PCS-902
Line Distance Relay
The PCS-902 provides comprehensive protection and control Component) distance protection and unique power swing
solutions for transmission lines with high-speed sub-cycle blocking releasing logic. Thus, guaranteeing accurate and
distance element. The PCS-902 is intended for application on reliable operations.
overhead lines and underground cables with diverse voltage
levels. These include series compensated, double-circuit, The PCS-902 is compatible with IEC 61850 station level and
heavily loaded, weak infeed (WI), short and long lines. It can process level applications. It supports IEC 61850-8-1 MMS,
meet the requirements of single-pole or three-pole tripping; GOOSE and IEC 61850-9-2 Sampled Value. The front panel RJ-
it also provides single and/or three-pole auto-reclosing 45 port is provided for testing and setting, allowing for smoother
functions. The PCS-902 is suitable for single and dual-breaker commissioning and maintenance.
applications, providing optional dual CT inputs, dual breaker
failure protections, dual breaker auto-reclosing and dual Functions
synchro-checks. Additionally, the relay integrates the remote/ Protection and Control
local control of circuit breaker, disconnector and earth switch. Five zone phase-to-phase distance protection (21P)
Directional, load encroachment, power swing blocking
The PCS-902 employs a wide range of innovative patented releasing and unique low-voltage elements are provided for
technologies, such as DPFC (Deviation Power Frequency phase-to-phase distance protection.
One zone phase-to-phase distance protection for pilot of-3 logic can be selected for protection criterion.
scheme (85)
One stage negative-sequence overvoltage protection (59Q)
The relay provides an independent zone for pilot scheme of
Four stage underfrequency protection and four stage
PUTT, POTT, Blocking, Unblocking, DTT & Zone Extension.
overfrequency protection (81)
The scheme integrates current reversal logic, weak-infeed
Frequency is calculated by using the positive-sequence
echo and open breaker echo.
voltage. The df/dt element is provided for the supervision of
Five zone phase-to-ground distance protection (21G) underfrequency protection.
The reactance characteristic, directional, load encroachment,
Phase overcurrent protection during VT failure (50PVT)
power swing blocking releasing and unique low-voltage
Independent phase overcurrent protection is automatically
elements are provided for phase-to-ground distance
enabled to substitute the phase-to-phase distance protection,
protection.
which is blocked during VT failure.
One zone phase-to-ground distance protection for pilot
Ground overcurrent protection during VT failure (50GVT)
scheme (85)
Independent ground overcurrent protection is automatically
The relay provides an independent zone for pilot scheme of
enabled to substitute the phase-to-ground distance
PUTT, POTT, Blocking, Unblocking, DTT & Zone Extension.
protection, which is blocked during VT failure.
The scheme integrates current reversal logic, weak-infeed
echo and open breaker echo. Switch-onto-fault (SOTF) logic
Switch-onto-fault logic is used to clear the faults during
High-speed DPFC distance protection (21D)
manual closing and auto-reclosing.
Innovative Deviation of Power Frequency Component
(DPFC) distance protection quickly clears faults in a sub- Unique power swing blocking releasing logic (PSBR)
cycle. DPFC is immune to the load fluctuation, weak-infeed The power swing blocking releasing logic prevents mal-
and power swing. operations during external faults in power swing situations. It
quickly clears the internal faults in power swing scenarios.
Pilot directional earth-fault protection (85)
The relay includes directional zero sequence comparison Out-of-step protection (78)
element for earth faults. The pilot scheme integrates current Broken conductor protection (46BC)
reversal logic, weak-infeed echo and open breaker echo. The ratio of negative to positive sequence current (2/1) is
adopted to detect the broken conductor.
Four stages phase overcurrent protection (50/51P)
Selectable time characteristics (definite-time or inverse-time) Dead zone protection (50DZ)
and directional elements (forward, reverse or non-directional) It is provided to clear the dead zone faults between CT and
are provided. A harmonic blocking function is integrated to breaker.
restrain each stage independently. Thermal overload protection (49)
Four stages neutral overcurrent protection (50/51G) Thermal accumulation using thermal models is implemented
Selectable time characteristics (definite-time or inverse-time) for overload protection. Two stages for alarm purpose or
and directional elements (forward, reverse or non-directional) tripping purpose are provided.
are provided. A harmonic blocking function is integrated to Pole discrepancy protection (62PD)
restrain each stage independently. It can be initiated by three auxiliary contacts of phase-
Three stages negative-sequence overcurrent protection segregate circuit breaker, and it can select zero-sequence
(50/51Q) current or negative-sequence current as auxiliary criterion.
Selectable time characteristics (definite-time or inverse-time) Reverse power protection (32R)
and directional elements (forward, reverse or non-directional) The reverse power protection monitors the direction of
are provided. Stage 3 can be set to alarm. active power flow and picks up when the mechanical energy
Breaker failure protection for one or two breakers (50BF) fails. This function can be used for operational shutdown
Breaker failure protection can be applied to single-breaker (sequential tripping) of the generator but also prevents
and dual-breaker applications. damage to the steam turbines.