Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
0% found this document useful (0 votes)
454 views1 page

Plumbing General Notes and Specifications

This document provides general notes for thrust blocks and anchor blocks, including that areas are based on an assumed soil bearing pressure of 100kPa, dimensions should be reduced or increased based on field conditions approved by an engineer, concrete strength should be a minimum of 17MPa, upward anchor block dimensions are based on internal pressure of 1.03MPa and a safety factor of 1.5, thrust blocks should be poured against undisturbed soil, and rebar should be embedded 0.3m into concrete. Thrust block dimensions also consider internal pressure of 1.21MPa and a safety factor of 1.5.

Uploaded by

Cad Pert
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
454 views1 page

Plumbing General Notes and Specifications

This document provides general notes for thrust blocks and anchor blocks, including that areas are based on an assumed soil bearing pressure of 100kPa, dimensions should be reduced or increased based on field conditions approved by an engineer, concrete strength should be a minimum of 17MPa, upward anchor block dimensions are based on internal pressure of 1.03MPa and a safety factor of 1.5, thrust blocks should be poured against undisturbed soil, and rebar should be embedded 0.3m into concrete. Thrust block dimensions also consider internal pressure of 1.21MPa and a safety factor of 1.5.

Uploaded by

Cad Pert
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

GENERAL NOTES :

1. ABOVE AREAS ARE BASED ON AN ASSUMED


SOIL BEARING PRESSURE OF 100.0KPa OR
14.5psi.

2. REDUCE OR INCREASE AREAS PROPORTIONALLY


TO SUIT ACTUAL FIELD CONDITIONS UPON
APPROVAL OF ENGINEER.

3. CONCRETE STRENGTH OF THRUST BLOCKS SHALL


BE 17.0MPa (MIN.) OR 2500psi

4. UPWARD ANCHOR BLOCKS DIMENSIONS BASED ON


INTERNAL PRESSURE OF 1.03MPa (150psi) AND
A SAFETY FACTOR OF 1.5.

5. POUR CONCRETE THRUST BLOCKS AGAINST


UNDISTURBED SOIL.

6. EMBED END OF BARS A MINIMUM OF 0.30m


INTO CONCRETE.

7. THRUST BLOCK DIMENSIONS ARE BASED ON


INTERNAL PRESSURE OF 1.21MPa (17.5psi)
AND A SAFETY FACTOR OF 1.5.