ATV312 DeviceNet Manual S1A10387 02
ATV312 DeviceNet Manual S1A10387 02
ATV312 DeviceNet Manual S1A10387 02
Altivar 312
Variable speed drives
for asynchronous motors
09/2012
S1A10387
www.schneider-electric.com
Contents
S1A10387 09/2012 3
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain
it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call
attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in
personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow
this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury or
equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment
damage.
CAUTION
CAUTION, used without the safety alert symbol, indicates a potentially hazardous situation which, if not avoided,
can result in equipment damage.
PLEASE NOTE
The word "drive" as used in this manual refers to the controller portion of the adjustable speed drive as defined by NEC.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by
Schneider Electric for any consequences arising out of the use of this product.
4 S1A10387 09/2012
Before you begin
Read and understand these instructions before performing any procedure with this drive.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Read and understand this manual before installing or operating the Altivar 312 drive. Installation, adjustment, repair, and
maintenance must be performed by qualified personnel.
• The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of
all equipment.
• Many parts of this drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically
insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA/+ and PC/– or across the DC bus capacitors.
• Before servicing the drive:
- Disconnect all power, including external control power that may be present.
- Place a “DO NOT TURN ON” label on all power disconnects.
- Lock all power disconnects in the open position.
- WAIT 15 MINUTES to allow the DC bus capacitors to discharge.
- Measure the voltage of the DC bus between the PA/+ and PC/– terminals to ensure that the voltage is less than 42 Vdc.
- If the DC bus capacitors do not discharge completely, contact your local Schneider Electric representative. Do not repair or
operate the drive
• Install and close all covers before applying power or starting and stopping the drive.
DANGER
UNINTENDED EQUIPMENT OPERATION
• Read and understand this manual before installing or operating the Altivar 312 drive.
• Any changes made to the parameter settings must be performed by qualified personnel.
WARNING
DAMAGED DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
LOSS OF CONTROL
• The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control
functions, provide a means to achieve a safe state during and after a path failure.
Examples of critical control functions are emergency stop and overtravel stop.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications of unanticipated
transmission delays or failures of the link.a
Failure to follow these instructions can result in death, serious injury, or equipment damage.
a. For additional information, refer to NEMA ICS 1.1 (latest edition), “Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control” and to
NEMA ICS 7.1 (latest edition), “Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive Systems.”
S1A10387 09/2012 5
Documentation structure
The following Altivar 312 technical documents are available on the Schneider Electric website (www.schneider-electric.com) as well as on
DVD-ROM (reference VW3A8200).
Installation manual
This manual describes how to install and wire the drive.
Programming manual
This manual describes the functions, parameters and use of the drive terminal (integrated display terminal, optional graphic display terminal
and optional remote terminal).
The communication functions are not described in this manual, but in the manual for the bus or network used.
Simplified manual
This manual is a simplified version of the User manual. This manual is delivered with the drive.
6 S1A10387 09/2012
Introduction
Presentation
The DeviceNet communication card (catalog number VW3A312 09) is used to connect an Altivar 312 drive to a DeviceNet network.
The communication card has an open-style 5-pin connector for connection to the network.
The graphic display terminal or the integrated display terminal can be used to access numerous functions for communication diagnostics.
Notation
Drive terminal displays
The graphic display terminal menus, available with the remote graphic display terminal option are shown in square brackets.
Example: [1.9 COMMUNICATION].
The integrated 7-segment display terminal menus are shown in round brackets.
Example: (COM-).
Parameter names are displayed on the graphic display terminal in square brackets.
Example: [Fallback speed]
Parameter codes are displayed on the integrated 7-segment display terminal in round brackets.
Example: (LFF).
Formats
Hexadecimal values are written as follows: 16#
Binary values are written as follows: 2#
Vocabulary
Depending on DeviceNet document and tools, equivalent wordings are used. The table below shows vocabulary used in the present
document and other corresponding definitions.
Abbreviations
Req. = Required
Opt. = Optional
S1A10387 09/2012 7
Hardware setup
Presentation
Relay outputs
Analog inputs
Logic inputs
Addressing
switches, SW1
DeviceNet
D2 - NS / Network Status
LEDs
Receipt
• Check that the card reference printed on the label is the same as that on the delivery note corresponding to the purchase order.
• Remove the option card from its packaging and check that it has not been damaged in transit.
DANGER
UNINTENDED EQUIPMENT OPERATION
• Do not plug or unplug the terminal board while drive is powered.
• Check the tightening of the fixing screw after any manipulation on the terminal board.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not touch the terminal board before:
• removing power on the drive,
• removing any voltage on input and output terminals.
8 S1A10387 09/2012
Hardware setup
1. Open the ATV312 front cover. Remove the plastic cover plate from the power terminals (see Installation manual).
2 & 3. Remove the terminal board fixing screw and take off the ATV312 standard terminal board.
(Be careful not to lose the terminal board fixing screw when removed since it may be used again.)
This step does not apply if you are using an ATV312.... B (product without standard IO terminal).
4. Install the DeviceNet card and secure it with the board fixing screw.
(M3 tapping screw tightening torque: 0.7 to 0.8Nm)
5. Stick the new cabling label above the DeviceNet option card.
Stick the DeviceNet card nameplate near the ATV312 nameplate. (Be careful not to cover slits on the ATV312 enclosure)
7. Wire and screw the EMC clamps for the DeviceNet cables (and control wires if required).
Note: To install or remove the terminal board, make it slide in or out in parallel with board.
S1A10387 09/2012 9
Hardware setup
10 S1A10387 09/2012
Wiring to the network
1 Not connected
2 Not connected
3 Not connected
4 D1
5 D0
6 Not connected
7 VP (1)
8 Common
DeviceNet
connector
EMC clamps
Line termination: If the drive is the first or the last device on the DeviceNet network, a line terminator (121 Ohm resistor) must be wired on
the removable DeviceNet female connector, between pins 2 and 4 (CAN_L and CAN_H).
S1A10387 09/2012 11
Wiring to the network
When wiring in electrical equipment rooms or large electrical equipment line-ups, observe the following guidelines for cable segregation
and separation of circuits:
• Use metallic conduit for drive wiring. Do not run control network and power wiring in the same conduit.
• Separate non-metallic conduits or cable trays used to carry power wiring from metallic conduit carrying low-level control network
wiring by at least 300 mm (11.9 in).
• Separate metallic conduits carrying power wiring or low-level control network wiring by at least 80 mm (3.15 in).
• Cross the metallic conduits and non-metallic conduits at right angles whenever power and control network wiring cross.
• Attenuate conducted emissions from the drive to the line in some installations to prevent interference with telecommunication, radio,
and sensitive electronic equipment. Such instances may require attenuating filters. Consult the Altivar catalog for selection and
application of these filters.
The ODVA standards (Release 2.0) specify 7 types of cables for use in DeviceNet networks:
• Thick cable
• Thin cable
• Flat cable
• Cable I
• Cable II
• Cable IV
• Cable V
The table below lists main specifications of cables. For more information, refer to the ODVA specifications.
Type of cable Data conductor pair size Power conductor pair size Data impedance
Thick cable 18 AWG 15 AWG 120 Ohm +/- 10 % (at 1 MHz)
Thin cable 24 AWG 22 AWG 120 Ohm +/- 10 % (at 1 MHz)
Flat cable 16 AWG 16 AWG 120 Ohm +/- 10 % (at 500 kHz)
Cable I 24 AWG 22 AWG 120 Ohm +/- 10 % (at 1 MHz)
Cable II 18 AWG 15 AWG 120 Ohm +/- 10 % (at 1 MHz)
Cable IV 18 AWG 16 AWG 120 Ohm +/- 10 % (at 500 kHz)
Cable V 18 AWG 16 AWG 120 Ohm +/- 10 % (at 500 kHz)
12 S1A10387 09/2012
Wiring to the network
The maximum permissible length of the network cable depends an the data rate and the type of cable.
For maximum length of the drops refer to table, whatever type of cable:
S1A10387 09/2012 13
Configuration
For more information, see the [Restore config.] (FCS) parameter in ATV312 programming manual on www.schneider-electric.com
DANGER
UNINTENDED EQUIPMENT OPERATION
Check that the modification of the current configuration is compatible with the wiring diagram used.
High = OFF = 0
Low = ON = 1
Any change to the switch setting takes effect at the next power-up.
14 S1A10387 09/2012
Configuration
The table below lists the switch setting for each valid node address.
Any change to the switch setting takes effect at the next power-up.
Examples
S1A10387 09/2012 15
Configuring by the drive HMI
Numerous configurations are possible. For more information, refer to the Programming manual and Communication parameters manual.
The following configurations are some of the possibilities available.
The choice of the assembly set is defined by the application at the DeviceNet scanner level. It cannot be set at the device level. See the
paragraph "Assembly Selection" in the chapter "Integration of the ATV312 in a DeviceNet network", page 26.
Please refer to the chapter "Supervision and control in LINE mode", page 28.
The ODVA AC drive profile is activated when one of the following assemblies is selected:
• 20: Basic speed control output
• 21: Extended speed control output
• 70: Basic speed control input
• 71: Extended speed control input
The advantage of using the ODVA drive profile standard is the interchangeability with other brands.
The DeviceNet card translates the commands, behaviour and monitoring information from of ODVA profile (on the network) to the Drivecom
profile (in the drive).
Available configurations
M If you use the native profile:
• 100: Native command Word and speed reference (CMD and LFRD)
• 101: Native status and current speed (ETA and RFRD)
The examples below are only possible if you use the communication scanner.
M If you use the ODVA AC drive profile, that is, the assemblies:
16 S1A10387 09/2012
Configuring by the drive HMI
1 Drive state
However separate mode is only allowed when the [ACCESS LEVEL] (LAC) parameter in the [COMMAND] (CtL-) menu is set to L3.
The Control of the drive is also detailed in the programming manual of the ATV312 in the chapter "Control Menu".
Terminals/Keypad
S1A10387 09/2012 17
Configuring by the drive HMI
Configuration via the graphic display terminal or the integrated display terminal:
Configuration via the graphic display terminal or the integrated display terminal:
18 S1A10387 09/2012
Configuring by the drive HMI
For more information, see the chapter "Assembly selection", page 26.
Explicit Messaging
Class Code
Hexadecimal Decimal
16#70 to 16#A8 112 to 424
Examples
Class code = ((ADL - 3000)/200) + 70hex
Attribute ID = (ADL modulo 200)+1
Instance = 1
Drive logical address Hexadecimal path
3 000 16# 70 / 01 / 01
3 100 16# 70 / 01 / 65
3 201 16# 71 / 01 / 02
S1A10387 09/2012 19
Configuring by the drive HMI
The communication between the master (external management system) and the drive is broken:
In this case, the drive will generate an (CnF) error message.
CFF [INCORRECT • The current configuration is • Return to factory settings or retrieve the backup
CONFIG.] inconsistent. configuration, if it is valid. See the [Restore config.]
• Addition or removal of an option (FCS) parameter in ATV312 programming manual.
CnF [NETWORK • Communication detected fault on the • Check the environment (electromagnetic compatibility).
FAULT] communication card • Check the wiring.
• Check the time out.
• Replace the option card.
• See the [CANopen fault mgt] (COL) parameter in the
ATV312 programming manual to define the stop mode
with a (CnF).
For the full list of the fault detected codes, see ATV312 programming manual on www.schneider-electric.com
20 S1A10387 09/2012
Integration of the ATV312 in a DeviceNet network
This chapter describes how to integrate an Altivar 312 in a DeviceNet network controlled by a Rockwell Automation PLC.
1. To install the new eds file, you can launch the EDS wizard from RSNetWorx for DeviceNet by selecting Tools > FDS Wizard.
Note: We recommend to use a recent version of RSNetWorx (V7.0 or later).
2. Click Next.
S1A10387 09/2012 21
Integration of the ATV312 in a DeviceNet network
4. Select the location where the eds file has been recorded, and then click Next.
22 S1A10387 09/2012
Integration of the ATV312 in a DeviceNet network
You should get the following result, that indicates that the eds file has been successfully imported.
5. Click Next.
6. The wizard will propose you to change the icon picture associated to the device.
If you don't need to change the icon file, click Next to terminate the eds registration.
7. Click Finish.
S1A10387 09/2012 23
Integration of the ATV312 in a DeviceNet network
The DeviceNet module is identified with the following symbol: Module_DNET. This identifier will be used later with tools like the Class
Instance Editor.
24 S1A10387 09/2012
Integration of the ATV312 in a DeviceNet network
S1A10387 09/2012 25
Integration of the ATV312 in a DeviceNet network
Assembly selection
The choice of the assembly set should be done from the PLC, by applying the required assembly number to the following objects:
• Output assembly: 5/0/64
• Input assembly: 5/0/65
The default setting of these assemblies is 21/71.
It is recommended to set by program (when PLC starts) the assemblies needed for the application.
26 S1A10387 09/2012
Diagnostics by the drive HMI
Signalling LEDs
Two LED indicators are placed on the board.
The behaviour is described in the following chapter.
Start-up sequence
A LED test is performed during start-up, after module init is complete.
Step Module Status LED "D1 - MS" Network Status LED "D2 - NS"
1 0.25s 0.25s Turned off
2 0.25s 0.25s
3 Turned off
Finished Standard indication Standard indication
LED states
LED state Visual description of the LED state
The LED is ON
S1A10387 09/2012 27
Supervision and control in LINE mode
Exiting the "Operation enabled" status via a "Disable voltage" (9) or "Shutdown" (8) command causes a freewheel stop.
28 S1A10387 09/2012
Supervision and control in LINE mode
The Altivar control process using the communication bus is based on the CiA 402 profile status chart compatible with the IEC 61800-7
standard. Each state represents an aspect of the internal behaviour of the drive.
This chart evolves according to whether the control word is sent (CMD W8501) or an event occurs (example: lock following malfunction).
The drive status can be identified by the value of the status word (ETA W3201).
A Quick stop (CMD = 16#0002) is an emergency stop that causes a stop on a short ramp followed by locking in the "Quick stop active" state.
To be able to restart the drive, you must first change to the "Switch on disabled" state via the "Disable voltage" command (CMD = 16#0000).
It is not possible, therefore, to execute a run command immediately after a Quick stop.
Note:
In access level L1 or L2 (parameter LAC):
• Priorities between channels are managed by the drive.
• At switch-on, the drive is in control via the terminals and changes automatically to the "Operation enabled" state. This means that, when
a run command is applied (for example: CMD = 16#000F), it starts without needing to follow the IEC 61800-7 status chart procedure.
When the drive is controlled via a communication bus, it is advisable to configure the access level LAC = L3:
• The active channel is set by configuring the following parameters: [Profile] (CHCF), [Ref. 2 switching] (rFC), [Cmd switching] (CCS), [Cmd
channel 1] (Cd1), [Cmd channel 2] (Cd2), [Ref.1 channel] (Fr1) and [Ref.2 channel] (Fr2).
• At switch-on, the drive configured for control via the bus changes to the "Switch on disabled" state. This means that it must follow the IEC
61800-7 status chart procedure to be able to start, and to help prevent any unwanted behaviour.
S1A10387 09/2012 29
Supervision and control in LINE mode
(1) This bit action depends on the [ACCESS LEVEL] (LAC) parameter and the functions configured by the user.
For example, to use bit 15 to switch the ramp, simply configure LAC = L3 (Access to advanced functions and management of mixed
modes) and set the [Ramp switch ass.] (rPS) configuration parameter to Cd15.
30 S1A10387 09/2012
Supervision and control in LINE mode
S1A10387 09/2012 31
Supported CIP objects
CIP require some mandatory objects; these are implemented as well as some vendor specific objects.
32 S1A10387 09/2012
Supported CIP objects
Class attributes
# Access Name Type Value Description
1 Get Revision UINT 0x0001 Revision 1
Instance attributes
# Access Name Type Value Description
1 Get Vendor ID UINT 0x00F3
2 Get Device type UINT 0x0002 AC Drive:
• Vendor Name: Schneider Electric
• Vendor ID: 0x00F3
• Product code: 0xXXXX
• Product Name: ATV-312
• Catalog: ATV-312
• EDS file name: 00F30002XXXX0100.EDS
3 Get Product code UINT 6153
4 Get Revision Struct of:
Major revision USINT N/A Firmware major version
Minor revision USINT N/A Firmware minor version
5 Get Status WORD - Status of the device, see table below.
6 Get Serial number UDINT Serial number The low 4 bytes of the drive serial number
7 Get Product name SHORT_STRING ATV312
100 Get Fatal log Array of UINT8 N/A
S1A10387 09/2012 33
Supported CIP objects
Error codes
Fault type Fault source
Minor Recoverable Faults Duplicate MACID, Switch value changed
Minor Unrecoverable Faults
Major Recoverable Faults Non-Volatile Fault (CRC-error on read), Faulted, Connection to ATV312 lost
Major Unrecoverable Faults Non-Volatile Fault (CRC-error on write)
34 S1A10387 09/2012
Supported CIP objects
Class attributes
No supported class attributes
Instance attributes
No supported instance attributes
S1A10387 09/2012 35
Supported CIP objects
Class attributes
# Access Name Type Value Description
1 Get Revision UINT 0x0002 Revision 2
Instance attributes
# Access Name Type Value Description
1 Get MAC ID USINT N/A The used node address 0-63
2 Get Baud Rate USINT N/A The used baud rate:
0 = 125 k baud
1 = 250 k baud
2 = 500 k baud
3 Get/Set BOI BOOL N/A Bus off interrupt, default = FALSE
4 Get/Set Bus off Counter USINT N/A Bus off counter
5 Get Allocation Struct of:
Information
Allocation BYTE N/A Allocation choice byte
choice byte
Master's MAC USINT N/A MAC ID of master
ID
6 Get MAC ID Switch BOOL N/A 0 - No change
Changed 1 - The Node Address switch have changed since last
power-up/reset
7 Get Baud Rate BOOL N/A 0 - No change
Switch Changed 1 - The Baud Rate switch have changed since last
power-up/reset
8 Get Mac ID Switch USINT N/A Actual value of Node Address switch 0-63
Value
9 Get Baud Rate USINT N/A Actual value of Baud Rate switch 0-3
Switch Value
10 Get/Set Quick Connect BOOL 0 = Disable Enable/Disable of Quick Connect feature. Disabled
1 = Enable by default. Stored in NVRAM.
36 S1A10387 09/2012
Supported CIP objects
Services
Class services Get_Attribute_Single
Instance services Get_Attribute_Single
Set_Attribute_Single
Class attributes
# Access Name Type Value Description
1 Get Revision UINT 2 Revision 2
2 Get Max Instance UINT 101 Max instance 101
Instance attributes
# Access Name Type Value Description
3 Get/Set Data ARRAY of BYTE - Data produced/consumed by the module
S1A10387 09/2012 37
Supported CIP objects
1 Drive state
38 S1A10387 09/2012
Supported CIP objects
S1A10387 09/2012 39
Supported CIP objects
Class attributes
# Access Name Type Value Description
1 Get Revision UINT 0x0001 Revision 1
100 Get/Set Polled/ COS/ UINT 20, 21, 100 Default value is assembly instance 21.
Cyclic Consuming For a change to this attribute will require a restart of
Instance the ATV-312-DEV to have effect. (When read the
stored value is returned).
Stored in NVRAM.
101 Get/Set Polled/ COS/ UINT 70, 71, 101 Default value is assembly instance 71.
Cyclic Producing For a change to this attribute will require a restart of
Instance the ATV-312-DEV to have effect. (When read the
stored value is returned).
Stored in NVRAM.
Instance descriptions
Instance 1 = Explicit messaging connection (Predefined in DeviceNet object)
Instance 2 = Polled connection / COS/Cyclic consuming connection
Instance 4 = COS/Cyclic producing connection
Instances 10-14 = Explicit server instances
40 S1A10387 09/2012
Supported CIP objects
S1A10387 09/2012 41
Supported CIP objects
42 S1A10387 09/2012
Supported CIP objects
S1A10387 09/2012 43
Supported CIP objects
44 S1A10387 09/2012
Supported CIP objects
Services
Class services Get_Attribute_Single
Instance services Get_Attribute_Single
Set_Attribute_Single
Class attributes
# Access Name Type Value Description
1 Get Revision UINT 0x0001 Revision of the object
S1A10387 09/2012 45
Supported CIP objects
Services
Class services Get_Attribute_Single
Instance services Get_Attribute_Single
Set_Attribute_Single
Reset
Class attributes
# Access Name Type Value Description
1 Get Revision UINT 0x0001 Revision of the object
Instance attributes
# Access Name Type Value Description
3 Get/Set Run1 BOOL N/A Run forward
See Run/Stop Event Triggers
4 Get/Set Run2 BOOL N/A Run reverse
See Run/Stop Event Triggers
5 Get/Set NetCtrl BOOL N/A Requests Run/Stop control to be local or from
network.
0 = Local Control
1 = Network Control
6 Get State USINT N/A 1 = Startup
2 = Not_Ready
3 = Ready
4 = Enabled
5 = Stopping
6 = Fault_Strop
7 = Faulted
For ATV312 DRIVECOM status to State translation,
see page 47.
7 Get Running1 BOOL N/A Enabled or Stopping or Fault_Stop
8 Get Running2 BOOL 0 Running2 is always 0 since negative speed indicated
on the Actual speed reference.
9 Get Ready BOOL N/A 1 = Ready or Enabled or Stopping
0 = Other state
10 Get Faulted BOOL N/A 0 = No Faults present
1 = Fault Occurred (latched)
ATV:6041#3
11 Get Warning BOOL N/A 0 = No Warnings present
1 = Warning (not latched)
12 Get/Set FaultRst BOOL N/A 0->1 = Fault Reset
0 = No Action
ATV:6040#7
15 Get CtrlFromNet BOOL N/A Status of Run/Stop control source.
0 = Control is local
1 = Control is from network
46 S1A10387 09/2012
Supported CIP objects
S1A10387 09/2012 47
Supported CIP objects
The following table defines how DRIVECOM commands are generated in the DRIVECOM control word. All other bits are unaffected.
48 S1A10387 09/2012
Supported CIP objects
Services
Class services No services implemented
Instance services Get_Attribute_Single
Set_Attribute_Single
Class attributes
No attributes are implemented at class level.
S1A10387 09/2012 49
Supported CIP objects
Class attributes
# Access Name Type Value Description
1 Get Revision UINT 0x0001 Revision of the object
Instance 1 attributes
# Access Name Type Value Description
1 Get/Set Acknowledge UINT 16 Time to wait for acknowledge (in ms) before
Timer resending
2 Get/Set Retry Limit USINT 1 Number of Ack timeouts before retry limit reached
event
3 Get Producing UINT 4 Connection instance, which contains the path of the
connection producing I/O application object, which will be notified
Instance of Ack Handler events.
50 S1A10387 09/2012
Supported CIP objects
Services
Class services Get_Attribute_Single
Instance services Get_Attribute_Single
Set_Attribute_Single
Class attributes
# Access Name Type Value Description
1 Get Revision UINT 0x0001 Revision of the object
Instance attributes
# Access Name Type Value Description
1 Get/Set Parameter with N/A N/A
Sub-index 0
... ... ... ... ... ...
N Get/Set Parameter with N/A N/A
Sub-index N
S1A10387 09/2012 51
52 S1A10387 09/2012
ATV312_DeviceNet_S1A10387_02
S1A10387 09/2012