SG-DV4420 v1-1 IM EN NA 29000633 R001
SG-DV4420 v1-1 IM EN NA 29000633 R001
SG-DV4420 v1-1 IM EN NA 29000633 R001
The Sur-Gard model SG-DV4420 is a combination of The EEPROM programming is done easily and quickly
Fire control panel and SCHED-3A communicator. This by using the SUR-GARD SG-DVT1 SCHED-3A tester. It
fire transmitter consists of six channels: Two class-A is only necessary to enter the account ID and options
alarms A1 and A2, one End of line resistor supervisory needed. Other data such as the function bytes, delays,
input S1, and three closed loop supervisory S2, S3 and etc. can be modified to meet different operating conditions.
S4. There is also one programmable output, an AC fail,
and a low battery detector. The SG-DV4420 can transmit
up to ten codes to the MLR2 receiver at the central STAND-ALONE MODE
station. It includes the 12V power supply/battery charger SG-DV4420B mounted in Multi 2XF metal cabinet with
and the 24V power supply for the F1/F2 modem. The built-in 115 to 14VAC transformer, meeting ULC
standby power is obtained from a 12V battery. requirements as a Stand-Alone fire/sprinkler transmitter.
1
SYSTEM OVERVIEW FEATURES
The SG-DV4420 is intended for use as a fire transmitter POWER SUPPLY
only, for connection to a sprinkler riser or to output relay
The SG-DV4420 has a built-in 12VDC to 24VDC
contacts of an existing fire alarm control panel. This unit
regulated converter power supply, to operate the F1F2
does not include U.L.C. requirements for a complete
subset modem, a one Amp 12VDC power supply and
building fire alarm system such as multi-zone with alarm
battery charger. The auxiliary power supply can be used
and trouble indicators.
to power smoke detectors and other devices requiring
12VDC. 800mA 12VDC is available from the AUX
INPUTS
(positive) and GND (negative) terminals. It also includes
• 2 Class A zones AC failure and low battery detector.
• 1 ELR supervisory zon
Supervisory loops
S1 – 2700 ohms ELR +/- up to 250 ohms WATCH DOG CIRCUIT
The Watch Dog reset circuit continously monitors the
S2,S3,S4 – 500 ohms. operation of the microprocessor. If a malfunction occurs
(due to lightning or other unusual event) this circuit will
Eprom part number: Type 27C256.
restart the microprocessor in less than 10 seconds.
Nominal current draw: 260mA with fully charged
battery and F1/F2 subset LOW BATTERY DISCONNECT CIRCUIT (NOT
powered.
ON BOARD ONLY VERSION)
Battery Required: 6.5 Amp hr minimum to 15 If the battery voltage fall below about 10.5V, the system
Amp hr rechargeable gel-cell will electrically disconnect the battery to prevent it from
or sealed lead-acid battery being deep discharged. The system remains disconnected
mounted in panel. from the battery until the AC power comes back ON or
until the dead battery is replaced with a sufficiently
TRANSFORMER charged battery.
Built-in, 16,5 Vac, 37VA Class 2 Transformer.
Dimensions: 29cm(W) x 35.5cm(H) x 12.5cm(D) CLASS A FIRE ZONES: “A1” & “A2”
The Fire zones A1 and A2 are supervised (normally
open alarm initiating contacts) Class A circuits designed
Weight: 3.7Kg
to accept sprinkler switches, manual pull stations, building
fire alarm control panel, alarm output relay contacts or
latching four-wire smoke detectors.
SELECTION JUMPERS
The program selection jumper must be left open.
3
INSTALLATION
BENCH TESTING running close to it, to avoid electrical noise causing
disturbance to the components.
The SG-DV4420 contains factory default programming.
Any additional programming required is done through You can use up to 5 SG-DV4420 on 1 F1/F2 subset
the SG-DVT1 tester. For many applications all that will provided they are in the same location or 1 SG-DV4420
be required is to enter the ID number. If you need help, and 1 other subscribers control such as SG-DV1660, by
talk to your Sur-Gard distributor. using the SUR- GARD SG-DS1 module (Y connector).
You have to connect together the 24V negative terminals
Program the SG-DV4420 using the SG-DVT1 Tester
of both units, separate the ID codes and program a
(with program version 5.0 or later) as an access terminal.
different all call select for each one.
The SG-DVT1 is plugged into the SCHED-3A line modular
jack. The program select jumper J2 should be removed F1/F2 SUBSET
from the SG-DV4420 circuit board.
1. Remove power to the F1/F2 subset by unplugging the
Connect a 2.7K end of line resistor between the S1 input A.C. adaptor from the 120 VAC outlet (if installed).
terminal and the GND terminal. Connect a jumper on each Do not remove the plug from the “Adapt" input of the
normaly closed supervisory zone S2, S3 and S4 input. F1/F2 subset while the adaptor is powered as it may
Connect 2 loops to the A1 and A2 Sprinkler/fire class A cause an arc at the input and damage the F1/F2 subset.
input terminals - out to - in , and + out to + in. To
completely test your Fire system including the communicator 2. If the telephone company installed a cable on the
data, it is necessary to connect the unit to a test set, such "Terminal" input of the F1/F2 subset, disconnect it
as the SG-DVT1 (see system testing procedure). and connect the 6 pin modular cable MCBL6 (6 ft.)
included with the SG-DV4420. Then connect the cable
Connect a 14Vac, 20VA transformer to the AC terminals. to the SG-DV4420 Fire Transmitter. A custom length
Before plugging in the transformer, be sure the circuit 6 pin modular cable(MCBL-C) is also available on
board is not resting on anything metallic which may special order from Sur-Gard. The custom cable is
cause a short. available in any length up to the maximum run length
of 50 feet. See the "F1/F2 Subset Connections" diagram
NOTE: The SG-DV4420 will not start up if AC is OFF
on page 10.
and the battery is low.
3. The F1/F2 subset should be installed close to the
MOUNTING THE PANEL control panel. However, if it is impossible, follow
these precautions:
Select a dry location, close to an unswitched AC source,
close to a ground connection, and close to the F1/F2 • Avoid cable runs close to noise generators like
subset (modem) location. power transformer, motor, fluorescent tube, etc...
Remove the printed circuit board and mounting hardware • If you can’t avoid this, or the F1/F2 subset is too
from the cardboard retainer inside the panel. Before far from the control panel, it is necessary to use
attaching the cabinet to the wall, press the five white low capacitance shielded cable to connect the
nylon printed circuit board mounting studs and the ground F1/F2 subset to the control panel.
connection screw into the cabinet from the back.
RECOMMENDED MAXIMUM WIRE RUN
Pull all the cables into the cabinet and prepare them for
The RS-232 communication (Rx & Tx) has a
connection before mounting the circuit board to the
recommended maximum wire run of 50 feet, using Sur-
back of the cabinet. Press the circuit board down onto
Gard's 6 pin modular cable.
the mounting studs.
The power supply (24Vdc) has a recommended maximum
With power off, wire the DV4420 as shown on fig. #1. All
wire run of 100 feet using:
normally closed (N/C) loops require a jumper if not used.
The connections to the F1/F2 subset are shown on fig. • #18 awg unshielded 4 conductor cable
#2. Avoid running the cable close to noise generators
• #22 or #24 awg unshielded 4 conductor cable with
like power transformer, motor, fluorescent tube, etc...
2 wires connected in parallel for each of the 24VDC
Connections.
HOOK-UP PROCEDURE
FOR LONGER DISTANCES
DO NOT connect the transformer or battery until all other
wiring has been connected (See power-up procedure). For RS-232 communication distances greater than 50 feet,
shielded cable with Sur-Gard's SG-DS1 connectors at
Connect a ground cable from the cabinet ground connection each end must be used. One SG-DS1 has to be installed
by the shortest and most direct route to a grounding rod inside the Fire Transmitter cabinet and another one inside
and to the Earth Ground Terminal on the panel. the F1/F2 subset box, (see Appendix B for theSG-DS1
wiring diagrams). The maximum distance maybe extended
Connect zone cables to zone loop inputs and put jumpers by using a shielded cable such as those described below.
or end of line resistors as required on any unused zones.
Connect wires supplying power to detectors to the auxiliary
supply. Make sure that the PC board is clear of wire 4
A. For 50 feet to 100 feet If the transmitter is not communicating (no signal on Rx
• Use #18 awg shielded 4 conductor cable such led of transmitter) to the central station at this point, call
as Provo (Cat. Num. 1782-21) or Belden (Cat. the telephone Company and ask them to make sure
Num. 9814). that the “Leg” is on. The telephone company will ask
you for the circuit number and the leg number which
• #22 or #24 awg shielded 4 conductor cable. can be found along with the service telephone number
on a card fixed on the F1/F2 subset.
B. For 100 feet to 500 feet
Use Low Capacitance #24 awg shielded 4 conductor
cable such as ALCATEL (Cat. Num. 371-02-24), Provo REQUIREMENTS FOR ULC
(Cat. Num. 6652-21), or Belden (Cat. Num. 9927) for INSTALLATION APPROVAL
the RS-232 communication (Rx, Tx, and SG).
• All components used in the system (contacts, detectors,
You must also use a 24Vdc power supply (such as etc...) must be ULC listed.
Sur-Gard's SG-2415 24Vdc power supply) close to
• Wire the transformer to the A.C. line according to the
the F1/F2 Subset to power it. Make sure to run a
electrical code on a separate circuit breaker.
wire (#18 or two #24 awg wires in parallel) between
the negative 24Vdc terminal of the Fire Transmitter • The F1/F2 subset should be placed in a metal box,
and the power supply, so that they are connected (for example the SUR-GARD SG-UMBX1) close to
together. the control panel.
• The battery must have a minimum ampere hour
POWER-UP PROCEDURE capacity of 6.5AH. In case of long time power failure,
the control panel must function normally for 24hrs.
Before applying power to the SG-DV4420 or the F1/F2
subset, connect the 24V output to the “Batt” input of the NOTE: Refer to ULC Standard booklet “FIRE ALARM
F1/F2 subset. CERTIFICATE SERVICE OF UNDEWRITER’S
LABORATORIES OF CANADA”. You can
Connect the tansformer, wait approx. 5 seconds. Check
contact ULC at Toronto for more information
that A1 and A2 loop status led lights are off and the
or to obtain the booklet.
green “A.C. POWER” led is on. If a led(s) does not turn
off, find the cause (such as loop open or shorted) and
correct it. If the “A.C. POWER LED” is off, find the cause CONTROL POINT INFORMATION
(such as breaker turned off) and correct it. Control point #1: programmable output PGM OUT
NOTE: To supply AC power to the SG-DV4420, the The control point #1 can be activated remotely from the
transformer should not be connected to an receiver. This is done by sending a command containing
outlet that is controlled by a switch. the subscriber unit ID, which identifies to which unit the
command message is addressed and the point ID which
Check for the WATCH-DOG led pulses. This led indicator
identifies the control point.
flashes once every 10 seconds to show unit is functioning
normally. Activate a zone to be sure that the panel is Point ID bytes are split into 2 digits. The first digit specifies
responding to signals. If the panel does not respond the type of command and the second digit indicates
and there are no indicators on, check that the wiring is which control point is to execute the command (on the
correct. If the panel is responding normally, connect the DV4420, the control point is always #1). The point ID
battery. The red battery lead attaches to the positive byte start with a letter from A to D, giving the desired
battery post and the black battery lead attaches to the output function, as follows:
negative battery post.
A. Turn On the specified point.
B. Turn Off the specified point (stop).
SYSTEM TESTING C. Turn On for 2 seconds (Pulse) the specified point.
First test the system thoroughly using an SG-DVT1 tester. D. Flash the specified point, 2 seconds On, 2 Seconds
Contact the monitoring station to request a transmission Off, until a command is received to stop (B).
test before connecting the 6 pin modular cable to the
modem. Trip an alarm on any loop. Wait for the When a new command is received, for the programmable
communication to complete and check with the monitoring output (control point #1), it replaces the command
station to confirm the transmission. You can use the Rx/ previously in effect, if any.
Tx Led indicator to see if the transmitter receives or
Control point #1 can be activated internally (locally) by
transmits. Perform additional transmissions required by
the unit, for an “on time” of 2 seconds, when the SG-
the monitoring station.
DV4420 receives the “Kiss OFF” character from the
The system should be tested on batteries only and AC receiver. The “Kiss Off” character is sent by the receiver
only, to be sure that both supplies are present and as a confirmation signal that the last change of status
adequate. Make sure that the AC Power to the unit is message from the SG-DV4420 was correctly received.
connected to a separate, well marked, circuit breaker This output command takes priority over any command
which will not be turned off by accident. that output point was already executing.
5
SG-DV4420 WIRING DIAGRAM
14V AC , 20VA
NOT
USED
14VAC,
6
F1/F2 SUBSET CONNECTION DIAGRAM
7
SG-DVT1 CONNECTION DIAGRAM
8
PROGRAMMING - GETTING STARTED
The SG-DV4420 has it’s own EEPROM which is used When the connection is established the SG-DV4420
to keep in memory all the installer programming and will identify itself on the display as follows:
that won’t erase in case of power failure.
PROGRAMMING MODE and SG-DV4420 V1.0
All programming must be done according to the CONNECTING... ... CONNECTED
standards and requirements of the central station to
which this equipment is connected, and according to At this point the connection is complete and the SG-
the restrictions of Underwriters' Laboratories of DV4420 is ready to accept programming commands
Canada, if applicable. from the SG-DVT1. The SG-DVT1 is in programmer mode
and will prompt you with the following message:
The system ID code and other programmable parameters
can be changed in the EEPROM by using the SG-DVT1 Prog. all data ?
Tester (with program version 5.0 or later) as an access YES NO EXIT
terminal. The SG-DVT1 is plugged into the SCHED-3A
ENT SEL1 SEL2
line modular socket. The program select jumper J2 should
be temporarily removed. At this message you can select if all data needs to be
programmed (press [ENT] to go in the programming all
TRANSFER OF DEFAULTS TO THE EEPROM data mode) or just selected few (press [SEL1] to go in
the programming selected data mode). You may also
(Hardware Reset of EEPROM to Factory Defaults). Use select EXIT option to quit programmer mode by pressing
the following procedure: the [SEL2] button.
1. Power down the SG-DV4420 by removing both AC
and battery power. PROGRAMMING ALL DATA MODE
2. Using a Plug-In jumper borrowed from J2, short pins Press [ENT] to programm all data.
marked EEPROM RESET J1 together.
Prog. all data ?
3. Power up the SG-DV4420 and wait approx. 5 seconds. YES NO EXIT
SELECT MODE V5.0 If you press [SEL1], then the SG-DV4420 will prompt
NOW: SCAN MODE you to go ahead with reset to factory defaults with the
following message:
ENT SEL1 SEL2
ARE YOU SURE ?
Select the “PROG MODE” on the SG-DVT1 by Pressing NO YES EXIT
[SEL1] twice. The SG-DVT1 screen should be as follows:
ENT SEL1 SEL2
SELECT MODE V5.0
NOW: PROG MODE Press [SEL1] to confirm or press [ENT] or [SEL2] to abort
the operation. If you press [ENT], the SG-DV4420 will go
to the Programming All Data Mode. If you press [SEL2],
START PROGRAMMER MODE the SG-DV4420 will return to the programmer mode. If
Press [ENT] to start the programmer mode. The SG- [SEL1] is pressed, the SG-DV4420 will prompt you with
DVT1 will initiate the handshake with the SG-DV4420. the following message if the operation was aborted:
SELECT ADDRESS:
ADDR=00
SELECT ADDRESS:
ADDR=00 DATA=0 1
Continue Prog. ?
YES REDO EXIT
10
PROGRAMMING GUIDE
NOTE: All data shown are generally in Decimal [03] TO [0C] TRANSMISSION SELECT
Values (Except for alarm/restore codes which It is possible to select, for each zone, no transmission,
may be in Hex value). The locations are in alarm transmission only or alarm and restore transmission.
Hex value. This feature provides for by-passing zones you don’t
want transmitted to the receiver.
LOCATION 00 = NO TRANSMISSION.
[00] IDENTIFICATION CODE 01 = TRANSMISSION OF ALARM ONLY.
You may change the account identification code by 02 = TRANSMISSION OF ALARM AND RESTORE
entering a two digit number in hex. (DEFAULT 01).
DEFAULT
[01] OPTION 1 - ALL CALL SELECT [03] Transmission Select for FIRE INPUT A1 02
An “All Call” is a command sent by the central station’s [04] Transmission Select for FIRE TROUBLE A1 02
receiver after each scanning of 8 identification codes. [05] Transmission Select for FIRE INPUT A2 02
If a transmitter has an alarm at this moment, it can be
sent immediately to the central station, if the unit is [06] Transmission Select for FIRE TROUBLE A2 02
programmed to respond to that “All Call”. With this feature, [07] Transmission Select for SUPERVISORY S1 02
it is usually not necessery for that transmitter to wait for [08] Transmission Select for SUPERVISORY S2 02
its turn to be polled, before it is able to send an alarm
[09] Transmission Select for SUPERVISORY S3 02
to the central station.
[0A] Transmission Select for SUPERVISORY S4 02
00 = NO RESPONSE ON ALL CALL, [0B] Transmission Select for LOW BATT. DETECT 02
01 = RESPONSE ON ALL CALL #1 ONLY, [0C] Transmission Select for AC FAIL DETECT 02
02 = RESPONSE ON ALL CALL #2 ONLY,
03 = RESPONSE ON BOTH ALL CALLS ( #1 AND #2 ).
[0D] TO [16] ZONE ASSIGNMENT
04 = RESPONSE ON ALL CALL #1 IF ID CODE IS This feature permits each zone to be assigned to the
ODD AND ON ALL CALL #2 IF ID CODE IS EVEN. zone number desired, taking full advantage of the receiver
line card decoding.
NOTE: A number programmed higher than 04 gives
the same selection as 04. When 2 transmitters DEFAULT
are used on the same F1F2 subset, each [0D] Zone Assignment for FIRE INPUT A1 01
must have a different All Call. (DEFAULT 04). [0E] Zone Assignment for FIRE TROUBLE A1 02
Example of receiver scanning [0F] Zone Assignment for FIRE INPUT A2 03
[10] Zone Assignment for FIRE TROUBLE A2 04
01-02-03..08-ALL CALL #1-09-0A-0B..10-ALL CALL #2-
[11] Zone Assignment for SUPERVISORY S1 05
..
[12] Zone Assignment for SUPERVISORY S2 06
It is recommended that just 1 All Call be selected, and [13] Zone Assignment for SUPERVISORY S3 07
the choice of All Call be divided evenly over the installations.
[14] Zone Assignment for SUPERVISORY S4 08
In this way, approximately an equal number of subscribers
will be programmed for All Calls #1 and #2. [15] Zone Assignment for LOW BATT. DETECT 01
[16] Zone Assignment for AC FAIL DETECT 02
If two units are connected on the same modem (F1F2
subset): Skip at least 2 codes between your 2 identification [17] TO [20] FUNCTION BYTE
codes. (ex: #01,#04 so that 02 and 03 are used at other
This feature permits each zone to be assigned to the
locations.) Each unit should have a different All Call
zone description desired, taking full advantage of the
selected. So with automatic all call selection, you should
receiver line card decoding for central station without
have an odd and an even identification code. No response
automation.
on All Call should be used for lower security installations,
and when more than two units are connected to one DEFAULT
modem - for the 3rd and additional units.
[17] Function Byte for FIRE INPUT A1 50
[02] OPTION 2 - ALL CALL ANSWER SELECT [18] Function Byte for FIRE TROUBLE A1 50
00 = ALL CALL ANSWER ON ALARM AND RESTORE. [19] Function Byte for FIRE INPUT A2 50
01 = ALL CALL ANSWER ON ALARM ONLY. [1A] Function Byte for FIRE TROUBLE A2 50
[1B] Function Byte for SUPERVISORY S1 50
The unit can send an alarm and a restore on All Call,
but it is possible and preferable to limit it to sending [1C] Function Byte for SUPERVISORY S2 50
only the alarms and wait for the polling of its account [1D] Function Byte for SUPERVISORY S3 50
code before sending the restores. (DEFAULT 01). [1E] Function Byte for SUPERVISORY S4 50
[1F] Function Byte for LOW BATT. DETECT 51
[20] Function Byte for AC FAIL DETECT 51
11
NOTE: For a listing of all function byte possibilities, [27] PROGRAMMABLE OUTPUT MODE
refer to “Line Card DVACS* Alarm Decoder The programmable output can be activated as indicated
Version 4” sheet. below. (DEFAULT = 04).
ADDRESS ___________________________________________________________________________________________
____________________________________________________________________________________________________
Automation
Location Default USER
13
Automation
Location Default USER
Input Zone Std. F. byte Funct. Zone Zone Std. F. byte Funct. Zone
Name bit Addr Zn bit Addr byte Description bit Addr Zn bit Addr byte Description
“AUTOMATION” means suggested function bytes to program if the receiver is used with a central station computer
software such as SIMS or TAMCO and/or to have the alarms received as zones 1-10 without descriptive words such
as “Fire” or “Valve”.
“LIBRARY 4/2 STYLE” means suggested function bytes to program to display a “4/2 style” zone description. When
output to the printer or RS-232 computer port, the first digit of the zone tells you what type of zone it is, and the second
digit tells you what zone number it is, (just like the 2 digit alarm code in 4/2 digital dialer format). In the example, the
zone will be received as “Water alarm zone #01” for the Fire zone A1, “Fire alarm zone #10” for the Fire zone A2, etc...
14
TROUBLE SHOOTING
PROBLEM, SYMPTOMS SOLUTION, ACTION
Questions to ask yourself when doing 1. Verify the Tx and Rx led indicators on the panel:
troubleshooting:
RX: Should flash with polling at fairly steady rate.
n New installation? If inactive, check that the panel is otherwise
functioning, check the watch dog led, and items
n Existing installation that was working? 2 through 4 below, then contact the telephone
company to be sure that leg is “ON”.
n Communication failed under what
circumstances? (during power failure, TX: Flashes each time panel answers polling, longer
after work done on building or system) burst for alarms, restores, openings, closings,
etc... The Interval between flashes depends on
n Intermittent problem?
the number of subscribers polled. When an alarm
triggered, check if there is only one transmission
(burst). Often needing two or more attempts to
communicate is a sign of network problems.
15
TROUBLE SHOOTING
PROBLEM, SYMPTOMS SOLUTION, ACTION
Panel sends ID ok, does not always respond to 6. If all the above checks indicate that the panel and wiring
status report requests, or does not send alarms are correct, and the SG-DVT1 cannot communicate with
or other longer transmissions, or, receiver has the central station, contact your telephone company.
periods of incorrect response for this subscriber. Advise the company technician of any action taken so
far. Request that the telephone company verify the
following:
n Hub options
16
APPENDIX A - SG-DS1 WIRING DIAGRAMS
17
APPENDIX B - SG-DV4420 PROGRAMMING FLOW CHART
18
Limited Warranty
Sur-Gard Security Systems Ltd. warrants that for a period of twelve months from the date of purchase, the product shall be free
of defect in materials and workmanship under normal use and that in fulfilment of any breach of such warranty,
Sur-Gard Security Systems Ltd. shall, at its option, repair or replace the defective equipment upon return of the equipment to
its repair depot. This warranty applies only to defects in parts and workmanship and not to damage incurred in shipping or
handling, or damage due to causes beyond the control of Sur-Gard Security Systems Ltd. such as lightning, excessive
voltage, mechanical shock, water damage, or damage arising out of abuse, alteration or improper application of the
equipment.
The foregoing warranty shall apply only to the original buyer, and is and shall be in lieu of any and all other warranties, whether
expressed or implied and of all other obligations or liabilities on the part of Sur-Gard Security Systems Ltd. This warranty
contains the entire warranty. Sur-Gard Security Systems Ltd. neither assumes, nor authorizes any other person purporting to
act on its behalf to modify or to change this warranty, nor to assume for it any other warranty or liability concerning this
product.
In no event shall Sur-Gard Security Systems Ltd. be liable for any direct, indirect or consequential damages, loss of
anticipated profits, loss of time or any other losses incurred by the buyer in connection with the purchase, installation or
operation or failure of this product.
WARNING: Sur-Gard Security Systems Ltd. recommends that the entire system be completely tested on a regular basis.
However, despite frequent testing, and due to, but not limited to, criminal tampering or electrical disruption, it is possible for
this product to fail to perform as expected.
© 1999 SG Security Communications
401 Magnetic Drive, Units 24-28
Downsview, Ontario Canada M3J 3H9
Tel (416) 665-4494
Fax (416) 665-4222
Toll Free 1-800-418-7618 29000633 R001
www.sur-gard.com Printed in Canada
INSTRUCTION
MANUAL
SG-DV4420
Software Version 1.1
Table of Contents
INTRODUCTION .............................................................................................................................................................................. 1
STAND-ALONE MODE .................................................................................................................................................................. 1
FEATURES ....................................................................................................................................................................................... 2
POWER SUPPLY ........................................................................................................................................................................... 2
EEPROM NON-VOLATILE MEMORY ............................................................................................................................................ 2
SERIAL OUTPUT .......................................................................................................................................................................... 2
LOW BATTERY DETECTION ......................................................................................................................................................... 2
WATCH DOG CIRCUIT ................................................................................................................................................................. 2
LOW BATTERY DISCONNECT CIRCUIT (NOT ON BOARD ONLY VERSION) ............................................................................. 2
CLASS A FIRE ZONES: “A1” & “A2” ............................................................................................................................................ 2
SUPERVISORY INPUTS: “S1”, “S2”, “S3”, & “S4” ........................................................................................................................ 3
PROGRAMMABLE OUTPUT: "PGM OUT" ..................................................................................................................................... 3
SELECTION JUMPERS ................................................................................................................................................................. 3
ON BOARD LED INDICATORS ..................................................................................................................................................... 3
SOFTWARE SPECIAL FEATURES ................................................................................................................................................ 3
INSTALLATION ................................................................................................................................................................................. 4
BENCH TESTING ......................................................................................................................................................................... 4
MOUNTING THE PANEL .............................................................................................................................................................. 4
HOOK-UP PROCEDURE .............................................................................................................................................................. 4
POWER-UP PROCEDURE ............................................................................................................................................................ 5
SYSTEM TESTING ........................................................................................................................................................................ 5
REQUIREMENTS FOR ULC INSTALLATION APPROVAL ............................................................................................................. 5
CONTROL POINT INFORMATION ................................................................................................................................................ 5
23
24