Structural Analysis and Design of Residential Building: Owner: Location
Structural Analysis and Design of Residential Building: Owner: Location
Structural Analysis and Design of Residential Building: Owner: Location
of
Residential Building
Owner:
Location:
Structural Analysis and Design Reports of Residential Building
Table of Contents
1. INTRODUCTION ............................................................................................................. 1
2. SEISMIC VULNERABILITY OF NEPAL....................................................................... 1
3. PHILISOPHY OF SEISMIC DESIGN .............................................................................. 1
4. BUILDING DESCRIPTION ............................................................................................. 3
5. STRUCTURAL SYSTEM................................................................................................. 4
6. LOADS ADOPTED........................................................................................................... 5
7. SEISMIC DESIGN PARAMETERS................................................................................. 7
8. PRELIMINARY DESIGN................................................................................................. 7
9. FINITE ELEMENT MODELING AND ANALYSIS OF BUILDING USING ETABS . 9
9.1 LOADS APPLIED ON BUILDING: ........................................................................ 10
9.2 LATERAL LOAD ESTIMATION ACCORDING TO IS 1893 part 1 2016 ........... 13
9.3 LOAD CASES AND COMBINATION ................................................................... 14
9.3.1 Load Cases ......................................................................................................... 14
9.3.2 Load Combinations ............................................................................................ 14
9.4 DRIFT OF THE BUILDING .................................................................................... 15
9.4.1 Lateral Loads to Different Axes ........................................................................ 15
9.4.2 Story Response - Maximum Story Drifts along different Axes ......................... 15
10. DESIGN OF STRUCTURL MEMBERS ..................................................................... 17
10.1 Design of slab ........................................................................................................ 17
10.2 Design of Beam ..................................................................................................... 18
10.3 Design of Column .................................................................................................. 20
10.4 Design of foundation ............................................................................................. 26
10.5 Design of staircase ................................................................................................. 27
11. CONCLUDING REMARKS ........................................................................................ 28
12. REFERENCE CODE .................................................................................................... 29
Annex 1: Column Detailing ..................................................................................................... 31
Annex 2: Beam Detailing......................................................................................................... 32
ETABS 2016 Concrete Frame Design ..................................................................................... 33
ETABS 2016 Concrete Frame Design ..................................................................................... 34
Structural Analysis and Design Reports of Residential Building
1. INTRODUCTION
The basic aim of the structural design is to build a structure, which is safe, fulfilling the
intended purpose during its estimated life span, economical in terms of initial and maintenance
cost, durable and also maintaining a good aesthetic appearance.
A building is considered to be structurally sound, if the individual elements and the building
as a whole satisfy the criteria for strength, stability and serviceability and in seismic areas
additional criteria for ductility and energy absorption capabilities. The overall building must
be strong enough to transfer all loads through the structure to the ground without collapsing or
losing structural integrity by rupture of the material at the critical sections, by transformation
of the whole or parts into mechanisms or by instability.
1
Structural Analysis and Design Reports of Residential Building
should not have any damage during minor level of shaking. In case of moderate shaking the
structure is allowed to have some non-structural damage without endangering life and property
within the structure. During such event the level of damage should be such that it can be
economically repaired.
The structures are generally designed for much lower seismic forces than what it may actually
experience during its life time. Since the structure is expected to undergo damage in the event
of a severe shaking, reliance is placed on the inelastic response of the structure beyond yield.
Therefore, structures have to be ductile and capable of dissipating energy through inelastic
actions. Ductility can be achieved by avoiding brittle modes of failures. Brittle modes of
failures include, shear and bond failure. Thus, structures should be designed on Weak Beam-
Strong column philosophy.
2
Structural Analysis and Design Reports of Residential Building
4. BUILDING DESCRIPTION
Location:
Parapet Height 3 ft
Slab thickness 5”
3
Structural Analysis and Design Reports of Residential Building
5. STRUCTURAL SYSTEM
Material: Reinforced Cement Concrete
Material Strengths:
Member Concrete Grade
Columns M20
Beams M20
Slabs M20
Foundation M20
4
Structural Analysis and Design Reports of Residential Building
Steel
6. LOADS ADOPTED
Load calculation is done using the NBC 102:1994 as reference. At first type of material is
selected and value of unit weight of the materials is taken from the above-mentioned code.
Thickness of the material is selected as per the design requirement. Knowing area, thickness
and unit weight of materials, loads on each section is found.
The following are assumed for detail load calculation.
R.C.C Slab, Beam and Column = 25.0 KN/m3
Screed (25mm thick) = 19.2 KN/m3
Cement Plaster (20mm thick) = 20.40 KN/m3
Marble Dressed = 26.50 KN/m3
Telia Brick = 19 KN/m3
5
Structural Analysis and Design Reports of Residential Building
Live Load
Live load for the floor and Roof is taken from IS 875 parts 2 as referred by National
building code. For Residential Building, following load has be taken (Table 1, IS 875
Part 2)
All rooms and kitchens - 2 KN/m2
Toilet and bath rooms - 2 KN/m2
Corridors, passages, staircases including tire escapes and storerooms - 3 KN/m2
Balconies - 3 KN/m2
For Roof Load, Table 2 of IS 875 parts 2 has been taken for the estimation.
Flat, sloping or curved roof with slopes up to and including 10 degrees
Access provided - 1.5 KN/m2
Access not provided except for maintenance -0.75 KN/m2
Floor Finish
Floor Finish Load is calculated Simple Marble Finishes. With load calculation
6
Structural Analysis and Design Reports of Residential Building
Wall Loads
Wall loads are applied on underneath beam if wall is rested on the beam. For partition wall
load is applied as the area load intensity. Load intensity is calculated by dividing total weight
of partition wall by the area of given slab portion.
Seismic Zone Z
Kathmandu 0.36
(Zone V)
Important Factor
Building Occupancy Type I
Residential Building 1.0
8. PRELIMINARY DESIGN
For the analysis, dead load is also necessary which depends upon the size of member itself. So
it is necessary to pre-assume logical size of member which will neither overestimate the load
nor under estimate the stiffness of the building. So, the tentative sizes of the structural elements
are determined through the preliminary design so that the pre-assumed dimensions may not
deviate considerably after analysis thus making the final design both safe and economical.
Tentative sizes of various elements have been determined as follows:
7
Structural Analysis and Design Reports of Residential Building
Slab:
Preliminary design of slab is done as per the deflection criteria as directed by code Clause
23.2.1 of [IS 456: 2000]. The cover provided is 20 mm and the grade of concrete used in the
design is M20.
According to which,
Span ≤ (Mft x Mfc) x Basic Value
Eff. Depth
Where, the critical span is selected which is the maximum shorter span among the all slab
element. This is done to make uniformity in slab thickness. The amount of reinforcement will
be varied slab to slab but the thickness will be adopted corresponding to the entire slab.
Beam:
Preliminary design of the beam is done as per the deflection criteria as directed by code Clause
23.2.1 of [IS 456: 2000] and ductility criteria of ACI code. The cover provided is 30 mm and
the grade of concrete used in the design is M20.
According to which,
Span ≤ (Mft x Mfc) x Basic Value x Correction Factor
Eff. Depth for span x Correction Factor for Flange
But,
According to Ductility code, Spacing of Stirrups in beam should not exceed d/4 or 8 times
diameter of minimum size of bar adopted and should not be less than 100 mm. So, for
considering construction difficulties in actual field, it is logical to use d/4 as spacing as per the
construction practice in Nepal.
COLUMN:
Preliminary design of column is done from the assessment of approximate factored gravity
loads and live loads coming up to the critical section. To compensate the possible eccentric
loading and earthquake loads the size is increased by about 25% in design. For the load acting
in the column, live load is decreased according to IS 875: 1978. Initially a rectangular column
is adopted in this building project so as to provide internal aesthetics required from architecture
point of view but the column size and shape will vary as per the requirement for the analysis,
design and aesthetic value. The cover provided is 40 mm and the grade of concrete used in the
column design is M20.
8
Structural Analysis and Design Reports of Residential Building
9
Structural Analysis and Design Reports of Residential Building
b) Live load
Application of live load is shown in figure below.
10
Structural Analysis and Design Reports of Residential Building
11
Structural Analysis and Design Reports of Residential Building
c) Wall load
Load coming from the weight of wall is applied on the beam underneath the wall if there is
not any beam below the wall load is applied to nearby beam in the direction of wall. Application
of wall load is shown in figure below.
12
Structural Analysis and Design Reports of Residential Building
13
Structural Analysis and Design Reports of Residential Building
i. 1.5 DL + 1.5 LL
ii. 1.2 DL + 1.2 LL + 1.2 EQ
iii. 1.2 DL + 1.2 LL - 1.2 EQ
iv. 1.5 DL + 1.5 EQ
v. 1.5 DL - 1.5 EQ
vi. 0.9 DL + 1.5 EQ
vii. 0.9 DL – 1.5 EQ
Where,
14
Structural Analysis and Design Reports of Residential Building
Input Data
Name StoryResp1
Plot
15
Structural Analysis and Design Reports of Residential Building
Input Data
Name StoryResp1
Plot
16
Structural Analysis and Design Reports of Residential Building
The maximum top displacement under extreme load condition (EQx and EQy) is about
4.1 mm in Y and 4.0 mm in X direction and the maximum story drift is 0.07 % which is
in the permissible value (0.4%) prescribed by the code.
17
Structural Analysis and Design Reports of Residential Building
18
Structural Analysis and Design Reports of Residential Building
19
Structural Analysis and Design Reports of Residential Building
20
Structural Analysis and Design Reports of Residential Building
Critical
Column
21
Structural Analysis and Design Reports of Residential Building
Critical
Column
22
Structural Analysis and Design Reports of Residential Building
Critical
Column
23
Structural Analysis and Design Reports of Residential Building
24
Structural Analysis and Design Reports of Residential Building
25
Structural Analysis and Design Reports of Residential Building
The dimension of footing has been calculated in the excel sheet as shown below: Joint Reaction
is given in below:
26
Structural Analysis and Design Reports of Residential Building
27
Structural Analysis and Design Reports of Residential Building
Experiences from past earthquakes and extensive laboratory works have shown that a well-
designed and detailed reinforced concrete structure is suitable for earthquake resistant
structure. Ductility and strength required to resist major earthquake can be achieved by
following the recommendations made in the standard codes of practice for earthquake resistant
design.
Design and construction of the structure are inter – related jobs. A building behaves in a manner
how it has been built rather than what the intensions is during designing. A large percentage of
structural failures are attributed due to poor quality of construction. Therefore, quality
assurance is needed in both design and construction.
28
Structural Analysis and Design Reports of Residential Building
29
Structural Analysis and Design Reports of Residential Building
ANNEX
30
Structural Analysis and Design Reports of Residential Building
31
Structural Analysis and Design Reports of Residential Building
32
Structural Analysis and Design Reports of Residential Building
Section Properties
b (mm) h (mm) bf (mm) ds (mm) dct (mm) dcb (mm)
228.6 355.6 228.6 0 30 30
Material Properties
Ec (MPa) fck (MPa) Lt.Wt Factor (Unitless) fy (MPa) fys (MPa)
22360.68 20 1 500 500
33
Structural Analysis and Design Reports of Residential Building
Section Properties
b (mm) h (mm) dc (mm) Cover (Torsion) (mm)
304.8 304.8 56 30
Material Properties
Ec (MPa) fck (MPa) Lt.Wt Factor (Unitless) fy (MPa) fys (MPa)
22360.68 20 1 500 500
34
Structural Analysis and Design Reports of Residential Building
35
Structural Analysis and Design Reports of Residential Building
Calculations
Assume the thickness of slab as 127 mm ; Effective depth, d = 108 mm
Effective span, lx = 3.175 m (or) 3.053 m whichever is less; d = 3.053 m
ly = 4.17 m (or) 4.048 m whichever is less; d = 4.048 m
(ly / lx ) = 1.33 < 2 ; Here, (l y / lx ) is less than 2, Hence design the slab as two way slab
Load Calculations
Dead Load of slab = 0.127 x 25 = 3.18 KN/m 2 Dust Load on slab = 0 KN/m 2
2
Finishes load on slab = 1.00 KN/m Other load on slab = 0 KN/m 2
2
Live Load on slab = 2.0 KN/m
Total Dead load acting on the Structure = 4.18 KN/m 2
Total live load acting on the Structure = 2.0 KN/m 2
2
Factored Design Load w = 9.27 KN/m
Moment Calculation
2 2
Max. BM per unit width, Mx = ax w l x & My = ay w l x
2 2
KNm N/mm % mm
For Short Span,
Reinforcement details
At mid span, 5.08 0.44 0.1252 152
At supports, 0.00 0.00 0 152 Provide Y 8 @ 150 mm c/c at midspan &
For Long span, supports for short span (Ast pro. = 335 mm 2 )
At mid span, 3.02 0.30 0.0846 91 Provide Y 8 @ 150 mm c/c at midspan &
At supports, 3.89 0.39 0.1106 119 supports for long span (Ast pro. = 335 mm 2 )
36
Structural Analysis and Design Reports of Residential Building
FORCES DETAILS :
Axial Load = P1 = 240 kN 240 kN
Moment along Major axis = Mx = 0.00 kN-m
Moment along Minor axis = Mz = 0 kN-m
FOOTING DETAILS :
Length = L = 60in 1.524 m
Width = B = 60in 1.524 m 1.0
Depth = D = 0.5 m
MATERIAL CONSTANT :
Concrete Grade = M - 20 N/mm2
R/f Grade = Fe - 500 N/mm2 1.52
Load Factor = gf = 1.5 Z Z
DESIGN FORCES :
Axial load = P = 240.00 kN
Self Weight of Footing = 24.00 kN X
1.52
PRESSURE CALCULATION :
SBC = 120 kN/m²
FOR EARTHQUAKE CONDITION ALLOWABLE S.B.C = 1.25 x 120 = 150 kN/m²
P + Mx + Mz
P=
A - Zx - Zz
37
Structural Analysis and Design Reports of Residential Building
1524
587
1524 350
350
587
113.7
kN/m² 113.7
kN/m²
38
Structural Analysis and Design Reports of Residential Building
0.587
1.52
V = 15.57 kN
1.5 x 15.57
= x 10000
1000 x 450
= 0.052 N / mm2
< tv
HENCE SAFE
39
Structural Analysis and Design Reports of Residential Building
0.587
1.52 0.587
0.137
1.52
V = 15.57 kN
Vu
\ Actual Shear stress tv =
bxd
1.5 x 15.57
= x 10000
1000 x 450
= 0.052 N / mm2
\ tc = 0.33 N / mm2 Pt tc
0.15 0.28
< tv 0.2 0.33
HENCE SAFE
1.52
0.8
d/2
40
Structural Analysis and Design Reports of Residential Building
= 113.67 x 1.682576
= 191.25 kN
= 3.20 m
Vu
\ Actual Shear stress tv =
bxd
1.5 x 191.25
= x 10000
3200.00 x 450
= 0.199 N / mm2
where,
ks = ( 0.5+b )
Where,
tc = 0.25 fck
tc = 0.25 M - 20 = 1.12 N/mm2
41
Structural Analysis and Design Reports of Residential Building
Mu= 0.36*fck*b*xu*(d-0.416*xu)+Asc*(fsc-fcc)*(d-d')
where,
xu
fs= 0.87*fy if the section is balanced or under reinforced < 0.87*fy if the section is
over reinforced and shall correspond to strain es= 0.0035(d-xu)/xu
a) Assume xu = xu,l
xu,l 132.703583 mm
0.696*fy/Es= 0.00174
Hence, fsc= 270.4723
Hence, fcc= 7.984658
c) Compute modified value of xu as,
xu= 53.75385253 OK
xu< xul Hence it is an Under Reinforced Section.
Mu= 58.858 KN-m
Sagging Moment Resistance Capacity (Mu)=58.858kN-m
The Hogging Moment Resisting Capacity =
42
Structural Analysis and Design Reports of Residential Building
Mu= 0.36*fck*b*xu*(d-0.416*xu)+Asc*(fsc-fcc)*(d-d')
where,
xu
fs= 0.87*fy if the section is balanced or under reinforced < 0.87*fy if the section is
over reinforced and shall correspond to strain es= 0.0035(d-xu)/xu
a) Assume xu = xu,l
xu,l 132.703583 mm
0.696*fy/Es= 0.00174
Hence, fsc= 270.4723
Hence, fcc= 7.984658
c) Compute modified value of xu as,
xu= 53.75385253 OK
xu< xul Hence it is an Under Reinforced Section.
Mu= 58.858 KN-m
Sagging Moment Resistance Capacity (Mu)=58.858kN-m
The Hogging Moment Resisting Capacity =
43
Structural Analysis and Design Reports of Residential Building
Lower Story
Grade of Concrete= M20
Grade of Steel= Fe500
Size Length(b)= 300mm Breadth(D)= 300mm
Pu= 0.00kN d'/D= 0.15
Ast Provided= 1256 mm²
d'/D= 0.15
p/fck= 0.06977778
Pu/fckbD= 0
Mu/fckbD²= 0.1 Use SP16 Chart 49 Pg. 134
Mu= 54.00kN-m
Upper Story
Grade of Concrete= M20
Grade of Steel= Fe500
Size Length= 300mm Breadth= 300mm
Pu= 0.00kN
Ast Provided= 1256 mm²
d'/D= 0.15
p/fck= 0.06977778
Pu/fckbD= 0
Mu/fckbD²= 0.11 Use SP16 Chart 49 Pg. 134
Mu= 59.40kN-m
Total= 113.40kN-m
Beam Column Ratio= 1.016
Hence The Beam Column Capacity Ratio is 1.016
44