Co2 Kidde
Co2 Kidde
Co2 Kidde
P/N 81-CO2MAN-002
CO2
Carbon Dioxide
Fire Suppression
Systems
Owner’s Manual
Fire Systems
January 2002
P/N 81-CO2MAN-002
CO2
Carbon Dioxide
Fire Suppression
Systems
Owner’s Manual
Fire Systems
THIS PAGE INTENTIONALLY LEFT BLANK.
FOREWORD
This Manual is written for those who fill Kidde Carbon Dioxide (CO2) Suppression System Cylinders.
IMPORTANT
Kidde assumes no responsibility for application of any systems other than those addressed in this manual. The technical data
contained herein is limited strictly for information purposes only. Kidde believes this data to be accurate, but it is published and
presented without any guarantee or warranty whatsoever. Kidde disclaims any liability for any use that may be made of the data and
information contained herein by any and all other parties.
Kidde Carbon Dioxide Engineered Fire Suppression Systems are to be designed, installed, inspected, maintained, tested and re-
charged by qualified, trained personnel in accordance with the following:
• Standard of the National Fire Protection Association No. 12, titled “Carbon Dioxide Extinguishing systems.” (Latest Edition)
• All instructions, limitations, etc., contained in the manual, P/N 81-CO2MAN-002.
• All information contained on the system nameplate(s).
Storage, handling, Transportation, service, maintenance, recharge and test of agent storage containers shall be performed only by
qualified, trained personnel in accordance with the information in the manual and Compressed Gas Association* pamphlets C-1, C-
6, G-6, G-6.3 and P-1.
• C-1, “Methods for Hydrostatic Testing of Compressed Gas Cylinders”
• C-6, “Standards for Visual Inspection of Steel Compressed Gas Cylinders”
• G-6, “Carbon Dioxide”
• G-6.3, “Carbon Dioxide Cylinder Filling and Handling Procedures”
• P-1, “Safe Handling of Compressed Gas In Containers”
*CGA pamphlets are available from:
Compressed Gas Association
Crystal Square Two
1725 Jefferson Davis Highway
Arlington, VA 22202-4102
Any questions concerning the information presented in the manual should be addressed to:
Kidde-Fenwal, Inc.
400 Main Street
Ashland, MA 01721
Phone: (508) 881-2000
Fax: (508) 881-8920
i
THIS PAGE INTENTIONALLY LEFT BLANK.
ii
TABLE OF CONTENTS
Foreword ....................................................................................................................................................... i
List of Tables ................................................................................................................................................. iv
iii
LIST OF TABLES
LIST OF APPENDICES
iv
ATTENTION INSTALLER
This form must be signed by the system owner indicating that he/she has received a copy of this Owner’s Manual
P/N 81-CO2MAN-002. Have the system installer fill-out this form.
1. System Installed:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
____________________________________________ _____________
Owner or Authorized Representative Date
____________________________________________
Title
v
THIS PAGE INTENTIONALLY LEFT BLANK.
vi
SAFETY SUMMARY
Safety precautions are essential whenever electrical or mechanical equipment is involved. Take precautions when handling, servic-
ing, and charging CO2 fire suppression systems cylinders. Using this equipment with the respect and caution demanded will consid-
erably lessen the possibility of personal injury. If safety precautions are overlooked or ignored, personal injury or property damage
may occur.
The following symbols are used throughout this manual. Always heed these precautions. They are essential to the safe use of the
equipment described in this manual.
! WARNING
The warning symbol identifies immediate hazards and provides specific instructions or procedures which if not
correctly followed may result in severe personal injury or death.
! CAUTION
This caution symbol identifies specific instructions or procedures which if not correctly followed could result in
equipment or property damage.
The following safety precautions should always be followed:
! WARNING
Pressurized (charged) cylinders are extremely hazardous and if not handled properly are capable of causing bodily
injury, death or property damage.
1. Read and understand this manual and the other documents referenced herein.
2. The valve cylinder safety cap MUST be installed on the cylinder at all times and only removed when performing charging,
testing, or salvaging operations in accordance with the procedures contained in this manual.
3. Wear safety glasses when working with pressurized cylinders and charging equipment
4. Make sure that all control heads, pressure operated control heads, or other type of actuation devices have been removed from
the cylinder valves. Ensure the protection caps are installed before performing any charging, leak tests or salvage operations.
Don’t get careless. Never assume a cylinder is empty. Treat all cylinders as if they are fully charged.
Smoking is prohibited in carbon dioxide fill and charging areas.
vii
THIS PAGE INTENTIONALLY LEFT BLANK.
viii
CO2 Fire Suppression Systems
CHAPTER 1
GENERAL INFORMATION
CHAPTER 2
INSTALLATION, OPERATION AND MAINTENANCE
2-3.1 CO2 System Operation Procedures 1. Immediately evacuate all personnel from the hazard
area. Close all doors.
The following operation procedures are based on the CO2
system being used in normally occupied areas or where 2. Proceed to cable pull station or manual electric station,
occupancy is possible. In these instances a pressure oper- (whichever applies) for the appropriate hazard.
ated time delay and a pressure operated siren are required, 3. Operate the station as directed on the device to actu-
to ensure that personnel are alerted and afforded the time ate the CO2 cylinders.
to evacuate the hazard area prior to system discharge, re- 4. For multiple hazard systems, operate the cable pull sta-
gardless of the actuation mode. In addition, a lock-out valve tion for the appropriate stop valve.
should be installed if the hazard is occupied by people not
5. Call the fire department immediately.
familiar with the system operation. During a lock-out pe-
riod, a trained employee should be assigned as a “fire watch” 6. If the system is provided with a reserve cylinder(s), see
with a suitable portable device, to maintain protection of Paragraph 6.4 of the Design, Installation, Operation and
the hazard until the CO2 system is restored. Maintenance Manual.
7. Contact a Kidde distributor for service.
Note: In occupied protected spaces, particularly those oc-
cupied by personnel unfamiliar with the presence 2-3.1.3 REMOTE NITROGEN ACTUATOR
of, or operational procedure of the Kidde CO2 sys- OPERATION (PNEUMATIC)
tem, Kidde recommends a lock-out valve be pro- 1. Immediately evacuate all personnel from the hazard
vided per Section 1-5.1.7 of NFPA 12, “Standard area. Close all doors.
on Carbon Dioxide Extinguishing Systems.”
2. Proceed to the remote nitrogen actuator station for the
These procedures are for reference to the system owner. appropriate hazard.
For additional information, refer to the Kidde Carbon Diox- 3. Operate the control head mounted on the nitrogen ac-
ide (CO2) Fire Suppression Systems Design, Installation, tuation cylinder.
Operation and Maintenance Manual, (P/N 81-CO2MAN-
4. Move the ball valve, installed in the actuation piping
001). Appendix B includes component descriptions of typi-
downstream of the nitrogen cylinder to the OPEN posi-
cal equipment that the personnel in charge of the equipment
tion.
should be aware of in the event of system actuation.
5. Call the fire department immediately.
Note: Be sure the Kidde distributor installing the system
6. If the system is provided with a reserve cylinder(s), see
provides a written description of the CO2 system
Paragraph 6.4 of the Design, Installation, Operation and
procedure of operation at the time the system is
Maintenance Manual.
commissioned.
7. Contact a Kidde distributor for service.
! WARNING 2-3.1.4 LOCAL MANUAL OPERATION–ALL
If the pressure operated time delay fails to SYSTEMS
operate, actuate the manual control head lever
installed on the time delay to immediately ! CAUTION
discharge the system once personnel have This manual control is not part of the normal
evacuated the area. system actuation mode and should only be
used in a last resort, emergency condition.
2-3.1.1 AUTOMATIC OPERATION
1. Immediately evacuate the hazard area. Close all doors.
When a system is operated automatically by the electric or
pneumatic detection system, proceed as follows: 2. Proceed to the cylinder(s) for the hazard.
3. Remove the locking pin from the cylinder control
1. All personnel must evacuate the hazard area promptly.
head(s).
Close all doors.
4. Rotate the local manual release lever to the RELEASED
2. Call the fire department immediately.
or OPEN position.
3. If the system is provided with a reserve cylinder(s), see
5. Proceed to hazard area stop (directional) valve if one
Paragraph 6.4 of the Design, Installation, Operation and
is installed. Remove the locking pin from the stop (di-
Maintenance Manual.
rectional) valve control head. Rotate the local manual
4. Contact a Kidde distributor for service. release lever to the RELEASED or OPEN position.
2-3.1.2 CABLE ACTUATOR AND ELECTRIC 6. Proceed to the system lock-out valve and be sure it is
SYSTEM OPERATION in the OPEN position.
Operate the system using the controls as follows: 7. Call the fire department immediately.
8. Contact a Kidde distributor for service.
2-3.1.5 HOSE REEL OR RACK SYSTEM MANUAL 2. The protected space has been thoroughly ventilated,
OPERATION ensuring that all products of combustion and carbon
1. Proceed to the carbon dioxide cylinder(s). dioxide are discharged into the atmosphere external of
the building. Forced ventilation may need to be required.
2. Remove the locking pin from the cylinder control head,
and rotate the local manual release lever to the RE- 3. In order to remove all traces of combustion products,
LEASED or OPEN position. arrange for all affected equipment to be cleaned at the
first available opportunity.
3. Unwind hose from reel or rack. Approach fire carefully.
Do not allow hose to lie in the path of the flames. 4. Contact the Kidde distributor to reset and recharge the
system. The system must be recharged immediately
4. Point horn at hazard. Open horn valve by pushing stir- and with the proper type and quantity of agent to en-
rup handle forward. sure continued protection.
5. Direct carbon dioxide discharge at base of the flames.
As flames recede, follow slowly. Follow detailed instruc-
tions below. 2-5 INSPECTION AND MAINTENANCE OF
THE SYSTEM
2-3.1.5.1 Surface Fires
1. Direct carbon dioxide discharge close to the edge of ! WARNING
the fire nearest you. DO NOT point the horn at the cen-
ter of the flame. If the hose horn must be aimed into an The owner of the Kidde Carbon Dioxide (CO2)
inaccessible fire, the horn must be in the OPEN posi- Fire Suppression System must comply with
tion. these instructions. Failure to do so may result
in inadequate system performance, property
2. Sweep the horn slowly back and forth across the base damage and personal injury.
of the flames. Chase flames slowly as the fire is extin-
guished. For bulkhead fires arising in Marine (ship- ! CAUTION
board) applications, direct the discharge at the bottom
and gradually work upward as the fire recedes. CO2 and nitrogen cylinder assemblies must be
stored, handled, transported, serviced,
3. Continue discharging carbon dioxide until all smolder-
maintained, tested and installed only by trained
ing material is covered with carbon dioxide “snow”.
personnel and in accordance with the
2-3.1.5.2 Electrical Fires–Switchboards, Motors, etc. instructions contained in the Kidde Carbon
1. Discharge carbon dioxide into all openings on burning Dioxide (CO 2 ) Fire Suppression Systems
substances. Design, Installation, Operation and
2. Continue to discharge carbon dioxide until flames have Maintenance Manual, (P/N 81-CO2MAN-001),
been extinguished and the burned material is coated NFPA-12, and CGA pamphlets C-1, C-6, G-6, G-
with carbon dioxide “snow”. This will prevent any in- 6.3 and P-1. CGA pamphlets may be obtained
candescent material from re-igniting. from the Compressed Gas Association, 1725
Jefferson Davis Highway, Arlington, VA 22202-
! CAUTION 4102. Before performing maintenance
procedures, refer to the material safety data
While it is not necessary to de-energize
sheets and safety bulletins in this manual and
equipment before discharging carbon dioxide
in the Appendix of the Kidde Carbon Dioxide
onto electrical fires, equipment must be de-
(CO 2 ) Fire Suppression Systems Design,
energized as soon as possible after system
Installation, Operation and Maintenance
discharge to prevent the fire from spreading.
Manual, (P/N 81-CO2MAN-001).
6. After the fire has been extinguished, leave the horn
valve open to relieve all pressure from the hose. ! WARNING
7. Perform post-fire maintenance. All actuation devices (control heads, discharge
8. Contact a Kidde distributor for service. heads, etc.) must be removed from the system
cylinders prior to performing system
maintenance. Observe all safety precautions
2-4 POST-OPERATION INSTRUCTIONS
applicable to handling pressurized equipment.
After the system has discharged and the fire has been ex- Recharge of CO 2 and nitrogen cylinder
tinguished, do not attempt to resume operations in the pro- assemblies must be performed by personnel
tected area containing the fire until the following steps have trained in Kidde CO 2 systems equipment.
been completed: Failure to do so may result in property damage
1. The fire department has given authorization to re-oc- or personal injury.
cupy the area.
Fire suppression systems require proper care to ensure 1. Check that all personnel who may have to operate the
normal operation at all times. Periodic inspections must be system are properly trained and authorized to do so. In
made to determine the exact condition of the system equip- particular, check that all new employees have been in-
ment. structed in the use of the system.
A regular program of systematic maintenance is essential 2. Make a general inspection survey of all cylinders and
for proper operation of the carbon dioxide system. A peri- equipment for damaged or missing parts. If any equip-
odic maintenance schedule must be followed and an in- ment requires replacement, contact a Kidde distribu-
spection log maintained for ready reference. As a minimum, tor.
the log should record inspection interval, inspection proce- 3. Ensure that access to hazard areas, remote nitrogen
dure performed, maintenance performed, if any, as a re- or cable pull stations, discharge nozzles, and cylinders
sult of inspection, and name of inspector performing task. are unobstructed and there are no obstructions that
If inspection indicates areas of rust or corrosion, immedi- would hinder the operation of the equipment or distri-
ately clean and repaint the area. bution of carbon dioxide.
Perform inspections and preventative maintenance in ac- 4. Inspect flexible actuation hoses for loose fittings, dam-
cordance to the schedule in Table 2.1. The inspection pro- aged threads, cracks, distortion, cuts, dirt and frayed
cedures and intervals are recommended and may be wire braid. Inspect flexible actuation hose adapters for
modified to fit into normal facility schedules providing the stripped threads and damage. Inspect couplings and
intervals do not exceed the time periods indicated. A draw- tees for tightness. If any of these defects are present,
ing of the major CO2 Fire Suppression System components contact a Kidde distributor to replace, tighten, or clean
is included with appropriate part numbers in Appendix B of system parts.
this manual. The component drawings are for owner refer- 5. Inspect control heads attached to CO2 cylinders, nitro-
ence only. gen cylinders, stop valves and time delays for physical
damage, deterioration, corrosion, distortion, cracks, dirt,
Table 2-1. Inspection and Maintenance Schedule
and loose couplings. If a defect is found, contact a Kidde
distributor; a replacement may be necessary. Ensure
S ch ed u le R eq u iremen t that all control heads, actuation devices, etc., are all in
Inspect hazard area system components the SET or CLOSED position with the locking pin in-
Monthly stalled and seal wire intact.
Check ni trogen cylinder pressure 6. Inspect carbon dioxide cylinder and valve assembly for
Check CO2 cylinder weight leakage, physical damage such as cracks, dents, dis-
tortion, and worn parts.
Semi-Annually Test electric control head 7. Inspect cylinder straps, cradles, and attaching hard-
Test pressure switch ware for loose, damaged, or broken parts. Check straps
and associated parts for corrosion, oil, grease, grime,
Check nitrogen cylinder pressure etc.
Check CO2 cylinder weight 8. Inspect CO2 system discharge heads for cracks, cor-
rosion, grime, etc.
Annually Blow out distribution pipi ng
9. Inspect flexible discharge hoses for loose fittings, dam-
Perform complete system function aged threads, cracks, rust, kinks, distortion, dirt, and
frayed wire braid.
Test pneumatic detection system
10. Inspect discharge manifold for physical damage, cor-
Hydrostatic test all CO2 and nitrogen rosion, and dirt. Inspect manifold support brackets and
Every 5 years
system hoses and flexible connectors. clamps for looseness and damage. Inspect check and
stop valves, where applicable, for deformation, leak-
Every 5 or CO2 cylinder hydrostatic test age, cracks, wear, corrosion, and dirt.
12 years
N2 cylinder hydrostatic test
! CAUTION
2-5.1 Monthly Inspection Do not paint nozzle orifices. The part number
The following monthly inspection program should be con- of each nozzle is stamped on the nozzle.
ducted visually only. If any defects are apparent as described Nozzles must be replaced by nozzles of the
below, SUSPEND ALL OPERATIONS IN THE PRO- same part number. Nozzles must never be
TECTED AREA, and immediately contact a Kidde Distribu- interchanged, since random interchanging of
tor. In addition, Kidde recommends that all inspections, nozzles will adversely affect proper CO 2
including the monthly inspection, be conducted by an au- distribution within a hazard area.
thorized Kidde distributor.
11. Inspect discharge nozzles for dirt, clogs and physical The flexible hoses must undergo hydrostatic testing every
damage. Where flangible discs are used, ensure they 5 years in accordance with NFPA12. Testing must be con-
are intact and clean. Look for holes or cuts. Broken ducted by a certified Kidde distributor ONLY. A detailed
discs will allow vapors, oils, etc., to enter into the nozzles description of the 5 and 12 year inspection can be found in
and system piping from the hazard, and seriously af- the Design, Installation, Operation and Maintenance
fect or block system discharge. Manual, Paragraph 7.9.
12. Inspect pressure switches for deformations, cracks, dirt
or other damage.
2-6 ADDITIONAL REQUIREMENTS
13. Check nitrogen cylinder pressure gauge for proper op-
erating pressure. If pressure loss (adjusted for tem- In addition to the CO2 system and for areas not protected
perature) exceeds 10%, recharge with nitrogen to 1800 by the system, portable fire extinguishers are required. Con-
psig at 70°F. See Figure 7.18.2 of the Kidde Carbon sult with the insurance carrier, local Authorities Having Ju-
Dioxide (CO2) Fire Suppression Systems Design, In- risdiction and a portable fire extinguisher distributor for sizes,
stallation, Operation and Maintenance Manual, (P/N 81- types, spacing and location requirements.
CO2MAN-001), for the pressure-temperature Read, understand and follow the instructions in this manual
relationship. and on the container nameplates. Review these instruc-
14. Inspect the lock-out valve. The valve must be secured tions with employees semi-annually, or more frequently.
and locked in the OPEN position. Place this manual in an accessible area near the CO2 sys-
15. Visually inspect control panel and detection system. tem for ready reference. Post the name, phone number
Ensure that the system is in “Normal” status and free and address of the Kidde distributor near all telephones.
from any “Alarm” or “Trouble” signals. Also, post the emergency telephone number of the fire de-
partment and the building street address near all telephones.
16. If any defects are found during the monthly inspection,
immediately contact a Kidde Distributor to service the If any condition exists which would render the CO2 sys-
systems. tems inoperative or ineffective, SUSPEND ALL OPERA-
TIONS IN THE PROTECTED AREA IMMEDIATELY. Have
2-5.2 Semi-Annual Inspection
the condition corrected by a Kidde distributor before re-
The system must be thoroughly inspected on a semi-an- suming operations.
nual basis by a certified Kidde distributor ONLY. The semi-
annual inspection includes a weighing of the agent cylinders,
an electric control head test, and a pressure switch test. A 2-7 ADDITIONAL SPECIFICATIONS AND
detailed description of the semi-annual inspection can be DOCUMENTATION
found in the Design, Installation, Operation and Maintenance The system must be designed, installed, operated and
Manual, Paragraphs 7.4, 7.5 and 7.6. maintained only in accordance with the following documents
2-5.3 Annual Inspection and specifications:
The system must be thoroughly inspected on an annual • Kidde Carbon Dioxide (CO2) Design, Installation, Op-
basis by a certified Kidde distributor ONLY. The annual in- eration and Maintenance Manual (P/N 81-CO2MAN-
spection includes a check of the CO2 cylinder weight, a 001), available from Kidde Distributors or from Kidde
check of the nitrogen cylinder pressure, a blowout proce- at:
dure for the distribution piping, a complete system perfor- Kidde-Fenwal, Inc.
mance function test, and a pneumatic detection system test. 400 Main Street
A detailed description of the annual inspection can be found Ashland, MA 01721
in the Design, Installation, Operation and Maintenance Phone: 508-881-2000
Manual, Paragraphs 7.7 and 7.8. Fax: 508-881-8920
2-5.4 5 Year and 12 Year Inspection and Test • National Fire Protection Association Standard No. 12,
Guidelines current edition, available from:
The carbon dioxide and nitrogen cylinders must undergo National Fire Protection Association
hydrostatic testing and be marked in accordance with DOT 1 Batterymarch Park
CFR 49 Section 173.34 every 5 years after a cylinder is Quincy, MA 02269
discharged or, if no discharge has occurred, every 12 years. • Copies of the Material Safety Data Sheet (MSDS) for
The cylinders must undergo hydrostatic testing immedi- Carbon Dioxide are available in the back of this manual
ately if they show evidence of distortion, damage, cracks, (Appendix A).
corrosion, or mechanical damage. Testing must be con-
ducted by a certified Kidde distributor ONLY.
APPENDIX A
MATERIAL SAFETY DATASHEETS
2. Composition/Information on Ingredients
This section covers materials of manufacture only. See sections 3, 8, 10, 11, 15, and 16 for
information on by-products generated during use, especially use in welding and cutting.
For custom mixtures of this product, request an MSDS for each component. See section 16 for
important information about mixtures.
INGREDIENT CAS NUMBER CONCENTRATION OSHA PEL ACGIH TLV-TWA
Carbon Dioxide 124-38-9 >99% 5,000 ppm* 5,000 ppm**
* The symbol > means “greater than”; the symbol <, “less than.”
** See section 3.
3. Hazards Identification
EMERGENCY OVERVIEW
WARNING! Cold liquid and gas under pressure.
Can cause rapid suffocation.
Can cause frostbite.
Can increase respiration and heart rate.
May cause nervous system damage.
May cause dizziness and drowsiness.
Self-contained breathing apparatus may be required by rescue workers.
Odor: None to slightly pungent
THRESHOLD LIMIT VALUE: TLV-TWA, 5,000 ppm (ACGIH, 1998). TLV-TWA, 15 min STEL,
30,000 ppm. ACGIH recommends a TLV-TWA of 5 mg/m3 for welding fumes not otherwise classified
(NOC) that may be generated during welding with this product.TLV-TWAs should be used as a guide in
the control of health hazards and not as fine lines between safe and dangerous concentrations.
Page 2 of 10
Product: Liquid Carbon Dioxide P-4573-A Date: May 1999
Page 3 of 10
Product: Liquid Carbon Dioxide P-4573-A Date: May 1999
Page 4 of 10
Product: Liquid Carbon Dioxide P-4573-A Date: May 1999
EFFECT: CONCENTRATION:
Page 5 of 10
Product: Liquid Carbon Dioxide P-4573-A Date: May 1999
Page 6 of 10
Product: Liquid Carbon Dioxide P-4573-A Date: May 1999
TSCA: TOXIC SUBSTANCES CONTROL ACT: Carbon dioxide is listed on the TSCA
inventory.
OSHA: OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION:
29 CFR 1910.119: PROCESS SAFETY MANAGEMENT OF HIGHLY HAZARDOUS
CHEMICALS: Requires facilities to develop a process safety management program based on
Threshold Quantities (TQ) of highly hazardous chemicals.
Carbon dioxide is not listed in Appendix A as a highly hazardous chemical.
STATE REGULATIONS:
CALIFORNIA: Carbon dioxide is not listed by California under the SAFE DRINKING WATER
AND TOXIC ENFORCEMENT ACT OF 1986 (Proposition 65).
WARNING: The combustion of this gas produces carbon monoxide— a chemical known to the
State of California to cause birth defects or other reproductive harm.
(California Health and Safety Code §25249.5 et seq.)
PENNSYLVANIA: Carbon dioxide is subject to the PENNSYLVANIA WORKER AND
COMMUNITY RIGHT-TO-KNOW ACT (35 P.S. Sections 7301-7320).
Page 7 of 10
Product: Liquid Carbon Dioxide P-4573-A Date: May 1999
Page 8 of 10
Product: Liquid Carbon Dioxide P-4573-A Date: May 1999
Praxair asks users of this product to study this MSDS and become aware of product hazards and safety
information. To promote safe use of this product, a user should (1) notify employees, agents, and
contractors of the information in this MSDS and of any other known product hazards and safety
information, (2) furnish this information to each purchaser of the product, and (3) ask each purchaser to
notify its employees and customers of the product hazards and safety information.
Page 9 of 10
Product: Liquid Carbon Dioxide P-4573-A Date: May 1999
The opinions expressed herein are those of qualified experts within Praxair, Inc. We
believe that the information contained herein is current as of the date of this Material
Safety Data Sheet. Since the use of this information and the conditions of use of the
product are not within the control of Praxair, Inc., it is the user’s obligation to
determine the conditions of safe use of the product.
Praxair MSDSs are furnished on sale or delivery by Praxair or the independent distributors and suppliers
who package and sell our products. To obtain current Praxair MSDSs for these products, contact your
Praxair sales representative or local distributor or supplier. If you have questions regarding Praxair
MSDSs, would like the form number and date of the latest MSDS, or would like the names of the Praxair
suppliers in your area, phone or write the Praxair Call Center ( Phone: 1-800-PRAXAIR; Address:
Praxair Call Center, Praxair, Inc., PO Box 44, Tonawanda, NY 14150-7891).
PRAXAIR, the FLOWING AIRSTREAM design, and LIQUIFLOW are trademarks or registered trademarks of
Praxair Technology, Inc. in the United States and other countries.
Praxair, Inc.
39 Old Ridgebury Road
Danbury, CT 06810-5113
APPENDIX B
COMPONENT DESCRIPTIONS
LIST OF ILLUSTRATIONS
APPENDIX B
B-1 25 lb. thru 50 lb.Carbon Dioxide Cylinders, Bent Siphon Tube .................................................. 1-2
B-2 75 lb. and 100 lb.Carbon Dioxide Cylinders ............................................................................... 1-3
B-3 Discharge Head, Plain Nut ........................................................................................................ 1-4
B-4 Flex Hose - 3/4" and 1/2" ........................................................................................................... 1-4
B-5 Nozzle Part Numbers ................................................................................................................ 1-5
B-6 Multijet Nozzle, Type "S" ............................................................................................................ 1-6
B-7 Multijet Nozzle, Type "S" Flanged .............................................................................................. 1-6
B-8 Multijet Nozzle, Type "M" ........................................................................................................... 1-7
B-9 Multijet Nozzle, Type "L" ............................................................................................................ 1-7
B-10 Lever or Pressure Operated Control Head ................................................................................ 1-8
B-11 Nitrogen Pilot Cylinder and Bracket ........................................................................................... 1-8
B-12 Ball Valve 1/4" ............................................................................................................................ 1-9
B-13 Stop (Directional) Valves, 1/2" thru 2" ........................................................................................ 1-9
B-14 Stop (Directional) Valves, 2-1/2" and 3" ..................................................................................... 1-10
B-15 4" Stop (Directional) Valve ......................................................................................................... 1-10
B-16 Valve, CO2 Lock Out w/Limit Switch ......................................................................................... 1-11
B-17 Safety Outlets ............................................................................................................................ 1-11
B-18 Pressure Operated Switch ......................................................................................................... 1-12
B-19 Pressure Operated Switch, Explosion Proof ............................................................................. 1-12
B-20 Discharge Delay with Manual Operated Control Head .............................................................. 1-13
B-21 Pull Box, Break Glass ................................................................................................................ 1-13
THREAD FOR
PROTECTION
CAP (35 LB, AND
50 LB CYL INDERS ONLY)
PART VALVE
CYLINDER A B
NUMBER TYPE
Figure B-1. 25 lb. thru 50 lb. Carbon Dioxide Cylinders, Bent Siphon Tube
THREAD FOR
PROTECTION CAP
3.81"
(97mm)
3.94"
(100mm)
SWIVEL NUT
(FOR CONNECTION P/N: 872450
TO CYLINDER VALVE)
P/N 872450
Figure B-3. Discharge Head, Plain Nut
HOSE
S iz e P /N L
1+ 930067 X X X X X
12 X X X X 842330 X
13 X X X X 842331 X
14 X X X X 842332 X
15 X X X X 842333 X
1.12"
(29mm)
HEX
5.00"
(127mm)
3.50"
(89mm) For P/N, refer to Table
in Figure B-5.
1.12"
(29mm)
HEX
5.00"
(127mm)
4.25"
(108mm)
1.38"
(35mm)
HEX
9.50"
(241mm)
152.4mm
3.625
(92.1 MM)
Available Finishes (nozzle only): For P/N, refer to Table
1. Red Paint in Figure B-5.
CLOSED
SEAL WIRE
OPEN
TO OPEN
4.50"
SET
OPERATED
MATERIAL
Lever: Stainless Steel 3.00"
P/N 878751
Body and Piston: Brass
SPECIFICATIONS
MATERIAL
Cylinder Capacity:
Cylinder: Steel, Painted Black 108 in3 (1770 cm3)
Valve: Brass 3.56" Safety Outlet Burst Range:
(90mm) 2650-3000 psi (183-207 bars) at 70°F (20°C)
Bracket: Steel, Painted Black
Nitrogen-BB-n-411b, Grade A, Type 1 1800 psi
Adapter: Brass
(124 bars at 70°F (20°C)
SEAL WIRE
SEPARATE
MATERIAL
Stainless Steel, Type 316
Operating Pressure:
3000 psig @ 170°F (77°C)
Minimum Bursting Pressure:
P/N 283888
10000psi (680 bars) 2.57
A B
10.5"
(267mm)
9.81"
INLET
(249mm)
SIDE VIEW
WITHOUT
ASSEMBLED FLANGE
Operating Pressure @ 70°F (20°C):
850 psi (58 bar)
Test Pressure:
2250 psi (155 bar) P/N 890010
Burst Pressure:
6000 psi (413 bar)
12.12"
(308mm)
11.06"
INLET
(281mm)
SIDE VIEW
WITHOUT
ASSEMBLED FLANGE
Operating Pressure @ 70°F (20°C):
850 psi (58 bar)
Test Pressure: P/N 890208
2250 psi (155 bar)
Burst Pressure:
6000 psi (413 bar)
E
G
D
A
RETAINING NUT
SEAL WIRE
PRESSURE RELIEF
PART OPERATES AT
AGENT
NUMBER
1.78" BODY PSI BARS
(45mm)
803242 N2/CO2 2400-2800 166-193
4.00"
OPERATED
SET
R
Kidde
PRESSURE OPERATED SWITCH
3P.D.T.
4.00"
UL
FM
P/N: 486536
4.37"
SET POSITION
3 POLE
PRESSURE
OPERATED
EXPLOSION
PROOF
SWITCH
9.00"
INLET
GAS
P/N: 981332
N
PE
3 O
1
4 TO
CLOSED
LOCAL CONTROL LEVER
(OPERATED POSITION)
TO OPEN
11
5
16
N o min al D elay
P /N
T ime
OUT
871071 30
IN
897636 60
1
15
8
9
3
16 DIA.
OPTIONAL
NAMEPLATE
(BY INSTALLER)
FOR FIRE
BREAK GLASS PULL HANDLE
R
Kidde
PULL
5.87" HANDLE
(149mm) PULL HARD
HAMMER
P/N 928103
5.00"
(127mm)
P/N: 871403
(Use this report to indicate deficiencies, user remarks and recommendations relating to the publication. Fold on dotted line, tape and mail to
KIDDE-FENWAL, Inc., 400 Main Street, Ashland, MA 01721, Attn. Documentation Manager or FAX to 508-881-8920)
DATE:
7. USER EVALUATION
12. ADDRESS
Place
Stamp
Here
KIDDE-FENWAL, Inc.
400 Main Street
Ashland, MA 01721
FOLD
LIMITED WARRANTY STATEMENT
Kidde-Fenwal, Inc. represents that this product is free from defects in material and workmanship, and it will repair or replace
any product or part thereof which proves to be defective in workmanship or material for a period of twelve (12) months from
the date of purchase but not to exceed eighteen (18) months after shipment by Kidde-Fenwal Inc. For a full description of
Kidde-Fenwal’s LIMITED WARRANTY, which, among other things, EXCLUDES warranties of MERCHANTABILITY and FIT-
NESS FOR A PARTICULAR PURPOSE and liability for CONSEQUENTIAL DAMAGES, please read the entire LIMITED WAR-
RANTY on the Kidde-Fenwal Quotation, Acceptance of Order and/or Original Invoice which will become part of your sales
agreement. Please contact Kidde-Fenwal directly for a return material authorization (RMA) number before returning material
to the factory at Ashland, Massachusetts, shipment prepaid. Kidde-Fenwal will repair or replace and ship prepaid.
These instructions do not purport to cover all the details or variations in the equipment
described, nor do they provide for every possible contingency to be met in connection
with installation, operation and maintenance. All specifications subject to change without
Fire Systems
notice. Should further information be desired or should particular problems arise which
are not covered sufficiently for the purchaser’s purposes, the matter should be referred
to Kidde-Fenwal, Inc., Ashland, Masssachusetts
Kidde-Fenwal Inc.
400 Main Street, Ashland, MA 01721 06-236177-001 Rev. AA ©2002 Kidde-Fenwal, Inc. Printed in USA
Tel: (508) 881-2000 Fax: (508) 881-8920
http://www.kiddefiresystems.com