CVS 1000L Electro Pneumatic Positioner
CVS 1000L Electro Pneumatic Positioner
CVS 1000L Electro Pneumatic Positioner
20 30 40 50 60
40 50 60 70 20 30
70
Stroke 30mm
PIPING CONNECTION
NOTE:
To avoid moisture, oil, or dust from entering the
product, please carefully select the supply
pressure compressor.
Supply Pressure Condition
1. Dry air with at least 10C lower than ambient
temperature.
2. Keep away from dusty air. Filter can only sort 5
micron or larger.
3. Avoid oil.
4. Comply with ANSI/ISA-57.3 1975(R1981).
5. Not to be used beyond the range of
1.4 - 7 kgf/cm
2
(20 - 100 Psi).
6. Set air filter regulators supplied pressure 10%
higher than actuators spring range pressure.
Pipe Condition
1. Make sure the inside of the pipe is empty.
2. Do not use pipeline that is squeezed or has holes.
3. To maintain flow rate, use the pipeline that has
more than a 6mm inner diameter.
4. Do not use an extremely long pipeline system. It
may affect flow rate due to the friction inside the
pipeline.
Piping Connection with Actuator
YT-1000 series single acting type is set out to use
OUT1 port. OUT1 port should be connected with the
supply pressure port from the actuator when using
single acting type spring return actuator. For double
acting, the piping connection can be changed due to
the operation direction. Please refer to the following
diagrams when piping.
(Figures 9 - 11)
CVS Controls Ltd.
Product Manual: CVS Rack & Pinion Actuator
7
CVS Controls Ltd.
Process Management
And Instrumentation
OUT1
OUT1
SUP.
AIR
SUPPLY
YT-200
OUT
AIR
SUPPLY
YT-200
OUT
OUT 1
OUT 2
OUT 2
SUP.
OUT 1
OUT 1
OUT 2
AIR
SUPPLY
AIR
SUPPLY
OUT 2
SUP.
OUT 1
INPUT
SIGNAL
4~20mA
DIRECT
ACTION
REVERSE
ACTION
OUT 2
OUT 1
OUT 2
SUP. OUT 1
POWER CONNECTION
Connection - Connection Port
1. Connection port size is 1/2 NPT.
NOTE: REFER TO THE CANADIAN ELECTRICAL
CODE FOR HAZARDOUS WIRING METHODS.
Connection Power
1. Open the terminal box cover.
2. Locate the poles and connect them properly.
Make sure to fasten the connection.
3. Close the terminal box cover. (Figure15)
ADJUSTMENT
Adjustment - Zero Point
1. Set supply signal at 4mA or 20mA and rotate
adjuster clockwise or counter-clockwise to adjust the
actuators initial point. When setting the initial point,
the specification of valve and system must be taken
into account. Please refer to Figure 17 for
increase/decrease of the zero point.
2. When a single acting actuator with spring is used,
please check if the pressure level, which is indicated
on the positioner, is the same as the supplied pressure
level.
CVS Controls Ltd.
Product Manual: CVS Rack & Pinion Actuator
8
CVS Controls Ltd.
Process Management
And Instrumentation
Upper Side
Lower Side
Ground
Red (+)
Black (-)
Adjustment - Span
1. After setting zero, supply 20mA or 4mA of signal.
Check the actuators stroke. If the stroke is too low,
adjust the span towards the (+) direction.
If the stroke point is too high, adjust the span towards
the (-) direction. (Figure 18)
2. Changing span points affects the zero point setting,
so the zero setting must be set again. After setting
zero point, confirm the span point. This step must be
repeated until both points are properly set.
3. After setting is completed, tighten lock screw.
Adjustment - A/M Switch (Auto/Manual)
1. A/M switch adjusts the valve operation to automatic
or manual.
2. When produced, YT-1000L is set at A(Automatic).
If user prefers the positioner setting as M(Manual),
the setting can be changed by turning the switch
counter-clockwise. (Figure 19)
3. If it is set as M(Manual), the air pressure will be
supplied to the actuator directly. Always set back to
A(Automatic) after setting change.
4. If OUT2 in single acting actuator or double acting
actuator is used, the A/M switch will not operate.
Adjustment - Seat Adjuster
1. Seat adjustment is set according to the customers
request before the positioner is delivered. Please do
not adjust the seat adjuster.
2. Seat adjuster is always used for double acting
actuators and adjusted when the pressure balance
point must be changed. Please do not touch the seat
adjuster, because it can affect the positioners
performance.
Adjustment - Orifice
1. If the size of the actuator is too small relative to the
flow rate, the positioner can have hunting. In order to
avoid hunting, orifice can be used. There are three
types of orifice.
CVS Controls Ltd.
Product Manual: CVS Rack & Pinion Actuator
9
CVS Controls Ltd.
Process Management
And Instrumentation
Lock Screw
Lock Screw
Seat Adjuster
Auto Manual Switch
Output
Pressure
Output
Pressure
Output
Pressure
High Pressure Balance
(0.9~1.0Ps) - Normal
Med. Pressure Balance
(0.5Ps) - Normal
Low Pressure Balance
(0.4~0.5Ps) - Normal
Balanced Point
Balanced Point
Balanced Point
Input Pressure
Ps=Supply Pressure
10
2. Remove the o-ring from OUT1 and OUT2 port and
insert appropriate orifice. After inserting orifice, replace
the o-ring. Make sure there are not any substances
entering into the port. (Figure 21)
3. If hunting persists after inserting the orifice, please
contact CVS Controls Ltd. or its appropriate agent.
TROUBLESHOOTING
Positioner does not respond to the input
signal.
1. Check supply pressure level. The lever must be at
least 1.4 kgf/cm
2.
For spring return type actuator, the
supply pressure level has to be larger than the springs
specification.
2. Check if the input signal is properly supplied to the
positioner. The signal should be 4~20mA DC.
3. Check if zero pint or span point is properly set.
4. Check if the positioners nozzle has been blocked.
Also, check if the pressure is supplied to
the positioner and the pressure is being exhausted
through the nozzle. If the nozzle has been blocked by
any substances, please send the product for repair.
5. Check if the feedback lever has been installed
properly.
The pressure of OUT1 reaches exhausting
pressure level and does not decrease.
1. Check A/M Switch. If the switch has been damaged,
replace the switch or pilot relay valve.
2. Check for a gap or damages between the nozzle
and the flapper. If damaged, pleae contact
CVS Controls Ltd.
The pressure is exhausted only by the A/M
switch.
1. Check if the positioners nozzle has been
blocked. Also, check if the pressure is supplied
to the positioner and the pressure is being
exhausted through the nozzle. If the nozzle has been
blocked by any substances, please contact
CVS Controls Ltd.
Linearity is too low
1. Check if the positioner is properly positioned.
Especially if the feedback lever is parallel to the
ground at 50% point.
2. Check if zero and span point have been properly
adjusted. If either one of the values is being adjusted,
another one must be adjusted as well.
3. Check if the supply air pressure level is stable from
the regulator. If the level is unstable, the regulator
must be replaced.
Hysteresis is too low
1. In case of a double acting actuator, check if seat
adjustment has been properly performed. Please
contact CVS for any further inquiries regarding the
seat adjustment.
2. Backlash can ccur when the feedback lever and
lever spring loosen. To avoid backlashing, please
adjust the lever spring.
3. Check if the connection bar to the feedback lever is
tightly fastened.
CVS Controls Ltd.
Product Manual: CVS Rack & Pinion Actuator
CVS Controls Ltd.
Process Management
And Instrumentation
Orifice Diameter
Orifice
O - Ring (P5)
OUT2
OUT1
Actuator Size Orifice Size Suffix Symbol
90 cm
3
less O 1 1
90 - 180 cm
3
O 2 2
180 cm
3
more none 3
NOTES:
CVS Controls Ltd.
Product Manual: CVS Rack & Pinion Actuator
11
CVS Controls Ltd.
Process Management
And Instrumentation
Head Office