Siprotec 4 7Sj61 Multifunction Protection Relay: Function Overview

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

5 Overcurrent Protection / 7SJ61

SIPROTEC 4 7SJ61
Multifunction Protection Relay
Function overview

Protection functions
• Time-overcurrent protection
(definite-time/inverse-time/user-def.)
• Sensitive earth-fault detection
• Intermittent earth-fault protection
• High-impedance restricted earth fault
• Inrush restraint
• Motor protection
LSP2299-afpen.eps

– Undercurrent monitoring
– Starting time supervision
– Restart inhibit
– Locked rotor
• Overload protection 5
• Temperature monitoring
Fig. 5/56 SIPROTEC 4 7SJ61 multifunction protection relay • Breaker failure protection
• Negative-sequence protection
• Auto-reclosure
• Lockout
Description
Control functions/programmable logic
The SIPROTEC 4 7SJ61 relays can be used • Commands for control of a
for line protection of high and medium circuit-breaker and of isolators
voltage networks with earthed (grounded),
low-resistance earthed, isolated or com- • Control via keyboard, binary inputs,
pensated neutral point. When protecting DIGSI 4 or SCADA system
motors, the SIPROTEC 4 7SJ61 is suitable • User-defined logic with CFC
for asynchronous machines of all sizes. The (e.g. interlocking)
relay performs all functions of backup pro-
tection supplementary to transformer dif- Monitoring functions
ferential protection. • Operational measured values I
The relay provides a simple control of the • Circuit-breaker wear monitoring
circuit-breaker and automation functions. • Slave pointer
The integrated programmable logic (CFC)
allows the user to implement their own • Time metering of operating hours
functions, e. g. for the automation of • Trip circuit supervision
switchgear (interlocking). The user is also • 8 oscillographic fault records
allowed to generate user-defined messages.
Communication interfaces
The flexible communication interfaces are
open for modern communication architec- • System interface
tures with control systems. – IEC 60870-5-103, IEC 618501)
– PROFIBUS-FMS/-DP
– DNP 3.0/MODBUS RTU
• Service interface for DIGSI 4 (modem)
• Front interface for DIGSI 4
• Time synchronization via IRIG B/DCF77
Hardware
• 4 current transformers
• 3/8/11 binary inputs
• 4/8/6 output relays

1) Version V4.51 and newer.

Siemens SIP · 2004 5/55


5 Overcurrent Protection / 7SJ61

Selection and ordering data Description Order No.


7SJ61 multifunction protection relay 7SJ61¨o – ¨¨¨¨¨ – ¨¨¨¨
Housing, binary inputs (BI) and outputs (BO)
Housing 1/3 19”, 3 BI, 4 BO, 1 live status contact 0
Housing 1/3 19”, 8 BI, 8 BO, 1 live status contact 1
Housing 1/3 19”, 11 BI, 6 BO, 1 live status contact 2 see
next
Measuring inputs ( 4 x I) page
Iph = 1 A, Ie = 1 A (min. = 0.05 A)
Position 15 only with A 1
Iph = 1 A, Ie = sensitive (min. = 0.001 A)
Position 15 only with B 2
Iph = 5 A, Ie = 5 A (min. = 0.25 A)
Position 15 only with A 5
Iph = 5 A, Ie = sensitive (min. = 0.001 A)
Position 15 only with B 6
Iph = 5 A, Ie = 1 A (min. = 0.05 A)
Position 15 only with A 7

Rated auxiliary voltage (power supply, indication voltage) 5


24 to 48 V DC, threshold binary input 19 DC3) 2
60 to 125 V DC1), threshold binary input 19 DC3) 4
110 to 250 V DC1), 115 to 230 V4) AC, threshold binary input 88 V DC3) 5

Unit version
For panel surface mounting, 2 tier terminal top/bottom B
For panel flush mounting, plug-in terminal (2/3 pin connector) D
For panel flush mounting, screw-type terminal (direct connection/ring-type cable lugs) E

Region-specific default settings/function versions and language settings


Region DE, 50 Hz, IEC, language: German, selectable A
Region World, 50/60 Hz, IEC/ANSI, language: English (GB), selectable B
Region US, 60 Hz, ANSI, language: English (US), selectable C
Region FR, 50/60 Hz, IEC/ANSI, language: French, selectable D
Region World, 50/60 Hz, IEC/ANSI, language: Spanish, selectable E

System interface (Port B): Refer to page 5/677


No system interface 0
Protocols see page 5/77

Service interface (Port C)


No interface at rear side 0
DIGSI 4/modem, electrical RS232 1
DIGSI 4/modem/RTD-box2), electrical RS485 2
DIGSI 4/modem/RTD-box2)5), optical 820 nm wavelength, ST connector 3

Measuring/fault recording
Fault recording 1
Slave pointer, mean values, min/max values, fault recording 3

1) Transition between the two auxiliary


voltage ranges can be selected by
means of jumpers.
2) Temperature monitoring box
7XV5662-oAD10, refer to “Accessories”.
3) The binary input thresholds can be
selected in two stages by means of jumpers.
4) 230 V AC, starting from device version
…/EE.
5) When using the temperature monitoring
box at an optical interface, the additional
RS485 fiber-optic converter

Siemens SIP · 2004 5/75


5 Overcurrent Protection / 7SJ61

Selection and ordering data Description Order No. Order


code
7SJ61 multifunction protection relay 7SJ61¨o – ¨¨¨¨¨ – ¨¨¨¨–¨¨¨¨
Designation ANSI No. Description
Basic version Control
50/51 Time-overcurrent protection
I>, I>>, Ip, reverse interlocking
50N/51N Earth-fault protection
IE>, IE>>, IEp
50N/51N Earth-fault protection via insensitive
IEE function: IEE>, IEE>>, IEEp1)
49 Overload protection (with 2 time constants)
46 Phase balance current protection
(negative-sequence protection)
50BF Breaker failure protection
74TC Trip circuit supervision
4 setting groups, cold-load pickup
Inrush blocking
86 Lockout F A

5 n IEF Intermittent earth fault P A


n 50Ns/51Ns Sensitive earth-fault detection (non-directional) F B 2)
n IEF 50Ns/51Ns Sensitive earth-fault detection (non-directional)
Intermittent earth fault P B 2)
n Motor IEF 50Ns/51Ns Sensitive earth-fault detection (non-directional)
Intermittent earth fault
37 Undercurrent monitoring
48 Starting time supervision
66/86 Restart inhibit R B 2)
n Motor 50Ns/51Ns Sensitive earth-fault detection (non-directional)
37 Undercurrent monitoring
48 Starting time supervision
66/86 Restart inhibit H B 2)
n Motor 37 Undercurrent monitoring
48 Starting time supervision
66/86 Restart inhibit H A
ARC Without 0
79 With auto-reclosure 1
ATEX100 Certification
For protection of explosion-protected motors (increased-safety type of protection “e”) Z X 9 9

n Basic version included


IEF = Intermittent earth fault

1) 50N/51N only with insensitive earth-current transformer


when position 7 = 1, 5, 7.
2) Sensitive earth-current transformer
only when position 7 = 2, 6.

5/76 Siemens SIP · 2004


5 Overcurrent Protection / 7SJ61

Order numbers for system port B Description Order No. Order


code
7SJ61 multifunction protection relay 7SJ61¨o – ¨¨¨¨¨ – ¨¨¨¨–¨¨¨
System interface (on rear of unit, Port B)
No system interface 0
IEC 60870-5-103 protocol, RS232 1
IEC 60870-5-103 protocol, RS485 2
IEC 60870-5-103 protocol, 820 nm fiber, ST connector 3
PROFIBUS-FMS Slave, RS485 4
PROFIBUS-FMS Slave, 820 nm wavelength, single ring, ST connector 1) 5
1
PROFIBUS-FMS Slave, 820 nm wavelength, double ring, ST connector ) 6
PROFIBUS-DP Slave, RS485 9 L 0A
1
PROFIBUS-DP Slave, 820 nm wavelength, double ring, ST connector ) 9 L 0B
MODBUS, RS485 9 L 0D
2
MODBUS, 820 nm wavelength, ST connector ) 9 L 0 E
DNP 3.0, RS485 9 L 0G
5
DNP 3.0, 820 nm wavelength, ST connector 2) 9 L 0H
1) Not with position 9 = “B”; if 9 = “B”, please order 7SJ6 unit with RS485 port and separate fiber-optic converters.
For single ring, please order converter 6GK1502-3AB10, not available with position 9 = “B”.
For double ring, please order converter 6GK1502-4AB10, not available with position 9 = “B”.
The converter requires a 24 V AC power supply (e.g. power supply 7XV5810-0BA00).
2) Not available with position 9 = “B”.

Sample order Position Order No. + Order code


7SJ6125-5EC91-3FA1+L0G

6 I/O’s: 11 BI/6 BO, 1 live status contact 2


7 Current transformer: 5 A 5
8 Power supply: 110 to 250 V DC, 115 V AC to 230 V AC 5
9 Unit version: Flush-mounting housing, screw-type terminals E
10 Region: US, English language (US); 60 Hz, ANSI C
11 Communication: System interface: DNP 3.0, RS485 9 L 0G
12 Communication: DIGSI 4, electric RS232 1
13 Measuring/fault recording: Extended measuring and fault records 3
14/15 Protection function package: Basic version FA
16 With auto-reclosure 1

Siemens SIP · 2004 5/77


5 Overcurrent Protection / 7SJ61

Accessories Description Order No.

DIGSI 4
Software for configuration and operation of Siemens protection units
running under MS Windows 95/98/ME/NT/2000/XP Professional Edition
Basis Full version with license for 10 computers, on CD-ROM
(authorization by serial number) 7XS5400-0AA00
Demo Demo version on CD-ROM 7XS5401-0AA00
Professional Complete version:
DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation) 7XS5402-0AA00

IEC 61850 System configuration tool


Software for configuration of stations with IEC 61850 communication under
DIGSI, running under MS Windows 95/98/ME/NT/2000/XP Professional Edition
Optional package for DIGSI 4 Basis or Professional
License for 10 PCs. Authorization by serial number. On CD-ROM 7XS5460-0AA00

5 SIGRA 4
Software for graphic visualization, analysis and evaluation of fault records.
Can also be used for fault records of devices of other manufacturers (Comtrade
format). Running under MS Windows 95/98/ME/NT/2000/XP Professional Edition.
(generally contained in DIGSI Professional, but can be ordered additionally)
Authorization by serial number. On CD-ROM. 7XS5410-0AA00

Temperature monitoring box


24 to 60 V AC/DC 7XV5662-2AD10
90 to 240 V AC/DC 7XV5662-5AD10

Varistor/Voltage Arrester
Voltage arrester for high-impedance REF protection
125 Vrms; 600 A; 1S/S 256 C53207-A401-D76-1
240 Vrms; 600 A; 1S/S 1088 C53207-A401-D77-1

Connecting cable
Cable between PC/notebook (9-pin con.) and protection unit (9-pin connector)
(contained in DIGSI 4, but can be ordered additionally) 7XV5100-4
Cable between temperature monitoring box and SIPROTEC 4 unit
- length 5 m /16.4 ft 7XV5103-7AA05
- length 25 m /82 ft 7XV5103-7AA25
- length 50 m /164 ft 7XV5103-7AA50

Manual for 7SJ61, English C53000-G1140-C118-7

5/78 Siemens SIP · 2004


5 Overcurrent Protection / 7SJ61

Accessories Description Order No. Size of package Supplier

LSP2289-afp.eps
Terminal safety cover
Voltage/current terminal 18-pole/12-pole C73334-A1-C31-1 1 Siemens
Voltage/current terminal 12-pole/8-pole C73334-A1-C32-1 1 Siemens
Connector 2-pin C73334-A1-C35-1 1 Siemens
Mounting rail
Connector 3-pin C73334-A1-C36-1 1 Siemens
1)
Crimp connector CI2 0.5 to 1 mm2 0-827039-1 4000 AMP
taped on reel
LSP2091-afp.eps
LSP2090-afp.eps

2 1)
Crimp connector CI2 0.5 to 1 mm 0-827396-1 1 AMP
2 1)
Crimp connector: Type III+ 0.75 to 1.5 mm 0-163084-2 1 AMP
Crimp connector: Type III+ 0.75 to 1.5 mm
2
0-163083-7 4000 AMP 1)
2-pin 3-pin
connector connector taped on reel

Crimping tool for Type III+ 0-539635-1 1 AMP 1)


and matching female 0-539668-2 1 AMP 1)
1)
Crimping tool for CI2 0-734372-1 1 AMP
LSP2093-afp.eps

LSP2092-afp.eps

1)
and matching female 1-734387-1 1 AMP
5
Short-circuit links
for current terminals C73334-A1-C33-1 1 Siemens
for other terminals C73334-A1-C34-1 1 Siemens
Short-circuit links Short-circuit links
for current termi- for other terminals Mounting rail for 19" rack C73165-A63-D200-1 1 Siemens
nals
Your local Siemens representative can inform you on local suppliers.

1) AMP Deutschland GmbH


Amperestr. 7–11
63225 Langen
Germany
Tel.: +49 6103 709-0
Fax +49 6103 709-223

Siemens SIP · 2004 5/79