F03
F03
F03
Group ‘G’
- Educational : School, Colleges, Recreations.
- Industrial : Assembly Plants, Labs, Pumping stations, Refineries, Saw
Group ‘C’ mills.
Sections:- As per section 4.6 (a) of part 3 & 7.4.1 (a) of part IV of N.B.C.
Section:- As per section 4.6 (c) of part C & 7.4.1(d) of part IV of N.B.C.
Every High rise building should have at least 2 means of access, one remote to the other, of
minimum width 4.5m. with height clearance of 5m. This minimum width is essential to facilitate
free movement of fire units.
SETBACK OR OPEN SPACES
c. Assembly building - Except in front, open space shall not be less than 6 meter and front open space shall not be less than 12
meters.
d. Business/Mercantile & storage building – Open space around the building shall not be
e. Industrial/Hazardous building – Minimum 4.5 meters open space shall be kept around the building for the height up to16
meters. Open space shall be increased by 0.25meters for next each 1 meter height of the building.
CAR PARKING
Car Parking shall have to be done at the basement with provision for minimum 2 ramps one
remote to other.
STAIRCASES
Section :- As per section 12.18 of part III, 8.5.1 (Table 24), 8.6.2,8.9,8.10,8.13, 9.3.5(a),10.4.1,11.3.2
of part IV & appendix D1.3,D1.4 of part of NBC.
g) Staircase shall not be extended to basement to prevent smoke , heat & gases. From the basement
smoke, heat 7 gases can be travel to upper floors.
h) Access to the basement from the ground should be through a separate staircase, which is not
connected to main staircase (i.e. It should be remote to each other.)
i) Staircase shall be of enclosed type to prevent entry of smoke & fire to the staircase & vice versa.
a) Minimum 1 lift capable of carrying minimum 8 persons weighing 545 kgs. Shall be provided for every high rise building.
b) Landing doors of lifts shall open to ventilated lobby & shall have a fire resistance of 1 hour.
each lift.
g) If more than 1 lifts are installed the partition wall should be of minimum 2 hours fire resistance.
THE REFUGE AREA
Section: As per section 8.12.3 on part IV of NBC, the refuge area shall be provided on the
periphery of the floor & open to air atleast on one side protected with suitable railing.
a) For floors above 24m & up to 39m one refuge area on the floor immediately above 24m.
b) For floors above 39m one refuge area on the floor immediately above 39m & so on after
15m refuge area shall be provided
SERVICE DUCTS
As per appendix D 1.9 part IV of N.B.C. all the services ducts, if provided, should have to be enclosed by walls of at least 2 hour
fire resistance & should have to be sealed at every alternate floor with non-combustible materials having at least 2 hour fire
resistance. The sealing at floor level is to prevent travel of smoke & fire to the upper floors through the ducts.
BUILT IN FIRE FIGHTING SYSTEM
WET RISER CUM DOWN COMMER SYSTEM
Wet riser : It is a vertical pipeline (dia. depends on
the floor area of the building) connected to a
bottom tank(underground water tank).
‣ For hotels wet-riser cum down commer both the systems shall be provided.
‣ For each 1000m2 floor area or it’s part one riser shall be provided.
‣ At every landing twin outlet each of 63mm dia. shall be provided (one should be connected to hose reel & another
should be to hose & branch).
‣ Length of hose should be shall that it should reach at the last point of floor area.
‣ Minimum two courtyard hydrants shall be provided (courtyard hydrant will be an extention to riser).
‣ Hose reel hose of 12mm dia. shall be provided from landing valve to wet-riser at each floor.
Above mentioned water tank capacity is for 1 riser. If the number of risers will be more than 1, than quantity of water shall be increased in that
proportionate. In addition to this if automatic sprinkler, drenchers are provided for special risk then this will be additional quantity of water.
PUMP CAPACITY
For underground water storage tank, pump shall be installed of a capacity either 1800 L.P.M. or 2400 L.P.M. depending on the type and occupancy of the
building along with jocky pump.
‣ At topmost hydrant we should get a pressure of not less than 3.5 bar.
‣ For terrace level water storage tank,pump shall be installed of a capacity either 450 L.P.M. occupancy of the building.
‣ Every building more than 15m in height shall provide both I.e. M.O.E.F.A
& A.F.A.
‣ Residential & office buildings between 15m & 24m in height may be
exempted from installation of automatic fire alarm system if local fire
brigade is well equipped to face the emergency up to 24m.
a separate car.