CompTrol 7000

INDEX 57
Issue 4.09

AIR CONDITIONING MICROPROCESSOR

OPERATING INSTRUCTIONS
© STULZ GmbH, Hamburg
Contents
1. Presentation of the system ........................................................................................5
2. Hardware components ...............................................................................................6
2.1 I/O controller (C7000 IOC) ................................................................................................................6
2.1.1 Board design .............................................................................................................................6
2.1.2 Assignment - I/O controller ........................................................................................................7
2.2 EDIO - extension board for digital in- and outputs .............................................................................9
2.2.1 Board design .............................................................................................................................9
2.2.2 Assignment - 1st EDIO board..................................................................................................10
2.3 EAIO - extension board for analogous in- and outputs ....................................................................12
2.3.1 Board design ...........................................................................................................................12
2.3.2 Assignment - EAIO ..................................................................................................................13
2.4 EEIO extension board for EEV ........................................................................................................14
2.4.1 Board design ...........................................................................................................................14
2.5 EBUS-extension board for RS485 bus ............................................................................................15
2.5.1 Board design ...........................................................................................................................15
2.5.2 Assignment - EBUS.................................................................................................................15
2.6 C7000 Advanced - Terminal (C7000 AT) .........................................................................................16
2.6.1 Board design ...........................................................................................................................16
2.7 Driver module ..................................................................................................................................17
3. Operator interface ....................................................................................................18
3.1 Operational elements - C7000 IOC .................................................................................................18
3.2 Operational elements - C7000 Advanced........................................................................................20
4. Controller start ..........................................................................................................21
4.1 Start - C7000 Advanced ..................................................................................................................21
5. Bus communication .................................................................................................25
5.1 System architecture with the C7000 ................................................................................................25
5.2 System architecture with the C7000 Advanced ...............................................................................26
5.3 Bus Layout.......................................................................................................................................27
5.3.1 General....................................................................................................................................27
5.3.2 Configuration of the IO bus .....................................................................................................27
5.3.3 Preparation before Installation ................................................................................................28
5.3.4 Setting the Bus Address ..........................................................................................................28
5.3.5 Bus overview ...........................................................................................................................29
5.3.6 Special cases ..........................................................................................................................30
6. Operation ...................................................................................................................33
6.1 Info level ..........................................................................................................................................33
6.1.1 Info commands - C7000 ..........................................................................................................33
6.1.2 Overview structure ..................................................................................................................34
6.1.3 C7000 Advanced Menu structure - Info level...........................................................................35
6.2 Control level .....................................................................................................................................45
6.2.1 Control commands - C7000 ....................................................................................................45
6.2.2 C7000 Advanced Menu structure - Control level .....................................................................46
6.3 Config Level .....................................................................................................................................64
6.3.1 C7000 Advanced Menu structure ............................................................................................64
7. Special functions ....................................................................................................101
7.1 Raised floor pressure control ........................................................................................................101
7.2 Changeover of the water circuits - CW2 units ...............................................................................102
7.3 Zone control ..................................................................................................................................104
7.3.1 Sequencing ...........................................................................................................................106
7.3.2 CW Standby Management ....................................................................................................107
7.3.3 Zone for proportional GE control ...........................................................................................107

E/0409/57/3
7.4 Free cooling with ECO-Cool Louver ..............................................................................................108
7.5 Pump station control ......................................................................................................................109
7.6 Summer-/winter operation .............................................................................................................114
8. Default configurations ...........................................................................................115
8.1 Preconfigurations ..........................................................................................................................125
9. Alarm treatment ......................................................................................................126
9.1 Alarm display .................................................................................................................................126
9.2 Possible Alarm texts ......................................................................................................................127
9.3 Component-related alarms ............................................................................................................128
9.4 Alarm Reset...................................................................................................................................128
9.5 Alarm texts in the case of hardware errors ....................................................................................129
10. Configuration notes .............................................................................................130
10.1 Loading a new Software ..............................................................................................................131
10.1.1 Operation of the program "C7000-Service.exe" ..................................................................132

This manual is based on the software versions IOC-V4.05 and AT-V4.04.

E/0409/57/4
1. Presentation of the system
The C7000 control system offers a maximum of opera- intelligent management of high/low pressure-alarms, a
ting safety for industrial applications combined with two proportional fan speed control which opens a wide spec-
versions for the operator interface. The C7000IOC takes trum of applications and time-based functions like:
charge of the control in itself and the optional C7000 - week timer
Advanced serves as a comfortable operator interface. - unit sequencing within definable unit groups
Distributed intelligence in networking cells represents the
most reliable system whenever operating safety is the The heart of the C7000 control system is the C7000 I/O
target. This is exactly how the Stulz C7000 control system controller on which up to 4 EAIO/EDIO boards for addi-
works, each A/C unit possesses its own controller while tional in- and outputs can be perpendicularly plugged.
all controllers can be linked together in a bus system. The exploitation of the third dimension provides maxi-
This way a natural redundancy is obtained which assu- mum accessibility and an easy board exchange in case
res the system functions with the least expense. And of modifications.
we locate the intelligence there where it is needed, in
the A/C unit without long cables which could mess up The C7000 control systems manages 3 busses:
the signals. 1. IIC-bus for the communication between the C7000
I/O controller and the EAIO/EDIO boards
Whereas the C7000 Advanced provides the well known
operating comfort - as did already the C6000 - the 2. RS485 IO-bus for the communication among the
C7000IOC can bring to bear his advantages when it A/C units
comes to modifications in the configuration of a large 3. RS485 BMS-bus for the communication with a
air conditioning system with several units. building management system
The idea of the second interface was to use a device
which is present everywhere, a computer. Using the For service purposes like software download and control
screen of a Laptop or PC provides the best way of visu- via laptop a RS232 interface is located on the I/O cont-
alizing parameter settings. This is the most comfortable roller the same as on the C7000 Advanced.
way of doing a component-related configuration.

Beyond the basic air conditioning functions, the C7000


control system provides some interesting features like an

Analogous (A) and digital (D) in- and outputs


A-IN A-OUT D-IN D-OUT Interfaces
IOC-board 5 4 11 7 1 x RS485 IO-bus, terminals
EAIO-board 4 4 / / 4 x IIC-Bus, SUB-D15
IOC-board
EBUS conn. SUB-D15
EDIO-board / / 8 6
RS232, SUB-D9
M a x i mu m e q u i p m e n t w i t h E E I O - B oard
EAIO-board IIC-Bus, SUB-D15
IOC + 3 EAIO 17 16 11 7
EDIO-board IIC-Bus, SUB-D15
IOC + 3 EDIO 4 4 35 25
EEIO-board IIC-Bus, SUB-D15
M a x i mu m e q u i p m e n t w i t h o u t E E I O - Board
I/O board conn. SUB-D15
IOC + 4 EAIO 21 20 11 7 EBUS-board
RS485 BMS-bus, terminals
IOC + 4 EDIO 5 4 43 31 2 x RS485 IO-bus + BMS,
terminals
EAIO-Board: Extension board for analogous in- and C7000AT-board
2 x RS232 BMS + service,
outputs SUB-D9
EDIO-Board: Extension board for digital in- and out-
puts IIC-Bus: internal data bus in the IO controller
EEIO-Board: Extension board for up to two electronical
expansion valves
EBUS- Board: Extension board for a RS485 bus

E/0409/57/5
2. Hardware components
Technical Data:
2.1 I/O controller (C7000 IOC) Voltage supply: 24(+15%) V (AC)
2.1.1 Board design Power consumption: 9,6 VA
Fuse: 2 A time-lag
Operating temp.: 5°C...40°C
Storage temp.: -30°C...60°C

Onboard LEDs
The function of the digital inputs is displayed by
green LEDs:
ON: voltage present
OFF: no voltage (alarm, failure)
The function of the digital outputs is displayed by
red LEDs:
ON: relay active
OFF: relay passive
The OK-LED displays the IIC-bus clock. This is the
pulse for sensor evaluation too.
The TX1/RX1-LEDs indicate data traffic on the
I/O bus (port 1).
The Error-LED lights up at any time, when an alarm
has occurred.

Pin position of X1
1 10 21 30 41 50

11 20 31 40 51 60

Service port JP 7 DIP-switches plug for EBUS JP 9 JP 8


RS232 for bus addr. ext. board Jumper setting depending on sensor types
Jp n° Pos.1-2 Pos.2-3
AIN 1 2
Analogous input

4-20mA

AIN 2 3
4 sockets 0-10V
for AIN 3 4
EDIOs/ AIN 4 5
EAIOs/
AIN 5 6 without function
EEIO
OK-LED
TX1-LED Jumper for software download
RX1-LED Jp n° Pos. 1-2 Pos. 2-3
Error-LED
7 Operation Download
Bus driver module
for IO-bus
For further information,
see page 17.

JP 6 EBUS activation
Jp n° Function, when set
8 EBUS Port 2 disabled
9 none
Jp8 has to be set, if no EBUS extension board is
present. On the contrary, it has to be removed to
enable the extension RS485 bus on a plugged
green LEDs for red LEDs for JP 2 3 4 5 EBUS extension board.
digital inputs 1-11 digital outputs 1-7
Jp 9 must always be set.

E/0409/57/6
2.1.2 Assignment - I/O controller
The assignment depends on the unit version (DX1, DX2, CW). A DX1-unit is an A/C unit with one refrigerant circuit, a DX2-unit
is an A/C unit with two refrigerant circuits. A CW-unit is an A/C unit with one or two water circuits (CW/CW2-versions).
E.g.: ALD 351 GE2 -> DX1, ASU 332 ACW -> DX2, ASD 960 CW -> CW

Pin Designation DX1 DX2 CW


1 24VAC
Power supply Power supply Power supply
2 GND
3 GND - - -
4 Din 1 Fan failure Fan failure Fan failure
5 Din 2 Compressor failure Compressor failure 1 Pump failure 1
6 Din 3 Low pressure Low pressure 1 Chiller failure
7 Din 4 E-reheat failure 1-3 E-reheat failure 1-3 E-reheat failure 1-3
8 Din 5 Filter alarm Filter alarm Filter alarm
9 Din 6 Humidifier failure/ENS 20µS Humidifier failure/ENS 20µS Humidifier failure/ENS 20µS
10 Din 7 Water detection Water detection Water detection
11 Din 8 Ext. alarm 1 Compressor failure 2 Ext. alarm 1
Ext. alarm 2 /
12 Din 9 Low pressure 2 Ext. alarm 2
Hotgas reheat alarm (OTE)
13 Din 10 Remote on/off Remote on/off Remote on/off
14 Din 11 Fire stat Fire stat Fire stat
15 Dout 1 (NO)
16 Dout 1 (COM) Enable fan Enable fan Enable fan
17 Dout 1 (NC)
18 Dout 2 (NO)
19 Dout 2 (COM) Compressor Compressor 1 Pump 2
20 Dout 2 (NC)
21 Dout 3 (NO)
22 Dout 3 (COM) E-reheat 1 E-reheat 1 E-reheat 1
23 Dout 3 (NC)
24 Dout 4 (NO)
E-reheat 2 / Hot gas E-reheat 2 / Hot gas
25 Dout 4 (COM) E-reheat 2 or HWR
reheat / HWR reheat / HWR
26 Dout 4 (NC)
27 Dout 5 (NO)
Dehumidification or Dehumidification or
28 Dout 5 (COM) on/off Humidifier or ENS
Hotgas-bypass Hotgas-bypass
29 Dout 5 (NC)
30 Dout 6 (NO)
31 Dout 6 (COM) Common alarm 1 Common alarm 1 Common alarm 1
32 Dout 6 (NC)
33 Dout 7 (NO)
34 Dout 7 (COM) Louver Compressor 2 Louver
35 Dout 7 (NC)

HWR - hot water reheat

E/0409/57/7
Assignment - I/O controller (continued)

Pin Designation DX1 DX2 CW


36 +15V
Active sensor 1 Active sensor 1 Active sensor 1
37 GND
38 Ain 1 Room/return air temp. Room/return air temp. Room/return air temp.
39 Ain 2 Room/return air humidity Room/return air humidity Room/return air humidity
40 +15V
Active sensor 2 Active sensor 2 Active sensor 2
41 GND
Supply temperature / Supply temperature / Supply temperature /
42 Ain 3
Water temperature (CW) Water temperature (CW) Water temperature (CW)
43 Ain 4 Supply humidity Supply humidity Supply humidity
44 +Ub
45 GND
no function no function no function
46 Ain 5
47 GND
48 Aout 1
Fan Fan Fan
49 GND
50 Aout 2 GE/CW valve/pump 1 GE/CW valve/pump 1 CW valve/pump 1
51 GND (GE) or actual temp. (GE) or actual temp. or actual temp.
52 Aout 3 Humidifier/ENS or Humidifier/ENS or Humidifier/ENS or
53 GND actual humidity actual humidity actual humidity
54 Aout 4
G-valve/pump 2 (G) G-valve/pump 2 (G) CW2-valve/pump 2
55 GND
56 Port 1-H
RS485-I/O-bus RS485-I/O-bus RS485-I/O-bus
57 Port 1-L
58 Port 1-H
RS485-I/O-bus RS485-I/O-bus RS485-I/O-bus
59 Port 1-L
60 +15V - - -
X10 SUB-D 15 Bus 3 IIC (socket1) Bus 3 IIC (socket1) Bus 3 IIC (socket1)
X11 SUB-D 15 Bus 3 IIC (socket2) Bus 3 IIC (socket2) Bus 3 IIC (socket2)
X12 SUB-D 15 Bus 3 IIC (socket3) Bus 3 IIC (socket3) Bus 3 IIC (socket3)
X13 SUB-D 15 Bus 3 IIC (socket 4) Bus 3 IIC (socket 4) Bus 3 IIC (socket 4)
X14 SUB-D 15 EBUS exp. (plug) EBUS exp. (plug) EBUS exp. (plug)
X15 SUB-D 9 RS232 service port (plug) RS232 service port (plug) RS232 service port (plug)

E/0409/57/8
2.2 EDIO - extension board for digital in- and outputs
2.2.1 Board design

Technical Data:
Power consumption: 10,1 VA
Operating temp.: 5°C...40°C
Storage temp.: -30°C...60°C

Pin position of X1

1 10 21 30

11 20 31 not assigned 40

Onboard LEDs
The function of the digital inputs is displayed by
green LEDs:
ON: voltage present
OFF: no voltage (alarm, failure)
The function of the digital outputs is displayed by
red LEDs:
ON: relay active
OFF: relay passive

enlarged section for onboard LEDs

LDO
13

12

green LEDs for red LEDs for


digital inputs 12-19 digital outputs 8-13
of the first EDIO-board 11

The EDIO-board is an expansion board for digital LDI 8


inputs and outputs. It can be plugged on the I/O 19
controller board at each of the 4 sockets and will be 18
recognized by the IOC due to a self test. 17
10
16
15
14
13 9
12

E/0409/57/9
2.2.2 Assignment - 1st EDIO board
The assignment depends on the unit version (DX1, DX2, CW). Explanation see page 7.
If several EDIO boards exist, the EDIO board on the lowest socket is detected as the first EDIO board and the in- and outputs
are assigned correspondingly when using the "loaddefault" command. The IOC board features four sockets for this purpose:
X10, X11, X12 and X13. X10 represents the lowest socket.

Pin Designation DX1 DX2 CW


1 Din 12 UPS UPS UPS
Pump 1(GE) failure / Pump 1(GE) failure /
2 Din 13 Fan 2 failure
Pump 3 (glycol) Pump 3 (glycol)
Pump 2 (G) failure / Pump 2 (G) failure /
3 Din 14 Pump 2 failure
Pump 4 (glycol) Pump 4 (glycol)
4 Din 15 Drycooler failure Drycooler failure Fan 3 failure
CW disable/DX enable or CW disable/DX enable or
5 Din 16 Ext. alarm 3
ext. alarm 3 ext. alarm 1
Ext. alarm 2 /
6 Din 17 Ext. alarm 4 Ext. alarm 4
Hotgas reheat alarm (OTE)
7 Din 18 ENS 5µS Ext. alarm 3/ENS 5µS ENS 5µS
8 Din 19 Phase control Phase control Phase control
9 Dout 8 (NO)
Pump 1 (GE) / Pump 1 (GE) /
10 Dout 8 (COM) Enable fan 2
Pump 3 (glycol) Pump 3 (glycol)
11 Dout 8 (NC)
12 Dout 9 (NO)
13 Dout 9 (COM) Drycooler 1 Drycooler 1 Enable fan 3
14 Dout 9 (NC)
Drycooler 2 or winter Drycooler 2 or winter
15 Dout 10 (NO) Winter operation
operation operation
Drycooler 2 or winter/sum- Drycooler 2 or winter/sum-
16 Dout 10 (COM) Winter/summer operation
mer operation mer operation
Drycooler 2 or summer Drycooler 2 or summer
17 Dout 10 (NC) Summer operation
operation operation
18 Dout 11 (NO)
Pump 2 (G) / Pump 2 (G) /
19 Dout 11 (COM) Pump 2
Pump 4 (Glycol) Pump 4 (Glycol)
20 Dout 11 (NC)
21 Dout 12 (NO)
22 Dout 12 (COM) E-reheat 3 E-reheat 3 E-reheat 3
23 Dout 12 (NC)
24 Dout 13 (NO)
Louver /
25 Dout 13 (COM) Humidifier on/off /ENS free
Humidifier on/off
26 Dout 13 (NC)
27 PWM1
free free free
28 GND
29 PWM2
E-reheat 1 (proportional) E-reheat 1 (proportional) E-reheat 1 (proportional)
30 GND
X10 SUB-D 15 Bus 3 IIC (plug) Bus 3 IIC (plug) Bus 3 IIC (plug)
Pins 31 to 40 are not assigned.

E/0409/57/10
2nd EDIO board
The assignment depends on the unit version (DX1, DX2, CW). Explanation see page 7. A third and fourth EDIO board are not
concerned by the "loaddefault" command, which means that the in- and outputs are not assigned.

Pin Designation DX1 DX2 CW


1 Din 20 free Ext. alarm 4 free
2 Din 21 free free free
3 Din 22 free free free
4 Din 23 free free free
5 Din 24 free free free
6 Din 25 free free free
7 Din 26 free free free
8 Din 27 free free free
9 Dout 14 (NO)
10 Dout 14 (COM) free free free
11 Dout 14 (NC)
12 Dout 15 (NO)
13 Dout 15 (COM) free free free
14 Dout 15 (NC)
15 Dout 16 (NO)
16 Dout 16 (COM) free free free
17 Dout 16 (NC)
18 Dout 17 (NO)
19 Dout 17 (COM) Drycooler 3 Drycooler 3 free
20 Dout 17 (NC)
21 Dout 18 (NO)
22 Dout 18 (COM) Drycooler 4 Drycooler 4 free
23 Dout 18 (NC)
24 Dout 19 (NO)
25 Dout 19 (COM) free free free
26 Dout 19 (NC)
27 PWM3
free free free
28 GND
29 PWM4
free free free
30 GND
X10 SUB-D 15 Bus 3 IIC (plug) Bus 3 IIC (plug) Bus 3 IIC (plug)
Pins 31 to 40 are not assigned.

E/0409/57/11
2.3 EAIO - extension board for analogous in- and outputs
2.3.1 Board design

Technical Data:
Power consumption: 10,1 VA
Operating temp.: 5°C...40°C
Storage temp.: -30°C...60°C

Pin position of X1

1 10 21 30

11 20 31 not assigned 40

The EAIO-board is an extension board for analogous


inputs and outputs. It can be plugged on the I/O
controller board at each of the 4 sockets and will be
recognized by the IOC due to a self test.
There are several jumpers on board - 5 for each
input - which serve to adapt the board to different
sensor types.

How to use the Jumper setting table:


- choose the analogous input at which you have
connected a sensor.
- in the same line you can see the jumpers which
relate to this input.
- in the lower part of the table you can read in each
column the setting depending on the sensor type
you connected.
Example:
You have connected a 0-10V sensor at AIN 8.
The corresponding jumpers are 300-304. Jumper
301,303,304 must be set on position 1-2, Jumper
302 on 2-3 and Jumper 300 not at all.
Jumper 100-400
(enlarged section)
corresp. Jumper 101-404 Table: Jumper setting
input (enlarged section)
Jumper designation
AIN 6 101 102 103 104 100
Analogous

AIN 9
AIN 7 201 202 203 204 200
input

AIN 8 301 302 303 304 300


AIN 8 AIN 9 401 402 403 404 400
Sensor

0-10V 1-2 2-3 1-2 1-2 0


type

AIN 7
4-20mA 1-2 1-2 1-2 1-2 0

AIN 6

E/0409/57/12
2.3.2 Assignment - EAIO
The assignment depends on the unit version (DX1, DX2, CW). Explanation see page 7.

Pin Designation DX1 DX2 CW


1 +Ub/Ib
Universal sensor 4
2 Ain 6 Universal sensor 4 Outside temperature / Universal sensor 4
3 GND Outside temperature evaporation pressure 1/ Outside temperature
evaporation temp. 1 (OTE)
4 GND
5 +Ub/Ib
Universal sensor 5 Universal sensor 5
6 Ain 7 Condensation pressure / Condensation pressure 1/ Universal sensor 5
7 GND condensation temp. condensation temp. 1 Water temp. 2 (CW2)
(OTE) (OTE)
8 GND
9 +Ub/Ib
Universal sensor 6 Universal sensor 6
10 Ain 8 Evaporation pressure / Condensation pressure 2/ Universal sensor 6
11 GND evaporation temp. condensation temp. 2 - free -
(OTE) (OTE)
12 GND
13 +Ub/Ib
Universal sensor 7
14 Ain 9 Universal sensor 7 Water temp. (G) or Universal sensor 7
15 GND Water temp. (G) evaporation pressure 2 / - free -
evaporation temp. 2 (OTE)
16 GND
17 Aout 5 Suction valve / pump 3 Suction valve / pump 3
(glycol)/ compressor1 or (glycol) / compressor1 or Actual humidity
18 GND actual humidity actual humidity
19 Aout 6 El. HGBP 1 / drycooler El. HGBP 1 / drycooler /
Actual temperature
20 GND actual temperature compressor 2/ act. temp.
21 Aout 7
HWR valve HWR valve HWR-valve
22 GND
23 Aout 8 Pump 4 (glycol) or Proportional
Pump 4 (glycol)
24 GND electr. HGBP valve 2 dehumidification
X10 SUB-D 15 Bus 3 IIC (plug) Bus 3 IIC (plug) Bus 3 IIC (plug)
HGBP - Hotgas bypass

E/0409/57/13
2.4 EEIO extension board for EEV
2.4.1 Board design

VCM 2 In A/C units with one refrigerant circuit the EEIO


board is equipped with one VCM module (VCM
1). In A/C units with two refrigerant circuits the
VCM 1 EEIO board is equipped with two VCM modules
(VCM 1 and VCM 2).

Pin position of X1

1 10

11 20

Pin Designation DX1 DX2


1 24 VAC
Power supply Power supply
2 GND 24 VAC
3 12 VDC
Back-up battery Back-up battery
4 GND 12 VDC
5 MO 11A/M0 1A EEV 1 step motor winding 1a EEV 1 step motor winding 1a
6 MO 11B/MO 1B EEV 1 step motor winding 1b EEV 1 step motor winding 1b
7 MO 12A/M0 2A EEV 1 step motor winding 2a EEV 1 step motor winding 2a
8 MO 12B/MO 2B EEV 1 step motor winding 2b EEV 1 step motor winding 2b
9 MO 21A/M0 3A - EEV 2 step motor winding 1a
10 MO 21B/MO 3B - EEV 2 step motor winding 1b
11 MO 22A/M0 4A - EEV 2 step motor winding 2a
12 MO 22B/MO 4B - EEV 2 step motor winding 2b
13 P0 1/PT4-1-out Output evaporation pressure 1 Output evaporation pressure 1
14 P1 1/PT4-1-in Input evaporation pressure 1 Input evaporation pressure 1
15 NTC1 1/NTC1 Input coil outlet temperature 1 Input coil outlet temperature 1
16 NTC2 1/AGND GND GND
17 P0 2/PT4-2-out - Output evaporation pressure 2
18 P1 2/PT4-2-in - Input evaporation pressure 2
19 NTC1 1/NTC2 - Input coil outlet temperature 2
20 NTC2 1/AGND - GND
X10 SUB-D 15 Bus 3 IIC (plug) Bus 3 IIC (plug)

E/0409/57/14
2.5 EBUS-extension board for RS485 bus
2.5.1 Board design

Technical Data:
Power consumption: 11,3 VA
Operating temp.: 5°C...40°C
Storage temp.: -30°C...60°C

Driver module

To adjust the driver module see chapter 2.7.


Port 2

Note:
Port 3 for the time being without function.

2.5.2 Assignment - EBUS

Pin Designation Function


1 Port 2-H
RS485 BMS-bus
2 Port 2-L
3 Port 3-H
no function
4 Port 3-L
X10 SUB-D 15 EBUS extension (socket)

Note:
Remove jumper 8 on the IOC board to use the EBUS port 2.

E/0409/57/15
2.6 C7000 Advanced - Terminal (C7000 AT)
2.6.1 Board design

RS232 - service port (SUB-D 9)


Technical Data:
Dimensions: 270 x 110 x 40 mm
Voltage supply: 24(+15%) VAC
Power consumption: 14 VA
Fuse: 2 A time-lag
Operating temp.: 5°C...40°C
Storage temp.: -30°C...60°C

Driver module for This figure shows the jumper


RS485-2 (BMS-bus) position for the board at the end
X4 Driver module for of the bus.
RS485-1 (IO-bus) For details to the driver module,
see next page.

RS232 - BMS port (SUB-D 9)


Pin
14
13 Pin Designation Function
X12 12
CPU 14 Port 2-L
11 RS485 BMS-bus
10 13 Port 2-H
9
12 Port 1-L
8 RS485 I/O-bus
7 11 Port 1-H
Real- 6
10-3 free terminal none
time 5
4 2 GND
clock Power supply
3
1 +24VAC
2
HW1 1

HW0
Fuse T2A
Jumper X6: Pos. A: Board in download mode

Contrast adjustment for display

E/0409/57/16
2.7 Driver module
The driver module has the following features:
1. a static bus termination (120 Ohm), which can be activated by a jumper.
2. a circuit to set the bias for the bus. By means of two jumpers either a low bias (bus middle) or a high bias (bus
end) can be set.
3. protection against electrostatic discharge (ESD) impulses on the data lines

The interference immunity of the bus is increased by the driver module.


As far as the jumper settings are concerned, only the two settings shown below are allowed. The jumpers must be
changed blockwise. Other settings result in an unstable bus communication.

Participant at the end of the RS485 bus


This figure shows the jumper position for the parti-
cipant at the end of the bus.
The rightmost jumper is located in a position where
the termination resistor is activated.
The other jumpers are set for a high bias.

Jumper to activate the termination resistance


{

Two jumpers to set the bias on the bus.

Participant in the middle of the RS485 bus


This figure shows the jumper position for the partici-
pant in the middle of the bus.
The rightmost jumper is located in a position where
the termination resistor is deactivated.
The other jumpers are set for a low bias.

E/0409/57/17
3. Operator interface
3.1 Operational elements - C7000 IOC
The operational elements for the C7000 IOC i.e. the I/O when connecting the laptop to the IOC service port.
controller consist of the keyboard of your PC or laptop. Start the terminal program.
You operate the C7000 IOC by specified commands
which follow an easily comprehensible syntax. If your PC is not equipped with a serial RS232 interface,
To establish the connection from your PC to the C7000 you may use a RS232-USB converter.
you need a 9-line cable with SUB-D 9 connectors at both
ends (crossed type), which can be obtained as an option You can now communicate with the connected I/O cont-
and a terminal program e.g "C7000-Serice". roller (ioc), in return the IOC sends the following prompt
Connect the cable at a serial port of your PC and at the to your PC:
service port X15 on the IOC. "ioc ##:>", where ## represents the bus address.

To prevent a destruction of electronical elements due to


potential differences, use a laptop with battery supply

The commands can be classified into three major categories:


1. bus specific control commands
2. commands related to A/C unit components
3. commands concerning the whole A/C unit

1. bus command 2. component command 3. A/C unit command


iobus sensor 1 equip
iobusok is 1
comp 1
state
suctionv 1
ups
gecwv
wprg
gvalve
event
drycool 1
log 1
pump 1
option
eheat 1 exalarmin 1
gasheat zone 1
pwwheat loaddefault dx1
humi 1
dehumi The commands on a lightgrey (yellow) background need
no further parameters. The commands which are followed
fan 1 by a number need this number because there are several
louver 1 components of the same type.

Each command displays a detailed help for further pa- The commands of the 2nd and 3rd category will be
rameters (if there are any) when it is followed by "h" like largely explained in the context of the description of the
e.g. "comp h". C7000 functions.
A command of the second (component command) or
third category (A/C unit comm.) which is typed in without The iobus command edits the actually stored IO-bus-
any parameters displays all the information about its configuration.
subject (except "loaddefault ###" which is an execution This command is a control command and shows neither
command). help nor information but execute the command right after
pressing the return/enter-key.

E/0409/57/18
General
The counting of any digital or analogous in- or output
begins with number 1. Despite this the digital/analogous Whenever a parameter is expressed by a logical function,
in- or output 0 can be assigned to any component. This 0 means no, disabled, 1 means yes, enabled.
will allow the component to stay part of the configuration
even if it does not take part in the control. If at unit start no valid configuration is found, a minimal
A double assignment of inputs and outputs is technically configuration for single refrigerant circuit-units is loa-
possible but only reasonable in exceptional cases. ded.
Outputs in the languages English and German are avai- Please note that no year date below 2000 can be en-
lable at the service interface. tered.
If within a command, where the input of a number is
expected, nothing is entered, the terminal program in-
terprets this as "0" (command "coolingprio" is interpreted
as "coolingprio 0").

E/0409/57/19
3.2 Operational elements - C7000 Advanced

<> = Selector key

Ok = Confirmation key

Reset = Reset key

LED = Alarm

LED = On/off

= On/off key
Audible indicator Display

Selector key You can select menus and change parameters with the selector key
Confirmation key You acknowledge the functions/parameters selected with the selector key with the con-
firmation key.
Reset key Alarm signals are acknowledged with the reset key. Press it once to silence the alarm tone.
Press it a second time to clear the alarm message (if the cause has been eliminated).
LED alarm This LED display flashes in the event of an alarm and remains lit after the reset key has
been pressed once.
LED start/stop This LED display lights up when at least one IOC within the bus is switched on.
Start/stop key The control of the selected A/C unit is switched on/off with this key.
Audible indicator The audible indicator issues an alarm tone when an alarm has occurred.
Display The display shows data, operating conditions and information for the operator's
guidance.

Operation - Navigation through the menus


The principal keys to navigate in and across the menus are the selector key
Selection menu
and the confirmation key, which have the function of the mouse for a PC.
The cursor, to keep the analogy with a PC, is represented by the inverse
display of a field content. This field may contain an expression, a number
or a symbol.
There are two types of menus: Selection menus and parameter menus. In
selection menus you can choose a menu point with the help of the selector
key and after having pressed the confirmation key it will bring you to the next
submenu. To get to the next menu on a level above there is a "Return"-field
Parameter menu
in the top left corner of every menu.
In parameter menus, which represent the end of a menu branch, you can
select parameters with the selector key, but if you press the confirmation key,
the parameter is displayed black on a clear background with a black frame
and indicates this way the change mode. By the selector key you can change
the parameter value. Pressing the confirmation key finishes the modification
and displays the cursor inversely again.
In a few parameter menus, there is the comment "more" in the bottom fra-
me line, which indicates that another window will be displayed after the last
parameter. You can also reach this window by typing the selector key "<"
when the cursor is on the field "return".

Note:
After the C7000AT has displayed a submenu of an IOC for 10 minutes without
key activation, it will show the main menu of the corresponding unit again.

E/0409/57/20
4. Controller start
4.1 Start - C7000 Advanced Main menu for C7000IOC

After having switched on the power


supply of the C7000 Advanced the bus
overview will appear.
With the selector key you can choose
the unit which you want to control.
A symbol/unit which is selected, is dis-
played inversely.
When you have selected a C7000IOC
and confirmed by the OK key, the main
menu for the C7000IOC is displayed.
When you have selected a C7000AT
and confirmed by the OK key, after
having entered the password 2718
the main menu for the C7000AT is Main menu C7000AT
displayed.

After having marked the last bus par- = OK


ticipant position (bus address 14 in
the example) you get to the following
display, with the selector key, where all
units are marked. In this state you can Confirmation view
switch on/off the whole system by the
local on/off key.
If some units are in operation, all units
are switched off if you press the on/off
key.
If you press the OK-button when all
positions are marked the existing con-
figuration is confirmed after the request >
and entry of the password 2718.

After the confirmation of this window


by "OK" followed by the password 2718
the placement view is displayed. In this
window you can shift the C7000AT, from
which you operate the system (ME) to
another position with the selector key. Placement view
By this you modify the bus address.
(MEold at position 0 and MEnew at po-
sition 17)

>
Finally you can adjust the time and date
by selecting the clock.
The following items can be adjusted in
sequence:

- Year, Month, Day, Hour, Minute, Second.

All active bus participants synchronize their


time to this setting.

E/0409/57/21
Main menu for a C7000 AT

If you select the C7000 AT for further


adjustments and confirm with OK
you will receive after having entered
the password 2718 the following
display with the menu ramification
as shown below:

1. In the bms-menu you can adjust the global address of the C7000 AT,
and an available interface on the C7000AT which can be either RS232 or
RS485 the same as the protocol and, if applicable, one of several data
point lists according to the BMS requirement.
You have further possibilities to adapt the system to the BMS by the
menu points „Handshake“ and „Baudrate“. For further information, see
BMS manual.

2. Here you can set the alarm delay for the bus alarm, which will be ge-
nerated when the bus is interrupted.

3. In the system menu you can switch on (-1-) or off the alarm buzzer.
Further you can adjust the buzzer pitch.
Menu item "Temp. unit" allows you to choose between degree Fahrenheit
or degree Celsius.
In the menu item languages you can adjust the operator language.
The info submenu simply displays the software version of the C7000 AT.

In menu item "backlight" you can choose between "on" (in this case the
light remains lit permanently) and "auto", here the light is switched out
automatically 10 minutes after the last key activation. With the first key
activation the light is switched on again.

E/0409/57/22
Main menu (for a C7000 IOC)

Menu line
Alarm text Control mode
Temperature

} Main function
Humidity
Maintenance symbol
Special software OTE
Stop cause UPS operation
Stop symbol Winter operation
Day/Night operation
Unit name
Alarm symbol Bus address Time
Global address

If you select an I/O controller you will receive the main menu as shown right
with the possibility to choose one of the three submenus "Info", "Operate" or
"Config".

In the middle of the window the control type (Room or Supply air) is displayed
and the corresponding actual values (Room or Supply air) below.
Below the actual values a symbol indicates, whether the unit runs in day or night
operation. Day operation corresponds to operation at the first setpoint tempe-
rature. Night operation corresponds to operation at the second setpoint.

Day operation Night operation

Further Symbols
This symbols lights up, when the controller has switched over to winter
operation. At summer operation the symbol is not visible.
This symbols lights up, when a voltage is detected at the input for UPS
operation or if UPS operation is requested by a BMS.
This symbols lights up, when the special OTE software is enabled and
the OTE mode is set.
This symbols lights up, when the maintenance interval which can be
adjusted in the config menu is expired.

Stop causes
The I/O-controller can be stopped by several functions or devices, which are
displayed on the C7000 AT.

This symbol indicates, that the IOC has been stopped.


stopped by fire alarm
The following symbols show the cause of the unit stop.
stopped by remote On/Off (remote switch connected to digital input)

stopped by PC (by BMS program)

stopped by internal timer (week program)

stopped by the on/off-key at the C7000 AT or by the command "state


stop" via the IOC service port.

stopped by the sequencing

E/0409/57/23
Symbols for operating states
When the control is in operation, the following symbols indicate the unit status
on the main menu. These symbols are not displayed in the submenus.

Cooling
Parameter values
Heating Instead of numerical values two other displays
are possible:
Humidification 1. ??? - value requested at the IOC, without
response yet
Dehumidification 2. XXX - component not configured

Symbols for alarm messages


When an alarm has occurred the following symbol is displayed in the
left bottom corner.

Passwords
To access the Operate level and the Config
level a password is required.
There are 4 passwords in total, a user-specific
password for the Operate and Config level each
and a master password for each level.
The user-specific password can be modified
and is "0000" for both levels with the delivery.
The master passwords are reserved for service
staff and can not be modified.

Entering the password


The digits can be modified by the selector
key, after you have pressed the confirmation
key. After the digit adjustment confirm with the
confirmation key and pass over to the next digit
with the selector key ">".
When you have reached the last digit at the
right, you access the main menu of the Operate
resp. Config level by activating the selector key
">" (if the password was right).

There is no limitation for the number of


attempts.

The passwords for the "operate" and "config"


level are saved on the IOC board. So it is
possible for example to adjust the "operate"
password "1234" for an IOC with bus address
3 and the "operate" password "5678" for an
IOC with bus address 5.

E/0409/57/24
5. Bus communication
5.1 System architecture with the C7000
Minimum configuration
C7000

RS-232

Notebook or PC equipped
with a terminal program
to communicate with the
I/O-controller

The basic configuration of the C7000 consists of an I/O controller. Everytime the name C7000 is used without any appendix
like "Advanced" it refers to the I/O controller.

Maximum configuration

C7000 C7000 C7000

RS-232

in all:
20 bus participants Notebook or PC equip-
ped with a terminal
program to commu-
RS-485 I/O-Bus nicate with the I/O-
controller
Up to 20 IOCs can be linked in a C7000 I/O bus system. The C7000 AT Box which serves to configure or to operate the A/C
units equipped with an I/O controller also takes part in the RS-485 bus.

C7000 C7000

RS-232

C7000 AT Box

in all:
19 IOCs
+ 1 C7000 AT Box Notebook or PC equip-
ped with a terminal
program to commu-
RS-485 I/O-Bus nicate with the I/O-
controller

E/0409/57/25
5.2 System architecture with the C7000 Advanced

Minimum configuration Maximum configuration (concerning n° of A/C units)


C7000 Advanced C7000 C7000 C7000 Advanced

in all:
19 units

The minimum configuration RS-485 I/O-Bus


consists of an A/C unit with The maximum configuration in relation to the number of A/C units consists of 18 A/C units with
a C7000 Advanced and an an I/O controller and 1 A/C unit with a C7000 Advanced and an I/O controller which results in
I/O controller. 20 bus sharing elements.

Maximum configuration (concerning the operational facilities & the n° of A/C units)
C7000 Advanced C7000 Advanced C7000 Advanced

in all:
10 units with IOC and
C7000 Advanced

RS-485 I/O-Bus
The maximum configuration in relation to the operational facilities and the number of A/C units consists of 10 A/C units with an
I/O controller and a C7000 Advanced which also results in 20 bus sharing elements.

E/0409/57/26
5.3 Bus Layout

5.3.1 General
The IO bus consists of maximum 20 participants. In case of the C7000 system only C7000 IOC or C7000 AT bus
participants can be in the IO bus.
Each bus participant has its own IO bus address which must only appear once in the data bus.
The IO bus addresses range from 0 to 19.

The display of the C7000 AT shows the IO bus addresses in a bus overview (start window) as follows:

5.3.2 Configuration of the IO bus

The configuration of the bus is done automatically during start-up and operation. That means that all connected
bus participants log on automatically. The same applies in case of a failure - all bus participants are logged off
automatically.

Following preconditions must be fulfilled:

1. Each bus participant has its own bus address which must be unique in the bus system.
2. Bus addresses must range between 0 and 19.
3. All bus participants are connected appropriately with bus cables according to requirements (see next page).
4. The bus has to be terminated at the beginning and at the end.

Each bus participant saves the latest registered configuration during shut-down. Furthermore the bus participant
expects the same configuration after its next start-up.
In case new systems have logged on to the bus during the shut-down period, the bus participant detects these
systems and records them in the bus configuration without editing a message or an alarm.
In case a system has been disconnected from the bus which was active before shut-down, the bus participant
detects this condition and a bus error is triggered in the bus participant after the end of the alarm delay.

The same happens when a bus participant (IOC or C7000AT) is de-energized during operation.

All systems that are connected to the bus detect a bus error automatically. Accordingly this error is displayed on
the AT and IOC.

E/0409/57/27
5.3.3 Preparation before Installation

You need a shielded cable with two lines twisted and a cable impedance of 120 Ω (Re-
commendation Belden 9841), which you have to connect from unit to unit at the terminals Bus DIP-switch
56-59 of each I/O controller (IOC). In the example below the bus termination of the two addr. 1 2 3 4 5
units which form the end of the bus (IOC 01 and IOC 17) must be enabled.
The example of a RS485 bus shows a typical application with 7 IOCs and 1 C7000 AT. 0 0 0 0 0 0
1 1 0 0 0 0
2 0 1 0 0 0
3 1 1 0 0 0
IOC bus IOC bus IOC bus
addr:01 addr:03 addr:07 4 0 0 1 0 0
5 1 0 1 0 0
RS 485 6 0 1 1 0 0
7 1 1 1 0 0
Bus termination: IOC bus
addr:08 8 0 0 0 1 0
See description of the driver
module on page 17. 9 1 0 0 1 0
terminals terminals
on IOC on IOC 10 0 1 0 1 0
Screen 11 1 1 0 1 0
56 57 58 59 56 57 58 59 IOC bus
HIGH addr:15 12 0 0 1 1 0
13 1 0 1 1 0
LOW
14 0 1 1 1 0
15 1 1 1 1 0
IOC bus IOC bus AT bus 16 0 0 0 0 1
addr:17 addr:14 addr:18
17 1 0 0 0 1
18 0 1 0 0 1
5.3.4 Setting the Bus Address
19 1 1 0 0 1
The bus address is adjusted with the dip-switches on the IOC. The table at the right
shows the corresponding adjustment for all possible bus addresses. Please note that
the counting begins with 0 and ends with 19. A "1" means dip-switch in "ON"-position.
If you set an address higher than 19, this one is reduced to 19 by the software.
An IOC is delivered with the address 1 as standard, a C7000 AT has the address 0 as
standard.
On a C7000 AT the bus address is adjusted in the placement view.

Placement view
With the selector key you can shift the C7000 AT represented by
symbol "ME" to a new position and change its bus address this
way.
Left display: old position address 0, new position address 17.
To confirm the selection press the OK key.
Now the bus configuration must be confirmed to avoid the display
of a bus error, because a bus participant with the address 0 does
not exist anymore.
The addresses of all other participants are not affected by this.

in short: How to get to the placement view and how to confirm the
1. connect units by bus lines configuration, see chapter 4, page 21.
2. set bus terminations (beginning/end)
3. adjust bus-IDs
4. confirm bus configuration

E/0409/57/28
5.3.5 Bus overview
Symbol for a C7000IOC
C7000AT "ME", on which this Actual temperature
content is displayed .
Operational sta-
Symbol for a C7000AT te of the control
At this unit an
alarm has oc-
curred.
Stop cause Actual humidity
Operational state of the This unit cannot be reached.
control of a selected IOC Global address of the selected
IOC
Selected IOC + Bus address

Example for a de-energized or disconnected (from the bus) IOC with data bus address 6

The AT with the bus address 19 edits the following configuration after the IOC 6 has been switched off :

ID glob.adr. dev.type reliab. config. Column "config" displays, which bus


0 - unknown 0% 0
addresses are expected as active
1 - unknown 0% 0
2 - unknown 0% 0 bus participants.
3 - unknown 0% 0
4 - IO-Controller 100% 1
5 - IO-Controller 100% 1
6 - unknown 0% 1 error
7 - IO-Controller 100% 1
8 - unknown 0% 0
9 - unknown 0% 0
10 - unknown 0% 0
11 - unknown 0% 0
12 - unknown 0% 0
13 - unknown 0% 0
14 - unknown 0% 0
15 - unknown 0% 0
16 255 AdvancedTerminal 100% 1
17 255 AdvancedTerminal 100% 1
18 255 AdvancedTerminal 100% 1
19 255 AdvancedTerminal me 1
When the availability of a con-
ERROR IN THE BUS CONFIGURATION DETECTED. figured unit is 0%, an error is
indicated.
The AT 19 detects, that the IOC 6 has been available in the bus, but can not be reached anymore. When the dis-
connected unit is switched on again, the bus error is automatically deleted at all bus participants. A bus error can
also be deleted by inputting the command "iobusok" at an IOC or an AT.

E/0409/57/29
There is another way to delete a bus error on the AT and to transfer
so the actual bus configuration.
For this purpose all systems have to be selected simultaneously
and afterwards the OK-button has to be pressed.
After entering the password (2718) the faulty unit (address 6) is
deleted from the bus. The bus error disappears.

5.3.6 Special cases


Disconnecting a bus

An important aspect concerning the display of the IO bus is that the display is always exclusively dependent on
the C7000AT which is in use at the moment.
For example a bus disconnection between the bus participants 4, 5, 6, 7, 16, 17 and the bus participants 18, 19
results in two completely independently running busses.
However the bus participants 4, 5, 6, 7, 16, 17 report the bus participants 18, 19 as faulty and vice versa.

IO bus belonging to the bus participant 17

ID glob.adr. dev.type reliab. config.


0 - unknown 0% 0
1 - unknown 0% 0
2 - unknown 0% 0
3 - unknown 0% 0
4 1 IO-Controller 100% 1
5 1 IO-Controller 100% 1
6 1 IO-Controller 100% 1
7 1 IO-Controller 95% 1
8 - unknown 0% 0
9 - unknown 0% 0
10 - unknown 0% 0
11 - unknown 0% 0
12 - unknown 0% 0
13 - unknown 0% 0
14 - unknown 0% 0
15 - unknown 0% 0
16 255 AdvancedTerminal 95% 1
17 255 AdvancedTerminal me% 1
18 - unknown 0% 1 error
19 - unknown 0% 1 error

ERROR IN THE BUS CONFIGURATION DETECTED.

E/0409/57/30
IO bus belonging to the bus participant 19

ID glob.adr. dev.type reliab. config.


0 - unknown 0% 0
1 - unknown 0% 0
2 - unknown 0% 0
3 - unknown 0% 0
4 - unknown 0% 1 error
5 - unknown 0% 1 error
6 - unknown 0% 1 error
7 - unknown 0% 1 error
8 - unknown 0% 0
9 - unknown 0% 0
10 - unknown 0% 0
11 - unknown 0% 0
12 - unknown 0% 0
13 - unknown 0% 0
14 - unknown 0% 0
15 - unknown 0% 0
16 - unknown 0% 1 error
17 - unknown 0% 1 error
18 255 AdvancedTerminal 100% 1
19 255 AdvancedTerminal me 1

ERROR IN THE BUS CONFIGURATION DETECTED.

The bus error has an adjustable alarm delay. Once this delay has expired the bus error is triggered. This delay is
separately adjustable for each bus participant.

Address conflict
The second failure concerning the bus is a conflict in the address. A conflict in the address occurs when two or
more bus participants have the same bus address.
That means that the two bus participants which have the same address send simultaneously data to the bus. This
on the other hand would destroy the data on the bus.
Communications via the bus would be limited.

But this does not happen because bus participants stop the data transfer immediately as soon as they detect that
another participant with the same address is sending a data package.
That means that they stop sending and hence do not participate in the communication on the bus anymore.

An address conflict is triggered immediately as soon as a unit has performed a deactivation.

In our example two ATs have the bus address 19.


As soon as the communication on the bus starts, one of them detects that the address 19 has been assigned
twice and performs a deactivation.

The result is that only one bus participant with the same address is active after a short time.

E/0409/57/31
The user is requested to choose another bus address at the C7000AT which has detected the address conflict.
For it the following positioning window is displayed.

ID glob.adr. dev.type reliab. config.


0 - unknown 0% 0
1 - unknown 0% 0
2 - unknown 0% 0
3 - unknown 0% 0
4 1 IO-Controller 100% 1
5 1 IO-Controller 100% 1
6 1 IO-Controller 100% 1
7 1 IO-Controller 100% 1
8 - unknown 0% 0
9 - unknown 0% 0
10 - unknown 0% 0
11 - unknown 0% 0
12 - unknown 0% 0
13 - unknown 0% 0
14 - unknown 0% 0
15 - unknown 0% 0
16 255 AdvancedTerminal 100% 1
17 255 AdvancedTerminal 100% 1
18 - unknown 0% 1
19 255 AdvancedTerminal me 1 conflict If an address conflict exists, this one
is indicated for the corresponding
BUS ADDRESS CONFLICT AT ADRESS ‚ME‘ = 19 DETECTED. bus participant.

The other AT with the bus address 19 continues operation without any interference.

After the bus address has been assigned properly the address conflict will be solved automatically.
An address conflict can only be displayed at the unit, which causes the address conflict, because it excludes itself
immediately from bus communication. If this unit is a C7000AT, this is displayed on the display. An address conflict
can only be displayed at unit "ME".
If the unit is a C7000IOC the error LED on the board flashes, the state of the bus configuration can then be re-
quested by using the service port.

E/0409/57/32
6. Operation
6.1 Info level
6.1.1 Info commands - C7000
Generally each component- or A/C unit command which is entered without parameters only displays information
without changing adjustments. However, the following commands give a general overview about the unit state and
configuration.
equip - shows the components and its number, also the extension cards (dig/ana)
state - shows the unit- and functional (cooling, heating etc.) runtimes and the unit/component state
is 1 - - setpoints, actual zone/unit values, limit values
is 2 - - alarm delay, priority, common alarm assignment for each limit value alarm
is 3 - - control type, sensor limitation values, cooling priority, winter operation, ups mode, outside temp. for
condensation pressure reduction, gradient for press. reduction, winter start delay, bus/global address,
temperature difference for overload activation, last service, service interval,
- assignment of in/outputs: common alarm, winter operation, remote on/off, ups operation,
actual temp./humidity, CW cooling off
wprg - shows the programmed timer function for the week (week program)

events - shows all registered events (maximum 200, alarms & unit on/off)
event 1 Prints the last events from number 1 to 20
event 2 Prints the last events from number 21 to 40
:
event 10 Prints the last events from number 181 to 200
event 20.07.2007 Prints all events of this date
event comp Prints all events which contain the expression „comp“
event clear Erases the event memory
event 1 13 Prints the events from number 1 to 13

ups - shows the ups (uninterrupted power supply) configuration


water - shows all settings concerning the water alarm.
fire - shows all settings concerning the fire alarm.
phase - shows all settings concerning the phase alarm.
flow - shows all settings concerning the water flow alarm.
service - shows all settings concerning the service alarm.
ain - shows the assignment of the analogous inputs.
aout - shows the assignment of the analogous outputs.
din - shows the assignment of the digital inputs.
dout - shows the assignment of the digital outputs.

option - Shows all information about activated special software options


e.g.: 002. Restart after fire (active)
option all Shows all possible special software options
001. OTE
002. Restart after fire
003. automatic alarm reset after limit value excess
004. SATS
005. HP DSC
option 5 1 Activates special software option number 5
option 3 0 Deactivates special software option number 3

E/0409/57/33
6.1.2 Overview structure

Due to the complexity of the menu ramification, it was im- Config) is placed, has no line identification. The rows
possible to display entire menu branches on one page. below for the submenus are named from "a" to "f".
We therefore applicated a city map screen on the menu There are up to 4 submenu levels.The first two submenu
overview, consisting of columns and rows which serve to levels are horizontally located. The third submenu level
easily relocate single submenus within the overview. is vertically located. The fourth submenu level is marked
Each page features a capital letter and is subdivided in by a grey background.
three columns.
The Info menu runs from page A to E. On the pages which follow the overview, only the pa-
rameter menus are explained, these are normally the
The Operate menu runs from page F to J.
menus of the lowest submenu level.
The Config menu runs from page K to S.
The top row, in which the top menu (Info, Operate or

Top level menu

1st submenu level

2nd submenu level

Sector B1d

sector 3rd submenu 4th submenu


level level

B1d

E/0409/57/34
A
6.1.3 C7000 Advanced Menu
structure - Info level

a
1 2 3
b
c
d
e
f
E/0409/57/35
B a
1 2 3
b
c
d
e
f
E/0409/57/36
C a
1 2 3
b
c +
(more)

d +
(more)

e
f
E/0409/57/37
D a
1 2 3
b
c
d
e
f
E/0409/57/38
E a +
(more)

1 2 3
b
c
d
e
f
E/0409/57/39
C7000 Advanced Values
Info
A1c This window shows the following temperatures:
1. The value, which is used for the control. It can also be a zone temperature.
These values represent an average value for each parameter, which is calculated
of all sensors of the units which are assigned to the same zone.
2. The adjusted setpoint
3. The setpoint shifted by the controller, the unit is controlled according to this pa-
rameter only. This value corresponds to the adjusted setpoint in most cases.
It may be different in the following cases by:
- week program - external setpoint shifting
- emergency operation - limitating control
- integral factor - HPDSC mode
4. The actual value of the room temperature sensor.
5. The actual value of the supply air temperature sensor.
A1d 6. The outside temperature

The corresponding humidity parameters are displayed in this window in the same
order.
1. The value, which is used for the control. It can also be a zone humidity.
2. Setpoint
3. Shifted setpoint
4. The actual value of the room humidity sensor.
5. The actual value of the supply air humidity sensor.

A1e
In this window the actual value and the setpoint for the differential pressure (pressure
gain in contrast to the room air pressure) in the raised floor is indicated.

A2b
Here the measured values of the cooling water circuits 1 and 2 are displayed.
1. Water temperature at the inlet, circuit 1
2. Water temperature at the outlet, circuit 1
3. Water temperature at the inlet, circuit 2
4. Water temperature at the outlet, circuit 2
5. Water pressure, actual value at the outlet
6. Water pressure setpoint at the outlet

A2c Here the measured values of the refrigerant circuits 1 and 2 are displayed.
1. Condensation pressure
2. Condensation temperature
3. Evaporation pressure
4. Evaporation temperature

A3b Here the temperature of a freely adjustable sensor is shown.


This value does not influence the control and is only displayed for information.

E/0409/57/40
C7000 Advanced Components
B2a Info
The C7000 Advanced gives a detailed repre-
sentation of the components' operating states.
In the window in the left margin the first five
menu items lead to submenus. In the last menu
item you can read the number of configured
external alarms.

B3c
In the following windows you can see the
operating state of each component:
-0- means component is off.
-1- means component is on.
B1c xxx means component does not exist.

Compressor operating state.

B2a This window displays the opening degree of


the G-valve in a percentage from 0 to 100.

For the suction valve, the GE/CW valve, the


hotgas bypass valve and the electronical ex- B3d
pansion valve (EEV) a submenu exists.
Each of the valves, except the G valve, can
appear twice in the cooling unit.

B3e

For the EEV a submenu exists for each valve.


B3f
The following values are displayed:
1. Superheat temperature
2. Superheat setpoint
3. Measured suction gas pressure
4. Saturated temperature
5. Measured suction gas temperature
B1e 6. Opening degree of the valve

In this menu the on/off state of the drycoolers


is displayed. Drycooler 1 may also be cont-
rolled proportionally, in this case the speed is
displayed from 0 to 100%.

B1f In this menu the on/off state of the pumps


is displayed. In case of speed controlled
pumps the actual speed is displayed from 0
to 100%.

E/0409/57/41
C7000 Advanced
B2b Info B2c
If your A/C unit is equipped with a heating,
the operating state is displayed in this window.
For proportional heating the actual capacity
is shown from 0-100%.
For the hot water reheat the actual capacity is
displayed in the shape of the opening degree
of the HWR valve.
In the submenu of the electrical heating the
number of configured electrical heatings and
the operating state is displayed. The first he-
ating can be quasi proportionally controlled
by pulse width modulation.

B3b If your A/C unit is equipped with a humidifier,


the operating state and the degree of steam
production of the humidifier is displayed in
this window.
In addition the display indicates whether the
dehumidification is switched on and whether
the dehumidification valve is opened. The
enabled dehumidification with a closed valve
indicates that the air is dehumidified by the
fan speed reduction.

C1b In this menu the number of configured fans


and louvers the same as the operating state
of the fans with the actual speed from 0-100%
is displayed.
If your A/C unit is equipped with louvers, -1-
C2c - C2f
indicates that the louver is open.

C2b This window displays the number of configu-


red sensors.
The submenus "D-IN", "D-OUT", "A-IN",
"A-OUT" serve for diagnosis purposes and
display the state of each digital and analogous
in/output.
In the first line the inputs from 1 to 4 are
displayed, in the second line the inputs from
5 to 8 etc.
The meaning of the displayed values can be
taken from the table below.

Display Signification
D-IN Voltage present -> no
1
alarm
D-OUT Relay activated* -> com-
1
ponent in service
A-IN 0-20mA, 0-10V corresp.
0-4095
to sensor type
A-OUT 0-4095 0-10V

* Exception: When dehumidification is carried


out, the relay is not activated.

E/0409/57/42
C7000 Advanced Zone
Info
D1a If the unit is assigned to a zone, in this window the values of the corresponding zone
are displayed. In the first line it is displayed if emergency operation for this zone is
activated. In the second line you see the sequencing cycle time. Then the room tem-
perature, the room humidity, the supply air temperature and the supply air humidity
of the zone are diisplayed.
If the determination of average values is disabled, these values correspond to the
measured unit values.

D1b Data logger

By the data logger you can save measured values or average values (zone data)
calculated by the controller and have them displayed in the shape of a graphical curve
so as to show the time course of these values.
Values of two different sensors can be simultaneously recorded.
You set the lapse of time which will be displayed. Further parameters (type of measured
value and cycle) can be adjusted in the service menu.
You can choose among 5 different lapses of time: hour (adjusting this lapse displays
the recent 3 hours), day, week, month and year.
The time lapse is displayed in horizontal direction, a vertical dashed line marks the
actual time.
In the vertical direction the range of the measured value within the limit values (if
existant for this type of value) is displayed. Two exterior dashed lines mark the limit
values. An interior dotted line marks the set value, if existant.
The course of the measured value is displayed by a continuous line.

Note:
Before these values can be displayed, the recording must be activated in the corre-
sponding Config menu.

C7000
The corresponding commands:
Type.............:1 (Unit room temp)
for data logger 1 each Store cycle......:15 Min
log 1 - displays adjustments, number of data and date Number of values.:938
of recent and eldest value. Youngest.........:11.08.2004 15:33:00
log 1 1 - displays the 20 recent values as follows. Eldest...........:01.08.2004 02:18:00
0001. 11.08.2004 15:33:00 Room temperature 22,9°C
0002. 11.08.2004 15:18:00 Room temperature 23,0°C
0003. 11.08.2004 15:03:00 Room temperature 23,1°C

log 1 2 - edits the 20 last but one values (value 21 to 40


going from the actual point of time).
log 1 72 - edits the eldest 20 values (value 1421 to 1440
going from the actual point of time).

log 1 15.05.2006 - edits all values of this day as far as stored.

log 1 1 13 - edits the values 1 to 13 going from the actual


point of time.
log 1 clear - deletes all stored values.

E/0409/57/43
C7000 Advanced
D2b Info Event-Log
All alarm messages and events of one A/C unit are listed in this window. The messages
contain the following information:
Alarm text, day and time. When the unit was started and stopped is also displayed.
Up to 200 events can be stored.

D3b Runtimes

The runtimes are shown in hours.


The unit runtime comprises all times, when the unit is not in a stop or standby
mode.
The stop time is counted, when the unit is in a stop or standby mode.
Stop mode means: Unit is supplied with power, the control is switched off.

D3c
The functional runtimes are displayed in a submenu.
The cooling runtime is counted each time when cooling is requested.
The heating runtime is counted each time when heating is requested.
The humidification runtime is the time in which the unit has humidified. The dehumidi-
fication runtime is counted each time when dehumidification is requested.
Runtime for free cooling is counted, when the opening degree of the GE valve is bigger
than zero, when no compressor request exists and if the GE valve is actually not used
for heating. Runtime for mixmode is counted, when the opening degree of the GE
valve is bigger than zero, when a compressor
D3d request exists and if the GE valve is actually D2c
not used for heating.

In another submenu the component runtimes


are displayed.
Here the fan and humidifier runtimes are
displayed.
For the components compressor, pump, E-
heating and drycooler exist further submenus
E1b of the kind as shown right.

Maintenance
In this menu the adjusted maintenance inter-
val and the date of the maintenance recently
carried out is displayed.

E2b
System
In this menu the software version and the unit
type are displayed.
The menu point "Option" leads to a submenu,
E2a which displays which special software options
are active.

Here the number of connected EAIO-, EDIO-,


EEIO- and EBUS-boards is indicated.
E3a

E/0409/57/44
6.2 Control level
6.2.1 Control commands - C7000

A typical control command is structured as follows:

top command sub-command

drycool 1 startsum 32,0


command component parameter parameter
number designation value

Following a summary of the most frequent sub-commands:

type 1/2/3.. sets the type of control (mostly 1=2-point control, 2 = proportional)
start #,# sets the startpoint (temperature or humidity according to the component)
startsum #,# sets the summer operation startpoint
startwin #,# sets the winter operation startpoint
hys #,# sets the hysteresis (for on/off-controlled components)
hyssum #,# sets the summer operation hysteresis
hyswin #,# sets the winter operation hysteresis
press # sets the pressure startpoint
grad #,# sets the gradient (for proportionally controlled components)
pretime # sets the pre-start time in seconds
preopen # sets the pre-opening of a valve in %
prespeed # sets the pre-speed of a fan or pump in %
conf 0/1 0 = deactivates a component from the configuration
1 = activates a component for the configuration
ain # assigns the analogous input # to the component (sensor)
din # / alarm # assigns the digital input # to the component related alarm
aout # assigns the component to the analogous output #
dout # assigns the component to the digital output #
commonalarm 0/1 0 = no common alarm when component alarm
1 = common alarm when component alarm
alarmdelay # sets the alarmdelay in seconds
alarmprio # assigns the alarm to alarm relay #
runtime # sets the runtime in hours
hand 0/1 0 = disables manual operation, 1 = enables manual operation
handon 0/1/# 0/1/# = switches off/on the component in manual operation or sets a value in % for pro-
portionally controlled components

E/0409/57/45
F
6.2.2 C7000 Advanced Menu
structure - Control level

a
1 2 3
b
c
d
e
f
E/0409/57/46
G a
1 2 3
b
c
d
e
f
E/0409/57/47
H a
1 2 3
b
c
d
e
f
E/0409/57/48
I a
1 2 3
b
c
d
e
f
E/0409/57/49
J a
1 2 3
b
c
d
e
f
E/0409/57/50
C7000 Advanced
Values
F1c Operate
The first item of the menu concerns the adjustment of temperature setpoints.The
following items serve to adjust the temperature limits, which are decisive for the
alarms "temperature/humidity too high/low".
Two temperature setpoints can be adjusted, setpoint 1 concerns the operation by
day, whereas setpoint 2 concerns operation at night according to the week timer
(page 78).
Following the limit values for the room air sensor. The "MIN" column contains the
values for the lower temperature limit and the "MAX" column relates to the upper
limits accordingly.
If e.g. the minimum room air temperature is passed under by the measured value,
the alarm "Room temperature too low" is displayed.
In the line below you can set the alarm delay in seconds.
The values for the supply air sensor can be adjusted in the same way.

F1d
You can set the same parameters for the air
humidity. However no difference between
day- and night setpoint is made.

F1e
Here you can input a setpoint for the raised
floor pressure. If this value is different from
zero, the raised floor pressure control will
begin. See chapter 7, special functions.

F2b
You can set alarm delays and limit values for
the water temperature. When the limit values
are exceeded, the alarms "Water tempera-
ture too low/high" are released.
For the operation of pump stations you can
set a pressure setpoint. The pressure setpoint represents the pressure increase by
the pumps.
When the C7000 is used to control a pump station, the water pressure is the only pa-
rameter which is controlled. This mode represents a special function of the C7000.
F3b
Here you can input a setpoint for the condensation pressure of the refrigerant. The
G valve is controlled according to this setpoint.
For the DX-mode and the mixmode in case of proportional GE control individual
values can be set. The setpoint for mixmode should be smaller than for DX mode
to discharge the compressor. This way free cooling by the water coil has a greater
part in total cooling.
For normal GE control only the DX value is operative.

C7000
The corresponding commands: Humidity (F1d)
Temperature (F1c), Water (F2b) sethumi 45,1
settemp 24.3 setwpress 3.0 minhumi room humi 3,0
nightsettemp 27.0 maxhumi supply alarmdelay 4

room Pressure (F1e) Refrigerant (F3b)


mintemp temp 15.0
supply airpressureset 60 cpset mix 12.3
maxtemp alarmdelay 4
water cpset dx 18.4
All combinations are possible.

E/0409/57/51
C7000 Advanced Components/Cooling
Compressor
G1c Operate
The parameters in the first four lines can be adjusted separately for compressor 1
and 2.
The start temperature for the compressor is entered as a positive difference to the
setpoint.
Two different start temperatures ➊a,➊b + hysteresis ➋a,➋b for summer and winter
operation can be entered.
The compressor pause is entered in seconds and serves to increase the service life
of the compressor by delaying the restart by the adjusted value. ➌

The compressor alarm delay ➍ can be adjusted the same as the low pressure alarm
➋b delay ➎a in seconds.
➋a
Comp.
ON
After the compressor start the low pressure alarm can be inhibited for an adjustable
time ➎b. If the unit is equipped with two compressors, the adjusted time is valid for
both compressors (1 and 2). This time avoids a low pressure alarm right after the
OFF compressor start when outside temperatures are low. The effect of this parameter
setpoint T/°C does not depend on the summer/winter operation.
➊a
➊b Compressor sequencing in units with two refrigerant circuits:
The controller software tries to equilibrate the compressor runtimes. Once in an
hour the software checks whether the difference between the runtimes is 20 hours
or more.
If this is the case and if the compressor with the bigger runtime has a smaller start
value than the other compressor, the start values and hysteresises for summer and
winter operation are exchanged between the compressors.

General:
The bullet items within the text refer to the corresponding com-
mand at the bottom of the page.
In general the parameters which can be modified, are num-
bered line by line from top to bottom. If a line contains several
parameters the bullet number is followed by a small letter for
each column.
For example, the parameter which is indicated by ➎b can be
found in the second column of the fifth line.

C7000
The corresponding commands:
➊a comp 1 startsum 0,6 ➎b winterdelay 180
➊b comp 1 startwin 1,2
➋a comp 1 hyssum 0,7
➋b comp 1 hyswin 0,7
➌ comp 1 pause 180
➍ comp 1 alarmdelay 5
➎a comp 1 alarmdelaylp 5

E/0409/57/52
C7000 Advanced Components/Cooling/Valves
Suction valve
G3d Operate
The start temperature for the suction valve is entered as a positive difference to the
room temperature setpoint. ➊
You can adjust a gradient, which determines the temperature range in which the
valve opening increases from 0 to 100%.➋

If the A/C unit is equipped with two refrigerant circuits, both refrigerant circuits can
be equipped with a suction valve.
Depending on how you choose the start point for the valve, the compressor starts
with partial or full capacity.

C7000
The corresponding commands:

➊ suctionv 1 start 0,2


➋ suctionv 1 grad 0,9

E/0409/57/53
C7000 Advanced Components/Cooling/Valves
GE-CW valve
Operate
G3e The start temperature ➊ for the GE/CW valve is entered as a positive difference to
the room temperature setpoint. For the second CW valve ➍ in line 4.
For the GE/CW-valve you can adjust a gradient ➋, which determines the temperature
range in which the valve opening increases from 0 to 100%. For the second CW
valve ➎ in line 5.
With the GE-off value in line 3 you determine a water temperature which establishes
the limit for GE-operation. If this value is exceeded, the GE-operation is switched off
by closing the valve and stopping the glycol pump. ➌

G3f
Electronical Expansion Valve (EEV)

Here you can adjust the setpoint for the superheating in normal operation ➊ and
the setpoint for the superheating in case of dehumidification ➋. Both values must be
entered as differences to the evaporation temperature.

Components/Cooling
Drycooler
G2e
The start temperature for the drycooler is entered as an absolute value for the water
temperature.
Two different start temperatures for summer ➊a and winter ➊b operation + hysteresis
➋ can be entered.
Note:
The summer/winter operation depends on the setting in the menu Config/Values
GE-mode. (see page 76)

The drycooler alarm delay can be adjusted in seconds. ➌


Drycooler
➋ ➋

ON

OFF
➊b ➊a T/°C
water
winter summer temp.
operation operation

C7000
The corresponding commands:
➊ gecwv 1 start 0,2 ➊ eev 1 supset 6,5 ➊a drycool 1 startsum 32,0
➋ gecwv 1 grad 0,9 ➋ eev 1 supsetdehum 7,2 ➊b drycool 1 startwin 15,0
➌ gecwv off 22 ➋ drycool 1 hys 3,0
➍ gecwv 2 start 0,2 ➌ drycool 1 alarmdelay 3
➎ gecwv 2 grad 0,9

E/0409/57/54
C7000 Advanced Components/Cooling
Pump
G2f Operate
Depending on which pump type you have configured, different parameters are de-
cisive. (see table 1)
The start temperature for the pump is entered as a positive difference to the room
temperature setpoint. ➊
The corresponding hysteresis for the pump stop is only valid for pumps with on/off-
control as the glycol pump.➋
For speed controlled pumps you can adjust a gradient, which determines the range
in which the pump speed increases from 0 to 100%.➌
The speed setpoint ➍ will only be used for the proportional GE control. For this a
GE-pump separate manual exists.
Pump The pump alarm delay can be adjusted in seconds. ➎
speed setpoint
100%
Table 1
Pump type (1) (2) (3) (4)
0%
Start temp. - ➊ ➊ -
➊ ➌ T/°C
Hysteresis - - ➋ -
Gradient - ➌ - -
Glycol-pump
Pump ➋ Pump type:
1: G pump for GE2 units of the series CyberAir 1
ON 2: GE pump for GE2 units of the series CyberAir 1
3: Glycol pump, external pump for units of type GE or
CW.
OFF 4: Pump station pump for units of the series CyberAir
➊ T/°C pump station (CPP)
setpoint

C7000
The corresponding commands:
➊ pump 1 start 0,1
➋ pump 1 hys 0,7
➌ pump 1 grad 0,6
➍ pump 1 speed 96
➎ pump 1 alarmdelay 6

E/0409/57/55
C7000 Advanced Components/Cooling
ECO Louver
G2b Operate
This function enables a "Free cooling" with outside air, which is directed by a louver
system. Three louvers are necessary, which will be controlled in parallel by a single
analogous output.

- Fresh air louver for the inlet of fresh outside air


- Circulating air louver for the circulation of the room air
- Exhaust air louver for the outlet of warm room air

The fresh air and exhaust air louver are operated in parallel, the circulating air louver
is operated in a reverse sense to these louvers. The setting is done by determinating
the sense of rotation at the louver actuators.

Free cooling is enabled, when:


1. room humidity is within determined limits (see diagram) and
2. outside air is cold enough. This means when the temperature of outside air is
below the EcoCool start value ➊.
Free cooling is stopped, when the outside temperature is above the EcoCool start
temperature ➊ + hysteresis ➋ or when the room air humidity is outside the limits.

The start temperature ➌ for the control must be entered as a positive difference to the
air temperature setpoint. In the fourth line you can set the gradient ➍, which defines
the range, in which the fresh air and exhaust air louver opens from 0 to 100% and
the circulating air louver closes in the same way.

Additionally to normal operation there exist an emergency operation. If no com-


pressor is in the condition to operate, the free cooling by EcoCool louvers is enabled
independently of the limits of air humidity and air temperature.

1. Enabling condition 2. Enabling condition


1 Humidific. hysteresis 1 ECO
2 2 Dehumidific. hysteresis Hysteresis

Outside
Humidific. Setpoint Dehumidif. ECO temp.
Start Humidity Start Start temp.
Humidific. Dehumidif.
Hysteresis Hysteresis

C7000
The corresponding commands:
➊ ecolv temp 18
➋ ecolv hys 1
➌ ecolv start 0,1
➍ ecolv grad 0,6

E/0409/57/56
C7000 Advanced Components/Heating
E-heating/Hotgas reheat/Hot water reheat
H1c Operate Depending on which heating type you have configured, different parameters are
decisive.
The start temperature for every heating is entered as a negative difference to the
room temperature setpoint. ➊
The hysteresis for the heating stop is only valid for heatings with on/off-control.➋
For proportional e-heatings/hot water reheats you can adjust a gradient, which
determines the temperature range in which the heating capacity increases from 0
to 100%.➌
The e-heating alarm delay can be adjusted in seconds. ➍

Only the first heating can be proportional. If this is the case and if there are several
H1d heatings (up to 3), only the start value and the gradient of the first heating are decisive
for the control. Each time the proportional heating reaches 100% heating capacity
another reheat is added and the first heating is reset to 0%. This way up to three
individual heatings act as one proportional heating. (see below)

H1e Heating
On/Off-control

Added heat capacities
setpoint
on
ON 3rd reheat
off

on
OFF 2nd reheat
off
setpoint T/°C
100%
➊ 1st reheat
0%

300%
Proportional
Heating 200%
total
100% 100%
setpoint
0%

0%
➌ ➌ ➌ ➊ T/°C
➌ ➊ T/°C

C7000
The corresponding commands:
➊ eheat 1 start 0,2 ➊ gasheat 1 start 1,3 ➊ pwwheat 1 start 1,3
➋ eheat 1 hys 0,7 ➋ gasheat 1 hys 0,6 ➋ pwwheat 1 hys 0,6
➌ eheat 1 grad 0,9 ➌ pwwheat 1 grad 0,5
➍ eheat 1 alarmdelay 3

E/0409/57/57
C7000 Advanced Components/Humidity
Humidifier
H2c Operate
Depending on which humidifier type you have, different parameters are decisive.
The start humidity for every humidifier is entered as a negative difference to the
room humidity setpoint. ➊
The hysteresis for the humidifier stop is only valid for humidifiers with on/off-cont-
rol.➋
For proportional humidifiers you can adjust a gradient, which determines the humidity
range in which the humidifying capacity increases from 0 to 100%.➌

The humidifier alarm delay ➍, the delay for the conductivity alarm at 5µS ➎ and at
20µS ➏ can be adjusted in seconds.

On/Off-control (type 1) These alarms are available with the application of a conductivity measuring instru-
Humidifier ment, which is required to control the water conductivity for Ultrasonic humidifiers.

ON

OFF
setpoint %r.h.

Proportional (type 2)
Humidifier
100%
setpoint

0%
➌ ➊ %r.h.

C7000
The corresponding commands:
➊ humi 1 start 7,3
➋ humi 1 hys 9,0
➌ humi 1 grad 10,0
➍ humi 1 alarmdelay 6
➎ humi 1 alarmdelay5 6
➏ humi 1 alarmdelay20 6

E/0409/57/58
C7000 Advanced Components/Humidity
Dehumidification (Part 1)
H2d Operate
The start humidity for dehumidification is entered as a positive difference to the
room humidity setpoint. ➊
In order to block the dehumidifying function in principle, the start humidity has to
be set on 100%.
The hysteresis for the dehumidification stop is entered in the 2nd line.➋

Adjusting the water temperature limits for the dehumidification refers to the possibility
of dehumidifying the air by the free cooling coil with fan speed reduction. ➌➍
If the water temperature limits are exceeded, the controller commutes to dehumidi-
On/Off-control fication by compressor operation.
Dehumidific. See detailed description next page.

ON Note:
The dehumidification fan speed is adjusted in the Air/Fan-menu.

OFF
setpoint %r.h.

Dehumidification range
min max GE-off

5 10 14 20 24 °C
water temp.

C7000
The corresponding commands:
➊ dehumi start 7,0
➋ dehumi hys 7,0
➌ dehumi min 4
➍ dehumi max 10

E/0409/57/59
Dehumidification (Part 2)
There four ways of realizing a dehumidification:
1. by reducing the fan speed and CW valve operation, this is units in mixed operation. Only if the compressor is actually in
the only way of dehumidification for CW-units. operation and if a dehumidification valve is present, the 2nd
2. by shutting down a part of the evaporator via a solenoid way of dehumidification is chosen. The two dehumidifying ways
valve. (not for CyberAir 2 units) are never applicated simultaneously.
3. by the electric expansion valve (only in CyberAir 2 units) If no dehumidification valve is present as in units of the series
CyberAir 2, dehumidification is carried out by the electric ex-
4. by reducing the fan speed and compressor operation.
pansion valve. If this is insufficient, the fan speed is reduced
The choice of the dehumidification type is made by the cont- additionally after a time delay.
roller according to the following conditions: The priority lies on
The decision procedures of the controller are displayed in detail
reducing the fan speed. This is the case for ACW/GCW/GE-
in the scheme below.

GE/CW- *Water temperature limits:


valve or GE pump no
configured ? Tw < TRTset and
Tw < TGEoff and
Twmin < Tw < Twmax
yes
Legend:
Tw - Water temperature
Water TRTset - Room temperature set point
no temperature sensor
configured ?
TGEoff - upper water temperature limit for GE-operation
Twmin - lower water temperature limit for dehumidification
Twmax - upper water temperature limit for dehumidification
yes

Water
yes temperature within no
the limits ?*

no
Cooling priority = 0 Cooling priority = 0
(GE) or 1 (CW) ? (GE) or 2 (DX) ?

yes yes

- Opens the CW valve to 100%


- Reduces the fan speed Dehu- Electrical
no no
midification valve expansion valve
configured ? configured ?

- no dehumidification yes yes

- Compressor start - Compressor start - Compressor


- Closes the dehumidifi- - Sends the new super- start
cation valve heat setpoint to the - Reduces the
EEV fan speed
- Reduces the fan speed
after the lapse of "Time
until dehumidifiction
reduction"

E/0409/57/60
C7000 Advanced Components/Air
Fan
H3c Operate
Reduction according to the temperature
The start temperature is entered as a negative difference to the air temperature
setpoint. ➊
The start fan speed is entered as a percentage of reduction from the maximum
speed. ➋
This reduced fan speed is gradually obtained with a decreasing temperature from
the room temperature setpoint to the adjusted temperature difference ➊ below
the setpoint. However, when heating or humidification is requested, the airflow is
increased to its original value.
Fan speed
setpoint The airflow alarm delay ➌ can be adjusted the same as the filter alarm delay ➍.

➋ nmaxDX or
nmaxCW
+ offset
➊ T/°C
heating
start

humidity
Humidif. setpoint
ON

OFF
%r.h.
humidif.
start
Heating
ON

OFF
T/°C
heating temp.
start setpoint Air
Louver
H3d
The pre-start serves to open the louver before the fan operation starts. This way a
fan operation against a closed louver is avoided. ➎

C7000
The corresponding commands:
➊ fan 1 start 3 ➎ louver 1 pretime 100
➋ fan 1 speed 15
➌ fan 1 alarmdelay 6
➍ fan 1 filteralarmdelay 6

E/0409/57/61
C7000 Advanced

I1b Operate Components/Sensor I1c


After the selection of the sensor you can en-
ter the alarm delay for the limit alarm ➊ and
for the sensor failure alarm ➋ in seconds.
With the offset you can calibrate the sensor
with the help of a reference measuring in-
strument. ➌
Compare the PHYSICAL VALUE with the va-
lue of the reference measuring instrument.

I2c I3c
Aux. Ports
Aux. Alarm
After the selection of the external alarm you
can enter the alarm delay ➍ in the following
window.

I2d Unit alarms


Concerning the unit alarms, you can adjust
the alarm delay for the fire alarm ➎, water
alarm ➏, water flow alarm ➐, phase failure
➑ and bus alarm ➒.

C7000
The corresponding commands:
➊ sensor 1 alarmdelay 7 ➎ fire
➋ sensor 1 alarmdelaybr 8 ➏ water
If, instead of a temperature, the ➌ sensor 1 trim 22,3 ➐ flow alarmdelay 7
expression "reset" is entered, the ➑ phase
sensor calibration is deleted. ➍ alarm 1 alarmdelay 5 ➒ bus

E/0409/57/62
C7000 Advanced
Zone
J1a Operate
The operating status of all units which are assigned to zone 1 is displayed in the top
line. From left to right the operating states of the units with the bus address from 19
to 0 are displayed. 0 stands for normal operation, 1 stands for standby operation.
In the line below you can define the operating status of the unit.
0 means normal operation, 1 means standby operation. ➊

System
J2b AT-Preferences

The acoustic signal which resounds in the case of an alarm and the beep for pressing
a key can be switched off (0=off, 1= on).
The pitch of the buzzertone can be adjusted as desired.
Further on you can adjust the temperature display in °C or °F ➋.
The operator language ➌ can also be selected.

J3a
Password

At this menu item you can adjust the password for the operate level.
This password is "0000" as default setting.

C7000
The corresponding commands:
➊ zone 1 unit 1 1

➋ unit c / unit f
➌ language e / language g c for °Celsius, f for °Fahrenheit
e for English, g for German

E/0409/57/63
K
6.3 Config Level
6.3.1 C7000 Advanced
Menu structure

a
1 2 3
b
c
d
e
f
E/0409/57/64
L a
1 2 3
b
c
d
e
f
E/0409/57/65
M a
1 2 3
b
c
d
e
f
E/0409/57/66
N a
1 2 3
b
c
d
e
f
E/0409/57/67
O a
1 2 3
b
c
d
e
f
E/0409/57/68
P a
1 2 3
b
c
d
e
f
E/0409/57/69
Q a
+

1 2 3
b
+

c
+

d
+

e
f
E/0409/57/70
R a
1 2 3
b
c
d
e
f
E/0409/57/71
S a
1 2 3
b
c
d
e
f
E/0409/57/72
C7000 Advanced Values
Air
K1b Config
Here you can choose the control type. The display of the actual values changes
corresponding to the above adjusted type of control (Room / Sup.Air). ➊
The room air control is the standard control. The temperature/humidity sensor is
placed in the return air intake or in the room and the C7000 controls in accordance
with the setpoints set in the menu F1c/F1d.
An external T/H sensor is required for supply air control. The control takes place for
the room air control in accordance with setpoints set in the menu F1c/F1d.

K1b

Return air
T/H sensor for
return air

T/H sensor for The sensor should be positioned


room air depending on the space available,
thermal load distribution and selected
type of control.
Height > 1.5 m

The maximum distance to the C7000


IOC is 20m.

Supply air
T/H sensor for supply air

C7000
The corresponding commands: The surrounded numbers refer to the corre-
Four different control types can be sponding passages in the descriptive text.
➊ control 2 chosen by entering the corresponding
➋ lim temp 16,3 number: See next page for explanation of the com-
➌ grad temp 0,6 1: room air mands ➋ - ➎.
lim humi 75,0 2: supply air

3: room air with supply air limitation
➎ grad humi 0,6
4: supply air with room air limitation

E/0409/57/73
C7000 Advanced Values
Air
K1b Config K1d
With the room control with supply air
limitation the control takes place via the
T/H sensor in the return air intake and
via a second T/H sensor in the supply
air. Primarily the control takes place as
for room air control, only if the measured
supply air temperature exceeds the start
temperature ➋ the temperature setpoint is
shifted. The extent of the setpoint increase
is determined by a factor which you enter,
as a gradient ➌, in the menu.
The relationship, according to which this
happens, is made clear by the graph
opposite. A steep gradient drastically
corrects the failure to meet the supply
Setpoint air temperature, but has the risk that the Setpoint
Room air sensor control circuit starts to oscillate. Room air sensor
With humidity control the setpoint shift
T/°C takes place in the opposite direction. If the r.h/%
Temperature adjusted starting humidity ➍ is exceeded Humidity
by the measured supply air humidity, the
20,5 setpoint is reduced. You can also enter a 50
20 gradient factor ➎ for this. The relationship 49
is shown in the graph opposite.
14 15 16 17 T/°C 68 70 72 74 r.h/%
➋ Actual value
New setpoint = old setpoint + gradient • ➍ Actual value
Supply air sensor Supply air sensor
(start value - actual value)
Example (temperature): Example (humidity):
20,5 = 20 + 0,5 • (16 - 15) 49 = 50 + 0,5 • (70 - 72)

K1b K1e
The supply air control with room air limita-
tion is based on the same control principle
as the supply-air limited room air control.
Only here the setpoint shift works in the
opposite direction, because it works on
the basis that the supply air is colder than
the return air.
If the room temperature exceeds the start
temperature entered ➋, the supply air
Setpoint Setpoint
Supply air sensor
temperature setpoint is reduced. Supply air sensor
If the room humidity drops below the
T/°C starting humidity entered ➍, the supply r.h/%
Temperature air humidity setpoint is increased. Humidity

18 50,5
17,5 50

21 22 23 24 T/°C 38 39 40 41 r.h/%
➋ Actual value ➍ Actual value
Room air sensor Room air sensor

Example: Example:
17,5 = 18 + 0,5 • (22 - 23) 50,5 = 50 + 0,5 • (40 - 39)

E/0409/57/74
C7000 Advanced Values
Air/Temperature
K1d Config
The controller offers the possibility to have start a stand-by unit when an adjustable
positive temperature difference to the air temperature setpoint is achieved. This dif-
ference can be adjusted by the parameter "Overloadstart" ➌ . The adjustment 0.0K
disables this function.
When the temperature difference is obtained the A/C unit, so far as it is defined as
standby unit, will be started. The sequencing function is not influenced by this. In
order to use this function, a zone must be defined.

You can determine an integral factor ➍ for the air temperature control to avoid a control
actual value discrepancy which is characteristic for P-controllers. In this case a variable setpoint
Svar, which is recalculated every 5 minutes is decisive for the control. This variable
setpoint is calculated by adding the setpoint alteration dS to the previous setpoint.
Sfix The values for the integral factor can be varied between 0 and 10%. A low value should
dS
be used to start with in order to prevent the control system from oscillating. 2% are
recommended and can stepwise be increased to find out the limit of safe control.
Svar
Concerning the limit alarms "Room temperature too low ➎/too high ➏" and Supply
air temperature too low ➐/too high ➑" you can adjust:
a. whether the corresponding alarm shall release a common alarm (1=yes).
time b. the alarm priority, where the corresponding alarm is assigned to an alarm relay
5 min. with this number (adjusted as alarm priority).

Svar n+1 = Svar n + dS with

dS = (Sfix - actual value ) x integral factor

sfix represents the fixed setpoint which is


adjusted in the menu F1c.

Air/Humidity
K1e The controller offers the possibility to have start a stand-by unit when an adjustable
negative humidity difference to the air humidity setpoint is achieved. This difference
can be adjusted by the parameter "Overloadstart" ➌ . The adjustment 0.0% disables
this function.
When the humidity difference is obtained the A/C unit, so far as it is defined as standby
unit, will be started. The sequencing function is not influenced by this.

Concerning the limit alarms "Room humidity too low ➍/too high ➎" and Supply air
humidity too low ➏/too high ➐" you can adjust:
a. whether the corresponding alarm shall release a common alarm (1=yes).
b. the alarm priority, where the corresponding alarm is assigned to an alarm relay
with this number (adjusted as alarm priority).

C7000
The corresponding commands:
Values/Air/Temperature Values/Air/Humidity
➌ load temp 2,5 ➌ load humi 10,5
➍ integral 10 ➍ minhumi room
➎ mintemp room ➎ maxhumi room a commonalarm 1
➏ maxtemp room a commonalarm 1 ➏ minhumi supply b alarmprio 8
➐ mintemp supply b alarmprio 8 ➐ maxhumi supply
➑ maxtemp supply
All combinations are possible.

E/0409/57/75
C7000 Advanced Values
Water
K1/2c Config
For the limit value alarms "Water temperature too low ➊/too high ➋" you can ad-
just:
a. whether the corresponding alarm shall trigger a common alarm (1 = yes).
b. the alarm priority, where the corresponding alarm is assigned to an alarm relay
with this number (adjusted as alarm priority).

Values
Miscellaneous Data
K2b For the function and setting of the cooling priority, see following page.
In the second line you can adjust a unit start delay ➋. By different start delays for
different units it is avoided that the most current consuming components start simul-
taneously and overcharge the power supply of the building.
With the parameter in the third line you can effect a change-over of the two chilled
water valves in CW2 units. The parameter in the fourth line displays the state of
change-over. For details, see chapter 7 "Special functions, CW2 units".
The parameter "OTE" ➎ in the fifth line is customer specific, for standard units the
setting must be "STULZ". For enabling the OTE software this parameter is set to
"OTE".
With the parameter ➏ in the sixth line you can determine whether the unit may be
started by a remote on/off signal. (0 = no, 1 = yes, all other stop causes (Timer, BMS,
local stop, sequencing) are deleted. The remote on/off signal has the priority).
With the parameter ➐ in the last line you can determine whether the unit restarts
automatically in case of power supply return after a phase failure. (0 = no, with this
setting the unit must be restarted locally, 1 = yes).

K2/3b Values
GE-mode

The outside temperature ➊ for the commutation from summer to winter operation is
decisive for the drycooler and compressor control. With this hysteresis ➋ the winter
operation changes to summer operation.
The winter operation is also switched over to summer operation, if an outside temp.
sensor breakdown is detected. An alarm "Outside temperature sensor defect" is
not displayed.
➋ If no outside temperature sensor is configured, summer operation is active.

Summer

Winter
T/°C


C7000
The corresponding commands:
Water Misc. data GE-Mode
➊ mintemp water a sammelalarm 1 ➊ coolingprio 1 ➊ sumwin start 16.0
➋ maxtemp water b alarmprio 8 ➋ startdelay 5 ➋ sumwin hys 2
➌ no correspondance ➌ presstemp 17.0
➍ --- ➍ pressgrad 5.4
➎ option 1 1
➏ remote start 1
➐ phase start 1

E/0409/57/76
C7000 Advanced Values
Misc. data
K2b Config
Cooling priority
The cooling priority determines the overriding cooling circuit for units with
two different cooling systems (Dual-Fluid units). The parameters GE, CW
and DX can be adjusted.
GE - no priority, this is the adjustment for GE-systems, where a mixed
operation of both systems is possible.
CW - means, that chilled water cooling is prior at ACW/GCW-units.
DX - means, that compressor cooling is prior at ACW/GCW-units.
The diagram below displays the conditions for a malfunction change-over
at Dual-Fluid units.

For a better understanding:


The OR-conditions are horizontally located.
The AND-conditions are vertically located.

Malfunction change-over Malfunction change-over


DX –> CW (cooling priority 2) CW –> DX (cooling priority 1)

Compressor "WT too high"


OR LP-alarm 1 OR CW-off = 1
failure 1* alarm

WT - water temperature 1
AND
CW-off - digital input (pre-set DIN16) to
Compressor enable DX-operation or to disable
OR LP-alarm 2
failure 2* CW-operation(see page 95)

AND
CW-off = 0
*HP-alarm or com-
pressor failure

Switching back to the original priority can only be done by an alarm reset.

C7000
The corresponding commands:

coolingprio 1 0: GE
1: CW
2: DX

E/0409/57/77
C7000 Advanced Values
Week program
K3b Config
The week timer is based upon two different temperature setpoints which you have
already adjusted in the menu F1c. Setpoint 1 is represented by a "1", setpoint 2 by
a "2".

The setting is user-friendly. Each digit represents an hour of the day. The weekdays
are displayed in lines. With the selector key you can jump between the hours of the
day. At the end of a line the cursor jumps to the beginning of the next line.

With the OK key you modify the value of the digit where the cursor is placed. Three
values are possible: 0, 1 and 2. By pressing the OK key these values appear in rising
order and will then begin at "0" again.

By pressing the key combination selector key + OK key the value, on which the
cursor is placed, will be copied to the next digit (corresponding to the selected direction
of the selector key). This way you can easily adjust several hours or days.

For each hour of each day of the week you choose among three settings:

Display in the main menu when Display:


the timer program is executed: 1. A/C unit off 0

2. A/C unit on with setpoint 1 1

3. A/C unit on with setpoint 2 2

C7000
The corresponding commands:
wprg mo 12 0 sets the timer stop mode for
monday from 12:00 to 12:59

Day: Hour: Status:


mo = monday 0 = from 0:00 to 0:59 0 = A/C unit off (timer stop)
tu = tuesday 1 = from 1:00 to 1:59 1 = A/C unit on with setpoint 1
we = wednesday 2 = etc. 2 = A/C unit on with setpoint 2
th = thursday
fr = friday
sa = saturday
su = sunday

E/0409/57/78
C7000 Advanced Components/Cooling
Compressor
L1b Config
In the first line you add the compressor to the configuration by entering "1". With "0"
you disable the compressor although all settings concerning the compressor are
kept. ➊
You can determine a digital output for the compressor on/off signal. ➋
In the third line you can:
- assign the digital input for the low pressure alarm ➌
- adjust, whether the low pressure alarm releases a common alarm (0= no, 1 = yes)
➌a
- adjust the alarm priority for the low pressure alarm ➌b
L1c In the fourth line you can:
- assign the digital input for the compressor alarm ➍
- adjust, whether the compressor alarm releases a common alarm (0= no, 1 = yes)
➍a
- adjust the alarm priority for the compressor alarm ➍b

Setting the alarm priorities means assigning the corresponding alarm to an alarm
relay with the adjusted number.

The low pressure alarm can be managed in a way to avoid a premature and unne-
cessary service intervention.
If the LP switch releases, the compressor is stopped and restarted after the com-
pressor pause has elapsed. The LP alarm is inhibited during the winter start delay.
This way the controller tries to bypass temporary LP alarms.
You can limit the number of compressor restarts in "RESTARTS" ➎ within a time
space you can adjust in the left column of the fifth line to avoid an LP alarm. You can
define the time space in the right column of the same line ➎b.
If after the maximum number of restarts, the LP switch still triggers, the LP alarm is
released and the compressor is definitely switched off. Using the optional LP-sensor
in addition you can adjust in the medium column of the same line a threshold ➎a
which marks the lower limit for the permissible pressure range.

With a HP sensor (either part of G-valve or separate option) high pressure alarms
can be equally managed for the same reasons as LP alarms.
You can limit the number of allowed compressor restarts in "RESTARTS" ➏ within a
time space you can adjust in the left column of the sixth line. You can define the time
space in the right column of the same line ➏b.

If the threshold ➏a of the HP within this time space is excessed at least the adjusted
number of times, the HP alarm is released and the measure which you have adjusted
in HP mode ➐ is taken.

0: HP alarm will be triggered


1: Unit continues operation

C7000
The corresponding commands:
➊ comp 1 conf 1 ➎ comp 1 lptries 6
➋ comp 1 dout 3 ➎a comp 1 lppress 4,6
➌ comp 1 alarmlp 7 ➎b comp 1 lptime 2
➌a comp 1 commonalarmlp 1 ➏ comp 1 hptries 3
➌b comp 1 alarmpriolp 1 ➏a comp 1 hppress 21
➍ comp 1 alarm 5 ➏b comp 1 hptime 2
➍a comp 1 commonalarm 1 ➐ comp 1 hpmode 1
➍b comp 1 alarmprio 1

E/0409/57/79
C7000 Advanced
Components/Cooling/Valves
L3b Config Suction valve

In the first line you add the suction valve to the configuration by entering "1". With "0"
you disable the suction valve. ➊
With the parameter "A-OUT" you adjust the analogous output of the proportional
signal for the suction valve. ➋
In the third line you can set the minimum opening degree ➌. This setting serves to
determine the lower limit for the refrigerant mass flow. Below this limit the possibility
exists that an LP alarm will occur.
By setting the minimum opening degree the effective proportional range is redu-
ced.

Example:
With a gradient of 1 K and a minimum opening degree of 20% the effective propor-
tional range reaches 0,8 K.
With a gradient of 1 K and a minimum opening degree of 50% the effective propor-
tional range reaches 0,5 K.

C7000
The corresponding commands:

➊ suctionv 1 conf 1
➋ suctionv 1 aout 3
➌ suctionv 1 min 20

E/0409/57/80
C7000 Advanced
Components/Cooling/Valves
Config
L3c GE/CW-valve

In the first line you add the GE/CW-valve to the configuration by entering "1". With
"0" you disable the GE/CW valve. ➊
With the parameters "A-OUT 1" and "A-OUT 2" you adjust the first and second ana-
logous output of the proportional signal for the GE/CW-valve. ➋a/b Two physical
GE/CW-valves exist in A/C-units of the CW2-type only.
In the third line you can set the digital output ➌ at which the actual state of the
changeover is output.
The digital input, which receives the signal for the commutation from output 1 to output
2, can be assigned in the fourth line. ➍
In the fifth line you can adjust the operating mode ➎ by which the valves of CW2 units
are controlled. (See chapter 7 "Special functions, CW2 units".)

Following menu:
In the first line you can adjust a setpoint ➏ for the opening degree of the GE valve.
This parameter is relevant only for the proportional GE control. For this a separate
manual exists.
Additionally you can prevent mixed operation of Freecooling and compressor cooling
Graphic A "close at comp = 0" by setting the "Close at comp" value ➐ to "1". (see graphic below).
setpoint In the third line you can adjust, whether the valve shall close as soon as the water
comp. temperature exceeds the air temperature setpoint ➑.
In the fourth line you can adjust, whether the valve shall be used for heating ➒. The
lve
va control characteristics will be changed by this setting. When the air temperature falls
GE the valve opens, a rising air temperature will close the valve gradually.
In the fifth line you can adjust, how the valve will be controlled ➓.
➊ ➋ Setting 0: Valve closed at 0V at the output, valve open at 10V at the output.
200%
Setting 1: Valve closed at 10V at the output, valve open at 0V at the output.
100% comp. In the sixth line you can set a time delay which must pass until the control of the
GE valve GE/CW valve begins and the water limit alarms are monitored. Until this time has
elapsed, the valve is fully (100%) opened.

The parameter in the seventh line is only important for CW2 units.
Here you can set an opening degree for the CW valve of the first water circuit. This
Graphic B "close at comp = 1" opening degree is kept by the valve while the cooling is produced by water circuit
setpoint
2. By this, a minimum water flow is guaranteed in circuit 1, which is necessary to
comp. measure the water temperature. With a sufficiently low water temperature the cooling
production can be switched back to circuit 1. Without a cooling request in circuit 1
lve the valve is completely closed.
va
GE

➊ ➋
200%

100%
comp. comp.
GE valve

C7000
The corresponding commands:
1st menu 2nd menu
➊ gecwv conf 1 ➏ gecwv opensp 70 gecwv switchopen 10
➋a gecwv aout1 3 ➐ gecwv compoff 1
➋b gecwv aout2 4 ➑ gecwv spclose 1
➌ gecwv dout 9 ➒ gecwv heating 1
➍ gecwv din 17 ➓ gecwv inv 1
➎ gecwv oper 0 gecwv 100 30

E/0409/57/81
C7000 Advanced
Components/Cooling/Valves
L3d Config G-valve

In the first line you add the G-valve to the configuration by entering "1". With "0" you
disable the G-valve. ➊
With the parameter "A-OUT" you adjust the analogous output of the proportional
signal for the G-valve. ➋

The pre-start serves to provide a sufficient flow for the heat absorbing medium and
to pre-cool the heat absorbing medium. When compressor operation is requested,
the G-valve opens and the compressor start is delayed by the pre-start time. ➌
The pre-open value is the G-valve opening degree which should be obtained during
the pre-start time. ➍
To avoid a constant discrepancy from the set value there are three parameters, which
imitate the behaviour of an integral control.
The control factor ➐ is the decisive value, by which the extent of the control correc-
tion is adjusted in the way of calculating the actuating variable after the lapse of an
adjustable control cycle ➎ according to the following formula:

Snew = Sold - f • (set value - actual value)

S: actuating variable - here valve opening


f: control factor
Set value: condensation pressure setpoint
Actual value: condensation pressure actual value

To avoid a drastical change you can adjust a maximum control correction ➏. This
control correction relates to the old actuating variable in each cycle.

The setpoint for the valve opening is entered in the eighth line. ➑ This setpoint is
relevant for proportional GE control only. The proportional GE control is described
in a separate manual.

In the last line you can enter a value for the minimal opening ➒ of the G-valve. The
minimal opening is only respected when a compressor request exists and can be
used to prevent a HP alarm.

C7000
The corresponding commands:
➊ gvalve conf 1 ➒ gvalve min 20
➋ gvalve aout 4
➌ gvalve pretime 30
➍ gvalve preopen 100
➎ gvalve concyc 5
➏ gvalve maxc 2
➐ gvalve fact 40
➑ gvalve opensp 70

E/0409/57/82
C7000 Advanced Components/Cooling/Valves
HGBP-valve
L3e Config
In the first line you add the HGBP-valve to the configuration by entering "1". With
"0" you disable the valve. ➊
With the parameter "A-OUT" you adjust the analogous output of the proportional
signal for the HGBP-valve. ➋

The opening degree of the HGBP valve is controlled according to the air tempera-
ture. If the actual temperature is below the setpoint, the opening degree rises to the
adjustable maximum opening degree. If the actual temperature is above the setpoint,
the opening degree falls to the adjustable minimum opening degree.
A proportional factor ➍, an integral factor ➎ and a differential factor ➏ can be adjusted
for the precise control. In the third line you can adjust the control cycle ➌.

The pre-runtime serves to softstart the compressor. When compressor operation


is requested, the HGBP valve opens and the compressor start is delayed by the
pre-runtime. ➐
The pre-opening is the valve opening degree to which the valve is opened during
the pre-runtime. ➑
In the last line you can set a minimum and a maximum opening for the HGBP valve.
The minimum opening ➒a limits the cooling capacity. The maximum opening ➒b
avoids a 100% short circuit of the refrigerant flow in case of a fully opened HGBP
valve. The compressor would operate in short circuit and trigger an HP alarm.
In case of a dehumidification request the HGBP valve is instantly closed in order to
keep a 100% refrigerant mass flow available.
The maximum refrigerant mass flow is needed for the effect of passing under the dew
point by partial cut-off of the evaporator (CyberAir 1, Compact DX and Mini-Space)
but also for fan speed reduction and dehumidification by the EEV (CyberAir 2).

C7000
The corresponding commands:
➊ hgbp 1 conf 1 ➒a hgbp 1 min 20
➋ hgbp 1 aout 4 ➒b hgbp 1 max 80
➌ hgbp 1 concyc 3
➍ hgbp 1 pfact 5
➎ hgbp 1 ifact 5
➏ hgbp 1 dfact 5
➐ hgbp 1 pretime 10
➑ hgbp 1 preopen 40

E/0409/57/83
C7000 Advanced Components/Cooling/Valves
Electronical Expansion valve (EEV)
L3f Config
The suction gas pressure and temperature are measured by a pressure sensor
and a temperature sensor and these values are transmitted via an EEIO board to
the controller. With these parameters the superheat is controlled by the expansion
valve.
➊. By the setting 1 the valve is configured and the failure of the pressure sensor,
the temperature sensor and the stepper motor for the valve control are monitored
and displayed by an alarm.
Setting 0 means: the valve is not configured.
➋. Here the valve type is determined. 1=EX4, 2=EX5, 3=EX6, 4=EX7, 5=EX8
➌. Setting of the refrigerant in use:
R22, R134a, R407C, R410A
➍. Setting of the pressure sensor in use:
PT4-07S, PT4-18S, PT4-30S, PT4-50S
➎. Control with suction pressure limit (MOP), 0=disabled, 1=enabled
➏. Temperature limit for MOP control. Above this evaporation temperature the ex-
pansion valve is not opened further.
➐. Superheat control mode: off= quick response,
on= slow response

Valve type Following menu:


The valve type depends on the unit ➊. Battery supply, setting 0 means: the buffer battery, which must be connected on
size. the EEIO board, is not charged by the battery charger.
Unit size Valve type Setting 1 means: the buffer battery is charged by the battery charger. This battery
serves to shut the expansion valve in case of a power failure.
ASD/U ALD/U
➋. Here you can adjust the lapse of time, for which the battery is still connected to
181 - 451, EX5
402 - 862
the battery charger after a power failure.
➌. Start opening degree for the expansion valve
ASD/U ALD/U ➍. Advanced start time for the expansion valve. The compressor start is delayed by
EX6
531, 1062
this time in order that the expansion valve can obtain its start opening degree.

Alarm treatment:
Pressure sensor Three alarms exist: ➎. Pressure sensor alarm, ➏. Temperature sensor alarm, ➐.
Stepper motor alarm
The pressure sensor depends on the
refrigerant used.
➎a, ➏a, ➐a: For all alarms you can adjust, whether the corresponding alarm releases
a common alarm (0= no, 1 = yes) .
Refrigerant Pressure sensor ➎b, ➏b, ➐b: Setting the alarm priorities means assigning the corresponding alarm
R407C to an alarm relay with the adjusted number.
R22 PT4-07S
R134a
R410A PT4-18S Note:
The EEV is not configured neither in the basic setting nor in any loaddefault setting.
If required it must be configured in this menu.

C7000 2nd menu


Valve type: ➊ eev 1 batchrg 1
The corresponding commands: 1: EX4
➋ eev 1 bht 90
2: EX5
1st menu Refrigerant: ➌ eev 1 preopen 60
3: EX6
➊ eev 1 conf 1 0: R22 ➍ eev 1 pretime 15
4: EX7
1: R134a ➎a eev 1 commonalarmpress 0
➋ eev 1 type 5 5: EX8
2: R507
➌ eev 1 refrig 4 ➏a eev 1 commonalarmtemp 1
3: R404A Pressure sensor:
➍ eev 1 sentype 2 4: R407C
➐a eev 1 commonalarmmotor 1
0: PT4-07S
➎ eev 1 mopcon 0 5: R410a 1: PT4-18S ➎b eev 1 alarmpriopress 18
➏ eev 1 moptemp 23,3 6: R124 2: PT4-30S ➏b eev 1 alarmpriotemp 17
➐ eev 1 supmode 1 7: R744 3: PT4-50S ➐b eev 1 alarmpriomotor 19

E/0409/57/84
C7000 Advanced Components/Cooling
Drycooler
L2e Config
In the first line you add the drycooler to the configuration by entering "1". With "0"
you disable the drycooler. ➊
With the parameter "D-OUT" you determine a digital output for the drycooler on/off
signal. ➋
With the parameter "A-OUT" you determine an analogous output for the proportional
drycooler control. ➌
The digital input for the drycooler alarm can be assigned by the "D-IN" parameter.
➍a
You can adjust, whether the drycooler alarm releases a common alarm (0= no,
1 = yes). ➍b
Setting the priority for the drycooler alarm ➍c means assigning the alarm to an
alarm relay with the adjusted number.

The parameters:
- control cycle ➎
- control factor ➏
- max. control correction ➐
- pre-speed ➑
- A-OUT ➌
are only necessary for the proportional GE-control, which is explained in a separate
manual.

Note:
For the dry cooler control, the configuration of an outside temperature sensor and
a water temperature sensor is required.

C7000
The corresponding commands:
➊ drycool 1 conf 1 ➐ drycool 1 maxc 4
➋ drycool 1 dout 10 ➑ drycool 1 prespeed 100
➌ drycool 1 aout 4
➍a drycool 1 alarm 5
➍bdrycool 1 commonalarm 1
➍c drycool 1 alarmprio 3
➎ drycool 1 concyc 10
➏ drycool 1 fact 3

E/0409/57/85
C7000 Advanced Components/Cooling
Pumps
L2f Config
By setting the parameter "ACTIVE" on 1 you add a pump to the configuration. With
"0" you disable the pump. ➊
In the next line you determine which type the pump shall belong to (G = G-pump,
which conveys the medium through the condenser in a GE2-unit, GE = GE-pump,
which conveys the medium through the free cooling coil in a GE2-unit, Glycol =
Glycol-pump - all pumps for G-, GE units which are located outside the A/C unit,
PS=pump station pump). ➋
With the parameter "D-OUT" you determine a digital output for a glycol pump on/off
signal. ➌ In case of a proportionally controlled pump the enabling signal is available
at this output.
With the parameter "A-OUT" you adjust the analogous output of the proportional
signal for a G/GE-pump and a PS-pump. ➍
The digital input for the pump alarm can be assigned by the "D-IN" parameter. ➎
You can adjust, whether the pump alarm releases a common alarm (0= no, 1 = yes).

Setting the priority for the pump alarm ➐ means assigning the corresponding alarm
to an alarm relay with the adjusted number.
For glycol pumps you can enable a sequencing based on time and failure. With
"partner pump" ➑ you select the number of the 2nd pump (0-4). The second pump
must be in the same unit. Setting "0" disables the pump sequencing. The sequencing
Table 1 is based on a runtime evaluation. In case of a runtime difference of more than 20
Pump type (1) (2)/(3) (4) hours the pump with the shorter runtime is put into operation.
Pre-start time ➊ - -
Following menu:
Pre-speed ➋ - - The pump pre-start serves to pre-cool the heat absorbing medium. When compressor
CTRL factor ➌ - ➌* operation is requested, the G-pump starts and the compressor start is delayed by
the pump pre-start time. ➊
I factor - - ➍ The pre-speed is the G-pump speed which should be obtained during the pre-start
D factor - - ➎ time. ➋
Cycle ➏ - ➏ The control factor ➌ is the decisive value, by which the extent of the control correc-
tion is adjusted in the way of calculating the actuating variable after the lapse of an
Max. adjust ➐ - -
adjustable control cycle ➏ according to the following formula:
Min speed - - ➑
Snew = Sold - f • (set value - actual value)
Pump type:
1: G pump for GE2 units of the series S: actuating variable - here pump speed
CyberAir 1 f: control factor
2: GE pump for GE2 units of the series Set value: condensation pressure setpoint
CyberAir 1 Actual value: condensation pressure actual value
3: Glycol pump, external pump for units
of type GE or CW. To avoid a drastical change you can adjust a maximum control correction ➐. This
4: Pump station pump for units of the control correction relates to the old actuating variable in each cycle.
series CyberAir pump station (CPP) For PS pumps an integral factor ➍ and a differential factor ➎ can be adjusted.
* The control factor for PS pumps is just By the parameter in the last line you can set a minimum speed ➑ for PS-pumps.
a proportional factor. The formula stated
in the right text is not applied.

C7000
The corresponding commands: 1st menu 2nd menu
➊ pump 1 conf 1 ➊ pump 1 pretime 5
➋ pump 1 type 2 ➋ pump 1 prespeed 60
➌ pump 1 dout 3 ➌ pump 1 fact 2
➍ pump 1 aout 4 ➍ pump 1 int 3
➎ pump 1 alarm 3 ➎ pump 1 diff 6
➏ pump 1 commonalarm 0 ➏ pump 1 concyc 5
➐ pump 1 alarmprio 3 ➐ pump 1 maxc 5
➑ pump 1 partpump 1 ➑ pump 1 min 20

E/0409/57/86
C7000 Advanced Components/Heating
E-heating
M1c Config By setting the parameter "ACTIVE" on 1 you add a reheat to the configuration. With
"0" you disable the electric reheat. ➊
In the next line you determine the reheat type (2-point: reheat with on/off control,
Linear: reheat with proportional control). ➋
With the parameter "D-OUT" you determine a digital output ➌ for the electric reheat.
The proportional electric reheat is controlled by pulse width modulation and the
reheat receives the control signal by a fixed PWM output. A digital output has not
to be set for the proportional electric reheat.

Alarm treatment:
The digital input for the electric reheat alarm can be assigned by the "D-IN" para-
meter. ➍ You can adjust, if the e-heating alarm releases a common alarm (0= no,
1 = yes). ➎
Setting the priority for the heating alarm ➏ means assigning the corresponding
alarm to an alarm relay with the adjusted number.

M1d Hotgas reheat


By setting the parameter "ACTIVE" on 1 you add a reheat to the configuration. With
"0" you disable the hotgas reheat. ➊
With the parameter "D-OUT" you determine a digital output for the hotgas reheat.

Alarm treatment:
The digital input for the hotgas reheat alarm can be assigned by the "D-IN" para-
meter. ➌ You can adjust, if the hotgas reheat alarm releases a common alarm
(0 = no, 1 = yes). ➍
Setting the priority ➎ means assigning the corresponding alarm to an alarm relay
with the adjusted number.

M1e Hot water reheat


By setting the parameter "ACTIVE" on 1 you add a hot water valve to the configu-
ration. With "0" you disable the valve. ➊
In the next line you determine the valve type (2-point: solenoid valve with on/off
control, Linear: 3-way valve with proportional control). ➋
With the parameter "D-OUT" you determine a digital output for the solenoid valve.

With the parameter "A-OUT" you adjust the analogous output of the proportional
signal for the valve of a hot water reheat. ➍

C7000
The corresponding commands:
E-heating Hotgas reheat Hot water reheat
➊ eheat 1 conf 1 ➊ gasheat 1 conf 1 ➊ pwwheat 1 conf 1
➋ eheat 1 type 1 ➋ gasheat 1 dout 10 ➋ pwwheat 1 type 1
➌ eheat 1 dout 3 ➌ gasheat 1 alarm 7 ➌ pwwheat 1 dout 5
➍ eheat 1 alarm 7 ➍ gasheat 1 commonalarm 1 ➍ pwwheat 1 aout 8
➎ eheat 1 commonalarm 1 ➎ gasheat 1 alarmprio 3
➏ eheat 1 alarmprio 3 Type 1: On/off control
Type 2: Proportional control

E/0409/57/87
C7000 Advanced Components/Humidity
Humidifier
M2c Config
By setting the parameter "ACTIVE" on 1 you add a humidifier to the configuration.
With "0" you disable the humidifier. ➊
In the next line you determine the humidifier type (2-point: humidifier with on/off control,
Linear: humidifier with proportional control). ➋
With the parameter "D-OUT" you determine a digital output for an on/off humidifier.

With the parameter "A-OUT" you adjust the analogous output of the proportional
signal for a humidifier. ➍
In the fifth line you can configure a conductivity meter which is required to monitor
the water conductivity when using Ultrasonic humidifiers. ➎
In the sixth line you can assign the digital input ➏a for the humidifier alarm, adjust
whether the humidifier alarm shall release a common alarm ➏b (0= no, 1 = yes) and
you can set the alarm priority ➏c.
In the seventh line these parameters can be adjusted for the conductivity alarm at
5µS ➐a-c and in the last line for the conductivity alarm at 20µS ➑a-c.
These alarms are available with the application of a conductivity meter.

Dehumidification
M2d
The first three parameters are irrelevant for units of the CyberAir2 series. For these
units the parameter "VALVE" must be set "0".
Other units (CyberAir 1, Compact DX, Mini-Space) can contain a dehumidification
valve and a mechanically controlled HGBP valve incl. solenoid valve.

By setting the parameter "VALVE" on 1 you add a dehumidification valve to the con-
figuration. With "0" you disable the dehumidification valve. ➊
In the second line you can configure a hotgas bypass for the compressor by entering
a "1". ➋
Dehumidif. -Stop When dehumidification with compressor operation is requested, the hotgas bypass
Deh. 1K is closed, because the maximum refrigerant mass flow is needed for the effect of
Temp. passing under the dew point.
setpoint This is also valid for dehumidification by compressor operation with fan speed re-
ON
duction.
With the parameter "D-OUT" you determine a digital output for the dehumidification
OFF (solenoid valve for partial evaporator cut-off). ➌
T/°C To avoid a feedback circle of dehumidification and cooling, where the sinking tempe-
➍ rature arouses an increased relative humidity which entails again a dehumidification
request, you can adjust a stop temperature ➍, which is entered as a negative diffe-
rence to the air temperature setpoint and avoids dehumidification when it is passed
under.
With a fixed hysteresis of 1 Kelvin the dehumidification is switched on again, when
the room temperature rises again above the stop temperature.

C7000
The corresponding commands:
Humidification Dehumidification
➊ humi 1 conf 0 ➏c humi 1 alarmprio 5 ➊ dehumi confvalve 1
➋ humi 1 type 2 ➐a humi 1 alarm5 7 ➋ dehumi confbypass 1
➌ humi 1 dout 11 ➐b humi 1 commonalarm5 1 ➌ dehumi dout 12
➍ humi 1 aout 4 ➐c humi 1 alarmprio5 5 ➍ dehumi stop 2,0
➎ humi 1 confcon 1 ➑a humi 1 alarm20 7
➏a humi 1 alarm 7 ➑b humi 1 commonalarm20 1
➏b humi 1 commonalarm 1 ➑c humi 1 alarmprio20 5

E/0409/57/88
C7000 Advanced Components/Air
Fan
M3c Config
By setting the parameter "ACTIVE" on 1 you add a fan to the configuration. With
"0" you disable the fan. ➊
In the next line you determine the fan type (2-point: fan with on/off control, Linear:
EC-fan with proportional speed control). ➋
With the parameter "D-OUT" ➌ you determine a digital output for an on/off fan.
In case of a proportionally controlled fan the enabling signal is available at this
output.
With the parameter "A-OUT" you adjust the analogous output of the proportional
signal for a speed controlled fan. ➍

The parameters:
- control cycle ➎
- max. control correction ➏
- control factor ➐
are only necessary for the proportional GE control, which is explained in a sepa-
rate manual and for the raised floor pressure control. With these parameters the
characteristics of an integral control can be performed.

The offset is used to adapt the airflow to unexpected conditions on the site ( lower/
higher pressure loss).➑
The minimum speed, which you can adjust here, can only be bypassed by the
adjustment in "REDUCE SPEED".
For DX units ➒a and CW units ➒b (determination by cooling priority) separate
minimum speeds can be adjusted.
The maximum speed should be adjusted according to the required layout airflow.
For DX units and GE units the "max. DX" speed ➓a is valid, for CW units the "max.
CW" speed ➓b is valid. For Dual-Fluid units the speed selection depends on the
cooling priority. In case of a malfunction changeover the corresponding speed is
taken. For a detailed description of the conditions for a malfunction changeover
see page 77.

M3d
The digital input ➊ for the airflow alarm can be assigned by the "D-IN" parame-
ter.
You can adjust, if the airflow failure alarm releases a common alarm (0 = no,
1 = yes). ➋
In the third line you can set the priority for the airflow alarm. ➌

The digital input for the filter alarm can be assigned by the "D-IN FILTER" para-
meter. ➍
You can adjust, whether the filter alarm releases a common alarm. ➎
In the last line you can set the priority for the filter alarm. ➏

C7000 Type 1: On/off control


Type 2: Proportional control
The corresponding commands:
Fan, M3c Fan, M3d
➊ fan 1 conf 1 ➑ fan 1 offset -5 ➊ fan 1 alarm 2
➋ fan 1 type 1 ➒a fan 1 min 60 ➋ fan 1 commonalarm 1
➌ fan 1 dout 11 ➒b fan 1 nmincw 40 ➌ fan 1 alarmprio 3
➍ fan 1 aout 11 ➓a fan 1 nmax 85 ➍ fan 1 filteralarm 6
➎ fan 1 concyc 8 ➓b fan 1 nmaxcw 90 ➎ fan 1 commonalarmfi 1
➏ fan 1 maxc 2 ➏ fan 1 filteralarmprio 4
➐ fan 1 fact 2

E/0409/57/89
C7000 Advanced Components/Air
Fan (Part 2)
M3e Config
With the parameter "START 100%" ➊ you adjust a time which must elapse before
the fan control begins. This way an airflow alarm is avoided which could occur due
to the fan inertia. During this time the fan is operated with 100% speed.
By the "PRERUN" parameter ➋ you adjust the delay for the inhibited start of all
components, except the glycol pump, in relation to the control start with alarm
monitoring. By different pre-runtimes for different units it is avoided that the most
current consuming components start simultaneously and overcharge the power
supply of the building.
Fan start phase The fan over-run time ➌, which you can adjust, serves to reject hot or cold air in
100%
the A/C unit and avoids an accumulation of heat at the reheat or of cold at the
nmax evaporator.
If during a time which you adjust with "REDUCE TIME" ➍a no action (cooling, he-
ating, humidification, dehumidification) has been taken, the fan speed is reduced
by the percentage which you adjust with "REDUCE SPEED" ➍b.
➊ ➋ t/sec
The "FILTER OFFSET" ➎ is entered as a positive difference to the maximum speed.
fan control compon. If a filter alarm is released, the maximum speed will be increased by the filter offset
start start start* in order to overcome the higher resistance of a clogged filter.
*start of all other control-relevant components
except the glycol pump, which can be started If during the time until the dehumidification reduction comes into effect ➏a a
earlier.
dehumidification request exists, the dehumidification is carried out by fan speed
reduction. This time delay allows to control the humidity by a dehumidification by
Fan stop phase the expansion valve in the meantime. For units without electrical expansion valve
this parameter should be set to "0".
The "DEHUM.SPEED" ➏b is entered as a negative difference in % to the maximum
speed. This is the fan speed for the first way of dehumidification.
The "UPS SPEED" ➐ is also entered as a negative difference in % to the maximum
speed. Receiving a UPS-signal the controller will apply this reduced speed for an
➌ over-run due t/sec emergency operation.
to fan inertia
unit stop fan stop
If the A/C unit is operated during nominal operation with a low airflow, the fan speed
can be raised, when the temperature setpoint is exceeded. The fan speed increase
depends on the temperature difference to the setpoint.
Speed levels For this you adjust a positive temperature difference ➑a to the setpoint, which
% represents the start point of the speed increase.
100 Then you adjust a maximum speed ➑a for the overload operation and another
Filter offset ➎
temperature difference ➒ to the setpoint,
90
Offset * which marks the end of the proportional
nMax Fan speed
fan speed increase. Having attained the
Reduced speed ➍b 80 second temperature difference, the fan Setpoint
is operated with the maximum speed
70 for the overload operation.This speed is
Dehumidif. speed ➏b
65 kept even if the temperature continues ➑b
UPS speed ➐ to rise. DXmax/
55 CWmax
*this item refers to the previous page.
➑a T/°C

C7000
The corresponding commands:
➊ fan 1 100 5 ❼ fan 1 ups 35
➋ fan 1 pre 15 ➑a fan 1 emerstart 0,7
➌ fan 1 after 20 ➑b fan 1 emernmax 95
➍a fan 1 redtime 30 ❾ fan 1 emerend 2,0
➍b fan 1 redspeed 20
➎ fan 1 filteroffset 15
➏a fan 1 dehumtime 26
➏b fan 1 dehum 25

E/0409/57/90
Components/Air/Fan (Part 3) - Calculating the fan speed
Cooling priority
1 (CW) 2 (DX) 0 (GE) The following processes of decision are passed
through by the controller for the fan speed calcula-
tion.
The fan speed nmaxDX or nmaxCW is chosen ac-
Are the conditions for Are the conditions for cording to the cooling priority and the conditions for
a malfunction change- a malfunction change- a malfunction change-over. (details for the cooling
over met for Dual- over met for Dual- priority, see page 77 )
Fluid-units ? Fluid-units ? Then 4 queries are passed, which entail a speed
Y reduction or increase. Finally the algorithm checks
N N whether the minimum speed is kept and whether
the conditions for the REDUCE SPEED are kept,
which can bypass the minimum speed as the sole
CW standby manage- nmax DX reduction.
ment enabled? Parameter
N Y setting:
nmaxDX: 100% Example 1: Example 2:
nmax CW nmax zone nmaxCW: 90% n = nmaxDX n = nmaxCW
supposing: condition not ok supposing: condition not ok
Is Tair > Tset + EMERSTART ? n = nmaxDX = 100% n = nmaxCW = 90%
(overload service)

supposing: condition ok supposing: condition ok


Are the conditions for
10% n = 100% - 10% n = 90% - 10%
STARTSPEED met?
n = 90% n = 80%

supposing: condition ok supp.: condition not ok


Does a dehumidification request n = 90% - 20% n = 80%
exist with the speed reduction 20% n = 70%
DEHUMSPEED?

supposing: condition ok supp.: condition not ok


Does the unit run in UPS ope- n = 70% - 30% n = 80%
ration with the speed reduction 30% n = 40%
USV-SPEED?

supposing: condition ok supposing: condition ok


Has a filter alarm occurred and n = 40% + 10% n = 80% + 10%
must the speed be increased by 10% n = 50% n = 90%
the filter offset ?

condition not ok condition ok


Is the minimum speed kept ? because n < 60% so n = 90%
60% so n = 60%

condition not ok supposing: condition ok


Can a speed reduction REDUCE- because of dehumidific. n = 90% - 50%
SPEED be made due to the non- 50% n = 60% n = 40%
request of climatic functions within
the REDUCE TIME ?
Legend: yes
next step
no

E/0409/57/91
C7000 Advanced
Components/Air
M3f Config Louver

By setting the parameter "ACTIVE" on 1 you add a louver to the configuration. With
"0" you disable the louver. ➊
With the parameter "D-OUT" you determine a digital output for the louver. ➋

Components/Cooling
ECO Louver
L2b
By setting the parameter "ACTIVE" on 1 you add an ECO louver to the configuration.
With "0" you disable the ECO-louver. ➊
With the parameter "A-OUT" you determine a analogous output for the louver. ➋

C7000
The corresponding commands:
➊ louver 1 conf 1
➋ louver 1 dout 11

➌ ecolv 1 conf 1
➍ ecolv 1 dout 11

E/0409/57/92
C7000 Advanced Components
Sensor
N1c Config
By setting the parameter "ACTIVE" on 1 you add a sensor to the configuration.
With "0" you disable the sensor. ➊
In the next line you determine the sensor type (current, voltage). ➋
With the parameter "PURPOSE" you specify for what the sensor is used ➌.
See left listing.
With the parameter "A-IN" you adjust the analogous input for the proportional
sensor signal. ➍
The following 5 items serve to calibrate the sensor. The minimum measure value
PURPOSE: (phys. value) ➏a is assigned to the minimum output (value). ➎a
1 - Room temperature The maximum measure value (phys. value) ➏b is assigned to the maximum output
2 - Room humidity (value). ➎b
3 - Supply temperature The unit of the adjusted measure value depends on the sensor purpose (1-23). The
4 - Supply humidity unit of the adjusted output depends on the sensor type (current, voltage).
5 - Water temperature, inlet 1 If there is more than one sensor with the same purpose, an average value is cal-
6 - Outside temperature culated. In the seventh line you can adjust a maximum difference to the average
7 - Outside humidity value.➐ If the maximum difference is exceeded, the alarm "Sensor ## excess" is
8 - Condensation temperature 1 released. For the evaluation of the sensor excess alarm at least three sensors with
9 - Condensation pressure 1 the same purpose are needed.
10 - Evaporation temperature 1
11 - Evaporation pressure 1 You can adjust in the eighth line, whether the sensor excess alarm shall release a
12 - Water temperature, inlet 2 common alarm ➑a. And you can assign the alarms to an alarm relay ➑b here.
13 - Condensation temperature 2 You can adjust in the ninth line, whether the sensor failure alarm shall release a
14 - Condensation pressure 2 common alarm ➒a. And you can assign the alarm to an alarm relay ➒b.
15 - Evaporation temperature 2
16 - Evaporation pressure 2
17 - Setpoint temperature
18 - Setpoint humidity NOTE:
19 - Water temperature, outlet 1 You need two water temperature sensors for:
20 - Water temperature, outlet 2 1. GCW-units with dry coolers
21 - Water pressure Water temperature 1 is always the temperature for the CW-circuit.
22 - Raised floor pressure Water temperature 2 is the cooling water temperature, by which the dry coolers
23 - Universal temperature 1 are controlled.
2. CW2-units
Sensors of the purpose
Water temperature 1 is always the temperature for the CW-valve which is active,
- Condensation temp.,
when no change-over has taken place (no voltage at DIN 3).
- Evaporation temp.
Water temperature 2 is the temperature for the second CW-valve, which is active
- Evaporation pressure
after a change-over.
are not used up to now.

For these sensors and for the sen-


sor condensation pressure no ave-
rage value is calculated, if several
sensors with the same purpose are
configured.

C7000
The corresponding commands:
➊ sensor 1 conf 1 ➐ sensor 1 div 20 Sensor type:
➋ sensor 1 type 3 ➑a sensor 1 commonalarm 1 1: Current
2: Voltage
➌ sensor 1 use 5 ➑b sensor 1 alarmprio 2
➍ sensor 1 ain 3 ➒a sensor 1 commonalarmbr 1
➎a sensor 1 minout 0,0 ➒b sensor 1 alarmpriobr 3
➎b sensor 1 maxout 9,0
➏a sensor 1 minmeas -20,0
➏b sensor 1 maxmeas 40,0

E/0409/57/93
C7000 Advanced Components
Aux. Ports/Aux. Alarm
N3c Config
In the first line you can type in the alarm text which you want to be displayed in case
of the alarm. ➊
By setting the parameter "ACTIVE" on 1 you add an external alarm to the configu-
ration. With "0" you disable the ext. alarm. ➋
With the parameter "D-IN" you adjust the digital input for the alarm signal. ➌
You can adjust, whether the external alarm releases a common alarm (0 = no,
1 = yes). ➍
Setting the priority for the external alarm ➎ means assigning the alarm to an alarm
relay with the adjusted number.
The external alarm delay can be adjusted. ➏

Aux. Ports/Unit alarms


N2d
In this window you can assign digital inputs to unit alarms (➊-➍)a, determine,
whether the corresponding alarm releases a common alarm (➊-➏)b and assign
the alarm to a relay (➊-➏)c.
1. Fire ➊, by an external smoke and temperature sensor
2. Water ➋ by an external water detector
3. Water flow failure ➌ by a flow sensor
4. Phase failure ➍ by a phase control module
5. Busalarm ➎,
6. Address conflict ➏, these alarms are detected by the controller and need
neither sensor nor digital input.

C7000
The corresponding commands:
➊ exalarmin 1 text xxx123 ➊ fire
a din 15
➋ exalarmin 1 conf 1 ➋ water
b commonalarm 1
➌ exalarmin 1 alarm 11 ➌ flow
c alarmprio 8
➍ exalarmin 1 commonalarm 0 ➍ phase
➎ exalarmin 1 alarmprio 9 ➎ busalarm b commonalarm 1
➏ exalarmin 1 alarmdelay 6 ➏ adrconflict c alarmprio 8

E/0409/57/94
C7000 Advanced Components
Aux. Ports/Aux. Ports
N2e Config
This windows serves to adjust digital in- and outputs for non-component-related
alarms or messages.
In detail you can adjust the digital output for the common alarm ➊ and for the win-
termode ➋. The wintermode signal can be forwarded to a BMS system. The state of
the free cooling mode ➌ (free cooling exists also in mixmode and when the Ecocool
louver is opened) and of the local stop ➍ (Control switched off by start/stop key)
can be output on a digital output.
Following you can adjust the digital inputs for the remote contact ➎, for the ups
operation ➏ and for the external cooling priority ➐.

Aux. Ports/Value output


N2f, N3f
In this window you can output analogous values on analogous outputs so that they
can be used by a BMS.
First choose a number for the value output. This number only serves to indicate
the value.
Then a window will appear, in which you can adjust parameters for the value output.
In the first line you can activate the value output. You can do the settings in line 2 to
5 in advance and save them, without having the value output be come into effect.
Only if you set the parameter in the first line to "1", the value output begins. When
several sensors with the same purpose exist, the average value is calculated.
In line 2 you determine the sensor the value of which will be output. The sensor is
selected by the purpose ➊ (as listed on page 93). If you select a purpose for which
no sensor exists, the output value is 0V. In the third line you set the analogous
output ➋.
The parameters in line 4 and 5 serve to calibrate the output. If you have selected a
sensor with the purpose "supply air temperature" and set the value 5.0 for the "min"
parameter ➌ in line 4, you define the lower limit by this. At 5,0°C a voltage of 0V will
be output. At 4,0°C also 0V will be output. By the "max" parameter ➍ in line 5 you
define the upper limit, at which 10V will be output.

UPS

N3b This windows serves to determine the air conditioning functions in case of operation
with Uninterrupted Power Supply.
If the controller receives the signal at its digital input for UPS operation, all the
functions which are enabled by "1" will be admitted, whereas the functions with a
"0" will be disabled.
Please note that also the fan speed may be reduced to a pre-adjusted value in case
of UPS-operation. See page 90.

C7000
The corresponding commands:
Aux. Alarms Value output UPS
➊ calarm dout 7 ➊ valout 1 use 2 ➊ ups cool 1
➋ winter dout 17 ➋ valout 1 aout 6 ➋ ups heat 0
➌ fcm dout 4 ➌ valout 1 min 5,0 ➌ ups humi 0
➍ localstop dout 8 ➍ valout 1 max 35,3 ➍ ups dehumi 0
➎ remote din 11
➏ ups din 13
➐ cwoff din 16

E/0409/57/95
C7000 Advanced Manual Operation

O2d Config
When manual operation is used the C7000 control is put out of force.
The manual operation menu consists of two columns of parameters which are
decisive for the operation.
In the first column (titled EN.) you enable the manual operation of the listed compo-
nent by setting the parameter to "1". ➊
The second column (titled STATE) displays the actual state of the component.
After you have enabled the man. op. in the first column, you can switch on/off the
component itself. ➋
For proportionally controlled components you can enter a percentage in the second
O3d column (titled VALUE) which corresponds to an opening degree for a valve or a
capacity for any other component.
Components which exist either with on/off control or with proportional control have
both columns (STATE and VALUE). But only the corresponding parameter comes
into effect.

Sensors and external alarms can be simulated by the manual operation for the
purpose of testing the controller function.

When the manual operation menu is left (e.g. when the menu "components" is rea-
ched again), the manual operation of each component is disabled and the controller
takes over the control again.

When the fan is switched off, any other component is electrically


blocked and can not be started.
If the unit is de-energized, all manual settings are reset.
However, the adjusted proportional values are kept.

C7000
The corresponding commands:

➊ eheat 1 hand 1
➋ eheat 1 handon 1 Instead of 0/1 for "off/on" you can enter
a percentage from 0 to 100 if the compo-
sensor 1 handon 25 nent is proportionally controlled.
sensor 1 hand 1

E/0409/57/96
C7000 Advanced Zone

Q1a Config You can find a detailed description of the zone control in chapter 7. Special Functions.
Here you can see an overview over the adjustable parameters. Zone parameters
must only be set at one unit of the zone. Unit parameters must be set individually
at each unit.

➊. Unit assignment (unit parameter)


A zone is defined by the assignment of units to this zone. Maximum 20 zones
can be defined with the adjustments from 1 to 20. Zone 0 means that the unit is
assigned to no zone. The assignment is made individually for each unit.

➋. Cycle time (zone parameter)


The cycletime determines the lapse of time after which a changeover will perio-
dically take place. With the setting "0" the sequencing is disabled.

➌. Number of defective units (zone parameter)


The entry is optional. If the number, adjusted here, is reached, the emergency
operation will be put into force. With the setting "0" the emergency operation is
disabled.

➍. Emergency temperature (zone parameter)


This temperature is the new sepoint when emergency operation is enabled.

➎. CW standby management (zone parameter)


With the setting "1" the CW standby management is enabled.

➏. Sequencing Test (zone parameter)


With the setting "1" the sequencing test with the fixed cycletime of 5 minutes is
enabled.

➐. Average value determination (zone parameter)


With the setting "1" the calculation of average values is enabled.

➑. Average value determination including standby units (zone parameter)


With the setting "1" also sensors from units, which are in standby mode, are taken
into account for the calculation of average values.

➒. Maximum fan speed (zone parameter)


The adjusted speed is valid for each unit of the zone, if the standby management is
enabled and when all units are running. In case of failure of one unit the remaining
units increase their fan speed so that the total air volume flow is kept constant.

C7000
The corresponding commands:
➊ zone 1 + 7 assigns unit 7 to zone 1 ➐ zone 1 average 1
zone 1 - 7 deletes unit 7 from zone 1 ➑ zone 1 sbaverage 0
➋ zone 1 seqtime 10 ➒ zone 1 nmax 85
➌ zone 1 emernum 3
➍ zone 1 emertemp 15,7
➎ zone 1 cwmode 1
➏ zone 1 test 1 en- (1) or disables (0) test sequencing

E/0409/57/97
C7000 Advanced

Q2a Zone
By setting one of the two following parameters or the parameters "water start
temperature or water hysteresis" different from zero the proportional GE control is
enabled.

➊. Start temperature (zone parameter)


Below the outside air temperature which is set as start temperature the operating
modes FC, EFC and MIX are enabled.

➋. Hysteresis (zone parameter)


With this hysteresis the operating modes FC, EFC and MIX are blocked. Only the
DX operating mode is enabled in this case.

➌. Standby units (unit parameter)


Q2b - Q2e A zone, in which a sequencing shall be carried out, must contain at least one
standby unit. With the setting "1" the actual unit is defined as standby unit. This
setting defines the initial state of the sequencing and changes according to the
actual state of the sequencing.

➍. Valid alarms (zone parameter)


With the setting "1" the corresponding alarm is defined as a valid alarm for the zone,
which entails that the unit is de-energized and the unit is registered as defect.

➎. Water start temperature (zone parameter)


Below the water temperature which is set as water start temperature the operating
modes FC, EFC and MIX are enabled.

➏. Water hysteresis (zone parameter)


With this hysteresis the operating modes FC, EFC and MIX are blocked. Only the
DX operating mode is enabled in this case.

C7000
The corresponding commands:
➊ zone 1 gestart 18,0 puts unit 3 into standby ➎ zone 1 gewstart 12,0
➋ zone 1 gehys 2,0 switches unit 3 on ➏ zone 1 gewhys 2,0
➌ zone 1 unit 3 0
zone 1 unit 3 1

➍ zone 1 alarm 2 0 deletes valid alarm 2


➎ zone 1 alarm 2 1 adds alarm 2 as valid alarm
➏ zone 1 alarm h displays list of all available alarms

E/0409/57/98
C7000 Advanced Statistics
Data logger
R1b Config
Here you can adjust the basic conditions for the data logger.
To this belongs sensor type ➊ and cycle ➋, the interval in which measure valures of
the corresponding sensor are stored.
Each data logger can store 1440 datapoints maximum. The 1441st datapoint deletes
the first datapoint etc.. If you adjust a cycle of 1 minute you obtain a grafic for a lapse
of time of 1440 minutes which corresponds exactly to 24 hours. With a cycle of 2
minutes, datapoints for a lapse of 2 days are stored etc..
Regarding the fact that the grafic represents a width of 180 pixels, we recommend to
choose the cycle depending on the lapse of time (Info menu) to be represented.
TYPE (for C7000 command) :
1 - unit room temperature
Lapse (Info menu) Cycle
2 - unit room humidity
- Hour 1 Min.
3 - unit supply temperature
- Day 8 Min.
4 - unit supply humidity
- Week 60 Min.
5 - water temperature 1
- Month 240 Min.
6 - outside temperature
- Year 2880 Min.
7 - outside humidity
8 - condensation pressure 1
9 - condensation temp. 1
At the modification of a parameter (type or cycle) all data of the cor-
10 - evaporation pressure 1
responding data logger is deleted.
11 - evaporation temp. 1
12 - zone room temperature
13 - zone room humidity
14 - zone supply temperature
15 - zone supply humidity

Statistics
Runtime
R2c, R2d
This summary of runtimes exists only for the C7000 Avanced. Being an exact copy
of the homonymous branch in the Info menu, the Config runtime menus provide the
possibility to reset the runtimes.

In contrast to the C7000 I/O controller, you can reset the runtimes of the global unit
functions in the C7000 Advanced.
When you change the controller you can continue the runtimes this way and set the
past runtimes at the new controller.

C7000
The corresponding commands:
➊ log 1 cycle 15 The first numeral designates the number of the ➊ comp 1 runtime 0
➋ log 1 type 2 data logger (1 or 2). ➋ fan 1 runtime 0
The second numeral stands for: ➌ eheat 1 runtime 0
- the cycle in minutes pump 1 runtime 0

- the measure values listed left top.
➎ humi 1 runtime 0
➏ drycool 1 runtime 0

E/0409/57/99
C7000 Advanced Statistics
Maintenance
R3b Config
This functionality helps you to maintain the A/C unit in a good condition by monitoring
the service intervals.
In case the service interval is expired the alarm "service required" in combination
with the symbol is displayed in the standard window.
In the first line you enter the service interval you consider as suitable. Possible values
are 0-24 months, with 0 months you avoid the monitoring ➊.
In the second line you can assign the maintenance alarm to an alarm relay ➋.
If a maintenance alarms occurs, it is displayed at 9:00 AM.
In the third line you can set, whether the maintenance alarm shall trigger a common
alarm ➌ (1-yes, 0-no).
If you are on the field "MAINT. DONE" and you press the OK-key, you confirm the
executed maintenance ➎. The controller then sets the actual date in the fourth line
and saves it.

S1a, S1b System


In this menu you can set the global address ➊ of the unit. This address serves to
identify the unit within a BMS.
In the first menu line you can enter a unit name with up to 20 characters, this entry
is not possible by C7000IOC commands.
In the third line the unit type which you can set in the submenu "Default setting" is dis-
played. 11 pre-configurations for several unit types are stored in the I/O controller.

By selecting a pre-configuration ➋ the settings which are specified for the unit type
come into effect. These settings are shown in the table on page 125.

S2a Password
At this menu item you can adjust the password for the "config" level.
This password is "0000" as default setting.

C7000
The corresponding commands:
➊ service int 4 ➊ globaddr 233
➋ service alarmprio 4 ➋ loaddefault dx1
➌ service commonalarm 1

➎ service 1 By "1" you confirm the execut-


ed maintenance.

E/0409/57/100
7. Special functions

7.1 Raised floor pressure control N1c


The pre-condition for this control is that every A/C unit is equipped with a
pressure sensor.
The option for a raised floor pressure sensor provided by Stulz features a
pressure range of 0-100 Pa or 0-250 Pa which is adjustable by jumpers. The
output signal can be adjusted to 0-10 V or 4-20 mA. This sensor must be
calibrated in the menu N1c.

F1e
The raised floor pressure control is enabled by a value in menu F1e which
is different from zero.
The control tries to keep the adjusted setpoint for the surpressure in the raised
floor. The air temperature control is continued but the pressure control has
priority to the temperature control.

M3c
For this control a proportionally controlled fan with an analogous output has
to be configured (Setting: LINEAR).
The control begins after the lapse of the "START 100%" time and the pre-
run time (M3e) with the maximum speed (max. DX or max. CW according to
the adjusted cooling priority). An offset value, which serves to adapt the air
volume flow to local conditions will not be considered.

Maximum speed serves only as an initial value for the control which starts
now by measuring the difference to the air pressure setpoint and reduces the
fan speed in case of exceeding the setpoint and increases fan speed when
the setpoint is passed under.
By three parameters (cycle, maximum control modification and control factor)
the characteristics of an integral control are achieved.
The adjusted minimum speeds are not passed under during control.

M3e
All speed increases or reductions for the fan with the exception of "reduction
according to time" (parameter called REDUCE SPEED) are put out of force. If
during the time adjusted here none of the functions "cooling, heating, humidifi-
cation, dehumidification" is requested, the speed is reduced by the percentage,
which you have adjusted in the 2nd column of "REDUCE SPEED".

After the unit stop the fan runs during an overrun time, which serves to reject
hot or cold air in the unit.

The menu items, which are irrelevant for the raised floor pressure control
have a grey backgroung.

E/0409/57/101
H3c
In the menus H3c and M3d you can configure the alarms "air flow alarm"
and "filter alarm" with all corresponding parameters.

In the menu A1e of the Info level you can read and compare the actual and
set value of the air pressure in the raised floor.

A1e
M3d

7.2 Changeover of the water circuits - CW2 units


In the menu L3c you can choose between two operating modes: L3c
1. Changeover operation (Parameter "Mode" : Separate)
2. Additional operation (Parameter "Mode" : Addedt)

Changeover operation
For changeover operation only the parameter settings for CW valve 1 (menu
G3e) are relevant (start temperature and gradient). In case of a changeover
these settings are applied on the active valve. The passive valve is completely
closed if it treats of valve 2. If the passive valve is valve 1 in the first water
circuit, it will be closed to the "value at switching". So to speak the output
A-OUT for valve 01 is commuted on A-OUT for valve 02 (or A-OUT 02 on
A-OUT 01).

If one or several of the following conditions are met, the output is commuted
from A-OUT 01 to A-OUT 02:
1. A voltage is present at the digital input (menu L3c, parameter D-IN), which
was assigned to the GE/CW valve.
2. DP 1025 is written with value "1" by a BMS.
3. DP 1025 is written with value "1" by inputting "1" for the parameter "CW2-
changeover" in menu K2b. G3e
4. Water temperature in circuit 1 is higher than parameter "GE-off" (menu
G3e).
5. Water temperature in circuit 1 is higher than the air temperature setpoint, in
case the parameter "Close, if water above SP" (menu L3c) has been set
"1".

If none of the above listed conditions is true, the output is switched back from
A-OUT 02 to A-OUT 01.

The changeover is displayed by the parameter "State" in the menu K2b of


K2b
the Config level and is output by a freely adjustable digital output (menu L3c,
parameter D-OUT).
If a dehumidification request exists, the active valve will be opened 100% to
provide maximum cooling capacity for dehumidification.

E/0409/57/102
Additional operation
During additional operation both CW valves can be open simultaneously. Start temperature 1 and gradient 1 apply
to CW valve 1, start temperature 2 and gradient 2 apply to CW valve 2 (menu G3e). A commutation is possible
also during additional operation. This is done by an exchange of start temperatures and gradients between both
valves.

If one or several of the following conditions are met, the parameters of both valves are exchanged:
1. A voltage is present at the digital input (menu L3c, parameter D-IN), which was assigned to the GE/CW valve.
2. DP 1025 is written with value "1" by a BMS.
3. DP 1025 is written with value "1" by inputting "1" for the parameter "CW2-changeover" in menu K2b.
4. Water temperature in circuit 1 is higher than parameter "GE-off" (menu G3e). Valve 1 will be closed to the "value
at switching" in this case.
5. Water temperature in circuit 1 is higher than the air temperature setpoint, in case the parameter "Close, if water
above SP" (menu L3c) has been set "1". Valve 1 will be closed to the "value at switching" in this case.

Attention: If condition 4 or 5 applies to valve 2, this valve is completely closed.

If none of the above listed conditions is true, the parameters of both valves are changed back.

The changeover is displayed by the parameter "State" in the menu K2b of the Config level and is output by a freely
adjustable digital output (menu L3c, parameter D-OUT).
If a dehumidification request and no condition for a parameter exchange exists, valve 1 is opened 100% to provide
maximum cooling capacity for dehumidification.
If a dehumidification request and a condition for a parameter exchange exist, valve 2 is opened 100%

E/0409/57/103
7.3 Zone control
The zone concept is based on the idea to obtain a homogeneous room
climate within a determined space by distributed generation of conditionned Setting the zone
air. number 1-20
Within an IO bus up to 20 zones can be defined. A zone is defined if at least
one unit is assigned to this zone. The assignment of a unit to a zone is done
Q1a
by setting a zone number in the main line of menu Q1a.
This assignment must be done individually for each unit (each IOC).

Average value determination


A basic principle of the zone control is the calculation of average values
of the measured values. Within a zone only one room temperature exists
which is calculated as the average value of all connected room temperature
sensors.
The same applies for the room humidity, supply temperature, supply humi-
dity, outside air temperature, water inlet temperature 1, water pressure and J1a
raised floor pressure, if existant.

The determination of average values can be disabled by the parameter in


the sixth line of menu Q1a (0 = off, 1 = on). By the parameter in the seventh
line of the same menu you can set whether standby units shall take part in
the calculation of average values. (0 = no, 1 = yes).

However the set values can be individually adjusted for each unit. If at all
they should only slightly vary. Q2a

Standby units
In the menus J1a and Q2a you can put the unit in standby by setting the
parameter in the third line "1".
The existence of standby units in a zone increase the airconditioning ope-
rating security and provides the possibility to replace defective units by
standby units.

Alarm changeover Q2b


In order to changeover units in the event of an alarm, you can define alarms
as valid by setting the corresponding parameter „1“ in the menus Q2b, Q2c,
Q2d and Q2e. If such an alarm (defined as valid) occurs, the defective unit
is switched off and the standby unit with the next higher bus address is
switched on. If another unit with a valid alarm occurs in the zone, the next
standby unit (if existant) is switched on.
Some alarms cause the cut-off of the defective unit or the deactivation of
functions even if the alarm has not been defined valid. (for details see chapter
8.1 alarm messages). Q2c
The alarm „unit not available“ can not be deleted from the alarm list. This
alarm is always part of the valid alarms and appears in case of a bus failure
or when the unit has been de-energized.

E/0409/57/104
Valid alarms:
--.Not available
02.Compressor lowpressure
01.Local stop
03.Compressor Failure
Q2d
04.E-heating Failure 05.Humidifier Failure
06.Humidifier 5uS 07.Humidifier 20uS
08.Fan error 09.Filter clocked
10.External alarm 11.Pump Failure
12.Drycooler Failure 13.Water detector
14.Roomtemp too high 15.Roomhumidity too high
16.Supplytemp too high 17.Supplyhumidity too high
18.Roomtemp too low 19.Roomhumidity too low
20.Supplytemp too low
22.Watertemp too high
21.Supplyhumiduty too low
23.Watertemp too low
Q2e
24.Fire/smoke detector 25.Sensor Failure
26.Sensor broken 27.Hotgas reheat Failure

Emergency operation
With the parameter in the second line of menu Q1a you can enable an
emergency operation. If this parameter is set "0", emergency operation is
disabled. By this parameter you set the number of defective units which are
necessary to enable emergency operation.
Emergency operation means that each A/C unit of the IO bus applies the
zone-specific emergency temperature as new temperature set value. The
Q1a
emergency temperature is set for each zone with the parameter in the third
line of menu Q1a.

Function of standby units


Even if the failing unit capacity of one zone is completely equalled by the
start of standby units, the defective units are counted as lacking.
To start an emergency operation just when the 100% unit capacity (without
standby units) is not reached anymore, the adjusted number of defective
units should be higher than the number of a zone's standby units.

Additional capacity - Temperature K1d


You can have started a standby unit if the air temperature setpoint is ex-
ceeded by the zone temperature (Average value or unit temperature, when
average value determination is disabled).
The excess of the setpoint can be adjusted by the parameter in the third line
of menu K1d in the shape of a temperature difference. Setting "0" disables
the additional capacity function.
When the temperature sinks again, the additional capacity unit is switched
off with a hysteresis of 1K.

Additional capacity - Humidity K1e


You can have started a standby unit if the air humidity setpoint is passed
under by the zone humidity (Average value or unit humidity, when average
value determination is disabled).
The undercut of the setpoint can be adjusted by the parameter in the third
line of menu K1e in the shape of a humidity difference. Setting "0" disables
the additional capacity function.
When the humidity rises again, the additional capacity unit is switched off
with a hysteresis of 3% relative humidity.

Precondition:
The additional capacity unit must be set as standby unit and must be as-
signed to a zone. Moreover the corresponding parameter (temperature or
humidity) "Overload" must have a value different from zero.

E/0409/57/105
The zone control comprises three specific functions:

1. Sequencing,
2. CW Standby Management, Q1a
3. Zone for proportional GE control

7.3.1 Sequencing
The sequencing provides a time dependent unit changeover. By the use
of standby units, a high operating reliability the same as an even unit ex-
ploitation is achieved.
By setting the cycle time (parameter in the first line of menu Q1a) you ad-
just the lapse of time, after which a changeover is done periodically. This
means that the standby status is changed over the units one by one. With
the setting 0 (hrs) no sequencing is made. Failure dependent change-over

Zone 02
Setting the cycletime causes the sequencing start.

Enabling the test sequencing (parameter in the fifth line of menu Q1a) Stand Stand
with the fixed cycletime of 5 minutes helps you to check the sequencing -by -by
function. Unit 02 Unit 04 Unit 05

All basic zone functions which


have been described on the pre- Time dependent change-over Stand
vious pages are also available (normal sequencing) -by
when the sequencing is enabled. e. g. with 2 standby units:
1. cycle unit 07, 11 standby Unit 06 Unit 09 Unit 10
2. cycle unit 08, 14 standby
a. Average value determination or 3. cycle unit 11, 01 standby
Cycle 1
deactivation etc.
b. Alarm changeover Zone 01 Zone 02
c. Emergency operation
d. Additional capacity
Stand Stand
The sequencing runs indepen- -by -by
dently from an additional capacity Unit 01 Unit 03 Unit 07 Unit 02 Unit 04 Unit 05
function and independently from
defective units.
Even a defective unit can be set Stand Stand
standby by the sequencing. Only -by -by
when the unit has to be switched Unit 08 Unit 11 Unit 14 Unit 06 Unit 09 Unit 10
on due to the changeover, the
control detects that the unit is Cycle 1 Due to Cycle 1
a failure of
defective and the unit remains unit 04 unit 05 is
switched off. Then the standby unit Zone 01
switched on.
Zone 02
with the next higher bus address
is switched on.
The unit, which is provided as
additional capacity, can only be
switched on during the cycles, in Unit 01 Unit 03 Unit 07 Unit 02 Unit 04 Unit 05
which it is in standby.

Stand Stand Stand Stand


-by -by -by -by
Unit 08 Unit 11 Unit 14 Unit 06 Unit 09 Unit 10

Cycle 2 Cycle 2

E/0409/57/106
7.3.2 CW Standby Management
Q1a
The CW standby management can be carried out with CW units and Dual-
fluid units with CW cooling priority. The basic idea is to share the heat load
permanently with as many as possible units in order to reduce the fan speed
of all units and thus to save energy. For this the provided standby units must
constantly take part in the cooling process. The total airflow is below the
airflow which is possible at most and is equalled in case of failure of one or
more units by increasing the fanspeed of the remaining units.

By "MAXFANSPEED" you adjust the fan speed which is to be kept in the


zone when all units are running. By "CW-ENERGY-SAVE" the CW-standby
management is enabled and in the same moment all standby units of the
zone are switched on. Both parameters are related to the zone and have
only to be adjusted at one unit of the zone.
n - units
nMax / %
The table beside displays how many units in a zone are necessary to keep f=1 f=2 f=3
the total airflow at the indicated fan speed in the left column, when "f" units 60 3 5 8
have failed.
65 3 6 9

This correlation is represented by the following formula. 70 4 7 10


75 4 8 12
80 5 10 15
85 7 14 20
n>f•( 100 )
100 - nMax 90 10 20 30

An A/C unit is switched off as defective unit if a valid alarm occurs at this
unit, in the same way as for the sequencing.
When a Dualfluid unit changes over to DX operation due to a fault like a "water
temperature too high" alarm , this unit applies the nMaxDX fan speed which
is higher than the MAXFANSPEED of the CW standby management.
The fan speed of the other units is not affected by this.

7.3.3 Zone for proportional GE control


Q2a
Such a zone consists of GE type A/C units, drycoolers and external glycol
pumps. Concerning the hardware, the zone exists in the shape of a com-
mon cooling water circuit and a common control of drycoolers and external
glycol pumps.
On the software level the zone operation is carried out by assigning the
A/C unit to the same zone and by setting the parameters "start tempera-
ture, hysteresis" or "water start temperature (=water inlet temperature 1),
hysteresis" different from "0". By this setting the proportional GE control is
activated. The zone parameters are transmitted to all units/controllers of the
zone and are assumed by these.
Some parameters as sequencing cycle and standby state are only operative
in DX mode. The proportional GE control is described in detail in a separate
manual.

E/0409/57/107
7.4 Free cooling with ECO-Cool Louver
L2b
This function enables a "Free cooling" with outside air, which is directed by a louver
system. Three louvers are necessary, which will be controlled in parallel by a single
analogous output.

1. Fresh air louver for the inlet of fresh outside air


2. Circulating air louver for the circulation of the room air
3. Exhaust air louver for the outlet of warm room air

The fresh air and exhaust air louver are operated in parallel, the circulating air louver
is operated in a reverse sense to these louvers. The setting is done by determinating G2b
the sense of rotation at the louver actuators.

Configuration
By setting the parameter "ACTIVE" on 1 you add an ECO louver to the configuration.
With "0" you disable the ECO-louver.
With the parameter "A-OUT" you determine a analogous output for the louver.

Control
Free cooling is enabled, when:
- room humidity is within determined limits (see diagram) and
Control
- outside air is cold enough. This means when the temperature of outside air is below
the EcoCool start value ➊. Fresh air-/
SP Circulating exhaust air
Free cooling is stopped, when the outside temperature is above the EcoCool start
air louver louver
temperature ➊ + hysteresis ➋ or when the room air humidity is outside the limits. 100%
The start temperature ➌ for the control must be entered as a positive difference to the
air temperature setpoint. In the fourth line you can set the gradient ➍, which defines
the range, in which the fresh air and exhaust air louver opens from 0 to 100% and
the circulating air louver closes in the same way.
0%
Additionally to normal operation there exist an emergency operation. If no com- ➌ ➍ Room
pressor is in the condition to operate, the free cooling by EcoCool louvers is enabled temp.
independently of the limits of air humidity and air temperature.

1st Enabling condition 2nd Enabling condition


1 1 ECO
2 Humidific. hysteresis 2 Dehumidific. hysteresis Hysteresis

on on

off off
%rel.hum.
Outside
Humidific. Setpoint Dehumidif. ECO ➊ temp.
Start Humidity Start Start temp.
Humidific. Dehumidif.
Hysteresis Hysteresis

Installation example
Fresh air louver Exhaust air
Circulating air louver Exhaust air louver
Fresh air Thermical
Circulating air load

A/C unit
(Downflow)

E/0409/57/108
7.5 Pump station control
The concept of pump station control is based upon the idea that one pump station
provides the water conveyance for up to five units, which need water for cooling.
S1b
Due to the differing need of cooling water the water pressure in the system is exposed
to big variations. This control assures that the water pressure at the unit outlet is kept
constant by pump speed control.
The pump station control represents a special control in the C7000 and can be set PS
in menu S1b by the pre-configuration "PS". The corresponding command via the
IOC service port is:
"loaddefault ps"

If the pump station is equipped with a C7000AT, the actual value of the water pres-
sure at the unit outlet and optionally the water temperature is displayed in the main
menu of this controller.
In the bus overview the pump station is displayed by a symbol, which contains the
values of these two parameters. Temperature
Pressure
The units, which are provided with water and the pump station itself form a zone,
which must be defined at the controller of the pump station.

Attention:
The pump station zone represents a special zone which must not be confused with
the zone operation, which you can set in menu Q1a.
This means, that an A/C unit can belong to a pump station zone and can be part of
another (sequencing) zone simultaneously.

The single units must be assigned to this zone at the pump station controller by means
of their bus addresses. At the C7000AT you can do this by setting the parameters
for the units "1“. In menu K2d of the Config level the possible units of the IO-bus are
displayed in four lines. The units with the bus addresses from 0 to 4 are displayed
in the first line by placeholders "-0-“. The other units are displayed in the following
K2d
three lines corrspondingly. By setting the parameter "0“, the corresponding controller
is taken out of the pump station zone.

Assigning units to a pump station zone is done in the C7000IOC of the pump station
by the command:

pszone + 3

By the following command the unit with the address 3 is taken out of the pump
station zone.

pszone - 3

When a unit sends a cooling water request on the IO bus, the pump station controller
verifies whether this unit is part of its pump station zone and starts pump operation
if the result is positive.

Cut off by error:


In case of an alarm of the flow monitor or a failure of all configured pumps the pump
station is switched off.

With the application of a pump station you do not have to configure pumps in the
GE units.

E/0409/57/109
Operate level

Values
F2b
For the operation of pump stations you can set a pressure setpoint. The pressure
setpoint represents the pressure increase by the pumps.
When the C7000 is used to control a pump station, the water pressure is the only
parameter which is controlled.

Command for the C7000IOC:


setwpress 3.0

Components/Cooling
Pump
G2f
The parameters in the first four lines of the pump menu in the Operate level are not
relevant for pump station control.
The pump alarm delay can be adjusted in seconds.

Command for the C7000IOC:


pump 1 alarmdelay 6

E/0409/57/110
Config level Components/Cooling
Pumps
L2f By setting the parameter "ACTIVE" on 1 you add a pump to the configuration. With
"0" you disable the pump. ➊
PS In the next line you determine which type the pump shall belong to (PS=pump
station pump). ➋
With the parameter "D-OUT" you determine a digital output ➌ for the pump enabling
signal.
With the parameter "A-OUT" you adjust the analogous output of the proportional
signal for the pump. ➍
The digital input for the pump alarm can be assigned by the "D-IN" parameter. ➎
You can adjust, whether the pump alarm releases a common alarm (0= no, 1 = yes).

Setting the priority for the pump alarm ➐ means assigning the corresponding alarm
to an alarm relay with the adjusted number.

Each pump station contains two pumps. In normal operation both pumps run at low
speed. In case of a pump failure the speed of the remaining trouble-free pump is
increased.
However, you can adjust a standby operation.
Standby operation can be enabled in the shape of a sequencing based on time and
failure. With "partner pump" ➑ you select the number of the 2nd pump (0-4). Setting
"0" disables the pump sequencing.
The sequencing is based on a runtime evaluation. In case of a runtime difference of
more than 20 hours the pump with the shorter runtime is put into operation.

Following menu:
The first two parameters are not relevant for pump station control.
With the control factor ➌ you set the proportional factor.

In order to avoid a remaining control discrepancy and to correct a drastic change of


water pressure, an integral factor ➍ and a differential factor ➎ can be adjusted.
You can set the control cycle ➏ by the parameter in the sixth line. With the control
cycle you adjust the control speed.
By the parameter in the last line you can set a minimum speed ➑ for pumps.

C7000IOC
Corresponding commands:
1st menu 2nd menu
➊ pump 1 conf 1 ➊ -
➋ pump 1 type 2 ➋ -
➌ pump 1 dout 3 ➌ pump 1 fact 2
➍ pump 1 aout 4 ➍ pump 1 int 3
➎ pump 1 alarm 3 ➎ pump 1 diff 6
➏ pump 1 commonalarm 0 ➏ pump 1 concyc 5
➐ pump 1 alarmprio 3 ➐ -
➑ pump 1 partpump 1 ➑ pump 1 min 20

E/0409/57/111
Components
Sensor
N1c
By setting the parameter "ACTIVE" on 1 you add a sensor to the configuration.
With "0" you disable the sensor. ➊
In the next line you determine the sensor type (current, voltage). ➋
With the parameter "PURPOSE" you specify for what the sensor is used ➌.
See left listing.
With the parameter "A-IN" you adjust the analogous input for the proportional
sensor signal. ➍
The following 5 items serve to calibrate the sensor. The minimum measure value
PURPOSE: (phys. value) ➏a is assigned to the minimum output (value). ➎a
21 - Water pressure The maximum measure value (phys. value) ➏b is assigned to the maximum output
(value). ➎b
optionally: The unit of the adjusted measure value depends on the sensor purpose (1-23). The
5 - Water temperature unit of the adjusted output depends on the sensor type (current, voltage).
If there is more than one sensor with the same purpose, an average value is cal-
culated. In the seventh line you can adjust a maximum difference to the average
value.➐ If the maximum difference is exceeded, the alarm "Sensor ## excess" is
released. For the evaluation of the sensor excess alarm at least three sensors with
the same purpose are needed.

You can adjust in the eighth line, whether the sensor limit alarm shall release a
common alarm ➑a. And you can assign the alarms to an alarm relay ➑b here.
You can adjust in the ninth line, whether the sensor failure alarm shall release a
common alarm ➒a. And you can assign the alarm to an alarm relay ➒b.

C7000IOC
Corresponding commands:
➊ sensor 1 conf 1 ➐ sensor 1 div 20 Sensor type:
➋ sensor 1 type 3 ➑a sensor 1 commonalarm 1 1: Current
2: Voltage
➌ sensor 1 use 5 ➑b sensor 1 alarmprio 2
➍ sensor 1 ain 3 ➒a sensor 1 commonalarmbr 1
➎a sensor 1 minout 0,0 ➒b sensor 1 alarmpriobr 3
➎b sensor 1 maxout 9,0
➏a sensor 1 minmeas -20,0
➏b sensor 1 maxmeas 40,0

E/0409/57/112
Assignment - I/O controller
The assignment for the pump station of unit type CPP is as follows:

Pin Designation DX1 Pin Designation CPP


1 24VAC 36 +15V
Power supply Active sensor 1
2 GND 37 GND
3 GND - 38 Ain 1 Water pressure, outlet
4 Din 1 Water flow failure 39 Ain 2 free
5 Din 2 Pump 1 failure 40 +15V
Active sensor 2
6 Din 3 Pump 2 failure 41 GND
7 Din 4 free 42 Ain 3 Water temperature
8 Din 5 free 43 Ain 4 free
9 Din 6 Phase detection 44 +Ub
10 Din 7 Water detection 45 GND Passive sensor 3
11 Din 8 free 46 Ain 5 free
12 Din 9 free 47 GND
13 Din 10 Remote on/off 48 Aout 1
free
14 Din 11 free 49 GND
15 Dout 1 (NO) 50 Aout 2
Pump 1
16 Dout 1 (COM) Pump 1 51 GND
17 Dout 1 (NC) 52 Aout 3
free
18 Dout 2 (NO) 53 GND
19 Dout 2 (COM) Pump 2 54 Aout 4
Pump 2
20 Dout 2 (NC) 55 GND
21 Dout 3 (NO) 56 Port 1-H
RS485-I/O-bus
22 Dout 3 (COM) free 57 Port 1-L
23 Dout 3 (NC) 58 Port 1-H
RS485-I/O-bus
24 Dout 4 (NO) 59 Port 1-L
25 Dout 4 (COM) free 60 +15V -
26 Dout 4 (NC) X10 SUB-D 15 Bus 3 IIC (socket1)
27 Dout 5 (NO) X11 SUB-D 15 Bus 3 IIC (socket2)
28 Dout 5 (COM) free X12 SUB-D 15 Bus 3 IIC (socket3)
29 Dout 5 (NC) X13 SUB-D 15 Bus 3 IIC (socket 4)
30 Dout 6 (NO) X14 SUB-D 15 EBUS exp. (plug)
31 Dout 6 (COM) Common alarm X15 SUB-D 9 RS232 service port (plug)
32 Dout 6 (NC)
33 Dout 7 (NO)
34 Dout 7 (COM) free
35 Dout 7 (NC)

E/0409/57/113
7.6 Summer-/winter operation

Values
GE-mode
K2/3b
The outside temperature ➊ for the commutation from summer to winter operation is
decisive for the drycooler and compressor control. With this hysteresis ➋ the winter
operation changes to summer operation.
The winter operation is also switched over to summer operation, if an outside temp.
sensor breakdown is detected. An alarm "Outside temperature sensor defect" is
not displayed.
If no outside temperature sensor is configured, summer operation is active.

In the main menu winter operation is indicated by the following symbol. ➋

Summer

Winter
T/°C
Components/Cooling
Compressor ➊

➋b
Two different start temperatures ➊a,➊b +
hysteresis ➋a,➋b for summer and winter
Comp.
➋a
G1c
operation can be entered. ON

OFF
Setpoint T/°C
➊a
➊b

Components/Cooling
Drycooler
Drycooler G2e
The start temperature for the drycooler is
➋ ➋
entered as an absolute value for the water
temperature. ON
Two different start temperatures for summer
➊a and winter ➊b operation + hysteresis
➋ can be entered. OFF
➊b ➊a T/°C
winter summer water
operation operation temp.

Components N2e
Aux. Ports/Aux. Ports

In this menu in the second line you can adjust the digital output for the wintermode.
The wintermode signal can be forwarded to a BMS system.

E/0409/57/114
8. Default configurations
Unit parameters Range Value
Unit name 20 characters Unit name
Bus address 0 - 19 0
Global address 0 - 37000 1
Local stop 0-1 1
Monitoring stop 0-1 0
Sequencing stop 0-1 0
Terminal language 0: English
1
1: German
Temperature unit 0: °C 1: °F 0
Temperature setpoint 5 - 50°C 24°C
Temperature setpoint, night 5 - 50°C 27°C
Humidity setpoint 5 - 90 % r. h. 45% r. h.
Water pressure setpoint 0 - 6 bar 1.5 bar
Raised floor pressure setpoint 0 - 1000 Pa 0 Pa
Condensation pressure DX 0 - 40 bar 18 bar
Condensation pressure Mix 0 - 40 bar 12 bar
Winter start delay 0 - 300 s 180 s
Summer/winter change-over 5 - 35°C 16°C
Summer/winter hysteresis 1 - 9,9 K 2K
Cooling priority 0: GE 1: CW 2: DX 0
Additional capacity - Temperature 0 - 9,9 K 0,0 K
Additional capacity - Humidity 0 - 20% r.h. 0% r.h.
Integral factor 0 - 10% 0%
Output D common alarm 0 - 31 6
Output D winter operation 0 - 31 0
Input D remote on/off 0 - 43 0
Output D local stop 0 - 31 0
Input D CW stop 0 - 43 0
Type of control 1-5 1
Limiting control - start temperature 0 - 40°C 16°C
Limiting control - temp. gradient 0 - 20 K 0,5 K
Limiting control - humidity start 0 - 90 % r.h. 70% r.h.
Limiting control - humidity gradient 0 - 20% r.h. 0,5% r.h.
Unit runtime 0 - 4294967295* 0h
Stop time 0 - 4294967295 0h
Cooling runtime 0 - 4294967295 0h
Heating runtime 0 - 4294967295 0h
Humidification runtime 0 - 4294967295 0h
Dehumidification runtime 0 - 4294967295 0h
Free cooling runtime 0 - 4294967295 0h
Mixed operation runtime 0 - 4294967295 0h

* 232 - 1 = 4294967295

E/0409/57/115
Last service - day 1 - 31 1
Last service - month 1 - 12 8
Last service - year 0 - 50 4
Service interval 0 - 24 0
Alarm priority service alarm 0 - 31 0
Common alarm for service alarm 0-1 0
UPS - input D 0 - 43 0
UPS - cooling admitted 0-1 1
UPS - heating admitted 0-1 1
UPS - humidification admitted 0-1 1
UPS - dehumidification admitted 0-1 1

Zone parameters Range Value Zone parameters Range Value


Zone 0 - 20 0 Average value determination 0-1 1
Sequencing time 0 - 65535 0h Average value determination
0-1 0
Test sequencing 0-1 0 with standby units

Valid alarms 1 - 27 1-13, 24-27 GE start temperature, air -100°C - 100°C 18°C

Number of defective units 0 - 20 0 GE hysteresis, air 0K - 9,9K 0K

Emergency temperature 0 - 40 16°C GE start temperature, water -100°C - 100°C 10°C

Zone fan speed nMax 0 - 100 85% GE hysteresis, water 0K - 9,9K 0K

CW standby management 0-1 0 Standby state 0-1 0

The parameter "zone" is not a zone parameter but can be adjusted separately for each unit.
Due to his context he is displayed in this table.

General alarms
Alarms Range Fire Water Flow Phase Bus alarm Addr. conflict
Alarm input D 0 - 43 0 0 0 0 - -
Alarm priority 0 - 31 0 0 0 0 0 0
Common alarm 0-1 1 1 1 1 0 0
Alarm delay 0 - 100 5s 5s 5s 5s 5s 5s
Restart 0-1 1

Limit alarms
Room temperature Supply temperature Water temperature
min max min max min max
Value 5°C (0-50) 35°C (5-55) 5°C (0-50) 35°C (5-55) -20°C (-20-30) 45°C (10-50)
Alarm delay 30 s (0-300) 30 s (0-300) 30 s (0-300) 30 s (0-300) 30 s (0-300) 30 s (0-300)
Alarm priority 0 (0-31) 0 (0-31) 0 (0-31) 0 (0-31) 0 (0-31) 0 (0-31)
Common alarm 1 1 1 1 1 1

Room humidity Supply humidity


min max min max
Value 5%h.r (0-90) 90%h.r (5-200) 5%h.r (0-90) 90%h.r (5-200) The values in brackets dis-
play the range.
Alarm delay 30 s (0-300) 30 s (0-300) 30 s (0-300) 30 s (0-300)
Alarm priority 0 (0-31) 0 (0-31) 0 (0-31) 0 (0-31)
Common alarm 1 1 1 1

E/0409/57/116
Week program
Hour Range 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
monday 0-2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
tuesday 0-2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...
sunday 0-2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Data logger
Data logger 1 Data logger 2
Data number 0 (0 - 1440) 0 (0 - 1440)
Interval 0 min (0 - 60000) 0 min (0 - 60000)
Type 1 (1 - 15) 1 (1 - 15)

Components
Compressor

Range Compressor 1 Compressor 2


Summer start 0 - 9,9 0,4 K 0,6 K
Summer hysteresis 0 - 9,0 0,7 K 0,7 K
Winter start 0 - 9,9 0,7 K 0,9 K
Winter hysteresis 0 - 9,0 0,7 K 0,7 K
Component configured 0-1 0 0
Output D 0 - 31 2 7
Alarm input D 0 - 43 2 8
Alarm priority 0 - 31 0 0
Common alarm 0-1 1 1
Alarm delay 0 - 100 5s 5s
Alarm input LP 0 - 43 3 9
Alarm priority LP 0 - 31 0 0
Common alarm LP 0-1 1 1
Alarm delay LP 0 - 100 5s 5s
LP management time 0 - 100 0h 0h
LP management press. 0 - 10 5 bar 5 bar
LP management restart 0 - 10 0 0
HP management time 0 - 100 0h 0h
HP management press. 0 - 35 21 bar 21 bar
HP management restart 0 - 10 0 0
HP management mode 0-1 0 0
Pause 10 - 1000 180 s 180 s
Runtime 0 - 4294967295 0h 0h

E/0409/57/117
Valves
Range Suction valve 1 Suction valve 2
Start 0 - 9,9 K 0K 0,4 K
Gradient 0,5 - 9,9 K 0,5 K 0,5 K
Minimum opening 0 - 100 % 20 20
Component configured 0-1 0 0
Output A 0 - 20 5 6

GE/CW-Valve G-Valve
Start 1 0,1 K (-9,9 - 9,9) Component configured 0 (0 - 1)
Gradient 1 0,6 K (0,5 - 9,9) Control cycle 5 s (1 - 10)
Start 2 0,5 K (-9,9 - 9,9) Max. alternation 2% (1 - 30)
Gradient 2 0,6 K (0,5 - 9,9) Control factor 40 (1 - 100)
Component configured 0 (0 - 1) Opening setpoint 70% (0 - 100)
Output A 1 2 (0 - 20) Output A 4 (0 - 20)
Output A 2 0 (0 - 20) Pre-open time 30 s (0 - 255)
Input D 0 (0 - 43) Pre-opening 100% (0 - 100)
Output D 0 (0 - 31) Minimum opening 0% (0 - 100)
Valve close at comp. 0 (0 - 1)
Valve operating mode 0 (0 - 1)
Valve close at setpoint 0 (0 - 1)
Heating 0 (0 - 1)
Output inversion 0 (0 - 1)
GE-off 23°C (0 - 100)
Setpoint 70% (0 - 100)
Value at switching 0% (0 - 100)

Hotgas bypass valve


Range HGBP-Valve 1 HGBP-Valve 2
Component configured 0-1 0 0
Output A 0 - 20 0 0
P-factor 0 - 100 20 20
I-factor 0 - 100 20 20
D-factor 0 - 100 20 20
Control cycle 1 - 10 s 2s 2s
Pre-open time 0 - 120 s 15 s 15 s
Pre-opening 0 - 100% 50% 50%
Minimum opening 0 - 100% 0% 0%
Maximum opening 0 - 100% 20% 100%

E/0409/57/118
Electronical expansion valve
Range EEV 1 EEV 2
Component configured 0-1 0 0
Valve type 1-5 0 0
Refrigerant 0-7 0 0
Pressure sensor 0-3 0 0
MOP control 0-1 0 0
MOP temperature -40 - 40°C 0°C 0°C
Superheating control mode 0-1 0 0
Battery supply 0-1 1 1
Battery time 0 - 254 s 20 s 20 s
Start opening 10 - 100% 0% 0%
Pre-open time 1 - 30 s 0s 0s
Alarm priority pressure sensor 0 - 31 0 0
Common alarm pressure sensor 0-1 0 0
Alarm priority temperature sensor 0 - 31 0 0
Common alarm temperature sensor 0-1 0 0
Alarm priority motor 0 - 31 0 0
Common alarm motor 0-1 0 0
Superheating SP normal 5 - 30°C 7°C 7°C
Superheating SP dehumidification 5 - 30°C 12°C 12°C

ECO-Cool louver
Range ECO-Cool
Component configured 0-1 0
Output A 0 - 20 0
Start outside temperature -100 - 100°C 18°C
Hysteresis 0 - 9,9 K 0K
Start temperature 0 - 9,9 K 0,1 K
Gradient 0,1 - 9,9 K 0,6 K

E/0409/57/119
Drycooler

Range Drycooler 1 Drycooler 2 Drycooler 3 Drycooler 4


Winter start 5 - 35°C 10°C 11°C 12°C 13°C
Summer start 10 - 50°C 34°C 35°C 36°C 37°C
Stop hysteresis 1 - 9,9 K 2K 2K 2K 2K
Component configured 0 -1 0 0 0 0
Output D 0 - 31 9 10 17 18
Output A 0 - 20 6 not available
Alarm input D 0 - 43 15 15 15 15
Alarm priority 0 - 31 0 0 0 0
Common alarm 0-1 0 0 0 0
Alarm delay 0 - 100 5s 5s 5s 5s
Preliminary speed 50 - 100% 100% 0% fix 0% fix 0% fix
Control cycle 1 - 255 s 1s 0 s fix 0 s fix 0 s fix
Max. alternation 1 - 30% 2% 0% fix 0% fix 0% fix
Control factor 1 - 100 40 0 fix 0 fix 0 fix
Runtime 0-4294967295 0h 0h 0h 0h

Pumps

Range Pump 1 Pump 2 Pump 3 Pump 4


Type 1-3 2 (GE) 1 (G) 3 (Glykol) 4 (PS pump)
Start 0 - 9,9 K 0,1 K 0,1 K 0,1 K 0,1 K
Stop hysteresis 0 - 9,9 K 0,3 K 0,3 K 0,3 K 0,3 K
Gradient 0,5 - 20 K 0,6 K 0,6 K 0,6 K 0,6 K
Component configured 0-1 0 0 0 0
Partner pump 0-4 0 0 0 0
Speed setpoint 0 - 100% 70% 70% 70% 0%
Minimum speed 0 - 100% 0% 0% 0% 0%
Output D 0 - 31 8 11 8 11
Output A 0 - 20 2 4 5 8
Alarm input D 0 - 43 13 14 13 14
Alarm priority 0 - 31 0 0 0 0
Common alarm 0-1 0 0 0 0
Alarm delay 0 - 100 s 5s 5s 5s 5s
Pre-open time 0 - 120 s 10 s 10 s 10 s 10 s
Preliminary speed 0 - 100 100% 100% 100% 100%
Control cycle 1 - 10 s 5s 5s 5s 1s
Max. alternation 1 - 30% 2% 2% 2% 50%
Control factor 1 - 100 40 40 40 50
I-factor 0 - 100 0 0 0 0
D-factor 0 - 100 0 0 0 0
Runtime 0 - 4294967295 0h 0 0 0

E/0409/57/120
Reheats

Range electr. reheat 1 electr. reheat 2 electr. reheat. 3


Type 1-2 1 1 fix 1 fix
Start 0 - 9,9 K 1,5 K 2K 2,5 K
Stop hysteresis 0 - 9,9 K 0,5 K 0,5 K 0,5 K
Gradient 0,3 - 9,9 K 0,5 K 0,5 K 0,5 K
Component configured 0-1 0 0 0
Output D 0 - 31 3 4 12
Alarm input D 0 - 43 4 4 4
Alarm priority 0 - 31 0 0 0
Common alarm 0-1 1 1 1
Alarm delay 0 - 2550 s 4s 4s 4s
Runtime 0 - 4294967295 0h 0h 0h

Range Hot water reh. Range Hot gas reheat


Type 1-2 1 Start 0 - 9,9 1,0 K
Start 0 - 9,9 K 1,0 K Stop hysteresis 0 - 9,9 0,5 K
Stop hysteresis 0 - 9,9 K 0,5 K Component configured 0-1 0
Gradient 0,5 - 9,9 K 0,5 K Output D 0 - 31 4
Component configured 0-1 0 Alarm input D 0 - 43 0
Output D 0 - 31 4 Alarm priority 0 - 31 0
Output A 0 - 20 7 Common alarm 0-1 0
Alarm delay 0 - 2550 s 1s
Humidifiers
Range Humidifier 1 Humidifier 2 Humidifier 3
Type 1-2 2 2 2
Start 0 - 20 0 %r.h. 0 %r.h. 0 %r.h.
Stop hysteresis 0 - 20 5 %r.h. 5 %r.h. 5 %r.h.
Gradient 0,5 - 20 10 10 10
Component configured 0-1 0 0 0
Conductivity meter conf. 0-1 0 0 0
Output D 0 - 31 13 0 0
Output A 0 - 20 3 6 7
Alarm input D 0 - 43 6 6 6
Alarm priority 0 - 31 0 0 0
Common alarm 0-1 1 1 1
Alarm delay 0 - 100 5s 5s 5s
Alarm input D 5µS 0 - 43 0 0 0
Alarm priority 5µS 0 - 31 0 0 0
Common alarm 5µS 0-1 0 0 0
Alarm delay 5µS 0 - 1000 300 s 300 s 300 s
Alarm input D 20µS 0 - 43 6 6 6
Alarm priority 20µS 0 - 31 0 0 0
Common alarm 20µS 0-1 1 1 1
Alarm delay 20µS 0 - 1000 300 s 300 s 300 s
Runtime 0 - 4294967295 0h 0h 0h

E/0409/57/121
Dehumidifier Range Dehumidifier
Start 0 - 100 %r.h. 10 %r.h.
Stop hysteresis 0 - 30 %r.h. 5 %r.h.
Dehumidification stop 0 - 10 K 5K
Dehumidif. valve conf. 0-1 0
Bypass valve conf. 0-1 0
Output D 0 - 31 5
Min water temperature -20 - 50°C 5°C
Max water temperature 0 - 100°C 14°C

Fans Range Fan 1 Fan 2 Fan 3


Type 1-2 2 2 2
Maximum speed DX 30 - 100 % 85% 85% 85%
Maximum speed CW 30 - 100 % 85% 85% 85%
Offset -10 - 10 % 0% 0% 0%
Pre-start 0 - 100 s 10 s 10 s 10 s
Overrun 0 - 250 s 60 s 60 s 60 s
Start temperature 0 - 9,9 K 0K 0K 0K
Start speed 0 - 10% 0% 0% 0%
100% start time 0 - 100 s 5s 5s 5s
Reduction time 30 - 120 min 30 min 30 min 30 min
Reduction speed 0 - 100 % 0% 0% 0%
Dehumidific. reduction 0 - 20 % 0% 0% 0%
Dehumidification time 0 - 30 min 0 min 0 min 0 min
UPS reduction 0 - 20 % 0% 0% 0%
Filter offset 0 - 10 % 0% 0% 0%
Minimum speed DX 0 - 100 % 70 % 70 % 70 %
Minimum speed CW 0 - 100 % 50 % 50 % 50 %
Output D 0 - 31 1 8 9
Output A 0 - 20 1 0 0
Alarm input D 0 - 43 1 13 15
Alarm priority 0 - 31 0 0 0
Common alarm 0-1 1 1 1
Alarm delay 0 - 100 s 10 s 10 s 10 s
Filter alarm input D 0 - 43 5 5 5
Filter alarm priority 0 - 31 0 0 0
Filter common alarm 0-1 1 1 1
Filter alarm delay 0 - 100 s 20 s 20 s 20 s
Emergency start 0 - 9,9 K 0K 0K 0K
End temperature 0 - 9,9 K 0K 0K 0K
Emergency speed 0 - 100 % 0% 0% 0%
Control cycle 0 - 255 s 5s 0s 0s
Max. alternation 0 - 30 % 2% 0% 0%
Control factor 1 - 100 40 0 0
Component configured 0-1 1 0 0
Runtime 0 - 4294967295 0h 0h 0h

E/0409/57/122
Louver
Range Louver 1 Louver 2 Louver 3
Pre-start 0 - 180 90 s 90 s 90 s
Output D 0 - 31 7 10 18
Component configured 0-1 0 0 0

Sensors
Range Sensor 1 Sensor 2 Sensor 3 Sensor 4
Purpose 1 - 23 1 2 3 4
Input A 1 - 21 1 2 3 4
Type 1-5 1 1 1 1
Component configured 0-1 1 1 0 0
Min. measure value -50 - 100 0°C (-50 - 100) 0%r.h (0 - 100) 0°C (-50 - 100) 0%r.h (0 - 100)
Max. measure value -50 - 100 50°C (-50 - 100) 100%r.h (0 - 100) 50°C (-50 - 100) 100%r.h (0 - 100)
Min. output value 0 - 20 4 mA (0 - 20) 4 mA (0 - 20) 4 mA (0 - 20) 4 mA (0 - 20)
Max. output value 0 - 20 20 mA (0 - 20) 20 mA (0 - 20) 20 mA (0 - 20) 20 mA (0 - 20)
Max. difference 0 - 100 10% 10% 10% 10%
Limit - alarm priority 0 - 31 0 0 0 0
Limit - common alarm 0-1 1 1 1 1
Limit - alarm delay 0 - 100 5s 5s 5s 5s
Failure - alarm priority 0 - 31 0 0 0 0
Failure -common alarm 0-1 1 1 1 1
Failure - alarm delay 0 - 100 5s 5s 5s 5s
Offset -50,0 - 50,0 0°C 0% r.h. 0°C 0% r.h.

Range Sensor 5 Sensor 6 Sensor 7 Sensor 8


Purpose 1 - 23 5 6 9 14
Input A 1 - 21 5 6 7 8
Type 1-5 1 2 1 1
Component configured 0-1 0 0 0 0
Min. measure value -50 - 100 -50°C (-50 - 100) -20°C (-50 - 100) 0 bar (0 - 35) 0 bar (0 - 35)
Max. measure value -50 - 100 50°C (-50 - 100) 40°C (-50 - 100) 30 bar (0 - 35) 30 bar (0 - 35)
Min. output value 0 - 20 0 mA (0 - 20) 0 V (0 - 20) 4 mA (0 - 20) 4 mA (0 - 20)
Max. output value 0 - 20 20 mA (0 - 20) 10 V (0 - 20) 20 mA (0 - 20) 20 mA (0 - 20)
Max. difference 0 - 100 10% 10% 10% 10%
Limit - alarm priority 0 - 31 0 0 0 0
Limit - common alarm 0-1 1 1 1 1
Limit - alarm delay 0 - 100 5s 5s 5s 5s
Failure - alarm priority 0 - 31 0 0 0 0
Failure -common alarm 0-1 1 1 1 1
Failure - alarm delay 0 - 100 5s 5s 5s 5s
Offset -50,0 - 50,0 0°C 0°C 0 bar 0 bar

E/0409/57/123
Sensors (continued)
Range Sensor 9 Sensor 10 Sensor 11 Sensor 12 - 21
Purpose 1 - 23 17 18 21 0
Input A 1 - 21 8 10 1 0
Type 1-5 2 2 1 0
Component configured 0-1 0 0 0 0
Min. measure value -50 - 100 10°C 0 %r.F. 0 bar 0
Max. measure value -50 - 100 30°C 100 %r.F. 10 bar 0
Min. output value 0 - 20 0V 0V 4 mA 0
Max. output value 0 - 20 10 V 10 V 20 mA 0
Max. difference 0 - 100% 0% 0% 10 % 0%
Limit - alarm priority 0 - 31 0 0 0 0
Limit - common alarm 0-1 0 0 1 1
Limit - alarm delay 0 - 100 s 0s 0s 5s 5s
Failure - alarm priority 0 - 31 0 0 0 0
Failure -common alarm 0-1 0 0 1 1
Failure - alarm delay 0 - 100 0s 0s 5s 5s
Offset -50,0 - 50,0 0°C 0 %r.F. 0 bar 0

External alarms
Range External alarm 1 External alarm 2 ... External alarm 10
Component configured 0-1 0 0 ... 0
Input D 0 - 43 0 0 ... 0
Alarm priority 0 - 31 0 0 ... 0
Common alarm 0-1 0 0 ... 0
Alarm delay 0 - 250 5s 5s ... 5s
Alarm text 20 characters Externer_Alarm_in_01 Externer_Alarm_in_02 ... Externer_Alarm_in_10

Value output
Range Value output 1 ... Value output 4
Component configured 0-1 0 ... 0
Purpose 1 - 23 1 ... 1
Min. limit value -50 - 100 0°C ... 0°C
Max. limit value -50 - 100 50°C ... 50°C
Output A 0 - 20 0 ... 0

E/0409/57/124
8.1 Preconfigurations

11 default configurations for different unit cooling systems are stored in the I/O
controller.
ACW/ Pump
Unit type A/G GE/GE1 GE2 CW
GCW station
1 circuit dx1 ge11 ge21 agcw1 cw ps
2 circuits dx2 ge12 ge22 agcw2 cw2 -
C7000 command: The table contains the parameters for the IOC-
loaddefault dx1 command.

The following table displays the differences in relation to the default settings when a pre-configuration is selected.

DX1 DX2 CW CW2 AG/CW1 AG/CW2 GE1-1 GE1-2 GE2-1 GE2-2


Compressor 1 conf. 1 1 - - 1 1 1 1 1 1
Compressor 2 conf. - 1 - - - 1 - 1 - 1
Sensor 5 configured - - - - 1 1 1 1 1 1
Sensor 6 configured - - - - - - 1 1 1 1
Sensor 7 configured - - - - - - 1 1 1 1
Sensor 8 configured - - - - - - - 1 - 1
Pump 1 configured - - - - - - - - 1 1
Pump 2 configured - - - - - - - - 1 1
Deshum. configured 1 1 - - 1 1 1 1 1 1
GE/CW valve conf. - - 1 1 1 1 1 1 - -
G valve conf. - - - - - - 1 1 - -
Dehum. reduction - - 20% 20% 20% 20% 20% 20% 20% 20%
Input D GE/CW valve - - - 3 - - - - - -
Cooling priority - - - - 1 1 - - - -

PS Notes:
Control mode 5 - For all unit versions except CW and CW2 of the series CyberAir 2 the
Input D - waterflow 1 dehumidification valve must be deconfigured and the electronic expansion
Sensor 1 purpose 21 valve configured.
- Settings "ge21" and "ge22" are only appropriate for GE units of the series
Sensor 2 configured 0
CyberAir 1 (green column in the table).
Sensor 5 configured 1 - Using setting "ps" sensor 5 must be deconfigured. If the water outlet tem-
Pump 1 configured 1 perature shall be measured, a sensor must be configured for this.
Pump 1 type 4
Pump 1 output D 1
Pump 1 input D 2
Pump 2 configured 1
Pump 2 type 4
Pump 2 output D 2
Pump 2 input D 3
Fan 1 configured 0

E/0409/57/125
9. Alarm treatment
9.1 Alarm display

C7000 AT
The alarm messages are displayed in the standard window of each unit with
IOC. At the same time the symbol in the left bottom indicates that an
alarm has occurred.
An alarm tone proves the presence of an alarm independantly of the actual
menu window of the C7000AT.
Attention: The alarm tone can be disabled. (See page 22)

C7000
„state“
The alarm display in the command level is passive. This means
Unit:Running that you have to type in the command "state" to see the occurred
alarms.
- Runtime:32167 min
- Stoptime:2167 min

Cooling:active (15356 min)


- Compressor 1:1
- CW/GE-valve:66 %

Heating:not active (3472 min)

Humidification:active (9265 min)


- Humidificator 1:31 %

Dehumidification:not active (28 min)

Alarms:
- Common alarm
- Drycooler 1
- Sensor break 11

E/0409/57/126
9.2 Possible Alarm texts
Cause Alarm message Effect
LP switch/LP threshold passed under LOW PRESSURE 1 Compressor 1 off
HP switch/HP threshold exceeded
COMP 1 FAILURE/HP Compressor 1 off
Internal compressor power switch
LP switch/LP threshold passed under LOW PRESSURE 2 Compressor 2 off
HP switch/HP threshold exceeded
COMP 2 FAILURE/HP Compressor 2 off
Internal compressor power switch
Temperature switch/heating MCB E-HEAT # FAILURE Heating # off
Humidifier MCB HUMIDIFIER # FAIL Humidifier # off
Airflow differential switch AIRFLOW FAILURE # all components off
Filter differential switch FILTER ALARM Fan speed increase according to parameter
"Filter offset"
External alarm signal EXTERNAL ALARM # no direct effect*
Conductivity >5µS HUMIDIFIER # 5µS no direct effect*
Conductivity >20µS HUMIDIFIER # 20µS Ultrasonic humidifier off
Glycol pump MCB GLYCOL PUMP # FAILURE Pump off
G-Pump MCB G-PUMP FAILURE Pump off
GE-Pump MCB GE-PUMP FAILURE Pump off
Drycooler # MCB DRYCOOLER # FAIL Drycooler # off
Water detector WATER ALARM Humidifier off
Return air temp. > limit value RETURN AIR TEMP TOO HIGH no immediate effect
Return air humidity > limit value RETURN AIR HUM TOO HIGH no immediate effect
Supply air temp. > limit value SUPPLY AIR TEMP TOO HIGH no immediate effect
Supply air humidity > limit value SUPPLY AIR HUM TOO HIGH no immediate effect
Water temp. > limit value WATER TEMP TOO HIGH no immediate effect
Return air temp. < limit value RETURN AIR TEMP TOO LOW no immediate effect
Return air humidity < limit value RETURN AIR HUM TOO LOW no immediate effect
Supply air temp. < limit value SUPPLY AIR TEMP TOO LOW no immediate effect
Supply air humidity < limit value SUPPLY AIR HUM TOO LOW no immediate effect
Water temp. < limit value WATER TEMP TOO LOW no immediate effect
Fire/smoke detector FIRE ALARM all components off
Phase failure, excess voltage, undervol- PHASE FAILURE all components off
tage, asymmetry, phase sequence
Tolerance exceeded SENSOR # EXCESS faulty sensor # excluded
Measured voltage/current out of defined SENSOR # DEFECT faulty sensor # excluded
range

# stands for a number.


* the corresponding alarm can be cofigured to release a common alarm which can control further equipment by a digital out-
put.
** the alarm text can be configured.

E/0409/57/127
9.3 Component-related alarms
The table shows the main components with their standard alarm input and the possible alarms.
DX/DX2-unit: Component Alarm input on board Alarm
Compressor 1 DIN 2 IOC COMP 1 FAILURE/HP
DIN 3 IOC LOW PRESSURE 1
Compressor 2 DIN 8 IOC COMP 2 FAILURE/HP
DIN 9 IOC LOW PRESSURE 2
Fan DIN 1 IOC AIRFLOW FAILURE 1
DIN 5 IOC FILTER 1 ALARM
E-heating DIN 4 IOC E-HEAT # FAILURE
Steam-Humidifier DIN 6 IOC HUMIDIFIER 1 FAIL
Pump 3 (Glycol) DIN 13 EDIO 1 PUMP 3 FAILURE
Pump 4 (Glycol) DIN 14 EDIO 1 PUMP 4 FAILURE
Drycooler DIN 15 EDIO 1 DRYCOOLER 1 FAIL

CW/CW2-unit: Component Alarm input on board Alarm


Fan DIN 1 IOC AIRFLOW FAILURE 1
DIN 5 IOC FILTER 1 ALARM
E-heating DIN 4 IOC E-HEAT 1 FAILURE
Steam-Humidifier DIN 6 IOC HUMIDIFIER 1 FAIL
Pump 1 DIN 2 IOC PUMP 1 FAILURE
Pump 2 DIN 14 EDIO 1 PUMP 2 FAILURE

9.4 Alarm Reset


C7000 AT
The alarms are reset by pressing the RESET-key. Pressing it once mutes the alarm tone. Pressing it again resets
all alarms. However, if the alarm cause has not been eliminated, the alarm will appear again.
Alarms can either be reset in the standard window for each single unit or in the bus configuration overview by
marking all bus participants for all units.

C7000
The alarms for one unit are reset with the command "alarmreset" or "ar".

E/0409/57/128
9.5 Alarm texts in the case of hardware errors
These alarms are edited by the terminal program as following:

HARDWARE ERROR Nr. 13 (Ext ID:Set IO-ports)

IIC bus reset!!!

The following errors are edited:


Nr. 00 Erase sector 6 flash 2 error
Nr. 01 Write in sector 6 flash 2 error
Nr. 02 Erase sector 7 flash 2 error
Nr. 03 Write in sector 7 flash 2 error
Nr. 04 Read of digital input error
Nr. 05 Write of digital output error
Nr. 06 Read of analoge input error
Nr. 07 Write of analoge output error
Nr. 08 Digital extension card error
Nr. 09 Cannot select extension port
Nr. 10 Analoge extension card error
Nr. 11 Analoge extension card: cannot read input
Nr. 12 Analoge extension card: cannot set output
Nr. 13 Ext ID:Set IO-ports
Nr. 14 Write bht in EEIO
Nr. 15 Data read from VCM 1
Nr. 16 Read of ext ID
Nr. 17 Read VCM 1 conf
Nr. 18 Read VCM 2 conf
Nr. 19 Write bchrg in EEIO
Nr. 20 Write VCM 1 refrig
Nr. 21 Write VCM 2 refrig
Nr. 22 Write VCM 1 MOP con
Nr. 23 Write VCM 2 MOP con
Nr. 24 Write VCM 1 MOP temp
Nr. 25 Write VCM 2 MOP temp
Nr. 26 Write VCM 1 SUP mode
Nr. 27 Write VCM 2 SUP mode
Nr. 28 Write VCM 1 SUP set
Nr. 29 Write VCM 2 SUP set
Nr. 30 Write VCM 1 start dur
Nr. 31 Write VCM 2 start dur
Nr. 32 Write VCM 1 start open
Nr. 33 Write VCM 2 start open
Nr. 34 Write VCM 1 valve type
Nr. 35 Write VCM 2 valve type
Nr. 36 Write VCM 1 press sen type
Nr. 37 Write VCM 2 press sen type
Nr. 38 Write VCM 1 hand on
Nr. 39 Write VCM 2 hand on
Nr. 40 Write VCM 1 hand val
Nr. 41 Write VCM 2 hand val
Nr. 42 Data read from VCM 2

bht: battery holding time


bchrg: battery charge

E/0409/57/129
10. Configuration notes
First steps after the reception of a new software
1. Load software on IOC, resp. on C7000AT. (see 10.1 Loading a new software)
2. Check bus configuration (configuration is kept after loading the software)
3. Load a default configuration according to the unit type (see 8.1 pre-configurations)
4. Check the equipment by command "equip".
5. Configure additional components.
At the C7000AT you can do this in the Config-level in the submenus of the menu point "Components". Part of
the configuration is the activation of the component, the allocation of an output for the component control and
eventually the assignment of an alarm input.

Possible maximum equipment according to unit type


Component A G GE ACW GCW CW CW2 max.
Louver 1 1 1 1 1 1 1 3
Fan 1 1 1 1 1 1 1 3
Compressor 1-2 1-2 1-2 1-2 1-2 2
Suction valve 1-2 1-2 1-2 1-2 1-2 2
Hotgas bypass valve 1-2 1-2 1-2 1-2 1-2 2
Electrical expansion valve 1-2 1-2 1-2 1-2 1-2 2
Dehum.valve 1 1 1 1 1 1
G-valve 1 1 1 1
GE/CW-valve 1 1 1 1 1 (2)* 1
Glycol pump 1-2 1-2 1-2 1-2 1-2 1-2 2
Drycooler 1-4 1-4 1-4 4
E-Heating 1-3 1-3 1-3 1-3 1-3 1-3 1-3 3
Hotgas reheat 1 1 1 1 1 1
PWW-reheat 1 1 1 1 1 1 1 1
Humidifier 1-3 1-3 1-3 1-3 1-3 1-3 1-3 3
Conductivity meter 1 1 1 1 1 1 1 1
* Only one GE/CW-valve can be configured, but 2 analogous outputs are available.
For both valve the same parameters are valid.

The following components can only be configured in a single quantity.


Please note that the commands do not require a specification of quantity.

Hotgas-Bypass dehumi confbypass 1


Dehumidif. valve dehumi confvalve 1 Further components
G-valve gvalve conf 1 Component max.
GE/CW-valve gecwv conf 1
Sensor 21
Hotgas reheat gasheat conf 1
PWW-reheat pwwheat conf 1 external alarm 10
Conductivity meter humi 1 confcon 1

E/0409/57/130
10.1 Loading a new Software
For a C7000-control system there are two different soft-
wares. The essential control software, which contains the
commands for the command level, is located in the Flash- Pos. 1-2
EPROM on the IOC-board. The second software contains
the menu structure of the C7000AT and is located in the
EPROM of the C7000AT board. Pos. 2-3
The control parameters in the IOC are resistent and do not
have to be re-entered after loading the software. This is also
the case for the IO bus configuration of the C7000AT.

For loading a software in the flash-EPROM of the IOC


you must connect the service port of the IOC to a serial
interface of your PC/Laptop by means of a RS232 modem
connection.
RS 232 - modem con-
Switch off the master switch. Set the jumper JP7 to position
nection with 2x9 poles
2-3. The master switch must then be switched on again. Sub-D (Female)
The IOC is now in the „download“-mode. Start the program
"C7000-Service.exe" on your PC. This program can be COM 1
downloaded from the Stulz-website.
After the new software has been loaded, the master switch
must be switched off and the jumper JP7 must be set in the
position 1-2. After this switch on the master switch.

For loading a software in the flash-EPROM of the C7000AT


you must connect the service port of the C7000AT to a serial Rear side of C7000 AT board
interface of your PC/Laptop by means of a RS232 modem
connection. C7000 AT
Switch off the master switch. After this the jumper X6 must
be set in the position A. The master switch must then be X4
switched on again. The C7000AT is now in the „download“-
mode. Start the program "C7000-Service.exe" on your PC.
After the new software has been loaded, switch off the mas-
ter switch and set the jumper X6 in position B. After this the
master switch must be on again. When switching on, ensure Pos. A Pos. B
that the new version number is correctly displayed.

*System requirements: Windows 95/98/NT/2000/ME/XP/


Vista

Only for the C7000 AT:


In the next step all parameters, if they deviate from the default settings and the bus configuration, must be readjusted.
The default language is English. If you require another language, you can change this in the „System\Languages“
menu.

E/0409/57/131
10.1.1 Operation of the program "C7000-Service.exe"
With an up-to-date WinXP/Vista system the program must only be copied onto the computer hard disk and can
directly be started by a doubleclick. The files (C7000-Service.exe and IOC-Service.exe) must be stored in the same
folder. With former WinXP versions, Win2000, WinME and Win98 the install-package which can be obtained from
the e-Stulz domain must be carried out.

Start C7000-Service.exe und click on the button "Terminal",


which starts the program IOC-Service.exe.
Select an interface to the PC (COM 1 - 9) and check the con-
nection to the IOC or C7000AT by pressing the Return key. If
you receive a response from the IOC/C7000AT the connection
is established.
Clicking on the "Download" button opens a window, in which
you can enter the file which shall be loaded. This is done by You can start the download now with the button "Start". The
clicking on the button "Select file", which opens a dialogue single steps are indicated in the "Help/State" line, the progress
windows for the selection of a file. The file is a hexadecimal of each step in the "Download Progress" line.
file with the extension *.h86.
Clicking on "Close" closes the download window. Pressing the
The file name gives information about the software destination.
"End" button quits the program IOC-Service.
C7000AT-Vxxx.H86 is destined for the C7000AT. C7000IOC-
Vxxx.h86 correspondingly for the IO-controller. The number
behind the V indicates the version.

Concerning the block size and the transmission rate, you can
take the preadjusted values (1024 Bytes and 38400 kBit/s).
The transmission will then take approx. 2 minutes for each
software. With a longer cable however, you may be obliged to
reduce the rate.

E/0409/57/132