Ion Exchange (India) Ltd.

DESIGN OF SCREEN
Average flow, m3/hr = 12.5
Peak flow (Q), m3/hr = 25
Type of screen = Medium
Clear spacing, mm = 20 to 50
Clear spacing selected, mm = 20
Velocity through screen (V), m/sec = 0.8
Clear area of openings through screen, m2 = Q/A
= 0.0087
Assume depth of flow in screen chamber, m = 0.3
Clear width of opening through rack, m = 0.029
Assume width of rectangular bar,mm = 5
Gross width of screen, m = 0.03625
Number of bars = 1
Total width of bar screen, mm = 45
Head loss through bar screen = 0.0728(V2-v2)
where V = velocity in through screen, m/sec = 1.6
(at 50% choked condition)
v = velocity in screen chamber, m/sec = 0.5144
Head loss through bar screen, m = 0.1671