C 300 Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 116

C300 series of Inverter

Non-sensor current vector-control

Manual

SHENZHEN SUNFAR ELECTRIC TECHNOLOGIES CO.,LTD


PREFACE

PREFACE
Thank you very much for choosing C300 series of sensorless vector low-power
inverter.

This manual provides guidance of using the inverter safely and carefully, containing
introduction of installation, wiring, parameters list, routine maintenance, operating
rules and cautions, etc.

In order to make good use of the inverter properly and safely, please read this
manual thoroughly before using. It may lead to abnormal operation and failure,
reduce using life, even damage the equipment and cause personal injury if you use
it wrongly.

This manual is attachment together with the inverter. Please keep it well and it
would be available to engineering and installation personnel, repairing and
maintaining during the product functioning period. SUNFAR has the right to modify
and ameliorate products, data and dimensions without notice, so this manual is
updated and all the contents in this manual are subject to change without any
notice.

Notice of Using:
C300 is Sensorless vector low-power inverter. Under the operation mode of vector
controlling, the inverter carry out the semi-closed-loop control of electricity, while if
you use the motor that its capacity is lower than the inverter itself, please input the
motor Nameplate parameter [F1.15]~[F1.18] again.

SHENZHEN SUNFAR ELECTRIC TECHNOLOGIES CO., Ltd.

C300 series of non-sensor current vector-control inverter manual


Table of Contents 1

Table of Contents
1 INTRODUCTION …………………………………………………………………11
1.1 Model explanation ………………………………………………………….. 1
1.2 Appearance description …………………………………………………… 2
1.3 Model of inverter……………………………………………………………… 3
1.4 Specifications……………………………………………………………….. 3
2 INSTALLATION GUIDELINES………………………………………………. 6
2.1 Environmental requirements ……………………………………………… 5 6
2.2 Installation dimension of inverter ………………………………………………
7
3 WIRING PROCEDURE……………………………………………………7 8
3.1 Precautions …………………………………………………………………7 8
3.2 Wiring of external components ………………………………………………9
3.3 Basic wiring ……………………………………………………………………10
3.4 Terminal of main circuit …………………………………………………… 11
3.5 Terminal of Control circuit ………………………………………………… 12
3.6 Wiring of RS485 interface and
remote panel interface………………………………………………………….
13
4 PANEL OPERATIONS……………………………………………………………14
4.1Panel functions……………………………………………………………… 14
4.2 Panel operation ……………………………………………………………… 15
4.3 State monitor parameter ……………………………………………………….
16
4.4 Operations …………………………………………………………………….17
5 PARAMETERS LIST………………………………………………………………19
6 DESCRIPTION OF SPECIFIC FUNCTIONS …………………………………
39
6.1 Basic operation parameter unit ………………………………………………39
6.2 Primary application of parameter unit……………………………………….45
6.3 Analog I/O parameter unit ………………………………………………… 51
6.4 Digital O/I parameter unit ……………………………………………….… 54
6.5 Auxiliary running parameter unit ………………………………………….. 58
6.6 Multi-speed running parameter unit ………………………………………. 64
6.7 Advanced running parameter unit ……………………………………… 67

C300 series of non-sensor current vector-control inverter manual


2 Table of Contents

6.8 Wobble freq. running parameter unit ………………………………………74 70


6.9 PID control parameter unit …………………………………………………78 72
78
6.10 Communication function parameter units ………………………………82 76
82
6.11 Special function parameter unit ………………………………………… 83 77
83
7 FAULT DIAGNOSIS AND COUNTERMEASURES……………………… 86
80
86
7.1 Protective functions and countermeasures…………………………… 86 80
86
7.2 Fault record inquiry ……………………………………………………… 89 82
89
7.3 Reset ……………………………………………………………………… 89 83
89
8 MAINTENANCE …………………………………………………………… 94 84
94
8.1 Daily Maintenance ……………………………………………………… 94 84
94
8.2 Damageable parts maintenance ………………………………………… 95 85
95
8.3 Storage……………………………………………………………………… 95 85
95
8.4 After sale services ………………………………………………………… 96 86
96
9 USAGE EXAMPLE …………………………………………………………… 97 87
97
9.1 Panel on-off control, Panel potentiometer
setting frequency and V/F control methods………………………… 97
87
97
9.2 External control mode, external voltage
setting frequency and V/F control……………………………………… 97 88
97
9.3 Multi-speed running, external control mode
and V/F control …………………………………………………………… 99 89
99
9.4 Panel on-off control,Panel potentiometer setting
frequency and linkage control with inverters …………………………… 99
90
99
9.5 PLC controls the startup and stop of inverter 101
101
and 3-speed operation…………………………………………………. 113 91
113
AppendixⅠ RS485 COMMUNICATION PROTOCOL………………… 113 113
94
AppendixⅡ OPTIONS ………………………………………………………… 114 106
114
1. Operation panel ………………………………………………………… 106
2. Brake resistance …………………………………………………………107

C300 series of non-sensor current vector-control inverter manual


PRECAUTIONS 1

— PRECAUTIONS
In order to use the inverter properly and safely, please read this manual carefully
before using. And you should follow the requirements of this manual to move, install,
run, operate and repair the inverter.

1. Opening
Ⅰ Please check any damage that may have occurred during transportation.
Ⅱ Please check whether the nameplate data of inverter is in accordance with
your order, if anything wrong, please contact supplier immediately.
Our product is manufactured, packed and transported in the strict quality system. But
in case there is any error, please contact with our company or local agent, we will
solve the problem as quickly as possible.

z Inverter’s nameplate data

TYPE: C300-4T0015 Inverter's model


SOURCE: 3PH 380V 50/60Hz Rated Parameters
OUTPUT: 2.4KVA 3.7A Rated output capacity and current
SERIAL No.: 0123456789 Product series No.
Bar code

Fig-1 Nameplate

2. Safety regulations
There are four kinds of symbols being related with cautions as follows:

Danger: If user does not operate according to requirements, it will lead


to death, grievous bodily harm or severe property loss.

Warning: If user does not operate according to requirements, it will


lead to injury or damage of inverter.

C300 series of non-sensor current vector-control inverter manual


2 PRECAUTIONS

This symbol will hint some useful information.

This symbol will hint some items that need to be noticed in operation.

2.1 Installing
2.1.1. Do not put the inverter on the combustible material.
2.1.2. C300 series inverter can’t install in the explosive ambient.
2.1.3. Do not drop other material into the inverter.

It is forbidden to disassemble and refit the inverter.

2.2 Wiring
2.2.1. It must be operated by professional worker when wiring.
2.2.2. Please be sure to turn off the power supply at least 10 min before wiring.
2.2.3. Inverter and motor must be grounded correctly.
2.2.4. Be sure to wire or inspect the inverter after power-off at least10 minutes.
2.2.5. Electron components are sensitive about static electricity, so do not drop
other material in inverter or touch the main circuit.

It is forbidden to connect an AC power supply with the U, V and W output


terminals directly

2.3 Maintenance

1. Do not touch the radiator after power-off at least 10 minutes.


2. The earth terminal of inverter must be connected to ground reliably.

C300 series of non-sensor current vector-control inverter manual


PRECAUTIONS 3

3. Attention Notes:
3.1. Be sure to install the inverter in a well-ventilated ambient.
3.2. The temperature at variable-frequency will be higher than at line-frequency,
which is normal phenomenon.
3.3. The ordinary motor cannot run in the low speed for a long time, so user
should select the special motor for inverter or reduce the motor load under
the low speed.
3.4. When the altitude is over 1000m, the inverter will be valid to decrease the
rated current, and the rated current will decrease 10% when the attitude is
increased 1500m.

Be sure not to connect the output terminals of inverter with the filter capacitors
and other surge absorbers.

4 Dispose:
When you dispose inverter and its parts, please pay attention to:
Capacitor: The capacitors in inverter may explode when they are burned.
Plastic: Poisonous gas may be generated when the front panel is burned, please
pay attention to the waste gas when the plastic parts are burned.
Method: Please dispose inverter as industry rubbish.

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 1

1. INTRODUCTION
1.1 Model Explanation
``

C300 - 4 T 0015

Applied Motor
Product capacity (KW)
Sensorless 0002 0.2
C300 Vector 0004 0.4
Low-power 0007 0.75
Drive ﹕ ﹕
﹕ ﹕
0450 45
0550 55

Voltage class
Power supply
2 220V
T 3-phase
4 380V
S 1-phase

1.2 Appearance description


1.2.1 Appearance of model I

Operation panel

Upper cover

RS485 interface

Remote panel interface


Cable inlet of control circuit

Cable inlet of main circuit

Mounting hole

It is fit for:C300-2S0002~C300-2S0007/C300-4T0004~C300-4T0007

C300 series of non-sensor current vector-control inverter manual


2 SUNFAR C300

1.2.2 Appearance of model II

Operation panel

Upper cover
Right cover
RS485 interface
Remote panel interface

Cable inlet of control circuit

Lower cover

Cable inlet of main circuit

Mounting hole

It is fit for:C300-2S0015~C300-2S0022/C300-4T0015~C300-4T0037

1.3 Model Of Inverter


Rated capacity Rated output
Model Applied motor power (KW)
(KVA) current (A)
C300-2S0002 0.69 1.8 0.25
C300-2S0004 1.1 3.0 0.4
C300-2S0007 1.9 5.0 0.75
C300-2S0015 2.9 7.5 1.5
C300-2S0022 3.8 10.0 2.2
C300-4T0004 1.3 2.0 0.4
C300-4T0007 1.5 2.3 0.75
C300-4T0015 2.4 3.7 1.5
C300-4T0022 3.6 5.5 2.2
C300-4T0037 5.6 8.5 3.7

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 3

1.4 Specifications
Three-phase ( 4T**** ) Single-phase(2S****)220V;
Rated voltage and freq.
380V;50/60Hz 50/60Hz
Input
Permissible voltage Three-phase(4T****) Single-phase(2S****)
fluctuation 320V ~ 460V 170V ~ 270V
Three-phase (4T****) Single-phase ( 2S**** )
Voltage
0 ~ 380V 0~220V
Output Frequency 0~600Hz
110% rated current for long-term; 150% rated
Over-loading Endurance
current for 1min; 180% rated current for 2s
Control System V/F control、Sensorless current vector control
Freq. Analog Input 0.1% of maximum output freq.
Control
Resolution Digital Input 0.01Hz

Analog Input Within 0.2% of maximum output freq.


Freq.
Precision
Digital Input Within 0.01% of setting freq.

Reference freq. can be discretionally set between 5


and 600Hz. And V/F curve with multi-mode can be
V/F curve discretionally set. There are also three curves
provided, Constant torque curve, Dec torque curve 1
and Dec torque curve 2.

Manual torque boost can be set between 0 and


V/F control
20 percent;
Control Torque boost
Automatic torque boost can be set according to
Charac- output current.
teristics
Automatic It will determine automatically the current and voltage of
current/voltage stator of motor, which will be controlled within the
limiting allowable range.

Automatically adjust the ration of voltage to frequency


Volt/Freq
according to the parameter of motor and unique
characteristics
arithmetic.

Sensorless Torque While freq equals 1, the torque is 150% rated torque. The
characteristics lasting accuracy is 0.1%
Current
vector Motor’s
The motor’s parameter self-detection can finish in
parameter
control static state mode.
self-detection

Current / voltage Current close-circuit control can avoid the


Restraint current attack.

C300 series of non-sensor current vector-control inverter manual


4 SUNFAR C300

It is special for the users with lower power supply and


Under voltage inhibit voltage fluctuate frequently, even the voltage is lower than
feature In running Permissible voltage, and the system will maintain the
longer running time.

Up to 8 stages of programmable multi-speed control, 6


Multi-speed selection kinds of running mode Wobble freq. function is composed
and wobble freq. running of preset freq., center freq. adjusted and saving state and
restart when inverter just had power off.

PID control Embedded PID controller can preset freq. Standard


positioning RS485 Manifoldcommunication protocols can
RS485 communication be selected, having synchronous linkage function.

Analog input DC voltage 0~10V,DC current 0~20mA


Freq.
Setting It can be set by Operation panel, RS485, UP/DW terminal
Digital input and combination setting.

One OC output and one faults electric delay out(TA,TB,


OC output
Output TC),16 options can be selected.
Signal One output 0~10V voltage and upper/lower limit can be
Analog output set by user
Typical
To get the most stable running effect, user can select
Functions Voltage stabilizing running
static stabilizing voltage, dynamics stabilizing voltage
Automatically
and non-stabilizing voltage.
Acceleration/deceleration
0.1 to 6000 seconds, S-curve or linear
Time setting
Regenerative
braking 75% above

Brake Start and stop can be selected respectively, action freq.


DC braking is form 0 to 50.0Hz, and action time is form 1 to 20.0s.
Continuous action is also optional.

To use the function of Smooth restarting and stop


Determine speed and restart restarting during motor works.
Embedded one counter, which will help the integration
Counter of system

Setting of upper limit freq. and lower limit freq., freq


hopping running, Reversal running limit, slip freq.
Operation functions compensate, RS485 communication, frequency
Acc/Dec control, self-recovery running, ect.

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 5

Out freq., Out current, Out voltage, Motor speed,


Operation Status Setting freq., Temperature of Module, PID setting,
Feedback value, Analog O/I, ect.
Display
Recently six faults recorded, output freq., setting freq.,
Fault details output current, output voltage, DC voltage and module
temperature

Over current, over voltage, under current, under


voltage, thermal relay, overheating, short circuit, out
Protection/Warning Functions voltage would be short of the phase, The parameters
of motor is abnormal, Main contactor can’t attract,
Internal memory faults, ect.

Ambient temperature: -10℃~+50℃


Ambient humidity: under 90%
Environmental Conditions Ambient atmosphere: indoors (non-corrosive,
non-inflammable, non-oil, non-fog etc.)
Altitude is lower than 1000m

Enclosure rating is IP20


Configuration
Cooling system is in the cooling mode.

Installation Hanging

C300 series of non-sensor current vector-control inverter manual


6 SUNFAR C300

2. INSTALLATION GUIDELINES

2.1 Environmental Requirements


1. Be sure to install the inverter in a well-ventilated room.
2. Ambient temperature is from -10℃ to 40℃.
3. Please avoid putting the inverter in a high temperature and moist
location. The humidity is less than 90% and non-condensing.
4. Keep away from combustible, explosive materials and caustic gas or
liquid.
5. No dust, floating fiber and metal particles.
6. The inverter must be installed in a firm and no vibration location.
7. The installation plane should be solid and not vibrant.

If users demand any special requirements of installation, please contact us firstly.

C300 series of inverter is in hanging model, so it should be installed in vertical way.


In order to ensure the air circulation around the inverter to be cool, there should be
enough space around the inverter (Fig. 2-1-A). Add the air deflector when apply the
up-down installation (Fig. 2-1-B).
Above 120mm

Fan ventilation

Inverter

Above 50mm Above 5mm Air flow


clapboard

Inverter
Above 120mm

Fig2-1-A Interval distance Fig2-1-B Multi-inverter Installation

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 7

2.2 Installation Dimension of Inverter


W
D W1
It is fit for:
C300-2S0002~C300-2S0007
C300-4T0004~C300-4T0007

H1
H
Shown as Fig. 2-2-A。

Fig2-2-A Dimension of model Ⅰ

W
D
W1

It is fit for:
C300-2S0015~C300-2S0022
C300-4T0015~C300-4T0037
H1
H
CAUTION
1. Refer to the instruction manual before installation
and operation.

Shown as Fig. 2-2-B。


2. DO not connect AC power to output terminals
UVW.
3. Isolate from supply and wait 10 minutes before
removing this cover.
4. Securely ground(earth) the equipment.

Fig2-2-B Dimension of modelⅡ

The following table shows the Installation Dimension of C300.

Inverter model Inverter model W1 W H1 H D Screw


(3-phase 400V) (1-phase 220V) (mm) (mm) (mm) (mm) (mm) spec

-- C300-2S0002
C300-4T0004 C300-2S0004 88 98 165 178 140 M4
C300-4T0007 C300-2S0007
C300-4T0015 C300-2S0015
C300-4T0022 C300-2S0022 95 105 190 200 160 M4
C300-4T0037 --

C300 series of non-sensor current vector-control inverter manual


8 SUNFAR C300

3. WIRING PROCEDURE
3.1 Precautions:
3.1.1. Installing a middle breaker between inverter and power supply in order to
avoid enlarging the accident.
3.1.2. Reducing the electromagnetic interference (EMI), please connect surge
absorber to the coils of electromagnetic contactors, relays, etc.
3.1.3. Frequency setting terminals VC、CC,Instrument circuit(AVO), etc., these
analog signal wires should be over 0.3mm2 shield wire. Shield layer is
connected with earth terminal GND and the length of wire should be less
than 30m.
3.1.4. Wire of relay input and output circuit (X1 ~ X4、OC、RST) must be selected
over 0.75mm2 shield wire. Shield layer should be connected to earth
terminal GND and the length of wire should be shorter than 50m.
3.1.5. Separating the main circuit wire from the signal/process circuit wiring,
paralleled wiring should be at a distance of over 10cm and crossed wiring
should be vertical with each other.
3.1.6. The wire must be less than 30m between motor and inverter. When the
length of wire is over 30m, the carrier frequency of inverter should be
reduced properly.
3.1.7. All of leading wires should be tightened with the terminal adequately to
ensure well-contact.
3.1.8. Compressive resistance of all the wire should match with the voltage grade
of inverter.

It is not allowed that U、V、W of inverter connect with the surge absorber capacitor
or other surge absorber equipment and shown as following Fig..

Motor
U
Inverter V M
W

RC absorb device

Fig.3-1 It is prohibited to connect RC absorb apparatus

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 9

3.2 Wiring of External Components

AC Power

P+ PB
R / L1 U

S / L2 V
CAUT ION
1 . Re fer to the instructio n manu al before in stallation

T
a nd opera tion.

W
2. D O not conne ct AC pow er to output term inals
UVW .
3 . Isolate from supp ly an d wa it 10 minutes be fore
removing this cover.
4. Securely ground(earth ) the equipm ent.

Circuit AC Electric
Air Breaker Switch Reactor
Breaker C300 Motor
Fig.3-2 wiring

z Power Supply
It is according to the rated input power specifications in manual.

z Air-break switch
1. When the inverter is in maintenance or leave-unused, the air-break switch should
isolate the inverter from power supply.
2. Input side of inverter takes place the fault of short-circuits or low-voltage, the
air-break would take the protection.

z Contactor
Control the power-on or power-off of inverter expediently.

z AC electric reactor
1. Improve the power factor.
2. Reduce the harmonic wave input for the electric network.
3. Weaken the imbalance effect on 3-phase power voltage.

z Brake resistor
In situation of the regenerative braking, avoiding bringing voltage too highly.

C300 series of non-sensor current vector-control inverter manual


10 SUNFAR C300

Recommending specification of commanded equipment is shown as following table.


Wire spec Magnetic
Air-break
Model Applied Motor(KW) (Main circuit) contactor
(A)
(mm2) (A)
C300-2S0002 0.25 2.5 10 6
C300-2S0004 0.4 2.5 10 6
C300-2S0007 0.75 4 16 12
C300-2S0015 1.5 4 20 18
C300-2S0022 2.2 6 32 18
C300-4T0004 0.4 2.5 10 6
C300-4T0007 0.75 2.5 10 6
C300-4T0015 1.5 2.5 16 12
C300-4T0022 2.2 4 16 12
C300-4T0037 3.7 4 20 18

3.3 Basic wiring


Three-phase Breaker
Motor
× R U
Three-phase × V M
S
~
× T W
Power supply
E
Earth
X1 Ta
X2 Tb Fault alarm output
PLC input terminal X3 Tc
X4

GND P+

E PB External brake resistor

24V Auxiliary DC power


Fault Reset RST
FWD Order FWD
AVO Voltmeter(0~10V)
REV Order REV
GND
GND
E
E
Open-circuit
VS Collector output
OC
0 ~ 10 V Frequency set VC

0 ~ 20mA Frequency set CC GND

GND
E
E

Fig.3-3 C300 series of inverter basic wiring


C300 series of non-sensor current vector-control inverter manual
SUNFAR C300 11

3.4 Terminal of main circuit


(1)I model(It is fit for C300-4T0004~C300-4T0037)
P+ PB R S T U V W E

It is fit for 0.4KW~0.75KW

Earth
DC Brake Resistance
Motor
Three-phase Power

P- P+ PB R S T U V W E

It is fit for 1.5KW~3.7KW

Earth
DC Brake Resistance Motor
Three-phase Power

Description of terminal:

Terminal Function Terminal Function

P- Negative Terminal of DC P+ Positive Terminal of DC

DC brake resistance can be Connecting three-phase AC


PB R、S、T
connected between P and PB. power supply

Connecting three-phase AC
U、V、W E Earth Terminal
motor

(2)II model(It is fit for C300-2S0002~C300-2S0022)

P+ PB L1 L2 U V W E

It is fit for 0.25KW~0.75KW

Earth
DC Brake Resistance
Motor
AC 220V Power

P- P+ PB L1 L2 U V W E

It is fit for 1.5KW~2.2KW

Earth
DC Brake Resistance Motor
AC 220V Power

C300 series of non-sensor current vector-control inverter manual


12 SUNFAR C300

Description of terminal:

Terminal Function Terminal Function


P- Negative Terminal of DC P+ Positive Terminal of DC
Negative
PB DC brake resistance can be L1、L2 Connecting 1-phase 220V
connected between P and PB. AC Power
U、V、W Connecting 220V AC motor E Earth Terminal

3.5 Terminal of Control circuit


(1) Terminal of Control circuit fig:

TA TB TC X1 X2 X3 X4 GND FWDRST REV OC 24V VS VC CC AVO

(2) Description of control-circuit terminal:


Type Terminal Function Notes
VS It provides +10V/10mA

Analog VC Frequency setting voltage signal input terminal 0~10V


Input
CC Frequency setting current signal input terminal 0~20mA
GND Common terminal of analog input signal
X1 Multi-function input terminal 1 The detailed function of
multi-function Input terminal
X2 Multi-function input terminal 2 is by setting parameter
X3 Multi-function input terminal 3 F3.0~F3.5, The terminal is
valid while being closed
X4 Multi-function input terminal 4 with GND terminal.
Control RST Fault reset input terminal
Terminal
FWD FWD control command terminal Those terminals are valid
when being connected with
REV REV control command terminal GND.And running direction
GND Common terminal of control is controlled by FWD-GND
state
It provides +24V/50mA power and is grounded
24V
by GND.
PLC voltage signal input terminal. It is set by
Analog AVO F2.9 and allowed to connect with external voltage signal output
voltmeter. 0~10V/1mA
Output
GND Common terminal of AVO
OC The maximum load-current
OC PLC open-circuit collector output is set by F3.4 is50mA .And the maximum
Output withstand voltage is 24V.
TA General , TA-TB is connected,TA-TC is
PLC Capacity:AC 250V 1A
TB unconnected when TA-TB is unconnected
output and TA-TC is connected,F3.8 is valid Resistive load
TC

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 13

3.6 Wiring of RS485 interface and remote panel interface

(1) RS485 interface wiring model,


as fig on the right:
(2)External keypad interface and RS485 -(B) +(A)
interface are connected by 6P crystal
pin line.

3.6.1 Model I
It is fit for:C300-2S0002~C300-2S0007/C300-4T0004~C300-4T0007

External keypad RS485 interface


interface

Fig. 3-4-A model Ⅰ


3.6.2Model II
It is fit for:C300-2S0015~C300-2S0022/C300-4T0015~C300-4T0037

Right cover
RS485 interface
External keypad
interface

Fig.3-4-B model Ⅱ

C300 series of non-sensor current vector-control inverter manual


14 SUNFAR C300

4. PANEL OPERATIONS

Mode indicate light

LED
Return
Unit

Increasing Switch
Potentiometer
Decreasing
Run、 Stop、 Reset

Set

4.1. Keypad functions


Item Function
LED It displays current state and setting parameter.
A、Hz、V The corresponding unit of current display.
RUN Operation indicator light. The inverter is running and U, V and W output voltage.

Data modify key. It is used for modifying the function code and parameter.
In state monitor mode, if F0.1 is 0, press this key will modify the frequency
instruction.

Return key. Press this key in normal monitor state to enter query mode of not
normal monitor state /monitor parameters to check running state. In any state,
press this key to return the upper state.

Set key. It affirms current state and parameter, and goes to the next function list.

Run/Stop key. When F0.4 is 000#, this key is valid for panel control. When the
inverter is stop and press this key, the inverter will run. When the inverter is stop
and press this key, the inverter will stop.
If inverter occur fault, press this key to reset it.

Shift key. When modify data ,Press the key to modify the digital bit, the
modification bit will be displayed blink.

Panel potentiometer. Running frequency is set by potentiometer on the panel


Potentiometer turning left will reduce running frequency, potentiometer turning
right will increase running frequency.

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 15

4.2. Panel operation


Normal Monitor State Display:45.00 Output freq.
(1)State parameters enquiries (eg.)
Return

State Parameter Inquiry Display:d.0 Monitor code

Return

State Parameter Inquiry Display:d.2 Monitor code

Parameter Inquiry Display:383 Output voltage

Parameter Edit Display:F0.0 Monitor code

Normal Monitor State Display:45.00 Output freq.


(2)Parameter enquiries

and edits (eg.) Parameter Inquiry Display:F0.0 Function code Continue Edit
or Return
Give up
Edit
Give up
Edit

Parameter Inquiry Display:F0.2 Function code

Parameter Inquiry Display:45.00 Parameter data

Parameter Edit Display:50.00 Parameter data

Parameter Storage Display:F 0.2 Function code

C300 series of non-sensor current vector-control inverter manual


16 SUNFAR C300

4.3 List of State monitor parameter


Monitor Code Content Unit
d-0 Current output frequent Hz
d-1 Current output current (Valid) A
d-2 Current output voltage (Valid) V
d-3 Rotational speed of motor Rpm
d-4 DC bus voltage V
d-5 Input voltage of inverter V
d-6 Setting freq. Hz
d-7 Count value of Internal counter
d-8 PID setting value
d-9 PID feedback value
d-10 Running linear speed m/s
d-11 Setting linear speed m/s
d-12 Analog input voltage VC V
d-13 Reserved
d-14 Analog input current CC mA
d-15 Reserved
d-16 State of input terminal
d-17 Temperature of module ºC
d-18 Analog output AVO
d-19 Reserved
d-20 Magnetization current A

d-21 Magnetization current setting A

d-22 Torque current A

d-23 Torque current setting A

d-24 Operation frequency Hz


d-25 Reserved
d-26 First fault record
d-27 Second fault record
d-28 Third fault record
d-29 Fourth fault record
d-30 Fifth fault record

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 17

d-31 Sixth fault record


d-32 Output frequency of last fault Hz

d-33 Setting frequency of last fault Hz


d-34 Output current of last fault A
d-35 Output voltage of last fault V

d-36 DC voltage of last fault V


d-37 Temperature of module of last fault ºC

4.4 Operations
4.4.1. Initialization
(1)Frequency input channel / mode selection([F0.1])
Initialization of inverter is different according to different model. If [F0.0] is 0, the
frequency of inverter is set by keypad.
(2)Operation channel selection([F0.4])
Initialization of inverter is different according to different model. If F0.4 is 00#0, start
and stop of inverter is controlled by key.

4.4.2. Simply operation

It is forbidden to connect Three-phase power to output terminal U, V and W directly.

Three-phase
Breaker
Motor
× R U
Power supply × S V M
× T W
E

Earth

Fig.4-1 simply running

C300 series of non-sensor current vector-control inverter manual


18 SUNFAR C300

① Please follow fig 4-1 to connect.


② Be sure that the wiring is correctly, then turn the power on, the inverter will
display “P.oFF” and”0” step by step.
③ Select inverter’s control mode([F0.0]=0,V/F method;[F0.0]=1,Vector control);
④ Be sure that F0.1 is 0.
⑤ Please set parameters [F1.3] and [F1.4], according to the nameplate parameters
of applied motor..If it is controlled by vector, using parameters[F1.15]~[F1.18] to set.
⑥ Please press key to start inverter, then the inverter will display 0.0Hz.
⑦ Please press upper key on the key to increase input frequency and motor
will run.
⑧ Please observe the motor whether it runs normally or not. If abnormal, please stop

running at once and turn off the power, and find out the reason, then restart.;

⑨ Press the key on the key to decrease the setting frequency.

⑩Press the key to stop running and turn the power supply off.

Carrier wave frequency is fixed value between 1.5 and 12 KHz. If motor does not
take any load, it will be a slight oscillate. So please decrease setting value of
F0.16.

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 19

5. PARAMETERS LIST
★ means that this parameter can not be changed during operation.
▲ means that this parameter is related to the inverter’s model.
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
F0. 0 Control methods 0:V/F method; 1:Vector control 1 1 ★
0:Frequency setting by operation panel
1:UP/DW Acc and Dec control
2:RS485 interface
Frequency input channel 3:Panel potentiometer
F0. 1 4:External voltage signal VC(0V~10V) 1 0
/ mode selection
5:External current signal CC(0~20mA)
6:Combination setting
7:External terminals
F0. 2 Frequency digital setting 0.00 ~ the upper limit frequency 0.01 0

Basic operation parameter unit


The first part of LED(form right to left):
0 : Setting freq. will save after power
down
1:Setting freq. will not save after power
Auxiliary control down
The second part of LED:
F0. 3 of freq. digital 0:Setting freq. is keep when stopping 1 0000
setting 1:Setting freq. will save in F0.2 when
stopping
2:Setting freq. isclear when stopping
The third and fourth part of LED(form
right to left):Reserved
The first part of LED (form right to left):
0:Panel control
1:External terminals
2:RS485 interface
Operation The second part ofLED:Function of key
F0. 4 Channel selection STOP 1 0000
0:It is valid for panel control.
1:It is valid for all kinds of control
method.
The third and fourth part of LED(form
right to left):Reserved

C300 series of non-sensor current vector-control inverter manual


20 SUNFAR C300
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
Combination methods 0:Two-line mode 1
F0.5 of running the command of 1:Two-line mode 2 1 0 ★
terminals 2:Three-line mode
The first part of LED (form right to left):
0:Running direction is consistent with
setting
direction
1:Running direction is opposite to setting
F0.6 Steering control direction 1 0000
The second part of LED:
0:Prevention REV is valid
1:Prevention REV is invalid

Basic operation parameter unit


The third and fourth part of LED(form
right to left):Reserved
F0.7 The lower limit frequency 0.0 Hz~ [F0.8] 0.01 0.0
F0.8 The upper limit frequency [F0.7] ~ 400.00Hz 0.01 50.00
F0.9 Reserved
F0.10 Acc time 1 0.1 ~ 6000 Sec/Min 0.1 ▲
F0. 11 Dec time 1 0.1 ~ 6000 Sec/Min 0.1 ▲
The first part of LED (form right to left):
0:Beeline 1:Scurve
The second part of LED:
0:Output freq. will be modified according
to Acc/Dec time.
Characteristics parameters 1:Output freq. will be automatically
F0. 12 1 0000
of Acc and Dec modified according to lode.
The third part ofLED:Unit of Acc/Dec
time
0:Sec 1:Min
The third and fourth part of LED:
Reserved

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 21
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
Acc/Dec initial section of
F0. 13 10 .0~ 50.0 (%) 0.1 20.0 ★
S curve
Acc/Dec ascend/decline
F0. 14 10.0 ~ 80.0 (%) 0.01 60.0 ★
section of S curve
F0. 15 Reserved
F0. 16 Carrier wave frequency 1.5~ 12.0 KHz 0.1 6.0*
The first part of LED (form right to left):

Basic operation parameter unit


Reserved
The second part of LED (form right to
left):
0:The relation between out current and
Carrier wave is off.
1:The relation between out current and
Carrier wave is on.
The third part of LED (form right to left):
F0. 17 Carrier wave characteristics 1 1110
0:The relation between module temp
and Carrier wave is off.
1:The relation between module temp
and Carrier wave is on.
The third part of LED (form right to left):
0:The relation between out frequent and
Carrier wave is off.
1:The relation between out frequent and
Carrier wave is on.
1:Forbid to modify all parameter, except
F0.2 and F0.18
F0. 18 Parameter write-protect 1 0
2:Forbid to modify all parameter, except
F0.18
Type of V/F Curve
0:Constant torque curve
paramete
Primary

(Parameters [F1.0]~
applied

r unit

1:Low-freq. torque curve 1


F1. 0 [F1.13] is only under the 1 0 ★
2:Low-freq. torque curve 2
control mode
3:V/F user-defined curve
that is [F0.0]=0,valid.)

C300 series of non-sensor current vector-control inverter manual


22 SUNFAR C300
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
F1. 1 Torque Boosting 0.0~20.0(%) 0.1 6.0
F1. 2 Torque boosting pattern 0:Manual 1:Automatic 1 0 ★
F1. 3 Base running frequency 5.00~the upper limit frequency 0.01 50.00
F1. 4 Max outputvoltage 200~500V; 100~250V 1 380V 220V
F1. 5 V/F freq. 3 [F1.7] ~ [F1.3] 0.01 0.0 ★
F1. 6 V/F voltage 3 [F1.8] ~ 100.0(%) 0.1 0.0 ★
F1. 7 V/F freq. 2 [F1.9] ~ [F1.5] 0.01 0.0 ★

Primary applied parameter unit


F1. 8 V/F voltage 2 [F1.10] ~ [F1.6] 0.1 0.0 ★
F1. 9 V/F freq.1 0.0 ~ [F1.7] 0.01 0.0 ★
F1. 10 V/F voltage 1 [F1.1] ~ [F1.8] 0.1 0.0 ★
DC braking current when
F1. 11 0.0 ~ 100.0(%) 0.1 50.0
starting
DC braking time when
F1. 12 0.0 ~ 20.0 S 0.1 0 ★
starting
F1.13 Reserved
F1.14 Compensate for slip freq. 0~150(%) 1 0
Rated voltage of applied
F1.15 200~500V; 100~250V 1 380V 220V
motor
F1.16 Rated freq. of applied motor 5.00~600.00Hz 0.01 50.00 ★
Rated current of applied
F1.17 0.01~300.0A 0.01 ▲ ★
motor
F1.18 Rated rev of applied motor 300~6000RPM 1 ▲ ★
Exciting current of
F1.19 [F0.17]/4~[F1.17]×3/4 0.01 ▲ ★
applied motor

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 23
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
0:Invalid
1:Determine parameters when motor is
Parameters static
F1.20 1 0 ★
self-determination 2 : Determine parameters when motor
runs
3:Both 1 and 2.
The first part of LED (form right to left):
0:Starting pre-excitation is Valid
1:Starting pre-excitation is Invalid
The second part of LED:
Selection of 0:Prepare pre-excitation is valid when
F1.21 1 0001
starting pre-excitation zero frequency

Primary applied parameter unit


1:Prepare pre-excitation is invalid when
zero frequency
The third and fourth part of LED :
Reserved
Pre-excitation of starting
F1.22 0.10~2.00Sec 0.01 0.30 ★
time
The first part of LED (form right to left):
0:Self-adapting rectify of stator
resistance will invalid.
1:Self-adapting rectify of stator
resistance will valid.
The second part of LED
0:Self-adapting
Self-adapting rectify of rectify of excitation current will invalid
F1.23 1 0010
motor parameters 1:Self-adapting
rectify of excitation current will valid.
The third part of LED:
0:Self-adapting ectify of rotor
resistance will invalid.
1:Self-adapting ectify of rotor
resistance will valid.
The fourth part of LED:Reserved

C300 series of non-sensor current vector-control inverter manual


24 SUNFAR C300
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
F1.24 Stator resistance 0.000~20.000 0.0011 ▲ ★

Primary applied parameter


F1.25 Rotor resistance 0.000~20.000 0.0011 ▲ ★
F1.26 Rotor inductance 0.00~600.00(mH) 0.01 ▲ ★
F1.27 Inductance of excitation 0.00~600.00(mH) 0.01 ▲ ★

unit
Leakage inductance
F1.28 0.00~100.00(mH) 0.01 ▲ ★
(coefficient)
Gain of compensation for
F1.29 0.50~1.50 0.01 1.00
speed drop
F1.30 Reserved
F2.0 Input lower limit voltage VC 0.0 ~ [F2.1] 0.1 0.0V
F2.1 Input upper limit voltage VC [F2.0] ~ 10.0V 0.1 5.0 V
F2.2 Input lower limit current CC 0.0mA~ [F2.3] 0.1 4.0

Analog I/O parameter unit


F2.3 Input upper limit current CC [F2.2] ~ 20.0mA 0.1 20.0
Frequency with the min
F2.4 0.0~[F2.5] 0.01 0.00
setting
Frequency with the max
F2.5 [F2.4]~550.0Hz 0.01 50.00
setting
The first part of LED (form right to left):
(VC channel)
0: positive characteristics
1:Negative characteristics
Characteristics selection of
F2.6 The second part of LED:Reserved 1 0000 ★
input channel
The third part of LED:(CC channel)
0: positive characteristics
1:Negative characteristics
The fourth part of LED:Reserved

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 25
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
External freq. set time
F2.7 0.01~1.00Sec 0.01 0.10
constant offiltering
F2.8 Combination setting mode Refer to the explanations about(0~19) 1 0

The first part of LED (form right to left):

Analog I/O parameter unit


AO1output
0:Output freq.
1:Output current
Analog output selection 2:Output voltage
F2.9 (AVO) 3:Rotational speed Of applied motor 1 0000
4:PID setting
5:PID feedback
The second and third and fourth part of
LED:Reserved

The lower limit of analog


F2.10 0.0~[F2.11] 0.1 0.0 V
output AVO
The upper limit of analog
F2.11 [F2.10]~12.0 0.1 10.0V
output AVO
F2.12 Reserved

-- -- -- -- -- --
--

C300 series of non-sensor current vector-control inverter manual


26 SUNFAR C300
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit

0:Control terminal is idle


Function selection of input 1:Multi-speed control terminal 1
F3.0 2:Multi-speed control terminal 2 1 1 ★
terminal 1 (0~25)
3:Multi-speed control terminal 3
4:Wobble freq. is valid
5:State of wobble freq. reset
6:FWD jog control
7:REV jog control
8:Acc& Dec time selection terminal 1

Auxiliary running parameter unit


9:Acc& Dec time selection terminal 2
Function selection of input
F3.1 10:Freq. setting channel selection 1 1 2 ★
terminal 2 (0~25)
11:Freq. setting channel selection 2
12:Freq. setting channel selection 3
13:Freq. is controlled gradually increase
(UP)
14:Freq. is controlled gradually increase
(DW)
15:UP-DW freq. clear
Function selection of input 16:Uncontrolled stop control
F3.2 1 3 ★
terminal 3 (0~25)
17:Fault signal of peripheral equipment
input
18:Three-line mode running control
19:DC braking control
20:Inner counter clear
21:Inner counter timer
22:PLC running valid
Function selection of input 23:PID running valid
F3.3 1 6 ★
terminal 4 (0~25) 24:Reserved
25:PLC state reset after stopping

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 27
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
0:In the running;
1:Frequency reaching;
2:Freq. level detection signal FDT;
3:Over-loading alarm;
4:External fault halt;
F3.4 Output terminal(OC) 5:Output frequency reaches the 1 0
upper-limit;
6:Output frequency reaches the
lower-limit;
7:Running in zero speed;
8:Inverter will stop when under voltage;
9:PLC stage is end of run;

Auxiliary running parameter unit


10:PLC periodic is end of run;
11:Reserved;
12:Setting value of counter arrives;
13:Designated value of counter arrives;
TA, TB and TC of relay 14:Reserved; 1
F3.5 16
contacts(TA、TB、TC) 15:Reserved;
16:Inverter fault;
17:Restrictions on wobble freq. of the
upper and lower limit freq.
18:Reserved;
Frequency reach the
F3.6 0.0~20. 00Hz 0. 01 5.00
checkout amplitude
F3.7 FDT setting 0.0~ the upper limit freq. 0.01 10.00

F3.8 delay time of FDT output 0.0~200.0s 0.1 2.0 ★

F3.9 level of over-loading alarm 50~200(%) 1 110

delay time of
F3.10 0.0~20.0s 0.1 2.0 ★
over-loading alarm
F3.11 Reserved

C300 series of non-sensor current vector-control inverter manual


28 SUNFAR C300
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
0:Routine mode
F4.0 Start mode 1 0 ★
1:Detect speed and restart

F4.1 Start frequency 0.0~10.00Hz 0.01 0.5

F4.2 Start frequency duration 0.0~20.0 S 0.1 0.0 ★

0:Decelerate mode
F4.3 Stop mode 1 0
1:Uncontrolled stop
Initial freq. of DC braking
F4.4 0.0~50.00Hz 0.01 3.00
when stopping

Auxiliary running parameter unit


Waiting time of
F4.5 0.0~5.0 S 0.1 0.1
DC braking when stopping
Action time of DC braking
F4.6 0.0~20.0 S 0.1 0 ★
whenstopping

DC braking current when


F4.7 0.0~100(%) 0.1 50.0
stopping
Running threshold of zero
F4.8 0.0~100.0Hz 0.01 0.0
freq.

F4.9 Return different of zero freq. 0.0~50.00Hz 0.01 1.00

F4.10 Jog frequency 0.0~the upper limit freq. 0.01 10.00

F4.11 Acc torque level 110~200(%) 1 160

F4.12 Braking torque lever 10~150(%) 1 80

Motor over-loading
F4.13 50~110(%) 1 100
protection coefficient

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 29
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
Automatic voltage regulation 0:Invalid 1: Dynamic valid
F4.14 1 2
(AVR) 2:Static valid
F4.15 Reserved
F4.16 Dead time of FWD&REV 0.0~5.0 S 0.1 0.0 ★
F4.17 Acceleration time 2 0.1~6000 s/min 0.1 ▲
F4.18 Deceleration time 2 0.1~6000 s/min 0.1 ▲
F4.19 Acceleration time 3 0.1~6000 s/min 0.1 ▲
F4.20 Deceleration time 3 0.1~6000 s/min 0.1 ▲

Auxiliary running parame


F4.21 Acc time 4/Jog Acc time 0.1~6000 s/min 0.1 ▲
F4.22 Dec time 4/Jog Dec time 0.1~6000 s/min 0.1 ▲
Modified rated of
F4.23 0.01~100.0Hz/Sec 0.01 10.00
UP/DW terminals
Start voltage of
F4.24 600~750V 1 700V
dynamic braking
Action ratio of
F4.25 10~100(%) 1 60%
dynamic braking
The first part of LED:
0:Invalid 1: Valid
The second part of LED:
Restart after power down
F4.26 0:Routine mode 1 0010 ★
setting
1:Detect speed and restart mode
The third and fourth part of LED :
Reserved
Waiting time of restart after
F4.27 0.0~10.0 s 0.1 0.5 ★
power down
F4.28 Reserved

C300 series of non-sensor current vector-control inverter manual


30 SUNFAR C300
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
The first part of
LED(form right to
left):PLC setting
0:PLC is invalid. 1:PLC is valid.
2:PLC is conditional invalid.
The second part of
LED:Simple PLC running mode selection
0:Single loop mode
1:Single loop and stop mode
2:Continuous loop mode
3:Continuous loop and stop mode
F5. 0 Multi-speed running mode 1 0000 ★

Multi-speed running parameter unit


4:Keep the end value
5:Keep the end value and stop mode
The third part of LED
0:Restart from the first stage freq.
1:Restart from running freq. which is
saved before running is break
2:Restart from setting freq. when
running is break.
The fourth part of LED:PLC save state
0:Non-save after power off
1:Save after power off
F5. 1 Multi-speed frequency 1 0.0 ~ the upper limit freq. 0.01 35.00
F5. 2 Multi-speed frequency 2 0.0 ~ the upper limit freq. 0.01 15.00
F5. 3 Multi-speed frequency 3 0.0 ~ the upper limit freq. 0.01 3.00
F5. 4 Multi-speed frequency 4 0.0 ~ the upper limit freq. 0.01 20.00
F5. 5 Multi-speed frequency 5 0.0 ~ the upper limit freq. 0.01 25.00
F5. 6 Multi-speed frequency 6 0.0 ~ the upper limit freq. 0.01 30.00
F5. 7 Multi-speed frequency 7 0.0 ~ the upper limit freq. 0.01 35.00
F5.8 Multi-speed frequency 8 0.0 ~ the upper limit freq. 0.01 40.00

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 31
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
Running time of
F5. 9 0.0~6000 s 0.1 10.0
Multi-speed 1
Running time of
F5. 10 0.0~6000 s 0.1 10.0
Multi-speed 2
Running time of
F5. 11 0.0~6000 s 0.1 10.0
Multi-speed 3
Running time of
F5. 12 0.0~6000 s 0.1 10.0
Multi-speed 4
Running time of
F5. 13 0.0~6000 s 0.1 10.0
Multi-speed 5

Multi-speed running parameter unit


Running time of
F5. 14 0.0~6000 s 0.1 10.0
Multi-speed 6
Running time of
F5.15 0.0~6000 s 0.1 10.0
Multi-speed 7
Running time of
F5.16 0.0~6000 s 0.1 10.0
Multi-speed 8
The first part of LED(form right to left):
0:Stage 1 FWD 1:Stage 1 REV
The second part of LED:
Running direction of PLC 0:Stage 2 FWD 1:Stage 2 REV
F5.17 The third part of LED: 1 0000
multi-speed
0:Stage 3 FWD 1:Stage 3 REV
The fourth part of LED:
0:Stage 4 FWD 1:Stage 4 REV

The first part of LED(form right to left):


0:Stage 5 FWD 1:Stage 5 REV
The second part of LED:
Running direction of PLC 0:Stage 6 FWD 1:Stage 6 REV
F5.18 The third part of LED: 1 0000
multi-speed
0:Stage 7 FWD 1:Stage 7 REV
The fourth part of LED:
0:Stage 8 FWD 1:Stage 8 REV
F5.19 Reserved

C300 series of non-sensor current vector-control inverter manual


32 SUNFAR C300
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
F6.0 Reserved
F6.1 Fault self-recovery time 0,1,2 1 0 ★
Interval time of
F6.2 0.2~20 S 0.1 2.0 ★
fault self-recovery
Final value set up of internal
F6.3 1~60000 1 1 ★
counter
F6.4 Internal timer setup 1~60000 1 1 ★
F6.5 Skip freq. 1 0.0~the upper limit freq. 0.01 0

Advanced running parameter unit


Amplitude accumulation of
F6.6 0.0~5.00Hz 0.01 0
Skip freq. 1
F6.7 Skip freq. 2 0.0~the upper limit freq. 0.01 0
Amplitude accumulation of
F6.8 0.0~5.00Hz 0.01 0
Skip freq. 2
Linear speed
F6.9 0.01~100.0 0.01 1
coefficient setting
Close-loop analog
F6.10 0.01~100.00 0.01 1.00
coefficient setting
Rotator speed
F6.11 0.01~10.00 0.01 1.00
coefficient setting
F6.12 Monitor item selection 1 0~11 1 0
F6.13 Monitor item selection 2 0~11 1 1
F6.14 Query or modify parameters 0 ~ 9999 1 1700

0:Parameter initialization is off.


F6.15 Parameter initialization 1:Parameterinitialization is on. 1 0 ★
2:Clean fault records

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 33
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
F6.16 Copy parameter function 0:Forbid 1:Allow 1 1

Advanced

paramete
running
F6.17 Manufactory password 0~9999 1 1000

r unit
F6.18 User password 0~9999 1 0
F6.19 Reference password 0 ~ 9999 1 ▲
The first part of LED (form right to left)
0:Function of wobble freq. is invalid.
1:Function of wobble freq. is valid.
2:Function of wobble freq. is conditional
valid.
The second part of LED: restart mode
0:Restart according to parameters saved
before stop
1:Restart

Wobble freq. running parameter unit


Wobble freq. The third part of LED:
F7.0 0:The wobble freq. is fixed 1 1000 ★
running mode
1:The wobble freq. is changeable.
The fourth part of
LED: Storage
characteristics of
wobble freq.
0:It will not save the running state of
wobble freq. after power off
1:It will save the running state of wobble
freq. after power off
F7.1 Preset freq. of wobble freq. 0.0~the upper limit freq. 0.01 10.00
F7.2 Waiting time of preset freq. 0.0~6000.0Sec 0.1 0.0 ★
F7.3 Amplitude of wobble freq. 0.0~50.0(%) 0.1 10.0
F7.4 Jumping freq. 0.0~80.0(%) 0.1 10.0
F7.5 Triangular rise time 0.1~1000.0Sec 0.1 10.0
F7.6 Triangular fall time 0.1~1000.0Sec 0.1 10.0
Preset center freq. of 0.0~the upper limit freq.
F7.7 wobble freq. 0.01 10.0

F7.8 Reserved

C300 series of non-sensor current vector-control inverter manual


34 SUNFAR C300
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
The first part of LED(form right to left):
Inner PID control
0:Inner PID control is invalid
1:Inner PID control is valid
2:Inner PID control is conditional valid.
The second part ofLED:
PID controller selection
0:proportion
F8.0 Inner PID control 1:Integral 1 0020 ★
2:Proportion and integral
The third part of LED:

PID control parameter unit


Regulating property of PID controller
0:positive interaction
1:Reactor
The fourth part of LED:
0: PID with unidirectional control
1: PID with two directions control
The first part of LED(form right to left):
0:Digital setting.
1:Serials interfacesetting
2:Panel potentiometer setting, it is on the
operationpanel.
3:External voltage signal VC(0~10V)
Inner PID setting and 4:External current signal CC
F8.1 1 0000 ★
channel selection The second part of LED: Reserved.
The third part of LED: It is used for
setting PID feedback channel.
0:External voltage input VC(0 ~ 10V)
1:External current input CC
2:VC + CC; 3:VC – CC;
4:Min{VC, CC}; 5:Max{VC, CC}
The fourth part of LED: Reserved

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 35
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
Inner PID close-loop digital
F8.2 0.00~10.00V 0.01 0.00
setting
F8.3 Minimum fixed value 0.0~[F8.4] 0.01 0.0
F8.4 Maximum fixed value [F8.3]~10.00 0.01 10.00
Feedback of minimum fixed
F8.5 0.0~10.00 0.01 0.0

PID control parameter unit


value
Feedback of maximum fixed
F8.6 0.0~10.00 0.1 10.00
value
F8.7 Proportion gain 0.0~5.00 0.01 1.00
F8.8 Integral time constant 1.0~100.0 s 0.1 10.0
F8.9 Allowable deviation limit 0~20.0(%) 0.1 0.0
F8.10 Preset freq. for close-loop 0.0~the upper limit freq. 0.01 0.0
Holding time of preset freq.
F8.11 0.0~6000.0Sec 0.1 0.0 ★
for close-loop
F8.12 Sleeping threshold 0.0~10.00 0.01 10.00
F8.13 Awakening threshold 0.0~10.00 0.01 0.0
F8.14 Reserved
The first part of LED(form right to left):
It is used for setting baud rate of serials
Serials communication

communication.
0:Reserved 1:1200bps
parameters

2:2400bps 3:4800bps
4:9600bps 5:19200bps
F9.0 Communication setting 1 0014 ★
The second part of LED:
To set data format of serials
communication.
0:Close 1: Even 2:Odd
The third and fourthpart of LED:
Reserved.

C300 series of non-sensor current vector-control inverter manual


36 SUNFAR C300
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
F9.1 Local address 0~30 1 0
F9.2 Response delay of local 0~1000ms 1 5ms

The first part of LED(form right to left):


0: The inverter is guest

Serials communication parameters


1: The inverter is host
The second part of LED:
Function setting of
Act selection after communication is lost
F9.3 communication 1 0000
0:Stop 1:Keep
auxiliary function
The third part of LED: Reserved.
The fourth part of LED:
Communication protocol setting, from 0
to 2

Checkout time of
F9.4 0.0~100.0s 0.1 10.0
communication overtime

F9.5 Linkage setting proportion 0.01~10.00 0.01 1.00

0:Close 1:Panel potentiometer


Rectify channel of
F9.6 2:External voltage signal VC(0 ~ 10V) 1 0
linkage setting proportion
3:External current signal CC(0 ~ 20mA)

F9.7 Reserved
Under voltage protection
FC.0 360~460V 1 380
level
Special function
parameter unit

FC.1 Over voltage limit level 660~760V 1 700

Current amplitude limiting


FC.2 150~200(%) 1 180
level

FC.3 Reserved

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 37
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
The first part of LED(form right to left):
Under voltage compensation intensity
The second part ofLED:
Over voltage inhibit intensity
Function Protection in
FC.4 The third part of LED: 1 3333
operation
Over current inhibit intensity
The fourth part ofLED:
Self-adaptingbraking torque adjust
intensity

the first part of LED(form right to left):

Special function parameter unit


Cooling fan control
0: Cooling fan run after inverter run.
1: Cooling fan will automatic run when
inverter is power on.
The second part ofLED:
Variable speed control of cooling fan
FC.5 Function Action selection 0:Invalid 1 0010
1:Valid
Cooling fan always keep the max speed.
The third part of LED:
Voltage over modulation
0:Invalid
1:Valid
The fourth part of LED:Reserved.
FC.6 Reserved
FC.7 Reserved
FC.8 Agency password 0 ~ 9999 1 100
FC.9 Rotational speed coefficient 0.10~5.00 0.01 1.00
Gain of closed loop of
FC.10 0.50~1.20 0.01 1.00
rotating speed

C300 series of non-sensor current vector-control inverter manual


38 SUNFAR C300
Parameters’ Minimum Manufacture Modify
Function Code Name Setting range
Types Setting Setting Limit
Integral time constants of

Special function
FC.11 closing loop of rotational 0.10~10.00 0.01 1.00

parameter unit
speed
Compensation rectify of
FC.12 0~25 1 0
death zone

FC.13 Program version 2000~2099 1 ▲

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 39

6.DESCRIPTION OF SPECIFIC FUNCTIONS

6.1 Basic operation parameter unit

F0.0 Control methods Setting range:0 ~ 1


Please select control method when inverter is working.
0:V/F method
It is used for variable speed inverter occasions where don’t demand high perf
ormance of speed control and low-frequency torque.
1:Sensorless Vector control
It used for the variable speed inverter occasions with high performance.

It will get prime performance when inverter matches the same capacity motor
under the method of vector control.

Notes:
1. It needs use some basic parameters of load motor when inverter takes vector
control. C300 serial inverter provides those basic parameters of motor, and
those parameters were set already.
2. When basic parameters of applied motor are different from parameters
provided by inverter, those parameters must be set again (code [F1.15] ~
[F1.18]). User can get those parameters by setting code F1.20 (Parameters
self-determination).
3. When you can’t gain nameplate parameters of applied motor or you need
inverter to inverter several motors, please take V/F method.

F0.1 Frequency input channel / mode selection Setting range:0 ~ 7


It is used for selecting input channel of frequency instruction.
0: Frequency digital setting by operation panel
Setting frequency of inverter can be set by parameter F0.2 as well as by the key
on the operation panel in normal monitor mode.
1: UP/DW Acc and Dec control
Running frequency is set by terminals UP and DW. And controlled terminals UP
and DW can be selected by parameters [F3.0]~[F3.3]. When UP is on, the running
frequency will increase. When DW is on, the running frequency will decrease.
When UP and DW is on or off at the same time, running frequency will be fixed.
The rate of modified frequency of terminals UP and DW is set by parameter F4.23.

C300 series of non-sensor current vector-control inverter manual


40 SUNFAR C300

2: RS485 interface
It receives instructions of setting frequency from the PC or Master by Serial
Communication RS485 interface.
3: Panel potentiometer
Running frequency can be set by potentiometer on the operation panel.
4: External voltage signal VC
Running frequency is set by external voltage signal VC(0.0~10.0V)Please set the
VC1 following the parameters F2.0 and F2.1.
5: External current signal CC
Running frequency is set by external current signal CC. (CC is form 0.0 to 20.0mA)
Please set the CC following the parameters F2.2 and F2.3.
6: Combination setting
Running frequency is set by linear combination of each channel, and combination
mode is decided by parameter F2.8.
7: External terminals
External terminals set input channel of frequency. And it can be set by parameters
F3.0~F3.3.

F0.2 Frequency digital setting


Setting range:0.0 ~ the upper limit frequency
When F0.1 is 0, frequency digital setting controls output frequency of inverter which

has been decided by this data. In normal monitor state, you can use the key to

modify this parameter.


As to the methods of setting frequency, F0.1 is 1 or methods of interfacing, F0.1 is
2, the frequency will save in parameter F0.3 after power off, if F0.3 is 00#0.

F0.3 Auxiliary control of freq. digital setting Setting range:0000 ~ 0021


When F0.1 is 0, 1 or 2, set parameter F0.3 to ensure that setting freq. is or not be
saved in F0.2.
The first part of LED(form right to left):
0: Inverter will run in setting freq. that is storage in F0.2 after stopping
1: Setting freq. will lost after stopping. And inverter will run in 0.0Hz when restart
The second part of LED(form right to left):
0:Setting freq. is keep when stop
1:Setting freq. will save in F0.2 when stop
2:Setting freq. is clear when stop
The third and fourth part of LED(form right to left):Reserved.

F0.4 Operation channel selection Setting range: 0000 ~ 0012

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 41

It is used for selecting operation channel of inverter and function of key


The first part of LED (form right to left): to select operation channel of inverter.
0: Panel control
The inverter is controlled by key on the panel. And external control terminal,
FWD state will affect output phase sequence of inverter. When FWD is on,
connecting with GND, output phase sequence will reverse with setting sequence,
on the contrary, output phase sequence will go the same way with setting
sequence.
1: External terminals control
The inverter receives running instruction form the situation of being on or off of
external terminals FWD、REV and GND, while the mode is decided by parameter
[F0.5]. The manufacture setting is shown as follows:

Instruction Stop instruction FWD instruction REV instruction

FWD FWD FWD FWD


Terminals
REV REV REV REV
State GND GND GND CM

2:Serial Communication RS485 interface


The inverter will receive running instruction from the PC or Master.
The second part of LED (form right to left): to select function of the key
0: It is valid for panel.
When F0.4 is 0000, key on the operation panel is available.
1: It is valid for all kinds of control method.
When F0.4 is not 0 and pressing key, inverter will stop urgently and twinkle
display Fu.16.
The third and fourth part of LED(form right to left):Reserved.

F0.5 Combination methods of instruction terminals Setting range:0 ~ 2

It is used for setting control modes of external terminals.

This parameter will valid only when F0.4 is set as ###1

0:Two-line mode 1(Manufacture Setting)

C300 series of non-sensor current vector-control inverter manual


42 SUNFAR C300

Instruction Stop instruction FWD instruction REV instruction

Terminals FWD FWD FWD FWD


REV REV REV REV
State GND GND
GND CM

1: Two-line mode 2
Instruction Stop instruction Run instruction FWD instruction REV instruction

Terminals FWD FWD REV REV


State GND GND GND GND

2:Three-line mode
Please select a three-line mode terminal to set three-line mode. (Refer to
description of parameters F3.0 ~ F3.3) X?is three-line mode terminals,and it is
any one among terminals X1 ~ X4.
Switch function is shown as follows:
1. SW1 ——Stop trigger switch of inverter
Output freq.
2. SW2 ——FWD trigger switch
3. SW3 ——REV trigger switch

SW1
X? Time
SW2
FWD
SW3
REV
GND
SW1

SW2
SW3
Fig.6-1 three-line mode wiring Fig.6-2 Output freq. when three-line

F0. 6 Steering control Setting range:0000 ~ 0011

This parameter is used for modifying the present output phase sequence of inverter,
which modifies the running motor direction. Control effect of panel control method
is shown as the following table.

Parameter F0.4 is valid together with direction control of external terminals.

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 43

FWD-GND [F0.6] Direction


OFF ##1# FWD
ON ##1# FWD
OFF ##00 FWD
OFF ##01 REV
ON ##00 REV
ON ##01 FWD

F0.7 The lower limit frequency Setting range:0.0 ~ [F0.8] Hz


F0.8 The upper limit frequency Setting range:[F0.7] ~ 400.00Hz
When setting freq. is lower than lower limit freq., the inverter will run in lower limit
freq. But the parameters F4.8 and F4.9 are priority over F0.7 and F0.8.

F0.9 Reserved

F0.10 Acc time 1 Setting range:0.1 ~ 6000 Sec/Min


F0.11 Dec time 1 Setting range:0.1 ~ 6000 Sec/Min

Acc time 1 is the time of output frequency accelerating from 0.0 Hz to 50.00Hz.
Dec time 1 is the time of output frequency decelerating from 50.00 Hz to 0.00Hz.
Units of Acc and Dec are set by parameter F0.12.

F0.12 character parameter of Acc and Dec Setting range:0000 ~ 0111


The first part of LED(form right to left):It is used for setting curve type when
inverter is accelerating or decelerating, shown as fig6-3.
0: Beeline
Output freq. of inverter will increase or decrease according to fixed rate.
1: S curve
Output freq. of inverter will increase or decrease according to graded rate.
Characteristics of S curve are set by parameter F0.13 and F0.14.
The second part of LED:To set Acc/Dec method
0: Output freq. will be modified according to Acc/Dec time.
1: Output freq. will be automatically modified according to lode.
The third part of LED: It is used for setting unit of Acc/Dec time, namely unit of
parameters F0.10, F0.11, F4.17, F4.18, F4.19, F4.20, F4.21 and F4.22.
0: Sec. 1: Minute
The fourth part of LED:Reserved.

C300 series of non-sensor current vector-control inverter manual


44 SUNFAR C300

Output freq.(Hz)

Beeline

S curve

[F0.13][F0.14] T(Sec/min)
Fig.6-3 Acc/Dec curve

F0.13 Acc/Dec initial section proportion of S curve Setting range:10.0 ~ 50.0(%)


F0.14 Acc/Dec ascending/decline section proportion of S curve Setting range:10.0 ~ 80.0(%)

Parameters F0.13 and F0.14 define characteristics of S curve. It is totally divided


into three sections, shown as fig6-3.
Acc/Dec initial section is the process that slope of output freq. is increase form 0
gradually. The slope will fix in Acc/Dec ascending/decline section. And the slope will
decrease to 0 gradually in end section.

F0.15 Reserved

F0.16 Carrier wave frequency Setting range: 1.5 ~ 12.0 KHz


The parameter has decided the switch frequency of the inner frequency of inverter.
As to the different power of inverter, there are differences between the highest
carrier wave frequency and the lowest carrier wave frequency under permission.
Carrier wave frequency mainly influences audio-frequency noise and calorific effect
in running. If you need the running situation that you can heighten the carrier wave
frequency a little, while the load capacity of inverter would decrease a little, and the
interference rates of inverter would increase little.
When environmental temperature is too high and motor’s load is too heavy, carrier
frequency should be decreased properly to improve the heat thermal performance.

F0.17 Carrier wave characteristics Setting range:0000 ~ 1110

It used for setting correlative characteristics about carrier wave.

F0.18 Parameter write-protection Setting range:1,2


It is used for preventing error modify about data.
1:Forbid to modify all parameter, except F0.2 and F0.18
2:Forbid to modify all parameter, except F0.18

In running, some parameters cannot be modified. At this time , if try to modify


these parameters, the inverter will display “— —”, please turn off the inverter
before modify those parameters.

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 45

6.2 Primary application of parameter unit


F1.0 Type of V/F Curve Setting range :0 ~ 3
0:Constant torque curve
The output voltage of inverter is in direct ratio to the output frequency, and most
load take this mode.
1: low-freq. torque curve 1
The output voltage of inverter is conic with the output frequency, which is suited to
the fan and pump load.
2: low-freq. torque curve 2
The output voltage of inverter is conic with the output frequency, which is suited to
the constant power load, such as fan, pump, etc. If there is some unstable
phenomenon in light-load running, please switch to run in the decreasing torque
curve 1.
3: V/F user-defined curve
It is used for setting user-defined curve which you need.
Voltage
[F1.4]
The max
output
voltage Constant torque curve

Decreasing torque curve 1

Decreasing torque curve 2

[F.1.3]
f

Fig. 6-4 V/F curve

F1.1 Torque Boost(output voltage at 0 Hz) Setting range:0 ~ 20(%)

It is used for improving the low-frequency torque character. In low-frequency


running, it will make boost compensation for the output voltage of inverter, as
shown in Fig.6-5.

[F1.1]
Boost voltage = × [F1.4]
100

C300 series of non-sensor current vector-control inverter manual


46 SUNFAR C300

Voltage Voltage
[F1.4] [F1.4]

[F1.1] [F1.1]

Boost voltage Boost voltage


f f

[F1.3] [F1.3]

(1)Decreasing torque curve (2)Constant torque curve

F1.2 Torque boost patterns Fig.6-5 Torque boost Setting range:0 ,1

0:Manual
Torque boost voltage is completely set by F1.1. There are two features: voltage will
steady boost. And motor will easily magnetic saturation when light-load.
1:Automatic
Torque boost voltage is changed with the stator current of motor. The boost voltage
is higher with the stator current higher.

[F1.1] Inverter’s output Current


Boost voltage = ×[F1.4]×
200 Inverter’s rated current

Auto torque boost can prevent the magnetic saturation, as the boost voltage is too
high with light load, which can avoid the over-heat phenomenon of motor in low
frequency running.
F1.3 Base running frequency Setting range: 5.00 ~ the upper frequency
F1.4 Maximal output voltage Setting range: 200 ~ 500V/100~250V
Basic running frequency is corresponding to minimum frequency when output
voltage of inverter is highest. Usually, it is rated frequency of motor.
Maximal output voltage is corresponding to output voltage when inverter outputs
the base running frequency. Usually, it is rated voltage of motor.

F1.5 V/F freq. 3 Setting range: [F1.7] ~ [F1.3]


F1.6 V/F voltage 3 Setting range:[F1.8] ~ 100%
F1.7 V/F freq. 2 Setting range: [F1.9] ~ [F1.5]
F1.8 V/F voltage 2 Setting range:[F1.10] ~ [F1.6]
F1.9 V/F freq. 1 Setting range:0.0 ~ [F1.7]
F1.10 V/F voltage 1 Setting range:[F1.1] ~ [F1.8]

Those parameters are used for setting user-defined curve which you need. Shown

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 47

as Fig.6-6:
V

[F1.4]

[F1.6]

[F1.8]

[F1.10]
[F1.1]
f
[F1.9] [F1.7] [F1.5] [F1.3]

Fig.6-6 V/Fuser-defined curve

F1.11 DC braking current when start Setting range:0.0 ~ 100.0 (%)


F1.12 DC braking time when start Setting range:0.0 ~ 20.0 S
Those parameters are fit for the occasion that inverter need brake before start.
DC braking current when starting
F1.11= ×100%
Rated current of inverter

When rated current of motor is lower than rated current of inverter, please pay
attention to set F1.11.Make sure that DC braking current is lower than rated
current of motor.

Parameter F1.12 defines duration time that inverter output DC braking current.
When F1.12 is 0, DC braking is invalid when start. Shown as Fig.6-7.
Output Freq.

Starting
freq. DC braking
[F1.12]
[F4.1] [F4.4]

Output
current

[F1.11] [F4.7]

[F4.6]
Instruction
[F4.2]
[F4.5]
Fig.6-7 Process of start and stop

F1.13 Reserved

C300 series of non-sensor current vector-control inverter manual


48 SUNFAR C300

F1.14 Compensation for slipping freq. Setting range: 0.0 ~ 150(%)


The inverter will modify output freq. automatically to offset effects that is acting on
rotational speed of motor form
Output freq. Compensation for slip freq. is 100%

150%

100%
Before After

50%
Rotor speed

Fig.6-8 Compensate for slip freq.

F1.15 Rated voltage of applied motor Setting range: 200 ~ 500/100 ~ 250 V
F1.16 Rated freq. of applied motor Setting range: 5.00 ~ 300.00 Hz
F1.17 Rated current of applied motor Setting range: 0.01 ~ 300.0 A
F1.18 Rated rev of applied motor Setting range: 300 ~ 6000 RPM
F1.19 Exciting current of applied motor Setting range: [F1.17]/4 ~ [F1.17]×3/4

Those parameters are nameplate data of applied motor. And they need input one
by one according to capacity of applied motor, when inverter takes vector method.
Generally, exciting current of applied motor needn’t modify. Because it will
automatically update when rated current of applied motor is modified.

F1.20 Parameters self-determination Setting range: 0 ~ 3

0: It will be invalid.
1: Determine parameters when motor stops
2: Determine parameters when motor runs(Reserved)
Both vector control method([F0.0] = 1)and panel control method([F0.4] = 00#0)are
valid.
When parameter F1.20 is valid, inverter will determine parameters by press .
Parameters will save automatically in inverter’s memory and Parameter F1.20 will
clear automatically.
Before start function of Parameters self-determination, please make sure that
nameplate parameters of motor([F1.15] ~ [F1.18])are input correctly and the motor
has stopped.
Self-determination function of static parameter: motor would always keep silent
when parameter is self-determining.
Self-determination function of dynamic parameter: motor runs to rated speed for a
while then stop automatically in the process of self-determining. Make sure that

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 49

motor is always below rated load, if not, you can’t implement the process.
(Reserved)
Self-determination function of synthesis: firstly, inverter implements motor’s static
self-determination, then, it runs the process of starting the dynamic
self-determination and then stop automatically.
(Reserved)
Attention: If motor, with inverter not connecting correctly, the process of
self-determination will stop, while display the signal Fu.30~Fu.33.
(Refer to the seventh chapter: Fault Diagnosis and Countermeasures)

When capacity of applied motor is equally match inverters, user start function of
Parameters self-determination is not necessary.
If motor isn’t connect with inverter correctly, self-determination will stop and LED
]
of inverter will show fault Fu.30~Fu.33.

F1.21 Selection of starting pre-excitation Setting range: 0000 ~ 0011


F1.22 Pre-excitation of starting time Setting range: 0.10 ~ 2.00 Sec

Those parameters are used for defining pre-excitation of motor startup.


It need some time to set motor air-gas flux (approximate rotor time). In order to get
enough start torque, it must set air-gas flux beforehand when motor is stop but it
will start.
Those parameters will valid while inverter takes vector control method only.
parameters[F1.21] (set by binary system)
The first part of LED (form right to left): To start Pre-excitation
0:To start Pre-excitation is invalid.
It isn’t needed to set air-gas flux beforehand when motor is from stopping to
starting.

In order to achieve vector control, inverter will forcibly give motor an excitation
current, even parameter F1.21 is set 0.

1: To start pre-excitation is valid


To give motor a pre-excitation before it startup, Pre-excitation of starting time is set
by parameter [F1.22].
The second part of LED (form right to left): zero-freq. excitation preparation
0: Prepare pre-excitation is invalid when zero frequency
When inverter’s Instruction is running, but the output freq. is 0, inverter will close
off output power and the stator current of motor is 0.
1:Prepare pre-excitation is valid when zero frequency

C300 series of non-sensor current vector-control inverter manual


50 SUNFAR C300

When inverter is running, it will output excitation current even the freq. output is 0.
So there is no pre-excitation of starting time when start-up motor.
The second and third part of LED (form right to left) reserved.
Current

[F1.19]

Output freq.

[F1.22]

Fig. 6-9 TO start pre-excitation

F1.23 Self-adapting rectify of motor parameters Setting range: 0000 ~ 0111


It is used for selecting self-adapting rectify of motor parameters function(set by
binary system).
The first part of LED (form right to left): to select self-adapting rectify of stator
resistance function
0:Self-adapting rectify of stator resistance is invalid
1:Self-adapting rectify of stator resistance is valid
The second part of LED (form right to left): to select self-adapting rectify of
excitation function
0:Self-adapting rectify of excitation is invalid
1:Self-adapting rectify of excitation is valid
The third part of LED (form right to left): to select self-adapting rectify of rotor
resistance function
0:Self-adapting rectify of rotor resistance is invalid
1:Self-adapting rectify of rotor resistance is valid
The fourth part of LED (form right to left): reserved.
Some parameters of motor have influenced by temperature change, and control
performance is affected if setting value isn’t precision. When motor have selected
corresponding function, inverter will optimize parameters automatically in running,
which can improve the performance and stability of motor.

F1.24 stator resistance Setting range: 0.000 ~ 20.000 (Ω)


F1.25 rotor resistance Setting range: 0.000 ~ 20.000 (Ω)
F1.26 rotor inductance Setting range: 0.00 ~ 600.00 (mH)
F1.27 excitation inductance Setting range: 0.00 ~ 600.00 (mH)
F1.28 Leakage inductance (coefficient) Setting range: 0.00 ~ 100.00 (mH)

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 51

Those parameters are used for setting motor’s basic parameter. They are
necessary for completing vector control arithmetic. Clients can use inverter‘s
interior parameters when capacity of inverter matches motor’s. When the
performance of inverter can’t satisfy the users’ demand, you can use function of
parameters self-determination to renew some parameters. If user can get these
parameters precisely beforehand, parameters also can be input one by one. When
parameters are initializing, inverter will renew interior acquiescence parameter
according to type.
Before start function of parameters self-determination, user must make sure the
input nameplate parameter of motor.

F1.29 Gain of compensation for speed dropping Setting range: 0.50 ~ 1.50
Parameter F1.29 is valid when inverter takes vector control method. It is used for
offsetting error of setting motor rotor parameter. The parameter is read only.

6.3 Analog I/O parameter unit

F2.0 VC input lower limit voltage Setting range: 0 .0 V ~ [F2.1]


F2.1 VC input upper limit voltage Setting range: [F2.0] ~ 10.0 V

F2.2 CC input lower limit voltage Setting range: 0.0 mA ~ [F2.3]


F2.3 CC input upper limit voltage Setting range: [F2.2] ~ 20.0 mA

[F2.0] and [F2.1] define the range of analog input voltage channel VC1, and it
should be set according to the actual input signal.
[F2.2] and [F2.3] define the range of analog input current channel CC, and it should
be set according to the actual input signal.

F2.4 frequency with the min setting Setting range: 0.0Hz ~ [F2.5]
F2.5 frequency with the max setting Setting range: [F2.4] ~ 550.0Hz

They define the Corresponding relation between analog input (pulse input) and
setting frequency. Shown as fig.6-10.

F2.6 Character selection of input channel Setting channel: 0000 ~ 0101


It is used for selecting input character of external analog value or pulse value.
The first part of LED (form right to left):It defines character of voltage signal analog
input VC.
0: positive character 1:Negative character
The second part of LED (form right to left): Reserved..
The third part of LED (form right to left): It defines character of current signal
analog input CC.

C300 series of non-sensor current vector-control inverter manual


52 SUNFAR C300

0: positive character 1:Negative character


The fourth part of LED (form right to left): Reserved..
The corresponding relation is shown as fig.6-10 between input signal and setting
freq.
Freq. Freq.

Output freq. Output freq.

[F2.9] [F2.9]

[F2.8] [F2.8]

Analog value Analog value Analog value Analog value


Input lower Input upper Input lower Input upper
limit limit limit limit
Positive character Negative character
Fig.6-10 corresponding relation between analog input and setting freq.

F2.7 External freq. set time constant of filtering Setting range: 0.01 ~ 1.00s

Setting freq. set by external analog input will be filtered to eliminate fluctuate. Time
constant of filtering have to appropriate set according to fluctuate of external input
signal.

F2.8 Combination setting mode Setting range:0 ~ 19

The parameter is valid only when the frequency input channel F0.1 is set 6.
Setting Setting
Combination setting mode Combination setting mode
Value Value
External voltage VC +
0 1 External voltage VC - External current CC
External current CC
2 External voltage VC + panel setting 3 External voltage VC - panel setting
4 External current + panel setting 5 External current - panel setting
External voltage VC + panel setting + External voltage VC - panel setting + digital
6 7
digital setting setting
External current + panel setting + External current - panel setting + digital
8 9
digital setting setting
Serials interface setting + External Serials interface setting – External
10 11
voltage VC voltage VC
Serials interface setting + External Serials interface setting - External current
12 13
current CC CC
Serials interface setting + External Serials interface setting + External
14 15
voltage VC +panel setting voltage VC - panel setting

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 53

External voltage VC + External External voltage VC + External


16 17
current+ panel setting Current – panel setting + digital setting
The max between External voltage1, Nonzero valid External voltage VC and
18 19
and External current External current CC

F2.9 Analog output selection Setting range: 0000 ~ 0005


It defines meanings of AVO.
The first part of LED: it defines the meanings of analog output terminal AVO.
0:Output freq.
Amplitude accumulation of AVO is in direct ratio to the output frequency. F2.11 is
corresponding to the upper limit freq.
1:Output current
Amplitude accumulation of AVO is in direct ratio to the output current. F2.11 is twice
rated current of inverter.
2:Output voltage
Amplitude accumulation of AVO is in direct ratio to the output voltage. F2.11 is
corresponding to [F1.4] and [F1.15].
3:Rotational speed of applied motor
Amplitude accumulation of AVO is in direct ratio to the motor rotational speed of
inverter. F2.11 is corresponding to rotational speed that is corresponded with the
upper limit freq.
4:PID setting
Amplitude accumulation of AVO is in direct ratio to the setting value of PID. F2.11 is
corresponding to feedback of 10.00.
5:PID feedback
Amplitude accumulation of AVO is in direct ratio to the PID feedback. F2.11 is
corresponding to feedback of 10.00.
The second, third and fourth part of LED: Reserved.

F2.10
Those parameters
the lower limit
define the Maximum
of analog andSetting
output AVO minimum value0.0ofVanalog
range: ~ [F2.11]
output
F2.11 the upper limit of analog output AVO Setting range: [F2.10] ~ 12.0 V
AO1and AO2, shown as fig 6-11.

C300 series of non-sensor current vector-control inverter manual


54 SUNFAR C300

AVO

[F2.11]

[F2.10]

1 Upper limit voltage Output freq.


2 Rated current Output current
3 The max/rated Voltage Output voltage
4 Rotor speed
5 10.00 PID setting
6 10.00 PID feedback

Fig.6-11 output of analog terminals

F2.12 Reserved

6.4 Digital O/I parameter unit


F3.0 Function selection of input ternimal1 Setting range:0 ~ 25
F3.1 Function selection of input ternimal2 Setting range:0 ~ 25
F3.2 Function selection of input ternimal3 Setting range:0 ~ 25
F3.3 Function selection of input ternimal4 Setting range:0 ~ 25
0:Control ter
1:Multi-speed control terminal 1
2:Multi-speed control terminal 2
3:Multi-speed control terminal 3
Combination of multi-speed control terminals is used for selecting output freq. of
multi-speed.
4:Wobble freq. is valid
When F7.0 is ###2 and any of those parameters are set 4, wobble freq. is valid.
5:State of wobble freq. reset
When inverter stop and F7.0 is ##0#, forcible reset will work by setting those
parameters.
6:FWD jog control
7:REV jog control
When F0.4 is ###1 and any of those parameters is set 6 or 7, external jog signal is
valid.
8:Acc& Dec time selection terminal 1
9:Acc& Dec time selection terminal 2

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 55

They are used for selecting external terminals Acc/Dec time 1~4.
10:Freq. setting channel selection 1
11:Freq. setting channel selection 2
12:Freq. setting channel selection 3
When F0.1 is 7, Frequency input channel is set by terminals state of 10, 11 and 12.
Refer to the explanation about parameter F0.1.
13:Freq. gradually increase to control (UP)
14:Freq. gradually decrease to control (DW)
15:UP-DW freq. clear
When F0.3 is##0#, one of terminal X1~X6 defined by this parameter have function
of forcible clear.
16:Uncontrolled stop control
If one of terminal X1~X6 defined by this parameter is connected with CM, the
inverter will lock output signal and applied motor will stop uncontrolled. Then
inverter will detect speed and restart after terminal is disconnected with CM.
17:Fault signal of peripheral equipment input
When one of terminal X1~X6 defined by this parameter, it is connected with CM,
and peripheral equipment is fault. The inverter will lock output signal and display
FU.16.
18:Three-line mode running control
When F0.5 is 2, one of external terminal X1~X6 defined by this parameter, it would
stop trigger switch of inverter. Refer to explanation about F0.5.
19:DC braking control
When inverter is stop and one of external terminals X1~X6 defined by this
parameter is connected with CM and output freq. is lower than Initial freq. of DC
braking, function of DC braking is valid until terminal is disconnected with CM.
Refer to explanation about F4.4~F4.7.
20:Inner counter clear
21:Inner counter timer
Only terminal X6 is used for Inner timer, namely parameter F3.3 is 21.
22:PLC running valid
When F5.0 is ###2 and any of those parameters is set 22, PLC running is valid.
23:PID running valid
When F8.0 is ###2 and any of those parameters is set 23, PID running is valid.。
24:Reserved
25:PLC state reset after stopping
If F5.0 is set as #1##, the PLC state will keep fix. But external terminals will force
reset, which is set by this function.

F3.4 Output terminal OC Setting range:0 ~ 18


F3.5 A, TB and TC of relay contacts Setting range:0 ~ 18
It defines expression content of relay contact and terminals OC1 and OC 2 when

C300 series of non-sensor current vector-control inverter manual


56 SUNFAR C300

collector is open-circuit. Shown as fig.6-12.。


When TA is on with TC, setting functions will available.

D R
While connecting the external
1
inductance cell (For example, Relay
coil), it must connect the parallel
fly-wheel diode D.
2

Fig.6-12 Inner wiring diagram of output terminals


0:In the running
When the inverter is in the running state, it will output the valid signal. While the
inverter is in stop mode, it will output the invalid signal.
1:Frequency reaching
When the output frequency of inverter approaches the certain range of the setting
frequency. (The range is decided by parameter F3.6), it outputs valid signal,
otherwise, outputs the invalid signal (High-resistance).
OC

H igh resistance

[F3.6]

Setting freq. O utput freq.


O utput freq.

t
Fig.6-13 Freq. reaching signal
2:Freq. level detection signal(FDT)
When the output frequency of inverter is over FDT Frequency level, the inverter
will output the valid signal (Low electrical level) after the setting delay time. When
the output frequency of inverter is lower than FDT frequency level, after the same
delay time, it will output the invalid signal (High resistance).
OC1

High resistance High resistance

f Setting frequency

[F3.7] FDT Level

[F3.8] [F3.8] t
Fig. 6-14 Freq. level detection signal(FDT)
C300 series of non-sensor current vector-control inverter manual
SUNFAR C300 57

3. Over-loading alarm
When the output current of inverter is over the over-loading alarm level, it will
output the valid signal (Low level) after the setting alarm delay time. When the
output current is lower than the over-loading alarm level, it will output the invalid
signal (High resistance) after the same delay time.

O u tp u t c u rre n t

A la r m
le v e l

OC

H ig h r e s is ta n c e H ig h r e s is ta n c e
t
[F 3 .1 0 ] [F 3 .1 0 ]

4:External fault halt Fig.6-15 Over-loading alarm


When the external fault input signal is valid and it will lead to stop-machine, the
terminal will output the valid signal (Low level), otherwise it will output the invalid
signal (High resistance).
5:Output frequency reaches the upper-limit
When the output frequency reaches the upper-limit frequency, the terminal will
output the valid signal (Low level). Otherwise, it will output the invalid signal (High
resistance).
6:Output frequency reaches the lower-limit
When the output frequency reaches the lower-limit frequency, the terminal will
output the valid signal (Low level). Otherwise, it will output the invalid signal (High
resistance)
7:Running in zero speed
Running instruction is valid and output freq. is 0, if inverter is input freq., the
terminal will output the valid signal (Low electrical level). If inverter is not input freq.,
the terminal will output the invalid signal (High resistance).
8:Internal timer reaches the setting time
When the internal timer reaches the setting time, the terminal will output the valid
pulse signal of 0.5 Sec pulse widths. (Low electrical level)
9:PLC stage is end of run
When simple PLC is valid and current stage is end, this port will output pulse signal
with 0.5s pulse width. 10:PLC periodic is the end of running.
When simple PLC is valid and current period is end, this port will output pulse
signal with 0.5s pulse width.
11:Reserved
12:Setting value of counter arrives

C300 series of non-sensor current vector-control inverter manual


58 SUNFAR C300

Refer to the explanation about parameter F6.3.


13:Designated value of counter arrives
Refer to the explanation about parameter F6.4.
14:Reserved
15:Reserved
16:Inverter faults
When inverter is running with faults, it will output available signal (low level).
17:Restrictions on wobble freq. of the upper and lower limit freq.
When parameters setting about wobble freq. result in that running freq. is beyond
the upper and lower limit freq., this port will output available signal (lower lever).
Generally, this port output high resistance.
18:Reserved

F3. 6 Frequency reach the checkout amplitude Setting range:0.0 ~ 20.00Hz


If output freq. of inverter is within setting value that is set in F3.9, selected terminal
will output valid signal. Shown as fig.6-13.
F3.7 FDT setting Setting range:0.0 ~ upper limit freq.
F3.8 FDT output delay time Setting range:0.0 ~ 200.0 s
The parameter is used for setting the frequency detection level. When output
frequency is higher than the setting value of FDT, after the setting delay time,
terminals will output the valid signal, shown as fig.6-14.
F3.9 Overload alarm level Setting range:50 ~ 200(%)
F3.10 Overload alarm delay time Setting range:0.0 ~ 20.0s
If output freq. beyond the setting value set by parameter F3.9, after the setting
delay time set by parameter F3.10, terminals output valid signal, shown as fig.6-15.

F3.11 Reserved

6.5 Auxiliary running parameter unit

F4.0 Start mode Setting range:0~1


F4.1 Start frequency Setting range:0.0~10.00Hz
F4.2 Start frequency duration Setting range:0.0~20.0s
Those parameters are used for defining characteristics with relation to start mode,
shown as fig6-16.
The explanation of F4.0 is shown as follows:
0: Routine mode
It is fit for mostly lodes, which have not special demand.
1:Detect speed and restart
It is fit for fault reset and restart occasion, or, power off and restart occasion.
Inverter will judge automatically running speed and direction of motor. Motor, which

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 59

have not stop, will start up directly according to detect result.


Start frequency :It is fit for system, which is big inertia, heavy load and high start
torque. f
D e celerate stop
w ith no D C braking
Setting freq.

[F 4.2] F ree stop


[F 4.1]

Start

Fig6-16 Start and stop freq. output curve

F4.3 Stop mode Setting range:0 ~ 1


0: Decelerate mode
Inverter will gradually decrease output freq. to 0 according to Dec time when
stopping.
1: Uncontrolled stop
Inverter will output zero freq. and lock output signal when stop, so motor will stop
uncontrolled.
If user needs restart motor before motor stop completely, function of detection
speed and restart must be valid when inverter stops uncontrolled.
Start mode and stop mode is shown as fig6-16.

F4.4 Initial freq. of DC braking when stopping Setting range:0.00 ~ 50.00 Hz


F4.5 Waiting time of DC braking when stopping Setting range:0.0 ~ 5.0 S
F4.6 Action time of DC braking when stopping Setting range:0.0 ~ 20.0 S
F4.7 DC braking current when stopping Setting range:0.0 ~ 100 ( % )
It is used for setting DC braking parameters when stopping, shown as fig6-7.
When output freq. is lower than setting freq. of Parameter F4.4, inverter will lock
output and start DC braking function after waiting setting time of parameter F4.5.
DC braking when stopping is invalid while F4.6 is 0.
DC braking current when stopping is the percentage of rated current of inverter.
When capability of applied motor is lower than inverter capability, please be sure to
set F4.7.

F4.8 Running threshold of zero freq. Setting range:0.00 ~ 100.00(Hz)


F4.9 Return different of zero freq. Setting
Those parameters define characteristics of freq. range:0.00 ~ 50.00(Hz)
zero-crossing.
When inverter takes analog input freq. to set freq., analog signal will fluctuate
around zero to cause sluggish input. Those parameters have lagging function to
avoid fluctuating around zero. Appropriate set
Function of sleeping and awakening will work, if those parameters are appropriate
set. For example analog input channel VC is shown as fig6-17.

C300 series of non-sensor current vector-control inverter manual


60 SUNFAR C300

VC input

[F2.1]

[F2.0]
Initial setting freq.

[F2.4] [F2.5]
Actual setting freq.
[F2.5]

[F4.8]
Initial setting freq.

[F4.9]

Fig6-17 freq. zero-crossing curve

F4.10 Jog frequency Setting range:0.0 ~ Upper limit frequency


Jog running is special running method of inverter.
Whatever the initial state of inverter stop or run, the jog signals will be received.
The transition form initial running freq. to jog freq. is act according to parameters
F4.21 and F4.22.

Jog Acc time


[F4.21]

Jog Freq. Jog Dec time


[F4.10] [F4.22]

t
Jog signal

f
Jog Acc time
[F4.22]
Jog Freq.
[F4.10] Jog Dec
[F4.21

t
Jog signal

Fig6-18 Jog running

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 61

F4.11 Acc torque level Setting range:110 ~ 200 (%)


F4.12 Braking torque lever Setting range:10 ~ 150 (%)
It is used for setting permissible output level of torque current under motor
acceleration state.
The restriction on torque level is set by F4.11. It is percentage of rated current of
inverter. For example, F4.11 set 150% that means the max output current is 150
percentage of rated current.
When output current of inverter is beyond setting value of F4.11, inverter will
prolong Acc/Dec time to inhibit output current in setting value of F4.11. Shown as
fig6-19.
It fits for occasions that demand high performance with braking torque. If setting
value of parameter F4.12 is big, the Braking effect will obvious. But inverter will
alarm about over voltage if inverter is not connect braking resistance.

Modified Dec time

Braking
torque
level

t
Fig6-19 Acc torque level

F4.13 Motor over-lode protection coefficient


图 6-19 加速力矩与制动力矩示意图 Setting range:50 ~ 110(%)
The parameter is used for setting the sensitivity of thermal relay protection for
applied motor. When the rated current of applied motor doesn’t match with the
rated current of inverter, it can accomplish the correct heat protection for the motor
to set this parameter.
The setting value of this parameter can be set by the following formula:

Rated current of motor


[F4.13]= ×100%
Inverter’s rated output current

C300 series of non-sensor current vector-control inverter manual


62 SUNFAR C300

While one inverter parallel running with multi-motors, the thermal relay protection
of inverter will be invalid, in order to protect the motor, please install the thermal
relay on inlet terminals the motor.

F4.14 Automatic voltage regulation(AVR) Setting range:0 ~ 2


The function of Automatic voltage regulation is to ensure the output voltage of
inverter not to fluctuate with the input voltage. When the range of fluctuation of
power supply voltage is too large, and expect to motor have the stabilized stator
voltage and current, this function should be open.
0:Invalid 1: Dynamic valid 2: Static valid
When user selects dynamic voltage regulation, fast dynamic voltage regulation can
inhibit form increasing current cause by DC voltage in motor deceleration. But it
easy brings current resonance.
For getting good performances in vector mode, please set AVR available (F4.14 is
1 or2).
F4.15 Reserved

F4.16 Dead time of FWD&REV Setting time:0.0 ~ 5.0 Sec


The parameter means that the duration at zero frequency when the inverter
changes its running direction, and it is shown as the following fig.6-20. FWD and
REV dead time is set for the big inertia load which has the mechanical dead zone.
Output frequency

[F3.10]

Fig.6-20 Dead zone between FWD and REV

F4.17 Acceleration time 2 Setting range:0.1 ~ 6000 Sec


F4.18 Deceleration time 2 Setting range:0.1 ~ 6000 Sec
F4.19 Acceleration time 3 Setting range:0.1 ~ 6000 Sec
F4.20 Deceleration time 3 Setting range:0.1 ~ 6000 Sec
F4.21 Acc time 4/Jog Acc time Setting range:0.1 ~ 6000Sec
F4.22 Dec time 5/Jog Dec time Setting range:0.1 ~ 6000Sec

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 63

Jog frequency has the highest priority. In any state, as long as Jog instruction is
input, the inverter will transit to run at Jog frequency according to the setting Acc
and Dec time.
f

t
Acc/Dec terminal 1

Acc/Dec terminal 2
Acc/Dec Acc/Dec Acc/Dec
time 1 time 2 time 3

Fig.6-21 Acc/Dec time selection

F4.23 Modified rated of UP/DW terminals Setting range:0.01 ~ 100.00 (Hz/Sec)


It defines rate that terminals UP/DW modify setting freq. Speed of F4.23 isn’t
controlled by Acc/Dec time.

F4.24 Start voltage of dynamic braking Setting range:600 ~ 720 V


F4.25 Action ratio of dynamic braking Setting range:10 ~ 100(%)
Those parameters are valid for inverter with the inner brake unit. And they define
the action parameter of inner brake unit. When inner DC voltage of inverter is
higher than the start voltage of dynamic braking, the inner brake unit will act. If
inverter connects external brake resistance, DC energy of inverter will be release
by it to decline DC voltage. When DC voltage declines to the certain value
([F3.19]-50V), inner brake unit of inverter will be off, shown as Fig.6-22.
Braking unit action ratio is used for defining the voltage on brake resistor, and the
voltage on brake unit is Voltage PWP. Duty cycle equals brake action ratio. The
ratio is larger, and the energy is consumed more quickly, at the same time, the
power of brake resistor is bigger. User can set parameter according to the
resistance and power of resistor and actual braking effect.
DC
Voltage

[F4.24]
[F4.24]-50V

Brake unit acts

t
Fig.6-22 dynamic braking
C300 series of non-sensor current vector-control inverter manual
64 SUNFAR C300

F4.26 Restart after power down setting Setting range:0000 ~ 0011


F4.27 waiting time of restart after power down Setting range:0.0 ~ 10.0s

The first part of LED:


0:Invalid 1: Valid
When restart after setting power off is invalid, the inverter will clear automatically all
running command and run according to new command after power on.
When restart after setting power off is valid, the inverter will save all running
command and run according to the save command after power on.
Please make sure that other equipments in system are ready before using function
of restart after power down.
The second part of LED:
Applied motor is still running when user select restarting. Here, you have to select
function of detected speed and restart.
The third and fourth part of LED: reserved.

F4.28 Reserved

6.6 Multi-speed running parameter unit


F5.1 Multi-speed frequency 1 Setting range:0.0 ~ the upper limit freq.
F5.2
F5.0 Multi-speed
Multi-speedfrequency 2
running mode Setting range:0.0
Setting ~ the ~upper
range:0000 1252limit freq.
F5.3 Multi-speed frequency 3 Setting range:0.0 ~ the upper limit freq.
F5.4 Multi-speed frequency 4 Setting range:0.0 ~ the upper limit freq.
F5.5 Multi-speed frequency 5 Setting range:0.0 ~ the upper limit freq.
F5.6 Multi-speed frequency 6 Setting range:0.0 ~ the upper limit freq.
F5.7 Multi-speed frequency 7 Setting range:0.0 ~ the upper limit freq.
F5.8 Multi-speed frequency 8 Setting range:0.0 ~ the upper limit freq.

F5.9 Running time of Multi-speed1 Setting range:0.0 ~ 6000s


F5.10 Running time of Multi-speed2 Setting range:0.0 ~ 6000s
F5.11 Running time of Multi-speed3 Setting range:0.0 ~ 6000s
F5.12 Running time of Multi-speed4 Setting range:0.0 ~ 6000s
F5.13 Running time of Multi-speed5 Setting range:0.0 ~ 6000s
F5.14 Running time of Multi-speed6 Setting range:0.0 ~ 6000s
F5.16 Running time of Multi-speed8 Setting range:0.0 ~ 6000s

F5.17 Running direction of PLC multi-speed Setting range:0000 ~ 1111


F5.18 Running direction of PLC multi-speed Setting range:0000 ~ 1111

Parameter F5.0 is multi-speed running mode. It is used for setting basic


characteristics of multi-speed running.
The first part of LED(form right to left):Simple PLC selection

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 65

0:Simple PLC is invalid.


1:Simple PLC is valid. If priority of freq. channel is permit after starting, inverter will
run in a simple PLC state.
2:Simple PLC is conditional valid. If external X1~X6 terminals is valid (F3.0~F3.3 is
set as 22), inverter will run at simple PLC state.
Priority of freq. channel is shown as following table.
Priority Setting freq.
High 1 JOG freq.
2 Wobble freq. running
3 PID output
4 PLC multi-speed freq.
5 External terminals select multi-speed freq.
Low 6 Freq. setting channel selection(Parameter [F0.1] )
The second part of LED:Simple PLC running mode selection
0:Single loop mode
The inverter will run in setting freq of the first stage and in turn output freq. of each
stage according to setting running time. If setting running time of a certain stage is
0, the inverter will skip this stage. When a cycle operation is end of running,
inverter will stop input until user input available running instrument to restart the
next cycle.
1:Single loop and stop mode
Its function has an analogy with single loop mode. The difference is that output freq.
is reduced to 0 within the given decelerate time after a certain stage is in the end of
running and inverter will run at next stage.
2:Continuous loop mode
Inverter will run eight stages in turn. If the eighth stage is at the end of running, the
inverter will run in the next cycle from the first stage.
3:Continuous loop and stop mode
Its function has an analogy with Continuous loop mode. The difference is that
output freq. is reduced to 0 within the given decelerate time after a certain stage at
the end of running and inverter will run at next stage.
4:Keep the final value
Its function has an analogy with single loop mode. The difference is that inverter
will run in the last stage with non-zero speed.
5:Keep the final value and stop mode
Its function has an analogy with keep the end value. The difference is that inverter
will reduce the output freq. to 0 after arriving setting value of Acc time after a
certain stage at the end of running and, then inverter will run the next stage.
The third part of LED
0:Restart from the first stage freq.
When inverter stops, caused by fault or receiving stop instrument in PLC running, it
will clear current running state and restart from the first stage freq.

C300 series of non-sensor current vector-control inverter manual


66 SUNFAR C300

1:Restart from running freq., which is saved before running is break


When inverter is stop caused by fault or receiving stop instrument in PLC running,
inverter will restart from running time and freq. that is saved before running is
break.
2:Restart from setting freq. when running is break.
When inverter stops, caused by fault or receiving stop instrument in PLC running,
setting of running time and freq. of a certain stage will be save. And inverter will
restart form setting of running time and freq. the different between mode 1 and
mode 2 is initial freq. Shown as fig6-24.
The fourth part of LED:PLC save state
0:Non-save after power off
It will not save PLC running state after power off. Inverter will run form the stage 1
when power on.
1:Save after power off
It will save PLC running state after power off. Inverter will run form the stage 1
when power on.
Freq.

[F5.3]
[F5.8]
[F5.14]
[F5.2]
[F5.13]
[F5.1]

t
[F5.9]
[F5.6] [F5.10]
[F5.11]
[F5.16]
[F5.5]

Instruction

Each stage
OC output

Whole Cyc
OC output

Fig.6-23 Single loop and stop mode

Freq.
Mode 1
[F5.3] Stop
[F5.8]

[F5.1]

t
[F5.9] [F5.11]
[F5.16]

Mode 2
[F5.3]
Stop
[F5.8]
[F5.1]

t
[F5.9] [F5.11]
[F5.16]

Fig.6-24 PLC recover running after restart

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 67

[F5.1]~[F5.8] Multi-speed freq.1~8


Those parameters are used for setting output freq. of multi-speed.
[F5.9]~[F5.16] Running time of Multi-speed 1~8
Those parameters are used for confirming running time of each stage.
[F5.17]~[F5.18] Running direction of PLC multi-speed
Those parameters are used for defining running direction of PLC multi-speed.
[F5. 17]
The first part of LED(form right to left):
0: Stage 1 FWD 1:Stage 1 REV
The second part of LED:
0: Stage 2 FWD 1:Stages 2 REV
The third part of LED:
0: Stage 3 FWD 1:Stages 3 REV
The fourth part of LED:
0: Stage 4 FWD 1:Stages 4 REV
[F5. 18] :
The first part of LED(form right to left):
0: Stage 5 FWD 1:Stages 5 REV
The second part of LED:
0: Stage 6 FWD 1:Stages 6 REV
The third part of LED:
0: Stage 7 FWD 1:Stages 7 REV
The fourth part of LED:
0: Stage 8 FWD 1:Stages 8 REV

F5.19 Reserved

6.7 Advanced running parameter unit

F6.0 Reserved

F6.1 Fault self-recovery time Setting range:0 ~ 2


F6.2 Interval time of fault self-recovery Setting range:0.2 ~ 20.0s

F6.1 is used for resetting some faults and run again.


F6.2 defines interval time between fault starting and fault recovery. If inverter can’t
recover in setting value of F6.1, it will output fault signal. Inverter will check speed
and restart.

Inverter can’t self-recovery about overheat or overload protect.

C300 series of non-sensor current vector-control inverter manual


68 SUNFAR C300

F6.3 Final value setup of internal counter Setting range:1 ~ 60000


F6.4 Internal timer setup Setting range:1 ~ 60000
The parameter defines the counting action of internal counter, and the clock
terminals of counter are selected by parameter F1.6.
The counting value of counter for the external clock reaches the value appointed
by parameter F3.3, and the corresponding Terminal OC outputs a valid signal of
same width with the external clock cycle.
When the counting value of counter for external clock reached the value appointed
by Parameter F6.3, the corresponding Terminal OC will output the valid signal, Go
on counting to the value provided by parameter F6.4, which will lead to reset and
the output valid signal will be withdrawn.
The clock cycle of counter should be over 5ms and the min width should be 2ms.
[F6.3]

[F6.4]

Pluse
OC

OC

Fig.6-25 Internal counter function

F6.5 Skip freq. 1 Setting range::0.0 ~ upper frequency


F6.6 Amplitude accumulation of Skip freq. 1 Setting range:0.0 ~ 5.00Hz
F6.7 Skip freq.2 Setting range:0.0 ~ upper frequency
F6.8 Amplitude accumulation of Skip freq. 2 Setting range:0.0 ~ 5.00Hz

It is used for avoiding resonance point of mechanical lode. Shown as fig. 6-26.
Adjusted setting freq.

Skip freq. 2
Amplitude accumulation of Skip freq. 2

Skip freq. 1 Amplitude accumulation of Skip freq. 1

Fig.6-26 Skip freq.

F6.9 Coefficient of linear speed settings Setting range:0.01 ~ 100.0

This parameter is used for confirming the diapaly value of running linear speed and

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 69

setting linear speed, and displaying other value being positive ratio with the output
frequency.

Running linear velocity(d-10)= F6.9 × output frequency (d-0)


Setting linear velocity(d-11)= F6.9 × Setting frequency (d-6)

F6.10 Close-loop analog coefficient setting Setting range:0.01 ~ 100.0

PID feedback value(d.9)= F6.10 × actual feedback value


PID setting value(d.8)= F6.10 × setting value

F6.11 Rotator speed coefficient setting Setting range: 0.01 ~ 10.00

It is used for rectifying the display value of rotator speed.

rotator speed(d.3)= F6.11 × actual output rotator speed

F6.12 Monitor item selection 1 / Main display Setting range:0 ~ 11


F6.13 Monitor item selection 2 / Auxiliary display Setting range:0 ~ 11
This parameter is used for confirming display content of operation panel under
state monitor mode.

F6.14 Query or modify parameters Setting range : 0 ~ 9999


It is used for getting check code to query or modify parameters.

F6.15 Parameter initialization Setting range:0 ~ 2


It is used for modifying inverter’s parameters to manufacture setting.
0:Parameter initialization is off.
1:When parameter initialization is on, please come back parameter unit F0 ~ F9 to
manufacture setting.
2:Clean fault records

F6.16 Copy function of parameter Setting range:0 ~ 1

C300 series of non-sensor current vector-control inverter manual


70 SUNFAR C300

0:Forbid
It is forbidden to copy the backup data from operation panel to inverter, but this
function doesn’t affect the copy and read parameter function.
1:Allow

F6.17 Manufactory password Setting range:0 ~ 9999

Don’t modify this parameter without our permission.

F6.18 User password Setting range:0 ~ 9999

It is used for getting some special power for user.


F6.19 Reference password Setting range:0 ~ 9999

It is always random number.

6.8 wobble freq. running parameter unit


F7.0 Wobbles freq. running mode Setting range: 0000~1112
It is used for setting basic characteristics of wobble freq. running.
The first part of LED (form right to left) :
0: Function of wobble freq. is invalid.
1: Function of wobble freq. is valid.
When inverter receives running instruction, inverter will run in setting freq. of F7.1.
Then inverter will in wobble freq. running mode after arriving setting time of F7.2.
2: Function of wobble freq. is conditional valid.
When external input terminals are valid (namely one of F3.0~F3.3 is 4), the inverter
will run in wobble freq. running mode. When external input terminals are invalid, the
inverter will run in preset freq. of wobble freq. (F7.1)。
The second part of LED: restart mode
0: Restart according to parameters saved before stop
1: Restart
The third part of LED: wobble freq. characteristics(Refer to explanation about
parameter F7.3)
0:The wobble freq. is fixed 1:The wobble freq. is changeable.
The fourth part of LED: Storage characteristic of wobble freq.
0:It will not save the running state of wobble freq. after power off
1:It will save the running state of wobble freq. after power off

F7.1 Preset freq. of wobble freq. Setting range:0.0 ~ the upper limit freq.
F7.2 Waiting time of preset freq. Setting range:0.0 ~ 6000.0s

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 71

Preset freq. of wobble freq. is running freq. before inverter is in or out wobble freq.
mode.
When [F7.0]=###1,inverter will start and run in preset freq. of wobble freq., then
run in wobble freq. mode after the setting time of F7.2.
When [F7.0]=###2 and the terminals of wobble freq. is valid (F3.0~F3.5 is 4),the
inverter will run in wobble freq. mode. When [F7.0]=###2 and the terminals of
wobble freq. is invalid, inverter will output preset freq. [F7.1].

F7.3 Amplitude of wobble freq. Setting range:0 ~ 50.0 %


F7.3 is rate of amplitude of wobble freq.
When F7.0 is [F7.0]=#0##,
Amplitude of wobble freq.= [F7.3]×the upper limit freq. [F0.8]
When F7.0]=#1##,
Amplitude of wobble freq.= [F7.3]×(Preset center freq. of wobble freq. [F7.7] +
External setting freq.)

F7.4 Jumping freq. Setting range:0.0 ~ 80.0 %

When freq. arrives the upper limit freq. the freq. will fast decline. Or when freq.
arrives the lower limit freq., the freq. will fast ascend. Jumping freq. is amplitude,
which freq. ascends or declines. Shown as fig6-27.
Actual jumping freq. = [F7.4]×Amplitude of wobble freq. [F7.3]

F7.5 Triangular rise time Setting range:0.1 ~ 1000.0 s


F7.6 Triangular fall time Setting range:0.1 ~ 1000.0 s
F7.5 defines the running time from lower limit freq. to upper limit freq. of wobble
freq., namely Acc time.
F7.5 defines the running time from upper limit freq. to lower limit freq. of wobble
freq., namely Dec time.
The sum of F7.5 and F7.6 is running cycle of wobble freq.

F7.5 and F7.6 define slope of Acc and Dec in wobble freq.

F7.7 Preset center freq. of wobble freq. Setting range: 0.0 ~ upper limit freq.
Center freq. of wobble freq. is central value of output freq. when inverter is in
wobble freq. mode. The sum of setting value of F7.7 and F0.1 is actual center
freq.
Running process of wobble freq. is shown as fig6-27.

C300 series of non-sensor current vector-control inverter manual


72 SUNFAR C300

Running freq.

[F7.4] ×Amplitude of wobble freq.

Amplitude of Preset center freq. of wobble freq.


wobble freq.

[F7.7]
[F7.1] [F7.5] [F7.6]

External freq. set by [F0.1]

t
[F7.2]

Fig.6-27 running process of wobble freq.


Running freq.

[F7.4] ×Amplitude of wobble freq.

Amplitude of Preset center freq. of wobble freq.


wobble freq.

[F7.7]
[F7.1] [F7.5] [F7.6]

External freq. set by [F0.1]

t
[F7.2]

6-28 Running process of wobble freq.

F7.8 Reserved

6.9 PID control parameter unit

F8.0 Inner PID control Setting range:0000 ~ 1122


The first part of LED(form right to left): Inner PID control
0:Inner PID control is invalid 1:Inner PID control is valid
2:Inner PID control is conditional valid. Inner PID is set by external terminals X1~
X4 ( Parameters F3.0~F3.3) .
The second part of LED: PID controller selection
0: proportion 1:Integral 2:Proportion and integral
The third part of LED: Regulating property of PID controller
0: positive interaction 1:Reactor
The fourth part of LED: The pole choosing of PID controller
0: Monopole PID control 1: ambipolar PID control
Under the monopole PID control mode, the output phase sequence of inverter is
mono-direction; and the external terminal decides the direction of output that it has
no relation with the output of PID controller. The adjusting effect of PID controller

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 73

only affect the output frequency of inverter. Please refer to fig 6-29.
Monopole PID control applies in water and voltage supply which do not need the
setting of motor’s reversion.
Under the ambipolar PID control mode, when the adjusting effect of PID controller
makes the output frequency as 0, and it has margin between PID setting and
feedback, the output phase sequence and motor’s reversion would change. That is
to say, the external terminal and PID controller decide the motor’s reversion
together under this control mode. Please refer to fig 6-30.

PID feedback

warp limit [F8.9] PID setting

Time

Output frequency
Under monopole PID
control mode, when
output frequency reduces
to o, the direction would not
change.
Time

Fig 6-29 Monopole PID control mode


PID feedback

Warp limit [F8.9]

Time

Output frequency

Under the ambipolar


PID control mode,,the
output frequency would
change the phase
sequence Time

Fig 6-30 Ambipolar PID control mode

F8.1 Inner PID setting and channel selection Setting range:0000 ~ 0504
It is used for setting inner PID and feedback channel.
The first part of LED(form right to left):It is used for setting PID channel .
0:Digital setting. It is set by parameter F8.2.
1:Serials interface setting
2:Panel potentiometer setting, it is on the operation panel.

C300 series of non-sensor current vector-control inverter manual


74 SUNFAR C300

3:External voltage signal VC(0V~10V)。


4:External current signal CC(0~20mA)。
The second part of LED: Reserved.
The third part of LED: It is used for setting PID feedback channel.
0:External voltage input VC is as feedback channel, which is in the range of
0~10V.
1:External current input CC is as feedback channel, which is in the range of
0~20mA.
2:VC+CC Feedback value is composed of VC1 and CC.
3:VC-CC Feedback value is that VC1 minus CC.
4:Min (VC, CC) Feedback value is min value between VC and CC.
5:Max (VC, CC) Feedback value is max value between VC and CC.
The fourth part of LED: Reserved.

F8.2 Inner PID close-loop digital setting Setting range:0.0 ~ 10.00V

If F8.1 is 0#00, setting value will be set by F8.2.

F8.3 Minimum fixed value Setting range:0.0 ~ [F8.4]


F8.4 Maximum fixed value Setting range:[F8.3] ~ 10.00
F8.5 Feedback of minimum fixed value Setting range:0.0 ~ 10.00
F8.6 Feedback of maximum fixed value Setting range:0.0 ~ 10.00
Parameters F8.3 and F8.4 define the upper and lower limit value of PID setting.
Parameters F8.5 and F8.6 define corresponding relation with PID feedback value.
Shown as fig.6-31.
Expected feedback value

[F8.6]

[F8.5]

PID setting value


[F8.3] [F8.4]

Fig.6-31 Relation between PID fixed value and expected feedback value

F8.7 Proportion gain Setting range:0.0 ~ 5.00


F8.8 Integral time constant Setting range:1.0 ~ 100 Sec

Those parameters are inner parameter of PID.

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 75

F8.9 Allowable deviation limit Setting range:0.0 ~ 20.0(%)


The parameter is the allowable deviation value relative to the setting max value.
When the difference between feedback value and the setting value is lower than
this setting value, PID controller will stop. Shown as fig.6-32.
This function is mainly suited to the system that has lower control precision and
needs to avoid adjusting frequently, for example, water-supply with constant
pressure system.
f PID action
PID feedback

[F8.9]

PID setting
PID action
t

Fig.6-32 PID Control allowable deviation limit

F8.10 Preset freq. for close-loop Setting range:0.00 ~ the upper limit freq.
F8.11 Holding time of preset freq. for close-loop Setting range:0.0 ~ 6000.0s
Those parameters define freq. and running time of inverter before actual PID
control is valid. In some control systems, inverters will forcible output a certain freq.
(F8.10) and keep it in setting time (F8.11) for controlled object arrives fast targeted
value. When controlled object almost arrives targeted value, PID controller will be
valid to improve response speed.

F8.12 Sleeping threshold Setting range: 0.0 ~ 10.0

It defines feedback value while inverter goes to sleep state. When actual feedback
value is bigger than setting value and inverter arrives lower limit value, the inverter
will go sleep. Shown as fig.6-33

F8.13 Awakening threshold Setting range:0.00 ~ 10.00


It defines feedback value while inverter goes to work state from sleep state.
When actual feedback value is lower than setting value, the inverter will start to
work. Shown as fig.6-33

C300 series of non-sensor current vector-control inverter manual


76 SUNFAR C300

PID feedback

[F8.11 ] Sleeping thres hold

PID Setting
[F8.13 ]
Awakening threshold
Output freq

The lower limit


freq [F0.7]

sleep awake
5 minute 5 minute

Fig.6-33 PID contro sleeping and awakening function

F8.14 Reserved

6.10 Communication function parameter units


F9.0 Communication setting Setting range:0000 ~ 0025
The first part of LED(form right to left): It is used for setting characteristics of
relating to communication.
0: Reserved 1:1200bps 2: 2400bps
3: 4800bps 4: 9600bps 5: 19200bps
To make sure both sides have the same baud rate, when client use serials
communication.
The second part of LED: To set data format of serials communication.
0:Close 1: Even 2:Odd
To make sure both sides have the same data format, when client use serials
communication.
The third and fourth part of LED: Reserved.
F9.1 Local address Setting range:0 ~ 30

F9.2 Response time of machine itself Setting range:0 ~ 1000 ms


It defines waiting time, which is the time from local receives correctly code to send
response data frames.

F9.3 Setting of communication Auxiliary function Setting range:0000 ~ 2011


The first part of LED(form right to left):
0: The inverter is slave 1: The inverter is master
The second part of LED: Act selection after communication is lost
0: Stop 1:Keep
The third part of LED: Reserved.

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 77

The fourth part of LED: communication protocol selection.

F9.4 Checkout time of communication overtime


Setting
If the local dosen’t receive data signals correctly range:0.0
in defined time~ interval,
100.0 Secthe
communication is fault. Inverter will keep on running or stopping according to
setting of parameter F9.3.

F9.5 Linkage setting proportion Setting range: 0.01 ~ 10.00


F9.6 Rectify channel of linkage setting proportion Setting range: 0 ~ 4

It is used for setting proportion of output freq. between Master and Slave, when
takes linkage setting control.
When F9.6 is 0, rectify channel of linkage setting proportion is invalid.
Slave freq. = Master freq.× [F9.5]
When F9.6 is 1, 2,3 or 4, rectify channel of linkage setting proportion is valid.
Slave freq. = Master freq.× [F9.5]×value of rectify channel or the max value of
rectify channel
F9.6 is used for selecting rectify channel.
Rectify channel 1:Panel potentiometer
Rectify channel 2:External voltage signal VC(0 ~ 10V)
Rectify channel 3:External current signal CC(0 ~ 20mA)

F9.7 Reserved

6.11 Special function parameter unit

FC.0 Under voltage protection level Setting range: 360V ~ 460V


It defines lower limit voltage which terminals P+ and P- are allow while inverter is
working normally. For some low voltage conditions, user can decrease under
voltage protection level to ensure that inverter is running normally.

FC.1 Over voltage limit level Setting range: 660V ~ 760V


It defines threshold of voltage stall protection while motor is decelerating. If DC
voltage caused by decelerating is beyond setting value of FC.1, deceleration time
will automatic prolong. Shown as fig6-34.

C300 series of non-sensor current vector-control inverter manual


78 SUNFAR C300

Adjust Dec time

DC voltage t

[FC.1]

t
Fig.6-34 voltage stall protection in Dec speed

FC.2 Current amplitude limiting level Setting range: 150 ~ 200%


It defines the maximum output current which is permitted by inverter. Whatever the
operation mode is, inverter will adjust output freq. to inhibit current within the range
of regulation, when output current of inverter is beyond setting value of FC.2.

FC.3 Reserved

FC.4 Running protection function setting Setting range: 0000 ~ 9999

It is used for setting some coefficients with special function in running process.
Generally, user needn’t set.
The first part of LED(form right to left): Under voltage compensation intensity
The second part of LED: Over voltage inhibit intensity
The third part of LED: Over current inhibit intensity
The fourth part of LED:Self-adapting braking torque adjust intensity

FC.5 Action function selection Setting range: 0000 ~ 0111


The first part of LED(form right to left): Cooling fan control
0:Cooling fan run after inverter run.
Cooling fan will stop after inverter stop. When temperature is above 40℃,the
cooling fan also will also run.
1:Cooling fan will automatic run when inverter is power on.
The second part of LED: Variable speed control of cooling fan
0:Invalid
1:Valid
Cooling fan always keep the max speed.
The third part of LED: Voltage over modulation
0:Invalid 1:Valid

FC.6 Reserved

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 79

FC.7 Reserved

FC.8 Agency password Setting range: 0~ 9999

They are closed loop control parameters about rotational speed and used to set.

FC.9 Rotational speed coefficient Setting range: 0.10 ~ 5.00


FC.10 Gain of closed loop of rotational speed Setting range: 0.50 ~ 1.20
FC.11 Integral time constants of closed loop of rotational speed
Setting range:0.10 ~ 10.00
Arithmetic of vector control. Generally, they need modify by professional person.

FC.12 Compensation rectify of dead zone Setting range: 0 ~ 25

It is read-only parameter for user. Rectify coefficient of dead zone can be modify by
parameter F1.20 only.

FC.13 Program version Range: 2000 ~ 2099


It is read-only parameter.

C300 series of non-sensor current vector-control inverter manual


80 SUNFAR C300

7. FAULT DIAGNOSIS AND COUNTERMEASURES

7.1 Protective functions and Countermeasures

Code Faults Probable Causes Solutions

1. Acceleration time is too 1.Prolong the acceleration


short. time
2. V/F curve is not suitable. 2. Descend the torque boost
3. You hasn’t set the right or adjust the V/F curve
motor parameters 3.Input motor’s parameter once
4. User start rotating motor again and do self-determination
over-current during to parameter.
Fu.1 directly, but doesn’t set
Acc
function of detecting speed 4.To set function of detecting
and restart. speed and restart.
5. Value of torque boost set 5.To decrease voltage of torque
too high. boost
6. Power grid voltage is too 6. Check power gird voltage,
low and reduce power then use
over-current
Fu.2 Deceleration time is too short. Prolong the deceleration time
during Dec
1. Decrease power supply
Over-current during 1.Load occurs mutation load fluctuation
Fu.3
Running or stopping 2.Power grid voltage is too low 2.Check voltage.

1.Check power supply voltage


1.Input voltage is too high 2.Decrease setting value of
over-voltage
Fu.4 2. Power supply is switched F4.11
during Acc
on or off frequently. 3.Control the on-off of inverter
by the control terminal
1.Extend the deceleration time
1.Deceleration time is too
over-voltage 2.Check power supply voltage
Fu.5 short.
during Dec 3.Install or select the brake
2.Input-voltage is abnormal
resistance
1.Power supply is abnormal
over-voltage 1.Check power supply
Fu.6 2.There are energy feedback
during running 2.Install or select brake resistor
load
over-voltage
Fu.7 Power supply is abnormal Check power supply voltage
during stop

1. Power supply is abnormal2. 1.Check power supply voltage


Fu.8 Under-voltage
There is great fluctuation of 2.Provide the power supply
during running
load in electric network. separately
1. Check wiring
1. Output is short-circuit or
protective action of ground 2. Reduce the load
Fu.9
inverterr 3. Check whether brake resistor
2. Load is too heavy
is short-circuit

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 81

1.The output terminal


of inverter grounds 1. Check the connecting wire
Output grounding 2. The wire is too long 2. Shorten the connection wire
Fu.10 or
(Reserved) between inverter and motor
and the carrier frequency is reduce the carrier frequency.
too high.
Fault action caused by
Add absorb circuit around
Fu.11 Interfere of inverter disturbance of
inverter
electromagnetism
1. Load is too heavy. 1.Reduce the load or replace
2. Acceleration time is with higher capacity inverter.
too short. 2. Prolong Acc time.
3. Torque boost is too high 3. Decrease the torque boost or
or V/F curve is not suitable. adjusting V/F curve.
Fu.12 Inverter over-loading 4. Check Voltage of Power
4. Voltage of Power supply is
too low supply
5. User starts rotating motor 5. To set function of detect
but doesn’t set function of speed
detecting speed and restart. and restart

1. Load is too heavy. 1. Reduce the load


2. Acceleration time is too 2. Prolong Acc time
short. 3. Increase the over-loading
Fu.13 Motor over-loading 3. The setting of protection protection factor of motor
factor is too small [F4.13])
4.Torque boost is too high or4. Decrease torque boost
V/F curve is not suitable. voltage and adjust V/F curve.
1. Clear air duct or improve the
1. Wind hole is blocked air condition.
Fu.14 Inverter overheat 2. Environmental temperature 2. Improve ventilation condition
is too high or decrease carrier frequency.
3. Fan is damaged 3. Replace fan.

Fu.15 Reserved

External equipment There is signal input on the Check the signal source and
Fu.16 failure peripheral. Equipment fault the
input terminal of Inverter pertinent equipments.
Inverter output
Fu.17 Inverter output lack phase Check the wire of applied motor.
lack phase
Fu.18 Reserved
1. Power supply is too low 1. Check power supply
2. Contactor is damaged. 2. Replace contactor
Main contactor of
Fu.19 3. Starting resistance is 3. Replace starting
inverter is poor contact
damaged. resistance.
4. Control circuit is damaged. 4. Contract Us
1.The current detecting
Current equipment or circuit is
Fu.20 damaged Contract Us
checking error 2.Auxiliary power supply has
problem

C300 series of non-sensor current vector-control inverter manual


82 SUNFAR C300

1. Signal line of temperature is


poor contact 1. Check jack
Fu.21 Temperature sensor
ococcur faults 2. Temperature sensor is 2. Contract Us
damage.
Fu.22-
Reserved
Fu.29
1. Checking the motor
nameplate, and input the right
1. The nameplate parameter
parameter.( [F1.15]~
what you have input is
[F1.18] )
Inverter can not check the wrong.
2. Make sure to do
Fu.30 motor parameter 2. Doing self-detection before
self-detection before stopping
normally. stopping.
the motor.
3. The connection of motor and
3. Check the connection cable
inverter is wrong.
of
motor.
1. The motor parameter is
1. Check the motor lines.
abnormal.
Fu.31 U phase motor parameters 2. Doing the self-detection of
are abnormal. 2. The self-detection of motor
otor parameter once again.
parameter is failed.
V phase motor parameters
are abnormal. 1. The motor parameter is
1. Check the motor lines.
abnormal.
Fu.32 Phase motor parameters 2. Doing the self-detection of
are abnormal. 2. The self-detection of motor
motor parameter once again.
phase motor parameters is parameter is failed.
abnormal.
1. The motor parameter is
1. Check the motor lines.
abnormal.
Fu.33 W phase motor 2.Doing the self-detection of
parameters are abnormal. 2. The self-detection of motor
motor parameter once again.
parameter is failed.
Fu.34-
Reserved
Fu.39

Inner data of storage is Read and write errors of the


Fu.40 Contract Us
wrong. control parameter

7.2 Fault record inquiry


C300 series inverter records the last six fault codes and the output parameters of
last fault. This information is aid in looking up the fault causes. Fault information and
State monitor parameters are stored uniformly, so please refer to the operation way
to look up the information.

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 83

Monitor Item Contents Monitor Item Contents


d-26 First fault record d-32 Output frequency of last fault
d-27 Second fault record d-33 Setting frequency of last fault
d-28 Third fault record d-34 Output current of last fault
d-29 Fourth fault record d-35 Output voltage of last fault

d-30 Fifth fault record d-36 DC voltage of last fault

d-31 Sixth fault record d-37 Module temperature of last fault

7.3 Reset
⑴ Be sure to check the fault cause and exclude it before reset, otherwise, which may lead
to the permanent damage for the inverter
⑵ If the inverter can not be reset or occur the fault again after reset, please find out the
reason. Continuous reset will damage the inverter
⑶ Over-load or over-heat protective action should delay 5 minutes to reset.

I. When the inverter happens to the fault, you can reset the inverter to resume
the normal running by any way as follows:
II. External reset input-terminal RST and GND terminal are closed, and then off.
III. While the fault code is displayed, press key.
IV. It will send fault reset instrument by RS485 interface.
V. Turn the power source off.

C300 series of non-sensor current vector-control inverter manual


84 SUNFAR C300

8.MAINTENANCE
As a result of ambient temperature, humidity, dust, vibration and aging of internal
components of inverter, the inverter will probably appear the potential problem
during running. In order to ensure the inverter to run steadily for a long time, the
inverter should be checked up once at 3 to 6 months.

¾ First of all, turn the inverter’s power off. And professional worker performs
maintenance.

8.1 Daily Maintenance


maintenance points:

Inspection Time Inspection


Criterion
items contents
Daily Periodic
1.When temperature is over 40℃, the
1.Temperature, panel should be open. Humidity is
Running less than 90%, and
√ Humidity
Environment no condensation
2.Dust, gases 2. No peculiar smell,no flammable
and explosive gases.

1.Installation environment is well


1.Installation ventilated, and the duct is not
Cooling Environment blocked.

system
2. Fan in inverter 2.Fan is normal and no abnormal
voice.
1. Vibration smooth, the temperature
1.Vibration, of air outlet is normal.
Temperature raise
Inverter √ 2. Noises 2.Not abnormal voice and no peculiar
smell
3. Wire、Terminal
3. Fastening screw is not loosed.
1.Vibration,
1. Running smooth, and temperature
Motor √ Temperature raise
is normal
2. Noises

Input/output 1. Input voltage 1. Input-voltage is in the setup range


√ 2. Output-current is under the rated
Parameters 2. Output current value

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 85

input voltage Moving-coil voltmeter


Output voltage Rectifier-type voltmeter
O/I current Tong-type ammeter

⑴ Inverter has done the electric insulating experiment before leave-factory, so


user don’t need to do the withstand voltage test.
⑵ Do the insulation test to the inverter if necessary, all of I/O terminals must be
connected in short-circuit (R, S, T,L1,L2, U, V, W, P, P-, PB). Strictly
prohibited from doing the insulation test for the single terminal. Please use
500V Meg-ohmmeter to perform this test.
⑶ Control circuit can not be used the Meg-ohmmeter to test.
⑷ For insulation test to motor, the connection wire between motor and inverter
should be disassembled.

8.2 Damageable parts maintenance


Some cells in inverter are worn out or the performance descends in the process of
usage process, in order to ensure the stable running of inverter, so the inverter
needs to do the preventative maintenance or replace the part if necessary
⑴ Filter capacitor
Pulse current in main circuit will take effect on the performance of aluminum
electrolytic filter capacitor, and the degree of effect has relation with the ambient
temperature and usage condition. In normal condition, the electrolytic capacitor of
inverter should be replaced at 4 to 5 years.
When the electrolytic capacitor leaks out, safety valve falls out or main block of
capacitor expands, the corresponding parts should be replaced immediately.
⑵ Cooling fan
The lifetime of all the cooling fans in the inverter is about 15000 hours (that inverter
is used continuously about two years). If the fan occurs the abnormal noise or
vibration, it should be replaced immediately.

8.3 Storage
If the inverter don’t used for a long time, please notice the following items:
⑴ To avoid storing the inverter at the environment with high-temperature,humidity,
vibration or metal dust, and ensure the well ventilation.
⑵ If the inverter is not used for a long time, it should be energized to resume the
capability of electrolyte capacitor once at 2 years,at the same time, check the

C300 series of non-sensor current vector-control inverter manual


86 SUNFAR C300

functions of inverter. When the inverter is electrified, its voltage should be increased
by an autotransformer step by step and the time should not be less than 5 hours.

¾ If inverter is not used for a long time, the performance of internal filter
capacitor will descend.

8.4 After sale services


Guarantee time of this inverter is 18 months (From the day of purchase).
In guarantee Time, if the inverter occurs fault or be damaged in normal usage, our
company will provide the free repair service or replacement.

Guarantee scale is just the master of inverter.

In guarantee time, if the faults are caused by the following cases, certain service
cost would be charged.
① Malfunction is caused by not following the operation manual or over using the
standard specification;
② Malfunction is caused by repairing without admision.
③ Malfunction is caused by the bad-storage.
④ Malfunction is due to application of inverter for abnormal functional needs.
⑤ Damage is caused by fire, salt-corrode, gas-corrode, earthquake, storm, flood,
lightning strike, voltage abnormal or other force majored.
Even if over guarantee time, our company will provide the paid service forever.

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 87

9. USAGE EXAMPLE

9.1 Panel on-off control, Panel potentiometer setting frequency


and V/F control methods

9.1.1 Initial settings


1. When F0.0 is 0, V/F method is valid.
2. When F0.4 is 00#0, panel control is valid.
3. When F0.1 is 3, panel potentiometer is valid.

9.1.2 Basic wiring

3-phase Breaker Motor


× R U
Power
Supply × S V M
× T W
E

AVO Voltmeter (0~10V)

GND

Fig9-1 Basic wiring

9.1.3 Operation Notes:


Press key to start the inverter, and then rotate the button of panel
potentiometer in clockwise to increase setting frequency step by step. Contrarily,
rotate in anti-clockwise to decrease setting frequency step by step.
Press key to stop the inverter.

External control terminal FWD decides the running direction of motor.

C300 series of non-sensor current vector-control inverter manual


88 SUNFAR C300

9.2 External control mode, external voltage setting frequency and


V/F control
9.2.1 Initial settings
1. When F0.0 is 0, V/F method is valid.
2. When F0.4 is 00#1, external terminals control is valid.
3. Setting X1-X3 are Multi-speed control terminals ([F3.0]~[F3.2])。
4. Setting each speed running frequency([F5.1]~[F5.7])。

9.2.2 Basic wiring


3-phase Breaker
Motor
Power × R U
supply × S V M
× T W
E

FWD FWD
REV REV
GND
X1
Multi-speed Voltmeter(0~10V)
X2 AVO
control terminals
X3
GND

Fig9-2 Basic wiring

9.2.3 Operation Notes:


FWD-GND is off,the motor will running forward. REV- GND is off, the motor will
running backward. FWD-GND and REV-GND are off or on at the same time, the
inverter will stop.
If X1, X2 and X3 are all opened with CM, the multi-speed running is invalid. The
inverter will run as the setting instruction speed. (The setting frequency channel is
selected by parameter F0.1)
If one terminal or all of X1, X2 and X3are connected with GND terminal, the inverter
will run as the multi-speed frequency selected by X1, X2 and X3.

Control method of terminals FWD and REV is set by parameter F0.5.(See


the explanation about parameter F0.5.)

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 89

9.3 Multi-speed running, external control mode and V/F control


9.3.1 Initial settings
1. When F0.0 is 1, Sensorless current vector-control is valid.
2. Setting parameters F1.15]~[F1.18] according to match motor’s rate nameplate
data
3. When set [F0.1] =1,and UP/DW Acc and Dec control.
4. Setting start and stop control is panel control([F0.4]=00#0).
5. Using Parameters self-determination to determine motor’s parameters.
6. Setting UP/DW terminal:select X1、X2 for UP/DW terminal. corresponding to
parameters settings are :
[F3.0]=13(X1 is UP terminal)
[F3.1]=14(X2 is DW terminal)

9.3.2 Basic wiring


3-phase Breaker
Motor
Power × R U
supply × S V M
× T W
E

Freq. ascending X1
Freq. descend X2
GND

AVO Voltmeter(0~10V)

GND

Fig9-3 Basic wiring

9.3.3 Operation Notes:


1. Motor’s nameplate parameters must be set before inverter run, sometime
parameters self-determination is necessary.
2. Press key start inverter, press key next time stop inverter.
3. When X1 terminal is connected, output freq. will ascend; when X2 terminal is
connected, output freq. will descend.

C300 series of non-sensor current vector-control inverter manual


90 SUNFAR C300

9.4 Panel on-off control,Panel potentiometer setting frequency


and linkage control with inverters

9.4.1 Initial settings


Console setting:
1. Freq. setting channel is panel potentiometer mode. Namely F0.1 is 3.
2. Operation channel selection is panel control, namely F0.4 is 00#0.
3. Communication setting (Parameter F9.0) is default.
4. If F9.3 is 0001, the inverter is console.
Slave setting:
1. Freq. setting channel is RS485 interface. Namely F0.1 is 2.
2. Operation channel selection isRS485 interface. Namely F0.4 is 00#2.
3. Communication setting (Parameter F9.0) is default.
4. If F9.3 is 0000, the inverter is slave.
5. Linkage setting proportion (Parameter F9.5) will be set by user needs.
6. Rectify channel of linkage setting proportion is external voltage signal VC.
Namely F9.6 is 2
9.4.2 Basic wiring
9.4.3 Operation Notes:
Running freq. of slave has a certain proportion with console. Linkage setting
proportion is set by parameter F9.5.
In this example, freq. proportion of console and slaves can get across by VC
channel.

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 91

3-Phase Breaker
Motor
Power × R U
supply × S V M
× T W
E

Host

A
RS485
B

3-Phase Breaker
Motor
Power × R U
supply × S V M
× T W

Guest

+5V
VC
A
GND
RS485
B

3-Phase Breaker
Motor
× R U
Power
supply × S V M
× T W

Guest
+5V
VC
GND A
RS485
B

Fig9-4 Basic wiring

9.5 PLC controls the startup and stop of inverter and 3-speed
operation
9.5.1 The brief introduction of example control function:
Through a simple example of PLC control inverter, the inverter achieves the aim of
integration with system under providing a typical control method. The control
approaches are as follows: 1, through terminal X0 to startup the running of inverter,
2, through terminal X5 to stop the running of inverter, 3, through the switching on
terminal X1, X2 and X3 which respectively correspond to 10Hz, 20Hz, 50Hz, and

C300 series of non-sensor current vector-control inverter manual


92 SUNFAR C300

the output frequency is invalid ( the output frequency is 0 ) if these terminals switch
on simultaneously.
9.5.2 The system configuration:
Main site: MITSUBISHI PLC Model: FX2N-16MR-001
Subordinative site: C300-2S0022 series of inverter
9.5.3 The connection of master and slave hardware:
SUNFAR inverter uses crystal pin telephone line to connect PLC, using RS485.
Please refer to the following fig9-5.

水晶插座
+ + + - - - RDA RDB SDA SDB SG

Fig 9-5 Wiring method

9.5.4 The master control wiring diagram of SUNFAR inverter and PLC:

Three- R S T
phase stop X5
power grid Speed
FX2N
3 X3
Speed
2 X2
Speed FX2N RDA C300
1 X1 -485
start X0 -BD RDB

COM +
-
L

N U V W

M
Fig 9-6 Main circuit wiring

9.5.5 The slave setting:


1, The channels of output frequency: communication interface(F0.1=2)

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 93

2, The channels of running command: communication interface(F0.4=00#2)


3, Communication setting F9.0 is default
4, Communication auxiliary function configuration F9.3=000: the inverter is slave.

9.5.6 Operation Notes:


PLC controls the running of inverter when terminal X0 is on.
The running speed of inverter is 10Hz when terminal X1 is on.
The running speed of inverter is 20Hz when terminal X2 is on.
The running speed of inverter is 500Hz when terminal X3 is on.
The inverter would stop when terminal X5 is on.

9.5.7 Master PLC trapezoidal chart:

M 8000
(M 8161)
[M O V H 0C 87 D 8120]
X 000 X 005 M 10 [R S D 100 K 15 D 485 K 33]
(T10)
T 10
3 (M 10)
M 10
6 [S E T M 8 1 2 2 ]
[ FM O V K 0 D 100 K 15 ]
X 000 M 8012
7 [ FM O V K 0 D 550 K 25]
M 8000
6 [M O V H 5A D 100]
[M O V H 4 D 103 ]
[M O V H 11 D 105]
[M O V H 0D D 114]

[M O V D 516 K 2M 160]
[M O V D 515 K 2M 168 ]
[M O V K 4M 160 D 530 ]
X 001 X 002 X 003
2 [M O V H 3 D 108 ]
[ M O V H 0E 8 D 109 ]
X 002 X 001 X 003
5 [M O V H 7 D 108 ]

X 002 [ M O V H 0D 0 D 109 ]
X 003 X 001
8 [M O V H 13 D 108 ]

M 8123 [ M O V H 88 D 109 ]
[M O V K 0 D 520]
[A D D D 505 D 520 D 520 ]
[A D D D 508 D 520 D 520 ]
[A D D D 511 D 520 D 520 ]

M 8123 [A D D D 512 D 520 D 520]


[C M P D 530 D 520 M 0]
M 1
[B M O V D 500 D 550 K 18 ]
[Z R S T M 0 M 2 ]
[R S T M 8123 ]
M 8122
[D M O V K 0 D 213 ]
[A D D A 103 D 213 D 213 ]
[A D D D 105 D 213 D 213 ]
[A D D D 108 D 213 D 213 ]
[A D D D 109 D 213 D 213 ]
[M O V D 213 K 4M 100 ]
[M O V K 2 M 1 0 8 D 1 1 2 ]
[M O V K 2M 100 D 113 ]
[E N D ]

Fig 9-7 Master PLC trapezoidal chart

C300 series of non-sensor current vector-control inverter manual


94 SUNFAR C300

AppendixⅠRS485 COMMUNICATION PROTOCOL

1. Summary
C300 series of inverter provides RS485 interface, users can carry out centralized
monitoring through PC/PLC to get operating requirements. The protocol in this
appendix is designed for the above functions.

1.1. About protocol


This serial communication protocol defines the transmission information and use
format in the series communication and it includes master-polling (or broadcasting)
format, master coding method and the content includes function code of action,
transferring data and error checking. The response of slave is the same structure,
and it includes action confirmation, returning the data and error checking etc. If
slave takes place the error while it is receiving the information or cannot finish the
action demanded by master, it will send one fault signal to master as a response.

1.2. Application scope


1.2.1. Application products
The protocol is fit for all sunfar series of inverters, for example C300, C320, E380
series of inverter, and some other inverters.
1.2.2. Application methods
(1) The inverter will be connected into a “Single-master Multi-slave ” PC/PLC
control net with RS485 bus.
( 2 ) The inverter will be connected into a “Point to Point” PC/PLC monitor
background.

2. BUS structure and protocol description


2.1. BUS structure
(1)Interface mode
There provide RS485 interface and RS232 interface, but RS232 interface need the
level translation accessories.
(2)Transmission mode
There provide asynchronous series and half-duplex transmission mode. At the
same time, just one can send the data and the other only receives the data between
master and slave. In the series asynchronous communication, the data is sent out
frame by frame in the form of message.
(3)Topological mode

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 95

In Single-master system, there are 32 sites at most. There are one master site and
31 slave sites among these sites. The address range of slave is 0~30, 31 (1FH) is
broadcast communication address. The address of slave must is exclusive in the
network. Point to point mode is a special application of single master and
multi-slaves mode. That is one condition of one slave machine.

2.2. Protocol description


C300 series inverter communication protocol is a kind of serial master-slave
communication protocol, in the network, only one equipment, and master can build
a protocol, (Named as “Inquire/Command”). Other equipments, slaves response
“Inquire/Command” of master only by providing the data or doing the action
according to the master’s “Inquiry/Command”. Here, master is Personnel Computer,
Industrial Machine or Programmable logical controller, and the slave is inverter.
Master not only visits some slave, but also sends the broadcast information to all
the slaves. For the single master “Inquiry/Command”, all of slaves will return a
signal that is a response; for the broadcast information provided by master, slave
needs not feedback a response to master machine.
2.2.1 Data format
3 kinds of data transmission format are optional:
⑴ 1 bit start-bit, 8-bit data bits, 1 bit stop-bit and no check bit.
⑵ 1 bit start-bit , 8-bit data bits, 1 bit stop-bit and odd check.
⑶ 1 bit start-bit , 8-bit data bits, 1 bit stop bit and even check. It is also manufacture
setting.
2.2.2Baud rate
There are five kinds of baud rate, 1200bps, 2400 bps, 4800 bps, 9600 bps and
19200 bps.
2.2.3Communication mode
(1) Point to point communication mode, which is master “Polling” and slave
“Responding”.
(2) Setting the serial interface communication parameters by the keypad of
inverter. These parameters include local address, baud rate and data format.

Master must set the same baud rate and data format of inverter

2.2.4Communication rule
(1) There are at least 5-byte startup interval time between data frames, only the

C300 series of non-sensor current vector-control inverter manual


96 SUNFAR C300

message with the stated startup internal time is valid.


(2) The waiting time of master, with the longest responding time of inverter is
8-byte input time. If not, determined as a failure.
(3) If inverter doesn’t receive any message during setting time of F9.4, it will be
occurred the wire-break fault. Running state of slaves is decided by setting
value of F9.3.

2.3 Message structure


The length of each message is between 11 and 18 bytes. The type of character are
ASCⅡ code and hex.

(1) 3800H is shown as ASCⅡ code.

Data list 9 10 11 12
Setting Setting Setting Setting
Data Data Data Data
Data(ASCⅡ) 33 38 30 30

(2) 3800H is shown as hex.

Data list 9 10 11 12
Setting Setting Setting Setting
Data Data Data Data
Data(Hex)
0 0 38 00

2.3.1 Master command frame


Sending Sequence Definition Sending Sequence Definition
0 Header 9 Setting data
1 Slave addr. 10 Setting data
Slave addr. Data area
2 Slave addr 11 Setting data
3 Type of order 12 Setting data
4 Operation order Order area 13 Check sum
5 Operation order 14 Check sum
Check area
6 Type of data 15 Check sum
7 Data addr. Addr. area 16 Check sum
8 Data addr. 17 Tail 0DH

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 97

2.4 Slave responding frame


Sending Sequence Definition Sending Sequence Definition
0 Header 9 Running data
1 Slave addr. 10 Running data
Slave addr. Data area
2 Slave addr 11 Running data
3 Slave 12 Running data
Responding
4 Operation order 13 Check sum
area
5 Operation order 14 Check sum
Check area
6 Type of data 15 Check sum
7 Data addr. Address area 16 Check sum
8 Data addr. 17 Tail 0DH

2.4.1 Header
This communication protocol defines that both 2AH (ASCⅡ code of character and
5AH are available. When header is 2AH, all of data behind header is ASCⅡ code.
When header is 5AH, all of data behind header is hex code and invalid byte fill 0.
Unaided headers of 2AH and 5AH aren’t rightful header. There need waiting time
above five bytes before sending header.
2.4.2 Slave address
Slave address is inverter address. The address range of slave machine is 0~30, 31
(1FH) is broadcast communication address.
2.4.3 Type of order

Type of order is only in master command frame and defines task of the data in this
frame. Length of each frame is different according to different order. Type of order is
shown as following table.

Data Operation
0 Read the state and information of slaves
1 Read the running parameter of slaves
2 Read code parameter
3 Modify code parameter in RAM, it will not save after power down
4 Send control order
5 Modify code parameter in EPROM, it will save after power down
6~F Reserved

2.4.4 Operation order


Master gives a control order to slaves. It exists in all messages and is shown as

C300 series of non-sensor current vector-control inverter manual


98 SUNFAR C300

following table.
Data Operation Data Operation
00H Invalid instrument 10H To set running freq. of slave
01H Start with FWD 11H Start with FWD and setting freq.
02H Start with REV 12H Start with REV and setting freq.
03H Stop 13H Stop with Start setting freq.
Slave will FWD running Slave will FWD running with setting
04H 14H
when jog freq. when jog
Slave will REV running Slave will REV running with setting freq.
05H 15H
when jog when jog
06H Jog running is stop 16H Slave will JOG running with setting freq.
… … … …
20H Slave will fault reset 30H Reserved
21H Slave will emergency stop 31H Reserved

When user need not send operation order, please send invalid order 00H.

2.4.5 Slave responding


Slave responding exists in all messages and is shown as following table.
Data Definition Data Definition
Data received form master is beyond the
0 Slave receive data and works well 1
permission range
When slave is running, data can’t be If modify the data, please input password
2 3
modified
4 To try read and write parameter 5 Reserved
6 Appointed code or addr. Is invalid 7 It exist invalid ASCⅡ code in message
Type of order or operation order is Reserved
8 9~F
invalid

¾ When data of slave responding is 6, 7 or 8, length of responding frame is


11 bytes.

Its frame format is shown as following.


0 1 2 3 4 5 6 7 8 9 10
Slave
responding Slave Slave Slave Check Check Check Check
0 0 Tail
Header address address responding Sum Sum Sum sum
Definition Slave address Order/responding area Check area 0DH

2.4.6 State feedback

Slave gives a running state about slave to master, and state feedback exists in all
messages. It is shown as following table.

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 99

Data Operation Data Operation


DC voltage of slave is not
00H 10H Reserved
ready
01H Slave is FWD running 11H Accelerating with FWD
02H Slave is REV running 12H Accelerating with REV
03H Slave is stop 13H Abruptly stop and restart
Slave will FWD running when
04H 14H Decelerating with FED
jog
Slave will REV running when
05H 15H Decelerating with REV
jog
06H Reserved 16H Slave is in DC braking state.
… … … …
20H Slave is in fault state 21H Slave is emergency

When slave occurs fault (data of state feedback is 20H), the seventh and eighth
of feedback rata frame is fault code.

2.4.7 Check sum


The sum of ASCⅡor hex form slave address to setting data (running data) is check
sum.
2.4.8 Frame Tail
0DH is hex, namely ASCⅡof CR is 0DH.

3. Description about frame format

When header, tail and check sum in message occur fault form master, slave may
b t di

(1) OrderⅠ is read state and information about slaves

0 1 2 3 4 5 6 7 8 9 10 11 12 13
Master
Sending
Slave Slave Operation Operation Data Check Check Check Check
Header 0 0 0 Tail
addr. addr. order order Type Sum Sum Sum Sum

C300 series of non-sensor current vector-control inverter manual


100 SUNFAR C300

Slave responding Sending Sequence


0 Header 9 Character information
1 Slave addr. 10 Character information
2 Slave addr 11 Character information
3 Slave responding 12 Character information
4 State feedback 13 Check sum
5 State feedback 14 Check sum
6 Data type 15 Check sum
7 Character information 16 Check sum
8 Character information. 17 Tail
Slave will give different characters information to master according to different data
type in master message.

Data Type (master sending) Character information (slave responding)


6 7 8 9 10 11 12
Read slave inf. about Voltage
0 0 Power Power Power Power
inverter model level
Read slave inf. about
1 Reserved Reserved Reserved Reserved Reserved Reserved
inverter series
Read slave inf. about
2 Reserved Reserved # # # #
program version
Read slave inf. about Master Setting freq.
3 Reserved Reserved Reserved Reserved
control information control of master
4~F Reserved # # # # # #

For example, if data type is 0, slave return 400185. 4 mean voltage level. 0 means
Character information. 0185 means power, 18.5Kw.

(2) OrderⅡis used for reading running parameter of slave


0 1 2 3 4 5 6 7 8 9 10 11 12 13

Master
Sending Slave Slave Operation Operation Data Data Check Check Check Check
Header 1 0 Tail
addr. addr. order order subentry subentry Sum Sum Sum Sum

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 101

Slave responding Sending Sequence


0 Header 9 Running data
1 Slave addr. 10 Running data
2 Slave addr. 11 Running data
3 Slave responding 12 Running data
4 State feedback 13 Check sum
5 State feedback 14 Check sum
6 0 15 Check sum
7 Data subentry 16 Check sum
8 Data subentry 17 Tail

Data subentry is state monitor parameters, shown as following table.


Monitor item Data subentry Returning data form slave
d-0 00 Output frequent
d-1 01 Output current
. . .
. . .
. . .
d-15 15 External pulse input
. . .
. . .
. . .
d-37 37 Temperature of module of last fault

¾ Refer to the explanation about state monitor parameter in the fourth chapter.

(3)Order Ⅲ is read parameters of code.

0 1 2 3 4 5 6 7 8 9 10 11 12 13
Master
Sending Subordi Subordi
Operation Operation Data Data Data Check Check Check Check
Header nation nation 2 Tail
order order type Addr. Addr. sum sum sum sum
addr. addr.

Slave responding Sending Sequence


0 Header 9 Parameter data
1 Slave addr. 10 Parameter data
2 Slave addr 11 Parameter data
3 Slave responding 12 Parameter data
4 State feedback 13 Check sum
5 State feedback 14 Check sum
6 Data type 15 Check sum

C300 series of non-sensor current vector-control inverter manual


102 SUNFAR C300

7 Data addr. 16 Check sum


8 Data addr. 17 Tail

¾ Data type and data address are defined in order Ⅳ and Ⅵ.

(4)order Ⅳ is used for modifying parameter of code in RAM.


order Ⅵis used for modifying parameter of code in EPROM.

Master Sending Sending Sequence


0 Header 9 Setting data
1 Slave addr. 10 Setting data

2 Slave addr 11 Setting data


3 3 or 5 12 Setting data

4 Operation order 13 Check sum

5 Operation order 14 Check sum

6 Data type 15 Check sum


7 Data addr. 16 Check sum
8 Data addr. 17 Tail

Slave responding Sending Sequence


0 Header 9 Setting data
1 Slave addr. 10 Setting data
2 Slave addr 11 Setting data
3 Slave responding 12 Setting data
4 State feedback 13 Check sum
5 State feedback 14 Check sum
6 Data type 15 Check sum
7 Data addr. 16 Check sum
8 Data addr. 17 Tail
Data type is shown as following table.

Parameter
F0 F1 F2 F3 F4 F5 F6 F7 F8 F9 FC FE FF FH FL FP
unit
Data
0 1 2 3 4 5 6 7 8 9 A B C D E F
type

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 103

For example, data address of F0.8, F1.8 and F#.8 are 8. But data type of them is
different.
Attention:When slaves don’t accomplish order form master, setting data is
0000.
(5)OrderⅤis used for sending control order.
It is fit for routine operation for inverter.

Master Sending Sending Sequence


0 Header 8 Setting data
1 Slave addr. 9 Setting data
2 Slave addr 10 Check sum
3 4 11 Check sum
4 Operation order 12 Check sum
5 Operation order 13 Check sum
6 14 Tail
7 Setting data
Slave responding Sending Sequence
0 Header 9 Running data
1 Slave addr. 10 Running data
2 Slave addr 11 Running data
3 Slave responding 12 Running data
4 State feedback 13 Check sum
5 State feedback 14 Check sum
6 0 15 Check sum
7 Monitor item 16 Check sum
8 Monitor item 17 Tail
Setting data in master sending is setting freq., which is send form master to slave.
Setting data in slave responding is running parameter, which is send form master. It
is set by parameter F6.12.

¾ See the explanation about list of parameter in chapter five.

C300 series of non-sensor current vector-control inverter manual


104 SUNFAR C300

4. Usage example

4.1. OrderⅠ
To read slave model of 0#.
master will send:
2A 30 30 30 30 31 30 30 30 30 31 38 31 0D
5A 00 00 00 00 01 00 00 00 00 00 00 01 0D
Slave will respond:(Inverter with 220V and 0.4KW)
2A 30 30 30 30 33 30 32 30 30 30 30 34 30 32 34 39 0D
5A 00 00 00 00 03 00 02 00 00 00 00 04 00 00 00 09 0D
4.2. Order Ⅱ
To read running parameter of 0# slave(namely read d.4, output freq.)
master will send:
2A 30 30 31 30 30 30 30 34 30 31 38 35 0D
5A 00 00 01 00 00 00 00 04 00 00 00 05 0D
Slave will respond:(Return current DC voltage of generatrix is 285V)
2A 30 30 30 30 33 30 30 34 30 31 31 44 30 32 35 44 0D
5A 00 00 00 00 03 00 00 04 00 00 01 1D 00 00 00 25 0D
4.3. Order Ⅲ
To read code parameter of 0# slave(namely parameter F0.16)
master will send:
2A 30 30 32 30 30 30 31 30 30 31 38 33 0D
5A 00 00 02 00 00 00 00 10 00 00 00 12 0D
Slave will respond:(Carrier wave freq. is 8KHZ)
2A 30 30 30 30 33 30 31 30 30 30 35 30 30 32 34 39 0D
5A 00 00 00 00 03 00 00 10 00 00 00 50 00 00 00 63 0D
4.4. Order Ⅳ
To modify digit setting freq of 0# slave (modify parameter F0.2 as 60.02)
master will send:(To set detect and restart mode)
2A 30 30 33 30 30 30 30 32 31 37 37 32 30 32 35 36 0D
5A 00 00 03 00 00 00 00 02 00 00 17 72 00 00 00 8E 0D

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 105

Slave will respond:(Parameter is modified)


2A 30 30 30 30 33 30 30 32 31 37 37 32 30 32 35 36 0D
5A 00 00 00 00 03 00 00 02 00 00 17 72 00 00 00 8E 0D
4.5. Order Ⅵ
To send control order of 0# slave(running freq. is 9.99HZ)
master will send:
2A 30 30 34 31 31 30 33 45 37 30 31 44 35 0D
5A 00 00 04 00 11 00 00 03 E7 00 00 00 FF 0D
Slave will respond:
2A 30 30 30 30 31 30 30 30 30 33 45 37 30 32 36 30 0D
5A 00 00 00 00 01 00 00 00 00 00 03 E7 00 00 00 EB 0D
4.6. OrderⅤ
To modify Torque Boost F1.1 of slave as 6.0
master will send:
2A 30 30 35 30 30 31 30 31 30 30 33 43 30 32 35 44 0D
5A 00 00 05 00 00 01 00 01 00 00 00 3C 00 00 00 43 0D
Slave will respond:
2A 30 30 30 30 31 31 30 31 30 30 33 43 30 32 35 39 0D
5A 00 00 00 00 01 01 00 01 00 00 00 3C 00 00 00 3F 0D

C300 series of non-sensor current vector-control inverter manual


106 SUNFAR C300

AppendixⅡ OPTIONS

1. Operation panel
Sometimes users need to take operation panel out of the inverter or control cabinet,
if users purchase panel base and wire, it is convenient to install and debug. Wire
between operation panel and inverter should be less than 15m. If the length is
above 15m, long-distance control line is needed.

1.1 Appearance of panel base


41.5
72 16

RUN Hz A V

ESC <<

SET REV FWD

UP DOWN STOP

Fig-A Dimension of panel

It is recommended that user takes Fig-B


Hole dimension of panel base.

Fig-B Dimension of panel base

C300 series of non-sensor current vector-control inverter manual


SUNFAR C300 107

a) Appearance of small panel base

Fig-D Hole dimension of small panel base。

Fig-C Dimension of small panel base

It is recommended that users take Fig-D Hole dimension of panel base.

1.3 Installation of panel base


Open a hole on the control cabinet according to dimension of panel base. And put
the panel horizontally into the hole. Then four locks in panel base will lock. There is
an interface on the bottom of base, please insert the long-distance control wire into
it.

2. Brake resistance
The brake resistance is shown following table.
Applied motor Power of brake Brake Brake torque
Model
(Kw) resistance(Kw) resistance(Ω) (%)
C300-2S0002 0.2 0.1 250 100
C300-2S0004 0.4 0.18 150 100
C300-2S0007 0.75 0.25 100 100
C300-2S0015 1.5 0.4 70 100
C300-2S0022 2.2 0.6 50 100
C300-4T0004 0.4 0.25 500 100
C300-4T0007 0.75 0.3 400 100

C300 series of non-sensor current vector-control inverter manual


108 SUNFAR C300

C300-4T0015 1.5 0.5 300 100


C300-4T0022 2.2 0.65 200 100
C300-4T0037 3.7 1.0 125 100
If the braking effect is not obvious, please decrease brake resistance and increase
power of brake resistance according to proportion.

C300 series of non-sensor current vector-control inverter manual