Liebert AC8
Liebert AC8
Liebert AC8
Liebert AC8
User Manual
TABLE OF CONTENTS
1.0
INTRODUCTION
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
2.0
INSTALLATION
2.1
Installation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1.1
2.2
2.4
2.3
1
1
1
1
2
3
4
6
8
3.0
3.1
3.2
Wiring Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Connecting Digital Inputs and Digital Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2.1
3.2.2
3.2.3
3.2.4
3.2.5
3.2.6
3.3
15
16
16
17
17
18
3.4
3.5
3.6
RS232 Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Phone Line Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.0
OVERVIEW OF MENUS
4.1
4.2
4.3
5.0
5.1
5.2
5.3
Alarm Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Backing Up the Alarm Log (Service Terminal Interface only) . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.4
Active Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Event Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Backing Up the Event Log (Service Terminal Interface only) . . . . . . . . . . . . . . . . . . . . . . . . . 28
Select a Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
View a Trend Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Backing Up the Trend Log (Service Terminal Interface only) . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.5
5.6
5.7
5.5.1
5.6.1
5.7.1
5.7.2
5.7.3
5.8
Output Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Select a Pager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
View a Pager Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
View a Pager PIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
View Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.8.1
5.8.2
5.9
Input Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Select a Zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
View Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Control Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.0
6.1
6.2
7.0
7.1
7.2
7.3
Login . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Setup System - Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Setup System - Setup Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
7.3.1
7.3.2
7.3.3
7.3.4
7.3.5
7.4
42
42
42
43
43
ii
7.5
7.6
55
57
59
61
Change Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Change Date & Time/Automatic Daylight Saving Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup Site ID. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connect Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Backup and Upload Configuration File (Service Terminal Interface only) . . . . . . . . . . . . . . .
Setup Serv Ph Num - Enter Phone Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup Serv Ph Num - Communications Check (Service Terminal Interface only) . . . . . . . . .
Factory Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Perform Firmware Update (Service Terminal Interface only) . . . . . . . . . . . . . . . . . . . . . . . . .
Initiate Remote Alarm Test (Service Terminal Interface only) . . . . . . . . . . . . . . . . . . . . . . . .
64
64
65
65
66
69
70
71
71
73
Setup Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
7.10.1
7.10.2
7.10.3
7.10.4
7.10.5
7.10.6
7.11
53
54
54
54
54
7.10
7.9
Set Up a Zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
7.8
46
46
46
47
47
47
48
48
49
49
50
7.7
76
78
78
79
79
80
7.12
Override Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
iii
7.13
84
84
85
85
8.0
SPECIFICATIONS
8.1
A.3
93
94
95
96
97
97
98
99
99
Silence Alarm & Back Up Log Files (Service Terminal Interface only). . . . . . . . . . . . . . . . 100
A.5.1
A.5.2
A.6
A.5
88
88
89
90
91
Overview of Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
A.3.1
A.3.2
A.3.3
A.4
Connection Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Create a Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Set Up the COM1 Port - Direct Connection Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Set Up the Connections Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connect to the Service Terminal Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup Common Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup Zones. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup Modem & Pagers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup System Info. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Override Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Clear Alarms & Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup I/O Matrix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
105
105
106
107
107
108
110
115
121
122
124
iv
FIGURES
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5
Figure 6
Figure 7
Figure 8
Figure 9
Figure 10
Figure 11
Figure 12
TABLES
Table 1
Table 2
Table 3
Table 4
Table 5
Table 6
Table 7
Table 8
Table 9
Table 10
Table 11
Table 12
Table 13
Table 14
Table 15
Table 16
Table 17
Table 18
Table 19
Table 20
Table 21
Table 22
Table 23
Table 24
Table 25
Table 26
Table 27
Table 28
Table 29
Table 30
Table 31
Table 32
Table 33
Table 34
Table 35
Table 36
vi
Introduction
1.0
INTRODUCTION
The Liebert AC8 is ideal for coordinated control of systems with redundant equipment, such as
multiple environmental units or pumps. When the Liebert AC8 controller detects an alarm in an
operating device, the Liebert AC8 enables a standby device and controls the device in alarm as
configured, either leaving that device operating or disabling it.
The Liebert AC8 controller can also balance usage of devices by rotating units through Operating and
Standby modes according to a user-defined schedule. This helps keep redundant equipment operating
efficiently and only when needed. The Liebert AC8 can perform routine testing of standby devices and
alert personnel if a standby device fails an operating test and requires attention.
The staging feature permits standby devices to be turned on or off when a sensor detects specified
levels. For example, the Liebert AC8 might be configured to turn on a fan when the temperature
reaches 75F, then turn on a second fan at 80F. When the temperature falls below 80F, the second
fan is turned off; when it drops below 75F, the first fan is turned off.
Another capability of the Liebert AC8 is monitoring the status of connected devices and keeping
personnel apprised through local alarming. The Liebert AC8 employs local alarming and remote
paging services to keep personnel on-site and at remote locations apprised of the status of equipment.
The Liebert AC8 controller can interface with anything that closes an electrical contact. To improve
process efficiency and troubleshooting, the controller tracks data in three types of logs: alarm, event
and trend. The Liebert AC8 has a local LCD interface and a remote dial-up interface.
When an alarm condition arises, the Liebert AC8 displays alarm information, sounds an audible
alarm, changes the state of the common alarm relay and turns connected devices on or off according to
user configuration. If configured, the controller also sends pager notifications. See 1.6 - Typical
Configuration for a more detailed example.
1.1
1.2
Data Logs
The three types of data logsalarm history, event history and trend data of analog sensor
readingscan be viewed on the LCD on the front of the Liebert AC8 and downloaded through
onboard communications ports.
1.3
Transformer Module
A Transformer Module converts 115VAC or 230VAC to 24VAC.
1.4
Available Alarms
The alarms available with the Liebert AC8 are:
Discrete input alarm
(for each digital input)
High setpoint
Low setpoint
Liebert AC8
Introduction
1.5
Figure 1
The enclosure
has knockouts
and access slots
on top and
bottom for
cables and wires.
Key lock
The enclosure houses the controller board and Transformer Module, as shown in Figure 2.
The enclosure must be secured to a wall, either flush-mounted or recessed in the wall, as described in
2.0 - Installation. Knockouts and access slots on the top and bottom allow easy connection of wires
and cables (see 3.0 - Wiring and Connections) with either mounting type.
Figure 2
Back of LCD
Controller Board
TB5: COMMON ALARM
NO C NC
NO C NC
(BOTTOM)
BOTTOM
LS1
TB7:
24V
V INPU
UT
START
P11
ENABLE
AUDIBLE
R402
R26
Q11
NO
N ALARM
SENS
TOP
LIEBERT
BAR CODE
TB3:
RELAY
OUTPUTS
(BOTTOM)
(TOP)
(BOTTOM)
4
3
2
REV
1
(TOP)
4
3
2
ASS
8
7
6
5
(BOTTOM)
8
7
6
5
TB2:
CONTACT
INPUTS
1-2 TOP
3-4 BOTTOM
MODEM
J11: PHONE
PIN 3-TIP
PIN 4-RI"N"G
ON
0: COMMS
MS
(TOP)
ALL CIRCUITS;
+
(BOTTOM)
On/Off switch
for Transformer
Module
Liebert AC8
Ground wire
for LCD
Power receptacle
(115VAC model only)
485
+
CLASS 2
TB9: ANALOG
GROUND
Knockouts and
access slots
(top and bottom)
Introduction
1.6
Typical Configuration
Figure 3 shows an example of external devices connected to the Liebert AC8 controller board. Up to
eight devices may be connected to the eight digital inputs and eight digital outputs. There may be up
to four analog sensors connected to the analog inputs, and up to two devices connected to the control
relay outputs. The EPOP connection allows for one device, possibly a UPS or generator input actuated
during a power failure.
Remote access is available via Liebert SiteScan Web and through the modem, which enables pager
notifications and use of the Service Terminal Interface. A computer may be connected to the RS232
port, providing access to the features of the Service Terminal Interface.
Figure 3
Typical Configuration
Contact relay
output
TB5: COMMON ALARM
RELAY OUTPUTS
NO C NC (TOP)
NO C NC
BOTTOM
LS1
TB7:
24V INPUT
START
P11
ENABLE
AUDIBLE
TB4:
TOP
Q11
P23:
BATTERY
LIEBERT
BAR CODE
RS232
BATTERY
(BOTTOM)
TP1
VBATT
RELAY
OUTPUTS
GND
ON
S2
OFF
ON
1
DIP
3
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
CTRLLOCK
SENLOCK
CMN ALR
DS56
DS54
DS63
DS83
DS84
DS61
DS60
DS62
DS55
DS57
DS59
DS58
DS53
CAN TX
CAN RX
(BOTTOM)
(TOP)
4
3
MOP
F PROG
574 TX
574 RX
485 RX
485 TX
PFM2
8
7
6
5
REV
(BOTTOM)
(TOP)
4
3
2
ASS
TB1
8
7
6
5
EPOP
P19
MODEM
DIS EN
J11: PHONE
(TOP)
485
+
(BOTTOM)
422
+
EPOP
AG TB9: ANALOG
GROUND
Analog inputs
TB1: EPOP
CONTACT
INPUT
Liebert SiteScan
Web
EPOP contact
input
DEVICES CONNECTED TO
DIGITAL INPUTS & OUTPUTS
TB2:
CONTACT
INPUTS
EPOP INPUT
1-2 TOP
3-4 BOTTOM
ON
PIN 3-TIP
PIN 4-RING
Humidity
lockout
PFM5
R334
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
C71
DS70
DS67
DS66
DS65
DS64
MODEM
Phone
line
NC
C
NO
NC
C
NO
LCD
CONTRAST
ZONE 1 DEVICES
Device 1
Device 2
connected to
Input 1 & Output 1
connected to
Input 2 & Output 2
Liebert
Challenger
3000
Liebert
Challenger
3000
ZONE 2 DEVICES
Device 4
Device 3
connected to
Input 3 & Output 3
connected to
Input 4 & Output 4
Liebert
Himod
Liebert
Himod
Generator
Liebert AC8
Introduction
1.7
HH - Transformer
Module
A - Power
On/Off switch
E - Audible horn
jumper
C - EIA422
B - Battery
D - Audible
LEDs
pack
horn
G - Digital output
status LEDs
GG - 24VAC power
connector
NO C NC (TOP)
BOTTOM
FF - Battery pack
connector
LS1
TB7:
24V INPUT
START
P11
ENABLE
AUDIBLE
LIEBERT
BAR CODE
P23:
BATTERY
BATTERY
(BOTTOM)
NC
C
NO
NC
C
NO
LCD
CONTRAST
TP1
VBATT
ON
S2
OFF
ON
1
DIP
3
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
CTRLLOCK
SENLOCK
CMN ALR
DS56
DS54
DS63
DS83
DS84
DS61
DS60
DS62
DS55
DS57
DS59
DS58
DS53
CAN TX
CAN RX
(BOTTOM)
(TOP)
2
PFM2
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
C71
K - Status LEDs
L - Digital output
loss-of-power
jumper
PFM5
R334
MOP
F PROG
574 TX
574 RX
485 RX
485 TX
DS70
DS67
DS66
DS65
DS64
J - Digital output
connectors
RELAY
OUTPUTS
GND
BB - Modem
status LEDs
REV
MODEM
(BOTTOM)
(TOP)
4
3
AA - Modem
ASS
TB1
8
7
6
5
TB2:
CONTACT
INPUTS
M - Digital input
connectors
TB1: EPOP
CONTACT
INPUT
N - Digital input
status LEDs
EPOP INPUT
1-2 TOP
3-4 BOTTOM
EPOP
ON
P19
MODEM
DIS EN
J11: PHONE
PIN 3-TIP
PIN 4-RING
(TOP)
485
+
(BOTTOM)
X - Power
receptacle W - Phone
U - EIA485
V - Serial
line
connector
interface
connector
connector
(RS232/EIA574)
Table 1
I - Manual
Override Switch
(outputs)
TB4:
TOP
Q11
EE - LCD contrast
adjustment
DD - LCD
connector
CC - DIP switch 1
Y - Power On/Off
switch
H - Control relay
outputs
RELAY OUTPUTS
NO C NC
Z - 24VAC
connector
F - Common
Alarm
connectors
422
+
AG TB9: ANALOG
GROUND
EPOP
O - EPOP
contact input
S - 12VDC/
Q - Analog
T - SiteScan
R - Analog
24VDC analog
ground
Web
input
input jumper
connector
connector
connectors
(EIA422)
P - EPOP
jumper
A - Power On/Off
switch
B - Battery pack
C - EIA422 LEDs
D - Audible horn
E - Audible horn
jumper
F - Common Alarm
connectors
G - Digital output
status LEDs
Description
Power switch for the controller board. When switched off, the battery
pack is disabled.
Provides battery backup during a power loss to maintain normal
operation of the panel for a minimum of 10 minutes. The analog inputs
will not be functional during a power loss (P/N 133455P1).
Indicates the connection status between the Liebert AC8 and Liebert
SiteScan Web.
Provides audible notification when an alarm occurs.
2.4:
N/A
N/A
3.0:
3.4:
7.4:
1.8:
LED Indicators
H - Control relay
outputs
I - Manual Override
Switch (outputs)
Placing the switch in the ON position will turn ON, or energize, all eight
outputs simultaneously. This switch removes all automatic output control
from the Liebert AC8.
The factory default is OFF (outputs controlled by programming).
Liebert AC8
Introduction
Table 1
Description
Q - Analog ground
connector
R - Analog input
connectors
3.0:
3.3:
5.5:
7.5:
S - 12VDC/24VDC
analog input jumper
T - SiteScan Web
connector (EIA422)
3.0:
3.5:
U - EIA485 connector
N/A
J - Digital output
connectors
K - Status LEDs
L - Digital output
loss-of-power
jumper
M - Digital input
connectors
N - Digital input
status LEDs
O - EPOP contact
input
P - EPOP jumper
V - Serial interface
connector (RS232/
EIA574)
3.0:
3.2.2:
5.6:
7.7:
1.8:
1.8:
LED Indicators
W - Phone line
connector
Connection for phone line. Used for pager notifications, service phone
number, and configuration and monitoring using the Service Terminal
Interface. Requires an RJ11 connector.
X - Power receptacle
(Transformer Module)
Y - Power On/Off
switch (Transformer
Module)
Z - 24VAC connector
(Transformer Module)
One of the two 24VAC connectors for power (the second is also on the
right side of the Transformer Module near the top). Each connector is
rated for 40VA.
AA - Modem
BB - Modem status
LEDs
CC - DIP switch 1
DD - LCD connector
EE - LCD contrast
adjustment
FF - Battery pack
connector
GG - 24VAC power
connector
HH - Transformer
Module
7.8:
1.8:
LED Indicators
N/A
2.4:
Liebert AC8
Introduction
1.8
LED Indicators
The Liebert AC8 controller board has LED indicators that show the status of inputs, outputs and the
common alarm, as well as the modem, Liebert SiteScan Web and EPOP connections.
BOTTOM
DS50
START
P11
ENABLE
AUDIBLE
TB4:
TOP
Q11
DS49
DS68
EPOP
NO C NC (TOP)
NO C NC
LS1
TB7:
24V INPUT
LIEBERT
BAR CODE
EIA422
SS Web
EIA422
SiteScan Web
& EPOP
LEDs
P23:
BATTERY
BATTERY
(BOTTOM)
NC
C
NO
TP1
RELAY
OUTPUTS
GND
ON
S2
OFF
ON
1
DIP
3
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
CTRLLOCK
SENLOCK
CMN ALR
DS56
DS54
DS63
DS83
DS84
DS61
DS60
DS62
DS55
DS57
DS59
DS58
DS53
CAN TX
CAN RX
(BOTTOM)
(TOP)
4
3
MOP
F PROG
574 TX
574 RX
485 RX
485 TX
R334
DS70
DS67
DS66
DS65
DS64
PFM2
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
C71
1
REV
MODEM
3
2
ASS
TB1
P19
DIS EN
J11: PHONE
(TOP)
485
+
(BOTTOM)
Status
LEDs
422
+
AG TB9: ANALOG
GROUND
EPOP
DS61
DS60
DS62
DS55
DS57
DS59
DS58
DS53
DS52
DS51
DS48
DS47
DS78
DS79
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
CTRLLOCK
SENLOCK
CMN ALR
MOP
F PROG
574 TX
574 RX
485 RX
485 TX
7
6
5
TB2:
CONTACT
INPUTS
TB1: EPOP
CONTACT
INPUT
DS69
DS71
DS72
DS70
DS67
DS66
DS65
DS64
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
Output LEDs
CTRLLOCK
Control Relay 2
SENLOCK
Control Relay 1
CMN ALR
Common Alarm
Status
LEDs
Input LEDs
LED Type
Output
LEDs
EPOP
PIN 3-TIP
PIN 4-RING
Modem
LEDs
EPOP INPUT
1-2 TOP
3-4 BOTTOM
ON
MODEM
EPOP LED
(BOTTOM)
(TOP)
EIA422
LEDs
PFM5
Modem LEDs
Table 2
LCD
CONTRAST
VBATT
MODEM
DS77
TX
DS76
RX
DS74
DTR
DS75
DCD
NC
C
NO
DS56
DS54
DS63
LED
422 TX
422 RX
EPOP IN
Color
Green
Green
Red
TX
RX
DTR
DCD
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
CTRLLOCK
SENLOCK
CMN ALR
Green
Green
Green
Green
Green
Green
Green
Green
Green
Green
Green
Green
Green
Green
Green
MOP
Green
FPROG
574 TX or 232 TX
574 RX or 232 RX
485 RX
485 TX
Green
Green
Green
Green
Green
Liebert AC8
Description
Liebert AC8 is transmitting information over the EIA422 port
Liebert AC8 is receiving information over the EIA422 port
Indicates Emergency Power Operation is open or in alarm
Liebert AC8 is transmitting information via the modem
Liebert AC8 is receiving information via the modem
Indicates data terminal is ready (DTR)lights up when modem is dialing
Indicates data carrier is detected (DCD)lights up when modem has connection
Indicates output is ON or energized
Indicates output is ON or energized
Indicates output is ON or energized
Indicates output is ON or energized
Indicates output is ON or energized
Indicates output is ON or energized
Indicates output is ON or energized
Indicates output is ON or energized
Indicates Control Relay 2 is ON or energized
Indicates Control Relay 1 is ON or energized
Indicates Common Alarm Relay is ON or energized
Indicates the microprocessor is operating properly (MOP)must be on before Liebert
AC8
will function
Indicates firmware is being upgradedlights up during upgrade process
Liebert AC8 is transmitting information via the RS232 port
Liebert AC8 is receiving information via the RS232 port
Not used
Not used
Introduction
Table 2
LED Type
Input
LEDs
Color
Red
Red
Red
Red
Red
Red
Red
Red
Description
Indicates input is ON or energized
Indicates input is ON or energized
Indicates input is ON or energized
Indicates input is ON or energized
Indicates input is ON or energized
Indicates input is ON or energized
Indicates input is ON or energized
Indicates input is ON or energized
Liebert AC8
Introduction
1.9
Typical Sequence
Figure 4 shows a typical sequence of how the Liebert AC8 functions after detecting a change in a
monitored device. Many responses depend on configuration settings. This example shows what
happens when a digital input changes stateassuming the input is defined as alarmableand when
the condition returns to normal.
Figure 4
UNIVERSAL MONITOR
05-SEP-02 14:04:13
V5.100.0
=STATUS/SETUP
PRESS
ESC
RETURN-TO-NORMAL SEQUENCE
RETURN TO NORMAL
The device that triggered the alarm
returns to its normal state.
UNIVERSAL MONITOR
05-SEP-02 14:04:13
V5.100.0
=STATUS/SETUP
PRESS
ESC
DEVICE_1 ALARM
CONTACT CLOSED
30-SEP-04
16:23:04
DEVICE_1 ALARM
CONTACT CLOSED
DEVICE_4 STARTED
30-SEP-04
Liebert AC8
16:23:10
ALARMS CLEARED
30-SEP-04
16:24:04
DEVICE_1 STARTED
DEVICE_2 STARTED
DEVICE_3 STARTED
DEVICE_4 OFF
30-SEP-04
16:24:06
Installation
2.0
INSTALLATION
This section provides instructions for installing, mounting and connecting power to the Liebert AC8.
2.1
Installation Considerations
The Liebert AC8 must be installed indoors and may be mounted on the surface of a wall or flushmounted, depending on the users application, the location of equipment and sensors to be monitored
and the type of wall the unit will be mounted on.
The Liebert AC8 should be mounted where it can be easily accessed. On-site personnel would access
the unit through the LCD on its front cover, service terminal connected to the RS232 port or through
Liebert SiteScan. For off-site monitoring, the Liebert AC8 should be placed near communications
means such as a telephone line connection that would permit remote access.
In addition to the communications connections, the site also must have electrical service and must
permit connecting the units eight digital inputs, eight digital outputs and four analog inputs.
The wall material must be capable of supporting the weight of the Liebert AC8: see 8.0 Specifications.
NOTE
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is
likely to cause harmful interference in which case the user will be required to correct the
interference at his own expense.
Packing Contents
Table 3
Packing manifest
Standard Components
Liebert AC8
Installation
2.2
Required tools
2.2.1
Electric drill (if surface is too hard to drive screws without pilot holes)
Screwdriver
Marker to denote layout of holes
Four screws, each #10
CAUTION
Check building plans and other relevant documents to determine whether mounting the
Liebert AC8 at the selected location might cause cutting or otherwise damaging electrical or
communication wiring or pipes.
1. Mark the wall for mounting holes, using the back of the unit as a template (see Figure 5).
2. Drill holes, if required, to install the four #10 screws that will secure the Liebert AC8 to the wall.
Clean up the debris.
3. If the wall material is not strong enough to hold the screws securely, use wall anchors.
4. Install the top two screwsthe screw heads must be small enough to slip through the larger,
bottom portion of the pear-shaped mounting slot in the Liebert AC8 (see inset in Figure 5). The
screws must also be large enough to extend over the edges of the top of the mounting slot.
5. Hang the Liebert AC8 on the screws, letting the panel slip down until the screws are in the
smaller, upper portion of the slot.
6. Tighten the screws until they are snug.
7. Insert the remaining two screws in the bottom holes on the back of the panel and tighten.
Figure 5
Mounting dimensions
ENCLOSURE
12"
(304.8mm)
0.213"
(5.4mm)
Liebert AC8
back plate
16"
(406.4mm)
0.375"
(9.6mm)
Mounting Slot
0.213" (5.4mm)
Bottom hole diameter
Liebert AC8
10
Installation
2.3
Required tools
2.3.1
Saw
Electric drill
Screwdriver
Marker to denote layout of the hole to accommodate the Liebert AC8
Mounting hardware
!
1.
2.
3.
4.
5.
6.
7.
8.
9.
CAUTION
Check building plans and other relevant documents to determine whether mounting the
Liebert AC8 at the selected location might cause cutting or otherwise damaging electrical or
communication wiring or pipes.
Mark the wall for the cutout to accommodate the panel, using the back of the unit as a template.
Drill a pilot hole for the saw blade, if required.
Use the saw to cut out the marked section of the wall (if not new construction).
Rest the Liebert AC8 in the wall and mark where mounting screws will be inserted into the wall
studs or other support member.
Remove the panel and drill the holes for the mounting screws or wall anchors. Clean up the
debris.
Reverse the slide direction of the rectangular access doors on the top and bottom of the Liebert
AC8. Leaving the doors as shipped from the factory prevents them from being opened when the
panel is flush mounted in a wall.
Attach any field-supplied mounting hardware.
Reinsert the assembly into the wall.
Insert and tighten the screws or wall anchors.
11
Liebert AC8
Installation
2.4
!
!
WARNING
CAUTION
The Liebert AC8 is designed for use on properly grounded (earthed) 115VAC or 230VAC
power, 60Hz or 50Hz. The ground wire for the power lead must be wired to the earth ground
terminal (stud located next to the 24VAC terminal block).
This equipment is intended to be installed by a qualified and certified electrician who must
review and approve customer supplied wiring and circuit breakers, verify correct input and
grounded (earthed) connections to ensure compliance with technical standards and national
and local electrical codes.
!
2.4.1
WARNING
Be sure that the Power On/Off switch is set to OFF before installing any wiring to this unit.
The switch is in the top left corner of the unit, just below the battery pack.
WARNING
Be sure that the Power On/Off switch is set to OFF before installing any wiring to this unit.
The switch is at the bottom of the unit.
TM230
Connection Type
White wire
Neutral (L2)
Neutral
Black wire
Line (L1)
Power (Line)
Green wire
Ground lead
Ground
5. Secure the incoming electrical service wires to the TM115 input wires with wire nuts as shown in
Figure 6 or to the TM230 connectors as shown in Figure 7.
Liebert AC8
12
Installation
TM230
Wire nuts
connecting
electrical
wiring
Knockout for
external wiring
Knockout for
external wiring
Ground
Ground
Neutral
(L2)
Line (L1)
24VAC output
(TB1)
24VAC output
(TB1)
2.4.2
Problem
Possible Solution
24VAC power
not available
from TB1 or TB2
Battery pack
!
2.4.3
WARNING
To prevent the risk of fire or explosion, replace only with 7.2 V rechargeable NiCad battery pack.
Dispose of the battery properly by sending it back to Emerson or an approved battery
recycling facility
Liebert AC8
3.0
!
3.1
CAUTION
Switch OFF electric power to the Liebert AC8 before installing any wiring to the unit or
changing input or output connections. The Power On/Off switch is in the top left corner of the
unit, just below the battery pack.
Wiring Specifications
Input and output connections to the Liebert AC8 may be made in any orderit is not necessary, for
example, to make all input connections before making any output connections. Use copper conductors
only for all wiring.
Table 4
Wiring specifications
Connection
Rating
Digital
Input/
EPOP
Dry Contact
(24VDC,
10 mA)
Digital
Output/
Control
Relay
18 AWG*
20 AWG
22 AWG
18-22 AWG Stranded & Unshielded (recommended)
18 AWG* (recommended)
@3A 50 ft. (15m) @3A 40 ft. (12m) @3A 25 ft. (7m)
Non Plenum - Belden 9740
@2A 100 ft. (30m) @2A 60 ft. (18m) @2A 35 ft. (10m)
Plenum - Belden 89740
@1A 200 ft. (60m) @1A 100 ft. (30m) @1A 75 ft. (23m)
24VAC@3A
Analog Input
2-Wire
Transducer
4-20 mA Signal
Input Selectable
Power Source
(12/24VDC)
Analog Input
4-Wire
Transducer
4-20 mA Signal
Input Selectable
Power Source
(12/24VDC)
Common
Alarm
Output
18 AWG*
20 AWG
22 AWG
18-22 AWG Stranded & Unshielded (recommended)
18 AWG* (recommended)
@3A 50 ft. (15m) @3A 40 ft. (12m) @3A 25 ft. (7m)
Non Plenum - Belden 9740
@2A 100 ft. (30m) @2A 60 ft. (18m) @2A 35 ft. (10m)
Plenum - Belden 89740
@1A 200 ft. (60m) @1A 100 ft. (30m) @1A 75 ft. (23m)
Communication
Null Modem Cable
RS232
24VAC
@3A
50 ft. (15m)
N/A
N/A
N/A
N/A
N/A
24VAC
@1.3A
Communication
EIA422
Liebert
SiteScan
Phone/Modem
Line
24VAC Power
Connection
(TB7)
115VAC
@4A
230VAC
230VAC
@0.5A
* Recommended
Liebert AC8
14
3.2
RELAY
OUTPUTS
4
3
2
1
REV
3
2
1
TB1
EPOP INPUT
EPOP
15
8
7
6
5
(BOTTOM)
(TOP)
ASS
NOTE
Connect digital inputs to
nonpowered (dry) contacts only.
(BOTTOM)
(TOP)
ON OFF
PFM2
ON OFF
PFM5
3.2.1
8
7
6
5
TB2:
CONTACT
INPUTS
DIGITAL INPUT
TERMINAL BLOCKS
Liebert AC8
ON
PF
3.2.2
!
3.2.3
(TOP)
ON OFF
PFM2
1
REV
(BOTTOM)
(TOP)
4
3
2
1
CAUTION
DIGITAL OUTPUT
TERMINAL BLOCKS
(BOTTOM)
ON OFF
PFM5
RELAY
OUTPUTS
8
7
6
5
TB2:
TB4:
Output status
(power loss & no battery backup)
Normally Open
ON
Normally Closed
(BOTTOM
NC
C
NO
NC
C
NO
ON OFF
PFM3
ON OFF
PFM8
OFF
RELAY
OUTPUTS
(BOTTOM)
(TOP)
4
3
ON OFF
PFM2
REV
ON OFF
PFM5
7
6
5
(BOTTOM)
(TOP)
4
3
8
7
6
5
Liebert AC8
16
Associated output
PFM1
Output 1
PFM2
Output 2
PFM3
Output 3
PFM4
Output 4
PFM5
Output 5
PFM6
Output 6
PFM7
Output 7
PFM8
Output 8
3.2.4
(BOTTOM)
NC
C
NO
NC
C
NO
ON OFF
PFM3
ON OFF
PFM8
RELAY OUTPUT
TERMINAL BLOCKS
!
3.2.5
RELAY
OUTPUTS
(BOTTOM)
(TOP)
CAUTION
To reduce the risk of fire or electric shock, do not interconnect the outputs of different Class 2
circuits.
17
Liebert AC8
REV
3
2
1
TB1
5
(BOTTOM)
(TOP)
ASS
3.2.6
ON OFF
PFM5
8
7
6
5
TB2:
CONTACT
INPUTS
EPOP INPUT
EPOP
P19
DIS EN
EPOP
TB1: EPOP
CONTACT
INPUT
Liebert AC8
18
3.3
3.3.1
1-2 TOP
3-4 BOTTOM
S 485
) +
+ +
1. Find the black analog jumper on the circuit board,
AG TB9: ANALOG
422
as shown at right. The jumper is at the bottom of OM) +
+ +
GROUND
the board near the middle (see 1.7 - Controller
Board Overview).
2. Decide whether your configuration requires the jumper to be 24VDC or 12VDC.
3. Set the jumper as needed:
To set the jumper to the 24VDC position, place the black jumper on the middle and right pins.
To set the jumper to the 12VDC position, place the black jumper on the middle and left pins.
3.3.2
Analog
input
19
Analog
ground
1-2 TOP
3-4 BOTTOM
TB10: COMMS
(TOP)
(BOTTOM)
Four-wire
transducer
Sensor
with
external
power
TB9: ANALOG
GROUND
+
4/20mA
Output
24V Input
24V from
external
power
source
Liebert AC8
3.4
NO C NC (TOP)
NO C NC
TB3, TB4, T
OUTPUT RE
RATINGS: 24
CLASS 2 O
BOTTOM
P11
ENABLE
AUDIBLE
TB4:
ONT
ELAY
UTP
TOP
C C
NO
O
MON ALARM
40
Q11
NC
C
NO
3.5
OP)
3.6
(TOP)
(BOTTOM)
422
+
EIA422 Liebert
SiteScan Web
Communications Connections
The Liebert AC8s Service Terminal Interface offers full
configuration and monitoring capability via the RS232 port
and the phone line connector (see A.2 - Connecting to the
Service Terminal Interface). The phone line connector is
also used for pager notifications and service phone number
options.
3.6.1
RS232 Connector
The RS232 port requires a null modem cable.
Connect one end of the cable to the Liebert AC8s RS232
port, as shown at right.
Connect the other end to the COM1 port of a laptop
computer or video terminal.
MODEM
RJ11: PHONE
PIN 3-TIP
PIN 4-RING
TB10: COMMS 48
(TOP)
Liebert AC8
20
(BOTTOM)
3.6.2
21
Liebert AC8
Overview of Menus
4.0
OVERVIEW OF MENUS
There are two ways to access the Liebert AC8: the LCD on the front of the enclosure and the Service
Terminal Interface, which is accessible through any computer using a communications program.
Many viewing and configuration tasks can be performed through either interface, but some are
available only through the Service Terminal Interface.
Step-by-step instructions for all functions appear in Sections 5.0 through 7.0. These instructions
use examples of LCD screens to illustrate most functions, except those not available via the LCD.
Examples of all Service Terminal Interface screens appear in Appendix A - Service Terminal
Interface, along with instructions on how to connect to the Service Terminal Interface.
Table 6 lists all Liebert AC8 functions and shows whether they can be performed through the LCD
interface and where to find information.
Table 6
Function
VIEW STATUS FUNCTIONS
View Active Alarms
View Alarm Log
View Event Log
View Trend Log
View Input Status
View Output Status
View Pager Numbers
View Operation
View Control Status
SILENCE ALARM & BACK UP LOGS FUNCTIONS
Silence Alarm (On the LCD, press any key to silence an alarm)
Back Up Log Files
SYSTEM & CONTROL FUNCTIONS
Login
Setup System
Setup Inputs
Setup Common Alarm
Setup Sensor
Setup Zones
Setup Outputs
Setup Modem & Pagers
Initialization String
Enter Liebert AC8 Phone Number
Modem
Enable Modem Diagnostic Messages
Setup
Change Modem Dial Prefix
Change Modem Hang Up Delay After a Call
Pager Number & PIN
Pager
Setup
Communications Check
Setup System Info
Change Password
Change Date & Time/Automatic Daylight Saving Time
Setup Site ID
Connect Battery
Backup and Upload Configuration File
Setup Serv Ph Num - Enter Phone Number
Setup Serv Ph Num - Communications Check
Factory Defaults
Perform Firmware Update
Initiate Remote Alarm Test
Setup Operation
Setup I/O Matrix
Override Output
Clear Alarms & Logs
Clear Active Alarms
Clear the Alarm Log
Clear the Event Log
Clear the Trend Logs
Liebert AC8
22
Where to find:
Instructions on
Service Terminal
using function
screen examples
page 26
page 27
page 28
page 29
page 31
page 32
page 33
page 34
page 33
page 93
page 94
page 95
page 96
page 97
page 97
page 98
page 99
page 99
page 36
page 37
page 100
page 101
page 39
page 41
page 41
page 44
page 45
page 51
page 53
page 55
page 55
page 57
page 57
page 57
page 57
page 59
page 61
page 63
page 64
page 64
page 65
page 65
page 66
page 69
page 70
page 71
page 71
page 73
page 74
page 81
page 83
page 84
page 84
page 84
page 85
page 85
page 103
page 104
page 105
page 105
page 106
page 124
page 107
page 108
page 109
page 109
page 109
page 109
page 109
page 108
page 108
page 110
page 110
page 111
page 111
page 111
page 112
page 113
page 113
page 113
page 114
page 114
page 115
page 124
page 121
page 122
page 122
page 122
page 123
page 123
Overview of Menus
4.1
4.2
4.3
Description
These features are available to all users. This permits all personnel to check the
status of any monitored equipment or location. From this menu, any user may:
View current monitoring dataactive alarms and the status of inputs and outputs
View data stored in alarm, event and trend logs
View pager numbers
View auto sequencing and standby testing status
These featuresavailable via the Service Terminal Interface onlyallow users to:
Silence the audible alarm
Back up the alarm, event and trend logs
These options require a password. Authorized users may:
Configure the Liebert AC8
Override automatic control of outputs to force an output ON or OFF
Clear active alarms and delete all records in the alarm, event and trend logs
23
Liebert AC8
Overview of Menus
Figure 8
Main Menu
VIEW STATUS
SYSTEM AND CONTROL
=SELECT
=NEXT
ACTIVE ALARMS
ALARM LOG
EVENT LOG
TREND LOG
INPUT STATUS
OUTPUT STATUS
PAGER NUMBERS
OPERATION
CONTROL STATUS
Liebert AC8
VIEW STATUS
> SYSTEM AND CONTROL
=SELECT
See Section
5.0
=NEXT
SETUP SYSTEM
OVERRIDE OUTPUT
CLEAR ALARMS & LOGS
24
7.0
=SELECT
See Section
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
See Section
See Section
7.2
7.12
7.13
5.0
View Operation
Figure 9 shows the main options available from the View Status menu.
Figure 9
Main Menu
> VIEW STATUS
SYSTEM AND CONTROL
=SELECT
=NEXT
View Status
VIEW
VIEW
VIEW
VIEW
VIEW
VIEW
VIEW
VIEW
VIEW
ACTIVE ALARMS
ALARM LOG
EVENT LOG
TREND LOG
INPUT STATUS
OUTPUT STATUS
PAGER NUMBERS
OPERATION
CONTROL STATUS
/ STATUS
+80.00 DEG
------ DEG
+79.50 RH
NORMAL
ALARM
EVENT
ALARM
ALARM
EVENT
NORMAL
NORMAL
MODEM
INTERNAL FAULT
29-AUG-05
09:20:00
DEVICE_1 FORCE ON
CONTACT CLOSED
06-MAY-05
02:47:03
DEVICE_8 ALARM
CONTACT CLOSED
29-AUG-05
07:30:00
DEVICE_8 ON
CONTACT OPEN
05-MAY-05
05:22:17
OUTPUT
> DEVICE_1
DEVICE_2
DEVICE_3
DEVICE_4
DEVICE_5
DEVICE_6
DEVICE_7
DEVICE_8
/ STATUS
ALARM
OPERATING
OPERATING
OPERATING
STANDBY
NOT USED
NOT USED
NOT USED
PAGER TO VIEW?
> PAGER NUMBER 1
PAGER NUMBER 2
PAGER NUMBER 3
PAGER NUMBER 4
PAGER 1 NUMBER
9,,18005551212##
See
Sec.
5.7
See
Section
5.3
SENSOR TO VIEW?
> SENSOR_1
SENSOR_2
SENSOR_3
SENSOR_4
View Operation
>
See
Section
5.4
CONTROL STATUS
RELAY 1 OFF
RELAY 2 OFF
AUTO SEQUENCING ON
DAY 01 OF 02 (08:55)
STANDBY TESTING OFF
PAGER 1 PIN
01234567891011121344
25
Liebert AC8
See
Sec.
5.9
5.1
Main Menu
The Active Alarm screen displays all alarms that are occurring, up to a > VIEW STATUS
SYSTEM AND CONTROL
maximum of 22.
=NEXT
=SELECT
A Current Alarm screen appears automatically whenever an alarm
occursexcept during setup. This screen can display only the two most
recent active alarms. To view any other active alarms, use the View
View Status Menu
Active Alarms feature.
> VIEW
VIEW
VIEW
From the Main Menu, use the arrows to choose View Status, as
VIEW
shown at right, and then press Enter .
VIEW
VIEW
From the View Status Menu, use the arrows to choose View
VIEW
Active Alarms and press Enter .
VIEW
VIEW
You may view active alarms at any time by using the following steps:
5.1.1
Active Alarms
ACTIVE ALARMS
ALARM LOG
EVENT LOG
TREND LOG
INPUT STATUS
OUTPUT STATUS
PAGER NUMBERS
OPERATION
CONTROL STATUS
Active Alarms
> ACTIVE ALARM 22/22
SENSOR_1
101.0 DEG
HIGH SETPOINT ALARM
SENSOR_2 ------ DEG
SENSOR PROBLEM
DEVICE_7 ALARM
CONTACT OPEN
BATTERY
CHECK BATTERY
Liebert AC8
26
5.2
Main Menu
5.2.1
Alarm Log
The Alarm Log screen displays up to 99 records showing alarm data,
including input alarms and other conditions, such as loss of power or
low battery. If the log contains any alarm records, the Alarm Log
screen displays details for each alarm:
the source of the alarm (for example, SENSOR_2 or MODEM)
the status of an input or output (80.0 DEG)
a brief description of the problem (HIGH SETPOINT ALARM or
INTERNAL FAULT)
the date and time the alarm occurred
Table 8 shows conditions that the alarm log records for digital inputs
and analog inputs and in the panel itself.
Table 8
SOURCE
CONDITIONS
RECORDED
Digital Input
ACTIVE ALARMS
ALARM LOG
EVENT LOG
TREND LOG
INPUT STATUS
OUTPUT STATUS
PAGER NUMBERS
OPERATION
CONTROL STATUS
Alarm Log
> ALARM RECORD 99/99
SENSOR_2
80.0 DEG
HIGH SETPOINT ALARM
29-AUG-05
09:29:10
MODEM
INTERNAL FAULT
29-AUG-05
09:20:00
DEVICE_8 ALARM
CONTACT CLOSED
29-AUG-05
07:30:00
Analog Input
ALARM
NORMAL
SOURCE
CONDITIONS
RECORDED
=SELECT
Panel
LOSS OF POWER
LOW BATTERY
CHECK BATTERY
BATTERY UNPLUGGED
ALARMS CLEARED
ALARM SILENCED
MODEM INTERNAL
FAULT
NO STANDBY AVAILABLE
STANDBY DEVICE FAILED
NO RESTART AVAILABLE
EMERGENCY PWR ALARM
If there are no alarms in the log, the screen displays the message:
NO ALARMS
5.2.2
27
Liebert AC8
5.3
Main Menu
5.3.1
=NEXT
=SELECT
ACTIVE ALARMS
ALARM LOG
EVENT LOG
TREND LOG
INPUT STATUS
OUTPUT STATUS
PAGER NUMBERS
OPERATION
CONTROL STATUS
Event Log
The Event Log screen displays up to 99 recent events. If the log
contains any event records, the Event Log screen displays details for
each event:
the event source (for example, PAGER or DEVICE_1)
the status of an input or output (FORCE ON)
a brief description of the event (UNSUCCESSFUL PAGE or CONTACT
CLOSED)
the date and time the event occurred
Table 9 shows conditions that the event log records for inputs and
outputs and in the panel itself.
Table 9
Event Log
> EVENT RECORD 99/99
PAGER
UNSUCCESSFUL PAGE
07-MAY-05
10:07:00
DEVICE_1 FORCE ON
CONTACT CLOSED
06-MAY-05
02:47:03
DEVICE_8 ON
CONTACT OPEN
05-MAY-05
05:22:17
SOURCE
Digital Input
CONDITIONS EVENT
RECORDED
NORMAL
Analog Input
HIGH SETPOINT EVENT
LOW SETPOINT EVENT
RETURN TO NORMAL
SENSOR PROBLEM
(denoted by dashes ------)
SOURCE
CONDITIONS ALARMS CLEARED
RECORDED
ALARM SILENCED
DIAL OUT TEST PASSED
DIAL OUT TEST FAILED
UNSUCCESSFUL PAGE
Panel
DEFAULT PASSWORD SET
MODEM RESET
TIME & DATE SET
USER LOGIN
NOT USED DEVICES IN ZONE
Digital Output
FORCE ON
DISABLED
STAGING DEVICE ON
FORCE OFF
AUTO
STAGING DEVICE OFF
RESTORED
HW FORCE ON
ON
STARTED
OFF
NO STANDBY OUTPUTS AVAILABLE
NO STANDBY TESTING DEVICE
AVAILABLE
EMERGENCY PWR ALARM
STAGING DISABLED
If there are no records in the log, the screen displays the message:
NO EVENTS
5.3.2
Liebert AC8
28
To delete all records in the event log, see 7.13 - Clear Alarms & Logs.
5.4
Main Menu
5.4.1
Select a Sensor
To select a sensor:
From the Main Menu, use the arrows to choose View Status,
then press Enter .
From the View Status Menu, use the arrows to choose View
Trend Log, then press Enter .
From the Sensor Selection Menu, use the arrows to choose the
sensor you want to viewSensor_1 in the example at rightand
press Enter .
5.4.2
=SELECT
ACTIVE ALARMS
ALARM LOG
EVENT LOG
TREND LOG
INPUT STATUS
OUTPUT STATUS
PAGER NUMBERS
OPERATION
CONTROL STATUS
SENSOR TO VIEW?
> SENSOR_1
SENSOR_2
The Trend Log screen displays up to 100 records for the selected sensor.
=NEXT =SELECT
If the log contains records, the screen displays details for each reading:
SENSOR_3
SENSOR_4
the name of the selected sensor (for example, SENSOR_1)
the reading (75.4 DEG)
Trend Log
a brief description of the reading status (NORMAL)
> TREND LOG 100/100
the date and time of the reading
SENSOR_1
75.4 DEG
Table 10 shows conditions that the trend log records for analog inputs. NORMAL
28-AUG-05
15:45:51
Each analog input has its own trend log.
SENSOR_1
70.5 DEG
Table 10 Trend log conditions
LOW SETPOINT EVENT
28-AUG-05
15:15:51
SOURCE
Analog Input
SENSOR_1
79.9 DEG
CONDITIONS
LOW SETPOINT ALARM
RETURN TO NORMAL
RECORDED
LOW SETPOINT EVENT
28-AUG-05
14:45:21
HIGH SETPOINT ALARM
HIGH SETPOINT EVENT
RETURN TO NORMAL
NORMAL
SENSOR PROBLEM (denoted by dashes ------)
If there are no records in the log, the screen displays the message:
NO TRENDS
5.4.3
29
Liebert AC8
To delete all records in the trend logs, see 7.13 - Clear Alarms & Logs.
Liebert AC8
30
5.5
Main Menu
The Input Status option allows you to view the current status of all
inputs: the four analog sensor inputs and the eight digital inputs.
=NEXT
From the Main Menu, use the arrows to choose View Status,
then press Enter .
From the View Status Menu, use the arrows to choose View
Input Status, then press Enter .
5.5.1
Input Status
The Input Status screen displays the status of each analog sensor and
digital input.
Analog Sensor Inputs
The following details are displayed for analog sensor inputs:
the name of the analog sensor input (for example, SENSOR_1)
the current reading (+80.00 DEG)values are updated constantly
while being viewed
There are three possible states for an analog input, as shown in
Table 11.
Table 11
State
Functional
Problem with
connection
Not configured
Description
Reading-for example, +80.00 DEG or +79.50 RH
Dashes (------)
=SELECT
ACTIVE ALARMS
ALARM LOG
EVENT LOG
TREND LOG
INPUT STATUS
OUTPUT STATUS
PAGER NUMBERS
Input Status
INPUT / STATUS
> SENSOR_1 +80.00 DEG
SENSOR_2 ------ DEG
SENSOR_3
SENSOR_4 +79.50 RH
> DEVICE_1 ALARM
DEVICE_2 NORMAL
DEVICE_3 NORMAL
DEVICE_4 NORMAL
DEVICE_5 ALARM
DEVICE_6 EVENT
DEVICE_7 NORMAL
DEVICE_8 NORMAL
Blank
NOTE
If the status displays dashes (------), the Liebert AC8 was unable to take a reading. There
may be a connection problem.
If the status is blank, the sensor is not configured as being connected.
Digital Inputs
The following details appear for digital inputs:
the name of the digital input (for example, DEVICE_1)
the current status (NORMAL)values are updated constantly while being viewed
There are three possible states for a digital input, as shown in Table 12.
Table 12
State
NORMAL
ALARM
EVENT
31
Liebert AC8
5.6
Main Menu
The Output Status option allows you to view the current status of all
eight outputs.
=NEXT
From the Main Menu, use the arrows to choose View Status,
then press Enter .
From the View Status Menu, use the arrows to choose View
Output Status, then press Enter .
5.6.1
Output Status
The Output Status screen displays the status of each digital output.
The following details appear for digital outputs:
the name of the output (for example, DEVICE_1)
the current status (ALARM)values are updated constantly while
being viewed
There are eight possible states for a digital output, as shown in
Table 13.
Table 13
State
OPERATING
STANDBY
ALARM
FORCE ON
FORCE OFF
HW FORCE ON
STAGED ON
EPOP OFF
PENDING
NOT USED
Description
Device operating, or ON
Device in standby mode
Device in alarm
Device forced ON by operator
Device forced OFF by operator
Device forced ON by hardware switch
Device staged on by high sensor
Device forced off by emergency power operation
Pending delay timer
Device not used
=SELECT
ACTIVE ALARMS
ALARM LOG
EVENT LOG
TREND LOG
INPUT STATUS
OUTPUT STATUS
PAGER NUMBERS
OPERATION
CONTROL STATUS
Output Status
OUTPUT / STATUS
> DEVICE_1 ALARM
DEVICE_2 OPERATING
DEVICE_3 OPERATING
DEVICE_4 OPERATING
Liebert AC8
32
5.7
Main Menu
The Liebert AC8 may be set up to dial pager numbers when an alarm is > VIEW STATUS
SYSTEM AND CONTROL
detected. Up to four pagers may be configured, as described in 7.8 Setup System - Setup Modem & Pagers.
=NEXT
=SELECT
The View Pager Numbers option allows you to view the pager numbers
and PINs for all configured pagers. Use the following steps to select a
View Status Menu
pager and view its information.
5.7.1
Select a Pager
To select a pager:
From the Main Menu, use the arrows to choose View Status,
then press Enter .
From the View Status Menu, use the arrows to choose View
Pager Numbers, then press Enter .
From the Pager Selection screen, use the arrows to choose the
pager you want to viewPager Number 1 in the example at
rightand press Enter .
Use the following steps to view a pager number or PIN for the
selected pager.
5.7.2
VIEW
VIEW
VIEW
VIEW
VIEW
VIEW
> VIEW
VIEW
VIEW
ACTIVE ALARMS
ALARM LOG
EVENT LOG
TREND LOG
INPUT STATUS
OUTPUT STATUS
PAGER NUMBERS
OPERATION
CONTROL STATUS
Pager Selection
PAGER TO VIEW?
> PAGER NUMBER 1
PAGER NUMBER 2
PAGER NUMBER 3
PAGER NUMBER 4
Pager Menu
Choose View Pager Number from the Pager Menu and press
> VIEW PAGER NUMBER
VIEW PAGER PIN
Enter .
The Pager Number screen displays the number that is configured
for the selected pager.
Pager Number
In the example at right, the telephone number is preceded by A to
PAGER 1 NUMBER
dial an alphanumeric pager and includes a comma (,) to pause two A1,8005551212
seconds after dialing 1 before proceeding to dial the area code and
number. To change this number, see 7.8.3 - Pager Setup - Pager
Number and PIN.
Press ESC to return to the Pager Menu.
5.7.3
Pager Menu
Choose View Pager PIN from the Pager Menu and press
Enter .
The Pager PIN screen displays the PIN that is configured for the
selected pager. To change this number, see 7.8 - Setup System Setup Modem & Pagers.
Press ESC to return to the Pager Menu.
33
Pager PIN
PAGER 1 PIN
01234567891011121344
Liebert AC8
5.8
View Operation
Main Menu
The Operation option allows you to view the current settings for Auto
Sequencing, Standby Testing and Staging in each zone.
Use the following steps to select a zone and view the status of these
features.
5.8.1
=SELECT
Select a Zone
To select a zone:
VIEW
VIEW
VIEW
VIEW
VIEW
VIEW
VIEW
> VIEW
VIEW
From the Main Menu, use the arrows to choose View Status,
then press Enter .
From the View Status Menu, use the arrows to choose View
Operation, then press Enter .
From the Zone Selection screen, use the arrows to choose the
zone you want to viewZone 1 in the example at rightand press
Enter .
5.8.2
=NEXT
View Operation
The Operation screen displays the following details for each feature:
the name of the feature (for example, AUTO SEQUENCING)
the status (ON or OFF)
the date and time when Auto Sequencing or Standby Testing is
scheduled to occur (for example, DAY 01 OF 02 (08:55). The time
appears in the format HH:MM (hours and minutes in military
time)
OR
the target setpoint and sensitivity level that will initiate Staging
To change these settings, see the following sections in 7.10 - Setup
Operation:
7.10.1 - Turn Automatic Sequencing On or Off
7.10.2 - Turn Standby Testing On or Off
Press ESC to return to the Zone Selection Menu.
Liebert AC8
34
ACTIVE ALARMS
ALARM LOG
EVENT LOG
TREND LOG
INPUT STATUS
OUTPUT STATUS
PAGER NUMBERS
OPERATION
CONTROL STATUS
Zone Selection
SELECT ZONE FOR
VIEWING
>
ZONE 1
=NEXT
=EDIT
Operation
AUTO SEQUENCING ON
DAY 01 OF 02 (08:55)
STANDBY TESTING OFF
STAGING OFF
5.9
Main Menu
The Control Status option allows you to view the current status of the
two control relays.
=NEXT
From the Main Menu, use the arrows to choose View Status,
then press Enter .
From the View Status Menu, use the arrows to choose View
Control Status, then press Enter .
5.9.1
Control Status
The Control Status screen displays the status of each relay.
the name of the output (for example, RELAY 1)
the status (ON or OFF)
=SELECT
ACTIVE ALARMS
ALARM LOG
EVENT LOG
TREND LOG
INPUT STATUS
OUTPUT STATUS
PAGER NUMBERS
OPERATION
CONTROL STATUS
Control Status
CONTROL STATUS
RELAY 1 OFF
RELAY 2 OFF
35
Liebert AC8
6.0
6.1
SILENCE ALARM
Silence alarm and reset
common alarm relay if
common alarm relay is
configured to reset with
silence alarm
1=SILENCE ALARM
2=RETURN TO MAIN MENU
SELECT A NUMBER:1
>ALARM HAS BEEN SILENCED
Liebert AC8
36
6.2
SELECT A NUMBER:1
4. At the prompt to initiate a backup of the selected log file, enter Y (Yes - begin) or N (No - cancel),
then press Enter. The current setting appears in brackets[N] in the following example.
>INITIATE A BACKUP OF ALARM LOG-YES(Y) OR NO(N)?
>[N]
>[
37
Liebert AC8
NOTE
The following instructions refer to the Microsoft Windows HyperTerminal program. These
steps may vary for other communications programs.
5. At the top of the HyperTerminal window, shown below, click on Transfer, then on Receive File.
Enter folder
Select Xmodem
Liebert AC8
38
7.0
Special characters
A-Z, 0-9
The System and Control options require a password to prevent unauthorized users from making
changes to the system.
This section presents step-by-step instructions for each of the following:
Login - enter the password
Setup System - configure inputs, outputs, modem, pagers, system features
Override Output - manually override automatic control of outputs; release the override
Clear Alarms & Logs - clear active alarms; delete records from the alarm, event and trend logs
NOTE
If an alarm occurs while a user is logged on, the LCD backlight will flash and the audible
alarm will sound. To obtain specific information about the alarm, you must access the Active
Alarm screen (see 5.1 - View Active Alarms) or the Alarm Log (see 5.2 - View Alarm Log).
7.1
Login
Users must enter a password to access any of the system and control
options. The password consists of four characters (see Table 14 for
valid characters); the default password is AAAA. To set up or change
the password, see 7.9.1 - Change Password.
To log in:
From the Main Menu, use the arrows to choose System and
Control, then press Enter , as shown at right.
Use the arrows to choose System and Control, and press
Enter . The Login menu appears.
To enter your password (the default is AAAA):
Use the arrows to choose a character.
Press Enter to advance to the next character position.
When finished, press Enter again.
The System and Control Menu appears next, with these options that
are described in the following sections:
Setup System (Section 7.2 - Section 7.9)
Override Output (Section 7.12)
Clear Alarms & Logs (Section 7.13)
Main Menu
VIEW STATUS
> SYSTEM AND CONTROL
=NEXT
=SELECT
Login
LOGIN
AAAA
=SELECT =NEXT/END
NOTE
If, after logging in, you press the ESC key to return to a previous screen that is not passwordprotected, you must log in again, including entering your password if you wish to access
password-protected functions.
Figure 10 shows the main options available from the System & Control menu.
39
Liebert AC8
Main Menu
VIEW STATUS
> SYSTEM AND CONTROL
=SELECT
=NEXT
Login Screen
LOGIN
AAAA
=NEXT/END
=SELECT
INPUTS
COMMON ALARM
SENSOR
ZONES
OUTPUTS
MODEM&PAGERS
SYSTEM INFO
OPERATION
I/O MATRIX
Select Output
See
Section
7.2
OVERRIDE OUTPUT
> DEVICE_1 AUTO
DEVICE_2 AUTO
.
.
.
DEVICE_8
CLEAR
CLEAR
CLEAR
CLEAR
ACTIVE ALARMS
ALARM LOG
EVENT LOG
TREND LOGS
See
Section
7.13
AUTO
Override Output
SELECT DEVICE_1
AUTO
Setup Inputs
SELECT INPUT
> DEVICE_1 NO-AL-L
DEVICE_2 NO-AL-L
.
.
.
7.4
Setup Sensor
7.5
SENSOR_4 +79.50 RH
DEVICE_8
NO-AL-L
SETUP DEVICE_1
LABEL: DEVICE_1
NORM OPEN/CLOSE: NO
ALARM/EVENT: AL
LATCHED: Y
DELAY: 00:01
SETUP SENSOR_1
CONNECTED: N
LABEL: SENSOR_1
UNITS: DEG
4 mA: +045.0
20 mA: +096.0
OFFSET: +000.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +0050.0
HIGH SETPT: +0090.0
SENSOR DELAY: 00:01
SELECT PAGER
PAGER NUMBER 1
.
.
.
See
Sec.
7.8
Liebert AC8
See Figure 11
for details on
Setup System Info
40
Setup Outputs
See
Sec.
7.6
SETUP ZONES
> ZONE 1:4
ZONE 2:0
ZONE 3:0
ZONE 4:0
ZONE
See
Sec.
7.7
SELECT OUTPUT
> DEVICE_1 NO-OP-E-E
DEVICE_2 NO-ST-E-E
.
.
.
DEVICE_8 NO-NU-E-E
# DEVICES IN ZONE
SETUP DEVICE_1
NORM OPEN/CLOSE: NO
MODE: OPERATING
IN ALARM: ENABLE
EMERG OP: ENABLE
1:4
Setup Operation
SELECT ZONE FOR
See
THE OPERATION
Sec.
ZONE 1
7.9 >
CHANGE PASSWORD
CHANGE DATE & TIME
SETUP SITE ID
CONNECT BATTERY
SETUP SERV PH NUM
FACTORY DEFAULTS
PAGER NUMBER 4
Setup Zones
SELECT SENSOR
See
> SENSOR_1 +80.00 DEG Sec.
.
.
.
See
Sec.
7.11
SELECT INPUT
DEVICE_1
DEVICE_2
SELECT SENSOR
SENSOR_1 HIGH STPT
SENSOR_1 LOW STPT
DEVICE_8
SENSOR_4 LOW
See Figure 12
for details on
Setup Operation
1 CONTROL RELAY
1 2
Y N
.
.
.
.
.
.
STPT
1H CONTROL RELAY
1 2
Y N
7.2
7.3
Setup Inputs
Setup Common Alarm
Setup Sensor
Setup Zones
Setup Outputs
Setup Modem & Pagers
Setup System Info
Setup Operation
Setup I/O Matrix
INPUT
NO-AL-L
NO-AL-L
=SELECT
NO-AL-L
NO-AL-L
NO-AL-L
NO-AL-L
NO-AL-L
NO-AL-L
Feature
LABEL
NORM OPEN/CLOSE
ALARM/EVENT
LATCHED
DELAY
Default
DEVICE_1
NO (Normally Open)
AL (Alarmable)
L (Latched) / Y (Yes)*
00:01 (1 second)
Other Options
Any name (up to eight characters)
NC (Normally Closed)
EV (Event)
NL (Unlatched) / N (No)*
Any time (in minutes and seconds) from 00:00 to 99:59
* NOTE: Different abbreviations are used to designate a digital input as Latched or Unlatched as shown below.
Settings - Select Input
Menu (see Section 7.3)
Unlatched
NL (Not Latched)
Latched
L (Latched)
Y (Yes, latched)
41
Liebert AC8
7.3.1
Each input has a default label (Device_1, Device_2, etc.) that you may
change to a more descriptive name for ease in recognizing alarms and
events associated with the input. The label may consist of up to eight
characters (see Table 14 for valid characters).
The device name assigned through this menu is also displayed for the
corresponding output.
Table 16
Label
Applies to:
Label
Applies to:
Device_1
Device_2
Device_3
Device_4
Device_5
Device_6
Device_7
Device_8
SETUP DEVICE_1
> LABEL: DEVICE_1
NORM OPEN/CLOSE: NO
ALARM/EVENT: AL
=NEXT
=SELECT
LATCHED: Y
DELAY: 00:01
Change Label
CHANGE LABEL
DEVICE_1
=SELECT =NEXT/END
7.3.2
7.3.3
Liebert AC8
42
=END
Alarmable / Event
IS INPUT AN ALARM
OR EVENT? AL
=AL/EV
=END
7.3.4
Latched / Unlatched
IS ALARM
LATCHED? N
=Y/N
=END
The only way to reset latched alarms is by clearing active alarms. This
step is required to return latched points to their normal state. For
details, see 7.13.1 - Clear Active Alarms.
7.3.5
Each input may be set up with a specified time delay between the
occurrence of an alarm or eventa monitored device changes state
and any response by the Liebert AC8. This feature can prevent
needless responses to transient conditions.
This delay is the amount of time that must elapse before the Liebert
AC8 acknowledges the change of state in the monitored device and
takes any further action, such as dialing configured pagers. The
default time delay is 1 second (displayed as 00 MIN : 01 SEC).
The time delay applies only when a monitored device changes from its
normal statefor example, the Liebert AC8 detects a closed contact
that is defined as Normally Open.
When the monitored device returns to its normal state, the Liebert
AC8 acknowledges the change of state immediately.
SETUP DEVICE_1
LABEL: DEVICE_1
NORM OPEN/CLOSE: NO
ALARM/EVENT: AL
=NEXT
=SELECT
LATCHED: N
DELAY: 00:01
Delay Time
DELAY TIME BEFORE
TRIGGER?
00 MIN : 01 SEC
=SELECT =NEXT/END
43
Liebert AC8
7.4
Liebert AC8
44
SETUP INPUTS
> SETUP COMMON ALARM
SETUP SENSOR
=NEXT =SELECT
SETUP ZONES
SETUP OUTPUTS
SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP OPERATION
SETUP I/O MATRIX
=END
7.5
To configure a sensor:
SETUP INPUTS
SETUP COMMON ALARM
> SETUP SENSOR
=NEXT =SELECT
SETUP ZONES
SETUP OUTPUTS
SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP OPERATION
SETUP I/O MATRIX
SENSOR
+80.00 DEG
------ DEG
=SELECT
+79.50 RH
Feature
Default
Other Options
CONNECTED*
N (Not connected)*
Y (Connected)**
LABEL
SENSOR_1
UNITS
DEG
4 mA
+045.0
20 mA
+096.0
OFFSET
+000.0
ALARM/EVENT
AL (Alarmable)
EV (Event)
LATCHED
N (Unlatched)
Y (Latched)
LOW SETPT
+0050.0
HIGH SETPT
+0090.0
SENSOR DELAY
00:01 (1 second)
* If a sensor is configured as N (Not connected), the display will show an empty reading (blank spaces).
** If a sensor is configured as Y (Connected) and is functioning properly, the display will show a reading.
If the connected sensor is not functioning properly, the display will show dashes (------) indicating a problem.
45
Liebert AC8
7.5.1
SETUP SENSOR_1
> CONNECTED: N
LABEL: SENSOR_1
=NEXT =SELECT
UNITS: DEG
4 mA: +045.0
20 mA: +096.0
OFFSET: +000.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +0050.0
HIGH SETPT: +0090.0
SENSOR DELAY: 00:01
Sensor Connected
IS THE SENSOR
CONNECTED? N
=Y/N
7.5.2
=END
Each sensor has a default label (Sensor_1, Sensor_2, etc.) that you may
change to a more descriptive name. The label may consist of up to eight
characters (see Table 14 for valid characters).
From the Setup Sensor Menu, choose Label for the selected sensorLabel: Sensor_1 in the exampleand press Enter .
To change the sensors label, which may consist of up to eight characters:
Use the arrows to choose a character.
Press Enter to advance to the next character position.
When finished, press Enter again.
SETUP SENSOR_1
CONNECTED: Y
> LABEL: SENSOR_1
=NEXT =SELECT
UNITS: DEG
4 mA: +045.0
20 mA: +096.0
OFFSET: +000.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +0050.0
HIGH SETPT: +0090.0
SENSOR DELAY: 00:01
7.5.3
SETUP SENSOR_1
CONNECTED: Y
LABEL: ROOM_TMP
=NEXT =SELECT
> UNITS: DEG
4 mA: +045.0
20 mA: +096.0
OFFSET: +000.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +0050.0
HIGH SETPT: +0090.0
SENSOR DELAY: 00:01
Liebert AC8
46
7.5.4
Change 4 mA Value
For the 4 mA value, enter the smallest value for the range of the
sensorfor example, 50F for a temperature sensor with a range of
50F to 90F.
The default value for each sensor is +045.0. Values that can be entered
range from -999.9 to +999.9.
To enter a new value:
From the Setup Sensor Menu, choose 4 mA for the selected sensor
and press Enter .
To change the 4 mA value:
Use the arrows to choose a character.
Press Enter to advance to the next character position.
When finished, press Enter again.
SETUP SENSOR_1
CONNECTED: Y
LABEL: ROOM_TMP
=NEXT =SELECT
UNITS: DEG
> 4 mA: +045.0
20 mA: +096.0
OFFSET: +000.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +0050.0
HIGH SETPT: +0090.0
SENSOR DELAY: 00:01
Change 4 mA Value
CHANGE 4 mA VALUE
4 mA: +050.0
=SELECT =NEXT/END
7.5.5
Change 20 mA Value
For the 20 mA value, enter the largest value for the range of the
sensorfor example, 90F for a temperature sensor with a range of
50F to 90F.
The default value for each sensor is +096.0. Values that can be entered
range from -999.9 to +999.9.
To enter a new value:
From the Setup Sensor Menu, choose 20 mA for the selected sensor and press Enter .
To change the 20 mA value:
Use the arrows to choose a character.
Press Enter to advance to the next character position.
When finished, press Enter again.
SETUP SENSOR_1
CONNECTED: Y
LABEL: ROOM_TMP
=NEXT =SELECT
UNITS: DEG
4 mA: +050.0
> 20 mA: +096.0
OFFSET: +000.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +0050.0
HIGH SETPT: +0090.0
SENSOR DELAY: 00:01
Change 20 mA Value
CHANGE 20 mA VALUE
20 mA: +090.0
=SELECT =NEXT/END
7.5.6
SETUP SENSOR_1
CONNECTED: Y
LABEL: ROOM_TMP
=NEXT =SELECT
UNITS: DEG
4 mA: +050.0
20 mA: +090.0
> OFFSET: +000.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +0050.0
HIGH SETPT: +0090.0
SENSOR DELAY: 00:01
47
Liebert AC8
7.5.7
SETUP SENSOR_1
CONNECTED: Y
LABEL: ROOM_TMP
=NEXT =SELECT
UNITS: DEG
4 mA: +050.0
20 mA: +090.0
OFFSET: +005.0
> ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +0050.0
HIGH SETPT: +0090.0
SENSOR DELAY: 00:01
Alarmable / Event
IS SENSOR AN ALARM
OR EVENT? AL
=AL/EV
7.5.8
Liebert AC8
48
=END
Latched / Unlatched
IS ALARM
LATCHED? N
=Y/N
=END
7.5.9
When the sensor detects a condition below the Low Setpoint value, an
alarm or event will occur, depending on the sensor configuration.
The Low Setpoint value must not be set below the sensors 4 mA value
plus the offset value. For example, if the 4 mA value is 50F and the
Offset value is 5F, the Low Setpoint must be 55F or higher.
The default Low Setpoint for each sensor is +0050.0. Values that can
be entered range from:
the 4 mA value + the Offset value (in the example, 50+5=55)
to
the 20 mA value + the Offset value (in the example, 90+5=95)
To view or change these values, see 7.5.4 - Change 4 mA Value,
7.5.5 - Change 20 mA Value and 7.5.6 - Change Offset Value.
To enter a new value:
From the Setup Sensor Menu, choose Low Setpt for the selected
sensor and press Enter .
To change the Low Setpoint:
Use the arrows to choose a character.
Press Enter to advance to the next character position.
When finished, press Enter again.
SETUP SENSOR_1
CONNECTED: Y
LABEL: ROOM_TMP
=NEXT =SELECT
UNITS: DEG
4 mA: +050.0
20 mA: +090.0
OFFSET: +005.0
ALARM/EVENT: AL
LATCHED: N
> LOW SETPT: +0050.0
HIGH SETPT: +0090.0
SENSOR DELAY: 00:01
When the sensor detects a condition above the High Setpoint value, an
alarm or event will occur, depending on the sensor configuration.
The High Setpoint value must not be set above the sensors 20 mA value
plus the offset value. For example, if the 20 mA value is 90F and the
Offset value is 5F, the High Setpoint must be 95F or lower.
The default High Setpoint for each sensor is +0090.0. Values that can
be entered range from:
the 4 mA value + the Offset value (in the example, 50+5=55)
to
the 20 mA value + the Offset value (in the example, 90+5=95)
To view or change these values, see 7.5.4 - Change 4 mA Value,
7.5.5 - Change 20 mA Value and 7.5.6 - Change Offset Value.
To enter a new value:
From the Setup Sensor Menu, choose High Setpt for the selected
sensor and press Enter .
To change the High Setpoint:
Use the arrows to choose a character.
Press Enter to advance to the next character position.
When finished, press Enter again.
49
SETUP SENSOR_1
CONNECTED: Y
LABEL: ROOM_TMP
=NEXT =SELECT
UNITS: DEG
4 mA: +050.0
20 mA: +090.0
OFFSET:
+005.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +0060.0
> HIGH SETPT: +0090.0
SENSOR DELAY: 00:01
Liebert AC8
Each sensor may be set up with a specified time delay between the
triggering of a high or low setpointa monitored sensor crosses the
high or low setpoint thresholdand any response by the Liebert AC8.
This feature can prevent transient conditions from prompting
unnecessary responses.
This delay is the amount of time that must elapse before the Liebert
AC8 acknowledges the change in the monitored sensor and takes any
further action, such as dialing configured pagers. The default time
delay is 1 second (displayed as 00 MIN : 01 SEC).
The time delay applies to the triggering of a high or low setpoint and
also after the monitored sensor returns to its normal state. When the
monitored device returns to its normal state, the specified time delay
must elapse before the Liebert AC8 acknowledges the return-to-normal
condition.
SETUP SENSOR_1
CONNECTED: Y
LABEL: ROOM_TMP
=NEXT =SELECT
UNITS: DEG
4 mA: +050.0
20 mA: +090.0
OFFSET: +005.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +0060.0
HIGH SETPT: +0085.0
SENSOR DELAY: 00:01
Delay Time
DELAY TIME BEFORE
TRIGGER?
00 MIN : 01 SEC
=SELECT =NEXT/END
Liebert AC8
50
7.6
7.6.1
Setup Zones
SETUP ZONES
> ZONE 1:4
ZONE 2:0
=NEXT
=SELECT
ZONE 3:0
ZONE 4:0
Set Up a Zone
From the Setup Zones Menu, choose a zonefor example,
Zone 1and press Enter .
In the Number of Devices screen, use the arrows to select the
number of outputs for this zone, then press Enter . The example
at right shows four outputs in Zone 1.
Number of Devices
# DEVICES IN ZONE
ZONE 1:4
=SELECT =NEXT/END
Zone 1
Zone 2
Zone 3
Zone 4
(none)
Outputs
1-4
Outputs
5-6
Outputs
7-8
(none)
MESSAGES:
1. Total devices > 8
51
Liebert AC8
Liebert AC8
Default zones
Zone
Zone 1
Zone 2
Zone 3
Zone 4
4 (Outputs 1-4)
0
0
0
52
7.7
OUTPUT
NO-OP-E-E
NO-ST-E-E
=SELECT
NO-ST-E-E
NO-ST-E-E
NO-NU-E-E
NO-NU-E-E
NO-NU-E-E
NO-NU-E-E
Use the steps following Table 19 to change the default settings for any
digital output.
Table 19
Feature
Default
Other Options
NORM OPEN/CLOSE
NO (Normally Open)
NC (Normally Closed)
MODE*
OP (Operating)
ST (Standby)
NU (Not Used)
IN ALARM
E (Enable)
D (Disable)
EMERG OP
E (Enable)
D (Disable)
* Outputs defined as Not Used should be kept in a separate zone that does not include
any outputs defined as Operating or Standby. The Auto Sequencing feature will not
function properly in a zone with outputs defined as Not Used. See 7.10.1 - Turn
Automatic Sequencing On or Off for more information.
7.7.1
Change State
SET TO NORMAL OPEN
OR NORMAL CLOSE? NO
=NO/NC
53
=END
Liebert AC8
7.7.2
Set Mode
7.7.3
7.7.4
SET MODE: OP
=OP/ST/NU
=EDIT
=EDIT
Enable or Disable a Device during Emergency Power Operation Setup Outputs Menu
You may choose whether to Enable or Disable an output when the
Liebert AC8 is in emergency power operation. The default setting for
all output points is Enabled.
From the Setup Outputs Menu, choose Emerg Op, as shown at
right, and press Enter .
To make a change, use the arrows to choose Enable or Disable
to specify what occurs in emergency power operation.
Press Enter .
7.7.5
SETUP DEVICE_1
NORM OPEN/CLOSE: NO
> MODE: OPERATING
=NEXT
=SELECT
IN ALARM: ENABLE
EMERG OP: ENABLE
SETUP DEVICE_1
NORM OPEN/CLOSE: NO
MODE: OPERATING
=NEXT
=SELECT
IN ALARM: ENABLE
> EMERG OP: ENABLE
=EDIT
=E/D
Each output has an associated jumper that can help prevent undesired
effects when the controller board loses power. For example, without the
proper fail-safe jumper setting, a loss of power might close a switch that is Normally Open (NO)
perhaps shutting off an environmental unit or a fan or closing a valve.
This fail-safe jumper setting is unrelated to configuring an output as Normally Open (NO) or
Normally Closed (NC), as described in 7.7.1 - Define Output as Normally Open or Normally
Closed.
To configure a digital output jumper for a loss of power:
Set the jumper in the OFF position (factory default) to make the output Normally Open (NO).
Set the jumper in the ON position to make the output Normally Closed (NC).
For more information, see 3.2.3 - Setting the Digital Output Jumpers.
Liebert AC8
54
7.8
7.8.1
Modem supports:
Pager access
9600 baud, even parity, 7 data bits, 1 stop bit and TAPI protocol version 1.8
International
dialing
For calls involving countries that do not support country code B5 (see Table 22):
Modem model MT5600SMI is required (model number is on the modem label).
+GCI=xx (xx is the country code) must be added to the initialization string (see Step 7 in
this section).
Default
Other Options
ATS0=1
N (disable)
Y (enable)
ATE0X4DT
Any string
10 seconds
55
Liebert AC8
SETUP INPUTS
SETUP COMMON ALARM
SETUP SENSOR
=NEXT =SELECT
SETUP ZONES
SETUP OUTPUTS
> SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP OPERATION
SETUP I/O MATRIX
4. From the Setup System Menu, shown at right, use the arrows
to choose Setup Modem&Pagers and press Enter .
5. Use the arrows to choose Setup Modem from the Pagers &
Modem Menu and press Enter .
6. The Setup Modem Menu displays the initialization string
(Init String), which may consist of up to 40 characters (see
Table 14 for valid characters). The default Init String is ATS0=1.
International Dialing
SETUP PAGERS
> SETUP MODEM
=NEXT
=SELECT
Country codes
Country
Argentina
Code*
07
Country
Code*
Country
Finland
FD
Italy
Code*
FD
Country
Code*
Philippines
B5
Australia
09
France
FD
Japan
00
Portugal
FD
Austria
FD
Germany
FD
Korea
B5
Slovak Republic
FD
Belgium
FD
Greece
FD
Liechtenstein
FD
Spain
FD
Canada
B5
Hong Kong
99
Luxembourg
FD
Sweden
FD
China
B5
Hungary
FD
Mexico
B5
Switzerland
FD
Cyprus
FD
Iceland
FD
Netherlands
FD
Taiwan
FE
Czech Republic
FD
Indonesia
99
New Zealand
7E
United Kingdom
FD
Denmark
FD
Ireland
FD
Norway
FD
United States
B5
* B5 is the default settinginitialization string +GCI=xx is not needed for these countries
Liebert AC8
56
7.8.2
SETUP MODEM&PAGERS
Input pager and
modem information
Select pager or modem
CURRENT NUMBER
*******************
An "A" is required
as 1st character
for an alpha pager,
an "N" for a numeric
pager, and an "M"
for a remote modem.
*******************
1=PAGER NUMBER 1
2=PAGER NUMBER 2
3=PAGER NUMBER 3
4=PAGER NUMBER 4
5=MODEM CONFIGURATION
6=RETURN TO SETUP MENU
7=RETURN TO MAIN MENU
SELECT A NUMBER:5
At the Change Modem Initialization String prompt, you may press Enter to bypass this option (or
see 7.8.1 - Modem Setup - Initialization String for instructions on entering the string).
>CHANGE MODEM INITIALIZATION STRING(40 CHARACTERS MAX).
>[ATS0=1]
>[
>COMMAND SUCCESSFUL
Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation message appears: Command Successful.
57
Liebert AC8
Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation message appears: Command Successful.
Change Modem Dial Prefix
At the Change Modem Dial Prefix prompt, enter the prefix to be dialed. The current setting
appears in brackets[ATE0X4DT] in the following example.
>CHANGE MODEM DIAL PREFIX.
>[ATE0X4DT]
>[
>COMMAND SUCCESSFUL
For international dialing involving countries that do not support B5 (see Table 22), add country
codes to the initialization string using the format +GCI=xx, where xx is the country code.
(Note: Also requires MT5600SMI modem; model number is on modem label.)
See 7.8.1 - Modem Setup - Initialization String for more information.
Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation message appears: Command Successful.
Change Modem Hang Up Delay After a Call
At the Change Modem Hang Up Delay After a Call prompt, enter the number of seconds to delay
hanging up after a call. The maximum is 99 seconds. The current setting appears in brackets
[10] in the following example.
>CHANGE MODEM HANG UP DELAY AFTER A CALL(99 SEC MAX).
>[10]
>[
>COMMAND SUCCESSFUL
Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation message appears: Command Successful.
Liebert AC8
58
7.8.3
LIEBERT TEST
DEVICE_1 ALARM
CONTACT CLOSED
2:07 PM 06/09/04
When an alarm is detected, the first pager number is dialedup to three times, if needed. After a
successful page or three dialing attempts, the next pager number is dialed, again with three attempts
as needed, and so on for all configured pagers.
Table 23
Result of Page
Successful
Action
Message Generated
Unsuccessful Page
(Event Log)
General modem
communication problem
No communication with
modem
(internal hardware problem)
To configure a pager:
SETUP INPUTS
SETUP COMMON ALARM
SETUP SENSOR
=NEXT =SELECT
SETUP ZONES
SETUP OUTPUTS
> SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP OPERATION
SETUP I/O MATRIX
=SELECT
59
Liebert AC8
Device type
Numeric
pager
Required entries
Example
N18005551212
Alphanumeric
The first character must be A.
pager
A18005551212
Remote
modem
Device type
Pager # - Numeric
ENTER PAGER 1 NUMBER
N1,8005551212,,,,123
4567#
=SELECT =NEXT/END
Pager # - Alphanumeric
ENTER PAGER 1 NUMBER
A9W18005551212
=SELECT =NEXT/END
M18005551212
Optional entries
Example
Numeric
pager
N1,8005551212
Liebert AC8
60
7.8.4
SETUP MODEM&PAGERS
Input pager and
modem information
Select pager or modem
CURRENT NUMBER
*******************
An "A" is required
as 1st character
for an alpha pager,
an "N" for a numeric
pager, and an "M"
for a remote modem.
*******************
1=PAGER NUMBER 1
2=PAGER NUMBER 2
3=PAGER NUMBER 3
4=PAGER NUMBER 4
5=MODEM CONFIGURATION
6=RETURN TO SETUP MENU
7=RETURN TO MAIN MENU
SELECT A NUMBER:1
At the Enter Pager Number prompt, you may press Enter to bypass this option (or see 7.8.3 Pager Setup - Pager Number and PIN for instructions on entering the pager number).
>ENTER PAGER NUMBER(40 CHARACTERS MAX).
>[]
>[
>COMMAND SUCCESSFUL
At the Enter Pager PIN Number prompt, you may press Enter to bypass this option (or see 7.8.3 Pager Setup - Pager Number and PIN for instructions on entering the pager PIN).
>ENTER PAGER PIN NUMBER (20 CHARACTERS MAX).
>[]
>[
>COMMAND SUCCESSFUL
61
Liebert AC8
Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation message appears: Command Successful.
Enter Time To Perform Communications Check
This function schedules the daily communications test between the Liebert AC8 and the selected
pager, as described in the previous section.
At the Enter Time To Perform Communications Check prompt, enter the time to initiate the communications check, using the format HH:MM (hours and minutes in military time), ranging from
00:00 for midnight to 23:59 for 11:59 p.m. The current setting appears in brackets[00:00] in the
following example.
>ENTER TIME TO PERFORM COMMUNICATIONS CHECK(HH:MM).
>[00:00]
>[
>COMMAND SUCCESSFUL
Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation message appears: Command Successful.
Liebert AC8
62
7.9
Figure 11 offers a quick look at the Setup System Info screens available via the LCD interface.
Figure 11 Menu overview - Setup System Info menu
Setup System Info
SETUP SYSTEM INFO
CHANGE PASSWORD
CHANGE DATE & TIME
SETUP SITE ID
CONNECT BATTERY
SETUP SERV PH NUM
FACTORY DEFAULTS
Connect Battery
IS THE BATTERY
CONNECTED? Y
Setup Site ID
SETUP SITE ID
See
AAAAAAAAAAAAAAAAAAAA Section
AAAAAAAAAAAAAAAAAAAA 7.9.3
63
Factory Defaults
See
Section
7.9.6
See
Section
7.9.8
Liebert AC8
7.9.1
Change Password
Change Password
CHANGE PASSWORD
AAAA
=SELECT =NEXT/END
7.9.2
0-31
JAN-DEC
00-99
00-23
00-59
00-59
Liebert AC8
64
7.9.3
Setup Site ID
You may enter a Site ID to identify the Liebert AC8s location, using a
name that may consist of up to 40 characters (see Table 14 for valid
characters). The Site ID will appear with each alarm.
To enter or change the Site ID:
From the Setup System Info Menu, use the arrows to choose
Setup Site ID, then press Enter .
To enter a Site ID:
Use the arrows to choose a character.
Press Enter to advance to the next character position.
If the Site ID is less than 40 characters, you may enter an
underscore (_) character to indicate the end of the name.
When finished, press Enter again.
7.9.4
Setup Site ID
SETUP SITE ID
AAAAAAAAAAAAAAAAAAAA
AAAAAAAAAAAAAAAAAAAA
=SELECT =NEXT/END
Connect Battery
By default, the Liebert AC8 checks the battery and sounds an alarm when the power fails, the battery
runs low or the battery needs to be checked. The batterys main purpose is to provide enough power to
the modem to notify pagers of a power loss.
NOTE
The battery will continue to power and provide full operation of the Liebert AC8 with the
exception of powering the analog inputs (sensors). The battery will provide backup for a
minimum of 10 minutes.
Using the following procedure to disconnect the battery will disable battery alarm features only. The
battery itself will continue to provide backup. If battery backup is not desired, the battery must be
unplugged from the circuit board. This can be done by removing the battery leads from the jumpers
(see 2.4.2 - Connecting the Battery Pack).
The default is to connect the battery. However, there may be times that you want to disconnect the
battery so that it does not provide backup.
Table 25 shows battery problems that will affect operation.
Table 25
Battery alarms
Result of Battery
Action
Message Generated
LOW BATTERY
CHECK BATTERY
BATTERY UNPLUGGED
LOSS OF POWER
From the Setup System Info Menu, use the arrows to choose
Connect Battery, then press Enter .
Use the arrows to choose Y (Yes - the battery is connected) or
N (No - the battery is not connected), then press Enter .
Connect Battery
IS THE BATTERY
CONNECTED? Y
=Y/N
65
=END
Liebert AC8
7.9.5
CONFIGURATION FILE
CONFIGURATION FILE
TO SETUP SYSTEM INFO MENU
TO SETUP MENU
TO MAIN MENU
SELECT A NUMBER:1
6. Enter 1 to back up the configuration file from the Liebert AC8 to the computer and proceed to
Step 8,
OR
7. Enter 2 to upload the configuration file from the computer to the Liebert AC8 and proceed to
Step 13. NOTE: This will replace the current configuration settings in the Liebert AC8 with the
most recent backup.
Liebert AC8
66
NOTE
The following instructions refer to the Microsoft Windows HyperTerminal program. These
steps may vary for other communications programs.
9. At the top of the HyperTerminal window, shown below, click on Transfer, then on Receive File.
Enter folder
Select Xmodem
67
Liebert AC8
NOTE
The following instructions refer to the Microsoft Windows HyperTerminal program. These
steps may vary for other communications programs.
14. At the top of the HyperTerminal window, shown below, click on Transfer, then on Send File.
Send button
Liebert AC8
68
7.9.6
Table 26
Action
Successful
Message Generated
Unsuccessful Page
(Event Log)
General modem
communication problem
Modem Reset
(Event Log)
From the Setup System Info Menu, use the arrows to choose
Setup Serv Ph Num, then press Enter .
See Table 27 for guidelines on entering the phone number, which
may consist of up to 40 characters. To enter the phone number:
Use the arrows to choose a character.
Press Enter to advance to the next character position.
When finished, press Enter again.
Table 27
Device type
Remote
modem
Device type
All types
of devices
Required entries
Example
M18005551212
Optional entries
Example
M918005551212
M9W18005551212
M1,8005551212
69
Liebert AC8
7.9.7
******************
An M is required
as 1st character.
******************
SELECT A NUMBER:1
At the Enter Service Phone Number prompt, you may press Enter to bypass this option (or see
7.9.6 - Setup Serv Ph Num - Enter Phone Number for instructions on entering the number).
>ENTER SERVICE PHONE NUMBER(40 CHARACTERS MAX).
>[]
>[
>COMMAND SUCCESSFUL
Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation message appears: Command Successful.
Enter Time To Perform Communications Check
This function schedules the daily communications test between the Liebert AC8 and the selected
service phone number, as described in the previous section.
At the Enter Time To Perform Communications Check prompt, enter the time to initiate the communications check, using the format HH:MM (hours and minutes in military time), ranging from
00:00 for midnight to 23:59 for 11:59 p.m. The current setting appears in brackets[00:00] in the
following example.
>ENTER TIME TO PERFORM COMMUNICATIONS CHECK(HH:MM).
>[00:00]
>[
>COMMAND SUCCESSFUL
Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation message appears: Command Successful.
Liebert AC8
70
7.9.8
Factory Defaults
At any time, you may restore all default values for settings in the
Liebert AC8 as it was shipped.
NOTE
This action will overwrite any configuration settings. You may
want to back up your settings before restoring the factory
defaults. See Backup and Upload Configuration File
(Service Terminal Interface only) in A.6.7 - Setup System
Info for details on backing up settings using the Service
Terminal Interface.
The password is the sole exception when reverting to the factory
default settings. The password can be reset to the factory default of
AAAA only through the DIP switches. For details, see Change
Password on page 64.
7.9.9
Factory Defaults
RESTORE ALL DEFAULTS
ARE YOU SURE? N
=Y/N
=END
71
Liebert AC8
NOTE
The following instructions refer to the Microsoft Windows HyperTerminal program. These
steps may vary for other communications programs.
2. The firmware update is a two-step processthis step describes how to upload the file
prog###.s19 (where ### is a numberfor example, prog118.s19) to the Liebert AC8:
a. At the top of the HyperTerminal window, shown below, click on Transfer, then on Send File.
Send button
Liebert AC8
72
At the Simulate An Alarm Condition prompt, enter Y if you wish to proceed or N if you want to
cancel the alarm simulation.
>SIMULATE AN ALARM CONDITION-YES(Y) OR NO(N)?
>[N]
>[
>COMMAND SUCCESSFUL
After the Command Successful message appears, disconnect from the modemat the top of the
HyperTerminal window, click on Call, then on Disconnect, as shown below.
Disconnect
Wait for the Liebert AC8 to dial out to send a test message.
To verify whether the test was successful, check the Event Log (see 5.3 - View Event Log) for
one of these two messages: Dial out test passed or Dial out test failed.
NOTE
Also verify that a message was received at the Service Phone Number.
If the test is NOT successful, check the following:
Modem configuration (see 7.8.1 - Modem Setup - Initialization String)
Pager configuration (see 7.8.3 - Pager Setup - Pager Number and PIN)
73
Liebert AC8
7.10
Setup Operation
The Liebert AC8 operation features allow you to set up a rotation
sequence to alternate which devices are operating and which are
placed on Standby, as well as test devices while in Standby mode and
specify what to do when a Standby device goes into alarm as it is
powered up. You may specify delay times after an output changes
state, directing the Liebert AC8 to wait before acknowledging inputs
(hold delay time) or turning an output on or off (restart delay time).
With staging, you may configure the Liebert AC8 to turn a standby
device on or off when an analog sensor detects a condition above or
below specified levels.
Table 28 shows the default settings for operation options: automatic sequencing, standby testing,
failed standby, hold delay, restart and staging.
Table 28 Default settings - operation features
Feature
Default
Other Options
AUTO SEQUENCING
OFF (Deactivated)
STANDBY TESTING
OFF (Deactivated)
ON (Activated)
FAILED STANDBY
N (Deactivated)
Y (Activated)
HOLD DELAY
RESTART
STAGING
OFF (Deactivated)
ON (Activated)
Figure 12 provides an overview of the Setup Operation screens available via the LCD interface.
Liebert AC8
74
Standby Testing
See
Section
7.10.1
Failed Standby
Hold Delay
HOLD DELAY
10 MIN : 00 SEC
FAILED STANDBY
Restart
See
Section
7.10.4
75
RESTART DELAY
00 MIN : 06 SEC
See
Section
7.10.3
Staging
See
Section
7.10.5
STAGING: ON
TARGET: +0070.0
SENSITIVITY: +005.0
See
Section
7.10.6
Liebert AC8
Monday:
Wednesday:
Friday:
Sunday:
NOTE
The Liebert AC8 will not cycle outputs that have been manually forced On or Off through the
Override Output Menu or the hardware switch (see 7.12 - Override Output).
Liebert AC8
76
Activate / Deactivate
AUTO SEQUENCING OFF
=NEXT
=EDIT
4. Specify the time of day the sequencing should begin in the At 00:00
field. The format is HH:MM for hours and minutes.
Use the arrows to choose from available entries for hours
(00-23), then press Enter to advance to minutes.
Use the arrows to select minutes (00-59).
When finished, press Enter again.
77
AUTO SEQUENCING ON
EVERY 03 DAYS
AT 00:00
=NEXT
=EDIT
=EDIT
Liebert AC8
Disabled
Remains enabled
Previously Operating
Device
Returns to Operating mode
Remains disabled
78
FAILED STANDBY
=NEXT
=END
79
Liebert AC8
Activate / Deactivate
STAGING: OFF
=NEXT
Staging
STAGING: ON
TARGET: +0070.0
SENSITIVITY: +005.0
=NEXT =SELECT
Message
(if sensor for zone is not
connected to AC8)
SENSOR NOT
CONNECTED
Liebert AC8
80
=EDIT
7.11
SETUP INPUTS
SETUP COMMON ALARM
SETUP SENSOR
=NEXT =SELECT
SETUP ZONES
SETUP OUTPUTS
SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP OPERATION
> SETUP I/O MATRIX
From the Setup System Menu, shown at right, use the arrows to
choose Setup I/O Matrix and press Enter .
Use the following instructions to set up the mapping of each digital input or analog sensor input
to each relay.
=SELECT
Select Input
SELECT INPUT
> DEVICE_1
DEVICE_2
=NEXT
=SELECT
DEVICE_3
DEVICE_4
DEVICE_5
DEVICE_6
DEVICE_7
DEVICE_8
Input-to-Relay Map
1
CONTROL RELAY
1 2
Y N
=Y/N
=NEXT/END
Digital input
Device_1
Device_2
Device_3
Device_4
Device_5
Device_6
Device_7
Device_8
81
Liebert AC8
=SELECT
Select Sensor
On the Sensor-to-Relay Map screen, you may map the selected senSELECT SENSOR
sor to either or both of the control relays (1-2). The example at right > SENSOR_1 HIGH STPT
SENSOR_1 LOW STPT
shows Sensor_1 High Stpt mapped to Control Relay 1.
=NEXT
=SELECT
To make changes to the mapping:
SENSOR_2 HIGH STPT
If needed, press Enter to advance to the position directly
SENSOR_2 LOW STPT
SENSOR_3 HIGH STPT
below the relay.
SENSOR_3 LOW STPT
Use the arrows to choose Y (Yes - Mapped to this relay) or
SENSOR_4 HIGH STPT
N (No - Not mapped), then press Enter .
SENSOR_4 LOW STPT
Press Enter to advance to the next position where you want
to make a change.
Sensor-to-Relay Map
Use the arrows to choose Y (Yes - Mapped to this relay) or
1H CONTROL RELAY
N (No - Not mapped), then press Enter .
1 2
When finished, press Enter again.
Y N
=Y/N
=NEXT/END
Analog input
Sensor_1
(none)
Sensor_2
(none)
Sensor_3
(none)
Sensor_4
(none)
Liebert AC8
82
7.12
Override Output
The Override Output feature allows you to manually change the state of any digital output to ON or
OFF, overriding automatic control by the Liebert AC8 (the default setting for all outputs). This menu
also allows you to release the manual override, returning any output to automatic control.
There are two ways to override automatic control of outputs:
Use the Override Output menu, as described in this section, to turn any output ON or OFF.
Use the hardware switch on the Liebert AC8 circuit board to force all eight outputs ON at the
same time (see Item I - Manual Override Switch (outputs) in 1.7 - Controller Board Overview).
After an output is forced manually ON or OFF through the Override Output menu, it remains in that
state until returned to automatic control through this menu.
Table 32 summarizes the four types of control, including the abbreviated message that appears on
the LCD and in log reports.
Table 32
Message
Description
AUTO
Automatic
FORCE ON
Manually ON
FORCE OFF
Manually OFF
HW FORCE ON
Manually ON
(all outputs)
83
Main Menu
VIEW STATUS
> SYSTEM AND CONTROL
=SELECT
=NEXT
Login
LOGIN
AAAA
=SELECT =NEXT/END
Select Output
OVERRIDE
> DEVICE_1
DEVICE_2
=NEXT
DEVICE_3
DEVICE_4
OUTPUT
AUTO
AUTO
=SELECT
AUTO
FORCE ON
Override Output
SELECT DEVICE_1
FORCE ON
=SELECT =END
Liebert AC8
7.13
Main Menu
The Clear Alarms & Logs menu allows you to clear active alarms or
delete all records from any of the Liebert AC8s three logs: alarm, event
and trend logs.
VIEW STATUS
> SYSTEM AND CONTROL
=NEXT
=SELECT
LOGIN
AAAA
=SELECT =NEXT/END
=END
Liebert AC8
84
=END
=END
=END
85
Liebert AC8
Specifications
8.0
SPECIFICATIONS
8.1
Power
Requirements
115VAC
UML11500
230VAC
UML23000
115VAC 10%
of nominal;
60Hz, 4A,
460VA
230VAC 10%
of nominal;
50Hz, 0.5A,
115VA
Dimensions
W x D x H, in. (mm)
18 x 2-3/4 x 18
(457.2 x 69.85 x 457.2)
Weight (Assembled)
Enclosure Type
Liquid Crystal Display (LCD)
NEMA 1
Four line, 20 character, backlit
Mounting Surface
Ambient Operating
Environment
Processor Specifics
Model
Motorola XC68HC812A4
Clock speed
16MHz
Total RAM
256Kb
Total FLASH
4M
Total EEPROM
4K
12 Bit
14.4K bps
Clock Type
Clock battery backup type
Clock battery life
Modem battery backup type
Real-Time Clock
Lithium Cell (non-replaceable)
7 years, constant, no power
Nickel Cadmium (replaceable)
Communications
Local Communications
Remote Communications
Modem (9600-N-8-1)
Supported pagers
RS232
Baud rate 9600 bps, Parity=None, Data bits=8, Stop bits=1
9600 E-7-1 supports TAPI protocol version 1.8
Agency Listings
UL
115VAC
(TM115)
230VAC
(TM230)
UL1012
UL1585
CE
Yes
FCC Compliance
N/A
24VAC, 3A
24VAC, 3A
Liebert AC8
86
NOTE
If the equipment is
used in a manner
not specified by the
manufacturer, the
protection provided
by the equipment
may be impaired.
A.1
Table 33
Function
VIEW STATUS FUNCTIONS
View Active Alarms
View Alarm Log
View Event Log
View Trend Log
View Input Status
View Output Status
View Pager Numbers
View Operation
View Control Status
SILENCE ALARM & BACK UP LOGS FUNCTIONS
Silence Alarm (On the LCD, press any key to silence an alarm)
Back Up Log Files
SYSTEM & CONTROL FUNCTIONS
Login
Setup System
Setup Inputs
Setup Common Alarm
Setup Sensor
Setup Outputs
Setup Modem & Pagers
Initialization String
Enter Liebert AC8 Phone Number
Modem
Enable Modem Diagnostic Messages
Setup
Change Modem Dial Prefix
Change Modem Hang Up Delay After a Call
Pager Number & PIN
Pager
Setup
Communications Check
Setup System Info
Change Password
Change Date & Time/Automatic Daylight Saving Time
Setup Site ID
Connect Battery
Backup and Upload Configuration File
Setup Serv Ph Num - Enter Phone Number
Setup Serv Ph Num - Communications Check
Factory Defaults
Perform Firmware Update
Initiate Remote Alarm Test
Setup Operation
Setup I/O Matrix
Override Output
Clear Alarms & Logs
Clear Active Alarms
Clear the Alarm Log
Clear the Event Log
Clear the Trend Logs
87
Where to find:
Instructions on
Service Terminal
using function
screen examples
page 26
page 27
page 28
page 29
page 31
page 32
page 33
page 34
page 35
page 93
page 94
page 95
page 96
page 97
page 97
page 98
page 99
page 99
page 36
page 37
page 100
page 101
page 39
page 41
page 41
page 44
page 45
page 53
page 55
page 55
page 57
page 57
page 57
page 57
page 59
page 61
page 63
page 64
page 64
page 65
page 65
page 66
page 69
page 70
page 71
page 71
page 73
page 74
page 81
page 83
page 84
page 84
page 84
page 85
page 85
page 103
page 104
page 105
page 105
page 106
page 107
page 108
page 109
page 109
page 109
page 109
page 109
page 108
page 108
page 110
page 110
page 111
page 111
page 111
page 112
page 113
page 113
page 113
page 114
page 114
page 115
page 124
page 121
page 122
page 122
page 122
page 123
page 123
Liebert AC8
A.2
Remote
N/A
The instructions in this section refer to the HyperTerminal programthey may vary for other communications programs.
3. In the Connection Description window, shown above right, enter a name for the connectionfor
example, AC8. This becomes the file name (with the extension .ht).
4. Click OK to close the window.
Liebert AC8
88
5. In the Connect To window, shown below, select the appropriate connection method from the
Connect Using drop-down list:
DIRECT CONNECTION
REMOTE CONNECTION
Choose COM1
& proceed to Step 6
7. Click OK. When the connection is open, the connection name appears in the title bar of the
HyperTerminal window. To complete the setup, continue with Step 8 (next section).
89
Liebert AC8
Properties Setup
8. Open the Properties window by clicking on File, then on Properties, as shown below left.
Settings
tab
9. In the Properties window, above right, click on the Settings tab and choose the following settings:
Function, arrow, and ctrl keys act as: Terminal keys
Backspace key sends: Ctrl+H
Emulation: ANSIW
Telnet terminal ID: VT100
Backscroll buffer lines: 500
Play sound when connecting or disconnecting: Unchecked
ASCII Setup
10. In the Properties window, click on the ASCII Setup button, shown below left.
ASCII
Setup
button
11. In the ASCII Setup window, shown above right, choose the following settings:
ASCII Sending: place a check mark () in the Send Line Ends With Line Feeds box.
ASCII Receiving: place a check mark () in the Wrap Lines That Exceed Terminal Width
box.
Click OK.
The setup is now complete. To use the new connection, proceed to the next section, A.2.5 - Connect
to the Service Terminal Interface.
Liebert AC8
90
4. In the Open window, shown above right, select the file nameLiebert AC8.ht in this example
and then click on the Open button.
5. Follow the steps below to display the Main Menu of the Service Terminal Interface:
a. For direct connection (via RS232 port):
Press Enter (or Escape) to initiate communication and bring up the Main Menu.
b. For remote connection (via modem):
The Connect window opens, as shown below left. Click the OK button.
In the Connect window, below right, click Dial.
If the dialing attempt is successful, the Main Menu appears.
Dial button
OK button
91
Liebert AC8
Overview of Menus
A.3
OVERVIEW OF MENUS
The Main Menu offers choices for viewing the status of the Liebert AC8, silencing the audible alarm
and backing up the units log files. It also allows access to the System and Control features, which
require a password.
The following shows where to find examples of the Main Menu screens:
Main Menu
1=VIEW ACTIVE ALARMS
8=SILENCE ALARM
Liebert AC8
92
A.4
Main Menu
After connecting to the Service Terminal Interface, the Main Menu appears, as shown below. This
section presents Service Terminal Interface screens for options 1 through 7:
Main Menu
LIEBERT AC8
VX.XXX.X
LIEBERT CORPORATION COPYRIGHT 2005
ALL RIGHTS RESERVED
MAIN MENU
Section A.4.1
Section A.4.2
Section A.4.3
Section A.4.4
Section A.4.5
Section A.4.6
Section A.4.7
8=SILENCE ALARM
9=BACKUP LOG FILES
A=VIEW OPERATION STATUS
Section A.4.8
Section A.4.9
93
Liebert AC8
Liebert AC8
94
95
Liebert AC8
75.4 DEG
15:45:10
SENSOR_1
70.5 DEG
LOW SETPOINT EVENT
28-AUG-05
15:15:10
SENSOR_1
79.9 DEG
RETURN TO NORMAL
28-AUG-05
14:45:10
SENSOR_1 ------ DEG
SENSOR PROBLEM
28-AUG-05
14:15:10
<ENTER>=MORE <ESC>=EXIT <A>=ALL
SENSOR_1
65.9 DEG
LOW SETPOINT ALARM
28-AUG-05
13:45:10
SENSOR_1
69.9 DEG
LOW SETPOINT EVENT
28-AUG-05
13:15:10
SENSOR_1
80.7 DEG
HIGH SETPOINT EVENT
28-AUG-05
12:45:10
1=REFRESH TREND LOG
2=VIEW A DIFFERENT SENSOR
3=RETURN TO MAIN MENU
SELECT A NUMBER:
Liebert AC8
96
STATUS
80.0
-----80.0
79.5
NORMAL
ALARM
EVENT
ALARM
ALARM
EVENT
NORMAL
NORMAL
DEG
DEG
DEG
RH
80.0 DEG
STATE
DEVICE_1
DEVICE_2
DEVICE_3
DEVICE_4
DEVICE_5
DEVICE_6
DEVICE_7
DEVICE_8
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
MODE
OPERATING
OPERATING
OPERATING
STANDBY
NOT USED
NOT USED
NOT USED
NOT USED
ZONE
1
1
1
1
0
0
0
0
*****************************************
OPERATING
= OPERATING/ON
STANDBY
= IN STANDBY MODE
ALARM
= IN ALARM
FORCE ON
= FORCE ON BY OPERATOR
FORCE OFF
= FORCE OFF BY OPERATOR
HW FORCE ON = FORCE ON BY HARDWARE SWITCH
PENDING
= PENDING DELAY TIMER
NOT USED
= DEVICE NOT USED
*****************************************
97
Liebert AC8
Liebert AC8
98
STATUS
OFF
OFF
99
Liebert AC8
Silence Alarm & Back Up Log Files (Service Terminal Interface only)
A.5
SILENCE ALARM & BACK UP LOG FILES (SERVICE TERMINAL INTERFACE ONLY)
This section presents two options from the Main Menu that are available via the Service Terminal
Interface only.
Main Menu
After connecting to the Service Terminal Interface, the Main Menu appears, as shown below. This
section presents Service Terminal Interface screens for options 8 and 9:
Main Menu
LIEBERT AC8
VX.XXX.X
LIEBERT CORPORATION COPYRIGHT 2005
ALL RIGHTS RESERVED
MAIN MENU
1=VIEW ACTIVE ALARMS
2=VIEW ALARM LOG
3=VIEW EVENT LOG
4=VIEW TREND LOG
5=VIEW INPUT & SENSOR STATUS
6=VIEW OUTPUT STATUS
7=VIEW PAGER NUMBERS
8=SILENCE ALARM
Section A.5.1
Section A.5.2
Liebert AC8
100
Silence Alarm & Back Up Log Files (Service Terminal Interface only)
SELECT A NUMBER:1
>INITIATE A BACKUP OF ALARM LOG-YES(Y) OR NO(N)?
>[N]
>[
INSTRUCTIONS TO PERFORM BACKUP:
ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION
- SELECT TRANSFER FROM THE TOOLBAR
- SELECT RECEIVE FILE
- ENTER FOLDER WHERE FILE IS TO BE RECEIVED
- SELECT XMODEM FROM THE PROTOCOL BOX
- SELECT RECEIVE BUTTON AND ENTER FILE NAME, E.G., ALARM.LOG
>BACKUP SUCCESSFUL
SELECT A NUMBER:2
>INITIATE A BACKUP OF EVENT LOG-YES(Y) OR NO(N)?
>[N]
>[
INSTRUCTIONS TO PERFORM BACKUP:
ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION
- SELECT TRANSFER FROM THE TOOLBAR
- SELECT RECEIVE FILE
- ENTER FOLDER WHERE FILE IS TO BE RECEIVED
- SELECT XMODEM FROM THE PROTOCOL BOX
- SELECT RECEIVE BUTTON AND ENTER FILE NAME, E.G., EVENT.LOG
>BACKUP SUCCESSFUL
101
Liebert AC8
Silence Alarm & Back Up Log Files (Service Terminal Interface only)
SELECT A NUMBER:3
>INITIATE A BACKUP OF TREND LOG-YES(Y) OR NO(N)?
>[N]
>[
INSTRUCTIONS TO PERFORM BACKUP:
ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION
- SELECT TRANSFER FROM THE TOOLBAR
- SELECT RECEIVE FILE
- ENTER FOLDER WHERE FILE IS TO BE RECEIVED
- SELECT XMODEM FROM THE PROTOCOL BOX
- SELECT RECEIVE BUTTON AND ENTER FILE NAME, E.G., SENSOR_1.LOG
>BACKUP SUCCESSFUL
Liebert AC8
102
Setup Menu
A.6
SETUP MENU
The Setup menu allows the user to configure the Liebert AC8setting up inputs and outputs and an
input/output matrix to trigger actions, the modem and pagers, and system features such as date and
time. This menu also provides a vehicle for manually changing the state of an output to ON or OFF,
clearing active alarms and deleting records from the Liebert AC8s alarm log, event log and trend
logs.
Main Menu
After you connect to the Service Terminal Interface, the Main Menu appears, as shown below.
Main Menu
LIEBERT AC8
VX.XXX.X
LIEBERT CORPORATION COPYRIGHT 2005
ALL RIGHTS RESERVED
MAIN MENU
1=VIEW ACTIVE ALARMS
2=VIEW ALARM LOG
3=VIEW EVENT LOG
4=VIEW TREND LOG
5=VIEW INPUT & SENSOR STATUS
6=VIEW OUTPUT STATUS
7=VIEW PAGER NUMBERS
8=SILENCE ALARM
9=BACKUP LOG FILES
A=VIEW OPERATION STATUS
B=VIEW CONTROL RELAYS STATUS
0=SETUP SYSTEM - LOGIN REQUIRED
SELECT A NUMBER:0
Login Menu
The System and Control options require a password to prevent unauthorized users from making
changes to the system. After you enter 0 in the Main Menu above, the Login Menu appears:
Login
YOU MUST LOGIN TO PERFORM
SETUP OR TO MAKE CHANGES
LOGIN WITH 4 CHARACTER
PASSWORD
>****
>INVALID PASSWORD, ENTER AGAIN
>PRESS <ESC> TO EXIT
>
Enter the password, and the Setup Menu appears, as shown in the following section.
103
Liebert AC8
Setup Menu
Setup Menu
This section presents Service Terminal Interface screens for each of the following:
Setup Menu
See:
Description
1=SETUP INPUT
Section A.6.1
Section A.6.2
3=SETUP SENSOR
Section A.6.3
4=SETUP ZONES
Section A.6.4
5=SETUP OUTPUTS
Section A.6.5
6=SETUP MODEM&PAGERS
Section A.6.6
Section A.6.7
8=SETUP OPERATION
Section A.6.8
9=OVERRIDE OUTPUT
Section A.6.9
0=CLEAR ALARMS&LOGS
Section A.6.10
Section A.6.11
SETUP MENU
Current
setting
shown in
brackets [ ]
Liebert AC8
104
Setup Menu
****************************
NO=NORMALLY OPENED
NC=NORMALLY CLOSED
DEFINITION
NO-EV-NL-00:01
NO-AL-L -00:01
NC-EV-NL-00:01
NO-AL-L -00:01
NC-AL-L -00:01
NO-EV-NL-00:01
NO-AL-L -00:01
NC-EV-NL-00:01
SETUP MENU
MAIN MENU
EV=EVENT
AL=ALARMABLE
NL=NOT LATCHED
L =LATCHED
MIN:SEC=DELAY TIME BEFORE
INPUT WILL TRIGGER
NOTE:EVENT CANNOT BE LATCHED
****************************
SELECT A NUMBER:1
>CHANGE LABEL(8 CHARACTERS MAX).
>[DEVICE_1]
>[]
>IS INPUT NORMALLY OPENED(NO) OR NORMALLY CLOSED(NC)?
>[NO]
>[]
>IS INPUT AN ALARM(AL) OR EVENT(EV)?
>[EV]
>[]
>IS ALARM LATCHED-YES(Y) OR NO(N)?
>[N]
>[]
>DELAY TIME BEFORE TRIGGER (MM:SS)?
>[00:01]
>[]
CURRENT
SETTING
N
SELECT A NUMBER:1
>RESET COMMON ALARM WITH SILENCE-YES(Y) OR NO(N)?
>[N]
>[
105
Liebert AC8
Setup Menu
VALUE
1=SENSOR_1
80.0 DEG
2=SENSOR_2 ------ DEG
3=SENSOR_3
80.0 DEG
4=SENSOR_4
79.5 RH
5=RETURN TO SETUP MENU
6=RETURN TO MAIN MENU
SELECT A NUMBER:1
>IS THE SENSOR CONNECTED-YES(Y) OR NO(N)?
>[N]
>[]
>CHANGE SENSOR LABEL(8 CHARACTERS MAX).
>[SENSOR_1]
>[]
>CHANGE UNITS LABEL(3 CHARACTERS MAX).
>[DEG]
>[]
>CHANGE 4 mA VALUE(+045.0 TO +096.0).
>[+045.0]
>[]
>CHANGE 20 mA VALUE(+045.0 TO +096.0).
>[+096.0]
>[]
>CHANGE OFFSET VALUE(-999.9 TO +999.9).
>[+000.0]
>[]
>IS SENSOR AN ALARM(AL) OR EVENT(EV)?
>[AL]
>[]
>IS SENSOR ALARM LATCHED-YES(Y) OR NO(N)?
>[Y]
>[]
>CHANGE LOW SETPOINT.
>[-0015.0]
>[]
>CHANGE HIGH SETPOINT.
>[+0015.0]
>[]
>DELAY TIME BEFORE TRIGGER (MM:SS)?
>[00:01]
>[]
Liebert AC8
106
Setup Menu
# DEVICES
1=ZONE 1
4
2=ZONE 2
0
3=ZONE 3
0
4=ZONE 4
0
5=RETURN TO SETUP MENU
6=RETURN TO MAIN MENU
SELECT A NUMBER:
># DEVICES IN ZONE 1
>[4]
>[
DEFINITION
NO-OP-E-E
NO-OP-E-E
NO-OP-E-E
NO-ST-E-E
NO-NU-E-E
NO-NU-E-E
NO-NU-E-E
NO-NU-E-E
SETUP MENU
MAIN MENU
*******************************************
NO=NORMALLY OPENED
NC=NORMALLY CLOSED
OP=OPERATING/ON
ST=STANDBY MODE
NU=NOT USED
D=DISABLE DEVICE ON ALARM CONDITION
E=LEAVE DEVICE OPERATING ON ALARM CONDITION
D=DISABLE DEVICE IN EMERGENCY POWER OP
E=LEAVE DEVICE OPERATING (EMERGENCY POWER OP)
*******************************************
SELECT A NUMBER:1
>SET TO NORMALLY OPENED(NO) OR NORMALLY CLOSED(NC)
>[NO]
>[]
>DEVICE_1 TO OPERATING/ON(OP), STANDBY MODE(ST), NOT USED(NU)
>[OP]
>[]
>DEVICE_1 TO ENABLE(E) OR DISABLE(D) DEVICE ON ALARM
>[E]
>[]
>DEVICE_1 TO ENABLE(E) OR DISABLE(D) DEVICE IN EMERGENCY POWER OP
>[E]
>[
107
Liebert AC8
Setup Menu
Pager Setup
For details on this feature, see 7.8.3 - Pager Setup - Pager Number and PIN and 7.8.4 - Pager
Setup - Communications Check (Service Terminal Interface only).
Setup Modem & Pagers - Pager Setup
SETUP MODEM&PAGERS
Input pager and
modem information
Select pager or modem
CURRENT NUMBER
*******************
An "A" is required
as 1st character
for an alpha pager,
an "N" for a numeric
pager, and an "M"
for a remote modem.
*******************
1=PAGER NUMBER 1
2=PAGER NUMBER 2
3=PAGER NUMBER 3
4=PAGER NUMBER 4
5=MODEM CONFIGURATION
6=RETURN TO SETUP MENU
7=RETURN TO MAIN MENU
SELECT A NUMBER:1
>ENTER PAGER NUMBER(40 CHARACTERS MAX).
>[]
>[
>COMMAND SUCCESSFUL
>ENTER PAGER PIN NUMBER (20 CHARACTERS MAX).
>[]
>[
>COMMAND SUCCESSFUL
Liebert AC8
108
Setup Menu
Modem Setup
For details on this feature, see 7.8.1 - Modem Setup - Initialization String and 7.8.2 - Modem
Setup - Additional Features (Service Terminal Interface only).
Setup Modem & Pagers - Modem Setup
SETUP MODEM&PAGERS
Input pager and
modem information
Select pager or modem
CURRENT NUMBER
*******************
An "A" is required
as 1st character
for an alpha pager,
an "N" for a numeric
pager, and an "M"
for a remote modem.
*******************
1=PAGER NUMBER 1
2=PAGER NUMBER 2
3=PAGER NUMBER 3
4=PAGER NUMBER 4
5=MODEM CONFIGURATION
6=RETURN TO SETUP MENU
7=RETURN TO MAIN MENU
SELECT A NUMBER:5
>CHANGE MODEM INITIALIZATION STRING(40 CHARACTERS MAX).
>[ATS0=1]
>[
>COMMAND SUCCESSFUL
>ENTER AC8 PHONE NUMBER(40 CHARACTERS MAX). (Service Terminal Interface only)
>[]
>[
>COMMAND SUCCESSFUL
>ENABLE MODEM DIAGNOSTIC MESSAGES-YES(Y) OR NO(N)? (Service Terminal Interface only)
>[N]
>[
>COMMAND SUCCESSFUL
>CHANGE MODEM DIAL PREFIX. (Service Terminal Interface only)
>[ATE0X4DT]
>[
>COMMAND SUCCESSFUL
>CHANGE MODEM HANG UP DELAY AFTER A CALL(99 SEC MAX). (Service Terminal Interface only)
>[10]
>[
>COMMAND SUCCESSFUL
109
Liebert AC8
Setup Menu
1=CHANGE PASSWORD
2=SET DATE & TIME
3=SETUP SITE ID
4=CONNECT BATTERY
5=BACKUP & UPLOAD CONFIGURATION FILE
6=SETUP SERVICE PHONE NUMBER
7=SET PANEL TO FACTORY DEFAULTS
8=PERFORM FIRMWARE UPDATE
9=INITIATE REMOTE ALARM TEST
0=RETURN TO SETUP MENU
I=RETURN TO MAIN MENU
SELECT A NUMBER:
Change Password
For details on this feature, see 7.9.1 - Change Password.
Change Password
CHANGE PASSWORD
1=CHANGE
2=RETURN
3=RETURN
4=RETURN
PASSWORD
TO SETUP SYSTEM INFO MENU
TO SETUP MENU
TO MAIN MENU
SELECT A NUMBER:1
>ENTER ORIGINAL PASSWORD(MUST BE 4 CHARACTERS).
>[****]
>ENTER NEW PASSWORD(MUST BE 4 CHARACTERS).
>[****]
>ENTER NEW PASSWORD AGAIN FOR CONFIRMATION.
>[****]
>PASSWORD CHANGE SUCCESSFUL
Liebert AC8
110
Setup Menu
DST
Y
Setup Site ID
For details on this feature, see 7.9.3 - Setup Site ID.
Setup Site ID
SETUP SITE ID
Define name to
reference panel
CURRENT SITE ID
1=SETUP SITE ID
2=RETURN TO SETUP SYSTEM INFO MENU
3=RETURN TO SETUP MENU
4=RETURN TO MAIN MENU
SELECT A NUMBER:1
>ENTER SITE ID NAME(40 CHARACTERS MAX).
>[]
>[
>COMMAND SUCCESSFUL
Connect Battery
For details on this feature, see 7.9.4 - Connect Battery.
Connect Battery
CONNECT BATTERY
CURRENT SETTING
Y
1=CONNECT BATTERY
2=RETURN TO SETUP SYSTEM INFO MENU
3=RETURN TO SETUP MENU
4=RETURN TO MAIN MENU
SELECT A NUMBER:1
>IS THE BATTERY CONNECTED-YES(Y) OR NO(N)?
>[Y]
>[
>COMMAND SUCCESSFUL
111
Liebert AC8
Setup Menu
CONFIGURATION FILE
CONFIGURATION FILE
TO SETUP SYSTEM INFO MENU
TO SETUP MENU
TO MAIN MENU
SELECT A NUMBER:1
>INITIATE A BACKUP OF CONFIGURATION FILE-YES(Y) OR NO(N)?
>[N]
>[
INSTRUCTIONS TO PERFORM BACKUP:
ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION
- SELECT TRANSFER FROM THE TOOLBAR
- SELECT RECEIVE FILE
- ENTER FOLDER WHERE FILE IS TO BE RECEIVED
- SELECT XMODEM FROM THE PROTOCOL BOX
- SELECT RECEIVE BUTTON AND ENTER FILE NAME,E.G., AC8_CONF.SAV
>BACKUP SUCCESSFUL
CONFIGURATION FILE
CONFIGURATION FILE
TO SETUP SYSTEM INFO MENU
TO SETUP MENU
TO MAIN MENU
SELECT A NUMBER:2
>INITIATE AN UPLOAD OF CONFIGURATION FILE-YES(Y) OR NO(N)?
>[N]
>[
INSTRUCTIONS TO PERFORM UPLOAD:
ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION
- SELECT TRANSFER FROM THE TOOLBAR
- SELECT SEND FILE
- ENTER FILE NAME-CONFIGURATION FILE LOCATION & NAME,E.G., AC8_CONF.SAV
- SELECT XMODEM FROM THE PROTOCOL BOX
- SELECT SEND BUTTON
>UPLOAD SUCCESSFUL
Liebert AC8
112
Setup Menu
******************
An M is required
as 1st character.
******************
SELECT A NUMBER:1
>ENTER SERVICE PHONE NUMBER(40 CHARACTERS MAX).
>[]
>[
>COMMAND SUCCESSFUL
>ENABLE COMMUNICATIONS CHECK-YES(Y) OR NO(N)? (Service Terminal Interface only)
>[N]
>
>COMMAND SUCCESSFUL
>ENTER TIME TO PERFORM COMMUNICATIONS CHECK(HH:MM). (Service Terminal Interface only)
>[00:00]
>[
>COMMAND SUCCESSFUL
Factory Defaults
For details on this feature, see 7.9.8 - Factory Defaults.
Factory Defaults
RESTORE FACTORY DEFAULTS
This command restores all panel
information to factory settings
1=RESTORE FACTORY DEFAULTS
2=RETURN TO SETUP SYSTEM INFO MENU
3=RETURN TO SETUP MENU
4=RETURN TO MAIN MENU
SELECT A NUMBER:1
>RESTORE THE PANEL TO FACTORY SETTINGS-YES(Y) OR NO(N)?
>[N]
[[
>COMMAND SUCCESSFUL
113
Liebert AC8
Setup Menu
Liebert AC8
114
Setup Menu
Auto Sequencing
For details on this feature, see 7.10.1 - Turn Automatic Sequencing On or Off.
Setup Operation - Auto Sequencing
SETUP OPERATION BY ZONE
Select the zone for which
operation is to change
ZONE
1=ZONE 1
2=ZONE 2
3=ZONE 3
4=ZONE 4
5=RETURN TO SETUP MENU
6=RETURN TO MAIN MENU
SELECT A NUMBER:1
SETUP OPERATION
Select operation to edit
for zone 1
OPERATION
STATE
115
Liebert AC8
Setup Menu
Standby Testing
For details on this feature, see 7.10.2 - Turn Standby Testing On or Off.
Setup Operation - Standby Testing
SETUP OPERATION BY ZONE
Select the zone for which
operation is to change
ZONE
1=ZONE 1
2=ZONE 2
3=ZONE 3
4=ZONE 4
5=RETURN TO SETUP MENU
6=RETURN TO MAIN MENU
SELECT A NUMBER:1
SETUP OPERATION
Select operation to edit
for zone 1
OPERATION
STATE
Liebert AC8
116
Setup Menu
Failed Standby
For details on this feature, see 7.10.3 - Specify Failed Standby Response.
Setup Operation - Failed Standby
SETUP OPERATION BY ZONE
Select the zone for which
operation is to change
ZONE
1=ZONE 1
2=ZONE 2
3=ZONE 3
4=ZONE 4
5=RETURN TO SETUP MENU
6=RETURN TO MAIN MENU
SELECT A NUMBER:1
SETUP OPERATION
Select operation to edit
for zone 1
OPERATION
STATE
117
Liebert AC8
Setup Menu
Hold Delay
For details on this feature, see 7.10.4 - Specify Hold Delay Time.
Setup Operation - Hold Delay
SETUP OPERATION BY ZONE
Select the zone for which
operation is to change
ZONE
1=ZONE 1
2=ZONE 2
3=ZONE 3
4=ZONE 4
5=RETURN TO SETUP MENU
6=RETURN TO MAIN MENU
SELECT A NUMBER:1
SETUP OPERATION
Select operation to edit
for zone 1
OPERATION
STATE
Liebert AC8
118
Setup Menu
Restart Delay
For details on this feature, see 7.10.5 - Specify Restart Time.
Setup Operation - Restart Delay
SETUP OPERATION BY ZONE
Select the zone for which
operation is to change
ZONE
1=ZONE 1
2=ZONE 2
3=ZONE 3
4=ZONE 4
5=RETURN TO SETUP MENU
6=RETURN TO MAIN MENU
SELECT A NUMBER:1
SETUP OPERATION
Select operation to edit
for zone 1
OPERATION
STATE
119
Liebert AC8
Setup Menu
Staging
For details on this feature, see 7.10.6 - Specify Staging.
Setup Operation - Staging
SETUP OPERATION BY ZONE
Select the zone for which
operation is to change
ZONE
1=ZONE 1
2=ZONE 2
3=ZONE 3
4=ZONE 4
5=RETURN TO SETUP MENU
6=RETURN TO MAIN MENU
SELECT A NUMBER:1
SETUP OPERATION
Select operation to edit
for zone 1
OPERATION
STATE
Liebert AC8
120
Setup Menu
CONTROL
1=DEVICE_1
AUTO
2=DEVICE_2
AUTO
3=DEVICE_3
AUTO
4=DEVICE_4
AUTO
5=DEVICE_5
AUTO
6=DEVICE_6
AUTO
7=DEVICE_7
AUTO
8=DEVICE_8
AUTO
9=RETURN TO SETUP MENU
0=RETURN TO MAIN MENU
********************************************
AUTO
= CONTROL BY PANEL
FORCE ON = FORCE ON BY OPERATOR
FORCE OFF= FORCE OFF BY OPERATOR
********************************************
SELECT A NUMBER:1
>OVERRIDE OUTPUT DEVICE_1-AUTO(2),FORCE ON(1),FORCE OFF(0).
>[2]
>[
>COMMAND SUCCESSFUL
121
Liebert AC8
Setup Menu
Liebert AC8
122
Setup Menu
123
Liebert AC8
Setup Menu
SELECT A NUMBER:1
SELECT A NUMBER:1
INPUT
CONTROL RELAY
1 2
1=DEVICE_1
N N
2=DEVICE_2
N N
3=DEVICE_3
N N
4=DEVICE_4
N N
5=DEVICE_5
N N
6=DEVICE_6
N N
7=DEVICE_7
N N
8=DEVICE_8
N N
0=RETURN TO SETUP I/O MATRIX
I=RETURN TO SETUP MENU
SENSOR
CONTROL RELAY
1 2
1=SENSOR_1 HIGH STPT
N N
2=SENSOR_1 LOW STPT
N N
3=SENSOR_2 HIGH STPT
N N
4=SENSOR_2 LOW STPT
N N
5=SENSOR_3 HIGH STPT
N N
6=SENSOR_3 LOW STPT
N N
7=SENSOR_4 HIGH STPT
N N
8=SENSOR_4 LOW STPT
N N
9=RETURN TO SETUP I/O MATRIX
0=RETURN TO SETUP MENU
SELECT A NUMBER:1
SELECT A NUMBER:1
Liebert AC8
124
Setup Menu
Default
Other Options
LABEL
DEVICE_1 - DEVICE_8
NORM OPEN/CLOSE
NO (Normally open)
NC (Normally closed)
ALARM/EVENT
AL (Alarmable)
EV (Event)
LATCHED
L (Latched) / Y (Yes)*
NL (Unlatched) / N (No)*
DELAY
00:01 (1 second)
* NOTE: Different abbreviations are used to designate a digital input as Latched (L/Y) or Unlatched (NL/N) in Select Input/Set Inputs screens.
Default
Other Options
CONNECTED*
N (Not connected)*
Y (Connected)**
LABEL
SENSOR_1 - SENSOR_4
UNITS
DEG
4 mA
+045.0
20 mA
+096.0
OFFSET
+000.0
ALARM/EVENT
AL (Alarmable)
EV (Event)
LATCHED
N (Unlatched)
Y (Latched)
LOW SETPT
+0050.0
HIGH SETPT
+0090.0
SENSOR DELAY
00:01 (1 second)
* If a sensor is configured as N (Not connected), the display will show an empty reading (blank spaces).
** If a sensor is configured as Y (Connected) and is functioning properly, the display will show a reading.
If the connected sensor is not functioning properly, the display will show dashes (------) indicating a problem.
Digital input
Device_1
(none)
Device_5
(none)
Device_2
(none)
Device_6
(none)
Device_3
(none)
Device_7
(none)
Device_4
(none)
Device_8
(none)
Analog input
Sensor_1
(none)
Sensor_3
(none)
Sensor_2
(none)
Sensor_4
(none)
Default
Other Options
NORM OPEN/CLOSE
NO (Normally open)
NC (Normally closed)
MODE*
OP (Operating)
ST (Standby)
NU (Not Used)
IN ALARM
E (Enable)
D (Disable)
EMERG OP
E (Enable)
D (Disable)
125
Liebert AC8
Setup Menu
Table 36
Default
Other Options
AUTO SEQUENCING
OFF (Deactivated)
STANDBY TESTING
OFF (Deactivated)
ON (Activated)
FAILED STANDBY
N (Deactivated)
Y (Activated)
HOLD DELAY
RESTART
STAGING
OFF (Deactivated)
ON (Activated)
JUMPER SETTINGS
Feature
Digital output loss-of-power jumpers
Default
OFF - Normally Open
Other Options
ON - Normally Closed
NOTE: The jumper position has no effect on the contact when the Liebert AC8 has power.
24VDC
Default: jumpered
(connected)
Default: jumpered
(connected)
EPOP jumper
Disabled
Audible horn
Enabled
Default
Other Options
Any string (up to 40 characters); for international
dialing, add +GCI=xx, where xx is the country code
(except B5 countriessee Table 22)
ATS0=1
Y (enable)
ATE0X4DT
Any string
10 seconds
Default
All are OFF (down)
Other Options
May be used to reset password to factory default (see
9.9.1- Change Password)
OTHER SETTINGS
Feature
Default
Other Options
Password
AAAA
N (not reset)
Battery connected
Y (connected)
N (not connected)
Liebert AC8
126
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572
SL-31100_REV2_02-13
Embedded Computing
Embedded Power
DC Power
Outside Plant
Power Switching & Controls
Precision Cooling
EmersonNetworkPower.com
Racks & Integrated Cabinets
Services
Surge Protection
Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies.
2009 Emerson Electric Co.