NR Electric Co., Ltd.

PCS-915ID
Distributed Busbar Relay

The PCS-915ID distributed-type busbar protection system is


designed for flexible installation and easy system extension. In
this protection system one central unit is connected to certain
Functions
number of bay units depends on different bus scheme and bay Protection and Control
number. It adopts distributed structure, consisting of one Central • Busbar current differential protection (87B)
Unit (CU) and a number of Bay Units (BUs). The Central Unit is It consists of phase current differential protection and
linked to up to 32 Bay Units via optical fibers in point-to- point DPFC differential protection. Voltage control element and
communication mode. The Central Unit is responsible for the CT saturation blocking element are available to supervise
protection calculation and relay management, the Bay Unit the current differential protection.
acquires and transmits the analog and binary data and executes -- Phase current differential protection
the trip/close commands issued by Central Unit. Dual restraint coefficients are provided to enhance the
sensitivity of weak-sourced busbar with opened bus
The device provides fast and secure low impedance busbar coupler/ section.
protection with sub-cycle tripping time. It integrates advanced
-- DPFC differential protection
and patented features to improve its sensitivity and security,
DPFC differential protection is sensitive to high resistance
such as innovative DPFC current differential protection and
fault and is immune to load fluctuations.
unique weighted CT saturation detection method.
-- Voltage control element
The PCS-915ID is compatible with IEC 61850 station bus and The used voltage can be phase voltage, zero sequence
process bus applications. It supports IEC 61850-8-1 MMS, voltage or negative sequence voltage.
GOOSE and IEC 61850-9-2 Sampling Value. The RJ-45 -- Detection of CT saturation
faceplate port is provided for testing and setting, allowing for Two principles for CT saturation detection are provided:
easier commissioning and maintenance. patented adaptive weighted anti-saturation algorithm
and harmonic algorithm. It keeps the current differential
protection stable to external faults and quickly clears
internal faults and external-to-internal evolving faults
during CT saturation.during CT saturation.

Read more on the web


www.nrec.com 23
NR Electric Co., Ltd.

-- Check zone and discrimination zone Monitoring and Measurement


The check zone differential element is used to distinguish • Dynamic busbar replica
between internal and external fault of the overall busbar
system, the discriminating zone differential elements are • CT circuit supervision
used to select faulty zone. • VT circuit supervision

• Self diagnostic
• Bus coupler/section protection
• Event recorder including 1024 change-of-binary-input events,
-- Breaker failure protection (50BF)
1024 supervision events and 1024 device logs
It can be supervised by voltage control element. Re-
tripping, bus coupler/bus section tripping and feeder • Disturbance recorder including 32 disturbance records with
tripping are executed in sequence. waveforms (The format is compatible with COMTRADE.)

-- Dead zone protection (50DZ) • Clock synchronization using IRIG-B, SNTP, PPS (Pulse-Per-
It is provided to clear the dead zone faults between CT Second) and PPM (Pulse-Per-Minute)
and breaker.

-- Pole disagreement protection (62PD)


Pole disagreement detection element is used to protect Communication
pole disagreement.
• Up to 32 optical point-to-point communication ports from
-- Switch-onto-fault protection (50SOTF) Central Unit to Bay Units
Switch-onto-fault logic of bus coupler/section is used for
• Up to four 10Base-T/100Base-TX copper Ethernet ports
bus energizing.
using IEC 61850, DNP3.0 or IEC 60870-5-103 over TCP/IP
-- Overcurrent protection (50/51)
• Up to two 100Base-FX optical Ethernet ports using IEC
Phase and ground overcurrent protection are both
61850, DNP3.0 or IEC 60870-5-103 over TCP/IP ( Sharing
provided.
two copper Ethernet ports)

• Two RS-485 serial ports using IEC 60870-5-103


• Feeder protection
-- Breaker failure protection (50BF) • One RS-485 serial port for clock synchronization
It can be supervised by voltage control element. Re-
• Optional Sampling Value and GOOSE communication
tripping, bus coupler/bus section tripping and feeder
module using IEC 61850-9-2 and IEC 61850-8-1 GOOSE
tripping are executed in sequence.

-- Dead zone protection (50DZ)


It is provided to clear the dead zone fault between CT
and breaker. User Interface
• HMI interface with large-size LCD and 9-button keypad on
-- Pole disagreement protection (62PD) the front panel
Pole disagreement detection element is used to protect
pole disagreement. • One front RJ-45 port for testing and setting

-- Overcurrent protection (50/51) • One RS-232 or RS-485 rear port for printer
Overcurrent protection consists of phase overcurrent • Language selection – English + selected language
element and ground overcurrent element, each can be
set as inverse-time or definite-time. • Assistant software - PCS-Explorer

• Voltage and current drift auto adjustment.


The relay automatically traces the drift and adjusts zero point
to normal value for voltage and current.

24 Read more on the web


www.nrec.com
NR Electric Co., Ltd.

Features
• Besides conventional current differential element, the • NR Electric's unique two-out-two hardware design
relay also integrated with NR Electric's innovative DPFC significantly improves relay reliability. The redundant
differential element for fast and sensitive fault clearance. The hardware including two independent data acquisition and
differential protection typical operation time is within 20ms processing circuits, one is fault detector and the other for
after fault. protection tripping. All tripping outputs are supervised by
both circuits to prevent the relay from mal-tripping caused by
• This device provides all-in-one busbar protection solution component error.
with up to 32 bays.
• Programmable hardware and logic are helpful for flexible
• CT ratio compensation is adapted to balance CT ratio operation. Modular and unified hardware, selective function
difference of current samplings. table and configurable I/Os allow users to utilize the relay for
customized applications. Most of the 20 IED indications can
• With patented adaptive-weight anti-saturation algorithm and be defined by software, with 3 color options.
harmonic restrain algorithm, this relay guarantees fast and
reliable performance during CT saturation. • IEC-61850 including IEC-81850-8-1 MMS/GOOSE and
IEC-61850-9-2 Sample Value are supported in the relay.
• Check zone element and discrimination zone element Maximum 6 Ethernet ports are equipped as IEC-61850
coordination make sure the relay can identify and trip the station bus and process bus communication interface.
faulty bus only when there are more than one bus protected
by the relay, so as to minimize outage area.

• Continuous feeder disconnector status monitoring are


available for automatic feeder current pulling out in
differential current calculation.

Read more on the web


www.nrec.com 25