Wayne-Dresser 1V, 2V & 3V Retrofit For Healy Systems, Inc. MODEL VP1000 Vapor Recovery Assist System
Wayne-Dresser 1V, 2V & 3V Retrofit For Healy Systems, Inc. MODEL VP1000 Vapor Recovery Assist System
Wayne-Dresser 1V, 2V & 3V Retrofit For Healy Systems, Inc. MODEL VP1000 Vapor Recovery Assist System
Page 161
OUTLINE
Notice: USE THIS PROCEDURE IF CONVERTING A BALANCE VAPOR RECOVERY
SYSTEM TO A HEALY VAPOR RECOVERY ASSIST SYSTEM
This Manual is to be used for new, replaced, retrofitted, or reconditioned dispensers/pumps.
1. Purpose
2. Safety
3. Models Covered
4. Parts Lists
5. Tools Required
6. Dispenser Access
7. Survey Scope of Work
8. Installing The Healy VP1000 System
9. Installing The Sealed Nipple Assembly
10. Wiring Inside The Electronics Compartment
11. Connecting Healy Systems Dispensing Equipment
12. VP1000 Theory Of Operation
13. Testing The System
14. Trouble Shooting The VP1000
15. VP1000 Vane & Rotor Service & Replacement Guide
Start-up / New Installation / Warranty / Annual Testing Form
Website: http://www.franklinfueling.com
Email: sales@franklinfueling.com
Telephone: 800-225-9787
Fax: 608-838-6433
ARB Approved IOM Executive Orders VR-201-E and VR-202-E (Vista Series Wayne Balance Dispenser)
Page 162
1. PURPOSE:
This procedure describes the tools, methods and skill levels required to install a Healy
Systems, Inc. Model VP1000 Vapor Recovery pump in vapor ready Wayne-Dresser 1V, 2V
& 3V series gasoline dispenser. Only Healy trained and certified contractors will be able to
perform these retrofits or warranty will be void. The installer shall be a skilled petroleum
technician and thoroughly familiar with the requirements of State, Federal and local codes
for installation and repair of gasoline dispensing equipment. Also, they shall be aware of all
the necessary safety precautions and site safety requirements to assure a safe and trouble
free installation. NOTE: All electrical and hydraulic plumbing fittings referred to in these
instructions must be UL listed or recognized for the purpose.
Note: Installations of vapor piping into the inlet side of the vacuum pump should be sloped such
that the natural flow direction is toward the vacuum pump. However, it is permissible to
have a piping slope tilted away from the vacuum pump provided that all other applicable
tests (Dispenser integrity and V/L) meet the specifications outlined in the appropriate
section of the Executive Order and ARB Approved Installation, Operation and
Maintenance Manual.
Note: For installations with In-Station Diagnostics (ISD), the vapor flow meter shall be installed
on the down stream side of the vacuum pump. Every effort shall be made to install the
vapor flow meter so that vapor piping between the vacuum pump and the vapor flow meter
is sloped such that the natural flow direction is toward the vapor flow meter. However, it
is permissible to have the piping slope away from the vapor flow meter provided that all
other applicable tests (Dispenser integrity, V/L and ISD Operability) meet the specifications
outlined in the appropriate section of the Executive Order and ARB Approved Installation,
Operation and Maintenance Manual.
2. SAFETY: Before installing the equipment, read, understand and follow:
- The National Electrical Code (NFPA 70)
- The Automotive and Marine Service Code (NFPA 30A)
- Any national, state and local codes that may apply.
The failure to install the equipment in accordance with NFPA 30A and 70 may
adversely affect the safe use and operation of the system.
Accurate, sound installations reduce service calls: Use experienced, licensed
contractors that practice accurate, safe installation techniques. Careful
installation provides a sound troubleshooting framework for field repairs and can
eliminate potential problems.
1. Read all instructions before beginning.
2. Follow all safety precautions:
Barricade the area.
Do not allow vehicles or unauthorized people in the area.
Do not smoke or allow open flames in the area.
Do not use power tools in the work area.
Wear eye protection during installation.
3. Use circuit breakers for multiple disconnects to turn off power and prevent
feedback from other dispensers.
ARB Approved IOM Executive Orders VR-201-E and VR-202-E (Vista Series Wayne Balance Dispenser)
Page 163
3. MODELS COVERED:
Wayne 1V, 2V & 3V series of blending and non-blending dispensers. The addition of
the Healy Systems VP1000 to these dispensers will increase the current draw of the
dispenser by 2 amps. Use the label supplied to note this change.
4. PARTS LISTS: (See Photo A)
1
VP1000 Vacuum Pump
1
1365A Wire Harness / MC100 Series Interface Module Assembly (for 3V) or
1
1363A Wire Harness / MC100 Series Interface Module Assembly (for 1V & 2V)
PHOTO A
PHOTO B
PHOTO C
PHOTO D
ARB Approved IOM Executive Orders VR-201-E and VR-202-E (Vista Series Wayne Balance Dispenser)
Page 164
Wire nuts
12
ARB Approved IOM Executive Orders VR-201-E and VR-202-E (Vista Series Wayne Balance Dispenser)
Page 165
DISPENSER ACCESS:
Secure Dispenser Access keys from Station Management.
Lock-out and tag-out all electrical power to dispenser being modified.
Remove both lower dress panels.
Remove side skin on the left side as viewed from the A side (J box). This is the side
where the 1 balance vapor pipe is installed.
Open both upper doors to the electronics compartment.
7. Survey Scope of Work: Perform this step before beginning steps 8 thru 10.
Read and familiarize yourself with the theory of operations sheet and wiring instructions
for the VP1000 Vapor Pump. The installation of the pump is accomplished by rotating the
motor mounting bracket bolting it to the dispenser frame on the same side as the electrical
J box in the free space on the left hand side, see photos E & F. From this survey, you will
have an indication of where the vapor plumbing fittings need to go and where the electrical
conduits need to be routed. The Healy potted conduit nipple is installed in the vapor
barrier above the meters, in a 1 1/8 hole that is already available but is plugged. See
Photo K and Section 9. CAUTION: ALL POWER TO DISPENSER UNDER MODIFICATION
SHOULD BE COMPLETELY DISCONNECTED AND CAPPED OFF AT JUNCTION BOX TO
AVOID UNINTENTIONAL FEEDBACK FROM OTHER DISPENSERS!!
Photo E
Photo F
ARB Approved IOM Executive Orders VR-201-E and VR-202-E (Vista Series Wayne Balance Dispenser)
Page 166
Photo H
ARB Approved IOM Executive Orders VR-201-E and VR-202-E (Vista Series Wayne Balance Dispenser)
Photo I
Photo J
Page 167
Photo K
ARB Approved IOM Executive Orders VR-201-E and VR-202-E (Vista Series Wayne Balance Dispenser)
Page 168
Photo M
On the pump motor, install a 1/2 x 7 conduit nipple, a 1/2 electrical coupling and a
1/2 x 4-1/2 nipple, see photo N.
Get the electrical J box, remove the cover and install a 3/4 x 1/2 reducer bushing
into each hub. Install the J onto the 4-1/2 nipple positioned as shown in photo N.
Install a 1/2 electrical close nipple to J box followed by the pull elbow, see photo O.
Remove the pull elbow cover.
Install the male half of the electrical union to the pull elbow. Run wires through the pull
elbow and into the J box. Connect the union halfs together being careful not to pinch
wires, reinstall the pull elbow cover and tighten the nut on the potted nipple.
At the J box, cut all the wires leaving at least 6 on each piece. Strip all wires about
1/2 and join the wires color for color, using wire nuts supplied. Coil all wires and place
into box, replace the cover.
ARB Approved IOM Executive Orders VR-201-E and VR-202-E (Vista Series Wayne Balance Dispenser)
Photo N
Page 169
Photo O
ARB Approved IOM Executive Orders VR-201-E and VR-202-E (Vista Series Wayne Balance Dispenser)
Photo P
Page 170
Photo Q
Photo R
NOTICE label for current increase (1405), install on the inside of the cabinet
panel near the existing power consumption label, see photo S.
Large NOTICE label (1406) relating to the vapor recovery upgrade and how to
reset the electronic module should be installed near the module, where it will
be readily visible to a service technician on the inside of the cabinet near the
nozzle spout housing, see photo T.
UL, retrofit kit identification number (1410), install near the electronic module.
ARB Approved IOM Executive Orders VR-201-E and VR-202-E (Vista Series Wayne Balance Dispenser)
Photo S
Page 171
Photo T
Vapor ready dispensers will require a Healy Systems adaptor to make the hose
threads compatible with other Healy Systems equipment. Install following
instructions packed with the adaptor. Various adaptors are available, depending on
how the dispenser is configured: M34 metric (Healy designation F3 or S3) or balance
ready (Healy designation S4).
Healy Vapor Recovery Hoses are available in various lengths to satisfy local
ordinances and still provide far side fueling capability. Install these following
instructions contained on the shipping box.
Breakaways are required: Install either Model 8701VV breakaway or Model 807
swivel breakaway; install using the instructions supplied with the unit.
The Healy Systems nozzle Model 900 (EVR) series is the only nozzle necessary
to complete the upgrade. Check to be sure that the nozzle hanger is mounted in
the highest position. Be sure to check for proper fit in the nozzle holster and that
the nozzle can be locked in the off position. Also, be sure that when the nozzle is
locked, that the dispenser cannot be activated from the locked position.
ARB Approved IOM Executive Orders VR-201-E and VR-202-E (Vista Series Wayne Balance Dispenser)
Page 172
MOTOR SPECIFICATIONS
Horsepower
1/8
Voltage
120VAC
INTERFACE SPECIFICATIONS
Input voltage
Relay current capacity
Input signals
Motor Input signal
120 VAC
5A AC
120 VAC
5 VDC @ 20 Hz 50% Duty Cycle
ARB Approved IOM Executive Orders VR-201-E and VR-202-E (Vista Series Wayne Balance Dispenser)
Page 173
Carefully review all work completed, being sure all mechanical joints are thoroughly
tightened and electrical connections sealed.
Open the product crash valves and restore power to the dispenser.
With the power on, but no nozzles authorized, the VP1000 should not be running
(unless the ambient temperature is below 40F), but the power LED (yellow) should
be energized on the interface module.
Authorize one handle and the vacuum system should activate when the gasoline
flow control valve is engaged. Repeat for all other nozzles, individually testing each
nozzle on each side of dispenser. With each authorization, one of the green LEDs
on the interface module should illuminate and the VP1000 activate.
Note: For unihose dispensers, conduct individual tests for each product grade on
each side of the dispener to ensure that the same LED activates for all grades on the
same side. If the other LED activates, wiring needs to be corrected.
Authorize one nozzle and listen to the speed of the VP1000. With only one nozzle
activated, the speed will be slower than if a nozzle on each side is activated. Activate
a nozzle on the other side of the dispenser and listen for the speed to change.
To test the tightness of the vapor plumbing installed on the suction side of the
system requires a 0-100 water column gauge. Connect the gauge into the 1/4 test
port of the reducing tee installed earlier in section 8, photo I. Continue by following
and completing the START-UP / NEW INSTALLATION / WARRANTY / ANNUAL
TESTING FORM.
ARB Approved IOM Executive Orders VR-201-E and VR-202-E (Vista Series Wayne Balance Dispenser)
Page 174
With the pump running, a fault can be simulated by shorting, with a jumper wire, the
FAULT INPUT (purple wire) to FAULT COMMON (orange). This should cause the
motor to shut off, the solenoid valves to lose power and the dispenser to shut down.
Also, as long as the short is maintained, the red LED will be illuminated. Removing
the short will not automatically reset the module. To reset the module, remove
the short, remove power to the dispenser for twenty seconds and restore power.
The module should now be reset and the red led extinguished. This can also be
accomplished by using the power reset (PWR RESET) on the module.
If diagnosing a problem where the LED is already illuminated, a steady light indicates
a low current condition, therefore expect a vane or rotor problem. If the LED is
blinking, that indicates a high current condition and would expect to find a jammed
rotor or vapor line flooded with product. See Start-up / New Installation / Warranty /
Annual Testing Form.
The electronics of the motor will make three attempts to have a successful start of
the motor. If it detects a problem, on the fourth unsuccessful start, it will short the
fault line to signal minus (DC-) and shut down the electronics.
MC100 Interface Module
ARB Approved IOM Executive Orders VR-201-E and VR-202-E (Vista Series Wayne Balance Dispenser)
Page 175
Use a spill cloth when removing the cover, as there may be some gasoline inside the pump cavity.
4. Carefully turn the rotor assembly by hand until the shaft key notch
is at the 12 oclock position. (See Figure 1)
Notch
Figure 1
5. Remove the rotor, vanes and shaft key from the pump housing.
VP1000VRC
Carbon Rotor
(limited availability)
Note: Place your hand or a container under the rotor while removing.
Do not use any sharp objects that would scratch the surfaces of
the pump cavity, pump shaft, rotor, or vanes.
6. Rotate the shaft by hand. If the shaft does not rotate freely, the
entire vacuum pump needs replacement (p/n VP1000-5).
7. If the rotor and vanes are cracked, chipped, excessively worn or
excessively dirty, the rotor and vanes should be replaced because
cleaning will not remedy these conditions (p/n VP1000VRC or
VP1000VRC-P).
8. If there is no visible damage, use a lint-free cloth with isopropyl
alcohol to clean the rotor and vanes.
Shaft Key
Vane
Notch
Figure 2:
VP1000VRC-P
Enhanced
Carbon Rotor
10. Reposition the shaft (if necessary) so that the shaft key notch is
in the 12 oclock position. Install the cleaned original or new shaft
key onto the shaft.
11. Carefully install the cleaned original or new rotor onto the shaft
followed by the cleaned original or new vanes into the rotor.
Note: The rotor assembly should slide on to the shaft easily, without
excessive force. (Rotors and vanes are reversible)
Shaft Key
Vane
12. Lightly lubricate and install the new O-Ring for the pump housing.
Note: Do not allow any lubricant to get inside the pump housing.
13. Install the pump cover using the four Allen head screws and lock washers removed in step 3 and cross tighten.
Note: Use caution when sliding the pump cover over the O-Ring seal to prevent cutting or tearing.
14. Re-connect the vapor piping to the IN and OUT ports of the pump cover assembly that was removed in Step 2.
15. Re-apply power. Test for normal operation. (See VP1000 Vacuum Performance Test Procedure)
ARB Approved IOM Executive Orders VR-201-E and VR-202-E (Vista Series Wayne Balance Dispenser)
Page 176
TELEPHONE
SERVICE TECHNICIAN
STATION ADDRESS
CITY
DISPENSER MAKE
STATE
SIDE A
DISPENSER EQUIPMENT CHECKLIST - Parts A-1 and A-2
YES
A-1
Is all the installed dispenser hanging hardware listed in Exhibit 1 of Executive Order
VR-201 or VR-202?
A-2
Proper installation of the VP1000 requires the test port and ball valve on the inlet side
of the vacuum pump. Are the test port and ball valve installed correctly?
NO*
*If the answer to either A-1 or A-2 is NO, the Healy Warranty is Void.
A-3
THE FOLLOWING TEST WILL PERFORM A POSITIVE PRESSURE LEAK CHECK OF THE VACUUM PUMP,
DISPENSER VAPOR PIPING, HANGING HARDWARE AND ALL NOZZLES ON BOTH SIDES OF THE
DISPENSER.
THE VP1000 OUTLET IS NOT CONNECTED TO UNDERGROUND PIPING DURING THIS TEST.
CAUTION: REGULATE GASEOUS NITROGEN TO 2.5 PSI (~70 WC) MAXIMUM BEFORE TESTING
1. Install a 0-100 inch water column ( wc) mechanical gauge at the VP1000 test port.
2. Use the water column gage positive (high) pressure port.
3. Gaseous nitrogen gas can now be connected to the outlet (exhaust) port of the VP1000.
4. Test pressure cannot exceed 70 wc.
5. Slowly introduce the gaseous nitrogen to a pressure between 60 70 wc.
6. After reaching the pressure range, close the valve supplying the gaseous nitrogen.
7. Record the initial pressure reading on the gauge - observe and record the final pressure reading after 60 seconds.
8. Leaks must be repaired when the pressure falls more than 4 wc in 60 seconds.
9. Retest until all leaks have been repaired.
10. Record test results in Section A-4.
A-4
PRESSURE TEST
2.5 PSI (~70wc) Maximum
ARB Approved IOM Executive Orders VR-201-E and VR-202-E (Vista Series Wayne Balance Dispenser)
Page 177
SIDE B
Warranty Service
Complete Troubleshooting Sections
B-1 and B-2
B-2
Re-Assemble / Reset Vacuum Pump and Module. (Power must be removed from both the vacuum pump and
the module for 20 seconds to reset the system) using the power reset switch on the MC100 module.
B-3
1.
2.
3.
4.
B-1
B-4
Dispenser
Vaacuum Test
B-5
Audible Increase
Test
B-6
Install 0-100 inch water column ( wc) vacuum mechanical gauge at the VP1000 test port.
Authorize the dispenser for fueling. The VP1000 will begin to run.
Close the ball valve at the pump inlet.
Record the initial vacuum reading on the gauge observe and record the final vacuum reading after 60
seconds.
5. Open the ball valve at the pump inlet.
6. Leaks must be repaired when the vacuum reading falls more than 4 wc in 60 seconds.
7. Retest until all leaks have been repaired.
8. Record data in Section B-4.
Note: If the initial vacuum reading is less than 60 wc, it could indicate a problem with the VP1000.
Remove the dispenser from service. Use the troubleshooting section of the manual to investigate
problem or contact the FFS Technical Help Desk at 800-984-6266 for assistance.
VACUUM TEST Using
VP1000 as vacuum source
With one side of the dispenser authorized (VP1000 running) and the ball valve at the pump inlet open, dispense
in handheld position a minimum of 0.5 gallons of fuel into a vehicle or test tank. Record the vacuum level while
dispensing. Repeat test for the other side of the dispenser.
1. Side A Dispensing Vacuum ____________ wc
2. Side B Dispensing Vacuum ____________ wc
Note: If the dispensing vacuum is less than 60 wc, remove the dispenser from service. See the troubleshooting section of the manual or contact FFS Technical Help Desk at 800-984-6266 for assistance.
Test the VP1000 Vacuum Pump for normal operation. Use the 6 step procedure titled, Testing the VP1000
Vacuum Pump for normal operation using the following test procedure: in Section 1.1 (Weekly Inspection and
Testing) of the Healy Systems Scheduled Maintenance document in the ARB Approved Installation, Operation
and Maintenance Manual for the Healy Phase II EVR System not Including ISD. This is to verify that the pump
recognizes when both sides of the dispenser are activated for fueling.
Does the VP1000 Vacuum Pump change speeds (audible increase) when both sides are activated for fueling?
Yes No
If the answer is no, use the troubleshooting section of the manual to investigate problem or contact the
FFS Technical Help Desk at 800-984-6266 for assistance.
Repairs - Comments