Horizontal Split Case & End Suction Type Electric Motor Driven Fire Pump Pre Start-Up Checklist (Canadian Version)
Horizontal Split Case & End Suction Type Electric Motor Driven Fire Pump Pre Start-Up Checklist (Canadian Version)
Horizontal Split Case & End Suction Type Electric Motor Driven Fire Pump Pre Start-Up Checklist (Canadian Version)
191
DATE: Oct. 15, 2000
SUPERSEDES: CF43.191
DATE: July 30, 2000
HORIZONTAL SPLIT CASE & END SUCTION TYPE ELECTRIC MOTOR DRIVEN FIRE PUMP PRE START-UP
CHECKLIST (CANADIAN VERSION)
This pre start-up checklist shows items that must be completed prior to a scheduled start-up. If the answer to any
questions is “No”(when it should be “Yes”), is left blank or contradicts the requirements of NFPA 20, the installation is not
ready for start-up. Indicate “N/A” for not applicable wherever appropriate. These questions should be answered in
conjunction with the fire pump (mechanical) contractor and electrical contractor. Check list must be returned signed and
dated below.
Fire Pump IO&M manuals are available from Armstrong’s website www.armstrongpumps.com
The sole purpose of this pre start-up checklist is to serve as a guide only. Armstrong does not assume any liability or
responsibility for the accuracy of this list or any items omitted. This list does not absolve the installing contractors of their
responsibilities for proper installation in accordance with the local and national codes and standards.
Page 1 of 4
III. MAIN FIRE PUMP INSTALLATION – ELECTRIC DRIVEN (HSC & ES):
1. Pump installed in the proper direction of flow in relation to the system (Suction & Discharge Orientation). ____ ____
2. Drive to Pump direction of rotation correct. (verified in conjunction with an electrician). ____ ____
3. Pump to drive coupling re-aligned after the entire pump assembly base installation completed
as per NFPA 20 A-3-5. ____ ____
4. Pump rotates freely when turned by hand. ____ ____
5. Minimum of 4 to 6 pipe diameters length of straight pipe installed at pump suction connection. ____ ____
6. Suction and Discharge system piping supports c/w anchors installed near to but independent of the pump
assembly. ____ ____
7. System piping does not exert any strain on the pump casing. ____ ____
8. Eccentric reducer installed on the pump suction side (as required by NFPA 20). ____ ____
9. Concentric Increaser installed on the pump discharge side (as required by NFPA 20). ____ ____
10. Suction line has been tested to ensure there aren’t any leaks. ____ ____
11. Listed OS&Y Gate Valve installed close to pump on the suction sided of the pump. ____ ____
12. Listed OS&Y Gate Valve or Butterfly Valve on pump discharge line. ____ ____
13. A Listed Check Valve is installed and is in the proper direction. ____ ____
VI. SENSING LINES FOR MAIN FIRE PUMP & JOCKEY PUMP:
1. Main fire pump and Jockey pump sensing lines totally independent of each other and connected to their
respective controllers in accordance with NFPA 20 Figure A-7-5.2.1 (a) & (b). ____ ____
2. Each sensing line ½” non-ferrous metallic piping [as per NFPA 20 7-5.2.1 (b)]. ____ ____
3. Each sensing line has 2 bronze check valves each with a 3/32” diameter hole drilled in the flapper. ____ ____
4. All sensing line check valves are orientated to open in the direction of the pump. ____ ____
5. Check valves spaced 5 feet from each other. ____ ____
I certify the above items are completed and were checked at the job site and the pump equipment is ready for a start-up
and performance test.
Once fully completed, please return the above Pre Start-Up Check List to _____________________________________
(local Armstrong Service Dealer/Agent) to the attention of ________________________________________________ .
Please note, all fire pump start-up requests may require a minimum of 2-3 weeks advanced notice in order to schedule a
date with the appropriate parties (equipment representatives & their technicians). The actual scheduled start-up date(s)
will be determined based on the availability of these parties. It is the responsibility of the installing contractor to arrange
for the other required parties to be present and have the installation ready on the scheduled date for the subject start-up.
Scheduling of fire pump start-up will commence only once the installation is deemed ready for start-up as derived from the
answers provided on this form.
Important: A standard start-up is based on a maximum 3 hours at the job site. Should the time required to complete the
start-up exceed this standard duration or should the start-up service need to be repeated due to circumstances caused by
other parties, and or situations out of our control, any additional service or incurred costs are the sole responsibility of the
installing contractor.
Page 3 of 4
Before performing any tests, to avoid false alarms where a supervisory service is provided, the alarm receiving facilities
must always be notified by the building owner or designated representative.
Prior to the Start-Up, the Installing Contractor must ensure that the Pre-Start-Up Verification has been performed and
provide confirmation to the local U.S. Armstrong Darling representative ensuring:
1. Pump Alignment.
2. Pump Packing Gland Adjusted.
3. System Integrity.
4. Electrical Integrity.
5. All applicable items on the Pre Start-Up Checklist have been verified and answered accordingly.
6. The installation is ready for start-up (including all air bled from the system and ready to flow water) and is in
accordance with all applicable national and local codes and standards.
7. All applicable documentation is on-hand at start-up (including pump certified performance curve(s), equipment
manuals & wiring diagrams).
8. All the appropriate parties (e.g. AHJ-Fire Marshall, Electrician, Millwright/Pipe Fitter, Building Owner/Representative,
etc.) will be present throughout the entire start-up.
S.A. Armstrong Limited Armstrong Pumps Limited Armstrong Pumps Inc. Armstrong Darling Inc.
23 Bertrand Avenue Peartree Road, Stanway 93 East Avenue 2200 Place Transcanadienne
Toronto, Ontario Colchester, Essex Buffalo, New York Montreal, Quebec
Canada, M1L 2P3 United Kingdom, C03 5JX U.S.A. 14120-6594 Canada, H9P 2X5
Tel: (416) 755-2291 Tel: 01206-579491 Tel: (716) 693-8813 Tel: (514) 421-2424
Fax: (416) 759-9101 Fax: 01206-760532 Fax: (716) 693-8970 Fax: (514) 421-2436
Visit us at www.armstrongpumps.com
© S.A. Armstrong Limited 2000
Page 4 of 4