Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

PowerFlex 700s Frames 9 A 14

Download as pdf or txt
Download as pdf or txt
You are on page 1of 220
At a glance
Powered by AI
The document discusses important safety information and instructions for installing, operating, and maintaining PowerFlex 700H and 700S AC drives.

Users are required to familiarize themselves with installation and wiring instructions and follow all safety codes and standards. Only trained personnel should install, operate, and maintain the equipment. Hazards such as electric shock, burns, and arc flash are present.

The document lists agency certifications, control and drive ratings, electrical, environmental, and protection specifications for the PowerFlex 700H and 700S drives.

Installation Instructions

PowerFlex 700H Adjustable Frequency AC Drive and PowerFlex 700S High Performance AC Drive
Frames 9...14

Important User Information


Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence. IMPORTANT Identifies information that is critical for successful application and understanding of the product.

Labels may also be on or inside the equipment to provide specific precautions.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures. ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, DriveExplorer, DriveExecutive, DriveTools SP, PowerFlex, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

Summary of Changes
This manual contains new and updated information.

New and Updated Information

This table contains the changes made to this revision.


Topic Added enclosure code H IP54, NEMA/UL Type 12 for PowerFlex 700S drives to the Enclosure options table. Updated the list of manuals in the Additional Resources table. Updated the DC Input Precharge Control Wiring information. Added a new Auto/Manual example when using PowerFlex 700H firmware version 5.004. Removed the chapter on Control Wiring for PowerFlex 700S Drives with Phase I Control Removed the Lifting and Mounting Instructions appendix - updated all references to refer to the appropriate Lifting and Mounting publications shipped with the drives for current information. Updated the recommended cable and wiring diagrams for the Stegmann HiResolution Encoder Feedback Option Card to include new motor/cable combination. Updated the recommended cable and wiring diagrams for the Multi-Device Interface Option Card to include new motor/cable combination. Added Appendix F - History of Changes to contain all previous manual revision information. Page 12 17 26 42

186

196 209

Changes to this manual for previous revisions are included in Appendix F History of Changes on page 209.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Summary of Changes

Notes:

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Table of Contents
Preface
Drive Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Enclosure Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Drive Frame Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Conventions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General Precautions, Continued. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 12 13 14 15 16 17

Chapter 1 General Installation Information


AC Supply Source Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Unbalanced, Ungrounded or Resistive Grounded Distribution Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Single-Phase Input Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input Power Conditioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Power Conditioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General Grounding Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Ground - PE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Shield Termination - SHLD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RFI Filter Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fuses and Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wire Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Motor Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CabIe Trays and Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EMC Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CE Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Low Voltage Directive (2006/95/EC). . . . . . . . . . . . . . . . . . . . . . . . . . EMC Directive (2004/108/EC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Essential Requirements for CE Compliance . . . . . . . . . . . . . . . . . . . . Using Input/Output Contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input Contactor Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Contactor Precaution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Common Bus/Precharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DC Input Precharge Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 19 19 20 20 20 21 21 21 21 22 22 22 23 23 23 23 23 23 24 24 25 25 25 25 26

Chapter 2 Control Wiring for PowerFlex 700H Drives


700H Control Circuit Board Designations . . . . . . . . . . . . . . . . . . . . . I/O Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I/O Cable Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog I/O Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hardware Enable Circuitry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auxiliary Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I/O Wiring Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reference Control Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

32 33 34 36 36 37 37 40
5

Table of Contents

Auto Speed Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Manual Speed Sources. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Changing Speed Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auto/Manual Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PLC = Auto, HIM = Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PLC = Auto, Terminal Block = Manual . . . . . . . . . . . . . . . . . . . . . . . . PLC = Auto, Terminal Block = Manual (HIM Control). . . . . . . . . Auto/Manual Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

40 40 40 41 41 42 42 43

Chapter 3 Control Wiring for PowerFlex 700S Drives with Phase II Control
I/O Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Main Control Board Switch and Jumper Settings . . . . . . . . . . . . . . . . . . . I/O Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring the Main Control Board I/O Terminals. . . . . . . . . . . . . . . . . I/O Wiring Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hardware Enable Circuitry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auxiliary Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Removing the Control Cassette. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 46 48 48 50 53 54 55

Chapter 4 Communication Options


Communication Module Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Communication Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Typical Programmable Controller Configurations . . . . . . . . . . . . . . Logic Command/Status Words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 58 58 58

Chapter 5 Frame 9 Mechanical Installation


Ungrounded, Unbalanced or High Resistive Ground Installations . . . . Minimum Mounting Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating Temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Nameplate Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Lifting Frame 9 Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remove the Drive Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Frame 9 DC Bus/Brake Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . Routing for I/O Wiring and Communication Cabling . . . . . . . . . . . . . . 63 64 64 64 65 66 66 67 68 69

Chapter 6 Frame 10 Mechanical Installation


Minimum Mounting Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating Temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Lifting and Mounting Frame 10 Drives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remove the Protective Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Move the Control Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remove the Airflow Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

71 72 73 76 76 76 77

Table of Contents

Remove the Protective Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 Installation on an Ungrounded Distribution System or High Resistive Ground. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 Installation on a Grounded B Phase Delta System . . . . . . . . . . . . . . . 79 Move the Common Mode Jumper to the Disconnected Position . 81 Insulate Terminal X4 on the Rectifier Circuit Board . . . . . . . . . . . . 82 Disconnect the Small Capacitors from the Input Terminals . . . . . . 83 Power Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

Chapter 7 Frame 11 Mechanical Installation


Minimum Mounting Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Operating Temperatures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 Lifting and Mounting Frame 11 Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Remove the Protective Covers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Move the Control Frame. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Remove the Airflow Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 Remove the Protective Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Installation on an Ungrounded Distribution System or High Resistive Ground. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Installation on a Grounded B Phase Delta System . . . . . . . . . . . . . . . 93 Move the Common Mode Jumper to the Disconnected Position . 95 Insulate Terminal X4 on the Rectifier Circuit Board . . . . . . . . . . . . 96 Power Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 AC Input Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97

Chapter 8 Frame 12 Mechanical Installation


Minimum Mounting Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 Operating Temperatures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103 Lifting and Mounting Frame 12 Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Remove the Protective Covers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 Move the Control Frame. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 Remove the Airflow Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Remove the Protective Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 Installation on an Ungrounded Distribution System or High Resistive Ground. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 Installation on a Grounded B Phase Delta System . . . . . . . . . . . . . . 109 Move the Common Mode Jumper to the Disconnected Position 111 Insulate Terminal X4 on the Rectifier Circuit Board . . . . . . . . . . . 112
Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013 7

Table of Contents

Disconnect the Small Capacitors from the Input Terminals . . . . . Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

113 114 114 116

Chapter 9 Frame 13 Mechanical Installation


Minimum Mounting Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 Operating Temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 Lifting and Mounting Frame 13 Drives. . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 Remove the Protective Covers from the Converter Unit . . . . . . . . . . . . 124 Move the Control Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124 Remove the Protective Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 Installation on an Ungrounded Distribution System or High Resistive Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 Installation on a Grounded B Phase Delta System . . . . . . . . . . . . . . 126 Move the Common Mode Jumper(s) to the Disconnected Position . . 126 Insulate Terminal X4 on the Rectifier Circuit Board. . . . . . . . . . . . 127 Remove the Protective Covers from the Inverter Unit . . . . . . . . . . . . . . 128 Remove the Lower Protective Screen . . . . . . . . . . . . . . . . . . . . . . . . . . 128 Remove the Protective Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129 Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130

Chapter 10 Frame 14 Mechanical Installation


Minimum Mounting Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134 Operating Temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135 Lifting and Mounting Frame 14 Drives. . . . . . . . . . . . . . . . . . . . . . . . . . . . 140 Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141 Remove the Protective Covers from the Converter Unit(s) . . . . . . . . . 142 Remove the Protective Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142 Move the Control Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143 Remove the Airflow Plate(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144 Remove the Protective Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145 Installation on an Ungrounded Distribution System or High Resistive Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146 Installation on a Grounded B Phase Delta System . . . . . . . . . . . . . . 146 Move the Common Mode Jumper(s) to the Disconnected Position . . 147 Insulate Terminal X4 on the Rectifier Circuit Board. . . . . . . . . . . . 148 Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149 Remove the Protective Covers from the Inverter Units . . . . . . . . . . . . . 149
Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Table of Contents

Remove the Protective Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remove the Airflow Plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remove the Protective Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 400 and 690 Volt Class AC Input Wiring for Frame 14 Drives . . Frame 14 Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Circuit Breaker DIP Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . Charging the MCCB Motor Operators . . . . . . . . . . . . . . . . . . . . . . . Closing the Circuit Breakers and Energizing the Drive. . . . . . . . . . Resetting the Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

149 150 151 151 158 159 160 161 162

Appendix A Specifications
Drive Catalog Number Designations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Drive Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Drive Fuse & Circuit Breaker Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fusing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167 167 175 175 175

Appendix B
Option Card Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185 PowerFlex 700S Stegmann HiResolution Encoder Feedback Option Supported Encoders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185 Wiring the Hi-Resolution Feedback Option Card to an Encoder. . . . 186 Recommended Cables and Wiring Diagrams for the Stegmann HiResolution Feedback Option Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . 186

Appendix C PowerFlex 700S Resolver Feedback Option Card


Option Card Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Compatible Resolvers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring the Resolver Feedback Option Card to a Resolver . . . . . . . . . . Recommended Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191 191 192 192

Appendix D PowerFlex 700S Multi-Device Interface (MDI) Option Card


MDI Option Card Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195 Supported Linear Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195 Supported Rotary Encoders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196 Wiring the MDI Option Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196 Recommended Cables and Wiring Diagrams for the MDI Option Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197

Appendix E Instructions for ATEX Approved PowerFlex 700H Drives in Group II Category (2) Applications with ATEX Approved Motors
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Motor Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Drive Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Removing the 20C-DG1 Option Board . . . . . . . . . . . . . . . . . . . . . . . . . . . Verify Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

203 203 204 206 208 208


9

Table of Contents

Appendix F History of Changes Index


PFLEX-IN006D-EN-P, March 2006 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210 PFLEX-IN006C-EN-P, October 2004 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211

10

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Preface

Topic Drive Description Enclosure Options Drive Frame Sizes Conventions General Precautions Additional Resources

Page 11 12 13 13 15 17

This manual provides information on mechanical installation and for connecting incoming power, the motor, and basic I/O to frame 914 PowerFlex 700H and 700S AC drives. The information provided is intended for qualified installers only. Only qualified personnel familiar with adjustable frequency AC drives and associated machinery should plan or implement the installation, start-up and subsequent maintenance of the system.

Drive Description

Frame 914 PowerFlex 700H and 700S AC drives are available in the following normal duty power ratings.
Drive 700H 700S AC Input Range 380500V 525690V 380500V 525690V Hp Range 2001900 1502400 2001250 1501600 kW Range 1321200 1602300 132800 1601500

The 700H features a parameter set modeled after the PowerFlex 700 AC drive. Standard I/O includes either 24V or 115V digital I/O plus analog I/O NetLinx communication options, including DeviceNet, ControlNet and EtherNet/IP networks. The PowerFlex 700S offers optimized integration for the most demanding drive control and drive system applications. Available with embedded highperformance Logix engine (DriveLogix) to produce a highly functional, costeffective drive and control solution.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

11

Preface

Enclosure Options

The following enclosure types are available for PowerFlex 700H and 700S drives:
Drive 700H Enclosure Code A B H J K Enclosure Type Rittal TS 8 Modular MCC Style Rittal TS 8 Modular No enclosure MCC Style NEMA/UL Rating IP21, NEMA/UL Type 1 IP20, NEMA/UL Type 1 IP54, NEMA/UL Type 12(1) IP00, NEMA/UL Type Open IP20, NEMA/UL Type 1 Description Single Door - Freestanding, Light Grey (RAL 7035) Single Door - Freestanding, Rollin, Roll-out power structure Single Door - Freestanding, Filters in Door and Roof Vent With Conformal Coated Circuit Boards Single Door - Freestanding, Rollin, Roll-out power structure, with Conformal Coated Circuit Boards Single Door - Freestanding, Light Grey (RAL 7035), with Conformal Coated Circuit Boards Single Door - Freestanding, Filters in Door and Roof Vent Single Door - Freestanding, Light Grey (RAL 7035) Single Door - Freestanding, Rollin, Roll-out power structure Single Door - Freestanding, Filters in Door and Roof Vent

Rittal TS 8 Modular

IP20, NEMA/UL Type 1

N W 700S A B H N

No enclosure Rittal TS 8 Modular w/Conformal Coat Rittal TS 8 Modular MCC Style Rittal TS 8 Modular No enclosure

IP00, NEMA/UL Type Open IP54, NEMA/UL Type 12 IP21, NEMA/UL Type 1 IP20, NEMA/UL Type 1 IP54, NEMA/UL Type 12(1) IP00, NEMA/UL Type Open

(1) For replacement filters, see the PowerFlex Architecture Class Spare Parts & Options list available at: http://www.ab.com/support/abdrives/powerflex70/PF7ReleasedParts.pdf

12

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Preface

Drive Frame Sizes

Similar PowerFlex 700H and 700S drive sizes are grouped into frame sizes to simplify spare parts ordering, dimensioning, etc. A cross reference of drive catalog numbers and their respective frame size is provided in the following publications. PowerFlex 700H Adjustable Frequency AC Drive Technical Data, publication 20C-TD001 PowerFlex 700S High Performance AC Drive - Phase II Control Technical Data, publication 20D-TD002 You can determine the frame size of your drive by checking the data nameplate on the control frame. The frame number is printed just above the serial number.

X50

Cat No.

20D

300 N 0 NNNBNNNN

UL Open Type/IP00

Cat No.

20D

300 N 0 NNNBNNNN

UL Open Type/IP00

540V 650V 160 kW 250 kW Normal Duty Power 132 kW 200 kW Heavy Duty Power Input: DC, 462 - 594 583 - 713 DC Voltage Range 350 350 Amps Output: 3 Phase, 0 - 320Hz AC Voltage Range 0 - 400 0 - 460 50 Hz 60 Hz Base Hz (default) 300/245 300/245 Continuous Amps 330/368 330/368 1 Min Overload Amps 2 Sec Overload Amps 450/490 450/490
MFD. in 1989 on Nov 9 Frame #: 9

Series: A
Standard I/O: NONE Original Firmware No. 2.04

UL

US

LISTED IND CONT EQ 9D42

Serial Number: 2622381652


MADE IN THE USA (FAC 1B)

2622381652

540V 160 kW Normal Duty Power 132 kW Heavy Duty Power Input: DC, 462 - 594 DC Voltage Range 350 Amps Output: 3 Phase, 0 - 320Hz AC Voltage Range 0 - 400 Base Hz (default) 50 Hz Continuous Amps 300/245 1 Min Overload Amps 330/368 2 Sec Overload Amps 450/490
MFD. in 2006 on Nov 9

650V
250 kW 200 kW 583 - 713 350 0 - 460 60 Hz 300/245 330/368 450/490
Frame #: 9

Series: A
Standard I/O: NONE Original Firmware No. 2.04

UL

US

LISTED IND CONT EQ 9D42

L1

L2

L3

L1

L2

L3

U/T1 V/T2 W/T3 U/T1 V/T2 W/T3

MADE IN THE USA (FAC 1B)

2622381652

Serial Number: 2622381652

Frame Number

Conventions

In this manual we see the PowerFlex 700H or 700S Adjustable Frequency AC Drive as: drive PowerFlex 700H 700H PowerFlex 700S 700S

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

13

Preface

To help differentiate parameter names and LCD display text from other text, the following conventions will be used: Parameter Names will appear in [brackets]. For example: [DC Bus Voltage]. Display Text will appear in quotes. For example: Enabled. The following words are used throughout the manual to describe an action:
Word Can Cannot May Must Shall Should Should Not Meaning Possible, able to do something Not possible, not able to do something Permitted, allowed Unavoidable, you must do this Required and necessary Recommended Not recommended

14

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Preface

General Precautions

ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference A-B publication 8000-4.5.2, Guarding Against Electrostatic Damage or any other applicable ESD protection handbook. ATTENTION: An incorrectly applied or installed drive can result in component damage or a reduction in product life. Wiring or application errors, such as, undersizing the motor, incorrect or inadequate AC supply, or excessive ambient temperatures may result in malfunction of the system. ATTENTION: Only qualified personnel familiar with adjustable frequency AC drives and associated machinery should plan or implement the installation, start-up and subsequent maintenance of the system. Failure to comply may result in personal injury and/or equipment damage. ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged completely before servicing. Check the DC bus voltage at the Power Terminal Block by measuring between the +DC and -DC terminals, between the +DC terminal and the chassis, and between the -DC terminal and the chassis. The voltage must be zero for all three measurements. ATTENTION: Risk of injury or equipment damage exists. DPI host products must not be directly connected together via 1202 cables. Unpredictable behavior can result if two or more devices are connected in this manner. ATTENTION: The sheet metal cover and mounting screws on the ASIC Board located on the power structure are energized at (-) DC bus potential high voltage. Risk of electrical shock, injury, or death exists if someone comes in contact with the assembly.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

15

Preface

General Precautions, Continued

ATTENTION: The adjust freq portion of the bus regulator function is extremely useful for preventing nuisance overvoltage faults resulting from aggressive decelerations, overhauling loads, and eccentric loads. It forces the output frequency to be greater than commanded frequency while the drive's bus voltage is increasing towards levels that would otherwise cause a fault. However, it can also cause either of the following two conditions to occur. 1.) Fast positive changes in input voltage can cause uncommanded positive speed changes. For PowerFlex 700H drives, an OverSpeed Limit fault will occur if the speed reaches [Maximum Speed] + [Overspeed Limit]. If this condition is unacceptable, action should be taken to 1) limit supply voltages within the specification of the drive and, 2) limit fast positive input voltage changes to less than 10%. Without taking such actions, if this operation is unacceptable, the adjust freq portion of the bus regulator function must be disabled (see parameters 161 and 162). For PowerFlex 700S drives, an Abs Overspd Det fault will occur if the speed reaches [Rev Speed Limit] - [Abs OverSpd Lim] or [Fwd Speed Limit] + [Abs OverSpd Lim]. If this condition is unacceptable, action should be taken to 1) limit supply voltages within the specification of the drive and, 2) limit fast positive input voltage changes. Without taking such actions, if this operation is unacceptable, disable the bus regulator by setting parameter 414 [Brake/ Bus Cnfg], bit 3 Bus Reg En to zero (0). 2.) Actual deceleration times can be longer than commanded deceleration times. For PowerFlex 700H drives, a Decel Inhibit fault is generated if the drive stops decelerating altogether. If this condition is unacceptable, the adjust freq portion of the bus regulator must be disabled (see parameters 161 and 162). The Decel Inhibit fault can be disabled by setting parameter 238 [Fault Config 1] bit 6 Decel Inhib to zero (0). For PowerFlex 700S drives, a Vref Decel Fail fault is generated if the drive stops decelerating altogether. If this operation is unacceptable, disable the bus regulator by setting parameter 414 [Brake/Bus Cnfg], bit 3 Bus Reg En to zero (0). This fault cannot be disabled in the PowerFlex 700S. Note: For both drives, installing a properly sized dynamic brake resistor or external dynamic brake will provide equal or better performance in most cases. Important: These faults are not instantaneous. Test results show they can take 212 seconds to occur.

16

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Preface

Additional Resources
Resource

These documents contain additional information concerning related products from Rockwell Automation.
Description Provides general guidelines for installing a Rockwell Automation industrial system. Provides declarations of conformity, certificates, and other certification details. Provides basic information needed to properly wire and ground Pulse Width Modulated (PWM) AC drives. Provides a checklist as a guide in performing preventive maintenance on industrial control and drive system equipment. Provides general guidelines for the application, installation, and maintenance of solidstate control in the form of individual devices or packaged assemblies incorporating solid state components. Provides a simple cross-reference of common schematic/wiring diagram symbols used throughout various parts of the world. Provides an explanation of the causes of Electrostatic Damage, and how you can guard against its effects. Provides detailed drive and option specifications, drive, fuse, and circuit breaker ratings, watts loss information, and derating guidelines. Provides detailed drive and option specifications, drive, fuse, and circuit breaker ratings, watts loss information, and derating guidelines. Provides information needed to start-up, program, and troubleshoot PowerFlex 700S Phase II adjustable frequency AC drives. Provides explanations of PowerFlex 700S drives with Phase II control functions and application programming in detail. Provides information needed to plan, install and configure the DriveGuard Safe Torque Off option for PowerFlex 700S and 700L AC drives. Provides information needed to start-up, program, and troubleshoot the PowerFlex 700H adjustable frequency AC drive. Provides information needed to plan, install and configure the Safe Torque Off option for PowerFlex 700H drives Provides instructions for the installation of PowerFlex 700S and 700H frames 1014, IP00, NEMA/UL Type Open power structures in a customer supplied enclosure(s). Provides troubleshooting and repair information for PowerFlex 700S and 700H frame 9 AC drives. Provides troubleshooting and repair information for PowerFlex 700S and 700H frame 10 AC drives. Provides troubleshooting and repair information for PowerFlex 700S and 700H frame 11 AC drives. Provides troubleshooting and repair information for PowerFlex 700S and 700H frame 12 AC drives. Provides troubleshooting and repair information for PowerFlex 700S and 700H frame 13 AC drives. Provides troubleshooting and repair information for PowerFlex 700S and 700H frame 14 AC drives.

Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Product Certifications website, http://www.ab.com Wiring and Grounding Guidelines for pulse Width Modulated AC Drives, publication DRIVES-IN001 Preventive Maintenance of Industrial Control and Drive System Equipment, publication DRIVES-TD001 Safety Guidelines for the Application, Installation and Maintenance of Solid State Control, publication SGI-1.1 A Global Reference Guide for Reading Schematic Diagrams, publication 100-2.10 Guarding Against Electrostatic Damage, publication 8000-4.5.2 PowerFlex 700H Adjustable Frequency AC Drive Technical Data, publication 20C-TD001 PowerFlex 700S High Performance AC Drive - Phase II Control Technical Data, publication 20D-TD002 PowerFlex 700S with Phase II Control Programming Manual, publication 20D-PM001 PowerFlex Reference Manual, publication PFLEX-RM003 DriveGuard Safe Torque Off Option for PowerFlex 700S Phase II and 700L AC Drives, publication 20D-UM007 PowerFlex 700H Programming Manual, publication 20C-PM001 PowerFlex 700H AC Drive Safe Torque Off Option User Manual, publication 20C-UM001 PowerFlex 700H and 700S IP00 Open Power Structure, Frames 1014 Installation Instructions, publication PFLEX-IN020 PowerFlex 700S and 700H Drives - Frame 9 Hardware Service Manual, publication PFLEXTG001 PowerFlex 700S and 700H Drives - Frame 10 Hardware Service Manual, publication PFLEX-TG002 PowerFlex 700S and 700H Drives - Frame 11 Hardware Service Manual, publication PFLEX-TG003 PowerFlex 700S and 700H Drives - Frame 12 Hardware Service Manual, publication PFLEX-TG004 PowerFlex 700S and 700H Drives - Frame 13 Hardware Service Manual, publication PFLEX-TG005 PowerFlex 700S and 700H Drives - Frame 14 Hardware Service Manual, publication PFLEX-TG006

You can view or download publications at http:/www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

17

Preface

Notes:

18

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter

General Installation Information

AC Supply Source Considerations

Frame 914 PowerFlex 700H and 700S drives are suitable for use on a circuit capable of delivering up to a maximum of 200,000 rms symmetrical amperes, and a maximum of 690 volts. ATTENTION: To guard against personal injury and/or equipment damage caused by improper fusing or circuit breaker selection, use only the recommended line fuses/circuit breakers specified in the drive Technical Data publications. See Additional Resources on page 17 for a list of technical publications for PowerFlex 700H and PowerFlex 700S drives. If a system ground fault monitor (RCD) is to be used, only Type B (adjustable) devices should be used to avoid nuisance tripping.

Unbalanced, Ungrounded or Resistive Grounded Distribution Systems


If phase to ground voltage will exceed 125% of normal or the supply system is ungrounded, see Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001, for more information. ATTENTION: PowerFlex 700H and 700S drives contain protective MOVs and common mode capacitors that are referenced to ground. These devices must be disconnected if the drive is installed on a resistive grounded distribution system or an ungrounded distribution system.

If you are installing a... Frame 9 drive Frame 10 drive Frame 11 drive Frame 12 drive Frame 13 drive Frame 14 drive

see: Ungrounded, Unbalanced or High Resistive Ground Installations on page 63 Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations on page 79 Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations on page 93 Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations on page 109 Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations on page 123 Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations on page 141

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

19

Chapter 1

General Installation Information

Single-Phase Input Power


The PowerFlex 700H and 700S drives are typically used with a three-phase input supply. The drives have been listed by UL to operate on single-phase input power with the requirement that the output current is derated by 80% of the three-phase ratings identified in Table 1 on page 167 through Table 8 on page 174.

Input Power Conditioning


All AC input drives include an internal line reactor. Certain events on the power system supplying a drive can cause component damage or shortened product life. These conditions are: The power system has power factor correction capacitors switched in and out of the system, either by the user or by the power company. The power source has intermittent voltage spikes in excess of 6000 volts. These spikes could be caused by other equipment on the line or by events such as lightning strikes. The power source has frequent interruptions. If any or all of these conditions exist, it is recommended that the user install a minimum amount of impedance between the drive and the source. This impedance could come from the supply transformer itself, the cable between the transformer and drive or an additional transformer or reactor. The impedance can be calculated using the information supplied in the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001.

Output Power Conditioning


Frame 14 drives can be ordered with or without output reactors (du/dt filters). The du/dt filter limits the rate of change of output voltage and the rate of change in the IGBT or output transistor switching event. See the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001, for minimum inductance on installations where du/dt filters are not installed.

20

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

General Installation Information

Chapter 1

General Grounding Requirements

Safety Ground - PE
The drive Safety Ground - PE must be connected to system ground. Ground impedance must conform to the requirements of national and local industrial safety regulations and/or electrical codes. The integrity of all ground connections should be periodically checked. For installations within a cabinet, a single safety ground point or ground bus bar connected directly to building steel should be used. All circuits including the AC input ground conductor should be grounded independently and directly to this point/bar.
Table 1 - Typical Grounding

R (L1) S (L2) T (L3)

U (T1) V (T2) W (T3)

PE

SHLD

Shield Termination - SHLD


The Shield terminal provides a grounding point for the motor cable shield. It must be connected to an earth ground by a separate continuous lead. The motor cable shield should be connected to this terminal on the drive (drive end) and the motor frame (motor end). A shield terminating cable gland may also be used. When shielded cable is used for control and signal wiring, the shield should be grounded at the source end only, not at the drive end.

RFI Filter Grounding


Using an optional RFI filter may result in relatively high ground leakage currents. Therefore, the filter must only be used in installations with grounded AC supply systems and be permanently installed and solidly grounded (bonded) to the building power distribution ground. Ensure that the incoming supply neutral is solidly connected (bonded) to the same building power distribution ground. Grounding must not rely on flexible cables and should not include any form of plug or socket that would permit inadvertent disconnection. Some local codes may require redundant ground connections. The integrity of all connections should be periodically checked. See the instructions supplied with the filter.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

21

Chapter 1

General Installation Information

Fuses and Circuit Breakers

Frame 914 drives can be installed with either input fuses or an input circuit breaker. National and local industrial safety regulations and/or electrical codes may determine additional requirements for these installations. See Fuses and Circuit Breakers listed in Table 9 on page 176 through Table 16 on page 183. ATTENTION: Frame 914 PowerFlex drives do not provide branch short circuit protection. Specifications for recommended fuses to provide protection against short circuits are provided in the Technical Data publications for the drives.

Power Wiring

ATTENTION: National Codes and standards (NEC, VDE, BSI etc.) and local codes outline provisions for safely installing electrical equipment. Installation must comply with specifications regarding wire types, conductor sizes, branch circuit protection and disconnect devices. Failure to do so may result in personal injury and/or equipment damage.
If you are installing... a Frame 9 drive a Frame 10 drive a Frame 11 drive a Frame 12 drive a Frame 13 drive a Frame 14 drive see: Power Wiring on page 67 Power Wiring on page 84 Power Wiring on page 97 Power Wiring on page 114 Power Wiring on page 130 Power Wiring on page 149

Wire Recommendations
Type Power (1)(2) Standard Description Four tinned copper conductors with XLPE insulation. Copper braid/aluminum foil combination shield and tinned copper drain wire. PVC jacket. Min. Insulation Rating 600V, 75 C (167 F)

(1) Control and signal wires should be separated from power wires by at least 0.3 meters (1 foot). (2) The use of shielded wire for AC input power may not be necessary but is always recommended.

22

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

General Installation Information

Chapter 1

Motor Considerations
Due to the operational characteristics of AC variable frequency drives, motors with inverter grade insulation systems designed to meet or exceed NEMA MG1 Part 31.40.4.2 standards for resistance to spikes of 1600 volts are recommended. Guidelines must be followed when using non-inverter grade motors to avoid premature motor failures. Refer to Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001 for recommendations.

Cable Trays and Conduit


If cable trays or large conduits are to be used, see guidelines presented in the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001. ATTENTION: To avoid a possible shock hazard caused by induced voltages, unused wires in the conduit must be grounded at both ends. For the same reason, if a drive sharing a conduit is being serviced or installed, all drives using this conduit should be disabled. This will help minimize the possible shock hazard from cross coupled motor leads.

EMC Instructions

CE Conformity
Conformity with the Low Voltage (LV) Directive and Electromagnetic Compatibility (EMC) Directive has been demonstrated using harmonized European Norm (EN) standards published in the Official Journal of the European Communities. PowerFlex Drives comply with the EN standards listed below when installed according to this manual. CE Declarations of Conformity are available online at: http://www.ab.com/certification/ce/docs.

Low Voltage Directive (2006/95/EC)


EN 61800-5-1 Adjustable speed electrical power drive systems Part 5-1: Safety requirements Electrical, thermal and energy.

EMC Directive (2004/108/EC)


EN 61800-3 Adjustable speed electrical power drive systems Part 3: EMC product standard including specific test methods.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

23

Chapter 1

General Installation Information

General Notes
The motor cable should be kept as short as possible in order to avoid electromagnetic emission as well as capacitive currents. Use of line filters in ungrounded systems is not recommended. PowerFlex drives may cause radio frequency interference if used in a residential or domestic environment. The user is required to take measures to prevent interference, in addition to the essential requirements for CE compliance listed below, if necessary. Conformity of the drive with CE EMC requirements does not guarantee an entire machine or installation complies with CE EMC requirements. Many factors can influence total machine/installation compliance. PowerFlex drives can generate conducted low frequency disturbances (harmonic emissions) on the AC supply system.

Essential Requirements for CE Compliance


Conditions 1-6 listed below must be satisfied for PowerFlex drives to meet the requirements of EN61800-3. 1. Standard PowerFlex 700H or 700S CE compatible Drive. For Frames 10 and up, the drive must also be installed in a suitable Rittal TS 8 (or equivalent) enclosure. 2. Review important precautions/attention statements throughout this manual before installing the drive. 3. Grounding as described on page 21. 4. Output power, control (I/O) and signal wiring must be braided, shielded cable with a coverage of 75% or better, metal conduit or equivalent attenuation. 5. All shielded cables should terminate with the proper shielded connector. 6. Conditions in Table 2.
Table 2 - PowerFlex EN61800-3 EMC Compatibility
Frame Second Environment Restrict Motor Cable to 30 m (98 ft.)

Any Drive and Option

9 10 11 12 13 14

24

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

General Installation Information

Chapter 1

Using Input/Output Contactors

Input Contactor Precautions


ATTENTION: A contactor or other device that routinely disconnects and reapplies the AC line to the drive to start and stop the motor can cause drive hardware damage. The drive is designed to use control input signals that will start and stop the motor. If an input device is used, operation must not exceed one cycle per minute or drive damage will occur. ATTENTION: The drive start/stop/enable control circuitry includes solid state components. If hazards due to accidental contact with moving machinery or unintentional flow of liquid, gas or solids exist, an additional hardwired stop circuit may be required to remove the AC line to the drive. An auxiliary braking method may be required.

Output Contactor Precaution


ATTENTION: To guard against drive damage when using output contactors, the following information must be read and understood. One or more output contactors may be installed between the drive and motor(s) for the purpose of disconnecting or isolating certain motors/loads. If a contactor is opened while the drive is operating, power will be removed from the respective motor, but the drive will continue to produce voltage at the output terminals. In addition, reconnecting a motor to an active drive (by closing the contactor) could produce excessive current that may cause the drive to fault. If any of these conditions are determined to be undesirable or unsafe, an auxiliary contact on the output contactor should be wired to a drive digital input that is programmed as Enable. This will cause the drive to execute a coast-to-stop (cease output) whenever an output contactor is opened.

Common Bus/Precharge

DC input drives do not have an internal precharge circuit. Therefore, the following must be provided. Precharge capability must be provided in the system to guard against possible damage. Disconnect switches must not be used between the input of the drive and a common DC bus without the use of an external precharge device.

IMPORTANT

Precharge circuitry is external to the drive and must be customer supplied.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

25

Chapter 1

General Installation Information

DC Input Precharge Control Wiring


If you are installing a DC input drive with a precharge interlock you must make the following connections on the X50 terminal block from the precharge circuit. See Figure 1 on page 27 for additional wiring information.
Table 3 - Frame 9 - X50 Terminal Block Connections
X50 Terminal Block Terminal 1 2 5 6 Description Charge Relay Contact Charge Relay Contact Precharge Complete Signal (+24V DC) Precharge Complete Signal (Common)

Table 4 - Frames 1014 - X50 Terminal Block Connections


X50 Terminal Block Frame 10, 11 & 13 Terminal 21 23 25 26 12 & 14 Power Structure 1 21 23 25 26 Power Structure 2 21 23 25 26 Charge Relay Contact (Jumper to Power Structure 1 Terminal 23) Charge Relay Contact Precharge Complete Signal (+24V DC) Precharge Complete Signal (Common) Charge Relay Contact Charge Relay Contact (Jumper to Power Structure 2 Terminal 21) Precharge Complete Signal (+24V DC) Precharge Complete Signal (Common) Precharge Circuit Connection Description Charge Relay Contact Charge Relay Contact Precharge Complete Signal (+24V DC) Precharge Complete Signal (Common)

Table 5 - X50 Terminal Block Specifications (All Frame Sizes)


Wire Size Range(1) Maximum 6.0 mm2 (10 AWG) Minimum 1.0 mm2 (18 AWG) Torque Recommended 0.8 Nm (7.0 lbin)

(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.

26

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

General Installation Information

Chapter 1

Figure 1 - Frame 9 Sample Precharge Wiring Diagram


Customer Connections - External Precharge Circuitry is Shown as Dashed Lines Terminal Block on Control Frame Drive Connections

DC+ M 1 2 +24V DC 0V DC

F1

R1 CR2

DC Source 5 6 M F2 R2 CR2 CR1 M Main DC Contactor


Important: For DC Input Only. Do Not Install on DC Input Drives.

Isolated

DCCR1 Pilot Relay

CR2 Precharge

* Refer to Table 6 on page 28 for contact ratings.

Figure 2 - Frames 10, 11 and 13 Sample Precharge Wiring Diagram


Customer Connections - External Precharge Circuitry is Shown as Dashed Lines Terminal Block on Control Frame Drive Connections

X50 M DC+ M 21 23 25 DC Source CR1 Pilot Relay M F2 R2 CR2 M CR2 Precharge DCCR1 M Main DC Contactor
Important: For DC Input Only. Do Not Install on DC Input Drives. * Refer to Table 6 on page 28 for contact ratings.

ASIC Board X15 21 23 25 26 X9 Charge Relay* Precharge Complete

F1

R1 CR2

26

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

27

Chapter 1

General Installation Information

Figure 3 - Frames 12 and 14 Sample Precharge Wiring Diagram


Customer Connections - External Precharge Circuitry is Shown as Dashed Lines Terminal Blocks on Control Frame Drive Connections

PU1 X50 M DC+


21 23

X15 21 Charge 22 23 Relay 25 26 X9 Precharge Complete*

ASIC Board #1

F1

R1 CR2 CR1 M CR2 M CR1

25 26

DC Source

PU2 X50
21

M F2 R2 CR2

DCM

23 25 26

X15 21 Charge 22 23 Relay 25 26 X9 Precharge Complete*

ASIC Board #2

Important: For DC Input Only. Do Not Install on DC Input Drives.

* Refer to Table 6 below for contact ratings.

Table 6 - ASIC Board Charge Relay Contact Ratings


Load Rated load Rated carry current Max. switching voltage Max. switching current Max. switching power Failure rate (reference value) Resistance load (cos = 1) 8 A at 250 VAC: 5 A at 30 VDC 8A 250 VAC; 30 VDC, (400 VAC) AC 8 A; DC 5 A 2,000 VA; 150 W 5 VDC 10 mA (for gold plating 0.35 min.)

28

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

General Installation Information

Chapter 1

Figure 4 - X50 Terminal Block Locations


Frame 9 Frames 1014

X50

X50 Terminal Block

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

29

Chapter 1

General Installation Information

Notes:

30

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter

Control Wiring for PowerFlex 700H Drives

Important points to remember about I/O wiring: Always use copper wire. Wire gauge requirements and recommendations are based on 75 C. Do not reduce wire gauge when using higher temperature wire. Wire with an insulation rating of 600V or greater is recommended. Control and signal wires should be separated from power wires by at least 0.3 meters (1 foot). IMPORTANT Control (I/O) terminals labeled () or Common are not referenced to earth ground and are designed to greatly reduce common mode interference. Grounding these terminals can cause signal noise.

ATTENTION: Inputs must be configured with software and jumpers (see page 36). In addition, configuring an analog input for 020 mA operation and driving it from a voltage source could cause component damage. Verify proper configuration prior to applying input signals. ATTENTION: Hazard of personal injury or equipment damage exists when using bipolar input sources. Noise and drift in sensitive input circuits can cause unpredictable changes in motor speed and direction. Use speed command parameters to help reduce input source sensitivity.
Table 7 - Recommended Control Wire
Type Signal (1)(2) Standard Analog I/O Remote Pot Digital I/O Safety Inputs Homing Input (1)(2) Un-shielded Shielded Wire Type Multi-conductor shielded cable Description 0.750 mm (18AWG), twisted pair, 100% shield with drain. 0.750 mm2 (18AWG), 3 conductor, shielded. Per US NEC or applicable national or local code. 0.750 mm2 (18AWG), 3 conductor, shielded. 300V, 60 C (140 F)
2

Min. Insulation Rating 300V, 7590 C (167194 F)

(1) Control and signal wires must be separated from power wires by at least 0.3 meters (1 foot). (2) If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire may not be necessary, but is always recommended.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

31

Chapter 2

Control Wiring for PowerFlex 700H Drives

700H Control Circuit Board Designations


The PowerFlex 700H control circuit board allows for a variety of I/O boards to be installed depending upon your application. Each option I/O circuit board is described below.
Figure 5 - PowerFlex 700H Control Circuit Board

Slot C

IMPORTANT

The boards identified in the table below can only be installed in the designated slot. Boards and slots are not interchangeable.

Table 8 - Control Board Slot Designations


Slot A Used for Circuit Board . . . 24V DC Digital Input with Analog I/O 115V AC Digital Input with Analog I/O B 24/115V Digital Output 24V DC Digital Gate Disable option(1) C D E (Not Used) (Not Used) DPI Option Board Part No. 20C-DA1-A 20C-DA1-B 20C-DO1 20C-DG1 20C-DPI1

(1) See Appendix E, Instructions for ATEX Approved PowerFlex 700H Drives in Group II Category (2) Applications with ATEX Approved Motors on page 203 and the PowerFlex 700H AC Drive Safe Torque Off Option User Manual, publication 20C-UM001, for more information on installing and configuring the Gate Disable option board.

32

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Control Wiring for PowerFlex 700H Drives

Chapter 2

Drive Catalog Numbers for 700H Control I/O Board Options


The following codes are designated in position 15 of the drive catalog string to indicate the desired combination of 700H I/O option boards supplied with the drive:
Code Board in Slot A A B G N 20C-DA1-A 20C-DA1-B 20C-DA1-A none Board in Slot B 20C-DO1 20C-DO1 20C-DG1 none Board in Slot E 20C-DPI1 20C-DPI1 20C-DPI1 20C-DPI1

Figure 6 - PowerFlex 700H I/O Terminal Blocks and Jumpers

J5 J3 & J4 J1 & J2

2 3 I/O Terminal Blocks and Jumpers

I/O Terminal Blocks


Table 9 - I/O Terminal Block Specifications
No. Name Description Wire Size Range (1) Maximum 1 2 3 Analog I/O Digital Inputs Digital Outputs Analog I/O Signals Digital Input Signals Digital Out Relays 2.5 mm2 (14 AWG) 2.5 mm2 (14 AWG) 2.5 mm2 (14 AWG) Minimum 0.5 mm (22 AWG) 0.5 mm2 (22 AWG) 0.5 mm2 (22 AWG)
2

Torque Maximum 0.2 Nm 1.8 lbin 0.2 Nm 1.8 lbin 0.5 Nm 4.5 lbin Recommended 0.2 Nm 1.8 lbin 0.2 Nm 1.8 lbin 0.5 Nm 4.5 lbin

(1) Maximum/minimum that the terminal block will accept - these are not recommendations.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

33

Chapter 2

Control Wiring for PowerFlex 700H Drives

I/O Cable Grounding


When installing shielded multi-conductor for analog and digital I/O, strip the cable at such a distance from the terminal plug so you can fix the shield to the cable clamp for grounding.

Position the exposed shield so it can fixed to the clamp.

Note: This clamp is not designed for strain relief.

34

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Control Wiring for PowerFlex 700H Drives

Chapter 2

Table 10 - I/O Terminal Designations


No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 Signal Analog Input 1 () (1) Analog Input 1 (+) (1) Analog Input 2 () (1) Analog Input 2 (+) (1) 10V Pot Reference Pot Common (GND) +10V Pot Reference Analog Output 1 (+) Analog Output Common Analog Output 2 (+) Digital Input 1 Digital Input 2 Digital Input 3 Digital Input 4 Digital Input 5 Digital Input 6/Hardware Enable Digital Input Common +24VDC (4) 24V Common (4) Digital Output 1 N.C. (5) Digital Output 1 Common Digital Output 1 N.O. (5) Digital Output 2 N.C. (5) Digital Output 2/3 Com. Digital Output 3 N.O. (5) Fault NOT Fault NOT Run Run Factory Default
(2)

Description Isolated (3), bipolar, differential, 9 bit & sign, 88 k input impedance. A jumper (page 36) selects: 010V, 10V, 020 mA. Default: 010V (Ri =200k), 420 mA (Ri=100 ).

Related Parameter(s) 320327


(2)

10 20

2 k minimum, 10 mA maximum load, 1% accuracy. For (+) and () 10V pot references. 2 k minimum, 10 mA maximum load, 1% accuracy. Bipolar (current out is not bipolar), 9 bit and sign, 2 k minimum load. A 340347 jumper (page 36) selects: 010V, 10V, 020 mA. 115V AC, 50/60 Hz - Opto isolated 361366 Low State: less than 30V AC High State: greater than 40V AC 24V DC - Opto isolated (250V) Low State: less than 5V DC High State: greater than 20V DC 11.2 mA DC Enable: Digital Input 6 is jumper selectable for HW Enable (see page 36). On-Time: < 16.7 ms, Off-Time < 1 ms Allows source or sink operation. Terminals 17, 18 and 19 can also be used to provide backup power to DPI and control devices. Drive supplied logic input power. Common for internal power supply. Max. Resistive Load: 240V AC/30V DC 1200VA, 150 W Max. Current: 5 A, Min. Load: 10 mA Max. Inductive Load: 240V AC/30V DC 840VA, 105 W Max. Current: 3.5 A, Min. Load: 10 mA

Stop - CF Start Auto/Man Speed Sel 1 Speed Sel 2 Speed Sel 3

21

380391

(1) (2) (3) (4) (5)

Important: Input must be configured with a jumper. Drive damage may occur if jumper is not installed properly. See page 36. These inputs/outputs are dependant on a number of parameters (see Related Parameters column in table). Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity. 150 mA maximum load. Not present on 115V versions. Can be used to provide control power from an external 24V source when main power is not applied. See page 36. Contacts in un-powered state. Any relay programmed as Fault or Alarm will energize (pick up) when power is applied to drive and de-energize (drop out) when a fault or alarm exists. Relays selected for other functions will energize only when that condition exists and will de-energize when condition is removed.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

35

Chapter 2

Control Wiring for PowerFlex 700H Drives

Analog I/O Configuration


IMPORTANT Analog I/O must be configured through programming, as well as the jumpers shown below. See the PowerFlex 700H Adjustable Frequency AC Drive Programming Manual, publication 20C-PM001.

See Figure 6 on page 33 for the location of the jumpers indicated in the table below.
Table 11 - I/O Configuration
Signal Analog Inputs Jumper J1 (Analog In 1) J2 (Analog In 2) Setting 020 mA
J1
A B C D

010V
J2
A B C D

10V
J2
A B C D

J1
A B C D

J1
A B C D

J2
A B C D

Analog Outputs

J3 (Analog Out 1) J4 (Analog Out 2)

020 mA
J3
A B C D

010V
J4
A B C D

10V
J4
A B C D

J3
A B C D

J3
A B C D

J4
A B C D

Hardware Enable Circuitry


By default, the user can program a digital input as an Enable input. The status of this input is interpreted by drive software. If the application requires the drive to be disabled without software interpretation, a dedicated hardware enable configuration can be utilized. This is done by removing jumper J5 (see table below) and wiring the enable input to digital input 6. Verify that parameter 366 [Digital In6 Sel] is set to 1-Enable.
Table 12 - Hardware Enable Configuration
Signal Hardware Enable Jumper J5 Setting Hardware Enable Input Programmable (No Hardware Enable)

J5
A B

J5
A B

36

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Control Wiring for PowerFlex 700H Drives

Chapter 2

Auxiliary Power Supply


You may use an auxiliary power supply to keep the 700H control unit energized, when input power is de-energized. This provides back-up power for the control unit and is sufficient for setting parameters. Connect 24V DC power to pin 19 and 24V DC common to pin 20 of the 24V DC version of the I/O card.
Table 13 - Auxiliary Power Supply Specifications
Voltage 24V DC 15% Current (Min) 150 mA Current (Max) 250 mA

If 24V terminals of several drives are connected in parallel, it is recommend that a diode circuit to block current flow in the opposite direction is used. Reverse current flow could damage the control board.
From Auxiliary Power Supply
24V dc Power 24V dc Common

:19

:20

:19

:20

:19

:20

:19

:20

I/O Wiring Examples


Input/Output Potentiometer Unipolar Speed Reference 10k Pot. Recommended (2 k Minimum) Connection Example Required Parameter Changes Set I/O configuration (see Analog I/O Configuration on page 36). Adjust Scaling: Parameters 91 [Speed Ref A Hi] / 92 [Speed Ref A Lo] and 325 [Analog In 2 Hi] / 326 [Analog In 2 Lo] View Results: Parameter 002 [Commanded Speed]

3 4 6 7 6

Joystick Bipolar Speed Reference 10V Input Important: See the Attention statement on page 31 for important information on bipolar wiring.

4 5 7

Set I/O configuration (see Analog I/O Configuration on page 36). Set parameter 190 [Direction Mode] = 1 Bipolar 3 Adjust Scaling: Parameters 91 [Speed Ref A Hi] / 92 6 [Speed Ref A Lo] and 325 [Analog In 2 Hi] / 326 [Analog In 2 Lo] View Results: Parameter 002 [Commanded Speed]

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

37

Chapter 2

Control Wiring for PowerFlex 700H Drives

Input/Output Connection Example Analog Input Bipolar Speed Reference 3 10V Input 4 Important: See the Attention statement on page 31 for important information on bipolar wiring.

Required Parameter Changes Set I/O configuration (see Analog I/O Configuration on page 36). Set parameter 190 [Direction Mode] = 1 Bipolar Adjust Scaling: Parameters 91 [Speed Ref A Hi] / 92 [Speed Ref A Lo] and 325 [Analog In 2 Hi] / 326 [Analog In 2 Lo] View Results: Parameter 002 [Commanded Speed]

Analog Voltage Input Unipolar Speed Reference 0 to +10V Input


3 4

Set I/O configuration (see Analog I/O Configuration on page 36). Configure Input with parameter 320 [Anlg In Config] Adjust Scaling: Parameters 91 [Speed Ref A Hi] / 92 [Speed Ref A Lo] and 325 [Analog In 2 Hi] / 326 [Analog In 2 Lo] View Results: Parameter 002 [Commanded Speed]

Analog Current Input Unipolar Speed Reference 420 mA Input


3 4

Set I/O configuration (see Analog I/O Configuration on page 36). Configure Input for Current: Parameter 320 [Anlg In Config] and add jumper at appropriate terminals Adjust Scaling: Parameters 91 [Speed Ref A Hi] / 92 [Speed Ref A Lo] and 325 [Analog In 2 Hi] / 326 [Analog In 2 Lo] View Results: Parameter 002 [Commanded Speed]

Analog Input, PTC 0-10V Input PTC OT set > 5V PTC OT cleared < 5V PTC Short < 0.2V

Ferrite Bead 1.8k PTC

1 2 6

3.32k Ohm

Analog Output 10V, 420 mA Bipolar +10V Unipolar (shown)


+
8 9

Set I/O configuration (see Analog I/O Configuration on page 36). Configure Analog Input for PTC function: Set parameter 259 [Alarm Config 1] bit 14 PTC Config = Enabled Configure Analog Input for Fault when input goes below 0.2V: Set parameter 324 [Analog In 1 Loss] = 1 Fault Enable Fault: Set parameter 238 [Fault Config 1] bit 7 Motor Therm = Enabled Enable Alarm: Set parameter 259 [Alarm Config 1], bit 11 Motor Therm = Enabled Set I/O configuration (see Analog I/O Configuration on page 36). Configure with Parameter 340 [Anlg Out Config] Select Source Value: Parameter 384 [Digital Out1 Sel] Adjust Scaling: Parameters 343 [Analog Out1 Hi] / 344 [Analog Out1 Lo]

38

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Control Wiring for PowerFlex 700H Drives

Chapter 2

Input/Output 2-Wire Control NonReversing(1) 24V DC internal supply

Connection Example
12

17 19 Stop-Run 20

Required Parameter Changes Disable Digital Input:#1: Parameter 361 [Digital In1 Sel] = 0 Not Used Set Digital Input #2: Parameter 362 [Digital In2 Sel] = 7 Run Set Direction Mode: Parameter 190 [Direction Mode] = 0 Unipolar Set Digital Input:#1: Parameter 361 [Digital In1 Sel] = 8 Run Forward Set Digital Input #2: Parameter 362 [Digital In2 Sel] = 9 Run Reverse

2-Wire Control Reversing(1) External supply (I/O board dependent)

115V/ +24V

Run Fwd. 11 12 Run Rev.

Neutral/ Common

17

3-Wire Control Internal supply

Stop

No Changes Required
11 12

Start 17 19 20

3-Wire Control External supply (I/O Board dependent). Requires 3-wire functions only ([Digital In1 Sel]). Using 2-wire selections will cause a type 2 alarm.

115V/ +24V

No Changes Required
Stop 11 12

Start Neutral/ Common 17

Digital Output Relays shown in powered state with drive faulted. See Table 10 on page 35. Two relays at terminals 2426.

Power Source or 21 22 23 24 25 26 Fault NOT Fault NOT Run Run

Select Source to Activate: Parameters 380 [Digital Out1 Sel] / 384 [Digital Out2 Sel]

Enable Input

Configure with parameter 366 [Digital In6 Sel] For dedicated hardware Enable: Remove Jumper J5 (see page 36)
16

(1) Important: Programming inputs for 2 wire control deactivates all HIM Start buttons unless parameter 192 [Save HIM Ref], bit 1 Manual Mode = 1. This will allow the HIM to control Start and Jog.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

39

Chapter 2

Control Wiring for PowerFlex 700H Drives

Reference Control Sources

Auto Speed Sources


The drive speed command can be obtained from a number of different sources. The source is determined by drive programming and the condition of the Speed Select digital inputs, Auto/Manual digital inputs or reference select bits of a command word. The default source for a command reference (all speed select inputs open) is the selection programmed in parameter 90 [Speed Ref A Sel]. If any of the speed select inputs are closed, the drive will use other parameters as the speed command source.

Manual Speed Sources


The manual source for speed command to the drive is either the HIM requesting manual control or the control terminal block (analog input) if a digital input is programmed to Auto/Manual.

Changing Speed Sources


The selection of the active Speed Reference can be made through digital inputs, DPI command, jog button or Auto/Manual HIM operation.

40

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Control Wiring for PowerFlex 700H Drives

Chapter 2

Figure 7 - Speed Reference Selection Chart(1)


= Default [Digital Inx Select]: Speed Sel 3 2 1 PI Exclusive Mode [PI Configuration]: Bit 0, Excl Mode = 0

Auto Speed Ref Options

Trim

Drive Ref Rslt

Pure Reference

Speed Ref A Sel, Parameter 090 Speed Ref B Sel, Parameter 093 Preset Speed 2, Parameter 102 Preset Speed 3, Parameter 103 Preset Speed 4, Parameter 104 Preset Speed 5, Parameter 105 Preset Speed 6, Parameter 106 Preset Speed 7, Parameter 107 DPI Port Ref 1-6, See Parameter 209

0 0 0 0 1 1 1 1

0 0 1 1 0 0 1 1

0 1 0 1 0 1 0 1

to follower drive for Frequency Reference

Auto

Mod Functions (Skip, Clamp, Direction, etc.) Min/Max Speed Commanded Frequency Acc/Dec Ramp and S Curve Post Ramp to follower drive for Frequency Reference

DPI Command

Manual Speed Ref Options


HIM Requesting Auto/Manual TB Man Ref Sel, Parameter 096 Jog Speed, Parameter 100 Man Digital Input Jog Command [Speed Mode]: 2 "Process Pi" 1 "Slip Comp" 0 "Open Loop"

Speed Adders
PI Output Slip Compensation None

Output Frequency

Auto/Manual Examples

PLC = Auto, HIM = Manual


A process is run by a PLC when in Auto mode and requires manual control from the HIM during set-up. The Auto speed reference is issued by the PLC through a communications module installed in the drive. Since the internal communications is designated as Port 5, [Speed Ref A Sel] is set to DPI Port 5 with the drive running from the Auto source.

Attain Manual Control


Press ALT then Auto/Man on the HIM. When the HIM attains manual control, the drive speed command comes from the HIM speed control keys or analog potentiometer.

Release to Auto Control


Press ALT then Auto/Man on the HIM again. When the HIM releases manual control, the drive speed command returns to the PLC.

(1) To access Preset Speed 1, set parameter 90 or 93 to Preset Speed 1.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

41

Chapter 2

Control Wiring for PowerFlex 700H Drives

PLC = Auto, Terminal Block = Manual


A process is run by a PLC when in Auto mode and requires manual control from an analog potentiometer wired to the drive terminal block. The auto speed reference is issued by the PLC through a communications module installed in the drive. Since the internal communications is designated as Port 5, [Speed Ref A Sel] is set to DPI Port 5 with the drive running from the Auto source. Since the Manual speed reference is issued by an analog input (Analog In 1 or Analog In 2), parameter 96 [TB Man Ref Sel] is set to the same input. To switch between Auto and Manual, parameter 364 [Digital In4 Sel] is set to 18 Auto/ Manual.

Attain Manual Control


Close the digital input. With the input closed, the speed command comes from the pot.

Release to Auto Control


Open the digital input. With the input open, the speed command returns to the PLC.

PLC = Auto, Terminal Block = Manual (HIM Control)


Note: This feature is only available for the 20-HIM-A3 / -A4-C3S / -C5S, Series B and PowerFlex 700H firmware v5.004 or higher. This version of firmware allows you to configure the drive to switch smoothly from a communicated speed reference to local speed reference produced by the Human Interface Module (HIM). When the drive is commanded to switch from the automatic (communicated) speed reference to the manual reference via a digital input, it pre-loads the last value from the communicated reference into the HIM. Then you can then modify the manual reference on the HIM. This avoids a step change in speed that would otherwise occur from the switch.

Example:
Use a communications adapter (like a 20-COMM-C or 20-COMM-E) in DPI port 5 for the primary - automatic speed reference. Use the on-board HIM in DPI port 1 for the secondary - manual speed reference. Wire digital input 4 to switch between automatic and manual references (high for manual, low for automatic). Make the following parameter selections: 90 [Speed Ref A Sel] = 22 DPI Port 5 96 [TB Man Ref Sel] = 18 DPI Port 1 193 [Man Ref Preload] = 1 Enabled 364 [Digital In4 Sel] = 18 Auto/Manual
42 Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Control Wiring for PowerFlex 700H Drives

Chapter 2

When digital input 4 is low, the drive runs in automatic mode, consuming the speed reference from the communications adapter. When digital input 4 goes high the drive takes the last value from the communication adapter and loads it into the HIM. So, the manual speed reference produced by the HIM starts at the last value produced by the communication adapter.

Application Note:
To facilitate a smooth transfer from manual HIM speed reference back to automatic (communicated) speed reference, you will need to execute the following in controller logic: While the drive is in manual mode, the controller will need to continually transfer the speed feedback or output frequency into its speed reference. This will eliminate any disturbance in the speed when the drive goes from manual mode back to automatic mode.

Auto/Manual Notes
Manual control is exclusive. If a HIM or terminal block takes manual control, no other device can take manual control until the controlling device releases manual control. If a HIM has manual control and power is removed from the drive, the drive will return to Auto mode when power is reapplied. Parameter 192 [Save HIM Ref ] can enable manual mode to allow starts and jogs from the HIM in 2-wire mode.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

43

Chapter 2

Control Wiring for PowerFlex 700H Drives

Notes:

44

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter

Control Wiring for PowerFlex 700S Drives with Phase II Control


I/O Wiring
Important points to remember about I/O wiring: Always use tinned copper wire. Wire gauge requirements and recommendations are based on 75 C. Do not reduce wire gauge when using higher temperature wire. Wire with an insulation rating of 600V or greater is recommended. Control and signal wires should be separated from power wires by at least 0.3 meters (1 foot). 4100CCF3 Flex I/O cable for use with DriveLogix is 3 ft. maximum length. IMPORTANT I/O terminals labeled () or Common are not referenced to earth ground and are designed to greatly reduce common mode interference. Grounding these terminals can cause signal noise.

ATTENTION: Hazard of personal injury or equipment damage exists when using bipolar input sources. Noise and drift in sensitive input circuits can cause unpredictable changes in motor speed and direction. Use speed command parameters to help reduce input source sensitivity.
Table 14 - Recommended Control Wire
Type Signal (1)(2) Wire Type Combined Description 0.750 mm2 (18AWG), twisted pair, 100% shield with drain. 0.750 mm2 (18AWG), 3 conductor, shielded. 0.196 mm2 (24AWG) individually shielded pairs. 0.196 mm2 (24AWG) individually shielded pairs. 0.750 mm2 (18AWG) individually shielded pairs. 0.330 mm2 (22AWG), power is 0.500 mm2 (20AWG) individually shielded pairs. 0.196 mm2 (24AWG) individually shielded pairs. 0.750 mm2 (18AWG) individually shielded pairs. 0.750 mm2 (18AWG) individually shielded pairs. Per US NEC or applicable national or local code. 0.750 mm2 (18AWG), 3 conductor, shielded. 300V, 60 C (140 F) Min. Insulation Rating 300V, 7590 C (167194 F)

Standard Analog I/O Remote Pot Encoder/ Pulse I/O <30 m (100 ft) Encoder/ Pulse I/O 30 to 152 m (100 to 500 ft) Encoder/ Pulse I/O 152 to 259 m (500 to 850 ft) Un-shielded Shielded

Signal Power Combined Signal Power Combined Multi-conductor shielded cable

Digital I/O Safety Inputs Homing Input (1)(2)

(1) Control and signal wires must be separated from power wires by at least 0.3 meters (1 foot). (2) If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire may not be necessary, but is always recommended.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

45

Chapter 3

Control Wiring for PowerFlex 700S Drives with Phase II Control

Main Control Board Switch and Jumper Settings

ATTENTION: The switches for Digital Inputs 46 are set to 24V DC at the factory. If you are running a 115V AC input application, the switches must be set as indicated below before applying power to the drive or damage to the main control board may occur.

IMPORTANT

There are two separate values for an encoder

Table 15 - Switch and Jumper Settings


Function Default HW Enable Jumper (P22) pins 2-4 HW Enbl Gate Enable Jumper (P13) Analog Input 1 Analog Input 2 Digital Inputs 4-6 Voltage Digital Input 1 Voltage Digital Input 2 Voltage Encoder Supply Voltage Encoder Signal A Voltage Encoder Signal B Voltage Encoder Signal Z Voltage Function DriveLogix Processor Jumper on pins 15-16 Voltage Voltage 24V DC 24V DC 24V DC 12V DC 12V DC 12V DC 12V DC Switch S1 Switch SHUNT Jumper SHUNT Jumper S5-2 S5-1 S4-1, S4-2 S3-1 S3-2 S2-4 S2-1 S2-2 S2-3 Down RUN Open pins 2-4 HW Enbl No Jmpr Voltage Voltage 115V AC 24V DC 24V DC 12V DC 12V DC 12V DC 12V DC Up PROG Closed pins 1-3 No Enbl Jumper on pins 15-16 Current Current 24V DC 12V DC 12V DC 5V DC 5V DC 5V DC 5V DC Center REMOTE Notes No Jmpr = HW Enbl See Hardware Enable Circuitry on page 53 for configuration. No Jmpr = Gate disable or SafeOff/Second Encoder board is present(1) Change with Power Off Change with Power Off Change with Power Off Change with Power Off Change with Power Off Change with Power Off Typically, set all switches the same

Notes Processor Mode

(1) Refer to publication 20D-UM007, DriveGuard Safe-Off Option for PowerFlex 700S Phase II AC Drives and PowerFlex 700L LiquidCooled AC Drives, for more information on the Safe-Off Option board, or publication, 20D-IN009 Installation Instructions - Second Encoder Option Card for PowerFlex 700S Drives with Phase II Control, for more information on the Second Encoder Option board.

46

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Control Wiring for PowerFlex 700S Drives with Phase II Control

Chapter 3

Figure 1 Main Control Board Switches and Jumpers


SWITCH S1
RUN PROG REMOTE

Down

Up

Center

JUMPER P22
4 2 3 1

= HW Enable

SWITCH S5
SIDE VIEW Up = Open = Off FRONT TOP VIEW

4 2

3 1

= No HW Enable

Down = Closed = On

1 2

JUMPER P13
16

16
= Gate Enabled = Gate Disabled

SWITCH S2
SIDE VIEW Up = Open = Off FRONT TOP VIEW

15

15

Down = Closed = On

1 2

3 4

SWITCH S4 SWITCH S3
SIDE VIEW Up = Open = Off FRONT TOP VIEW Up = Open = Off SIDE VIEW FRONT TOP VIEW

Down = Closed = On Down = Closed = On


1 2

1 2

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

47

Chapter 3

Control Wiring for PowerFlex 700S Drives with Phase II Control

I/O Terminal Blocks

Wiring the Main Control Board I/O Terminals


Terminal blocks TB1 and TB2 contain connection points for all inputs, outputs and standard encoder connections. Both terminal blocks reside on the main control board in the control cassette. See Figure 8 below for locations. Table 17 and Table 18 on page 49 contain detailed descriptions for the terminals on TB1 and TB2. Remove the terminal block plug from the socket and make the appropriate connections. See Removing the Control Cassette on page 55 for instructions on removing the control cassette from the drive. IMPORTANT For NEMA/UL Type 1 applications, all wiring must be routed through the conduit plate on the drive. Route any wires from the expanded cassette to the base cassette and out of the drive.

Reinstall the plug when wiring is complete. The terminal blocks have keys, which make it difficult to insert a terminal plug into the wrong socket.
Table 16 - Control & Encoder Terminal Block Specifications
Name I/O Terminal Blocks Wires Size Range (1) Maximum Minimum Signal & Encoder power 1.5 mm2 0.14 mm2 connections (16 AWG) (28 AWG) Description Torque Maximum 0.25 Nm (2.2 lbin) Recommended 0.22 Nm (1.9 lbin)

(1) Maximum/minimum sizes the terminal block will accept - these are not recommendations.

Figure 8 - Main Control Board I/O Terminal Block Locations

Control Cassette

TB1 Terminals

TB2 Terminals

48

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Control Wiring for PowerFlex 700S Drives with Phase II Control

Chapter 3

Table 17 - TB1 Terminal Descriptions


Terminal
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Signal
Analog Input 1 Comm. Analog Input 1 (+/-) Shield Analog Input 2 Comm. Analog Input 2 (+/-) Analog Input 3 [NTC-] Comm. Analog Input 3 [NTC+] Shield Analog Output 1 (-) Analog Output 1 (+) Analog Output 2 (-) Analog Output 2 (+) +10V Reference Reference Common -10V Reference Encoder A Encoder A (Not) Encoder B Encoder B (Not) Encoder Z Encoder Z (Not) Encoder Reference (+) Encoder Reference (-) Encoder Shield

Factory Default
(Volt) NA (Volt) (Volt) NA (Volt) (Volt) NA NA NA NA NA NA NA NA NA NA NA NA

Description
Bipolar, differential input, +/-10V, 0-20 mA, 13 bit + sign 20 k impedance at Volt; 500 impedance at mA(1) Analog Input shield Bipolar, differential input, +/-10V, 0-20 mA, 13 bit + sign 20 k impedance at Volt; 500 impedance at mA Differential input, 0-10V, 10 bit (for motor control mode FVC2, this is the temperature adaptation input). Analog Output shield Bipolar, differential output, +/-10V, 0-20 mA, 11 bit + sign 2 k minimum load

Related Parameter
800

1 2 3 4 5 6 7 8 9 10 11 12

806 812

832, 833 839, 840

13 14 15 16 17 18 19 20 21 22 23 24

Rating: 20 mA maximum load (Recommend 5 k pot)

Normal current draw per channel: 20 mA

230233

12 or 5V DC power supply for primary encoder interface Rating: 300 mA maximum Connection point for encoder shield

(1) The analog inputs are not isolated. However, the analog inputs can be connected in series when using current mode. Note that at 20 mA the voltage source must be capable of providing 10V DC at the drive terminals for one drive - - 20V DC is required for two drives and 30V DC is required for three drives.

Table 18 - TB2 Terminal Descriptions


Terminal
1 2 3

Signal
24V DC Common (-) 24V DC Source (+) Digital Output 1

Factory Default
NA NA

Description
Drive supplied 24V DC logic input power Rating: 300 mA maximum load 24V DC Open Collector (sinking logic) Rating: Internal Source = 150 mA max. External Source = 750 mA Common for Digital Output 1 & 2 24V DC Open Collector (sinking logic) Rating: Internal Source = 150 mA max. External Source = 750 mA Relay contact output Rating: 115V AC or 24V DC = 2 A max. Inductive/Resistive Common for Digital Inputs 1-3 High speed 12V or 24V DC(1), sinking Load:15 mA at 24V DC

Related Parameter

1 2 3 4 5 6 7 8

816, 847

4 5

Digital Output 1/2 Com Digital Output 2

NA

851, 852

9 10 11 12 13 14 15 16

6 7 8 9 10 11 12 13 14 15 16

Relay Output 3 (NC) Relay Output 3 Com Relay Output 3 (NO) Digital Input 1-3 Com Digital Input 1 Digital Input 2 Digital Input 3 Digital Input 4-6 Com Digital Input 4 Digital Input 5 Digital Input 6

856, 857

NA NA

Load:15 mA at 24V DC sourcing Common for Digital Inputs 4-6 Load: 10 mA at 24V DC sinking/sourcing Load: 7.5 mA at 115V AC Note: The 115 VAC Digital Inputs can withstand 2 mA of leakage current without turning on. If an HW Enable output device has a leakage current greater than 2 mA, a burden resistor is required. A 68.1 K resistor with a 0.5 W rating should be used to keep the 115 VAC output below 2 mA. NA

825 826 827 828 829 830

(1) Digital Inputs 1 and 2 are configured for 12V or 24V DC via DIP switches S3-1 and S3-2, respectively. 24V DC is the default setting.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

49

Chapter 3

Control Wiring for PowerFlex 700S Drives with Phase II Control

I/O Wiring Examples


Input/Output 010V Analog Input Internal Source Connection Example

Table 19 - TB1 Terminals Analog Wiring Examples


Required Parameter Changes No Changes Required

1 2 3 4 5 6 7 8 9 10 11 12

13 14 15 16 17 18 19 20 21 22 23 24

010V Analog Input Bi-Polar

No Changes Required

1 2 3 4 5 6 7 8 9 10 11 12

13 14 15 16 17 18 19 20 21 22 23 24

010V Analog Input External Source

No Changes Required
1 2 3 4 5 6 7 8 9 10 11 12

-Signal or Source Common +Signal Shield / Common -Signal or Source Common +Signal Shield / Common -Signal or Source Common +Signal Shield / Common

Analog Output +/-10V DC Used to drive analog meters displaying speed and current

1 2 3 4 5 6 7 8 9 10 11 12 + +

Using Analog Out 1, -10V to + 10V to meter Motor RPM and direction: Send the data to the Analog Output Par 833 [Anlg Out1 Real] (the destination) linked to Par 71 [Filtered SpdFdbk] (the source) Scale the Output to the source parameter Par 835 [Anlg Out1 Scale] = 175 (Par 4 [Motor NP RPM] = 1750 / 10V) Using Analog Out 2, -10V to + 10V to meter Motor Current: Send the data to the Analog Output Par 840 [Anlg Out2 Real] (the destination) linked to Par 308 [Output Current] (the source) Scale the Output to the source parameter Par 822 [Anlg Out2 Scale] = xx (Par 2 [Motor NP FLA] / 10 V Output)

50

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Control Wiring for PowerFlex 700S Drives with Phase II Control

Chapter 3

Input/Output Connection Example Primary Encoder Interface 13 Internal Supply 14 Supports 5V/12V DC 15 differential encoders with 16 internal power supply.
17

Required Parameter Changes Using Encoder 0 as speed feedback: Par 222 [Motor Fdkbk Sel] = 0 - Encoder 0 (default) Par 232 [Encoder0 PPR] = Pulses/Rev for installed encoder
Encoder A AB BZ Z+ -

Used as primary closed loop speed feedback.

18 19 20 21 22 23 24

Primary Encoder Interface External Supply Used as primary closed loop speed feedback.

13 14 15 16 17 18 19 20 21 22 23 24
Encoder A A-

Using Encoder 0 as speed feedback: Par 222 [Motor Fdkbk Sel] = 0 - Encoder 0 (default) Par 232 [Encoder0 PPR] = Pulses/Rev for installed encoder

B BZ Z+ -

Power +V Common -V Shield

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

51

Chapter 3

Control Wiring for PowerFlex 700S Drives with Phase II Control

Table 20 - TB2 Terminals - Digital Input Wiring Examples


Input/Output Digital Inputs - Used for enable and precharge control. Note: 24V DC supply - supports only on-board digital inputs. Do not use for circuits outside the drive. Note: The factory default for Digital Inputs is 24V. This must be switched in order to use 115V. Connection Example Sourcing Digital Inputs - Internal Power Supply
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Com 24V DC

Required Parameter Changes Sourcing and Sinking Definitions: The digital inputs and digital outputs of the PowerFlex 700S AC drive support Sourcing or Sinking configuration. Typically, digital inputs are sourcing devices and digital outputs are sinking devices. The following definitions apply throughout this section: Sourcing a Digital Input - The digital input common (return) is connected to the power supply common. Applying a positive voltage to the digital input will cause it to activate (pull up). Sinking a Digital Input - The digital input common (return) is connected to the power supply positive voltage. Applying 0V or common to the digital input will cause it to activate (pull down). Sourcing a Digital Output - The digital output common (return) is connected to the power supply common. The device to be controlled by the digital output is connect to the positive voltage and the device common is connected to the digital output. Sinking a Digital Output - The digital output common (return) is connected to the power supply positive voltage. The digital output is connect to the device to be controlled and the device common is connected to the power supply common. Note: Digital Inputs 13 can only be configured as sourcing inputs. Digital Inputs 46 can be configured as sourcing or sinking inputs.

Sourcing Digital Outputs - Internal Power Supply


1 2 3 4 5 6 7 8
Com 24V DC

Sinking Digital Inputs - Internal Power Supply


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Com 24V DC

Sinking Digital Output - Internal Power Supply


1 2 3 4 5 6 7 8
Com 24V DC

52

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Control Wiring for PowerFlex 700S Drives with Phase II Control

Chapter 3

Input/Output Connection Example Digital Inputs Com Sourcing Digital Inputs 1 Internal Power Supply, 2-Wire 24V DC 2 Control, 24V DC
3 4 5 6 7 8 9 10 11 12 13 14 15 16
Run Enable

Required Parameter Changes Set the value of Par 829 [Dig In5 Sel] to a value of 7 - Run Set bit 8 3WireControl of Par 153 [Control Options] to Off (0) for 2wire control. Set Par 168 [Normal Stop Mode] for the desired stopping mode: 0 = Ramp Stop 1 = CurLim Stop 2 = Coast Stop

Digital Inputs Sourcing Digital InputsInternal Power Supply, 3-Wire, 24V DC

1 2 3 4 5 6 7 8

Com 24V DC

9 10 11 12 13 14 15 16
Start Stop Enable

Set the value of Par 829 [Dig In5 Sel] to a value of 14 - Normal Stop Set Par 828 [Dig In4 Sel] to a value of 5 - Start Set Par 168 [Normal Stop Mode] for the desired stopping mode: 0 = Ramp Stop 1 = CurLim Stop 2 = Coast Stop

Hardware Enable Circuitry

By default, Digital Input 6 (Par 830 [Dig In6 Sel]) is configured for hardware enable input. This is for applications requiring the drive to be disabled without software interpretation. With the HW Enable Jumper (Shunt - P22) on the pins closest to the PCB (2 and 4), Digital Input 6 is configured as a dedicated hardware enable. See Figure 1 on page 47 for jumper location. If this configuration is not required, the HW Enable Jumper (Shunt) may be moved to the out board pins (1 and 3), making Digital Input 6 user programmable via Par 830 [Dig In6 Sel].

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

53

Chapter 3

Control Wiring for PowerFlex 700S Drives with Phase II Control

Auxiliary Power Supply

You may use an auxiliary power supply to keep the 700S control assembly energized, when input power is de-energized. This allows the main control board, DriveLogix controller and any feedback option cards to continue operation. Connect auxiliary power to J15 on the fiber optic interface board. You must set parameter 153 [Control Options], bit 17 Aux Pwr Sply to enable this feature. IMPORTANT For drives manufactured prior to June 2006, the voltage feedback board provides the bulk 24 volts for the fiber optic interface board. If the auxiliary power supply (24 volts) is greater than the voltage feedback board (24 volts) then the switch mode power supply on the voltage feedback board will shut down. If the auxiliary power supply has an adjustable voltage, then the voltage should be lowered (23.75). This will allow the voltage feedback board power supply to supply the 24 volts. If the auxiliary power supply cannot be adjusted, then a 500 W resistor needs to be added to the voltage feedback board. In this case, please contact Drives Technical Support for details.

Table 21 - Auxiliary Power Supply Specifications


Voltage 24V DC 5% Current (Min) 3A Power (Min) 75 W

Figure 9 - PowerFlex Fiber Optic Interface Board

J15 Auxiliary Power Connector Pin 1 (24V DC power) Pin 3 (24V DC common)

54

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Control Wiring for PowerFlex 700S Drives with Phase II Control

Chapter 3

Removing the Control Cassette

Follow the steps below to remove the control cassette in order to gain access to the I/O and control terminal blocks. 1. Disconnect any installed communications cables from the control assembly. 2. Disconnect the ribbon cables from the main control board. 3. Loosen the captive screw on the control assembly mounting plate and swing the control assembly mounting plate away from the control frame.

Frame 9

Frames 1014

X50

=
Loosen captive screw and swing mounting plate away from drive.

4. Loosen the two mounting screws on the front of the control assembly and slide the control cassette off the mounting bracket.
Frame 9 shown

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

55

Chapter 3

Control Wiring for PowerFlex 700S Drives with Phase II Control

Notes:

56

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter

Communication Options

Communication Module Locations

Figure 10 - DPI Port Locations


1 The HIM panel opens to allow access to the DPI interface board on back side of panel. To open the panel, remove the screws on left side of the HIM panel and swing open.

Back View

X2

2, 3

X1

4 To drive control (Main Control board on 700S, DPI Interface board on 700H). No. 1 2 3 4 Connector DPI Port 1 DPI Port 2 DPI Port 3 or 2 DPI Port 5 Description HIM connection when installed in the drive. Cable connection for handheld and remote options. Splitter cable connected to DPI Port 2 provides additional port. Cable connection for communications adapter.

Note: DPI Port 4 is not available.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

57

Chapter 4

Communication Options

Communication Configurations

Typical Programmable Controller Configurations


IMPORTANT If block transfers are programmed to continuously write information to the drive, care must be taken to properly format the block transfer. If attribute 10 is selected for the block transfer, values will be written only to RAM and will not be saved by the drive. This is the preferred attribute for continuous transfers. If attribute 9 is selected, each program scan will complete a write to the drives non-volatile memory (EEprom). Since the EEprom has a fixed number of allowed writes, continuous block transfers will quickly damage the EEprom. Do Not assign attribute 9 to continuous block transfers. See the individual communications adapter User Manual for details.

Logic Command/Status Words


Figure 11 - PowerFlex 700H Logic Command Word
Logic Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
x x x x x x

Command
Stop (1) Start (1)(2) Jog Clear Faults Direction

Description
0 = Not Stop 1 = Stop 0 = Not Start 1 = Start 0 = Not Jog 1 = Jog 0 = Not Clear Faults 1 = Clear Faults 00 = No Command 01 = Forward Command 10 = Reverse Command 11 = Hold Present Direction 0 = No Local Control 1 = Local Control 0 = Not Increment 1 = Increment 00 = No Command 01 = Use Accel Time 1 10 = Use Accel Time 2 11 = Use Present Time 00 = No Command 01 = Use Decel Time 1 10 = Use Decel Time 2 11 = Use Present Time 000 = No Command 001 = Ref. 1 (Ref A Select) 010 = Ref. 2 (Ref B Select) 011 = Ref. 3 (Preset 3) 100 = Ref. 4 (Preset 4) 101 = Ref. 5 (Preset 5) 110 = Ref. 6 (Preset 6) 111 = Ref. 7 (Preset 7) 0 = Not Decrement 1 = Decrement

x x x x

Local Control MOP Increment Accel Rate

Decel Rate

Reference Select (3)

MOP Decrement

(1) A 0 = Not Stop condition (logic 0) must first be present before a 1 = Start condition will start the drive. The Start command acts as a momentary Start command. A 1 will start the drive, but returning to 0 will not stop the drive. (2) This Start will not function if a digital input (Pars 361366) is programmed for 2-Wire Control (option 7, 8 or 9). (3) This Reference Select will not function if a digital input (Pars. 361366) is programmed for Speed Sel 1, 2 or 3 (option 15, 16 or 17). Note that Reference Selection is Exclusive Ownership.

58

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Communication Options

Chapter 4

Figure 12 - PowerFlex 700H Logic Status Word


Logic Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Status
x Ready x x x x x x x x x x x Active Command Direction Actual Direction Accel Decel Alarm Fault At Speed Local Control (1)

Description
0 = Not Ready 1 = Ready 0 = Not Active 1 = Active 0 = Reverse 1 = Forward 0 = Reverse 1 = Forward 0 = Not Accelerating 1 = Accelerating 0 = Not Decelerating 1 = Decelerating 0 = No Alarm 1 = Alarm 0 = No Fault 1 = Fault 0 = Not At Reference 1 = At Reference 000 = Port 0 (TB) 001 = Port 1 010 = Port 2 011 = Port 3 100 = Port 4 101 = Port 5 110 = Reserved 111 = No Local 0000 = Ref A Auto 0001 = Ref B Auto 0010 = Preset 2 Auto 0011 = Preset 3 Auto 0100 = Preset 4 Auto 0101 = Preset 5 Auto 0110 = Preset 6 Auto 0111 = Preset 7 Auto 1000 = Term Blk Manual 1001 = DPI 1 Manual 1010 = DPI 2 Manual 1011 = DPI 3 Manual 1100 = DPI 4 Manual 1101 = DPI 5 Manual 1110 = Reserved 1111 = Jog Ref

Reference Source

(1) See Owners for further information.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

59

Chapter 4

Communication Options

Figure 13 - PowerFlex 700S Logic Command Word


Logic Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command
x Normal Stop x x x x x Start (1) Jog 1 Clear Fault(2) Unipolar Direction

Description
0 = Not Normal Stop 1 = Normal Stop 0 = Not Start 1 = Start 0 = Not Jog using [Jog Speed 1] 1 = Jog using [Jog Speed 1] 0 = Not Clear Fault 1 = Clear Fault 00 = No Command 01 = Forward Command 10 = Reverse Command 11 = Hold Direction Control 0 = Not Jog using [Jog Speed 2] 1 = Jog using [Jog Speed 2] 0 = Not Current Limit Stop 1 = Current Limit Stop 0 = Not Coast to Stop 1 = Coast to Stop

x x x x x x x x x

Reserved Jog 2 Current Limit Stop Coast Stop Reserved Reserved Spd Ref Sel0 Spd Ref Sel1 Spd Ref Sel2

Bits 14 0 0 0 0 1 1 1 1

13 0 0 1 1 0 0 1 1

12 0 1 0 1 0 1 0 1

= = = = = = = =

Spd Ref A Spd Ref B Preset 2 Ref. 3 (Preset 3) Ref. 4 (Preset 4) Ref. 5 (Preset 5) Ref. 6 (Preset 6) Ref. 7 (Preset 7)

Reserved

(1) A Not Stop condition (logic bit 0 = 0, logic bit 8 = 0, and logic bit 9 = 0) must first be present before a 1 = Start condition will start the drive. (2) To perform this command, the value must switch from 0 to 1.

60

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Communication Options

Chapter 4

Figure 14 - PowerFlex 700S Logic Status Word


Logic Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Status
x Active x x x x x x x x x x x x x x x

Description

0 = Not Active 1 = Active Running 0 = Not Running 1 = Running Command 0 = Reverse Direction 1 = Forward Actual Direction 0 = Reverse 1 = Forward Accel 0 = Not Accelerating 1 = Accelerating Decel 0 = Not Decelerating 1 = Decelerating Jogging 0 = Not Jogging 1 = Jogging Fault 0 = No Fault 1 = Fault Alarm 0 = No Alarm 1 = Alarm Flash Mode 0 = Not in Flash Mode 1 = In Flash Mode Run Ready 0 = Not Ready to Run 1 = Ready to Run 0 = Not At Limit At Limit (1) 1 = At Limit Tach Loss Sw 0 = Not Tach Loss Sw 1 = Tach Loss Sw At Zero Spd 0 = Not At Zero Speed 1 = At Zero Speed At Setpt Spd 0 = Not At Setpoint Speed 1= At Setpoint Speed Enable 0 = Not Enabled 1 = Enabled

(1) See Parameter 304 [Limit Status] in the PowerFlex 700S Phase II drive for a description of the limit status conditions.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

61

Chapter 4

Communication Options

Notes:

62

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter

Frame 9 Mechanical Installation

Most start-up difficulties are the result of incorrect wiring. Every precaution must be taken to assure that the wiring is done as instructed. All information in Chapter 1 General Installation Information and in this chapter must be read and understood before the actual installation begins. ATTENTION: The following information is merely a guide for proper installation. Rockwell Automation, Inc. cannot assume responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.

Ungrounded, Unbalanced or High Resistive Ground Installations

CE frame 9 drives are equipped with common mode capacitors that are referenced to ground. Operating a CE frame 9 drive on a resistive ground or ungrounded distribution system could result in drive damage. ATTENTION: If you intend to operate a frame 9 drive on a resistive ground or ungrounded distribution system, you must order a non-CE PowerFlex drive.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

63

Chapter 5

Frame 9 Mechanical Installation

Minimum Mounting Clearances

400.0 mm (15.75 in.)

400.0 mm (15.75 in.)

50.0 mm (1.97 in.)

80.0 mm (3.2 in.)

50.0 mm (1.97 in.)

350.0 mm (13.8 in.)

350.0 mm (13.8 in.)

See Figure 15 on page 65 for detailed dimension information.

Operating Temperatures

Frame 9 drives require a minimum of 1300 m3/h (765 cfm) of cooling air.
PowerFlex Drive 700H 700S Voltage Class All 400/480V AC (540/650V DC) 600/690V AC (810/932V DC) Amp Rating All All 170 208 Surrounding Air Temperature Normal Duty Heavy Duty 040 C 050 C (32104 F) (32 to 122 F) 040 C 040 C (32104 F) (32104 F) 040 C 040 C (32104 F) (32104 F) 035 C 040 C (3295 F) (32104 F)

Nameplate Location

See Figure 15 on page 65.

64

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 9 Mechanical Installation

Chapter 5

Dimensions
5.0 (0.20) 14.0 (0.55)

Figure 15 - Frame 9 Dimensions


Dimensions are in millimeters and (inches).
480.0 (18.90) 400.0 (15.75) 240.0 (9.45) 45.0 (1.77) Mounting Holes 9.0 (0.35) 363.3 (14.32) 339.5 (13.37)

Nameplate

Lifting Holes

Wire Way

1150.0 (45.28) 1120.0 (44.09)


Nameplate

Mounting Holes

9.0 (0.35) Lifting Hole 21.0 (0.83) 372.5 (14.67) 292.5 (11.52) 142.5 (5.61) 62.5 (2.46) 245.53 (9.67) 59.0 (2.32) 191.64 (7.54) 100.12 (3.94)

285.0 (11.22)

Detail A Brake Option Top Hat

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

65

Chapter 5

Frame 9 Mechanical Installation

Lifting Frame 9 Drives

See the PowerFlex 700H and 700S Frame 9 Drive Lifting Instructions, publication PFLEX-IN003, for detailed instructions. This instruction sheet is shipped with the drive. When you have completed the instructions in PFLEXIN003, continue with the installation as directed below.

Remove the Drive Covers

Remove the Lower Cover

(8 Screws)

Remove the Upper Cover

L1

L2

L3

L1

L2

L3

U/T1 V/T2 W/T3 U/T1 V/T2 W/T3

(8 Screws)

L1

L2

L3

L1

L2

L3

U/T1 V/T2 W/T3 U/T1 V/T2 W/T3

(3 Screws)

L1

L2

L3

L1

L2

L3

U/T1 V/T2 W/T3 U/T1 V/T2 W/T3

Remove the Conduit Cover

66

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 9 Mechanical Installation

Chapter 5

Power Wiring
No. 1 2 3 4 Name Input Power Terminal Block (2) L1, L2, L3 Output Power Terminal Block (2) U/T1, V/T2, W/T3 SHLD Terminal, PE, Motor Ground DC Bus (3) (2 Terminals; DC, DC+) DC Bus w/Brake (3) (3 Terminals; DC, DC+/R+, R) 5 Cable Clamp for Shield

Table 22 - Power Terminal Specifications


Description Input power Motor connections Terminating point for wiring shields DC input or external brake resistor (Internal Brake option not provided - See Frame 9 DC Bus/ Brake Connections on page 68.) DC input/internal brake Internal Brake option not provided - See Frame 9 DC Bus/ Brake Connections on page 68.) Wire Size Range (1) Maximum Minimum 185.0 mm2 95.0 mm2 (350 MCM) (4/0 AWG) 185.0 mm2 95.0 mm2 (350 MCM) (4/0 AWG) 95.0 mm2 5.0 mm2 (4/0 AWG) (10 AWG) 185.0 mm2 95.0 mm2 (350 MCM) (4/0 AWG) 185.0 mm2 (350 MCM) 95.0 mm2 (4/0 AWG) Torque Recommended 40 Nm (354 lbin) 40 Nm (354 lbin) 22 Nm (195 lbin) 40 Nm (354 lbin) 40 Nm (354 lbin)

(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations. (2) Do Not exceed maximum wire size. Parallel connections may be required. (3) DC terminal and brake lugs can be removed.

Figure 16 - Terminal Locations and Power Terminal Block


4

L1

L2

L3

L1

L2

L3

U/T1 V/T2 W/T3 U/T1 V/T2 W/T3


D C

AC Line Input Power

To Motor Leads

D C + /R + R

2 3 DC-, DC+/R+, R- terminals shown with protective cover removed.


D C D C + /R + R

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

67

Chapter 5

Frame 9 Mechanical Installation

Frame 9 DC Bus/Brake Connections


Figure 17 - Connecting to DC Source Only (No Brake Option Ordered)
DC Source

DC

DC+/ R+

Figure 18 - Connecting to an External Brake Resistor (Brake Option Ordered)


See Table 23 on page 69 for brake resistor sizing information. DB Resistor

DC

DC+/ R+

Figure 19 - Connecting to an External Braking IGBT and Resistor (No Brake Option Ordered)

DB Resistor

Braking IGBT

DC

DC+/ R+

68

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 9 Mechanical Installation

Chapter 5

Table 23 - Frame 9 Brake Resistor Ratings


Input Voltage 400V AC Drive Catalog Number 20DC261 20DC300 480V AC 20DD261 20DD300 600V AC 20DE170 20DE208 690V AC 20DF170 20DF208 ND Rating 132 kW 160 kW 200 HP 250 HP 150 HP 200 HP 160 kW 200 kW Cont. Output (Amps) 261 300 261 300 170 208 170 208 Maximum Brake Current (Amps) 222 222 222 222 157.1 157.1 157.1 157.1 Resistor Nominal (Ohms) 3.3 3.3 3.3 3.3 7 7 7 7

Routing for I/O Wiring and Communication Cabling


Network Communication Cabling

700S
Control Wiring

700H

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

69

Chapter 5

Frame 9 Mechanical Installation

Notes:

70

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter

Frame 10 Mechanical Installation

Most start-up difficulties are the result of incorrect wiring. Every precaution must be taken to assure that the wiring is done as instructed. All information in Chapter 1 General Installation Information and in this chapter must be read and understood before the actual installation begins. ATTENTION: The following information is merely a guide for proper installation. Rockwell Automation, Inc. cannot assume responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.

Minimum Mounting Clearances

Figure 20 - Enclosure Codes: A (NEMA/UL Type 1, IP21), M (NEMA/UL Type 1, IP21 w/Conformal Coat), H (NEMA/UL Type 12, IP54) and W (NEMA/UL Type 12, IP54 w/Conformal Coat)

200 mm (7.87 in.) Min.

Enclosure Code A (NEMA/UL Type 1, IP21) Shown

800 mm (31.50 in.) Min.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

71

Chapter 6

Frame 10 Mechanical Installation

Figure 21 - Enclosure Code B (NEMA/UL Type 1, IP21) and K (NEMA/UL Type 1, IP21 w/Conformal Coat)

200 mm (7.87 in.) Min.

Powerful Performance, Flexible Control.

838 mm (33.0 in.) Min.

Operating Temperatures

Frame 10 drives require a minimum of 2600 m3/h (1530 cfm) of cooling air.
PowerFlex Drive 700H & 700S Voltage Class 400/480V AC (540/650V DC) 600/690V AC (810/932V DC) 600/690V AC (810/932V DC) Amp Rating All 261, 325, 385 416 Surrounding Air Temperature Normal Duty Heavy Duty 040 C 040 C (32104 F) (32104 F) 040 C 040 C (32104 F) (32104 F) 035 C 040 C (3295 F) (32104 F)

72

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 10 Mechanical Installation

Chapter 6

Dimensions

Figure 22 - Enclosure Code A (NEMA/UL Type 1, IP21) and M (NEMA/UL Type 1, IP21 w/Conformal Coat)
Dimensions are in millimeters and (inches). * This dimension is the depth for drives with the optional door-mounted HIM installed.

606.0 (23.85) 534.7 (21.05) 32.3 (1.27)

632.5* (24.90) 605.5 (23.84) 498.0 (19.61)

42.0 (1.65)

Lifting Holes

2275.0 (89.57) 2201.8 (86.68)

2234.0 (87.95)

144.5 (5.7) 73.3 (2.9) Max. 116 (4.5) Gap with Overlapping Plate Removed

439 (17.3)

83 (3.3) Stationary metal front bottom plate Two pieces of soft foam taped to adjacent metal plates Overlapping metal bottom plate (slightly adjustable) Stationary metal back bottom plate

57.2 (2.3) Standard

Wire entry for this enclosure is between two pieces of soft foam. If the adjustable plate is slid back, a gap develops between the foam pieces. Otherwise, the foam acts as a loose gasket around the wires.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

73

Chapter 6

Frame 10 Mechanical Installation

Figure 23 - Enclosure Code B (NEMA/UL Type 1, IP20 MCC) and K (NEMA/UL Type 1, IP20 MCC w/ Conformal Coat)
Dimensions are in millimeters and (inches).

Removeable Lifting Angle


63.5 (2.5)

Powerful Performance, Flexible Control.

2286 (90.0)

635 (25.0) 50.8 (2.0) 533.4 (21.0)

635 (25.0)

241.3 (9.5) 548.6 (21.6)

Area available for conduit routing

43.2 (1.7) 19.0 (0.75)

295.5 (11.75)

295.5 (11.75)

0.625 Dia. - 6 Mounting Holes

74

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 10 Mechanical Installation

Chapter 6

Figure 24 - Enclosure Code H (NEMA/UL Type 12 - IP54) and W (NEMA/UL Type 12 - IP54 w/ Conformal Coat)
Dimensions are in millimeters and (inches).

NEMA/UL Type 12 Roof Assembly w/Filters


478 (19) 198.5 (7.8) 655.04 (25.8) 454 (18)

2403.5 (94.6)

NEMA/UL Type 12 External Filters

606 (24) 144.5 (5.7) 73.3 (2.9) Max. 116 (4.5) Gap with Overlapping Plate Removed 57.2 (2.3) Standard 439 (17.3) 83 (3.3)

Stationary metal front bottom plate Two pieces of soft foam taped to adjacent metal p Overlapping metal bottom plate (slightly adjusta Stationary metal back bottom plate

Wire entry for this enclosure is between two pieces of soft foam. If the adjustable plate is slid back, a gap develops between the foam pieces. Otherwise, the foam acts as a loose gasket around the wires.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

75

Chapter 6

Frame 10 Mechanical Installation

Lifting and Mounting Frame 10 Drives

See the Lifting and Mounting PowerFlex 700S and 700H Drives, Frames 1014, Installation Instructions, publication PFLEX-IN005, for detailed instructions. These instructions are shipped with the drive. When you have completed the instructions in PFLEX-IN005, continue with the installation as directed below.

Remove the Protective Covers

Move the Control Frame


To gain access to the power wiring terminals, airflow plate and protective covers you may need to move the control frame out of the way. If you do not need to move the control frame, continue with Remove the Airflow Plate on page 77.
Task A B Description Loosen the T8 Torx-head screws that secure the control frame to the drive enclosure (remove screws on early frame 10 drives). Swing the control frame out and away from the power structure.

or

Frame 10 drives, from early production runs, have holes instead of slots for these screws. You must completely remove the screws from these drives in order to swing-open the control frame.

76

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 10 Mechanical Installation

Chapter 6

Remove the Airflow Plate


The drive is equipped with a plate, located near the top of the drive enclosure (just above the control frame, if installed), that directs air flow through the drive. You may need to remove this plate in order to access the protective covers and the power terminals. If you do not need to remove the airflow plate, continue with Remove the Protective Covers on page 78.
Task A B Description Remove the T8 Torx-head screws that secure the airflow plate to the drive. Slide the airflow plate off of the drive.

B A

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

77

Chapter 6

Frame 10 Mechanical Installation

Remove the Protective Covers


You must remove the protective covers to gain access to the power structure.
Task A Description Remove the four M5 POZIDRIV screws that secure the top and bottom protective covers to the main front protective cover, then remove the top and bottom protective covers. Note: you only need to remove the top and bottom covers to gain access to the power terminals. You can remove the other covers without removing the top and bottom ones. Remove the four M5 POZIDRIV screws that secure the main front protective cover to the drive, then remove the protective cover. Remove the side protective covers.

B C

C A

78

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 10 Mechanical Installation

Chapter 6

Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations

Frame 10 size drives are equipped with common mode capacitors and capacitors that are connected to the input terminals. To guard against drive damage, these capacitors should be disconnected depending upon the type of ground system on which the drive is installed.

Installation on an Ungrounded Distribution System or High Resistive Ground


If you are installing a 400/480V AC input drive on an ungrounded distribution system or high resistive ground, you: Must move the common mode jumper to the disconnected position - see Move the Common Mode Jumper to the Disconnected Position on page 81. Should insulate terminal X4 on the Rectifier circuit board- see Insulate Terminal X4 on the Rectifier Circuit Board on page 82. Must disconnect the small capacitors from the input terminals - see Disconnect the Small Capacitors from the Input Terminals on page 83. If you are installing a 600/690V AC input drive on an ungrounded distribution system or high resistive ground you: Must move the common mode jumper to the disconnected position - see Move the Common Mode Jumper to the Disconnected Position on page 81. Must insulate terminal X4 on the Rectifier circuit board- see Insulate Terminal X4 on the Rectifier Circuit Board on page 82. Must disconnect the small capacitors from the input terminals - see Disconnect the Small Capacitors from the Input Terminals on page 83.

Installation on a Grounded B Phase Delta System


If you are installing a drive on a grounded B phase Delta system you: Must move the common mode jumper to the disconnected position - see Move the Common Mode Jumper to the Disconnected Position on page 81. Must insulate terminal X4 on the Rectifier circuit board- see Insulate Terminal X4 on the Rectifier Circuit Board on page 82. Must disconnect the small capacitors from the input terminals - see Disconnect the Small Capacitors from the Input Terminals on p age 83. Note: See Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, Installation Instructions, publication DRIVES-IN001, for additional information on an ungrounded distribution system or high resistive ground installation.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

79

Chapter 6

Frame 10 Mechanical Installation

Figure 25 - Common Mode Jumper and Rectifier Circuit Board Location


Common Mode jumper Front View of Assembly

There is one common mode jumper located on the upperright side of the power structure.

Rectifier Circuit Board

Control Frame not shown for clarity only.

80

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 10 Mechanical Installation

Chapter 6

Move the Common Mode Jumper to the Disconnected Position


Follow the steps below to move the common mode jumper to the disconnected position (see Figure 25 on page 80 for jumper location).
Task A B C D Description Loosen the upper screw. Remove the lower screw. Move the jumper to the horizontal position. Install and tighten the screws.

Front View of Power Structure

C B
Rectifier Circuit Board

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

81

Chapter 6

Frame 10 Mechanical Installation

Insulate Terminal X4 on the Rectifier Circuit Board


Follow the steps below to insulate terminal X4 on the rectifier circuit board (see Figure 25 on page 80 for rectifier board location).
Task A B Description Remove the screw from the X4 connection on the rectifier circuit board. Insulate the top and bottom of the X4 connection on the rectifier circuit board.

IMPORTANT

Do not install the screw and washer that was removed from this connection.

Side View of Power Structure

X4 X1
X41

X4 X1
X41

Rectifier Circuit Board

82

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 10 Mechanical Installation

Chapter 6

Disconnect the Small Capacitors from the Input Terminals


Follow the lettered steps below to disconnect the small capacitors from the input terminals. IMPORTANT It is not necessary to remove the power wiring from the terminals in order to insulate the capacitor leads.

Task A B C

Description Remove the screws and lock washers that secure each of the three capacitor supply wires to the input power terminals. Insulate the capacitor leads and leave disconnected. Install and tighten the screws and lock washers only.

IMPORTANT

Do not re-install the capacitor leads.

L1
Input power terminal

L2

L3
Front View of Input Power Terminals

Side View of Input Power Terminals Insulator

B
Capacitor Capacitor lead - leave disconnected

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

83

Chapter 6

Frame 10 Mechanical Installation

Power Wiring

IMPORTANT

Once power wiring has been completed, the protective covers must be reinstalled before energizing the drive. Installation is in reverse order of removal (see Remove the Protective Covers on page 78).

Table 24 - Power Terminal Specifications


No. Name 1 2 3 4 5 Input Power Terminal Block (3) L1, L2, L3 Output Power Terminal Block (3) U/T1, V/T2, W/T3 SHLD Terminal, PE, Motor Ground (3) DC Bus (3) (2 Terminals; DC, DC+) Cable Clamp for Shield Description Input power Motor connections Terminating point for wiring shields DC input or external brake Wire Size Range (1)(2) Maximum Minimum 300 mm2 2.1 mm2 (600 MCM) (14 AWG) 300 mm2 2.1 mm2 (600 MCM) (14 AWG) 300 mm2 2.1 mm2 (600 MCM) (14 AWG) 300 mm2 2.1 mm2 (600 MCM) (14 AWG) Torque Recommended 40 Nm (354 lbin) 40 Nm (354 lbin) 40 Nm (354 lbin) 40 Nm (354 lbin) Terminal Bolt Size (3)(4) M12 M12 M10 M12

(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations. (2) Do Not exceed maximum wire size. Parallel connections may be required. (3) These connections are bus bar type terminations and require the use of lug type connectors. (4) Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.

Figure 26 - Power Terminal Locations

DCDC+

V/T2
DANGER
DC BUS CONDUCTORS AND CAPACITORS OPERATE AT HIGH VOLTAGE. REMOVE POWER AND WAIT 5 MINUTES BEFORE SERVICING

Cat No.

FIELD INSTALLED OPTIONS:


1234567890-* 1234567890-*

U/T1
2

W/T3

L1 L2
1

L3

84

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter

Frame 11 Mechanical Installation

Most start-up difficulties are the result of incorrect wiring. Every precaution must be taken to assure that the wiring is done as instructed. All information in Chapter 1 General Installation Information and in this chapter must be read and understood before the actual installation begins. ATTENTION: The following information is merely a guide for proper installation. Rockwell Automation, Inc. cannot assume responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.

Minimum Mounting Clearances

Figure 27 - Enclosure Codes: A (NEMA/UL Type 1, IP21), M (NEMA/UL Type 1, IP21 w/Conformal Coat), H (NEMA/UL Type 12, IP54) and W (NEMA/UL Type 12, IP54 w/Conformal Coat)

200 mm (7.87 in.) Min.

Enclosure Code A (NEMA/UL Type 1 IP21) shown

800 mm (31.5 in.) Min.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

85

Chapter 7

Frame 11 Mechanical Installation

Figure 28 - Enclosure Code B (NEMA/UL Type 1, IP21) and K (NEMA/UL Type 1, IP21 w/Conformal Coat)
200 mm (7.87 in.) Min.

838 mm (33.0 in.) Min.

Operating Temperatures

Frame 11 drives require a minimum of 3900 m3/h (2295 cfm) of cooling air.
PowerFlex Drive 700H 700S Voltage Class All 400/480V AC (540/650V DC) 600/690V AC (810/932V DC) 600/690V AC (810/932V DC) Amp Rating All All 460, 502 590 Surrounding Air Temperature Normal Duty Heavy Duty 040 C 040 C (32104 F) (32104 F) 040 C 040 C (32104 F) (32104 F) 040 C 040 C (32104 F) (32104 F) 035 C 035 C (3295 F) (3295 F)

86

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 11 Mechanical Installation

Chapter 7

Dimensions

Figure 29 - Enclosure Code A NEMA/UL Type 1 - IP21 and M (NEMA/UL Type 1, IP21 w/Conformal Coat)
Dimensions are in millimeters and (inches).

* This dimension is the depth for drives with the optional door-mounted HIM installed.
797.0 (31.38) 736.0 (28.98) 32.25 (1.27) 621.74* (24.48) 605.5 (23.84) 498.0 (19.61) 42.0 (1.65)

DANGER

2275.0 (89.57) 2205.0 (86.81)

2234.0 (87.95)

144.5 (5.7) 73.3 (2.9) Max. 153.5 (6.0) Gap with Overlapping Plate Removed 57.2 (2.3) Standard

640 (25.2)

83 (3.3)

Stationary metal front bottom plate Two pieces of soft foam taped to adjacent metal plates Overlapping metal bottom plate (slightly adjustable) Stationary metal back bottom plate)

Wire entry for this enclosure is between two pieces of soft foam. If the adjustable plate is slid back, a gap develops between the foam pieces. Otherwise, the foam acts as a loose gasket around the wires.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

87

Chapter 7

Frame 11 Mechanical Installation

Figure 30 - Enclosure Code B (NEMA/UL Type 1, IP20 MCC) and K (NEMA/UL Type 1, IP20 MCC w/ Conformal Coat)
Dimensions are in millimeters and (inches).

Removable Lifting Angle

63.5 (2.5)

2286 (90.0)

889 (35.0) 50.8 (2.0) 241.3 (9.5) 787 (31.0)

635 (25.0)

548.6 (21.6)

Area available for conduit routing

43.2 (1.7)

425.5 (16.75) 19.0 (0.75)

425.5 (16.75)

15.88 (0.625) Dia. - 6 Mounting Holes

88

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 11 Mechanical Installation

Chapter 7

Figure 31 - Enclosure Code H (NEMA/UL Type 12, IP54) and W (NEMA/UL Type 12 - IP54 w/ Conformal Coat)
Dimensions are in millimeters and (inches).

678 (26.7) 213 (8.4)

NEMA/UL Type 12 Roof Assembly (1)

655.04 (25.8) 454 (18.0)

2414.5 (95.0)

NEMA/UL Type 12 External Filters

806 (31.7) 144.5 (5.7) 73.3 (2.9) Max. 153.5 (6.0) Gap with Overlapping Plate Removed 57.2 (2.3) Standard 640 (25.2) 83 (3.3)

Stationary metal front bottom plate Two pieces of soft foam taped to adjacent metal plates Overlapping metal bottom plate (slightly adjustable) Stationary metal back bottom plate)

Wire entry for this enclosure is between two pieces of soft foam. If the adjustable plate is slid back, a gap develops between the foam pieces. Otherwise, the foam acts as a loose gasket around the wires.
(1)

NEMA/UL Type 12/IP54 Roof Assembly is 242 mm (9.5 in.) for frame 11, 400V 730A and 600V, 590A drives. For these drives, the total height of the drive is 2443.5 mm (104.5 in.).

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

89

Chapter 7

Frame 11 Mechanical Installation

Lifting and Mounting Frame 11 Drives

See the Lifting and Mounting PowerFlex 700S and 700H Drives, Frames 1014, Installation Instructions, publication PFLEX-IN005, for detailed instructions. These instructions are shipped with the drive. When you have completed the instructions in PFLEX-IN005, continue with the installation as directed below.

Remove the Protective Covers

Move the Control Frame


To gain access to the power wiring terminals, airflow plate and protective covers you may need to move the control frame out of the way. If you do not need to move the control frame, continue with Remove the Airflow Plate on page 91.
Task A B Description Loosen the T8 Torx-head screws that secure the control frame to the drive enclosure. Swing the control frame out and away from the power structure.

A B

90

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 11 Mechanical Installation

Chapter 7

Remove the Airflow Plate


The drive is equipped with a plate, just above the control frame, that directs air flow through the drive. You may need to remove this plate in order to access the protective covers and the power terminals. If you do not need to remove the airflow plate, continue with Remove the Protective Covers on page 92.
Task A B Description Remove the T8 Torx-head screws that secure the airflow plate to the drive. Slide the airflow plate off of the drive.

B A

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

91

Chapter 7

Frame 11 Mechanical Installation

Remove the Protective Covers


You must remove the protective covers to gain access to the power terminals.
Task A B Description Remove the four M5 POZIDRIV screws that secure the top and bottom protective covers to the main front protective cover, then remove the top and bottom protective covers. Remove the four M5 POZIDRIV screws that secure the main front protective cover to the drive, then remove the protective cover.

B A

A B A

Risk Disc of elec veri onnect tric sho fy Foll DC power, ck and ow bus Ear inst volt wait dea th grouruct age 5 min th. ions befo utes nd requ in man re serv and ired ual icin . befo g. re use .

DA NG

ER

B A

92

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 11 Mechanical Installation

Chapter 7

Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations

Frame 11 size drives are equipped with common mode capacitors. To guard against drive damage, these capacitors should be disconnected depending upon the type of ground system on which the drive is installed.

Installation on an Ungrounded Distribution System or High Resistive Ground


If you are installing a 400/480V AC input drive on an ungrounded distribution system or high resistive ground, you: Must move the common mode jumper to the disconnected position - see Move the Common Mode Jumper to the Disconnected Position on page 95. Should insulate terminal X4 on the Rectifier circuit board- see Insulate Terminal X4 on the Rectifier Circuit Board on page 96. If you are installing a 600/690V AC input drive on an ungrounded distribution system or high resistive ground, you: Must move the common mode jumper to the disconnected position - see Move the Common Mode Jumper to the Disconnected Position on page 95. Must insulate terminal X4 on the Rectifier circuit board- see 96 on page Insulate Terminal X4 on the Rectifier Circuit Board.

Installation on a Grounded B Phase Delta System


If you are installing a drive on a grounded B phase Delta system, you: Must move the common mode jumper to the disconnected position - see Move the Common Mode Jumper to the Disconnected Position on page 95. Must insulate terminal X4 on the Rectifier circuit board- see Insulate Terminal X4 on the Rectifier Circuit Board on page 96. Note: See Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, Installation Instructions, publication DRIVES-IN001, for additional information on an ungrounded distribution system or high resistive ground installation.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

93

Chapter 7

Frame 11 Mechanical Installation

Figure 32 - Common Mode Jumper and Rectifier Circuit Board Location


There is one jumper located on each Rectifying Module. The Rectifying Modules are located on the upper-right side of the center and right side power stack of the drives power structure. Common Mode jumper Front View of Assembly

Rectifier Circuit Board

Control Frame not shown for clarity only

94

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 11 Mechanical Installation

Chapter 7

Move the Common Mode Jumper to the Disconnected Position


Follow the steps below to move the common mode jumper to the disconnected position (see Figure 32 on page 94 for jumper location).
Task A B C D Description Loosen the upper screw. Remove the lower screw. Move the jumper to the horizontal position. Install and tighten the screws.

Front View of Power Structure

C B
Rectifier Circuit Board

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

95

Chapter 7

Frame 11 Mechanical Installation

Insulate Terminal X4 on the Rectifier Circuit Board


Follow the steps below to insulate terminal X4 on the rectifier circuit board (see Figure 32 on page 94 for rectifier board location).
Task A B Description Remove the screw from the X4 connection on the rectifier circuit board. Insulate the top and bottom of the X4 connection on the rectifier circuit board.

IMPORTANT

Do not install the screw and washer that was removed from this connection.

Side View of Power Structure

X4 X1
X41

X4 X1
X41

Rectifier Circuit Board

96

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 11 Mechanical Installation

Chapter 7

Power Wiring

AC Input Wiring
The table below identifies which frame 11 drives contain only one rectifying module and which frame 11 drives contain two rectifying modules. Drives with one rectifying module contain only one set of input power terminals. Drives with two parallel rectifying modules contain two sets of input power terminals--you must supply power to both sets of input terminals on these drives. There are several methods for accomplishing this. Each of these methods is shown below.
Voltage Class 400/480V AC Input Amps 590 650 730 460 502 590 Number of Rectifiers 2 2 2 1 1 2

600/690V AC Input

IMPORTANT

Parallel wiring must have the same cable dimensions, type and routing. Nonsymmetrical wiring may cause unequal loading between the converters and reduce the drives ability to deliver current to the motor.

Figure 33 - AC Wiring Example: Two Fuses per Phase

L1

L2

L3

AC Input Power Wiring, Fuses, and Disconnect Device Provided by Customer

1L1

1L2

1L3

2L1

2L2

2L3

AC Input Power Terminals Inside Drive

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

97

Chapter 7

Frame 11 Mechanical Installation

Figure 34 - AC Wiring Example: One Fuse per Phase

L1

L2

L3

1L1

1L2

1L3

2L1

2L2

2L3

Figure 35 - AC Wiring Example: Circuit Breaker

L1

L2

L3

1L1

1L2

1L3

2L1

2L2

2L3

IMPORTANT

Once power wiring has been completed, the protective covers must be installed before energizing the drive. Installation is in reverse order of removal (see Remove the Protective Covers on page 90).

98

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 11 Mechanical Installation

Chapter 7

Table 25 - Power Terminal Specifications


No. Name 1 2 3 4 5 Input Power Terminal Block (3) 1L1, 1L2, 1L3, 2L1, 2L2, 2L3 Output Power Terminal Block (3) U/T1, V/T2, W/T3 SHLD Terminal, PE, Motor Ground (3) DC Bus (3) (2 Terminals; DC, DC+) Cable Clamp for Shield Description AC Input power Motor connections Terminating point for wiring shields DC input or external brake Wire Size Range (1)(2) Maximum Minimum 300 mm2 2.1 mm2 (600 MCM) (14 AWG) 300 mm2 2.1 mm2 (600 MCM) (14 AWG) 300 mm2 2.1 mm2 (600 MCM) (14 AWG) 300 mm2 2.1 mm2 (600 MCM) (14 AWG) Torque Recommended 40 Nm (354 lbin) 40 Nm (354 lbin) 40 Nm (354 lbin) 40 Nm (354 lbin) Terminal Bolt Size (3)(4) M12 M12 M10 M12

(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations. (2) Do Not exceed maximum wire size. Parallel connections may be required. (3) These connections are bus bar type terminations and require the use of lug type connectors. (4) Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.

Figure 36 - Power Terminal Locations


4

DC+ DC-

2 3

U/T1

V/T2

W/T3

1L1 1L2

1L3

2L1 2L2

2L3

1 Note: 600V AC input, 460A and 502A frame 11 drives only have one set of Input Power Terminals.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

99

Chapter 7

Frame 11 Mechanical Installation

Notes:

100

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter

Frame 12 Mechanical Installation

Most start-up difficulties are the result of incorrect wiring. Every precaution must be taken to assure that the wiring is done as instructed. All information in Chapter 1 General Installation Information and in this chapter must be read and understood before the actual installation begins. ATTENTION: The following information is merely a guide for proper installation. Rockwell Automation, Inc. cannot assume responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.

Minimum Mounting Clearances

Figure 37 - Enclosure Codes A (NEMA/UL Type 1, IP21), M (NEMA/UL Type 1, IP21 w/Conformal Coat), H (NEMA/UL Type 12, IP54) and W (NEMA/UL Type 12, IP54 w/Conformal Coat)

200 mm (8.00 in.) Min.

Enclosure Code A (NEMA/UL Type 1, IP21) Shown

800 mm (31.5 in.) Min.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

101

Chapter 8

Frame 12 Mechanical Installation

Figure 38 - Enclosure Code B (NEMA/UL Type 1, IP21) and K (NEMA/UL Type 1, IP21 w/Conformal Coat)
200 mm (8.0 in.) Min.

Powerful Performance, Flexible Control.

Powerful Performance, Flexible Control.

838 mm (33.0 in.) Min.

Operating Temperatures

Frame 12 drives require a minimum of 5200 m3/h (3060 cfm) of cooling air.
PowerFlex Drive 700H Voltage Class 400/480V AC (540/650V DC) 400/480V AC (540/650V DC) 600/690V AC (810/932V DC) 600/690V AC (810/932V DC) 400/480V AC (540/650V DC) 400/480V AC (540/650V DC) 600/690V AC (810/932V DC) 600/690V AC (810/932V DC) Amp Rating 820, 920 1030 820, 920 1030 820, 920 1030 820, 920 1030 Surrounding Air Temperature Normal Duty Heavy Duty 040 C (32104 F) 040 C (32104 F) 040 C (32104 F) 040 C (32104 F) 035 C (3295 F 040 C (32104 F) 040 C (32104 F) 040 C (32104 F) 035 C (3295 F 035 C (3295 F) 040 C (32104 F) 040 C (32104 F) 040 C (32104 F) 035 C (3295 F 040 C (32104 F) 035 C (3295 F

700S

102

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 12 Mechanical Installation

Chapter 8

Dimensions

Figure 39 - Enclosure Code A (NEMA/UL Type 1 - IP21) and M (NEMA/UL Type 1, IP21 w/Conformal Coat)
Dimensions are in millimeters and (inches).

* This dimension is the depth for drives with the optional door-mounted HIM installed.
632.5* (24.90) 605.5 (23.84) 32.3 (1.27) 498.0 (19.61) 42.0 (1.65)

1205.05 (47.45) 534.7 (21.05)

2275.0 (89.57) 2202.75 (86.72)

2234.0 (87.95)

87.9 (3.5)
144.5 (5.7) 73.3 (2.9) Max. 116 (4.5) Gap with Overlapping Plate Removed 439 (17.3)

57.2 (2.3) Standard

Stationary metal front bottom plate Two pieces of soft foam taped to adjacent metal plates Overlapping metal bottom plate (slightly adjustable) Stationary metal back bottom plate

Wire entry for this enclosure is between two pieces of soft foam. If the adjustable plate is slid back, a gap develops between the foam pieces. Otherwise, the foam acts as a loose gasket around the wires.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

103

Chapter 8

Frame 12 Mechanical Installation

Figure 40 - Enclosure Code B (NEMA/UL Type 1, IP21) and K (NEMA/UL Type 1, IP21 w/Conformal Coat)
Dimensions are in millimeters and (inches).

Removeable Lifting Angle 63.5 (2.5)

Powerful Performance, Flexible Control.

Powerful Performance, Flexible Control.

2286 (90.0)

635 (25.0) 1270 (50.0) 50.8 (2.0)

635 (25.0)

635 (25.0)

533.4 (21.0)

241.3 (9.5) 548.6 (21.6) Area available for conduit routing

43.2 (1.7) 19.0 (0.75)

295.5 (11.75)

295.5 (11.75)

15.88 (0.625) Dia. - 6 Mounting Holes

104

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 12 Mechanical Installation

Chapter 8

Figure 41 - Enclosure Code H (NEMA/UL Type 12, IP54) and W (NEMA/UL Type 12, IP54 w/Conformal Coat)
Dimensions are in millimeters and (inches).

478 (18.8)

(4.8)

478 (18.8)

NEMA/UL Type 12 Roof Assembly

655.04 (25.8)

454 (17.9)

198.5(7.8)

2403.5 (94.6)

NEMA/UL Type 12 External Filters

144.5 (5.7) 73.3 (2.9) Max. 116 (4.5) Gap with Overlapping Plate Removed

87.9 (3.5)

1205.05

439 (17.3)
Stationary metal front bottom plate Two pieces of soft foam taped to adjacent metal plates Overlapping metal bottom plate (slightly adjustable) Stationary metal back bottom plate

57.2 (2.3) Standard

Wire entry for this enclosure is between two pieces of soft foam. If the adjustable plate is slid back, a gap develops between the foam pieces. Otherwise, the foam acts as a loose gasket around the wires.

Lifting and Mounting Frame 12 Drives

See the Lifting and Mounting PowerFlex 700S and 700H Drives, Frames 1014, Installation Instructions, publication PFLEX-IN005, for detailed instructions. These instructions are shipped with the drive. When you have completed the instructions in PFLEX-IN005, continue with the installation as directed below.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

105

Chapter 8

Frame 12 Mechanical Installation

Remove the Protective Covers

Move the Control Frame


To gain access to the power wiring terminals, airflow plate and protective covers you may need to move the control frame out of the way. If you do not need to move the control frame, continue with Remove the Airflow Plate on page 107.
Task A B Description Loosen the T8 Torx-head screws that secure the control frame to the drive enclosure (Remove screws on early frame 10 drives). Swing the control frame out and away from the power structure.

106

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 12 Mechanical Installation

Chapter 8

Remove the Airflow Plate


The drive is equipped with a plate, just above the control frame, that directs air flow through the drive. You may need to remove this plate in order to access the protective covers and the power terminals. If you do not need to remove the airflow plate, continue with Remove the Protective Covers on page 108.
Task A B Description Remove the T8 Torx-head screws that secure the airflow plate to the drive. Slide the airflow plate off of the drive.

B A

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

107

Chapter 8

Frame 12 Mechanical Installation

Remove the Protective Covers


You must remove the protective covers to gain access to the power structure.
Task A Description Remove the four M5 POZIDRIV screws that secure the top and bottom protective covers to the main front protective cover, then remove the top and bottom protective covers. Note: you only need to remove the top and bottom covers to gain access to the power terminals. You can remove the other covers without removing the top and bottom ones. Remove the four M5 POZIDRIV screws that secure the main front protective cover to the drive, then remove the protective cover. Remove the side protective covers.

B C

C A

108

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 12 Mechanical Installation

Chapter 8

Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations

Frame 12 size drives are equipped with common mode capacitors and capacitors that are connected to the input terminals. To guard against drive damage, these capacitors should be disconnected depending upon the type of ground system on which the drive is installed.

Installation on an Ungrounded Distribution System or High Resistive Ground


If you are installing a 400/480V AC input drive on an ungrounded distribution system or high resistive ground, you: Must move the common mode jumper to the disconnected position - see Move the Common Mode Jumper to the Disconnected Position on page 111. Should insulate terminal X4 on the Rectifier circuit board- see Insulate Terminal X4 on the Rectifier Circuit Board on page 112. Must disconnect the small capacitors from the input terminals - see Disconnect the Small Capacitors from the Input Terminals on page 113. If you are installing a 600/690V AC input drive on an ungrounded distribution system or high resistive ground, you: Must move the common mode jumper to the disconnected position - see Move the Common Mode Jumper to the Disconnected Position on page 111. Must insulate terminal X4 on the Rectifier circuit board- see Insulate Terminal X4 on the Rectifier Circuit Board on page 112. Must disconnect the small capacitors from the input terminals - see Disconnect the Small Capacitors from the Input Terminals on page 113.

Installation on a Grounded B Phase Delta System


If you are installing a drive on a grounded B phase Delta system, you: Must move the common mode jumper to the disconnected position - see Move the Common Mode Jumper to the Disconnected Position on page 111. Must insulate terminal X4 on the Rectifier circuit board- see Insulate Terminal X4 on the Rectifier Circuit Board on page 112. Must disconnect the small capacitors from the input terminals - see Disconnect the Small Capacitors from the Input Terminals on page 113. Note: See Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, Installation Instructions, publication DRIVES-IN001, for additional information on an ungrounded distribution system or high resistive ground installation.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

109

Chapter 8

Frame 12 Mechanical Installation

Figure 42 - Common Mode Jumper and Rectifier Circuit Board Location


Common Mode jumper There is one jumper located on each Rectifying Module. The Rectifying Modules are located on the upper-right side of the right side power stack of in each enclosure of the drives power structure. Front View of Assembly

Rectifier Circuit Board


DANGER
DC BUS CONDUCTORS AND CAPACITORS OPERATE AT HIGH VOLTAGE. REMOVE POWER AND WAIT 5 MINUTES BEFORE SERVICING

DANGER
DC BUS CONDUCTORS AND CAPACITORS OPERATE AT HIGH VOLTAGE. REMOVE POWER AND WAIT 5 MINUTES BEFORE SERVICING

Control Frame not shown for clarity only

110

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 12 Mechanical Installation

Chapter 8

Move the Common Mode Jumper to the Disconnected Position


Follow the steps below to move the common mode jumper to the disconnected position (see Figure 42 on page 110 for jumper location).
Task A B C D Description Loosen the upper screw. Remove the lower screw. Move the jumper to the horizontal position. Install and tighten the screws.

Front View of Power Structure

C B
Rectifier Circuit Board

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

111

Chapter 8

Frame 12 Mechanical Installation

Insulate Terminal X4 on the Rectifier Circuit Board


Follow the steps below to insulate terminal X4 on the rectifier circuit board (see Figure 42 on page 110 for rectifier board location).
Task A B Description Remove the screw from the X4 connection on the rectifier circuit board. Insulate the top and bottom of the X4 connection on the rectifier circuit board.

IMPORTANT

Do not install the screw and washer that was removed from this connection.

Side View of Power Structure

X4 X1
X41

X4 X1
X41

Rectifier Circuit Board

112

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 12 Mechanical Installation

Chapter 8

Disconnect the Small Capacitors from the Input Terminals


Follow the steps below to disconnect the small capacitors from the input terminals. IMPORTANT It is not necessary to remove the power wiring from the terminals in order to insulate the capacitor leads.

Task A B C

Description Remove the screws and lock washers that secure each of the three capacitor supply wires to the input power terminals. Insulate the capacitor leads and leave disconnected. Install and tighten the screws and lock washers only.

IMPORTANT

Do not re-install the capacitor leads.

L1
Input power terminal

L2

L3
Front View of Input Power Terminals

Side View of Input Power Terminals Insulator

B
Capacitor Capacitor lead - leave disconnected

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

113

Chapter 8

Frame 12 Mechanical Installation

Power Wiring

Input Power Wiring


Frame 12 drives utilize two parallel power structures, and therefore have two sets of AC input power terminals. You must supply power to both sets of input terminals. There are several methods for accomplishing this. IMPORTANT Parallel wiring must have the same cable dimensions, type and routing. Nonsymmetrical wiring may cause unequal loading between the converters and reduce the drives ability to deliver current to the motor.

For applications that require that the DC and DC+ terminals for PowerFlex 700S or 700H frame 12 drives be connected in common (for example, 12 pulse applications, or when using a dynamic brake), you must purchase and install the frame 12 DC Bus Connector kit, which is sold separately from the drive. See the PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit, Installation Instructions, publication PFLEX-IN022.
Figure 43 - Frame 12 AC Wiring Example: Two Fuses per Phase

L1

L2

L3

AC Input Power Wiring, Fuses, and Disconnect Device Provided by Customer

1L1

1L2

1L3

2L1

2L2

2L3

AC Input Power Terminals Inside Drive

114

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 12 Mechanical Installation

Chapter 8

Figure 44 - Frame 12 AC Wiring Example: One Fuse per Phase

L1

L2

L3

1L1

1L2

1L3

2L1

2L2

2L3

Figure 45 - Frame 12 AC Wiring Example: Circuit Breaker

L1

L2

L3

1L1

1L2

1L3

2L1

2L2

2L3

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

115

Chapter 8

Frame 12 Mechanical Installation

Output Power Wiring


Frame 12 drives utilize two parallel power structures, and therefore have two sets of output power terminals. You must connect the motor to both sets of output power terminals. IMPORTANT Parallel wiring must have the same cable dimensions, type and routing. Nonsymmetrical wiring may cause unequal loading between the converters and reduce the drives ability to deliver current to the motor. The minimum cable length for parallel motor cables from the drive to the point where the cables connect is 5 m (16.4 ft). Join the parallel cables at the motor end (not the drive end). Or, install a reactor on the output of each power module with a minimum of 5 H prior to joining the parallel cables at the motor end.

IMPORTANT

Figure 46 - Frame 12 Motor Wiring Example

1T1

1T2

1T3

PE

2T1

2T2

2T3

PE

5m minimum

Motor Motor Frame

IMPORTANT

Once power wiring has been completed, the protective covers must be installed before energizing the drive. Installation is in reverse order of removal (see Remove the Protective Covers on page 106).

116

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 12 Mechanical Installation

Chapter 8

Table 26 - Power Terminal Specifications


No. Name 1 2 3 4 5
(1) (2) (3) (4)

Description Input power Motor connections Terminating point for wiring shields DC input or external brake

Input Power Terminal Block (3) 1L1, 1L2, 1L3, 2L1, 2L2, 2L3 Output Power Terminal Block ((3) 1U/1T1, 1V/1T2, 1W/1T3, 2U/2T1, 2V/2T2, 2W/2T3 SHLD Terminal, PE, Motor Ground (3) DC Bus (3) (2 Terminals; DC, DC+) Cable Clamp for Shield

Wire Size Range (1)(2) Maximum Minimum 300 mm2 2.1 mm2 (600 MCM) (14 AWG) 300 mm2 2.1 mm2 (600 MCM) (14 AWG) 300 mm2 (600 MCM) 300 mm2 (600 MCM) 2.1 mm2 (14 AWG) 2.1 mm2 (14 AWG)

Torque Recommended 40 Nm (354 lbin) 40 Nm (354 lbin) 40 Nm (354 lbin) 40 Nm (354 lbin)

Terminal Bolt Size (3)(4) M12 M12 M10 M12

Maximum/minimum sizes that the terminal block will accept - these are not recommendations. Do Not exceed maximum wire size. Parallel connections may be required. These connections are bus bar type terminations and require the use of lug type connectors. Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.

Figure 47 - Power Terminal Locations

DC- DC+ 1V/T2


DANGER
DC BUS CONDUCTORS AND CAPACITORS OPERATE AT HIGH VOLTAGE. REMOVE POWER AND WAIT 5 MINUTES BEFORE SERVICING
Cat No.

DC- DC+
FIELD INSTALLED OPTIONS:
1234567890-*

2V/T2
DANGER
DC BUS CONDUCTORS AND CAPACITORS OPERATE AT HIGH VOLTAGE. REMOVE POWER AND WAIT 5 MINUTES BEFORE SERVICING

1U/T1
2

1W/T3

2U/T1

2W/T3
2

1L1 1L2 1L3

2L1 2L2 1 2L3

Enclosure Style A Shown 3

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

117

Chapter 8

Frame 12 Mechanical Installation

Notes:

118

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter

Frame 13 Mechanical Installation

Most start-up difficulties are the result of incorrect wiring. Every precaution must be taken to assure that the wiring is done as instructed. All information in Chapter 1 General Installation Information and in this chapter must be read and understood before the actual installation begins. ATTENTION: The following information is merely a guide for proper installation. Rockwell Automation, Inc. cannot assume responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

119

Chapter 9

Frame 13 Mechanical Installation

Minimum Mounting Clearances


200 mm (8.0 in.) Min.

800 mm (31.50 in.) Min.

1600 mm, Style A Enclosure Shown.

Operating Temperatures

Frame 13 drives require a minimum of 4200 m3/h (2472 cfm) of cooling air for the inverter unit and 1150 m3/h (677 cfm) of cooling air for each converter unit.
PowerFlex Drive 700H 700S Voltage Class All 400/480V AC (540/650V DC) 600/690V AC (810/932V DC) 600/690V AC (810/932V DC) Amp Rating All All 920, 1030 1180 Surrounding Air Temperature Normal Duty Heavy Duty 040 C (32104 F) 040 C (32104 F) 040 C (32104 F) 040 C (32104 F) 040 C (32104 F) 035 C (3295 F) 040 C (32104 F) 035 C (3295 F)

120

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 13 Mechanical Installation

Chapter 9

Dimensions

Figure 48 - Enclosure Code A (NEMA/UL Type 1, IP21) and M (NEMA/UL Type 1, IP21 w/Conformal Coat)

A B C

619.2 (24.4) 603 (23.7) 44 (1.73)

2275 (89.6) 2197 (86.5) 2231 (87.8)

1108.25 (43.6)

D
65 (2.6)

535 (21.1)

Stationary metal front bottom plate Two pieces of soft foam taped to adjacent metal plates Overlapping metal bottom plate (slightly adjustable) Stationary metal back bottom plate

Wire entry for this enclosure is between two pieces of soft foam. If the adjustable plate is slid back, a gap develops between the foam pieces. otherwise, the foam acts as a loose gasket around the wires.

Table 27 - Frame 13 Dimensions for Enclosure Code A (NEMA/UL Type 1, IP21) and M (NEMA/UL Type 1, IP21 w/Conformal Coat)
Amps A 1150 1412 (56) 1300 1600 (63) 1450 600/690V AC 920 1412 (56) (810/932V DC) 1030 1180 Dimensions are in mm and (in.) Voltage Class 400/480V AC (540/650V DC) B 1329 (52) 1529 (60) 1329 (52) C 1264 (50) 1464 (58) 1264 (50) D 535 (21) 735 (29) 535 (21) E 735 (29) 735 (29) 735 (29) F 1264 (50) 1464 (58) 1264 (50)

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

121

Chapter 9

Frame 13 Mechanical Installation

Figure 49 - Enclosure Code H (NEMA/UL Type 12, IP54) and W (NEMA/UL Type 12, IP54 w/Conformal Coat)

A B D
122 (4.8)

NEMA/UL Type 12 Roof Assembly

662 (26.1) 454 (17.8)

NEMA/UL Type 12 External Filters

65 (2.6)

535 (21.1)

Stationary metal front bottom plate Two pieces of soft foam taped to adjacent metal plates Overlapping metal bottom plate (slightly adjustable) Stationary metal back bottom plate

13 (0.5)
2 Places

Wire entry for this enclosure is between two pieces of soft foam. If the adjustable plate is slid back, a gap develops between the foam pieces. otherwise, the foam acts as a loose gasket around the wires.

Table 28 - Frame 13 Dimensions for Enclosure Code H (NEMA/UL Type 12 - IP54) and W (NEMA/UL Type 12, IP54 w/Conformal Coat)
Voltage Class 400/480V AC (540/650V DC) Amps 1150 A 1412 (56) B 478 (18.8) 678 (26.7) 478 (18.8) C 678 (26.7) 678 (26.7) 678 (26.7) D 1 @ 242 (9.5) 1 @ 213 (8.4) 2 @ 242 (9.5) 1 @ 242 (9.5) 1 @ 213 (8.4) E 2443.5 (104.5) max. 2443.5 (104.5) 2443.5 (104.5) max. F 535 (21) 735 (29) 535 (21) G 735 (29) 735 (29) 735 (29) H 1264 (50) 1464 (58) 1264 (50)

1300 1600 (63) 1450 600/690V AC 920 1412 (56) (810/932V DC) 1030 1180 Dimensions are in millimeters and (inches).

122

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 13 Mechanical Installation

Chapter 9

Lifting and Mounting Frame 13 Drives

Enclosed Frame 13 Drives with DC Input


Enclosed Frame 13 drives with DC input are shipped with the control pan mounted in the motor connection area of the right-hand enclosure. The control pan must be moved from this location to a location in the adjacent enclosure, away from the power connections. See the Lifting and Mounting PowerFlex 700S and 700H Drives, Frames 1014, Installation Instructions, publication PFLEX-IN005, for detailed instructions. These instructions are shipped with the drive. When you have completed the instructions in PFLEX-IN005, continue with the installation as directed below.

Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations

Frame 13 size drives are equipped with common mode capacitors. To guard against drive damage, these capacitors should be disconnected depending upon the type of ground system on which the drive is installed. To access and move the common mode jumper(s) and disconnect the capacitor connections you must first move the control frame and remove the protective covers from the converter unit. These steps are detailed on the following pages. Note: See the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives - Installation Instructions, publication DRIVES-IN001, for additional information on an ungrounded distribution system or high resistive ground installation.
Figure 50 - Common Mode Jumper and Rectifier Circuit Board Location
Rectifier Board Front View of Assembly Converter Unit Inverter Unit

Common Mode Jumper There is one jumper for each rectifier module. The rectifier modules and jumpers are located on the left side of the power stack on the drives rectifying structure (left side enclosure). Note: Control frame not shown for clarity only.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

123

Chapter 9

Frame 13 Mechanical Installation

Remove the Protective Covers from the Converter Unit

Move the Control Frame


You must move the control frame in order to access and remove the protective covers from the drives converter unit.
Task A B Description Loosen the T8 Torx-head screws that secure the control frame to the drive enclosure. Swing the control frame out and away from the converter unit.

124

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 13 Mechanical Installation

Chapter 9

Remove the Protective Covers


You must remove the protective covers from the converter unit to gain access to the common mode jumper(s) and rectifier circuit board. Remove the four M5 POZIDRIV screws that secure each of the two or three main and bottom protective covers to the drive, then remove the protective covers.
Remove screws and covers.

DC OP BUS AN ERAT COND DW E UC AIT AT HI TO 5 M GH RS INUTVO AN ES LTAGD CA PA BE E. RE CITO FO RE MOV SE E RS RV PO ICIN WER G

DA N

GE

DC OP BUS AN ERAT COND DW E UC AIT AT HI TO 5 M GH RS INUTVO AN ES LTAGD CA PA BE E. RE CITO FO RE MOV SE E RS RV PO ICIN WER G

DA N

GE

DC OP BUS AN ERAT COND DW E UC AIT AT HI TO 5 M GH RS INUTVO AN ES LTAGD CA PA BE E. RE CITO FO RE MOV SE E RS RV PO ICIN WER G

DA N

GE

Remove screws and covers.

Installation on an Ungrounded Distribution System or High Resistive Ground


If you are installing a 400/480V AC input drive on an ungrounded distribution system or high resistive ground, you: Must move the common mode jumper(s) to the disconnected position see Move the Common Mode Jumper(s) to the Disconnected Position on page 126. Should insulate terminal X4 on the rectifier circuit board - see Insulate Terminal X4 on the Rectifier Circuit Board on page 127.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

125

Chapter 9

Frame 13 Mechanical Installation

If you are installing a 600/690V AC input drive on an ungrounded distribution system or high resistive ground, you: Must move the common mode jumper(s) to the disconnected position see Move the Common Mode Jumper(s) to the Disconnected Position on page 126. Must insulate terminal X4 on the rectifier circuit board - see Insulate Terminal X4 on the Rectifier Circuit Board on page 127.

Installation on a Grounded B Phase Delta System


If you are installing a drive on a grounded B phase Delta system, you: Must move the common mode jumper(s) to the disconnected position see Move the Common Mode Jumper(s) to the Disconnected Position on page 126. Must insulate terminal X4 on the rectifier circuit board - see Insulate Terminal X4 on the Rectifier Circuit Board on page 127.

Move the Common Mode Jumper(s) to the Disconnected Position


Follow the steps below to move the common mode jumper(s) to the disconnected position for each converter unit (see Figure 50 on page 123 for jumper location).
Task A B C Description Loosen the screws and two fasteners that secure the jumper. Rotate the jumper to the lower position. Tighten the screw and two fasteners.

Front View of Converter Unit

Rectifying Circuit Board

126

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 13 Mechanical Installation

Chapter 9

Insulate Terminal X4 on the Rectifier Circuit Board


Follow the steps below to insulate terminal X4 on the rectifier circuit board for each converter unit (see Figure 50 on page 123 for rectifier board location).
Task A B Description Remove the screw from the X4 connection on the rectifier circuit board. Insulate the top and bottom of the X4 connection on the rectifier circuit board.

IMPORTANT

Do not install the screw and washer that was removed from this connection.

Side View of Rectifying Structure

Rectifying Circuit Board

X41

X41

X1 X4

X1 X4

Jumper

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

127

Chapter 9

Frame 13 Mechanical Installation

Remove the Lower Protective Screen Remove the Protective Covers from the Inverter Unit

To access the power terminals, you must first remove the lower protective screen (on NEMA/UL Type 1 and Type 12 enclosures). Remove the screws that secure the lower protective screen to the right side enclosure only and remove the screen.

Remove screws and screen.

128

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 13 Mechanical Installation

Chapter 9

Remove the Protective Covers


You must remove the protective covers to gain access to the inverter units. Remove the four M5 POZIDRIV screws that secure each of the two or three main and bottom protective covers to the drive, then remove the protective covers.
Remove screws and covers.

DC OP BUS AN ERAT COND DW E UC AIT AT HI TO 5 M GH RS INUTVO AN ES LTAGD CA PA BE E. RE CITO FO RE MOV SE E RS RV PO ICIN WER G

DA N

GE

DC OP BUS AN ERAT COND DW E UC AIT AT HI TO 5 M GH RS INUTVO AN ES LTAGD CA PA BE E. RE CITO FO RE MOV SE E RS RV PO ICIN WER G

DA N

GE

DC OP BUS AN ERAT COND DW E UC AIT AT HI TO 5 M GH RS INUTVO AN ES LTAGD CA PA BE E. RE CITO FO RE MOV SE E RS RV PO ICIN WER G

DA N

GE

Remove screws and covers.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

129

Chapter 9

Frame 13 Mechanical Installation

Power Wiring

Frame 13 400 and 600 Volt Class AC Input Power Wiring


Frame 13 size drives utilize two or three parallel power structures that are preconnected to line reactors through a fused input switch. IMPORTANT Parallel wiring must have the same cable dimensions, type and routing. Nonsymmetrical wiring may cause unequal loading between the converters and reduce the drives ability to deliver current to the motor.

Figure 51 - Frame 13 AC Wiring Example: Three Internal Fuses per Phase


L1 L2 L3

AC Input Power Wiring Provided by Customer

400V, 1300 & 1450 Amp Example Shown

L1

L2

L3

AC Input Power Terminals Inside Drive

Converter 1

Converter 2

Converter 3

Inverter Unit Motor Out


U /T1 V /T2 W /T3

130

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 13 Mechanical Installation

Chapter 9

Output Power Wiring


Connect the motor to the output power terminals. IMPORTANT Parallel wiring must have the same cable dimensions, type and routing. Nonsymmetrical wiring may cause unequal loading between the converters and reduce the drives ability to deliver current to the motor.

Figure 52 - Frame 13 Motor Wiring Example

U/T1

V/T2

W/T3

PE

Motor

Motor Frame

IMPORTANT

Once power wiring has been completed, the protective covers must be installed before energizing the drive. Installation is in reverse order of removal (see Remove the Protective Covers from the Converter Unit on page 124 and Remove the Protective Covers from the Inverter Unit on page 128).

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

131

Chapter 9

Frame 13 Mechanical Installation

Table 29 - Power Terminal Specifications


No. 1 2 3 4
(1) (2) (3) (4)

Name Input Power Terminal Block (1) L1, L2, L3 Output Power Terminal Block (3) U/T1, V/T2, W/T3 SHLD Terminal, PE, Motor Ground (3) DC Bus (3) (3 Terminals; DC, DC+)

Description Input power Motor connections Terminating point for wiring shields DC input or external brake

Wire Size Range (1)(2) Maximum Minimum 300 mm2 2.1 mm2 (600 MCM) (14 AWG) 300 mm2 2.1 mm2 (600 MCM) (14 AWG) 300 mm2 2.1 mm2 (600 MCM) (14 AWG) 300 mm2 2.1 mm2 (600 MCM) (14 AWG)

Torque Recommended 40 Nm (354 lbin) 40 Nm (354 lbin) 40 Nm (354 lbin) 40 Nm (354 lbin)

Terminal Bolt Size (3)(4) M12 M12 M10 M12

Maximum/minimum sizes that the terminal block will accept - these are not recommendations. Do Not exceed maximum wire size. Parallel connections may be required. These connections are bus bar type terminations and require the use of lug type connectors. Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.

Figure 53 - Power Terminal Locations


4
DC+ DCDC+ DCDC+ DC-

U/T1

V/T2

W/T3

U/T1

V/T2

W/T3

1
Output Power Terminals
L1

L2

L3

Note: Right enclosure shown only.

132

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter

10

Frame 14 Mechanical Installation

Most start-up difficulties are the result of incorrect wiring. Every precaution must be taken to assure that the wiring is done as instructed. All information in Chapter 1 General Installation Information and in this chapter must be read and understood before the actual installation begins. ATTENTION: The following information is merely a guide for proper installation. Rockwell Automation, Inc. cannot assume responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

133

Chapter 10

Frame 14 Mechanical Installation

Minimum Mounting Clearances


200 mm (8.0 in.) Min.

1500A Drive - 2400 mm Enclosure Shown.

800 mm (31.50 in.) Min.

Operating Temperatures

Frame 14 drives require a minimum of 4200 m3/h (2472 cfm) of cooling air for each Inverter unit and 1150 m3/h (677 cfm) of cooling air for each Converter unit.
PowerFlex Drive 700H Voltage Class 400/480V AC (540/650V DC) 600/690V AC (810/932V DC) 600/690V AC (810/932V DC) 600/690V AC (810/932V DC) Amp Rating All 1500, 1900 2250 1500 Surrounding Air Temperature Normal Duty Heavy Duty 040 C (32104 F) 040 C (32104 F) 040 C (32104 F) 035 C (3295 F) 040 C (32104 F) 040 C (32104 F) 035 C (3295 F) 040 C (32104 F)

700S

Table 30 - Frame 14 Number of Inverter and Converter Units Per Drive


Voltage Class 400/480V AC 600/690V AC Amp Rating 1700, 2150 2700 1500 1900, 2250 No. Converter Units 4 6 3 4 No. Inverter Units 6 6 6 6

134

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 14 Mechanical Installation

Chapter 10

Dimensions
Lifting Points

Figure 54 - Drives Above 1500 A, 2800 mm Enclosure Code A (NEMA/UL Type 1, IP21) and M (NEMA/ UL Type 1, IP21 w/Conformal Coat)
Dimensions are in millimeters and (inches).
Lifting Points 620 (24.5) 603 (24) 44 (1.7)

Shipping Split At This Location

CLOSE

OPEN

2276 (90) 2232 (88)

1400 (55)

1400 (55)

Access Holes for Motor Output Cables

Access Holes for AC Input Cables (2 Places)

32.75 (1.3)

10.2 16 Places

535 (21.0)

32.25 (1.3)

535 (21.0) 65 (2.6)

735 (29.0) 65 (2.6) 2800 (110.2)

735 (29.0) 65 (2.6)

535 (21.0)

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

135

Chapter 10

Frame 14 Mechanical Installation

Figure 55 - Drives Above 1500 A 2800 mm Enclosure Code H (NEMA/UL Type 12, IP54) and W (NEMA/UL Type 12, IP54 w/Conformal Coat)
Dimensions are in millimeters and (inches).
Lifting Points Lifting Points

NEMA/UL Type 12 Roof Assembly w/Filters


454 (18)

662 (26)

Shipping Split At This Location

CLOSE

OPEN

2276 (90) 2232 (88)

NEMA/UL Type 12 External Door Filters

1400 (55)

1400 (55)

Access Holes for Motor Output Cables

Access Holes for AC Input Cables (2 Places)

10.2 16 Places

32.75 (1.3)

535 (21.0)

535 (21.0) 65 (2.6)

735 (29.0) 65 (2.6) 2800 (110.2)

735 (29.0) 65 (2.6)

535 (21.0)

32.25 (1.3)

136

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 14 Mechanical Installation

Chapter 10

Figure 56 - 1500 A Drives 2400 mm Enclosure Code A (NEMA/UL Type 1, IP 21) and M (NEMA/UL Type 1, IP21 w/Conformal Coat)
Dimensions are in millimeters and (inches).
Lifting Points Lifting Points 620 (24.5) 603 (24) 44 (1.7)

Shipping Split At This Location

CLOSE

OPEN

2276 (90) 2232 (88)

797 (31.4)

797 (31.4)

797 (31.4)

Access Holes for Motor Output Cables

Access Holes for AC Input Cables (2 Places)

10.2 12 Places

32.75 (1.3)

535 (21.0)

735 (29.0) 65 (2.6)

735 (29.0) 65 (2.6) 2397 (94.4)

735 (29.0)

32.25 (1.3)

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

137

Chapter 10

Frame 14 Mechanical Installation

Figure 57 - 1500 A Drives 2400 mm Enclosure Code H (NEMA/UL Type 12, IP54) and W (NEMA/UL Type 12, IP54 w/Conformal Coat)
Dimensions are in millimeters and (inches). NEMA/UL Type 12 Roof Assembly w/Filters
454 (18) 662 (26)

Lifting Points

Lifting Points

Shipping Split At This Location

CLOSE

OPEN

2276 (90) 2232 (88)

NEMA/UL Type 12 External Door Filters

797 (31.4)

797 (31.4) 2400 (94.4)

797 (31.4)

10.2 12 Places

Access Holes for Motor Output Cables

Access Holes for AC Input Cables (2 Places) 32.75 (1.3)

535 (21.0)

735 (29.0) 32.25 (1.3) 65 (2.6)

735 (29.0) 65 (2.6)

735 (29.0)

32.25 (1.3)

138

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 14 Mechanical Installation

Chapter 10

Figure 58 - DC Input Drive Enclosure Code A (NEMA/UL Type 1, IP 21) and M (NEMA/UL Type 1, IP21 w/Conformal Coat)
Dimensions are in millimeters and (inches).
620 (24.5) 601 (23.7) 44 (1.7)

2270 (89.4) 2232 (88)

1597 (63.0)
Wire entry for this enclosure is between two pieces of soft foam. If the adjustable plate is slid back, a gap develops between the foam pieces. Otherwise, the foam acts as a loose gasket around the wires. Stationary metal front bottom plate Two pieces of soft foam taped to adjacent metal plates Overlapping metal bottom plate (slightly adjustable) Stationary metal back bottom plate

62.25 (2.5)

675 125 (5.0) (26.6)

675 (26.6)

475 (18.7) 65 (2.6) 68.75 (2.7) 799.5 (31.5)

30 (1.2)

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

139

Chapter 10

Frame 14 Mechanical Installation

Figure 59 - DC Input Drive Enclosure Code H (NEMA/UL Type 12, IP54) and W (NEMA/UL Type 12, IP54 w/Conformal Coat)
Dimensions are in millimeters and (inches).
Lifting Points 454 (18) 662 (26)

CLOSE

OPEN

2276 (90) 2232 (88)

799.5 (31.5) 1597 (63.0)

799.5 (31.5)
Wire entry for this enclosure is between two pieces of soft foam. If the adjustable plate is slid back, a gap develops between the foam pieces. Otherwise, the foam acts as a loose gasket around the wires. Stationary metal front bottom plate Two pieces of soft foam taped to adjacent metal plates Overlapping metal bottom plate (slightly adjustable) Stationary metal back bottom plate

62.25 (2.5)

675 125 (5.0) (26.6)

675 (26.6)

475 (18.7) 65 (2.6) 68.75 (2.7) 799.5 (31.5)

30 (1.2)

Lifting and Mounting Frame 14 Drives

Enclosed Frame 14 Drives with DC Input


Enclosed frame 14 drives with DC input are shipped with the control pan mounted in the motor connection area of the left-hand enclosure. The control pan must be moved from this location to a location in the adjacent enclosure, away from the power connections. See the Lifting and Mounting PowerFlex 700S and 700H Drives, Frames 1014, Installation Instructions, publication PFLEX-IN005, for detailed instructions. These instructions are shipped with the drive. When you have completed the instructions in PFLEX-IN005, continue with the installation as directed below.

140

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 14 Mechanical Installation

Chapter 10

Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations

Frame 14 size drives are equipped with common mode capacitors. To guard against drive damage, these capacitors should be disconnected depending upon the type of ground system on which the drive is installed. To access and move the common mode jumper(s) and disconnect the capacitor connections you must first move the control frame and remove the protective covers from the converter unit. These steps are detailed on the following pages. Note: See Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives - Installation Instructions, publication DRIVES-IN001, for additional information on an ungrounded distribution system or high resistive ground installation.
Figure 60 - Common Mode Jumper and Rectifier Circuit Board Location

Rectifier board

Drives Above 1500A

Rectifier board

1500A Drives

Common Mode Jumper There is one jumper for each rectifying module. The rectifying modules and jumpers are located on the left side of the power stack on the drives converter units.

Converter Unit

Inverter Unit

Inverter Unit

Converter Unit Control Frame not shown for clarity only

Converter Unit

Inverter Unit

Inverter Unit

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

141

Chapter 10

Frame 14 Mechanical Installation

Remove the Protective Covers from the Converter Unit(s)

Remove the Protective Screens


To access the components within the converter unit(s), you must first remove the protective screens from the drive. Remove the screws that secure the protective screens to the converter unit(s) and remove the screens.
1500A Drive Shown

Remove screws and screens

142

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 14 Mechanical Installation

Chapter 10

Move the Control Frame


To gain access to the airflow plate and protective covers on the left side converter unit of the drive you must move the control frame.
Task A B Description Loosen the T8 Torx-head screws that secure the control frame to the drive enclosure. Swing the control frame out and away from the converter unit.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

143

Chapter 10

Frame 14 Mechanical Installation

Remove the Airflow Plate(s)


The drive is equipped with a plate(s), just above the converter unit(s), that directs airflow through the drive enclosure(s). You must remove this plate(s) in order to access the protective covers.
Task A B Description Remove the T8 Torx-head screws that secure the airflow plate to the drive. Slide the airflow plate off of the drive.

1500A Drive Shown

A A

144

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 14 Mechanical Installation

Chapter 10

Remove the Protective Covers


You must remove the protective covers to gain access to the converter unit(s). Remove the four M5 POZIDRIV screws that secure each of the two or three main and bottom protective covers to the drive, then remove the protective covers.
Remove screws and covers

DC OP BUS AN ERAT COND DW E UC AIT AT HI TO 5 M GH RS INUTVO AN ES LTAGD CA PA BE E. RE CITO FO RE MOV SE E RS RV PO ICIN WER G

DA N

GE

DC OP BUS AN ERAT COND DW E UC AIT AT HI TO 5 M GH RS INUTVO AN ES LTAGD CA PA BE E. RE CITO FO RE MOV SE E RS RV PO ICIN WER G

DA N

GE

DC OP BUS AN ERAT COND DW E UC AIT AT HI TO 5 M GH RS INUTVO AN ES LTAGD CA PA BE E. RE CITO FO RE MOV SE E RS RV PO ICIN WER G

DA N

GE

Remove screws and covers

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

145

Chapter 10

Frame 14 Mechanical Installation

Installation on an Ungrounded Distribution System or High Resistive Ground


Must move the common mode jumper(s) to the disconnected position see Move the Common Mode Jumper(s) to the Disconnected Position on page 147. Should insulate terminal X4 on the Rectifier circuit board - see Insulate Terminal X4 on the Rectifier Circuit Board on page 148. If you are installing a 600/690V AC input drive on an ungrounded distribution system or high resistive ground, you: Must move the common mode jumper(s) to the disconnected position see Move the Common Mode Jumper(s) to the Disconnected Position on page 147. Must insulate terminal X4 on the Rectifier circuit board - see Insulate Terminal X4 on the Rectifier Circuit Board on page 148.

Installation on a Grounded B Phase Delta System


If you are installing a drive on a grounded B phase Delta system, you: Must move the common mode jumper(s) to the disconnected position see Move the Common Mode Jumper(s) to the Disconnected Position on page 147. Must insulate terminal X4 on the Rectifier circuit board - see Insulate Terminal X4 on the Rectifier Circuit Board on page 148.

146

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 14 Mechanical Installation

Chapter 10

Move the Common Mode Jumper(s) to the Disconnected Position


Follow the steps below to move the common mode jumper(s) to the disconnected position for each converter unit (see Figure 60 on page 141 for MOV jumper location).
Task A B C Description Loosen the screws and two fasteners that secure the jumper. Rotate the jumper to the lower position. Tighten the screw and two fasteners.

Front View of Converter Unit

Rectifying Circuit Board

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

147

Chapter 10

Frame 14 Mechanical Installation

Insulate Terminal X4 on the Rectifier Circuit Board


Follow the steps below to insulate terminal X4 onFigure 60 on page 141 the rectifier circuit board for each converter unit (see for rectifier board location).
Task A B Description Remove the screw from the X4 connection on the rectifier circuit board. Insulate the top and bottom of the X4 connection on the rectifier circuit board.

IMPORTANT

Do not install the screw and washer that was removed from this connection.

Side View of Rectifying Structure

Rectifying Circuit Board

X41

X41

X1 X4

X1 X4

Jumper

148

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 14 Mechanical Installation

Chapter 10

Power Wiring

To access the power terminals, you must first remove the protective screens (on NEMA/UL Type 1 and Type 12 enclosures), air flow plate and protective covers from the inverter units. These steps are detailed below.

Remove the Protective Covers from the Inverter Units

Remove the Protective Screens


To access the power terminals, you must first remove the protective screens from the inverter units. Remove the screws that secure the protective screens to the inverter units and remove the screens.

Remove screws and screens

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

149

Chapter 10

Frame 14 Mechanical Installation

Remove the Airflow Plates


The drive is equipped with plates, just above the top of the protective covers, that direct airflow through the drive enclosure. You must remove these plates in order to access the protective covers.
Task A B Description Remove the T8 Torx-head screws that secure the airflow plates to the drive. Slide the airflow plates off of the drive.

B A A

150

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 14 Mechanical Installation

Chapter 10

Remove the Protective Covers


You must remove the protective covers from the inverter units in order to gain access to the power terminals. Remove the four M5 POZIDRIV screws that secure each of the three main and bottom protective covers to the drive, then remove the protective covers.
Remove screws and covers

DC OP BUS AN ERAT COND DW E UC AIT AT HI TO 5 M GH RS INUTVO AN ES LTAGD CA PA BE E. RE CITO FO RE MOV SE E RS RV PO ICIN WER G

DA N

GE

DC OP BUS AN ERAT COND DW E UC AIT AT HI TO 5 M GH RS INUTVO AN ES LTAGD CA PA BE E. RE CITO FO RE MOV SE E RS RV PO ICIN WER G

DA N

GE

DC OP BUS AN ERAT COND DW E UC AIT AT HI TO 5 M GH RS INUTVO AN ES LTAGD CA PA BE E. RE CITO FO RE MOV SE E RS RV PO ICIN WER G

DA N

GE

Remove screws and covers

400 and 690 Volt Class AC Input Wiring for Frame 14 Drives
Frame 14 size drives utilize three parallel converter units or two pairs of two parallel converter units that are pre-connected to line reactors and are fed through motor operated circuit breakers.

IMPORTANT

Parallel wiring must have the same cable dimensions, type and routing. Nonsymmetrical wiring may cause unequal loading between the converters and reduce the drives ability to deliver current to the motor.

Frame 14 drives can be ordered with or without du/dt filters. The du/dt filter limits the rate of change of output voltage and the rate of change in the IGBT or output transistor switching event. See the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001, for minimum inductance on installations where du/dt filters are not installed.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

151

Chapter 10

Frame 14 Mechanical Installation

Figure 61 - 1500A Drive AC Wiring Example:


AC Input Power Wiring Provided by Customer
L1 L2 L3

L1

L2

L3

AC Input Power Terminals Inside Drive

L1

L2

L3

L1

L2

L3

L1

L2

L3

Converter 1

Converter 2

Converter 3

B-

B+

B-

B+

B-

B+

6x BB+ BB+

6x

Inverter 1

Inverter 2

U V W /T1 /T2 /T3

U V W /T1 /T2 /T3

L1

L2

L3

L1

L2

L3

du/dt Filter Motor Output


U V /T1 /T2 W /T3

du/dt Filter Motor Output


U V /T1 /T2 W /T3

152

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 14 Mechanical Installation

Chapter 10

Figure 62 - Drives Above 1500A AC Wiring Example:


AC Input Power Wiring Provided by Customer
L1 L2 L3 L1 L2 L3

L1

L2

L3

AC Input Power Terminals Inside Drive

L1

L2

L3

L1

L2

L3

L1

L2

L3

L1

L2

L3

L1

L2

L3

Converter 1

Converter 2

Converter 3

Converter 4

B-

B+

B-

B+

B-

B+

B-

B+

6x BB+ BB+

6x

Inverter 1

Inverter 2

U V W /T1 /T2 /T3

U V W /T1 /T2 /T3

L1

L2

L3

L1

L2

L3

du/dt Filter Motor Output


U /T1 V /T2 W /T3

du/dt Filter Motor Output


U /T1 V /T2 W /T3

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

153

Chapter 10

Frame 14 Mechanical Installation

Output Power Wiring for Frame 14 Drives


Frame 14 drives utilize two parallel power structures, and therefore have two sets of output power terminals. You must connect the motor to both sets of output power terminals. IMPORTANT Parallel wiring must have the same cable dimensions, type and routing. Nonsymmetrical wiring may cause unequal loading between the converters and reduce the drives ability to deliver current to the motor.

IMPORTANT

The minimum cable length for parallel motor cables from the drive to the point where the cables connect is 5 m (16.4 ft.). Join the parallel cables at the motor end (not the drive end). Or, install a reactor on the output of each power module with a minimum of 5 H prior to joining the parallel cables at the motor end.

154

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 14 Mechanical Installation

Chapter 10

Figure 63 - Motor Wiring Example

INU1
1U/T1 1V/T2 1W/T3 PE 2U/T1

INU2
2V/T2 2W/T3 PE

1L1

1L2

1L3

2L1

2L2

2L3

du/dt Filter 1
1U/T1 1V/T2 1W/T3 PE 2U/T1

du/dt Filter 2
2V/T2 2W/T3 PE

5m minimum

Motor

Motor Frame

IMPORTANT

Once power wiring has been completed, the protective covers must be installed before energizing the drive. Installation is in reverse order of removal (see Remove the Protective Covers from the Converter Unit(s) on page 142 and Remove the Protective Covers from the Inverter Units on page 149).

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

155

Chapter 10

Frame 14 Mechanical Installation

Table 31 - Power Terminal Specifications


No. Name 1 2 3 4 Input Power Terminal Block (1) L1, L2, L3 Output Power Terminal Block (3) U/T1, V/T2, W/T3 SHLD Terminal, PE, Motor Ground (3) DC Bus (3) (3 Terminals; DC, DC+) Description Input power Motor connections Terminating point for wiring shields DC input or external brake Wire Size Range (1)(2) Maximum Minimum 300 mm2 2.1 mm2 (600 MCM) (14 AWG) 300 mm2 2.1 mm2 (600 MCM) (14 AWG) 300 mm2 2.1 mm2 (600 MCM) (14 AWG) 300 mm2 2.1 mm2 (600 MCM) (14 AWG) Torque Recommended 40 Nm (354 lbin) 40 Nm (354 lbin) 40 Nm (354 lbin) 40 Nm (354 lbin) Terminal Bolt Size (3)(4) M12 M12 M10 M12

(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.

(2) Do Not exceed maximum wire size. Parallel connections may be required. (3) These connections are bus bar type terminations and require the use of lug type connectors. (4) Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.

Figure 64 - 1500A Drive Power Terminal Locations


DC Bus Terminals DC 4 (Front Terminals)

Center Enclosure Shown DC+ (Back Terminals) Input Power Terminals

2 Output Power Terminals without du/dt Filters

1
L1

U/T1

V/T2

W/T3

L2

Side View
L3

3 Ground Terminals

U/T1

V/T2

W/T3

2 Output Power Terminals with du/dt Filters

156

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 14 Mechanical Installation

Chapter 10

Figure 65 - Drives Above 1500A Power Terminal Locations


4 DC Bus Terminals (In Both Enclosures)

DC (Front Terminals)

2 Output Power Terminals without du/dt Filters (in two center enclosures)

U/T1

V/T2

W/T3

Side View

DC+ (Back Terminals) 1 Input Power Terminals


L1

1 Input Power Terminals


L1

L2

L2

L3

L3

3 Ground Terminals

U/T1

V/T2

W/T3

Center Enclosures Shown

2 Output Power Terminals with du/dt Filters (in two center enclosures)

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

157

Chapter 10

Frame 14 Mechanical Installation

Frame 14 Circuit Breakers

Frame 14 drives utilize molded case circuit breakers (MCCBs) to provide overload/overcurrent and undervoltage protection on the incoming AC lines and to synchronize the energizing of the power structures. The circuit breakers are located inside of the enclosures in front of the AC chokes.
Drives Above 1500A 1500A Drives

Push On

Push Off

Push On

Push Off

DISCHARGED SPRING

OFF

DISCHARGED SPRING

OFF

S I

L N

S I

Rectifying Structure

Power Structure

Power Structure

Rectifying Structure Note: Control Frame not shown for clarity only.

Rectifying Structure

Power Structure

Power Structure

158

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 14 Mechanical Installation

Chapter 10

Circuit Breaker DIP Switch Settings


The DIP switches on the circuit breakers are configured to the correct settings at the factory. However, the settings detailed in Table 32 below should be verified before charging the circuit breaker motor operators and operating the drive. Once the settings have been verified, continue with Charging the MCCB Motor Operators on page 160.
Table 32 - Circuit Breaker DIP Switch Settings
Voltage Class 400/480V AC 600/690V AC Drive ND Continuous Amp Rating 1770 2150 1500 1900 2250 L I1 0.76 0.92 0.88 0.84 0.96 t1 3s 3s 3s 3s 3s S/I S S S S S S/I I3 1.5 1.5 1.0 1.0 1.5 t2 0.1 s 0.1 s 0.1 s 0.1 s 0.1 s ON/OFF OFF OFF OFF OFF OFF N 50% / 100% na na na na na

Figure 66 - Circuit Breaker DIP Switches Location

I1 = In x (0.4+

L
DISCHARGED SPRING

t1

S I

I2= In x I3=

t2

N
OFF

S I

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

159

Chapter 10

Frame 14 Mechanical Installation

Charging the MCCB Motor Operators


The stored energy motor operators must be charged prior to the first time the circuit breakers are closed and whenever input power is removed and re-applied to the drive. ATTENTION: When an external device for circuit breaker motor operator status is not used, the enclosure door(s) must be open in order to view the status indicator on the circuit breakers. Only qualified personnel familiar with PowerFlex 700S and 700H drives and associated machinery should plan or implement the installation, start-up and subsequent maintenance of the system. Failure to comply may result in personal injury and/or equipment damage. 1. With the doors of the enclosures containing the MCCBs open, apply control voltage to the drive. 2. Press and hold the Open (red) control button on the enclosure door until the status text Charged Spring displays on each of the MCCBs (see illustration below).
Close and Open buttons location on enclosure door.

CLOSE

OPEN

CLOSE

OPEN

160

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Frame 14 Mechanical Installation

Chapter 10

Status Text displays Charged Spring when charged.

CHARGED SPRING
Push On Push Off

DISCHARGED SPRING

OFF

S I

3. The MCCBs can now be closed. Continue with Closing the Circuit Breakers and Energizing the Drive on page 161 below.

Closing the Circuit Breakers and Energizing the Drive


1. Close and latch all enclosure doors. 2. Press the Close (green) control button on the enclosure door. 3. The circuit breakers can be opened by pressing the Open (red) control button on the enclosure door. The motor operators are automatically recharged when they are opened.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

161

Chapter 10

Frame 14 Mechanical Installation

Resetting the Circuit Breakers


The electronic trip unit will open the circuit breaker in the case of a drive overload/overcurrent condition. When a voltage drop (U < 0.7 x Un) or loss of the main supply occurs, the undervoltage release coil of the circuit breakers will open. The trip indicator contacts of the circuit breakers are connected in series. Therefore, if one circuit breakers trips due to an undervoltage or overload/ overcurrent condition, all circuit breakers will open/trip. If the circuit breakers have opened due to an overcurrent fault, the condition that caused the fault must be corrected and the fault cleared before the circuit breakers can be reset and the drive started. In this case, see Charging the MCCB Motor Operators on page 160.

162

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Appendix

Specifications

Category
Agency Certification

PowerFlex 700H
Listed to UL 508C and CAN/CSA-C2.2 No. 14-M91.

PowerFlex 700S
UL and cUL Listed to UL 508C and CAN/CSA - 22.2 No. 14-95.

Marked for all applicable European Directives (1) EMC Directive (89/336/EEC) Emissions: EN 61800-3 Adjustable Speed electrical power drive systems Low Voltage Directive (73/23/EEC) EN 50178 Electronic Equipment for use in Power Installations Certified to AS/NZS, 1997 Group 1, Class A.
N223

Marked for all applicable European Directives EMC Directive (89/336/EEC) Emissions: EN 61800-3 Adjustable Speed electrical power drive systems Part 3 Low Voltage Directive (73/23/EEC) EN 50178 Electronic Equipment for use in Power Installations Certified to AS/NZS, 1997 Group 1, Class A.

II 2 G/D

Certified to ATEX directive 94/9/EC. Group II Category (2) GD Applications with ATEX Approved Motors. Refer to Appendix E Instructions for ATEX Approved PowerFlex 700H Drives in Group II Category (2) Applications with ATEX Approved Motors on page 203 for more information. (not applicable)

Certified to ATEX directive 94/9/EC. Group II Category (2) GD Applications with ATEX Approved Motors. PowerFlex 700S Phase II Control drives only. Refer to Appendix E ATEX Approved PowerFlex 700S, Phase II Drives in Group II Category (2) Applications with ATEX Approved Motors, in publication 20D-PM001 for more information. TUV functional safety report only (no FS mark on the label)

TUV Rheinland Product Safety

..

Production inspected

EN 50178
Bauart geprft
Functional

TUV Rheinland

..

Type approved

(1) Applied noise impulses may be counted in addition to the standard pulse train causing erroneously high [Pulse Freq] readings.

W
Safety

The drive is also designed to meet the following specifications: NFPA 70 - US National Electrical Code NEMA ICS 7.1 - Safety standards for Construction and Guide for Selection, Installation and Operation of Adjustable Speed Drive Systems. IEC 146 - International Electrical Code.

The drive is designed to meet applicable requirements of the following codes/ standards: IEC 61800-2 Adjustable speed electrical power drive systems - General requirements IEC 61800-5-1 Adjustable speed electrical power drive systems - Safety requirements NFPA 70 - US National Electrical Code

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

163

Appendix A

Specifications

Category
Protection

Specification
Drive AC Input Overvoltage Trip: AC Input Undervoltage Trip: Bus Overvoltage Trip: Bus Undervoltage Shutoff/Fault: Nominal Bus Voltage (Full Load): Heat Sink Thermistor: Drive Overcurrent Trip Software Overcurrent Trip: Hardware Overcurrent Trip: Instantaneous Current Limit: Line transients: Control Logic Noise Immunity: Power Ride-Thru: Logic Control Ride-Thru: Ground Fault Trip: Short Circuit Trip: Altitude: Maximum Surrounding Air Temperature without De-rating: Storage Temperature (all const.): Atmosphere:

PowerFlex 700H
380/400V 480V 500V 611V AC 611V AC 611V AC 235VAC 235VAC 235VAC 911VDC 911VDC 911VDC 333VDC 333VDC 333VDC 517VDC 621VDC 645VDC Monitored by microprocessor overtemp trip 600V 806V AC 326VAC 1200V DC 461VDC 776VDC 690V 806V AC 326VAC 1200V DC 461VDC 890VDC

PowerFlex 700S
380/400V 480V 500V 675V AC 675V AC 675V AC Adjustable 911VDC 911VDC 911VDC Adjustable 540VDC 648VDC 645VDC Monitored by microprocessor overtemp trip 600V 889V AC 1200V DC 810VDC 690V 889V AC 1200V DC 931V DC

Environment

360% of rated Heavy Duty current (typical) up to 6000 volts peak per IEEE C62.41-1991 Showering arc transients up to 1500V peak 15 milliseconds at full load 0.5 seconds minimum, 2 seconds typical Phase-to-ground on drive output Phase-to-phase on drive output 1000 m (3300 ft.) maximum without derating. Derate the drive by 1% for every 100 m (328 ft.) above 1000 m (3300 ft.). Based on drive rating, refer to Drive Ratings on page 167. 40 to 60 C (40 to 140 F) Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere. 5 to 95% non-condensing 15G peak for 11ms duration (1.0 ms) 2 mm (0.0787 in.) displacement, 1G peak EN50178 / EN60068-2-6 Frame Sound Level Back- ground Note: Sound pressure level is Noise Level measured at 1 meter. All devices measured are 400V 9 78 dba 49 dba IP21 and in power up mode. 10 77 dba 49 dba 13 76d ba 46 dba 10% 4763 Hz. Three-phase input provides full rating for all drives. Single-phase operation provides 50% of rated current. 0.98 across entire speed range. 97.5% at rated amps, nominal line volts. 200,000 Amps symmetrical. Determined by AIC rating of installed fuse/circuit breaker. Recommended not greater than 2:1 ratio.

Calculated value, 105% of motor rated to 200% of drive rated 360% of rated Heavy Duty current (typical) Up to 6000 volts peak per IEEE C62.41-1991 Showering arc transients up to 1500V peak 15 milliseconds at full load 0.25 seconds, drive not running Phase-to-ground on drive output Phase-to-phase on drive output 1000 m (3300 ft.) maximum without derating. Derate the drive by 1% for every 100 m (328 ft.) above 1000 m (3300 ft.). Based on drive rating, refer to Drive Ratings on page 167. 40 to 70 C (40 to 158 F) Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere. 5 to 95% non-condensing 15G peak for 11ms duration (1.0 ms) 2 mm (0.0787 in.) displacement, 1G peak EN50178 / EN60068-2-6 Frame Sound Level Back- ground Note: Sound pressure level is Noise Level measured at 1 meter. All devices measured are 400V 9 78 dba 49 dba IP21 and in power up mode. 10 77 dba 49 dba 13 76d ba 46 dba 10% 4763 Hz. Three-phase input provides full rating for all drives. Single-phase operation provides 50% of rated current. 0.98 across entire speed range. 97.5% at rated amps, nominal line volts. 200,000 Amps symmetrical. Determined by AIC rating of installed fuse/circuit breaker. Drive to motor rating cannot exceed a 2:1 ratio.

Relative Humidity: Shock: Non-operational Vibration: Sound:

Electrical

AC Input Voltage Tolerance: Frequency Tolerance: Input Phases: Displacement Power Factor: Efficiency: Maximum Short Circuit Rating: Actual Short Circuit Rating: Maximum Drive to Motor Power Ratio:

164

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Specifications

Appendix A

Category
Control

Specification
Method:

PowerFlex 700H

PowerFlex 700S

Carrier Frequency:

Output Voltage Range: Output Frequency Range: Frequency Accuracy Digital Input: Analog Input: Frequency Control:

Sine coded PWM with programmable carrier frequency. Ratings apply to all Sine coded PWM with programmable carrier frequency, Indirect Selfdrives (refer to the Derating Guidelines in the PowerFlex Reference Manual). The Organized, Field-Oriented Control, Current-regulated. Ratings apply to all drives drive can be supplied as 6 pulse or 12 pulse in a configured package. (refer to the Derating Guidelines in the PowerFlex 700S Phase II Reference Manual, publication PFLEX-RM003). The drive can be supplied as 6 pulse or 12 pulse in a configured package. 16 kHz. 2 kHz Settings: 2, 4, 6, 8, 10 kHz (6 kHz is for V/Hz operation only) 0 to rated motor voltage 0 to rated motor voltage 0320 Hz 0400 Hz Note: For output frequencies above 320400 Hz consult the factory. Within 0.01% of set output frequency. Within 0.4% of maximum output frequency. Speed regulation - with Slip Compensation 0.5% of base speed across 40:1 speed range 40:1 operating range

Speed Control:

Torque Regulation:

Selectable Motor Control: Stop Modes: Accel/Decel: S-Curve Time: Intermittent Overload: Current Limit Capability: Electronic Motor Overload Protection:

Speed regulation - without feedback 0.1% of base speed across 120:1 speed range 120:1 operating range 50 rad/sec bandwidth Speed regulation - with feedback 0.001% of base speed across 120:1 speed range 1000:1 operating range 300 rad/sec bandwidth Torque Regulation - without feedback 10%, 600 rad/sec bandwidth Torque Regulation - with feedback 5%, 2500 rad/sec bandwidth Sensorless Vector with full tuning. Standard V/Hz with full custom capability. Field Oriented Control with and without a feedback device and permanent magnet motor control Multiple programmable stop modes including - Ramp, Coast, DC-Brake, Ramp- Multiple programmable stop modes including - Ramp, Coast and Current Limit. to-Hold and S-curve. Two independently programmable accel and decel times. Each time may be Two independently programmable accel and decel times. Each time may be programmed from 03276.7 seconds in 0.1 second increments. programmed from 06553.5 seconds in 0.1 second increments. 0100% of accel/decel time. Adjustable from 0.54.0 seconds. 110% Overload capability for up to 1 minute 110% Overload capability for up to 1 minute 150% Overload capability for up to 2 seconds 150% Overload capability for up to 3 seconds Proactive Current Limit programmable from 20 to 160% of rated output Independent Motoring and Regenerating Power Limits programmable to 800% current. Programmable proportional gain. of rated output current Provides class 10 motor overload protection according to NEC article 430 and Provides class 10 motor overload protection according to NEC article 430 and motor over-temperature protection according to NEC article 430.126 (A) (2). motor over-temperature protection according to NEC article 430.126 (A) (2). UL 508C File E59272. UL 508C File E59272.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

165

Appendix A

Specifications

Category
Feedback

Specification
Encoder Inputs (2): Encoder Voltage Supply:

PowerFlex 700H

PowerFlex 700S
Dual Channel Plus Marker, Isolated with differential transmitter Output (Line Drive) Incremental, Dual Channel Quadrature type 5V DC or 12 V DC 320 mA/channel 5V DC minimum high state voltage of 3.0V DC, maximum low state voltage at 0.4V DC 12 V DC minimum high state voltage of 7.0V DC, maximum low state voltage of 0.4V DC Encoder PPR ratings are limited to the values specified in the table below:
n = 2n = 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 2 4 8 16 32 64 128 256 512 1024 2048 4096 8192 16384 x mod 75 mod 125 mod 225 mod 375 mod 625 mod1125 75 150 300 600 1200 2400 ---------125 250 500 1000 2000 4000 ---------225 450 900 1800 3600 7200 ---------375 750 1500 3000 6000 12000 ---------625 1250 2500 5000 10000 20000 ---------1125 2250 4500 9000 18000 -----------

Encoder PPR Rating:

Maximum Required Input Frequency: Hi-Resolution Stegmann Option: Encoder Voltage Supply: Hi-Resolution Feedback: Maximum Cable Length: RS-485 Interface: Customer-I/O Plug (P1) - Hi Res: Resolver Option: Excitation Frequency: Excitation Voltage: Operating Frequency Range: Feedback Voltage: Maximum Cable Length: User Available MemoryBase: With Memory Expansion Board: Battery: Serial Cable:

400 kHz Refer to specifications on 185 11.5V DC @ 130 mA Sine/Cosine 1V P-P Offset 2.5 182 m (600 ft.) Hi-Resolution Feedback Option card obtains the following information via the Hiperface RS-485 interface shortly after power-up: Address, Command Number, Mode, Number of turns, Number of Sine/Cos cycles, Checksum Allen-Bradley PN: S94262912 Weidmuller PN: BL3.50/90/12BK 2400 Hz 4.2526 Vrms 110 kHz 2V 300 mV 304.8 meters (1000 ft) 256 kbytes 768 kbytes 1756-BA1 (Allen-Bradley PN 94194801) 0.59g lithium 1761-CBLPM02 to 1761-NET-AIC 1761-CBLPA00 to 1761-NET-AIC 1756-CP3 directly to controller 1747-CP3 directly to controller category 3 (2) Up to (8) modules 640 mA maximum @ 5.1V DC 4100-CCF3

DriveLogix

Flex I/O Connection: FLEXBUS Current Output: Cable:

166

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Specifications

Appendix A

Drive Catalog Number Designations

The first three characters of the drive catalog numbers in the drive ratings and protection devices tables on the following pages designate the type of drive control. The information in the tables are valid for PowerFlex drives with both the 700H and 700S control. Therefore, the third character of the drive catalog number in each table is replaced with an x. For ordering purposes, drives with the 700H control are designated as 20C and drives with the 700S control are designated as 20D.

Drive Ratings
The tables on the following pages provide drive ratings (including continuous, 1 minute and 3 seconds), PWM frequency ratings, ambient operating temperatures and watts loss information.
Table 1 - 400 Volt AC Input Frames 914 Drive Ratings
Frame Drive Catalog Number kW Rating ND HD PWM Freq. kHz Temp. C Input Ratings Amps Output Amps Cont. 1 Min. 3 Sec. Watts Loss Watts

20xC261 20xC300 20xC385 20xC460 20xC500 20xC590 20xC650 20xC730 20xC820 20xC920 20xC1K0 20xC1K1 20xC1K3 20xC1K4 20xC1K7(1) 20xC2K1(1) 20xC2K7(1)

9 9 10 10 10 11 11 11 12 12 12 13 13 13 14 14 14

132 160 200 250 250 315 355 400 450 500 560 630 710 800 1000 1200 1600 -

110 132 160 200 250 250 315 355 400 450 500 560 630 710 900 1100 1300

2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 35 40 40 40 40 40 40 40 40 40 40 40 40

263 207 302 247 388 302 463 388 504 423 594 524 655 594 735 655 826 735 927 826 1038 927 1158 1038 1310 1158 1461 1209 1783 1612 2166 1954 2720 2317

261 205 300 245 385 300 460 385 500 420 590 520 650 590 730 650 820 730 920 820 1030 920 1150 1030 1300 1150 1450 1200 1770 1600 2150 1940 2700 2300

287 308 330 368 424 450 506 578 550 630 649 780 715 885 803 975 902 1095 1012 1230 1133 1370 1265 1545 1430 1725 1595 1800 1947 2400 2365 2910 2970 3287

410 410 450 490 600 600 770 770 750 840 956 956 1062 1062 1095 1170 1230 1314 1380 1476 1555 1600 1620 1620 2079 2079 2175 2400 2655 2880 3225 3492 3933 3933

2700 2700 3100 3100 4320 4320 5335 5335 5921 5921 6620 6620 7538 7538 8312 8312 9201 9201 10670 10670 11729 11729 13801 13801 15077 15077 16511 16511 24800 24800 29900 29900 39680 39680

(1) Not available with 700S Control.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

167

Appendix A

Specifications

Table 2 - 480 Volt AC Input Frames 914 Drive Ratings


Frame Drive Catalog Number 20xD261 20xD300 20xD385 20xD460 20xD500 20xD590 20xD650 20xD730 20xD820 20xD920 20xD1K0 20xD1K1 20xD1K3 20xD1K4 20xD1K7(1) 20xD2K1(1) 20xD2K7(1) HP Rating ND 200 250 300 350 450 500 500 600 700 800 900 1000 1200 1250 1500 1900 2300 HD 150 200 250 300 350 450 500 500 600 700 800 900 1000 1000 1400 1700 2000 PWM Freq. kHz 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Temp. C 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 35 40 40 40 40 40 40 40 40 40 40 40 40 Input Ratings Amps 252 207 290 247 372 302 444 388 483 423 570 524 628 594 705 655 792 735 888 826 994 927 1110 994 1255 1110 1400 1158 1709 1545 2076 1873 2607 2220 Output Amps Cont. 261 205 300 245 385 300 460 385 500 420 590 520 650 590 730 650 820 730 920 820 1030 920 1150 1030 1300 1150 1450 1200 1770 1600 2150 1940 2700 2300 1 Min. 287 308 330 368 424 450 506 578 550 630 649 780 715 885 803 975 902 1095 1012 1230 1133 1370 1265 1545 1430 1725 1595 1800 1947 2400 2365 2910 2970 3287 3 Sec. 410 410 450 490 600 600 770 770 750 840 956 956 1062 1062 1095 1170 1230 1314 1380 1476 1555 1600 1620 1620 2079 2079 2175 2400 2655 2880 3225 3492 3933 3933 Watts Loss Watts 2700 2700 3100 3100 4320 4320 5335 5335 5921 5921 6620 6620 7538 7538 8312 8312 9201 9201 10670 10670 11729 11729 13801 13801 15077 15077 16511 16511 24800 24800 29900 29900 39680 39680

9 9 10 10 10 11 11 11 12 12 12 13 13 13 14 14 14

(1) Not available with 700S Control.

168

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Specifications

Appendix A

Table 3 - 600 Volt AC Input Frames 914 Drive Ratings


Frame Drive Catalog Number 20xE170 20xE208 20xE261 20xE325 20xE385 20xE416 20xE460 20xE502 20xE590 20xE650 20xE750 20xE820(1) 20xE920 20xE1K0 20xE1K1 20xE1K5 20xE1K9(2) 20xE2K2(2) HP Rating ND 150 200 250 350 400 450 500 500 600 700 800 900 1000 1100 1300 1600 2000 2400 HD 150 150 200 250 350 350 400 500 500 650 700 700 900 1000 1100 1400 1600 2000 PWM Freq. kHz
(3)

Temp. C 40 40 35 40 40 40 40 40 40 40 35 40 40 40 40 40 35 35 40 40 40 40 35 35 40 40 40 40 35 35 40 40 40 40 30 30

9 9 10 10 10 10 11 11 11 12 12 12 13 13 13 14 14 14

(3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3)

Input Ratings Amps 164 139 201 164 252 201 314 252 372 314 402 314 444 372 485 444 570 485 628 570 724 628 792 628 888 792 994 888 1139 994 1448 1255 1834 1448 2172 1834

Output Amps Cont. 170 144 208 170 261 208 325 261 385 325 416 325 460 385 502 460 590 502 650 590 750 650 820 650 920 820 1030 920 1180 1030 1500 1300 1900 1500 2250 1900 1 Min. 187 216 230 250 287 312 358 392 424 488 458 488 506 578 552 690 649 753 715 885 825 975 902 975 1012 1230 1133 1380 1298 1463 1650 1950 2090 2250 2475 2782 3 Sec. 245 245 289 289 375 375 470 470 585 585 585 585 693 693 828 828 885 904 1062 1062 1170 1170 1170 1170 1380 1410 1545 1755 1755 1755 2250 2340 2700 2700 3335 3335

Watts Loss Watts 4206 4206 4751 4751 5527 5527 5622 5622 6345 6345 6925 6925 7539 7539 9502 9502 10570 10570 11082 11082 12690 12690 15907 15907 17306 17306 22500 22500 28500 28500 33400 33400

(1) 20DE820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz. (2) Not available with 700S Control. (3) Rated PWM for 700H control 1.5kHz, Rated PWM for 700S control 2.0kHz.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

169

Appendix A

Specifications

Table 4 - 690 Volt AC Input Frames 914 Drive Ratings


Frame Drive Catalog Number 20xF170 20xF208 20xF261 20xF325 20xF385 20xF416 20xF460 20xF502 20xF590 20xF650 20xF750 20xF820(1) 20xF920 20xF1K0 20xF1K1 20xF1K5 20xF1K9(2) 20xF2K2(2) kW Rating ND 160 200 250 315 355 400 450 500 560 630 710 800 900 1000 1100 1500 1800 2000 HD 132 160 200 250 315 315 355 400 500 560 630 630 800 900 1000 1300 1500 1800 PWM Freq. kHz 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Temp. C 40 40 35 40 40 40 40 40 40 40 35 40 40 40 40 40 35 35 40 40 40 40 35 35 40 40 40 40 35 35 40 40 40 40 30 30 Input Ratings Amps 171 145 210 171 263 210 327 263 388 327 419 327 463 388 506 463 594 506 655 594 756 655 826 655 927 826 1038 927 1189 1038 1511 1310 1914 1511 2267 1914 Output Amps Cont. 170 144 208 170 261 208 325 261 385 325 416 325 460 385 502 460 590 502 650 590 750 650 820 650 920 820 1030 920 1180 1030 1500 1300 1900 1500 2250 1900 1 Min. 187 216 230 250 287 312 358 392 424 488 458 488 506 578 552 690 649 753 715 885 825 975 902 975 1012 1230 1133 1380 1298 1463 1650 1950 2090 2250 2475 2782 3 Sec. 245 245 289 289 375 375 470 470 585 585 585 585 693 693 828 828 885 904 1062 1062 1170 1170 1170 1170 1380 1410 1545 1755 1755 1755 2250 2340 2700 2700 3335 3335 Watts Loss Watts 4206 4206 4751 4751 5527 5527 5622 5622 6345 6345 6925 6925 7539 7539 9502 9502 10570 10570 11082 11082 12690 12690 15907 15907 17306 17306 22500 22500 28500 28500 33400 33400

9 9 10 10 10 10 11 11 11 12 12 12 13 13 13 14 14 14

(1) 20DF820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz. (2) Not available with 700S Control.

170

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Specifications

Appendix A

Table 5 - 540 Volt DC Input Frames 914 Drive Ratings


Frame Drive Catalog Number 20xH261 20xH300 20xH385 20xH460 20xH500 20xH590 20xH650 20xH730 20xH820 20xH920 20xH1K0 20xH1K1 20xH1K3 20xH1K4 20xH1K7(1) 20xH2K1(1) 20xH2K7(1) kW Rating ND HD 132 110 160 132 200 160 250 200 250 250 315 250 355 315 400 355 450 400 500 450 560 500 630 560 710 630 800 710 1000 900 1200 1100 1600 1300 PWM Freq. kHz 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Temp. C 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 35 40 40 40 40 40 40 40 40 40 40 40 40 DC Input Ratings Amps 307 241 353 288 453 353 541 453 589 494 695 612 765 695 859 765 965 859 1083 965 1213 1083 1354 1213 1530 1354 1707 1413 2084 1883 2531 2284 3178 2708 Output Amps Cont. 1 Min. 261 287 205 308 300 330 245 368 385 424 300 450 460 506 385 578 500 550 420 630 590 649 520 780 650 715 590 885 730 803 650 975 820 902 730 1095 920 1012 820 1230 1030 1133 920 1370 1150 1265 1030 1545 1300 1430 1150 1725 1450 1595 1200 1800 1770 1947 1600 2400 2150 2365 1940 2910 2700 2970 2300 3287 3 Sec. 410 410 450 490 600 600 770 770 750 840 956 956 1062 1062 1095 1170 1230 1314 1380 1476 1555 1600 1620 1620 2079 2079 2175 2400 2655 2880 3225 3492 3933 3933

9 9 10 10 10 11 11 11 12 12 12 13 13 13 14 14 14

(1) Not available with 700S Control.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

171

Appendix A

Specifications

Table 6 - 650 Volt DC Input Frames 914 Drive Ratings


Frame Drive Catalog Number 20xJ261 20xJ300 20xJ385 20xJ460 20xJ500 20xJ590 20xJ650 20xJ730 20xJ820 20xJ920 20xJ1K0 20xJ1K1 20xJ1K3 20xJ1K4 20xJ1K7(1) 20xJ2K1(1) 20xJ2K7(1) HP Rating ND HD 200 150 250 200 300 250 350 300 450 350 500 450 500 500 600 500 700 600 800 700 900 800 1000 900 1200 1000 1250 1000 1500 1400 1900 1700 2300 2000 PWM Freq. kHz 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Temp. C 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 35 40 40 40 40 40 40 40 40 40 40 40 40 DC Input Ratings Amps 294 231 338 294 434 338 519 434 564 474 666 587 733 666 824 733 925 824 1038 925 1162 1038 1297 1162 1467 1297 1636 1354 1997 1805 2425 2189 3046 2595 Output Amps Cont. 1 Min. 261 287 205 308 300 330 245 368 385 424 300 450 460 506 385 578 500 550 420 630 590 649 520 780 650 715 590 885 730 803 650 975 820 902 730 1095 920 1012 820 1230 1030 1133 920 1370 1150 1265 1030 1545 1300 1430 1150 1725 1450 1595 1200 1800 1770 1947 1600 2400 2150 2365 1940 2910 2700 2970 2300 3287 3 Sec. 410 410 450 490 600 600 770 770 750 840 956 956 1062 1062 1095 1170 1230 1314 1380 1476 1555 1600 1620 1620 2079 2079 2175 2400 2655 2880 3225 3492 3933 3933

9 9 10 10 10 11 11 11 12 12 12 13 13 13 14 14 14

(1) Not available with 700S Control.

172

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Specifications

Appendix A

Table 7 - 810 Volt DC Input Frames 914 Drive Ratings


Frame Drive Catalog Number 20xK170 20xK208 20xK261 20xK325 20xK385 20xK416 20xK460 20xK502 20xK590 20xK650 20xK750 20xK820 (1) 20xK920 20xK1K0 20xK1K1 20xK1K5 20xK1K9(2) 20xK2K2(2) HP Rating ND HD 150 150 200 150 250 200 350 250 400 350 450 350 500 400 500 500 600 500 700 650 800 700 900 700 1000 900 1100 1000 1300 1100 1600 1400 2000 1600 2400 2000 PWM Freq. kHz 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Temp. C 40 40 35 40 40 40 40 40 40 40 35 40 40 40 40 40 35 35 40 40 40 40 35 35 40 40 40 40 35 35 40 40 40 40 30 30 DC Input Ratings Amps 192 162 235 192 294 235 367 294 434 367 469 367 519 434 566 519 666 566 733 666 846 733 925 733 1038 925 1162 1038 1331 1162 1692 1467 2143 1692 2538 2143 Output Amps Cont. 1 Min. 170 187 144 216 208 230 170 250 261 287 208 312 325 358 261 392 385 424 325 488 416 458 325 488 460 506 385 578 502 552 460 690 590 649 502 753 650 715 590 885 750 825 650 975 820 902 650 975 920 1012 820 1230 1030 1133 920 1380 1180 1298 1030 1463 1500 1650 1300 1950 1900 2090 1500 2250 2250 2475 1900 2782 3 Sec. 245 245 289 289 375 375 470 470 585 585 585 585 693 693 828 828 885 904 1062 1062 1170 1170 1170 1170 1380 1410 1545 1755 1755 1755 2250 2340 2700 2700 3335 3335

9 9 10 10 10 10 11 11 11 12 12 12 13 13 13 14 14 14

(1) 20DK820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz. (2) Not available with 700S Control.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

173

Appendix A

Specifications

Table 8 - 932 Volt DC Input Frames 914 Drive Ratings


Frame Drive Catalog Number 20xM170 20xM208 20xM261 20xM325 20xM385 20xM416 20xM460 20xM502 20xM590 20xM650 20xM750 20xM820(1) 20xM920 20xM1K0 20xM1K1 20xM1K5 20xM1K9(2) 20xM2K2(2) kW Rating HD 132 160 200 250 315 315 355 400 500 560 630 630 800 900 1000 1300 1500 1800 PWM Freq. kHz 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Temp. C 40 40 35 40 40 40 40 40 40 40 35 40 40 40 40 40 35 35 40 40 40 40 35 35 40 40 40 40 35 35 40 40 40 40 30 30 DC Input Ratings Amps 200 170 245 200 307 245 383 307 453 383 490 383 542 453 591 542 695 591 765 695 883 765 965 765 1038 925 1162 1038 1331 1162 1766 1530 2237 1766 2649 2237 Output Amps Cont. 170 144 208 170 261 208 325 261 385 325 416 325 460 385 502 460 590 502 650 590 750 650 820 650 920 820 1030 920 1180 1030 1500 1300 1900 1500 2250 1900 1 Min. 187 216 230 250 287 312 358 392 424 488 458 488 506 578 552 690 649 753 715 885 825 975 902 975 1012 1230 1133 1380 1298 1463 1650 1950 2090 2250 2475 2782 3 Sec. 245 245 289 289 375 375 470 470 585 585 585 585 693 693 828 828 885 904 1062 1062 1170 1170 1170 1170 1380 1410 1545 1755 1755 1755 2250 2340 2700 2700 3335 3335

ND 9 160 9 200 10 250 10 315 10 355 10 400 11 450 11 500 11 560 12 630 12 710 12 800 13 900 13 1000 13 1100 14 1500 14 1800 14 2000

(1) 20DM820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz. (2) Not available with 700S Control.

174

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Specifications

Appendix A

Drive Fuse & Circuit Breaker Ratings

The tables on the following pages provide recommended AC line input fuse and circuit breaker information. See Fusing and Circuit Breakers below for UL and IEC requirements. Sizes listed are the recommended sizes based on 40 C (104 F) and the U.S. NEC. Other country, state, or local codes can require different ratings. Tables with DC link fuse recommendations for DC input drives are also provided.

Fusing
The recommended fuse types are listed below. If available current ratings do not match those listed in the tables provided, choose the next higher fuse rating. IEC BS88 (British Standard) Parts 1 & 2, EN60269-1, Parts 1 & 2(1), type gG or equivalent should be used. UL - UL requirements specify that UL Class CC, T, or J fuses must be used for all drives in this section.

Circuit Breakers
The non-fuse listings in the following tables include inverse time circuit breakers and instantaneous trip circuit breakers (motor circuit protectors). If one of these is chosen as the desired protection method, the following requirements apply: IEC Both types of circuit breakers are acceptable for IEC installations. UL Only inverse time circuit breakers are acceptable for UL installations.

(1) Typical designations include, but may not be limited to the following; Parts 1 & 2: AC, AD, BC, BD, CD, DD, ED, EFS, EF, FF, FG, GF, GG, GH.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

175

Appendix A

Specifications

Table 9 - 400 Volt AC Input Frames 914 Drive Protection Devices


Frame Drive Catalog Number 20xC261 20xC300 20xC385 20xC460 20xC500 20xC590 kW Rating ND 132 160 200 250 250 315 20xC650 11 355 20xC730 11 400 20xC820 12 450 20xC920 12 500 20xC1K0 12 560 20xC1K1 13 630 20xC1K3 13 710 20xC1K4 13 800 20xC1K7(1) 14 1000 20xC2K1(1) 14 1200 20xC2K7(1) 14 1600 (1) (2) (3) (4) HD 110 132 160 200 250 250 315 355 400 450 500 560 630 710 900 1100 1300 Input Ratings Amps 263 207 302 247 388 302 463 388 504 423 594 524 655 594 735 655 826 735 927 826 1038 927 1158 1038 1310 1158 1461 1209 1783 1612 2166 1954 2720 2317 Dual Element Time Delay Fuse Min. (2) 350 275 400 350 500 400 600 500 650 550 750 (1 per phs) 375 (2 per phs) 700 (1 per phs) 350 (2 per phs) 850 (1 per phs) 425 (2 per phs) 750 (1 per phs) 375 (2 per phs) 1000 (1 per phs) 500 (2 per phs) 850 (1 per phs) 425 (2 per phs) 1100 (1 per phs) 550 (2 per phs) 1000 (1 per phs) 500 (2 per phs) 1200 (1 per phs) 600 (2 per phs) 1100 (1 per phs) 550 (2 per phs) 1350 (1 per phs) 700 (2 per phs) 1200 (1 per phs) 600 (2 per phs) 1350 (1 per phs) 700 (2 per phs) 1500 (1 per phs) 750 (2 per phs) 1700 (1 per phs) 850 (2 per phs) 1500 (1 per phs) 750 (2 per phs) 1900 (1 per phs) 950 (2 per phs) 1600 (1 per phs) 800 (2 per phs) 2500 (1 per phs) 825 (3 per phs) 2100 (1 per phs) 700 (3 per phs) 3000 (1 per phs) 1000 (3 per phs) 2500 (1 per phs) 825 (3 per phs) 3500 (1 per phs) 1200 (3 per phs) 3000 (1 per phs) 1000 (3 per phs) Max. (3) 550 450 650 500 850 650 1000 850 1100 900 1300 1100 1400 1300 1600 1400 1800 1600 2000 1800 2300 2000 2300 2500 2900 2500 3000 2700 3900 3500 4800 4300 6000 5000 Non-Time Delay Fuse Min. (2) 350 275 400 350 500 400 600 500 650 550 750 (1 per phs) 375 (2 per phs) 700 (1 per phs) 350 (2 per phs) 850 (1 per phs) 425 (2 per phs) 750 (1 per phs) 375 (2 per phs) 1000 (1 per phs) 500 (2 per phs) 850 (1 per phs) 425 (2 per phs) 1100 (1 per phs) 550 (2 per phs) 1000 (1 per phs) 500 (2 per phs) 1200 (1 per phs) 600 (2 per phs) 1100 (1 per phs) 550 (2 per phs) 1350 (1 per phs) 700 (2 per phs) 1200 (1 per phs) 600 (2 per phs) 1350 (1 per phs) 700 (2 per phs) 1500 (1 per phs) 750 (2 per phs) 1700 (1 per phs) 850 (2 per phs) 1500 (1 per phs) 750 (2 per phs) 1900 (1 per phs) 950 (2 per phs) 1600 (1 per phs) 800 (2 per phs) 2500 (1 per phs) 825 (3 per phs) 2100 (1 per phs) 700 (3 per phs) 3000 (1 per phs) 1000 (3 per phs) 2500 (1 per phs) 825 (3 per phs) 3500 (1 per phs) 1200 (3 per phs) 3000 (1 per phs) 1000 (3 per phs) Max.(3) 700 600 900 700 1100 900 1300 1100 1500 1200 1700 1500 1900 1700 2100 1900 2400 2100 2700 2400 3000 2700 3000 3400 3900 3400 4300 3600 5300 4800 6400 5800 8000 6900 Bussmann Style SemiConductor Fuse 170M5813 170M5813 170M5813 170M5813 170M5813 170M5813 170M8547 170M8547 170M8547 170M8547 170M5813 170M5813 170M5813 170M5813 170M5813 170M5813 170M8547 170M8547 170M8547 170M8547 170M8547 170M8547 170M6466 (4) 170M6466 (4) 170M6466 (4) 170M6466 (4) 170M6466 (4) 170M6466 (4) 170M6466 170M6466 170M6466 170M6466 170M6466 170M6466 Circuit Breaker (5) Max. (6) 700 600 900 700 1100 900 1300 1100 1500 1200 1700 1500 1900 1700 2100 1900 2400 2100 2700 2400 3000 2700 3000 3400 3900 3400 4300 3600 5300 4800 6400 5800 8000 6900 Motor Circuit Protector (7) Max. 400 300 400 400 600 400 600 600 700 600 800 700 1000 800 1200 1000 1200 1200 1200 1200 1400 1200 1400 1500 1700 1500 1900 1600 2500 2100 3000 2500 3500 3000

9 9 10 10 10 11

Not available with 700S Control. Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping. Maximum protection device size is the highest rated device that supplies drive protection. These fuses and disconnect are supplied with AC input NEMA/UL Type 1 drives.

176

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Specifications

Appendix A

(5) Inverse time breaker. Ratings shown are maximum. (6) Maximum allowable rating by US NEC. Exact size must be chosen for each installation. (7) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.

Table 10 - 480 Volt AC Input Frames 914 Drive Protection Devices


Frame Drive Catalog Number 20xD261 20xD300 20xD385 20xD460 20xD500 20xD590 HP Rating ND 200 250 300 350 450 500 20xD650 11 500 20xD730 11 600 20xD820 12 700 20xD920 12 800 20xD1K0 12 900 20xD1K1 13 1000 20xD1K3 13 1200 20xD1K4 13 1250 20xD1K7(1) 14 1500 20xD2K1(1) 14 1900 20xD2K7(1) 14 2300 HD 150 200 250 300 350 450 500 500 600 700 800 900 1000 1000 1400 1700 2000 Input Ratings Amps 252 207 290 247 372 302 444 388 483 423 570 524 628 594 705 655 792 735 888 826 994 927 1110 994 1255 1110 1400 1158 1709 1545 2076 1873 2607 2220 Dual Element Time Delay Fuse Min. (2) 350 275 400 350 500 400 600 500 650 550 750 (1 per phs) 375 (2 per phs) 700 (1 per phs) 350 (2 per phs) 800 (1 per phs) 400 (2 per phs) 750 (1 per phs) 375 (2 per phs) 900 (1 per phs) 450 (2 per phs) 850 (1 per phs) 425 (2 per phs) 1000 (1 per phs) 500 (2 per phs) 900 (1 per phs) 475 (2 per phs) 1200 (1 per phs) 600 (2 per phs) 1100 (1 per phs) 550 (2 per phs) 1300 (1 per phs) 650 (2 per phs) 1200 (1 per phs) 600 (2 per phs) 1400 (1 per phs) 700 (2 per phs) 1300 (1 per phs) 650 (2 per phs) 1600 (1 per phs) 800 (2 per phs) 1400 (1 per phs) 700 (2 per phs) 1800 (1 per phs) 900 (2 per phs) 1500 (1 per phs) 750 (2 per phs) 2200 (1 per phs) 750 (3 per phs) 2000 (1 per phs) 675 (3 per phs) 2600 (1 per phs) 900 (3 per phs) 2400 (1 per phs) 800 (3 per phs) 3000 (1 per phs) 1100 (3 per phs) 2800 (1 per phs) 900 (3 per phs) Max. (3) 550 450 650 550 850 650 1000 850 1000 900 1300 1100 1400 1300 1600 1400 1800 1600 2000 1800 2300 2000 2500 2300 2900 2500 3200 2700 3800 3600 4800 4300 6000 5000 Non-Time Delay Fuse Min. (2) 350 275 400 350 500 400 600 500 650 550 750 (1 per phs) 375 (2 per phs) 700 (1 per phs) 350 (2 per phs) 800 (1 per phs) 400 (2 per phs) 750 (1 per phs) 375 (2 per phs) 900 (1 per phs) 450 (2 per phs) 850 (1 per phs) 425 (2 per phs) 1000 (1 per phs) 500 (2 per phs) 900 (1 per phs) 475 (2 per phs) 1200 (1 per phs) 600 (2 per phs) 1100 (1 per phs) 550 (2 per phs) 1300 (1 per phs) 650 (2 per phs) 1200 (1 per phs) 600 (2 per phs) 1400 (1 per phs) 700 (2 per phs) 1300 (1 per phs) 650 (2 per phs) 1600 (1 per phs) 800 (2 per phs) 1400 (1 per phs) 700 (2 per phs) 1800 (1 per phs) 900 (2 per phs) 1500 (1 per phs) 750 (2 per phs) 2200 (1 per phs) 750 (3 per phs) 2000 (1 per phs) 675 (3 per phs) 2600 (1 per phs) 900 (3 per phs) 2400 (1 per phs) 800 (3 per phs) 3000 (1 per phs) 1100 (3 per phs) 2800 (1 per phs) 900 (3 per phs) Max. (3) 700 600 900 700 1100 900 1300 1100 1500 1200 1700 1500 1900 1700 2100 1900 2400 2100 2700 2400 3000 2700 3400 3000 3900 3400 4300 3600 5300 4800 6400 5800 8000 6900 Bussmann Style SemiConductor Fuse 170M5813 170M5813 170M5813 170M5813 170M5813 170M5813 170M8547 170M8547 170M8547 170M8547 170M5813 170M5813 170M5813 170M5813 170M5813 170M5813 170M8547 170M8547 170M8547 170M8547 170M8547 170M8547 170M6466 (4) 170M6466 (4) 170M6466 (4) 170M6466 (4) 170M6466 (4) 170M6466 (4) 170M6466 170M6466 170M6466 170M6466 170M6466 170M6466 Circuit Breaker (5) Max. (6) 700 600 900 700 1100 900 1300 1100 1500 1200 1700 1500 1900 1700 2100 1900 2400 2100 2700 2400 3000 2700 3400 3000 3900 3400 4300 3600 5300 4800 6400 5800 8000 6900 Motor Circuit Protector (7) Max. 400 300 400 400 600 400 600 600 700 600 800 700 800 800 900 900 1000 1000 1200 1200 1300 1200 1400 1300 1600 1400 1800 1500 2200 2000 2600 2400 3300 2800

9 9 10 10 10 11

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

177

Appendix A

Specifications

(1) (2) (3) (4) (5) (6) (7)

Not available with 700S Control. Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping. Maximum protection device size is the highest rated device that supplies drive protection. These fuses and disconnect are supplied with AC input NEMA/UL Type 1 drives. Inverse time breaker. Ratings shown are maximum. Maximum allowable rating by US NEC. Exact size must be chosen for each installation. Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.

Table 11 - 600 Volt AC Input Frames 914 Drive Protection Devices


Frame Drive Catalog Number 20xE170 20xE208 20xE261 20xE325 20xE385 20xE416 20xE460 HP Rating ND 150 200 250 350 400 450 500 20xE502 11 500 20xE590 11 600 20xE650 12 700 20xE750 12 800 20xE820(1) 12 900 20xE920 13 1000 20xE1K0 13 1100 20xE1K1 13 1300 20xE1K5 14 1000 HD 150 150 200 250 350 350 400 500 500 650 700 700 900 1000 1100 900 Input Ratings Amps 164 139 201 164 252 201 314 252 372 314 402 314 444 372 485 444 570 485 628 570 724 628 792 628 888 792 994 888 1139 994 1448 1255 Dual Element Time Delay Fuse Min. (3) 225 175 275 225 325 275 400 325 475 400 525 400 575 (1 per phs) 300 (2 per phs) 475 (1 per phs) 250 (2 per phs) 625 (1 per phs) 325 (2 per phs) 575 (1 per phs) 300 (2 per phs) 725 (1 per phs) 375(2 per phs) 625 (1 per phs) 325 (2 per phs) 800 (1 per phs) 400 (2 per phs) 725 (1 per phs) 375 (2 per phs) 950 (1 per phs) 475 (2 per phs) 800 (1 per phs) 400 (2 per phs) 1000 (1 per phs) 500 (2 per phs) 800 (1 per phs) 400 (2 per phs) 1200 (1 per phs) 600 (2 per phs) 1000 (1 per phs) 500 (2 per phs) 1300 (1 per phs) 650 (2 per phs) 1200 (1 per phs) 600 (2 per phs) 1500 (1 per phs) 750 (2 per phs) 1300 (1 per phs) 650 (2 per phs) 1900 (1 per phs) 650 (3 per phs) 1600 (1 per phs) 550 (3 per phs) Max. (4) 375 300 450 375 575 450 725 575 850 725 900 725 1000 850 1100 1000 1300 1100 1400 1300 1600 1400 1800 1400 2000 1800 2300 2000 2600 2200 3300 2900 Non-Time Delay Fuse Min. (3) 225 175 275 225 325 275 400 325 475 400 525 400 575 (1 per phs) 300 (2 per phs) 475 (1 per phs) 250 (2 per phs) 625 (1 per phs) 325 (2 per phs) 575 (1 per phs) 300 (2 per phs) 725 (1 per phs) 375(2 per phs) 625 (1 per phs) 325 (2 per phs) 800 (1 per phs) 400 (2 per phs) 725 (1 per phs) 375 (2 per phs) 950 (1 per phs) 475 (2 per phs) 800 (1 per phs) 400 (2 per phs) 1000 (1 per phs) 500 (2 per phs) 800 (1 per phs) 400 (2 per phs) 1200 (1 per phs) 600 (2 per phs) 1000 (1 per phs) 500 (2 per phs) 1300 (1 per phs) 650 (2 per phs) 1200 (1 per phs) 600 (2 per phs) 1500 (1 per phs) 750 (2 per phs) 1300 (1 per phs) 650 (2 per phs) 1900 (1 per phs) 650 (3 per phs) 1600 (1 per phs) 550 (3 per phs) Max.(4) 500 500 600 500 775 600 950 775 1100 950 1200 950 1300 1100 1500 1300 1700 1500 1900 1700 2200 1900 2400 1900 2700 2400 3000 2700 3500 3000 4500 3900 Bussmann Style SemiConductor Fuse 170M3819 170M3819 170M3819 170M3819 170M5813 170M5813 170M5813 170M5813 170M5813 170M5813 170M5813 170M5813 170M8547 170M8547 170M8547 170M8547 170M5813 170M5813 170M5813 170M5813 170M5813 170M5813 170M5813 170M5813 170M6466 (5) 170M6466 (5) 170M6466 (5) 170M6466 (5) 170M6466 (5) 170M6466 (5) 170M6466 170M6466 Circuit Breaker (6) Max (7) 500 500 600 500 700 600 900 750 1100 900 1200 900 1300 1100 1500 1300 1700 1500 1900 1700 2200 1900 2400 1900 2700 2400 3000 2700 3500 3000 4500 3900 Motor Circuit Protector (8) Max. 250 200 300 250 350 300 450 400 500 450 550 450 600 500 650 600 800 700 900 800 1000 900 1100 900 1200 1100 1300 1200 1500 1300 1900 1700

9 9 10 10 10 10 11

178

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Specifications

Appendix A

Frame

Drive Catalog Number 20xE1K9


(2)

HP Rating ND 1100 HD 1000 1100

14

Input Ratings Amps 1834 1448 2172 1834

Dual Element Time Delay Fuse Min. (3) 2300 (1 per phs) 800 (3 per phs) 1900 (1 per phs) 650 (3 per phs) 2800 (1 per phs) 950 (3 per phs) 2300 (1 per phs) 800 (3 per phs) Max. (4) 4200 3200 5000 4200

Non-Time Delay Fuse Min. (3) 2300 (1 per phs) 800 (3 per phs) 1900 (1 per phs) 650 (3 per phs) 2800 (1 per phs) 950 (3 per phs) 2300 (1 per phs) 800 (3 per phs) Max.(4) 5700 4500 6700 5700

Bussmann Style SemiConductor Fuse 170M6466 170M6466 170M6466 170M6466

Circuit Breaker (6) Max (7) 5700 4500 6700 5700

Motor Circuit Protector (8) Max. 2400 1900 2900 2400

20xE2K2(2)

14

1200

(1) (2) (3) (4) (5) (6) (7) (8)

20DE820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz. Not available with 700S Control. Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping. Maximum protection device size is the highest rated device that supplies drive protection. These fuses and disconnect are supplied with AC input NEMA/UL Type 1 drives. Inverse time breaker. Ratings shown are maximum. Maximum allowable rating by US NEC. Exact size must be chosen for each installation. Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.

Table 12 - 690 Volt AC Input Frames 914 Drive Protection Devices


Frame Drive Catalog Number 20xF170 20xF208 20xF261 20xF325 20xF385 20xF416 20xF460 kW Rating ND 160 200 250 315 355 400 500 20xF502 11 560 20xF590 11 580 20xF650 12 630 20xF750 12 710 20xF820(1) 12 800 20xF920 13 900 HD 132 160 200 250 315 315 400 500 500 560 630 630 800 Input Ratings Amps 171 145 210 171 263 210 327 263 388 327 419 327 463 388 506 463 594 506 655 594 756 655 826 655 927 826 Dual Element Time Delay Fuse Min. (3) 225 200 275 225 350 275 425 350 500 425 525 425 600 (1 per phs) 300 (2 per phs) 500 (1 per phs) 250 (2 per phs) 650 (1 per phs) 325 (2 per phs) 600 (1 per phs) 300 (2 per phs) 750 (1 per phs) 375 (2 per phs) 650 (1 per phs) 325 (2 per phs) 850 (1 per phs) 425 (2 per phs) 750 (1 per phs) 375 (2 per phs) 950 (1 per phs) 475 (2 per phs) 850 (1 per phs) 425 (2 per phs) 1100 (1 per phs) 550 (2 per phs) 850 (1 per phs) 425 (2 per phs) 1200 (1 per phs) 600 (2 per phs) 1100 (1 per phs) 550 (2 per phs) Max. (4) 375 300 450 375 575 450 725 575 850 725 900 700 1000 850 1100 1000 1300 1100 1400 1300 1600 1400 1800 1400 2000 1800 Non-Time Delay Fuse Min. (3) 225 200 275 225 350 275 425 350 500 425 525 425 600 (1 per phs) 300 (2 per phs) 500 (1 per phs) 250 (2 per phs) 650 (1 per phs) 325 (2 per phs) 600 (1 per phs) 300 (2 per phs) 750 (1 per phs) 375 (2 per phs) 650 (1 per phs) 325 (2 per phs) 850 (1 per phs) 425 (2 per phs) 750 (1 per phs) 375 (2 per phs) 950 (1 per phs) 475 (2 per phs) 850 (1 per phs) 425 (2 per phs) 1100 (1 per phs) 550 (2 per phs) 850 (1 per phs) 425 (2 per phs) 1200 (1 per phs) 600 (2 per phs) 1100 (1 per phs) 550 (2 per phs) Max. (4) 500 500 600 500 775 600 950 775 1100 950 1200 950 1300 1100 1500 1300 1700 1500 1900 1700 2200 1900 2400 1900 2700 2400 Bussmann Style SemiConductor Fuse 170M3819 170M3819 170M3819 170M3819 170M5813 170M5813 170M5813 170M5813 170M5813 170M5813 170M5813 170M5813 170M8547 170M8547 170M8547 170M8547 170M5813 170M5813 170M5813 170M5813 170M5813 170M5813 170M5813 170M5813 170M6466 (5) 170M6466 (5) Circuit Breaker (6) Max. (7) 500 400 600 500 750 600 900 750 1100 900 1200 900 1300 1100 1500 1300 1700 1500 1900 1700 2200 1900 2400 1900 2700 2400 Motor Circuit Protector (8) Max. 250 200 300 250 350 300 450 400 500 450 550 450 600 500 650 600 800 700 900 800 1000 900 1100 900 1200 1100

9 9 10 10 10 10 11

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

179

Appendix A

Specifications

Frame

Drive Catalog Number 20xF1K0

kW Rating ND 1000 HD 900 1000 1300 1500 1800

13

Input Ratings Amps 1038 927 1189 1038 1511 1310 1914 1511 2267 1914

Dual Element Time Delay Fuse Min. (3) 1300 (1 per phs) 650 (2 per phs) 1200 (1 per phs) 600 (2 per phs) 1500 (1 per phs) 750 (2 per phs) 1300 (1 per phs) 650 (2 per phs) 1900 (1 per phs) 650 (3 per phs) 1700 (1 per phs) 575 (3 per phs) 2400 (1 per phs) 800 (3 per phs) 1900 (1 per phs) 650 (3 per phs) 2900 (1 per phs) 950 (3 per phs) 2400 (1 per phs) 800 (3 per phs) Max. (4) 2300 2000 2600 2300 3300 2900 4200 3200 5000 4200

Non-Time Delay Fuse Min. (3) 1300 (1 per phs) 650 (2 per phs) 1200 (1 per phs) 600 (2 per phs) 1500 (1 per phs) 750 (2 per phs) 1300 (1 per phs) 650 (2 per phs) 1900 (1 per phs) 650 (3 per phs) 1700 (1 per phs) 575 (3 per phs) 2400 (1 per phs) 800 (3 per phs) 1900 (1 per phs) 650 (3 per phs) 2900 (1 per phs) 950 (3 per phs) 2400 (1 per phs) 800 (3 per phs) Max. (4) 3000 2700 3500 3000 4500 3900 5700 4500 6700 5700

Bussmann Style SemiConductor Fuse 170M6466 (5) 170M6466 (5) 170M6466 (5) 170M6466 (5) 170M6466 170M6466 170M6466 170M6466 170M6466 170M6466

Circuit Breaker (6) Max. (7) 3000 2700 3500 3000 4500 3900 5700 4500 6700 5700

Motor Circuit Protector (8) Max. 1300 1200 1500 1300 1900 1700 2400 1900 2900 2400

20xF1K1

13

1100

20xF1K5

14

1500

20xF1K9(2)

14

1800

20xF2K2(2)

14

2000

(1) (2) (3) (4) (5) (6) (7) (8)

20DF820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz. Not available with 700S Control. Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping. Maximum protection device size is the highest rated device that supplies drive protection. These fuses and disconnect are supplied with AC input NEMA/UL Type 1 drives. Inverse time breaker. Ratings shown are maximum. Maximum allowable rating by US NEC. Exact size must be chosen for each installation. Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.

Table 13 - 540 Volt DC Input Frames 914 Drive Protection Devices


Drive Catalog Number Frame kW Rating ND HD 20xH261 9 132 110 20xH300 9 160 132 20xH385 10 200 160 20xH460 10 250 200 20xH500 10 250 250 20xH590 11 315 250 20xH650 11 355 315 20xH730 11 400 355 20xH820 12 450 400 20xH920 12 500 450 20xH1K0 12 560 500 20xH1K1 13 630 560 20xH1K3 13 710 630 180 DC Input Ratings Amps 307 241 353 288 453 353 541 453 589 494 695 612 765 695 859 765 965 859 1083 965 1213 1083 1354 1213 1530 1354 Fuse 500 500 630 630 700 700 900 900 500 (2 per phs) 500 (2 per phs) 550 (2 per phs) 550 (2 per phs) 630 (2 per phs) 630 (2 per phs) 700 (2 per phs) 700 (2 per phs) 700 (2 per phs) 700 (2 per phs) 550 (3 per phs) 550 (3 per phs) 630 (3 per phs) 630 (3 per phs) 2400 2400 2400 2400 Bussmann Style Fuse 170M6608 170M6608 170M6610 170M6610 170M6611 170M6611 170M6613 170M6613 170M6608 170M6608 170M6609 170M6609 170M6610 170M6610 170M6611 170M6611 170M6611 170M6611 170M6609 170M6609 170M6610 170M6610 170M7107 170M7107 170M7107 170M7107

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Specifications

Appendix A

Drive Catalog Number Frame kW Rating ND HD 20xH1K4 13 800 710 20xH1K7(1) 14 1000 900 20xH2K1(1) 14 1200 1100 20xH2K7(1) 14 1600 1300
(1) Not available with 700S Control.

DC Input Ratings Amps 1707 1413 2084 1883 2531 2284 3178 2708

Fuse 2400 2400

Bussmann Style Fuse 170M7107 170M7107 170M8610 170M8610 170M8610 170M8610 170M8610 170M8610

Table 14 - 650 Volt DC Input Frames 914 Drive Protection Devices


Drive Catalog Number Frame HP Rating ND HD 20xJ261 9 200 150 20xJ300 9 250 200 20xJ385 10 300 250 20xJ460 10 350 300 20xJ500 10 450 350 20xJ590 11 500 450 20xJ650 11 500 500 20xJ730 11 600 500 20xJ820 12 700 600 20xJ920 12 800 700 20xJ1K0 12 900 800 20xJ1K1 13 1000 900 20xJ1K3 13 1200 1000 20xJ1K4 13 1250 1000 20xJ1K7(1) 14 1500 1400 20xJ2K1(1) 14 1900 1700 20xJ2K7(1) 14 2300 2000
(1) Not available with 700S Control.

DC Input Ratings Amps 294 231 338 294 434 338 519 434 564 474 666 587 733 666 824 733 925 824 1038 925 1162 1038 1297 1162 1467 1297 1636 1354 1997 1805 2425 2189 3046 2595

Fuse 500 500 630 630 700 700 900 900 500 (2 per phs) 500 (2 per phs) 550 (2 per phs) 550 (2 per phs) 630 (2 per phs) 630 (2 per phs) 700 (2 per phs) 700 (2 per phs) 700 (2 per phs) 700 (2 per phs) 550 (3 per phs) 550 (3 per phs) 630 (3 per phs) 630 (3 per phs) 2400 2400 2400 2400 2400 2400

Bussmann Style Fuse 170M6608 170M6608 170M6610 170M6610 170M6611 170M6611 170M6613 170M6613 170M6608 170M6608 170M6609 170M6609 170M6610 170M6610 170M6611 170M6611 170M6611 170M6611 170M6609 170M6609 170M6610 170M6610 170M7107 170M7107 170M7107 170M7107 170M7107 170M7107 170M8610 170M8610 170M8610 170M8610 170M8610 170M8610

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

181

Appendix A

Specifications

Table 15 - 810 Volt DC Input Frames 914 Drive Protection Devices


Drive Catalog Number Frame HP Rating ND HD 20xK170 9 150 150 20xK208 9 200 150 20xK261 10 250 200 20xK325 10 350 250 20xK385 10 400 350 20xK416 10 450 350 20xK460 11 500 400 20xK502 11 500 500 20xK590 11 600 500 20xK650 12 700 650 20xK750 12 800 700 20xK820 (1) 12 900 700 20xK920 13 1000 900 20xK1K0 13 1100 1000 20xK1K1 13 1300 1100 20xK1K5 14 1600 1400 20xK1K9(2) 14 2000 1600 20xK2K2(2) 14 2400 2000 DC Input Ratings Amps 192 162 235 192 294 235 367 294 434 367 469 367 519 434 566 519 666 566 733 666 846 733 925 733 1038 925 1162 1038 1331 1162 1692 1467 2143 1692 2538 2143 Fuse 400 400 450 450 450 450 550 550 700 700 800 800 450 (2 per phs) 450 (2 per phs) 500 (2 per phs) 500 (2 per phs) 500 (2 per phs) 500 (2 per phs) 500 (2 per phs) 500 (2 per phs) 630 (2 per phs) 630 (2 per phs) 630 (2 per phs) 630 (2 per phs) 2400 2400 2400 2400 2400 2400 Bussmann Style Fuse 170M5608 170M5608 170M5609 170M5609 170M5609 170M5609 170M6609 170M6609 170M6611 170M6611 170M6612 170M6612 170M5609 170M5609 170M6608 170M6608 170M6608 170M6608 170M6608 170M6608 170M6610 170M6610 170M6610 170M6610 170M7107 170M7107 170M7107 170M7107 170M7107 170M7107 170M8610 170M8610 170M8610 170M8610 170M8610 170M8610

(1) 20DK820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz. (2) Not available with 700S Control.

182

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Specifications

Appendix A

Table 16 - 932 Volt DC Input Frames 914 Drive Protection Devices


Drive Catalog Number Frame kW Rating ND HD 20xM170 9 160 132 20xM208 9 200 160 20xM261 10 250 200 20xM325 10 315 250 20xM385 10 355 315 20xM416 10 400 315 20xM460 11 450 355 20xM502 11 500 400 20xM590 11 560 500 20xM650 12 630 560 20xM750 12 710 630 20xM820(1) 12 800 630 20xM920 13 900 800 20xM1K0 13 1000 900 20xM1K1 13 1100 1000 20xM1K5 14 1500 1300 20xM1K9(2) 14 1800 1500 20xM2K2(2) 14 2000 1800 DC Input Ratings Amps 200 170 245 200 307 245 383 307 453 383 490 383 542 453 591 542 695 591 765 695 883 765 965 765 1038 925 1162 1038 1331 1162 1766 1530 2237 1766 2649 2237 Fuse 315 315 400 400 500 500 630 630 700 700 700 700 450 (2 per phs) 450 (2 per phs) 500 (2 per phs) 500 (2 per phs) 500 (2 per phs) 500 (2 per phs) 550 (2 per phs) 550 (2 per phs) 630 (2 per phs) 630 (2 per phs) 630 (2 per phs) 630 (2 per phs) 2400 2400 2400 2400 2400 2400 Bussmann Style Fuse 170M3746 170M3746 170M5742 170M5742 170M5744 170M5744 170M5746 170M5746 170M6745 170M6745 170M6745 170M6745 170M5743 170M5743 170M5744 170M5744 170M5744 170M5744 170M5745 170M5745 170M5746 170M5746 170M5746 170M5746 170M7107 170M7107 170M7107 170M7107 170M7107 170M7107 170M8610 170M8610 170M8610 170M8610 170M8610 170M8610

(1) 20DM820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz. (2) Not available with 700S Control.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

183

Appendix A

Specifications

Notes:

184

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Appendix

PowerFlex 700S Stegmann Hi-Resolution Encoder Feedback Option

Option Card Specifications

Consideration Encoder Voltage Supply Stegmann Feedback Maximum Cable Length Maximum Frequency (Encoder Speed) RS-485 Interface

Description 11.5V DC @ 130 mA Sine/Cosine 1V P-P Offset 2.5 90 m (295 ft) 12.5 s/cycle (4687.5 RPM for encoders with 1024 sine cycles per revolution) (9375 RPM for encoders with 512 sine cycles per revolution) The Hi-Resolution Feedback Option card obtains the following information via the Hiperface RS-485 interface shortly after power-up: Address Command Number Mode Number of turns Number of Sine/Cos cycles Checksum

Supported Encoders

Table 17 below specifies which encoders are supported by the Stegmann HiResolution Encoder Feedback Option card. IMPORTANT Please note that encoders must be ordered as Single Ended. This will ensure that the RS-485 channel has the proper termination network installed at the factory.

Table 17 - Supported Stegmann Encoders


Model SINCOS SCS-60, SCS-70, SCM-60, and SCM-70 SINCOS SCS-KIT-101 and SCM-KIT101 SINCOS SRS-50, SRS-60, SRM-50, and SRM-60 SINCOS SRS/M 25 SINCOS SRS660 SINCOS SHS-170 Resolution 512 sine cycles per revolution 1024 sine cycles per revolution 1024 sine cycles per revolution 1024 sine cycles per revolution 1024 sine cycles per revolution 512 sine cycles per revolution Comment SCM-60 and SCM-70 have built-in mechanical turns counter. SCM-60 and SCM-70 have built-in mechanical turns counter. SRM-50 and SRM-60 have built-in mechanical turns counter. SRS25 and SRM25 have built-in mechanical turns counter. IP65 Protection Class. Size 25 square flange mounting. Hollow-shaft up to 14 mm diameter While the software supports this encoder, the SHS-170 draws excessive current and should only be used with an external power supply. Has built-in mechanical turns counter. IP65 Protection Class. Size 25 square flange mounting.

Allen-Bradley 842HR

1024 sine cycles per revolution

SINCOS, SINCODER and LINCODER are registered trademarks of Stegmann Inc.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

185

Appendix B

PowerFlex 700S Stegmann Hi-Resolution Encoder Feedback Option

Wiring the Hi-Resolution Feedback Option Card to an Encoder

Terminal block P1 contains connection points for a Stegmann Hiperface encoder. This terminal block resides on the Hi-Resolution Encoder Feedback Option card.
Hiperface is a registered trademark of Stegmann Inc.

Table 18 - Terminal Block Descriptions


Terminal 12 11 10 9 8 7 6 5 4 3 2 1 Signal POWER COMMON POWER REFSIN +SIN REFCOS +COS SHIELD SHIELD N/C N/C DATA+ (RS 485) DATA- (RS 485) Description Power supply for encoder interface. Negative Sine signal. Positive Sine signal. Negative Cosine signal. Positive Cosine signal. Connection point for encoder cable shield. Not connected. Positive DH485 terminal. Negative DH485 terminal.

Recommended Cables and Wiring Diagrams for the Stegmann HiResolution Feedback Option Card
If you are using this motor and feedback device: Allen-Bradley MPL-A/B3xx, -A/B4xx, -A/B45xx, -A/B5xx, and -A/B6xx motors with embedded Stegmann rotary encoder Allen-Bradley MPL-A/B3xx, -A/B4xx, -A/B45xx, -A/B5xx, and -A/B6xx motors with embedded Stegmann rotary encoder HPK-Series motors with embedded Stegmann rotary encoder Allen-Bradley 1326AB-BXXXX-21ML and -21MKXL motors with embedded Stegmann rotary encoder Allen-Bradley 1326AB-BXXXX-M2L, -M2KXL, -S2L and -S2KXL motors with embedded Stegmann rotary encoder Allen-Bradley MPL-A5xx and all MPL-Bxxx motors with embedded Stegmann rotary encoder Allen-Bradley 1326AB-BXXXX-M2L, -M2KXL, -S2L and -S2KXL motors with embedded Stegmann rotary encoder Allen-Bradley MPL-A5xx and all MPL-Bxxx motors with embedded Stegmann rotary encoder Allen-Bradley MPL-A3xx - MPL-A45xx and all MPG series motors with embedded Stegmann rotary encoder Allen-Bradley MPL-A3xx - MPL-A45xx and all MPG series motors with embedded Stegmann rotary encoder Any other motor with external Stegmann SHS-170 rotary encoder Any other motor with external Stegmann SCS-60, SCS-70, SCM-60 or SCM-70, SRS-50, SRS-60, SRM-60, SRM-60, SRS-25, SRM-25, or Allen-Bradley 842HR rotary encoder Any other motor with external Stegmann SCS-Kit 101 or SCK-Kit 101 rotary encoder Any other motor with external Stegmann SRS660 rotary encoder Use this cable: Allen-Bradley 2090-CFBM7E7-CDAFXX Allen-Bradley 2090-CFMB7DF-CDAFXX Allen-Bradley 2090-XXNFMF-SXX Allen-Bradley 1326-CECU-XXL-XXX Allen-Bradley 2090-CDNFDMP-SXX Allen-Bradley 2090-CDNFDMP-SXX Allen-Bradley 2090-XXNFMP-SXX Allen-Bradley 2090-XXNFMP-SXX Allen-Bradley 2090-XXNFMP-SXX Allen-Bradley 2090-UXNFDMP-SXX Stegmann shielded twisted-pair cable with 12-pin DIN style connector Stegmann shielded twisted-pair cable with 10-pin MS style connector Stegmann shielded twisted-pair cable with 8-pin Berg style connector Is available only with pre-attached Stegmann shielded twisted-pair cable of various lengths See this wiring diagram: Figure 1 on page 187 Figure 1 on page 187 Figure 2 on page 187 Figure 3 on page 187 Figure 4 on page 188 Figure 4 on page 188 Figure 5 on page 188 Figure 5 on page 188 Figure 6 on page 188 Figure 7 on page 189 Figure 8 on page 189 Figure 9 on page 189 Figure 10 on page 190 Figure 11 on page 190

186

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

1 2

3 4 5 6

7 8

9 10 11 12

PowerFlex 700S Stegmann Hi-Resolution Encoder Feedback Option

Appendix B

Connection Examples

Figure 1 - All MPL-A/B3xx, -A/B4xx, -A/B45xx, -A/B5xx, and -B6xx motors with 2090-CFBM7E7-CDAFXX or 2090-CFBM7DF-CDAFXX cable
Note: Thermal Switch cannot be accessed using 2090-CFBM7X7-CDAFXX cable.
Hi-Res Feedback Option Board POWER COMMON 12 POWER 11 REFSIN 10 +SIN 9 REFCOS 8 +COS 7 SHIELD 6 SHIELD 5 N/C 4 N/C 3 DATA+ (RS 485) 2 DATA- (RS 485) 1 WH/GY OR WH/BK BK WH/RD RD BK WH/BK RD WH/RD GN WH/GN OR WH/GY A B C D E F N P R S ENCODER +SIN REFSIN +COS REFCOS DATA+ (RS-485) DATA- (RS 485) POWER COMMON TS+ TS-

GN WH/GN

Figure 2 - HPK-Series motors with 2090-XXNFMF-SXX cable


Note: Thermal Switch cannot be accessed using 2090-XXNFMF-SXX cable.
Hi-Res Feedback Option Board POWER COMMON 12 POWER 11 REFSIN 10 +SIN 9 REFCOS 8 +COS 7 SHIELD 6 SHIELD 5 N/C 4 N/C 3 DATA+ (RS 485) 2 DATA- (RS 485) 1 WH/GY OR WH/BK BK WH/RD RD BK WH/BK RD WH/RD GN WH/GN OR WH/GY A B C D E F N P R S ENCODER +SIN REFSIN +COS REFCOS DATA+ (RS-485) DATA- (RS 485) POWER COMMON TS+ TS-

GN WH/GN

Figure 3 - 1326AB-BXXXX-21ML, and -21MKXL motors with a 1326-CECU-XXL-XXX cable


Hi-Res Feedback Option Board POWER COMMON 12 POWER 11 REFSIN 10 +SIN 9 REFCOS 8 +COS 7 SHIELD 6 SHIELD 5 N/C 4 N/C 3 DATA+ (RS 485) 2 DATA- (RS 485) 1 WH BK BK RD BK BU BK WH BK RD BK BU BK GN A B C D E F G H I J ENCODER POWER POWER COMMON REFSIN +SIN REFCOS +COS DATA+ (RS-485) DATA- (RS-485) SHIELD OVERALL SHIELD

BK GN

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

187

Appendix B

PowerFlex 700S Stegmann Hi-Resolution Encoder Feedback Option

Connection Examples

Figure 4 - MPL-A5xx and all MPL-Bxxx motors or 1326AB-BXXXX-M2L, -M2KXL, -S2L, and -S2KXL motors with 2090-CDNFDMP-SXX cable
Hi-Res Feedback Option Board POWER COMMON 12 POWER 11 REFSIN 10 +SIN 9 REFCOS 8 +COS 7 SHIELD 6 SHIELD 5 N/C 4 N/C 3 DATA+ (RS 485) 2 DATA- (RS 485) 1 WH/OR OR BK/WH BK WH/RD RD BK BK/WH RD WH/RD GN WH/GN OR WH/OR BU WH/BU A B C D E F N P R S ENCODER +SIN REFSIN +COS REFCOS DATA+ (RS-485) DATA- (RS 485) POWER COMMON TS+ TS-

BU WH/BU GN WH/GN

Figure 5 - MPL-A5xx and all MPL-Bxxx Motor or 1326AB-BXXXX-M2L, -M2KXL, -S2L, and -S2KXL motor with 2090-XXNFMP-SXX cable
Note: Thermal Switch cannot be accessed using 2090-XXNFMP-SXX cable.
Hi-Res Feedback Option Board POWER COMMON 12 POWER 11 REFSIN 10 +SIN 9 REFCOS 8 +COS 7 SHIELD 6 SHIELD 5 N/C 4 N/C 3 DATA+ (RS 485) 2 DATA- (RS 485) 1 WH/GY OR WH/BK BK WH/RD RD BK WH/BK RD WH/RD GN WH/GN OR WH/GY A B C D E F N P R S ENCODER +SIN REFSIN +COS REFCOS DATA+ (RS-485) DATA- (RS 485) POWER COMMON TS+ TS-

GN WH/GN

Figure 6 - MPL-A3xx - MPL-A45xx and all MPG series motors with 2090-XXNFMP-SXX cable
Note: Thermal Switch cannot be accessed using 2090-XXNFMP-SXX cable.
Hi-Res Feedback Option Board POWER COMMON 12 POWER 11 REFSIN 10 +SIN 9 REFCOS 8 +COS 7 SHIELD 6 SHIELD 5 N/C 4 N/C 3 DATA+ (RS 485) 2 DATA- (RS 485) 1 WH/GY GY BK/WH BK WH/RD RD BK BK/WH RD WH/RD GN WH/GN GY WH/GY A B C D E F K L R S ENCODER +SIN REFSIN +COS REFCOS DATA+ (RS-485) DATA- (RS 485) POWER COMMON TS+ TS-

GN WH/GN

188

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

PowerFlex 700S Stegmann Hi-Resolution Encoder Feedback Option

Appendix B

Connection Examples

Figure 7 - MPL-A3xx - MPL-A45xx and all MPG series motors with 2090-UXNFDMP-SXX cable
Hi-Res Feedback Option Board POWER COMMON 12 POWER 11 REFSIN 10 +SIN 9 REFCOS 8 +COS 7 SHIELD 6 SHIELD 5 N/C 4 N/C 3 DATA+ (RS 485) 2 DATA- (RS 485) 1 WH/GY GY BK/WH BK WH/RD RD BK BK/WH RD WH/RD GN WH/GN GY WH/GY BU WH/BU A B C D E F K L R S ENCODER +SIN REFSIN +COS REFCOS DATA+ (RS-485) DATA- (RS 485) POWER COMMON TS+ TS-

BU WH/BU GN WH/GN

Figure 8 - Stegmann shielded twisted-pair cable with 12-pin DIN style connector
Hi-Res Feedback Option Board POWER COMMON 12 POWER 11 REFSIN 10 +SIN 9 REFCOS 8 +COS 7 SHIELD 6 SHIELD 5 N/C 4 N/C 3 DATA+ (RS 485) 2 DATA- (RS 485) 1 BU RD BN WH BK PK RD BU PK GN BN WH 12 11 10 9 8 7 6 5 4 3 2 1 ENCODER POWER N/C POWER COMMON SHIELD +COS DATA- (RS 485) REFSIN +SIN N/C N/C DATA+ (RS 485) REFCOS

GY GN

GY BK

Figure 9 - Stegmann shielded twisted-pair cable with 10-pin MS style connector


Hi-Res Feedback Option Board POWER COMMON 12 POWER 11 REFSIN 10 +SIN 9 REFCOS 8 +COS 7 SHIELD 6 SHIELD 5 N/C 4 N/C 3 DATA+ (RS 485) 2 DATA- (RS 485) 1 BU RD BN WH BK PK RD BU BN BK GY GN WH PK A B C D E F G H I J ENCODER POWER POWER COMMON REFSIN REFCOS DATA+ (RS 485) DATA- (RS 485) +SIN +COS N/C SHIELD

GY GN

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

189

Appendix B

PowerFlex 700S Stegmann Hi-Resolution Encoder Feedback Option

Connection Examples

Figure 10 - Stegmann shielded twisted-pair cable with 8-pin Berg style connector
Hi-Res Feedback Option Board POWER COMMON 12 POWER 11 REFSIN 10 +SIN 9 REFCOS 8 +COS 7 SHIELD 6 SHIELD 5 N/C 4 N/C 3 DATA+ (RS 485) 2 DATA- (RS 485) 1 BU RD BN WH BK PK RD BU BN BK GY GN WH PK 1 2 3 4 5 6 7 8 ENCODER POWER POWER COMMON REFSIN REFCOS DATA+ (RS 485) DATA- (RS 485) +SIN +COS

GY GN

Figure 11 - Pre-attached Stegmann shielded twisted-pair cable


Hi-Res Feedback Option Board POWER COMMON 12 POWER 11 REFSIN 10 +SIN 9 REFCOS 8 +COS 7 SHIELD 6 SHIELD 5 N/C 4 N/C 3 DATA+ (RS 485) 2 DATA- (RS 485) 1 BU RD BN WH BK PK RD BU BN BK GY GN WH PK 1 2 3 4 5 6 7 8 ENCODER POWER POWER COMMON REFSIN REFCOS DATA+ (RS 485) DATA- (RS 485) +SIN +COS

GY GN

190

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Appendix

PowerFlex 700S Resolver Feedback Option Card

Option Card Specifications

Consideration Excitation Frequency Excitation Voltage Resolver Feedback Voltage

Description 23819300 Hz 826 Vrms 2 Vrms 300 mV

Compatible Resolvers

Table 19 below specifies which resolvers are supported by the Resolver Feedback Option card.
Table 19 - Compatible Resolvers
Manufacturer Tamagawa Tamagawa Tamagawa Tamagawa Tamagawa Tamagawa Tamagawa Tamagawa Advanced Micro Controls Inc. (AMCI) Manufacturer Catalog Number TS-2014N181E32 TS-2014N182E32 TS-2014N185E32 TS-2087N12E9 TS-2087N1E9 TS-2087N2E9 TS-2087N5E9 TS-2087N11E9 R11X-C10/7 Parameter 277 [Reslvr0 Type Sel] Configuration 1 - T2014/2087x1 2 - T2014/2087x2 3 - T2014/2087x2 2 - T2014/2087x2 1 - T2014/2087x1 2 - T2014/2087x2 3 - T2014/2087x2 1 - T2014/2087x1 14 - AmciR11XC107 Notes x 1, flange-mounted enclosure x 2, flange-mounted enclosure x 5, flange-mounted enclosure x 2, HD foot-mounted enclosure, double shaft x 1, HD foot-mounted enclosure x 2, HD foot-mounted enclosure x 5, HD foot-mounted enclosure x 1, HD foot-mounted enclosure, double shaft

Allen-Bradley servo motors may be ordered with factory installed resolvers. Table 20 specifies which factory installed resolvers are supported by the Resolver Feedback Option card.
Table 20 - Compatible Factory Installed Resolvers
Motor / Resolver Type 1326 AB 460V Primary Resolver 1326 AB 460V Secondary Resolver Parameter 277 [Reslvr0 Type Sel] Configuration 9 - 1326Ax 460v 13 - Reserved Notes Transmitter type resolver - supported Secondary resolver is geared to motor - not intended for motor speed / position feedback Transmitter type resolver - supported Transmitter type resolver - supported Transmitter type resolver - supported Transmitter type resolver - supported

1326AH 460V Explosion Proof Motor 9 - 1326Ax 460v Primary Resolver 1326AS 460V Rare Earth Primary Resolver 9 - 1326Ax 460v MPL 460V Primary Resolver 4 - MPL 460v

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

191

Appendix C

PowerFlex 700S Resolver Feedback Option Card

Recommended Cable
Rockwell Automation strongly recommends the use of Reliance Electric 417900207CG or Belden 9730 cable for installation, or an equivalent cable that meets these specifications: 3 Twisted Pairs, 80 C, 300V Chrome FPR Jacket, Plenum Rated Conductor Size: 18 AWG Twists Per Inch: 2-3 twists per inch of wire lay per pair Capacitance Per Pair: not to exceed 30 pF per foot 0.3 pF as read on a GEN_RAD Model 1658 RLC Digibridge or equivalent Capacitance Difference Pair to Pair: not to exceed 0.6 pF per foot as read on a GEN_RAD Model 1658 RLC Digibridge or equivalent Resistance per 1000 ft: 17.15 10% Inductance per 1000 ft: 0.13 mH 10% as read on a GEN_RAD Model 1658 RLC Digibridge or equivalent Insulation Thickness: 0.008 in. Conductor Stranding 16/30 Jacket Thickness: 0.018 in.

192

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

1 2 3 4 5

7 8

Wiring the Resolver Feedback Option Card to a Resolver

Table 21 - Terminal Block Description


Terminal 8 7 6 5 4 3 2 1 Signal REF HIGH SHIELD REF LOW SIN HIGH SHIELD SIN LOW COS HIGH COS LOW Description Positive Reference signal Connection point for resolver cable shield Negative Reference signal Positive Sine signal Connection point for resolver cable shield Negative Sine signal Positive Cosine signal Negative Cosine signal

PowerFlex 700S Resolver Feedback Option Card

Appendix C

Figure 12 - Resolver Wiring Examples


Connection Examples Resolver Interface - Clockwise Rotation = Count Up

+ REF SIN COS

REF HIGH 8 SHIELD 7 REF LOW 6 SIN HIGH 5 SHIELD 4 SIN LOW 3 COS HIGH 2 COS LOW 1
+

Resolver Interface - Clockwise Rotation = Count Down (Reverse Polarity of Sine or Cosine Signals)

+ REF SIN COS

REF HIGH 8 GROUND 7 REF LOW 6 SIN HIGH 5 GROUND 4 SIN LOW 3 COS HIGH 2 COS LOW 1
+

+ REF SIN COS

REF HIGH 8 SHIELD 7 REF LOW 6 SIN HIGH 5 SHIELD 4 SIN LOW 3 COS HIGH 2 COS LOW 1
+

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

193

Appendix C

PowerFlex 700S Resolver Feedback Option Card

Notes:

194

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Appendix

PowerFlex 700S Multi-Device Interface (MDI) Option Card

MDI Option Card Specifications

Consideration Rotary Encoder Voltage Supply Rotary Encoder Hi-Resolution Feedback Rotary Encoder Maximum Cable Length Linear Encoder Maximum Cable Length Rotary Encoder RS-485 Interface

Registration Inputs

Description 11.5V DC @ 130 mA Sine/Cosine 1V P-P Offset 2.5 90 m (295 ft) 245 m (800 ft) The MDI Option card obtains the following information via the Hiperface RS-485 interface shortly after power-up: Address Command Number Mode Number of turns Number of Sine/Cos cycles Checksum High speed 1224V DC sinking digital inputs

Supported Linear Sensors

Temposonics R-Series Linear sensors with MTS part numbers ending in 1S2G1102 work with the MDI option.
Part Number Character 1 S 2 G 1 1 02 Characteristic Input Voltage = +24VDC SSI output Data Length = 24 Bits Output Format = Gray Code Resolution = 0.005 mm Performance = Standard Scale Orientation = Forward-acting Synchronized

Temposonics is a registered trademark of MTS Systems Corporation.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

195

Appendix D

PowerFlex 700S Multi-Device Interface (MDI) Option Card

Supported Rotary Encoders


IMPORTANT Please note that encoders must be ordered as Single Ended. This will ensure that the RS-485 channel has the proper termination network installed at the factory.

Model SINCOS SCS-60, SCS-70, SCM-60, and SCM-70 SINCOS SCS-KIT-101 and SCMKIT-101 SINCOS SRS-50, SRS-60, SRM-50, and SRM-60 SINCOS SRS/M 25 SINCOS SRS660 SINCOS SHS-170

Resolution 512 sine cycles per revolution. 1024 sine cycles per revolution. 1024 sine cycles per revolution. 1024 sine cycles per revolution 1024 sine cycles per revolution 512 sine cycles per revolution.

Allen-Bradley 842HR

1024 sine cycles per revolution

Comment SCM-60 and SCM-70 have built-in mechanical turns counter. SCM-60 and SCM-70 have built-in mechanical turns counter. SRM-50 and SRM-60 have built-in mechanical turns counter. SRS25 and SRM25 have built-in mechanical turns counter. IP65 Protection Class. Size 25 square flange mounting. Hollow-shaft up to 14 mm diameter While the software supports this encoder, the SHS-170 draws excessive current and should only be used with an external power supply. Has built-in mechanical turns counter. IP65 Protection Class. Size 25 square flange mounting.

SINCOS, SINCODER and LINCODER are registered trademarks of Stegmann Inc.

Wiring the MDI Option Card


Terminal 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

Table 22 - Terminal Block Description


Description Power supply for Rotary Encoder interface Positive Sine signal for Rotary Encoder interface Negative Sine signal for Rotary Encoder interface Negative Cosine signal for Rotary Encoder interface Positive Cosine signal for Rotary Encoder interface Positive DH485 terminal for Rotary Encoder interface Negative DH485 terminal for Rotary Encoder interface Positive Clock terminal for Linear Sensor interface Negative Clock terminal for Linear Sensor interface Positive SSI terminal for Linear Sensor interface Negative SSI terminal for Linear Sensor interface Positive terminal for Rotary Encoder registration strobe Negative terminal for Rotary Encoder registration strobe Positive terminal for Linear Sensor registration strobe Negative terminal for Linear Sensor registration strobe Connection point for cable shields

Signal Rotary Encoder POWER COMMON Rotary Encoder POWER Rotary Encoder REFSIN Rotary Encoder +SIN Rotary Encoder REFCOS Rotary Encoder +COS Rotary Encoder DATA+ (RS485) Rotary Encoder DATA- (RS485) Linear Sensor CLOCK+ Linear Sensor CLOCKLinear Sensor DATA+ Linear Sensor DATARotary Encoder REGISTRATION+ Rotary Encoder REGISTRATIONLinear Sensor REGISTRATION+ Linear Sensor REGISTRATIONCHASSIS GND

196

9 10 11 12 13 14 15 16 17

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

PowerFlex 700S Multi-Device Interface (MDI) Option Card

Appendix D

Recommended Cables and Wiring Diagrams for the MDI Option Card
If you are using this motor and feedback device: Allen-Bradley MPL-A/B3xx, -A/B4xx, -A/B45xx, -A/B5xx, and -A/B6xx motors with embedded Stegmann rotary encoder Allen-Bradley MPL-A/B3xx, -A/B4xx, -A/B45xx, -A/B5xx, and -A/B6xx motors with embedded Stegmann rotary encoder HPK-Series motors with embedded Stegmann rotary encoder Temposonics R-Series Linear sensors with MTS part numbers ending in 1S2G1102 Allen-Bradley 1326AB-BXXXX-M2L, -M2KXL, -S2L, and -S2KXL motors with embedded Stegmann rotary encoder Allen-Bradley MPL-A5xx and MPL-Bxxx motors motors with embedded Stegmann rotary encoder Allen-Bradley 1326AB-BXXXX-M2L, -M2KXL, -S2L, and -S2KXL motors with embedded Stegmann rotary encoder Allen-Bradley MPL-A5xx and MPL-Bxxx motors motors with embedded Stegmann rotary encoder Allen-Bradley MPL-A3xx - MPL-A45xx and all MPG series motors with embedded Stegmann rotary encoder Allen-Bradley MPL-A3xx - MPL-A45xx and all MPG series motors with embedded Stegmann rotary encoder Any other motor with external Stegmann SHS-170 rotary encoder Any other motor with external Stegmann SCS-60, SCS-70, SCM-60 or SCM-70, SRS-50, SRS-60, SRM-60, SRM-60, SRS-25, SRM-25 or Allen-Bradley 842HR rotary encoder Any other motor with external Stegmann SCS-Kit 101 or SCK-Kit 101 rotary encoder Any other motor with external Stegmann SRS660 rotary encoder Use this cable: Allen-Bradley 2090-CFBM7E7-CDAFXX Allen-Bradley 2090-CFMB7DF-CDAFXX Allen-Bradley 2090-XXNFMF-SXX Mating MTS molded extension cable for RG connector or integral P cable Allen-Bradley 2090-CDNFDMP-SXX Allen-Bradley 2090-CDNFDMP-SXX Allen-Bradley 2090-XXNFMP-SXX Allen-Bradley 2090-XXNFMP-SXX Allen-Bradley 2090-XXNFMP-SXX Allen-Bradley 2090-UXNFDMP-SXX Stegmann shielded twisted-pair cable with 12-pin DIN style connector Stegmann shielded twisted-pair cable with 10-pin MS style connector Stegmann shielded twisted-pair cable with 8-pin Berg style connector Is available only with pre-attached Stegmann shielded twisted-pair cable of various lengths See this wiring diagram: Figure 13 below Figure 13 on page 197 Figure 14 on page 198 Figure 15 on page 198 Figure 16 on page 198 Figure 16 on page 198 Figure 17 on page 199 Figure 17 on page 199 Figure 18 on page 199 Figure 19 on page 199 Figure 20 on page 200 Figure 21 on page 200 Figure 22 on page 200 Figure 23 on page 201

Table 23 - Connection Examples


Example

Figure 13 - All MPL-A/B3xx, -A/B4xx, -A/B45xx, -A/B5xx, and -B6xx motors with 2090-CFBM7E7-CDAFXX or 2090-CFBM7DF-CDAFXX cable
Note: Thermal Switch cannot be accessed using 2090-CFBM7X7-CDAFXX cable.
Hi-Res Feedback Option Board POWER COMMON 12 POWER 11 REFSIN 10 +SIN 9 REFCOS 8 +COS 7 SHIELD 6 SHIELD 5 N/C 4 N/C 3 DATA+ (RS 485) 2 DATA- (RS 485) 1 WH/GY OR WH/BK BK WH/RD RD BK WH/BK RD WH/RD GN WH/GN OR WH/GY A B C D E F N P R S ENCODER +SIN REFSIN +COS REFCOS DATA+ (RS-485) DATA- (RS 485) POWER COMMON TS+ TS-

GN WH/GN

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

197

Appendix D

PowerFlex 700S Multi-Device Interface (MDI) Option Card

Example

Figure 14 - HPK-Series motors with 2090-XXNFMF-SXX cable


Note: Thermal Switch cannot be accessed using 2090-XXNFMF-SXX cable.
MDI Feedback Option Board Rotary Encoder POWER COMMON Rotary Encoder POWER Rotary Encoder REFSIN Rotary Encoder +SIN Rotary Encoder REFCOS Rotary Encoder +COS Rotary Encoder DATA+ (RS485) Rotary Encoder DATA- (RS485) Linear Sensor CLOCK+ Linear Sensor CLOCKLinear Sensor DATA+ Linear Sensor DATARotary Encoder REGISTRATION+ Rotary Encoder REGISTRATIONLinear Sensor REGISTRATION+ Linear Sensor REGISTRATIONCHASSIS GND 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

ENCODER WH/GY OR BK/WH BK WH/RD RD BK BK/WH RD WH/RD GN WH/GN OR WH/GY A B C D E F N P R S +SIN REFSIN +COS REFCOS DATA+ (RS-485) DATA- (RS 485) POWER COMMON TS+ TS-

GN WH/GN

Figure 15 - Linear Sensor connections with MDI RG connector or P integral cable


EXTERNAL 24 Vdc POWER SUPPLY POWER COMMON RD or BN WH MDI Feedback Option Board 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

Rotary Encoder POWER COMMON Rotary Encoder POWER Rotary Encoder REFSIN Rotary Encoder +SIN Rotary Encoder REFCOS Rotary Encoder +COS Rotary Encoder DATA+ (RS485) Rotary Encoder DATA- (RS485) Linear Sensor CLOCK+ Linear Sensor CLOCKLinear Sensor DATA+ Linear Sensor DATARotary Encoder REGISTRATION+ Rotary Encoder REGISTRATIONLinear Sensor REGISTRATION+ Linear Sensor REGISTRATIONCHASSIS GND

LINEAR SENSOR WH RD or BN GN YE GY PK 7 6 5 4 3 2 1 No Connection DC Ground +24 Vdc (-) CLOCK (+) CLOCK (+) DATA (-) DATA

YE GN GY PK

Figure 16 - Rotary Encoder connections for MPL-A5xx and MPL-Bxxx motors or 1326AB-BXXXX-M2L, -M2KXL, -S2L, and -S2KXL motors with 2090CDNFDMP-SXX cable
MDI Feedback Option Board Rotary Encoder POWER COMMON Rotary Encoder POWER Rotary Encoder REFSIN Rotary Encoder +SIN Rotary Encoder REFCOS Rotary Encoder +COS Rotary Encoder DATA+ (RS485) Rotary Encoder DATA- (RS485) Linear Sensor CLOCK+ Linear Sensor CLOCKLinear Sensor DATA+ Linear Sensor DATARotary Encoder REGISTRATION+ Rotary Encoder REGISTRATIONLinear Sensor REGISTRATION+ Linear Sensor REGISTRATIONCHASSIS GND 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 WH/OR OR BK/WH BK WH/RD RD GN WH/GN BU WH/BU BK BK/WH RD WH/RD GN WH/GN OR WH/OR BU WH/BU A B C D E F N P R S ROTARY ENCODER +SIN REFSIN +COS REFCOS DATA+ (RS-485) DATA- (RS 485) POWER COMMON TS+ TS-

198

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

PowerFlex 700S Multi-Device Interface (MDI) Option Card

Appendix D

Example

Figure 17 - Rotary Encoder connections for MPL-A5xx and MPL-Bxxx motors or 1326AB-BXXXX-M2L, -M2KXL, -S2L, and -S2KXL motors with 2090XXNFMP-SXX cable
Note: Thermal Switch cannot be accessed using 2090-XXNFMP-SXX cable.
MDI Feedback Option Board Rotary Encoder POWER COMMON Rotary Encoder POWER Rotary Encoder REFSIN Rotary Encoder +SIN Rotary Encoder REFCOS Rotary Encoder +COS Rotary Encoder DATA+ (RS485) Rotary Encoder DATA- (RS485) Linear Sensor CLOCK+ Linear Sensor CLOCKLinear Sensor DATA+ Linear Sensor DATARotary Encoder REGISTRATION+ Rotary Encoder REGISTRATIONLinear Sensor REGISTRATION+ Linear Sensor REGISTRATIONCHASSIS GND 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 WH/GY OR BK/WH BK WH/RD RD GN WH/GN BK BK/WH RD WH/RD GN WH/GN OR WH/GY A B C D E F N P R S ROTARY ENCODER +SIN REFSIN +COS REFCOS DATA+ (RS-485) DATA- (RS 485) POWER COMMON TS+ TS-

Figure 18 - Rotary Encoder connections for MPL-A3xx - MPL-A45xx and all MPG series motors with 2090-XXNFMP-SXX cable
Note: Thermal Switch cannot be accessed using 2090-XXNFMP-SXX cable.
MDI Feedback Option Board Rotary Encoder POWER COMMON Rotary Encoder POWER Rotary Encoder REFSIN Rotary Encoder +SIN Rotary Encoder REFCOS Rotary Encoder +COS Rotary Encoder DATA+ (RS485) Rotary Encoder DATA- (RS485) Linear Sensor CLOCK+ Linear Sensor CLOCKLinear Sensor DATA+ Linear Sensor DATARotary Encoder REGISTRATION+ Rotary Encoder REGISTRATIONLinear Sensor REGISTRATION+ Linear Sensor REGISTRATIONCHASSIS GND 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 WH/GY GY BK/WH BK WH/RD RD GN WH/GN BK BK/WH RD WH/RD GN WH/GN GY WH/GY A B C D E F N P R S ROTARY ENCODER +SIN REFSIN +COS REFCOS DATA+ (RS-485) DATA- (RS 485) POWER COMMON TS+ TS-

Figure 19 - Rotary Encoder connections for MPL-A3xx - MPL-A45xx and all MPG series motors with 2090-UXNFDMP-SXX cable
MDI Feedback Option Board Rotary Encoder POWER COMMON Rotary Encoder POWER Rotary Encoder REFSIN Rotary Encoder +SIN Rotary Encoder REFCOS Rotary Encoder +COS Rotary Encoder DATA+ (RS485) Rotary Encoder DATA- (RS485) Linear Sensor CLOCK+ Linear Sensor CLOCKLinear Sensor DATA+ Linear Sensor DATARotary Encoder REGISTRATION+ Rotary Encoder REGISTRATIONLinear Sensor REGISTRATION+ Linear Sensor REGISTRATIONCHASSIS GND 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
WH/GY GY BK/WH BK WH/RD RD BK BK/WH RD WH/RD GN WH/GN GY WH/GY BU WH/BU A B C D E F K L R S ENCODER +SIN REFSIN +COS REFCOS DATA+ (RS-485) DATA- (RS 485) POWER COMMON TS+ TS-

BU WH/BU GN WH/GN

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

199

Appendix D

PowerFlex 700S Multi-Device Interface (MDI) Option Card

Example

Figure 20 - Stegmann shielded twisted-pair cable with 12-pin DIN style connector
MDI Feedback Option Board Rotary Encoder POWER COMMON Rotary Encoder POWER Rotary Encoder REFSIN Rotary Encoder +SIN Rotary Encoder REFCOS Rotary Encoder +COS Rotary Encoder DATA+ (RS485) Rotary Encoder DATA- (RS485) Linear Sensor CLOCK+ Linear Sensor CLOCKLinear Sensor DATA+ Linear Sensor DATARotary Encoder REGISTRATION+ Rotary Encoder REGISTRATIONLinear Sensor REGISTRATION+ Linear Sensor REGISTRATIONCHASSIS GND 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 BU RD BN WH BK PK GY GN RD BU PK GN BN WH 12 11 10 9 8 7 6 5 4 3 2 1 ROTARY ENCODER POWER N/C POWER COMMON SHIELD +COS DATA- (RS 485) REFSIN +SIN N/C N/C DATA+ (RS 485) REFCOS

GY BK

Figure 21 - Rotary Encoder connections with Stegmann shielded twisted-pair cable and 10-pin MS style connector
MDI Feedback Option Board Rotary Encoder POWER COMMON Rotary Encoder POWER Rotary Encoder REFSIN Rotary Encoder +SIN Rotary Encoder REFCOS Rotary Encoder +COS Rotary Encoder DATA+ (RS485) Rotary Encoder DATA- (RS485) Linear Sensor CLOCK+ Linear Sensor CLOCKLinear Sensor DATA+ Linear Sensor DATARotary Encoder REGISTRATION+ Rotary Encoder REGISTRATIONLinear Sensor REGISTRATION+ Linear Sensor REGISTRATIONCHASSIS GND 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 BU RD BN WH BK PK GY GN RD BU BN BK GY GN WH PK A B C D E F G H I J ROTARY ENCODER POWER POWER COMMON REFSIN REFCOS DATA+ (RS 485) DATA- (RS 485) +SIN +COS N/C SHIELD

Figure 22 - Rotary Encoder connections with Stegmann shielded twisted-pair cable and 8-pin Berg style connector
MDI Feedback Option Board Rotary Encoder POWER COMMON Rotary Encoder POWER Rotary Encoder REFSIN Rotary Encoder +SIN Rotary Encoder REFCOS Rotary Encoder +COS Rotary Encoder DATA+ (RS485) Rotary Encoder DATA- (RS485) Linear Sensor CLOCK+ Linear Sensor CLOCKLinear Sensor DATA+ Linear Sensor DATARotary Encoder REGISTRATION+ Rotary Encoder REGISTRATIONLinear Sensor REGISTRATION+ Linear Sensor REGISTRATIONCHASSIS GND 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
BU RD BN WH BK PK RD BU BN BK GY GN WH PK 1 2 3 4 5 6 7 8

ROTARY ENCODER
POWER POWER COMMON REFSIN REFCOS DATA+ (RS 485) DATA- (RS 485) +SIN +COS

GY GN

200

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

PowerFlex 700S Multi-Device Interface (MDI) Option Card

Appendix D

Example

Figure 23 - Rotary Encoder connections with Stegmann pre-attached shielded twisted-pair cable
MDI Feedback Option Board Rotary Encoder POWER COMMON Rotary Encoder POWER Rotary Encoder REFSIN Rotary Encoder +SIN Rotary Encoder REFCOS Rotary Encoder +COS Rotary Encoder DATA+ (RS485) Rotary Encoder DATA- (RS485) Linear Sensor CLOCK+ Linear Sensor CLOCKLinear Sensor DATA+ Linear Sensor DATARotary Encoder REGISTRATION+ Rotary Encoder REGISTRATIONLinear Sensor REGISTRATION+ Linear Sensor REGISTRATIONCHASSIS GND 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
BU RD BN WH BK PK BU RD BN WH BK PK GY GN

ROTARY ENCODER
POWER COMMON POWER REFSIN +SIN REFCOS +COS DATA+ (RS 485) DATA- (RS 485)

GY GN

Figure 24 - Registration Sensor connection


EXTERNAL 12 or 24 Vdc POWER SUPPLY POWER COMMON MDI Feedback Option Board 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

Rotary Encoder POWER COMMON Rotary Encoder POWER Rotary Encoder REFSIN Rotary Encoder +SIN Rotary Encoder REFCOS Rotary Encoder +COS Rotary Encoder DATA+ (RS485) Rotary Encoder DATA- (RS485) Linear Sensor CLOCK+ Linear Sensor CLOCKLinear Sensor DATA+ Linear Sensor DATARotary Encoder REGISTRATION+ Rotary Encoder REGISTRATIONLinear Sensor REGISTRATION+ Linear Sensor REGISTRATIONCHASSIS GND

Rotary Registration Sensor + Power Common

Linear Registration Sensor + Power Common

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

201

Appendix D

PowerFlex 700S Multi-Device Interface (MDI) Option Card

Notes:

202

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Appendix

Instructions for ATEX Approved PowerFlex 700H Drives in Group II Category (2) Applications with ATEX Approved Motors

General Information

This document provides information on operation of an ATEX(1) Approved drive and ATEX approved motor. The motor is located in a defined hazardous environment, while the drive is not. A protective system is required to stop current flow to the motor when an over temperature condition has been sensed in the motor. When sensed, the drive will go into a stop condition. To restart the drive, the over temperature condition must be resolved, followed by a valid start command to the drive. The PowerFlex 700H drive must have the 20C-DG1 option board installed in slot B of the control assembly for ATEX applications. See 700H Control Circuit Board Designations on page 32 for more information. The drive is manufactured under the guidelines of the ATEX directive 94/9/EC. These drives are in Group II Category (2) Applications with ATEX Approved Motors. Certification of the drive for the ATEX group and category on its nameplate requires installation, operation, and maintenance according to the requirements found in this document and the appropriate Motor Instruction Manual(s). ATTENTION: Operation of this ATEX certified drive with an ATEX certified motor that is located in a hazardous environment requires additional installation, operation, and maintenance procedures beyond those stated in the standard user manual. Equipment damage and/or personal injury may result if all additional instructions in this document are not observed.

Motor Requirements

The motor must be manufactured under the guidelines of the ATEX directive 94/9/EC. It must be installed, operated, and maintained per the motor manufacturer supplied instructions. Only motors with nameplates marked for use on an inverter power source, and labeled for specific hazardous areas, may be used in hazardous areas on inverter (variable frequency) power. When the motor is indicated for ATEX Group II Category 2 for use in gas environments (Category 2G) the motor must be of flameproof construction, EEx d (according to EN50018) or Ex d (according to EN60079-1 or IEC60079-1). Group II motors are marked with a temperature or a temperature code.
(1) ATEX is the French acronym for Atmosphres Explosibles which translates to Explosive Atmospheres in English.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

203

Appendix E

Instructions for ATEX Approved PowerFlex 700H Drives in Group II Category (2) Applications with ATEX Approved Motors

When the motor is indicated for ATEX Group II Category 2 for use in dust environments (Category 2D) the motor must be protected by an enclosure (according to EN50281-1-1 or according to IEC61241-1: Ex tD). Group II motors are marked with a temperature. The motor over temperature signal supplied to the drive must be a normally closed contact (open during over temperature condition) compatible with the digital (logic) input circuitry of the drive. If multiple sensors are required in the motor, the connection at the drive must be the resultant of all required contacts wired in series. See all product markings for additional cautions that may apply. Typical motor markings are contained on a motor certification nameplate similar to the sample below.

FLAMEPROOF Exd ENCLOSURE


EExd I/IIB II 2 G/D I M2 Sira ATEX Tamb C to 0518 C

MFG. BY ROCKWELL AUTOMATION

Drive Wiring
IMPORTANT ATEX certification of this drive requires that two separate inputs be configured to monitor a normally closed over temperature contact (or multiple contacts wired in series) presented to the drive from the motor.

The first input must energize the SD1 input (terminals X5-1 & X5-2) on the drive option board (20C-DG1). The second input must energize the SD2 input (terminals X5-3 & X5-4) on the option board. This option board must be installed in the drive for ATEX applications. It is offered with 24V DC input only. Both input signals are wired with respect to the drive's digital input common when using a control board with 24V I/O. See Figure 6 on page 33 for wiring examples. Motor supplied contacts must have ratings compatible with the input circuit ratings and applied voltage level of the drive.

204

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Instructions for ATEX Approved PowerFlex 700H Drives in Group II Category (2) Applications with ATEX Approved Motors

Appendix E

Table 24 - Terminal Descriptions


Term. Blk. X5 No. 1 2 3 4 21 22 23 25 26 28 29 Signal SD1+ SD1 SD2+ SD2 Digital Out 1 - N.C. Digital Out 1 Common Digital Out 1 - N.O. Digital Out 2 Common Digital Out 2 N.O. TI1+ TI1 Description Isolated Disable input 1 +24V +/-20% 10... 15 mA Virtual GND 1 Isolated Disable input 2 +24V +/-20% 10... 15 mA Virtual GND 2 Max. Resistive Load: 240V AC / 30V DC - 1200VA, 150 W Max. Current: 5 A, Min. Load: 10 mA Max. Inductive Load: 240V AC / 30V DC - 8400VA, 105 W Max. Current: 3.5 A, Min. Load: 10 mA Thermistor input: Rtrip 4.0 k (PTC)

ON OFF

X2

X10

X3 X7
25 26

28 29

X7 X3
21 1 2 3 4 22 23

X2

X5

IMPORTANT

The drive will not run unless one of the following conditions is met:

A wire must be installed in the hardware thermistor input (X7-28 and X729) and the thermistor short circuit supervisor jumper X10 must be installed in the OFF position. OR A thermistor must be installed in the hardware thermistor input (X7-28 and X7-29).

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

205

Appendix E

Instructions for ATEX Approved PowerFlex 700H Drives in Group II Category (2) Applications with ATEX Approved Motors

Figure 25 - Wiring Example - Internal 24V Power Supply


PowerFlex 700H Control Unit Slot A 19 +24V DC 20 24V DC Common

Motor Over Temperature Sensor(s)


1 2 3 4 SD1+ SD1SD2+ SD2-

Slot B 20C-DG1 Disable Option

Micro Controller

Hardware Disable 1 Hardware Disable 2

28 TI1+ 29 TI1-

PowerFlex 700H Power Unit

Configuration

The PowerFlex 700H drive can be configure in one of five ways when using the 20C-DG1 option board, each resulting in the drive being put into a Gate Disabled state when digital inputs are removed or the thermistor is out of range. 1. Gate Disable Fault (59): Configured by setting bit 10 Gate Disable of parameter 238 [Fault Config1]. If both digital inputs open, the drive output will be disabled and the motor will coast to a stop. The drive HIM will display fault 59 Gate Disable. When the condition is cleared, the fault can be reset and the drive can be restarted. If only one digital input opens, the drive output will be disabled and the motor will coast to a stop. See Table 25 on page 208 for a description of drive conditions and actions.

206

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Instructions for ATEX Approved PowerFlex 700H Drives in Group II Category (2) Applications with ATEX Approved Motors

Appendix E

2. Gate Disable Alarm (59): Configured by setting bit 15 Gate Disable of parameter 259 [Alarm Config1]. If both digital inputs open, the drive output will be disabled and the motor will coast to a stop. The drive HIM will display alarm 59 Gate Disable. When the condition is cleared, the alarm will automatically clear in 10 seconds and the drive can be restarted. If only one digital input opens, the drive output will be disabled and the motor will coast to a stop. See Table 25 on page 208 for a description of drive conditions and actions. 3. Neither of the Gate Disable bits, 10 in parameter 238 [Fault Config1] or 15 in parameter 259 [Alarm Config1], are set. If both digital inputs open, the drive output will be disabled and the motor will coast to a stop. No fault or alarm indication will be given, but the Gate Disable status can be seen in bit 0 Gate Disable of parameter 359 [20CDG1 Status]. When the condition is cleared, the drive can be restarted after 3 seconds. If only one digital input opens, the drive will be disabled and the motor will coast to a stop. See Table 25 on page 208 for a description of drive conditions and actions. 4. Both Gate Disable bits, 10 in [Fault Config1] and 15 in [Alarm Config1], are set: The Gate Disable fault takes precedence. 5. Thermistor Input: If the thermistor input goes out of range, the drive output will be disabled and the motor will coast to a stop. The drive will display fault 60 Hrdwr Therm on the drive HIM. When the condition is cleared, the fault can be reset and the drive can be restarted. This configuration requires that the two digital inputs remain closed to function.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

207

Appendix E

Instructions for ATEX Approved PowerFlex 700H Drives in Group II Category (2) Applications with ATEX Approved Motors

Removing the 20C-DG1 Option Board

During maintenance or service there may be a need to remove the 20C-DG1 option board. The drive is designed to generate a non-resettable fault F10 System Fault if the option board is removed. The operator must manually change parameter 358 [20C-DG1 Remove] to 1- Remove and then back to 0 - Ready to clear and acknowledge the fault. Once maintenance or service is completed and the 20C-DG1 option card has been reinstalled, the drive will recognize the option card on power-up.

Verify Operation

At regular intervals during the life of the machine check the protective system for proper operation. Both channels shall be verified using the table below. How frequently the protective system is checked is dependent on the safety analysis of the machine section controlled by the drive.
Table 25 - Gate Disable Status and Verification
Protective System Status Drive In Drive In Gate Disable Gate Disable State State Channel Operation Bit 3 = 1 Bit 3 = 0 No Power Applied Power Applied Bit 4 = 1 No Power Applied Bit 4 = 1 No Power Applied Drive In Gate Disable State Bit 3 = 1 No Power Applied Bit 4 = 0 Power Applied Drive Able To Run

SD1 - terminals X5-1 & X5-2 Par 359 [20C-DG1 Status], bit 3 No Enable CH1 SD2 - terminals X5-3 & X5-4 Par 359 [20C-DG1 Status], bit 4 No Enable CH2 PowerFlex 700H Drive Status Par 359 [20C-DG1 Status], Bit 0 Gate Disable or Bits 2 Unexp In Pro and 15 Unexp HW Pro Fault or Alarm

Bit 3 = 0 Power Applied Bit 4 = 0 Power Applied

Description For Verification Output Disabled Output Disabled Output Disabled Output Enabled Bit 0 = 1 Bit 2 = 1 Bit 2 = 1 Bit 0 = 0 Bit 15 = 1 Bit 15 = 1

F59 Gate Disable F10 System Fault F10 System Fault (Fault or Alarm Based on drive set up)

None

208

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Appendix

History of Changes

Topic PFLEX-IN006D PFLEX-IN006C

Page 210 211

This appendix briefly summarizes changes that have been made with revisions of this manual. Reference this appendix if you need information to determine what changes have been made across multiple revisions. This may be especially useful if you are deciding to upgrade your hardware or software based on information added with previous revisions of this manual.

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

209

Appendix F

History of Changes

PFLEX-IN006D-EN-P, March 2006

Change Updated the Normal Duty power ratings Updated the Reference Materials List Added information on installations using single-phase input power Updated the Common Bus/Precharge information Added a description for the use of output reactors on frame 14 drives Updated the 700H I/O board options chart Updated the Auto/Manual Notes section to include information on enabling manual mode to allow starts and jogs from the HIM in 2-wire mode Added a note to the analog inputs on the 700S Phase II control Added terminal wiring illustration for external brake resistor and external brake IGBT and resistor connections on frame 9 drives Updated all Frame 10 dimension drawings to include cable routing information. Added a dimension drawing for the frame 10 Motor Control Center (MCC), Enclosure Codes B and K Updated the instructions for frame 10 Ungrounded, High Resistive Ground or Grounded B Phase Delta installations Updated the Power Terminal Block designations for frame 10 (removed brake option terminals) Updated all Frame 11 dimension drawings to include cable routing information. Added a dimension drawing for the frame 11 Motor Control Center (MCC), Enclosure Codes B and K Updated the instructions for frame 11 Ungrounded, High Resistive Ground or Grounded B Phase Delta installations Updated all Frame 12 dimension drawings to include cable routing information. Added a dimension drawing for the frame 12 Motor Control Center (MCC), Enclosure Codes B and K Updated the instructions for frame 12 Ungrounded, High Resistive Ground or Grounded B Phase Delta installations Updated all Frame 13 dimension drawings to include cable routing information. Updated the frame 13 dimensions for the NEMA/UL Type 12 - IP54 Enclosures Updated the instructions for frame 13 Ungrounded, High Resistive Ground or Grounded B Phase Delta installations Added Chapter 11 - Frame 14 Installation Updated the Agency Certification information for drives with 700H control Separated the drive ratings information from the drive protection devices - now in separate tables Updated the drive rating, fusing and circuit breaker specifications Added new Appendix B to consolidate the common lifting and mounting instructions Added the Allen-Bradley 842HR rotary encoder to the list of compatible encoders Updated wiring diagrams for the Hi-Resolution Encoder Updated wiring diagrams for Resolvers Updated wiring diagrams for the MDI board Added Appendix E on ATEX Approved PowerFlex 700H Drives in Group II Category (2) Applications with ATEX Approved Motors

210

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

History of Changes

Appendix F

PFLEX-IN006C-EN-P, October 2004

Change Updated the drive ratings for PowerFlex 700H and 700S Updated the information on installing unbalanced, ungrounded or resistive grounded distribution systems Added information on DC input precharge control wiring Updated the Control Board Slot Designations table for the new 20C-DG1 digital I/O option board Added drive catalog numbers for 700H control I/O board options Updated the Analog Input, PTC 0-10V Input wiring example Added Chapter 4, Control Wiring for PowerFlex 700S Drives with Series II Control Updated information on frame 9 operating temperatures Updated frame 9 installation instructions for unbalanced, ungrounded or resistive grounded distribution systems Updated frame 10 minimum mounting clearances Updated frame 10 operating temperatures Added dimensions drawing for frame 10 NEMA/UL Type 12 - IP54 Enclosure Updated frame 10 Moving Control Frame to show slotted holes in Control Frame Updated frame 10 Removing Protective Covers to omit screws that were not present. Updated frame 10 installation instructions for unbalanced, ungrounded or resistive grounded distribution systems Updated frame 11 minimum mounting clearances Updated frame 11 operating temperatures Added dimensions drawing for frame 11 NEMA/UL Type 12 - IP54 Enclosure Updated frame 11 installation instructions for unbalanced, ungrounded or resistive grounded distribution systems Added Chapter 9, Frame 12 Installation Added Chapter 10, Frame 13 Installation Updated the agency certifications Updated the drive protection specifications Updated the fusing and circuit breaker specifications Added specifications and wiring diagram for using the Stahltronic linear encoder

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

211

Appendix F

History of Changes

Notes:

212

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Index
Numerics
20C-DG1 option board configuration 206 description of use 203 operation 208 removing 208 terminal descriptions 205 wiring example 206 bus capacitors discharging precaution 15, 16 Bus Overvoltage Trip 700H,700S 164 Bus Undervoltage Shutoff/Fault 700H,700S 164 bus/brake connections (frame 9) 68

A
AC Input Circuit Breakers 175 Line Fuses 175 AC input ground 21 AC Input Overvoltage Trip 700H,700S 164 AC Input Undervoltage Trip 700H,700S 164 AC Input Voltage Tolerance 700H,700S 164 AC supply source 19 unbalanced 19 ungrounded 19 Accel/Decel 700H,700S 165 Actual Short Circuit Rating 700H,700S 164 Agency Certification 163 Altitude Rating 700H,700S 164 ambient temperature frame 10 72 frame 11 86 frame 12 102 frame 13 120 frame 14 134 frame 9 64 ATEX drive configuration 206 drive wiring 204 motor requirements 203 Atmosphere 700H,700S 164 Auto mode 40 Auto/Manual control 41 modes 40 auxiliary power supply 54

C
cable SHLD terminal 21 cable trays using 23 Carrier Frequency 700H,700S 165 CE conformity 23 requirements 24 circuit breakers closing (frame 14) 161 DIP switch settings (frame 14) 159 input 22 resetting (frame 14) 162 clearances mounting (frame 10) 71 mounting (frame 11) 85 mounting (frame 12) 101 mounting (frame 13) 120 mounting (frame 14) 134 mounting (frame 9) 64 common mode interference 45 reducing 31 communications logic command word (700H) 58 logic command word (700S) 60 logic status word (700H) 59 logic status word (700S) 61 programmable controller 58 routing for cabling (frame 9) 69 conditioning input power 20 conduit using 23 configure ATEX applications 206 hardware enable (700H) 36 hardware enable (700S) 53 control Auto/Manual 41 Control Logic Noise Immunity 700H,700S 164 Control Method 700H,700S 165 control wire 700H 31 700S 45 frame 9 69

B
bipolar inputs hazards 31 using 45 brake resistor ratings (frame 9) 69

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

213

Index

converter covers opening (frame 13) 124 opening (frame 14) 142 covers opening (frame 10) 76 opening (frame 11) 90 opening (frame 12) 106 opening (frame 9) 66 Current Limit Capability 700H,700S 165

D
digital inputs wiring examples (700S) 52 dimensions frame 10 - IP21 enclosure 73 frame 10 - IP54 enclosure 75 frame 10 - MCC enclosure 74 frame 11 - IP21 enclsoure 87 frame 11 - IP54 enclosure 89 frame 11 - MCC enclosure 88 frame 12 - IP21 enclosure 103 frame 12 - IP54 enclosure 105 frame 12 - MCC enclosure 104 frame 13 - IP21 enclosure 121 frame 13 - IP54 enclosure 122 frame 14, 1500 A - IP21 enclosure 137 frame 14, 1500 A - IP54 enclosure 138 frame 14, DC input - IP21 enclosure 139 frame 14, DC input - IP54 enclosure 140 frame 14, over 1500 A - IP21 enclosure 135 frame 14, over 1500 A - IP54 enclosure 136 frame 9 65 DIP switches circuit breaker settings (frame 14) 159 settings (700S) 46 Displacement Power Factor 700H,700S 164 distribution systems unbalanced 19 ungrounded 19 DPI port locations 57 drive grounding 21 Drive Ratings 175 DriveLogix Specifications Battery 166 Flex I/O Connection 166 Serial Cable 166 User Available MemoryBase 166 With Memory Expansion Board 166

enclosure rating frame 10 72 frame 11 86 frame 12 102 frame 13 120 frame 14 134 frame 9 64 Encoder inputs 166 maximum required input frequency 166 PPR rating 166 voltage supply 166

F
Feedback Encoder Option 166 first environment installations 24 frame 10 dimensions - IP21 enclosure 73 dimensions - IP54 enclosure 75 dimensions - MCC enclosure 74 power terminal block 84 frame 11 dimensions - IP21 enclsoure 87 dimensions - IP54 enclosure 89 dimensions - MCC enclosure 88 power terminal block 99 frame 12 dimensions - IP21 enclosure 103 dimensions - IP54 enclosure 105 dimensions - MCC enclosure 104 power terminal block 117 frame 13 dimensions - IP21 enclosure 121 dimensions - IP54 enclosure 122 power terminal block 132 frame 14, 1500 A dimensions - IP21 enclosure 137 dimensions - IP54 enclosure 138 power terminal block 156 frame 14, DC input dimensions - IP21 enclosure 139 dimensions - IP54 enclosure 140 frame 14, over 1500 A dimensions - IP21 enclosure 135 dimensions - IP54 enclosure 136 power terminal block 157 frame 9 brake resistor ratings 69 DC bus/brake connections 68 dimensions 65 power terminal block 67 Frame Designations 175 Frequency Accuracy Analog Input 700H 165 Frequency Accuracy Digital Input 700H 165 Frequency Control 700H 165

E
Efficiency 700H,700S 164 Electronic Motor Overload Protection 700H,700S 165 EMC directive 23 instructions 23

214

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Index

Frequency Tolerance 700H,700S 164 Fuses Ratings 175 fuses input 22

J
jumpers setting (700S) 46

L
Line transients 700H,700S 164 logic command word 700H 58 700S 60 Logic Control Ride-Thru 700H,700S 164 logic status word 700H 59 700S 61 Low Voltage directive 23

G
Ground Fault Trip 700H,700S 164 grounding bus 21 conductor 21 general 21 impedance 21 RFI filter 21 safety, PE 21 shields 21

H
hardware enable configuration (700H) 36 configuration (700S) 53 Hardware Overcurrent Trip 700H,700S 164 Heat Sink Thermistor 700H,700S 164 Hi-Resolution Stegmann Option 166 Customer-I/O Plug (P1) - Hi Res 166 Encoder Voltage Supply 166 Hi-Resolution Feedback 166 specifications 166

M
Manual mode 40 Maximum Drive to Motor Power Ratio 700H,700S 164 Maximum Short Circuit Rating 700H,700S 164 Maximum Surrounding Air Temperature without De-rating 700H,700S 164 MCCB motor operators charging (frame 14) 160 modes, Auto/Manual 40 mounting clearances frame 10 71 frame 11 85 frame 12 101 frame 13 120 frame 14 134 frame 9 64 MOV 19 Multi-Device Interface option card recommended cables 197 wiring 196

I
I/O terminal block wire size (700H) 33 I/O terminal blocks 700H 35 input devices circuit breakers 22 fuses 22 using 25 input fusing 22 Input Phases 700H,700S 164 input power conditioning 20 interference common mode 45 Intermittent Overload 700H,700S 165 inverter covers opening (frame 13) 128 opening (frame 14) 149

N
Nominal Bus Voltage (Full Load) 700H,700S 164 Non-operational Shock 700H,700S 164

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

215

Index

O
opening converter covers (frame 13) 124 converter covers (frame 14) 142 covers (frame 10) 76 covers (frame 11) 90 covers (frame 12) 106 covers (frame 9) 66 inverter covers (frame 13) 128 inverter covers (frame 14) 149 operating temperature frame 10 72 frame 11 86 frame 12 102 frame 13 120 frame 14 134 frame 9 64 output devices using 25 Output Frequency Range 700H,700S 165 Output Voltage Range 700H,700S 165

Relative Humidity 700H,700S 164 removing 20C-DG1 option board 208 converter covers (frame 13) 124 converter covers (frame 14) 142 covers (frame 10) 76 covers (frame 11) 90 covers (frame 12) 106 covers (frame 9) 66 inverter covers (frame 13) 128 inverter covers (frame 14) 149 resistive ground supply 63 Resolver feedback option card recommended cables 192 wiring 192 Resolver Option 166 excitation frequency 166 excitation voltage 166 feedback voltage 166 maximum cable length 166 operating frequency range 166 RFI filter grounding 21

P
PE ground 21 ports DPI 57 potentiometer wiring (700H) 37 Power Ride-Thru 700H,700S 164 power supply auxiliary 54 power terminals specifications (frame 10) 84 specifications (frame 11) 99 specifications (frame 12) 117 specifications (frame 13) 132 specifications (frame 14) 156 specifications (frame 9) 67 precautions discharging bus capacitors 15, 16 ESD 15, 16 using input contactors 25 using output contactors 25 programmable controller configurations 58

S
safety ground PE 21 S-Curve Time 700H,700S 165 Selectable Motor Control 700H,700S 165 SHLD terminal grounding 21 short circuit protection 22 Short Circuit Trip 700H,700S 164 signal wire recommended (700H) 31 recommended (700S) 45 sinking input (700S) 52 sinking output (700S) 52 Software Overcurrent Trip 700S 164 Sound 700S 164 sourcing input (700S) 52 sourcing output (700S) 52 Specifications Agency Certification 163 Control 165 Drive Ratings 175 Electrical 164 Environment 164 Protection 164 speed command sources 40

R
Ratings, Drive 175 recommended cables Multi-Device Interface option card 197 Resolver feedback option card 192 Stegmann Hi-Resolution feedback option card 186 reference control sources 40

216

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Index

speed reference Auto mode 40 control 40 manual mode 40 Speed regulation with feedback 700S 165 Speed regulation without feedback 700S 165 Stegmann Hi-Resolution feedback option card recommended cables 186 wiring 186 Stop Modes 700H,700S 165 Storage Temperature 700H,700S 164 supply source 19 switches settings (700S) 46 system grounding 21

W
wire size encoder (700H) 33 power (frame 10) 84 power (frame 11) 99 power (frame 12) 117 power (frame 13) 132 power (frame 14) 156 power (frame 9) 67 wiring frame 9 control and communication 69 hardware enable (700H) 36 hardware enable (700S) 53 Multi-Device Interface option card 196 potentiometer (700H) 37 Resolver feedback option card 192 Stegmann Hi-Resolution feedback option card 186 wiring examples digital inputs (700S) 52

T
TB1 terminal descriptions (700S) 49 TB2 terminal descriptions (700S) 49 terminal block location power (frame 10) 84 power (frame 11) 99 power (frame 12) 117 power (frame 13) 132 power (frame 14, 1500 A) 156 power (frame 14, over 1500 A) 157 power (frame 9) 67 Torque Regulation with feedback 700S 165 Torque Regulation without feedback 700S 165

U
unbalanced ground supply 63 ungrounded ground supply 63

V
Vibration 700H,700S 164

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

217

Index

218

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Rockwell Automation Support


Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/.

Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada Outside United States or Canada 1.440.646.3434 Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative.

New Product Satisfaction Return


Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Outside United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process. Please contact your local Rockwell Automation representative for the return procedure.

Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

*PN-208997*
PN-208997
Rockwell Otomasyon Ticaret A.., Kar Plaza Merkezi E Blok Kat:6 34752 erenky, stanbul, Tel: +90 (216) 5698400

Publication PFLEX-IN006E-EN-P - July 2013 220


Supersedes Publication PFLEX-IN006D-EN-P - August 2008 Copyright 2013 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like