Transformer
Transformer
Transformer
Building Services
In a multi!storied building, the substation shall preferably be installed on the lowest floor level, but direct access
from the street for installation or removal of the equipment shall be provided. The floor level of the substation or
switch room shall be above the highest flood level of the locality. Suitable arrangements should exist to prevent
the entrance of storm or flood water into the substation area.
The location of a substation will depend on (i) the feed point of the 11 KV Supply Authority line and (ii) the
location of the LT vertical riser cables.
It is preferable to locate the air!conditioning plant room (if any) adjacent to the electrical substation in such a way
that the distance from the controlling switchboard of the air!conditioning plant rooms and corresponding
switches in the electrical substation are kept minimum.
In case of a building complex, or a group of buildings belonging to the same organization, the substation should
preferably be located in a separate building and should be adjacent to the generator room, if any. Location of
substation in the basement floor and on the floors above ground floor level (GFL) preferably be avoided. If Sub!
Station it to be installed on the basement floor or the floors above ground floor level (GFL) special safety
measures is to be taken by the user or owner. Measures are as follows:
(i) No objection certificate stating the Sub!Station safe by the Fire Service and Civil Defense
Department.
(ii) Certification of the building consultant stating safe, Proper ventilation, Easy entrance and exit and
safe load bearing capacity of the floors above the ground floor level (GFL).
(iii) Proper undertaking of the Sub!Station user or owner as the case may be, Stating safety and liability
will be ensured by them.
In case the electric substation has to be located within the main building itself for unavoidable reasons, it
should be located on ground floor or Basement floor or the floors above the ground floor (GFL) with easy
access from outside.
1.3.23.3 Height, Area, Floor Level and other requirements of a Substation Room
a) The minimum height of a substation room should be 3.0m to 3.6m depending upon the size of the
transformer.
b) The minimum area required for substation and transformer room for different capacities are given in
Table 8.1.24.
c) For transformers having large oil content (more than 2000 litres), soak pits are to be provided.
The areas given in Table 8.1.24 hold good if they are provided with windows and independent access doors in
accordance with local regulations.
All the rooms shall have significant ventilation. Special care should be taken to ventilate the transformer rooms
and where necessary louvers at lower level and exhaust fans at higher level shall be provided at suitable locations
in such a way that cross ventilation is maintained. Fans should be provided so that the transformer gets air supply
from the fans.
The floor level of the substation should be high. Arrangement shall be made to prevent storm water entering the
transformer and switch rooms through the soak pits, if floor level of the substation is low.
Sub!Station of higher voltage may also be considered to the basement floor having proper & safe building design.
Table 8.1.24 Area Required for Transformer and Recommended Minimum Area for Substation of Different Capacities
Capacity of Transformer Total Substation Area (with HT, LT Panels & Transformer Room
Transformer Area but without Generators)
(kVA) (m2) (m2)
1x150 12 45
1x250 13 48
2x250 26 100
1x400 13 48
2x400 30 100
3x400 40 135
8!46 Vol. 3
Electrical and Electronic Engineering Services for Buildings Chapter 1
2x630 26 100
3x630 40 190
2x1000 40 180
3x1000 45 220
!"!#"!$! %&'()*+',+-(.+/01*+'2+320+/01*+/2456,'27*26+
Dry type transformer should be installed where risk of spreading of fire is high and where flammable materials are
to be kept around the substation.
For Hospital buildings, Multistoried Shopping Centers Dry type transformers should be used to for minimizing fire
risks.
An Industrial buildings containing inflammable materials, Chemical and having the substation in the same
building Dry type transformers should be used for minimizing fire risks.
in such a way that cross ventilation is maintained. Ceiling fans must be provided so that the transformer gets air
supply from the ceiling fans.
Capacity Area
(kW) (m2)
1x25 20
1x48 24
1x100 30
1x150 36
1x300 48
1x500 56
8!48 Vol. 3