Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Manual Usuario

Download as pdf or txt
Download as pdf or txt
You are on page 1of 48

Liebert® FDC™

User Manual
TABLE OF CONTENTS
SUPPORT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IV

IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1


1.0 SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.0 UNPACKING AND INSPECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.1 External Inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 Handling and Unloading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2.1 Handling Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2.2 Unloading the Unit from the Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 Internal Inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

3.0 LOCATING THE LIEBERT FDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10


3.1 Location Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.1.1 Recommended Minimum Service Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.1.2 Heat Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.1.3 Operating Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.2 Final Positioning of the Liebert FDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.2.1 Seismic Floor Stand (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

4.0 POWER AND CONTROL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13


4.1 Input Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.2 System Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.3 Output Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.4 Control Wiring Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.4.1 Current Plus Monitoring™—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.4.2 Liebert LDMF™—Optional. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

5.0 INTRODUCTION TO LIEBERT FDC OPERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28


5.1 System Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.2 Factory Backup and Service Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

6.0 EQUIPMENT INSPECTION AND STARTUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29


6.1 Exterior Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.2 Internal Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.3 Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
6.4 Current Monitoring Panel (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
6.5 Current Plus Monitoring™ (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
6.6 Liebert LDMF™—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
6.7 Liebert LDMF Display—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

i
7.0 OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.1 Startup Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.1.1 Normal System Turn ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.2 Normal System Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.3 Current Monitoring Panel (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.4 Current Plus Monitoring (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.5 Liebert LDMF™ (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

8.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8.1 Inspection & Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8.2 Inspection Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8.3 Proper Tightening of Nuts and Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

9.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35


9.1 Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9.2 Input/Output Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9.3 System Current Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9.4 Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9.5 Frame and Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9.6 Casters and Leveling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
9.7 Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
9.8 Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
9.9 Cable Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
9.10 Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
9.11 Main Panelboard Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
9.12 Distribution Panelboards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
9.13 Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
9.14 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
9.14.1 Current Monitoring Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
9.14.2 Current Plus Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
9.14.3 EZ-View Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
9.14.4 Solid Sheet Metal Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
9.14.5 Plug-In Main Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
9.14.6 Maintenance Tie-Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
9.14.7 Isolated Ground Busbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
9.14.8 65kAIC Main Panelboard Circuit Breaker (380-480V, 60Hz, units) . . . . . . . . . . . . . . . . . . . 37
9.14.9 Liebert LDMF™ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
9.14.10 Side Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
9.14.11 Export Crating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
9.14.12 Seismic Floor Stands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
9.14.13 65kAIC Main Panelboard Circuit Breaker (380-480V, 60Hz, units) . . . . . . . . . . . . . . . . . . . 38

ii
FIGURES
Figure 1 Typical bottom exit cabinet and floor planning dimension data . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 2 Typical tie-breaker bottom exit cabinet and floor planning dimension data. . . . . . . . . . . . . . . . . . 5
Figure 3 Typical top exit cabinet and floor planning dimension data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 4 Typical 380-480V, 60Hz, cabinet and floor planning dimension data . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 5 Shipping brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 6 Recommended minimum service and ventilation clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 7 Seismic floor stand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 8 Electrical field connections, 1 input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 9 Electrical field connections, 2 inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 10 Electrical field connections, 4 inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 11 Top exit electrical field connections, 1 input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 12 Top exit electrical field connections, 2 inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 13 Top exit electrical field connections, 4 inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 14 380-480V, 60Hz, electrical field connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 15 Current Plus Monitoring location - bottom exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 16 Current Plus Monitoring™ location - top exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 17 Current Plus Monitoring and Liebert LDMF communication and summary alarm
connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 18 Control connections for Liebert LDMF - bottom exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 19 Control connections for Liebert LDMF™ - top exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 20 Control connections for Liebert LDMF™ 380-480V, 60Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 21 Connections for replacement Current Transformer (CT) for Liebert LDMF™ CT sensor
module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 22 Connections to Liebert LDMF™ SiteScan® monitoring interface - bottom exit . . . . . . . . . . . . . . 26
Figure 23 Connections to Liebert LDMF™ SiteScan® monitoring interface - top exit . . . . . . . . . . . . . . . . . 27
Figure 24 Current Monitoring Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 25 Current Plus Monitoring panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

TABLES
Table 1 Torque tightening . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Table 2 Input/output voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 3 System current ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

iii
SUPPORT INFORMATION
If you require assistance for any reason:
• In the United States, call 1-800-LIEBERT (1-800-543-2378).
• Outside the 48 contiguous United States, contact Emerson Network Power Liebert Services, if
available in your area. For international areas not covered by Liebert Services, the Emerson
authorized distributor can provide qualified factory-authorized service.
Please have the following information available.
Model Number: ___________________________________________________________________
Serial Number: ___________________________________________________________________
Date Purchased: __________________________________________________________________
Date Installed: ____________________________________________________________________
Location: _________________________________________________________________________

iv
IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS


This manual contains important instructions that should be followed during the installation and
maintenance of the Liebert FDC.

! WARNING
The unit contains hazardous voltages when input source is on. To isolate the unit, turn OFF
and lock out the input power source.
Verify that the input power source is de-energized and locked out before installing cables or
making connections in the unit.
Lethal voltages exist inside the unit during normal operation. Only qualified service
personnel should perform maintenance on the Liebert FDC.

NOTE
Read the entire manual before installing or operating the system. Adhere to all operating
instructions and warnings on the unit and in this manual.
Emerson Network Power neither recommends nor knowingly sells this product for use with life
support or other FDA-designated “critical” devices.
The Liebert FDC is suitable for indoor use only. Protect the unit from excessive moisture and
install the unit in an area free from flammable liquids, gases and corrosive substances.
Provide input overcurrent protection in accordance with the unit ratings. Wire and ground the
unit according to national and local electrical safety codes. All wiring should be installed by a
qualified electrician.
Before the unit is placed into service for the first time, as well as after equipment relocation and
after the unit has been de-energized for an extended period of time, thorough equipment
inspection and supervised startup by qualified service personnel are strongly recommended.

! CAUTION
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J
of the FCC rules. These limits provide reasonable protection against harmful interference in a
commercial environment. This unit generates, uses and radiates radio frequency energy and,
if not installed and used in accordance with this instruction manual, may cause harmful
interference to radio communications. Operation of this unit in a residential area may cause
harmful interference that users must correct at their own expense.

! WARNING
Locate the center of gravity symbols and determine the unit’s weight before handling the
cabinet.

! WARNING
The shipping bands may be under tension. Use appropriate eye, face and hand protection to
safeguard against injury from band backlash.

NOTE
The unit should NOT be loosened from the shipping pallet until all handling by forklift or
pallet jack is completed.

1 Liebert® FDC™
Safety Precautions

1.0 SAFETY PRECAUTIONS


Read this manual thoroughly before working with the Liebert FDC.
Be sure to review the warnings under Important Safety Instructions on page 1.
Refer to 2.2.1 - Handling Considerations before attempting to move the unit.
Under typical operation and with the doors closed, only normal safety precautions are necessary. The
area around the Liebert FDC should be kept free from puddles of water, excess moisture and debris.
The areas in front and to the rear of the unit should be kept unobstructed to ensure a smooth airflow
through the unit for cooling.
ONLY qualified service personnel should perform maintenance on the Liebert FDC. When performing
maintenance on any part of the equipment under power, service personnel and test equipment should
be located on rubber mats. The service personnel should wear insulating shoes for isolation from
direct contact with the floor.
Unless all power is removed from the input source to the unit, one person should never work alone. A
second person should be on hand to assist and summon help, should an accident occur.

Liebert® FDC™ 2
Unpacking and Inspections

2.0 UNPACKING AND INSPECTIONS

NOTE
Read the entire manual before installing and operating the unit. Upon receipt of the Liebert
FDC, the installer should perform the following steps to ensure a high-quality installation.

A high-quality installation begins on the receiving dock. The Liebert FDC and its packaging should be
inspected when the unit is delivered. If the packaging is not damaged, unpack the unit and conduct
an internal inspection before beginning the installation process. This section discusses inspecting and
unpacking of the Liebert FDC.

2.1 External Inspections


1. Upon receipt and before unpacking, inspect the equipment and shipping material for any signs of
damage or mishandling. Do not attempt to install the system if damage is apparent.
2. Check the Shock-Watch™ indicator.
• If the indicator is red, note on shipper’s receipt and check for concealed damage.
• If any damage as a result of shipping is observed, file a damage claim with the shipper within
24 hours and contact your local Emerson representative or Emerson Network Power® Liebert
Services at 1-800-LIEBERT (1-800-543-2378) to report the damage claim and the condition of
the equipment.
3. Locate the bag containing the keys for the front and rear doors. The bag is attached to the cabinet.
4. Compare the contents of the shipment with the bill of lading. Report any missing items to the
carrier and to Liebert Services immediately.
5. Check the nameplate on the cabinets to verify that the model numbers correspond with the one
specified. Record the model number and serial number above under Support Information. A
record of this information is necessary should servicing be required.
6. If unit is to be stored before installation, it is recommended to store the unit in a dry environment
with temperatures in the range of -67°F (-55°C) to 185°F (85°C). Use original packing materials or
other suitable means to keep the unit clean. When removing the shipping material, use care not
to puncture the equipment with sharp objects.
If any damage as a result of shipping is observed: Immediately file a damage claim with the
shipping agency and forward a copy to:
Emerson Network Power
1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43229 USA

2.2 Handling and Unloading


2.2.1 Handling Considerations
The Liebert FDC is bolted to a wooden pallet to allow handling by a forklift, pallet jack or similar
equipment.
• Check size and weight. Refer to the outline drawings furnished with the unit for size and
weight information. Typical cabinet dimensions and weights are shown in Figures 1 and 2.
• Plan the route. The route that the unit will follow to its installation area should be planned to
ensure that all passages are large enough to accommodate the unit and that the floors are strong
enough to support the weight. Check all doorways, hallways elevators, ramps and other portions
of the route to determine if there are any obstructions and to ensure each is large enough and
strong enough to allow easy passage.
• Move with care. The Liebert FDC should be moved to the installation area on the wooden pallet
using forklift or pallet jack.
• Casters for easy movement. The unit is furnished with integral casters that allow the unit to
be rolled into place after it has reached its location and is removed from the pallet.

3 Liebert® FDC™
Unpacking and Inspections

Figure 1 Typical bottom exit cabinet and floor planning dimension data

17.3"
120° Door Swing
(439mm)
3.1" (79mm)

Input Landing Area


Minimum Clearance (18" x 9") 25.9"
of 36" (914mm) (457 x 229mm) (657mm)
is Recommended at
Front and Rear 5.3"
13.4" (135mm)
for Service Access
(340mm)

TOP VIEW BOTTOM


120° Door Swing
VIEW Output
Conduit
25.5" 38" Plates
Monitoring
(648mm) Panel (965mm)
(Optional)

78.5"
(1994mm)

FDC12107
FRONT AND REAR VIEW RIGHT SIDE VIEW
Rev. 0
NOTES
1. Weight: 750 lb. (340kg)
2. Heat Output: 3412 BTU/Hr (1kW)
3. Casters are removable
Height without casters: 77 in. (1956mm)

Liebert® FDC™ 4
Unpacking and Inspections

Figure 2 Typical tie-breaker bottom exit cabinet and floor planning dimension data

Minimum Clearance
120° Door Swing 17.3"
of 18" (457mm)
(439mm)
is Recommended 3.1" (79mm)
Above Unit for Input Landing
Cooling Airflow Area
18"x9"
(457x229mm) 25.9"
Minimum Clearance (657mm)
of 36" (914mm)
is Recommended at 5.3"
Front, Rear and Side 13.4" (135mm)
for Service Access (340mm)

TOP VIEW
BOTTOM
120° Door Swing VIEW

25.5" Monitoring 38"


(648mm) Panel (965mm)
(Optional)

Tie Breaker
Access Door

78.5"
(1994mm)

FDC12104
FRONT AND REAR VIEW RIGHT SIDE VIEW Rev. 1
NOTES
1. Weight: 750 lb. (340kg)
2. Heat Output: 3412 BTU/Hr (1kW)
3. Casters are removable
Height without casters: 77 in. (1956mm)

5 Liebert® FDC™
Unpacking and Inspections

Figure 3 Typical top exit cabinet and floor planning dimension data

Minimum Clearance 17.3"


of 18" (457mm) 120° Door Swing (439mm)
is Recommended 3.1" (79mm)
Input Conduit Plates
Above Unit for
12.8"x6.5"
Cooling Airflow
(325x165mm)
25.9"
Output Conduit
Minimum Clearance (657mm)
Plates
of 36" (914mm) 5.3"
is Recommended at 11.8" (135mm)
Front and Rear (300mm)
for Service Access
TOP VIEW BOTTOM
120° Door Swing VIEW

25.5" 38"
(648mm) (965mm)

Monitoring
Panel
(Optional)

78.5"
(1994mm)

FDC14102
FRONT AND REAR VIEW RIGHT SIDE VIEW Rev. 0
NOTES
1. Weight: 750 lb. (340kg)
2. Heat Output: 3412 BTU/Hr (1kW)
3. Casters are removable
Height without casters: 77 in. (1956mm)

Liebert® FDC™ 6
Unpacking and Inspections

Figure 4 Typical 380-480V, 60Hz, cabinet and floor planning dimension data

Minimum Clearance 17.3"


120° Door Swing
of 18" (457mm) (439mm)
is Recommended 3.1" (79mm)
Input Conduit
Above Unit for
Plates (4)
Cooling Airflow
5.9" x 4.9"
(150 x 125mm)
Minimum Clearance 25.9"
of 36" (914mm) (657mm)
Output
is Recommended at Conduit
Front and Rear 5.3"
Plates (4) 13.4" (135mm)
for Service Access
(340mm)

TOP VIEW
BOTTOM
120° Door Swing VIEW Output
Conduit
Plates (2)
25.5" Monitoring 38"
(648mm) Panel (965mm)
(Optional)

78.5"
(1994mm)

FDC12025
FRONT AND REAR VIEW RIGHT SIDE VIEW Rev. 1
NOTES
1. Weight: 750 lb. (340kg)
2. Heat Output: 3412 BTU/Hr (1kW)
3. Casters are removable
Height without casters: 77 in. (1956mm)

7 Liebert® FDC™
Unpacking and Inspections

2.2.2 Unloading the Unit from the Pallet


The Liebert FDC may be easily removed from the shipping pallet and installed by customer
personnel. A typical procedure is as follows:
1. Move the unit on the shipping pallet as close to the final location as possible.

! WARNING
Exercise extreme care when handling the Liebert FDC to avoid equipment damage or injury
to personnel.
Risk of unit damage. Do not exceed a 15-degree tilt with the forklift.

2. Set the shipping pallet in a level area where there is enough room to roll the Liebert FDC off the
pallet onto the floor.
3. Cut the shipping bands.

! WARNING
The shipping bands may be under tension. Use appropriate eye, face and hand protection to
safeguard against injury from band backlash.

4. Remove the factory-provided ramp from its shipping


position. One ramp is provided per order, packed UNIT ON
either in front or to the rear of the unit. Place the SHIPPING
ramp adjacent to the pallet to provide a smooth path PALLET
from pallet to floor.
5. Remove the packing material and inspect the
equipment for any obvious shipping damage. Use
care to avoid puncturing the packing material with
sharp objects that would damage the unit. Make
sure cardboard is removed from top of the unit.
6. If the unit is supplied with side panels, remove side
panels. Remove the two shipping brackets used to
Shipping
hold the unit to the shipping pallet. The brackets are blocks
located on each side of the unit, as shown in under each
Figure 5. Remove the three bolts that attach the corner
bracket to the pallet, then remove the two bolts of unit
located under the frame that attach the bracket to
the unit. Brackets and bolts should be saved in case
the unit is relocated in the future.
7. Remove the shipping blocks from under the unit
frame. Extend the leveling feet or use a forklift to Ramp
raise the unit off the blocks. Ensure that the forklift
is clear of the unit’s caster and leveling feet. Lift the unit from the side. Raise the leveling feet (if
lowered).
8. Roll the unit off the pallet onto the floor.
9. Reattach the side panels if supplied
10. Roll the unit to the location of installation. If placing the unit on a raised floor, use care when
positioning the unit over the floor cutout to prevent casters from falling through the cutout.

! WARNING
If moving the unit up a ramp on its casters or a pallet jack, ensure that the incline does not
exceed fifteen (15) degrees. Locate the center of gravity symbols and determine the unit’s
weight before handling the cabinet.
If you are moving the unit by forklift or pallet jack after it has been removed from the pallet,
be aware of the location of the casters and leveling feet so as not to damage them.
Before maneuvering the unit into its final position, read and follow all advisories in 3.0 - Locating
the Liebert FDC.

Liebert® FDC™ 8
Unpacking and Inspections

Figure 5 Shipping brackets

UNIT ON
SHIPPING
PALLET

Shipping
blocks
under each
corner
of unit

Bracket and bolts


securing unit to pallet

2.3 Internal Inspections


After the Liebert FDC has been unpacked, conduct an internal inspection:
1. Verify that all items have been received.
2. Open the doors and panelboard accent panels and remove the side panels to check for shipping
damage to internal components.
3. Check for loose connections or unsecured components in the cabinet.
4. Check for any unsafe condition that may be a potential safety hazard.
After the Liebert FDC has been inspected and no problems are found, the unit can be moved to its
installation location. If using a forklift, remember to lift the unit from the side. Ensure that the
forklift is clear of the unit’s casters and leveling feet.

9 Liebert® FDC™
Locating the Liebert FDC

3.0 LOCATING THE LIEBERT FDC


3.1 Location Considerations
The Liebert FDC should be placed in a clean, cool and dry location. The unit should be located within
the data center and/or close to any loads that it is supplying. The Liebert FDC requires front and rear
access for installation and maintenance. Units with optional Maintenance Tie-Breakers require front,
rear and right-side access. If bottom cable exit is used, sufficient cable bending space must be
provided by a raised floor.
Equipment Location should employ the shortest output distribution cable runs consistent with
logical equipment arrangement and allowances for future additions.
Units with bottom cable/conduit exit require bottom clearance for entry and exit of cables/conduits
and for air intake. This clearance is automatically provided by a raised floor with a minimum height
of 12 in. (305mm).
Minimum of 18 in. (457mm) clearance above the unit is required for cooling air exhaust.
Units with top cable/conduit exit require top clearance for entry and exit of cables/conduits and for
cooling air exhaust.
3.1.1 Recommended Minimum Service Clearances
Recommended minimum service clearances are shown in Figure 6. The indicated clearances at the front
and rear of the unit are required by the National Electrical Code (NEC) for service access. If optional
Maintenance Tie-Breakers are supplied, right-side access is also required by the NEC for service
access.
Figure 6 Recommended minimum service and ventilation clearances

Minimum Clearance
of 18" (457mm)
is Recommended 78-1/2"
Above Unit for (1994mm)
Cooling Airflow

Minimum Clearance
of 6" (152mm) Cross-hatched
is Recommended areas indicate
Below Unit for recommended
Cooling Airflow clearance of
and Cable Exit 36" (914mm)
at right side
if Maintenance
38" Tie-Breaker
Cross-Hatched
(965mm) option is
Areas Indicate
supplied
Recommended
Clearance of
23.5" 1"
36" (914mm) at FDC12027
(597mm) (25mm)
Front and Rear Rev. 0
for Service Access SIDE PANEL

Liebert® FDC™ 10
Locating the Liebert FDC

3.1.2 Heat Output


As with all electrical devices, the Liebert FDC produces heat under normal operation. The maximum
heat output is 3412 BTU/hr (1 kWH). This heat output should be included when calculating the
environmental conditions of the room.

3.1.3 Operating Environment


The unit is designed to be installed indoors where the ambient air temperature is in the range of 32°F
to 104°F (0°C to 40°C) with a relative humidity of 0% to 95% (non-condensing).
Operating altitude up to 6,600 ft. (2000m) above Mean Sea Level.
Audible noise under normal operation shall not exceed 45dBA measured 5 ft. (1.5m) from the surface
of the Liebert FDC.

3.2 Final Positioning of the Liebert FDC


Set the Liebert FDC in final position. The Liebert FDC is furnished with casters and leveling feet.
After final positioning of the unit, adjust the leveling feet, located in each corner of the frame base, to
level and stabilize the unit. For additional stability, the Liebert FDC should be bolted to the floor.

3.2.1 Seismic Floor Stand (Optional)


1. Unpack the floor stand from the pallet and place in its final position. Adjust the leveling feet,
located in each corner of the floor stand base, to level and stabilize the floor stand.
2. To adjust the height of the feet, loosen the top nut and adjust the bottom nut to desired height.
Tighten the top nut and jam nut to specified torque (shown in detail A and B in Figure 7).
3. Use 1/2" red head concrete anchors to mount the floor stand to a concrete surface (supplied by
customer).
4. Disassemble mounting brackets from the floor stand. Roll the Liebert FDC onto the floor stand or
use a forklift to raise the unit off the floor and onto the floor stand. Ensure that the forklift is clear
of the unit's caster and leveling feet. Lift the unit from the side.
5. Align the Liebert FDC on top of the floor stand and then reinstall mounting brackets (see detail C
in Figure 7).
6. Check all hardware for proper torque prior to installation. Reference hardware torque chart in
Figure 7.

11 Liebert® FDC™
Locating the Liebert FDC

Figure 7 Seismic floor stand

23.3"
(591mm)

Nut
Jam Nut

36.9"
DETAIL A
(937mm)

TOP

20.1"
(510mm)

See Detail C See Detail B

See Detail A FRONT


22.9" Ø 0.625"
(584mm) (16mm)
TYP.
2.47"
(63mm)
TYP. Nut
36.6"
29.5" (930mm)
(750mm) Detail B
3.53"
(90mm) DETAIL C
TYP. Notes:
1. Disassemble mounting brackets from floor stand. Align unit
6.2" on top of floor stand and then reinstall mounting brackets
2.47" (See Detail C).
(157mm) 2. Check all hardware for proper torque prior to installation.
(63mm) 10.5" TYP. Refer to hardware torque chart.
TYP. (266.7mm) 3. To adjust vertical height of feet, loosen top nut and adjust
bottom nut to desired height. Tighten top nut to specified
BOTTOM torque and jam nut shown in foot Details A and B.
4. 1/2" red head concrete anchors that mount floor stand to
concrete surface must be supplied by the customer.
FPC17000
Rev. 1
HARDWARE TORQUE HEIGHT TABLE
CHART
HEIGHT RATING HEIGHT MAX HEIGHT MIN
1.0" NUT 320 FT-LBS
18.0" 19.25" 16.75"
M8-1.25 16 FT-LBS
24.0" 25.25" 22.75"
M10-1.5 31 FT-LBS
30.0" 31.25" 28.75"
M12-1.75 53 FT-LBS
36.0" 37.25" 34.75"

Liebert® FDC™ 12
Power and Control Wiring

4.0 POWER AND CONTROL WIRING


A qualified electrician should install all power and control wiring. All power and control wiring must
comply with the NEC and applicable local codes. Unless otherwise labeled, use the recommended
tightening torque as shown in Table 1.
Cables can be installed through the top on top entry/exit units or through the bottom on bottom entry/
exit through removable conduit plates. See Figures 1, 3 and 4 for wiring entrance locations.
The input power connections are made to the power blocks and/or busbars provided inside the unit.
These power blocks/busbars are accessible through the front and rear of the unit. Output power
connections are made to the panelboard breakers, ground and neutral busbars. The ground and
neutral busbars are accessible through the front and rear of the unit. See Figures 8 through 14 for
details on the busbars.

! WARNING
Verify that all incoming line voltage (power) circuits are de-energized and locked out before
installing cables or making connections in the unit.

4.1 Input Power Connections


1. Remove the front and rear doors and the right side external panel, if supplied.
2. For bottom cable exit units:
a. Remove the internal side panel, if side access is available, and panelboard accent panels.
b. Remove the front and rear lower accent plates.
3. For top cable exit units, remove the panelboard accent panels.
4. Remove the front and rear clear Plexiglas input power terminal block and busbar covers.
5. Remove front and rear output conduit plates.
6. Remove input conduit tray and punch to match number and size of input conduit(s).
7. Replace input conduit tray and attach input conduit(s).
8. Connect input power cables to the input terminal blocks and/or busbars located in the bottom for
bottom cable exit unit or top for top cable exit unit. (See Figures 8 through 14 and the electrical
field connection drawing supplied with the unit for details.)
To minimize disturbances caused by other loads in the building, the 3-phase power input to the unit
should be supplied directly from a dedicated power source.
The input feeder circuit should be sized in accordance with the NEC and any local building codes to
ensure the feeder’s ability to safely carry the system’s full load current, including losses.
Input feeder conductors should be sized for no more than 2% voltage drop. If operation at
undervoltage conditions for extended periods of time is desired, the input feeders must be oversized.
The main input feeder must consist of 3-phase conductors and one neutral and one (safety) ground
conductor (4W + G). If the unit has optional isolated ground busbars, then an isolated ground must be
supplied with the input feeder.

13 Liebert® FDC™
Power and Control Wiring

Figure 8 Electrical field connections, 1 input


0.562" 0.375"
1.75" (14.3mm) (9.5mm)
(44.5mm)
1.103"
(28mm)

See Detail
1.75"
(44.5mm)
DETAIL BUSBAR

A B C N

Neutral Ground
GND
Distribution Cable
Conduit Plate
Input Cable Tray Contains
Connections 168 Holes for
Input Connections
1/2" (12.7mm) Conduit
(7/8" [22.2mm] Holes)
FRONT VIEW INPUT CONNECTIONS
(With Door and Panel Removed)
FDC13100
Rev. 0

Figure 9 Electrical field connections, 2 inputs

0.562" 0.375"
(14.3mm) (9.5mm)
1.75"
(44.5mm) 1.103"
(28mm)

1/2 - 13 Stud See Detail


1.75" Hardware Supplied
(44.5mm)
DETAIL BUSBAR

N N
A B C C B A

Neutral Ground
GND
Distribution Cable
Conduit Plate
Cable Tray Contains
Input 168 Holes For
Connections Input Connections
1/2" (12.7mm) Conduit
(7/8" [22.2mm] Holes)
FRONT VIEW INPUT CONNECTIONS
(With Door and Panel Removed) FDC13103
Rev. 0

Liebert® FDC™ 14
Power and Control Wiring

Figure 10 Electrical field connections, 4 inputs


M10 - 1.5 Customer Connections
Hardware
1.75"
Supplied
(44.5mm)

1.38"
(35mm)
SECTION AA 1/2 - 13 Stud
(Ground Busbar)
Hardware Supplied

A B C NB N C BB A

Neutral Ground
Ground
Distribution Cable
Busbar
Conduit Plate
Cable Tray Contains
Input 168 Holes for
Connections Input Connections
1/2" (12.7mm) Conduit
(7/8" [22.2mm] Holes)
FRONT VIEW INPUT CONNECTIONS FDC13106
(With Door and Panel Removed) (Typical Front & Rear Enlarged) Rev. 0

Figure 11 Top exit electrical field connections, 1 input

Distribution Cable 0.562" 0.375"


Conduit Plate (14.3mm) (9.5mm)
Cable Tray Contains
168 Holes for 1/2" (12.7mm) 1.103"
Conduit (7/8" [22.2mm] Holes) (28mm)
Ground
Ground
1.75"
(44.5mm)
Neutral Neutral 1.75"
(44.5mm)

Ground
See
Detail
Main Main
Panelboard Panelboard
GND
Circuit Circuit
Breaker Breaker

A B C N

FRONT VIEW INPUT CONNECTIONS FDC15100


(With Door and Panel Removed) Rev. 0

15 Liebert® FDC™
Power and Control Wiring

Figure 12 Top exit electrical field connections, 2 inputs

Distribution Cable Conduit Plate


0.562" 0.375"
Cable Tray Contains 168 Holes for
Input Connections 1/2" (12.7mm) Conduit (14.3mm) (9.5mm)
(7/8" [22.2mm] Holes) 1.103"
(28mm)
Ground Ground

1.75"
(44.5mm)
Neutral Neutral 1.75" DETAIL BUSBAR
(44.5mm)
Ground
See Detail
Main Main
Panelboard
GND
Panelboard
Circuit Circuit
Breaker Breaker A B C C B A
N N

1/2 - 13 Stud
Hardware
Supplied
INPUT CONNECTIONS
FRONT VIEW FDC15102
(With Door and Panel Removed) Rev. 0

Figure 13 Top exit electrical field connections, 4 inputs

Distribution Cable
Conduit Plate M10 - 1.5 Customer Connections
Cable Tray Hardware
Contains 168 Holes 1.75"
Supplied (44.5mm)
for 1/2" (12.7mm) Conduit
(7/8" [22.2mm] Holes)
1.38"
Ground Ground (35mm)
Neutral Neutral SECTION AA
(Ground Busbar)
Ground

Main Main
Panelboard Panelboard
Circuit Circuit
Breaker Breaker

1/2 - 13 Stud
Hardware
Supplied INPUT CONNECTIONS
(Front & Rear Enlarged) FDC15104
FRONT VIEW
(With Door and Panel Removed) Rev. 0

Liebert® FDC™ 16
Power and Control Wiring

Figure 14 380-480V, 60Hz, electrical field connections


Distribution Cable Conduit Plate
Cable Plates Contain 84 Holes
for 1/2" Conduit
With 7/8" (22mm) Holes

See Detail A
Input
Connections

Main Panelboard
Breakers Ground

White
Dot Neutral CT
(Optional)
See Note 1
Neutral

Neutral
CT

Distribution Cable
Conduit Plate
Cable Plates
Contain 84 Holes
DETAIL A for 1/2" Conduit
NOTES:
1. If neutral is supplied, cut wire-ties and remove CT With 7/8" (22mm)
from neutral terminal strip. Run input neutral Holes
cable through the CT and wire-tie the CT to the FRONT VIEW
cable. Install CT on the cable with the white dot (Door and Accent FDC16000
(see Detail A), facing the neutral terminal strip.
Panel Removed) Rev. 3

17 Liebert® FDC™
Power and Control Wiring

4.2 System Grounding


Equipment grounding - Grounding is primarily for equipment and personnel safety, although
proper grounding also enhances equipment performance.
All input and output power feeds must include an equipment grounding means as required by the
NEC and local codes.
An insulated equipment ground conductor is recommended to run with each input and output power
feed. The equipment ground conductors should be at least the minimum size conductor per the NEC
based on the upstream overcurrent protection device.
Isolated ground - If the unit is supplied with optional output panelboard isolated ground busbars,
connect the isolated ground conductor from the load cable to the panelboard isolated ground busbar.

4.3 Output Power Connections


Output panelboards with ground and neutral provisions are provided inside the unit for connecting
loads as required (see Figures 8, 9 and 10).
Flexible output distribution cables are used in data processing areas under a raised floor. Cable
lengths and layout should be well planned:
• Cable routes should follow aisles between equipment. This will facilitate access to cables for
installation, routine inspection, and future changes.
• Determine the required cable length by measuring the distance to the load equipment following
right-angle paths, rather than diagonally or directly. Always measure to the extreme far side of
the equipment with respect to the unit to insure adequate cable length.
• Prevent restriction of airflow under the raised floor by running the flexible conduits flat on the
subfloor in parallel paths.
• Balancing of loads across the three phases is good design practice on any 3-phase system.

! WARNING
Verify that incoming line voltage circuits are de-energized and locked out before installing
output breakers and cables.

• All output cables and connections must comply with the NEC and all other applicable codes.
• All output cables without receptacles that are hard-wired to the load equipment must be equipped
with a padlock-off accessory for the output circuit breaker. The padlock-off accessory is used to
lock out and tag the circuit breaker while service is performed on the hard-wired load equipment
in accordance with OSHA safety rules.

Liebert® FDC™ 18
Power and Control Wiring

4.4 Control Wiring Connections


No control wiring is needed on the standard Liebert FDC. Only the optional Current Plus Monitoring
(CPM) and Liebert Distribution Monitoring™ (LDMF) require external control wiring.

4.4.1 Current Plus Monitoring™—Optional


If the optional Current Plus Monitoring is supplied, remote communication and Summary Alarm
connections are available. Current Plus Monitoring is supplied with three Liebert IntelliSlot™ bays.
Three Liebert IntelliSlot cards can be added for customer connection to a Building Management
System (BMS). Current Plus Monitoring can communicate to Liebert SiteScan™ using an RS-485
connection on the adapter board.
See Figures 15 and 17 for location and connection details.

Figure 15 Current Plus Monitoring location - bottom exit

See Current Plus


Detail Monitoring Interface Board
A Assembly for
Panelboards
3 and 4

Fuses
Behind
Cover
TOP VIEW Current Plus
Monitoring
Assembly for
Panelboards
1 and 2
Front
See
Detail DETAIL A
B
DETAIL C
Current Plus Monitoring
Drawer Assembly

DETAIL D
DETAIL B
Current Plus Monitoring Adapter Board
on Back of Door FDC13550
Setup Connection
(See Figure 17 Rev. 0
FRONT & REAR VIEW DB9 Connector for Connection Details)

19 Liebert® FDC™
Power and Control Wiring

Figure 16 Current Plus Monitoring™ location - top exit


Interface
Board

See Fuse
Detail
B

Current Plus
Monitoring Assembly
DETAIL A for Panelboards
1 and 2.
(Current Plus
Monitoring Assembly
DETAIL C
for Panelboards 3 and 4
Liebert LDMF Drawer Assembly
on Rear of Unit.)
See
Detail
A

FRONT & REAR VIEW

DETAIL B DETAIL D
Current Plus Monitoring Setup Connection Current Plus Monitoring FDC15550
DB9 Connector Adapter Board on Back of Door Rev. 0
(See Figure 17 for
Connection Details)

Liebert® FDC™ 20
Power and Control Wiring

Figure 17 Current Plus Monitoring and Liebert LDMF communication and summary alarm connections

Modbus LDMF
RS-485 Summary Alarm

Shield

COM
NO
NC
+ -

LDM13006
Rev. 0

21 Liebert® FDC™
Power and Control Wiring

4.4.2 Liebert LDMF™—Optional


Remote communication is available if the optional Liebert LDMF is supplied. The Liebert LDMF has
three Liebert IntelliSlot™ bays. Three Liebert IntelliSlot cards can be added for customer connection
to a Building Management System (BMS). The Liebert LDMF will communicate to Liebert SiteScan®
using the Liebert SiteScan Monitoring Interface option.
See Figures 18, 19, 22 and 23 for location and connection details.

Figure 18 Control connections for Liebert LDMF - bottom exit

See LDMF Interface Board


Detail A Assembly for
Panelboards
3 And 4

LDMF
Fuses
Behind
Cover
TOP VIEW
LDMF
Liebert Assembly for
IntelliSlot Panelboards
Bays; 1 And 2
To Install
Liebert IntelliSlot Front
Card, Remove DETAIL A
See and Discard Cover
Detail DETAIL C
B LDMF Drawer Assembly

DETAIL D
LDMF Adapter Board -
DETAIL B Located on Back of the Door
LDMF Setup Connection
DB9 Connector (See Figure 17
for Connection Details)
FDC13520
Rev. 0
FRONT & REAR VIEW

Liebert® FDC™ 22
Power and Control Wiring

Figure 19 Control connections for Liebert LDMF™ - top exit


Interface Board

Fuse

See
LDMF
Detail
Liebert Assembly for
B
IntelliSlot Panelboards
Bays; 1 and 2.
To Install LDMF
Liebert IntelliSlot Assembly for
DETAIL A
Card, Remove Panelboards
and Discard Cover 3 and 4 Located
on Rear of Unit.

DETAIL C
LDMF Drawer Assembly

See
Detail
A

DETAIL B
LDMF Setup DETAIL D
FRONT & REAR VIEW Connection FDC15520
LDMF Adapter Board -
DB9 Connector Rev. 0
Located on Back of the Door
(See Figure 17
for Connection Details)

23 Liebert® FDC™
Power and Control Wiring

Figure 20 Control connections for Liebert LDMF™ 380-480V, 60Hz


Liebert IntelliSlot Ports
To Install Liebert IntelliSlot
See Card, Remove and White
Detail Discard Cover Dot
A Liebert
LDMF
Fuses
Behind Liebert
Cover LDMF
Assembly for Neutral
Panelboards CT
TOP VIEW 1 and 2
(Center Vent
See Panel Removed)
Detail B Front DETAIL C
DETAIL A

See Input
Detail C Connections DETAIL B Interface Board
Liebert LDMF Setup Connection
Main Ground DB9 Connector
Panelboard
Breakers

Neutral
LDM Current
Sensors

Distribution Cable
Conduit Plate
Cable Plates DETAIL D
Contain 84 Holes Liebert LDMF Adapter
for 1/2” Conduit Board on Back of Door
With 7/8” (22mm) (See Figure 17 DETAIL E
Holes for Connection Details) Liebert LDMF Drawer Assembly
FRONT & REAR VIEW
(Door and Accent NOTES:
1. If neutral is supplied, cut wire-ties and remove CT from neutral terminal strip.
Panel Removed) FDC16100
Run input neutral cable through the CT and wire-tie the CT to the cable. Install
CT on the cable with the white dot (see Detail C), facing the neutral terminal strip. Rev. 0

Liebert® FDC™ 24
Power and Control Wiring

Figure 21 Connections for replacement Current Transformer (CT) for Liebert LDMF™ CT sensor module

Connection Location for CT Module


6 Replacement CTs.
Indicates Pin 1.
Connect CT White Wire to Pin 1
Connect CT Black Wire to Pin 2

Power Source Power Source


Branch Circuit Branch Circuit

Load Load

Item 2 Item 3

Replacement CT
(6 Places Typ.)

Panelboard A Panelboard B LDM13004


DETAIL A Rev. 0

NOTES
1. Remove CT from the box. Route wiring from the transformer through the panel to the Liebert
LDMF control board.
2. Connect the CT connector to the proper panel location using the first available connection:
a. For Panelboard A, use P2(A1), P3(A2), P4(A3).
b. For Panelboard B, use P5(B1), P6(B2), P7(B3).
Ensure all routed wiring is properly secured to the panel with tie wraps.
3. The top piece of the current transformer (CT) is removable by pulling away from the center of
the transformer (Item 2).
4. Place the main body of the current transformer around the cable, making sure the CT is
installed in the direction shown (see Item 2).
5. Replace the top piece of the CT to complete securing the CT around the cable (see Item 3).
using the enclosed tie wraps to secure the CT to the cable.

! WARNING
Do not open-circuit the secondary windings of current transformers. Failure to
follow these instructions may result in serious injury or death.

25 Liebert® FDC™
Power and Control Wiring

Figure 22 Connections to Liebert LDMF™ SiteScan® monitoring interface - bottom exit


Liebert SiteScan
Monitoring
Interface

See
Detail
A

Liebert SiteScan
Monitoring Interface
Located in
Liebert LDMF
TOP VIEW Remove Assembly for
Cover to Panelboards
Install 1 And 2 (see
Ethernet Cable Detail B)
Front
DETAIL A See Detail C DETAIL B
Liebert LDMF
Drawer Assembly

Access
Local

Expansion
ARCnet

Remote
10/100 Base T
Ethernet Port

Rnet

Xnet
Port
100 LAN LINK

BACnet

Rnet +

Xnet +
Shield

Rnet -

Xnet -
Net +

+12V
Net -

Gnd

Gnd

FDC13530
DETAIL C Rev. 0
FRONT & REAR VIEW

Liebert® FDC™ 26
Power and Control Wiring

Figure 23 Connections to Liebert LDMF™ SiteScan® monitoring interface - top exit

Liebert SiteScan
Liebert SiteScan Monitoring
Monitoring Interface Interface
Located in
Remove Liebert LDMF
Cover to Assembly for
Install Panelboards
Ethernet Cable 1 And 2 (see
Detail B)
DETAIL A

See
Detail
B

DETAIL B
Access
Local

See Detail C
Liebert LDMF
Expansion Drawer Assembly
ARCnet

Remote
10/100 Base T
Ethernet Port

Rnet

Xnet
Port
100 LAN LINK

BACnet

Rnet +

Xnet +
Shield

Rnet -

Xnet -
Net +

+12V
Net -

Gnd

Gnd

See
Detail
A

FDC15530
DETAIL C Rev. 0
FRONT VIEW

27 Liebert® FDC™
Introduction to Liebert FDC Operations

5.0 INTRODUCTION TO LIEBERT FDC OPERATIONS

5.1 System Description


The Liebert FDC is designed to provide additional distribution capacity. The unit can be furnished
with one, two, three or four panelboards. While most units are supplied with four panelboards, you
have the option of ordering fewer to suit your needs and applications.
The Liebert FDC contains vertically mounted Square D or GE panelboards for distribution to the
intended loads. Panelboards can be supplied to use either bolt-in or plug-in type branch circuit
breakers. The unit is designed to have two panelboards that can be accessed from the front of the unit
and two panelboards that be accessed from the rear of the unit. Each panelboard is totally enclosed
with a hinged accent panel that provides access to that panelboard without exposing other portions of
the unit. The panelboard has a rating of 225 amperes for 208V, 380-415V, 50Hz, and 400 amperes for
380-480V, 60Hz, with an overall short-circuit current rating of 22kA RMS (208-240V), 35kA
(380-480V, 60Hz) symmetrical amperes. Panelboards can be rated for 65kA (380-480V, 60Hz) when
the optional 65kA main breaker is used (not available at 380-415V, 50Hz). Each panelboard provides
42 single-pole branch circuit breaker positions. Each panelboard includes separate isolated neutral
and safety-ground busbars for the neutral and safety-ground connections for at least 42 output
circuits. The neutral busbar and wiring are sized for at least 1.73 times the panelboard full load
rating to accommodate high harmonic neutral currents associated with single-phase nonlinear loads.
Each distribution panelboard is protected by a main panelboard circuit breaker. The breaker is UL
listed and IEC rated for use at the system voltage. The main panelboard circuit breaker has a rating
of 225A or 400A with an overall short-circuit current rating of 22kA or 35kA RMS symmetrical
amperes. Optional main panelboard breakers are available rated for 65kA (380-480V, 60Hz) RMS
symmetrical amperes (not available at 380-415V, 50Hz).
Monitoring can be supplied, as an option, to monitor current parameters (Current Monitoring Panel)
or voltage, current and power parameters; two options are available Current Plus Monitoring or
Liebert LDMF. Front and rear displays are provided with push-button switches for operator interface
on some options.
Remote communication is available only on the Current Plus and Liebert LDMF options, which
provide external communication through Liebert IntelliSlot cards: IS-UNITY-DP card for
HTTP/HTTPS, Emerson® Protocol, e-mail, SMS, SNMP v1/v2c/v3, BACnet IP/MSTP and Modbus
TCP/RTU output using a serial RS-485 two-wire connection.

5.2 Factory Backup and Service Assistance


Because improper installation can cause a system to fail, a Liebert Services or factory-trained service
technician should thoroughly inspect the unit to ensure it is properly installed and its operating
parameters are properly configured.
If you need assistance or have questions:
• In the United States, call 1-800-LIEBERT (1-800-543-2378).
• Outside the 48 contiguous United States contact Liebert Services, if available in your area. For
international areas not covered by Liebert Services, the Emerson authorized distributor can pro-
vide technical support.

Liebert® FDC™ 28
Equipment Inspection and Startup

6.0 EQUIPMENT INSPECTION AND STARTUP

6.1 Exterior Inspection


Exterior Inspection Checklist
___ 1. Confirm that the exterior of the unit is undamaged.
___ 2. Confirm that service and ventilation clearances are adequate. (See Figure 6).

6.2 Internal Inspection


A detailed internal inspection should be performed after the unit is in place and before it is energized,
to insure trouble-free startup. The same internal inspection should be carried out when performing
preventive maintenance.

! WARNING
Verify that all incoming power circuits are de-energized and locked out before performing the
internal inspection.

Gain access to the internal components of the Liebert FDC unit by removing the right side panel, if
supplied, and the interior panel.

Interior Inspection Checklist


___ 1. Inspect all wire and conductor insulation for damage.
___ 2. Check all breaker connections for tightness. Retorque if necessary. Unless otherwise labeled,
use the recommended tightening torque as shown in Table 1.
___ 3. Check trip settings of adjustable breakers.
___ 4. Check all terminal block connections for tightness. Retorque if necessary. Unless otherwise
labeled, use the recommended tightening torque as shown in Table 1.
___ 5. Remove any foreign objects from the components or the interior area of the unit.
___ 6. Check that the exhaust air screen is clean and free of obstructions.

29 Liebert® FDC™
Equipment Inspection and Startup

6.3 Startup
A qualified electrician should be employed to perform the equipment inspection and startup. System
startup may be arranged by calling your local Emerson sales representative or Liebert Services. In
the United States, call 1-800-LIEBERT (1-800-543-2378).
A copy of the appropriate checklist (furnished with the equipment) must be completed, signed, dated,
and returned to Emerson. Warranty coverage of the equipment is not effective unless the checklist is
received by the factory.

! WARNING
Equipment inspection and startup should be performed only by qualified trained personnel.
Electrical safety precautions must be followed throughout inspection and startup.
Hazardous voltages are present in the equipment throughout the majority of the startup
procedure. Use proper safety equipment. Proceed with caution.

Startup Checklist
___ 1. Make certain that all circuit breakers are in the OFF position and that power to the unit is
locked out.
___ 2. Verify proper input power connections to unit, including the equipment grounding conductor.
___ 3. Turn ON the building power to the unit.
___ 4. Check the phase rotation at the input terminal blocks. Phase rotation should be A, B, C,
left-to-right.
___ 5. Check and record the input voltage for each input. Measured voltages should correspond to
the unit’s nameplate input voltage.
Input 1 Input 2 Input 3 Input 4
Volts, phase A to phase B =
Volts, phase B to phase C =
Volts, phase C to phase A =

___ 6. Check the phase rotation at the panelboard main breakers. Phase rotation should be A, B, C,
left-to-right.
___ 7. Check and record the input voltage at each of the panelboard main breakers. Measured
voltages should correspond to the unit’s nameplate input voltage.
Panelboard 1 Panelboard 2 Panelboard 3 Panelboard 4
Volts, phase A to phase B =
Volts, phase B to phase C =
Volts, phase C to phase A =

If output voltage or phase rotation is incorrect, check for wiring errors or incorrect input
voltage, Contact Liebert Services at 1-800-LIEBERT (1-800-543-2378) in the USA or the local
factory representative for assistance.
___ 8. Turn ON the panelboard main breakers.
___ 9. Replace internal panel and side panels, if supplied.

Liebert® FDC™ 30
Equipment Inspection and Startup

6.4 Current Monitoring Panel (Optional)


If the unit is equipped with a Current Monitoring Panel:
1. Turn the unit ON.
2. Ensure that the LCD display is on. The Current Monitoring Panel displays output and neutral
currents for each panelboard (load must be applied to get an accurate reading).
Figure 24 Current Monitoring Panel

PANEL 2 PANEL 2
L1
L2 180 L1
L2
L3 L3
H AMPS H

If the monitoring panel is not functioning properly, contact Liebert Services at 1-800-LIEBERT
(1-800-543-2378) in the USA or the local factory representative for assistance.

6.5 Current Plus Monitoring™ (Optional)


If the unit is equipped with a Current Plus Monitoring:
1. Turn the unit ON.
2. Ensure that the LCD display is on. The Current Plus Panel displays volt, currents, frequency,
power factor, and power for each panelboard (load must be applied to get an accurate reading).
Displays are located on the front and the rear of the unit.
Figure 25 Current Plus Monitoring panel

PANEL BOARD LABEL

IX = XXXX IN = XXXX

IY = XXXX IG = XX.X

IZ = XXXX
s

NEXT SUB BRANCH


MAIN SEQ FEEDS BRKRS

F1 F2 F3 F4 HELP

If the monitoring panel is not functioning properly, contact Liebert Services at 1-800-LIEBERT
(1-800-543-2378) in the USA or the local factory representative for assistance.

6.6 Liebert LDMF™—Optional


The optional Liebert LDMF is on when power is supplied to the unit. The Liebert LDMF comes
factory-configured for 1 pole 20A branch breakers. Alarm, alarm setpoints, circuit breaker names and
circuit breaker ratings are all field-adjustable through the LDMF SETUP DB9 connector next to the
panelboard main circuit breaker. See the Liebert LDMF user manual, SL-20200, for details.

6.7 Liebert LDMF Display—Optional


If the unit is equipped with a Liebert LDMF display:
1. Turn the unit On.
2. Ensure that the LCD is On. The Liebert LDMF will display voltage, currents, frequency, power
factor and power for each panelboard and branch breaker. The load must be applied to get an
accurate reading.

31 Liebert® FDC™
Operating Instructions

7.0 OPERATING INSTRUCTIONS

7.1 Startup Procedures


Perform equipment inspection and startup procedures as detailed in 6.0 - Equipment Inspection
and Startup before the unit is placed in service after initial installation, as well as after equipment
relocation and after equipment has been de-energized for an extended period of time.
After initial system startup, the following guidelines can be used for standard equipment operation.
These guidelines should be reviewed for any special equipment modifications, special site
considerations or company policies that may require changes to the standard equipment operation.
7.1.1 Normal System Turn ON
• Make certain all unit circuit breakers are in the OFF position. All unit circuit breakers are
located behind the front and rear doors.
• Turn ON building power to the unit.
• Turn ON the panelboard main circuit breakers. If the circuit breaker has been tripped OFF
(instead of being turned OFF), the circuit breaker handle must be moved to the OFF position
before being turned ON.
• Individually turn ON each panelboard circuit breaker following the load equipment manufac-
turer’s startup sequence.

7.2 Normal System Shutdown


To perform a normal system shutdown:
• Perform an orderly load equipment shutdown according to the load equipment manufacturer’s
recommended shutdown sequence.
• The load equipment can be turned OFF at each piece of load equipment or at the Liebert FDC
panelboards (circuit breaker) located behind the unit’s front and rear doors.
• Turn OFF all unit panelboard main breakers.
To remove all power from the unit, turn OFF the building power to the unit.

7.3 Current Monitoring Panel (Optional)


The Current Monitoring Panel consists of a four-digit display in a high-visibility liquid crystal display
(LCD) to monitor three-phase and neutral currents for each panelboard. Front and rear LCDs are
provided with push-button switches for selecting currents.

7.4 Current Plus Monitoring (Optional)


Current Plus Monitoring provides the current and voltage of each panelboard main circuit breaker.
These measurements are used for reporting the average RMS current, power and other parameters.
The CPM reports alarm and status conditions for each panelboard main circuit breaker.
The CPM will also detect and annunciate alarm messages. All alarm thresholds for monitored
parameters are adjustable by way of the service port to match site requirements.
The CPM has a Form C summary alarm contacts for remote alarm status—1 NO and 1 NC. The
contacts are rated at 24VAC @ 1A. There is one alarm contact for every two (2) panelboard main
breakers. The contact changes state upon occurrence of any type of alarm, including a warning alarm,
and resets when the alarm is cleared.
All alarms are stored in non-volatile memory to protect against erasure by a power outage. Alarms
must be reset manually after the alarm condition has been corrected. Alarms may be reset through
Modbus.
Alarms are saved in an event log. The event log stores 128 events using a first-in, first-out (FIFO)
method.
CPM has three Liebert IntelliSlot™ bays. Three Liebert IntelliSlot cards can be added for customer
connection to a Building Management System (BMS). CPM can communicate to Liebert SiteScan®
using an RS-485 connection.

Liebert® FDC™ 32
Operating Instructions

7.5 Liebert LDMF™ (Optional)


The Liebert LDMF monitors the current and voltage for each branch circuit breaker mounted on the
panelboards as well as the panelboard main circuit breaker. These measurements are used for
reporting the average RMS current, power and other parameters.
The Liebert LDMF reports alarm and status conditions for each branch circuit breaker and the
panelboard main circuit breaker. There are three user-settable alarm points for each branch breaker.
When the current reaches the setpoints, a separate alarm for each setpoint is generated and
communicated to a remote monitoring system.
The Liebert LDMF monitors the power parameters for each branch circuit breaker and panelboard
main circuit breaker. The Liebert LDMF will also detect and annunciate alarm messages. All alarm
thresholds for monitored parameters are adjustable by way of the service port to match site
requirements.
The Liebert LDMF has a Form C summary alarm contact for remote alarm status—1 NO and 1 NC.
The contacts are rated at 24VAC @ 1A. The contact changes state upon occurrence of any type of
alarm, including a warning alarm, and resets when the alarm is cleared.
All alarms are stored in non-volatile memory to protect against erasure by a power outage. Alarms
must be reset manually after the alarm condition has been corrected.
Alarms are saved in an event log. The event log stores 128 events using a first-in, first-out format
(FIFO).
The Liebert LDMF has three Liebert IntelliSlot™ bays. Three Liebert IntelliSlot cards can be added
for customer connection to a Building Management System (BMS). The Liebert LDMF can
communicate to Liebert SiteScan® using the Liebert SiteScan Monitoring Interface option.

33 Liebert® FDC™
Maintenance

8.0 MAINTENANCE

! WARNING
Only qualified service personnel should perform maintenance on the Liebert FDC.
Lethal voltages exist inside the unit during normal operation.
The unit is supplied by multiple AC power sources. Disconnect and lock out all power sources
before working inside the unit.
Minimal periodic maintenance of the Liebert FDC is required. As with all electrical distribution
components, the system should be regularly inspected for electrical connection integrity, signs of
excessive temperatures, dirt accumulation and proper system operation.
Standard electrical troubleshooting procedures should be used to isolate problems in the unit.
If you have questions, don’t hesitate to contact Emerson Network Power® Liebert Services.
Repair or replacement of standard items, such as circuit breakers, can be either handled by
qualified electricians or referred to Liebert Services.
Repairs related to the monitoring system should be referred to Liebert Services.
To contact Liebert Services for information or repair service in the USA, call 1-800-LIEBERT
(1-800-543-2378).

8.1 Inspection & Cleaning


Air circulation through the cabinet may cause dust to accumulate on internal components. Cleaning
should be done as necessary during electrical inspections.
Annual general system inspections, cleaning and operation checks are recommended to ensure
system performance and long service life.

8.2 Inspection Schedule


• It is difficult to establish a schedule for periodic cleaning because conditions vary from site to site.
Inspections after the first 24 hours, after 30 days and after six months of operation should help
determine a pattern for the inspection schedule.
• Electrical connections and component mountings should be inspected after the first 24 hours,
after 30 days and after six months of operation. Inspections should be conducted annually
thereafter.
• Ventilation openings and grilles should be inspected and cleaned every six months to one year.
• A complete inspection and operational checkout should be performed annually. This is best done
by performing the inspection and startup procedure as detailed in 6.0 - Equipment Inspection
and Startup.
• Liebert Services offers a complete range of preventive maintenance services. These include thor-
ough equipment performance checks and calibration of electronics. Contact Liebert Services in
the USA at 1-800-LIEBERT (1-800-543-2378) for details.

8.3 Proper Tightening of Nuts and Bolts


Table 1 shows the recommended tightening torque for all nuts and bolts, unless otherwise labeled.
All power connections are designed to remain at proper torque throughout the lifetime of the unit.
Table 1 Torque tightening
Grade 5 - Imperial Electrical Connections
Grade 8.8 - Metric With Belleville Washers
Bolt Shaft in-lb N-m in-lb N-m
Size (inch-pound) (Newton-meter) (inch-pound) (Newton-meter)
10-32 (M5) 25 3 35 4
1/4-20 (M6) 53 6 80 9.0
5/16-18 (M8) 107 12 180 20.4
3/8-16 (M10) 192 22 240 27.1
1/2-13 (M12) 428 48 480 54.3

Liebert® FDC™ 34
Specifications

9.0 SPECIFICATIONS

9.1 Frequency
The Liebert FDC accepts input frequencies of 50Hz and 60Hz. The frequency should be within ±0.5Hz
of the nominal frequency.

9.2 Input/Output Voltage


Liebert FDC models are available in various voltages. The input voltage must be three-phase AC
(4-wire-plus-ground). The voltage should be within ±10% of the nominal voltage. The output voltage
must be three-phase AC (4-wire-plus-ground). Nominal output voltage is the same as input voltage.
Table 2 provides nominal voltages listed according to frequency
Table 2 Input/output voltage
60Hz 50Hz
[L-L/L-N] [L-L/L-N]
208/120V 208/120V
380/220V 380/220V
400/230V 400/230V
415/240V 415/240V
480/277V —

9.3 System Current Ratings


The ratings in Table 3 are based on continuous current rating. These ratings are for all voltages and
frequencies. All units are 100% continuous current rated.
Table 3 System current ratings
Inputs Current per Input
One 720A
Two 360A
Four 180A

9.4 Environmental Requirements


A. Storage temperature range: -55 to +85°C (-67 to +185°F)
B. Operating temperature range: 0 to 40°C (+32 to 104°F)
C. Relative humidity: 0% to 95% without condensation
D. Operating altitude: Up to 6,600 ft. (2,000m) above Mean Sea Level. Derated for higher altitude
applications.
E. Storage/transport: Up to 40,000 ft. (12,200m) above Mean Sea Level.
F. Audible noise: Under normal operation noise level is less than 45 dBA measured 5 ft. (1.5m)
from the surface of the Liebert FDC.

9.5 Frame and Enclosure


The frame is constructed of steel painted powder-coat black and pop-riveted to provide a strong
substructure. The cabinet is a freestanding NEMA type 1 enclosure and meets IP10 requirements. A
tool is required to remove internal accent side panels that access the hazardous voltage area of the
unit.
The cabinet dimensions without side panels are a maximum of 23.5 in. wide x 78.5 in. high x 38 in. deep
(597 x 1994 x 965mm). The distributed floor weight is less than 250 lb./sq. ft. (1225 kg/sq. m).

35 Liebert® FDC™
Specifications

9.6 Casters and Leveling


The enclosure is mounted on four (4) heavy-duty swivel casters for portability and ease of installation
and is provided with four permanent leveling feet for final installation.

9.7 Cooling
The unit is naturally convection-cooled. The convection cooling method allows continuous full-load
operation. Heat rejection is through a screened protective top that prohibits entry of foreign material.

9.8 Access
The Liebert FDC is designed so all repairs and maintenance can be performed with access to the
front, rear and top. (Units with optional side-mounted maintenance tie-breakers require front, rear
and right-side access). Retrofitting additional power distribution cables require access to the front or
rear of the unit only.
All power connections are designed to maintain proper connection torque over the lifetime of the unit
without any maintenance. The integrity of the connections can be checked via infrared scanning
safely from the front, rear or top of the unit.

9.9 Cable Access


The unit has easily removable output cable trays with a minimum of 168 cable/conduit openings. The
Liebert FDC is designed for top or bottom cable entry. Output cable access is top or bottom and through
the side.

9.10 Doors
The unit has lockable, removable, hinged, perforated front and rear doors that are 16-gauge sheet
metal construction with a perforated sheet metal insert to maximize ventilation. Doors provide access
to the main panelboard circuit breakers and to all output circuit breakers. Doors and panels are
finished in powder-coat black.

9.11 Main Panelboard Circuit Breaker


Each distribution panelboard is protected by a main panelboard circuit breaker. The breaker is UL
listed and IEC rated for use at the system voltage. The main panelboard circuit breaker has a rating
of 225A with an overall short-circuit current rating of 22kA RMS symmetrical amperes (208-240V
only).

9.12 Distribution Panelboards


The Liebert FDC contains up to four vertically mounted Square D or GE bolt-in or plug-in
panelboards for distribution to the intended loads. Two panelboards can be accessed from the front of
the unit and two panelboards can be accessed from the rear of the unit. Each panelboard is totally
enclosed with a hinged accent panel that provides access to that panelboard without exposing other
portions of the unit. The panelboard has a rating of 225 amperes (208-240V and 380-415V, 50Hz) or
400 amperes (380-480V, 60Hz), with an overall short-circuit current rating of 22kA (208-240V only) or
35kA (380-480V, 60Hz) RMS symmetrical amperes. Each panelboard provides a total of 42 single-pole
branch circuit breaker positions. Each panelboard includes separate isolated neutral and safety-
ground busbars for the neutral and safety-ground connections for at least 42 output circuits. The
neutral busbar and wiring are sized for at least 1.73 times the panelboard full load rating to
accommodate high harmonic neutral currents associated with single-phase nonlinear loads.

Liebert® FDC™ 36
Specifications

9.13 Monitoring
No monitoring is standard. Three options are available:
• Current Monitoring Panel
• Current Plus Monitoring
• Liebert Distribution Monitoring
See 9.14.1 - Current Monitoring Panel, 9.14.2 - Current Plus Monitoring, and 9.14.9 -
Liebert LDMF™ for details.

9.14 Options
The following options are available for the Liebert FDC:

9.14.1 Current Monitoring Panel


The Current Monitoring Panel consists of a four-digit, high-visibility Liquid Crystal Display (LCD) to
monitor current parameters. Front and rear displays are provided with push-button switches for
operator interface. The three-phase and neutral currents for each panelboard are displayed. The
display and switches are accessible without opening the door. All currents are monitored using true
RMS measurements for accurate representation of non-sinusoidal waveforms typical of computers
and other sensitive loads.

9.14.2 Current Plus Monitoring


CPM monitors the current and voltage of the panelboard main circuit breaker. These measurements
are used for reporting the average RMS current, power and other parameters.
The CPM reports alarm and status conditions for each panelboard main circuit breaker.
CPM has three Liebert IntelliSlot™ bays. Three Liebert IntelliSlot cards can be added for connection
to a Building Management System (BMS). CPM can communicate to Liebert SiteScan® using an
RS-485 connection.

9.14.3 EZ-View Doors


The enclosure is provided with a removable, lockable, hinged door with a clear acrylic scratch- and
impact-resistant Plexiglas insert to allow for external viewing of the branch breakers without opening
the door.

9.14.4 Solid Sheet Metal Doors


The enclosure is provided with a removable, lockable, hinged solid sheet metal door.

9.14.5 Plug-In Main Breakers


Plug-in main panelboard circuit breakers are provided to allow easy replacement. The plug-in feature
of the breaker includes interlock, which prevents the breaker from being unplugged without being in
the Off (open) position. The circuit breakers have a rating of 225 amperes with an overall short-circuit
current rating of 22kA RMS symmetrical amperes (208-240V only).

9.14.6 Maintenance Tie-Breakers


Optional maintenance tie-breakers are provided to allow connection of the panelboards in the
Liebert FDC to different inputs. The inputs must be fed from the same source so they can be safely
tied together. Breakers are located behind a lockable hinged door on the side of the unit. Side access is
required with this option.

9.14.7 Isolated Ground Busbar


An isolated ground busbar is provided for each panelboard to connect the output cable isolated ground
conductor. The isolated ground busbar is in addition to the standard-equipment ground busbar.

9.14.8 65kAIC Main Panelboard Circuit Breaker (380-480V, 60Hz, units)


The main panelboard circuit breaker shall have an overall short-circuit current rating of 65kA RMS
symmetrical amperes.

37 Liebert® FDC™
Specifications

9.14.9 Liebert LDMF™


The Liebert LDMF monitors each individual branch circuit of 42-pole panelboards. In addition to
monitoring the branch circuit breakers, the Liebert LDMF monitors the current and voltage of the
panelboard main circuit breaker. These measurements are used for reporting the average RMS
current, power and other parameters.
The Liebert LDMF reports alarm and status conditions for each branch circuit breaker and the
panelboard main circuit breaker. The Liebert LDMF is supplied with three Liebert IntelliSlot™ bays.
Three Liebert IntelliSlot cards can be added for customer connection to a Building Management
System (BMS). The Liebert LDMF can communicate to Liebert SiteScan® using the Liebert SiteScan
Monitoring Interface option.

9.14.10 Side Panels


The unit is supplied with 20-gauge sheet metal side panels. A 7/32" hex wrench is required to
remove the exterior panels that access the hazardous voltage area of the unit.

9.14.11 Export Crating


Heavy-duty solid wood crating can be provided to meet international requirements regarding
package strength and special markings for overseas shipments.

9.14.12 Seismic Floor Stands


A floor stand is provided to support and level the unit and provide bottom cabling access without
relying on a raised floor for support. The nominal height of the floor pedestals is 18 in. (457mm),
24 in. (610mm), 30 in. (762mm) or 36 in. (914mm).

9.14.13 65kAIC Main Panelboard Circuit Breaker (380-480V, 60Hz, units)


The main panelboard circuit breaker shall have an overall short-circuit current rating of 65kA RMS
symmetrical amperes.

Liebert® FDC™ 38
Specifications

NOTES

39 Liebert® FDC™
Specifications

Liebert® FDC™ 40
Technical Support / Service
Web Site
www.liebert.com
Monitoring
liebert.monitoring@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
liebert.upstech@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
While every precaution has been taken to ensure the accuracy Fax: +39 049 5841 257
and completeness of this literature, Liebert Corporation assumes no Asia
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
29/F, The Orient Square Building
© 2014 Liebert Corporation F. Ortigas Jr. Road, Ortigas Center
All rights reserved throughout the world. Specifications subject to change Pasig City 1605
without notice. Philippines
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks +63 2 687 6615
or registered trademarks of their respective owners. Fax: +63 2 730 9572
SL-20402_REV5_12-15

Emerson Network Power


Liebert
www.emerson.com

You might also like