-R 8 0 T /N a -K
u n it:m m G M V (L )-R 9 0 T /N a -K
G M V (L )-R 1 0 0 T /N a -K 340
G M V (L )-R 1 1 2 T /N a -K
G M V (L )-R 1 2 5 T /N a -K
G M V (L )-R 1 4 0 T /N a -K
G ro u n d
s u rfa c e
111
DC INVERTER MULTI VRF INSTALLATION
Gasket (attachment)
Insert
Hoisting stand
Gasket anchor board
Tighten (double nuts) (attachment)
Water lever
Bolt (attachment)
[Fix the install cardboard]
Note!
● Please do tighten the nuts and bolts to prevent air conditioner breaking off.
● Connect the refrigerant pipe
☆ When connecting the pipe to the unit or remove it from the unit, please do use both spanner
and torque wrench. as shown in fig.3.
☆ When smearing both inside and outside of the flare nut with antifreezing motor oil, screw it by
hand and then tighten it with spanner.
☆ Refer to form 1 to check if the wrench has been tightened (too tight would mangle the nut and
lead leakage).
☆ Examine the connection pipe for gas leakage, and then take the treatment of heat insulation, as
shown in the fig.3.
☆ Only use median sponge to entwine the wiring interface of the gas pipe and heat preservation
sheath of the gas collection pipe.
112
DC INVERTER MULTI VRF INSTALLATION
Thread fasten(x4)
Torque wrench
Heat preservation
sheath of liquid inlet
tube (attachment) (for
liquid tube)
Heat preservation
Spanner sheath of gas collection
Gas collection tube tube (attachment)(for
gas tube)
Liquid inlet tube
Flare nut
● Drainage hose
1. Installing the drain hose
☆ The diameter of the drainage hose should be equal or bigger than the connection pipe’s. (The
diameter of polythene pipe: Outer diameter 25mm Surface thickness ≥1.5mm)
☆ Drainage hose should be short and drooping gradient should be at least 1/100 to prevent the
formation of air bubble.
☆ If drainage hose cannot has enough drooping gradient, drain raising pipe should be added.
☆ To prevent bent of the drain hose, the distance between hoisting stands should is 1 to 1.5m.
1-1.5m
113
Sponge (gray) Drain hose Below 4mm
DC INVERTER MULTI VRF INSTALLATION
right angle with the unit, and distance to unit should not be beyond 300mm.
Roof
Hoisting stand
Within 300mm 1-1.5m below280mm
Drain hose
below500mm
Drain raising
.
hose
220mm
.
Ceiling Clamp(attachment)
Instruction
☆ The slant gradient of the attached drainage
hose should be within 75mm so that the drain D ra in h o s e (a tta c h m e n t)
below75mm
hole doesn’t has to endure the unnecessary
below500mm
outside force.
.
☆ Please install the drainage hose according to
the following process if several drain hoses
connected together.
T-tie in join drain hose
Above100mm
.
The specs of the selected join drain hose should fits the running capacity of the unit.
114
DC INVERTER MULTI VRF INSTALLATION
115
DC INVERTER MULTI VRF INSTALLATION
116
DC INVERTER MULTI VRF INSTALLATION
Fig.1
4.3.4 Installation demonstration
● There are 2 styles of installation
☆ Ceiling type
☆ Floor type
Each type is similar to the other as follows:
1. Determine the mounting position on ceiling or wall by using paper pattern to indicate indoor
frame. Mark the pattern and pull out the paper pattern. (Refer to Fig.2)
2. Remove the return grill, the side panel and the hanger bracket from the indoor unit as per
procedure bellow.
☆ Press the fixing knob of the return air inlet grills, the grilles will be opened wider and then pull
them out from the indoor.
☆ Remove the side panel fixing screw and pull to the front direction (arrow direction) to remove.
Side panel fixing screw (Refer to Fig.3).
☆ Loosen two hanger bracket setting bolts (M8) on eath side for less than 10mm. Remove two
hanger bracket fixing bolts (M6) on the rear side. Detach the hanger bracker by pulling it
backward (Refer to Fig.5).
Fig.2 Fig.3
117
DC INVERTER MULTI VRF INSTALLATION
3. Set the suspension bolt. (Use W3/8 or M10 size suspension bolts)
☆ Adjust the distance from the unit to the ceiling slab beforehand (Refer to Fig.4)
4. Fix the hanger bracket to the suspension bolt.
Warning!
☆ Make sure that extended suspension bolt from the ceiling stays inside the arrowed position.
Readjust the hanger bracket when it is outside the arrowed position. (Refer to Fig.6)
☆ Suspension bolt stays inside the cap of indoor unit. Never remove the cap.
5. Lift the unit and slide forward unit the dent. (Refer to Fig.7)
6. Screw tightly both hanger bracket-setting bolts (M8). (Refer to Fig.5)
7. Screw tightly both hanger bracket-fixing bolts (M6) to prevent the movement of the indoor unit.
(Refer to Fig.5)
8. Adjust the height so that rear side of the drainpipe slightly inclines to improve drainage.
Caution!
☆ Adjust the height by turning the nut with a spanner.
Insert the spanner from the hanger bracket opening. (Refer to Fig.8)
In case of hanging
It is possible to install using inward facing hanger brackets by not removing the brackets from the
indoor unit. (Refer to Fig.9)
Be sure to use only the specified accessories and parts for installation work.
118
DC INVERTER MULTI VRF INSTALLATION
119
DC INVERTER MULTI VRF INSTALLATION
B
A C
120
DC INVERTER MULTI VRF INSTALLATION
>150
>150 >150
>3000 wall
>2000
unit:mm
ground ground
Important Notice:
The unit must be installed by the professional personnel according to this install instruction to
ensure the well use.
Please contact the local authorized repair department of Gree before installation. Any malfunction
caused by the unit that is installed by unauthorized center would not be treated on time by the
inconvenience of the business contact.
It should be guided under the professional personnel when the air conditioner unit is moved to
other place.
121
DC INVERTER MULTI VRF INSTALLATION
Fig.1
1. Find the horizontal position by seton method; since the drainage hose is on the left side,
adjust the rear panel to make its left side a little bit lower.
2. Fix the rear panel on the wall by bolt.
3. After installing the rear panel, pull it by hand to check if it is firm enough. The hang panel should
support the weight of an adult (60KG), and the weight shared by every bolt for steady should be
fairly even.
4. The diameter showed on the fig.1 is 65mm.
Installation the Wall Mounted Type indoor unit
☆ Make the piping hole (Φ65mm) in the wall at a slight downward slant to the outdoor side. The
center of the hole should be determined refer to Fig.1
☆ Insert the piping-hole sleeve into the hole to prevent the connected piping and wiring from being
damaged when passing through the hole.
● Install the drainage hose
For well draining, the drainage hose should be placed at
a downward slant. Wrenched
Bent
Do not wrench or bend the drainage hose or flood its
end bywater. (Fig.2)
☆ Wrap heat resistant material when connect the
longer drainage hose though indoor. Flooded
Fig .2
● Install the connection pipes
Connect the connection pipe with the two relative leading pipes, and tie the nut on tie –in of the
connect pipe tightly.
Note!
☆ Be careful in bending the connection pipes, or you will damage the pipes.
☆ If the tightening torque is too great in tightening the flare nut, leakage will happen.
1. Obstruct should be away from the air intake or outlet vent of the indoor unit so that the
airflow blow all over the place of the room.
2. Make sure the installation of the indoor unit accords with the requirement for installation
dimension drawing.
3. Select the place which can withstand 4 times weight of the indoor unit and would not
increase the operating noise and shake.
122
DC INVERTER MULTI VRF INSTALLATION
5. Select the place, where coagulated water is easy to discharge and outside unit to be
connected.
6. Above 18000mm between the earth and indoor unit should be ensured for maintenance and
repair.
7. Use hoisting screw to check if the installation place can withstand 4 times weight of the units and
strengthen it before installing.
4.5.2 Dimensions Data
Important notice:
Drilling the hole of the ceiling and installing the units must be operated by
professionals
123
DC INVERTER MULTI VRF INSTALLATION
Fig 3
Attach the hoisting stand base to hoisting screw. In order to firm the hoisting stand
base, use nuts with washers on either end of it.(refer to Fig. 1)
2. Please refer to the dimension of ceiling opening on the cardboard for installation
● There is a mark for ceiling opening center on the cardboard.
● There is also a mark for main body center on the cardboard.
● Use screws to fix the installation cardboard on the unit. (refer to Fig.3)
3. Adjust the unit to right installation place.
4. Check if the unit is horizontal.
Inner drainage pump and bobber switch are installed in indoor unit. Check if every
side of the unit is horizontal by water lever. (If the unit slants to opposite direction
towards which coagulate water flows, it will bring malfunction to the bobber switch
and cause water drops. (refer to Fig.2)
5. Unscrew the screws on the cardboard, which can be used for installing front panel.
124
DC INVERTER MULTI VRF INSTALLATION
● Drainage pipe
1. Installing drainage pipe
The diameter of drainage pipe should be larger than that of connecting pipe. (Polythene pipe:
dimension: outer diameter 25mm wall thickness≥1.5mm)
● Drainage pipe should be as short as possible and drooping gradient at least 1/100 to avoid
the formation of air bubble.
● If drainage hose cannot have enough drooping gradient, drainage raising pipe should be
installed.
● In order not to bend the drainage hose, the distance between hoisting stands should be 1 to
1.5m..
● With accessory drainage hose and clamp, insert the drainage hose into the drainage faucet,
and then tighten the clamp.
● Entwine the clamp of drainage hose with the big sponge to isolate heat.
● Isolate heat for the outdoor drainage host.
125
DC INVERTER MULTI VRF INSTALLATION
Ceiling
Note:
● The gradient of the accessory drainage hose should be within 75mm so that the drainage
faucet need not endure extra outside force.
● If several drainage hoses join together, please install them according to the following
process.
The specs of the selected joint hose should fit the running capacity of the
units.
126
DC INVERTER MULTI VRF INSTALLATION
2. AS shown in Fig.4, install the panel body, and then tighten the screws according to the
sequences in the figures.
3 .As shown in Fig.5, install the panel on the panel ,and then turn it for fastening
Fig.1
6. Make sure that there are enough space for care and maintenance. Make sure that the weight between the
indoor unit and ground is above 1800mm.
7. When installing the steeve bolt, check if the install place can stand the weight 4 times of the unit’s. If not,
reinforce before installation. (Refer to the install cardboard and find where should be reinforced)
Note!
There will be lots of lampblack and dust stick on the acentric, heat exchanger and water pump in dining
room and kitchen, which would reduce the capacity of heat exchanger, lead water leakage and abnormal
operation of the water pump. The following treatment should be taken under this circumstance:
1. Ensure that the smoke trap above cooker has enough capacity to obviate lampblack to prevent the indraft
of the lampblack by the air conditioner.
2. Keep the air conditioner far from the kitchen so that the lampblack would not be indraft by the air
conditioner.
● Important notice:
☆ To guarantee the good performance, the unit must be installed by professional personnel according with
this instruction.
☆ Please contact the local Gree special nominated repair department before installation. Any malfunction
caused by the unit that is installed by the department that is not special nominated by Gree would not deal
with on time by the inconvenience of the business contact.
128
DC INVERTER MULTI VRF INSTALLATION
Ceiling
Above 20
Fig.2
Notes: The dimension for the ceiling openings with * marks can be as large as 910mm. But
the overlapping sections of the ceiling and the decorated surface boards should be maintained
at no less than 20mm.
☆ When attach the hoisting stand on hoisting screw, do use nut and gasket individually at the upper and
lower of the hoisting stand to fix it. The use of gasket anchor board can prevent gasket break off.
2 Use install cardboard
☆ Please refer to the install cardboard about the dimension of ceiling opening.
☆ The central mark of the ceiling opening is marked on the install cardboard.
☆ Install the install cardboard on the unit by bolt (3 piece), and fix the angle of the drainage pipe at the
outlet vent by bolt.
3 Adjust the unit to the suitable install place. (Refer to the fig.2)
4 Check if the unit is horizontal.
☆ Inner drainage pump and bobber switch are included in the indoor unit, check if 4 angle of every unit are
horizontal by water lever. (If the unit is slant toward the opposite of the coagulate water flow, there may be
malfunction of the bobber switch and lead water drop.)
5 Backout the gasket anchor board used to prevent gasket break off and tighten the nut on it.
6 Backout the install cardboard.
Nut (supplied at scene)
Gasket (attachment)
Insert
Hoisting stand
Gasket anchor board
Tighten (double nuts) (attachment)
Water lever
Bolt (attachment)
[Fix the install cardboard]
Note!
● Please do tighten the nuts and bolts to prevent air conditioner break off.
130
DC INVERTER MULTI VRF INSTALLATION
Thread fasten(x4)
Torque wrench
Heat preservation
sheath of liquid inlet
tube (attachment) (for
liquid tube)
Heat preservation
Spanner sheath of gas collection
Gas collection tube tube (attachment)(for
gas tube)
Liquid inlet tube
Flare nut
● Drainage hose
1. Install the drain hose
131
DC INVERTER MULTI VRF INSTALLATION
☆ The diameter of the drain hose should be equal or bigger than the connection pipe’s. ( The diameter of
polythene pipe: Outer diameter 25mm Surface thickness ≥1.5mm)
☆ Drain hose should be short and drooping gradient should at less 1/100 to prevent the formation of air
bubble.
☆ If drain hose cannot has enough drooping gradient, drain raising pipe should be added.
☆ To prevent bent of the drain hose, the distance between hoisting stand should is 1 to 1.5m.
1-1.5m
☆ Use the drain hose and clamp attached. Insert the drain Sponge(attachment)
Roof
Hoisting stand
Within 300mm 1-1.5m below280mm
Drain hose
below500mm
Drain raising
.
hose
220mm
.
Ceiling Clamp(attachment)
Instruction
☆ The slant gradient of the attached drain hose should be within 75mm so that the drain hole doesn’t has to
endure the unnecessary outside force.
132
DC INVERTER MULTI VRF INSTALLATION
☆ Please install the drain hose according to the following process if several drain hoses join together.
D ra in h o s e (a tta c h m e n t)
below75mm
below500mm
.
T-tie in join drain hose
Above100mm
.
The specs of the selected join drain hose should fits the running capacity of the unit.
● Electrical wiring
Note: The power of the entire indoor unit must be unity power supply
☆ About the electrical wiring, please see the circuit diagram attached with the unit.
☆ All the installation of electrical wiring must be done by professional personnel.
☆ Please do take the earthing treatment.
Wiring method of connection unit and controller
☆ Connection wiring (communication):
① Open electric box cover, drag the wiring (communication)from the rubber plug A, and impact them well
individually by impact fastener.
② Wiring according to the indoor side circuit diagram.
☆ Fix the impact fastener after connection.
☆ Entwine the small sponge on the electric wire ( do entwine it to prevent condensation)
☆ Impact tightly by impact fastener after connection and then fit on the electric box.
☆ Connect the 3 cord rubber wire to the counter terminal of the 3 way terminal board.
L
L
N
power supply
N
133
DC INVERTER MULTI VRF INSTALLATION
2. Function of it is as follow:
Dial switch
Function Dial ON Dial OFF
Silk screen
Selection of memory mode:
Standby
A:Selection between reset mode and standby mode after Reset after
1(S / R) after
energizing energizing
energizing
B:This function is available without wired controller.
Selection between manual controller and receiver
Selecting Selecting
A:If manual controller is selected, remote-control function of
2(L / I) wired receiver
receiver will be shielded.
controller joint
B:If receiver is selected, wired controller will be non-effective.
Setting of main and slave indoor units
Main indoor Slave
3(M / S) A:For resolution of conflict among the modes.
unit indoor unit
B:This function is available without wired controller.
Piping position
① Bolt (attachment)
Bolt (attachment)
Fig 4
Note
1. Improper screwing of the screws may cause the troubles shown in fig.5.
135
DC INVERTER MULTI VRF INSTALLATION
Air leak
Fig.5
2. If gap still exist between ceiling and decoration panel after tightening
the screws, readjust the height of the indoor unit. (As shown in fig.6)
If the raising lever and drain hose are
not affect, can adjust the height of
indoor unit by the hole on the corner
of panel.
Fig.6
※ After fixing, be sure no gap left between the ceiling and the panel.
3. Wiring of the decoration panel (Fig.7)
☆ Connect the joints for swing flap motor lead wire (at 2 places) installed on the panel.
At body At pane
At body At pane
Fig.7
136
DC INVERTER MULTI VRF INSTALLATION
Drainage hose
Guide louver
(placed in air
outlet vent)
Fig.8
137
DC INVERTER MULTI VRF INSTALLATION
5.2 Allowable Length and Height Differences of the Refrigerant Piping between the Indoor and Outdoor
Units
Allowable Value
Pipe
100,120,140,160
Total Length (Actual Length) of Pipes 150m L1+L2+L3+a+b++c+d
Actual Length 70m
Length of farthest pipe (m) L1+L2+L3+d
Equivalent Length 80m
Length of pipe from the 1st manifold to the farthest indoor unit 25m L2+L3+d
138
DC INVERTER MULTI VRF INSTALLATION
Note: When the capacity of indoor unit is less than 5KW, if the distance from the nearest manifold
to the indoor unit exceeds 10m, the fitting pipe on liquid side of the pipe shall be increased of one
dimension.
139
DC INVERTER MULTI VRF INSTALLATION
Fabrication according to
piping design dimension
Installation of
connection pipes
Welding
Purge
Airtight test
Vacuuming and
drying
140
DC INVERTER MULTI VRF INSTALLATION
Plot the line on ground if possible and use laser to project it onto the roof. This is quick and
correct.
In case that the metal embedded parts cannot be used due to design change, the expansion
CAUTION:
Never let the pipe in direct contact with the fixing metal parts. Thermal insulation shall be
provided around the fixing metal parts; otherwise, condensing will occur.
2)Fixing of vertical pipe
The vertical pipe may be fixed by using the commodity tools in market or self-made tools. As
above, the fixing point shall also be thermally insulated.
3)Fixing of other points
Measures shall be taken to prevent the extension or shrinkage of pipes from causing excessive
loads to some positions, machine joint and waterproof points. Generally, such positions refer to
the branch pipe joint, pipe ends, four sides of indoor unit and wall-cross hole.
141
DC INVERTER MULTI VRF INSTALLATION
Clamp the pipe end to flat and weld on the clearance. Then, charge nitrogen 2~
2
5kgf/cm . This will be more effective.
Method for wrapping with adhesive tape
Seal the pipe end with ethylene tape.
2)Coil unwinding
CAUTION:
When unwinding the coil, take care not to drag it on the ground. The coil shall be slowly unwound
on ground without any twisting. In case of excessive compression by any hard object during
unwinding, the thermal insulation materials may be damaged and cannot be recovered, which will
deteriorate the performance of thermal insulation. Do not unwind carelessly. Otherwise, the fitting
pipe might be flattened.
The copper pipe shall be rounded if the pipe end is deformed.
(The higher the size, the higher the possible deformation)
3)Measuring of pipe
(To reduce the resistance and length of copper pipe), the dimension of main refrigerant pipe shall
be so taken that the bends shall be minimized, the radius of bend section shall be increased and
the upstream and downstream section shall be reduced. Use the method that can reduce the
actual length and equivalent length of the copper pipe.
Sometimes the connection pipe of indoor unit must be adjusted due to the relation with
accessories, drainage hose and connection surface. Therefore, a fairly marginal dimension
shall be taken.
142
DC INVERTER MULTI VRF INSTALLATION
4)Cut·Chamfer
Cut
Cut vertically to axis direction by using special pipe cutter that is suitable to the dimension of
copper pipe (big, medium, small).
During operation, press and rotate the pipe cutter slowly and cut off the copper pipe without
causing any deformation.
Never use saw or grinding wheel, because the copper scraps may be left inside the pipe. Even use
of such tools once will make all works scrapped. It is useless no matter how good the quality of
other works. It is best that all operators shall have one pipe cutter and at least one pipe cutter of
big dimension shall be provided on site.
CAUTION:
To prevent the invasion of water or waste, avoid placing the copper pipe directly on ground.
Chamfer
Burrs may occur on the cutting face of copper pipe and must be removed. Meanwhile, purge the
foreign articles out of the pipe and refinish the pipe end.]
● Use scraper or other tools to remove the burrs on inner side.
(To prevent copper scraps from falling into the pipe, please keep the pipe end downward during
operation).
● If the pipe end is obviously deformed, please cut and throw it off, and then refinish the pipe end.
● Eliminate the copper scraps thoroughly, and use cotton yarn to wipe the pipe clean.
※ The flared joint must be kept smooth.
※ When removing the burrs with scraper, do not remove too much, especially for the fitting pipe of
small diameter; otherwise the contact surface of the flared joint will be reduced. Do not cause any
scores, and avoid cracking after the flared joint is formed.
※ Adverse impact if the burrs are removed too much with scraper:
143
DC INVERTER MULTI VRF INSTALLATION
Flared nut
5)Pipe bending
◆ Work Methods:
Bend by hand ………………………..Suitable to fine copper pipe (φ6.35mm-φ12.7mm).
Machining with spring pipe bender …….. Bend by inserting the spring into copper pipe or
sheathing onto the copper pipe (φ6.35mm-φ22.2mm).
Machining with hand-operated pipe bender……Use the pipe bender of suitable dimension
(φ6.35mm-φ22.2mm).
Machining with electric pipe bender (hydraulic)……Suitable for mass machining of fine and coarse
fitting pipes (φ6.35mm-φ69.9mm).
Advantages
Decrease the weld joint, thus reduce the possibility of leakage and oxidization.
For example:
It can decrease the weld by 8 spots. Please act now to improve the quality.
※ No joint is required, which will save the material costs. Reduced waste of fitting pipe materials.
※ Reduced resistance in the fitting pipe. The bending radius higher than the pipe joint.
◆CAUTIONS
※ During bending, there shall be no wrinkling or deformation on the inner side of the copper pipe.
※Spring pipe bend
※ The bender inserted into the copper pipe must be cleaned.
※ Do not bend over 90º. (Otherwise, wrinkling may be formed on the inner side of copper pipe
and in the future, the copper pipe will be broken from this position.)
144
DC INVERTER MULTI VRF INSTALLATION
Steel pipe
Jacketed bender
Section
Correct section
Bend section
6)Flaring
The flaring refers to expansion of pipe opening. The copper pipe is inserted here to replace the
casing pipe. In this way, it is only needed to weld on one position where the pipe is expanded.
Welding
145
DC INVERTER MULTI VRF INSTALLATION
146
DC INVERTER MULTI VRF INSTALLATION
Within 30°
Within 30°
The connection method that copper pipe is in couple with a smaller branch pipe shall not be used:
147
DC INVERTER MULTI VRF INSTALLATION
Correct connection
Wrong connection
Copper pipe shall not be inserted too much for connection with branch pipe:
Correct connection
Wrong connection
Approx. 1m Approx. 1m
i. To avoid the position difficult to weld, you may add a prefabricated assembly below.
Drainage pipe
Difficult to weld at
this position
149
DC INVERTER MULTI VRF INSTALLATION
4)Operation order
Basic procedures for welding:
Assemble copper
pipes
Cleaning
Fill nitrogen N2
150
DC INVERTER MULTI VRF INSTALLATION
After assembling, nitrogen begins to charge until welding is finished and will continue over
10s during cooling after welding.
※ Main points of nitrogen charge(See the drawing below)
◆ When nitrogen is charged, the press switch on the quick connector and inflator shall be
closed to let nitrogen totally filled in the pipe.
◆ Make sure nitrogen reaches all welding connectors in order to effectively discharge air.
◆ A vent port must be available when nitrogen charge is continuously performed, or otherwise
gas would escape from gap around connector, making welding stuffing difficult and prone to
pores.
Nitrogen N2
氮气(N2) Vent port
出气口
d. Welding heating
Notes:
● Braze welding is flame hard braze welding. Relevant safety operating regulations must be
abided by.
● Confirm that nitrogen is flowing through before copper pipe is heated.
● Neutral flame or slightly reducing flame shall be used for red copper braze welding. Outer
flame is normally used. Copper pipe connectors shall be heated uniformly. Take care to
distribute heat in terms of dimension of pipe material. Generally, insert pipe shall be
preheated at first for close matching and then swayed along length of connector to make it
heated uniformly until braze welding temperature is approached; then copper pipe is heated
circularly to reach braze welding temperature (copper pipe becomes light red) and at the
same time brazing filler metal is added circularly to fill in the clearance around the connector
uniformly; and afterwards, the welding torch is slowly moved away from the pipe and a small
amount of brazing filler metal continues to be filled in until smooth fillet is formed.
● During heating, welding rod shall not be burned directly by flame. Heating time shall not be
very long.
● During welding, flame shall be controlled well on its direction and kept away from rubber
casing, sponge and cables.
e. Post-welding treatment(cooling)
● After welding, in the condition of nitrogen protection available, the connector shall be heated
until the copper pipe changes color (200-300℃), i.e. annealing treatment.
● Before welding seam becomes completely solidified, welded pieces shall not be moved or
shocked.
● For welded piece cooled by water, take care not to let water enter into copper pipe and try to
prevent residue water flowing into the pipe when welded piece is laid aside.
f. Quality and inspection of braze welding
151
DC INVERTER MULTI VRF INSTALLATION
Welding seam should have smooth surface. Fiilet should be even and full with natural arc
transition. Braze welding connector should be free from defects such as over-burning, welding
blockage, crack, rough surface of welding seam and burning through. Welding seam should be
free from defects such as pore, slag inclusion, underfill, rosin joint and overlap.
Weld spot
5)Others
◆ When braze welding is to be performed underneath, a simple support shall be built, such as
two ladders.
152
DC INVERTER MULTI VRF INSTALLATION
Solder Solder
Weld torch
Weld torch
Solder
Transverse
Weld torch
Upward
Downward
◆Cooling
To avoid getting a burn in following processes, common wet cloth (humidity content is low,
meaning that there shall not be water drips when welded part is cooled; and because shrinkage
factor of copper is different from that of welding material, too quick cooling that would cause
cracking of braze welding shall be avoided) can be used for cooling welded parts.
◆The following items shall be checked after welding is completed
● Is there any pore or hole on welded part?
● Is there evident “sagging of brazing filler metal”?
2)Cleaning steps:
a. Mount a pressure gauge on nitrogen cylinder;
Nitrogen bottle
Indoor unit A outdoor unit B
Liquid pipe
Outdoor side
b. High pressure end of the pressure gauge is connected to the refrigerant filling nozzle of the
small pipe (liquid pipe)
c. All copper pipe ports outside the A side of indoor unit shall be blocked by blanking plugs.
Copper pipe Blanking plug
Cleaning process
d. The valve on nitrogen cylinder shall be opened to maintain pressure at 28Kgf/ cm2
e. Check whether nitrogen flows through the liquid pipe of indoor unit A
f. Cleaning
The mouth of the pipe shall be blocked with insulation material held by hand until pressure rises to
a level difficult to be withstood, and at the moment the insulation material shall be released quickly.
And then the mouth shall be blocked again. Repeat such procedures several times. Afterwards,
use a wood board posted with white paper to check it. If there is not evident dirt on the white paper,
the pipe will be considered clean.
g. Shut off the main valve of nitrogen
h. Repeat the above procedures on indoor unit B
i. After cleaning of liquid pipe, gas pipe shall be cleaned in the same way.
154
DC INVERTER MULTI VRF INSTALLATION
◆ Pressurization
Use nitrogen to add pressure from Freon nozzle of the gas and liquid pipe on outdoor unit side:
Step 1: Increase the pressure to 0.5MPa and wait for 5 minutes or longer
Step 2: Increase the pressure to 1.5MPa and wait for 5 minutes or longer
The step 1 and 2 are focused on checking the significant leakage point. If any, reweld immediately
or repair the leakage point.
Step 3: Increase the pressure to 4.15MPa and keep it for approx. 24 hours to check the small
leakage.
Though the pressure is increased to 4.15MPa, it cannot be guaranteed to find out the small
leakage if the waiting time is too short. Therefore, the pressure in Step 3 must be kept for 24
hours.
Note: During pressure maintaining after nitrogen is filled, the pressure gauge shall not be
dismantled, because activities of dismantling or mounting pressure gauge would affect pressure
change.
◆Check pressure drop
Criteria for Inspection eligibility:
※ Except for temperature influences (pressure changes about 0.01MPa for temperature change
of 1℃), if pressure drop is not more than 0.02MPa within 24h, the system will be eligible. For
example, nitrogen is filled to reach 2.5MPa at 30℃; after 24 hours, when temperature becomes
25℃, the system will be eligible if pressure is over 2.43 MPa and ineligible below 2.43 MPa.
※ If ineligible, leak sources must be located. After leak sources are found, re-welding or repair
welding is necessary. Then, the above procedures shall be repeated. Nitrogen is filled,
pressurized and maintained until pressure drop remains within required range.
◆Leak check
[Check 1] When pressure drop is found, leak hunting shall be performed in the ways as follows:
a. By ears…….to listen voices related to leakage
b. By hands……to sense whether leakage is existent at connecting parts
[Check 2] If no leakage is found using the above methods, nitrogen shall be discharged and
refrigerant shall be filled in to reach 0.5MPa.
a. By soap and water……soap bubbles will show leakage positions if any.
b. Detector (such as halide detector) can be used for leak hunting
Using the above methods, check all possible leak sources.
If leakage still fails to be located, sectional check shall be taken for refrigerant piping that would be
divided into multiple check portions for locating leak source in a certain section.
2 ) Pressure maintaining and leak hunting of the system ( with refrigerant piping in
connection with indoor unit and outdoor unit)
When refrigerant piping is to be installed, pressure maintaining and leak hunting is required for the
piping. After refrigerant piping is in connection with indoor unit and outdoor unit, pressure
maintaining and leak hunting is also required. The purpose of the test is to check whether any leak
is existent at threaded connection of indoor unit and outdoor unit and at new welded points.
155
DC INVERTER MULTI VRF INSTALLATION
Steps:
◆Nitrogen is charged to reach 4.15MPa and remains at the pressure for 24h (nitrogen shall be
filled from refrigerant filling nozzles at the big valve as well as the small valve using a pressure
gauge; during pressure maintaining after nitrogen is charged, the pressure gauge shall not be
dismantled.)
◆ 2Observe whether pressure changes in 24 hours. (for eligibility criteria, see pressure
maintaining and leak hunting of refrigerant piping in 5.5.2)
◆If any leakage, please check threaded connections and new welded spots of indoor unit and
outdoor unit. Repair welding shall be performed immediately. Afterwards, pressure maintaining is
repeated until eligibility is reached.
2)Cautions:
a. The range of pressure gauge for R410A system test shall be over 4.5Mpa;
b. At the same time, record the readings on pressure gauge, ambient temperature and test time;
c. Pressure correction: The pressure will change by 0.01Mpa with temperature changing by every 1℃;
d. It is only acceptable when the pressure is kept unchanged;
e. To keep the pressure for a long time, the pressure shall be decreased to 0.5MPa or lower. High pressure of a
long time might cause leakage at the weld and result in safety risk.
f. Before completing the airtight test of refrigerant pipe, never carry out thermal insulation or wrapping work at the
weld and flared connection of indoor unit. The pressure shall be simultaneously applied from the pipes on outdoor
side. Never apply pressure from a single side;
Apply pressure
simultaneously from gas
pipe and liquid pipe
1.4 Caution: Before completing the airtight test of refrigerant pipe, never carry out thermal insulation or wrapping
work at any weld.
6.10 Heat Preservation of Refrigerant Piping
1) Connection of thermal insulation pipe
Carry out thermal insulation to the refrigerant pipe after confirming that it has no leakage.
Please perform thermal insulation to the refrigerant pipe according to the steps below
◆Check if the thermal insulation pipe has met the thickness requirements. If not, the condensing
water is easy to attach on thermal insulation pipe and finally drips. The thickness requirements are
shown below:
Thickness of Thermal Insulation
Refrigerant Pipe (mm) (Outer Dia. x Thickness)
Materials (mm)
Φ6.35×0.5 ≥10
Φ9.52×0.71 ≥10
Φ12.7×1 ≥15
Φ15.9×1 ≥15
Φ19.05×1 ≥15
Φ22.2×1.5 ≥20
Φ25.4×1.5 ≥20
Φ28.6×1.5 ≥20
Φ34.9×1.5 ≥20
◆Wrap the refrigerant pipe according to required thickness. The clearance between thermal
insulation pipes shall be sealed with self-adhesive sticker.
◆Wrap the thermal insulation pipes with tapes, thus to extend their ageing time.
2)Cautions:
The thermal insulation materials shall be able to withstand the pipe temperature. For heat pump
156
DC INVERTER MULTI VRF INSTALLATION
unit, it is required to withstand a temperature not lower than 70℃ on liquid pipe side and not lower
than 120℃ on gas pipe side. For cooling-only unit, it is required to withstand a temperature not
lower than 70℃ on both liquid pipe side and gas pipe side.
Example: Heat resistant PVC foam (over 120℃); Foam PVC (over 100℃)
The connector between indoor unit and outdoor unit shall be wrapped with thermal insulation
materials, and shall have no clearance to the wall on which the outdoor unit is mounted, as shown
below.
No clearance
When wrapping the thermal insulation tape, each circle shall suppress half of the previous circle.
To avoid reducing the thermal isolation effect, do not wrap the tapes too tight.
After completing the protection work and wrapping the pipes, use the sealing materials to block the
holes in the wall.
157
DC INVERTER MULTI VRF INSTALLATION
Vacuum pump
Connector on liquid side
Start the vacuum pump and turn on “LO” and “HI” knobs
b. Continue for 0.5~1.0 hour after the vacuum level reaches -0.1MPa (gauge pressure -1kgf/cm2).
Then, close the “VH” knob on high pressure end and “VL” knob on low pressure end to stop the
vacuum pump.
c. Remove the hose connected to vacuum pump and reconnect it to the refrigerant tank. Expel the
air in the hose. Open the “VL” knob on low pressure end to charge refrigerant to the system piping.
When the pressure reaches 0.0kgf/ cm2, close the “VL” knob on low pressure end.
d.Remove the hose connected to refrigerant tank and reconnect it to vacuum pump. Start the
vacuum pump and open the “VH” knob on high pressure end. Pump for 30 minutes from high
pressure end and then open the “VL” knob to pump from low pressure end, until the vacuum level
reaches -0.1MPa (gauge pressure -1kgf/cm2).
If the vacuum level reaches -0.1MPa (gauge pressure) or lower, the vacuuming process is then
ended. Stop the vacuum pump and place still for 1 hour. Then, check the vacuum level for any
change. n case of any change, it indicates that there is leakage. In this case, proceed to leakage
detection and repair.
e. Complete the vacuuming according to above procedures and then proceed to charging of
additional refrigerant
158
DC INVERTER MULTI VRF INSTALLATION
Refrigerant cylinder
Spring balance
b. Open pressure gauge valve VH, then fill liquid state refrigerant into the liquid pipe side until
required amount is reached.
If refrigerant can not be charged in system unless the unit is turned on, let the system run at
full-load cooling mode. Open VH and discharge air in the hose. The high pressure end of pressure
gauge is connected to the refrigerant filling nozzle on the small valve of outdoor unit. Open VL and
charge gas state refrigerant into the gas pipe until required charging amount is reached.
c.Observe electronic balance or spring balance. When required amount is reached, the valve shall
be closed very quickly and then source valve on the refrigerant valve shall be shut off.
d. The amount of charging refrigerant shall be recorded.
Refrigerant charge shall be recorded as per the following table.
Unit Mark Amount of charging refrigerant(Kg)
Unit 1
Unit 2
………
Unit n
159
DC INVERTER MULTI VRF INSTALLATION
To Indoor To Outdoor
Unit Unit Vertically
Verticall upward
y To Indoor To Outdoor
Unit Unit
To Indoor To Outdoor
To Indoor To Outdoor
Unit Unit
Unit Vertically Unit Vertically
upward upward
To Outdoor To Outdoor
To Indoor To Indoor
Unit Unit
Unit Vertically Unit Vertically
upward upward
Welding Welding
To Indoor To Outdoor
Unit Unit
Vertically
upward
160
DC INVERTER MULTI VRF INSTALLATION
WARNING: The length of connection pipe must be 1m≤L≤1. 5m. The electronic
expansion valve sub-assembly must be connected to the indoor and outdoor unit in a
direction as marked. If connected in reverse direction, severe error will be caused to the
unit.
(2) Pipe connection: Tighten the nuts with your hands correctly. Then, use another spanner to
hold the pipe joint on machine side and use torque wrench to tighten securely.
Hold the spanner
(4) Final treatment: The section where the pipe is connected must be wrapped for thermal
insulation.
WARNING!
Please ensure the pipe is fully covered by sponge and not exposed in air. Condensing
water will be generated on the pipe if the thermal insulation is poor.
161
DC INVERTER MULTI VRF INSTALLATION
2). Determine the direction and elevation of condensate pipe before installation. To ensure the
gradient smooth and straight, avoid intersecting with other pipelines. The height of the
clamp fixing the pipe hanger frame shall be adjustable and fixed from the outer of thermal
insulation.
3).Distance between hanger frames:
Outer diameter of water
pipe (mm) ф≤25 32>ф≥25 ф≥32
Spacing between
horizontal pipes (mm) 800 1000 1500
Spacing between
standpipes (mm) 1500 2000
Each standpipe shall have two hanger frames at least.
4). The gradient of condensate pipe shall be over 1% and the gradient of main pipe shall not
be less than 0.3%, while there shall be no overhanging slope.
Over 1/100
5). When connecting the 3-way section of condensate pipe, the 2-way straight section on 3-way
pipe shall be on the same gradient. The two ends of 2-way section shall not have different
gradient. See the schematics below:
错误的接法 正确的接法
Correct connection
Wrong connection
6). Confluence toward the horizontal pipe shall be best from the upper. Back flow is easy to
occur if from the lengthwise direction.
162
DC INVERTER MULTI VRF INSTALLATION
Indoor Unit
Mounting of horizontal pipe
7)Do not tie the condensate pipe and refrigerant pipe together.
8) To ensure smooth drainage of condensate, a vent hole shall be set at the highest point of
drainage hose .
9) Carry out water flow test and full water test after the pipe connection is completed. On one
hand, check if the drainage is smooth; on another hand, check the piping system for any
leakage.
10) Steel sheath shall be provided to the pipe crossing the wall or slab. The pipe joint shall not
be positioned within the sheath. The steel sheath shall be flush with the wall surface or slab
base, but 20mm higher than the slab base. The sheath shall not affect the pipe gradient.
The clearance between pipe and sheath shall be blocked by using flexible inflammable
materials. The sheath shall not be used as the supporting point of the pipe.
11) The joint of thermal insulation materials must be adhered by using special glue and then
wrapped with plastic tape having a width not less than 5cm to avoid condensing.
12). Ensure a gradient over 1% when connecting the drainage hose to the indoor unit.
13) When connecting the drainage hose to the indoor unit, please fix with the included pipe
clamp and do not use glue water, thus to ensure easy repair.
14) Installation requirements for auxiliary drainage hose
Pipe clamp
Drainage PVC pipe
163
DC INVERTER MULTI VRF INSTALLATION
Pipe
管盖cover
15) The long drainage hose may be fixed by using hanger bolts, thus to ensure a gradient
of 1/100 (PVC cannot be bent).
The spacing between the supports of horizontal pipe is 0.8-1.0m. Twisting will be caused and
thus air bag will be formed if the spacing is too high. Once the air bag is formed, the pump can
only compress the air bag no matter how forcible it pushes, but there is no flowing water, thus
resulting in abnormal water level. This will cause flooding of the ceiling.
16). If the air flow of indoor unit is high, this might cause negative pressure and result in return
suction of outdoor air. Therefore, U-type water trap shall be designed on the drainage
side of each indoor unit.
Indoor unit.
164
DC INVERTER MULTI VRF INSTALLATION
Joint
Joint
17) Connection of drainage branch pipe to the standpipe or horizontal pipe of drainage main
pipe
The horizontal pipe cannot be connected to the vertical pipe at a same height. It can be
connected in a manner as shown below:
N01:3-way connection of drainage hose joint
3-way connection of
drainage pipe joint
Connection of drain
elbow
Connection of
horizontal pipe
Drainage hose is requisite for air conditioner unit. During cooling, the moisture in the air will
condense on the surface of evaporator. Such condensing water must be drained out of the unit.
Meanwhile, the drainage hose has an important role to determine if the air conditioner can plays
its full functions.
165
DC INVERTER MULTI VRF INSTALLATION
18). All the condensate pipes must be installed at a distance over 500mm from the electric
box of the unit.
8.3 Installation of drainage hose for different types of indoor unit
1) Duct-type Indoor Unit (Including General Static Pressure and Low Static Pressure)
a. Installation of drainage hose
¾ The diameter of drainage hose shall be equal to or higher than the diameter of
connection pipe. (PVC pipe: Dimension: Outer diameter 25mm, 32mm)
¾ The drainage hose shall be short and has a down gradient of 1/100 at least, thus to
avoid air bag.
¾ To ensure that the drainage hose will not be bent and has enough gradient, a distance of
1 ~ 1.5m shall be kept between the hanger frames.
C. To prevent foreign articles from entering the pipe, please minimize the bend of pipeline, thus
to ensure cleanliness of the drainage elbow.
D. The drainage hose must be wrapped with thermal insulation tube, thus to avoid
condensing on the outer surface of drainage hose . See below for the thickness of thermal
insulation tube.
166
DC INVERTER MULTI VRF INSTALLATION
Thermal insulation of
condensate pipe
Pipe cover
Over 100mm
Fig. The specification of collecting drainage hose shall be suitable to the working capacity of
the unit
We may collect the drainage hose s of all the indoor units in one system (An outdoor unit
and all the indoor units connected to this outdoor unit are called one system), or collect the
drainage hose s of all the indoor units in several systems.
Notes: The ceiling height must be considered, and a specific gradient shall be ensured along
the water flow direction.
2)Cassette Type (Including 4-way and 1-way)
a. Installation of drainage hose
¾ The drainage hose shall be installed to ensure smooth flow of water.
¾ The diameter of drainage hose shall be equal to or higher than the diameter of connection
pipe (PVC pipe) (exclusive of the rise section).
¾ The drainage hose shall be short and has a down gradient of 1/100 at least, thus to avoid air
bag
¾ If the inclination of the drainage hose is insufficient, drainage rise pipe shall be mounted.
¾ The installing height of drainage rise pipe shall be less than 280mm.
¾ The drainage rise pipe shall be in right angle to the unit and the distance to the unit shall not
exceed 300mm.
167
DC INVERTER MULTI VRF INSTALLATION
Roof
Hanger seat
Within 300mm
Below 280mm
Drainage hose
(accessory)
Below 500mm
Drainage rise
pipe
¾ The inclination of included drainage hose shall be within 75mm, so that the drainage insert
will not bear excessive force.
Drainage hose
(accessory)
Below 500mm
Below 75mm
¾ To prevent the drainage hose from dropping downward, hanger rods shall be erected every
1.0~1.5m.
Correct Incorrect
¾ Use the included drainage hose and clamp. Insert the drainage hose to the drainage port and
tighten the clamp.
¾ For thermal insulation, wrap the big sponge to the drainage hose clamp.
¾ The indoor drainage hose shall be thermally insulated.
Big sponge (accessory)
¾ To connect the drainage hoses for multiple machines, please use the method of multi-pipe
collection, as shown below.
168
DC INVERTER MULTI VRF INSTALLATION
Fig. The specification of collecting drainage hose shall be suitable to the working capacity of the
unit
We may collect the drainage hoses of all the indoor units in one system (An outdoor unit and
all the indoor units connected to this outdoor unit are called one system), or collect the drainage
hoses of all the indoor units in several systems.
The ceiling height must be considered, and a specific gradient shall be ensured along the
water flow direction. The cassette-type indoor unit is provided with water pump, and the maximum
lift of its drainage hose is 280mm.
¾ During installation, please take care that:
The diameter of drainage hose connected to the indoor unit must meet the specifications. The
pipe diameter shall not be too small; otherwise the water may overflow.
The main drainage hose depends on the number of indoor units. Generally, it is required to be
equal to or higher than ф35mm.
The drainage hose shall be thermally insulated. The thickness of thermal insulation pipe must
meet the requirements. The clearance between thermal insulation pipes shall be sealed with
adhesive sticker.
Please discharge the water to the ground drain, water closet or any other place easy to drain the
water out.
b) After installation, check if the drainage is smooth.
3) Wall-mounted Type
Assemble the drainage hose as shown below and take measures to prevent condensing.
Improper assembly of the drainage hose may cause leakage, or even expose the furniture to
moisture.
a) Assembly of drainage hose
¾ To avoid air in water elbow, the drainage hose shall be kept as short as possible and inclined
downward, as shown below.
¾ During connection, please use PVC pipe of equal size higher than this size (Nominal Dia,:
20mm; Outer Dia.: 26mm)
¾ The drainage hose must be arranged in down inclination along water flow direction, thus to
avoid air bubble blocking. Take care not to arrange the pipe in twisting, protrusion or
waveform. Do not put the outlet of drainage hose into water.
Protrusion
Twisting
169
DC INVERTER MULTI VRF INSTALLATION
¾ The extended section of drainage hose shall be wrapped with thermal insulation sheath when
passing the room.
Thermal insulation of
condensate pipe
Pipe cover
Fig.3.41
¾ After installation of the drainage hose, be sure to make water test and check if the water can
be drained smoothly.
Drainage hose
Drainage hose
171
DC INVERTER MULTI VRF INSTALLATION
9 ELECTRICAL INSTALLATION
9.1 Precautions for Electrical Installation
☆ Carry out installation according to national cabling rules.
☆ Rated supply voltage and special circuit for air conditioner must be used.
☆ Do not pull the power cables with force.
☆ All the electric installations must be carried out by specialist technicians in accordance with the
local laws, rules and these instructions.
☆ The diameter of power cords must be large enough. The damaged power cords and connection
wires must be replaced with special cords.
The earthing shall be secure. The earthing wire shall be connected to the special earthing device
on the construction. The installation must be done by specialist technicians. The air switch shall
have both the magnetic tripping and thermal tripping functions to ensure protection against the
short circuit and overload.
●Earthing Requirements
☆ The air conditioner belongs to Category I Electric Appliance. Therefore, be sure to take reliable
earthing measures.
☆The yellow-green wire inside the air conditioner is used for earthing. Do not use it for other
purposes or cut it. Do not fix with tapping screw. Otherwise, it will cause the risk of electric shock.
☆The earthing resistance shall comply with the national standard GB17790
☆Reliable earthing terminal must be provided on the user’s power supply. Never connect the
earthing wire to the following places:
①Water pipe; ②Gas pipe; ③Sewage pipe;
④Other places that the specialist technicians think unreliable.
Connection Schematics for Indoor / Outdoor Power Cords and Communication Line (3-phase)
172
DC INVERTER MULTI VRF INSTALLATION
Connection Schematics for Indoor / Outdoor Power Cords and Communication Line
9.4 Dial-up
Gree DC Multi VRF unit is provided with three dial-up, i.e. function dial-up, address dial-up and
capacity dial-up. ou may adjust the function dial-up to set the control, mode and functions of the
unit; adjust the address dial-up to set the matching relation between indoor unit and wired
controller; and adjust the capacity dial-up to set the capacity demands of the indoor unit.
9.4.1 Function Dial-up
CAUTIONS! The S7 function dial-up is located on the mainboard of indoor unit. It can be
operated only when the client needs to change the default function settings; otherwise the default
position shall be maintained.
Functional dial switch S7
DIP Dial-up Setting
Functional Description:
swicth 0 (ON Position) 1
Setting of memory
1(S/R) Standby (S) Restore (R)
mode
Wired control Remote
2(L/I) Setting of control mode
(L) control (I)
Setting of master / slave Master indoor Slave indoor
3(M/S)
indoor unit unit (M) unit (S)
Setting of ambient
Return air inlet
4(I/O) temperature acquisition Receiver (O)
(I)
point
Setting of high / low Low static
5(L/H) High static(H)
static pressure fan pressure (L)
Functional description of function dial-up:
DIP swicth 1 (S/R): Setting of memory mode, including the standby mode and restoration mode.
The standby mode refers to that the previous parameters will be kept but the
unit will not run automatically after the power supply is resumed. This setting is
factory defaulted (DIP swicth pulled to “ON” position). For example, if the
parameters of an indoor unit set before power shutdown are High Fan and 24℃,
the unit will be under standby state after the power supply is resumed and after
the unit is manually started, the parameters will remain as High Fan and 24℃.
The restoration mode refers to that not only the previous parameters will be kept,
but also that the unit can start automatically after the power supply is resumed.
But if the unit is under STOP state before power shutdown, it will be also under
STOP state after the power supply is resumed.
DIP swicth 2 (L/I): Setting of control mode, including wired control and remote control. The wired
control mode refers to that the indoor unit is controlled from wired controller
(wired controller). This setting is factory defaulted (DIP swicth pulled to “ON”
position). When the setting is wired control mode, the function dial-up on S7 for
“setting of memory mode” and “setting of master / slave indoor unit” will be
disabled. These two settings can be done from the wired controller directly. The
remote control mode refers to that the indoor unit is controlled from remote
controller. When the setting is remote control mode, its function dial-up must be
set on S7.
DIP swicth 3 (M/S): The setting of master / slave indoor unit refers to the master / slave setting of
indoor run mode, mainly used to meet the needs of special people on priority
(e.g. leader, patients, etc). The factory default setting is that all indoor units are
master (DIP swicth pulled to “ON” position).
When all the indoor units are set as slave, the outdoor unit will run according to
173
DC INVERTER MULTI VRF INSTALLATION
the mode of slave indoor unit that is firstly started. If the mode of slave indoor
unit started later has in conflict against the mode started earlier, the system will
display mode conflict error, so that the indoor unit started later cannot work. In
this case, the run mode of the unit is decided by the slave indoor unit that is
firstly started.
When only one indoor unit is set as master, no matter if the master indoor unit is
firstly started or not, the slave indoor unit will give out mode conflict error as long
as its mode is in conflict against the mode of master indoor unit (except that the
master indoor unit is stopped). In this case, the unit run according to the mode
of master indoor unit on priority.
When several indoor units are set as master, the mode of master indoor unit
with a lower address code will be taken as the master run mode of the unit.
when the master indoor unit with the lowest address code is changed from
STOP state to RUN state, the mode of other master indoor units or slave indoor
units shall be kept identical to its mode; otherwise the system will give out mode
conflict error. Therefore, when there are several master indoor units, the
address code of the unit shall be set from lower to higher according to priority
level.
DIP swicth 4 (I/O): Setting of ambient temperature acquisition point. This setting is mainly used
when the temperature of air conditioner area differs largely from the return air
inlet temperature of the unit. Meanwhile, this setting is only valid when the
receiver is connected, including the setting of temperature acquisition point at
return air inlet and setting of the temperature acquisition point at receiver head.
The factory default setting is acquisition of return air inlet temperature (DIP
swicth pulled to “ON” position).
DIP swicth 5 (L/H): Setting of high / low static pressure fan. This setting includes the setting of high
static pressure fan and low static pressure fan, adjusted as needed for the
project. The factory default setting is low static pressure fan (DIP swicth pulled
to “ON” position).
Cautions:
1)The above settings must be done under power shutdown state.
2)The DIP swicth of function code is classified into 3-bit code, 4-bit code and 5-bit code. The 4-bit
code or 5-bit code is used for duct-type unit only (including multi duct-type unit and 1-to-1
duct-type unit).
3)When the “setting of control mode” is “L”, the function dial-up for “setting of memory mode" and
“setting of master / slave indoor unit” will be disabled. When the “setting of control mode” is “I”, this
function dial-up setting is enabled.
4)The DIP swicth shall be put to position correctly, and shall not be put to middle position. Dialing
of the switch to “ON” position indicates “0” and the dialing to opposite direction indicates “1”.
5)After dialing up, please mark the address code of the unit(√)
Address code S1
Functional dial
switch S7
174
DC INVERTER MULTI VRF INSTALLATION
Capacity code S2
175
DC INVERTER MULTI VRF INSTALLATION
controller)
☆Below is factory default setting:
The default setting of address dial-up code is 0000 and the address is 1 (See above for the
position of dial lever).
☆Dial-up Value
The dial-up value of address code is set in binary system. The dial-up value is “0” when the
lever is dialed to “ON” end; the dial-up is “1” when the lever is dialed to numerical end on opposite
side. For number 4~1 on the address code, the dial-up #4 refers to high bit and the dial-up 1#
refers to low bit.
The default Capacity dial-up is the maximum capacity of indoor unit. As shown above, the capacity
is (See above for the lever position)
☆Dial-up Value
The dial-up value of capacity code is set in binary system. The dial-up value is “0” when the lever
is dialed to “ON” end; the dial-up is “1” when the lever is dialed to numerical end on opposite side.
For number 4~1 on the capacity code, the dial-up #4 refers to high bit and the dial-up 1# refers to
low bit.
177
DC INVERTER MULTI VRF MAINTENANCE
MAINTENANCE
178
DC INVERTER MULTI VRF MAINTENANCE
MAINTENANCE
1 List of Unit Errors
1.1 List of Error Display on Wired Controller
Error Error Source of
Notes on Control
Code Description Error Signal
The high pressure protection value is 4.2MPa. When it is detected
Compressor
High-pressure three times successively that a compressor is under high
E1 high-pressure
Switch pressure, this compressor will be stopped. In this case, error code
protection
E1 will be displayed and the run indicator will blink.
When it is detected for 10 minutes successively that Tevap. is ≤-2℃
Indoor (varying with indoor unit), the antifreeze protection will be
Evaporator
E2 antifreeze activated, in which case the outdoor unit will immediately shut off
sensor
protection the indoor electronic expansion valve and the capacity will be set
to “0”.
Compressor When the low pressure reaches the protection value (absolute
Low-pressure
E3 low-pressure pressure: 0.15MPa), the low pressure switch will be cut off, in
Switch
protection which case the low pressure protection will be displayed.
When the exhaust temperature (Texhau.) is equal to and higher
than 113 ℃ , the compressor will be stopped. Upon the first
occurrence of exhaust protection, the error code E4 will be
Compressor
Exhaust displayed. When the exhaust temperature is lower than TR℃, the
exhaust
E4 temperature compressor will resume to operation after it has been stopped for
temperature
sensor 3 minutes. The compressor can resume to operation for the first
protection
two times. But if this occurs three times successively in 1 hour, the
unit must be disconnected from power supply before it can
restarted.
Frequency
The drive board of variable frequency compressor is incurred to
converter Compressor
E5 error. For details on the error message, please refer to the Display
overcurrent drive
Code on Digital Tube of Outdoor Unit.
protection
The mainboard of indoor unit or the wired control is incurred to
Communication
E6 Communication communication error with outdoor unit. The indoor unit incurred to
error
communication error will be stopped and display the error code.
The run mode of the unit that is started later is inconsistent to the
mode that is started earlier. Only the cooling and dry mode has
possible mode conflict against the heat mode. For fan mode,
E7 Mode conflict User operation
there is no mode conflict against the cooling, dry or heat mode. In
case mode conflict occurs, the indoor unit with mode conflict will
display E7 and be stopped.
When water full is detected for 8 seconds successively, the
system will enter into water-full protection state, in which case the
wired controller will display E9 and give out alarm. In case of
Water-full
E9 Water pump water-full protection under each mode, the other loads of the
protection
indoor unit will be stopped, except that the water pump will remain
working and give out alarm. In this case, the outdoor unit shall
adjust the capacity output accordingly
Indoor ambient
Indoor room The indoor unit incurred to sensor error will display error code and
F0 temperature
sensor be stopped.
sensor error
Indoor coil inlet Indoor coil-inlet
The indoor unit incurred to sensor error will display error code and
F1 temperature temperature
be stopped.
sensor error sensor
Indoor coil Indoor
middle coil-middle The indoor unit incurred to sensor error will display error code and
F2
temperature temperature be stopped.
sensor error sensor
Outdoor coil
Indoor coil-exit
inlet The indoor unit incurred to sensor error will display error code and
F3 temperature
temperature be stopped.
sensor
sensor error
DC INVERTER MULTI VRF MAINTENANCE
180
DC INVERTER MULTI VRF MAINTENANCE
181
DC INVERTER MULTI VRF MAINTENANCE
: : : : : : :
: : : : : : :
High-pressure protection
Yes No
Yes
Yes
Yes
No
Check if the air inlet and outlet
of the indoor and outdoor Remove the obstructions
exchanger is smooth?
Yes
Yes
Yes
Yes
Yes
No
Focus on checking the inlet and outlet of the connection between indoor units and main
The system pipe is blocked pipe. Also focus on checking the electronic expansion valve of indoor unit and outdoor
unit. Replace the electronic expansion valve, drying filter and other parts
183
DC INVERTER MULTI VRF MAINTENANCE
Yes
No
Yes
Yes
Yes
No
Check if the air inlet and outlet
of the indoor and outdoor Remove the obstructions
exchanger is smooth?
Yes
Yes
Check if the indoor and Measure the fan motor and
outdoor fans run normally? signal input
No
No
Check if the indoor swing Measure the swing motor
louver is fully open? and signal input
Yes
No
Check if the capacity output of
outdoor unit is equal to the Refer to the dial-up of indoor and outdoor unit
capacity demand of indoor
units?
Yes
Yes
Yes
Check if the indoor / outdoor
filters or radiating fins are Refer to the Repair and Maintenance
dirty or blocked?
No
Focus on checking the inlet and outlet of the connection between indoor units and main
The system pipe is blocked pipe. Also focus on checking the electronic expansion valve of indoor unit and outdoor
unit. Replace the electronic expansion valve, drying filter and other parts
DC INVERTER MULTI VRF MAINTENANCE
No Measure if the
Measure if the exhaust resistance of No
temperature of compressor temperature sensor
reaches 118℃? is correct?
Yes
Yes
Yes
Yes
Change the outdoor unit Change corresponding electronic
mainboard expansion valve sub-assy
When the exhaust No
temperature of compressor is Change the mainboard chip of the outdoor units
higher than 110℃, Whether
compressor reduces its
capacity?
Yes
No
Check if the capacity
output of outdoor unit is Refer to the dial-up of indoor and outdoor unit
equal to the capacity
demand of indoor units?
Yes Notes:
(1) The AC frequency conversion machine includes air-out senor
Repair the leakage of system pipe and and shell top sensor.
add refrigerant according to the required
volume (2) The temperature protection point in different machines are
different.
(3) There is no liquid refrigerant by-pass in frequency conversion
machine.
185
DC INVERTER MULTI VRF MAINTENANCE
Yes
No
If the current value is
higher than the preset
Replace the overcurrent protector
value of protector
Yes
Yes
No
If the voltage is Contact the power supply company
normal
Yes
Upon AC inverter startup overcurrent, the indicator will display the current protection.
Current protection
If the voltage is No
normal Adjust the power parameters
Yes
Remove the
compressor cables
and restart
If overcurrent No
protection Replace the compressor
Yes
Module damaged. Replace Note: For DC VRF unit, it is not allowed to test
the module with compressor cable removed.
186
DC INVERTER MULTI VRF MAINTENANCE
Overcurrent occurs in operation, i.e. the indicator will display the current protection just after startup.
Check the indoor units for
matching
Within 135%
Correct the match of indoor units to
allowable capacity
187
DC INVERTER MULTI VRF MAINTENANCE
通讯故障error
Communication
检查 否
No
Check if the 确认插头与插口的
Check the orientation of plug and socket
室内机通讯线连接是否
communication line of
indoor unit is connected 方位
正确?
是
Yes
测量 否
No
Measure if the
通讯线是否为
communication line is 更换通讯线
Replace the communication line
through?
通路?
是
Yes
检查室内 否
No
Check if the communication 确认插头与插口的
外机连接的通讯线连接
line of indoor and outdoor
Check the orientation of plug and socket
unit is是否正确?
connected correctly? 方位
Yes
是
检查通讯 否
No
Check if the two ends of 请缠绕上随机配套
线两端是否分别套有
communication line are Please mount the included magnetic ring
mounted with magnetic ring? 的磁环
磁环?
是
Yes
查看所 否
No
Check if the outdoor unit 请给室外机接通电
Please supply power to the outdoor unit
连室外机是否已
is electrically powered?
源
供电?
Yes
是
同系统 否
No
If the address codes of 修改相关重复的地
Change the repeated address codes
中的室内机地址码是否
indoor units in the same
system are repeated? 址码
有重复?
Yes
是
线控器地址 否
No
If the address code of wired
码和所连的室内机地址
controller complies with the 修改线控器地址码
Change the address code of wired controller
address code of the connected
码是否相符?
indoor unit?
188
DC INVERTER MULTI VRF MAINTENANCE
a) Water-full protection
故障显示
Fault display
检查是否有水溢
Check if the water 否
No 液位开关端子的
If the voltage of liquid 否
No
overflows? level switch terminal Replace the mainboard of indoor unit
更换室内机主板
出? 电压是否正确?is correct?
是
Yes 是
Yes
Check检查液位开关
the liquid level switch
是
Yes 是
Yes
Check 检查排水泵配线
the wiring of drainage pump
排水管是否疏通?
If the drainage pipe is No
否
unblocked and if the 调整排水管
Adjust the drainage pipe
流水是否顺畅?
water flow is smooth?
Yes
是
Check检查排水泵
the drainage pump
2.7 Error with room sensor, tube-inlet, tube middle and tube-exit sensor; error with room sensor, tube-inlet, tube
middle and tube-exit sensor and exhaust / casing top sensor; error with the compressor bottom sensor
Yes
Yes
Yes
是
If 机组内接线板L、N是否
the voltage of L & N on 否
No Check the power supply of
terminal board inside the unit 检查接线板电源是否故障
terminal board for any fault
为220V
is 220V
Yes
是
No
否
检查机组内空气开关
Check if the air switch in Put the air switch to ON
the unit is ON 将空气开关打为ON
是否打开 position
Yes
是
否
No
The air switch is damaged or
If the input of filter board 空气开关损坏或松脱
滤波板输入是否有电 loosened
is energized
Yes
是
No
否
If the output of filter Replace the filter board
滤波板输出是否有电
board is energized 更换滤波板
Yes
是
191
DC INVERTER MULTI VRF MAINTENANCE
3 WIRING DIADRAM
3.1 Outdoor unit
GMV(L)-Pd100W/NaB-K,GMV(L)-Pd120W/NaB-K,GMV(L)-Pd140W/NaB-K
GMV(L)-Pd160W/NaB-K
192
DC INVERTER MULTI VRF MAINTENANCE
193
DC INVERTER MULTI VRF MAINTENANCE
GMV-R56P/Na-K,GMV-R71P/Na-K,GMV-R80P/Na-K,GMVL-R56P/Na-K,GMVL-R71P/Na-K,GMVL-R80P/Na-K
GMV-R90P/Na-K,GMV-R112P/Na-K,GMV-R140P/Na-K,GMVL-R90P/Na-K,GMVL-R112P/Na-K,GMVL-R140P/Na-K
194
DC INVERTER MULTI VRF MAINTENANCE
GMV-R125P/Na-K,GMVL-R125P/Na-K
GMV-R22P/NaB-K、GMV-R28P/NaB-K、GMV-R36P/NaB-K、GMV-R45P/NaB-K、GMV-R56P/NaB-K、
GMV-R71P/NaB-K
195
DC INVERTER MULTI VRF MAINTENANCE
GMV-R90P/NaB-K、GMV-R112P/NaB-K、GMV-R140P/NaB-K
C1 C2
GMV-R22PS/NaB-K、GMV-R28PS/NaB-K、GMV-R36PS/NaB-K
196
DC INVERTER MULTI VRF MAINTENANCE
GMV-R45PS/NaB-K、GMV-R56PS/NaB-K、GMV-R71PS/NaB-K
GMV-R90PS/NaB-K、GMV-R112PS/NaB-K、GMV-R140PS/NaB-K
C1 C2
197
DC INVERTER MULTI VRF MAINTENANCE
GMV-R22T/NaA-K、GMV-R28T/NaA-K、GMV-R36T/NaA-K、GMV-R45T/NaA-K
GMV-R28T/Na-K,GMV-R36T/Na-K,GMV-R45T/Na-K,GMV-R50T/Na-K,GMV-R56T/Na-K,GMV-R71T/Na-K,GMV-R8
0T/Na-K,GMV-R90T/Na-K,GMV-R112T/Na-K,GMV-R125T/Na-K,GMV-R140T/Na-K,GMVL-R28T/Na-K,GMVL-R36T/
Na-K,GMVL-R45T/Na-K,GMVL-R50T/Na-K,GMVL-R56T/Na-K,GMVL-R71T/Na-K,GMVL-R80T/Na-K,GMVL-R90T/
Na-K,GMVL-R112T/Na-K,GMVL-R125T/Na-K,GMVL-R140T/Na-K
Swing Motor
Limit Switch
Water Level Switch
Environment
1 Temp.sensor
Out
2
Temp.sensor
3 Mid
Temp.sensor
Manual Panel In
4
Temp.sensor
GMV-R22G/NaB-K,GMVL-R22G/NaB-K,GMV-R28G/NaB-K,GMVL-R28G/NaB-K,GMV-R36G/NaB-K,GMVL-R36G/N
aB-K,GMV-R45G/NaB-K,GMVL-R45G/NaB-K
198
DC INVERTER MULTI VRF MAINTENANCE
GMV-R50G/NaB-K,GMV-R56G/NaB-K,GMVL-R50G/NaB-K,GMVL-R56G/NaB-K
GMV-R22G/NaC-K,GMV-R28G/NaC-K ,GMV-R36G/NaC-K,GMV-R45G/NaC-K,GMVL-R22G/NaC-K,GMVL-R28G/Na
C-K ,GMVL-R36G/NaC-K,GMVL-R45G/NaC-K
199
DC INVERTER MULTI VRF MAINTENANCE
GMV-R71G/Na-K,GMV-R80G/Na-K,GMVL-R71G/Na-K,GMVL-R80G/Na-K
200
DC INVERTER MULTI VRF MAINTENANCE
GMV-R28Zd/Na-K,GMV-R36Zd/Na-K,GMV-R50Zd/Na-K,GMV-R71Zd/Na-K,GMV-R90Zd/Na-K,GMV-R112Zd/Na-K,G
MV-R125Zd/Na-K,GMVL-R28Zd/Na-K,GMVL-R36Zd/Na-K,GMVL-R50Zd/Na-K,GMVL-R71Zd/Na-K,GMVL-R90Zd/N
a-K,GMVL-R112Zd/Na-K,GMVL-R125Zd/Na-K
GMV-R22Td/Na-K,GMV-R28Td/Na-K,GMV-R36Td/Na-K
DC INVERTER MULTI VRF MAINTENANCE
Use spanner to
remove the bolts fixing
the compressor.
Remove the
compressor
DC INVERTER MULTI VRF MAINTENANCE
Use spanner to
remove the
bolts fixing the
compressor.
Use spanner to
remove the bolts fixing
the compressor.
203
DC INVERTER MULTI VRF MAINTENANCE
206
DC INVERTER MULTI VRF MAINTENANCE
207
DC INVERTER MULTI VRF MAINTENANCE
208
DC INVERTER MULTI VRF MAINTENANCE
fan
209
DC INVERTER MULTI VRF MAINTENANCE
8. Mount the fan and tighten ● Mount the fan and use
the fixing bolts spanner to tighten the bolts
fixing the fan.
210
DC INVERTER MULTI VRF MAINTENANCE
3. Pull out the water outlet ●Pull out the water outlet
pipe and loosen the screws pipe and use screwdriver
fixing the water pump. 1.Loosen the water outlet pipe to loosen the screws
2.Loosen the screws fixing the water pump
fixing the water pump
212
DC INVERTER MULTI VRF MAINTENANCE
213
DC INVERTER MULTI VRF MAINTENANCE
214
DC INVERTER MULTI VRF MAINTENANCE
215
DC INVERTER MULTI VRF MAINTENANCE
216
DC INVERTER MULTI VRF MAINTENANCE
217
DC INVERTER MULTI VRF MAINTENANCE
218
DC INVERTER MULTI VRF MAINTENANCE
z Duct-Type Unit
Removal and Assembly of Fan Motor
Remarks: Before removing the fan, make sure to cut off the power firstly.
Step Illustration Handling Instruction
1. Unplug the motor ●Cut off the power
cables supply of indoor unit.
Use screwdriver to
remove the electric box
cover and unplug the
motor cables in electric
box.
219
DC INVERTER MULTI VRF MAINTENANCE
220
DC INVERTER MULTI VRF MAINTENANCE
222
DC INVERTER MULTI VRF MAINTENANCE
224
DC INVERTER MULTI VRF MAINTENANCE
z Wall-mounted Unit
Removal and Wall-mounted Unit Assembly of Fan Motor
Remarks: Before removing the compressor, make sure that there is no refrigerant inside the pipe system and
that the power has been cut off.
Step Illustration Handling Instruction
1. Firstly, ●Firstly, use
remove screwdriver to loosen
the front the screws.
panel, ●Unplug the motor
front case terminals in the electric
and box. Loosen the earth
electric screws and lift up.
box
Screw
DC INVERTER MULTI VRF MAINTENANCE
E5 displayed on
hand controller
No If it is moistened,
dirty or short
circuited?
Yes
Yes Yes
1. If it is moistened, find out the cause and Check if the PFC in Yes
take proper measures to prevent moisture. Dry the mainboard is
the PFV board and apply moisture-proof glue. damaged
2. If it is dirty, find out the cause and take
dustproof measures. If the air quality of
service environment is poor, it is also required No
to clear off the dirt periodically.
3. If it is short circuit, find out the cause and
clean the electric box to prevent the iron
scraps or other conductive substances from Replace the mainboard
attaching on the board.
E5 displayed on
hand controller
If it is moistened,
No dirty or short
circuited?
Yes
If it is moistened, dirty
or short circuited?
Check if +15V in No
the mainboard is
stable, as well as
1,2 role of 15VA
Yes
2.11 Tripping
Tripping
Check if it is
Yes
leakage and
the switch
changed,
No
If the switching
capacity can No
meet the
requirements?
Yes
No
Tripped once
energized
Yes
Record and
feed back
DC INVERTER MULTI VRF MAINTENANCE
E5 displayed on
hand controller
Radiator
overheat Display Hc
protection
Yes
No
Yes
Yes
E5 displayed
on hand
controller
Overvoltage
protection of Display Hc
DC voltage
Yes
Yes
No
No
Yes
3 Power Distribution
3.1 Principle of Power Distribution
231
DC INVERTER MULTI VRF MAINTENANCE
232
DC INVERTER MULTI VRF MAINTENANCE
233
DC INVERTER MULTI VRF MAINTENANCE
15704113⑩
43 Capacitor BOX 01424173 1
44 Panel Grille 22414102 2
45 4-wayValveSub-Assy 04144169 1
46 4-Way Valve 43000338 1
47 4-way Valve Fittings 4300040029 1
48 Gas-liquid Separator 07228767 1
49 Support 01804201 1
50 Wiring 40110142 1
51 Connection Wire 4003014301 1
52 Magnet Coil for Electronic Expansion Valve 4300010822 1
Note:
1. Condenser Assy ① is only applicable toGMV(L)-Pd100W/NaB-K,GMV(L)-Pd120W/NaB-K
2. Condenser Assy ② is only applicable to GMV(L)-Pd140W/NaB-K,GMV(L)-Pd160W/NaB-K
3. Electric Box Assy ③ is only applicable to GMV(L)-Pd100W/NaB-K
4. Electric Box Assy ④ is only applicable to GMV(L)-Pd120W/NaB-K
5. Electric Box Assy ④ is only applicable to GMV(L)-Pd140W/NaB-K
6. Electric Box Assy ④ is only applicable to GMV(L)-Pd160W/NaB-K
7. Cut-off Valve ⑦ is only applicable to GMV(L)-Pd100W/NaB-K,GMV(L)-Pd120W/NaB-K, GMV(L)-Pd140W/NaB-K
8. Cut-off Valve is ⑧ is only applicable to GMV(L)-Pd160W/NaB-K
9. Fan Motor is only applicable to GMV(L)-Pd100W/NaB-K,GMV(L)-Pd120W/NaB-K,GMV(L)-Pd140W/NaB-K
10. Fan Motor is only applicable to GMV(L)-Pd160W/NaB-K
234
DC INVERTER MULTI VRF MAINTENANCE
235
DC INVERTER MULTI VRF MAINTENANCE
GMV-R28T/Na-K,GMV-R36T/Na-K GMVL-R28T/Na-K,GMVL-R36T/Na-K
No. Part Name
Code Qty. Code Qty.
1 Tube Exit Plate 01382710 1 01382710 1
2 Body Fixed Plate 01332701 4 01332701 4
3 Front Side Plate 01302717 1 01302717 1
4 Left Side Plate 01302740 1 01302740 1
5 Base Plate 01222702 1 01222702 1
6 Rear Side Plate 01302719 1 01302719 1
7 Bottom Foam 52012716 1 52012716 1
8 Motor Gasket 76712711 3 76712711 3
9 Bolt 70212701 3 70212701 3
10 Motor Fixer 01702701 1 01702701 1
11 Fan Motor 15704901 1 15704901 1
12 Centrifugal Fan 10312721 1 10312721 1
13 Evaporator Connection 01072004 1 01072004 1
14 Cable-cross Loop 76513101 2 76513101 2
15 shunt 072287842 1 072287842 1
16 Water Tray 12412701 1 12412701 1
17 Screw 70140032 4 70140032 4
18 Electric Box Base Plate 01412721 1 01412721 1
19 Flow Guide Loop 10372701 1 10372701 1
20 Electric Box 20102701 1 20102701 1
21 Wire Clamp 71010102 4 71010102 4
22 Terminal Board T360B 42011222 1 42011222 1
23 Transformer 43110233 1 43110233 1
24 Electric Box Cover I 20102702 1 20102702 1
25 Electric Box Cover II 20102703 1 20102703 1
26 Main Board 30226316 1 30226316 1
27 Capacitor 33010010 1 33010010 1
28 Rubber plug 76712701 1 76712701 1
29 Evaporator 01038778 1 01038778 1
30 Evaporator Support 01072003 2 01072003 2
31 Nut with Washer M6 70310012 1 70310012 1
32 Bolt subassembly 70210051 1 70210051 1
33 Pipe Pump PJV-1415 43130324 1 43130324 1
34 Pump Gasket 76712702 3 76712702 3
35 Pump Support 01332001 1 01332001 1
36 Water Level Switch 45010201 1 45010201 1
37 Drainage hose Pump 05232721 1 05232721 1
38 Right Side Plate 01302710 1 01302710 1
39 Cable-cross Loop 76512702 1 76512702 1
40 Pump Cover 01252710 1 01252710 1
41 Bolt 70212701 3 70212701 3
Electronic Expansive 0713411201/07334 0713411201/0733428
42 1 1
Valve 281 1
236
DC INVERTER MULTI VRF MAINTENANCE
GMV-R45T/Na-K,GMV-R50T/Na-K GMVL-R45T/Na-K,GMVL-R50T/Na-K
No. Part Name
Code Qty. Code Qty.
1 Tube Exit Plate 01382710 1 01382710 1
2 Body Fixed Plate 01332701 4 01332701 4
3 Front Side Plate 01302717 1 01302717 1
4 Left Side Plate 01302740 1 01302740 1
5 Base Plate 01222702 1 01222702 1
6 Rear Side Plate 01302719 1 01302719 1
7 Bottom Foam 52012716 1 52012716 1
8 Motor Gasket 76712711 3 76712711 3
9 Bolt 70212701 3 70212701 3
10 Motor Fixer 01702701 1 01702701 1
11 Fan Motor 15704901 1 15704901 1
12 Centrifugal Fan 10312721 1 10312721 1
13 Evaporator Connection 01072004 1 01072004 1
14 Cable-cross Loop 76513101 2 76513101 2
15 shunt 07228807 1 07228807 1
16 Water Tray 12412701 1 12412701 1
17 Screw 70140032 4 70140032 4
18 Electric Box Base Plate 01412721 1 01412721 1
19 Flow Guide Loop 10372701 1 10372701 1
20 Electric Box 20102701 1 20102701 1
21 Wire Clamp 71010102 4 71010102 4
22 Terminal Board T360B 42011222 1 42011222 1
23 Transformer 43110233 1 43110233 1
24 Electric Box Cover I 20102702 1 20102702 1
25 Electric Box Cover II 20102703 1 20102703 1
26 Main Board 30226316 1 30226316 1
27 Capacitor 33010010 1 33010010 1
28 Rubber plug 76712701 1 76712701 1
29 Evaporator 01038778 1 01038778 1
30 Evaporator Support 01072003 2 01072003 2
31 Nut with Washer M6 70310012 1 70310012 1
32 Bolt subassembly 70210051 1 70210051 1
33 Pipe Pump PJV-1415 43130324 1 43130324 1
34 Pump Gasket 76712702 3 76712702 3
35 Pump Support 01332001 1 01332001 1
36 Water Level Switch 45010201 1 45010201 1
37 Drainage hose Pump 05232721 1 05232721 1
38 Right Side Plate 01302710 1 01302710 1
39 Cable-cross Loop 76512702 1 76512702 1
40 Pump Cover 01252710 1 01252710 1
41 Bolt 70212701 3 70212701 3
Electronic Expansive 0713411201/07334 0713411201/07334
42 1 1
Valve 281 281
237
DC INVERTER MULTI VRF MAINTENANCE
GMV-R56/63/71/80T/Na-K GMVL-R56/63/71/80T/Na-K
No. Part Name
Code Qty. Code Qty.
1 Tube Exit Plate 01382711 1 01382711 1
2 Body Fixed Plate 01332701 4 01332701 4
3 Front Side Plate 01302718 1 01302718 1
4 Left Side Plate 01302715 1 01302715 1
5 Base Plate 01222702 1 01222702 1
6 Rear Side Plate 01302714 1 01302714 1
7 Bottom Foam 52012711 1 52012711 1
8 Motor Gasket 76712711 3 76712711 3
9 Bolt 70212701 3 70212701 3
10 Motor Fixer 01702701 1 01702701 1
11 Fan Motor 15704102 1 15704102 1
12 Centrifugal Fan 10312705 1 10312705 1
13 Evaporator Connection 01072710 1 01072710 1
14 Cable-cross Loop 76513101 2 76513101 2
15 shunt 07228806 1 07228806 1
16 Water Tray 12412701 1 12412701 1
17 Screw 70140032 4 70140032 4
18 Electric Box Base Plate 01412721 01412721
1 1
19 Flow Guide Loop 10372701 1 10372701 1
20 Electric Box 20102701 1 20102701 1
21 Wire Clamp 71010102 4 71010102 4
22 Terminal Board T360B 42011222 1 42011222 1
23 Transformer 43110233 1 43110233 1
24 Electric Box Cover I 20102702 1 20102702 1
25 Electric Box Cover II 20102703 1 20102703 1
26 Main Board 30226316 1 30226316 1
27 Capacitor 33010010 1 33010010 1
28 Rubber plug 76712701 1 76712701 1
29 Evaporator 01004641 1 01004641 1
30 Evaporator Support 01072715 2 01072715 2
31 Nut with Washer M6 70310012 1 70310012 1
32 Bolt subassembly 70210051 1 70210051 1
33 Pipe Pump PJV-1415 43130324 1 43130324 1
34 Pump Gasket 76712702 3 76712702 3
35 Pump Support 01332001 1 01332001 1
36 Water Level Switch 45010201 1 45010201 1
37 Drainage hose Pump 05232721 1 05232721 1
38 Right Side Plate 01302716 1 01302716 1
39 Cable-cross Loop 76512702 1 76512702 1
40 Pump Cover 01252711 1 01252711 1
41 Bolt 70212701 3 70212701 3
42 Electronic Expansive Valve 0713411401 1 0713411401 1
238
DC INVERTER MULTI VRF MAINTENANCE
(2) GMV(L)-R90T/Na-K,GMV(L)-R112T/Na-K,GMV(L)-R125T/Na-K
239
DC INVERTER MULTI VRF MAINTENANCE
GMV-R90/112/125/Na-K GMVL-R90/112/125/Na-K
No. Part Name
Code Qty. Code Qty.
1 Tube Exit Plate 01382711 1 01382711 1
2 Body Fixed Plate 01332701 4 01332701 4
3 Front Side Plate 01302713 1 01302713 1
4 Left Side Plate `01302711 1 `01302711 1
5 Base Plate 01222702 1 01222702 1
6 Rear Side Plate 01302709 1 01302709 1
7 Bottom Foam 52012717 1 52012717 1
8 Motor Gasket 76712711 3 76712711 3
9 Bolt 70212701 3 70212701 3
10 Motor Fixer 01702701 1 01702701 1
11 Fan Motor 15704103 1 15704103 1
12 Centrifugal Fan 10310101 1 10310101 1
13 Evaporator Connection 01072733 1 01072733 1
14 Cable-cross Loop 76512702 2 76512702 2
15 shunt 07228804 1 07228804 1
16 Electronic Expansive Valve `07334102 1 `07334102 1
17 Water Tray 12412701 1 12412701 1
18 Screw 70140032 4 70140032 4
19 Electric Box Base Plate 01412721 1 01412721 1
20 Flow Guide Loop 10372701 1 10372701 1
21 Electric Box 20102701 1 20102701 1
22 Wire Clamp 71010102 4 71010102 4
23 Terminal Board T360B 42011142 1 42011142 1
24 Transformer 43110233 1 43110233 1
25 Electric Box Cover I 20102702 1 20102702 1
26 Electric Box Cover II 20102703 1 20102703 1
27 Main Board 30226316 1 30226316 1
28 Capacitor 33010012 1 33010012 1
29 Rubber plug 76712701 1 76712701 1
30 Evaporator 01004640 1 01004640 1
31 Evaporator Support 01072708 2 01072708 2
32 Nut with Washer M6 70310012 1 70310012 1
33 Bolt subassembly 70210051 1 70210051 1
34 Pipe Pump PJV-1415 43130324 1 43130324 1
35 Pump Gasket 76712702 3 76712702 3
36 Pump Support 01332001 1 01332001 1
37 Water Level Switch 45010201 1 45010201 1
38 Drainage hose Pump 05232721 1 05232721 1
39 Right Side Plate 01302716 1 01302716 1
40 Cable-cross Loop 76512702 1 76512702 1
41 Pump Cover 01252711 1 01252711 1
42 Bolt 70212701 3 70212701 3
240
DC INVERTER MULTI VRF MAINTENANCE
241
DC INVERTER MULTI VRF MAINTENANCE
242
DC INVERTER MULTI VRF MAINTENANCE
243
DC INVERTER MULTI VRF MAINTENANCE
245
DC INVERTER MULTI VRF MAINTENANCE
GMV(L)-R22P/Na-K,GMV(L)-R25P/N GMV(L)-R28P/Na-K,GMV(L)-R32P/
No. Part Name a-K Na-K,GMV(L)-R36P/Na-K
Code Qty. Code Qty.
1 Top Cover Sub-assy 01259052 1 01259052 1
2 Hook 02112446 2 02112446 2
3 Seal of Left Side Plate Sub-assy 01499051 1 01499051 1
4 Seal of Connection Pipe Sub-assy 01499053 1 01499053 1
5 Electric Box Assy 01408739 1 01394605 1
6 Left Side Plate Sub-assy 01308788 1 01308788 1
7 Left Support of Evaporator 01078774 1 01078774 1
8 Liquid-entered Pipe Sub-assy 03334601 1 03338810 1
9 Collect Gas Pipe Sub-assy 01305018 1 04674609 1
10 Evaporator Sub-assy 01038785 1 01038786 1
11 Fan Fixed Plate Sub-assy 01339095 1 01339095 1
12 Centrifugal fan 10319051 1 10319051 1
13 Return air inlet side-board Sub-assy 01499055 1 01499055 1
14 Motor 15019053 1 15019522 1
15 Centrifugal fan 10319051 1 10319051 1
16 Bottom Cover 01259086 1 01259086 1
17 Cover of Air-in 01259056 1 01259056 1
18 Water Tray Assy 01279051 1 01279051 1
19 Right Side Plate Sub-assy 01309055 1 01309055 1
20 Hook 02112446 2 02112446 2
21 Left Support of Evaporator 01079056 1 01079056 1
22 Return air inlet side-board Sub-assy 01498783 1 01498783 1
246
DC INVERTER MULTI VRF MAINTENANCE
(2)GMV(L)-R40P/Na-K,GMV(L)-R45P/Na-K,GMV(L)-R50P/Na-K
247
DC INVERTER MULTI VRF MAINTENANCE
GMV(L)-R40P/Na-K,GMV(L)-R45P/Na-K,GMV(L)-R50P/Na-K
No. Part Name
Code Qty.
1 Top Cover Sub-assy 01259064 1
2 Hook 02112446 2
3 Seal of Connection Pipe 2 01498644 1
4 Seal of Connection Pipe 1 01498604 1
5 Electric Box Assy 01404688 1
6 Left Side Plate Sub-assy 01308668 1
7 Left Support of Evaporator 01078629 1
8 Liquid-entered Pipe Sub-assy 04324601 1
9 Collect Gas Pipe Sub-assy 04674601 1
10 Evaporator Sub-assy 01038623 1
11 Fan Fixed Plate Sub-assy 01339058 1
12 Centrifugal fan 10319051 1
13 Return air inlet Sub-assy 01499061 1
14 Motor FG70B 15018322 1
15 Centrifugal fan 10319051 1
16 Bottom Cover 01258649 1
17 Cover of Air-in 01258650 1
18 Water Tray Sub-assy 01278633 1
19 Right Side Plate Sub-assy 01308670 1
20 Hook 02112446 2
21 Left Support of Evaporator 01078625 1
22 Return air inlet Sub-assy 01498641 1
248
DC INVERTER MULTI VRF MAINTENANCE
(3)GMV(L)-R56P/Na-K,GMV(L)-R63P/Na-K,GMV(L)-R71P/Na-K,GMV(L)-R80P/Na-K
249
DC INVERTER MULTI VRF MAINTENANCE
GMV(L)-R56P/Na-K,GMV(L)-R63P/Na-K,GMV(L)-R71
No. Part Name P/Na-K,GMV(L)-R80P/Na-K
Code Qty.
1 Top Cover Sub-assy 01258652 1
2 Hook 02118504 2
3 Left Side Seal-hole Plate Sub-assy 01308680 1
4 Seal of Connection Pipe 01498610 1
5 Electric Box Assy 01394609 1
6 Left Side Plate Sub-assy 01308676 1
7 Left Support of Evaporator 01078603 1
8 Liquid-entered Pipe Sub-assy 04324603 1
9 Collect Gas Pipe Sub-assy 04674602 1
10 Evaporator Sub-assy 01054601 1
11 Fan Fixed Plate Sub-assy 01338631 1
12 Fan Motor (Left)SYP-200/190J-1 15018603 1
13 Return air inlet side-board Sub-assy 01499074 1
14 Motor FG150B 15018612 1
15 Fan motor (Right)SYP-200/190J-1 15018604 1
16 Bottom Cover 01258612 1
17 Cover of Air-in 01258614 1
18 Water Tray Assy 01278612 1
19 Right Side Plate Sub-assy 01308677 1
20 Hook 02118504 2
21 Left Support of Evaporator 01078604 1
22 Return air inlet Sub-assy 01498612 1
250
DC INVERTER MULTI VRF MAINTENANCE
(4)GMV(L)-R90P/Na-K,GMV(L)-R100P/Na-K,GMV(L)-R112P/Na-K,GMV(L)-R125P/Na-K,GMV(L)-R140P/Na-K
251
DC INVERTER MULTI VRF MAINTENANCE
GMV(L)-R90P/Na-K,GMV(L)-R100P/Na-K,GMV(L)-R11
No. Part Name 2P/Na-K,GMV(L)-R125P/Na-K,GMV(L)-R140P/Na-K
Code Qty.
1 Top Cover Sub-assy 01258606 1
2 Hook 02118504 2
3 Left Side Seal-hole Plate Sub-assy 01308673 1
4 Seal of Connection Pipe 01498601 1
5 Electric Box Assy 01394602 1
6 Left Side Plate Sub-assy 01308676 1
7 Left Support of Evaporator 01078603 1
8 Liquid-entered Pipe Sub-assy 03338802 1
9 Collect Gas Pipe Sub-assy 04674608 1
10 Evaporator Sub-assy 01038624 1
11 Fan Fixed Plate Sub-assy 01338630 1
12 Motor FG75B 15018613
13 Fan Motor (Left)SYP-200/190J-1 15018603 2
14 Return air inlet side-board Sub-assy 01499066 1
15 Motor FG150B 15018612 1
16 Fan motor (Right)SYP-200/190J-1 15018604 1
17 Bottom Cover Assy 01258603 1
18 Cover of Air-in 01258602 1
19 Water Tray Assy 01278603 1
20 Right Side Plate Sub-assy 01308677 1
21 Hook 02118504 2
22 Left Support of Evaporator 01078604 1
23 Return air inlet Sub-assy 01498608 1
252
DC INVERTER MULTI VRF MAINTENANCE
List of components
Qty
No Name Material Code
GMVL-R22P/NaB-K GMVL-R28P/NaB-K GMVL-R36P/NaB-K
1 Side Plate of Air outlet 01494118 1 1 1
Left Support of
2 01094122 1 1 1
Evaporator
01024231 1
3 Evaporator Assy
01024232 1 1
Electric expand valve
4 43040001 1 1 1
fitting
Right Support of
5 01094121 1 1 1
Evaporator
Left Side Plate Sub
6 01314172 1 1 1
-assy
Seal of left side Plate
7 01494115 1 1 1
Sub-assy
Seal of Connection Pipe
8 01494132 1 1 1
Sub-assy
9 Hook 02112446 4 4 4
10 Electric Box Cover 01424319 1 1
11 Top Cover Board Assy 01264176 1 1 1
Right Side Plate Sub
12 01314175 1 1 1
-assy
13 Motor Support 0170905801 1 1 1
1570520103 1
14 Fan Motor
1570520201 1 1
254
DC INVERTER MULTI VRF MAINTENANCE
Qty
No Name Material Code
GMVL-R22PS/NaB-K GMVL-R28PS/NaB-K GMVL-R36PS/NaB-K
1 Side Plate of Air outlet 01494118 1 1 1
Left Support of
2 01094122 1 1 1
Evaporator
01024231 1
3 Evaporator Assy 01024230 1
01024232 1
Electric expand valve
4 43040001 1 1 1
fitting
Right Support of
5 01094121 1 1 1
Evaporator
Left Side Plate Sub
6 01314172 1 1 1
-assy
Seal of left side Plate
7 01494115 1 1 1
Sub-assy
Seal of Connection Pipe
8 01494116 1 1 1
Sub-assy
9 Hook 02112446 4 4 4
10 Electric Box Cover 01424319 1 1
11 Top Cover Board Assy 01264176 1 1 1
Right Side Plate Sub
12 01314175 1 1 1
-assy
13 Motor Support 0170905801 1 1 1
1570520103 1
14 Fan Motor
1570520201 1 1
255
DC INVERTER MULTI VRF MAINTENANCE
Qty
No Name Material Code
GMV-R22P/NaB-K GMV-R28P/NaB-K GMV-R36P/NaB-K
1 Side Plate of Air outlet 01494118 1 1 1
Left Support of
2 01094122 1 1 1
Evaporator
01024231 1
3 Evaporator Assy
01024232 1 1
Electric expand valve
4 43040001 1 1 1
fitting
Right Support of
5 01094121 1 1 1
Evaporator
Left Side Plate Sub
6 01314172 1 1 1
-assy
Seal of left side Plate
7 01494115 1 1 1
Sub-assy
Seal of Connection Pipe
8 01494132 1 1 1
Sub-assy
9 Hook 02112446 4 4 4
10 Electric Box Cover 01424319 1 1
11 Top Cover Board Assy 01264176 1 1 1
Right Side Plate Sub
12 01314175 1 1 1
-assy
13 Motor Support 0170905801 1 1 1
1570520103 1
14 Fan Motor
1570520201 1 1
256
DC INVERTER MULTI VRF MAINTENANCE
Qty
No Name Material Code
GMV-R22PS/NaB-K GMV-R28PS/NaB-K GMV-R36PS/NaB-K
1 Side Plate of Air outlet 01494118 1 1 1
2 Left Support of Evaporator 01094122 1 1 1
01024231 1
3 Evaporator Assy 01024230 1
01024232 1
4 Electric expand valve fitting 43040001 1 1 1
5 Right Support of Evaporator 01094121 1 1 1
6 Left Side Plate Sub-assy 01314172 1 1 1
7 Seal of left side Plate Sub-assy 01494115 1 1 1
Seal of left Connection Pipe
8 01494116 1 1 1
Sub-assy
9 Hook 02112446 4 4 4
10 Electric Box Cover 01424319 1 1
11 Top Cover Board Assy 01264176 1 1 1
Right Side Plate Sub
12 01314175 1 1 1
-assy
13 Motor Support 0170905801 1 1 1
1570520103 1
14 Fan Motor
1570520201 1 1
257
DC INVERTER MULTI VRF MAINTENANCE
Qty
No Name Material Code
GMVL-R45PS/NaB-K GMVL-R45P/NaB-K
1 Side Plate of Air outlet 01498641 1 1
2 Left Support of Evaporator 01805280 1 1
3 Evaporator Sub-assy 01024211 1 1
4 Electric expand valve fitting 43040001 1 1
5 Right Support of Evaporator 01078625 1 1
6 Left Side Plate Sub-assy 01314230 1 1
7 Seal of left side Plate Sub-assy 01494128 1 1
8 Seal of Connection Pipe Sub-assy 01498640 1 1
9 Hook 02112466 4 4
10 Electric Box Cover 01425249 1 1
11 Top Cover Board Assy 01259064 1 1
12 Right Side Plate Sub-assy 01308670 1 1
13 Motor Support 01709056 1 1
14 Fan Motor 1501832202 1 1
30226221 1
25 Main Bord
30226167 1
26 Connecting Wire 4001039509 1 1
27 Display Bord 30296013 1 1
28 Sensor sub-assy 39004167 1 1
258
DC INVERTER MULTI VRF MAINTENANCE
Qty
No Name Material Code
GMV-R45PS/NaB-K GMV-R45P/NaB-K
1 Side Plate of Air outlet 01498641 1 1
2 Left Support of Evaporator 01805280 1 1
3 Evaporator Assy 01024211 1 1
4 Electric expand valve fitting 43040001 1 1
5 Right Support of Evaporator 01078625 1 1
6 Left Side Plate Sub-assy 01314230 1 1
7 Seal of left side Plate Sub-assy 01494128 1 1
8 Seal of Connection Pipe Sub-assy 01498640 1 1
9 Hook 02112466 4 4
10 Electric Box Cover 01425249 1 1
11 Top Cover Board Assy 01259064 1 1
Right Side Plate Sub
12 01308670 1 1
-assy
13 Motor Support 01709056 1 1
14 Fan Motor 1501832202 1 1
30226222 1
25 Main Bord
30226168 1
26 Connecting Wire 4001039509 1 1
27 Display Bord 30296014 1 1
28 Sensor sub-assy 39004167 1 1
259
DC INVERTER MULTI VRF MAINTENANCE
Qty
No Name Material Code
GMVL-R56P/NaB-K GMVL-R71P/NaB-K
1 Side Plate of Air outlet 01499074 1 1
2 Left Support of Evaporator 01078603 1 1
3 Evaporator Assy 01024221 1 1
4 Electric expand valve fitting 43040001 1 1
5 Right Support of Evaporator 01078604 1 1
6 Left Side Plate Sub-assy 01315255 1 1
7 Seal of left side Plate Sub-assy 01308680 1 1
Seal of left Connection Pipe
8 01498610 1 1
Sub-assy
9 Hook 02112466 4 4
10 Electric Box Cover 01425249 1 1
11 Top Cover Board Assy 01258651 1 1
Right Side Plate Sub
12 01308679 1 1
-assy
13 Motor Support 01708502 1 1
14 Fan Motor 1570521101 1 1
15018603 1 1
15 Motor Sub-assy
15018604 1 1
Border Plate Assy of Air Return
16 01499074 1 1
End
17 Filter 11129066 1 1
18 Electric Box 01394962 1 1
19 Lower Cover Plate Sub-assy 01258612 1 1
20 Fan motor mounting Plate Sub-assy 01338632 1 1
21 Water Pump Assy 15404119 0 0
22 Terminal Border 42011106 1 1
23 Capacitor 33010014 1 1
24 Transformer 43110239 1 1
25 Main Bord 30226167 1 1
26 Connecting Wire 4001039509 1 1
27 Display Bord 30296013 1 1
28 Sensor sub-assy 39004167 1 1
260
DC INVERTER MULTI VRF MAINTENANCE
Qty
No Name Material Code
GMVL-R56PS/NaB-K GMVL-R71PS/NaB-K
1 Side Plate of Air outlet 01499074 1 1
2 Left Support of Evaporator 01078603 1 1
3 Evaporator Sub-assy 01024234 1 1
4 Electric expand valve fitting 43040001 1 1
5 Right Support of Evaporator 01078604 1 1
6 Left Side Plate Sub-assy 01314225 1 1
7 Seal of left side Plate Sub-assy 01494131 1 1
Seal of left Connection Pipe
8 01494129 1 1
Sub-assy
9 Hook 02112466 4 4
10 Electric Box Cover 01425249 1 1
11 Top Cover Board Assy 01258651 1 1
Right Side Plate Sub
12 01308679 1 1
-assy
13 Motor Support 01708502 1 1
14 Fan Motor 1570521101 1 1
15018603 1 1
15 Motor Sub-assy
15018604 1 1
16 Border Plate Assy of Air Return End 01499074 1 1
17 Filter 11129066 1 1
18 Electric Box 01394997 1 1
19 Lower Cover Plate Sub-assy 01258612 1 1
20 Fan motor mounting Plate Sub-assy 01324350 1 1
21 Water Pump Assy 15404119 1 1
22 Terminal Border 42011106 1 1
23 Capacitor 33010014 1 1
24 Transformer 43110239 1 1
25 Main Bord 30226221 1 1
26 Connecting Wire 4001039509 1 1
27 Display Bord 30296013 1 1
28 Sensor sub-assy 39004167 1 1
261
DC INVERTER MULTI VRF MAINTENANCE
Qty
No Name Material Code
GMV-R56P/NaB-K GMV-R71P/NaB-K
1 Side Plate of Air outlet 01499074 1 1
2 Left Support of Evaporator 01078603 1 1
3 Evaporator Sub-assy 01024234 1 1
4 Electric expand valve fitting 43040001 1 1
5 Right Support of Evaporator 01078604 1 1
6 Left Side Plate Sub-assy 01314225 1 1
7 Seal of left side Plate Sub-assy 01494131 1 1
8 Seal of left Connection Pipe Sub-assy 01494129 1 1
9 Hook 02112466 4 4
10 Electric Box Cover 01425249 1 1
11 Top Cover Board Assy 01258651 1 1
12 Right Side Plate Sub-assy 01308679 1 1
13 Motor Support 01708502 1 1
14 Fan Motor 1570521101 1 1
15018603 1 1
15 Motor Sub-assy
15018604 1 1
16 Border Plate Assy of Air Return End 01499074 1 1
17 Filter 11129066 1 1
18 Electric Box 01394997 1 1
19 Lower Cover Plate Sub-assy 01258612 1 1
20 Fan motor mounting Plate Sub-assy 01324350 1 1
21 Water Pump Assy 15404119 0 0
22 Terminal Border 42011106 1 1
23 Capacitor 33010014 1 1
24 Transformer 43110239 1 1
25 Main Bord 30226168 1 1
26 Connecting Wire 4001039509 1 1
27 Display Bord 30296014 1 1
28 Sensor sub-assy 39004167 1 1
262
DC INVERTER MULTI VRF MAINTENANCE
Qty
No Name Material Code GMVL-R56PS/NaB-K GMVL-R71PS/NaB-K
☆GMV-R56PS/NaB-K ☆GMV-R71PS/NaB-K
1 Side Plate of Air outlet 01499074 1 1
01078603
2 Left Support of Evaporator 1 1
☆01805279
3 Evaporator Assy 01024234 1 1
4 Electric expand valve fitting 43040001 1 1
5 Right Support of Evaporator 01078604 1 1
6 Left Side Plate Sub-assy 01314225 1 1
7 Seal of left side Plate Sub-assy 01494131 1 1
8 Seal of Connection Pipe Sub-assy 01494129 1 1
9 Hook 02112466 4 4
10 Electric Box Cover 01425249 1 1
11 Top Cover Board Assy 01258651 1 1
Right Side Plate Sub
12 01308679 1 1
-assy
13 Motor Support 01708502 1 1
14 Fan Motor 1570521101 1 1
15018603 1 1
15 Motor Sub-assy
15018604 1 1
16 Border Plate Assy of Air Return End 01499074 1 1
11129066/
17 Filter 1 1
☆11129067
01394997
18 Electric Box 1 1
☆01394739
19 Lower Cover Plate Sub-assy 01258612 1 1
20 Fan motor mounting Plate Sub-assy 01324350 1 1
21 Water Pump Assy 15404119 1 1
22 Terminal Border 42011106 1 1
23 Capacitor 33010014 1 1
24 Transformer 43110239 1 1
30226221
25 Main Bord 1 1
☆30226222
4001039509
26 Connecting Wire 1 1
/☆40010232
30296013
27 Display Bord 1 1
☆30296014
28 Sensor sub-assy 39004167 1 1
263
DC INVERTER MULTI VRF MAINTENANCE
264
DC INVERTER MULTI VRF MAINTENANCE
Qty
No Name Material Code
GMVL-R90P/NaB-K GMVL-R112P/NaB-K GMVL-R140P/NaB-K
1 Air outlet side board assy 01498608 1 1 1
2 Water pump assy 15404119 0 0 0
3 Water level switch 45010201 0 0 0
4 Electric expand valve fitting 43040001 1 1 1
01024222 1 1
5 Evaporator assy
01024218 1
01805279 1 1
6 Left support of evaporator
01804703 1
Fan motor mounting Plate 01324356 1 1
7
Sub-assy 01804703 1
01258607 1 1
8 Top Cover Board Assy
01264627 1
01078604 1 1
9 Right support of evaporator
01805221 1
10 Right Side Plate Sub-assy 01308679 1 1
11 Air intake side-board sub-assy 01375221 1 1 1
12 Filter Sub-assy 11725205 1 1 1
13 Fan Motor 15018603 2 2 2
14 Fan Motor 15018604 1 1 1
1570521101 1 1
15 Motor
1570520901 1
1570521201 1 1
16 Motor
1570521001 1
01258603 1 1
17 Bottom cover plate assy
0125860301 1
18 Cover of air-in 01258602 1 1 1
01278603 1 1
19 Water tray assy
01285229 1
01394963 1 1
20 Electric box assy
01394964 1
33010014 1 1
21 Capacitor
33010056 1
22 Capacitor 33010064 1 1 1
23 Terminal board 42011106 1 1 1
24 Transformer 43110239 1 1 1
25 Main board 30226167 1 1 1
26 Electric box cover 01425249 1 1 1
01308672 1 1
27 Seal of lefr side plate sub-assy
01495212 1
28 Left side plate assy 01315255 1 1 1
01498601 1 1
29 Seal of connection pipe
01495213 1
30 Hook 02118504 4 4 4
31 Connecting Wire 4001039509 1 1 1
32 Display board 30296013 1 1 1
33 Sersor sub-assy 39004167 1 1 1
265
DC INVERTER MULTI VRF MAINTENANCE
Qty
No Name Material Code
GMVL-R90PS/NaB-K GMVL-R112PS/NaB-K GMVL-R140PS/NaB-K
1 Air outlet side board assy 01498608 1 1 1
15404119 1 1
2 Water pump assy
15404118 1
45010201 1 1
3 Water level switch
450102012 1
4 Electric expand valve fitting 43040001 1 1 1
01024233 1 1
5 Evaporator assy
01024218 1
01805279 1 1
6 Left support of evaporator
01804703 1
Fan motor mounting Plate 01324356 1 1
7
Sub-assy 01325293 1
01258607 1 1
8 Top Cover Board Assy
01264627 1
01078604 1 1
9 Right support of evaporator
01805221 1
10 Right Side Plate Sub-assy 01308679 1 1
11 Air intake side-board sub-assy 01375221 1 1 1
12 Filter Sub-assy 11725205 1 1 1
13 Fan Motor 15018603 2 2 2
14 Fan Motor 15018604 1 1 1
1570521101 1 1
15 Motor
1570520901 1
1570521201 1 1
16 Motor
1570521001 1
01258603 1 1
17 Bottom cover plate assy
0125860301 1
18 Cover of air-in 01258602 1 1 1
01284160 1 1
19 Water tray assy
01284157 1
01394998 1 1
20 Electric box assy
01394999 1
33010014 1 1
21 Capacitor
33010056 1
22 Capacitor 33010064 1 1 1
23 Terminal board 42011106 1 1 1
24 Transformer 43110239 1 1 1
25 Main board 30226221 1 1 1
26 Electric box cover 01425249 1 1 1
01494125 1 1
27 Seal of lefr side plate sub-assy
01494121 1
01494124 1 1
28 Left side plate assy
01314222 1
01494123 1 1
29 Seal of connection pipe
01494120 1
30 Hook 02118504 4 4 4
31 Connecting Wire 4001039509 1 1 1
32 Display board 30296013 1 1 1
33 Sersor sub-assy 39004167 1 1 1
DC INVERTER MULTI VRF MAINTENANCE
Qty
No Name Material Code
GMV-R90P/NaB-K GMV-R112P/NaB-K GMV-R140P/NaB-K
1 Air outlet side board assy 01498608 1 1 1
2 Water pump assy 15404119 0 0 0
3 Water level switch 45010201 0 0 0
4 Electric expand valve fitting 43040001 1 1 1
01024222 1 1
5 Evaporator assy
01024218 1
01805279 1 1
6 Left support of evaporator
01804703 1
01324356 1 1
7 Fan motor mounting Plate Sub-assy
01325293 1
01258607 1 1
8 Top Cover Board Assy
01264627 1
01078604 1 1
9 Right support of evaporator
01805221 1
10 Right Side Plate Sub-assy 01308679 1 1
11 Air intake side-board sub-assy 01375221 1 1 1
12 Filter Sub-assy 11725205 1 1 1
13 Fan Motor 15018603 2 2 2
14 Fan Motor 15018604 1 1 1
1570521101 1 1
15 Motor
1570520901 1
1570521201 1 1
16 Motor
1570521001 1
01258603 1 1
17 Bottom cover plate assy
0125860301 1
18 Cover of air-in 01258602 1 1 1
01284160 1 1
19 Water tray assy
01285229 1
01394957 1 1
20 Electric box assy
01394896 1
33010014 1 1
21 Capacitor
33010056 1
22 Capacitor 33010064 1 1 1
23 Terminal board 42011106 1 1 1
24 Transformer 43110239 1 1 1
25 Main board 30226168 1 1 1
26 Electric box cover 01425249 1 1 1
01308672 1 1
27 Seal of lefr side plate sub-assy
01495212 1
28 Left side plate assy 01315255 1 1 1
01498601 1 1
29 Seal of connection pipe
01495213 1
30 Hook 02118504 4 4 4
31 Connecting Wire 4001039509 1 1 1
32 Display board 30296014 1 1 1
33 Sersor sub-assy 39004167 1 1 1
267
DC INVERTER MULTI VRF MAINTENANCE
Qty
No Name Material Code
GMV-R90PS/NaB-K GMV-R112PS/NaB-K GMV-R140PS/NaB-K
1 Air outlet side board assy 01498608 1 1 1
15404119 1 1
2 Water pump assy
15404118 1
45010201 1 1
3 Water level switch
450102012 1
4 Electric expand valve fitting 43040001 1 1 1
01024233 1 1
5 Evaporator assy
01024218 1
01805279 1 1
6 Left support of evaporator
01804703 1
Fan motor mounting Plate 01324356 1 1
7
Sub-assy 01325293 1
01258607 1 1
8 Top Cover Board Assy
01264627 1
01078604 1 1
9 Right support of evaporator
01805221 1
10 Right Side Plate Sub-assy 01308679 1 1
Air intake side-board
11 01375221 1 1 1
sub-assy
12 Filter Sub-assy 11725205 1 1 1
13 Fan Motor 15018603 2 2 2
14 Fan Motor 15018604 1 1 1
1570521101 1 1
15 Motor
1570520901 1
1570521201 1 1
16 Motor
1570521001 1
01258603 1 1
17 Bottom cover plate assy
0125860301 1
18 Cover of air-in 01258602 1 1 1
01284160 1 1
19 Water tray assy
01284157 1
01394986 1 1
20 Electric box assy
01024218 1
33010014 1 1
21 Capacitor
33010056 1
22 Capacitor 33010064 1 1 1
23 Terminal board 42011106 1 1 1
24 Transformer 43110239 1 1 1
25 Main board 30226222 1 1 1
26 Electric box cover 01425249 1 1 1
Seal of lefr side plate 01494124 1 1
27
sub-assy 01494121 1
01314225 1 1
28 Left side plate assy
01314222 1
01494120 1 1
29 Seal of connection pipe
01494123 1
30 Hook 02118504 4 4 4
31 Connecting Wire 4001039509 1 1 1
32 Display board 30296014 1 1 1
33 Sersor sub-assy 39004167 1 1 1
268
DC INVERTER MULTI VRF MAINTENANCE
269
DC INVERTER MULTI VRF MAINTENANCE
GMV(L)-R22G/NaB-K,GMV(L)-R28G/NaB-K
No. Part Name
Code Qty.
1 Wall-Mounting Frame 01252220 1
2 Rear Case 222020012 1
3 Evaporator Assy 01004628 1
4 Cross Flow Fan 10352001 1
5 Ring of Bearing 76512203 1
6 Drainage hose 0523001401 1
7 Water Tray 20182027 1
8 Swing Louver 10512032 1
9 Swing Linkage 1 10582002 1
10 Swing Linkage 2 10582003 1
11 Front Case 20002215 1
12 Screw Cover 24252006 3
13 Filter 11122002 2
14 Remote Control Y612C 305125033 1
15 Decorate Piece 68012019 1
16 Receiver Board 30545702 1
17 Front Panel 20002209 1
18 Guide Louver 2 10512034 1
19 Guide Louver 1 10512033 1
20 Motor MP28VA 15212110 1
21 Motor Clamp A 26112017 1
22 Motor FN14A 150121081 1
23 Electric Box Cover 22242030 1
24 Terminal Board T4B3A 42011233 1
25 Covering Plate 201220061 1
26 Electric Box 20102178 1
27 Main PCB Z6H15C 30226074 1
28 Transformer 48X26F 43110226 1
29 Wire Clamp 71010103 1
30 Rear Clamp 24242001 1
31 Signal Cable 400103953 1
270
DC INVERTER MULTI VRF MAINTENANCE
(2)GMV(L)-R36G/NaB-K;GMV(L)-R45G/NaB-K
271
DC INVERTER MULTI VRF MAINTENANCE
GMV(L)-R36G/NaB-K;GMV(L)-R45G/NaB-K
No. Part Name
Code Qty.
1 Wall-Mounting Frame 01252384 1
2 Rear Case 22202050 1
3 Evaporator Assy 01004629 1
4 Cross Flow Fan 10352005 1
5 Ring of Bearing 76712015 1
6 Drainage hose 05232411 1
7 Water Tray 20182030 1
8 Swing Louver 10512041 12
9 Swing Linkage 10582439 1
10 Front Case 200022955 1
11 Screw Cover 24252007 3
12 Filter 11122440 2
13 Remote Control Y612C 305160051 1
14 Decorate Piece 68012019 1
15 Receiver Board 30545552 1
16 Front Panel 20002292 1
17 Guide Louver 26112043 1
18 Guide Louver 26112042 1
19 Motor MP28EA 15212105 1
20 Right Motor Clamp 26112429 1
21 Motor FN22A 15012062 1
22 Electric Box Cover 22242017 1
23 Terminal Board T4B3A 42011233 1
24 Covering Plate 20102119 1
25 Electric Box 20102108 1
26 Main PCB Z6J15C 30226072 1
27 Transformer 48X26F 43110226 1
28 Wire Clamp 71010103 1
29 Rear Clamp 26112430 1
30 Signal Cable 400103953 1
272
DC INVERTER MULTI VRF MAINTENANCE
(3)GMV(L)-R50G/NaB-K;GMV(L)-R56G/NaB-K
273
DC INVERTER MULTI VRF MAINTENANCE
GMV(L)-R50G/NaB-K;GMV(L)-R56G/NaB-K
No. Part Name
Code Qty.
1 Wall-Mounting Frame `01252004 1
2 Rear Case `22202329 1
3 Fan Bearing `76512203 1
4 Screw Cover `24252015 3
5 Swing Louver `10512429 11
6 Swing Link 1 `10582057 1
7 Swing Link 2 `10582058 1
8 Water Tray `20182057 1
9 Guide Louver(up) `10512085 1
10 Guide Louver(down) `10512086 1
11 Cross Flow Fan `10352022 1
12 Evaporator Assy `01024147 1
13 Drainage hose `0523001403 1
14 Evaporator Support `24212067 1
15 Filter `11122048 2
16 Front Case `200026529 1
17 Front Panel `01544115 1
18 Remote Controller Y512 `305125063 1
19 Displaying Light Board `22432071 1
20 Electric Box Cover 1 `20112019 1
21 Wire Clamp `71010103 1
22 Terminal Board T4B3A `42011233 1
23 Electric Box Cover `20112020 1
24 Main PCB `30226116 1
25 Transformer 57X25C `43110237 1
26 Room Sensor 15k `3900019813 1
`3900019814 1
27 Tube Sensor 20k `3900019815 1
`3900019816 1
28 Sensor Insert `42020063 3
29 Electric Box `20112018 1
30 Lower Shield of Electric Box `01592037 1
31 Upper Shield of Electric Box `01592038 1
32 Stepping Motor MP35XY `15212117 1
33 Motor Clamp 26112095 1
34 Helicoid tongue `26252009
35 Motor FN20C-PG `150120671 1
36 Pipe Clamp `24242001 1
37 Signal Cable `400103953 1
38 Fix sub-assy `01324110P 1
39 EXV sub-assy `07334255 1
40 Connecting Wire `40010267 1
274
DC INVERTER MULTI VRF MAINTENANCE
(4)GMV(L)-R71G/Na-K;GMV(L)-R80G/Na-K
275
DC INVERTER MULTI VRF MAINTENANCE
GMV(L)-R71G/Na-K;GMV(L)-R80G/Na-K
No. Part Name
Code Qty.
1 Wall-Mounting Frame ` 01252398 1
2 Rear Case ` 22202091 1
3 Fan Bearing ` 76512203 1
4 Screw Cover ` 242520053 3
5 Swing Louver ` 10512110 15
6 Swing Link ` 10582040 3
7 Water Tray ` 20182043 1
8 Guide Louver(up) ` 10512062 1
9 Guide Louver(down) ` 10512063 1
10 Cross Flow Fan ` 10352420 1
11 Evaporator Assy ` 0102411202 1
12 Drainage hose ` 0523001404 1
13 Evaporator Support(left) ` 24212041 1
14 Filter ` 11122051 2
15 Front Case ` 26904107 1
16 Front Panel ` 20002698 1
17 Front Panel A ` 22432258 1
18 Remote Controller Y512 ` 305125063 1
19 Receiver Board JD ` 30046093 1
20 Electric Box Cover ` 20102252 1
21 Switch Lever ` 10582007 1
22 Wire Clamp ` 71010103 1
23 Terminal Board T4B3A ` 42011233 1
24 Electric Box Cover ` 201022513 1
25 Main PCB ` 30226420 1
26 Transformer 48X26G ` 43110233 1
27 Room Sensor `3900019813 1
`3900019814 1
28 Tube Sensor `3900019815 1
`3900019816 1
29 Sensor Insert ` 42020063 3
30 Electric Box ` 20102250 1
31 Lower Shield of Electric Box ` 01592034 1
32 Upper Shield of Electric Box ` 01592033 1
33 Stepping Motor MP24GA 15212102 1
34 Evaporator Support(rihgt) ` 24212042 1
35 Motor Clamp ` 26112069 1
36 Motor FN26D ` 150121053 1
37 Fixer(evaporator) ` 02112009 1
38 Pipe Clamp ` 26112071 1
39 Signal Cable `400103953 1
40 Fix sub-assy `01324110P 1
41 EXV sub-assy `07334255 1
42 Connecting Wire `40010267 1
276
DC INVERTER MULTI VRF MAINTENANCE
(5)GMV(L)-R22G/NaC-K;GMV(L)-R28G/NaC-K
277
DC INVERTER MULTI VRF MAINTENANCE
GMV(L)-R22G/NaC-K;GMV(L)-R28G/NaC-K
No. Part Name
Code Qty.
1 Wall Mounting Frame 01252220 1
2 Rear Case 222020012 1
3 Evaporator Assy 01004628 1
4 Cross Flow Fan 10352001 1
5 O-Gasket of Cross Fan Bearing 76512203 1
6 Drain Pipe 0523001401 1
7 Water Tray 201820272 1
8 Air Louver 10512080 1
9 Swing Lever 10582002 1
10 Swing Lever 10582003 1
11 Front Case 200024442 1
12 Screw Cap 24252006 3
13 Filter 11122002 2
14 Remote Control Y512 305125063 1
15 Display Board 30545707 1
16 Front Panel 20002522 1
17 Guide Louver 10512034 1
18 Guide Louver 10512033 1
19 Stepping Motor 15212110 1
20 Motor Press Plate 26112014 1
21 Fan Motor 150121081 1
22 Electric Box Cover 22242030 1
23 4-bit Terminal Board 42011233 1
24 Electric Box Cover 201220061 1
25 Electric Box 20102178 1
26 Main PCB Z6H251B 30226077 1
27 Transformer 43110226 1
28 Fixed Clamp 71010103 1
29 Pipe Clamp 24242001 1
30 Connecting Wire(communicate) 400103953 1
278
DC INVERTER MULTI VRF MAINTENANCE
(6)GMV(L)-R36G/NaC-K;GMV(L)-R45G/NaC-K
279
DC INVERTER MULTI VRF MAINTENANCE
GMV(L)-R36G/NaC-K;GMV(L)-R45G/NaC-K
No. Part Name
Code Qty.
1 Wall Mounting Frame 01252384 1
2 Rear Case Sub-Assy 22202051 1
3 Evaporator Assy 01004629 1
4 Cross Flow Fan 10352005 1
5 Ring of Bearing 76712015 1
6 Drain Pipe 0523001401 1
7 Water Tray 201820302 1
8 Air Louver 10512041 12
9 Swing Lever 10582439 1
10 Front Case 200025253 1
11 Screw Cap 24252007 3
12 Filter 11122440 2
13 Remote Control Y512 305125063 1
14 Display Board 30545558 1
15 Front Panel 20002524 1
16 Lower Guide Louver 26112043 1
17 Upper Guide Louver 26112042 1
18 Stepping Motor 15212105 1
19 Motor Right Clamp 26112429 1
20 Motor FN22G 150120623 1
21 Electric Box Cover 22242017 1
22 4-bit Terminal Board 42011233 1
23 Covering Plate 20102119 1
24 Electric Box 20102108 1
25 Main PCB Z6J251B 30226075 1
26 Transformer 43110226 1
27 Fixed Clamp 71010103 1
28 Rear Clamp 26112430 1
29 Connecting Wire(communicate) 400103953 1
280
DC INVERTER MULTI VRF MAINTENANCE
281
DC INVERTER MULTI VRF MAINTENANCE
GMV(L)-R28Zd/Na-K,GMV(L)-R36Zd/Na-K,GMV(L)-R50Zd/Na-K
No. Part Name
Code Qty.
1 Rear Side Plate 01302013 1
2 Handle 26232001 4
3 Left Decoration Plate 261124152 1
4 Rear Side Plate of Air Outlet 0130201501 1
5 Louver 1051953202 1
6 Right Decoration Plate 261124162 1
7 Shaft of Louver II 10512026 2
8 Louver Support 24212019 2
9 Shaft of Louver I 10512025 1
10 Louver Fixer 24212018 1
11 Swing Louver 10512027 12
12 Connecting Lever 10582009 1
13 Connecting Lever 10582008 2
14 Right Swing Motor Fixer 26152006 1
15 Right Fixing Plate of Evaporator 01072411 1
16 Right Side Foam sub-assy 12312404 1
17 Right Fixing Plate 01332404 1
18 Right Decoration Panel 26112027 1
19 Pipe Clamp Plate 0107243701 1
20 Capacitor 1uF/500V 33010089 1
21 Transformer 57X25C 43110237 1
22 Electric Box 01402407 1
23 Main PCB Z6935 30226903 1
24 Terminal Board RS9413G 42011159 1
25 Wire Base 24253001 1
Wire Clamp 24253002 1
26 Fuse 5A 250VAC 46010013 1
27 Cover of Electric Box 01412408 1
28 Pipe Clip 70812001 1
29 Drainage hose 05235433 1
30 Display Board 5T52 30545654 1
31 Electric Box 20102138 1
32 Front Grill Clip 1 26252002 4
33 Filter 11122013 2
34 Front Grill 22412010 2
35 Front Grill Clip 2 26252003 4
36 Front Panel 01544106 1
37 Front Panel 01532001P 1
38 Water Tray Panel 01272205P 1
39 Motor Support 01709532 1
40 Left Decoration Panel 26112028 1
41 Left Fixing Plate 01332405 1
282
DC INVERTER MULTI VRF MAINTENANCE
GMV(L)-R28Zd/Na-K,GMV(L)-R36Zd/Na-K,GMV(L)-R50Zd/Na-K
No. Part Name
Code Qty.
43 Left Fixing Plate of Evaporator 01072410 1
44 Motor Clamp 26112026 4
45 Step Motor MP35CA 15212402 2
46 Left Swing Motor Fixer 26152005 1
01024134 ① 1
47 Evaporator Assy 01024135 ② 1
01024121 ③ 1
48 Water Lead Panel 01362001 1
49 Cover of Evaporator 01072409 1
50 Fixed Mount 01708763 1
51 Centrifugal Fan 10312401 2
52 Rear Snail Shell 22202032 2
53 Front Snail Shell 22202031 2
54 Bar Clasp 70819522 4
55 Hoop 70819521 1
15707302 ④ 1
Motor
56 157073024 ⑤ 1
57 Remote Controller 305125063 1
58 Signal Cable 400103953 1
59 Fix sub-assy 01324110P 1
60 EXV sub-assy 07334258 1
61 EXV SPF-16D70 07334191 1
62 Magnet Coil for EXV DPF-AS001A 430001087 1
63 Display Board Z63351F 30296309 1
Note:
11. Evaporator Assy ① is only applicable to GMV(L)-R28Zd/Na-K
12. Evaporator Assy ② is only applicable to GMV(L)-R36Zd/Na-K
13. Evaporator Assy ③ is only applicable to GMV(L)-R50Zd/Na-K
14. Motor ④ is only applicable to GMV(L)-R28Zd/Na-K,GMV(L)-R36Zd/Na-KMotor
15. Motor⑤ is only applicable to GMV(L)-R50Zd/Na-K
283
DC INVERTER MULTI VRF MAINTENANCE
(2)GMV(L)-R71Zd/Na-K
284
DC INVERTER MULTI VRF MAINTENANCE
GMV(L)-R71Zd/Na-K
No. Part Name
Code Qty.
1 Left Decoration Plate 261124172 1
2 Shaft of Louver I 10512025 2
3 Swing Louver Fixer sub-assy 013324232 1
4 Louver Support 24212020 3
5 Louver Fixer 24222016 2
6 Louver 105124042 1
7 Shaft of Louver II 10512026 2
8 Right Decoration Plate 261124212 1
9 Left Swing Motor Fixer 26152007 1
10 Front Panel 01532414 1
11 Display Box 20102138 1
12 Display Board 5T52 30545654 1
13 Front Panel 01544106 1
14 Right Swing Motor Fixer 26152008 1
15 Step Motor MP35CA 15212402 2
16 Motor Clamp 26112026 4
17 Water Tray 01272412 1
18 Auxiliary Water Tray 01272413 1
19 Pipe Clip 70812001 1
20 Drainage hose 05235433 1
21 Handle 26232001 4
22 Right Side Foam sub-assy 12312407 1
23 Right Fixing Palte 01332404 1
24 Support of Motor Bearing 01792408 2
25 Fixer of Motor Support 01792409 1
26 Right Decoration Panel 26112033 1
27 Pipe Clamp 01072424 1
28 Electric Box 01402407 1
29 Wire Base 24253001 1
30 Wire Clamp 24253002 1
31 Terminal Board 42011159 1
32 Fuse 5A 250VAC 46010013 1
33 Main PCB Z6935 30226903 1
34 Ring of Bearing 76512404 2
35 Fan Bearing 76512210 2
36 Transformer 57X25C 43110237 1
37 Cover of Electric Box 01412408 1
38 Centrifugal Fan 10312401 4
39 Rotary Axis 73012401 2
40 Capacitor CBB61 3uF/450 33010027 1
41 Motor FN100A 15012406 1
42 Motor Fixer 01722409 1
43 Motor Clamp 01702405 2
44 Axes Connector 73012403 2
285
DC INVERTER MULTI VRF MAINTENANCE
286
DC INVERTER MULTI VRF MAINTENANCE
(3)GMV(L)-R90Zd/Na-K,GMV(L)-R112Zd/Na-K,GMV(L)-R125Zd/Na-K
287
DC INVERTER MULTI VRF MAINTENANCE
GMV(L)-R71Zd/Na-K
No. Part Name
Code Qty.
1 Left Decoration Plate 261124152 1
2 Shaft of Louver I 10512025 3
3 Swing Louver Fixer sub-assy 0133241802 1
4 Louver Support 24212019 4
5 Louver Fixer 24212018 3
6 Shaft of Louver II 10512026 2
7 Louver 105124082 1
8 Right Decoration Plate 261124162 1
9 Left Swing Motor Fixer 26152005 1
10 Front Panel 01532413 1
11 Display Box 20102138 1
12 Display Board 5T52 30545654 1
13 Front Panel 01544106 1
14 Right Swing Motor Fixer 26152006 1
15 Step Motor MP35CA 15212402 2
16 Motor Clamp 26112026 4
17 Water Tray 0127240802 1
18 Auxiliary Water Tray 01272409 1
19 Pipe Clip 70812001 1
20 Drainage hose 05235433 1
21 Handle 26232001 4
22 Right Side Foam sub-assy 12312404 1
23 Right Fixing Palte 01332404 1
24 Support of Motor Bearing 01792408 2
25 Fixer of Motor Support 01792407 1
26 Right Decoration Panel 26112027 1
27 Pipe Clamp 01072425 1
28 Electric Box 01402407 1
29 Wire Base 24253001 1
30 Wire Clamp 24253002 1
31 Terminal Board 42011159 1
32 Fuse 5A 250VAC 46010013 1
33 Main PCB Z6935 30226903 1
34 Ring of Bearing 76512404 2
35 Fan Bearing 76512210 1
36 Transformer 57×25C 43110237 1
37 Cover of Electric Box 01412408 1
38 Centrifugal Fan 10319051 4
39 Rotary Axis 73012402 2
33010064 ① 1
40 Capacitor
33010056 ② 1
15012405 ③ 1
41 Motor
15012404 ④ 1
42 Motor Fixer 01722410 1
288
DC INVERTER MULTI VRF MAINTENANCE
Note:
16. Capacitor ① is only applicable to GMV(L)-R90Zd/Na-K
17. Capacitor ② is only applicable to GMV(L)-R112Zd/Na-K,GMV(L)-R125Zd/Na-K
18. Motor ③ is only applicable to GMV(L)-R90Zd/Na-K
19. Motor ④ is only applicable to GMV(L)-R112Zd/Na-K,GMV(L)-R125Zd/Na-K
289
DC INVERTER MULTI VRF MAINTENANCE
(1)GMV(L)-R22Td/Na-K
Code
No. Part Name Qty.
GMV-R22Td/Na GMVL-R22Td/Na
1 Front Panel Assy(MT01) 1 TL1000120 TL1000120
2 Water Tray Assy 1 12412702 12412702
3 引水架 1 24212708 24212708
4 Evaporator Assy 1 01024103 01024103
5 Left Side Plate Assy 1 01302729 01302729
6 Cross Flow Fan 1 10352701 10352701
7 Base Plate Assy 1 01222714 01222714
8 Right Side Plate Assy 1 01302746 01302746
9 Rear Case assy 1 22202702 22202702
10 Fan Motor 1 1570410401 1570410401
11 Electric Box Assy 1 01404655 01404697
12 Main Board 1 30226034 30226033
13 Electric Box Cover Plate 1 01412725 01412725
14 Terminal Board Cover 1 222427221 222427221
15 Drainage Pump 1 43132701 43132701
16 Electronic Expansion Valve 1 07334129 07334129
17 Supporter 1 01792703 01792703
(2)GMV(L)-R28Td/Na-K、GMV(L)-R36Td/Na-K
Code
No. Part Name Qty. GMV-R28Td/H; GMVL-R28Td/H;
GMV-R36Td/H GMVL-R36Td/H
1 Front Panel Assy(MT01) 1 TL1000120 TL1000120
2 Water Tray Assy 1 12412702 12412702
3 Water Lead Panel 1 24212708 24212708
290
DC INVERTER MULTI VRF MAINTENANCE
291