Manual Usuario
Manual Usuario
Manual Usuario
User Manual
TABLE OF CONTENTS
SUPPORT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IV
i
7.0 OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.1 Startup Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.1.1 Normal System Turn ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.2 Normal System Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.3 Current Monitoring Panel (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.4 Current Plus Monitoring (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.5 Liebert LDMF™ (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
8.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8.1 Inspection & Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8.2 Inspection Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8.3 Proper Tightening of Nuts and Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
ii
FIGURES
Figure 1 Typical bottom exit cabinet and floor planning dimension data . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 2 Typical tie-breaker bottom exit cabinet and floor planning dimension data. . . . . . . . . . . . . . . . . . 5
Figure 3 Typical top exit cabinet and floor planning dimension data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 4 Typical 380-480V, 60Hz, cabinet and floor planning dimension data . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 5 Shipping brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 6 Recommended minimum service and ventilation clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 7 Seismic floor stand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 8 Electrical field connections, 1 input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 9 Electrical field connections, 2 inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 10 Electrical field connections, 4 inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 11 Top exit electrical field connections, 1 input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 12 Top exit electrical field connections, 2 inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 13 Top exit electrical field connections, 4 inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 14 380-480V, 60Hz, electrical field connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 15 Current Plus Monitoring location - bottom exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 16 Current Plus Monitoring™ location - top exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 17 Current Plus Monitoring and Liebert LDMF communication and summary alarm
connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 18 Control connections for Liebert LDMF - bottom exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 19 Control connections for Liebert LDMF™ - top exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 20 Control connections for Liebert LDMF™ 380-480V, 60Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 21 Connections for replacement Current Transformer (CT) for Liebert LDMF™ CT sensor
module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 22 Connections to Liebert LDMF™ SiteScan® monitoring interface - bottom exit . . . . . . . . . . . . . . 26
Figure 23 Connections to Liebert LDMF™ SiteScan® monitoring interface - top exit . . . . . . . . . . . . . . . . . 27
Figure 24 Current Monitoring Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 25 Current Plus Monitoring panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
TABLES
Table 1 Torque tightening . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Table 2 Input/output voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 3 System current ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
iii
SUPPORT INFORMATION
If you require assistance for any reason:
• In the United States, call 1-800-LIEBERT (1-800-543-2378).
• Outside the 48 contiguous United States, contact Emerson Network Power Liebert Services, if
available in your area. For international areas not covered by Liebert Services, the Emerson
authorized distributor can provide qualified factory-authorized service.
Please have the following information available.
Model Number: ___________________________________________________________________
Serial Number: ___________________________________________________________________
Date Purchased: __________________________________________________________________
Date Installed: ____________________________________________________________________
Location: _________________________________________________________________________
iv
IMPORTANT SAFETY INSTRUCTIONS
! WARNING
The unit contains hazardous voltages when input source is on. To isolate the unit, turn OFF
and lock out the input power source.
Verify that the input power source is de-energized and locked out before installing cables or
making connections in the unit.
Lethal voltages exist inside the unit during normal operation. Only qualified service
personnel should perform maintenance on the Liebert FDC.
NOTE
Read the entire manual before installing or operating the system. Adhere to all operating
instructions and warnings on the unit and in this manual.
Emerson Network Power neither recommends nor knowingly sells this product for use with life
support or other FDA-designated “critical” devices.
The Liebert FDC is suitable for indoor use only. Protect the unit from excessive moisture and
install the unit in an area free from flammable liquids, gases and corrosive substances.
Provide input overcurrent protection in accordance with the unit ratings. Wire and ground the
unit according to national and local electrical safety codes. All wiring should be installed by a
qualified electrician.
Before the unit is placed into service for the first time, as well as after equipment relocation and
after the unit has been de-energized for an extended period of time, thorough equipment
inspection and supervised startup by qualified service personnel are strongly recommended.
! CAUTION
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J
of the FCC rules. These limits provide reasonable protection against harmful interference in a
commercial environment. This unit generates, uses and radiates radio frequency energy and,
if not installed and used in accordance with this instruction manual, may cause harmful
interference to radio communications. Operation of this unit in a residential area may cause
harmful interference that users must correct at their own expense.
! WARNING
Locate the center of gravity symbols and determine the unit’s weight before handling the
cabinet.
! WARNING
The shipping bands may be under tension. Use appropriate eye, face and hand protection to
safeguard against injury from band backlash.
NOTE
The unit should NOT be loosened from the shipping pallet until all handling by forklift or
pallet jack is completed.
1 Liebert® FDC™
Safety Precautions
Liebert® FDC™ 2
Unpacking and Inspections
NOTE
Read the entire manual before installing and operating the unit. Upon receipt of the Liebert
FDC, the installer should perform the following steps to ensure a high-quality installation.
A high-quality installation begins on the receiving dock. The Liebert FDC and its packaging should be
inspected when the unit is delivered. If the packaging is not damaged, unpack the unit and conduct
an internal inspection before beginning the installation process. This section discusses inspecting and
unpacking of the Liebert FDC.
3 Liebert® FDC™
Unpacking and Inspections
Figure 1 Typical bottom exit cabinet and floor planning dimension data
17.3"
120° Door Swing
(439mm)
3.1" (79mm)
78.5"
(1994mm)
FDC12107
FRONT AND REAR VIEW RIGHT SIDE VIEW
Rev. 0
NOTES
1. Weight: 750 lb. (340kg)
2. Heat Output: 3412 BTU/Hr (1kW)
3. Casters are removable
Height without casters: 77 in. (1956mm)
Liebert® FDC™ 4
Unpacking and Inspections
Figure 2 Typical tie-breaker bottom exit cabinet and floor planning dimension data
Minimum Clearance
120° Door Swing 17.3"
of 18" (457mm)
(439mm)
is Recommended 3.1" (79mm)
Above Unit for Input Landing
Cooling Airflow Area
18"x9"
(457x229mm) 25.9"
Minimum Clearance (657mm)
of 36" (914mm)
is Recommended at 5.3"
Front, Rear and Side 13.4" (135mm)
for Service Access (340mm)
TOP VIEW
BOTTOM
120° Door Swing VIEW
Tie Breaker
Access Door
78.5"
(1994mm)
FDC12104
FRONT AND REAR VIEW RIGHT SIDE VIEW Rev. 1
NOTES
1. Weight: 750 lb. (340kg)
2. Heat Output: 3412 BTU/Hr (1kW)
3. Casters are removable
Height without casters: 77 in. (1956mm)
5 Liebert® FDC™
Unpacking and Inspections
Figure 3 Typical top exit cabinet and floor planning dimension data
25.5" 38"
(648mm) (965mm)
Monitoring
Panel
(Optional)
78.5"
(1994mm)
FDC14102
FRONT AND REAR VIEW RIGHT SIDE VIEW Rev. 0
NOTES
1. Weight: 750 lb. (340kg)
2. Heat Output: 3412 BTU/Hr (1kW)
3. Casters are removable
Height without casters: 77 in. (1956mm)
Liebert® FDC™ 6
Unpacking and Inspections
Figure 4 Typical 380-480V, 60Hz, cabinet and floor planning dimension data
TOP VIEW
BOTTOM
120° Door Swing VIEW Output
Conduit
Plates (2)
25.5" Monitoring 38"
(648mm) Panel (965mm)
(Optional)
78.5"
(1994mm)
FDC12025
FRONT AND REAR VIEW RIGHT SIDE VIEW Rev. 1
NOTES
1. Weight: 750 lb. (340kg)
2. Heat Output: 3412 BTU/Hr (1kW)
3. Casters are removable
Height without casters: 77 in. (1956mm)
7 Liebert® FDC™
Unpacking and Inspections
! WARNING
Exercise extreme care when handling the Liebert FDC to avoid equipment damage or injury
to personnel.
Risk of unit damage. Do not exceed a 15-degree tilt with the forklift.
2. Set the shipping pallet in a level area where there is enough room to roll the Liebert FDC off the
pallet onto the floor.
3. Cut the shipping bands.
! WARNING
The shipping bands may be under tension. Use appropriate eye, face and hand protection to
safeguard against injury from band backlash.
! WARNING
If moving the unit up a ramp on its casters or a pallet jack, ensure that the incline does not
exceed fifteen (15) degrees. Locate the center of gravity symbols and determine the unit’s
weight before handling the cabinet.
If you are moving the unit by forklift or pallet jack after it has been removed from the pallet,
be aware of the location of the casters and leveling feet so as not to damage them.
Before maneuvering the unit into its final position, read and follow all advisories in 3.0 - Locating
the Liebert FDC.
Liebert® FDC™ 8
Unpacking and Inspections
UNIT ON
SHIPPING
PALLET
Shipping
blocks
under each
corner
of unit
9 Liebert® FDC™
Locating the Liebert FDC
Minimum Clearance
of 18" (457mm)
is Recommended 78-1/2"
Above Unit for (1994mm)
Cooling Airflow
Minimum Clearance
of 6" (152mm) Cross-hatched
is Recommended areas indicate
Below Unit for recommended
Cooling Airflow clearance of
and Cable Exit 36" (914mm)
at right side
if Maintenance
38" Tie-Breaker
Cross-Hatched
(965mm) option is
Areas Indicate
supplied
Recommended
Clearance of
23.5" 1"
36" (914mm) at FDC12027
(597mm) (25mm)
Front and Rear Rev. 0
for Service Access SIDE PANEL
Liebert® FDC™ 10
Locating the Liebert FDC
11 Liebert® FDC™
Locating the Liebert FDC
23.3"
(591mm)
Nut
Jam Nut
36.9"
DETAIL A
(937mm)
TOP
20.1"
(510mm)
Liebert® FDC™ 12
Power and Control Wiring
! WARNING
Verify that all incoming line voltage (power) circuits are de-energized and locked out before
installing cables or making connections in the unit.
13 Liebert® FDC™
Power and Control Wiring
See Detail
1.75"
(44.5mm)
DETAIL BUSBAR
A B C N
Neutral Ground
GND
Distribution Cable
Conduit Plate
Input Cable Tray Contains
Connections 168 Holes for
Input Connections
1/2" (12.7mm) Conduit
(7/8" [22.2mm] Holes)
FRONT VIEW INPUT CONNECTIONS
(With Door and Panel Removed)
FDC13100
Rev. 0
0.562" 0.375"
(14.3mm) (9.5mm)
1.75"
(44.5mm) 1.103"
(28mm)
N N
A B C C B A
Neutral Ground
GND
Distribution Cable
Conduit Plate
Cable Tray Contains
Input 168 Holes For
Connections Input Connections
1/2" (12.7mm) Conduit
(7/8" [22.2mm] Holes)
FRONT VIEW INPUT CONNECTIONS
(With Door and Panel Removed) FDC13103
Rev. 0
Liebert® FDC™ 14
Power and Control Wiring
1.38"
(35mm)
SECTION AA 1/2 - 13 Stud
(Ground Busbar)
Hardware Supplied
A B C NB N C BB A
Neutral Ground
Ground
Distribution Cable
Busbar
Conduit Plate
Cable Tray Contains
Input 168 Holes for
Connections Input Connections
1/2" (12.7mm) Conduit
(7/8" [22.2mm] Holes)
FRONT VIEW INPUT CONNECTIONS FDC13106
(With Door and Panel Removed) (Typical Front & Rear Enlarged) Rev. 0
Ground
See
Detail
Main Main
Panelboard Panelboard
GND
Circuit Circuit
Breaker Breaker
A B C N
15 Liebert® FDC™
Power and Control Wiring
1.75"
(44.5mm)
Neutral Neutral 1.75" DETAIL BUSBAR
(44.5mm)
Ground
See Detail
Main Main
Panelboard
GND
Panelboard
Circuit Circuit
Breaker Breaker A B C C B A
N N
1/2 - 13 Stud
Hardware
Supplied
INPUT CONNECTIONS
FRONT VIEW FDC15102
(With Door and Panel Removed) Rev. 0
Distribution Cable
Conduit Plate M10 - 1.5 Customer Connections
Cable Tray Hardware
Contains 168 Holes 1.75"
Supplied (44.5mm)
for 1/2" (12.7mm) Conduit
(7/8" [22.2mm] Holes)
1.38"
Ground Ground (35mm)
Neutral Neutral SECTION AA
(Ground Busbar)
Ground
Main Main
Panelboard Panelboard
Circuit Circuit
Breaker Breaker
1/2 - 13 Stud
Hardware
Supplied INPUT CONNECTIONS
(Front & Rear Enlarged) FDC15104
FRONT VIEW
(With Door and Panel Removed) Rev. 0
Liebert® FDC™ 16
Power and Control Wiring
See Detail A
Input
Connections
Main Panelboard
Breakers Ground
White
Dot Neutral CT
(Optional)
See Note 1
Neutral
Neutral
CT
Distribution Cable
Conduit Plate
Cable Plates
Contain 84 Holes
DETAIL A for 1/2" Conduit
NOTES:
1. If neutral is supplied, cut wire-ties and remove CT With 7/8" (22mm)
from neutral terminal strip. Run input neutral Holes
cable through the CT and wire-tie the CT to the FRONT VIEW
cable. Install CT on the cable with the white dot (Door and Accent FDC16000
(see Detail A), facing the neutral terminal strip.
Panel Removed) Rev. 3
17 Liebert® FDC™
Power and Control Wiring
! WARNING
Verify that incoming line voltage circuits are de-energized and locked out before installing
output breakers and cables.
• All output cables and connections must comply with the NEC and all other applicable codes.
• All output cables without receptacles that are hard-wired to the load equipment must be equipped
with a padlock-off accessory for the output circuit breaker. The padlock-off accessory is used to
lock out and tag the circuit breaker while service is performed on the hard-wired load equipment
in accordance with OSHA safety rules.
Liebert® FDC™ 18
Power and Control Wiring
Fuses
Behind
Cover
TOP VIEW Current Plus
Monitoring
Assembly for
Panelboards
1 and 2
Front
See
Detail DETAIL A
B
DETAIL C
Current Plus Monitoring
Drawer Assembly
DETAIL D
DETAIL B
Current Plus Monitoring Adapter Board
on Back of Door FDC13550
Setup Connection
(See Figure 17 Rev. 0
FRONT & REAR VIEW DB9 Connector for Connection Details)
19 Liebert® FDC™
Power and Control Wiring
See Fuse
Detail
B
Current Plus
Monitoring Assembly
DETAIL A for Panelboards
1 and 2.
(Current Plus
Monitoring Assembly
DETAIL C
for Panelboards 3 and 4
Liebert LDMF Drawer Assembly
on Rear of Unit.)
See
Detail
A
DETAIL B DETAIL D
Current Plus Monitoring Setup Connection Current Plus Monitoring FDC15550
DB9 Connector Adapter Board on Back of Door Rev. 0
(See Figure 17 for
Connection Details)
Liebert® FDC™ 20
Power and Control Wiring
Figure 17 Current Plus Monitoring and Liebert LDMF communication and summary alarm connections
Modbus LDMF
RS-485 Summary Alarm
Shield
COM
NO
NC
+ -
LDM13006
Rev. 0
21 Liebert® FDC™
Power and Control Wiring
LDMF
Fuses
Behind
Cover
TOP VIEW
LDMF
Liebert Assembly for
IntelliSlot Panelboards
Bays; 1 And 2
To Install
Liebert IntelliSlot Front
Card, Remove DETAIL A
See and Discard Cover
Detail DETAIL C
B LDMF Drawer Assembly
DETAIL D
LDMF Adapter Board -
DETAIL B Located on Back of the Door
LDMF Setup Connection
DB9 Connector (See Figure 17
for Connection Details)
FDC13520
Rev. 0
FRONT & REAR VIEW
Liebert® FDC™ 22
Power and Control Wiring
Fuse
See
LDMF
Detail
Liebert Assembly for
B
IntelliSlot Panelboards
Bays; 1 and 2.
To Install LDMF
Liebert IntelliSlot Assembly for
DETAIL A
Card, Remove Panelboards
and Discard Cover 3 and 4 Located
on Rear of Unit.
DETAIL C
LDMF Drawer Assembly
See
Detail
A
DETAIL B
LDMF Setup DETAIL D
FRONT & REAR VIEW Connection FDC15520
LDMF Adapter Board -
DB9 Connector Rev. 0
Located on Back of the Door
(See Figure 17
for Connection Details)
23 Liebert® FDC™
Power and Control Wiring
See Input
Detail C Connections DETAIL B Interface Board
Liebert LDMF Setup Connection
Main Ground DB9 Connector
Panelboard
Breakers
Neutral
LDM Current
Sensors
Distribution Cable
Conduit Plate
Cable Plates DETAIL D
Contain 84 Holes Liebert LDMF Adapter
for 1/2” Conduit Board on Back of Door
With 7/8” (22mm) (See Figure 17 DETAIL E
Holes for Connection Details) Liebert LDMF Drawer Assembly
FRONT & REAR VIEW
(Door and Accent NOTES:
1. If neutral is supplied, cut wire-ties and remove CT from neutral terminal strip.
Panel Removed) FDC16100
Run input neutral cable through the CT and wire-tie the CT to the cable. Install
CT on the cable with the white dot (see Detail C), facing the neutral terminal strip. Rev. 0
Liebert® FDC™ 24
Power and Control Wiring
Figure 21 Connections for replacement Current Transformer (CT) for Liebert LDMF™ CT sensor module
Load Load
Item 2 Item 3
Replacement CT
(6 Places Typ.)
NOTES
1. Remove CT from the box. Route wiring from the transformer through the panel to the Liebert
LDMF control board.
2. Connect the CT connector to the proper panel location using the first available connection:
a. For Panelboard A, use P2(A1), P3(A2), P4(A3).
b. For Panelboard B, use P5(B1), P6(B2), P7(B3).
Ensure all routed wiring is properly secured to the panel with tie wraps.
3. The top piece of the current transformer (CT) is removable by pulling away from the center of
the transformer (Item 2).
4. Place the main body of the current transformer around the cable, making sure the CT is
installed in the direction shown (see Item 2).
5. Replace the top piece of the CT to complete securing the CT around the cable (see Item 3).
using the enclosed tie wraps to secure the CT to the cable.
! WARNING
Do not open-circuit the secondary windings of current transformers. Failure to
follow these instructions may result in serious injury or death.
25 Liebert® FDC™
Power and Control Wiring
See
Detail
A
Liebert SiteScan
Monitoring Interface
Located in
Liebert LDMF
TOP VIEW Remove Assembly for
Cover to Panelboards
Install 1 And 2 (see
Ethernet Cable Detail B)
Front
DETAIL A See Detail C DETAIL B
Liebert LDMF
Drawer Assembly
Access
Local
Expansion
ARCnet
Remote
10/100 Base T
Ethernet Port
Rnet
Xnet
Port
100 LAN LINK
BACnet
Rnet +
Xnet +
Shield
Rnet -
Xnet -
Net +
+12V
Net -
Gnd
Gnd
FDC13530
DETAIL C Rev. 0
FRONT & REAR VIEW
Liebert® FDC™ 26
Power and Control Wiring
Liebert SiteScan
Liebert SiteScan Monitoring
Monitoring Interface Interface
Located in
Remove Liebert LDMF
Cover to Assembly for
Install Panelboards
Ethernet Cable 1 And 2 (see
Detail B)
DETAIL A
See
Detail
B
DETAIL B
Access
Local
See Detail C
Liebert LDMF
Expansion Drawer Assembly
ARCnet
Remote
10/100 Base T
Ethernet Port
Rnet
Xnet
Port
100 LAN LINK
BACnet
Rnet +
Xnet +
Shield
Rnet -
Xnet -
Net +
+12V
Net -
Gnd
Gnd
See
Detail
A
FDC15530
DETAIL C Rev. 0
FRONT VIEW
27 Liebert® FDC™
Introduction to Liebert FDC Operations
Liebert® FDC™ 28
Equipment Inspection and Startup
! WARNING
Verify that all incoming power circuits are de-energized and locked out before performing the
internal inspection.
Gain access to the internal components of the Liebert FDC unit by removing the right side panel, if
supplied, and the interior panel.
29 Liebert® FDC™
Equipment Inspection and Startup
6.3 Startup
A qualified electrician should be employed to perform the equipment inspection and startup. System
startup may be arranged by calling your local Emerson sales representative or Liebert Services. In
the United States, call 1-800-LIEBERT (1-800-543-2378).
A copy of the appropriate checklist (furnished with the equipment) must be completed, signed, dated,
and returned to Emerson. Warranty coverage of the equipment is not effective unless the checklist is
received by the factory.
! WARNING
Equipment inspection and startup should be performed only by qualified trained personnel.
Electrical safety precautions must be followed throughout inspection and startup.
Hazardous voltages are present in the equipment throughout the majority of the startup
procedure. Use proper safety equipment. Proceed with caution.
Startup Checklist
___ 1. Make certain that all circuit breakers are in the OFF position and that power to the unit is
locked out.
___ 2. Verify proper input power connections to unit, including the equipment grounding conductor.
___ 3. Turn ON the building power to the unit.
___ 4. Check the phase rotation at the input terminal blocks. Phase rotation should be A, B, C,
left-to-right.
___ 5. Check and record the input voltage for each input. Measured voltages should correspond to
the unit’s nameplate input voltage.
Input 1 Input 2 Input 3 Input 4
Volts, phase A to phase B =
Volts, phase B to phase C =
Volts, phase C to phase A =
___ 6. Check the phase rotation at the panelboard main breakers. Phase rotation should be A, B, C,
left-to-right.
___ 7. Check and record the input voltage at each of the panelboard main breakers. Measured
voltages should correspond to the unit’s nameplate input voltage.
Panelboard 1 Panelboard 2 Panelboard 3 Panelboard 4
Volts, phase A to phase B =
Volts, phase B to phase C =
Volts, phase C to phase A =
If output voltage or phase rotation is incorrect, check for wiring errors or incorrect input
voltage, Contact Liebert Services at 1-800-LIEBERT (1-800-543-2378) in the USA or the local
factory representative for assistance.
___ 8. Turn ON the panelboard main breakers.
___ 9. Replace internal panel and side panels, if supplied.
Liebert® FDC™ 30
Equipment Inspection and Startup
PANEL 2 PANEL 2
L1
L2 180 L1
L2
L3 L3
H AMPS H
If the monitoring panel is not functioning properly, contact Liebert Services at 1-800-LIEBERT
(1-800-543-2378) in the USA or the local factory representative for assistance.
IX = XXXX IN = XXXX
IY = XXXX IG = XX.X
IZ = XXXX
s
F1 F2 F3 F4 HELP
If the monitoring panel is not functioning properly, contact Liebert Services at 1-800-LIEBERT
(1-800-543-2378) in the USA or the local factory representative for assistance.
31 Liebert® FDC™
Operating Instructions
Liebert® FDC™ 32
Operating Instructions
33 Liebert® FDC™
Maintenance
8.0 MAINTENANCE
! WARNING
Only qualified service personnel should perform maintenance on the Liebert FDC.
Lethal voltages exist inside the unit during normal operation.
The unit is supplied by multiple AC power sources. Disconnect and lock out all power sources
before working inside the unit.
Minimal periodic maintenance of the Liebert FDC is required. As with all electrical distribution
components, the system should be regularly inspected for electrical connection integrity, signs of
excessive temperatures, dirt accumulation and proper system operation.
Standard electrical troubleshooting procedures should be used to isolate problems in the unit.
If you have questions, don’t hesitate to contact Emerson Network Power® Liebert Services.
Repair or replacement of standard items, such as circuit breakers, can be either handled by
qualified electricians or referred to Liebert Services.
Repairs related to the monitoring system should be referred to Liebert Services.
To contact Liebert Services for information or repair service in the USA, call 1-800-LIEBERT
(1-800-543-2378).
Liebert® FDC™ 34
Specifications
9.0 SPECIFICATIONS
9.1 Frequency
The Liebert FDC accepts input frequencies of 50Hz and 60Hz. The frequency should be within ±0.5Hz
of the nominal frequency.
35 Liebert® FDC™
Specifications
9.7 Cooling
The unit is naturally convection-cooled. The convection cooling method allows continuous full-load
operation. Heat rejection is through a screened protective top that prohibits entry of foreign material.
9.8 Access
The Liebert FDC is designed so all repairs and maintenance can be performed with access to the
front, rear and top. (Units with optional side-mounted maintenance tie-breakers require front, rear
and right-side access). Retrofitting additional power distribution cables require access to the front or
rear of the unit only.
All power connections are designed to maintain proper connection torque over the lifetime of the unit
without any maintenance. The integrity of the connections can be checked via infrared scanning
safely from the front, rear or top of the unit.
9.10 Doors
The unit has lockable, removable, hinged, perforated front and rear doors that are 16-gauge sheet
metal construction with a perforated sheet metal insert to maximize ventilation. Doors provide access
to the main panelboard circuit breakers and to all output circuit breakers. Doors and panels are
finished in powder-coat black.
Liebert® FDC™ 36
Specifications
9.13 Monitoring
No monitoring is standard. Three options are available:
• Current Monitoring Panel
• Current Plus Monitoring
• Liebert Distribution Monitoring
See 9.14.1 - Current Monitoring Panel, 9.14.2 - Current Plus Monitoring, and 9.14.9 -
Liebert LDMF™ for details.
9.14 Options
The following options are available for the Liebert FDC:
37 Liebert® FDC™
Specifications
Liebert® FDC™ 38
Specifications
NOTES
39 Liebert® FDC™
Specifications
Liebert® FDC™ 40
Technical Support / Service
Web Site
www.liebert.com
Monitoring
liebert.monitoring@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
liebert.upstech@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
While every precaution has been taken to ensure the accuracy Fax: +39 049 5841 257
and completeness of this literature, Liebert Corporation assumes no Asia
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
29/F, The Orient Square Building
© 2014 Liebert Corporation F. Ortigas Jr. Road, Ortigas Center
All rights reserved throughout the world. Specifications subject to change Pasig City 1605
without notice. Philippines
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks +63 2 687 6615
or registered trademarks of their respective owners. Fax: +63 2 730 9572
SL-20402_REV5_12-15