MV Protection Relay
MV Protection Relay
© ABB Oy O242 EN
MV Protection Relay Applications
Content:
1 General
2 Introduction
3 Overcurrent Protection
4 Earth-fault Protection
5 Transformer Protection
6 Generator Protection
7 Motor protection
8 Disturbance Recording
10
11
12
1 General information
1.1 Course schedule
1.2 Notice
O242 Medium Voltage Protection Relay Applications Place: Hotel Silveria and
Week 14 (31.3. -4.4. 2008) Technobotnia
Time schedule
Introduction
Introduction MV Protection Relay
Applications
Introduction
Topics:
Brief History
Start in the Strömberg Research Center in the mid 1960´s
1965 First static protective relay (J3 series)
1970’s Digital technique and wider product range
1982 First microprocessor relay
1985 SPACOM product line introduced
1985 MicroSCADA programs for Substation Automation and SCADA
1987 Customer installations of fully integrated Substation Automation
and SCADA systems
1995 REF 54_ series introduced
2003 RE_ 600 protection relay family introduced
Powerful growth in the 1990´s
ABB Substation Automation Oy since April 1,1999
PRU Substation Automation since January 1 2002
PG Distribution Automation since 2004
Introduction
Electromechanical relays
1st generation, primary connected
measurement
2nd generation, power supplied from the
instrument transformers
Static relays
Power supplied by an external auxiliary voltage
Introduction
Numerical Relays
Microprosessor technology provides features as
in statical relays and more…
Introduction
Purpose of Protection
Detect all electrical faults and some abnormal operating conditions
Protect human beings and properties around the power network
The operation must be selective
disconnect minimum possible part of the power network
Introduction
Introduction
A A A A A A
Rated voltage Primary
of primary Primary winding
winding
20000/1.73 N N N N N N
Rated secondary n n n
Secondary
dn dn dn
voltage 100 /1.73 Secondary
winding winding
a a a da da da
V V V V
Introduction
Current sensor
Rogowski coil
Electrical symbol
Introduction
Current sensors
The current sensor is based on the principle of the Rogowski coil
The Rogowski coil has no iron core
1000
Saturation
10
0,1
Conventional transformer
with iron core
0,01
0,01 0,1 1 10 100 1000
Introduction
Current sensors
Linear response on all the measurement range
No saturation
No hysteresis
Single instrument for protection and measurement functions
High accuracy rating
High degree of immunity to electromagnetic disturbances
The output signal is a voltage (150 mV) function of the
time/current ratio
A single coil covers the range 0-3200A
The winding can stay open while the MV switchboard is in
service
Introduction
Voltage sensor
Resistive divider
Electrical symbol
Introduction
Z1 = 250 MΩ
Z2 = 25 kΩ Z1
U1
Z2 U2
Z2
U2 = * U1
Z1 + Z2
Introduction
Voltage sensors
Linear response on all the measurement range
No saturation
No iron-resonance
Single instrument for protection and measurement functions
High accuracy rating
High degree of immunity to electromagnetic disturbances
The output signal is a voltage proportional to the primary
voltage
The partition ratio is 10000 / 1
A single divider is used for the whole range 0 to 24 kV rated
voltage
Introduction
Combined sensors
Integrated instrument for both current and voltage sensors
Introduction
CT connections
Introduction
VT connections in SPACOM
Introduction
VT connections in REF54_
Nominal voltage setting by parameter
Parameter alternatives: 100V / 110V / 115V / 120V
Introduction
Sensor connections
Introduction
Technical details
Introduction
a) three-phase b) phase-to-phase
c) phase-to-phase-to-earth d) earth fault
e) cross-country fault
Introduction
10
3I>
1
3 I >>
t>
Time/s
I>
0,1
t>>
I>>
0,01
100 1000 10000
Current/A
Introduction
3I>
Introduction
3I>>
50
3-phase overcurrent relay with Instantaneous overcurrent relay
settable time delay, high set stage
I >
51N
Earth fault current relay with See 51 above, suffix letter N = Neutral
settable time delay (or network)
Id> 87
Differential current relay Differential protective relay
Introduction
Measuring principles
Non-directional overcurrent
(short-circuit protection)
Overload protection
Unbalance protection
Phase discontinuity
protection
Undercurrent protection or
loss of load protection
Introduction
Measuring principles
Non-directional earth-fault
protection
Sum connection
Ring core CT
Introduction
Measuring principles
Over- / Undervoltage
protection
Frequency protection
Introduction
Measuring principles
Earth-fault protection
Residual voltage protection
Introduction
Measuring principles
Directional overcurrent
protection
Directional earth-fault
protection
Voltage dependent
overcurrent protection
Distance protection
Over-/Under magnetizing
protection
Over / Under / Reverse
power protection
Introduction
Measuring principles
Differential protection
Introduction
Measuring principles
Differential protection Restricted earth-fault protection
Introduction
Measuring principles
Residual current protection
Differential current principle
Operates also when generator circuit
breaker is open
SPACOM module SPCJ 2C30
Setting range typically: 0.5 - 5.0%
Introduction
Measuring principles
Capacitor bank protection by SPACOM relays
Introduction
Measuring principles
Capacitor bank protection by REF54_ relays
Introduction
Measuring principles
Bus-differential protection e.g. by SPAE010
Introduction
Measuring principles
Current and voltage
sensors
Introduction
Introduction
Introduction
Introduction
http://inside.abb.com/sa-dsupportline
Chapter 3
Overcurrent protection
Short Circuit Protection
110 kV
1000.00
100.00
10 kV 10.00
1.00
10 kV
0.10
3I> 0.01
0 5 10 15 20
ABB Automation
Short_Circuit_Protection.ppt p 1 (78) EN 00.11, 1MRS751555
Contents
• Introduction
• Current measuring
– Accuracy limit factor
– Setting of the high-set current stage
• Introduction of protection methods
• Current selective protection
• Time selective protection
– Two type of time delays
– Time grading
ABB Automation
Short_Circuit_Protection.ppt p 2 (78) EN 00.11, 1MRS751555
Contents
• Time and current selective protection
• Blocking based protection
• Time and direcionally selective
• Others
– Differential protection
– Distance protection
• Backup protection
• Relay setting
• Excercise
ABB Automation
Short_Circuit_Protection.ppt p 3 (78) EN 00.11, 1MRS751555
Introduction
Causes of a short circuit
ABB Automation
Short_Circuit_Protection.ppt p 4 (78) EN 00.11, 1MRS751555
Introduction
Damage to a plant due to fault current
• Direct effects:
• Damages between charged components due to mechanical forces
• Damages to charged components due to thermal effects of the current
• Mechanical damages and danger of life due to arc
• Dangerous voltages between earthed components
• Disturbance voltages near the fault
• Indirect effects:
• Under voltage in the undamaged part of the network
• Temporary load peaks after the fault situation
• Loss of system stability
ABB Automation
Short_Circuit_Protection.ppt p 5 (78) EN 00.11, 1MRS751555
Introduction
Purpose of protection
ABB Automation
Short_Circuit_Protection.ppt p 6 (78) EN 00.11, 1MRS751555
Introduction
Purpose of protection
100 ms Small damages, minor repairs and cleaning required before the
switchgear is ready to use
ABB Automation
Short_Circuit_Protection.ppt p 7 (78) EN 00.11, 1MRS751555
Current measuring
Current transformer (CT)
I1
P1 S1 I2 P1 1S1
Measuring core
A and winding
A
1S2
P2 S2 2S1
Protection core
and winding
One core current transformer rel 1
2S2
C1 C2 3S1
Protection core
P2
rel 2 and winding
P1
3S2
P2
Three core current transformer
S1 S2
Two primary windings
ABB Automation
Short_Circuit_Protection.ppt p 8 (78) EN 00.11, 1MRS751555
Current measuring
Current sensor (Rogowski coil)
ABB Automation
Short_Circuit_Protection.ppt p 9 (78) EN 00.11, 1MRS751555
Current measuring
Main functions of CT / sensor:
ABB Automation
Short_Circuit_Protection.ppt p 10 (78) EN 00.11, 1MRS751555
Current measuring
Current transformer (CT)
Rated burden
- the sum of the burdens of all devices connected to the
P=Protection load of the current transformer plus the load of the
conductors must not be greater than the rated burden
Accuracy class
- typical values for current
transformers 5P (5%) and 10P (10%)
When dimensioning the CT´s and when making the relay settings the possible saturation has to be
taken into account
ABB Automation
Short_Circuit_Protection.ppt p 11 (78) EN 00.11, 1MRS751555
Current measuring
Saturation of CT
ISaturate ≥ Fa x IN
(=total error exceeds 5% at class 5P,
respectively 10% at 10P)
ABB Automation
Short_Circuit_Protection.ppt p 12 (78) EN 00.11, 1MRS751555
Current measuring
Saturation of CT
ABB Automation
Short_Circuit_Protection.ppt p 13 (78) EN 00.11, 1MRS751555
Current measuring
Calculating the accuracy limit factor ALF
S + Sn Where,
Fa = Fn × in Fn = nominal accuracy limit factor
Sin + Sa Sin = internal burden of the CT
Sn = nominal burden of the CT
Sa = actual burden of the CT
S = I2 x R
ABB Automation
Short_Circuit_Protection.ppt p 14 (78) EN 00.11, 1MRS751555
Current measuring
Calculating the accuracy current limit factor ALF
ABB Automation
Short_Circuit_Protection.ppt p 15 (78) EN 00.11, 1MRS751555
Current measuring
Exercise, calculate ALF
Calculate the actual over current limit factor ALF (Fa) for a three
phase connection with common return conductor.
ABB Automation
Short_Circuit_Protection.ppt p 16 (78) EN 00.11, 1MRS751555
Current measuring
Correct answer to exercise
300 / 5 5P20 10VA
Nominal current In = 5 A
Nominal accuracy limit factor Fn = 20
Nominal burden of the CT Sn = 10 VA
ABB Automation
Short_Circuit_Protection.ppt p 17 (78) EN 00.11, 1MRS751555
The maximum current setting (high-set) for the protection relay (rule of thumb)
I K min
= 0 .7 × or 0.7 × Fa whichever is smaller
I 1n
Where Ikmin is the minimum primary current,
at which protection must operate
ABB Automation
Short_Circuit_Protection.ppt p 18 (78) EN 00.11, 1MRS751555
Protection methods
Introduction
• “SLOW” methods:
time selective protection
time- and directionally selective protection
ABB Automation
Short_Circuit_Protection.ppt p 19 (78) EN 00.11, 1MRS751555
• Typical application 1
• Fault-current in LV-side does not
exceed setting in HV- side => LV trip
I>
• Fault-current in HV side => HV trip
I>>
ABB Automation
Short_Circuit_Protection.ppt p 20 (78) EN 00.11, 1MRS751555
Current selective protection
Lines
• Typical application 2
I> Trip
I>>
40 ms
zone of
protection
I>
I>>
ABB Automation
Short_Circuit_Protection.ppt p 21 (78) EN 00.11, 1MRS751555
• Advantages
• Operation time in relay ~40 ms
• Simple and reliable
• Low-priced
• Disadvantages
• Coarse operation (setting ~10 - 20*In)
• Applications restricted: specially in line protection
• Separate backup protection necessary
ABB Automation
Short_Circuit_Protection.ppt p 22 (78) EN 00.11, 1MRS751555
Time selective protection
Basis
I>
I>>
ABB Automation
Short_Circuit_Protection.ppt p 23 (78) EN 00.11, 1MRS751555
- current
- time delay in secs.
10.00
1.00
0.10
0 5 10 15 20
ABB Automation
Short_Circuit_Protection.ppt p 24 (78) EN 00.11, 1MRS751555
Time selective protection
Two type of time delays
1000.00
• Two settings:
- current 0.01
- time multiplier (k = 0.05..1) 0 5 10 15 20
ABB Automation
Short_Circuit_Protection.ppt p 25 (78) EN 00.11, 1MRS751555
ABB Automation
Short_Circuit_Protection.ppt p 26 (78) EN 00.11, 1MRS751555
Time selective protection
Co-operative action of multiple overcurrent stages
1000.00
Minimum of
operation
100.00
100.00
times
10.00
10.00
1.00
1.00
0.10
0.10
0.01
0.01
0 5 10 15 20
0 5 10 15 20
ABB Automation
Short_Circuit_Protection.ppt p 27 (78) EN 00.11, 1MRS751555
ΔtDT
I>
1 I>>
I>>>
ABB Automation
Short_Circuit_Protection.ppt p 28 (78) EN 00.11, 1MRS751555
Time selective protection
Time grading - definite time
Δt DT = 2 × t E + t R + tCB + t M
where t E = tolerance of the relay op.time
t R = retardation time of the relay tR = Retardation time (Overshoot time) =
tCB = operation time of CB time needed to cancel the trip.
t M = marginal time
tM = Delay of an auxiliary relay (if used)
+ Possible delay of operation due saturation
of CT. In theory this could be same as the
time constant of DC-component. In
practice 20 ms is enough because all
protection stages will be delayed.
ABB Automation
Short_Circuit_Protection.ppt p 29 (78) EN 00.11, 1MRS751555
Δt DT = 2 × t E + t R + tCB + t M
ABB Automation
Short_Circuit_Protection.ppt p 30 (78) EN 00.11, 1MRS751555
Time selective protection
Time grading - inverse time
ABB Automation
Short_Circuit_Protection.ppt p 31 (78) EN 00.11, 1MRS751555
⎛ E1 ⎞
⎜ 1 + ⎟
Δt IDMT = t1 × ⎜ 100 − 1⎟ + t R + tCB + t M
⎜1− 2 E ⎟
⎜ ⎟
⎝ 100 ⎠
where t1 = op.time of the relay of the closest location
ABB Automation
Short_Circuit_Protection.ppt p 32 (78) EN 00.11, 1MRS751555
Time selective protection
Time grading - inverse time - example step by step
Load 500A
ABB Automation
Short_Circuit_Protection.ppt p 33 (78) EN 00.11, 1MRS751555
1200A 1700A
ABB Automation
Short_Circuit_Protection.ppt p 34 (78) EN 00.11, 1MRS751555
Time selective protection
Time grading - inverse time - example step by step
ABB Automation
Short_Circuit_Protection.ppt p 35 (78) EN 00.11, 1MRS751555
1
ΔtIDMT
2
t1x(1-E1/100)/(1-E2/100)-1) 256 ms
op.time of CB 50 ms
retardation time 30 ms
marginal 20 ms
356 ms
ABB Automation
Short_Circuit_Protection.ppt p 37 (78) EN 00.11, 1MRS751555
Using
- Normal Inverse curve
⎛⎛ I ⎞α ⎞
- current 2.4 x setting ⎜⎜ ⎟ −1⎟ × t
⎜⎝ I > ⎠ ⎟
- operation time 1.356 s k=⎝ ⎠
=> the time multiplier k ≈ 0.18 β
ABB Automation
Short_Circuit_Protection.ppt p 38 (78) EN 00.11, 1MRS751555
Time and current selective protection
Principle
ABB Automation
Short_Circuit_Protection.ppt p 39 (78) EN 00.11, 1MRS751555
ABB Automation
Short_Circuit_Protection.ppt p 40 (78) EN 00.11, 1MRS751555
Time and current selective protection
Example
101 1G SHORT-CIRCUIT CURRENT FOR 1 GENERATOR
1 3
1 1 GENERATOR THERMAL WITHSTAND
3G EQUIVALENT SHORT-CIRCUIT CURRENT FOR 3 GEN.
1G
1 2 3 4 5 10 20 30 I/Ing
ABB Automation
Short_Circuit_Protection.ppt p 41 (78) EN 00.11, 1MRS751555
Fault
Blocking
Op.time
Min. 100ms
ABB Automation
Short_Circuit_Protection.ppt p 42 (78) EN 00.11, 1MRS751555
Blocking based protection
Typical applications
ABB Automation
Short_Circuit_Protection.ppt p 43 (78) EN 00.11, 1MRS751555
ABB Automation
Short_Circuit_Protection.ppt p 44 (78) EN 00.11, 1MRS751555
Blocking based protection
Advantages and disadvantages
• Advantages
• Technical solution is simple
• Rather fast operation, operation time is 100 ms
• Includes a backup protection (time delay)
• Low-priced
• Disadvantages
• Auxiliary connection is needed in Line protection
applications
ABB Automation
Short_Circuit_Protection.ppt p 45 (78) EN 00.11, 1MRS751555
0 ms
Starting time of the relay
40 ms
Input delay on the relay to be blocked
50 ms
Retardation time
80 ms
Marginal
100 ms
ABB Automation
Short_Circuit_Protection.ppt p 46 (78) EN 00.11, 1MRS751555
Blocking based protection
Time needed for blocking - exercise
3I>
t3
Blocking line 1
3I>
t1
ABB Automation
Short_Circuit_Protection.ppt p 47 (78) EN 00.11, 1MRS751555
I fault
U
3I>
R2
U I load
I load
operation
operation I fault
ABB Automation
Short_Circuit_Protection.ppt p 48 (78) EN 00.11, 1MRS751555
Time and directionally selective
Exercise
Station A Station B
3I> 3 3I>
250ms
100ms
3I> 3I> 1
400ms 100ms
3I> 4 3I>
250ms
5 100ms 2
ABB Automation
Short_Circuit_Protection.ppt p 49 (78) EN 00.11, 1MRS751555
ABB Automation
Short_Circuit_Protection.ppt p 50 (78) EN 00.11, 1MRS751555
Time and directionally selective
Advantages/disadvantages 1 2
ABB Automation
Short_Circuit_Protection.ppt p 51 (78) EN 00.11, 1MRS751555
ABB Automation
Short_Circuit_Protection.ppt p 52 (78) EN 00.11, 1MRS751555
Time and directionally selective
Principles of direction criteria
ABB Automation
Short_Circuit_Protection.ppt p 53 (78) EN 00.11, 1MRS751555
Memorized voltage
(flywheel)
Actual voltage
Short circuit
ABB Automation
Short_Circuit_Protection.ppt p 54 (78) EN 00.11, 1MRS751555
Differential protection
ABB Automation
Short_Circuit_Protection.ppt p 55 (78) EN 00.11, 1MRS751555
Differential protection
Advantages:
• Operation time in stabilized stage ~ 50 ms,
operation time in instantaneous stage ~10 ms
• Sensitivity (basic setting P > 20 % *In
for transformers, P > 5 % *In for generators)
• Usable for many different applications
• Exactly defined protected zones (absolutely
selective)
Disadvantages:
• Separate backup protection necessary
• High accuracy of current transformers (Fa>40)
• High-priced
ABB Automation
Short_Circuit_Protection.ppt p 56 (78) EN 00.11, 1MRS751555
Line differential protection
Basic diagram of modern line differential protection system
ABB Automation
Short_Circuit_Protection.ppt p 57 (78) EN 00.11, 1MRS751555
Advantages:
• Selective protection to meshed networks
• Operation time in relay ~30 ms
• High sensitivity
• Exactly defined protected zones (absolutely selective)
• May include a backup protection
• Fiber optics connection can be used also in substation control systems and
that will provide a chance to make absolutely selective earth-fault protection
• Unaffected by power variation
• Zone of protection could be over a serial capacitor
Disadvantages:
• Fiber optics connection is expensive
• Busbar protection not included
• Difficult to perform in branch line applications
ABB Automation
Short_Circuit_Protection.ppt p 58 (78) EN 00.11, 1MRS751555
Distance protection
ZL=R+jX
Load
Z< Z<
R
ABB Automation
Short_Circuit_Protection.ppt p 59 (78) EN 00.11, 1MRS751555
Distance protection
Advantages:
• Selective line protection to meshed networks
• Operation time is typically ~30 ms in relay
• Backup protection for other relays because of many protection zones
• 1st zones are establishing fast and almost absolutely selective protection,
which will cover about 85 % of protected zone
• Auxiliary connection is not necessary
• Unaffected by connecting and loading variation
• Versatile operation (short circuits, earth-faults, network and load variations)
ABB Automation
Short_Circuit_Protection.ppt p 60 (78) EN 00.11, 1MRS751555
Distance protection
Disadvantages:
• Sensitivity is depending on load impedance
• Next reasons are impeding the operation
- weak background network + short line (operation accuracy, selectivity)
- fluctuating power (latching is optional)
- effect of a fault resistance (accuracy, sensitivity)
• High-priced, optional functions are increasing a price of relay
• Difficult to calculate the settings
ABB Automation
Short_Circuit_Protection.ppt p 61 (78) EN 00.11, 1MRS751555
Backup protection
• Protection should be active even when one device is damaged
=> each protection unit must have a backup and the operation of each breaker must
be secured.
Methods:
Remote back-up protection
• Is formed naturally from successive protection stages upstream in the network
(time selective protection)
• Sometimes these stages do not overlap totally, when local back-up protection
and circuit-breaker failure protection are called for
Local backup
• Separate relay is used, main and back-up protection trip the same CB,
e.g. O/C relay is used as back-up protection for differential relay
Th
erm
al
ca
pa
cit
y
normal load current
inrush current
current
ABB Automation
Short_Circuit_Protection.ppt p 63 (78) EN 00.11, 1MRS751555
Relay setting
Take into account in fault calculation
1,0
0,87
0,5 0,5 0,5
0,87
0,5
ABB Automation
Short_Circuit_Protection.ppt p 64 (78) EN 00.11, 1MRS751555
Relay setting
Adapting of relay settings according to feeder connections
• When connection- and load situations are shifting, relay settings have
to be changed
• Example
• Decrease of minimum fault current due to feeder connections
• Reversal of supply: use of backup supply, changing of supply in the
meshed networks
• Connection of parallel transformer (in time when parallel connection)
ABB Automation
Short_Circuit_Protection.ppt p 65 (78) EN 00.11, 1MRS751555
Relay setting
Example for adapting the relay setting
Transformers are connected temporarily to parallel connection, then
short circuit is increasing over the rated short circuit current value
ABB Automation
Short_Circuit_Protection.ppt p 66 (78) EN 00.11, 1MRS751555
Relay setting examples
Time selective protection
110 kV 30 kA SPAJ 144 C I> 1320 A Coordination curves
3I> k 0,17 1000
very inverse
3I d
25 MVA SPAJ 144 C I> 1080 A cable (**
I> k 0,1 10
1
3I>
very inverse
Time [s]
800/1 A 3I>> I>> 2080 A
t >> 0,45 s transformer (*
2
3I>>> I>>> 3600 A 1
2 t >>> 0,2 s
20 kV 6,5 kA
½ × IS
IN (transformer)
0,1
SPAJ 144 C I> 330 A 3
300/1 A k 0,15
3I>
very inverse
FAULT 3I>> I>> 900 A IS
t >> 0,3 s 0,01
100 1000 10000 100000
3I>>> I>>> 3000 A
AHXAMK-W 3×185
1 t >>> 0,04 s Current [A]
IS = transformer inrush current INMAX for cable = 330 A (* the Transformer through-fault current duration curve
half-time for inrush current = 0,1 - 0,3 s Ikmax for cable = 17,5 kA / 1 s (** the Cable current duration curve
ABB Automation
Short_Circuit_Protection.ppt p 67 (78) EN 00.11, 1MRS751555
very inverse
3I>> I>> 3300 A
t >> 0,1 s
150/1 A 100
3I>>> I>>> 8250 A
3 t >>> 0,04 s
3I d
25 MVA SPAJ 144 C I> 1080 A 1 cable (**
I> 10
3I> k 0,1
Time [s]
3I>>
20 kV 6,5 kA
blocked
IN (transformer)
0,1 stages
SPAJ 144 C I> 330 A 3
300/1 A k 0,15
3I>
very inverse
3I>>
FAULT IS
3I>> I>> 600 A 0,01
t >> 0,3 s 100 1000 10000 100000
AHXAMK-W 3×185 3I>>> I>>> 1800 A Current [A]
1 t >>> 0,04 s
3I>> stage of relay 1 sends a blocking signal to relay 2 and 3I>> stage of relay 2 sends a blocking signal to relay 3.
Now, 3I>> stages of the relay 2 and relay 3 are blocked.
IS = transformer inrush current INMAX for cable = 330 A (* the Transformer through-fault current duration curve)
half-time for inrush current = 0,1 - 0,3 s Ikmax for cable = 17,5 kA / 1 s (** the Cable current duration curve)
ABB Automation
Short_Circuit_Protection.ppt p 68 (78) EN 00.11, 1MRS751555
Relay setting examples
Blocking based protection
110 kV 30 kA
Coordination curves
SPAJ 144 C I> 1320 A
k 0,30 1000
3I>
Time [s]
3I>> very inverse
800/1 A 3I>> I>> 1600 A 2
3I>>
t >> 0,1 s transformer (*
3I>>> 1
I>>> 4000 A
FAULT 2
t >>> 0,2 s
blocked
½ × IS
20 kV 6,5 kA
stage
IN (transformer)
0,1
SPAJ 144 C I> 330 A 3
300/1 A k 0,15
3I>
very inverse
3I>>
IS
3I>> I>> 600 A 0,01
t >> 0,3 s 100 1000 10000 100000
AH XAM K-W 3×185 3I>>> I>>> 1800 A Current [A]
1 t >>> 0,04 s
No blocking signal from relay 1. So, 3I>> stage of relay 2 is not blocked. Now, the relay 2 trips in 0,1 s.
3I>>> stage of relay 2 sends a blocking signal to relay 3. 3I>> stage of relay 3 is blocked.
IS = transformer inrush current INMAX for cable = 330 A (* the Transformer through-fault current duration curve)
half-time for inrush current = 0,1 - 0,3 s Ikmax for cable = 17,5 kA / 1 s (** the Cable current duration curve)
ABB Automation
Short_Circuit_Protection.ppt p 69 (78) EN 00.11, 1MRS751555
Exercise
Cable 1: maximum nominal current = 260 A (0,4 kV)
10 kV, S'' = 160MVA allowed 1 second short circuit current = 10kA
Cable 2: maximum nominal current = 94 A (10 kV)
150 / 5 A 3I> allowed 1 second short circuit current = 3 kA
10 kV
50 / 5 A 50 / 5 A 50 / 5 A Formulas:
3I> 3I> 3I>
ABB Automation
Short_Circuit_Protection.ppt p 70 (78) EN 00.11, 1MRS751555
Exercise
Selectivity graph Selectivity curves
axes. fuse
The ready made curve is for 100
the fuse on 400V side.
10
Time [s]
1
0,1
0,01
1,0A 10,0A 100,0A 1 000,0A 10 000,0A
Current [A]
ABB Automation
Short_Circuit_Protection.ppt p 71 (78) EN 00.11, 1MRS751555
Exercise
Cable thermal curve
Cable 1 Inmax = 260A (0.4kV)
Ik1sec = 10kA (0.4kV) (=400A in 10kV)
2 2
tmax × Ikmax = t1s × Ik1s
2
⎛I ⎞
2
⎛ 400 ⎞
t max = ⎜⎜ k1s ⎟⎟ × t1s = ⎜ ⎟ ×1sec =
⎝ Ikmax ⎠ ⎝ 200 ⎠
ABB Automation
Short_Circuit_Protection.ppt p 72 (78) EN 00.11, 1MRS751555
Exercise
Cable thermal curve
Ik1sec = 8 kA
ABB Automation
Short_Circuit_Protection.ppt p 73 (78) EN 00.11, 1MRS751555
Exercise
Relay 1
IEC 354, short time energ. loading
of distr. transformers is 2.0 p.u.
I > = 2 x transformer nominal current = _____ A
1.1× 6.06MVA
Ik ' ' = = 9.62kA (Short circuit current in 400V side)
3 × 0.4kV
ABB Automation
Short_Circuit_Protection.ppt p 74 (78) EN 00.11, 1MRS751555
Exercise
Relay 1 continues
Current in 10kV side:
0.4kV
I= × 9.62kA = 385 A
10kV
1.1× 160MVA
Ik ' ' = = 10.2kA
3 × 10kV
ABB Automation
Short_Circuit_Protection.ppt p 75 (78) EN 00.11, 1MRS751555
Exercise
Relay 2
630kVA
In = = 36 A
3 × 10kV
Max. total load = 1.1 x 3 x 36A = 119 A. Therefore I> = 150A is OK!
ABB Automation
Short_Circuit_Protection.ppt p 76 (78) EN 00.11, 1MRS751555
Exercise
Relay 2
I >> should be at least 1.2 x half life value of inrush current. Inrush current is
normally about 10 times the nominal current.
Is = 10 × In = 10 × 36 = 360 A
ABB Automation
Short_Circuit_Protection.ppt p 77 (78) EN 00.11, 1MRS751555
Exercise
Relay 2 continues
Is = 3 x (10X36) = 1080A
0.5 x Is = 540 A
ABB Automation
Short_Circuit_Protection.ppt p 78 (78) EN 00.11, 1MRS751555
T rip cu rve fo r 10kV sid e
1000
100
10
Time (s)
0,1
0,01
1 10 100 1000 10000
C u r r e n t (A )
Chapter 4
Earth-fault protection
Earth-Fault Protection MV Protection Relay
Applications
Earth-Fault Protection
Topics:
What is earth-fault?
Earth-Fault Protection
Earth-fault situations
Earth-Fault Protection
Hazard voltages
Earth-Fault Protection
Earth-Fault Protection
Isolated neutral
Isolated neutral
One phase earth-fault
L1
L2
110 / 20kV
L3
Rf
ΣI 3C0
Ief
U0
L1
L2
L3
ΣI 3C0
L1
L2
L3
ΣI 3C0
Earth-Fault Protection
Isolated neutral
Unsymmetrical system
is
ir=ie
-Uo
it
r ir+is+it=io
ut
s
ut us 3*Uo t
Rf = 0
us
is
-Uo
Uo it
r ir+is+it=io
s
t
Earth-Fault Protection
Isolated neutral
Calculation of earth fault current
In the case where the fault resistance Rf is zero (0), the
fault current can be calculated as follows:
Ie = 3ωC0E
Co = earth capacitance per phase
E = phase voltage
For overhead lines the earth fault current (Rf=0) can
roughly be calculated as follows:
U×l
Ie = [A ]
300
U = phase-phase voltage [kV]
l = length of the galvanically connected OH-lines [km]
Earth-Fault Protection
Isolated neutral
Ie
Ief =
2
⎛I ⎞
1 + ⎜ e Rf ⎟
⎝E ⎠
Earth-Fault Protection
Isolated neutral
(I - I )
ΣIef = e e feeder × Ief
Ie
ΣIef = residual current measurement of the faulty feeder
Ie = earth fault of the network, when Rf = 0
Ief = calculated earth fault current at a certain fault resistance Rf
Iefeeder = earth fault current of the faulty feeder, when Rf = 0
Earth-Fault Protection
Isolated neutral
Calculation of zero sequence voltage (U0)
Zero sequence voltage indicates that there is an earth fault in the network
If the fault resistance Rf = 0, the zero sequence voltage level is the same as
the phase voltage (E)
Ief
U0 = , or
3ωC0
E
U0 =
2
⎛I ⎞
1 + ⎜ e Rf ⎟
⎝E ⎠
Earth-Fault Protection
Isolated neutral
Protection relays in isolated network
Non-directional or directional earth-fault relays can be used
Relay can operate by Io or Isinϕ principle
Isinϕ principle requires also Uo measuring
Earth-Fault Protection
Isolated neutral
Isinϕ principle
U0
TRIP BLOCK
I0 ϕ
~8·Iϕ>
Earth-Fault Protection
Compensated neutral
Earth-Fault Protection
Compensated neutral
One phase earth-fault
L3
V3N
L2
N
V2N
L1
V1N
CE CE CE
IL IC V1E V2E V3E
V0
I2 I3
N=E V1N=V1E
V0 = 0 V2E V3E V0 = V1N
I3
L1=E
IC IL
L1
L1
I2
Earth-Fault Protection
Residual voltage:
U0 = Residual voltage Rr
RY = Parallel resistance U0 = ×E
2
2⎛ 1 ⎞
Rf = Fault resistance
(R f + Rr ) 2
+ R f Rr ⎜ 3ωC0 −
2
⎟
RL = coil leakage resistance ⎝ ω L⎠
R0 = system leakage resistance
L = coil inductance
Ce = network earth capacitances
Cj = earth capacitance of an faulty feeder
Earth-Fault Protection
Compensated neutral
Degree of compensation
The amount of compensation is called for compensation degree, K
If value of K is one or near it, the network is completely compensated
Over compensated, if K > 1
Under compesated, if K < 1
Compensated neutral
Principle of operation
low earth-fault current
recovery voltage is increasing slowly up to phase voltage level
because of compesation coil
improbability of new arc ignition
Earth-Fault Protection
Compensated neutral
Principle of compensation
DECENTRALIZED COMPENSATION CENTRALIZED COMPENSATION
Earth-Fault Protection
Compensated neutral
Principle of compensation
CENTRALIZED COMPENSATION FOR TWO
SEPARATE NETWORKS
Earth-Fault Protection
Compensated neutral
Centralized compensation
Example connection for centralized
compensation
Station own
consumption
Earth-Fault Protection
Compensated neutral
Typical operation for parallel resistor
Resistor will be connected with short delay after the fault detection
Resistor is continuously in use
Resistor is continuously in use but will be unconnected after fault
detection - if the earth-fault will not be self extinguished within short
time delay the parallel resistor will be connected again
Earth-Fault Protection
Compensated neutral
Protection relays in compensated network
Directional earth-fault relays must be always used
Directional E/F protection requires Uo and Io measuring
Relay direction must be possible to set by basic angle or by
changing the operation characteristics in Isinϕ or Icosϕ
The protection should have back-up protection in case of
service or repair for primary system, meanwhile the network
is in isolated position
- separate protection relay
- using of second settings
- by setting the relay according to new network connection
Earth-Fault Protection
Compensated neutral
Basic angle operation
U0
Base angle ϕ0 = 0o
ϕ
I0
Δϕ TRIP
BLOCK
In
Earth-Fault Protection
Compensated neutral
Icosϕ operation
U0
Icosϕ I0
ϕ
TRIP
BLOCK Iϕ >
-Icosϕ ~8·Iϕ>
Earth-Fault Protection
Earth-Fault Protection
UR Z
~ R equivalent circuit
US Z Ief Rf IRe
~ S IC
U0
UT Z ~ Re
~ T Up 3·ω ⋅C0
Re Ief C0
Rf
Earth-Fault Protection
equivalent circuit
The earth fault current Ief:
Ief Rf IRe IC
E 1 + (Re 3ωC0 )
2
U0
Ief = ~ Re
(Rf + Re) + (Rf Re 3ωC0)
2 2
Up 3·ω ⋅C0
Earth-Fault Protection
Ief Uo Re
Uo = 2 or when Xc0>>R: =
⎛ 1⎞ E Re + Rf
⎜ ⎟ + ( 3ωCo)
2
⎝ Re ⎠
Earth-Fault Protection
Earth-Fault Protection
Earth-Fault Protection
Solidly earthed neutral
UR Z
~ R
US Z
~ S
UT Z
~ T
Ief C0
Rf
3E
If =
Z0+Z1+Z2+3Zf
Earth-Fault Protection
D y
Rs
ΔI0 >
Earth-Fault Protection
Measurements
Measurements
Rogowski current sensors
Earth-Fault Protection
Measurements
Cable core transformer Efficency factor n for a 100/1 transformer as a function
of the networks earth fault current (solid line).
Within the mentioned current range is the phase angle error
The efficiency factor n should less than 5 degrees.
100 %
be considered when 99 %
97 % 100/1
n Isn
Iorelay = * * I0 96 %
100 Ipn
n(%)
95 %
CT
91 %
Ipn = Rated primary current of the
90 %
CT 0,01 0,1 1 10
Io/Ipn
I0 = Primary earth fault current (A) continued...
Earth-Fault Protection
Measurements
Residual connection of current transformers
Earth-Fault Protection
Measurements
Residual connection of current transformers
Iorelay =
(I0 − I0 ap)Isn
Ipn
Iorelay = relay setting (A)
Isn = Rated secondary current of the CT
Ipn = Rated primary current of the CT
I0 = Primary earth fault current
I0ap = Max apparent residual current (primary value)
Earth-Fault Protection
Measurements
Residual voltage
Earth-Fault Protection
Measurements
Residual voltage
Upr : 20/sqrt(3) kV
Usr : 2/sqrt(3) V
accuracy: Class 1 / 3P
Chapter 5
Transformer protection
ABB Oy, Distribution Automation Power Transformer
Vaasa, Finland
Differential Protection
Transformer Protection
Contents
Part 1 - Introduction
Part 2 - Differential Protection: Applications, Theory and Settings
Part 3 - Differential Protection: Advantages of Numerical Relay
Part 4 - Differential Protection: Setting calculations
Part 5 - Overcurrent and Earth-Fault Protection
Transformer Protection
Part 1
Introduction
Transformer Protection
Faults
c a
Transformer Protection
SPAD 346C
Grouping of the Transformer
Protection
Winding short circuit and interturn
protection: differential relay
Earth-fault protection
Overcurrent protection
Transformer Protection
Overall Power Transformer Protection
RET 54x
Basic version
All protection functions that uses only
current measurements
DIFF, OC, EF, Thermal, NPS
Optionally automatic voltage regulator
Multi version
Basic plus functions using voltage
Directional protection, Voltage protection,
Frequency protection, Overexcitation,
underimpedance
Control version
No protection, automatic voltage
regulator
Transformer Protection
REF 542plus
Transformer Protection
Overall Power Transformer Protection
Transformer Protection
Gas relay (Buchholz)
Installed in the tube between the
coil conservator and the
transformer tank
Partial discharge etc. => bubbles
in the oil are trapped into the relay
=> alarm
Heavy fault => oil impulse wave
=> trip in about 100 - 300 ms
Pressure relay of the on-load tap
changer.
Transformer Protection
Transformer Protection
Over load protection: Oil thermometer, winding
temperature inductor system, thermal overload
relay
Over voltage protection: Spark-gaps, surge
arresters
Oil quality analysis, partial discharge
monitoring etc
Transformer Protection
Protection scheme, example
110 kV Trip
20 kV Trip
Alarm
Measuring Backup
Gas relay
Tap changer protection
Winding temperature
Oil temperature
Oil height (swimmer)
Transformer Protection
Differential prot.
Part 2
Differential Protection
Applications, Theory and Settings
Transformer Protection
Principle, pros and cons
Advantages:
• Operation time in stabilized stage ~ 50 ms,
operation time in instantaneous stage ~10 ms
• Sensitivity (basic setting P > 20 % *In
for transformers, P > 5 % *In for generators)
• Usable for many different applications
• Exactly defined protected zones (absolutely
selective)
Disadvantages:
• Separate backup protection necessary
• High accuracy of current transformers (Fa>40)
• High-priced
Transformer Protection
A IA + IK Ia a
Ik
B IB + IK b
Ib
C IC c
Ic
Transformer Protection
A IA Ia
a Rf
U
B I B+ IK Ib b Ik
Ib Ib
C IC Ic c
Transformer Protection
Principle of Differential Protection Relay
Protection Area
I1 I2
Bias Bias
Diff
I1 + I 2
I Diff = I 1 − I 2 I Bias =
2
Operation characteristics
IDiff
Operation Area
Non-operation
Area
1 xIn IBias
Transformer Protection
Operation characteristics
IDiff
Inside
Fault
Outside
Fault
No fault
1 xIn IBias
Stabilized
Differential = Sensitivity & Stability
Protection
Transformer Protection
Varying tap-changer
positions
Transformer no-load
current
P Non-operation Area
Transformer over-
magnetisation U>, f<
1 xIn IBias
setting range 5 - 50%
≥ 20% for transformers
≥ 5% for generators
Transformer Protection
Operation characteristics, settings (SPAD/RET)
Part 3
Differential Protection
Advantages of Numerical Relay
Transformer Protection
Need for interposing CTs (old relays)
Differential
relay
Transformer Protection
Differential
relay
Transformer Protection
Need for interposing CTs (old relays)
E/F
E/Fcurrent
currentflows
flowsininthe
theHV-side
HV-sideonly.
only.
Without
Without elimination the relay willsee
elimination the relay will see
this as a differential current!
this as a differential current!
Numerical
computation of
Vector group matching
DIFF-protection
CT ratio corrections
Vector Vector
Zero sequence group- group-
elimination matching matching
(HV-side) (LV-side)
Eliminates the need
of interposing CTs Zero-seq.elimination Zero-seq.elimination
(for two-winding
transformers). Diff and Bias elements
87
Transformer Protection
Advantages of Numerical Relay
Phase angles
Values are after Vector Group Matching
120 degree between phases
0 degree between HV and LV
Part 4
Differential Protection
Setting calculations
Transformer Protection
CT ratio correction, SPAD 346C
SN
Power Transformer Rated current IN =
3 ×UN
I1 IN
CT ratio correction =
IN I CT −primary
⎜ IN I I ⎟
⎝ CT − primary relay ⎠
25 MVA
110 kV 21 kV
300 / 1 1000 / 1
Transformer Protection
CT ratio correction, SPAD 346C
SN 110 kV 25 MVA 21 kV
IN = 300 / 1 1000 / 1
3 ×UN
I1 IN
=
I N I CT −primary
HV-side IN =
I1/IN =
LV-side IN =
Transformer Protection
I2/IN =
Operation characteristics
200/5
S - setting 5P20
(HV ct) 15 VA
(LV ct)
(Tap changer) 25 MVA 3Id>
I2tp =
because I1/In was rised, also I2/In must be rised (same per cent)
Differential Protection
Vector Groups and Blocking
Transformer Protection
CT connections
Type II
Type I
Transformer Protection
Vector Groups
Phase angles
0 = 0º
1 = 30º
2 = 60º
6 = 180º
Transformer Protection
Vector Groups
Phase angles
0 = 0º
1 = 30º
2 = 60º
6 = 180º
Transformer Protection
Do I need zero-sequence elimination?
No, if
D -winding
Otherwise
activate elimination
Transformer Protection
⇒ Dyn1
11 1
Transformer Protection
Inrush current at transformer energising
transformer core 80 %
I 3 (% of I 1)
60 %
30 %
I 5 (% of I 1)
10 %
⇒ de-blocking
Over-excitation
100 %
40 %
I m (% of I n)
10 %
I 7 (% of I 1)
0%
Deblocking in use, 50 % setting: 100 105 110 115 120 125 130 135 140
Overcurrent
and
Earth-Fault Protection
Transformer Protection
Overcurrent protection
I>
I> stage time selective with zone of I>> T
40 ms
down stream relay => protection
“slow” protection
Compares fundamental
components of the measured Io
and calculated sum of phase
currents
Non-linear
resistor
Stabilizing
Transformer Protection
resistor
Io
Transformer Protection
Contents of chapter 6
6 Generator protection
Generator protection
Part I
• Protection objectives
• Faults and failures
G G
Protection zone
of generator 1
Objectives (2/2)
Network outside of
the protection zone
of generator 1
G G
Gen. 1
Objectives
• Minimized effects in fault location
• Disturbances to the network minimized
• Fast and sensible operation
Objectives
• Limiting the effects to the generator and
network to a safe level.
• Sensible and accurate operation
Objective
• Limiting the effects to the generator and network to
a safe level.
• Selective and stable operation
• Sensible and accurate operation
ESV UCB2
Part II
Fault situations:
• Stator internal fault
• Stator external fault (for example in the machine terminals)
• Backup for the network short-circuit
Effects:
• Runaway (especially in close-up short-circuits, the voltage collapses, generator
cannot generate power to the network => speed increases rapidly)
• Loss of stability/mechanical stress when short-circuit is tripped => fast
operation needed
Short-circuit protection
Stator internal fault, does it matter where a
I>
G G G
I>
Short-circuit protection
Terminal short-circuit protection, voltage controlled overcurrent protection,
old way:
Short-circuit protection
Terminal short-circuit protection, under-impedance protection:
LINE
PROTECTION
t> = 1 s
t>> = 0.1s
FAULT DATA
Zsource / Zload Ik / I n Uk / U n Zrelay / Zload
FAULT DATA
Zsource / Zload Ik / In Uk / Un Zrelay / Zload
14
13
No damages
12
Small welding scars on surface Bad burning scars ( )
11
Duration of earth-fault current [s]
10
5 Dimension of burning
scars is 10 mm.
4
0
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140
Y-winding: D-winding:
2)
2)Sensitive
Sensitiveearth-fault
earth-faultprotection
protection
(such
(such as REJ517
as REJ 517oror
NEF1Low&High
NEF1Low&Highfunction
functionblock
block
1)
Ur=40 Vac
Effects:
• Mechanical and thermal stress to the prime mover
• In case of out-of-synchronism: strong swinging of active and reactive power and
terminal voltages => mechanical and thermal stress to the generator and to the
prime mover.
Reverse power
+P
Reverse
power
Generator protection p 24 (43)
Reverse power
+Q
setting
Operation
+P
Reverse Forward
power power
Reverse power
Protection:
• Reverse power protection with 2 (or 3) stages:
• 1. stage: controlled “soft” stopping, the stage operates and opens the main
and field breakers (prevents over-speeding)
• Short operation time
• 3. stage can use integrating time-relay that ensure the operation in case of
asynchronous operation.
Turbine
shut-down
Soft stopping t1
P<
Tripping of the
t2 generator CB
Actual protection P<
• If no shut-down has been carried out, the second stage (t2) trips the
generator in a reverse power situation
Under-excitation
Effects:
• Rotor-iron heating by the eddy currents in rotor iron and dampers
• Under-voltage at the terminals because of increased reactive power
• Stator heating by the increased reactive current and magnetic flux
• Moving from synchronous to asynchronous operation (out-of-sync.):
• Strong swinging of active and reactive power and terminal voltages
• Disturbs the network and consumers
• Thermal and mechanic stress
Protection:
• 1- or 2-stage (alarm + trip) under-reactance protection (mho-relay)
+X
xd '
Offset = +R
2
Diameter = xd xxd’ ’==transient
transientreactance
reactance
d
xxd ==synchronous
synchronousreactance
reactance
d
a a
b b
c c
Effects :
• Negative phase sequence (NPS) in stator current (I2)
• Eddy currents in rotor iron and dampers → dangerous rotor heating (additional
losses by negative phase sequence current (I2)2 x t
• Vibration, mechanical stress
Protection:
• 1 or 2-stage negative phase-sequence current protection (alarm + trip)
• Allowed continuous NPS tolerance must be known
(Typically 8..12% with turbogenerator and 20..30% with salient pole machine)
• Typical short time tolerance (I2)2 x t
• Turbine-generator 30 sec.
• Hydraulic generator 40 sec.
• Diesel generator 40 sec.
• Rotating compensator 30 sec.
Effects:
• Stress caused to the insulator material by over-voltage
• Thermal stress of iron core by over-magnetising (over-voltage)
• Increasing of magnetic flux density: B = k * (E/f)
• Saturation of iron core
• Increasing of leakage flux and spreading of flux to unlaminated parts
• Stator overload because of sudden diminution of the network (inductive overload
→ under-voltage)
Protection:
• Over-voltage protection with two stages:
• 1. Stage: definite time, setting according the voltage tolerance of the
machine
• 2. Stage: definite time (fast operation), prevents instant damages to the
insulator material and damaging over-magnetising of iron core
• Typical settings:
1. stage: 1.10 x Un, tolerance of the machine ± 5 %
1.13 x Un, tolerance of the machine ± 7.5 %
1.15 x Un, tolerance of the machine ± 10 %
operation time 5 - 10 s
2. stage: 1.3-1.4 x Un
operation time 0.1 s
Over- or under-frequency
Fault situation:
• Sudden changes of load. E.g. loosing the connection to main grid (infinite
system) → underfreq. or sudden tripping of large load → overfreq.
• Fault if power control or prime mover while operating in island
• During starting and stopping the generator
Effects:
• Mechanical and thermal stress to the prime mover (over/under-freq.)
• Thermal stress to the iron core by the over-magnetising (undrefreq.)
• Increasing of magnetic flux density: B = k * (E/f)
• Saturation of iron core
• Increasing of leakage flux and spreading of flux to unlaminated parts
Protection:
• 2-stage over-frequency protection (alarm + trip)
• 2- or 3-stage under-frequency protection (alarm + 2 x trip)
Over-magnetising
Effects:
• Thermal stress to the iron core by the over-magnetising (overvoltage.)
• Increasing of magnetic flux density: B = k * (E/f)
• Saturation of iron core
• Increasing of leakage flux and spreading of flux to unlaminated parts
•Protection:
• 2-stage protection based on U/f -ratio.
Asynchronous operation
Fault situation: Generator set out of synchronous operation
• Under-excitation
• Fault in the network
• Incorrect phase order when switching in
Effects:
• Strong swinging of active- and reactive power and terminal voltages
• Rotor-iron heating by the eddy currents in rotor iron and dampers
• Stator heating because of the increased current and magnetic flux
• Mechanical and thermal stress to the generator and prime mover
Effects:
• Local overheating of the winding, which may result in severe damage
Protection:
• Protection is required if two or more turns of the same phase winding
are located in the same winding slot.
Protection:
Based on current Based on voltage
(split winding) (open delta)
The
TheVTVTprimary
primaryside
sidestar-
star-
Δ point is directly connected
point is directly connected
totothe
thegenerator
generatorstar-point.
star-point.
In cases where the measured variable (e.g. reactance, reverse power) swing in to
and out from the operation area (i.e. the protection starts and resets periodically)
the relay might not trip.
ta tb Start
Start Trip
ta tb
Trip
Motor protection
ABB Oy, Distribution Automation AC Motor Protection
Vaasa, Finland
(3-phase induction and
synchronous motors)
Contents
Part 0 – AC Motors
Part 1 - Introduction
Part 2 - Thermal Protection (general information)
Part 3 - Thermal Overload Protection
Part 4 - Consecutive starts (cumulative start-up counter)
Part 5 - Start-Up Supervision (Locked rotor protection)
Part 6 - Temperature Protection (RTD inputs)
Part 7 - Short-Circuit Protection
Part 8 - Unbalance Protection
Part 9 - Loss of Load
Part 10 - Earth Fault Protection
Part 11 - Miscellaneous
Part 0
AC Motors
Induction AC motor
There are only two main components: the stator and the rotor. The
stator contains a pattern of copper coils arranged in windings. As
alternating current is passed through the windings, a moving magnetic
field is formed near the stator.
Stator
(stationary part)
Rotor
(rotating part)
Induction AC motor
The rotor is constructed of a number of conducting bars running parallel
to the axis of the motor and two conducting rings on the ends. The
assembly resembles a squirrel cage, thus this type of motor is often
called a squirrel-cage motor.
Image from Machine Elements in Mechanical Design, Robert L. Mott Animation © Motorola, Inc.
Synchronous AC motor
The synchronous motor operates at exactly synchronous speed with no
slip. The rotor is of a constant polarity (either a permanent magnet or an
energized electromagnet) and the windings of the stator are wrapped in
such a way as to produce a rotating magnetic field. Such motors provide
very little torque at zero speed, and thus need some kind of separate
starting apparatus. Often a squirrel-cage rotor is built into the main rotor.
When the motor reaches a few percent of synchronous speed, the rotor
is energized and the squirrel cage becomes ineffective.
Image from Machine Elements in Mechanical Design, Robert L. Mott Animation © Motorola, Inc.
Part 1
Introduction
Protection objectives
Insulation faults 30 %
Faulty protection 5 %
Other causes 19 %
Faulty
protection 5 %
REF/REM
REF/REM54x
54x
REM
REM610
610
SPAM
SPAM150C
150C
REX
REX521-
521-H07
H07
Definitions
Thermal Protection
Developed Dissipated
heat heat
∝ I2R ∝T
KK ==constant
constant
Load
ee ==2.7183
2.7183(Neper)
(Neper)
tt ==time
time
t ττ ==time
timeconstant
constant
II ==highest
highestphase
phasecurrent
current
Θ IFLC
I
FLC
==Full Load Current
Full Load Current
t
Motor Thermal Behaviour
Load
Low load
Time
Time
“Thermal” Protections
Part 3.0
10000
10
1
1 2 3 4 5 6 7
10
1
1 2 3 4 5 6 7
1000
Time in sec.
HOT motor
10
Locked rotor limit
1
1 2 3 4 5 6 7
Example 1
Squirrel
Squirrelcage
cage
motor
motorHXR
HXR500
500
••900
900kW
kW
••33kV
kV
••200
200AA
••1492
1492rpm
rpm
Example 2
Protection consideration
100%
Margin
Consumption of
a single start-up
θinh
time
Restart Inhibition level
start − up time
consumptio n = × 100%
trip time
Setting considerations
Should be higher than the thermal level of the motor
which has been running for a long time with full load
Should give enough time to reduce the load
Generally, prior alarm level is set to 80 .. 95 % of the trip level
Undesirable alarms?
At motor restart (compare alarm level to restart-inhibit margin)
At relay power-on
Relay has no memory of the situation before power-off, therefore a
hot (warm) motor condition is assumed. For example SPAM 150C
begins from 74% after power-on.
Part 3.1
% Thermal capacity
100
ΘA ΘA
80
ΘB
ΘB
60 I > IΘ I < IΘ
80 %
9
70 % 7
60 % 6
Stator
stator and rotor
× IN
50 % 5
40 % 4
30 % 3
10 %
Rotor
2
Consecutive Starts
General
Supplementary & Backup protection to the thermal overload
Limits the number of consecutive starts ⇒ protection against
cumulative thermal stress caused by the starts
Settings
The inhibit level
Σtsi = (n-1) × ts +10%
where n = number of allowed start-ups
ts = starting time (in seconds)
Countdown rate
ΔΣts = ts / Δt
where ts = starting time (in seconds)
Δt = count time for one start-up (in hours)
Start-Up Supervision
= Locked Rotor Protection
I>
1000
Time in sec.
100
t>
10
1
1 2 3 4 5 10
1000
Time in sec.
Max permitted
100 I2×t locked rotor time
10
1
1 2 3 4 5 10
1000
Time in sec.
100
Max permitted
locked rotor time
10
1
1 2 3 4 5 10
1000 Stall
Time in sec.
I2×t
100
Max permitted
locked rotor time
10
1
1 2 3 4 5 10
Temperature Protection
Short-Circuit Protection
Doubling effect
I>> setting can be set for automatic doubling during a motor
start-up. Setting is selected 75% - 90% of start-up current
⇒ High-set Overcurrent functions as a fast run-time stall protection
Phase current
I>> setting
time
Start-up Run-time STALL
Part 8
Unbalance Protection
Unbalance protection
Unbalance Protection
L1 L1
L1+L3
-(L1+L3)
L3 L3
Unbalance Protection
175
K=
(Istart ) 2
where Istart = start-up current of the motor x FLC
Unbalance protection, Min-Max Principle
IL max − IL min
ΔI = × 100%
IL max
If the phase currents are less than the FLC
IL max − IL min
ΔI = × 100%
IFLC
ΔΙ and negative phase sequence (NPS) are not the same!
Part 9
Loss of Load
Undercurrent Protection
Part 10
Apparent E/F
current will occur
at startup due to
the saturation of
CT when sum
connection of CTs
is used.
Miscellaneous
8 Disturbance recording
Veikko Lehesvuo Disturbance
Recording
IRF
STEP
RESET
TRIGGED/READY
1516
SPCR 8C27
Analog Digital
signal S/H ADC output
Measured signal
Quantization
Basics of measuring technology
Simultaneously Multiplexed
sampling sampling
anti-aliasing filter
frequency
Fs/2 Fs
Original signal
Recorded data
Basics of measuring technology
Triggering
Triggering
Manual triggering
Periodic triggering