EI Lecture No.19
EI Lecture No.19
EI Lecture No.19
where
V20 (line-to- line voltage) corresponds to the transformer no-load voltage which
is 3 to 5% greater than the on-load voltage across the terminals. For example, in
400 V networks, the line-to-line voltage adopted is V = 420 V and the line -to-
neutral voltage is V /√ 3 = 242.5 V.
Or
V20 = line -to- line voltage of the open circuited secondary windings of the
power supply transformer(s).
ZT = total impedance per phase of the installation upstream of the fault location
(in Ω)
Method of calculating ZT
Each component of an installation (MV network, transformer, cable,
circuit-breaker, bus bar, and so on...) is characterized by its impedance Z,
comprising an element of resistance (R) and an inductive reactance (X).
It may be noted that capacitive reactances are not important in short-
circuit current calculations.
The parameters R, X and Z are expressed in ohms, and are related by the
sides of a right angled triangle, as shown in the impedance diagram of
Figure 1.
1
Electrical Installation Lecture No.19 Dr. Mohammed Tawfeeq Alzuhairi
The method consists in dividing the network into convenient sections, and to
calculate the R and X values for each.
Where sections are connected in series in the network, all the resistive elements
in the section are added arithmetically; likewise for the reactances, to give RT
and XT. The impedance (ZT) for the combined sections concerned is then
calculated from
Any two sections of the network which are connected in parallel, can, if
predominantly both resistive (or both inductive) be combined to give a single
equivalent resistance (or reactance) as follows:
Let R1 and R2 be the two resistances connected in parallel, then the equivalent
resistance R3 will be given by:
or for reactances
A formula which makes this deduction and at the same time converts the
impedance to an equivalent value at LV is given, as follows:
where
2
Electrical Installation Lecture No.19 Dr. Mohammed Tawfeeq Alzuhairi
(ii) up to 36 kV
MV/LV transformer.
in milli-ohms
where
Pcu = total losses in watts
In = nominal full-load current in amps
Rtr = resistance of one phase of the transformer in milli-ohms (the LV and
3
Electrical Installation Lecture No.19 Dr. Mohammed Tawfeeq Alzuhairi
corresponding MV
3 - Circuit-breakers
4 - Busbars
4
Electrical Installation Lecture No.19 Dr. Mohammed Tawfeeq Alzuhairi
5 - Circuit conductors
20 °C EPR/XLPE 90 °C PVC 70 °C
Copper 18.51 23.6928 22.212
Alu 29.41 37.6448 35.292
Cable reactance values can be obtained from the manufacturers. For c.s.a. of
less than 50 mm2 reactance may be ignored. In the absence of other information,
a value of 0.08 mΩ / meter may be used (for 50 Hz systems) or 0.096 mΩ/meter
(for 60 Hz systems). For prefabricated bus-trunking and similar pre-wired
ducting systems, the manufacturer should be consulted.
6 - Motors
At the instant of short-circuit, a running motor will act (for a brief period) as a
generator, and feed current into the fault.
In general, this fault-current contribution may be ignored. However, if the total
power of motors running simultaneously is higher than 25% of the total
power of transformers, the influence of motors must be taken into account.
Their total contribution can be estimated from the formula:
Iscm = 3.5 In from each motor i.e. 3.5(m In) for m similar motors operating
concurrently.
The motors concerned will be the 3-phase motors only; single-phase-motor
contribution being insignificant.
5
Electrical Installation Lecture No.19 Dr. Mohammed Tawfeeq Alzuhairi
7 - Fault-arc resistance
Solution:
Is given by
Network upstream of
the MV/LV transformer Fig.2
From Table – 1 ,for
short-circuit level of 500MVA.
6
Electrical Installation Lecture No.19 Dr. Mohammed Tawfeeq Alzuhairi
From Table -3: Let the cable type XLPE , ρ = 23.7 approx.,hence,
(mΩ)
For the main circuit breaker: R and X are Not considered in practice.
7
Electrical Installation Lecture No.19 Dr. Mohammed Tawfeeq Alzuhairi
3- Short circuit calculation at point D: Bus bar B/B2 , Not considered in practice
.Only the impedance of the three-core cable ,20 m , 10 mm2 copper,
(mΩ)
Summary
8
Electrical Installation Lecture No.19 Dr. Mohammed Tawfeeq Alzuhairi
9
Electrical Installation Lecture No.19 Dr. Mohammed Tawfeeq Alzuhairi
(2) If there are several conductors in parallel per phase, then divide the
resistance of one conductor by the number of conductors. The reactance remains
practically unchanged.
10