Document No. 5.12008.08
Part No. 444496
Status 26-Apr-2017
b maXX 4000
Basic Units/
Power modules
with Servo Controller
1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.1 Information on the instruction handbook . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.2 Key to symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.3 Limitation of liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.4 Copyright protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.5 Other applicable documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.6 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.7 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.8 Guarantee provisions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.9 Customer service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.10 Terms used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.11 List of other applicable documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.1 Contents of the instruction handbook . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.2 Changes and modifications to the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.3 Usage for the intended purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.4 Responsibility of the operating company . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.5 Protective devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.6 Training of the personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.7 Personal protective equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.8 Special hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.9 Fire fighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.10 Safety equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.11 Conduct in case of danger or accidents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.12 Signs and labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.1.1 Dimensions BM441X. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.1.2 Dimensions BM442X. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.1.3 Dimensions BM4X3X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.1.4 Dimensions BM4X4X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.1.5 Dimensions BM4X5X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3.1.6 Dimensions BM4X6X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3.1.7 Dimensions BM4X7X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
3.2 Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
3.3 Operating requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
3.3.1 System types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
3.3.2 Requirements to the energy supply / supply system. . . . . . . . . . . . . . . . . . . . . . . . . 52
3.3.3 Motor requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
3.3.4 Required environmental conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
3.3.5 Correction factors if the operating conditions are changed . . . . . . . . . . . . . . . . . . . . 56
3.3.5.1 Mounting height . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
3.3.5.2 Environmental temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
3.3.5.3 Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
3.3.6 Coherence between rated current and peak current. . . . . . . . . . . . . . . . . . . . . . . . . 59
3.3.7 Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
6 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
6.1 Safety notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
6.2 Preparing for mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
6.2.1 Drilling patterns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
6.2.1.1 Drilling patterns BM441X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
6.2.1.2 Drilling patterns BM442X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
6.2.1.3 Drilling patterns BM4X3X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
6.2.1.4 Drilling patterns BM4X4X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
6.2.1.5 Drilling patterns BM4X5X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
6.2.1.6 Drilling patterns BM4X6X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
6.2.1.7 Drilling patterns BM4X7X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
6.3 Mounting instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
6.3.1 Requirements mounting plate for cold plate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
6.3.2 Connecting the water cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
7 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
7.1 Safety notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
7.2 Voltage test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
7.3 Demands on the power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
7.3.1 Connection instructions at special power supply systems . . . . . . . . . . . . . . . . . . . . 167
7.4 Requirements to the connecting cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
7.5 Protection of the device and the cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
7.6 PE connection and RCD compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
7.7 Installation requirements with regard to EMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
7.8 Requirements for the motor temperature sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
7.9 Installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
7.10 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
7.10.1 Connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
7.10.1.1 BM44XX, BM46XX, BM47XX (basic units). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
7.10.1.2 BM44XX, BM46XX, BM47XX power module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
7.10.2 Terminal overviews . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
7.10.2.1 Terminals BM4412, BM4413 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
7.10.2.2 Terminals BM4414 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
7.10.2.3 Terminals BM442X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
7.10.2.4 Terminals BM443X, BM463X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
7.10.2.5 Terminals BM444X, BM464X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
7.10.2.6 Terminals BM445X, BM446X, BM465X, BM466X . . . . . . . . . . . . . . . . . . . . . . . . . 186
7.10.2.7 Terminals BM466X, BM476X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
7.10.2.8 Terminals BM4755 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
7.10.2.9 Terminals BM447X, BM4773 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
7.10.3 Electrical connection power unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
7.10.4 Requirements for the screwing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
7.11 Controller terminals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
7.11.1 Encoder connection slot/position A and B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
7.11.2 Analog input slot/position D and E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
7.11.3 Digital inputs slot A to E/position D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
8 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
8.1 Safety notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
8.2 Operating concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
8.2.1 Enable signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
8.3 Power on switching frequency / DC link charging . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
8.3.1 Power supply switch-on frequency BM441X and BM442X . . . . . . . . . . . . . . . . . . . 225
8.3.2 Power supply switch-on frequency BM443X (Generation 1) . . . . . . . . . . . . . . . . . . 225
8.3.3 Power supply switch-on frequency BM443X generation 2, BM4X4X to BM4X7X . . 226
8.3.4 Calculation of the maximum permitted external capacity. . . . . . . . . . . . . . . . . . . . . 227
8.3.5 Effects of the different charging circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
8.3.6 Table of charging times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
9 Troubleshooting and fault correction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
9.1 Behavior in case of malfunctions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
9.2 Monitoring functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
9.3 Fault detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
9.4 Error handling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
9.4.1 Error reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
9.4.2 Error parameters, error messages, error reactions . . . . . . . . . . . . . . . . . . . . . . . . . 240
9.4.2.1 Error messages (2nd level) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
9.4.2.2 Sub-error messages (3rd level) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
9.4.3 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
10 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
10.1 Safety notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
10.2 Environmental condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
10.3 Inspection intervals - maintenance notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
10.3.1 Periodic maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 264
10.4 Repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
11 Accessories and Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
11.1 Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
11.1.1 Cables power supply - device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
11.1.2 Cables device - motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270
11.1.3 Cable control voltage supply/signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
11.1.4 Interface cable RS232 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272
11.2 Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273
11.2.1 Fuses BM441X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275
11.2.2 Fuses BM442X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277
11.2.3 Fuses BM4X3X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280
11.2.4 Fuses BM4X4X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
11.2.5 Fuses BM4X5X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 284
11.2.6 Fuses BM4X6X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288
11.2.7 Fuses BM447X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
11.2.8 UL fuse in the ballast circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
11.2.9 24V extra-low voltage protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
11.3 Mains filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
11.3.1 Block diagram of filter for mains applications (simplified) . . . . . . . . . . . . . . . . . . . . 294
11.3.2 Baumüller mains filter type code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
11.3.3 Required mains filter environmental conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
11.3.4 Electrical data mains filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295
11.3.5 Mains filter selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 298
These instruction handbook provides important information on handling the device. A pre-
requisite for safe work is compliance with all specified safety notes and procedural in-
structions.
Additionally, the valid accident prevention regulations and general safety regulations ap-
plicable to the scope of application the device must be complied with.
Read the instruction handbook, particularly the safety notes chapter, completely before
beginning any work on the device. The instruction handbook is part of the product and
must be kept accessible to personnel at all times in the immediate vicinity of the device.
Warning notes
Warning notes are identified by symbols in these instruction handbook. The notes are in-
troduced by signal words that express the extent of the danger.
It is imperative that these notes be complied with and are conscientiously regarded in or-
der to prevent accidents, personal injury and material damage.
DANGER!
....points out an immediately dangerous situation that will lead to severe injuries or
death if not avoided.
WARNING!
....points out a potentially dangerous situation that could lead to severe injuries or
death if not avoided.
CAUTION!
....points out a potentially dangerous situation that could lead to minor or slight inju-
ries if not avoided.
NOTICE!
....points out a potentially dangerous situation that could lead to material damage if
not avoided.
Recommen-
dations
NOTE!
....highlights useful tips and recommendations, as well as information for efficient and
problem-free use.
All specifications and notes in these instruction handbook were compiled taking into ac-
count the applicable standards and regulations, the state of the art and our knowledge
and experience of many years.
The manufacturer assumes no liability for damages due to:
m noncompliance with the instruction handbook
m usage for other than the intended purpose
m usage by untrained personnel
The actual scope of delivery can vary in case of optional equipment, laying claim to addi-
tional order options, or on account of the latest technical changes to the explanations and
representations described herein.
The user bears the responsibility for performing service and initial operation in accor-
dance with the safety regulations of the applicable standards and all other relevant gov-
ernmental or local regulations concerning the dimensioning and protection of conductors,
grounding, disconnectors, overcurrent protection, etc.
The person who carried out the mounting or installation is liable for any damage incurred
when assembling or connecting the device.
NOTE!
The specific contents, text, drawings, images and other representations are copy-
righted and subject to industrial property rights. Any prohibited usage is punishable
by law.
NOTE!
Please note, that BAUMÜLLER is not responsible to examine whether any (industrial
property) rights of third parties are infringed by the application-specific use of the
BAUMÜLLER products/components or the execution.
Components of other manufacturers are integrated into the device. For these purchased
parts, hazard assessments have been performed by the respective manufacturers. The
compliance of the design construction with the applicable European and national regula-
tions has been declared for the components by the respective manufacturers.
WARNING!
False or defective spare parts can lead to damage, malfunction or complete
failure, thus endangering safety.
Therefore:
m Only use original spare parts of the manufacturer.
Procure spare parts through an authorized dealer or directly from the manufacturer.
See also ZAccessories and Spare Parts– from page 267.
1.7 Disposal
Insofar as no take-back or disposal agreement has been made, please disassemble units
correctly and properly recycle the constituent parts.
See also ZDisposal– on page 317.
The guarantee provisions are stated in a separate document of the sales documents.
The devices described herein may only be operated in accordance with the stipulated
methods, procedures and conditions. Anything else not presented here, including the op-
eration of devices in mounted positions, is not permitted and must be cleared with the
plant on a case-by-case basis. If the devices are operated in any other manner than as
described within these instruction handbook, then all guarantee and warranty rights are
rendered null and void.
The term „device“ or the item designation BM4XXX are also used in this documentation
for this Baumüller product „b maXX 4000“. A list of the abbreviations used can be found
in ZAppendix A - Abbreviations– from page 321.
Instruction
handbook
Doc No. Part No. Part No.
German English
Instruction Handbook basic unit b maXX 4400, 4600, 4700 (ES) 5.12008 444495 444496
Parameter manual
Instruction hand-
book
function modules Doc No. Part No. Part No.
German English
Analog I/O module BM4-F-AIO-XX or AIO-XX 5.01045 354844 372665
Digital I/O module BM4-F-DIO/FIO-XX or DIO/FIO-XX 5.01046 354843 372666
Encoder module BM4-F-ENC-XX or ENC-XX 5.01042 354842 372861
Incremental encoder emulation module BM4-F-IEE-XX or IEE-XX 5.02020 354858 376728
SSI encoder emulation module BM4-F-SIE-XX or SIE-XX 5.03056 377123 379049
Instruction hand-
book
option modules Doc No. Part No. Part No.
German English
DISC-NT slave BM4-O-DNT-XX 5.03007 367670 -
CANopen slave BM4-O-CAN-03 5.02014 368692 368693
CANopen slave programming handbook for controller 5.02065 368694 372860
CANopen over EtherCAT programming handbook 5.07017 413208 432414
CANopen slave for b maXX PLC application handbook 5.03057 376486 376487
b maXX drive PLC 5.01051 366197 354845
b maXX drive PLC application handbook 5.02004 366198 372017
BM4-O-ETH-01, BM4-O-ETH-02, BM4-O-CAN-04 for b maXX PLC 5.03001 366202 372042
BM4-O-ETH-01, BM4-O-ETH-02, BM4-O-CAN-04 CANopen master for 5.03002 366203 372043
b maXX PLC application handbook
CANsync master for b maXX PLC 5.02056 366199 372025
Each person who is tasked with performing work on or with the device must have read
and understood the instruction handbook before working with the device. This also ap-
plies if the person who is involved with this kind of device or a similar one, or has been
trained by the manufacturer.
The device is conceived and constructed exclusively for usage compliant with its intended
purpose described in these instruction handbook.
The devices of the model series BM4400, BM4600, BM4700 are either mains rectifier or
active mains rectifier in combination with power modules with servo controller. Devices
are also available in graduated design size and performance classes.
The devices BM4400, BM4600, BM4700 are used exclusively as a converter for con-
trolling a motor.
A device is considered as being used compliant with its intended purpose if all notes and
information of these instruction handbook are adhered to.
WARNING!
Danger arising from usage for an unintended purpose!
Any usage that goes beyond the intended purpose and/or any non-compliant use of
the device can lead to dangerous situations.
Therefore:
m Only use the device compliant with its intended purpose.
m Observe all specifications of these instruction handbook.
m Ensure that only qualified personnel work with/on this device.
m When configuring, ensure that the device is always operated within its specifica-
tions.
m Mount the device on a wall that can sufficiently bear the load.
m The device must always be operated within a control cabinet.
m Ensure that the power supply complies with the stipulated specifications.
m The device may only be operated in a technically flawless condition.
m Only operate the device in combination with components approved by Baumüller
Nürnberg GmbH.
m The device has been developed in such a manner that it fulfills the requirements
of the category C3 according to IEC 61800-3:2012.
m The device is not intended to be connected to the public power supply system. To
operate the device in primary surroundings of the category C2/C1 (residential,
business and commercial areas, directly on a public low-voltage power supply
without an intermediate transformer), special measures to reduce the transient
emissions (line-internal and radiated) must be provided for and certifiable by the
system builder. Otherwise, EMC interference could occur without such additional
measures.
The device will be used in commercial areas. Thus, the proprietor of the device is subject
to the legal work safety regulations.
Along with the notes on work safety in these instruction handbook, the safety, accident
prevention and environmental protection regulations valid for the area of application of
this device must be complied with. Whereby:
m The operating company must inform himself about the applicable work health and safe-
ty regulations and ascertain, in a hazard assessment, any additional hazards that could
arise from the special working conditions in the use area of the device. These must
then be implemented in the form of instruction handbook for operation of the device.
m These instruction handbook must be kept accessible to personnel working with the de-
vice at all times in the immediate vicinity of the device.
m The specifications of the instruction handbook must be adhered to completely and
without exception.
m The device may only be operated in a technically faultless and operationally safe con-
dition.
Protection class
BM441X, BM442X IP 20
BM443X, BM444X IP 20, with a contact-isolated con-
BM463X, BM464X nection in accordance with IP 20,
otherwise IP 10.
BM445X, BM446X, BM447X IP 00
BM465X, BM466X
BM475X, BM476X, BM477X
All devices BM4400, BM4600, BM4700 must be installed in an appropriate control cab-
inet to meet the protection classification required in EN 61800-5-1, chapter 4.2.3.3 (IP 30:
only upper horizontal surfaces; IP 20: all other surfaces).
DANGER!
Risk of fatal injury from electrical current!
There is an immediate risk of fatal injury if live electrical parts are contacted.
Therefore:
m The device must be in operated inside of a control cabinet that provides protection
against direct contact of the devices and at least meets the requirements of
EN 61800-5-1, Chapter 4.2.3.3.
WARNING!
Risk of injury due to insufficient qualifications!
Improper handling can lead to significant personal injury and material damage.
Therefore:
m Certain activities can only be performed by the persons stated in the respective
chapters of these instruction handbook.
In these instruction handbook, the following qualifications are stipulated for various areas
of activity:
m Operating personnel
n The drive system may only be operated by persons who have been specially trained,
familiarized and authorized.
n Troubleshooting, maintenance, cleaning, maintenance and replacement may only
be performed by trained or familiarized personnel. These persons must be familiar
with the instruction handbook and act accordingly.
n Initial operation and familiarization may only be performed by qualified personnel.
m Qualified personnel
n Electrical engineers authorized by Baumüller Nürnberg GmbH, and qualified electri-
cians of the customer or a third party who have learned to install and maintain
Baumüller drive systems and are authorized to ground and identify electrical power
circuits and devices in accordance with the safety engineering standards of the com-
pany.
n Qualified personnel have had occupational training or instruction in accordance with
the respective locally applicable safety engineering standards for the upkeep and
use of appropriate safety equipment.
The wearing of personal protective equipment is required when working in order to mini-
mize health and safety risks.
m The protective equipment necessary for each respective type of work shall always be
worn during work.
m The personal safety signs present in each working area must be observed.
Hard hat
to protect against falling down and flying around objects.
Safety shoes
to protect against heavy objects falling down.
Protective gloves
to protect hands against friction, abrasion, puncturing or more severe injuries, as well
as contact with hot objects.
In the following section, the remaining marginal risks will be stated that have been iden-
tified as a result of the hazard analysis.
Observe the safety notes listed here and the warning notes in the further chapters of this
Instruction handbook to reduce health risks and dangerous situations.
Electrical current
DANGER!
Risk of fatal injury from electrical current!
There is an immediate risk of fatal injury if live electrical parts are contacted. Damage
to the insulation or individual components can be life-threatening.
Therefore:
m Switch off the electrical power immediately in case of damage to the power supply
insulation.
m Only allow work on the electrical system to be performed by qualified personnel.
m Switch off the current when any kind of work is being performed on the electrical
system and ensure safety before switching on again.
DANGER!
Risk of fatal injury from electrical current!
Stored electric charge.
Discharge time of the rack system = discharge time of the device with the longest DC
link discharge time in the rack system.
See ZElectrical data basic units– from page 63.
Therefore:
m Do not touch electrically live parts before taking into account the discharge time of
the capacitors.
m Pay attention to the corresponding notes on the device.
m If additional capacitors are connected to the DC link, the DC link discharge can
take a much longer time. In this case, the necessary waiting period must itself be
determined or a measurement made as to whether the equipment is de-energized.
This discharge time must be posted, together with an IEC 60417-5036 (2002-10)
warning symbol, on a clearly visible location of the control cabinet.
Moving compo-
nents
WARNING!
Risk of injury from moving components!
Rotating components and/or components moving linearly can result in severe injury.
Therefore:
m Do not touch moving components during operation.
m Do not open any covering during operation.
m The amount of residual mechanical energy depends on the application. Powered
components still turn/move for a certain length of time even after the power supply
has been switched off. Ensure that adequate safety measures are taken.
DANGER!
Risk of fatal injury from electrical current!
There is a risk of electric shock if an electrically-conductive, fire-extinguishing agent
is used.
Therefore:
m Use the following fire-extinguishing agent:
WARNING!
Risk of fatal injury due to non-functional safety equipment!
Safety equipment provides for the highest level of safety in a facility. Even if safety
equipment makes work processes more awkward, under no circumstances may they
be circumvented. Safety can only be ensured by intact safety equipment.
Therefore:
m Before starting to work, check whether the safety equipment is in good working or-
der and properly installed.
And if something m Stop operation of the device immediately with an EMERGENCY Stop.
does happen: re- m Initiate first aid measures.
spond properly.
m Evacuate persons from the danger zone.
m Notify the responsible persons at the scene of operations.
m Alarm medical personnel and/or the fire department.
m Keep access routes clear for rescue vehicles.
The following symbols and information signs are located in the working area. They refer
to the immediate vicinity in which they are affixed.
WARNING!
Risk of injury due to unreadable symbols!
Over the course of time, stickers and symbols on the device can become dirty or oth-
erwise unrecognizable.
Therefore:
m Maintain all safety, warning and operating labels on the device in easily readable
condition.
Electrical voltage
Only qualified personnel may work in work areas that identified with this.
Unauthorized persons may not touch working materials marked correspondingly.
DANGER!
Risk of fatal injury from electrical current!
Stored electric charge.
Discharge time of the rack system = discharge time of the device with the longest DC
link discharge time in the rack system.
See ZElectrical data basic units– from page 63.
Therefore:
m Do not touch before taking into account the discharge time of the capacitors and
electrically live parts.
m Heed corresponding notes on the equipment.
m If additional capacitors are connected to the DC link, the DC link discharge can
take a much longer time. In this case, the necessary waiting period must itself be
determined or a measurement made as to whether the equipment is de-energized.
This discharge time must be posted, together with an IEC 60417-5036 (2002-10)
warning symbol, on a clearly visible location of the control cabinet.
NOTE!
When in operation, the top of the device can heat up to temperatures > 70 °C!
NOTE!
Only a device marked with the TÜV Rheinland certification label and the safety label
fulfills a certified safety function within the meaning of PL classification according
ISO 13849 or SIL according EN 61800.
4400_0012_rev01_int.cdr
Einbau-Einzelleistun
Ostendstr. 80-90 D-90482 Nürnberg
gseinheit
BAUMÜLLER NÜRNBERG GMBH
Typ:
www.baumueller.de
BM4453-FI-01244-
Made in Germany
S01-03
Eingang: 3x400V (480V)
AC 50/60Hz
Einbau-Einzelleistun
Ostendstr. 80-90 D-90482 Nürnberg
BM4453-FI-01244-
Made in Germany
Typ:
www.baumueller.de
S01-03 BM4453-FI-01244-
Made in Germany
S01-03
Eingang: 3x400V Art.Nr.:
(480V) AC 50/60Hz Eingang: 3x400V (480V) 06500275
Ausgang: 3x0...400V AC 50/60Hz Ser.Nr.:311035532
(460V) AC 3x150A Ausgang: 3x0...400V (460V)
Betriebsart: GBK (125A) 0..450Hz AC 3x150A (125A)
130% <1min Betriebsart: GBK 0..450Hz
130% <1min
Art.Nr.: 06500275
Ser.Nr.:311035532 Art.Nr.: 06500275
Ser.Nr.:311035532
Einbau-Einzelleistun
Ostendstr. 80-90 D-90482 Nürnberg
gseinheit
BAUMÜLLER NÜRNBERG GMBH
Typ:
www.baumueller.de
BM4453-FI-01244-
Made in Germany
S01-03
Eingang: 3x400V
(480V) AC 50/60Hz
Ausgang: 3x0...400V
(460V) AC 3x150A
Betriebsart: GBK (125A) 0..450Hz
130% <1min
Art.Nr.: 06500275
Ser.Nr.:311035532
Einbau-Einzelleistungseinheit
Ostendstr. 80-90 D-90482 Nürnberg
BAUMÜLLER NÜRNBERG GMBH
The following dimension drawings show the main dimensions of the devices. By means
of the dimension drawings the space requirements within the control cabinet are deter-
mined. The dimension drawings in ZDrilling patterns– from page 147 must be used in or-
der to do the required drilling / segments.
NOTE!
All dimensions in mm.
NOTE!
Only the basic controller has a design cover.
NOTE!
The following devices are shown with design cover. The ES controller is designed
without a design cover. The depth of the device was reduced by 66.5 mm due to this.
It must be considered that the connectors and cables require additional space.
Figure 8: Dimensions BM442X-F/C *: Observe minimum clearance, Observe ZCooling– from page 61.
**: Dimensions specified with design cover. The ES controller is not
equipped with a design cover.
Figure 9: Dimensions BM443X-S/Z, BM443X-A/F *: Observe minimum clearance, Observe ZCooling– from page 61.
**: Dimensions specified with design cover. The ES controller is not
equipped with a design cover.
Figure 10: Dimensions BM443X-C, BM463X-F *: Observe minimum clearance, Observe ZCooling– from page 61.
**: Dimensions specified with design cover. The ES controller is not
equipped with a design cover.
Figure 11: Dimensions BM444X-S/Z, BM464X-S/Z *: Observe minimum clearance, Observe ZCooling– from page 61.
**: Dimensions specified with design cover. The ES controller is not
equipped with a design cover.
Figure 12: Dimensions BM444X-A/F, BM464X-A/F *: Observe minimum clearance, Observe ZCooling– from page 61.
**: Dimensions specified with design cover. The ES controller is not
equipped with a design cover.
Figure 13: Dimensions BM445X-S/Z, BM465X-S/Z *: Observe minimum clearance, Observe ZCooling– from page 61.
**: Dimensions specified with design cover. The ES controller is not
equipped with a design cover.
***: Width including screw heads.
Figure 14: Dimensions BM445X-A/F, BM465X-A/F *: Observe minimum clearance, Observe ZCooling– from page 61.
**: Dimensions specified with design cover. The ES controller is not
equipped with a design cover.
***: Width including screw heads.
NOTE!
The device BM4X5X-AX-0XXX was extended by about 70 mm downwards with an
additional protective plate against contact.
Figure 18: Dimensions BM446X-S/Z *: Observe minimum clearance, Observe ZCooling– from page 61.
**: Dimensions specified with design cover. The ES controller is not
equipped with a design cover.
***: Width including screw heads.
Figure 19: Dimensions BM446X-A/F and BM466X-A/F *: Observe minimum clearance, Observe ZCooling– from page 61.
**: Dimensions specified with design cover. The ES controller is not
equipped with a design cover.
***: Width including screw heads
NOTE!
The device BM4X6X-AX-0XXX was extended by about 80 mm downwards by an ad-
ditional protective plate against contact.
Figure 22: Dimensions BM447X-F, BM477X-F *: Observe minimum clearance, Observe ZCooling– from page 61.
**: Dimensions specified with design cover. The ES controller is not
equipped with a design cover.
Figure 23: Dimensions BM447X-A *: Observe minimum clearance, Observe ZCooling– from page 61.
**: Dimensions specified with design cover. The ES controller is not
equipped with a design cover.
3.2 Weight
1) The first row specifies the dimensions of the devices BM441X-XXX-00XXX-XX and BM441X-XXX-01XXX-
XX. The second value specifies the dimensions of the device BM441X-XXX-02XXX-XX.
2) Dimensions for the devices BM44XX-S and BM46XX-S. The deviations of the other cooling versions see
ZDimensions– from page 31.
3) The dimensions for the device BM447X-F and BM477X-FXX-3XXXX are specified. The specified depth is
the total depth of the device. See ZFigure 23– on page 49.
There are three basic types of the current supply systems regarding the grounding, which
conform with DIN VDE0100 part 300 and IEC 60364:
m The TN system has a directly grounded point (system grounding). The cabinet of the
electrical installation is connected via the protective conductors and PE conductors
with this point.
m The TT system has a directly grounded point (system grounding). The cabinet of the
electrical installation is connected with grounding electrodes. The grounding elec-
trodes are separated from system grounding.
m The IT system has no direct connection between the active conductors (L1, L2, L3, N)
and grounded parts (PE). The cabinet of the electrical installation is grounded. The
separation is reached by using an isolating transformer or an independent current
source (generator, battery).
If the low-impedance ground fault is adequate, an upstream fuse within the TN system or
the TT system responds. At a high-impedance ground fault a fuse does not respond. This
ground current (residual currents) can be dangerous. Therefore sensitive circuit breakers
are used for residual current monitoring.
At a ground fault In an IT system there is no ground current. The upstream fuses do not
respond. Therefore the operation procedure is maintained. A second ground fault at an-
other phase leads to residual currents. This can initiate a fuse. In order to detect the first
ground fault a ground leakage monitor is required. In order to detect the second ground
fault a residual current monitoring is required.
NOTICE!
The operation of the BM4400, BM4600, BM4700 devices is possible at IT systems
and at TN / TT systems.
NOTE!
Certain device types are available in type BM4XXX - XIX only. This devices can be
operated on IT, TN/TT systems and grounded delta systems.
Voltage dips 10 % to 80 % 1)
EN 61800-3:2004 and A1:2012
Devices BM4400, BM4600, BM4700 are designed to operate three-phase current mo-
tors with a terminal motor voltage of 3 x 350 V (typical for servo motors of Baumüller). De-
vices BM4400, BM4600, BM4700 are designed to operate 3 x 400 V (standard
asynchronous motors and customer-specific motors of Baumüller). The motors must be
operated wye-connected. The rated DC link voltage is 540 VDC. The DC link voltage may
rise up to 780 V to 800 V in braking operation. The connected motor must be designed
for these DC link voltages.
The DC link voltage remains between 640 V and 760 V continuously (not only in the brak-
ing operation), if the BM4400, BM4600, BM4700 power modules are operated at a volt-
age-controlled DC link (e.g. BM51XX). The connected motor must be able to operate at
these voltages continuously.
The device can be used at lower voltages, also (e.g. 3 x 230 V). However, here, the three-
phase current motors must be designed for the operation with power inverters with up to
800 V DC link voltage, because the brake resistor threshold remains (see ZElectrical data
basic units– from page 63). For these reasons three-phase motors with UDC,
rated 540 V must be used, only.
Degree of pollution 2
EN 61800-5-1, table 6, Tab. 2
1)
For the operation in an environment of category C2 according to IEC 61800-3:2012, additional measures may be required.The manu-
facturer of the installation / user must provide the following evidence in this case: The additional measures are effective. The specified
limit values of category C2, which are described in IEC 61800-3, are complied with.
2) See correction factors at environmental conditions, which were changed ZMounting height– on page 56.
NOTICE!
Normally, non-conductive pollution occurs. Conductive pollution is unacceptable.
Conductive pollution can lead to the destruction of the device. The customer is re-
sponsible for destructions, which were caused by pollution due to conductive materi-
als or components.
If the devices BM4400, BM4600, BM4700 are operated at operating conditions, which
lead to different correction factors, then all correction factors must be considered by mul-
tiplying them simultaneously to calculate the output power and the output current.
The following correction factors are to be considered if nothing other is specified at the
„Technical data“ of the device:
If the devices BM4400, BM4600, BM4700 are operated above an absolute altitude of
1000 m, then the output power must be reduced against the rated power according to the
following curve.
120%
100%
80%
Output power
Rated power
60%
40%
20%
0%
0m 1.000m 2.000m 3.000m 4.000m 5.000m
Mounting height
Figure 24: Reducing of the output power in dependence of the absolute altitude
NOTE!
Baumüller devices, which are provided for the operation at grounded delta systems
or IT supply systems, may have an operating altitude of 2000 m at these systems,
only. If the altitude is higher than 2000 m to 4000 m these devices must be operated
at TN systems and TT systems. Such systems, e. g. can be achieved by using an iso-
lating transformer with a secondary-sided star point.
100 %
Output current device
50 %
498 V
Output voltage device
370 V
177 V
System voltage
207 V 400 V 528 V
Figure 26: Reducing the output voltage in dependence with the input voltage
Output power
100 % PRated
Output power device
The output power of the device is obtained by multiplying the output current with the
output voltage.
SOut = UOut x IOut x 3
It is necessary to reduce the output current to a value between 400 V and 528 V, in or-
der to obtain the specified curve / surface.
i(t)
I I
3 3
I I
1 1
I I
2 2
t1 t2 t3 t1 t2 t3
t
T
k 2 tn 2 t 2 t 2 t
I eff = n = 1 I n ---
- = I 1 ---1- + I 2 ---2- + I 3 ---3-
T T T T
i(t)
I I
peak peak
t
t peak T + tpeak
T
t peak I rated 2
----------- = -----------
-
T I peak
m Coherence between peak current of drive and the braking peak current
Typical values:
UDC link, braking = 780 V
UDC link, acceleration = 540 V
Motor = 0.9
3)
Rated flow = 10 l/min
If you have other cooling water flow rates than the ones, which were mentioned above, please contact Baumüller Nürnberg GmbH.
The cooling water must meet the following requirements:
NOTE!
Instead of a continuous flow of the water coolers, it is possible to operate with a tem-
perature-controlled, switched water supply. In this case the customer must install a
control equipment, so that the flow of the water can be enabled or avoided. This con-
trol equipment must read and process the available value „heat sink temperature“ in
the controller. It is recommended to enable water flow, if 58 °C were reached. The
water flow also must be possible to be stopped if it reached 57 °C. The maximum per-
mitted hysteresis of 5 K. Therefore, the closing temperature can be set to 60 °C and
the opening temperature to 55 °C. It is advantageous to set the hysteresis lower, as
the controller is a free parameterizable 2-point controller. The integrated 2-point con-
troller can now directly access the variable „heat sink temperature“.
The temperature controlled, switched water supply is able to use water, which is sig-
nificantly colder. The 2-point hysteresis control of the heat sink temperature avoids
impermissible condensation. This way, more power can be emitted via the heat sink.
This is advantageous, if water-cooled devices are used, which have an additionally
integrated brake resistor (see ZAdditional data referring to water-cooled brake resis-
tors– from page 106).
Contact the local Baumüller office for support concerning configuration of alternative
cooling water temperature control.
1)
The rated value refer to a DC link voltage of 540 V, a control voltage of 24 V and an environmental temperature of 40 °C.
2)
The output voltage is a pulsed DC voltage. The operating range refers to the RMS value of the fundamental wave.
U DC
U AC = 3 0 V to 3 ----------
- – 10 V without overmodulation of PWM
2
3)
Switching frequency of the inverter (adjustable).
4)
RMS value at an environmental temperature of 40 °C.
5)
At a rated supply voltage the unit provides rated output currents and maximum output currents. At input voltages above the rated supply
voltage the output currents at constant output power have to be reduced accordingly.
6)
Between 40° C and 55° C the output current must be reduced. See correction factors at changed operating conditions ZEnvironmental
temperature– on page 57.
7)
The peak output current is supplied for the maximum peak current period for the motor at the first acceleration (cold power unit). The in
fact possible overload time is dependent on the preload of the device and on the heat sink temperature, it is determined by the overload
monitoring of the device.
8) These values are specified for the mounting to a heat-conducting surface with a thermal resistance of 0.115 K/W. The maximum per-
mitted temperature of the cabinet at the measuring point is 75 °C. See ZFigure 82– on page 181.
9)
NOTE!
There are other peak current limits, if BM4414 is in braking operation, only. The fol-
lowing peak currents are possible: 15 A at 4 kHz switching frequency and 10 A at
8 kHz switching frequency
12) The
range of the output frequency is based on a stationary operation in the linear range of the PWM, i. e. without overmodulation.
The quality of the generated output voltages depends on the ratio between output frequency and current controller frequency fI-R
( fI-R = 1/cycle time current controller).
The maximum output frequency fmax , generated with high quality, is calculated as follows:
f I-R
f max = -------- , typical K Pf 18
K pf
Furthermore the controller sets an upper limit for the output frequency of 599 Hz (please contact the responsible Baumüller sales de-
partment, keyword: export restriction).
The range of the output frequency is defined as follows:
PWM frequency Current controller cycle time Range of the output frequency
2 kHz 250 µs 0 - 225 Hz
4 kHz/8 kHz 125 µs 0 - 450 Hz
The controller allows the device to generate output voltages with frequencies between fmax and 599 Hz. However the quality of this volt-
ages cannot be guaranteed.
Typical the devices are marked with the max output frequency at 4 kHz switching frequency: 0 ... 450 kHz.
13)
The continuously permitted output current must be reduced complying with ZOutput frequency dependent continuous current derating
BM4XXX– on page 112, if the statical output frequency is lower than 15 Hz and the frequency remains between 0 and 15 Hz for over
5 seconds.
1)
All rated values refer to a DC link voltage of 540 V, a control voltage of 24 V and an environmental temperature of 40 °C.
2) Using the power choke listed in ZPower chokes– on page 300 at a power supply with UK,power supply = 0.4 %.
3)
The output voltage is a pulsed DC voltage. The operating range refers to the RMS of the fundamental wave.
U DC
U AC = 3 0 V to 3 ----------
- – 10 V without overmodulation of the PWM.
2
4)
Switching frequency of the inverter (adjustable).
5)
RMS at an environmental temperature of 40 °C.
6)
At rated input supply voltage the device supplies the rated- / maximum output currents. At input voltages above the rated supply voltage
the output currents at constant output power have to be reduced, accordingly.
7) The input current must be reduced between 40 °C and 55 °C, see correction factors at changed operating conditions ZEnvironmental
temperature– on page 57.
8)
The peak output current is supplied for the maximum peak current period for the motor at the first acceleration (cold power unit). The in
fact possible overload time is dependent on the preload of the device and on the heat sink temperature, it is determined by the overload
monitoring of the device.
7000
6000
external DC link capacitance [µF]
5000
3000
BM 4422, 4423
2000
BM 4426-XTX-XXX85
1000
0
200 250 300 350 400 450 500
Maximum power supply voltage [V]
10)
The sum of the transferred mean effective power via the DC link terminals and the transferred mean effective power via the motor ter-
minals may not exceed the specified value continuously.
11) The
range of the output frequency is based on a stationary operation in the linear range of the PWM, i. e. without overmodulation.
The quality of the generated output voltages depends on the ratio between output frequency and current controller frequency fI-R
( fI-R = 1/cycle time current controller).
The maximum output frequency fmax , generated with high quality, is calculated as follows:
f I-R
f max = -------- , typical K Pf 18
K pf
Furthermore the controller sets an upper limit for the output frequency of 599 Hz (please contact the responsible Baumüller sales de-
partment, keyword: export restriction).
The range of the output frequency is defined as follows:
PWM frequency Current controller cycle time Range of the output frequency
2 kHz 250 µs 0 - 225 Hz
4 kHz/8 kHz 125 µs 0 - 450 Hz
The controller allows the device to generate output voltages with frequencies between fmax and 599 Hz. However the quality of this volt-
ages cannot be guaranteed.
Typical the devices are marked with the max output frequency at 4 kHz switching frequency: 0 ... 450 kHz.
12) The continuously permitted output current must be reduced complying with ZOutput frequency dependent continuous current derating
BM4XXX– on page 112, if the statical output frequency is lower than 15 Hz and the frequency remains between 0 and 15 Hz for over
5 seconds.
7)
The input current must be reduced between 40 °C and 55 °C. See correction factors at changed operating conditions ZEnvironmental
temperature– on page 57.
8)
The peak output current is supplied for the maximum peak current period for the motor at the first acceleration (cold power unit). The in
fact possible overload time is dependent on the preload of the device and on the heat sink temperature, it is determined by the overload
monitoring of the device.
9) The sum of the mean effective power, which is transmitted via the DC link terminals and the mean effective power at the motor terminals,
may not exceed the specified value continuously.
10)
The range of the output frequency is based on a stationary operation in the linear range of the PWM, i. e. without overmodulation.
The quality of the generated output voltages depends on the ratio between output frequency and current controller frequency fI-R
( fI-R = 1/cycle time current controller).
The maximum output frequency fmax , generated with high quality, is calculated as follows:
f I-R
f max = -------- , typical K Pf 18
K pf
Furthermore the controller sets an upper limit for the output frequency of 599 Hz (please contact the responsible Baumüller sales de-
partment, keyword: export restriction).
The range of the output frequency is defined as follows:
PWM frequency Current controller cycle time Range of the output frequency
2 kHz 250 µs 0 - 225 Hz
4 kHz/8 kHz 125 µs 0 - 450 Hz
The controller allows the device to generate output voltages with frequencies between fmax and 599 Hz. However the quality of this volt-
ages cannot be guaranteed.
Typical the devices are marked with the max output frequency at 4 kHz switching frequency: 0 ... 450 kHz.
11)
See ZExplanation version code– on page 130 at generation 2.
12)
At maximum 4 A, if UL508 C is complied with.
13)
The continuously permitted output current must be reduced complying with ZOutput frequency dependent continuous current derating
BM4XXX– on page 112, if the statical output frequency is lower than 15 Hz and the frequency remains between 0 and 15 Hz for over
5 seconds.
1)
All rated values refer to a DC link voltage of 540 V, a control voltage of 24 V and an environmental temperature of 40 °C.
2)
Using the power choke listed in ZPower chokes– on page 300 at a power supply with UK,power supply = 0.4 %.
3) The output voltage is a pulsed DC voltage. The operating range refers to the RMS of the fundamental wave.
U DC
U AC = 3 0 V to 3 ----------
- – 10 V without overmodulation of the PWM.
2
Derating of the output current BM4444 Derating of the output current BM4444
Output current [%]
Derating of the output current BM4445 Derating of the output current BM4446
Output current [%]
7)
The input current must be reduced between 40 °C and 55 °C. See correction factors at changed operating conditions ZEnvironmental
temperature– on page 57.
8)
The peak output current is supplied for the maximum peak current period for the motor at the first acceleration (cold power unit). The in
fact possible overload time is dependent on the preload of the device and on the heat sink temperature, it is determined by the overload
monitoring of the device.
9) Peak current can be supplied at a heat sink temperature of <75 °C (BM4X43) and <80 °C (BM4X44), only.
If these heat sink temperature thresholds are exceeded, the output current is automatically derated to the rated current.
10)
For cooling versions S and A, only.
11) The sum of the transmitted mean effective power via the DC link terminals and the mean effective power at the motor terminals, may
not exceed the specified value continuously.
12)
Available at device with type code BM44XX-XX-XXXXX-03 with controller version code 4-yyy-xxx, whereat yyy > 024 and the controller
firmware version must be 3.09 or higher. Switching off a device at a motor short circuit may damage the device.
PWM frequency Current controller cycle time Range of the output frequency
2 kHz 250 µs 0 - 225 Hz
4 kHz/8 kHz 125 µs 0 - 450 Hz
The controller allows the device to generate output voltages with frequencies between fmax and 599 Hz. However the quality of this volt-
ages cannot be guaranteed.
Typical the devices are marked with the max output frequency at 4 kHz switching frequency: 0 ... 450 kHz.
14)
At a hardware status of < 4006 or if UL508C is complied with: at maximum 4 A
15)
The continuously permitted output current must be reduced complying with ZOutput frequency dependent continuous current derating
BM4XXX– on page 112, if the statical output frequency is lower than 15 Hz and the frequency remains between 0 and 15 Hz for over
5 seconds.
16)
The motor connection of the device provides a limited short-circuit protection.
7)
The input current must be reduced between 40 °C and 55 °C. See correction factors at changed operating conditions ZEnvironmental
temperature– on page 57.
8) The peak output current is supplied for the maximum peak current period for the motor at the first acceleration (cold power unit). The in
fact possible overload time is dependent on the preload of the device and on the heat sink temperature, it is determined by the overload
monitoring of the device.
9)
For cooling versions S and A.
10) UL508C is complied with: max. 4.0 A.
11)
See ZMotor requirements– on page 54.
12)
The range of the output frequency is based on a stationary operation in the linear range of the PWM, i. e. without overmodulation.
The quality of the generated output voltages depends on the ratio between output frequency and current controller frequency fI-R
( fI-R = 1/cycle time current controller).
The maximum output frequency fmax , generated with high quality, is calculated as follows:
f I-R
f max = -------- , typical K Pf 18
K pf
Furthermore the controller sets an upper limit for the output frequency of 599 Hz (please contact the responsible Baumüller sales de-
partment, keyword: export restriction).
The range of the output frequency is defined as follows:
PWM frequency Current controller cycle time Range of the output frequency
2 kHz 250 µs 0 - 225 Hz
4 kHz/8 kHz 125 µs 0 - 450 Hz
The controller allows the device to generate output voltages with frequencies between fmax and 599 Hz. However the quality of this volt-
ages cannot be guaranteed.
Typical the devices are marked with the max output frequency at 4 kHz switching frequency: 0 ... 450 kHz.
13)
With an output frequency lower than 0.5 Hz, the output current may be 80 % at maximum of the rated output current.
14)
The continuously permitted output current must be reduced complying with ZOutput frequency dependent continuous current derating
BM4XXX– on page 112, if the statical output frequency is lower than 15 Hz and the frequency remains between 0 and 15 Hz for over
5 seconds.
1)
All rated values refer to a DC link voltage of 540 V, a control voltage of 24 V and an environmental temperature of 40 °C.
2)
Using the power choke listed in ZPower chokes– on page 300 at a power supply with UK,power supply = 0.4 %.
3) The output voltage is a pulsed DC voltage. The operating range refers to the RMS of the fundamental wave.
U DC
U AC = 3 0 V to 3 ----------
- – 10 V without overmodulation of the PWM.
2
7)
The input current must be reduced between 40 °C and 55 °C. See correction factors at changed operating conditions ZEnvironmental
temperature– on page 57.
8)
The peak output current is supplied for the maximum peak current period for the motor at the first acceleration (cold power unit). The in
fact possible overload time is dependent on the preload of the device and on the heat sink temperature, it is determined by the overload
monitoring of the device.
9)
For cooling versions S and A, only.
10)
If UL508C is complied with: max. 4.0 A.
11) See ZMotor requirements– on page 54.
PWM frequency Current controller cycle time Range of the output frequency
2 kHz 250 µs 0 - 225 Hz
4 kHz/8 kHz 125 µs 0 - 450 Hz
The controller allows the device to generate output voltages with frequencies between fmax and 599 Hz. However the quality of this volt-
ages cannot be guaranteed.
Typical the devices are marked with the max output frequency at 4 kHz switching frequency: 0 ... 450 kHz.
13)
Using internal brake resistors, the continuous brake resistor power is 5 kW.
14)
The controller firmware version must be 3.10 or higher.
15) The
continuously permitted output current must be reduced complying with ZOutput frequency dependent continuous current derating
BM4XXX– on page 112, if the statical output frequency is lower than 15 Hz and the frequency remains between 0 and 15 Hz for over
5 seconds.
16) The
motor connection of the device provides a limited short-circuit protection.
4)
Switching frequency of the inverter (adjustable).
5)
RMS at an environmental temperature of 40 °C.
7)
The input current must be reduced between 40 °C and 55 °C. See correction factors at changed operating conditions ZEnvironmental
temperature– on page 57
8)
Two temperature values may occur (cooling air, which flows through the internal space of the device / cooling air, which flows through
the heat sink). Enter the higher value.
Example: Rated output current = 150 A environmental temperature = 46 °C
I o = 150A 1
– 46°C - 40°C
-------------------------------- 0 03 = 150A 0 82
The output current must be reduced to: 123 A
°C
9)
The peak output current is supplied for the maximum peak current period for the motor at the first acceleration (cold power unit). The in
fact possible overload time is dependent on the preload of the device and on the heat sink temperature, it is determined by the overload
monitoring of the device.
10) The sum of
the instantaneously drawn power via the DC link terminals and the input power (motor output / motor efficiency) of the motor
at the same time may not exceed the maximum power input of 250 kW and 315 kW.
11) If
UL508C is complied with: max. 4.0 A.
12)
See ZMotor requirements– on page 54.
13)
If UL508C is complied with:
The permitted typical motor output is limited to 295 kW at a maximum. The device BM4473 belongs to the category < 400 HP, < 298
kW ratings complying with table 45.1 of UL508C. Therefore, the short-circuit test using 18k A can be executed. Baumüller does not offer
devices in the class 600 HP, 447 kW with 30 kA short-circuit current in accordance with UL508C.
14) The range of the output frequency is based on a stationary operation in the linear range of the PWM, i. e. without overmodulation.
The quality of the generated output voltages depends on the ratio between output frequency and current controller frequency fI-R
( fI-R = 1/cycle time current controller).
The maximum output frequency fmax , generated with high quality, is calculated as follows:
f I-R
f max = -------- , typical K Pf 18
K pf
Furthermore the controller sets an upper limit for the output frequency of 599 Hz (please contact the responsible Baumüller sales de-
partment, keyword: export restriction).
The range of the output frequency is defined as follows:
PWM frequency Current controller cycle time Range of the output frequency
2 kHz 250 µs 0 - 225 Hz
4 kHz/8 kHz 125 µs 0 - 450 Hz
The controller allows the device to generate output voltages with frequencies between fmax and 599 Hz. However the quality of this volt-
ages cannot be guaranteed.
Typical the devices are marked with the max output frequency at 4 kHz switching frequency: 0 ... 450 kHz.
15) The continuously permitted output current must be reduced complying with ZOutput frequency dependent continuous current derating
BM4XXX– on page 112, if the statical output frequency is lower than 15 Hz and the frequency remains between 0 and 15 Hz for over
5 seconds.
Acceleration units are developed for a cycle with 1.25 s peak current at a total cycle of
5 s, see ZFigure 29– on page 59. The units are not developed for using at standstill or
output frequencies lower than 10 Hz with peak current. For this units the ZOutput fre-
quency dependent continuous current derating BM4XXX– on page 112 and the ZOutput
frequency dependent maximum current derating BM46XX– on page 113.
NOTE!
The acceleration units require a controller FW version 3.10 or higher!
BM4632
Rated input power 1)2) 36,7 kVA
Rated input current 1)2) (I
eff) 53,0 A
Distortion factor of the input current 1)2) (THDI) 57 %
Input current, max. 2) (I
eff) 128 A
DC link rated voltage 1) 540 VDC
DC link capacitance (internal) 3000 F
DC link capacitance (external), permitted see ZPage 227–
DC link discharging time (internal DC link capacitance) 140 s
Waiting time between two power up processes no
1)3)
Output voltage (UAC) 3 x 0 V to 3 x 370 V
Output frequency at 4 kHz 10) 0 Hz to 450 Hz
1)5)6)7)12) 4)
Rated output current (IAC) at 4 kHz 60 A
Rated output current 1)5)6)7)12) (IAC) at 8 kHz 4) 48 A
1)5)6)8)12) 4)
Output peak current (IAC) at 4 kHz 120 A
Output peak current 1)5)6)8)12) (IAC) at 8 kHz 4) 96 A
8)
Max. peak current period 1,25 s
Power input DC link terminals 9) max. 10,0 kW
Brake resistor current, permitted (Î) max. 70,0 A
Brake resistor external 11
Brake resistor threshold (Û) 780 V
Brake resistor peak power 56 kW
Permitted continuous power brake resistor external 10 kW
Power loss referring to power input 840 W
Power input referring to control voltage max. 88 W
Current of integrated brake control max. 8 A 11)
Cooling air requirement device internal space 60 m3/h
Requirements to water cooling see ZPage 61–
1)
All rated values refer to a DC link voltage of 540 V, a control voltage of 24 V and an environmental temperature of 40 °C.
2)
Using the power choke listed in ZPower chokes– on page 300 at a power supply with UK,power supply = 0.4 %.
3) The output voltage is a pulsed DC voltage. The operating range refers to the RMS of the fundamental wave.
U DC
U AC = 3 0 V to 3 ----------
- – 10 V without overmodulation of the PWM.
2
7)
The input current must be reduced between 40 °C and 55 °C. See correction factors at changed operating conditions ZEnvironmental
temperature– on page 57.
8)
The peak output current is supplied for the maximum peak current period for the motor at the first acceleration (cold power unit). The in
fact possible overload time is dependent on the preload of the device and on the heat sink temperature, it is determined by the overload
monitoring of the device.
9) The sum of the mean effective power, which is transmitted via the DC link terminals and the mean effective power at the motor terminals,
may not exceed the specified value continuously.
10)
The range of the output frequency is based on a stationary operation in the linear range of the PWM, i. e. without overmodulation.
The quality of the generated output voltages depends on the ratio between output frequency and current controller frequency fI-R
( fI-R = 1/cycle time current controller).
The maximum output frequency fmax , generated with high quality, is calculated as follows:
f I-R
f max = -------- , typical K Pf 18
K pf
Furthermore the controller sets an upper limit for the output frequency of 599 Hz (please contact the responsible Baumüller sales de-
partment, keyword: export restriction).
The range of the output frequency is defined as follows:
PWM frequency Current controller cycle time Range of the output frequency
2 kHz 250 µs 0 - 225 Hz
4 kHz/8 kHz 125 µs 0 - 450 Hz
The controller allows the device to generate output voltages with frequencies between fmax and 599 Hz. However the quality of this volt-
ages cannot be guaranteed.
Typical the devices are marked with the max output frequency at 4 kHz switching frequency: 0 ... 450 kHz.
11) At maximum 4 A, if UL508 C is complied with.
12)
The continuously permitted output current must be reduced complying with ZOutput frequency dependent maximum current derating
BM46XX– on page 113, if the statical output frequency is lower than 15 Hz and the frequency remains between 0 and 15 Hz for over 5
seconds.
4)
Switching frequency of the inverter (adjustable).
5)
RMS at an environmental temperature of 40 °C.
6) At rated power supply voltage the unit supplies rated / maximum output currents. With input voltages above the rated power supply
voltage the output currents must be reduced at constant output power.
7)
The input current must be reduced between 40 °C and 55 °C. See correction factors at changed operating conditions ZEnvironmental
temperature– on page 57.
8)
The peak output current is supplied for the maximum peak current period for the motor at the first acceleration (cold power unit). The in
fact possible overload time is dependent on the preload of the device and on the heat sink temperature, it is determined by the overload
monitoring of the device.
9)
For cooling versions S and A, only.
10)
The sum of the mean effective power, which is transmitted via the DC link terminals and the mean effective power at the motor terminals,
may not exceed the specified value continuously.
11)
The range of the output frequency is based on a stationary operation in the linear range of the PWM, i. e. without overmodulation.
The quality of the generated output voltages depends on the ratio between output frequency and current controller frequency fI-R
( fI-R = 1/cycle time current controller).
The maximum output frequency fmax , generated with high quality, is calculated as follows:
f I-R
f max = -------- , typical K Pf 18
K pf
Furthermore the controller sets an upper limit for the output frequency of 599 Hz (please contact the responsible Baumüller sales de-
partment, keyword: export restriction).
The range of the output frequency is defined as follows:
PWM frequency Current controller cycle time Range of the output frequency
2 kHz 250 µs 0 - 225 Hz
4 kHz/8 kHz 125 µs 0 - 450 Hz
The controller allows the device to generate output voltages with frequencies between fmax and 599 Hz. However the quality of this volt-
ages cannot be guaranteed.
Typical the devices are marked with the max output frequency at 4 kHz switching frequency: 0 ... 450 kHz.
12) The continuously permitted output current must be reduced complying with ZOutput frequency dependent maximum current derating
BM46XX– on page 113, if the statical output frequency is lower than 15 Hz and the frequency remains between 0 and 15 Hz for over 5
seconds.
13)
At maximum 4 A, if UL508 C is complied with.
1)
All rated values refer to a DC link voltage of 540 V, a control voltage of 24 V and an environmental temperature of 40 °C.
2)
Using the power choke listed in ZPower chokes– on page 300 at a power supply with UK,power supply = 0.4 %.
3)
The output voltage is a pulsed DC voltage. The operating range refers to the RMS of the fundamental wave.
U DC
U AC = 3 0 V to 3 ----------
- – 10 V without overmodulation of the PWM.
2
4)
Switching frequency of the inverter (adjustable).
5) RMS at an environmental temperature of 40 °C.
6)
At rated power supply voltage the unit supplies rated / maximum output currents. With input voltages above the rated power supply
voltage the output currents must be reduced at constant output power.
Derating of output current BM465X
Output current [%]
7)
The input current must be reduced between 40 °C and 55 °C. See correction factors at changed operating conditions ZEnvironmental
temperature– on page 57.
8) The peak output current is supplied for the maximum peak current period for the motor at the first acceleration (cold power unit). The in
fact possible overload time is dependent on the preload of the device and on the heat sink temperature, it is determined by the overload
monitoring of the device.
9)
For cooling versions S and A, only.
10)
At maximum 4 A, if UL508 C is complied with.
11) See ZMotor requirements– on page 54.
12)
The range of the output frequency is based on a stationary operation in the linear range of the PWM, i. e. without overmodulation.
The quality of the generated output voltages depends on the ratio between output frequency and current controller frequency fI-R
( fI-R = 1/cycle time current controller).
The maximum output frequency fmax , generated with high quality, is calculated as follows:
f I-R
f max = -------- , typical K Pf 18
K pf
Furthermore the controller sets an upper limit for the output frequency of 599 Hz (please contact the responsible Baumüller sales de-
partment, keyword: export restriction).
The range of the output frequency is defined as follows:
PWM frequency Current controller cycle time Range of the output frequency
2 kHz 250 µs 0 - 225 Hz
4 kHz/8 kHz 125 µs 0 - 450 Hz
The controller allows the device to generate output voltages with frequencies between fmax and 599 Hz. However the quality of this volt-
ages cannot be guaranteed.
Typical the devices are marked with the max output frequency at 4 kHz switching frequency: 0 ... 450 kHz.
13)
The continuously permitted output current must be reduced complying with ZOutput frequency dependent maximum current derating
BM46XX– on page 113, if the statical output frequency is lower than 15 Hz and the frequency remains between 0 and 15 Hz for over 5
seconds.
14)
The device is available in cooling type „Z“ and „F“ with standard size (BM46XX-XXX-0XXXX) or short size (BM46XX-XXX-3XXXX).
4)
Switching frequency of the inverter (adjustable).
5) RMS at an environmental temperature of 40 °C.
6)
At rated power supply voltage the unit supplies rated / maximum output currents. With input voltages above the rated power supply
voltage the output currents must be reduced at constant output power.
Derating of output current BM466X
Output current [%]
7)
The input current must be reduced between 40 °C and 55 °C. See correction factors at changed operating conditions ZEnvironmental
temperature– on page 57.
8)
The peak output current is supplied for the maximum peak current period for the motor at the first acceleration (cold power unit). The in
fact possible overload time is dependent on the preload of the device and on the heat sink temperature, it is determined by the overload
monitoring of the device.
9)
For cooling versions S and A, only.
10) At
maximum 4 A, if UL508 C is complied with.
11) See
ZMotor requirements– on page 54.
12) The
range of the output frequency is based on a stationary operation in the linear range of the PWM, i. e. without overmodulation.
The quality of the generated output voltages depends on the ratio between output frequency and current controller frequency fI-R
( fI-R = 1/cycle time current controller).
The maximum output frequency fmax , generated with high quality, is calculated as follows:
f I-R
f max = -------- , typical K Pf 18
K pf
Furthermore the controller sets an upper limit for the output frequency of 599 Hz (please contact the responsible Baumüller sales de-
partment, keyword: export restriction).
The range of the output frequency is defined as follows:
PWM frequency Current controller cycle time Range of the output frequency
2 kHz 250 µs 0 - 225 Hz
4 kHz/8 kHz 125 µs 0 - 450 Hz
The controller allows the device to generate output voltages with frequencies between fmax and 599 Hz. However the quality of this volt-
ages cannot be guaranteed.
Typical the devices are marked with the max output frequency at 4 kHz switching frequency: 0 ... 450 kHz.
13) The continuously permitted output current must be reduced complying with ZOutput frequency dependent maximum current derating
BM46XX– on page 113, if the statical output frequency is lower than 15 Hz and the frequency remains between 0 and 15 Hz for over 5
seconds.
14)
The device is available in cooling type „Z“ and „F“ with standard size (BM46XX-XXX-0XXXX) or short size (BM46XX-XXX-3XXXX).
15) The motor connection of the device provides a limited short-circuit protection.
1)
All rated values refer to a DC link voltage of 540 V, a control voltage of 24 V and an environmental temperature of 40 °C.
2)
Using the power choke listed in ZPower chokes– on page 300 at a power supply with UK,power supply = 0.4 %.
3)
The output voltage is a pulsed DC voltage. The operating range refers to the RMS of the fundamental wave.
U DC
U AC = 3 0 V to 3 ----------
- – 10 V without overmodulation of the PWM.
2
4)
Switching frequency of the inverter (adjustable).
5)
RMS at an environmental temperature of 40 °C.
6) At rated power supply voltage the unit supplies rated / maximum output currents. With input voltages above the rated power supply
voltage the output currents must be reduced at constant output power.
Figure 44: Derating the output current BM47XX continuous current units
7) The input current must be reduced between 40 °C and 55 °C. See correction factors at changed operating conditions ZEnvironmental
temperature– on page 57.
8)
The peak output current is supplied for the maximum peak current period for the motor at the first acceleration (cold power unit). The in
fact possible overload time is dependent on the preload of the device and on the heat sink temperature, it is determined by the overload
monitoring of the device.
9)
For cooling versions S and A, only.
10)
At maximum 4 A, if UL508 C is complied with.
11) See ZMotor requirements– on page 54.
PWM frequency Current controller cycle time Range of the output frequency
2 kHz 250 µs 0 - 225 Hz
4 kHz/8 kHz 125 µs 0 - 450 Hz
The controller allows the device to generate output voltages with frequencies between fmax and 599 Hz. However the quality of this volt-
ages cannot be guaranteed.
Typical the devices are marked with the max output frequency at 4 kHz switching frequency: 0 ... 450 kHz.
13)
The continuously permitted output current must be reduced complying with ZOutput frequency dependent continuous current derating
BM4XXX– on page 112, if the statical output frequency is lower than 15 Hz and the frequency remains between 0 and 15 Hz for over
5 seconds.
14) The
device is available in cooling type „Z“ and „F“ with standard size (BM47XX-XXX-0XXXX) or short size (BM47XX-XXX-3XXXX).
1) All rated values refer to a DC link voltage of 540 VDC and a control voltage of 24 V.
2)
The output voltage is a pulsed DC voltage. The operating range refers to the RMS of the fundamental wave.
U DC
U AC = 3 0 V to 3 ----------
- – 10 V without overmodulation of the PWM.
2
3)
Switching frequency of the inverter (adjustable).
4) RMS at an environmental temperature of 40 °C.
5) The input current must be reduced between 40 °C and 55 °C. See correction factors at changed operating conditions ZEnvironmental
temperature– on page 57.
7)
The peak output current is supplied for the maximum peak current period for the motor at the first acceleration (cold power unit). The in
fact possible overload time is dependent on the preload of the device and on the heat sink temperature, it is determined by the overload
monitoring of the device.
8)
The range of the output frequency is based on a stationary operation in the linear range of the PWM, i. e. without overmodulation.
The quality of the generated output voltages depends on the ratio between output frequency and current controller frequency fI-R
( fI-R = 1/cycle time current controller).
The maximum output frequency fmax , generated with high quality, is calculated as follows:
f I-R
f max = -------- , typical K Pf 18
K pf
Furthermore the controller sets an upper limit for the output frequency of 599 Hz (please contact the responsible Baumüller sales de-
partment, keyword: export restriction).
The range of the output frequency is defined as follows:
PWM frequency Current controller cycle time Range of the output frequency
2 kHz 250 µs 0 - 225 Hz
4 kHz/8 kHz 125 µs 0 - 450 Hz
The controller allows the device to generate output voltages with frequencies between fmax and 599 Hz. However the quality of this volt-
ages cannot be guaranteed.
Typical the devices are marked with the max output frequency at 4 kHz switching frequency: 0 ... 450 kHz.
9)
The continuously permitted output current must be reduced complying with ZOutput frequency dependent continuous current derating
BM4XXX– on page 112, if the statical output frequency is lower than 15 Hz and the frequency remains between 0 and 15 Hz for over
5 seconds.
1)
All rated values refer to a DC link voltage of 540 VDC and a control voltage of 24 V.
2)
The output voltage is a pulsed DC voltage. The operating range refers to the RMS of the fundamental wave.
U DC
U AC = 3 0 V to 3 ----------
- – 10 V without overmodulation of the PWM.
2
7)
The peak output current is supplied for the maximum peak current period for the motor at the first acceleration (cold power unit). The in
fact possible overload time is dependent on the preload of the device and on the heat sink temperature, it is determined by the overload
monitoring of the device.
8)
The range of the output frequency is based on a stationary operation in the linear range of the PWM, i. e. without overmodulation.
The quality of the generated output voltages depends on the ratio between output frequency and current controller frequency fI-R
( fI-R = 1/cycle time current controller).
The maximum output frequency fmax , generated with high quality, is calculated as follows:
f I-R
f max = -------- , typical K Pf 18
K pf
Furthermore the controller sets an upper limit for the output frequency of 599 Hz (please contact the responsible Baumüller sales de-
partment, keyword: export restriction).
The range of the output frequency is defined as follows:
PWM frequency Current controller cycle time Range of the output frequency
2 kHz 250 µs 0 - 225 Hz
4 kHz/8 kHz 125 µs 0 - 450 Hz
The controller allows the device to generate output voltages with frequencies between fmax and 599 Hz. However the quality of this volt-
ages cannot be guaranteed.
Typical the devices are marked with the max output frequency at 4 kHz switching frequency: 0 ... 450 kHz.
9)
The continuously permitted output current must be reduced complying with ZOutput frequency dependent continuous current derating
BM4XXX– on page 112, if the statical output frequency is lower than 15 Hz and the frequency remains between 0 and 15 Hz for over
5 seconds.
1)
All rated values refer to a DC link voltage of 540 VDC and a control voltage of 24 V.
2)
The output voltage is a pulsed DC voltage. The operating range refers to the RMS of the fundamental wave.
U DC
U AC = 3 0 V to 3 ----------
- – 10 V without overmodulation of the PWM.
2
PWM frequency Current controller cycle time Range of the output frequency
2 kHz 250 µs 0 - 225 Hz
4 kHz/8 kHz 125 µs 0 - 450 Hz
The controller allows the device to generate output voltages with frequencies between fmax and 599 Hz. However the quality of this volt-
ages cannot be guaranteed.
Typical the devices are marked with the max output frequency at 4 kHz switching frequency: 0 ... 450 kHz.
11) At a hardware status of < 4006 or if UL508C is complied with: at maximum 4 A
12)
The continuously permitted output current must be reduced complying with ZOutput frequency dependent continuous current derating
BM4XXX– on page 112, if the statical output frequency is lower than 15 Hz and the frequency remains between 0 and 15 Hz for over
5 seconds.
1)
All rated values refer to a DC link voltage of 540 VDC and a control voltage of 24 V.
2)
The output voltage is a pulsed DC voltage. The operating range refers to the RMS of the fundamental wave.
U DC
U AC = 3 0 V to 3 ----------
- – 10 V without overmodulation of the PWM.
2
6)
The input current must be reduced between 40 °C and 55 °C. See correction factors at changed operating conditions ZEnvironmental
temperature– on page 57.
7)
The peak output current is supplied for the maximum peak current period for the motor at the first acceleration (cold power unit). The in
fact possible overload time is dependent on the preload of the device and on the heat sink temperature, it is determined by the overload
monitoring of the device.
8)
For cooling versions S and A, only.
9)
The range of the output frequency is based on a stationary operation in the linear range of the PWM, i. e. without overmodulation.
The quality of the generated output voltages depends on the ratio between output frequency and current controller frequency fI-R
( fI-R = 1/cycle time current controller).
The maximum output frequency fmax , generated with high quality, is calculated as follows:
f I-R
f max = -------- , typical K Pf 18
K pf
Furthermore the controller sets an upper limit for the output frequency of 599 Hz (please contact the responsible Baumüller sales de-
partment, keyword: export restriction).
The range of the output frequency is defined as follows:
PWM frequency Current controller cycle time Range of the output frequency
2 kHz 250 µs 0 - 225 Hz
4 kHz/8 kHz 125 µs 0 - 450 Hz
The controller allows the device to generate output voltages with frequencies between fmax and 599 Hz. However the quality of this volt-
ages cannot be guaranteed.
Typical the devices are marked with the max output frequency at 4 kHz switching frequency: 0 ... 450 kHz.
10) The continuously permitted output current must be reduced complying with ZOutput frequency dependent continuous current derating
BM4XXX– on page 112, if the statical output frequency is lower than 15 Hz and the frequency remains between 0 and 15 Hz for over
5 seconds.
1)
All rated values refer to a DC link voltage of 540 VDC and a control voltage of 24 V.
2)
The output voltage is a pulsed DC voltage. The operating range refers to the RMS of the fundamental wave.
U DC
U AC = 3 0 V to 3 ----------
- – 10 V without overmodulation of the PWM.
2
6) The input current must be reduced between 40 °C and 55 °C. See correction factors at changed operating conditions ZEnvironmental
temperature– on page 57.
7)
The peak output current is supplied for the maximum peak current period for the motor at the first acceleration (cold power unit). The in
fact possible overload time is dependent on the preload of the device and on the heat sink temperature, it is determined by the overload
monitoring of the device.
8)
For cooling versions S and A, only.
9)
If UL508C is complied with: max. 4.0 A.
10)
The range of the output frequency is based on a stationary operation in the linear range of the PWM, i. e. without overmodulation.
The quality of the generated output voltages depends on the ratio between output frequency and current controller frequency fI-R
( fI-R = 1/cycle time current controller).
The maximum output frequency fmax , generated with high quality, is calculated as follows:
f I-R
f max = -------- , typical K Pf 18
K pf
Furthermore the controller sets an upper limit for the output frequency of 599 Hz (please contact the responsible Baumüller sales de-
partment, keyword: export restriction).
The range of the output frequency is defined as follows:
PWM frequency Current controller cycle time Range of the output frequency
2 kHz 250 µs 0 - 225 Hz
4 kHz/8 kHz 125 µs 0 - 450 Hz
The controller allows the device to generate output voltages with frequencies between fmax and 599 Hz. However the quality of this volt-
ages cannot be guaranteed.
Typical the devices are marked with the max output frequency at 4 kHz switching frequency: 0 ... 450 kHz.
11)
The continuously permitted output current must be reduced complying with ZOutput frequency dependent continuous current derating
BM4XXX– on page 112, if the statical output frequency is lower than 15 Hz and the frequency remains between 0 and 15 Hz for over
5 seconds.
Technical data
brake resistors
1) The total depth of the device in the cooling version F increases by the specified value (see ZDimensions–
from page 31). At devices of the cooling version Z the dimensions of the device do not change.
2) The DC link voltage must not exceed 800 V.
Calculation of the permitted length of the braking procedure see ZCalculations– from page 107.
3) The mentioned continuous power is reached if the water flow amount is at least 10 l/min. The inlet tempera-
ture may not be greater than 45 °C.
The brake resistor output power diminishes from the rated value to 0, if the inlet temperature increases from
45°C to 60 °C.
NOTE!
The water-cooled brake resistors offer the optimum of power loss, which can be dis-
sipated, at a minimum unit volume. However, 10 % of the brake resistor power is not
dissipated via the cooling water. It is emitted to the environmental air.
At operation with rated power the brake resistors reach temperatures of 200 °C on
the rear side.
on on
Figure 50: Conversion brake power time area in triangular time area
1 1
A = t 1 P S + --- t 2 P S = --- t on P S
2 2
brake
cycle
Figure 51: Braking cycle
PDmax Maximum continuous brake power, see ZTechnical data brake resistors–
on page 106
toff_1 to toff_n Off time periods, between the brake time periods
C1, C2, C3 Constants, see ZTechnical data brake resistors– on page 106
Please contact
The internal brake resistor
Baumüller PS_n PSmax no
cannot be used for this
if Ps_n PSmax and ton_n 1 s application
ton_1 ... ton_n 1 s
yes
n n
T cycle = t on_n + t off_n
1 1
yes
TM = PD C1
Start value T0 = PD C1
T 1 = T 0 + C 2 P s_1 t on_1
C 3 t off_1
T2 = T1 – TM e + T M + C 2 P s_2 t on_2
C 3 t off_n-1
Tn = Tn – 1 – TM e + T M + C 2 P s_n t on_n
C 3 t off_n
Tn + 1 = Tn – TM e + TM
T = Tn+1 - T0
End
PSmax 3) PDmax 2) 3) C1 C2 C3
PS ton toff
PS_1 = 20 kW < 61 kW ton_1 = 0.15 s < 1 s toff_1 = 1.11 s
PS_2 = 13 kW < 61 kW ton_2 = 0.15 s < 1 s toff_2 = 1.79 s
PS_3 = 20 kW < 61 kW ton_3 = 0.15 s < 1 s toff_3 = 6.85 s
PS_4 = 23 kW < 61 kW ton_4 = 0.15 s < 1 s toff_4 = 1.85 s
PS_5 = 24 kW < 61 kW ton_5 = 0.15 s < 1 s toff_5 = 5.65 s
n n
Tcycle = t on _n + t off _n = 5 0.15s + 1.11s + 1.79s + 6.85s + 1.85s + 5.65s = 18 s
1 1
P s_1 t ein_1 + ......+ P s_n t off _n 1 20kW + 13kW + 20kW + 23kW + 24kW 0 15s
PD =D = 1--- ------------------------------------------------------------------------------------------------------
- = --- -----------------------------------------------------------------------------------------------------------------------------------
2 T cycle 2 18s
= 0.417 kW = 417 W < PDmax < 1.5 kW internal brake resistor can be used
C 3 t off _1
T2 = = T1 – TM e + T M + C 2 P s_2 t on _2
–1
· – 0,9169s 1,11s
= = 131 ,55K – 83,4K e + 83,4K + 0,01605K/Ws 13000W 0,15s = 132.1 K
–1
· – 0,9169s 1,79s
= = 132 ,06K – 83,4K e + 83,4K + 0,01605K/Ws 20000W 0,15s = 140.98 K
C 3 t off _3
T4 = T4 = T3 – TM e + T M + C 2 P s_4 t on _4
–1
· – 0,9169s 6,85s
= = 140 ,92K – 83,4K e + 83,4K + 0,01605K/Ws 23000W 0,15s = 138.88 K
C 3 t off _4
T5 = = T 4 – T M e + T M + C 2 P s_5 t on _5
–1
· – 0,9169s 1 ,85s
= = 138 ,81K – 83,4K e + 83,4K + 0,01605K/Ws 24000W 0,15s = 151.35 K
C 3 t off _5 –1
· – 0,9169s 5,65 s
T6 = = T 5 – T M e + T M = 151 ,29K – 83,4K e + 83,4K
–1
· – 0,9169s 5 ,65s
= = 151 ,29K – 83,4K e + 83,4K = 83.78 K
T1 to T5 400 K
The specified rated currents of all Baumüller devices are permitted continuously. The
electrical output frequency in S1 operation is permitted from 15 Hz onwards. The contin-
uously permitted output current must be reduced complying with the following character-
istic curve, if the statical output frequency is lower than 15 Hz and the frequency remains
between 0 and 15 Hz for more than 5 seconds.
Examples:
n Speed control operations without positioning.
n Standstill operations, if current is required to keep a torque / a force.
n At operations, if it is likely that the mechanics block, for example when starting cold ex-
truders.
The following operations are not affected:
n Typical positioning operations.
n Operating motors, which use an operating brake at standstill.
n Operations, where the higher-level control has a standstill and block monitoring.
The use of Irated is permitted, as long as the derating range is passed through quickly
enough. The frequency change must be 15 Hz/s.
Derating of the motor-sided output current I of the inverter against the rated output current
Irated is dependent on the static output frequency f of the inverter.
I
Irated
4000_0753_rev01_int
current
75
0 10 Hz
Output frequency
Automatical reduction of the
PWM frequency to 4/2 kHz
Figure 53: Reduction BM46XX max. current and PWM frequency at output frequencies < 10 Hz
The maximum current of the drive must be limited more severely at output frequencies
below 10 Hz if no PWM frequency reduction is possible.
5000_0326_rev01_int
current P6.25
50
Hz
0 10 Hz
Output frequency
Figure 54: Reduction BM46XX only max. current at output frequencies < 10 Hz
Standard devices
Ixt types PT1 model Integration
model
Device identification
Size 1 BM4412, BM4413,
BM441X BM4414
Size 2 BM4420, BM4421,
BM442X BM4422, BM4423,
BM4424, BM4425,
BM4426
Size 3 BM4432, BM4433,
BM443X BM4434, BM4435
Size 4 BM4442, BM4443, BM4446 *)
BM444X BM4444, BM4445
Size 5 BM4452, BM4453,
BM445X BM4454
Size 6 BM4462, BM4463, BM4464
BM446X BM4465, BM4466
Size 7 BM4473 BM4472
BM447X
*)
Temperature model additionally to the integration model.
Special devices
Ixt types PT1 model Integration
model
Device identification
BM46XX BM46XX
BM47XX no Ixt monitoring is executed
Design cover
(only standard controller)
Standard controller
BM4XXX-XXX-XX1XX
BM4XXX-XXX-XX2XX
BM4XXX-XXX-XX3XX
ES controller
BM4XXX-XXX-XX4XX
BM4XXX-XXX-XX5XX
The rated current of the devices reach from 2.5 A to 720 A. The devices differ in size, pow-
er, equipment (hard- and software) and cooling types, for further information refer to
ZType code– from page 126.
4.1 Functioning
Basic unit The present alternating voltage at the three-phase system is converted into direct voltage
by the input sided rectifier. The DC link capacitors smooth this DC link direct voltage. The
output sided inverter generates a three-phase system from the direct voltage with variable
frequency and voltage for the supply of the connected motor.
Additionally you can draw d. c. from the device via the DC link connections.
Power module The output sided inverter generates a three-phase system via the DC link connection
from the direct voltage with variable frequency and voltage for the supply of the connected
motor.
BM4400 BM4400 are universal converters, for achieving electrical drives in industrial applications.
BM4400 offers the largest configuration possibilities as well as the most available options.
BM4600 BM4600 (acceleration units) are especially developed servo drives derived from BM4400
for acceleration applications. Characteristic for these devices is, that the peak current is
twice as large as the rated current, even at large output currents. The devices were de-
veloped for a cycle, which could provide the peak current for 1.25 s at a whole cycle du-
ration of 5 s according to ZFigure 29– on page 59.
This units are not developed for peak current using at standstill or output frequencies low-
er than 10 Hz. For this units the ZOutput frequency dependent maximum current derating
BM46XX– from page 113 is valid.
BM4700 BM4700 (continuous current units) are servo converters especially developed for main
drives, derived from BM4400. The devices were developed to maximize the available rat-
ed current by water cooling. For this reason these devices are only available with water
cooling (cooling type -F and -Z) and with none peak current (only BM5773 with low peak
current).
Controller unit The power unit is controlled by the controller unit. You can operate the controller part ei-
ther with the operating software WinBASS II (up to FW 3.09) or ProDrive (from FW 3.07)
or via a PLC or via a field bus and PLC.
NOTE!
Only the operation with ProDrive is described. If the software is not available, please
contact Baumüller Nürnberg GmbH or visit our Website www.baumueller.de for
download.
NOTE!
Only the controller part without function/option modules is described in this Instruc-
tion handbook. A corresponding instruction handbook is available for each function/
option module, see ZList of other applicable documents– from page 13.
Single row
This version is a 1-row equipped This version is a 1-row equipped
controller unit in a 3-rowed controller unit in a 2-rowed instal-
installation space. lation space.
2-rowed
This version is a 2-row equipped This version is a 2-row equipped
controller unit in a 3-rowed controller unit in a 2-rowed instal-
installation space. lation space.
3-rowed
This version is a 3-row equipped
controller unit in a 3-rowed
installation space.
A The controller communicates via a functional module bus with plug-in modules in
these slots.
B
1-, 2- and 3-rowed
Slot D can initiate an interrupt. Therewith slot D is particularly suitable for measur-
C ing modules.
D
Optional modules can not be inserted into these slots.
E
F Controller module, not exchangeable with RS232 or Ethernet interface
G The controller communicates via the BACI-bus with plug-in modules in these slots.
2- and 3-rowed
H
Function modules can not be inserted into these slots.
J The controller communicates via the BACI-bus with plug-in modules in these slots.
K
3-rowed
NOTICE!
Plug-in module, which has not been manufactured from Baumüller Nürnberg
GmbH. Modules of other manufacturers can damage/destroy the device.
Only use BM4-F-XXX- and BM4-O-XXX-plug-in modules.
Dependable of the existing controller unit version on your device you can retrofit optional
plug-in modules (functional modules and optional modules).
BM4-O-ETH-01* (Ethernet)
BM4-F-DIO-XX (digital I/O)
BM4-O-PLC-XX (SPS)
BM4-F-ENC-XX
BM4-O-PLK-01
A X - - o o o - o o - - - - - - - - - - - - - -
B - X - o o o - X o - - - - - - - - - - - - - -
C - - - o o o V - o - - - - - - - - - - - - - -
D - - - o X X - - X - - - - - - - - - - - - - -
E - - X X o o - - - - - - - - - - - - - - - - -
F Controller unit
G - - - - - - - - - o o o o o o o X X X X X X X
H - - - - - - - - - X X X X X X X o - o o o o o
J - - - - - - - - - - P P - - - - o o o o - - -
K - - - - - - - - - - P P - - - - o o o o o o o
L - - - - - - - - - - P P - - - - o o o o o o o
M - - - - - - - - - - P P - - - - o o o o o o o
X: preferred slot
Baumüller Nürnberg GmbH recommends, in order to reach the highest functional range, to
insert the plug-in modules into these slots.
P: only possible, if on slot G or H a PLC module (PLC) is plugged and the PLC (and not the
controller) operates the communication to the field bus slave module.
Steckkarten_Rev20_e
NOTE!
Only 2 analog outputs can be parametrized or linked even more than one AIO module
is plugged.
4.2.2 ES controller
The controller is ordered with the desired function/option modules. The modules cannot
be changed later.
Refer to ZType code– from page 126.
Following controller part types are available:
narrow
In this type up to 5 additional
function/option modules can be
installed.
wide
In this type up to 5 additional
function/option modules can be
installed.
Position of Function/option modules enlarge the controller functionality. All modules are permanently
function/option installed and cannot be exchanged.
modules
Each slot is identified by a code letter
BM4-O-PLC-XX (SPS) *
BM4-O-VAR-01 *
BM4-F-ENC-XX
BM4-O-PRO-XX
BM4-O-SER-XX
BM4-O-CAN-03
BM4-F-IEE-XX
BM4-F-SIE-XX
BM4-O-ECT-01
BM4-O-PLK-01
BM4-O-EIP-01
for controller
(encoder 1)
A X - - o o o - o - - - - - - - -
B - X - o o o - X - - - - - - - -
C - - - o o o X - - - - - - - - -
D - - - X X X - - - - - - - - - -
E - - F - - - - - - - - - - - - -
F Controller Unit with RS232- or Ethernet interface
G - - - - - - - - X - - - - X - -
H - - - - - - - - - X X X X - X X
Steckkarten_ES_Rev01_e X: prefered slot
F: permanently installed
o: possible slot, only the prefered slot is occupied
-: not possible
*: in preparation
NOTE!
Only 2 analog outputs can be parametrized or linked even more than one AIO module
is available.
There can be different encoder modules In slot/position A and B, see also ZType code–
from page 126.
Here is a choice of encoders, which you can connect to the encoder modules:
The device is part of the Baumüller series b maXX BM4400, BM4600, BM4700 and can
be connected together with other Baumüller devices.
Because of the many possible combinations and of the many applications that can be op-
erated by b maXX BM4400, BM4600, BM4700 , we have refrained from drawing up a
guide for the interconnection of the devices in written form. Please contact the for you re-
sponsible sales department or the for you responsible employees of the application de-
partment, to discuss your concrete questions on the requirements to develop together a
solution for your problem.
NOTE!
Read the version code to identify BM443X generation 1 or generation 2, refer to ZEx-
planation version code– on page 130.
NOTE!
When replacing a BM443X generation 1 by a generation 2 device the fuses must be
adjusted as well, refer to ZFuses BM4X3X– from page 280.
On the type plate you will find, besides others, the type code of the device.
NOTE!
The type code of the standard controller is only valid for the basic unit without plug-
in modules. Each plug-in module has its own type code.
BM4XXX - XXX - XXXXX[Ryy] - [XXXXXXXX] - [XXX] - XX Current grading (output rated current)
0 to 6 (current value is dependent on the size of housing)
BM4XXX - XXX - XXXXX[Ryy] - [XXXXXXXX] - [XXX] - XX ES controller field bus interface, position G
00 No field bus
10 EtherCAT for controller, SoE, standard see BM4-O-ECT-01
11 EtherCAT for controller, CoE, standard
12 EtherCAT for PLC, CoE
14 EtherCAT for controller, SoE,
special version 16 bit ramp function generator
20 CANopen see BM4-O-CAN-03
NOTE!
A device with safety relay, whose part number does not start with „06“, does not ap-
ply as a safety device as defined by the PL classification according to ISO 13849 or
SIL according to EN 61800. This device is not certificated for safety functions
Devices with the approval mark of TÜV Rheinland and the Safety label provide a cer-
tified safety function, only, refer to ZPage 29–.
NOTE!
Only version codes necessary for the user are explained.
NOTE
Overvoltage Protection Device have to be installed in front of the input circuit of the
device to limit the maximum overvoltage peak to 2.5 kV.
4.7.1 LEDs
m ES controller
BM4XXX - XXX - XX4XX and BM4XXX - XXX - XX5XX:
On the front side of the device there are 6 LEDs. Both upper LEDs (UH1 and UH2) are
reserved. The four lower LEDs (H1 to H4) show information about the operating status
and are also displayed in the operating software.
ZES controller– on page 197 shows the position of the display elements.
LED Both LEDs UH1 and UH2 are not led through to the design cover.
(UH1, UH2) Not available with BM4XXX - XXX - XX0XX and BM4XXX - XXX - XX1XX.
H1
NOTE!
LED H1 shows only the torque direction, it cannot be used to show the direction of
rotation.
H2
flashing green/orange: Pulses enabled for generating the magnetic field of asyn-
chronous machines. No torque enable yet.
green with short orange flashing memory access EEPROM, if possible do not switch off
or the device in this phase.
orange with short green flashing:
Current limit
H3
Error LED doesn’t light up: the internal monitoring have not found an error.
H4
The single drive statuses are specified in chapter device management in parameter man-
ual 5.03039.
The display shows the error code in error status. Only errors are displayed, which enable
an error reaction or have enabled one. Errors without reaction and warnings are not dis-
played (see ZFault detection– from page 234).
IP address The IP address of the controller consists of 32 bits or 4 bytes (e.g. 192.168.125.203). Both
S1 to S4 of the first bytes are set with the base address (192.168.) at the factory.
Both of the last bytes are set by means of the address switches S1, S2, S3 and S4. In the
process, S1 and S2 as well as S3 and S4 each represent an 8 bit value.
The IP address 192.168.0.0 is not permitted or, respectively, is reserved.
For information on changing the base address, see the parameter manual.
Example
Switch
Baud rate S2
20 kBit/s 125 kBit/s
1 MBit/s
Address S3/S4
NOTICE!
Damage due to unauthorized transport!
Transport handled by untrained personnel can lead to a substantial amount of mate-
rial damage.
Therefore:
m The unloading of the packages upon delivery as well as the in-house transport
should only be done by trained personnel.
m Contact Baumüller Nürnberg GmbH sales office if necessary.
WARNING!
Danger of mechanical hazard!
Secure devices against falling down.
Therefore:
m Take suitable measures, such as supports, hoists, straps, etc., to ensure that de-
vices cannot fall down.
m Use appropriate handling material.
For initial transport of the device, it is packed at the manufacturer. If the device is to be
further transported, ensure that the following conditions are met throughout the entire
transport:
m Climate class 2 K 3 as per EN 60721-3-2
m Temperature range - 25 °C up to + 70 °C
m Vibration, shock, continuous shock class 2 M 1 as in EN 60721-3-2
Upon receiving the delivered goods, immediately examine them for completeness and
transport damage.
If there is outwardly visible transport damage, proceed as follows:
m Do not accept the delivery or conditionally accept it with reservations.
m Note the extent of the damage on the transport documents or on the delivery note of
the transport agent.
m Immediately file a complaint with the freight carrier. Have the complaint confirmed in
writing and immediately contact the responsible representative of Baumüller Nürnberg
GmbH.
NOTE!
The device may not be operated if there is visible transport damage!
5.4 Unpacking
NOTE!
Claim each individual deficiency as soon as it has been detected. Damage claims can
only be validly asserted within the claim registration period.
The packaging consists of cardboard, plastic, metal parts, corrugated cardboard and/or
wood.
h When disposing of the packaging, comply with the national regulations.
NOTE!
Mounting shall only be performed by employees of the manufacturer or by other qual-
ified personnel.
Qualified personnel are persons who – on account of their occupational training, ex-
perience, instruction and knowledge of relevant standards and stipulations, accident
prevention regulations and operating conditions – are authorized by the persons re-
sponsible for the safety of the facilities to perform the respective activities that are
necessary, while at the same time recognizing and preventing any potential risks.
The qualifications necessary for working with the device are, for example:
m Occupational training or instruction in accordance with the standards of safety en-
gineering for the care and use of appropriate safety equipment.
WARNING!
Danger as a result of faulty mounting!
The mounting requires qualified personnel with adequate experience. Faulty mount-
ing can lead to life-threatening situations or substantial material damage.
Therefore:
m Only allow mounting to be performed by employees of the manufacturer or by oth-
er qualified personnel.
WARNING!
Danger of mechanical impact!
Secure devices against falling down.
Therefore:
m Take suitable measures, such as supports, hoists and assisting personnel, to en-
sure that device cannot fall down.
m Use appropriate means of transport.
NOTICE!
Danger due to electrostatic discharge.
The connecting terminals of the device are partially at risk due from ESD.
Therefore:
Please heed the respective notes.
Therefore:
m Ensure that only qualified personnel, who are familiar with the safety notes and as-
sembly instructions, mount this device.
Based on the planning documents and the drilling pattern (see ZDrilling patterns– from
page 147), the cutout sections and the positions of the attachment drill holes can be de-
termined.
NOTICE!
Property damage due to conductive contamination.
Therefore:
m When performing installation work of any kind, it must be ensured that no foreign
material (e.g. drill shavings, copper strands, etc.) gets into the device as a result.
m If possible, the drilling of the holes should be done before mounting the device and
the configuring of the cables should take place outside of the control cabinet. If this
is not possible, the device must be appropriately covered.
Remove this covering again prior to start!
CAUTION!
Eye injury due to flung particles.
Metal particles are flung when making the drill holes and the cutout sections.
Therefore:
Use the drilling pattern to make the necessary drill holes/cutout sections.
NOTE!
Consider the minimum clearances for cooling when making the drill holes.
All dimensions in millimeters [mm].
Further notes see ZDimensions– from page 31 and ZCooling– from page 61.
How to determine the required space in the control cabinet, see ZDimensions– from
page 31.
Tolerance
specifications
Drill hole dimensioning ±0.2 mm
Dimensioning openings +1.0 mm
Relative tolerance of discretionary divisions ±0.1 mm
Hole
WARNING!
Danger because of conductive fluid in connection with electricity!
1 The mounting drills are outside of the gasket. With non-waterproof fastening holes,
e. g. the liquid coolant can ingress into the control cabinet.
m Seal the mountings against water. Use, e.g., waterproof draw-in bolts and sealants
between screws and bolts.
NOTE
The following required control cabinet mounting is only valid for control cabinets with
protection class IP54 or higher.
The cooling version cold plate is a particular efficient cooling alternative. The heat dissi-
pation is done via 2 contact surfaces. The first one is the mounting platform within the con-
trol cabinet or on the machine base, the other is the cold plate on the device’s back. High
requirements e.g. to surface roughness and evenness for this surface are specified, to
ensure an optimal heat flow. Already a slight damage/pollution of the surface can cause
a significant deterioration in heat dissipation to the mounting plate.
For this reason while handle the units protect the sensitive function surface to avoid dam-
age.
NOTICE!
Property damage due to overheating
Scratches and burrs can inhibit the heat dissipation of cold plate devices.
Therefore
m When mounting cold plate devices, ensure that the surface quality of the mounting
plate meets the specifications and ensure that the device’s rear panel/mounting
plate does not have any scratches or burrs.
In case you refer to UL 508 C: There must be a pressure-relief valve with a threshold pres-
sure of maximum 6 bar in the cooling circulation.
NOTE!
Installation shall only be performed by employees of the manufacturer or by other
qualified personnel.
Qualified personnel are persons who – on account of their occupational training, ex-
perience, instruction and knowledge of relevant standards and stipulations, accident
prevention regulations and operating conditions – are authorized by the persons re-
sponsible for the safety of the facilities to perform the respective activities that are
necessary, while at the same time recognizing and preventing any potential risks.
The qualifications necessary for working with the device are, for example:
m Occupational training or instruction, and the authorization to commission, ground
and mark electrical power circuits and devices in accordance with the standards of
the safety engineering.
m Occupational training or instruction, in accordance with the standards of work safe-
ty, for the care and use of appropriate safety equipment.
WARNING!
Danger because of faulty installation and initial commissioning!
Installation and commissioning require qualified personnel with adequate experi-
ence. A installation fault can cause danger situations or large damage of property.
Therefore:
m Only personnel from manufacturer or qualified personnel operate while installation
and initial commissioning
DANGER!
Risk of fatal injury from electrical current!
Inevitably, when operating this electrical device, certain parts of it are energized with
hazardous voltage.
Therefore:
m Pay heed to areas on the device that could be dangerous during the electrical in-
stallation.
m Pay heed to areas on the device that could still be electrically energized after op-
eration.
DANGER!
Risk of fatal injury from electrical current!
Stored electric charge.
Discharge time of the system = discharge time of the device with the longest DC link
discharge time in the DC link connection.
Refer to ZElectrical data basic units– from page 63.
Therefore:
m Do not touch before taking into account the discharge time of the capacitors and
electrically live parts.
m Heed corresponding notes on the equipment.
m If additional capacitors are connected to the DC link, the DC link discharge can
take a much longer time. In this case, the necessary waiting period must be deter-
mined or a measurement made as to whether the equipment is de-energized. This
discharge time must be posted, together with an IEC 60417-5036 (2002-10) warn-
ing symbol, on a clearly visible location of the control cabinet.
DANGER!
Risk of fatal injury from electrical current!
During the routine test of these devices, a voltage test is performed by Baumüller
Nürnberg GmbH in accordance with EN 61800-5-1, Section 5.2.3.2. It is thus unnec-
essary for the customer to do this.
Therefore:
m Subsequent tests of the devices using high voltages may only be performed by
Baumüller Nürnberg GmbH.
m Disconnect the converter from the system during high-voltage testing!
For all important data, see ZRequirements to the energy supply / supply system– from
page 52.
Minor deviations from requirements in the power supply can lead to malfunctioning of the
device. If the power supply deviates too much from the requirements, the device can be
destroyed.
The devices may only be operated in industrial networks.
The destruction of the device can cause personal injury.
DANGER!
Risk of fatal injury from electrical current!
If the requirements for the power supply are not complied, the device can be dam-
aged or destroyed, thereby greatly endangering individuals.
Therefore:
m Prior to installation, ensure that the demands for power supply have been fulfilled.
right wrong
Figure 75: Single phase connection (BM442X ... BM447X, basic units)
n Connection to single phase grounded power supply systems with isolated trans-
former for the following cases
1) BM441X, BM442X except for IT power supply systems
2) BM443X ... BM447X, BM46XX, BM47XX at operating altitude > 2000 m
Figure 76: Connection to single phase grounded power supply systems with an isolated transformer
h Take into account IEC/EN 60204-1, Chapter 13 when selecting the cable.
h The protective ground cross-section of the cable must be compliant with IEC/
EN 60204-1, Section 5.2, Tab. 1.
h A fixed connection for the protective ground conductor is mandatorily specified for op-
eration of the device.
h Use copper cable approved for a minimum of 60 °C (drives < 3 x 100 A) or 75 °C
(drives 3 x 100 A), if comply with UL 508C.
For further details (e.g. maximum permitted length), see ZCabling– from page 268.
Fuses must be installed to protect this device and the cables against overload and pos-
sible damage/destruction through the electrical power supply. For data on the required
fuses, see ZFuses– from page 273.
Depending on the functional principle, leakage current >3.5 mAAC or >10 mADC can flow
through the protective ground conductor. Consequently, a stationary ground conductor
connection in accordance with EN 61800-5-1 is required.
DANGER!
Risk of fatal injury from electrical current!
This product can cause direct and/or alternating current in the protective ground con-
ductor.
The leakage current, due to the functional principle of the device, can lead to prema-
ture triggering of the fault current protective device or generally prevent triggering of
it.
Therefore:
m Wherever a differential current device (RCD) is used for protection in case of direct
or indirect contact, only an RCD of the type B is permitted on the power supply side
of the device.
m Otherwise a different protective measure must be utilized, such as separation from
the surroundings by means of double or enhanced isolation, or separation from the
power supply system by means of an isolating transformer, for example.
NOTE!
The emission of radio frequency interference (RFI) is to a great extent dependent on
the wiring, spatial expansiveness and the arrangement of the components in the sys-
tem. Ensuring electromagnetic compatibility compliance in accordance with legal re-
quirements is therefore only possible on the completely assembled system and is
thus the responsibility of the system manufacturer or proprietor (re Art. 6, Par. 9 of
the EMVG; European EMC law).
NOTE!
The important information on EMC-compliant installation can be found in these in-
struction handbook. Additional notes on building a CE-compliant system, that are im-
perative to take heed of, can be found in the Baumüller manual „Mains filter BFN“,
5.09010. This manual can be obtained from Baumüller Nürnberg GmbH.
In order to have EMC-compliant and problem-free use within the framework of the legis-
lation, the following aspects must be taken into account.
In case of any questions, please contact Sales or the Applications department of
Baumüller Nürnberg GmbH.
m Only use Baumüller motor cables and Baumüller components.
m Use suitable mains filters recommended by Baumüller Nürnberg GmbH.
m Mount all components on a single mounting plate with a continuously good electrically-
conductive surface (e.g. galvanized steel plate).
m Keep the ground connection device/ground plate as short as possible (< 30 cm) , using
fine-stranded cables with a large cross-section (>10 mm2).
m When installing, be sure to follow the correct sequence:
power supply system - fuse - filter - choke - (ferrite core) - BM4400, BM4600, BM4700
- (motor filter) - motor.
m Ensure that the motor cable is continuous, without interruption.
Do not interrupt motor cables with terminals, contactors or fuses, for example.
m Route the cables directly on the surface of the grounded mounting plate.
(smallest possible effective aerial height).
m When routing in parallel, a minimum clearance of 20 cm should be observed between
signal and control cables vis-à-vis the power cables.
m Cross cables with different EMC categories (signal cables - supply cables or motor ca-
bles) only in a 90° angle.
m Contact the major cable shield when laying cables through walls, which separate dif-
ferent EMC areas.
m Contact all the cable’s shields on both sides surface-to-surface and also well-conduc-
tive with ground.
To protect the motor against not permitted overheating, a motor temperature sensor can
be connected to the b maXX device. The device switches off of the motor when a settable
threshold temperature has been exceeded.
NOTE!
The motor temperature sensor should be installed in such a manner that „safe elec-
trical separation“ is ensured. The motor temperature sensors integrated into
Baumüller motors meet these requirements. If third-party motors are connected, the
proprietor must ensure that the temperature sensors used in the motor of a third-party
manufacturer motor comply with the „safe electrical separation“ function.
DANGER!
Risk of fatal injury from electrical current!
Electrically live parts are life-threatening.
Therefore:
m Make certain that the parts to be mounted (e.g. power supply cables) and the
mounting areas are de-energized for the entire duration of mounting the device.
HINWEIS!
Steps which are not necessary for the installation of b maXX power modules are
marked.
NOTE!
Plugging in and pulling out encoder cables while they are energized is prohibited, and
could lead to their destruction.
Therefore, always first switch off the 24 V supply voltage and lock the encoder con-
nectors when operating.
9 Connect the temperature sensor of the motor. (Observe the proper polarity!)
10 Connect the signal generator for the pulse enable:
terminals X3-5, X3-3
11 Connect the signal generator for the quick stop:
terminals X3-4, X3-3
12 Perhaps connect (dependent on the application - not necessary for power modules
- a brake resistor (RB) via terminals Ba+, Ba-.
13 Connect the brake of the motor (option):
Terminals X101-1/2 and X101-3/4
14 Connect the safety relay (if existing) via X102-3 and X102-4 as well as X103-3 and
X103-4 (connection data safety relay also see ZC.5 Technical data safety relay mod-
ule– on page 350).
Ballast bus
Mains bus
+ 24 V **
* PE U V W
M 24 V
M 24 V
M 24 V
230 V
+ 24 V
+ 24 V
S1
S2 L2
L1
PC
1U1
1V1
1W1
X100-5
X100-2
X100-3
PE
X100-4
X100-1
X100-6
X36-N
X36-L
X102-1
X102-2
X102-3
X102-4
X103-1
X103-2
X103-3
X103-4
SUB-D, 1:1
9 ProDrive
X1
X3-1
X3-2
X3-3 M 24 V
X3-4 + 24 V
X3-5 + 24 V
X3-6
X101-1 + 24 V **
X101-2
X101-3
X101-4 M 24 V
X101-5
X101-6
A
BM4-ENC-XX
X1
1W2
1U2
1V2
1D1
1C1
Ba+
Ba-
PE
4000_0059_rev12_int.cdr
S3 15
M ENC
RB 3
Motor temperature
bra
Figure 77: Connection diagram with a directly controlled motor brake - basic units
HINWEIS!
If the motor brake is connected directly via X101-2 and X101-3 (see ZFigure 77– on
page 173), the shown direct installation is allowed only. It is not allowed within a multi-
axis installation e.g. to connect the plus and ground connections of all motor brakes
with each other.
An additional relay is necessary, if the voltage of the brake is 24V, or if the current of the
brake is greater than the switching capacitance of X101 (see ZX101 (SELV/PELV)– on
page 194) or if you consider UL508C and the current of the brake is greater 4 A.
Perhaps consider a limited operating voltage range of the brake because of the internal
voltage drop up to max. 2.6 V.
Ballast bus
Mains bus
+ 24 V**
* PE U V W
M 24 V
M 24 V
M 24 V
+ 24 V
+ 24 V
230 V
S1
S2 L2
L1
PC
1U1
1V1
1W1
X100-5
X100-2
X100-3
PE
X100-4
X100-1
X100-6
X36-N
X36-L
X102-1
X102-2
X102-3
X102-4
X103-1
X103-2
X103-3
X103-4
SUB-D, 1:1
9 ProDrive
X1
X3-1
X3-2
X3-3 M 24 V
X3-4 + 24 V
X3-5 + 24 V
X3-6
X101-1 + 24 V **
X101-2
X101-3
X101-4 M 24 V
X101-5
X101-6
A
BM4-ENC-XX
X1
1W2
1U2
1V2
1D1
1C1
Ba+
Ba-
PE
4000_0568_rev03_int.cdr
S3 15
M ENC
RB 3
Motor temperature
bra
Brake
voltage
Figure 78: Connection diagram with motor brake controlled via an add. relay - basic units
Ballast bus
Mains bus
+ 24 V **
* PE
M 24 V
M 24 V
M 24 V
230 V
+ 24 V
+ 24 V
S2
PC
X100-5
X100-2
X100-3
PE
X100-4
X100-1
X100-6
X36-N
X36-L
X102-1
X102-2
X102-3
X102-4
X103-1
X103-2
X103-3
X103-4
SUB-D, 1:1
9 ProDrive
X1
X3-1
X3-2
X3-3 M 24 V
X3-4 + 24 V
X3-5 + 24 V
X3-6
X101-1 + 24 V **
X101-2
X101-3
X101-4 M 24 V
X101-5
X101-6
A
BM4-ENC-XX
X1
1W2
1U2
1V2
1D1
1C1
Ba+
Ba-
PE
4000_0612_rev02_int.cdr
S3 15
M ENC
RB 3
Motor temperature
bra
S4
U DC link
Connection to other
BM41XX or BM44XX units
Figure 79: Connection diagram with a directly controlled motor brake - power modules
An additional relay is necessary, if the voltage of the brake is 24V, or if the current of the
brake is greater than the switching capacity of X101 (see ZX101 (SELV/PELV)– on page
194) or if you consider UL508C and the current of the brake is greater 4 A.
Perhaps consider a limited operating voltage range of the brake because of the internal
voltage drop up to max. 2.6 V.
Ballast bus
Mains bus
+ 24 V**
* PE
M 24 V
M 24 V
M 24 V
+ 24 V
+ 24 V
230 V
S2
PC
X100-5
X100-2
X100-3
PE
X100-4
X100-1
X100-6
X36-N
X36-L
X102-1
X102-2
X102-3
X102-4
X103-1
X103-2
X103-3
X103-4
SUB-D, 1:1
9 ProDrive
X1
X3-1
X3-2
X3-3 M 24 V
X3-4 + 24 V
X3-5 + 24 V
X3-6
X101-1 + 24 V **
X101-2
X101-3
X101-4 M 24 V
X101-5
X101-6
A
BM4-ENC-XX
X1
1W2
1U2
1V2
1D1
1C1
Ba+
Ba-
PE
4000_0613_rev01_int.cdr
S3 15
M ENC
RB 3
Motor temperature
bra
S4
** The power supply at X100 or X101 must externally be protected. At selection of the fuse
you must consider the cross-section of the connecting cable and the maximum allowable
load capacity (for X100: see X100 on ZPage 193–, for X101: see X101 on ZPage 194–).
In case you consider UL 508 C, you must limit the power supply to 100 W or fuse it with a
UL-listed 4 A fuse.
Ba- ... 1D1 Connections for brake resistor and DC link, see ZFigure 82– on page 181 and the follow-
ing
RB Brake resistor
PE....1W1 Power supply connection, see ZFigure 82– on page 181 and the following
S1 Fuse (cable + device), see ZFuses– from page 273
S2 Fuse (fan) *)
S3 Fuses brake resistor circuit (required for BM447X, BM477X),
see ZFuses BM447X– on page 292.
S4 DC link fuse
L1 Power choke (not necessary for BM441X and BM442X except BM4426)
L2 Mains filter
X1 Serial interface (RS 232), see ZFigure 91– on page 196.
X3 Connections for ready-for-use, quick stop, pulse enable, see ZFigure 91– on page 196.
X36 Connections for fans (only BM444X-S/-A, BM445X-S/-A, BM465X-S/-A, BM446X-S/-A,
BM466X-S/-A, BM447X-A)
X100 Connections for 24 V power supply, additional data see ZFigure 91– on page 196 (SELV/
PELV) and table ZX100 (SELV/PELV)– on page 193.
X101 Terminals for brake, motor temperature, see ZFigure 82– on page 181 and the following
(SELV/PELV) and table X101 from ZPage 181–.
X102 Connections of the safety relay, see ZFigure 82– on page 181 and the following (SELV/
PELV) and table ZX102 (option) Safety relay– on page 194.
X103 Terminals of the optional, second safety relay (only BM443X - BM447X, BM46XX,
BM47XX), see ZFigure 85– on page 184 and the following (SELV/PELV) and table ZX103
(0ption) Safety relay– on page 194.
A - X1 Encoder module, see documentation 5.01042 (SELV/PELV)
ENC Encoder
BRA Brake
PE....1W2 Connections for motor, see ZFigure 82– on page 181 and the following.
ZFigure 82– on page 181 and the following show the connections for protective conduc-
tors, power supply, motor, brake resistor, DC-link, safety relays and motor temperature
sensor (X101). ZFigure 91– on page 196 shows the control voltage and the connections
of the controller unit.
NOTE!
When having a switched off safety relay it is not possible to use the brake at BM441X
and BM442X
NOTE!
The characterization 1C1 and 1D1 is from the standard DIN EN 60445.
1C1 is the connection to the positive DC link cable/current bar and was labeled with
ZK+ by Baumüller in the past.
1D1 is the connection to the negative DC link cable/current bar and was labeled with
ZK- by Baumüller in the past.
NOTE!
When replacing a BM443X generation 1 by a generation 2 device (differentiation see
ZExplanation version code– on page 130) the fuses must be adjusted as well, refer
to ZFuses BM4X3X– from page 280.
Under certain conditions a mix mode of BM443X generation 1 and 2 is possible, see
ZMix mode BM443X generation 1 and 2– on page 124.
Figure 82: Electrical connections for power supply, motor, ... for BM4412 and BM4413
Figure 83: Electrical connections for power supply, motor, ... for BM4414
NOTE!
The brake resistor is connected at BM445X and BM446X between Ba- and 1C1.
Also see ZFigure 77– on page 173.
Figure 88: Electrical connections for power supply, motor, ... for BM466X and BM476X
Figure 89: Electrical connections for power supply, motor, ... for BM4755
*) only BM447X-A
Figure 90: Electrical connections for power supply, motor, ... for BM447X and BM4773
NOTE!
The brake resistor is connected at the devices BM447X, BM477X between Ba- and
1C1. Also see ZFigure 77– on page 173.
DANGER!
Risk of fatal injury from electrical current!
Therefore:
After attaching all power cables to the device BM447X and BM477X, screw on the
cover careful to all screwing points by using the enclosed screws (6xM4x12) and
washers. The cover only must be able to be removed from the device with use of
tools.
The use of semiconductor fuses is obligatory at the power supply connection of
BM447X, BM477X devices. Semiconductor fuses are required in the brake resistor
circuit except the user assures the short-circuit protection of resistor and cable.
BM463X
BM444X 50 mm2 Screw terminal min. 6 Nm
BM464X max. 8 Nm
BM445X 2 x 95 mm2 1)3) Cable lug min. 10 Nm
BM465X for M8 max. 13 Nm
BM475X
BM446X 2 x 185 mm2 2)3) Cable lug min. 12 Nm
BM466X for M10 max. 25 Nm
BM476X
BM447X 2 x 185 mm2 2) Cable lug min. 12 Nm
BM477X 4 x 95 mm2 1) for M10 max. 25 Nm
1) The cable lug may be 25 mm wide at most. The maximum cable diameter is dependent on the cable lug. In
case the cable lug, which you use, can safely clamp a stronger cable than 95 mm2, you may also use stronger
cables than 95 mm2. Also see ZCables power supply - device– from page 268.
2)
The cable lug may be 35 mm wide at most. The maximum cable diameter is dependent on the cable lug. In
case the cable lug, which you use, can safely clamp a stronger cable than 185 mm2, you may also use stron-
ger cables than 185 mm2. Also see ZCables power supply - device– from page 268.
3)
One cable of the mentioned cross section is sufficient for the operation.
4)
See also ZExplanation type code– on page 126.
BM463X
BM444X 50 mm2 Screw terminal min. 6 Nm
BM464X max. 8 Nm
BM445X 2 x 95 mm2 4)6) Cable lug min. 10 Nm
BM465X for M8 max. 13 Nm
BM475X
BM446X 2 x 185 mm2 5)6) Cable lug min. 12 Nm
BM466X for M10 max. 25 Nm
BM476X
BM447X 2 x 185 mm2 5) Cable lug min. 12 Nm
BM477X for M10 max. 25 Nm
1)
Not short-circuit-proof, consider maximum load! See „Brake resistor external“ in chapter ZTechnical Data–
from page 31.
2)
Not short-circuit-proof, consider maximum load! See „connected load DC link“ in chapter ZTechnical Data–
from page 31.
3)
See „permitted brake resistor continuous power“ in chapter ZTechnical Data– from page 31.
4)
The cable lug may be 25 mm wide at most. The maximum cable diameter is dependent on the cable lug. In
case the cable lug, which you use, can safely clamp a stronger cable than 95 mm2, you may also use stronger
cables than 95 mm2. Also see ZCables power supply - device– from page 268.
5)
The cable lug may be 35 mm wide at most. The maximum cable diameter is dependent on the cable lug. In
case the cable lug, which you use, can safely clamp a stronger cable than 185 mm2, you may also use stron-
ger cables than 185 mm2. Also see ZCables power supply - device– from page 268.
6)
One cable of the mentioned cross section is sufficient for the operation.
7)
See also ZExplanation type code– on page 126.
Notes on the usage of an OSSD test pulse see ZC.4 Requirements on an OSSD test
pulse– on page 349.
Notes on the usage of an OSSD test pulse see ZC.4 Requirements on an OSSD test
pulse– on page 349.
NOTE!
Follow the mentioned torques in ZFigure 87– on page 186 and in ZFigure 90– on
page 189 to ensure an adequate conductivity.
NOTE!
This Instruction Handbook describes the controller without function and option mod-
ules. A corresponding manual is available to each function/option module, refer to
ZList of other applicable documents– on page 13.
HINWEIS!
1) If you consider UL508C, limit the current to 4 A.
2)
Do not apply voltage to the terminals X100-3 or X100-4, if the device is not supplied
via X100-1/2 with voltage.
The signals „mains on“ and „brake resistor“ are internal digital control signals of the
system b maXX 4000. They are used at applications with DC link connection.
3) )
The PSI-module may not be attached or withdrawn, if the b maXX 4000 24 V pow-
er supply is ON. Beforehand switch off the device.
Further notes for the usage of the PSI module are to be found in parameter manual.
4) not BM44XX - XXX - XX0XX and BM44XX - XXX - XX1XX
Standard
controller
X4: reserved
H5 7-segment display 4)
also see ZDisplay and operation elements– from page 132
X2:
Connection for Baumüller memory module PSI 3) 4)
H5 7-segment display 4)
also see ZDisplay and operation elements– from page 132
X2:
Connection for Baumüller memory module PSI 3) 4)
1: reserved
2: TxD RS232
3: RxD RS232
4: DTR, DSR
5: Ground RS232
6: DTR, DSR
7: RTS
8: CTS
9: reserved
WARNING!
Risk of injury because of mechanical hazard!
If a PC is not connected via an isolated transformer, the machine can do unexpected
actions.
Therefore:
Connect the PC via an isolated transformer or use a battery operated PC (e. g. lap-
top, notebook) without connecting a charger.
NOTE!
In case you don’t use an optically decoupled interface cable, the cable shield has only
to be connected to the connector housing at the controller connector.
The company Baumüller Nürnberg GmbH recommends the usage of optically decou-
pled transmitters (e.g. from the company Ratioplast part No. 901SV232C6095 and
part No. 901SV232T6095)
Refer to ZInterface cable RS232– on page 272, if the cable is made by the customer.
X1
H11 1: TX+
2: TX-
3: RX+
4: reserved
5: reserved
6: RX-
7: reserved
H12
8: reserved
Name Meaning
H11 off: no activity
yellow: half duplex
green: full duplex
H12 off: no connection
yellow: 10 Mbit
green: 100 Mbit
Notes on the usage of an OSSD test pulse see ZC.4 Requirements on an OSSD test
pulse– on page 349.
X5 IN
H51 1: TX+
2: TX-
3: RX+
4: reserved
5: reserved
6: RX-
7: reserved
H52
8: reserved
X6 OUT
H61 1: TX+
2: TX-
3: RX+
4: reserved
5: reserved
6: RX-
7: reserved
H62
8: reserved
NOTE!
Setting the IP address, see ZEtherCAT®– from page 136.
X5 IN
H51 1: CAN high
2: CAN low
3: Ground (GND)
4: reserved
5: reserved
6: not connected
7: Ground (GND)
H52
8: not connected
X6 OUT
H61 1: CAN high
2: CAN low
3: Ground (GND)
4: reserved
5: reserved
6: reserved
7: Ground (GND)
H62
8: reserved
NOTE!
Setting the IP address, see ZCANopen®– from page 139.
NOTE
For further information see Instruction Handbook Encoder modules 5.01042.
Number of pole pairs The ratio between the number of motor pole pairs and
of the number of pole pairs of the encoder must be
integer. 1)
Permitted current input max. 160 mA
Excitation frequency 4 kHz
Excitation current 160 mA
Transmission ratio BM4-F-ENC-01 0.5
BM4-F-ENC-11 0.28
NOTE
Resolvers are to be used only for motors with maximum ten pole pairs.
1)
Example:
3
Number of pole pairs motor =3 --- = 3 permitted
Number of pole pairs resolver =1 1
3
Number of pole pairs motor =3 --- = 1 5 not permitted
Number of pole pairs resolver =2 2
2)
Requirements to the temperature sensor:
Power supply 8 V DC
Signal level Hiperface® - specification of operation data channel
(~1Vss; REFSIN/REFCOS 2.5V)
Permitted current input max. 250 mA
1)
Requirements to the temperature sensor:
2)
NOTE
At use of module in connection with pre-assembled Baumüller encoder cables the
temperature sensor is not connected to the encoder cable!
You can connect the temperature sensor separately at the module (in the D-sub con-
nector) or at the power unit.
Power supply 5 V DC
Signal level RS422 (TTL)
Permitted current input max. 250 mA
NOTE
A broken wire of the zero point cable is not detected by the controller.
1)
Requirements to the temperature sensor:
NOTE
Encoder cable for EnDat® 2.2 without incremental signals (original encoder cable of
Heidenhain), see ZEncoder cables– from page 307.
NOTE
The connection cable is not offered by Baumüller and must be made by the user!
NOTE
The connection cable is not offered by Baumüller and must be made by the user!
X1 Socket 2-pin
NOTE
Only if the cable break monitoring is supported (see ProDrive, page „Slot identifica-
tion“) and if the cable break monitoring is activated (see parameter handbook P0573)
both cable break and missing of the 24V power supply and a cable break in Data+/
Data- is identified. Otherwise the availability of the 24 V power supply is not checked
and a broken cable is not detected by the controller.
Instruction:
6 1
7 2
8 3
9 4
5
1 1
2 2
8 3
9 4
6 0,5 mm² 5
7 0,5 mm² 6
4
1 2
6 5
7 3
NOTE
A broken wire of the reference signal cable [R+], [R-] or commutation signal cable
[C+], [C-], [D+], [D-] is not detected by the controller
NOTE
The connection cable is not offered by Baumüller and must be made by the user!
NOTE!
The module AIO-01 is always integrated in ES controller (position E, connector X4).
The module AIO-02, 03 or 04 can be ordered at position D.
The module BM4-F-AIO-01 can be plugged in slot E in standard controller. The mod-
ule BM4-F-AIO-02, 03 or 04 can be plugged in slot D or E.
NOTE!
Choose position E in ProDrive for configuration of analog inputs/outputs AIO-01 (con-
nector X4)in ES controller.
Further information referring to analog inputs/outputs, see manual BM4-F-AIO-XX
(5.01045).
1)
The analog output speed can be changed from „slow output“ to „fast output“ by the operation software and
vice versa.
NOTE!
The module DIO/FIO can used only in position D of ES controller.
The module BM4-F-DIO/FIO can be used in all slots of the standard controller, but
preferred should be slot D.
NOTE!
Further information referring to digital inputs/outputs, see manual BM4-F-DIO/FIO
(5.01046).
1)
Unlike DIO/FIO-01 inside DIO/FIO-11 the contact „ground external“ is not connected to PE.
2)
On tripping, there appears an error message on the controller.
3)
Limit the current to 2.5 A. (Due to this also UL 508 C with a maximum current of 4 A will be considered).
Basic information
WARNING!
Risk of injury due to improper operation!
Improper operation can lead to severe personal injury or material damage.
Therefore:
m Perform all operational steps according to the details of these instruction hand-
book.
m Before beginning any work, ensure that all coverings and protective devices are
installed and are functioning properly.
m The control cabinet in which the device is installed should be protected against
contact with electrically live parts.
Keep all doors of the control cabinet closed during operation.
NOTICE!
Environmental conditions that do not meet the requirements.
Environmental conditions that are non-compliant can lead to property damage.
Therefore:
m Ensure that the environmental conditions are kept compliant during operation (see
ZRequired environmental conditions– on page 55).
WARNING!
Risk of injury due to insufficient qualifications!
Inevitably, when operating this electrical device, certain parts of this device are ener-
gized with hazardous voltage. Improper handling can lead to significant personal in-
jury and material damage.
Therefore:
m Only qualified personnel may work on this device!
After the device has been commissioned it is parameterized (i.e. adapted to the applica-
tion). Once parameterization has been completed, the device can be operated with one
of the two following operation systems:
System 1 m Two enable signals (see ZEnable signals– on page 224) via digital inputs/outputs
System 2 m Two enable signals (see ZEnable signals– on page 224) via digital inputs/outputs
m Higher level control, which controls the two enable signals and in addition give com-
mands via digital inputs/outputs and/or e.g. the field bus.
These signals must have a signal level of 24 V (DC) and must be connected to the termi-
nals X3-4 and X3-5 (ZFigure 91– on page 196).
Pulse enable During operation the signal „pulse enable“ must constantly be available, so that the de-
vice supplies power. Additionally the pulse enable has to be generated by the controller.
Both signals are AND-linked, so the failure of one of these signals results in impulse in-
hibit of the power unit.
Quick stop Disable the signal „quick stop“ only, if you must stop the installation/device as quick as
possible.
During operation the signal „quick stop“ must be available, so that the device supplies
power.
The devices use a rectifier with 6 diodes (B6U circuit). There is a resistor between rectifier
and DC link capacitor limiting the charging surge. The resistor is bridged by a relay after
the charging. Smaller waiting periods between the DC link discharge and charge reduce
the lifetime of the devices. The specified waiting time of the device is increased to at least
90 seconds when an additional external DC link capacitance is connected. The maximum
permitted external DC link capacitance depends on the power supply voltage (see ZFig-
ure 32– on page 65 or ZFigure 34– on page 69).
h up to
BM 4 4 4 X - X X X - XXXXX[Ryy] - [XXX] - XX[xx] - 4005 -X-XXX-XXX
BM 4 4 5 X - X X X - XXXXX[Ryy] - [XXX] - XX[xx] - 5003 -X-XXX-XXX
BM 4 4 6 X - X X X - XXXXX[Ryy] - [XXX] - XX[xx] - 6003 -X-XXX-XXX
BM 4 4 7 X - X X X - XXXXX[Ryy]
BM 4 6 4 X - X X X - XXXXX[Ryy]
BM 4 6 5 X - X X X - XXXXX[Ryy]
BM 4 6 6 X - X X X - XXXXX[Ryy]
BM 4 7 X X - X X X - XXXXX[Ryy]
Above shown character string shows the type code on the type plate. The bold group of
four strings (fifth segment of type code) determines the power unit’s technical status. All
devices with type to 4005-, -5003- and -6003- use the before mentioned time-controlled
charge procedure and behave similar to BM443X, but the charging time of the DC link is
approximately 1 second.
Instead of the technical status shown directly on the type plate, the version of the power
unit firmware can be shown in ProDrive (page power unit, top left, device data: firmware
version). Up to version 03.06 ZPower supply switch-on frequency BM443X (Generation
1)– from page 225.
h from
BM 4 4 3 X - X X X - XXXXX[Ryy] - [XXX] - XX[xx] - 3006 -X-XXX-XXX
BM 4 4 4 X - X X X - XXXXX[Ryy] - [XXX] - XX[xx] - 4006 -X-XXX-XXX
BM 4 4 5 X - X X X - XXXXX[Ryy] - [XXX] - XX[xx] - 5004 -X-XXX-XXX
BM 4 4 6 X - X X X - XXXXX[Ryy] - [XXX] - XX[xx] - 6004 -X-XXX-XXX
BM 4 4 7 X - X X X - XXXXX[Ryy]
BM 4 6 3 2 - X X X - XXXXX[Ryy]
BM 4 6 4 X - X X X - XXXXX[Ryy]
BM 4 6 5 X - X X X - XXXXX[Ryy]
BM 4 6 6 X - X X X - XXXXX[Ryy]
BM 4 7 X X - X X X - XXXXX[Ryy]
For technical status higher than the above mentioned, an alternative procedure is imple-
mented.
This version of the power unit firmware can be shown in ProDrive. It is 04.00 and higher.
The devices use a rectifier with 3 diodes and 3 thyristors (B6HK circuit). The circuit mea-
sures the voltage on the phase conductor and the DC link. The corresponding thyristor is
fired, if the phase conductor voltage minus DC link voltage is lower than a fixed threshold.
Thereby an almost constant voltage time area is applied to the series connection of phase
conductor and DC link capacitor. The charge of the DC capacitor is done with current
pulses of approx. same level. This level depends on the inductance of the commutation
choke, the impedance of the power supply and the power supply voltage. The thyristors
are fired, if the DC link is charged to 50 V difference between peak power supply voltage
and DC link voltage and there is a potential drop in blocking direction. The thyristor shows
a behavior like a diode.
HINWEIS!
Please check first if it is a device with the old charge circuit (see ZPage 226–).
Should it be such a device of the sizes 3 to 6, then it is to consider that the maximum
permitted capacity on the DC link (device internal capacity plus external capacity) has
not to be larger than 20 mF.
The time for a charge sequence depends on the height of the charging current pulses and
also the height of the internal and external capacity (see ZTable of charging times– on
page 228). After 20 seconds the charging is discontinued.
For the charging function the device must be connected to a power supply with clockwise
rotating field. No charging is started in case of counterclockwise rotating field. In rare cas-
es a counterclockwise rotating field can cause an abrupt charging and a tripped fuse.
No charging is started at failure of one or two mains phases.
The external chargeable capacity is not limited because the height of the loading current
of the DC link capacitor is approx. constant. But the time until the complete charge of the
DC link is increased proportional to the capacity, that has to be charged. Error 089 („pow-
er unit not ready-to-operate“ is generated, if the charging is not finished after 20 s.
20s
Maximum external capacity = built in capacity ------------------------------------------------------------------------------- – 1
Charging time according table
20s
= 1880µF ------------ – 1 = 92mF
0.4 s
Following incompatibilities result because of charging and must be checked by the user
operating devices with the new current-controlled charging-method.
m Charging time: Adapt timeout values in master-control to avoid possible error messag-
es because of not in time ready-to-operate signal.
m Ensure clockwise-rotating-field. The device does not identify the direction of the rotat-
ing field.
In case of a counter-clockwise-rotating-field no charging is done, after 20 s the attempt
of charging is stopped and error 089 (power unit not ready-to-operate) is generated.
In rare cases a counterclockwise rotating field can cause an abrupt charging and a
tripped fuse.
For error correction two power supply phases must be exchanged, e. g. the cables
connected to 1U1 and 1V1. The error is corrected, assumed there is no other error.
The advantages of the current-controlled charging are (in short):
m The maximum chargeable DC link capacitance is higher than without the current-con-
trolled charging.
m The dependency of the DC link capacitance on the charging current is reduced. The
self-protection level of the device against incorrect dimensioning is improved.
Basic information
DANGER!
Risk of fatal injury from electrical current!
Inevitably, when operating this electrical device, certain parts of it are energized with
hazardous voltage.
Therefore:
m Pay heed to areas on the device that could be dangerous.
WARNING!
Risk of injury due to improper fault correction!
Therefore:
m Only qualified personnel may work on this device!
m Personnel that work with the b maXX device must be trained in the safety regula-
tions and the handling of the device, and be familiar with the correct operation of
it. In particular, reacting to error indications and conditions requires that the oper-
ator must have special knowledge.
A survey of the most important monitoring functions and the generated warning/error
messages you will find in the following table. How to identify the error is explained in
ZFault detection– from page 234.
Threshold adjustable
Reaction adjustable
limit in parameters
Activation by
Adjusting of
parameter
Reaction
Warning
Error
Monitoring function Warning/error
Threshold adjustable
Reaction adjustable
limit in parameters
Activation by
Adjusting of
parameter
Reaction
Warning
Error
Monitoring function Warning/error
Ground fault This monitoring function checks, if there is a short-circuit between the motor terminals and
the ground. If a short-circuit is detected, there is immediately a pulse inhibit.
This monitoring function doesn’t exist by BM441X and BM442X.
Overcurrent This monitoring function checks, if the motor current is greater than 1.3 x output peak cur-
rent. It serves as „Disaster prevention“ in case of an output-sided short-circuit.
DC link This monitoring function checks the voltage of the DC link. In case the voltage is below a
value, which was internally specified (about 50 V under the set value), the warning DC
link undervoltage is generated by the controller. In case the voltage exceeds an adjusted
value about 820 V, the error „DC link overvoltage“ is signaled by the controller and the
pulses are inhibited immediately.
Overload This monitoring function checks the current calculated load thereupon, if the power unit
monitoring can provide the peak current at the moment. In case the peak current is not possible, the
message „Power unit overload“ is generated.
Temperature This monitoring function checks the temperature in the internal space of the device.
device m In case the temperature is higher than the warning threshold, the controller generates
internal space a warning.
m In case the temperature is too high, the pulses are inhibited immediately.
Temperature This monitoring function checks the temperature of the heat sink.
heat sink m In case the temperature is higher than the warning threshold, the controller generates
a warning.
m In case the temperature is too high, the pulses are inhibited immediately.
Only for If the set temperature threshold 1 is exceeded, then the warning „Temperature threshold
KTY84 and PT1000 1 exceeded“ is generated by the controller.
sensor
If the set temperature threshold 2 is exceeded, then the warning „Temperature threshold
2 exceeded“ is generated by the controller.
If the temperature falls below the minimum measurable value, or if a short circuit occurs
at the sensor, then the error message „Temperature sensor short circuit“ is generated.
If the temperature exceeds the maximum measurable temperature, or if the sensor is not
connected, then the error message „Temperature sensor not connected“ is generated by
the controller.
For all If the threshold set (type-specific) in the temperature switch or in the sensor is exceeded,
sensors then the error message „Over temperature“ is generated by the controller and the pulses
are inhibited immediately.
Position controller This monitoring function checks the position deviation limit statical/dynamical. In case the
position deviation error is statical/dynamical greater than the set position deviation error
limit, there is an error message „position deviation error statical“ and „position deviation
error dynamical“. After monitoring time (position deviation time), additionally an error
message is generated and the pulses are inhibited immediately.
Safety relay This monitoring function checks if the safety relay is ready and if the control voltage in
order to activate the safety relay is connected. In case of an error the controller either gen-
erates an error or a warning, depending on, if the pulse enable is active or not.
Blocking This monitoring function checks the motor speed and the motor current.
monitoring If, for the period of time „blocking monitoring time“, the following two conditions are ful-
filled, the error/warning „drive blocked“ is generated by the controller and the pulses are
inhibited immediately.
m Motor speed = 0
m The motor current which is supplied by the device is equal to the set motor limit current
(current limit).
LED H4 The occurrence of an error state is signalized by the lighting up of the red LED H4 on the
front side of the housing of b maXX 4000 devices.
NOTE!
If warnings or errors occur without error reaction the LED H4 „error“ flashes. Only er-
ror messages with error reaction are displayed by constantly lighting up.
7-segment display Additionally the error code is shown via the 7-segment display on the front side of the
housing (not BM4XXX - XXX - XX0XX and BM4XXX - XXX - XX1XX).
By the displayed code the error message can be determined with help of ZError param-
eters, error messages, error reactions– from page 240. The displayed error is without ex-
ception an LEVEL 2 error (P0201 - P0216).
The display of an error code starts therewith, that „F“ is displayed for 1.5 s. Then the three
characters of the error code are displayed. The separate characters are displayed for
about 0.8 s, interrupted by a short break. If there are other errors, these are displayed in
the same manner. The procedure is repeated as soon as all errors were displayed.
Example: Error 125 and 91 are generated:
NOTE!
The controller software version and the operating software version must be compat-
ible to use ProDrive with all functions.
In case the software version of the controller and the ProDrive version is not compatible,
following message is displayed (also see online help ProDrive):
NOTE!
Please contact Baumüller Nürnberg GmbH or visit our website www.baumueller.de
for download the latest version of ProDrive, if the controller software version is not
available in your ProDrive version.
Start screen
NOTE
If you are not able to start the motor, although the red LED H4 is not lighting up and
although the LED H2 is lighting up green, check the parameterization of the
b maXX 4000 with the parameter list in ProDrive.
Error possibilities are e. g.: torque limit = 0 has been set or notch position is not cor-
rect (also see parameter manual b maXX 4000).
If no LEDs are lighting up on the front side of the device, check the 24V supply.
Error memory From firmware 3.11 onwards an internal error memory exists to read out errors by a high-
er-level open-loop control. All occurrent errors which lead to an error response of the drive
are saved chronologically in this error memory.
A read access to the error memory is done element by element with an index parameter
(P0258) and a value parameter (P0259).
The error memory will be deleted completely at error acknowledgment (bit No.7 = 1 in
control word).
For a further description see parameter P0257 in the Parameter Manual.
Error display If an error appears, the according definite error message is displayed within a short time
in ProDrive in the menu „device manager“ and on the 7-segment display.
NOTE!
The device is provided with predefined error reactions. You are able to set the error
reaction of the device in „Depending on settings“ in the column „Reaction“ marked er-
ror messages. An exception here are errors, which have to have an immediate pulse
inhibit as a consequence. These can not be changed due to safety reasons.
If the red error LED is lighting up, there is at least one error.
There are several methods to reset errors:
m Via ProDrive (from FW 3.07):
Button „Quit errors“ (either in the dialog box „Device manager“ or on the page “Device
manager“.
That means, that you inform the device, that you have noted the error, that you have
removed it or that you want to pass over it. Due to error reset all error messages are
reset. An individual error reset is not possible. The button Quit errors causes a resetting
of the error, in case the cause for the error message exists no longer.
2nd level Order of the error messages see survey (ZFigure 103– on page 240).
3rd level 2nd level error messages are displayed on the 7-segment display in ProDrive.
NOTE!
3rd level errors are only displayed in ProDrive separated by a decimal point from the
corresponding 2nd level error.
e.g.:
Motor error 102: Group error find notch position (2nd level)
Find notch position error 102.64: Drive moved more than 4 times delta angle.
(3rd level)
In the column „Reaction“ the reaction of the system to the error is shown:
m „IS“ = pulse inhibit;
m „adjustable“ = the error reaction can be set via ProDrive (Window „Drive management“,
toolbar button „Error reaction“).
m „no reaction“ means, the drive is continuing to work and the red error LED is blinking.
146 Encoder module 1 not available IS Check if the correct encoder is connected to slot A
147 Encoder module 2 not available IS Check if the correct encoder is connected to slot B
148 Encoder module for measured value storage IS Install the encoder module
not available
149 When using a resolver no measured value stor- IS Use a SinCos- or incremental encoder
age possible
150 Triggering not possible, no incremental encoder IS Use for this option an incremental encoder
151 Digital I/O module not available IS Install the digital I/O module
152 Incremental encoder emulation is require but IS Install the incremental encoder emulation module
not available
153 Encoder module 1 is required for incremental IS Install the encoder module on slot A
encoder emulation but not available
154 Encoder module 2 is required for incremental IS Install encoder module on slot B
encoder emulation but not available
155 Initialization error of the incremental encoder IS Restart b maXX 4000
emulation module
156 Incremental encoder emulation module hard- IS Restart b maXX 4000, exchange the module at repeti-
ware signal error tive error messages
157 Error incremental encoder emulation module IS Use for this option an incremental encoder
158 SSI encoder emulation module is not available IS Install SSI encoder emulation module
159 Error in set value source encoder 1 or encoder IS See error messages encoder 1 or 2
2
NOTE!
3rd level errors are only displayed in ProDrive separated by a decimal point from the
corresponding 2nd level error (see ZFigure 103– on page 240), exception error pow-
er supply monitor P036 (see ZSeite 253–).
e.g.:
Motor error 102: Group error
Find notch position error 102.64: Drive moved more than 4 times delta angle.
(3rd level)
2 encoders can be connected to a b maXX 4000 at most. Accordingly errors can appear
in function module 1 and function module 2. The term „encoder 1“ or „encoder 2“ in the
column „device part“ stands for one of the five currently existing encoder module types.
9.4.3 Warnings
Basic information
DANGER!
Risk of fatal injury from electrical current!
Inevitably, when operating this electrical device, certain parts of it are energized with
hazardous voltage.
Therefore:
m Pay heed to areas on the device that could be dangerous during the electrical in-
stallation.
m Pay heed to areas on the device that could still be electrically energized after op-
eration.
WARNING!
Risk of injury due to improperly performed maintenance work!
Improper maintenance can lead to severe personal injury and material damage.
Therefore:
m Before beginning work, make sure that there is enough space for mounting.
m Make sure that the mounting area is kept clean and orderly. Parts and tools that
are loosely stacked or lying around are a potential accident source.
If the prescribed environmental conditions are adhered to, then the device is mainte-
nance-free. For the prescribed environmental conditions see ZRequired environmental
conditions– on page 55.
The most important prescribed environmental conditions are:
m Dust-free environmental air
m Temperature: Min. 5 °C to max. +55 °C
m Relative humidity: 5% to 85%, no condensation
m Installation altitude: From 1000 m and higher derating
Daily Basic check points as to whether discrepancies have occurred during operation:
inspection: m Does the motor work as desired?
m Is the operating environment normal?
m Is the cooling system working normally?
m If an unusual vibration or noise is noticed during operation.
m Does the motor overheat during operation?
Regularly sched- Before checking, switch off the input voltage and wait until the device's capacitors have
uled inspection: discharged.
DANGER!
Risk of fatal injury from electrical current!
Stored electric charge.
Discharge time of the system = discharge time of the device with the longest DC link
discharge time in the DC link connection.
Refer to ZElectrical data basic units– from page 63.
Therefore:
m Do not touch before taking into account the discharge time of the capacitors and
electrically live parts.
m Heed corresponding notes on the equipment.
m If additional capacitors are connected to the DC link, the DC link discharge can
take a much longer time. In this case, the necessary waiting period must be deter-
mined or a measurement made as to whether the equipment is de-energized. This
discharge time must be posted, together with an IEC 60417-5036 (2002-10) warn-
ing symbol, on a clearly visible location of the control cabinet.
m Environmental condition
Check points Methods and criteria Inspection intervals
Daily Semi- Annu-
annu- ally
ally
Check environmental temperature, humidity and Visual inspection and measurement of the environmen- O
vibrations. tal conditions, comparison with standard values.
Check whether dust, oil or drops of water appear.
Check whether there are hazardous objects in the Visual inspection O
vicinity.
m Voltage
Check points Methods and criteria Inspection intervals
Daily Semi- Annu-
annu- ally
ally
Check the voltage of the power supply system and Measurement and comparison with standard values. O
the control circuits
m Mechanical parts
Check points Methods and criteria Inspection intervals
Daily Semi- Annu-
annu- ally
ally
Are there any abnormal noises or vibrations? Visual and audio check O
Are there any loose screws? Tighten the screws. O
Are there any bent or damaged parts? Visual inspection O
Have there been any color changes due to over- Visual inspection O
heating?
Are there any dust or dirt deposits? Visual inspection O
m Power supply
Check points Methods and criteria Inspection intervals
Daily Semi- Annu-
annu- ally
ally
Are there any missing or loose screws? Replace the screws or, respectively, tighten them. O
Is there any deformation, cracking, damage or Visual inspection O
color change on the device as a result of overheat-
ing or aging?
Are there any dust or dirt deposits? Visual inspection O
10.4 Repairs
11.1 Cabling
6) Connection lugs (current bars). Position see ZFigure 87– on page 186
Screw maximum two cable lugs to the current bar - one on the front side, one on the
reverse side of the bar.
7)
Connection lugs (current bars). Position see ZFigure 90– on page 189
At connection cross-section 95 mm2,Cable lug width max. 25 mm:
Screw maximum two cable lugs to the current bar - one on the front side, one on
the reverse side of the bar.
At connection cross-section 185 mm2,Cable lug width max. 35 mm:
Screw two cable lugs to the current bar at maximum- one on the front side, one on
the reverse side of the bar.
6)
Connection lugs (current bars). Position see ZFigure 90– on page 189
At a connection cross-section of 95 mm2, cable lug width max. 25 mm:
Screw maximum two cable lugs to the current bar - one on the front side, one on
the reverse side of the bar.
At a connection cross-section of 185 mm2, cable lug width max. 35 mm:
Screw two cable lugs to the current bar at maximum- one on the front side, one on
the reverse side of the bar.
A pre-assembled cable is available as a spare part, see ZCable RS232– on page 304.
1 Use the following materials:
m Cable: LIYCY 6x2x0.14 mm2
m D-sub connectors, 9-pin, female, cabinet plastics metalized
m D-sub connector, 9-pin, male, cabinet plastics metalized
2 Connect the cable shield with the cabinet and with the shield of the D-sub connector
NOTE!
The fuse specification are valid for basic units, only.
A distinction is made between protecting the power supply cables and protecting the de-
vice. To fulfill CE specifications – here in particular EN 60204-1 – fuse the power supply
cables.
.
NOTE!
Approved, UL-listed safety fuses and/or circuit breakers must be used in UL-autho-
rized systems.
Cable protection Use safety fuses of the operating class gL DIN VDE 0636-201 / IEC 60269-2-1 / HD
630.2.1 54 or circuit breaker triggering characteristic K, in accordance with DIN VDE
0636-201 / IEC 60269-2-1 / HD 630.2.1 54, to protect the cable. These fuses protect
against overloads and consequential damage from defects, for example as a result of fire.
However, they cannot prevent a device from being extensively destroyed in case of a
short circuit or ground fault in the DC link.
Carry out the fusing in accordance with EN 60204-1 („Electrical Equipment of Machines“).
Dimension the cable fuse based on the cross-section of the power supply cable used, and
in accordance with the respective applicable national standards and local regulations.
The current-carrying capacity of the cables is specified in Table 5 of EN 60204-1. For your
application, the corresponding value must still be determined based on the standard itself,
i.e. taking into account the cable routing.
NOTE!
Use suitable fuses with the tripping characteristic gL or gR.
Device protection Use semiconductor fuses with the tripping characteristic aR (DIN VDE 0636-201 / IEC
60269-2-1 / HD 630.2.1 54). Connect these in series with the cable protection fuses. In
the event of a short circuit, these protect the line-side rectifier unit circuit on the input side
against complete destruction, in order that it is possible to repair the device.
Dimension suitable device protection fuses depending on peak current and the maximum
load integral i2toff.
25A/690V: 170M1561 u
Size
1 40A/690V: 170M3808
Ferraz Shawmut 000 16A/690V: 6,9 URD 000 PV 016 20A/690V: 6,9 URD 000 PV 020
Size
Ferraz Shawmut 000 16A/690V: 6,9 GGR 000 PV 016 20A/690V: 6,9 GGR 000 PV 020
00 35A/690V: 2047720/35A
Size
1 40A/690V: 170M3808
Ferraz Shawmut 000 20A/690V: 6,9 URD 000 PV 020 25A/690V: 6,9 URD 000 PV 025
32A/690V: 6,9 URD 000 PV 032 40A/690V: 6,9 URD 000 PV 040
Size
Size
32A/1000V: 170M2675
1 40A/660V: 170M3808
Ferraz Shawmut 000 16A/690V: 6,9 URD 000 PV 016 20A/690V: 6,9 URD 000 PV 020
25A/690V: 6,9 URD 000 PV 025 32A/690V: 6,9 URD 000 PV 032
Size
32A/660V: 170M1562 u
32A/690V: 170M2695
Size
32A/1000V: 170M2675
1 40A/660V: 170M3808
Ferraz Shawmut 000 20A/690V: 6,9 URD 000 PV 020 25A/690V: 6,9 URD 000 PV 025
32A/690V: 6,9 URD 000 PV 032 40A/690V: 6,9 URD 000 PV 040
Size
00 25A/690V: 2047720/25A
Size
40A/1000V: 170M2676
63A/660V: 170M3810
Ferraz Shawmut 000 25A/690V: 6,9 URD 000 PV 025 32A/690V: 6,9 URD 000 PV 032
40A/690V: 6,9 URD 000 PV 040 50A/690V: 6,9 URD 000 PV 050
Size
NOTE!
Please note, that the fuses must be adapted, if a BM443X generation 1 is replaced
by a BM443X generation 2 (ZExplanation version code– on page 130).
Operation of BM443X generation 1 and generation 2 in combination see ZMix mode
BM443X generation 1 and 2– on page 124.
Semiconductor fuses aR (device) BM443X generation 2 see next page.
1 63A/690V: 2021120/63A
Size
m Semiconductor fuses aR
(device) BM443X generation 1, design type NH
Size
00 100A/690V: 3NE1021-2 U
Size
Size
125A/690V: 170M2701 1)
Size
1)
For the connection of an additional DC link capacitance or the parallel operation of up to five devices suitable,
that means the DC link of several devices is connected with at the same time existent power supply connec-
tion of every device.
125A/1000V: 170M2682
Size
1)
For the connection of an additional DC link capacitance or the parallel operation of up to five devices suitable,
that means the DC link of several devices is connected with at the same time existent power supply connec-
tion of every device.
Size
Size
Size
1 250A/690V: 2021120.250 U
Size
160A/690V: 170M2702
315A/690V: 170M5883 1)
3 350A/690V: 170M6080 1)
Size
1) For the connection of an additional DC link capacitance or the parallel operation of up to five devices suitable,
that means the DC link of several devices is connected with at the same time existent power supply connec-
tion of every device.
3 500A/660V: 170M6808 1)
Size
1)
For the connection of an additional DC link capacitance or the parallel operation of up to five devices suitable,
that means the DC link of several devices is connected with at the same time existent power supply connec-
tion of every device.
Size
Size
Size
Size
Size
Size
NOTE!
The semiconductor fuses can be used for the device BM4755 provided that:
m The total DC link capacitance of all connected devices is lower than 20 mF
m The used mains filter and power choke fulfill the Baumüller specifications.
3 500A/660V: 170M6808 U
Size
450A/690V: 170M58861)
450A/690V: 170M6082 1)
350A/690V: 2021234/350AU1)
Size
1)
For the connection of an additional DC link capacitance or the parallel operation of up to five devices suitable,
that means the DC link of several devices is connected with at the same time existent power supply connec-
tion of every device.
00 225A/900V: 170M2685 1)
630A/660V: 170M58121)
Size
Size
1)
For the connection of an additional DC link capacitance or the parallel operation of up to five devices suitable,
that means the DC link of several devices is connected with at the same time existent power supply connec-
tion of every device.
Size
550A/690V: 170M5811D U
Size
2 350A/690V: 2021134.350 U
Size
Size
HINWEIS!
The semiconductor fuses can be used for the device BM4766 provided that:
m The total DC link capacitance of all connected devices is lower than 20 mF
m The used mains filter and power choke fulfill the Baumüller specifications.
3 550A/660V: 170M6809 U
3 560A/690V: 6,9URD2PV0560
2 450A/1000V: 3NE3333 U
Size
DANGER!
Danger to life from electric current!
Parts, which are under tension are perilous. Damage in isolation or damage of single
parts can be can be highly dangerous.
Therefore:
The use of semiconductor fuses is obligatory at the power supply connection of
BM447X devices. Semiconductor fuses are required in the connection between
brake resistor and device except the user assures the short-circuit protection of re-
sistor and cable.
BM4472:
Size
NOTE
The 710 A fuse is recommended if the BM4472 is operated constantly at rated power
and/or peak power is required frequently, because the 710 A fuse provides higher
thermal reserve compared with 500A/560A fuses and therefore the risk of fuse trip-
ping at normal run (without real error) is reduced.
BM4473, BM4773:
Size
BM447X, BM477X
Size
HINWEIS!
If the current consumption is lower than 4 A, several connections can be protected
together with a UL-listed fuse (release current max. 4 A).
Line filters are combinations of capacitors, chokes, resistors and voltage limiters, which
reduce the electromagnetic influence of environment. Further information see Instruction
handbook Mains Filter BFN, 5.09010.
TN/TT systems
BFN 3-1-... -001 0007 0016 0030 0042 0056 0075 0100 0130 0180
Max. input supply voltage 3 x 480 VAC +10 %,
50/60 Hz
Rated current 7A 16 A 30 A 42 A 56 A 75 A 100 A 130 A 180 A
(at TB = 50 °C)
Peak current 1.5 x IN for < 1 min per hour
(at TB = 50 °C)
Current derating
ambient
I = I rated 85 – --------------------
35°C
EPCOS B84143A0150R410
Max. input supply voltage 3 x 480 VAC +10 %,
50/60 Hz
Rated current 150 A
(at TB = 50 °C)
Peak current 1.5 x IN for < 1 min per hour
(at TB = 50 °C) 2.5 x IN for < 1 min per hour
Test voltage line - line: 2240 VDC / 2 s
line - housing: 2720 VDC / 2 s
Connection L1/L2/L3: safe-to-touch screw terminals
PE: bolt M10
Maximum connection 95 mm2
cross-section
Protection class IP 20
DANGER!
Risk of fatal injury due to high leakage current!
Therefore:
m The cross-section of the protective ground conductor must be at least 10 mm2
(EN 61800-5-1, Chapter 4.3.5.5.2).
NOTE!
The rated current of the filters that are used must be larger than or have same RMS-
value as the actual power suppl.y current (actual power supply current = RMS-value
of the power supply current during the entire cycle time of the drive). During short-
time operation (S3), the RMS-value is calculated as follows:
T
1
I rms = --- i 2 dt
T
0
TT/TN system
NOTE!
No power chokes are necessary for the devices BM441X, BM4422, BM4423,
BM4424 and BM4425.
UL certified power chokes must be used in UL compliant machines/systems.
Current Select the power chokes dependent upon your application and based on the input rated
current. Take into account that the max. input current of the chokes may not lead to sat-
uration.
Inductance Select the power chokes depending on the short-circuit voltage of the power supply, so
that the required inductance of the power supply see ZRequirements to the energy supply
/ supply system– on page 52 is adhered to.
NOTE
There is a different short-circuit voltage with the same choke at 60 Hz than there is at
50 Hz; according to the formula uk = (LIN3) / UN (with = 2f) the short-circuit
voltage that would result at another power supply frequency can be calculated.
NOTE
The rated inductance is constant up to 1.1 times of rated current. You can expect that
the inductance is reduced, if the current flow through the commutation choke is higher
than this value. If it is important for the application, that the commutation inductance
is equal its rated value when for longer time (e. g. with 30 s or 60 s) peak current at
peak power is needed, chose a commutation choke with a peak current smaller or
equal of the 1.1 times of the rated value of the commutation choke.
If you have any doubt selecting a commutation choke for a specific application,
please contact the responsible sales representative of Baumüller.
NOTE
At installation heights higher than 1000 m above MSL the current must be reduced
for 10 % per 1000 m.
At operation temperatures from 40 °C up to 55 °C the current must be reduced for
1 % per °C
The listed chokes are specified for the operation at 400 V /50 Hz or 480 V / 60 Hz.
At a power supply voltage of 400 V and a frequency of 50 Hz at rated current the chokes
have a short-circuit voltage > 3% of the power supply voltage.
UL approval
The chokes are design-tested in accordance with UL (e.g. UL1561) and signified by the
ú“ symbol.
Irated AC Induc- Type code Part No. Part No. For devices
tance
type -101, type -102,
connection connection
copper bar terminal
24 A 1,22 mH BK3-0024/0029 - 456715 BM4426
53 A 0,55 mH BK3-0053/0070 - 456717 BM4632
82 A 0,36 mH BK3-0082/0100 - 456718 BM4641
95 A 0,31 mH BK3-0095/0116 - 456720 BM4642
125 A 0,23 mH BK3-0125/0153 - 456722 BM4650
160 A 0,18 mH BK3-0160/0196 - 456723 BM4651
190 A 0,15 mH BK3-0190/0232 456725 - BM4652
240 A 0,12 mH BK3-0240/0294 456728 - BM4661
285 A 0,10 mH BK3-0285/0350 456729 - BM4662
Irated AC Induc- Type code Part No. Part No. For devices For devices
tance
type -001, type -002,
connection connection operation with operation with
copper bar terminal peak current rated current
NOTE!
In case you don’t use an optically decoupled interface cable, the cable shield has only
to be connected to the connector housing at the controller connector.
The company Baumüller Nürnberg GmbH recommends the usage of optically decou-
pled transmitters (e.g. from the company Ratioplast part no. 901SV232C6095 and
part no. 901SV232T6095)
m CANopen®-connection cables:
m Cable connector and accordingly encoder cable for resolver, sine-cosine encoder with
Hiperface® interface and square wave incremental encoder
15-pin D-sub connector/12-pin encoder plug (assembled - alternatively trailing cable,
length see selections, further lengths on request).
SpeedTec
not trailing cable trailing cable trailing cable
Length Part no. Part no. Part no.
1m 243601 - 448941
2m 211338 - 448943
3m 219333 246658 448944
4m 231166 243379 448945
5m 209879 239540 448948
6m 220197 242954 448946
7m 216455 - 448947
8m 220429 239541 448949
10 m 210052 239542 448956
15 m 215716 239543 448961
20 m 218568 239544 448967
25 m 218569 239545 448970
30 m 217094 239546 448971
35 m 216444 239547 448973
40 m 217095 240520 448976
45 m 217567 240521 448978
50 m 217568 240522 448979
55 m 217569 244033 448981
60 m 217570 245484 448982
70 m 232088 - -
In case the cable is produced self, please use the instructions stated below:
NOTE
The cable connector must be produced according to the illustration which is shown above!
In case there is another assignment of the pins, the cable will not operate and defects as well
as at the encoder module and also at the encoder can appear!
SpeedTec
not trailing cable trailing cable trailing cable
Length Part no. Part no. Part no.
2m 383152 393889 448816
3m 383923 369864 448817
5m 393885 394014 448818
7m 389445 389807 448819
8m 380138 393890 448820
9m 389446 389808 448821
10 m 393886 393891 448822
15 m 388505 393892 448823
17 m - 371494 448824
20 m 388418 393893 448825
25 m 393887 393894 448826
30 m 393888 380358 448827
35 m 387958 391216 448828
40 m 382006 382005 448830
50 m 388419 378022 -
70 m 384473 - -
90 m 387391 - -
NOTE
With this encoder cables no evaluation of the motor temperature sensor is possible!
Use the instructions stated below, in order to make the cable self:´´
NOTE
The cable connector must be produced according to the illustration which is shown
above!
In case there is another assignment of the pins, the cable will not operate and defects
as well as at the encoder module and also at the encoder can appear!
BM444X, BM464X
BM447X, BM477X
BM4413 1)
BM4413 2)
BM4414 1)
BM4414 2)
BM4412
BM4412
BM442X
Part No.
Design cover (yellow) small X - X - - - - - - - 351209
Design cover (yellow) wide - X - X X X X X X X 351210
Connector „Motor“ X X X X - - - - - - 354746
Phoenix: GIC 2,5/4-ST-7,62, 1828825
Connector „1C1/1D1“ or „1C1/1D1/Ba“ X X X X - - - - - - 354746
Phoenix: GIC 2,5/4-ST-7,62, 1828825
Connector „Ba+/Ba-“ - - X X - - - - - - 381872
Phoenix: GIC 2,5/2-ST-7,62
Connector „Power supply“ X X X X - - - - - - 309377
Phoenix: GMSTB 2,5/4-ST, 1766903
Wieland: 8313B/4 OBGN, 25.360.3453.7
Connector X3 X X X X X X X X X X 354874
Phoenix: FK-MCP 1,5/6-ST-3,81, 1851083
Connector X100 and X101 X X X X X X X X X X 354810
Wieland: 8513 BFK, 25.630.3653.0
Connector X102 3)4) - - - - - X X X X X 363845
Phoenix: FK-MCP 1,5/4-ST-3,81, 1851067
Wieland: 8513 BFK, 25.630.3453.7 X X X X X - - - - - 354809
4)
Connector X103 - - - - - X X X X X 363845
Phoenix: FK-MCP 1,5/4-ST-3,81, 1851067
1)
BM441X - XXX - 01
2)
BM441X - XXX - 02
3)
BM44XX - XX1, BM44XX - XX3
4)
BM44XX - XX2, BM44XX - XX4
h Refer to ZSafety– from page 15 and the information in ZTransport and Packaging–
from page 141.
The shutdown of the device may only be carried out by for this qualified personnel.
DANGER!
Risk of fatal injury from electrical current!
Stored electric charge.
Discharge time of the system = discharge time of the device with the longest DC link
discharge time.
Therefore:
m Do not touch electrically live parts before taking into account the discharge time of
the capacitors.
m Assure, that all electric connections are current-free and are safe against switch-
on.
m Before working, check at the electrical connections with suitable measuring devic-
es, that the connections are off-circuit.
m Remove the connections not until the safe isolation from supply has been checked.
m If additional capacitors are connected to the DC link, the DC link discharge can
take a much longer time. In this case, the necessary waiting period must itself be
determined or a measurement made as to whether the equipment is de-energized.
This discharge time must be posted, together with an IEC 60417-5036 (2002-10)
warning symbol, on a clearly visible location of the control cabinet.
The personnel, who is appointed to setting out of operation, must have the required
knowledge and instructions, which is necessary for an execution according to the rules.
Select the personnel in such a way, that the safety instructions, which are mounted to the
device and its parts as well as to the connections, are understood and applied to.
12.3 Shutdown
12.4 Demounting
NOTICE!
Note sharp edges.
In case, while installing, you lift a device with unprotected hands, fingers/palm can be
cut. If the device falls off, your feet can be cut up.
Therefore:
m Ensure that only qualified personnel, who are familiar with the safety notes and as-
sembly instructions, demount this device.
The device is maintenance-free. If you keep to the environmental conditions during the
entire period of storage, you can assume, that the device will not be damaged. In case
the environmental conditions during storage are not kept, you should assume that the de-
vice is damaged after storage.
CAUTION!
Property damage because of incorrect storage conditions
Incorrect storage can damage/destroy the device.
Therefore:
Assure, that the environmental conditions are kept during the entire period of storage:
m Climatic category 1K4
m Temperature range -25 °C to +55 °C
CAUTION!
Recommissioning without forming of the capacitors.
From six months storage period on, the capacitors are destroyed during commission-
ing, if they are not formed beforehand
m Reform the DC link capacitors:
n by supplying the device ready-to-operate for at least one hour with supply volt-
age
n but do not transmit a pulse enable during this time.
m Consider, that it is imperative, to connect the accordingly prescribed line commu-
tating reactor for this forming procedure. Devices, where no line commutating re-
actor is necessary can directly be supplied with mains voltage.
12.6 Recommissioning
CAUTION!
Recommissioning without forming of the capacitors.
From six months storage period on, the capacitors are destroyed during commission-
ing, if they are not formed beforehand
m Reform the DC link capacitors:
n by supplying the device ready-to-operate for at least one hour with
supply voltage
n but do not transmit a pulse enable during this time.
m Consider, that it is imperative, to connect the accordingly prescribed line commu-
tating reactor for this forming procedure. Devices, where no line commutating re-
actor is necessary can directly be supplied with mains voltage.
NOTE!
Baumüller products are not subject to the scope of application of the EU's Waste
Electrical and Electronic Equipment Directive (WEEE, 2012/19/EU). Hence,
Baumüller is not obligated to bear any costs for taking back and disposing of old de-
vices.
DANGER!
Risk of fatal injury from electrical current!
Stored electric charge.
Discharge time of the system = discharge time of the device with the longest DC link
discharge time in the DC link connection.
Refer to ZElectrical data basic units– from page 63.
Therefore:
m Do not touch before taking into account the discharge time of the capacitors and
electrically live parts.
m Heed corresponding notes on the equipment.
m If additional capacitors are connected to the DC link, the DC link discharge can
take a much longer time. In this case, the necessary waiting period must be deter-
mined or a measurement made as to whether the equipment is de-energized. This
discharge time must be posted, together with an IEC 60417-5036 (2002-10) warn-
ing symbol, on a clearly visible location of the control cabinet.
CAUTION!
Danger due to sharp edges.
If the device is lifted with unprotected hands during deinstallation, palms or fingers
can be cut. If the device falls, feet could be injured.
Therefore:
m Ensure that only qualified personnel, who are familiar with the safety notes and as-
sembly instructions, mount this device.
WARNING!
Danger of physical impact!
Secure device against falling down.
Therefore:
m Take suitable measures, such as supports, hoists and assisting personnel, to en-
sure that device cannot fall down.
m Use appropriate means of transport.
NOTICE!
Avoid polluting the environment as a result of improper disposal.
Therefore:
m Only dispose in compliance with the health and safety regulations.
m Take heed of any special local regulations. If you are unable to directly ensure safe
disposal yourself, commission a suitable disposal contractor.
m In the event of a fire, hazardous substances could possibly be generated or re-
leased.
m Do not expose electronic components to high temperatures.
m Beryllium oxide is used as inner insulation, for example for various power semicon-
ductors. The beryllium dust that is generated upon opening is injurious to the
health.
Do not open electronic components.
m Dispose of capacitors, semiconductor modules and electronic scrap as special
waste.
Ensure that the disposal is handled in compliance with the disposal policies of your com-
pany, as well as with all national regulations of the responsible disposal facilities and au-
thorities. In case of doubt, consult the bureau of commerce or environmental protection
authority responsible for your company.
are developed, designed and manufactured in accordance with the EMC Directive 2014/30/EU and the Low
Voltage Directive 2014/35/EU.
Applied harmonized standards:
Standard Title
DIN EN 62061:2010-05 Safety of machinery - Functional safety of safety-related electrical, electronic and programmable
electronic control systems
DIN EN 61800-5-1:2008-04 Adjustable speed electrical power drive systems.
Part 5-1: Safety requirements. Electrical, thermal and energy
DIN EN 61800-5-2:2008-04 Adjustable speed electrical power drive systems.
Part 5-2: Safety requirements. Functional
DIN EN 61800-3:2012-09 Adjustable speed electrical power drive systems.
Part 3: EMC requirements and specific test methods
Nuremberg / 14-Jun-2016
Location / Date
Nuremberg / 14-Jun-2016
Location / Date
Subject to change of this declaration of EC conformity without notice. Actual valid edition on request.
In order to avoid danger for persons, for example operators, service- and maintenance techni-
cians, the machine must be kept in a safe state (safe stop), while taking action in the dangerous
area of the machine. Therefore a reliable prevention of an unexpected starting is required (Ma-
chine Directive 06/42/EG, attachment I, 1.2.4; EN ISO 12100-1; EN 60204-1, 5.4; EN 62061;
EN 61800-5-2). Unexpected starting causes a risk for persons, because of its unexpected oc-
currence (EN 292-1).
Besides the transmission of the enable state into the operating state of the machine, the unex-
pected starting of the machine must be considered. This is the transmission from the safe stop
into an unsafe moving. Unexpected starting refers to an interruption of the control loop of the
machine. The drive achieves the maximum speed at maximum acceleration, due to its control.
The operator will not be able to leave the danger area or to remove his hand from the danger
area. Therefore, the drive must be kept safe „off-position“ with opened and electrical interlocked
safety devices. The motor must be in torqueless state. Thus, the motor cannot generate a dan-
gerous movement.
The prevention of an unexpected starting of the machine is reached with electrical separated
safety devices, e.g. contactors.
This is not state of the art, because the conventional operation in the power circuit of the drive
may cause unnecessary wear on the switching element and long response times in the ma-
chine.
Some machine types are not electrically isolated between the electrical connection of the drive
and the power supply. If, for example, a drive supplied by a power converter is stopped and
started again very often and in short intervals. The constant discharging and recharging of the
DC link represents a great stress for the parts and leads to disturbing delays and early failures
of the parts.
The integration of the protection function is more efficient for preventing an unexpected starting
directly into the inverter. Here, the drive is not isolated from the power supply. However, the
commutation of the power semiconductors is safety prevented in the inverter.
In Baumüller inverters of the b maXX 4000, this occurs by the safety relay, which switches the
power supply off for the IGBT control.
In the Baumüller converters of b maXX 4000 this is accomplished by the safety relay, which
switches the power supply off for the IGBT control.
The device models are available with one safety relay (BM4000 size 1 - 7) or with two safety
relays (BM4000, size 3 - 7). The version with one safety relay is shutdown path 1. The version
with double safety relay are the shutdown paths 1 and 2.
For a safe two-channel shutdown with one safety relay, a second shutdown path at the
Baumüller BM4000 controller LC3 is achieved via the pulse enable circuit of the controller. Ad-
ditionally the pulses for the IGBT control are disabled at this circuit.
Refer to ZC.2 Safe Torque Off (STO)– from page 330 for additional information.
Physical relationship
The precondition for starting an AC motor is the generation of a rotating field, which drives the
armature of the motor. When having variable-speed AC current drives, in the microprocessors
usually a complex pulse pattern is generated. Then the pulses are amplified and are used for
switching the power semiconductors. If no defined pulse pattern is available or the amplifying
connection is interrupted, e. g. by switching off the power supply with a relay (safety relay), then
a rotary field cannot be generated. An error at the pulse pattern generation therefore cannot lead
to a starting of the motor, as long as the second precondition, namely the interruption of the am-
plifying power supply is available and vice versa. The protection against unexpected starting is
reached by an electromechanical method which is superior to the electronics. This is reached
by a safe isolation, which is not executed in the load circuit.
Energy supply of the motor windings at a stop is reached by inhibiting the power semiconduc-
tors. Semiconductors can fail or can be started accidentally, due to electromagnetic interferenc-
es. The behavior of the shut down drive must be considered, in case of this error. The fail and
the accidental switching on of a single or of several power semiconductors at the same DC-link
pole, does not cause does not lead to an uncontrollable starting, as there is no current flow. If
an additional power semiconductor is enabled at another pole, current is able to flow through
the motor. If, thereby the DC link is directly short-circuited, the fuses which are upstreamed to
the converter are tripped, the motor doesn’t start. If the DC link is „short-circuited“ over a winding
of the motor, a magnetic field can be set up in the motor. If it is an asynchronous motor, then the
generated d. c. magnetic field cannot cause a movement of the rotor. By the permanent-mag-
netic synchronous motor the rotor will rotate into a notch position. The angular movement which
is covered is dependable of the choke ‘s position and the number of pole pairs of the motor. It
amounts to maximum 180°/number of pole pairs. Subsequently the enabled DC link operates
like a brake, this means after the ending of the movement the drive is in a blocked state. A start-
ing of the drive is impossible. If a machine with a synchronous motor is planned, the possible
movement must be considered, because it can lead to a dangerous movement. Therefore the
machine constructor must carry out a safety evaluation for the residual movement.
NOTE
The function is limited to the prevention of an unexpected starting. The switching of
the safety relay, while the rotor of the motor is rotating, causes an uncontrolled
„coasting“ of the machine. Braking with the converter is not possible.
DANGER!
Danger to life by electrical current!
Power supply voltage can be present at the motor and at the device, if STO / Safe
stop function is active.
Therefore:
m De-energize the device, as it would be done with a device without safety relay. The
device and the motor is not de-energized by the safety relay!
NOTE
There is no isolation from the supply system if the function STO/Safe stop is activat-
ed. There can be potential at the converter and at the motor. In the case of mainte-
nance-, service- and repair- works on electrical components of the drive system,
protection against dangers must be provided by other means (e. g. main switch).
NOTE
If the safety relay is switched off, it is not possible to use a ballast switch at BM441X
and BM442X.
NOTE
A device with safety relay is not a safe device. The device with safety relay does not
comply with the PL level according to ISO 13849 and SIL according to EN 61800, if
the part number does not start with „06“. This device is not certified for safety func-
tions!
NOTE!
Devices with the approval mark of TÜV Rheinland and the Safety label provide a cer-
tified safety function, only, refer to ZPage 29–.
1) Two-channel connection of the shutdown via 1 safety relay at the basic unit and the
pulse enable channel of the BM4000-controller LC3:
Device models BM4XXX-XXY-XXXXXRyy]-S01-XX
with Y= 1, 3 or 5 (devices with a safety relay):
Size 1 - 7
m PL-d according to EN ISO 13849-1
with the following parameters:
n Structure: cat 4
n MTTFd: high
n DC: low
m SIL 2 according to EN 62061 and 61508
with PFHDssD = 1.5 x 10-10
NOTE
The safety classifications are valid, if the following safety notes were consid-
ered and were complied with.
m The classification of the safety category applies only to the STO function.
m The following switching measures must be met to achieve the safety function:
n Two-channel connection of the shutdown via 1 safety relay and the pulse enable circuit of
the BM4000- controller LC3 for applications which require to minimize risks according to
PL-d or SIL 2.
n Two-channel connection of the shutdown via 2 safety relays for applications which require
to minimize risks according to PL-e or SIL 3.
1) Applications that require a minimizing risk according to performance level d (EN ISO 13849-
1) or SIL 2 (EN 62061) according to chapter ZC.2.1 Safety classifications and safety notes–
from page 330 must have 2 independent shutdown paths, which are used to shut down the
commutation in the power section of the inverter.
For this risk minimization the two-channel shutdown via 1 safety relay with feedback on the
basic unit and the pulse enable circuit of the BM4000 controller LC3 are implemented.
The following Baumüller inverters BM4XXX-XXY-XXXXX[Ryy]-S01-XX in combination with
the Baumüller BM4000 controller LC3 of the accordant device model have these shutdown
paths:
BM4XXX-XXY-XXXXX[Ryy]-S01-XX with Y = 1, 3, 5:
device model with one safety relay and a discrete pulse enable circuit (size 1-7)
2) Applications for a minimizing risk according to performance level e (EN ISO 13849-1) or
SIL 3 (EN62061) therefore need 2 independent shutdown paths, too.
The difference to 1) is that the two-channel shutdown must be implemented via two safety
relays in order to achieve a minimizing risk.
The Baumüller inverters of the b maXX of the device model
BM4XXX-XXY-XXXXX[Ryy]-S01-XX in combination with the Baumüller BM4000 controller
LC3 of the accordant device model are provided with these shutdown paths:
BM4XXX-XXY-XXXXX[Ryy]-S01-XX with Y= 2, 4, 6:
device model with two safety relays (size 3-7)
These device models provide an additional functional shutdown via the pulse enable circuit
of the BM4000 controller LC3, besides the shutdown via both safety relays.
As the two-channel shutdown reaches performance level e and SIL3 using both safety relays,
the third shutdown path will not be responded to regarding the safety requirements.
The connection diagrams ZC.2.2.3 Connection diagrams– from page 338 and notes ZC.2.1
Safety classifications and safety notes– from page 330 must be complied with.
NOTE
The starting and the shutdown sequence of the enabling signals and the safety relay
must be considered, in order to assure a faultless operation of the drive.
See ZFigure 111– on page 335.
The starting and the shutdown sequence of the release signals and of the safety relay must be
considered, in order to assure a faultless operation of the drive.
NOTE
The safety function must be checked, before commissioning the machine, in which
the BM4000, with the safety function STO is installed. For this purpose a protective
function must be enabled (for example door contact). The motor must be with zero-
torque.
Different starting / shutdown sequences possible. See table ZDifferent starting / shutdown op-
tions BM4X1X to BM4X7X– on page 337.
1 TBoot_controller dependent on the used option module (from firmware version 03.05)
approx. 5 s.
2 Tcharge DC link: 1.5 s (exception BM4X3X: 6 s).
3 TSR pulse enable: 20 ms (exception BM4X2X: 200 ms).
BM4X1X
BM4X2X
BM4X3X
BM4X4X
BM4X5X
BM4X6X
BM4X7X
Auxiliary supply (24 V) and yes yes yes yes yes yes yes
safety relay 1 + 2 and
power supply
simultaneously ON
Auxiliary supply (24 V) and yes yes yes yes yes yes yes
safety relay 1 + 2
simultaneously ON
Power supply „OFF“ power yes yes yes yes yes yes yes
supply „ON“ at pulse inhibit
Pulse enable „ON“ at an activated yes yes yes yes yes yes yes
safety relay
Pulse enable and no no no no no no no
safety relay 1 + 2
simultaneously „ON“
Pulse enable and no no no no no no no
safety relay 1 + 2
simultaneously „OFF“
Safety relay 1 + 2 “ON“ yes no 1) yes yes yes yes yes
20 ms before pulse enable
Safety relay 1 + 2 “OFF“ yes no 1) yes yes yes yes yes
20 ms after pulse enable
1)
„yes“, if TSR pulse enable = 200 ms
m Device models BM4000 with one safety relay (first safe shutdown path) and pulse
enable at the controller LC3 (sizes 1 - 7) (second safe shutdown path)
BM4000
Figure 113: Shutdown paths with a safety relay and pulse enable at the controller
m Device models BM4000 with two safety relays (safe shutdown paths) and pulse enable
at the controller (functional)
BM4000
Dependent on the possible dangers (these dangers are rated due to the consideration of the
severity of the injuries, the frequency of the length of stay within the danger area and the possi-
bilities to prevent dangers) safety-related components of machines must meet defined safety
criteria. The requirements to safety-based parts are divided into five categories in the standard
EN ISO 13849-1.
Category B requires basic requirements. Safety-approved components and principles in cate-
gory 1, additionally. In category 2 an error between inspection intervals can lead to a loss of the
safety function.
Category 3 complies with the level „the single-error-certainty to recognize errors partially”. The
safety-related components may not lead to a loss of safety function, if one single error occurs.
The errors are not all detected by the system, however. The accumulation of undetected errors
can lead to a loss of the safety function.
Category 4 complies with level „Self-monitoring”. This component detects possible errors.
These errors are reported in time. Therefore, the loss of the safety function is avoided.
The function of the safety relay is performed in fail safe technology (closed circuit principle). The
safety function „Safe stop” if no voltage is applied to the input terminals (X102-3/4; X103-3/4).
The operation of the safety function is ensured at power failure. 24V must be applied to the avail-
able terminals, to deactivate „Safe stop“ (X102-3/4; X103-3/4).
The present switching state can be obtained from the positively driven feedback contacts for the
external monitoring of the safety relay (X102-1/2; X103-1/2). If there is no voltage at the safety
relay („Safe stop“). The feedback contacts are closed (NC contact). Cable break is also detected
as an error.
The converter generates „Power unit warning 20: undervoltage safety relay“ or „Power unit error
87: error safety relay“), if the voltage at the input terminals of the relay (X102-3/4;X103-3/4) is
switched off. At inhibited pulse enable the warning „warning is not saved“ is generated and at
pulse enable the error message (errors are saved) is generated. A commissioning or enable of
drive is possible, if no error is detected in error memory. Error memory can be reset via the dig-
ital input X1/1 of the function module DIO-01. Input X1/1 must be configured accordingly. The
switch error storage can, for example, be reset over the digital input X1/1 of the function module
DIO-01. For this the input X1/1 accordingly must be configured. The starting pulse length at X1/
1 must last at least 5 ms.
The following diagram shows the use and cabling of a Baumüller b maXX 4000 converter in a
machine tool. Complying with category 3 (EN ISO 13849-1), in this machine tool the safe remov-
al of work pieces at an open cover, is possible.
m Application example for machine of category 3 with two shutdown channels:
Pulse enable and one safety relay.
The diagram displays the use and cabling of a Baumüller converter of b maXX 4000 (BM4X3X-
XX2, BM4X4X-XX2, BM4X5X-XX2, BM4X6X-XX2, BM4X7X-XX2) in a machine tool. Complying
with category 4 (EN ISO 13849-1), in this machine tool the safe removal of work pieces at an
open cover, is possible.
The switching-off of the electrical drive motor is executed with three channels.
n S1 (NC contact) has hardware effects on the safety relay of the converter. Only if S1 displays
a closed cover (safe state), voltage is applied at the safety relay input (X102-3). A torque now
can be generated at the motor shaft. The NO contact of S1 is connected with the monitoring
circuit.
n S2 (NC contact) and S3 (NO contact) effect the other safety relay of the converter. Only if S2
and S3 display a closed cover (safe state), voltage is applied to the safety relay input (X103-
3). A torque now can be generated at the motor shaft.
n S3 (NC contact) has hardware effects on the pulse enable input of the converter (X3-5). Only
if S3 displays a closed cover (safe state), voltage is applied to the pulse enable input of the
converter.
n The monitoring circuit is a fail-safe monitoring control of the category 4 (EN ISO 13849-1). It
checks the directly connected switching contacts of the position switch S1 (NO contact), S2
(NO contact) and S3 (NC contact) and the feedback contacts of the safety relay (X102-1/2
NO contact, X103-1/2 NO contact). The control circuit will not receive an enable signal from
the monitoring circuit, if the cover is not completely closed or if a technically impossible state
of the position switch contacts occurs (for example S1 and S2 display different switch states
The connection cables between the safety relay inputs (X102-3/4; X103-3/4) as well as between
the pulse enable input (X3-5) and the control circuit may not be installed in a common cable
channel outside the control cabinet.
All information given in the instruction handbook of the converter, especially the chapters safety
instructions, installation and commissioning, must be complied with.
For the use and the installation of the safety devices the relevant legal and official requirements
of the Safety Authorities and of the EU Directives for safety-related requirements at installations
and machines (for example EN 60204-1, Safety of machinery - Electrical equipment of ma-
chines - Part 1: General requirements and EN 292-2, Safety of machinery; basic concepts and
general principles for design; technical principles and specifications.
The safety function „Safe stop“ is provided via three independent switch off channels and a
hardware pulse enable input (category 4 according to EN ISO 13849-1) at the b maXX 4000
converter (BM4X3X-XX2 to BM4X7X-XX2).
However, in many ranges it is not required to operate „Safe Stop“ in category 4.
In the following, application examples are viewed, at which only two of the three switch off chan-
nels are used.
m Application example 1
Application example for machine of category 3 with hardwired pulse enable input and process
data communication via a field bus.
Switching off occurs by means of safety relay 1 and safety relay 2.
Herd the hardware pulse enable input (X3:5) is hardwired. The activation of the „Safe Stop“ is
made with two channels via the safety relay 1 and 2 (X102:3 / X103:3).
The release of the converter and the process data communication is made via field bus.
Here the safety relays 1 and 2 are triggered by a position switch and together generate the first
channel. The second channel is generated by the hardware pulse enable input, which is inde-
pendently triggered by the safety relay.
m Application example 3
Pulse enable and one safety relay, only
This b maXX 4000 converter is equipped with one safety relay, only. The hardware is identical
with the other converters of this series - the second relay is not assembled. The internal relay
switch off paths are combined and commonly generate the first channel.
The second channel generates a hardware pulse enable input, which is independently triggered
by the safety relay.
The test pulses detect static error conditions in the safety-related circuits. The implementation
of the test pulses automatically takes place in the background. The drive functions and the safe-
ty functions are not affected.
The pulse enable inputs (X3-5) and the safety relays (X102-3/4, X103-3/4) of b maXX 4000 are
provided for the use of an OSSD test pulse.
The test pulses have the following limit values:
Value Description
tTPLmax 3 ms maximum low time of the test pulse
tTPmin 100 ms minimum period of the test pulse
Input Threshold
X3-5 Low level: 0 V to 5 V
(pulse enable) High level: 12 V to 28 V
X102-3/4, X103-3/4 High level: 20 V to 28 V (24 V -15 % / +20 %)
(safety relay)
DANGER!
Risk of injury by moving parts!
Mechanical effects due to the failure of the safety relay.
Therefore:
The minimum load of the contacts X102-1 and X102-2 (accordingly X103-1 and
X103-2) may not fall below the specified values. Operate the safety relay within the
specification.
NOTE
A device with safety relay is not a safe device. The device with safety relay does not
comply with the PL level according to ISO 13849 and SIL according to EN 61800, if
the part number does not start with „06“.
This device is not certified for safety functions!
NOTE
Devices with the approval mark of TÜV Rheinland and the Safety label provide a cer-
tified safety function, only, refer to ZPage 29–.
1)
Customer-specific versions, only.
Contact Baumüller Nürnberg GmbH before using this version.
2)
A switching current of at least 20 mA is recommended. If the load is below 20 mA the switching current must be in-
creased by a base load (see ZFigure 121– on page 352).
1)
Customer-specific versions, only.
Contact Baumüller Nürnberg GmbH before using this version.
2)
A switching current of at least 20 mA is recommended. If the load is below 20 mA the switching current must be in-
creased by a base load (see ZFigure 121– on page 352).
Table of Figures
Signs and labels BM4X1X............................................................................................................................ 25
Signs and labels BM4X3X/BM4X4X ............................................................................................................ 26
Signs and labels BM4X5X............................................................................................................................ 27
Signs and labels BM4X6X, BM4X7X ........................................................................................................... 28
Type code labeling ....................................................................................................................................... 29
Dimensions BM441X.................................................................................................................................... 32
Dimensions BM442X-S/A............................................................................................................................. 33
Dimensions BM442X-F/C............................................................................................................................. 34
Dimensions BM443X-S/Z, BM443X-A/F ...................................................................................................... 35
Dimensions BM443X-C, BM463X-F............................................................................................................. 36
Dimensions BM444X-S/Z, BM464X-S/Z ...................................................................................................... 37
Dimensions BM444X-A/F, BM464X-A/F ...................................................................................................... 38
Dimensions BM445X-S/Z, BM465X-S/Z ...................................................................................................... 39
Dimensions BM445X-A/F, BM465X-A/F ...................................................................................................... 40
Dimensions BM465X-FXX-3XXXX and BM475X-FXX-3XXXX.................................................................... 41
Dimensions BM465X-FXX-3XXXX-RYY, BM475X-FXX-3XXXX-RYY......................................................... 42
Dimensions BM465X-ZXX-3XXXX-[RYY], BM475X-ZXX-3XXXX-[RYY]..................................................... 43
Dimensions BM446X-S/Z............................................................................................................................. 44
Dimensions BM446X-A/F and BM466X-A/F ................................................................................................ 45
Dimensions BM466X-FXX-3XXXX and BM476X-FXX-3XXXX.................................................................... 46
Dimensions BM466X-Z-3XXXX and BM476X-Z-3XXXX ............................................................................. 47
Dimensions BM447X-F, BM477X-F ............................................................................................................. 48
Dimensions BM447X-A ................................................................................................................................ 49
Reducing of the output power in dependence of the absolute altitude ........................................................ 56
Output current in dependence of the input voltage ...................................................................................... 57
Reducing the output voltage in dependence with the input voltage ............................................................. 58
Reducing the output power in dependence of the system voltage............................................................... 58
Calculation of the thermal RMS current ....................................................................................................... 59
Coherence between peak current and rated current.................................................................................... 59
Cooling air requirement................................................................................................................................ 61
Derating of output current BM441X universal units...................................................................................... 64
Maximum external DC link capacitance BM441X ........................................................................................ 65
Derating the output current BM442X universal units.................................................................................... 68
Maximum external DC link capacitance BM442X ........................................................................................ 69
Derating the output current BM443X universal units.................................................................................... 71
Derating the output current BM444X universal units.................................................................................... 74
Reducing of output current BM445X universal units .................................................................................... 77
Reducing of output current BM 446X universal units ................................................................................... 80
Derating the output current BM 447X universal units................................................................................... 83
Derating the output current BM4632 acceleration units ............................................................................... 86
Derating the output current BM464X acceleration units............................................................................... 88
Derating the output current BM465X acceleration units............................................................................... 90
Derating the output current BM466X acceleration units............................................................................... 92
Derating the output current BM47XX continuous current units .................................................................... 94
Derating the output current BM442X power modules .................................................................................. 97
Derating the output current BM443X power modules .................................................................................. 99
Derating the output current BM444X power modules ................................................................................ 101
Derating the output current BM445X power modules ................................................................................ 103
Derating the output current BM446X power modules ................................................................................ 105
Conversion brake power time area in triangular time area ........................................................................ 107
Braking cycle.............................................................................................................................................. 108
Continuous current derating at a statical output frequency < 15 Hz .......................................................... 112
Reduction BM46XX max. current and PWM frequency at output frequencies < 10 Hz ............................. 113
Reduction BM46XX only max. current at output frequencies < 10 Hz ....................................................... 113
Position of type plate.................................................................................................................................. 125
EtherCAT® Address switch setting............................................................................................................. 138
CANopen® address switch ......................................................................................................................... 140
Danger area near the mechanical mounting .............................................................................................. 145
Drilling pattern BM441X ............................................................................................................................. 147
C G
Cable connectors Guarantee provisions 12
length 307
Cable protection 273 H
Cable RS 232 304 Hard hat 20
Cabling 268 Hardware type 127
Caution 10 Hazards, special 21
Choice of encoders 123 Heidenhain 123
Combinations 120 Hiperface® 205
Connection cables 306
Connection technology 191 I
Connectors 312 Inductance 52
Continuous current derating 112 Initial commissioning 163
Control, higher level 224 Inputs, no. of DI 221
Cooling 61 Inspection 262
Cooling type 126 inspection 262
Crossover package 305 Installation 163
Cross-section 191 Installation, procedure 171
Current power 205 Instruction
Customer service 13 Make cable connector 308, 310
Interconnect devices 123
D
Danger 10 K
Danger situation 23 Key to symbols 10
DC link discharge time 165, 263, 317
Declaration of conformity 323 L
Demounting 314 LED 132
Design cover 312 LED H2 237
Device protection 274 LED H4 237
Display elements 132 Limitation of liability 11
Disposal 12, 317
Drive management 237
M
Mains filters 294
E Maintenance 261
Edges, sharp 145, 314 Maintenance, periodic 264
Electrical current, dangers of 21 Malfunctions, behavior 229
Enable signals 224 Modifications 15
Encoder module 123 Monitoring functions 230
Encoder type 123 Motor temperature sensor 170
Encoders, connectable 123 Moving 22
EnDat 207, 208, 209, 210, 212, 214, 216 Moving components, danger from 22
Energy supply / requirements 52
P T
Packaging, disposal of 142 Temperature range 55
Parameter list 237 Temperature sensor 170
Parameterization 237 Terminals, controller 195
PE connection 169 Termination plug 306
Personnel, qualified 19 Torque 186
Personnel, training 19 Transport 141
Power chokes 300 Transport inspection 142
Power consumption, external 221 Type plate 29
Power consumption, internal DI 221
Power supply 221 U
Power supply system 126 UL 508 C 162
ProDrive 237 Unexpected starting 327
Protective equipment 20 Unpacking 142
Protective eye wear 20 Usage, compliant with the intended purpose
Protective gloves 20 16
Protective work clothing 20
PSI module 195 V
Pulse enable 133, 224 Voltage test 165
Q W
Quick stop 224 Warning 10
Warning messages 258
R Warning notes 10
Rated supply voltage / frequency 52 Washers 156
Recommissioning 316 Weight 50
Repairs 266
Required environmental conditions 55
Residual energy, danger from 21, 165
Resolver 203
S
Safe stop 327
Safety categories 340
Safety equipment 23
Safety fuses 273
Safety relay 127, 231, 334, 341
Durability 351
Safety shoes 20
Screws 156
Semiconductor fuses 274
Shielding clamp 304
Overview of Revisions
All information given in this manual is customer information, subject to change without notice. We reserve the right to futher develop and actualize
our products continuously using our permanent revision service. Please notice, that specifications/data/information are current values according to the printing date.
These statements are not legally binding according to the measurement, computation and calculations. Before you make any information given in this manual to the basis
of your own calculations and/or applications, please make sure that you have the latest edition of the information in hand.
No liability can be accepted concerning the correctness of the information.