Variador Seryman
Variador Seryman
Variador Seryman
Thanks for choosing E280 Vectorial General Purpose Inverter produced by Shenzhen Simphoenix
This Manual is the operating manual for E280 Vectorial General Purpose Inverter. It provides all
relevant instructions and precautions for installation, wiring, functional parameters, daily care and
In order to use this series of inverters correctly, guarantee product's best performance and ensure
safety of users and equipment, be sure to read this manual carefully before using E280 series
inverters. Improper use may cause abnormity and malfunction of the inverter, reduce its service life
and even damage equipments and lead to personal injury and death, etc.
This user manual is delivered with the device. Please keep it properly for future overhaul and
maintenance.
Owing to constant improvement of products, all data may be changed without further notice.
Version: V1.2
11 EMC..................................................................................................................................................213
11.1 CE .......................................................................................................................213
is a label on the outer packing, please confirm the model and specification of it to see if they are in
accordance with your order. If any damage or discrepancy is found, please contact the supplier
Confirm the frequency inverter body and accessories carefully when unpacking, to see if there is any
damage during the transit, and if the parts and components are damaged or dropped, and if there is
1) Operation instruction;
2) Certification;
3) Product list;
If there is any omission or damage, please contract the supplier promptly for solution.
On the frequency inverter, there is a nameplate marked with model, rated parameters, product
serial-number and bar code of frequency inverter. The content of nameplate is shown as below:
proper operation of this product. "Tip", "Attention", "Danger" and "Warning" in this operation
1. The frequency inverter shall not be installed on combustibles, in case of the risk of fire.
2. The frequency inverter shall not be installed at places with direct sunlight, in case of danger.
3. The frequency inverter of this series shall not be installed in the environment of explosive gases,
4. Frequency inverter with damage or lack of components shall not be applied; otherwise it may
6. No foreign matter is allowed to be dropped into the frequency inverter, in case of breakdown of
7. During installation, the frequency inverter shall be installed at the place able to bear its weight;
1. Please authorize the professional staff to conduct wiring. If the wiring operation is not proper, it
2. Please start to wire after the panel digital tube of frequency inverter is out for ten minutes,
3. The grounding terminal of frequency inverter must be reliably grounded; otherwise, there can be
5. Confirm that the input voltage and frequency converter are in consistent with rated voltage value;
6. Confirm that the motor and frequency converter are adaptive with each other, otherwise, the
7. Brake resistor can not be connected onto the (+), (-) of DC bus directly; otherwise, there can be
fire risk.
1. Please do not operate the switch with wet hand; otherwise, there can be electric shock.
2. Please install the front cover prior to plugging in, and shall not demount the cover while power is
3. During the frequency converter is with power on, even the motor is stopped, do not touch the
4. If you apply the function of restart, do not approach the load equipment, for it may restart
5. Please set the system as ensuring personal and property safety even when restarting.
6. Please set additional emergency stop switch, otherwise, personal injuries may be caused.
7. The temperature of cooling fin and direct current reactor can be very high, therefore, do not touch
1. Maintenance operations of overhaul and device replacement only can be done by trained
professional maintenance staff. During operation, insulation protection tools shall be applied. It is
strictly prohibited to leave thrum and metal in the machine. Otherwise, there can be dangers of
2. After replacement of control board, corresponding parameters must be set before operation,
1. The temperature when driving general motor applied with frequency converter can be a little
higher than that of industrial frequency power. With long-term operation at low speed, the
operation life of motor can be affected due to the poorer heat dissipation effect. In this case,
2. If when the equipment is installed with frequency converter drive, sometimes, there can be
resonance due to the natural vibration frequency of mechanical system, please consider about
applying flexible coupling and insulation rubber, or applying the function of hopping frequency of
3. There can be larger noise when driving general motor applied with frequency converter than that
of industrial frequency power. In order to reduce the noise, the carrier frequency can be increased
properly.
1. For high-speed motor, if the set frequency of frequency converter is above 120Hz, please
conduct combination test with motor, to make sure it can be operated safely.
2. For synchronous motor, there must be correspondences according to the types of motor. Please
3. Operation of single-phase motor is not applied with frequency converter. Even when input with
single phase, there is three-phase output, please apply with three-phase motor.
Application shall be applied in the indoor range with environment temperature of -10 to +45℃,
humidity around 5~95% (without condensation of moisture), no dust, no direct sunlight, no corrosive
gas, no combustible gas, no oil mist, no steam, no water or floating fiber or mental particles; if there
1. For the protection of wirings, please configure breaker for wirings on the input side of frequency
converter. Please do not apply device with larger capacity than recommendation.
2. If it needs to switch to industrial frequency power and others, when installing electromagnetic
contactor on the output side of frequency converter, please switch after frequency converter
3. When applying with motor thermal relay, if the wiring of motor is too long, sometimes it is affected
with the high-frequency current flowing through capacitance distributed with wiring, current
below the set value of thermal relay may also cause trip. In this case, please lower the carrier
4. For noise interference, connection filter, magnet ring and shielded wire can be applied as
corresponding measures.
1. During product handling, please capture the both sides of the bottom of the entity, rather than
2. Please do not make the parts of plastic excessive forced, otherwise, there can be falling down
or damage.
3. When it is for temporary storage and long-term storage, pay attention to the followings:
z Try to be packaged in the packing case of our company as the original package for
storage.
therefore, it shall be powered on every half year at least, and with conduction time more
than half an hour, and the input voltage must be risen to the rated value gradually with
voltage regulator.
2. Waste gas of plastic burning: harmful and toxic gas may be produces while burning the plastic
3. Disposal methods: please deal with the frequency converter as industrial waste.
2. If serious accident or serious losses caused due to the failure of this product, please install
Voltage grade
T Three phase
Operating panel
Upper cover Port of operating panel
Upper housing Crystal connector position
(remote operation)
Lower housing
Lower cover
Wiring entrace of extension loopr Control loop terminal
Wiring entrace of control loop Major loop terminal
Wiring entrace of main loop
Plugboard
Upper cover
Operating panel
Lower cover
Upper cover
Operating panel
major loop
Operating
panel
right door
panel
left door
panel
Control loop terminal
Output
Frequency running mode: 0.00~300.00Hz;
frequency
Deceleration and
0.01~600.00Sec. / 0.01~600.0Min.
acceleration time
Wakening and sleeping Built-in PID, with simple sleeping and wakening functions.
Typical
Function MODBUS Standard MODBUS communication protocol (optional)
communication allowing for flexible parameter reading and mapping.
Special
Function Virtual IO terminal 8-circuit one-to-one virtual output and input terminals,
allowing for complicated engineering onsite application in
Load dynamic Also allows for dynamic balance of multi-motor load (not
limited to communication linkage) and able to achieve
balance torque motor characteristics.
Application macro:
Allowing for conveniently setting and partially curing
multiple common group parameters and simplifying
parameter setting for common applications.
Macro parameter
System macro:
Allowing for conveniently switching equipment’s working
mode (e.g. switching between high and low frequency
running modes), and automatically redefining local
parameters.
vertically. In order to be in favor of circulation and heat dissipation, please install the frequency inverter at
indoor place with good ventilation. Please refer to 1.3.3 for installation environment. If there is special
y Mounting surface
The temperature of cooling fin may rise to around 90℃, so please install the mounting surface at the place
y Installation space
Requirements for installation spacing distance of single frequency inverter are as shown in figure 3-1.
y Multiple installations
If install more than 2 sets of frequency inverters in device or control cabinet, please conduct parallel
installation in principle as shown in figure 3-3. If there is no choice but vertical installation, please consider
setting partition plate as shown in figure 3-2, to ensure no influence on upper frequency inverter from lower
frequency inverter.
Fan exhaust
风扇
D
排气
Inverter
A A diversion
partifion
Inverter
Figure 3-1 Spacing distance for installation Figure 3-2 Upper and lower Installation dimensions of
¾ When horizontally and closely installed under 4.0KW, the ambient temperature is -10℃ -
45℃.
¾ Horizontally close installation is only for 4.0KW below, and -10℃ - 45℃ environmental
temperature.
¾ For parallel installation of frequency inverters with different sizes, please carry out
installation after aligning the upper parts of all the frequency inverters, thus to be in favor
¾ Please don’t install frequency inverter in the environment with tattered cotton yarn and
damp dust which may cause blockage of cooling fin. If necessary to operate in such
environment, please install in the control cabinet which can keep tattered cotton yarn out.
¾ If necessary to install at the place with more than 1000m height above sea level, please
derate operation. See 2.4 product technical indexes and specifications for details.
Name Two-line LED small panel Two-line LED standard operating panel
Model DPNL350EM DPNL360EA
Code 050M007033701 050M007360003
Applicable
E280-4T0040G/4T0055P and below models E280-4T0055G/4T0075P and above models
models
LED main display
LED主显示
LED main display
LED主显示
LED display area
LED 数码 LED display
LEDarea
数码
LED auxiliary
显 示 区 LED auxiliary
LED辅显示 显 示 区 LED辅显示
Unit combination display display
单位组合 Unit combination
单位组合
indicator
显 示 灯 显 示 灯
indicator
Appearance Functional
Functional
Function
功 能 功能组合 Function
功 能 功能组合
combination
operating
操作区area combination
显 示 灯 operating操作区
area 显 示 灯
indicator
indicator
Put fingers on the slot at front part of Put fingers on the slot at front part of the
the panel and then simply raise the panel panel and then simply raise the panel.
Disassembling
After aligning the panel with the panel slot, After aligning fixed hook month at the
press down the panel evenly. bottom of the panel with the clasp under the
panel base, simply press down the top of
卡扣
Clasp the panel.
卡槽
Slot
卡扣
Clasp Slot
卡槽
Installation
Clasp
卡扣
Slot
卡槽
Clasp
卡扣
Remove the operating panel and make Remove the operating panel and detach
connection with the extension cable as the crystal connector and place it at
shown in following figure. specified position to avoid loss, and then
use extension cable to make connection
as shown in following figure.
外接卡扣
Clasp for external connection
Clasp for
external Crystal connector
connection
外接卡扣 水晶转接头
Prolonged connecting
连接线 connecting
连接线 wire
wire
external
外接卡扣
Clasp for
connection
external
connection Clasp for
external外接卡扣
connection
¾ It is a must to use extension cable or commercial LAN cable (straight cables) in the market.
¾ Extension cable shall not exceed 15 meters; shielding layer is connected with grounding
terminal of frequency inverter. Please select remote operation panel if the extension cable is
more than 15 meters long.
¾ Do not carry out wiring horizontally close to the power line.
¾ Panel shall be fastened on stable fixed surface or work bench so as to avoid damage.
3.3 Installation size of the panel (the operating panel can be flexibly selected
according to actual installation requirement)
Name Two-line LED small panel Two-line LED standard operating panel
55 25 70 27
23
22
50
101
126
130
105
Installation size
66
51
46.5
30
102*52 127*67
67
52
Installation
External Installation
安装 板
board
安装板
connection without board
tray, installation
127
board hole
102
diagram
Installation board
安装板
97
12
螺钉
Fixed
固定
5 with
screws
External 5
9 5
connection with 2
1
This connection mode is not applicable
tray, installation
4
1
0
board hole -
Th
diagram ro
ug
hh
o le
Removal: put fingers on the handle slot at the bottom of cover plate (the position of clasp as figure 3-3),
and forcibly lift it upward until the card clasps between cover plate and shell break away, then pull the
cover plate down can disassemble the shell. See figure 3-3
Installation: slant cover plate into about 15°, then insert the fixed stator at the top of cover plate into fixed
slot on shell. Forcibly press the cover plate down until heard a click, which means the cover plate has been
in place.
Control
控制回路端子 loop terminal
Fastener position Main
主回路端子loop terminal
扣手位置 下盖板Front
Lower 前插板plug
cover plate board
Removal: First, knock off two set screws in cover board, and push down the lower cover board by 15mm,
then remove upwards the lower cover board, as Figure 3-4 is shown.
Installation: First, put the lower cover board on the sheet-metal guide rail, and push the lower board to reach
upper cover board, then make sure the screw holes match each other; finally knock in screws.
Figure 3-4 The Disassembly and Installation Diagram of Sheet-metal Cover Board
W
W1 D
H1
H
W
W1 D
H1
H
W D
W1
H1H
W D
W1
H1
H
W1:Distance between installation holes on the side board W:Side board width
H1:Distance between installation holes on the side board H :Side board height
E280-4T0011G/4T0015P
87 97 152 162 130 M4
E280-4T0015G/4T0022P
E280-4T0022G/4T0030P
E280-4T0040G/4T0055P
E280-4T0090G/4T0110P
169 180 290 305 179 M5
E280-4T0110G/4T0150P
E280-4T0150G/4T0185P
160 210 387 405 202 M6
E280-4T0185G/4T0220P
E280-4T0220G/4T0300P
160 250 422 445 216 M8
E280-4T0300G/4T0370P
E280-4T0370G/4T0450P
E280-4T0550G/4T0750P
E280-4T0900G/4T1100P
E280-4T1320G/4T1600P
E280-4T1600G/4T1850P
400 580 760 793 300 M10
E280-4T1850G/4T2000P
E280-4T2000G/4T2200P
550 700 960 1000 340 M10
E280-4T2200G/4T2500P
E280-4T2500G/4T2800P
E280-4T3150G/4T3500P
• Make sure intermediate circuit breaker is connected between the frequency inverter
and power supply to avoid expanded accident when the frequency inverter is faulty.
• Please use shielded wire of above 0.3mm² for the wiring of such analog signals as
frequency setting terminal and instrument loop, etc. The shielding layer shall be
connected on the grounding terminal of the frequency inverter (keep the shielding layer
earthed at single end) with wiring length less than 30m.
• The stranded wire or shielded wire of above 0.75mm² shall be selected for the wiring
of input and output loop of relay.
• The control wire shall be separated from the power line of major loop; it shall be at a
distance of above 10cm for parallel wiring and vertical for cross wiring.
• All the leading wires shall be completely fastened with the terminal to ensure good
contact. The leading wires of major loop shall be adopted cables or copper bar. When
using cables, wiring must not be carried out until they are cold pressed or welded well
by lug plate with corresponding section.
• The pressurization of all the leading wires shall be in compliance with the voltage class
of the frequency inverter.
电动机
Motor
U
变频器
Inverter V M
W
阻容吸收装置
RC absorber
Figure 4-1 The ketch of forbidding connecting a RC absorber at the output terminal
• Air switch
1)When the frequency inverter is maintained or not in use for a long time, the air
switch will separate the frequency inverter from the power supply;
2)When the input side of the frequency inverter has failures like short circuit, the air
switch can protect.
• AC input reactor
When the interaction of higher harmonic between the frequency inverter and power
supply can not meet the requirements after serious wave form distortion of power
grid or the frequency inverter is equipped with DC reactor, the AC input reactor can
be added. The AC input reactor can improve the power factors at input side of the
inverter and reduce the influence caused by unbalanced voltage of three-phase
power supply.
• Contactor
It can cut off the power supply when the system protective function acts to prevent
failure expanding.
• DC reactor:
In order to defend the influence of power supply to frequency inverter, protect the
inverter and restrict higher harmonic, DC reactor shall be equipped under the
following conditions:
1)When the power supply of frequency inverter has switch LBMJ on the node or with
silicon controlled phase control load, the voltage jump of the grid resulted from
reactive transient caused by capacitor switching and harmonic and grid wave form
gap caused by phase control load may damage the input rectifying circuit of the
frequency inverter.
2)When the three-phase power supply of the frequency inverter is unbalanced;
3)When the power factors at the input end of the frequency inverter are required to
improve.
• Filter at output side
EMI filter can be selected to restrict the interference noise generated at the output side
of the inverter and wire leakage current.
• AC output reactor
When the wiring from the frequency inverter to the motor is longer (exceeding 20m), it
can restrict radio interference and leakage current.
• Braking resistor
Improve the braking capacity of frequency inverter to avoid overvoltage failure when
slowing down
E280-4T0090G/4T0110P 9.0 11 10 50 32
E280-4T0110G/4T0150P 11 15 10 63 32
E280-4T0150G/4T0185P 15 18.5 10 63 38
E280-4T0185G/4T0220P 18.5 22 16 80 45
E280-4T0220G/4T0300P 22 30 16 100 63
E280-4T0300G/4T0370P 30 37 25 125 75
E280-4T0370G/4T0450P 37 45 25 160 85
Model of frequency inverter Screw specification Tightening torque(N*m) Recommended lug model no
General control terminal Screw specification Tightening torque(N*m) Recommended lug model no
control board/extension
M2 0.1~0.2 E0.5-6
card terminal
control board/extension
M3 0.3~0.4 E0.75-6
card terminal
T185-12 12.7 23 19 34 30 73
Lug model no d2(mm) W(mm) F(mm) L(mm) H(mm) d1(mm) D(mm) T(mm)
W W
E d2 T W
T
窥视孔
F
F
L
L
H
d1
H
L B
?d
?D
d1
D
D
CON4
Category I: CON3 and CON4 CON3 DI1 DI2 DI3 DI4 DI5 24V CM
terminals
TC TB TA AI1 AI2 AO1 VS GND DO1 CM
Applicable to:
E280-4T0040G/4T0055P and below
d l
CON1
Category II: CON1 and CON2
CON2 DI1 DI3 DI5 DO1 24V AI1 AO1 VS
terminals
TA TB TC DI2 DI4 DI6 DO CM AI2 AO2 GND
Applicable to:
E280-4T0055G/4T0075P and above
Multifunctional
DI1-CM
output terminal DI1 6-circuit programmable
switching value input Opto-isolated inputs:
Multifunctional
DI2-CM terminal, allowing for
output terminal DI2
selection of 98 kinds of 24Vdc/5mA
Multifunctional operational control
DI3-CM
Control output terminal DI3 commands via
Input impedance:
terminal Multifunctional programming offunction
DI4-CM codes in F3.0 group. See
output terminal DI4 Z = 4.7 KΩ
Comparison Table of
Multifunctional Multifunctional Output Input frequency:
DI5-CM
output terminal DI5 Terminal Functions for f <1k Hz
Multifunctional details (page P67).
DI6-CM
output terminal DI6
Input/output 2-circuit programmable NPN model OC
CM terminal common open-circuit collector output Maximum load
port output and 1-circuit current: 150mA,
Multifunctional programmable relay highest withstand
DO1-CM output terminal; 63 kinds voltage: 24V
output terminal DO1
of operating status output Output frequency:
Operating Multifunctional can be selected by the f <1k Hz
DO2-CM
status output output terminal DO2 function code in F3.1
TA Multifunctional relay group by programming.
output RO1 See Comparison Table for Contact capacity:
TB TA-TB normally Variables of AC 250V/2A
closed Multifunctional Output DC 30V / 0.5A
TC TA-TC normally Terminal for detail Cosθ=1
open (page 68).
below models
JP3
V
Shift V: Indicating that AO terminal externally outputs A
拨码
Dial
0~10V voltage signal 开关
switch
Shift A: Indicating that AO terminal provides
externally 0~20mA current signal.
JP1
Shift VO1: Indicating that AO1 terminal outputs
voltage signal. VO1 VO2 5V
拨码
Dial OFF OFF OFF
Shift OFF: Indicating that AO1 terminal is at vacant 开关
switch
CO1 CO2 10V
state.
Shift CO1: Indicating that AO1 outputs current signal.
JP2
Shift VO2: Indicating that AO2 terminal outputs voltage signal.
Shift OFF: Indicating that AO2 terminal is at vacant state.
Shift CO1: Indicating that AO2 outputs current signal.
JP3
Shift 5 V: Indicating that VS terminal provides externally 5V voltage signal.
Shift OFF: Indicating that VS terminal is at vacant state.
Shift 10V: Indicating that VS terminal provides externally 10V voltage signal.
E Earthing terminal -- --
R S T P+ U V W PB E
Motor
Ground
Three-phase power supply
R S T P+ E U V W PB
Ground Motor
P+ R S T U V W PB E
Motor
Ground
Three-phase power supply
P+ P- R S T E U V W PB
Motor Ground
错误!链接无效。
Energy consumption braking resistor
P P+ P- R S T E U V W
DC 直流电抗器
reactor
Ground Motor
P P+ P- R S T E U V W
直流电抗器
DC reactor
Ground Motor
P+ P P- R S T U V W E
直流电抗器 大地
Ground
DC reactor
E280-4T0550G/4T0750P
R S T P P+ P- U V W E
直流电抗器
DC reactor 大地
Ground
R S T P P+ P- U V W E
直流电抗器
DC reactor Ground
大地
E280-4T3150G/4T3500P
Ground 三 相 电源power
输入 supply
大地 Three-phase
E R S T
E U V W P- P+ P
大地
Ground 直
DC流电 抗器
reactor
电 动机
Motor Brake
制 动单元unit
R U 电动机
Motor
S V M
T W
E 接大地
Grounding
DI1 TA
DI2 TB
可编程输出
Programmable output
DI3 TC
DI4
P+
DI5 Connected
P- to braking
外接制动电阻
DI6 resistor
PB
CM
E 24V 辅助直流电源
Auxiliary power supply
V350 CM
0-10V 频率设定
0-10Vfrequency
VS
AI1
E280 AO1 电压表( 0-10V
Volt gauge )/电流表(0-20mA
(0-10V)/ammeter )
(0-20mA)
AO2 电压表( 0-10V
Volt gauge )/电流表(0-20mA
(0-10V)/ammeter )
(0-20mA)
0-20mA
0-20mA 频率设定
frequency AI2
GND
GND
E
E Open collector
output
开路集电极输出
DO1
PG扩展卡(选配) DO2
+12V
CM
GD
E
A+
PG expansion A-
card (optional) PG B+
B-
Z+
Z-
E
Chapter 5
The panel of the frequency inverter mainly has two functions apart of basic starting and stopping
control: monitoring of parameters for operating status and query and modification of internal
parameters. Accordingly, the operation panel is divided into two operating modes: monitoring
mode and parameter modification/query mode.
When powered on, the major display field will show the company’s Logo abbreviation from right
to left and restore to normal display in 3 seconds. At the same time, the auxiliary display column
displays the serial number of the frequency inverter statically such as “E-580” and displays the
model information of the frequency inverter except “T, S” 3 seconds later such as “4.0037” and
displays normally 3 seconds later. At this time, the operating parameters displayed in the
operation panel are determined by the internal parameters of the frequency inverter [F0.0.12],
[F0.0.13]. The operation panel will return normal monitoring mode at any status if there is no
keying operation within 1 minute. (See Chapter 3 for the appearance of the operation panel).
功能组合
Functional Function Functional
功能组合 combination
Function operating功area
能 功 能
indicator
操作区 显 示 灯
combination operating操作区
area 显 示 灯
indicator
Figure 4-1-A Two-Line LED Small Panel Standard Figure 4-1-B Two-Line LED Standard Operating Panel
configuration for E280-4T0040G/4T0055and below models Standard Configuration for E280-4T0055G/4T0075P and
above models
Main digital Display the current operating status parameters and setting parameters of the
display frequency inverter.
Auxiliary
Display the current operating status parameters and setting parameters of the
digital
display frequency inverter
A, HZ, V displays the corresponding measurement unit of the data of the main digital
display. % displays compound unit
A, Hz, V, %
The compound unit indicator is defined as follows:
Hz+A = RPM; V+% = Sec. ;A + V = Min
Indicator for operating status, its flicker shows the frequency inverter is in F/R
FWD, REV
operation and has voltage output.
The indicator is off: the external terminal command is valid; the indicator is on: the
PANEL/REM operation panel command is valid;
OTE the indicator is flashing: the communication interface (or expanded communication
board or expanded function board) command is valid.
Alarm indicator:
ALARM The indicator is on: the frequency inverter is in warning status. It shall check up and
eliminate abnormalities; otherwise, the frequency inverter may be faulty and shut down.
Stop/reset key
When this key is pressed in operating status, the frequency inverter will shut down as per set
mode; and when pressing this key in fault conditions, the frequency inverter will reset and
return to normal stopped status.
Keys can be locked or functions can be changed by users (refer to Functional
Parameter F0.011).
Return key
At any status, it will return to the status of last level till normal monitoring mode by pressing this
key.
Mode key
Switch display function parameter set and monitoring parameter set in parameter modification
status. The corresponding “EROM stored value”, “value at this time of energizing” and “panel
backup value” of the current function code will be displayed at auxiliary display column in turn
by pressing this key.
Item Functions
Ok key
Confirm the current status and parameters (the parameters are stored in the internal memory)
and enter into next-level function menu.
The operation panel also has the following special functions aside from such basic functions as
forward operation, reverse operation, inching operation, shut down, fault reset, parameter
This operation panel allows for copying the internal parameters of the frequency inverter to the
operation panel (only the internal parameters opened to users) and storing permanently.
Therefore, users can backup their typical setting parameters to the operation panel for emergency.
The backup parameters in the operation panel do not influence the operation of the frequency
When [F0.0.08]=####1, the keyboard will begin to read the internal parameters of the frequency
inverter and the operation panel will display the process of reading parameters in real time. After
the completion of parameter backup, the display mode will recover to normal monitoring
automatically. During parameter backup, the operation can be stopped at any time by pressing
key and the display will switch to normal monitoring mode.If alarm information is occurred,
This operation panel allows for copying the backup parameters to the internal memory of the
frequency inverter (only the internal parameters opened to users) and users can write in their
typical setting parameters backed up in the operation panel into the frequency inverter at one
When the frequency inverter set F0.0.08 as # # 1 2 or # # 1 3 in stopped mode, the keyboard will
begin to copy the backup parameters to frequency inverter and the operation panel will display
the process in real time. After the completion of copying, the display mode will recover to normal
monitoring automatically.
During parameter copying, the operation can be stopped at any time to abandon the copied
parameters by pressing key and the display mode will switch to normal monitoring
In normal monitoring mode, the internal parameters of the frequency inverter can be checked
In normal monitoring mode, the backup parameters in the operation panel can be checked and
modified by pressing and key simultaneously (double key compound use) and the
high-order code “F” will display flickeringly when function code is displayed. The modification
1) Locking: part of or all the keying functions of the panel can be locked through setting the
application parameter F0.0.11. If the parameter is set as panel locking mode, the panel will be
2) Unlocking: the panel will be unlocked for 5 minutes temporarily by pressing and
maintaining and pressing twice in order within 5 seconds and it will automatically
Key function
key function is limited by the application parameter F0.0.11. In function enabling and
“normal monitoring mode”, press key to switch the operation command channel in
panel”. indicator displays the selected command channel which will be valid by
pressing within 3 seconds. It will abandon the switch and return to original status by
The operation command channel switched by this function is not stored permanently. It will
recover to original setting after the frequency inverter is power down and restarted. Relevant
主显示:50.00Output
输出频率
Main display: 50.00
frequency
常态监控模式
Normal monitoring mode
辅显示:2.3
Auxiliary display: 2.3 输出电流
Output current
(单击2次)
(Click twice)
Return
返
normal
回
control
常
态
控
制
Return
the
确定查询
Confirm query for status
parameters last
状态参数 level
主显示: 380Output
输出电压
Main display: 380
voltage
参数查询
Parameter inquiry
辅显示: 2.3 输出电流
Auxiliary display: 2.3 Output current
进入参数
Enter into parameter
Main display: F0.0.01 Function code
modification mode Parameter modification
修改模式
(refer to the next section)
参数修改模式mode Auxiliary display: 2.3 Parameter data
(参见下节)
主显示:50.00
Main 输出频率
display: 50.00 Output frequency
Normal monitoring
Auxiliary display: 2.3 Output current
Modification/
备份参数
query for
修改/查询backup
(Click once)
parameters (单击1次)
选择被
Select queried/modified
Abandon放 parameter items
查询/修改参数项
弃
modification
修
改
确定查询
Confirm query for status
状态参数
过的参数
Remark:In this status, the auxiliary display column will display the following in turn by
parameters in operation panel, the numerical value will flicker when “EROM regional numerical
value”, “parameter values at initial energizing” and “backup parameters in operation panel” are
displayed.
Mode 0: vector control without PG, i.e. vector control without velocity sensor, also called open
loop vector control. It is applicable to the place where encoder is not installed, has higher
requirement to starting torque and speed control precision and the normal V/F control mode can
not satisfied.
Mode 1: vector control with PG, i.e. vector control with velocity sensor, also called closed loop
vector control. It is applicable to the place where faster response of torque and higher control
precision is required.
Mode 2: V/F control mode. Except normal V/F control application, it can also be applied to the
place where the frequency inverter drives more than one motor.
The control modes of frequency inverter vary from the type and control requirements of motor
and set by parameter F0.0.09=####. For instance, the field where three-phase asynchronous
motor is used can be selected through setting F0.0.09=###0 and the field where the control
precision is highly required with velocity sensor can be set to F0.0.09=##1# speed closed loop
vector control mode.
E280 frequency inverter has 29 frequency setting modes for each of the channel.
Figure 5-3 Wiring for the operation of SVC mode Figure 5-4 Wiring for the operation of VC mode
Use operation panel to conduct digital frequency setting and start-stop control.
1.Connect as per Figure 5-3;
shortcut))
4.Press key to start frequency inverter. If the name plate parameters (F2.0.00 ~
F2.0.04) of the motor are modified in ③, the primary static parameter identification will be
started automatically, the frequency inverter will output 0 frequency and the auxiliary
display column will display the current output current (not limited by F0.0.13 at this time).
When the display current is stable as 0.0, the automatic learning is finished and operation
is started;
5.Press key to increase set frequency, where the output frequency of the frequency
6.Observe the operation of motor, if there are abnormalities, stop it immediately and power
8.Press key to stop operation and cut off the power supply.
Note:
"×": Indicates that the set value of the parameter cannot be changed when the inverter is running.
"☆": Indicates the parameter is relevant with the model of the inverter.
"R": Indicates the parameter is just for reading and cannot be changed;
"R/I": Indicates the parameter is just for reading and cannot be changed, but can be cleared by
initialization.
"—": Indicates the parameter is relevant with the type or status of connected accessories.
Variables: (H)-hexadecimal number; only bitwise data change is permitted (carry bit is not allowed),
LCD language
F0.0.03 0:Chinese 1:Reserved 0 1 -
selection
F0.2.26 Reserved
Minimum
value of
F0.2.27 0.0Hz~[F0.2.28] 0.0 0.01
frequency
setting
Maximum
F0.2.28 [F0.2.27]~[F0.1.20] 50.0 0.01
value of
Tens: Reserved
Hundreds: Frequency
decreasing and current
limiting adjustor
0: Closed 1: Effective
Kilobit: Reserved
Action level of the
F1.4.43 660~800 V 740 1
overvoltage adjustor
Overvoltage adjusting
F1.4.44 0.10~10.00 1.00 0.01
gain
Action level of the
F1.4.45 [FF.2.35]~480V 330V 1
undervoltage adjustor
Undervoltage adjusting
F1.4.46 0.10~10.00 1.00 0.01
gain
Action level of the
frequency decreasing
F1.4.47 20~200(%) 180 1
and current limiting
adjustor
Adjusting gain of the
frequency decreasing
F1.4.48 0.10~10.00 1.00 0.01
and current limiting
adjustor
0~5(the self-recovery
Recovery times of fault
F1.4.49 function is deactivated when 0 1
self resetting
it is set to 0)
0.2~5.0Sec (Real waiting
The recovery waiting
F1.4.50 time progressive increase with 1.0 0.1
time of fault self resetting
recovery times)
Time period for self
F1.4.51 900~36000Sec. 3600 1
resetting timing
The minimum unit of stator resistance, stator inductance and total leakage inductance o
asynchronous machines is relevant with models.
Setting Range
Function Factory Minimum Change
Name and
Code Default Unit Limit
Description
Lower limiting value of monitor 3
F3.1.34 0.0~100.0 (%) 0.0 0.1
variables (relative to full scale value
Upper limiting value of monitor 3
F3.1.35 0.0~100.0 (%) 100.0 0.1
variables (relative to full scale value
6.14 Pulse input (Configured with standard expansion I/O board, and this
group of parameters are effective when D19 selects the frequency input function)
Function Setting Range and Factory Minimum Change
Name
Code Description Default Unit Limit
Minimum pulse input
F3.2.36 0.0~100.00KHz 0.0 0.01
frequency DI9/Fin
Maximum pulse input
F3.2.37 0.01~100.00KHz 10.0 0.01
frequency DI9/Fin
F3.2.38 Pulse detection cycle 1ms~20ms 10 1
F3.2.39 Number of single-loop pulse 1~4096 1024 1
Mechanical transmission
F3.2.40 ratio (=pulse shaft revolution: 0.010 ~ 10.000 1.000 0.001
motor shaft revolution )
Driving wheel diameter
F3.2.41 0.1~2000.0mm 100.0 0.1
(for liner speed calculation)
Maximum accumulative length
F3.2.42 10m~50000m 50000 1m
value
F3.2.43 Maximum liner speed 0.01~500.00m/sec. 10.00 0.01
Current accumulative length
F3.2.44 0~50000m — 1 R
value
F3.2.45 Current liner speed 0.0~500.00m/sec. — 0.01 R
6.15 Pulse output (Equipped with standard expansion I/O board, and this
group of parameters are effective when DO3 terminal selects the frequency
output function)
Function Setting Range and Factory Minimum Change
Name
Code Description Default Unit Limit
0: 0.25~100.00KHz
frequency signal
Type of output pulse 1: 10.0~1000.0Hz frequency
F3.3.46 0 1
signal DO3/Fout signal
2: Pulse width modulation
(PWM) signal
Minimum output
F3.3.47 0.25~100.00KHz 0.25 0.01
frequency DO3/Fout
Maximum output 0.25~100.00KHz (PWM
F3.3.48 10.0 0.01
frequency DO3/Fout signal reference frequency)
Pulse output mapping 0~45 (monitor variable
F3.3.49 0 1
variable comparison table)
DO3/Fout assignment
F3.3.50 0.0~[F3.3.51] 0.0 0.1
lower limit
DO3/Fout assignment
F3.3.51 [F3.3.50]~100.0 (%) 100.0 0.1
upper limit
6.30 Process PID sleep function (Effective when PID output is used as the
frequency command)
Function Factory Minimum Change
Name Setting Range and Description
Code Default Unit Limit
0: Closed 1: Activated
2: Activated when the
F7.2.34 Sleep function 0 1
multifunctional input selection is
valid (Function No. 33)
F7.2.35 Sleep frequency 0.0~[F0.1.21] 0.0 0.01
F7.2.36 Sleep delay 0.1~3600.0Sec. 60.0 0.1
Awakening deviation
F7.2.37 (compared with the 0.0~100.0 (%) 25.0 0.1
100% set value )
F7.2.38 Awakening delay 0.1~3600.0Sec. 60.0 0.1
The unit:
0: Stop command
1: Running command
dE.0.16 Command status 0000 1 R/I
Tens: Reserved
Hundreds: Reserved
Kilobit: Reserved
As shown in figure 6-1, DI2, DI3, DI7, DI9 terminal input is in effective status, and other
terminals are at void status.
terminal 3 (switching)
Maximum torque limiting set value Zero torque (zero loss) tracks free
36 37 sliding
selection
0.10~100.00KHz pulse input port (Fin 1.0~1000.0Hz pulse input port (Fin
97 98
effective) effective)
Monitor 1 input variable below the Monitor 1 input variable above the upper
26 lower limit (Void when above the 27 limit
upper limit) (void when below the lower limit)
Monitor 1 input variable between the Monitor 2 variable below the lower limit
28 29
upper limit and the lower limit (void when above the upper limit)
Monitor 3 input variable below the Monitor 3 input variable above the upper
32 lower limit 33 limit
(void when above the upper limit) (void when below the lower limit)
Analog input AI1 wire breakage Analog input AI2 wire breakage detection
36 37
detection effective effective
70 SDO5⊕SDO6 OR 71 SDO7⊕SDO8 OR
20~23 Reserved --
39~44 Reserved
Remark: Unless otherwise especially instructed, the status of terminals will be defined under
positive logic conditions (“ON” terminals effective, and “OFF” terminals void).
Group F0.0 parameters are especially used to define system control parameters, e.g. locking,
initializing, motor type and control mode as well as display of monitoring parameters, etc.
F0.0.00 Macro parameters (H) Setting range: 0000~2006 Factory default: 0000
Macro parameters include application macro, system macro and special configuration macro; the
application macro allows for conveniently setting and curing multiple common parameters and
simplifying parameter setting for general applications; the system macro allows for conveniently
switching equipment’s work mode (e.g. switching between high and low frequency operation mode)
and automatically defining partial parameters; the special macro allows for internal integration and
settings for special functions or parameters with one key according to typical industrial applications.
Macro parameters are not influenced by the initializing parameter F0.0.07 and partial macro-related
Customized settings, all parameters can be customized without being influenced by the application
macro parameters.
1: Digital setting of panel operation
Refer to Figure 7-1 for the application wiring diagram, and refer to Table 7-1 for macro-related
parameters.
2: Shuttle setting panel operation
Refer to Figure 7-1 for the application wiring diagram, and refer to Table 7-1 for macro-related
parameters.
3: Two-Line Control 1/AI1 Setting
Refer to Figure 7-2-A for the application wiring diagram, and refer to Table 7-1 for macro-related
parameters.
4: Two-Line Control 2 /AI1 Setting
Refer to Figure 7-2-B for the application wiring diagram, and refer to Table 7-1 for macro-related
parameters.
Refer to Figure 7-3 for the application wiring diagram, and refer to Table 7-1 for macro-related
parameters.
6: Machine tool spindle drive macro / AI1 setting.
Refer to Figure 7-4 for the application wiring diagram, and refer to Table 7-1 for macro-related
parameters.
F0.3.33 0 0 1 1 1 Locked
F0.3.35 — — 0 1 2 Locked
F0.4.37 0 0 0 0 0 Locked
F0.4.38 0 0 0 0 0 Locked
F3.0.01 — — — — 19 Locked
F3.0.02 — — 7 7 7 Locked
F3.0.03 — — 8 8 8 Locked
F3.0.04 13 13 13 13 13 Locked
F6.1.15 0 0 0 0 0 Relocatable
F6.2.46 0 0 0 0 0 Relocatable
F7.0.00 0 0 0 0 0 Relocatable
F8.0.00 0 0 0 0 0 Relocatable
FA.2.25 0 0 0 0 0 Relocatable
DI5 故障复位输入(RESET)
Fault reset input (RESET)
Figure 7-1 Wiring Diagram for Panel
Operation Digital/Shuttle Setting CM 数字输入公共地
Digital input public address
AI1 ? ? frequency
Input ? ? ? ?given:
: 0~0~10V
10V
1~10KO
1~10KΩ
GND Analog
? ? ?input
? ?address
DI3 ? ? ? command
Running ?
Setting Wiring Diagram
DI4 ? ? ?disengaged:
Switch ? : ? ? ?FWD
? ?command
? ? ?engaged:
Switch ? : ? ?REV
? ?command
?
DI5 ? ? resetting
Fault ? ? ? ?input
( RESET)
(RESET)
CM ? ?input
Digit ? ?public
? ? address
?
AI1 ? ?frequency
Input ? ? ? given:
? : 0~ 10V
0~10V
1~10KΩ
1~10KO
GND Analog
? ? input
? ? address
?
+10V Reference
? ? ? ?voltage: 10 VDC, ?max.
: 10VDC, 10mA
? 10mA
DI2 ? ? ? ?
Three-line ? ? control
running
Figure 7-3 Three-Line Control 1/AI1
DI3 Forward(FWD)
? ? FWD?running
? ? ?command
( ? ? (pulse
) )
Setting Wiring Diagram
DI4 Reverse (REV) running
? ? REV? ? ? ? command
( ? ? (pulse
) )
DI5 ? ?resetting
Fault ? ? ? input
? ( (RESET)
RESET)
CM ? input
Digit ? ? public
? ? ?address
?
AI1 ? ? frequency
Input ? ? ? ?given:
: 0~0~10V
10V
1~10KΩ
1~10KO
GND Analog
? ? ?input
? ?address
+10V Reference
? ? ? ? voltage: 10 VDC,
: 10VDC, ? ?max. 10mA
10mA
DI2 ? ?to?electric
Shift ? drive
Figure 7-4 Driven by machine tool
DI3 Forward (FWD)?running
? ? FWD? ? ? command
spindle / AI1 preset wiring diagram
DI4 Reverse
? ? REV?(REV)? running
? ? command
DI5 ? ? resetting
Fault ? ? ? ?input
( RESET)
(RESET)
DI6 ? ? switching
Motor ? ?
CM ? ?input
Digit ? ?public
? ? address
?
TA
TB ? ?output
Fault ? ?
TC
Macro-related parameters
Related
F0.0.09 F0.2.25 F0.3.33 F0.3.35 F0.4.37 F0.4.38 F3.0.01 F3.0.02 F3.0.03
parameters
Macro set value 0000 9 1 0 0 0 67 7 8
Value locking N Y Y Y Y Y Y Y Y
Related
F3.0.04 F3.0.05 F3.1.21 F5.3.32 F6.1.15 F6.2.46 F7.0.00 F8.0.00 F8.3.39
parameters
Macro set value 13 41 4 1 0 0 0 0 0
Value locking Y Y Y Y N N N N N
Hundred: Reserve
Kilobit: Batch recovery or batch storage of parameters
The macro parameter F0.0.00 is not subject to the influence of this function.
2: Abandon modifying all un-saved parameters (restoring to original value)
All unsaved parameters will be rapidly restored to the values stored in the memory with one key.
This function can only be used when the device is stopped. If this function is activated when the
device is running, the inverter will send alarm aL.058 and give up operation.
5: Batch storing all modified and unsaved parameters
All modified and unsaved parameters will be saved in the memory.
9: resume all parameters to initial values at the last power-on
To restore all parameters to the initial values at the last power-on. Even after initialization, all
parameters can be restored to the preliminary power-on values with this function. This function is
used to make correction during field commissioning when the system works abnormally because no
one knows which parameter is modified incorrectly at the current power-on.
This function can only be used when the device is stopped. If this function is activated when the
device is running, the inverter will send alarm aL.059 and give up operation.
[F0.0.00] and [F0.0.01] are not limited by the parameter display mode, and will not
be concealed in any display mode. The panel displaying parameters concealed
due to parameter display mode will not influence the access to the concealed
parameter via communication port.
For modifying the system macro setting (kilobit) of the macro parameter F0.0.00, the modification
password 1580 must be entered. This password will automatically disappear after 30 seconds. The
macro parameter cannot be modified once within 30 seconds upon input of the password. If it is
intended to make modification once again, the password should be entered again.
This parameter is valid when LCD operating panel is configured, and is used to set language of LCD
display.
0: Chinese 1: English (the reserved option for this series of products)
F0.0.04 LCD display setting (H) Setting range: 0000~0037 Factory default: 0023
This function is only effective for the operating panel equipped with LCD.
The unit: Contrast ratio, setting range 0~7.
Tens: Normal display mode
0: Steady mode
1: Single parameter display
The LCD panel will only display the status parameters set for F0.0.12 in the normal monitoring mode.
F0.0.05 Parameter locking (H) Setting range: 0000~0012 Factory default: 0000
After the parameter locking is effective, during modification of the locked parameter, LED panel will
display “---”; LCD panel will prompt “password locked and modification forbidden”. This function is used
to forbid modification of functional parameters by unauthorized personnel.
The password setting will take effect if OK key is pressed down within 30 seconds. If no confirmation
(OK key) is conducted beyond 30 seconds or any other key is pressed down within 30 seconds, the
password setting will be given up. The sketch of locking operation is as below:
Main display 0 Main display F0.0.00 Main display F0.0.05 Main display 0000 Main display 0000
Auxiliary display 0.0 Auxiliary display 0000 Auxiliary display 0000 Auxiliary display 0.0 Auxiliary display 0.0
5
9 8 7 6
Main display 12345 Main display 0 Main display Main display Main display 0010
F0.0.06 F0.0.05
0 Auxiliary display 0.0
Auxiliary display Auxiliary display 0.0 Auxiliary display 0 Auxiliary display 0010
10
The locking password is
effective, and is 12345.
Main display F0.0.06 No keys are pressed within 30s Main display F0.0.06
Auxiliary display 12345 Auxiliary display 0
Enter preset password and then press OK, and then the parameter locking status will be relieved. The
sketch of unlocking operation is as below:
1 2 3 4 5
Main display 0 Main display F0.0.00 Main display F0.0.06 Main display 0 Main display 12345 Main display F0.0.06
Auxiliary display 0.0 Auxiliary display 0000 Auxiliary display 0 Auxiliary display 0.0 Auxiliary display 0 Auxiliary display 0
Successfully unlocked
F0.0.08 Parameter copying (H) Setting range: 0000~0013 Factory default: 0000
Uploading and downloading is forbidden when the inverter is operating, and the
settings of this parameter are invalid.
During parameter upload and download, all keys except for STOP key on the panel are temporarily
locked. Press STOP key to forcedly terminate upload and download; when the unload operation is
forcedly terminated, the parameters uploaded will be stored in the panel memory, and the
parameters not unloaded will be kept unchanged;
When the download operation is forcedly terminated, the inverter will give up all parameters already
downloaded into the control board memory, and automatically restore to the values before down-
load.
The alarm signal relevant with this parameter is as below:
aL.071 – Parameter unload failed. Uploaded parameters will be saved in the panel memory, and
parameters not uploaded will be kept unchanged.
aL.072 – Uploaded parameter storage failed. The panel memory is damaged or the memory is una-
vailable.
aL.074 – Parameter download failed. Terminate the parameter download process, and all parame-
ters downloaded will be automatically restored to the values before download.
aL.075 – The board memory parameters are not consistent with the frequency inverter parameters
in terms of the version.
aL.076 – There are no effective parameters in the board memory.
aL.077 – Some set values among the panel parameters are out of the allowable range. Terminate
the parameter download process, and all parameters downloaded will be automatically restored to
the values before download.
F0.0.11 Selection of panel key functions (H) Setting range: 0000~0224 Factory default: 0000
When the button locking function is set by this parameter, the locking will not take
effective unless ESC button is pressed to back to the normal monitoring mode.
See 5.2 Basic Function and Operating Methods of Control Panel for details.
• When the functional setting of PANEL/REMOTE keys is effective, and in the normal monitoring
mode, the PANEL/REMOTE keys can be used to switch the running command channel. The
switching status is not saved, and will get lost after power-off. The running command channel for the
inverter is still the operating panel after power-on once again.
• If PANEL/REMOTE keys are used to circularly switch to desired running command channel, it is
required to press “OK” key for confirmation within 5 s. Otherwise, it will not get effective.
• The switching sequence of the running command channel: Operating panel running command chan-
nel (PANEL/REMOTE light on)→external terminal operating running command channel (PANEL/
REMOTE light off) → communication port running command channel (PANEL/REMOTE light
flashing) → operating panel running command channel (PANEL/REMOTE light on).
The command channel switching at the running status of the inverter should
be used carefully. Be sure the safety before operation. If the running command
(FWD/REV/JOG) after switching is inconsistent with that before switching, the
inverter will change its current running status (stop, run or REV), which may
cause accident.
F0.0.12 Principal
Setting range: d0.00~d0.55 / d1.00~d1.55 Factory default: d0.00
monitoring parameter (H)
The corresponding physical quantity of the display data can be referred to the status monitoring
parameter table. When the inverter is conducting detection of motor parameters, the auxiliary display
will display the value of the current output current, which is not restricted by the parameter F0.0.13.
F0.1.20 Maximum
Setting range: 10.00~300.00Hz Factory default: 60.00
output frequency
F0.1.21 Upper
Setting range: [F0.1.22]~Min (300.00Hz,[F0.1.20]) Factory default: 50.00
limiting frequency
F0.1.22 Lower
Setting range: 0.0Hz~[F0.1.21] Factory default: 0.0
limiting frequency
1. The maximum output frequency is the allowable output maximum frequency of the inverter as set by
users (maximum stator synchronous frequency of the asynchronous motor);
2.The upper limiting frequency is the maximum frequency allowed for running of the asynchronous
motor as set by users (the maximum frequency corresponding to the mechanical rotor of the
asynchronous motor);
3.The maximum output frequency must be higher than the upper limiting frequency;
4.The lower limiting frequency is the minimum frequency allowed for running of the motor as set by
users.
5.The maximum output frequency, upper limiting frequency and lower limiting frequency shall carefully
set according to the actual nameplate parameters and operating status of the controlled motor and.
The relationship among the three is shown in Figure 7-7.
Output
输出电压 voltage
[F1.2.16]
Output
输出频率 frequency
[F1.2.15] in figure 7-7 represents the motor’s reference frequency, and [F1.2.16]
referents the motor’s reference voltage.
F0.1.23 FWD jog frequency Setting range: 0.0Hz~[F0.1.21] Factory default: 10.00
F0.1.24 REV jog frequency Setting range: 0.0Hz~[F0.1.21] Factory default: 10.00
Jog running is a special running mode of the inverter. No matter the inverter is initially stopped or
running, as long as the jog command is inputted, the inverter will transit to the jog frequency according
to the preset jog acceleration and deceleration time. However, it is also influenced by the startup
frequency and startup frequency duration as well as the functions of DC band-type braking, startup
delay and startup pre-excitation.
正转点动
FWD jog 减速时间 1/2/3/4
Deceleration time
频率
frequency FWD
正转点动jog
加速时间time
Deceleration 1/2/3/4
1/2/3/4
频率
frequency
时间
Time Time
时间
Jog signal Jog signal
点动信号
点动信号
2: Panel digital setting (maintained after stop and saved after power-off)
Similar to the case of “0,1” as above, the inverter will automatically save the current set value after
power-off, and take the saved value as the initial set value after power-on once again.
The relationship between the status setting combination of the three external switches and the current
frequency set value of the inverter is shown in Figure 7-2.
Preconditions for below instruction: multifunctional terminal DI1 frequency or process PID setting UP
function ([F3.0.00]=15), DI2 sets frequency or process PID DW function ([F3.0.03]=16), and DI5 sets
UP/DW with frequency clear function ([F3.0.04]=17).
UP switch
UP? ?
DI1 I 设
Set
n 定
DOWN?
Down ?
switch Frequency
频 Maintai Increas Deceas Maintai
DI2 ?v 端
子
Terminal 率 ned ed ed ned
Zero
Clear
? ? ?switch
? ?er 状
态
Status
DI5
?t DI1 OFF ON OFF ON Random
e
COM r DI2 OFF OFF ON ON Random
DI5 OFF OFF OFF OFF ON
6: Terminal UP/DW setting (maintained after stop and saved after power-off)
Similar to the case of “4” as above, the set value will be saved automatically after power-off, and the
initial set data will be the set value at the last power-off when the inverter is powered on once again.
The inverter’s actual running direction is according to “XOR” calculation of the command direction
(FWD, REV) and the set frequency direction.
8: Terminal UP/DW two-way setting (maintained in bipolar mode after stop and saved after
power-off)
The basic operation is similar to the case of “7” as above. The set value will be saved automatically
after power-off, and the initial set data will be the set value at the last power-off when the inverter is
powered on once again.
18: AI1+AI2
The frequency set value = the frequency value corresponding to the analog input AI1 + the frequency
value corresponding to the analog input AI2.
19: AI2+AI3
The frequency set value = the frequency value corresponding to the analog input AI2 + the frequency
value corresponding to the analog input AI3
22: AI1/AI2
The frequency set value= the frequency value corresponding to AI1/the frequency value corresponding
to AI2.
24: Compensation PID output (the reserved item of this function for this series of products)
To select the input physical channel of the inverter control commands (start, stop, forward, reverse,
jog and reset, etc).
0: Operating panel
The running control command is given via the operating panel. Please see Chapter 5 for the use of
the operating panel.
1: External control terminal
The running control command is given via external control commands, and the terminal function is
set by the parameter F3.0.
2: MODBUS fieldbus/standard expansion card configuration
The operation command is specified through the expansion communication mode.
F0.3.35 External control terminal Setting range: 0000~0013 Factory default: 0000
action mode (H)
The unit: Control command action mode
Preconditions for below instructions: the multifunctional terminal DI3 is for FWD command function
([F3.0.02]=7),DI4 is for REV function ([F3.0.03]=8), and DI5 is for three-line running control function
([F3.0.04]=19).
0: Two-line mode 1
1: Two-line mode 2 Control Operation
DI4 DI3 Figure
mode command
2: Three-line mode 1
OFF OFF Stop FWD I
When K0 is engaged, FWD and REV DI3 n
v
Two-line OFF ON FWD 变
control is effective; and when K0 is REV
e
mode DI4 频
r
unengaged, FWD and REV control is 1 ON OFF REV t
器
e
void, and the inverter will stop. COM r
ON ON Stop
DI3 terminal ascending edge indicates
OFF OFF Stop
FWD running command FW D
INVERTER
D I3
Kilobit: The action mode when the running permission signal is void
0: Free stop
The inverter stops outputting, and the motor stops freely.
1: Deceleration stop
The inverter will stop at deceleration mode according to preset deceleration time.
Start
启动允许 permission
运行允许permission
Running
运行命令
Running command
Auto clear
自动清 Re-giving
重新给 不清除命令
Not clear
command
除命令 command
定命令 command
电机状态
Motor status
加速时间
Acceleration 自由停机
time Free stop Deceleration
减速停机 减速时间 time
Deceleration
stop
F0.4.38 Start/Stop Mode (H) Setting range: 0000~0101 Factory default: 0000
At free stop, if it is needed to restart the motor before the motor stops running completely, it is
necessary to appropriately configure the revolution tracking start function; otherwise, it will leads to
overcurrent or overvoltage fault protection.
If the motor has not stopped completely in deceleration way, because of high load inertia of the field
work and short deceleration time, it is then applicable to start DC band-type braking control. See the
instructions of the parameter F0.4.44 for details.
Free stop
自由停机
Motor revolution
电机转速
Inverter 变频器
output
输出频率
frequency
Running
运行指令
command
Detecting检测电机转速及方向
motor revolution and direction
F0.4.40 Start frequency holding time Setting range: 0.00~10.00Sec. Factory default: 0.0
The start frequency means the initial frequency when the inverter starts up, and is not limited by the
lower limiting frequency F0.1.22.
The start frequency holding time means the duration of operation at the start frequency, and can be
set according to actual needs. When it is set to 0, the start frequency is void.
For the system with high inertia, heavy load and high requirement of start torque, the start frequency
can effectively overcome the difficult of start, and the start frequency is also effective in each
acceleration process when the inverter switches between forward and reverse running.
频率 Current
电流
Frequency
[F1.2.15] [F0.4.41]
F[0.4.41]
Current
Output
输出频率
[F0.4.39] frequency
[F0.4.40] 时间
F[0.4.42]
[F0.4.42]
Figure 7-14 Start Frequency Sketch Figure 7-15 Start Frequency Sketch
F0.4.41 Start pre-excitation current Setting range: 0.0~100(%) Factory default: 35.0
F0.4.42 Start pre-excitation time Setting range: 0.00~10.00Sec. Factory default: 0.10
It costs some time to develop air gap flux for asynchronous motor (approaching to the constant of the
rotor time). When it is at stop status before the motor is started, in order to get enough start torque, it is a
must to develop the air gap flux. Therefore, it is needed to start pre-excitation for the asynchronous
motor. See Figure 7-15 for the pre-excitation process.
The set value of start pre-excitation current is the percentage with respect to the inverter rated output
current.
The start pre-excitation time means the duration in which the inverter inputs start pre-excitation current
for the inverter.
When the rated current of the adapter motor differs greatly from the rated current
of the inverter, please carefully set the pre-excitation current (F0.4.41), as
excessive setting may damage the motor.
Start delay means the waiting time before the inverter starts after receiving the running command.
F0.4.44 DC band-type brake control (H) Setting range: 0000~0001 Factory default: 0000
When both the set value and the actual speed of the motor has decreased below [F0.4.45], the inverter
will stop generating sine current but will inject direct current to the motor, and the current value is to be
set by the parameter [F0.4.47]. When the given speed or the motor speed has surpassed the
parameter [F0.4.45], the inverter will stop DC power supply and restore to the normal running status. If it
is started, the permission signal will be disconnected, and the DC band-type brake will be void.
参考值
Reference value
[F0.4.45]
时间
Time
电机转速
Motor revolution DC band-type
brake
直流抱闸
时间
Time
Injecting current to the moor may lead over-temperature of the motor. In the
circumstances where long-time DC band-type brake is needed, forced air-cooling
motor should be used. During the long time of band-type braking, if there is con-
stant load in the motor band-type brake, DC band-type brake will not guarantee
that the motor shaft will not rotate.
F0.4.46 DC brake action time Setting range: 0.0~10.00Sec. Factory default: 0.0
The DC band-tape brake/brake injection current means the brake current outputted at the time of
inverter DC band-type brake/brake. Its set value is the percentage with respect to the rated current.
DC brake
Output initial
frequency frequency
Start
frequency Start
起动频率 frequency
起动频率 holding
保持时间 time
DC brake action time
直流制动作用时间
Stop
Start Running
运行时间 time
起动频率 DC brake
直流制动
Start frequency initial
FWD and REV
正反转 起始频率
frequency dead zone time
死区时间 frequency
holding time
The forward and reverse transition dead time is used to set the waiting time for the motor to shift from
FWD to REV or from REV to FWD. This function is used to overcome reversal current compact caused
by mechanical dead zone, as shown in Figure 7-18.
Output
输出频率 frequency Output frequency
输出频率
Time
时间 Time
时间
-[F0.4.39]
[F0.4.50]
[F0.4.50]
Figure 7-18 FWD and REV Transition Dead Zone Figure 7-19 Sketch of Start Frequency FWD and
F0.4.51 Forward and reverse switch mode Setting range: 0, 1 Factory default: 0
F0.4.53 Zero speed delay time Setting range: 0.0~10.00Sec. Factory default: 0.1
When the inverter output frequency is lowered to zero, it will immediately lock the output. At this time,
the motor revolution may not at zero, but the motor is completely at the free stop status, and will slide to
stop.
Within the delay time, when the inverter output frequency is lower than the zero speed (frequency)
detected level [F0.4.52], within the zero speed delay time [F0.4.53], the inverter will keep working and
output a DC current, and the motor will keep excitation. The inverter may rapidly restart at any time.
无零速延时 零速延时
No zero speed delay Zero speed delay
Speed
速度 速度
Speed
[F0.4.52] [F0.4.52]
Time
Time
时间 时间
[F0.4.53]
Figure 7-20 Comparison diagram when with or without zero speed delay
As shown in item ① in Figure 7-21, the acceleration starting/deceleration ending period of S curve is
indicated by the percentage of the total acceleration and decoration time.
As shown in item ② in Figure 7-21, the acceleration rising/deceleration decreasing period of S curve is
indicated by the percentage of the total acceleration and decoration time.
Output frequency(Hz)
Straight line
2 2
S Curve
1 1
Time
[F0.0.01] [F0.0.02] (Sec./min.)
F1.0.03~F1.0.08
Setting range: 0.01~600.00 (Sec./Min.) Factory default: ☆
Acceleration/deceleration time 1/2/3
F1.0.09
Setting range: 0.01~600.00 (Sec./Min.) Factory default: ☆
Acceleration 4/jog acceleration time
F1.0.10
Setting range: 0.01~600.00 (Sec./Min.) Factory default: ☆
Deceleration 4/jog deceleration time
The acceleration time means the time required for the inverter to accelerate from 0.00Hz to maximum
output frequency [F0.1.21].
The deceleration time means the time required for the inverter to decelerate from the maximum output
frequency [F0.1.21] to 0.00Hz.
E280 series inverters are defined with 4 kinds of acceleration/deceleration time. The acceleration/
deceleration time 1~4 during the running process of the inverter can be selected through different
combinations of external terminals. During simple PLC running, it is also applicable to use them as the
acceleration and deceleration time at the time of switching among different running frequency at each
stage. See instructions of F6.1 group parameters for detail.
The acceleration/deceleration time 4/jog acceleration/deceleration time are also used as the accele-
ration and declaration running time at the status of jog running. The jog frequency has the highest
priority. At any state, the inverter will immediately transit to the jog frequency running state according to
the preset jog acceleration and deceleration time as long as the jog command is inputted. (See the
instructions of the functional parameter F0.1.23 and F0.1.24) the unit (sec., min.) of the acceleration and
deceleration time is determined by the tens’ digit of the parameter F1.0.00.
Frequency
Time
Acceleration and deceleration
time selection terminal 1
Acceleration and deceleration Acceleration/ Acceleration/
time selection terminal 2 Acceleration/ Acceleration/ deceleration deceleration
deceleration deceleration time 3 time 4
time 1 time 2
Operation command
Figure 7-22 External Terminal Selection Mode for Acceleration and Deceleration Time
The time for decelerating from the maximum output frequency [F0.1.20] to the zero frequency will only
function when the inverter stops in deceleration way (F0.4.54 is set to 0) after receiving EMS emergency
stop command (function no. 14).
It is the switch frequency determining the inverter’s internal power module. The allowable maximum
carrier frequency is relevant with the inverter model. The carrier frequency mainly influences the audio
noise and heat effect during running. When mute running is required, it is applicable to appropriately
increase the value of the carrier frequency, but the maximum load allowable for the inverter may be
somewhat reduced, accompanied by somewhat increase of interference of the inverter to the outside
world. For the circumstances where the motor wire is too long, it may lead to leaking current between
motor wires and between the wire and the ground. When the ambient temperature is too high and the
motor load is too high, or the inverter is failed due to above reasons, it is suggested to appropriately
decrease the carrier frequency to improve thermal characteristics of the inverter.
Setting range:
F1.2.16 Reference voltage of motor Factory default: 380/220
50~500V/25~250V
The reference frequency means the minimum frequency when the inverter outputs the maximum
voltage, and generally is rated frequency of the motor.
The reference voltage means the output voltage when the inverter outputs the reference frequency, and
generally is rated voltage of the motor.
This group of parameters is set according to the motor’s parameters, and do no need to be modified
except for special circumstances.
F1.2.18 Motor torque increasing voltage Setting range: 0.0~20.0% Factory default: ☆
It is used to improve the inverter’s low frequency torque characteristics. When the inverter runs at
low frequency, it will make compensation for the inverter's output voltage. Its set value is the
percentage relative to the motor’s reference voltage [F1.2.16]. See figure 7-23-A and 7-23-B.
? ?
Voltage Voltage
电压
[F1.2.15] [F1.2.15]
[F1.2.18]
? voltage
? ? ? [F1.2.18]
Boost
Boost提升电压
voltage
[F1.2.16] ?Frequency
? [F1.2.16] 频率
Frequency
Figure 7-23-A Sketch of Torque Booster for Figure 7-23-B Sketch of Torque Booster for Constant
Descending Torque Curve Torque Curve
F1.2.19 Frequency point 1 of motor V/F curve Setting range: 0.0~[F0.1.21] Factory default: 0.0
F1.2.20 Voltage point 1 of Motor V/F curve Setting range: 0~500V Factory default: 0.0
F1.2.21 Frequency point 2 of motor V/F curve Setting range: 0.0~[F0.1.21] Factory default: 0.0
F1.2.22 Voltage point 2 of Motor V/F curve Setting range: 0~500V Factory default: 0.0
F1.2.23 Frequency point 3 of motor V/F curve Setting range: 0.0~[F0.1.21] Factory default: 0.0
F1.2.24 Voltage point 3 of Motor V/F curve Setting range: 0~500V Factory default: 0.0
This group of parameters is used to flexibly set V/F curve desired by users, as shown in Figure 7-24.
Voltage
电压
[F1.2.16]
F[1.2.16]
[F1.2.24]
F[1.2.24]
F[1.2.22]
[F1.2.22]
[F1.2.20]
F[1.2.20]
[F1.2.19] F[1.2.21]
F[1.2.19] [F1.2.21] [F1.2.15] 频率Hz
[F1.2.23]F[1.2.15]
F[1.2.23] Frequency(Hz)
F1.2.25 Motor slip frequency compensation Setting range: 0~150(%) Factory default: 0
The actual revolution difference of the motor may vary with the change of the load. Through setting of
this parameter, the inverter will automatically adjust the inverter's output frequency according to the load,
so as to offset the influence of the load to the motor revolution.
Acceleration
Frequency
频率 time adjustment
加速时间调整
Output current
Output current Slip compensation is 100%
Slip compensation is 100%
150%
150%
Time
时间
Current
电流
100%
100% After slip
Before slip
Before slip compensation After slip compen
compensation
compensation [F1.4.39]
50%
50%
Motor revolut
Motor revolution
Time
时间
Figure7-25 Sketch of Slip Frequency Compensation Figure 7-26 Sketch of Acceleration and
Deceleration Current Limit
When the output current of frequency inverter exceeds the specified level of this parameter,
acceleration and deceleration time will be automatically delayed, to ensure the output current limited
within the range of this level, refer to the figure 7-26. Thus, for occasions requiring shorter acceleration
time, acceleration torque level shall be properly improved.
F1.4.40 Strong start current limiting level Setting range: 120~200 (%) Factory default: 150(%)
F1.4.41 Strong start current holding time Setting range: 0.00~5.00Sec. Factory default: 0.0
Function is similar with [F1.4.39], limit the current value when frequency inverter is in acceleration and
starting. For some systems with large inertia, or requires to overcome great static friction at start, large
starting current can be set for a certain time ([F1.4.41]), to meet the requirement. Setting value is the
relevant percentage of rated output current of frequency inverter.
When F1.4.41 is set as zero, it means the function of current limit of strong start is
closed.
F1.4.42 Function selection for adjustors Setting range: 0000~0111 Factory default: 0111
F1.4.43 Action level of the overvoltage adjustor Setting range: 660~800V Factory default: 740
F1.4.44 Overvoltage adjusting gain Setting range: 0.10~10.00 Factory default: 1.00
When the motor is dragging overvoltage or in process of deceleration stop with large inertia, it may
access into recycle braking state, causing rapid rise of direct current bus voltage of frequency inverter,
leading to overvoltage protection action. When frequency inverter detects the direct current bus voltage
exceeds [F1.4.43], it will adjust output frequency (extended deceleration time or increase frequency), to
ensure continually safe running.
Frequency Frequency
频率增加 incase
频率
[F1.4.20] Frequency
频率
[F0.1.20]
Extension of
deceleration time
延长减速时间
Voltage直流侧电压
at the DC side Time
时间 Voltage at直流侧电压
the DC side Time
时间
[F1.4.43]
[F1.4.43] [F1.4.43]
[F1.4.43]
Time
时间 Time
时间
The larger the overvoltage adjusting gain is, the more obvious the suppression is, but
it may lead to unsteady running.
F1.4.45 Action level of the undervoltage adjustor Setting range: [FF.2.35]~480V Factory default: 330V
F1.4.46 Undervoltage adjusting gain Setting range: 0.10~10.00 Factory default: 1.00
When frequency inverter detects the direct current bus voltage is below [F1.4.45], it may lower output
frequency automatically, accessing into recycle braking state, keep running with mechanical energy.
The larger the undervoltage adjusting gain is, the stronger undervoltage suppression is.
Frequency
频率 Frequency
频率增加incase Frequency
Output frequency(Hz)
[F0.1.20]
Straight line of deceleration time
Extension
2 2
Time Time
时间
Voltage at the DC side
直流侧电压 VoltageS
at Curve
the DC side
[F1.4.43]
1 1
Time
Time
时间 0 01] [F0 0 02] (Sec./min.)
Time
Figure 7-28-A Sketch of Undervoltage Adjusting Figure 7-28-B Sketch of Undervoltage Adjusting
F1.4.47 Action level of current limiting adjustor Setting range: 20~200(%) Factory default: 180
F1.4.49 Recovery times of fault self resetting Setting range: 0~5 Factory default: 0
F1.4.51 Time period for self resetting timing Setting range: 900~36000Sec Factory default: 3600
Fault self resetting refers to that when the frequency inverter breaks down, with a period of time, fault
self resetting can be operated and recover to run with starting way of speed inspection. When
accumulated resetting times exceeds setting value [F1.4.49], self resetting action terminates. When self
resetting time [F1.4.49] is set as zero, it means this function is banned.
Recovery waiting time of fault self resetting gets longer with resetting times: waiting time=[F1.4.50] *
already reset times.
Each time it passes the set parameter period [F1.4.51], or external forced fault reset, it will automatically
eliminate one self resetting record.
F1.4.52 Self-restoration fault selection Setting range: 0000~1111 Factory default: 0.000
F2.0.10 Slip compensation coefficient Setting range: 0.50~1.50 Factory default: 1.00
Slip compensation coefficient is used for slip frequency calculation, valid with vector control mode.
With SVC running, this parameter can be amended to adjust speed for compensation control
F2.0.24 Z pulse initial angle Setting range: 0.0~359.9 Factory default: 0.0
This parameter is valid when Z pulse selection is valid ([F8.0.07] = 1), used for set corresponding
mechanical rotating angle of Z pulse position.
This parameter is used for setting sensitivity of heat relay protection to load motor of frequency
inverter. When the rated current of the load motor does not match with the rated current of the
inverter, correct thermal protection can be secured by setting this value.
The set value of this parameter can be confirmed through below formula:
[F2.0.25]=motor rated current /inverter rated current*100%.
When fixed value of this parameter is 131.0%, overload protection function of motor closes.
When one frequency inverter runs with several motors in parallel, function of heat
relay protection of frequency inverter will be out of action automatically. In order to
protect motor efficiently, it is suggested that installation of heat protection relay in
each motor.
This parameter is valid with vector operation; the pre-excitation action must be conducted prior to start
of motor, to build air gap flux to obtain enough starting torque. This excitation process shall be conducted
after action defined of parameter F0.4.42, excitation current shall be calculated automatically as selected
time. The shorter the excitation time is, the larger the current is.
Motor parameter measurement function must be started when vector control mode is selected (tens of
F0.0.09 is set as 0 or 1).
When this function (when F2.2.53 is set as 1 or 2) is enabled, parameter identification operation will be
carried when the frequency inverter is start. After parameter identification is over, F2.2.53 will be
automatically reset. Obtained motor parameters will be stored in internal memory of the frequency
inverter, and value of parameter F2.0.05 ~ F2.0.09 will be automatically updated.
0: Closed
1: Static identification
During parameter setting, the motor will be always kept in stop status (idling motor may be subject to
slight offset of axis angle).
2: Static + operating identification
Frequency inverter will conduct static identification at first, and then automatically start operation
identification process. During operation identification process, stop order can be input to forcedly
terminate identification process. At that time, the identification request is not cleared out, so when
restarted, identification process will be enabled again.
Top operating frequency of operation identification will reach 80% of rated frequency of motor. Before
identification starts, please be sure to confirm the equipment safety, and it will automatically stop
operating when identification ends.
Control terminals Dl1~Dl9/Fin are functional programmable switch input terminals; they can define
the Dl1~Dl9/Fin functions respectively by way of the setup of F3.0.00~F3.0.08 values; See their set
values and relevant functions in Exhibit 1 (Comparison Table of Multifunctional Terminals (DI/EDI/
SDI) Function).
For example: Define F3.0.00 as 23, so the function of DI1 can be defined as "Simple PLC Multistage
Operation Input"; when the DI1 terminal status validates, simple PLC multi-stage operation input
function can be realized.
正转/停止
FWD/Stop
The command of
禁止加减速指令
forbidding acceleration
and deceleration
输出频率
Output frequency
时间
Time
保持
Holding 保持
Holding
Table 7-12 Maximum torque limit selection contrast table of frequency inverter
Terminal status Maximum torque limit setting value
ON Maximum torque limit 2
OFF Maximum torque limit 1
37: Reserved
38: Load dynamic balance effective
39: Communication linkage setting effective
During communication linkage control, the linkage setting of (effective) slave machine can be
separately removed. Then other setting channel can be automatically selected according to the
priority setting.
40: RS485 external/Standard operation panel switching
When two operation panels are inserted to frequency inverter at the same time, one is for master
control panel switching, and the other is for monitoring only, and the order cannot be inputted in.
Table 7-13 Control command channel switching and selecting table for frequency inverter
Terminal state Control command channel of frequency inverter
ON RS485 external panel
OFF Standard operation panel
This terminal is used for resetting of single pulse accumulative length counting value.
62~64: Reserved parameters
65: Input magnetic flux brake
It is applied to input and removal of magnetic flux brake during the deceleration halt process.
66: Position pulse counting resetting
The inverter contains a 32-bit PG encoder pulse accumulative /regressive device, which is used to
display the current position of the transmission shaft (PG mounting shaft) (monitoring parameter
d1.2.18~19). This function is used for value clearing of pulse accumulative/regressive device.
67: Automatic shifting
This function is especially used for transmission machineries with mechanical shifting function (e.g.
machine tool drive)。 When it is effective, the inverter will drive motor to rotate forward or reversely
at low speed, so as to facilitate smooth shifting and avoid mechanical lock.
68~96: Reserved
97: Pulse input port (0.10 ~ 100.00 KHz)
This function is applied to multi-function input terminal DI9/Fin (F3.0.08), and signal of 0.10~
100.00 KHz can be received effectively.
98: Pulse input port (1.0 ~ 1000.0Hz)
This function is applied to multi-function input terminal DI9/Fin (F3.0.08) and low frequency signal
of1.0~1000.0Hz can be received effectively.
Set the filtering time of the input terminal detection. When state of the input terminal changes, while
after the setting filter time setting it remains the same, the change of terminal state is effective,
otherwise it will remains the former state, thus the interference triggered by false operation can be
reduced.
F3.0.11 Input terminal effective level (H) Setting range: 0000~01FF Factory default: 0000
Table 7-15 Correspondence between Binary Number Setting and Digital Show Value
F3.1.12 Multifunctional output terminal DO1 Setting range: 0~71 Factory default: 1
F3.1.13 Multifunctional output terminal DO2 Setting range: 0~71 Factory default: 2
F3.1.21 Multifunctional relay output (RO1A/B/C) Setting range: 0~71 Factory default: 4
The control terminal D01-D03 is the on-off output terminal with programmable function, and its functions
can be defined by set values of F3.1.12-F3.1.14; output R01and R02 of relay is on-off output terminal
with programmable function, which can be defined by set values of F3.1.21 and F3.1.22. Please refer to
the attached list for their setting values and corresponding functions (Reference table of variables of
multi-function output terminal (DO/EDO/SDO).
1: Inverter running ready
When inverter is in normal running ready state, terminal will output effective signal/relay will pick up
(connection of TA and TC).
2: Inverter is running
When the inverter is in running state, terminal will output effective signal/relay will pick up.
3: Equipment normal
When inverter is fault free, and DC busbar voltage is normal, terminal will effectively indicate signal/
relay will pick up.
4: Equipment fault
When inverter goes wrong and sends fault signal, terminal will output effective signal/relay will pick up.
5: Equipment alarm
When there is exception of inverter and sending warning signal, terminal will output effective signal/
relay will pick up.
6: Equipment fault or alarm
When there is fault for exception of inverter and sending fault or warning signal, terminal will output
effective signal/relay will pick up.
7: Reverse running
When electric motor rotates reversely, the terminal will output the valid signal/relay will pick up.
8: Valid running command
When running instruction of inverter is valid, the terminal will output the valid signal/relay will operate.
9: Running at zero speed
When running instruction is valid but output frequency of inverter is at zero and there is current output,
terminal will output effective signal/relay will pick up.
10: Speed not at zero
When the speed of rotator of electric motor is not at zero (VC mode) or output frequency is not at zero
(VF or SVC mode), terminal will output the valid signal/relay will pick up.
11: Inverter undervoltage stop
When inverter is in under-voltage stop and reporting Fu.008, the terminal will output the valid signal/
relay will pick up.
12: Valid external control
When control command of frequency converter is given not on panel, terminal will output the valid
signal/relay will pick up.
14: Running at power generating status (braking)
When inverter is in regenerative braking running state, terminal will output the valid signal/relay will pick
up.
19: Completion of current stage of multi-stage running (0.5s pulse)
After completion of current stage of multi-stage running, terminal will output the valid pulse signal with
0.5S width/relay will disconnect after pick-up for 0.5S.
20: Multi-stage running completed (0.5S pulse)
After completion of one cycle of multi-stage speed running, terminal will output the valid impulse signal
with 0.5S width/relay will disconnect after pick-up for 0.5S.
21: Multi-stage running completed (continuous level output)
After completion of one cycle of multi-stage speed running, terminal will output continuous valid
signal/relay will pick up.
22: Multi-stage running cycle completed (0.5Spulse)
After completion of one cycle of multi-stage speed running, terminal will output effective impulse
signal with 0.5S width/relay will disconnect after pick-up for 0.5S.
23: Swing frequency upper and lower limit
After selection of wobbulation, if the frequency fluctuation range of wobbulation, which calculated
based on center frequency, is above upper limit frequency F0.1.21 or below lower limit frequency
F0.1.22, then terminal will output effective signal/relay will pick up.
24: Encoder direction
It is used to indicate the directional signal output by current encoder frequency division.
26/29/32: Monitoring parameters 1/2/3 below the lower limit
When monitoring parameters 1/2/3 are below the lower limit values, terminal will output the valid
signal/relay will pick up, which keeps until monitoring parameters 1/2/3 are above the upper limit
values, then output the invalid signal/relay disconnects (as shown in figure 7-30-A).
Monitor
监控器参数值 reference value Monitor
监控器参数值 reference value
Upper
上限值 limit Upper
上限值limit
Lower
下限值 limit Lower
下限值limit
时间Time 时间
Time
Relay
继电器吸合 pull-in Relay
继电器吸合pull-in
时间Time Time
时间
Figure 7-30-A Monitor Functional Sketch 1 Figure 7-30-B Monitor Functional Sketch 2
Upper
上限值 limit
Lower
下限值 limit
Time
时间
Relay
继电器吸合 pull-in
Time
时间
F3.1.27~ F3.1.29 monitor 1-3 variable selection Setting range: 0~44 Factory default: 0~2
Different state parameters can be monitored by setting the values of F3.1.27~F3.1.29 (please refer to
“Comparison Table of Monitor Variables”).
7.14 Pulse input (this group of parameters will effective when expansion I/O
board is configured and D19 selects frequency input function) (Group F3.2)
F3.2.36 Minimum pulse input
Setting range: 0.0~100.00KHz Factory default: 0.0
frequency DI9/Fin
This group of parameters defines multi-function input terminal DI9/Fin as frequency range and
detection cycle of external pulse signal for pulse input (F3.0.08 is set as 97-98), effective breadth of
external pulse signal is 5-30V.
F3.2.39 Number of single-loop pulse Setting range: 1~4096 Factory default: 1024
When input frequency signal of DI9/Fin terminal is used for length accumulation or speed
measurement, these parameters are used to set pulse signal quantity for each rotation of encoder.
F3.2.40 Mechanical transmission ratio Setting range: 0.010~10.000 Factory default: 1.000
This group of parameters is used for linear speed calculation or length accumulation.
Mechanical transmission ratio = driving wheel revolution/revolution of speed measuring coded disc.
Setting range:
F3.2.42 Maximum accumulative length value Factory default: 50000
10m~50000m
Setting range:
F3.2.43 Maximum liner speed Factory default: 10.00m/s
0.01~500.00m/sec.
To limit the maximum accumulative length and maximum liner speed. The terminal signal can be input
when it reaches or exceed the maximum value.
F3.2.44 Current accumulative length value Setting range: 0~50000m Factory default: —
7.15 Pulse output (this group of parameters will effective when expansion I/O
board is configured and DO3 selects frequency output function) (Group F3.3)
F3.3.46 Type of output pulse signal DO3/Fout Setting range: 0~2 Factory default: 0
F3.3.50 DO3/Fout assignment lower limit Setting range: 0.0~[F3.3.51] Factory default: 0.0
F3.3.51 DO3/Fout assignment upper limit Setting range: [F3.3.50]~100.0% Factory default: 100.0
This group of parameters can determine the corresponding relationship between maximum, minimum
frequency of the pulse output DO3/Fout and its pulse output mapping variables, while the set values are
the percentages of full pulse output mapping variables. Corresponding relationship between the two
parameters is as shown in figure 7-31:
Fout输出频率
Fout output frequency
[F3.3.48]
[F3.3.47]
Corresponding
对应变量 variable
Corresponding variable Corresponding
对应变量
variable
最大值 max.
Corresponding
variable max. Corresponding
对应变量
variable
最小值 min.
[F4.0.00] AI1
[F4.0.01]
- Corresponding
-对 应 变 量
Corresponding variable min.
variable min. 最小值
[F4.0.00]+[F4.0.01]
2
- Corresponding
-对 应 变 量
[ F 4 .0 . 0 0 ] [ F 4 .0 .0 1 ] variable max.
最大值
Figure 7-32-A Sketch of AI1 Analog Input and Figure 7-32-B Sketch of AI1 Analog Input and
Corresponding Variables (Unipolarity) Corresponding Variables (bipolarity)
Corresponding variable
Corresponding variable Corresponding
variable max.
Corresponding
variable max. Corresponding
variable min.
-[F 4 .0 .0 5 ] [F 4 .1 .1 7 ]
A I3
-[F 4 .1 .1 7 ]
Corresponding
variable min.
-Corresponding
variable min.
[F4.0.04] [F4.0.05] AI3
- Corresponding
variable max.
Figure 7-33-A Sketch of AI3 Analog Input Figure 7-33-B Sketch of AI3 Analog Input
and Corresponding Variables (Unipolarity) and Corresponding Variables (Unipolarity)
When the unipolar input signal AI1 and AI2 are applied as bipolar signal, if input
signal disconnects and input value is maximum reserve setting, it may be dange-
rous to human and property safety. Please use in combination with disconnection
fault detection function of analog input port.
Carry out filtering treatment to external analog input quantity to effectively eliminate interference
signal. Filtering time constant (time needed for given signal rising to 63% of stable value) should be
set properly according to fluctuation range of external input signal, if it is too high, anti-interference
capacity will be strong while delaying the response speed to setting signal.
This group of parameters is used to conduct nonlinear correction to analog input value as required.
Curve correction of analog input AI1 is as shown in figure 7-34, while the curve correction methods of
AI2 are similar to analog input AI1.
AI1
A Iper
1 标unit
幺 value
值
Curve before
矫 正 correction
前曲线
矫正值2
Correction value 2
[ F 4 .0 .1 2 ]
Correction
矫 正 点point
1 1 Correction
矫 正point
点 22 A I1
[ F 4 .0 .0 9 ] [ F 4 .0 .1 1 ]
Set hysteresis width of middle point between maximum value and minimum value of AI3, when it is
applied as bipolar signal, forward and reverse fluctuation of zero setting value will be frequent as shown
in Figure 7-34. It should be set to 0 when applied as unipolar signal.
This group of parameters is used to conduct nonlinear correction on analog input values if necessary.
The curve correction method for analog input AI3 is similar to that for analog input AI1. Refer to figure
7-34 for the curve correction.
Multifunction analog output AO1, AO2 can output voltage signal of 0~10V or current signal of
1~20mA, selected by the dial switch on the control board. Frequency inverter status represented by
the analog output signal is set by this group of parameters. Please see Appendix 3 (comparison
table of status variable).
F4.2.26 AO1 lower limiting value Setting range: 0.0~[F4.2.27] Factory default: 0.0
F4.2.27 Upper limiting value Setting range: [F4.2.26]~100.0% Factory default: 100.0
F4.2.32 Lower limiting value/standard
Setting range: 0.0~[F4.2.33] Factory default: 0.0
expansion card
Corresponding relationship between maximum and minimum of AO1, AO2 output given by this
group of parameters and mapping variable (see figure below), whose set value is the percentage
relevant to the full output of mapping variable of AO1, AO2.
AO Output voltage
AO输出电压
AOAO最大值
maximum
AO最小值
AO minimum
AO assignment
AO赋值下限 AO assignment Per
AO赋值上限 unit value of AO
AO映射
upper lower limit upper limit 变量标幺值
mapping variable
F4.2.28 AO1 AO1 filtering time coefficient Setting range: 0.01~10.00Sec. Factory default: 0.10
Setting range:
F4.2.29 AO1 fixed output value Factory default: 0.0
0.00~20.00mA (0.00~10.00V)
F4.3.39 Action selection after AI1 wire-break Setting range: 0~4 Factory default: 0
F4.3.43 Action selection after AI2 wire-break Setting range: 0~4 Factory default: 0
F4.3.48 Action selection after AI3 wire-break Setting range: 0~4 Factory default: 0
Define corresponding actions after frequency inverter detects analog input wire-breakage.
0: No action (for non-stop alarm)
When detecting analog input wire-break, if the frequency inverter operates normally, it only reports
aL.036-aL.038 warning signal. If the wire-break fault is cleared, the warning signal can be cleared
automatically.
If the wire-break fault is cleared, the warning signal can be cleared automatically, meanwhile, the analog
input signal is restored to input value.
[F5.0.04] [F5.0.05]
[F5.0.02] [F5.0.03]
[F5.0.00] [F5.0.01]
Time
[F5.1.09]
[F5.1.10]
Trigger
触发信号signal
Signal
时钟(S) (S)
Comparative value比较值到达(脉冲)
reaching (pulse) Reset
复位
Comparative value比较值到达(电平)
reaching (level)
Figure 7-37-A
Schematic diagram of comparison value of timer 1 reaching for the basic function (F5.1.06=11#1)
[F5.1.09]
[F5.1.10]
Trigger
触发信号signal Signal
时钟(S) (S)
REV after
周期到达反转reaching the cycle
Figure 7-37-B
Schematic diagram of comparison value of timer 1 reaching for the basic function (F5.1.06=10#1)
[F5.1.09]
Clock
时钟
Trigger signal
触发信号
Gating
门控信号signal
Figure 7-37-C
Starting trigger and gate control signal function of timer 1 (UT1) (F5.1.06=1111;F5.1.15=0001)
UT1
[F5.1.09]
Trigger
触发信号 signal
时钟
Clock
UT2
Trigger
触发信号 signal
Signal
时钟
Figure 7-37-D
Pulse concatenation function of timer 1(UT1) (F5.1.06=10#1;F5.1.07=###3)
UT1
Timing
定时周期cycle
Trigger signal
触发信号 Clock
时钟
Trigger
触发信号 signal
UT2
Clock
时钟
UT1UT1
cycle reaching signal UT2
周期到达信号作为 as the trigger signal of UT2
触发信号
Trigger
触发信号 signal
UT3
时钟
Clock
UT2
UT2 cycle reaching signalUT3
周期到达信号作为 触发信号
as the trigger signal of UT3
Differences: Counter will continue to count upwards without reset, and start from 0 on until overflew.
Set
设定值 value22
Set
设定值 value11
Clock
时钟脉冲 pulse
Set value设定值
1 reaching (0.5 Sec. pulse)
1 到达(0.5s 脉冲) Reset
复位
设定值 1 1到达(电平)
Set value reaching (level)
Set
设定值value22
Set
设定值value 11
Clock
时钟脉冲 pulse
Set value设定值
2 reaching (0.5 Sec.脉冲)
2 到达(0.5s pulse) 复位
Reset
Set value
设定值 2 reaching (level)
2 到达(电平)
设定值
REV 2 到达反转
after reaching set value 2
设定值
Set value 1 或设定值
1 or set 2 到达反转
value 2 reaching REV
This parameter applies to the situation that frequency inverter operates with V/F mode; forcedly operate
with VC, SVC modes. Automatic voltage regulation function is used for ensuring the output voltage of
frequency inverter not fluctuates as the input voltage fluctuates. In condition that grid voltage fluctuates
greatly, while stable stator voltage and current of motor is required, this function shall be operated.
F5.3.29 Lower limiting frequency action mode Setting range: 0, 1 Factory default: 0
0: Output 0 frequency when it is below the lower limiting frequency
If the inverter’s frequency setting value is lower than the lower limit frequency, the output frequency of
the inverter is zero.
1: Output the lower limiting frequency when it is below the lower limiting frequency
If the inverter’s frequency setting value is lower than the lower limit frequency, the output frequency of
the inverter is the lower limit frequency.
Frequency inverter can increase the magnetic flux when the motor slows down to stop, to make the
motor stop more rapidly (see figure below).
The electric energy produced during the braking process is manly consumed in form of heat inside of
the motor. Therefore, frequent braking with magnetic flow will lead to the internal temperature of the
motor increase. Please be sure the motor temperature shall not over the maximum admissible value.
When input operation order during magnetic flow braking, magnetic flow will be canceled, and frequency
inverter will speed up again to the selected frequency.
有磁通制动
Brake with magnetic flux
40
0 Time
25 50 Frequency
频率(Hz) Hz
Figure 7-39 Magnetic Brake curve Figure 7-40 Energy Consumption Brake
F5.3.35 Use ratio of dynamic braking Setting range: 50~100% Factory default: 100
Utilization rate of dynamic braking is used to define the average voltage value forced on braking
resistor of braking unit action. Voltage on braking resistor is pulse width modulation wave. Duty ratio
equals to action ratio of dynamic braking. The large the action ratio is, the faster energy releases,
and the more obvious the effect is, as well as the larger power consumed on braking resistor is.
Operator may consider setting the parameters comprehensively according to the resistance of
braking resistor, power and required braking effect.
Only valid with V/F control method. Selecting this parameter can restrain the output current oscillation.
Set 0.0 to close this function. The larger the value is, the slower restraining action is and the wider the
biggest adjustment range is
F5.3.39 Reference source for dynamic balance load Setting range: 0 ~ 4 Factory default: 0
F5.3.40 Reference value for dynamic balance load Setting range: 0.0~200.0% Factory default: 100.0
F5.3.41 Dynamic balance adjustment gain 0.0 ~ 100.00 (%) Factory default: 50.00
F5.3.42 Dynamic balance adjustment limit 0.0 ~ 100.00 (%) Factory default: 1.00
Load dynamic balance function is used for balancing load with multiple motors linkage, or occasions
requiring torque motor characteristics of "Frequency inverter-asynchronous electrical units".When this
function is valid, frequency inverter shall take the input value of dynamic balance load reference source
(relative value of rated current) as reference, automatically amend the input of frequency/revolving
speed integrator, adjusting output frequency to balance the load. The adjustment to output frequency for
dynamic balance function is relatively slow, and influenced by selections of acceleration and deceleration
time.
If rapid response of linkage balance operation is required, please apply with linkage operation
self-balancing function (referring to instruction of parameters in FA group), or applying with compensation
PID to build flexibly as necessary, which can conduct adjustment directly to the output of frequency
integrator.
Adjusting gain value=[F5.3.41]*rated current of equipment/100, when the difference of output current
and reference value reaches the adjusting gain value, output frequency will drop to the adjusting
amplitude limit value.
Adjusting amplitude limit value= [F5.3.42]*current selected frequency/100; this value is the amplitude
peak of dynamic balance adjustment.
Load 负载
Reference
参照负载load
(F5.3.39) Output frequency
(F5.3.39)
Time
时间 Adjusting amplitude
limiting value
Frequency
频率 Adjusting gain
Reference value
value
[F5.3.42]
[F5.3.42]
Output limit
Time
时间
Adjusting area
Figure 7-41 Sketch of Load Dynamic Balance Function Figure 7-42 Sketch of Dynamic Balance Variables
The parameter is for the setup of multi-stage operation's frequency and can be used to multistage
velocity operation and simple programmable multi-stage operation. Refer to the detailed specifica-
tions of multi-velocity control function 1, 2, 3, 4 of multifunctional input terminals F3.0.00-F3.0.07
and simple programmable multistage operation in F6.1 group parameters. Frequency inverter can
transform frequency and direction automatically according to the running time to satisfy the require-
ment of technology, as Figure 7-43-A shown.
f14
f3
d4 a14 a15
f2 a3
f4 f13 f15
a2
f1 d5
a13 d15
a1
PLC running
PLC运行
a5 d13
f5
In the figure, a1-a15 and d1-d15 are current stage's time of acceleration and deceleration, while
f1-f15 and T1-T15 are current stage's given frequency and operating time. All these will be defined
in this parameter respectively.
The completion of simple programmable multi-stage operation for stage, cycle and so on can access
to multifunctional output terminals or relay's output index signal. Refer to Function 20, 21 (multi-stage
operation completed) and 22 (multi-stage operating cycle completed) among the F3.1.15-F3.1.20.
f14
f3
d4 a14 a15
f2 a3
f4 f13 f15
a2
f1 d5
a13 d15
PLC running a1
PLC运行
a5 f5 d13
PLCRUN指令
command
Frequency
频率
[F6.0.03]
[F6.0.02]
[F6.0.35]
[F6.0.01]
[F6.0.34]
[F6.0.00]
Time
时间
[F6.0.31]
[F6.0.05]
[F6.0.32] [F6.0.33]
[F6.0.36]
[F6.0.04]
Running command
运行指令
Stage
阶段结束 end
DO
DOoutput
输出
Cycle
周期结束 end
DO
DOoutput
输出
RUN command
f14
f3
d4 a14 a15
f2 a3
f15
f4 f13
a2
f1 d5
a13
PLC PLC运行
running a1
a5 f5 d13
RUNRUN指令
command
Figure 7-43-E Simple PLC Operation Keeping the Final Value mode
Interruption signal
中断信号
f1
a1
d2 f3
f2 a3
a2
d2
f3
a1 f2 a3
a2
Start run from the stage
setting at the interruption
Time
时间t (t)
ti
Stage 1 Running time Remained
of stage 2 time of stage 2
F6.1.16~ F6.1.30 Setting of stage 1~15 Setting range: 0000~1321 Factory default: 0000
Running frequency
运行频率 Swing frequency amplitude
[F6.2.50]×摆频幅值
[F6.2.53]
[F6.2.47] [F6.2.51] [F6.2.52]
时间
Time
[F6.2.48]
F6.2.46 Function selecting (H) Setting range: 0000~1112 Factory default: 0000
The unit: Function setting
0: Function off The functional parameter of Group F6.2 is invalid.
1: Function effective.
In case that the priority of frequency (revolution) instruction source allows by, the frequency inverter
adopts swing function.
2: Terminal selectivity effective
When the multifunctional input terminal of definition 24 (swing operation input) is valid, the frequency
inverter adopts swing function In case that the priority of frequency (revolution) instruction source allows.
If it is invalid, frequency converter operates in accordance with the setting value of preset frequency
F6.2.47 of swing frequency. In this mode, waiting time of preset frequency is invalid.
F6.2.47 Preset frequency of swing frequency Setting range: 0.00~[F0.1.21] Factory default: 10.00
F6.2.48 Waiting time of preset frequency Setting range: 0.0~6000.0Sec. Factory default: 0.0
Preset frequency is referred to the operation frequency before frequency inverter adopts swing
frequency operation or breaks away from operation frequency of swing frequency operation. Determine
the operation mode of preset frequency according to the instruction of swing frequency function.
When the selected swing frequency function is valid ([F6.2.46]=###1), frequency inverter starts swing
frequency preset frequency after running, then runs the swing frequency operation status after the
waiting time [F6.2.48] of preset frequency.
In case of the selected swing frequency function terminal is available ([F6.2.46]=###2), when swing
frequency operation input terminal is valid, frequency inverter runs the swing frequency operation status;
When it is invalid, frequency converter outputs preset frequency ([F6.2.47]), and the waiting time of
preset frequency is unavailable.
F6.2.49 Swing frequency amplitude Setting range: 0.0~50.0 (%) Factory default: 10.0
F6.2.50 Sudden jump frequency Setting range: 0.0~50.0(%) Factory default: 10.0
Sudden jump frequency is the amplitude of frequency's fast descending after it reaches upper
boundary in swing frequency cycle, that is, the amplitude of frequency's fast ascending after it reaches
lower boundary. Please refer to Reference Diagram 7-50 for details.
Practical sudden jump frequency = [F6.2.50] × practical swing frequency amplitude.
F6.2.51 Triangular wave rising time Setting range: 0.1~1000.0Sec. Factory default: 10.0
F6.2.52 Triangular wave decreasing time Setting range: 0.1~1000.0Sec. Factory default: 10.0
The parameter in this group is referred to acceleration and deceleration slope in the process of swing
frequency.
Triangular wave rising time is referred to the time spent from the lower boundary frequency to the
upper boundary frequency in swing frequency operation, that is, the acceleration time in the cycle of
swing frequency operation.
Triangular wave decreasing time is referred to the time spent from the upper boundary frequency to
the lower boundary frequency in swing frequency operation, that is, the deceleration time in the cycle
of swing frequency operation.
The sum of triangular wave rising time and decreasing time is the swing frequency operation cycle.
The swing frequency center frequency refers to the center value of frequency converter output
frequency in the process of swing frequency operation.
Center frequency of actual output = [F6.2.53] + set frequency confirmed by F0.2.25.
Refer to the following figure for the structure of Process PID and functions of each functional parameter:
Kp setting
0~[F0.1.21] 0或0~[F0.1.21]
1 0 上限频率
Upper limiting
[F7.0.4] [F7.0.5] Setting + frequency
[F7.0.02] combination + 1 + Torque setting
TiS MUX
100% - -1 +
[F7.0.18] Independent
AI1 Deviation PID
PID [F7.0.01] 1 Output polarity
AI2 M 偏差极性
polarity Kd.S 输出极性限制 AO output
1+TdS AO输出
……
……
Multi-stage 反馈1
……
……
1
PID setting Feedback 0
*K 反馈
PLC-PIDST7 combination [F7.0.12] [F7.0.13]
组合
[F7.0.10]
100%
[F7.1.27]~[F7.1.33]
[F7.0.16] AI1
PID
Feedback
AI2
反馈2
……
[F7.0.09] 1
0
[F7.0.14] [F7.0.15]
[F7.0.11]
When analog channel input is selected for setting source of process PID, corresponding relationship
between set value of process PID and analog port can be altered with this group of parameters. The
When the analog channel input is selected for feedback source of process PID, corresponding
relationship between feedback value of process PID and analog port can be altered with this group
Figure 7-47 Sketch of Definition Of Set Value of Figure 7-48 Sketch of Corresponding Relationship of
Process PID Feedback Value of Process PID
This function is mainly applied in occasions of flow calculation with differential pressure. When the
feedback value is not in accordance with the given value of process PID, while there is a certain linear
relation, this group of parameters can be selected to make it accordant of the meaning expressed by
feedback value and given value of process PID. For example, if the given value of process PID means
flow of the pipe, feedback value of process PID means flow rate of the pipe, supposing the set value of
this parameter means cross sectional area of the pipe, then the given value and feedback value of
F7.0.20 Differential inertia filtering time Setting range: 0.01~100.00 Sec. Factory default: 10.00
Proportional gain defines the magnification of deviation. The bigger the set value is, the faster the
response of system is, but oscillation can be caused when it's too big; the smaller the set value is, the
slower the response is.
Adjusting only with proportional gain will not eliminate the deviation completely. In order to eliminate the
remained deviation, integral time shall be selected. The smaller the integral time is set, the faster the
response is, but oscillation of system can be caused when it's too big or too small.
target
target value deviation is
PID 目标值 目标值
value 积分控制时
PID反馈 0 when with
feedback 偏差
deviation 偏差为0
integral
反馈
feedback feedback
反馈 control
time
时间 time
时间
Differentiator can make response to the change rate of deviation. The larger the change is, the larger
the output gain is, that is, its gain is in proportion to change rate of deviation. But it won't make response
to constant deviation. When differential coefficient is 0.0, it means the differential function closing the
The larger the differential coefficient is set, the stronger the differential function is. In general system,
Larger differential inertia filtering time can make the differential adjustment more smooth, generally, it's
F7.0.21 PID controller characteristics configuretion(H) Setting range: 0000~0111 Factory default: 0000
0: Positive deviation When feedback signal gets weaker, PID output is increased.
1: Negative deviation When feedback signal gets weaker, PID output is decreased.
For single polarity of PID control mode, output of PID adjuster is always positive value, lower limit is
0. For frequency settings, operation direction of frequency inverter is determined with external
control order, while PID output can't change the operation direction. Generally, it applies for devices
without motor reversal for water and pressure delivery. Refer to Figure 7-50-A.
For dual polarity of PID control mode, output of PID adjuster is negative value. For frequency
settings, operation direction of frequency inverter is determined with external control order and
"exclusive OR" calculation of PID output direction, and PID output can change the operation
direction. If the direction lock parameter (F0.1.17) is valid, efficient PID output shall take the absolute
Permitted limiting
value of deviation PID feedback
PID feedback PID 反馈
PID 反馈
Deviation limiting (F7.0.22)
range (F7.0.22)
偏差允许限值[F7.0.22]
偏差限幅[F7.0.22] PID setting
PID 设定
Time
时间
Output
Time
时间 输出频率
frequency For dual polarity of PID control,
For single polarity of output 双极性
frequency can change
PID 控制时,输
输出频率 PID, when output the出频率会改变相序
phase sequence
frequency is 0, the
单极性 PID 时,当输出频 时间
direction
率降到doesn't
0,不改变方向 change
Output Time
frequency
Time
时间
Figure 7-50-A Single Polarity of PID Control Mode Figure 7-50-B Dual Polarity of PID Control Mode
Controller output value is the permitted maximum deviation amount with given value of controller.
When feedback value is within the range of maximum deviation range, the controller stops adjusting.
Proper setting of his function contributes to covering the accuracy and stability of output of system.
Feedback 反馈量
PID feedback
amount
时间
Time
Output frequency
输出频率
时间
Time
F7.0.24 Preset hold time before PID starting Setting range: 0.0~3600.0Sec. Factory default: 0.0
This function can make it earlier to access to the sable stage for PID adjustment. Preset value of PID
When frequency inverter start to operate, first of all, it shall be sped up to the preset frequency of PID,
and operate as closed-loop characteristics after running continually for a while at this point of frequency
[F7.0.24].
输出频率
output
feedback value of process PID
frequency preset frequency
预置频率 过程PID反馈值
100%
feedback value of
sensor
传感器反馈数值
time
0
时间T [F7.0.26] [F7.0.25]
预置频率保持时间
retention time of preset frequency
Figure 7-52 Sketch of Closed-Loop Frequency Figure 7-53 Relationship Curve of Feedback Percentage
Operation and Preset Corresponding Sensor Value
This group of parameter determines the corresponding relationship between feedback percentage and
feedback physical quantity, which determines display values of monitoring parameters d0.1.36 and
This group of parameter defines the set value of process PID multi-stage operation. Set value is the
Multi-stage operation of process PID can be flexibly realized with multifunction input terminal, please
refer to function instruction of given terminal 1, 2, 3(28~30) of multi-stage process PID of terminal
Output frequency
T<[F7.2.36] [F7.2.36]
[F7.2.35]
Time(T)
Set value of awakens deviation F7.2.37 is the relevant percentage of PID given
value.
KD
[F8.1.29]
Given revolution + Speed + Given torque
给定转速 速度误差
error 1 + 转矩给定
Ts
- +
Feedback revolution [F8.1.30]
反馈转速 Kd S
1
1+TdS
转矩限制
Torque limit
[F8.1.21]~[F8.1.28]
This parameter is used to define revolution setting channel. Selecting mode of revolution setting channel
is similar with that of frequency setting source channel. Refer to instruction of F0.2.25 parameter.
Revolution set value is obtained from transition of frequency set value selected by F0.2.25: revolution
Value of F8.0.03 is set as revolution set value, automatically preserved when outage.
Take the pulse signal input by pulse input port Fin as revolution set value.
Note: Select revolution setting channels 3~7, upper and lower limiting parameters shall be correctly
selected F8.0.01 and F8.0.02.
This parameter is used to set the relationship curve of set value and corresponding motor revolution
Motor revolution
电机转速
[F8.0.02]
[F8.0.01]
0
最小
Minimum 最大
Maximum 转速
Revolution
set value set value channel
设定值 设定值 通道设定
setting
Figure 7-56 Corresponding Relation of Revolution Set Value and Motor Revolution
F8.0.06 PG rotation direction (valid for PG card) Setting range: 0,1 Factory default: 0
In the system of inductive vector controlling, frequency inverter output phase sequence (depending on
the connection order between the motor and frequency inverter U, V, W) and the connection order
between pulses of encoder Phase A and Phase B should keep uniform. Or it can't function normally and
cause the Fu. 020 fault or 0 speed shock when starting. Then it can be solved with modifying the
parameter.
Systems of tension control or hoisting equipment, etc, which may lead to motor shaft
side-pulling, may result in Fu.020 fault and at this moment please shield the protective
function (FF.1.22 = # 0 # #).
F8.0.09 Revolution check /control cycle Setting range: 0~0805 Factory default: 0101
When revolution feedback channel selects an encoder, the parameter sets speed check cycle.
The parameter should set smaller values; overlarge revolution check cycle may lead to unstable
closed-loop running and decelerate response. When use larger check cycle for ensuring the exactness
of measuring speed, please lower the proportionality factors F8.1.21, F8.1.25 (default parameters) of
revolution closed-loop regulator and enlarge integral time constants F8.1.22, F8.1.26 (default parameters)
moderately.
When set revolution is bigger than the wire breakage zero speed signal level (its set value is relative to
the percentage of the largest set speed [F8.0.02]), while feedback speed is smaller than wire breakage
zero speed signal level, and revolution of frequency inverter checks wire breakage protective function
If speed measuring loop interference is great, it can enlarge [F8.0.13] to prevent wrong judgments from
interference; otherwise decrease the set value to strengthen the response speed of the system to wire
breakage check.
Filtering time coefficient of set revolution feedback in this parameter is available to all of the speed
measuring modes (channels). When use encoder for speed measuring, the function is similar to check
cycle parameter (F8.0.09), therefore there is a need to set smaller values for the system of fast-speed
response.
The parameter is used to set relations between revolution feedback signal (feedback channel 1~4) and
Motor revolution
Figure 7-57 Corresponding Relation of Revolution Feedback Value and Motor Revolution
ASR-PID ASR-PID
P= [F8.1.25] P= [F8.1.25]
I= [F8.1.26] I= [F8.1.26]
D= [F8.1.27] D= [F8.1.27]
P= [F8.1.21] P= [F8.1.21]
I= [F8.1.22] I= [F8.1.22]
D= [F8.1.23] Motor revolution D= [F8.1.23] Motor revolution
Figure 7-58-A Double PID parameter (hysteresis Figure 7-58-B Double PID parameter (continuous
switching) switching)
The parameters are effective in the condition of double PID parameter hysteresis switching; the first
group parameter is effective when it is lower than the switching lower revolution [F8.1.18]; the second
group parameter is effective when it is higher than the switching upper revolution [F8.1.19].
F8.1.21 Proportional gain 1 (ASR-P1) Setting range: 0.50~1.20 Factory default: 1.00
Setting range:
F8.1.22 Integral time 1 (ASR-I1) Factory default: 1.50
0.0,0.01~50.00Sec.
F8.1.23 Differential coefficient 1 (ASR-D1) Setting range: 0.0,0.01~10.00 Factory default: 0.0
F8.1.25 Proportional gain 2 (ASR-P2) Setting range: 0.50~1.20 Factory default: 0.80
Setting range:
F8.1.26 Integral time 2 (ASR-I2) Factory default: 5.00
0.0,0.01~50.00Sec.
F8.1.27 Differential coefficient 2 (ASR-D2) Setting range: 0.0,0.01~10.00 Factory default: 0.0
The parameters are applied to adjust proportional gain of speed adjuster, integral time and differential
1) Proportional gain P: As value is bigger, the response id faster, however the stability of system is
2) Integral time coefficient I: As value is greater, the response id faster, and the revolution over-adjusting
is greater, while the stability is worse. In general, the parameters are direct proportional to system
inertia. When inertia is great, the parameter also set with great value.
3) Differential coefficient D: it is the reverse to differential time constant; there is no need in general
system and it should be set to be zero. Differential adjusting in reality is a kind of trend forecasting
adjustment; the parameter set is bigger, the differential function is stronger. Proper differential set
can fast the response speed, improve the stability, and it is used to the system with requirements of
4) Differential output filtering time constant DT: Differential output to the adjuster for a stage of inertia
The parameter is applied to set adjuster output amplitude and limit system's transient forward and
backward torque. Its set value is the percentage corresponding to rated torque.
Actual output torque is also limited by adjuster output lower limit amplitude [F1.4.47]
and should pick up the lower among the two. When running acceleration and
deceleration, it is mainly limited by electricity limit level.
F8.2.33 Over speed (OS) detection action Setting range: 0~3 Factory default: 1
The parameter is used to set excessive action of revolution deviation (DEV) and over speed (OS)
detection action.
0: No action
Inverter immediately blockades output and reports overlarge deviation of rotating speed of Fu.018
Inverter slows down to stop according to effective time of deceleration, and reports overlarge deviation
Inverter keeps on running, whereas reports overlarge deviation of rotating speed (aL.018) or overspeed
These parameters are used to set detecting value and time for overlarge deviation of rotating speed
(DEV).
Provided that deviation of rotating speed is continuously greater than given DEV detecting value within
given DEV detecting time [F8.2.35], then inverter shall be in line with the setting action of F8.2.32. Set
F8.2.36 Detected value of over speed (OS) Setting range: 0.0~150.0(%) Factory default: 120.0(%)
F8.2.37 Detection time of over speed (OS) Setting range: 0.0~2.00Sec. Factory default: 0.10
These parameters are used to set detecting value and time of over-speed (OS).
Provided that feedback rotating speed is continuously faster than given OS detecting value within given
OS detecting time [F8.2.37], then inverter shall be in line with the setting action of F8.2.33. Set value of
F8.3.41 Torque digital setting Setting range: -250~250(%) Factory default: 0.0
Its set value, the setting with symbols (direction), is corresponding to the percentage of rated torque;
actual given direction of torque is “Exclusive OR” of control command direction and set value direction.
This parameter is used to set the address of the local inverter in the case of serial port commu-
nication. It is only effective when the inverter is a slave one. During communication, the local device
only receives commands for the data frames consistent with the address of this device, and then
FA.0.03 Local inverter response delay Setting range: 0~1000mS Factory default: 5 mS
The response delay of the inverter refers to the waiting time since the inverter serial port has
received and explained the command sent from the slave device till the response frames are sent.
FA.0.04 Communication failure judging time Setting range: 0.01~10.00Sec. Factory default: 1.00
If the local inverter has not received correct data signal beyond the time interval defined by this
parameter, then the communication is judged to be failed for the local inverter. The inverter will
When E580 series inverter makes access to functional parameters or monitoring parameters via the
buss, corresponding address can be predicted directly with the functional code (refer to Chapter 10.
parameters or monitoring parameters with discontinuous address, multiple-frame data are needed in
this method.
The mapping parameter access is actually a needle access mode. When accessing (reading or writing)
several functional parameters or status parameters with discontinuous address, these parameters can
be mapped into an area with continuous address (bus-control parameter area) for accessing.
See the following table for the bus-control parameters of E580 series inverters.
For example, in one frame of standard MODBUS protocol data, it’s impossible to read the status
parameters d0.0.02, d0.0.05, d1.0.01 and d1.1.31 and status word once and for all with a common method. To
map status parameters into the bus-controlled parameter area with continuous address, set with the following
method:
[FA.1.14]=d0.02
[FA.1.15]=d0.05
[FA.1.16]=d1.01
[FA.1.17]=d1.31
Then you it just needs to read the data in the continuous address 0x130A ~ 0x130D.
0: No fine adjustment
If the fine adjustment source for linkage proportion coefficient is void, then:
Slave frequency command = master frequency command * [FA.2.26] of the salve machine.
If AI1 is selected for the fine adjustment source for linkage proportion coefficient, then:
Slave frequency command = master frequency command * [FA.2.26] of the salve machine *AI1/AI1
maximum.
If AI2 is selected for the fine adjustment source for linkage proportion coefficient, then:
Slave frequency command = master frequency command * [FA.2.26] of the salve machine *AI2/AI2
maximum.
If AI3 is selected for the fine adjustment source for linkage proportion coefficient, then:
Slave frequency command = master frequency command * [FA.2.26] of the salve machine *AI3/AI3
maximum.
This parameter of the master inverter does not function, and it is used to select the auxiliary
frequency of the slave machine:
Actual output frequency of the salve machine=master machine frequency command * slave machine
linkage proportion (including fine adjustment) + offset frequency
0: No offset
No offset frequency/revolution; the frequency set value of the slave machine is determined by the
frequency command of the master device and the setting of FA.2.26 and FA.2.27.
1: Determined by frequency setting source 1
The frequency set value of the slave machine frequency setting source 1 is regarded as the offset
frequency/revolution of the slave machine.
2: Determined by frequency setting source 2
The frequency set value of the slave machine frequency setting source 2 is regarded as the offset
frequency/revolution of the slave machine.
0: Void
1: Current balance
With reference to the load current of the master device, each slave device will automatically conduct
fine adjustment to the output of local device so as to keep consistency with the master device’s current.
2. Torque balance
With reference to the torque of the master device, each slave device will automatically conduct fine
adjustment to the output of local device so as to keep consistency with the master device’s torque.
3: Power balance
With reference to the power of the master device, each slave device will automatically conduct fine
adjustment to the output of local device so as to keep consistency with the master device’s torque.
FA.2.30 Linkage balancing gain Setting range: 0.001~10.000 Factory default: 1.000
When the linkage balancing function is effective, this parameter is used to set the adjusting gain
output by this device, and it is only effective for the slave device. The higher the gain is, the higher
Fb.2.19 Automatic shift switching cycle Setting range: 0.10 ~ 2.00Sec. Factory default: 0.30
Combined with the multifunctional input terminal (Function No. 67), it is especially used for transmission
machineries with mechanical shifting function (e.g. machine tool spindle drive). This parameter is used
to set the operating frequency and FWD and REV shift cycle when the function is valid.
This parameter is to set the bind-type brake function at 0 speed. When it is set to 1, the actions on DC
are completely identical. The electronic bind-type brake at that time can ensure the motor completely
In the VC control mode with PG feedback, if it is set to 2, the equipment will output 0 speed torque in the
mode of position locking. Even if it is dragged by loads, the motor axis will not rotate.
Fb.2.21 position locking gain1 Setting range: 0.01 ~ 10.00 Factory default: 1.00
When the zero-frequency torque is kept at 2, this parameter is used to set the gains between the motor
output torque and the axis deviation. The larger the number is, the higher the 0 speed torque is. If the
FF group parameters include special and internal function parameters, and their setting and initialization
are confined. This group of parameters is used to set the user’s authority for operating FF parameters.
The virtual output nodes SDO1~SDO8 are functionally the same as the multifunctional output terminals
DO1~DO3, but do not output any signal. They are directly connected in the controller of the inverter to
Using virtual nodes can not only help simplify wiring but can also avoid interference. The function of
SDO1~SDO8 can be defined by setting the value of FF.0.01~FF.0.08. Please refer to Table 2
( Comparison Table for Variables of Multifunctional Output Terminals (DO/EDO/SDO) for the variables
FF.0.09~FF.0.16 Definition of virtual input node (SDI1~ SDI8) Setting range: 0~96 Factory default: 0
The virtual input nodes SDI1~SDI8 are functionally the same as the multifunctional input terminals
DI1~DI9. But there are no actual physical input nodes. They are connected to the virtual output SDO1~
SDO8 one to one, and are directly taken from the virtual output signal.
The virtual input nodes SDI1~SDI8 are functionally programmable, and their function can be defined by
setting the values of FF.0.09~FF.0.16. Please refer to Table 1 (Comparison Table for Functions of
The parameters are used to set the connection logic status of the virtual output nodes SDO1~SDO8
and virtual input nodes SDI1~SDI8. When it is set to be reverse polarity connection, the virtual
output signal will be negated before being inputted to the virtual input port, as shown in Figure 7-59.
SDOX SDIX
This group of parameters is used to define if the protecting function needs to be activated or not.
FF.2.26 AI1 gain correction Setting range: 0.950~1.050 Factory default: 1.000
This group of parameters is sued to make fine adjustment to AI1 zero point and AI1. The relationship
AI1 input value= AI1 gain correction* AI1 value before adjustment +AI1 zero offset.
FF.2.27 4mA deviation adjustment for AI2 Setting range: -0.500~0.500mA Factory default: 0.0
FF.2.28 AI2 gain correction Setting range: 0.950~1.050 Factory default: 1.000
FF.2.29 AI3 Zero offset adjustment Setting range: -0.500~0.500V Factory default: 0.0
FF.2.30 AI3 gain correction Setting range: 0.950~1.050 Factory default: 1.000
FF.2.31 AO1 zero offset correction Setting range: -0.500~0.500V Factory default: 0.0
FF.2.32 AO1 gain correction Setting range: 0.950~1.050 Factory default: 1.000
FF.2.33 AO2 zero offset correctio Setting range: -0.500~0.500V Factory default: 0.0
FF.2.34 AO2 gain correction Setting range: 0.950~1.050 Factory default: 1.000
The correction principle for each analog input/output port is the same as AI1. The relationship curves
with zero offset adjustment and gain correction are respectively as below. Generally, users do not need
Figure 7-60-A AI1 Zero Offset Correction Curve Figure 7-60-B AI1 Gain Correction Curve
AI2矫正值(mA)
AI2 Corrected value (mA) AI2矫正值(mA)
AI2 Corrected value (mA)
20 20
19.5 19
[FF.2.27]=0.500
[FF.2.28]=1.050
4.5 [FF.2.28]=0.950
4 [FF.2.27]=-0.500 4
3.5
Figure 7-61-A AI2 Zero Offset Correction Curve Figure 7-61-B AI2 Gain Correction Curve
10
10 9.5
9.5
[FF.2.29]=0.500
[FF.2.26]=1.050
0.5 AI3 Actual value (V) AI3 Actual value (V)
-10 -9.5 -10
9.5 10 0 10
-0.5
[FF.2.26]=0.950
[FF.2.29]=-0.500
-9.5 -9.5
-10 -10
Figure 7-62-A -AI3 Zero Offset Correction Curve Figure 7-62-B AI3 Gain Correction Curve
FF.2.35 Undervoltage protection action level Setting range: 320~450V Factory default: 320V
This parameter sets the allowable lower limiting voltage at the DC side during normal operation of
the inverter. For some occasions with lower power grid, it is applicable to appropriately reduce the
When the power grid is under excessive low voltage, the output torque of the motor
will decrease. In the occasion of constant power load and constant torque load,
excessive low voltage of the power grid will lead to increase of the inverter’s input
current, hence reducing the reliability of inverter operation.
The set value for this parameter [FF.2.35] must be no more than the undervoltage adjustment action
level [F1.4.45].
When the actual bus of the inverter is deviated from the value of the DC side voltage monitoring
parameter d0.0.07, it is applicable to set this parameter combined with the correction of potentiometer
The modification of this group of parameters should be conducted under the guidance of professionals,
This function helps effectively reducing the instantaneous power required for starting the fan, hence
The revolution of the cooling fan can be automatically adjusted according to the ambient temperature
and operation status of the inverter, so as to maximize service life of the cooling fan.
The fan will run according to the settings in the unit and ten’s digit of this parameter immediately after
FF.4.42 Operating panel control options Setting range: 0000~2001 Factory default: 0000
0: Standard panel interface control (can be connected to monitoring panel via RS485)
The control command can only be given through the standard operating panel, and external monitoring
1: RS485 port external panel control (the standard panel only for monitoring)
The control command can only be given via RS485 port, and the standard panel is only used for
monitoring.
The master control panel is selected by the multifunctional input terminal (function no. 40) and the
FF.4.43 Special function configuration (H) Setting range: 0000~1111 Factory default: 0101
0: Forbidden
1: Permitted
After modifying the motor nameplate parameters, the inverter will automatically set static self identifi-
1: Two-phase composition
Another modulation method for space voltage vector. This method can help appropriately reduce heat-
thousand:reserved
Chapter 8
Fault
Display Possible causes Solutions
description
Fault
Display Possible causes Solutions
description
Overvoltage
The voltage of the power supply is
Fu.007 when shutting Check voltage of power supply
abnormal
down
Undervoltage
1. The voltage of the power
during operation 1. Check voltage of power supply
Fu.008 supply is abnormal
(can be 2. Supply power separately
2. Large load is started in the grid.
shielded)
Fault
Display Possible causes Solutions
description
Drive protection
1. Check the main loop.
Fu.009 action (can be Main loop fault or interruption
2. Shield this protection.
shielded)
Fault
Display Possible causes Solutions
description
External equipment is The external equipment of the Check signal source and relevant
Fu.017 faulty or the panel has frequency inverter is faulty, the equipment and find the root leading
forced stoppage input terminal has signal input to the stoppage of the panel.
1. Reduce load
1. The load is too large.
2. Prolong acceleration and
2. The acceleration time is too
deceleration time.
Excessive protection short.
3. Confirm the mechanical system
Fu.018 of revolution deviation 3. The load is locked.
of the load
(DEV) 4. The detection value ([F8.2.34])
4. Reset the detection value
and time ([F8.2.35]) for DEV is set
([F8.2.34]) and time ([F8.2.35]) for
improperly.
DEV.
Fault
Display Possible causes Solutions
description
Fault
Display Possible causes Solutions
description
The temperature
The temperature detecting circuit
Fu.054 sensor 1 is faulty Seek for manufacturer’s support
is abnormal.
(can be shielded)
Fault
Display Possible causes Solutions
description
The connection of
Fu.072 accessories is
abnormal
Conflicting
Fu.201 Please contact the direct supplier.
parameter setting
Can be
Display Warnings shielded Solutions other than shielding
or not
Can be
Display Warnings shielded Solutions other than shielding
or not
1. Check the connection of analog
aL.036 AI1 input is disconnected
Can be input signal
aL.037 AI2 input is disconnected
shielded 2. Check whether there’re signals in
aL.038 AI3 input is disconnected
the signal source
aL.039
Fin input is disconnected (retained)
1. Check the connection of speed
The revolution detecting loop is
aL.040 measuring module
disconnected
2. Seek for manufacturer’s support
No-load operation fails to identify the
aL.041
parameters of motor
The parameters of U phase of motor is
abnormal
aL.042
The parameters of V phase of motor is Check whether the winding of motor is
aL.043
abnormal faulty
aL.044
The parameters of W phase of motor is
abnormal
Select special motor for frequency
aL.045 Over temperature of motor conversion for long-term low speed
operation
The driving circuit is abnormal and
aL.049
unbalanced
Can be
aL.054 The temperature sensor is faulty Replace the temperature sensor.
shielded
The parameters can not be recovered in
aL.058
batch during operation
The numerical value when energized
aL.059
can not be recovered during operation
The connection between expanded
aL.061 communication module and master
control board is interrupted abnormally
1. The expansion unit selected is
inappropriate and can not be used with
The function expansion unit 1 has a
aL.062 such type of frequency inverter
hardware conflict
2. The function expansion unit has a
internal fault
Can be
Display Warnings shielded Solutions other than shielding
or not
1. The expansion unit selected is
inappropriate and can not be used with
The function expansion unit 2 has a
aL.063 such type of frequency inverter
hardware conflict
2. The function expansion unit has a
internal fault
The function expansion unit has a This expansion unit can not be used
aL.064
resource conflict with other expansion units
Fail to establish communications with
aL.065
function expansion unit 1
Fail to establish communications with
aL.066
function expansion unit 2
The communication links of function
aL.067 expansion unit 1 is interrupted
abnormally
The communication links of function
aL.068 expansion unit 2 is interrupted
abnormally
The parameter download is failed
(note: download is from operation Check whether the communication
aL.071 panel to control panel of frequency interface between operation panel and
inverter; upload is from control panel control panel is normal or not
to operation panel)
The memory of panel fails to be
aL.072
operated
The memory of panel inhibits write and
aL.073
can not download parameters
1. Check whether the communica- tion
interface between panel and control
The upload of parameters is failed
panel is normal or not.
aL.074 (automatically recover to the numerical
2. In the parameter F0.0.08, parameter
value before uploading)
upload is forbidden in terms of local
upload.
The version of panel parameters is
Re-upload panel parameters same as
aL.075 different from that of equipment
the version of equipment parameters
parameters; it can not be uploaded
Can be
Display Warnings shielded Solutions other than shielding
or not
The panel has no effective parameters The panel parameters are not modified
aL.076
and can not be uploaded effectively and need not to be uploaded
The panel parameters exceed the
Confirm the allowed parameter scope,
aL.077 setting scope INV allowed and fail to be
reset and upload
uploaded
The operation panel is abnormally After power off, reinsert and pull out of
aL.099
connected the panel or replace the panel
The control program is failed resulted
aL.100 Improve electromagnetic environment
from electromagnetic interference
The setting motor parameters are
aL.103 conflicted (rated frequency, revolution Reset the motor parameters
conflict)
The setting motor parameters are
conflicted (no-load current, rated current,
aL.104 Reset the motor parameters
rated revolution, rated frequency and
rotor time constant)
The inductance parameters of motor
Reset the inductance parameters of
aL.105 stator overflow (the motor parameter is
motors stator
incorrectly set)
The setting parameters are conflicted
aL.201 Immediately contact the direct supplier
and it’s about to shut down
Subjecting to influence of many factors such as temperature, humidity, dust, vibration as well
as internal components aging, the inverter has potential risk of faults. In order to ensure long
and steady operation of the system, regular care and maintenance must be conducted.
After long-distance transportation of the frequency inverter, users should check whether the
components are in good condition, or the screws are fastened before use them. During the
normal use period, users shall regularly clean the internal dust of frequency inverter and
check whether the screws are loose.
Due to the high voltage of frequency inverter in service, the wrong operation can result in
serious injury or death, therefore, the power supply of the frequency inverter shall be cut off,
and the maintenance operation after ten minutes after the nixie tube of the frequency inverter
panel extinguishing can be carried out.
1.Vibration,
1. Smooth operation and normal temperature
Generator √ temperature rise
2. No abnormalities and inconsistent noise
2. Noise
Input or 1. Input voltage 1. The input voltage is in the specified scope
√
output 2. Output current 2. Output current is below the rated value
9.3 Storage
After purchase of the frequency inverter, if the frequency inverter will be spared for a while or
stored for a long time, users shall pay attention to the following items:
Environmental
Requirements Remarks
Characteristics
Long-term storage temperature is no
more than 45 ℃, so as to avoid the
degradation of capacitance
Ambient
-10℃~45℃ characteristics. It shall avoid
temperature
condensation and frozen
environment caused by sudden
change of temperature.
Relative
5~95%
humidity
Free from direct sunlight, no dust, It can adopt measurement like plastic
Storage no corrosive, no combustible gas, film sealing and desiccant.
environment no oil, no steam, no gas, no drip,
no vibration, and with little salt
• If the frequency inverter is not in use for a long time, the current shall be applied to restore
filter capacitor characteristics every half year, and at the same time other features of the
frequency converter shall also be checked. When the current is applied, it shall increase the
voltage gradually through autotransformer, and the conduction time should be above half
an hour.
9.4 Warranty
If the frequency inverter body has the following cases, the company will provide warranty
service:
• If faults or damages occur in normal use condition within the warranty period (within 18
months from the date of purchase), our company will provide free maintenance. Our
company will charge a reasonable cost of maintenance when the warranty period has
expired (more than 18 months).
• Even in the warranty period, if any fault is caused by the following cases, our company
will charge certain amount of maintenance cost:
① Fault due to that the users do not operate the device according to the operation
manual or beyond the standard;
② Fault due to random repair and modification without permission;
③ Fault caused by poor preservation;
④ Fault caused by improper use of the inverter for unintended purposes;
⑤ Damage to the machine due to fire, corrosive salt, gas corrosion, earthquake,
storms, floods, thunder, abnormal voltage or other force majeure.
• The company will provide lifelong paid maintenance services even the warranty period
expires.
Chapter 10
protocol can be conveniently applied, it has been considered as the general industry
standard and is widely applied to the integrated system of master controllers and slave units.
By applying this protocol, units of various brands can be connected together and functioning
as an industrial network.
Modbus defines 3 types of transmission modes: ASCII, RTU and TCP. E280 Frequency
E280 utilizes RS485 (RS232, optional, which has to be converted by a level) as the physical
interface for Modbus, and one host can control one or more (maximum 247 units) frequency
inverters.
By applying the asynchronous serial half-duplex transmission method, only master unit or
slave unit can transmit data at one particular moment, and the other unit can only receive
data.
①1 start bit, 8 data bits, 1 stop bit, without parity bit (factory setting)
2) Baud rate
Seven optional baud rates: 1200bps, 2400 bps, 4800 bps, 9600 bps, 19200 bps, 38400bps,
79600 bps
3) Communication rules
Starting interval between data frames is longer than 3.5 byte transmission cycle (standard),
but the minimum interval should not be shorter than 0.5 ms.
FA.0.01 = 00XX, unit bit is used to choose baud rate, and tens bit is used to choose data format;
X indicates that this bit can be any value in the allowed range.
Read/write to
This function equals to combining 0x03 and
multiple hold 0x17
0x10 into a new command.
registers
Input register
Analog input 0x04- Read input register
(0x1200-0x1300)
Application parameters,
Hold registers
Status parameters, 0x03- Read multiple registers
(application
Control words, 0x06- Write to a single register
parameter area,
Status words, 0x10- Write to multiple registers
status parameter
Set values, 0x17- Read/write to multiple
area,
Mapping status parameters, registers
0x1300-0x1400)
Mapping application parameters
For detailed address distribution, please refer to below section of Modbus detailed
address-finding distribution.
Relevant Modbus functional codes:0x01 (read coil status), 0x05 (write to a single coil), 0x0F (write to
multiple coils)
Relevant Modbus functional codes: 0x03 (read multiple registers), x06 (write to single register), 0x10
② Status parameter address (read-only): The address conversion method for status parameter is
similar to that for application parameter. However, there is no ROM access address.
Notes:
c If there is no need to keep the parameters permanently, it suffices to write the parameters
to the RAM area. However, if the parameters have to be maintained permanently, it is
required to write the parameter values into the ROM area. The service life of ROM area
will be shortened if parameters are frequently written to the ROM area. If value F2.1.13
needs to be written and maintained permanently, the register address where it should be
written to is 0xE213.
d When reading/writing control words, it can be achieved via reading/writing to the coil
mapped to each bit of control words, and it can also be achieved via reading/writing to
the hold register corresponding to the control words. Both methods can achieve identical
results. If it is needed to set the value for operation allowed,we can set the value of the
bit 1 for control word (address 0x1001) as 1 via functional code 05, we can also set the
value of control word (address 0x1300) as 0x0002 via functional code 06. When reading
the status words, the method is similar to that for reading/writing control words. It can be
achieved via reading the discrete input mapped to each bit of status words, and it can
also be achieved via reading the hold register corresponding to the status words. If we
need to read the operation direction, we can read the status bit 5 (address 0x1105) via
functional code 02, we can also read the status word (address 0x1309) via functional
code 03.
6) Fault Diagnosis:
Relevant Modbus functional code 0x08 (Diagnosis)
Sub-function code list
Sub-function Query Response
Function
code Data Data
Image query
00 Return the identical query data Random
data
Re-start communication option (restore the FF00/00
01 FF00/0000
“listen only" status for 04 sub-code) 00
Enforce slave unit into “Listen Only" status
and the salve unit will not reply; the failed
04 0000 No reply
salve unit can be removed from the
communication chain.
Clear all calculators and diagnosing Image query
0A 0000
registers data
Total number
Return the number of bus information
of bus
0B items (for salve unit, count from the last 0000
information
reset or after clearing)
items
Return the number of bus communication CRC error
0C 0000
faults (CRC error calculation) number
Number of
Return the number of bus anomaly faults
0D 0000 anomaly data
(data abnormity error)
items
Return the number of salve unit information Number of
0E items (corresponding with slave unit 0000 valid data
address or the broadcasting information) items
Chapter 11 EMC
11.1 CE
The product can be sold freely in the market of EEA (European Economic Area) with CE
label, and to be ensured to meet other requirements as LVD and EMC.
11.2 Definition
EMC (Electromagnetic Compatibility) means the capacity of anti-interference for
electric and electron equipments, and the product could not interfere other local equips
also. EMC rules are defined requirements of anti-interference for EU area.
1) 1st Environment: including power supply equips of civil low voltage grid.
2) 2nd Environment: including power supply equips of non-civil low voltage grid.
z C1 Inverter: when rated power of electric transmission system is under 1000V, use
in 1st environment.
z C2 Inverter: when rated voltage of electric transmission system is under 1000V, it
would be plug equips or mobile equips. When it uses in 1st environment, it
should install and adjust by professional engineer.
z C3 Inverter: when rated voltage of electric transmission system is under 1000V, it is
suitable in 2nd environment, but not 1st environment.
z C4 Inverter: when rated voltage of electric transmission system is not under 1000V
or rated current is not lower than 400A, or it is suitable in complicated system
of 2nd environment.
E280 Series meet the requirements of standard EN61800-3: 2004 C2, which is
suitable in 1st and 2nd environment.
interference. Except CE requirements, user should take some necessary action to avoid this
interference.
The installation of AC input reactor at the inverter’s input port can restrain the harmonic wave
caused by inverter from transmitting to power grid, reduce the influence of the harmonic wave on
other components, improve the quality of power grid, increase power factor and limit the
abnormal fluctuation of power grid voltage and impulse current on the grid, so as to level
waveform and reduce the influence on inverter.
AC output reactor must be installed at the inverter’s output port to limit the capacitive charge
current between output cable and the ground and passivate the rise rate of the voltage of
inverter’s PWM wave. This can reduce leak current, increase power factor, improve the quality
of power gird and level waveform.
DC input reactor is mainly used in inverter and rectification circuit to increase power factor, filter
the current interference of ripple wave voltage and reduce inverter’s harmonic interference.
Shielded cable has 3 phase conductive shielded cable and 4 phase conductive shielded
cable. If conductive performance of shielded layer cannot meet requirement, it would add
one separate PE wire or use 4 phase conductive shielded cable with one PE wire.
PE wire and
shielded layer Shielded layer Shielded layer
In order to restrain shooting and conducting of radio frequency effectively, shielded layer
Cable Core
6) Filter, inverter, and motor should be in good connection with system (mechanical
equips) with painting protection of installed parts and sufficient contact with
conductive metal.
Wiring distance as below fig.
Drive cable
Minimum 200mm
Control cable
E280
Inverter
Control cable
Minimum 500mm
Motor cable
Drive cable
Minimum 300mm
Motor cable
Attention
should keep high frequency ground in 360 degree to restrain electro magnetic
interference. In addition, cable shield layer should connect with PE wire to meet
safety regulation.
2) In floating or high ground (>30Ohms) power system, EMI filter cannot be installed.
1) The output of inverter is high-speed pulse voltage, therefore it will generate high
frequency leakage current. To prevent electro shock and fire evoked by leakage
current, please install leakage circuit breaker for inverter.
2) The leakage current produced by inverter is relatively large, instant leakage current
of large power inverter may be tens of milliamperes, so inductive current of leakage
circuit breaker should be larger than 100mA.
3) High frequency pulse interference might cause leakage circuit breaker malfunction
under interference, please choose leakage circuit breaker with a high frequency
filter.
4) If to install several inverters, each inverter should have a leakage circuit breaker.
5) Factors that affect leakage current, as follows:
◆ Inverter capacity
◆ Carrier frequency
◆ Type and length of motor cable
◆ EMI filter
6) When leakage current of inverter cause leakage circuit breaker work:
◆ Improve sensitivity of the current value of leakage circuit breaker
◆ Replace a new leakage circuit breaker with high frequency inhibition function
◆ Reduce carrier frequency
◆ Shorten length of output cable
◆ Install a leakage suppression equipment
11.8 Common EMC Interference Problem and Solution
Frequency inverter is strong anti-interference equipment, when there is problem in
wiring and ground connection, still maybe will comes out interference. When it happens,
we have below solutions:
Remark:If you have any other EMC interference questions, please contact the
manufacturer.
and connecting cable if the control keyboard is needed to put outside the inverter’s control
screen or control cabinet, which can greatly help your installation and adjustment. Square
inverter allows the connecting cable to be less than 15m between the control port of the control
4-φ4.0
TA1
TA1-TB1 normally closed contact;
Programmable
TB1 TA1-TC1 normally open contact;
Relay Output
Contact capacity: AC 250V/1A
TC1
Terminal
Terminal Name Function
Type
TA
Programma Contact capacity:
ble Relay TB Normally open contact: 240V AC 2A,
Output Normally closed contact: 240V AC 1A,
TC
Model: IOV-A102
Applicable to E280-4T0040G/4T0055P and below models with Class I appearance; the
Terminal
Terminal Type Function
Name
TA
Programmable Normally open contact: 240V AC 2A,
Relay Output TB Normally closed contact: 240V AC 1A,
TC
Communication RS+
RS485 communication physical interface
Interface
RS-
Model: IOV-A103
Applicable to E280-4T0040G/4T0055P and below models with Class I appearance; the
Terminal
Terminal Type Function
Name
TA
Programmable Normally open contact: 240V AC 2A,
Relay Output TB Normally closed contact: 240V AC 1A,
TC
E280 series inverters adopt closed-loop vector control mode; when user is engaged in such
mode, it's necessary to select PG card fittings. PG card can receive encoder signals of
1) Signal lines and power lines of PG expansion card shall be laid separately; no parallel
routing.
3) The shielded layer of encoder shielded cable shall be grounding (e.g. E terminal of
interference to signals.
winding/unwinding control.
The expansion card can calculate the high stable tension control parameters to meet the
application requirement in the field on the basis of rolling diameter. As for winding and
unwinding operations of wire drawing machine, the tension control on PID adjustment in
speed mode can be achieved by means of external speed setting and real-time signals of
tension oscillating bar for winding and unwinding, to quickly enable tension oscillating bar at
optional position at a time to reach equilibrium position, and to keep stable winding and
Rolling diameter Rolling diameter thickness integral, rolling diameter line speed
calculation calculation and rolling diameter frequency ratio calculation, etc.
Constant tension
Output 0-100 % adjustable torque at zero speed
at zero speed
Breakage
Conduct rapid detection on breakage via feedback input
detection
Steady-state
Less than 5%
wave motion
round timber and veneer cutting and other round timber processing functions.
Terminal
Type Function
Name
auxiliary power
+24V Provide +24V/100mA current for external devices
supply
common
GD Power supply reference ground
terminal
common
CM DO3, DI7, DI8, DI9 common terminals
terminal
Veneer tail-board The thickness uniformity deviation of last rotary-cut part (30mm)
uniformity is less than ± 0.10 mm;
Slitting board
The width deviation of middle board is ±2mm
width
resistance value cann’t be lower than recommended value in below table, while selected resistance
power can be bigger). Selection of brake resistance depends on motor generation power in system,
and in concern with system inertia, deceleration time, energy of potential energy load etc. The bigger
system inertia, shorter deceleration time and more frequent braking time, then to choose bigger
Production Serial
Number Voltage Class
the resistant value must not be less than the recommended values in the figure, while the
power can be more than those in the figure.) The selection of brake resistor should be decided
according to the power range of the electrical machine in the practical application system,
which is relevant to the system inertia, deceleration time, the power of potential energy load, etc.
Customers should make the decision according to the actual situation. The larger the system
inertia is, the shorter the necessary deceleration time will be, and the more frequent the brake,
which causes the brake resistor needs to choose larger power and the resistant value becomes
smaller.
While braking, almost all motor regeneration energy consumes at braking resistance. The formula:
U*U/R=Pb
U---- braking voltage under stable system braking state (it varies from different systems, it takes
Pb----power of braking
The power of brake resistance and power of braking keep consistent in theory, but should take 70%
0.7*Pr=Pb*D
D---- braking frequency (time proportion of regeneration process accounts for the whole process),
Power of
Adaptive Brake Brake
brake
Model motor resistance torque Brake unit
resistance
(KW) value(Ω) (100%)
(KW)
W
W1 D
H
H1
HO EBR RUN
E E
P+ P- PB P+ P+ P-
Brake Resisto