Final Questions EPS-2 - 2019
Final Questions EPS-2 - 2019
Final Questions EPS-2 - 2019
Technology
Electrical Engineering
(3 & 4 Marks)
1. Define V.R. of a transmission line. List out methods for line compensation
based on value of V.R.
2. What is receiving end power circle diagram? Write down steps to draw
It.
3. Explain types of transmission Line.
4. Explain the importance of Power Circle Diagram.
5. How the Impedance Drop, Voltage Drop & Voltage Regulation do in
connection with transmission line differs?
Numericals:-
1) Determine the voltage, current and power factor at the sending end of a 3
phase, 50 Hz, Overhead transmission line 160 km long delivering a load of 100
MVA at 0.8 pf lagging and 132 KV to a balanced load. Resistance per km is
0.16Ω, inductance per km is 1.2 mH and capacitance per km conductor is
0.0082μF. Use nominal π method. (Winter 2016)
2) A 3-phase. 50-Hz overhead transmission line 100 km long has the following
constants.
Resistance/km/phase = 0.1 Ώ
Inductive reactance/km/phase = 0.2 Ώ
Capacitive susceptance/km/phase = 0.04 × 10 -4 Siemen
Determine (i) the sending end current (ii) sending end voltage (iii) sending
end power factor and (iv) Transmission efficiency when supplying a balance load
of 10,000 kW at 66 kV p.f. 0.8 lagging. Use nominal T method. (Winter 2018
2016)
3) Using the nominal π method, find the sending end voltage and voltage
regulation of a 250km, 3-Φ, 50Hz transmission line delivering 25 MVA at 0.8
power factor (lagging) to a balanced load at 132 kV. The line conductors are
spaced equilaterally 3m apart. The conductor resistance is 0.11 Ω/km and its
effective diameter is 1.6 cm. Neglect leakages. (May/June 2012)
4) A single circuit 60Hz transmission line 370km long. The load on the line is
125MW at 215 kV with 100% power factor. Find the voltage, current and power
at sending end and the voltage regulation of the line. (Given: z=0.5239/_ 79.02º
Ω/km and y = 3.17 x 10-6 /_ 90º mho/km). (Nov/Dec 2011)
5) A 275kV transmission line has the following line constants A= 0.85 /_5º, B =
/_ 75º.1) Determine the power at unity power factor that can be received if the
voltage profile at each end is maintained at 275kV. 2) What type and rating of
compensation equipment would be required if the load is 150MW at unity power
factor with the same voltage profile as in part (1). (Summer 2014)
7) A 60 Hz short transmission line having R= 0.62 ohms per phase and L = 93.24
mH per phase, supplies a three phase, wye-connected 100MW load of 0.9lagging
power factor at 21kV line to line voltage. Calculate the sending end voltage per
phase. (Winter 2017)
8) A 200km long three phase overhead line has a resistance of 48.7 ohms per
phase, inductive reactance of 80.2 ohms per phase and capacitance (line to
neutral) 8.42nF per km. It supplies a load of 13.5MW at a voltage of 88 kV at 0.9
lagging power factor. Using nominal T circuit, find sending end voltage , sending
end current , voltage regulation and power angle of given line. (Summer 2018)
9) A 50Hz transmission Line 300km long has a total series impedance of (40 +j
125) ohms and a total shunt admittance of 10-3 mho. The receiving end load is
50MW at 220kV with 0.8 lagging power factor. Find sending end voltage and
current using exact method. (Winter 2015)
12) A three phase, 60 Hz, completely transposed 345 kV, 200 km line has z=
0.032+ j0.35 Ω /km and y= j4.2 x 10-6 S/km. Full load at the receiving end is 700
MW at 0.99 p.f. leading and at 95% of rated voltage. Assuming a medium length
line, determine the following: ABCD parameters of the nominal π circuit, sending
end voltage and current and real power delivered by sending end. (Winter 2013)
13) Consider a 230 mile long 60 Hz transmission line. Its series impedance z is
0.1603 + j8277 -/mile and shunt admittance y is j5.105 X 10-mho/mile. The load
on the line is 125 MW at 215 kV with unity power factor. Find the voltage, current
and power at the sending end and the voltage regulation of the line. Also find the
wavelength and velocity of propagation in miles and miles/s respectively. Please
consider the line as a long line. (June 2011)
NUMERICALS
9. Three 20MVA generators each having a reactance of 0.2 p.u. are operating in
parallel. A fault occurs at generator bus. Find the fault MVA if fault is
symmetrical.
10. A three phase 20MVA, 10kV alternator has an internal reactance of 5% and
negligible resistance. Find the external reactance to be connected in series with
each phase so that steady state current in each phase does not exceed 8 times
full load current.
Numericals:-
1. The currents in three phase unbalanced system are Ia = (12 + j6), Ib = (12 -
j12), Ic = (- 15 + j10) A. The phase sequence is abc. Calculate, positive,
negative and zero sequence components of current.(Winter -2018,Summer
2017,2016,Winter 2014)
2. In a three phase four wire system the currents in line a, b and c under abnormal
condition are Ia = 100/_ 30º A, Ib =50/_300º A, Ic=30/_1800 A. Calculate the
zero positive and negative phase sequence currents in line a and return current
in the neutral conductor.(Summer 2017,2016)
3. One conductor of a 3 phase line is open as shown in fig. 3. The current flowing
to the Δ connected load through the line R is 10 A. With the current in line R
as reference and assuming that line B is open, find the symmetrical components
of the line currants.(Nov-Dec 2011)
Numericals:-
1. A 3 phase, 11kV, 25 MVA generator with Xo = 0.05 p.u, X1 = 0.2 p.u and
X2 = 0.2 p.u is grounded through a reactance of 0.3 Ώ .Calculate fault
current for a single line to ground fault.(Summer 2016)
2. Considering system shown in fig. 2 at no load, find out the line current ‘Ia’
at fault point when A-G fault occurs at the terminals of the motor. Let zero
sequence reactance of generator and motor is 50 % each. Zero sequence
reactance of transformers is 25 % each and zero sequence reactance of line
is 20 %. 1 ohm each is connected in the neutral circuit of both the
synchronous machines. (Summer 2015)
3. Considering system shown in fig. 2 at no load, find out the line current ‘Ia’
at fault point when B-C-G fault occurs at the terminals of the motor. Let
zero sequence reactance of generator and motor is 50 % each. Zero
sequence reactance of transformers is 25 % each and zero sequence
reactance of line is 20 %. 1 ohm each is connected in the neutral circuit of
both the synchronous machines.(Summer 2015)
4. Figure 3 shows a three phase generator rated 300 MVA, 23 kV. It supplies
a system load of 240 MVA, 0.9 p.f. lag at 230 kV through a 330 MVA,
23/230 kV. DY step-up transformer of leakage reactance 11 %. Neglecting
magnetizing current and choosing base values at the load as 100 MVA and
230 kV, find currents IA, IB and IC supplied to the load in p.u. with VA
(voltage of h.v. side for A phase) as reference. Also determine current Ia, Ib
and Ic supplied by the generator and generator terminal voltage.(Summer
2015)
NUMERICALS
1. A surge of 15kV magnitude travels along a cable towards its junction with an
overhead line. The inductance and capacitance of the cable and overhead line
are respectively 0.3 mH, 0.4µ F and 1.5 mH, 0.02 µF per km. Find the voltage
rise at the junction due to the surge.
CHAPTER – 6 CORONA