A2F-FF: CMP Products Cable Gland Catalogue
A2F-FF: CMP Products Cable Gland Catalogue
A2F-FF: CMP Products Cable Gland Catalogue
F E
A2F Internationally Approved, Flat-Form Mechanical Classifications* Impact = Level 8, Cable Anchorage = Class B
Explosive Atmosphere Cable Gland Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
• -60˚C to +130˚C (standard), -20˚C to 200˚C (ThermEx option) Compliance Standards IEC 60079-0,1,7,15,31
Cable Gland Material Brass, Electroless Nickel Plated Brass, Stainless Steel, Aluminium
* Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444
** When CMP installation accessories are used. Refer to page 7 or www.cmp-products.com for further information.
*** IP68 tested to a minimum depth of 30 metres for 12 hours, alternate depths / durations can be provided upon request
Cable Gland Selection Table Dimensions listed below are for metric cable glands only
Refer to illustration at the top of the page. Dimensions for alternative threads may vary, please see supplementary technical data sheet
Available Entry Threads “C” Across
(Alternate Metric Thread Lengths Available) Overall Cable Across Combined Ordering Reference
Corners
Diameter “A” (h x w) Flats “D” (*Brass Metric) Cable
Cable Gland Standard Option “D” Protrusion
Gland Weight
Size Thread Length “F”
Thread Length Ordering (Kgs)
Metric NPT Length (NPT) NPT Min Max Max Max Size Type
(Metric) “E” Suffix
“E”
20S M20 15.0 ½” 19.9 ¾” 4.0 x 6.2 6.8 x 11.7 24.0 26.4 25.1 20S A2FFF 1RA 0.054
20 M20 15.0 ½” 19.9 ¾” 5.7 x 8.0 8.7 x 13.5 27.0 29.7 27.2 20 A2FFF 1RA 0.059
*For material options add the following suffix to the Ordering Reference; Brass (no suffix required); Nickel Plated Brass ‘5’; 316 Grade Stainless Steel ‘4’; Copper Free Aluminium ‘1’
For NPT options please add the following digits to the material suffix ; ½” = 31, ¾” = 32, 1” = 33
Examples: 25A2FFF1RA432 = Stainless Steel ¾” NPT, 20A2FFF1RA5 = Nickel Plated Brass M20