Vertiv Netsure 701 PDF
Vertiv Netsure 701 PDF
Vertiv Netsure 701 PDF
Table of Contents
Admonishments Used in this Document ............................................................................................................... vi
Important Safety Instructions ............................................................................................................................. vii
General Safety ....................................................................................................................................................... vii
Voltages ................................................................................................................................................................ vii
Battery .................................................................................................................................................................. vii
Hazardous Voltage ............................................................................................................................................... viii
Handling Equipment Containing Static Sensitive Components ............................................................................... viii
Static Warning ..................................................................................................................................................... ix
FCC Information .................................................................................................................................................... x
System Overview .................................................................................................................................................. 1
Preface ................................................................................................................................................................... 1
System Description ................................................................................................................................................. 1
Navigating the MCA .............................................................................................................................................. 2
MCA Messages ....................................................................................................................................................... 5
System Operating Procedures ............................................................................................................................. 21
LMS1000 Operating Procedures ............................................................................................................................ 21
Rectifier Operating Procedures ............................................................................................................................. 21
WinLink Software User Instructions ....................................................................................................................... 21
MCA Ethernet Card WEB Interface User Instructions .............................................................................................. 21
Pre-Charging Load Capacitors ............................................................................................................................... 21
Battery Temperature Probe Concentrator Module (TXM) ....................................................................................... 21
Local Controls, Indicators, and Test Points ............................................................................................................. 21
Location and Identification ............................................................................................................................ 21
MCA Display .................................................................................................................................................. 24
MCA Front Panel Accessed Interface Pad ........................................................................................................ 25
Low Voltage Disconnect NOR/INH Switch and INH Indicator (if low voltage disconnect load
contactor is furnished) ................................................................................................................................... 28
Manual Battery Disconnect Switch and Indicator (List RB, RC, RD Only) ........................................................... 29
Optional System Load Shunt Test Point Kit ..................................................................................................... 29
List 63 and 64 DC-DC Converter System (if furnished)..................................................................................... 30
External Alarms..................................................................................................................................................... 31
Starting and Stopping System Operation ............................................................................................................... 33
Rectifier Module Normal Starting Procedure .................................................................................................. 33
Rectifier Module Stopping Procedure (Local) .................................................................................................. 33
Rectifier Module Stopping Procedure (Remote) (if LMS1000 Monitoring System furnished) ............................ 33
List 63 and 64 DC-DC Converter System Starting and Stopping Procedures (if furnished) ................................ 34
Initially Connecting Battery and System Output to the Controlled Load(s) when Low Voltage
Disconnect Load Contactor is Furnished and Set for Manual Reconnect .......................................................... 34
Output Voltage Mode of Operation Selection ........................................................................................................ 34
Placing the System into the Float Mode of Operation ...................................................................................... 34
DANGER! Warns of a hazard the reader will be exposed to that will likely result in death or serious injury
if not avoided. (ANSI, OSHA)
Danger
WARNING! Warns of a potential hazard the reader may be exposed to that could result in death or
serious injury if not avoided. This admonition is not used for situations that pose a risk only to
equipment, software, data, or service. (ANSI)
Warning
CAUTION! Warns of a potential hazard the reader may be exposed to that could result in minor or
moderate injury if not avoided. (ANSI, OSHA) This admonition is not used for situations that pose a risk
only to equipment, data, or service, even if such use appears to be permitted in some of the applicable
Caution standards. (OSHA)
ALERT! Alerts the reader to an action that must be avoided in order to protect equipment, software,
data, or service. (ISO)
Alert
ALERT! Alerts the reader to an action that must be performed in order to prevent equipment damage,
software corruption, data loss, or service interruption. (ISO)
Alert
FIRE SAFETY! Informs the reader of fire safety information, reminders, precautions, or policies, or of the
locations of fire-fighting and fire-safety equipment. (ISO)
Fire Safety
SAFETY! Informs the reader of general safety information, reminders, precautions, or policies not related
to a particular source of hazard or to fire safety. (ISO, ANSI, OSHA)
Safety
DANGER!
DANGER! This system produces DC Power and may have
YOU MUST FOLLOW APPROVED SAFETY PROCEDURES.
Danger
Danger a battery source connected to it. Although the DC
Performing the following procedures may expose you to voltage is not hazardously high, the rectifiers and/or
hazards. These procedures should be performed by battery can deliver large amounts of current. Exercise
qualified technicians familiar with the hazards extreme caution not to inadvertently contact or have
associated with this type of equipment. These hazards any tool inadvertently contact an output terminal or
may include shock, energy, and/or burns. To avoid battery terminal or exposed wire connected to an
these hazards: output terminal or battery terminal. NEVER allow a
metal object, such as a tool, to contact more than one
a) The tasks should be performed in the order termination or battery terminal at a time, or to
indicated. simultaneously contact a termination or battery
terminal and a grounded object. Even a momentary
b) Remove watches, rings, and other metal objects. short circuit can cause sparking, explosion, and injury.
Voltages
AC Input Voltages WARNING! Special safety precautions are required for
Warning procedures involving handling, installing, and servicing
DANGER! This system operates from AC input voltage batteries. Observe all battery safety precautions in this
capable of producing fatal electrical shock. AC input manual and in the battery instruction manual. These
Danger
power must be completely disconnected from the precautions should be followed implicitly at all times.
branch circuits wiring used to provide power to the
system before any AC electrical connections are made.
Follow local lockout/tagout procedures to ensure
upstream branch circuit breakers remain de-energized
during installation. DO NOT apply AC input power to
the system until all electrical connections have been
completed and checked.
WARNING! A battery can present a risk of electrical DANGER! This equipment may be used in conjunction
Warning shock and high short circuit current. Servicing of Danger with lead-acid batteries. Working near lead-acid
batteries should be performed or supervised only by batteries is dangerous!
properly trained and qualified personnel knowledgeable
• Batteries contain sulfuric acid.
about batteries and the required precautions.
• Batteries generate explosive gases during normal
The following precautions should be observed when operation. Systems containing batteries should
working on batteries: never be installed in an airtight room or space.
Only install in a ventilated environment.
• Remove watches, rings, and other metal objects.
• Batteries are an energy source that can produce
• Eye protection should be worn to prevent injury
high amounts of electrical current.
from accidental electrical arcs.
FOR THESE REASONS, IT IS OF CRITICAL IMPORTANCE
• Use certified and well maintained insulated tools.
THAT YOU READ THESE INSTRUCTIONS AND FOLLOW
Use double insulated tools appropriately rated for
THEM EXACTLY.
the work to be performed. Ensure that wrenches
with more than one working end have only one end WHEN WORKING WITH LEAD-ACID BATTERIES:
exposed.
• Wear complete protection for eyes, face, hands,
• Do not lay tools or metal parts on top of batteries. and clothing. Examples are safety goggles or face
shield, a rubber apron and gloves.
• Disconnect charging source prior to connecting or
disconnecting battery terminals. • If battery acid enters your eye, immediately flush
your eye with running cold water for at least 15
• Risk of explosion if battery is replaced with an
minutes. Get medical attention immediately.
incorrect type or if polarity is reversed. When
replacing batteries, replace with the same • If battery acid contacts skin or clothing, wash
manufacturer and type, or equivalent. immediately with soap and water.
Static Warning
This equipment contains static sensitive components. The warnings listed below must be observed to prevent damage to these
components. Disregarding any of these warnings may result in personal injury or damage to the equipment.
2. Before touching any equipment containing static sensitive components, discharge all static electricity from yourself by wearing
a wrist strap grounded through a one megohm resistor. Some wrist straps, such as Emerson Network Power Part Number
631810600, have a built-in one megohm resistor; no external resistor is necessary. Read and follow wrist strap manufacturer’s
instructions outlining use of a specific wrist strap.
4. After removing equipment containing static sensitive components, place the equipment only on conductive or anti-static
material such as conductive foam, conductive plastic, or aluminum foil. Do not use ordinary Styrofoam™ or ordinary plastic.
5. Store and ship equipment containing static sensitive components only in static shielding containers.
6. If necessary to repair equipment containing static sensitive components, wear an appropriately grounded wrist strap, work on a
conductive surface, use a grounded soldering iron, and use grounded test equipment.
FCC Information
The MCA Interface Modem Option (if installed) has been granted a registration number by the Federal Communications Commission,
under Part 68 rules and regulations for direct connection to the telephone lines. In order to comply with these FCC rules, the following
instructions must be carefully read and applicable portions followed completely:
1. Direct connection to the telephone lines may be made only through the standard plug- ended cord furnished to the
utility-installed jack. No connection may be made to party or coin phone lines. Prior to connecting the device to the telephone
lines, you must:
2. Call your telephone company and inform them you have an FCC registered device you desire to connect to their telephone
lines. Give them the number(s) of the line(s) to be used, the make and model of the device, the FCC registration number and
ringer equivalence. This information will be found on the device or enclosed with instructions as well as the jack suitable for
your device.
3. After the telephone company has been advised of the above you may connect your device if the jack is available, or after the
telephone company has made the installation.
4. Repairs may be made only by the manufacturer or his authorized service agency. Unauthorized repairs void registration and
warranty. Contact seller or manufacturer for details of permissible user performed routine repairs, and where and how to have
other than routine repairs.
5. If, through abnormal circumstances, harm to the telephone lines is caused, it should be unplugged until it can be determined if
your device or the telephone line is the source. If your device is the source, it should not be reconnected until necessary repairs
are effected.
6. Should the telephone company notify you that your device is causing harm, the device should be unplugged. The telephone
company will, where practicable, notify you, that temporary discontinuance of service may be required. However, where prior
notice is not practicable, the telephone company may temporarily discontinue service, if such action is reasonably necessary, in
such cases the telephone company must (A) Promptly notify you of such temporary discontinuance, (B) Afford you the
opportunity to correct the condition and (C) Inform you of your rights to bring a complaint to the FCC under their rules.
7. The telephone company may make changes in its communications facilities, equipment, operations or procedures, where such
action is reasonably required in the operation of its business and is not inconsistent with FCC rules. If such changes can be
reasonably expected to render any customer’s devices incompatible with telephone company facilities, or require modification
or alteration, or otherwise materially affect its performance, written notification must be given to the user, to allow
uninterrupted service.
The following information is provided here and on a label attached to the outside of the MCA Interface Modem Option (if installed).
FUNCTION FUNCTION
ALARM CUTOFF SELECT SET
YES
Navigating the MCA is an easy process. You just have to remember a few key combinations (as shown in the following chart).
FUNCTION
SET At any level in the MCA menus,
YES pressing YES and NO simultaneously
Getting to Home Position
takes you back to the beginning of the
NO MCA menu tree.
NOTES
Low voltage disconnect alarms are not displayed if no LVDs are installed.
Low voltage disconnect entries are not displayed if no LVDs are installed.
The "RESTORE MFG CAL" entry is displayed only if "CAL SYS" or "CAL SUB" has been changed from its default.
MCA Messages
The following chart provides an explanation of each MCA message appearing on the MCA Menu Tree (Section 6022). The MCA Menu
Tree is located in the separate INSTALLATION MANUAL and the CD CARRIER MANUAL. It is also provided on the CD (Electronic
Documentation Package) furnished with your system. Note that each line in the MCA Menu Tree contains a number. This number is
referenced in the following chart.
MCA
Menu
Tree Associated Can this value be
Message Displayed Definition
Line No. with... changed?
(Section
6022)
0 SYSTEM OK Normal Display NO ALARMS ARE ACTIVE. No
THERE ARE ACTIVE ALARMS.
## ALARMS ACTIVE ## = number of active alarms.
or or
1 NOT RUNNING YET! Normal Display No Rectifier Modules (PCUs) are No
or communicating with the MCA.
............................... or
Display has "timed-out".
Displays if a Rectifier Module (PCU)
Main
2 ALARM EMERG STOP emergency shutdown or fire alarm No
Alarm Menu
disconnect signal is applied to the system.
Main Displays if any low voltage disconnect
3 ALARM LVD ACTIVE No
Alarm Menu circuit has disconnected.
ALARM SYS 50% BOD Displays if system voltage decreases to a
or preset adjustable value, indicating that the
Main
4 ALM VERY LO VOLT battery has been continuously supplying No
Alarm Menu
or the load and has discharged to
ALARM LO VOLTAGE approximately half its reserve time.
MCA
Menu
Tree Associated Can this value be
Message Displayed Definition
Line No. with... changed?
(Section
6022)
Displays if AC input voltage to all Rectifier
Main
13 ALARM ALL AC OFF Modules (PCUs) decreases to a preset No
Alarm Menu
non-adjustable value.
Main
14 ALARM HI AC LINE Not implemented in this system. No
Alarm Menu
Displays if any Rectifier Module (PCU) fail
alarm occurs.
ALM ## PCUs FAIL ## = number of failed Rectifier Modules
or (PCUs).
ALARM MRFA or
Main Multiple Rectifier Modules (PCUs) Failed.
15 or No
Alarm Menu
ALARM 1 RFA or
or 1 Rectifier Module (PCU) Failed.
NO PCUs FOUND or
No Rectifier Modules (PCUs) are
communicating with the MCA.
Displays if the Rectifier Module (PCU) is
Main not sharing the load properly.
15B ALM PCU## SHARE No
Alarm Menu
## = number of Rectifier Module (PCU).
Main Displays if any Temperature Sensor alarm
15A ALM TEMP SENSOR No
Alarm Menu occurs.
Main Displays if system current increases to a
16 ALM SYSTEM CURR No
Alarm Menu preset adjustable value.
Displays if subsystem (if connected)
Main
17 ALM SUBSYS CURR current increases to a preset adjustable No
Alarm Menu
value.
Main Displays if battery recharge current limit is
17A ALM BAT CHG CURR No
Alarm Menu exceeded.
Main Displays if a subsystem minor alarm
18 ALM SUBSYS MINOR No
Alarm Menu occurs.
Main
19 ALARM MCA/SHELF Displays if an MCA fail alarm occurs. No
Alarm Menu
Main
20 FUNCTION MENU Moves you to this menu. No
Alarm Menu
Moves you to the beginning of the MCA
Main
21 NORMAL DISPLAY Menu Tree. "SYSTEM OK" or No
Alarm Menu
"##ALARMS ACTIVE" is displayed.
Displays which low voltage disconnect
circuit operated (either 1A, 1B, 2A, 2B,
LVD 3A, and/or 3B).
22 LVD ** ACTIVATED No
Alarm Menu
** = the designation of the LVD alarm
(either 1A, 1B, 2A, 2B, 3A, or 3B).
MCA
Menu
Tree Associated Can this value be
Message Displayed Definition
Line No. with... changed?
(Section
6022)
Allows manual reconnection of an
activated low voltage disconnect circuit.
** = the designation of the LVD circuit
(either 1A, 1B, 2A, 2B, 3A, or 3B). The
first activated LVD circuit is displayed.
Press the FUNCTION SELECT UP or
DOWN arrow pushbutton to display the Yes, see "System
LVD next or previous activated, respectively,
23 RECONNECT LVD ** Operating
Alarm Menu LVD circuit. Press the ALARM CUTOFF Procedures".
and FUNCTION SET ENTER pushbuttons
simultaneously to cause this LVD circuit to
reconnect. At the "ARE YOU SURE? + -"
prompt, press either the FUNCTION SET
YES (+) pushbutton to reconnect, or the
FUNCTION SET NO (-) pushbutton to
cancel this operation.
LVD
24 MAIN ALARM MENU Moves you back to this menu. No
Alarm Menu
Moves you to the beginning of the MCA
LVD
25 NORMAL DISPLAY Menu Tree. "SYSTEM OK" or No
Alarm Menu
"##ALARMS ACTIVE" is displayed.
Displays which Rectifier Module (PCU)
PCU failed.
26 PCU ** FAILURE No
Alarm Menu ** = the designation of the Rectifier
Module (PCU) alarm.
PCU
27 MAIN ALARM MENU Moves you back to this menu. No
Alarm Menu
Moves you to the beginning of the MCA
PCU
28 NORMAL DISPLAY Menu Tree. "SYSTEM OK" or No
Alarm Menu
"##ALARMS ACTIVE" is displayed.
Displays if battery temperature increases
Temperature to a preset adjustable value.
28A TEMP SENSOR ** HI No
Alarm Menu ** = the designation of the temperature
probe.
Displays if battery temperature decreases
Temperature to a preset adjustable value.
28B TEMP SENSOR ** LO No
Alarm Menu ** = the designation of the temperature
probe.
Temperature
28C MAIN ALARM MENU Moves you back to this menu. No
Alarm Menu
Moves you to the beginning of the MCA
Temperature
28D NORMAL DISPLAY Menu Tree. "SYSTEM OK" or No
Alarm Menu
"##ALARMS ACTIVE" is displayed.
MCA
29 MCA BOARD FAIL Displays if the MCA circuit card failed. No
Alarm Menu
MCA Displays if the MCA "system" or "sense"
30 A/D INPUT FUSE No
Alarm Menu fuse opens.
MCA
Menu
Tree Associated Can this value be
Message Displayed Definition
Line No. with... changed?
(Section
6022)
MCA
31 NO SYSTEM VOLTS Displays if no system voltage detected. No
Alarm Menu
MCA Displays if no subsystem (if connected)
32 NO SUBSYS VOLTS No
Alarm Menu voltage detected.
Displays if no sense voltage detected, or
NO SENSE VOLTS an error is detected between the system
MCA
33 or voltage and sense voltage values or No
Alarm Menu
SENSE VOLT ERROR between these values and the
temperature compensation setting.
SHUNT** NO REPLY Displays if bad shunt type detected or
MCA shunt communications lost.
34 or No
Alarm Menu
SHUNT** BAD TYPE ** = the designation of the shunt.
Displays if battery recharge current
exceeds Battery Recharge Current Limit
setting because the Limit feature is
inhibited due to:
• Shunt Type alarms are present, or
MCA • Shunt No Reply alarms are present,
34A BAT CL INHIBITED No
Alarm Menu or
• a =10% of system capacity mismatch
between the Rectifier Module (PCU)
output current and the sum of the
system and battery shunt currents is
present.
LVD** NO REPLY
or
LVD** EPROM FAIL Displays if low voltage disconnect
or communications lost, a low voltage
MCA disconnect circuit card failed, or low
35 LVD** A/D FAILED voltage disconnect communications link to No
Alarm Menu
or MCA broken.
LVD** RELAY FAIL ** = the designation of the LVD circuit.
or
LVD** NO MCA CMD
MCA Displays if the low voltage disconnect
36 LVDs INHIBITED No
Alarm Menu circuits are manually inhibited.
MCA
37 REMOTE NO REPLY Displays if remote communications lost. No
Alarm Menu
MCA Displays if the display communications
38 DISPLAY NO REPLY No
Alarm Menu lost.
Displays if temperature sensor
MCA communications lost.
38A TEMP ** NO REPLY No
Alarm Menu ** = the designation of the temperature
probe.
MCA
39 MAIN ALARM MENU Moves you back to this menu. No
Alarm Menu
MCA
Menu
Tree Associated Can this value be
Message Displayed Definition
Line No. with... changed?
(Section
6022)
Moves you to the beginning of the MCA
MCA
40 NORMAL DISPLAY Menu Tree. "SYSTEM OK" or No
Alarm Menu
"##ALARMS ACTIVE" is displayed.
41 MEASUREMENT MENU Function Menu Moves you forward to this menu. No
Completing this operation places the
SET TEST/EQ MODE system into the float or test/equalize mode
or as determined by the setting displayed Yes, see "System
42 SET FLOAT MODE Function Menu before the "ARE YOU SURE? + -" prompt. Operating
or or Procedures".
TestEq Switch On The user tried to set Float Mode while the
external test/equalize input switch was on.
43 ADJUSTMENT MENU Function Menu Moves you forward to this menu. No
44 CONFIGURE MENU Function Menu Moves you forward to this menu. No
45 CALIBRATION MENU Function Menu Moves you forward to this menu. No
Moves you to the beginning of the MCA
46 NORMAL DISPLAY Function Menu Menu Tree. "SYSTEM OK" or No
"##ALARMS ACTIVE" is displayed.
Displays if Rectifier Module (PCU) in
PCU Emergency Stop Mode.
47 PCU## EMERG STOP No
Detail Menu ## = the designation of the Rectifier
Module (PCU).
Displays if Rectifier Module (PCU) AC fail
PCU alarm active.
48 PCU## AC FAIL No
Detail Menu ## = the designation of the Rectifier
Module (PCU).
PCU
49 PCU## HI AC LINE Not implemented in this system. No
Detail Menu
Displays if Rectifier Module (PCU) fan
PCU failed.
50 PCU## FAN FAIL No
Detail Menu ## = the designation of the Rectifier
Module (PCU).
PCU
51 PCU## BRKR OFF not used in this system No
Detail Menu
Displays if Rectifier Module (PCU) in high
PCU voltage shutdown.
52 PCU## HVS ACTIVE No
Detail Menu ## = the designation of the Rectifier
Module (PCU).
Displays if Rectifier Module (PCU) internal
PCU A/D circuit failed.
53 PCU## A/D FAIL No
Detail Menu ## = the designation of the Rectifier
Module (PCU).
Displays if Rectifier Module (PCU) internal
PCU converter circuit failed.
54 PCU## CONVERTER No
Detail Menu ## = the designation of the Rectifier
Module (PCU).
MCA
Menu
Tree Associated Can this value be
Message Displayed Definition
Line No. with... changed?
(Section
6022)
Displays if Rectifier Module (PCU) high
PCU temperature alarm active.
55 PCU## HIGH TEMP No
Detail Menu ## = the designation of the Rectifier
Module (PCU).
Displays if an external sense lead opens.
PCU
56 PCU## OPEN SENSE ## = the designation of the Rectifier No
Detail Menu
Module (PCU).
PCU
57 PCU## SWITCH OFF not used in this system No
Detail Menu
Displays if the Rectifier Module’s (PCU’s)
PCU communications link is lost.
58 PCU## NO REPLY No
Detail Menu ## = the designation of the Rectifier
Module (PCU).
PCU
59 PCU ALARM MENU Moves you back to this menu. No
Detail Menu
Moves you to the beginning of the MCA
PCU
60 NORMAL DISPLAY Menu Tree. "SYSTEM OK" or No
Detail Menu
"##ALARMS ACTIVE" is displayed.
Measurement Displays system output voltage.
61 SYSTEM ###.##VDC No
Menu ## = value.
Measurement Displays total system load current.
62 SYS LOAD #####A No
Menu ## = value.
Displays total Rectifier Module (PCU) load
Measurement current.
63 PCU LOAD #####A No
Menu
## = value.
Measurement Displays subsystem output voltage.
64 SUBSYS ###.##VDC No
Menu ## = value.
Measurement Displays total subsystem load current.
65 SUB LOAD #####A No
Menu ## = value.
BAT CHG #####A Displays total battery charge current,
or battery charge current limit setting if
Measurement battery charge current is in current limit, or
65A BAT CHG CL #####A No
Menu total battery discharge current.
or
BAT DIS #####A ## = value.
Displays the Sensor Temperature.
Measurement ###ºC = value.
65B T SENSOR ** ###ºC No
Menu ** = the designation of the temperature
probe.
Measurement
66 FUNCTION MENU Moves you back to this menu. No
Menu
Moves you to the beginning of the MCA
Measurement
67 NORMAL DISPLAY Menu Tree. "SYSTEM OK" or No
Menu
"##ALARMS ACTIVE" is displayed.
Adjustment
68 ADJUST SYSTEM Moves you forward to this menu. No
Menu
MCA
Menu
Tree Associated Can this value be
Message Displayed Definition
Line No. with... changed?
(Section
6022)
Adjustment
69 ADJUST ALARMS Moves you forward to this menu. No
Menu
Adjustment
70 ADJUST LVDs Moves you forward to this menu. No
Menu
Adjustment
71 FUNCTION MENU Moves you back to this menu. No
Menu
Moves you to the beginning of the MCA
Adjustment
72 NORMAL DISPLAY Menu Tree. "SYSTEM OK" or No
Menu
"##ALARMS ACTIVE" is displayed.
Configure
73 VERIFY INVENTORY Moves you to the Inventory Menu. No
Menu
SHARE ALARM OFF Yes, see "System
Configure Displays the 'Load Share Alarm' feature
73A or Operating
Menu disabled or enabled.
SHARE ALARM ON Procedures".
EMERG STOP OFF Yes, see "System
Configure Displays the 'Emergency Stop' feature
73B or Operating
Menu disabled or enabled.
EMERG STOP ON Procedures".
REMOTE HVS OFF Yes, see "System
Configure Displays the 'Remote High Voltage
73D or Operating
Menu Shutdown' feature disabled or enabled.
REMOTE HVS ON Procedures".
DISPLAY ROLL OFF Yes, see "System
Configure Displays the alternating display feature
73C or Operating
Menu disabled or enabled.
DISPLAY ROLL ON Procedures".
Configure Moves you to the Rectifier Module (PCU)
74 SET PCU ON / OFF No
Menu Enable Menu.
LOW SPEED FAN OFF Yes, see "System
Configure Displays the Rectifier Module (PCU) low
74A or Operating
Menu speed fan feature disabled or enabled.
LOW SPEED FAN ON Procedures".
Displays the MCA audible alarm cutoff
NAG MINUTES = ## reset time period or that this feature has Yes, see "System
Configure been disabled.
75 or Operating
Menu
AUDIBLE NAG OFF ## = current setting for the Alarm Cutoff Procedures".
Reset Feature (0-15).
MCA
Menu
Tree Associated Can this value be
Message Displayed Definition
Line No. with... changed?
(Section
6022)
Displays the timed test/equalize setting
(and indicates the manually initiated timed
test/equalize feature is enabled).
## = current setting for the manually
initiated timed test/equalize feature (1-99).
or
If the "TEST/EQ HRS = ##" value is
increased above 99, "TEST/EQ MAN
STOP" is displayed to indicate the
manually initiated timed test/equalize
feature is disabled and the system must
TEST/EQ HRS = ## be manually returned to the float mode if
or placed in the test/equalize mode. Yes, see "System
Configure
76 TEST/EQ MAN STOP or Operating
Menu
or If manually initiated timed test/equalize Procedures".
END TEQ ##.##HRS feature is enabled and the system is
placed in the test/equalize mode (via the
MCA interface), remaining test/equalize
time is displayed.
Note: When "TEST/EQ MAN STOP" or
"END TEQ ##.##HRS" is being
displayed, press and release the
ALARM CUTOFF and
FUNCTION SET ENTER
pushbuttons simultaneously to
change the "TEST/EQ HRS =
##" setting.
Indicates the auto test/equalize feature is
disabled.
AUTO EQ DISABLED
or
or Yes, see "System
Configure Displays the auto test/equalize multiplier
76A AUTO EQ MUL = ## Operating
Menu value.
or Procedures".
or
END AUTO ##.## HR
Displays remaining auto test/equalize
time.
Yes, see "System
Configure Sets the Alarm Relay Test feature's time
77 RELAYTEST = ###SEC Operating
Menu period.
Procedures".
Configure
77A SET SPANISH TEXT Sets the Text to Spanish. Yes
Menu
Configure
78 FUNCTION MENU Moves you back to this menu. No
Menu
Moves you to the beginning of the MCA
Configure
79 NORMAL DISPLAY Menu Tree. "SYSTEM OK" or No
Menu
"##ALARMS ACTIVE" is displayed.
Yes, see "MCA
Calibration Allows calibration of the display meter for
80 CAL SYS = ###.##V System
Menu system output voltage reading.
Adjustments".
MCA
Menu
Tree Associated Can this value be
Message Displayed Definition
Line No. with... changed?
(Section
6022)
Yes, see "MCA
Calibration Allows calibration of the display meter for
81 CAL SUB = ###.##V System
Menu subsystem output voltage reading.
Adjustments".
Returns system voltage calibration and
subsystem voltage calibration values back
to their factory defaults. Yes, see "MCA
Calibration
82 RESTORE MFG CAL When the "CAL SYS" or "CAL SUB" System
Menu
setting has been changed, the setting can Adjustments".
be returned to its default value by
performing this operation.
ANALOG TC OFF
or
Calibration
83 TC CAL = ##.##V not used in this system --
Menu
or
TempCmp Hardware
Allows adjusting the system to operate
DIGITAL TC OFF with a battery charge temperature
compensation probe or disabling the
or Yes, see "MCA
Calibration feature.
83A SLOPE = .###V/ºC System
Menu or
or Adjustments".
The user tried to set the SLOPE value
TempCmp Hardware when a temperature compensation
module was also present.
Yes, see "MCA
Calibration Displays maximum voltage with
83B MAX W/T = ##.##V System
Menu temperature compensation set point.
Adjustments".
Yes, see "MCA
Calibration Displays minimum voltage with
83C MIN W/T = ##.##V System
Menu temperature compensation set point.
Adjustments".
TCOMP ON SENSOR1 Selects the temperature compensation
or source. Options are 'SENSOR1' when Yes, see "MCA
Calibration
83D TCOMP ON AVERAGE only one temperature probe is used, or System
Menu
or 'AVERAGE' or 'HIGHEST' when multiple Adjustments".
TCOMP ON HIGHEST probes are used.
Calibration
84 FUNCTION MENU Moves you back to this menu. No
Menu
Moves you to the beginning of the MCA
Calibration
85 NORMAL DISPLAY Menu Tree. "SYSTEM OK" or No
Menu
"##ALARMS ACTIVE" is displayed.
Displays individual load current through a
System system shunt.
86 SYSLOAD** #####A No
Load Menu ** = designation of the system load shunt.
#### = value.
System
87 MEASUREMENT MENU Moves you back to this menu. No
Load Menu
MCA
Menu
Tree Associated Can this value be
Message Displayed Definition
Line No. with... changed?
(Section
6022)
Moves you to the beginning of the MCA
System
88 NORMAL DISPLAY Menu Tree. "SYSTEM OK" or No
Load Menu
"##ALARMS ACTIVE" is displayed.
Displays individual Rectifier Module
(PCU) Load Current
PCU
89 PCU** LOAD #####A ** = designation of the Rectifier Module No
Load Menu
(PCU).
#### = value.
PCU
90 MEASUREMENT MENU Moves you back to this menu. No
Load Menu
Moves you to the beginning of the MCA
PCU
91 NORMAL DISPLAY Menu Tree. "SYSTEM OK" or No
Load Menu
"##ALARMS ACTIVE" is displayed.
Displays individual load current through a
subsystem shunt.
Subsystem
92 SUBLOAD** #####A ** = designation of the subsystem load No
Load Menu
shun.
#### = value.
Subsystem
93 MEASUREMENT MENU Moves you back to this menu. No
Load Menu
Moves you to the beginning of the MCA
Subsystem
94 NORMAL DISPLAY Menu Tree. "SYSTEM OK" or No
Load Menu
"##ALARMS ACTIVE" is displayed.
Displays individual charge or discharge
BAT** CHG #####A
Battery current through a battery shunt.
94A or No
Load Menu ** = designation of the battery shunt.
BAT** DIS #####A
#### = value.
Battery
94B MEASUREMENT MENU Moves you back to this menu. No
Load Menu
Moves you to the beginning of the MCA
Battery
94C NORMAL DISPLAY Menu Tree. "SYSTEM OK" or No
Load Menu
"##ALARMS ACTIVE" is displayed.
System Yes, see "MCA
95 FLOAT = ###.##V Adjustment Displays float voltage set point. System
Menu Adjustments".
System Yes, see "MCA
96 TEST/EQ = ###.##V Adjustment Displays test/equalize voltage set point. System
Menu Adjustments".
System Yes, see "MCA
97 SET HVS = ###.##V Adjustment Displays high voltage shutdown set point. System
Menu Adjustments".
98 [Reserved] -- -- --
Displays system current limit set point.
CURR LIM = ####A System Yes, see "MCA
or
99 or Adjustment System
Menu Displays sum of maximum capabilities of Adjustments".
CURRLIM = ####MAX
all Rectifier Modules (PCUs) installed.
MCA
Menu
Tree Associated Can this value be
Message Displayed Definition
Line No. with... changed?
(Section
6022)
Indicates the battery recharge current limit
BATTLIM DISABLED System feature is disabled. Yes, see "MCA
99A or Adjustment or System
BATTLIM = #####A Menu Displays battery recharge current limit set Adjustments".
point.
This value is only displayed. MCA
System
calculates the value from all Rectifier
100 100% CURR: ####A Adjustment No
Modules (PCUs) installed. There is no
Menu
user adjustment.
System
101 ADJUSTMENT MENU Adjustment Moves you back to this menu. No
Menu
System Moves you to the beginning of the MCA
102 NORMAL DISPLAY Adjustment Menu Tree. "SYSTEM OK" or No
Menu "##ALARMS ACTIVE" is displayed.
SYS HV1 = ###.##V Alarm Yes, see "MCA
Displays high voltage alarm 1 (high float)
103 or Adjustment System
alarm set point.
HI FLOAT = ###.##V Menu Adjustments".
SYS HV2 = ###.##V Alarm Yes, see "MCA
Displays high voltage alarm 2 (high
104 or Adjustment System
voltage) alarm set point.
HI VOLTAGE = ###.##V Menu Adjustments".
SYS BOD = ###.##V Alarm Yes, see "MCA
Displays battery on discharge (low float)
105 or Adjustment System
alarm set point.
LO FLOAT = ###.##V Menu Adjustments".
SYS 50% = ###.##V
or Alarm Yes, see "MCA
Displays 50% battery on discharge (very
106 VERYLOVOLT = ###.##V Adjustment System
low voltage) (low voltage) alarm set point.
or Menu Adjustments".
LO VOLTAGE = ###.##V
Alarm Yes, see "MCA
107 SYSCURR = #####A Adjustment Displays system current alarm set point. System
Menu Adjustments".
Alarm Yes, see "MCA
Displays subsystem high voltage alarm
108 SUB HV = ###.##V Adjustment System
set point.
Menu Adjustments".
Alarm Yes, see "MCA
Displays subsystem low voltage alarm set
109 SUB LV = ###.##V Adjustment System
point.
Menu Adjustments".
Alarm Yes, see "MCA
Displays subsystem current alarm set
110 SUBCURR = #####A Adjustment System
point.
Menu Adjustments".
Alarm Yes, see "MCA
Displays battery recharge current alarm
110A BAT CHG = #####A Adjustment System
set point.
Menu Adjustments".
MCA
Menu
Tree Associated Can this value be
Message Displayed Definition
Line No. with... changed?
(Section
6022)
Displays the High Temperature Alarm set
point or that this feature has been
HI TEMP ** = ###ºC Alarm disabled. Yes, see "MCA
110B or Adjustment ###ºC = current setting for the High System
HI TEMP ** IS OFF Menu Temperature Alarm. Adjustments".
** = the designation of the temperature
probe.
Displays the Low Temperature Alarm set
point or that this feature has been
LO TEMP ** = ###ºC Alarm disabled. Yes, see "MCA
110C or Adjustment ###ºC = current setting for the Low System
LO TEMP ** IS OFF Menu Temperature Alarm. Adjustments".
** = the designation of the temperature
probe.
TEST ALM RELAYS Activates the alarm relay test feature or
indicates this feature is currently in
or Alarm Yes, see "System
progress.
111 TESTING RELAY ## Adjustment Operating
or
or Menu Procedures".
The user tried to activate this feature
Alarm(s) Active when alarm relays were in an alarm state.
Alarm
112 ADJUSTMENT MENU Adjustment Moves you back to this menu. No
Menu
Alarm Moves you to the beginning of the MCA
113 NORMAL DISPLAY Adjustment Menu Tree. "SYSTEM OK" or No
Menu "##ALARMS ACTIVE" is displayed.
Displays low voltage disconnect circuit
LVD disconnect set point. Yes, see "MCA
114 LVD ** = ##.#V Adjustment System
Menu ** = the designation of the LVD circuit Adjustments".
(either 1A, 1B, 2A, 2B, 3A, or 3B).
LV RECON = ##.#V LVD Displays low voltage disconnect circuits Yes, see "MCA
115 or Adjustment reconnect set point or that low voltage System
MANUAL RECONNECT Menu disconnect is set for manual reconnect Adjustments".
LVD
116 ADJUSTMENT MENU Adjustment Moves you back to this menu. No
Menu
LVD Moves you to the beginning of the MCA
117 NORMAL DISPLAY Adjustment Menu Tree. "SYSTEM OK" or No
Menu "##ALARMS ACTIVE" is displayed.
Display of installed Rectifier Modules
(PCUs) and their type (Amperage).
PCU** TYPE ####A ** = the designation of the Rectifier
or Module (PCU).
118 PCU** TYPE ####+ Inventory Menu ###A = the amperage rating of the No
or displayed Rectifier Module (PCU).
NO PCUs FOUND or
No Rectifier Modules (PCUs) are
communicating with the MCA.
MCA
Menu
Tree Associated Can this value be
Message Displayed Definition
Line No. with... changed?
(Section
6022)
Displays number of Rectifier Module
(PCU) mounting positions available for
type of Rectifier Module (PCU)
(amperage)
***A = the designation of the Rectifier
Module (PCU) type.
## = number of positions available for that
type of Rectifier Module (PCU).
Press the FUNCTION SELECT UP or
DOWN arrow pushbutton to display an
entry. Press the ALARM CUTOFF and Yes, see
FUNCTION SET ENTER pushbuttons "Installing Rectifier
simultaneously to change the value of the Modules and
VACANT ****A = ## displayed entry. The display changes to Initially Starting
119 or Inventory Menu "***A PLACES = ##", where *** is the the System" in the
****A PLACES = ## Rectifier Module (PCU) amperage and ## separate
is the total (filled and empty) number of Installation
available mounting positions in the system Instructions
for this amperage Rectifier Module (PCU). (Section 5974).
Use the FUNCTION SET YES (+) or NO
(-) pushbutton to increment or decrement,
respectively, the value. Press the
FUNCTION SET ENTER pushbutton a
second time to lock the value being
displayed. At the "ARE YOU SURE? + -"
prompt, press either the FUNCTION SET
YES (+) pushbutton to accept the new
setting, or the FUNCTION SET NO (-)
pushbutton to cancel this operation
without changing the existing setting.
SHUNT** TYPE SYS Display of number of system shunts
and connected, number of subsystem shunts
connected, and number of battery shunts
SHUNT** TYPE SUB connected.
120 or Inventory Menu ** = the designation of the shunt. No
SHUNT** TYPE BAT or
or
No shunt A/Ds are communicating with
NO SHUNTS FOUND the MCA.
Display of number of low voltage
disconnect circuits installed.
LVD** INSTALLED
** = the designation of the LVD circuit.
121 or Inventory Menu No
or
NO LVDs FOUND
No LVDs are communicating with the
MCA.
MCA
Menu
Tree Associated Can this value be
Message Displayed Definition
Line No. with... changed?
(Section
6022)
Indicates if an analog battery charge
temperature compensation module is
installed.
ANALOG TC FOUND or
or Indicates if a digital battery charge
temperature compensation probe is
121A T SENSOR ** INST Inventory Menu installed. No
or ** = the designation of the temperature
NO TEMP SENSORS probe.
or
Indicates if temperature compensation is
not installed.
SUBSYS INSTALLED
Indicates if a subsystem is installed or is
122 or Inventory Menu No
not installed.
NO SUBSYS FOUND
REMOTE INSTALLED
or Indicates if remote communications is
installed or is not installed. If installed,
123 REMOTE ACTIVE Inventory Menu No
indicates if a remote communications
or session is currently active.
NO REMOTE FOUND
Allows resetting the inventory count when
an inventory item is removed from the
system by the user.
When an inventory item is removed from
the system, an alarm will be reported until
"VERIFY INVENTORY" is re-entered, and
this operation is completed.
Example: If a Rectifier Module (PCU) is
removed from the system, "PCU** TYPE
###A" will change to reflect this but the
PCU will not be removed from the MCA's
inventory until "VERIFY INVENTORY" is
UPDATE INVENTORY entered and the "UPDATE INVENTORY"
or operation is completed. Yes, see "System
124 REPLACE ** PCUs? Inventory Menu Press the FUNCTION SELECT UP or Troubleshooting
or DOWN arrow pushbutton to display this and Repair".
PLEASE WAIT… entry. Press the ALARM CUTOFF and
FUNCTION SET ENTER pushbuttons
simultaneously to activate this operation.
At the "ARE YOU SURE? + -" prompt,
press either the FUNCTION SET YES (+)
pushbutton to perform the operation, or
the FUNCTION SET NO (-) pushbutton to
cancel this operation.
or
"REPLACE ## PCUs?" is automatically
displayed when a new Rectifier Module
(PCU) is detected and a PCU no reply
alarm is active, or becomes active within
MCA
Menu
Tree Associated Can this value be
Message Displayed Definition
Line No. with... changed?
(Section
6022)
two minutes. The message is displayed
for 2 minutes. [The message timer is
restarted every time a new PCU is
detected or a new PCU no reply alarm
becomes active.]
The timer is terminated and the ALM ##
PCUs FAIL message is displayed if the
NO (-) pushbutton is pressed.
PCUs equal to the number of new PCUs
or the number of PCU no reply alarms,
whichever is less, are removed from the
inventory if the YES (+) pushbutton is
pressed or if the timer expires without a
push-button being pressed. The MCA
displays the PLEASE WAIT message
while it updates the PCUs in its
permanent inventory, and then displays
the CURRLIM = #####A message.
125 CONFIGURE MENU Inventory Menu Moves you back to this menu. No
Moves you to the beginning of the MCA
126 NORMAL DISPLAY Inventory Menu Menu Tree. "SYSTEM OK" or No
"##ALARMS ACTIVE" is displayed.
127 SPECNO ######### Inventory Menu Displays MCA Configuration (Spec. No.). No
128 MCA SWV ######## Inventory Menu Displays MCA software revision number. No
Displays remote device software revision
129 REM SWV ######## Inventory Menu No
number.
Set Rectifier Module (PCU) On/Off (Local
TR Feature) - allows inhibiting operation
of specified Rectifier Module (PCU).
The first Rectifier Module (PCU) is
displayed. Press the FUNCTION
SELECT UP or DOWN arrow pushbutton
to display the next or previous,
respectively, Rectifier Module (PCU).
Press the ALARM CUTOFF and
PCU** ON: SET OFF FUNCTION SET ENTER pushbuttons
or simultaneously to change the TR setting Yes, see "System
PCU for this Rectifier Module (PCU). At the
130 PCU** OFF: SET ON Operating
Enable Menu
or "ARE YOU SURE? + -" prompt, press Procedures".
Energy Mgmt. On either the FUNCTION SET YES (+)
pushbutton to accept the new setting, or
the FUNCTION SET NO (-) pushbutton to
cancel this operation without changing the
existing setting.
** = the designation of the Rectifier
Module (PCU).
Rectifier Modules (PCUs) cannot be
turned on or off if energy management is
active.
MCA
Menu
Tree Associated Can this value be
Message Displayed Definition
Line No. with... changed?
(Section
6022)
PCU
131 CONFIGURE MENU Moves you back to this menu. No
Enable Menu
Moves you to the beginning of the MCA
PCU
132 NORMAL DISPLAY Menu Tree. "SYSTEM OK" or No
Enable Menu
"##ALARMS ACTIVE" is displayed.
Startup, see "Installing Rectifier Modules
Startup and Initially Starting the System" in the
133-152 "Startup" No
Sequence separate Installation Instructions (Section
5974).
Refer to Figure 1.
Figure 1. Controls, Indicators, and Test Points Locations (cont'd on next page)
DISTRIBUTION CABINET
NORM DISC
BAT DISC
List RB Only
(Inside Cabinet)
Main and Supplemental Bays
BATTERY
DISCONNECT
1 2 3 4 5 6 7 8 9
NOR INH
FUNCTION FUNCTION
ALARM CUTOFF SELECT SET
YES
FUNCTION FUNCTION
ALARM CUTOFF SELECT SET
YES
NO
Figure 1. Controls, Indicators, and Test Points Locations (cont'd from previous page, cont'd on next page)
FUNCTION FUNCTION
ALARM CUTOFF SELECT SET
YES
Label
MAJOR MINOR AC TEST DISPLAY ENTER
EQ
NO
Label
System Current
50mV = 800A
+
_
A B C D
Distribution Row
(Row A is bottom row)
Label Detail
Figure 1. Controls, Indicators, and Test Points Locations (cont'd from previous page)
DC-DC CONVERTER
(LIST 63, 64)
CONVERTER
SHELF
INPUT
OK
INPUT OK (right side)
INPUT
OK
MINOR ALARM
ALARM
MINOR
STANDBY
OUTPUT
ON
OK
MAJOR ALARM
MAJOR
ALARM
ON / STANDBY OUTPUT OK
SWITCH INDICATOR
MCA DISPLAY
Refer to "Navigating the MCA" for MCA Display descriptions. The display times out (goes back to "SYSTEM OK" or "ALARMS ACTIVE") after
a predetermined non-adjustable time period of no user input activity.
Refer to Table 1.
Table 1
FUNCTION SELECT UP
Moves up and down, respectively, through the list of available entries in the currently
FUNCTION SELECT DOWN
displayed menu.
(Arrow Pushbuttons)
Used to move to another menu, as determined by the currently displayed entry. Also
used to lock the displayed setting or value of the currently selected menu entry, when
in the adjustment or change setting mode.
FUNCTION SET ENTER Note: Pressing the ALARM CUTOFF pushbutton and the FUNCTION SET ENTER
(Pushbutton) pushbutton simultaneously, allows the user to enter the adjustment or change
setting mode, to change the value or setting of the currently selected menu entry,
if available.
Used to increase or decrease the value of the currently selected menu entry when in
the adjustment or change setting mode.
Note: Pressing the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously moves
the user to the "Initial Message" display (beginning).
FUNCTION SET YES (+)
FUNCTION SET NO (-) Note: When in the adjustment or change setting mode, depressing the FUNCTION SET
(Pushbuttons) YES (+) pushbutton after the "ARE YOU SURE? + -" prompt accepts the new value
or setting, depressing the FUNCTION SET NO (-) pushbutton after the "ARE YOU
SURE? + -" prompt cancels the adjustment or change setting mode without
making any changes.
Silences the audible alarm connected to the system. Any new alarms will reactivate
the audible alarm. (No function when not equipped with external MCA Audible Alarm
relay contacts.)
ALARM CUTOFF Note: Pressing the ALARM CUTOFF pushbutton and the FUNCTION SET ENTER
(Pushbutton) pushbutton simultaneously, allows the user to enter the adjustment or change
setting mode, to change the value or setting of the currently selected menu entry,
if available.
Illuminates yellow when the MCA audible alarm has been silenced using the ALARM
ALARM CUTOFF
CUTOFF Pushbutton. (No function when not equipped with external MCA Audible
(Indicator)
Alarm relay contacts.)
Table 1
Table 1
Illuminates green if AC input voltage to all Rectifier Modules is greater than the preset
AC non-adjustable low AC input voltage inhibit and less than the preset non-adjustable
(Indicator) high AC input voltage inhibit. Illuminates red if AC input voltage to any Rectifier Module
decreases below or increases above the respective inhibit value.
TEST/EQ Illuminates yellow when the system is placed in the test/equalize mode, locally or
(Indicator) remotely.
This is a locking type toggle switch. To operate switch, pull out switch handle and move
handle left or right to desired position. Release handle to lock into new position.
NOR/INH • For normal low voltage disconnect operation, place this switch in the NOR position.
(Normal/Inhibit Switch)
• NOR • The low voltage disconnect circuit is disabled and the battery and system output
(Normal Switch Position) remain connected to the controlled load(s) when this switch is in the INH position. This
allows testing, adjusting, or removal of the low voltage disconnect circuit card(s)
• INH without disconnection of the load(s).
(Inhibit Switch Position)
Note: Placing this switch in the INH position inhibits the LVD function only in cabinet
containing this switch. Other cabinets containing LVD contactors or controlling
external LVD contactors will continue to operate with normal LVD function.
Low Voltage Disconnect Illuminates when the low voltage disconnect circuit has been disabled through the use of
INH (Inhibit) Indicator the NOR/INH switch as described above.
MANUAL BATTERY DISCONNECT SWITCH AND INDICATOR (LIST RB, RC, RD ONLY)
Refer to Table 3.
NORM/DISC This is a locking type toggle switch. To operate switch, pull out switch handle and
(Normal/Disconnect move handle left or right to desired position. Release handle to lock into new position.
Switch)
• DISC • Placing the switch in this position causes the associated contactor to open, thus
(Disconnect Switch Position) disconnecting battery from the power system and loads.
• NORM • Returning the switch to this position reconnects battery to the power system and
(Normal Switch Position) loads.
BAT DISC Illuminates red if the NORM/DISC battery disconnect switch is placed in the DISC
(Battery Disconnect Indicator) position.
When installed, a series of test points as shown in Figure 1 are located on the MCA front panel in the Main Bay and the similar blank panel
in Supplemental Bays. Connect a multimeter between the sets of test points to measure the current of each System Load Shunt (50mV =
800A).
Note: The Optional System Load Shunt Test Point Kit is a universal kit that can be installed in a 1-, 2-, 3-, or 4-Row cabinet. If your
cabinet has less than 4-Distribution Rows, some test points will have no function. Note also that test points will have no
function for rows that do not contain system distribution.
ON/STANDBY (I / ) Switch: Located on each Converter Module. Placing this switch in the ON position enables the converter to provide
output power. Placing the switch in the STANDBY position inhibits converter output.
OUTPUT OK Indicator: Located on each Converter Module. This green light emitting diode (LED) illuminates to indicate the converter is
operating normally. A failure condition is indicated by an extinguished LED. Failure conditions include:
• Converter output increases above 26 volts DC or decreases below 22 volts DC for any reason, including converter failure, High
Voltage Shutdown, input voltage below 41 volts DC (low input inhibit) or an overload condition.
• Cooling fan has slowed or stopped due to fan failure or blocked rotor.
INPUT OK ← Indicator: Located on the front panel of the Converter Mounting Shelf. This green LED illuminates to indicate that DC power
applied to the converter modules in the left-hand half of the shelf is above the low input voltage inhibit level of the converters.
INPUT OK → Indicator: Located on the front panel of the Converter Mounting Shelf. This green LED illuminates to indicate that DC power
applied to the converter modules in the right-hand half of the shelf is above the low input voltage inhibit level of the converters.
MINOR ALARM Indicator: Located on the front panel of the Converter Mounting Shelf. This yellow LED illuminates if a failure condition in
one DC-DC Converter Module is detected. Also, external minor alarm circuits are activated, if connected. See “OUTPUT OK Indicator” for
a list of failure conditions. The LED remains illuminated in the event of a major alarm condition.
MAJOR ALARM Indicator: Located on the front panel of the Converter Mounting Shelf. This red LED illuminates if a failure condition in
more than one converter module is detected. Also, external major alarm circuits are activated, if connected. See “OUTPUT OK Indicator”
for a list of failure conditions.
External Alarms
Nine (9) Form-C alarm relay contacts are provided. These alarm relays are mapped to MCA alarms as shown in the following chart. Refer
to “External Alarm, Reference, and Control Connections” in "Making Electrical Connections" of the separate INSTALLATION
INSTRUCTIONS (SECTION 5974) for location and operation of the external alarm contacts. Refer to the following for alarm conditions.
Power System
10 11 12 13
List No.
MCA
Configuration 534876 534877 534878 534879
No.
Major Major Major Major
Relay K1
Alarm Alarm Alarm Alarm
Minor Minor Minor Minor
Relay K2
Alarm Alarm Alarm Alarm
Test/EQ
High High High
Mode
Relay K3 Voltage 1 Voltage 1 Voltage 1
Indication
Alarm Alarm Alarm
2
Rectifier
High MCA
Module Fuse
Relay K4 Voltage 2 Fail
Fail Major Alarm
Alarm Alarm
Alarm
Battery On Battery On Battery On Battery On
Relay K5 Discharge Discharge Discharge Discharge
Alarm Alarm Alarm Alarm
Rectifier
50%
Module Very Low AC Fail
Battery On
Relay K6 Fail Voltage Major
Discharge
Minor Alarm Alarm
Alarm
Alarm
AC AC AC AC
Relay K7 Fail Fail Fail Fail
Alarm Alarm Alarm Alarm
MCA MCA
Fuse
Relay K8 Audible Audible LVD Alarm
Alarm
Alarm Alarm
Rectifier
Test/EQ Test/EQ
Fuse Module
Relay K9 Mode Mode
Alarm Fail
Indication Indication
Alarm
1) Major Alarm: Refer to description of the MAJOR alarm indicator for alarm conditions.
2) Minor Alarm: Refer to description of the MINOR alarm indicator for alarm conditions.
3) High Voltage 1 Alarm: Activates if system output voltage increases to a preset adjustable value.
or
Test/Equalize Mode Indication 2: Activates if the system is placed in the test/equalize mode, locally or remotely.
4) High Voltage 2 Alarm: Activates if system output voltage increases to a preset adjustable value.
or
Rectifier Module Fail Major Alarm: Activates if the Rectifier Module Fail alarm on two or more Rectifier Modules is
active. Refer to description of Rectifier Module Fail indicator for alarm conditions.
or
MCA Fail Alarm: Activates if the MCA Fail alarm is active. Refer to description of MCA Fail alarm for alarm conditions.
or
Fuse Alarm: Activates if any fuse or circuit breaker in the system opens.
5) Battery On Discharge Alarm: Activates if system output voltage decreases to a preset adjustable value, indicating that
the battery is supplying the load and is discharging.
6) 50% Battery On Discharge or Very Low Voltage Alarm: Activates if system output voltage decreases to a preset
adjustable value, indicating that the battery has been continuously supplying the load and has discharged to approximately
half its reserve time.
or
AC Fail Major Alarm: Activates if the AC Fail Alarm activates on two or more Rectifier Modules. Refer to description of
AC Fail Alarm for alarm conditions.
or
Rectifier Module Fail Minor Alarm: Activates if the Rectifier Module Fail alarm on only one Rectifier Module is active.
Refer to description of Rectifier Module Fail indicator for alarm conditions.
7) AC Fail Alarm: Activates if AC input drops below the low AC input voltage inhibit or increases above the high AC input
voltage inhibit..
8) MCA Audible Alarm: Activates if any alarm condition monitored by the MCA occurs, and is provided for connection to an
audible alarm circuit.
or
Fuse Alarm: Activates if any fuse or circuit breaker in the system opens.
or
LVD Alarm: Activates if any LVD circuit in the system activates.
9) Test/Equalize Mode Indication: Activates if the system is placed in the test/equalize mode, locally or remotely.
or
Fuse Alarm: Activates if any fuse or circuit breaker in the system opens.
or
Rectifier Module Fail Alarm: Activates if the Rectifier Module Fail alarm on any Rectifier Module is active. Refer to
description of Rectifier Module Fail indicator for alarm conditions.
Procedure
1. Apply input power to the Rectifier Module or insert the Rectifier Module into the shelf.
Complete Shutdown
1. Remove input power from the Rectifier Module or remove the Rectifier Module from the shelf.
Local TR Shutdown
Note: When a Rectifier Module (PCU) is shut down via the Local TR Shutdown feature, it must be manually restarted (by turning AC
power to the Rectifier Module off then on, or by removing and re-inserting the Rectifier Module). The Local TR Shutdown
feature DOES NOT automatically restart Rectifier Modules to deliver current in any operational or alarm state of the DC plant.
The Rectifier Module must be manually restarted by navigating the MCA and selecting to turn the Rectifier Module back ON as
detailed in the following procedure.
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE MENU" is displayed.
4. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "SET PCU (Rectifier Module) ON / OFF".
6. Repeatedly press and release the FUNCTION SELECT UP or DOWN arrow pushbutton until the Rectifier Module to be stopped
using the local TR feature is displayed.
7. With this Rectifier Module being displayed, press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons
simultaneously.
8. "ARE YOU SURE? + -" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
9. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
RECTIFIER MODULE STOPPING PROCEDURE (REMOTE) (IF LMS1000 MONITORING SYSTEM FURNISHED)
Procedure
1. Apply the remote on/off (TR) signal via LMS1000 to the respective Rectifier Module. Remove the signal to restart Rectifier
Module operation.
LIST 63 AND 64 DC-DC CONVERTER SYSTEM STARTING AND STOPPING PROCEDURES (IF FURNISHED)
Procedure
• To start Converter Module operation, place the ON/STANDBY switch in the ON position.
• To stop Converter Module operation, place the ON/STANDBY switch in the STANDBY position.
INITIALLY CONNECTING BATTERY AND SYSTEM OUTPUT TO THE CONTROLLED LOAD(S) WHEN LOW VOLTAGE DISCONNECT LOAD
CONTACTOR IS FURNISHED AND SET FOR MANUAL RECONNECT
If the low voltage disconnect circuit(s) is set for manual reconnect, and a load contactor is furnished, the battery and system output have
to be initially connected to the controlled load(s) when the system is first started or restarted after being shut down. (Battery voltage
must be above the upper setting of the low voltage disconnect circuit.) Perform the following procedure to reconnect the low voltage
disconnect circuits.
Procedure
2. With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
3. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "ALARM LVD ACTIVE".
5. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until the low voltage disconnect circuit to be
reconnected is displayed ("RECONNECT LVD**", **=the designation of the low voltage disconnect circuit).
6. To reconnect the low voltage disconnect circuit being displayed, press and release the ALARM CUTOFF and FUNCTION SET
ENTER pushbuttons simultaneously.
7. "ARE YOU SURE? +-" is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The low voltage disconnect circuit
reconnects.
8. If the system contains additional low voltage disconnect circuits, separately reconnect these by repeating steps 5) through 7).
9. When done, press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously. You are returned to the
beginning of the MCA menu tree.
Local Procedure
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
Note: In the following step, if "SET TEST/EQ MODE" is displayed, the system is already operating in the float mode. DO NOT
perform the following steps.
2. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "SET FLOAT MODE".
3. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
4. "ARE YOU SURE? + -" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
5. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
Warning: Do not supply equalize output voltage for a longer period than necessary. Prolonged higher battery charge
voltage overcharges the battery cells and reduces battery life.
There are four methods of placing the system from the float mode to the test/equalize mode.
Method 1 (Manual Test/Equalize) Procedure
In this method, a user manually places the system into the test/equalize mode via the MCA interface. A user must manually return the
system to the float mode via the MCA interface. To invoke method 1, follow the procedures described below.
Setting for Manual Test/Equalize: Set the "TEST/EQ HRS = ##" menu item in the MCA configure menu to above 99. The display changes to
"TEST/EQ MAN STOP" to indicate manual test/equalize mode is set. A step-by-step procedure is provided next.
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE MENU" is displayed.
4. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "TEST/EQ HRS = ##" or "TEST/EQ MAN STOP"
is displayed.
Note: If "TEST/EQ MAN STOP" is displayed, the system is already set for manual test/equalize. In this case, proceed with step
9).
Note: If "END TEQ ##.##HRS" is displayed, the system is set for manually initiated timed test/equalize, and a timed
test/equalize is in progress. In this case, you can proceed with steps 5) through 8) to cancel the timed test/equalize in
progress and change the current setting, or proceed with step 9) to proceed with the timed test/equalize in progress
and make no changes.
5. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "TEST/EQ HRS =" portion of
the display flashes.
6. Press the FUNCTION SET YES (+) pushbutton until the value displayed increases above 99, then release the pushbutton.
"TEST/EQ MAN STOP" is displayed.
8. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
9. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
Placing the System into Test/Equalize Mode: Manually place the system into test/equalize mode by navigating to and activating the "SET
TEST/EQ MODE" menu item in the MCA function menu. The system is placed in the test/equalize mode and must be manually placed
back to the float mode. A step-by-step procedure is provided next.
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
Note: In the following step, if "SET FLOAT MODE" is displayed, the system is already operating in the test/equalize mode. In
this case, DO NOT perform steps 2) through 4), proceed with step 5).
2. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "SET TEST/EQ MODE".
3. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
4. "ARE YOU SURE? + -" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
5. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
Returning to Float Mode: To return to float mode, navigate to and activate the "SET FLOAT MODE" menu item in the MCA function menu,
as previously described in this section.
In this method, a user manually places the system into the test/equalize mode via the MCA interface. The system automatically returns
to the float mode after a preset programmable time period (1-99 hours, in increments of one hour). To invoke method 2, follow the
procedures described below.
Setting for Manually Initiated Timed Test/Equalize: Set the "TEST/EQ HRS = ##" menu item in the MCA configure menu to a value
between 1 and 99. A step-by-step procedure is provided next.
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE MENU" is displayed.
4. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "TEST/EQ HRS = ##" or "TEST/EQ MAN STOP"
is displayed.
Note: If "TEST/EQ HRS = ##" is displayed, the system is already set for manually initiated timed test/equalize. In this case, you
can proceed with steps 5) through 8) to change the current setting, or proceed with step 9) if no changes are required.
Note: If "END TEQ ##.##HRS" is displayed, the system is already set for manually initiated timed test/equalize, and a timed
test/equalize is in progress. In this case, you can proceed with steps 5) through 8) to cancel the timed test/equalize in
progress and change the current setting, or proceed with step 9) to proceed with the timed test/equalize in progress
and make no changes.
5. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "TEST/EQ HRS =" portion of
the display flashes.
6. Press the FUNCTION SET YES (+) or FUNCTION SET NO (-) pushbutton until the desired value is displayed, then release the
pushbutton. Note that as you scroll above 99, "TEST/EQ MAN STOP" is displayed. Scroll back down to redisplay "TEST/EQ HRS =".
7. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
8. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
9. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
Placing the System into Test/Equalize Mode: Manually place the system into test/equalize mode by navigating to and activating the "SET
TEST/EQ MODE" menu item in the MCA function menu. The system is placed in the test/equalize mode for the time period set in
"TEST/EQ HRS = ##". The system automatically returns to the float mode when this time period expires. A step-by-step procedure is
provided next.
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
Note: In the following step, if "SET FLOAT MODE" is displayed, the system is already operating in the test/equalize mode. In
this case, DO NOT perform steps 2) through 4), proceed with step 5).
2. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "SET TEST/EQ MODE".
3. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
4. "ARE YOU SURE? + -" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
5. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
Returning to Float Mode: The system automatically returns to float mode when the "timed test/equalize period" expires.
Note: Navigating to "END TEQ ##.##" of the MCA configure menu displays the hours remaining in the timed test/equalize period.
Note: Timed test/equalize is canceled and the system is placed in the float mode if any of the following occurs.
1) Manually placing the system in the float mode by navigating to and activating "SET FLOAT MODE" menu item in the MCA
function menu, as previously described in this section.
2) Resetting the "TEST/EQ HRS = ##" value in the MCA configure menu when "END TEQ ##.##HRS" is being displayed, as
described in the previous procedure.
In this method, a user enables the Automatic Equalize feature via the MCA interface. The system is automatically placed in the equalize
mode and automatically returns to float mode for the conditions as described below. To invoke method 3, follow the procedures
described below.
Note: The automatic equalize feature is intended for use only with wet cell batteries. Using this feature with valve regulated batteries
is not recommended.
Description
This feature can be enabled or disabled by a user via the MCA. The default state is disabled.
The Automatic Equalize feature is a time based function which is controlled by a customer selectable multiplier and by the Battery on
Discharge (BOD) alarm setpoint. The MCA’s default setting is for a multiplier of zero, which disables the Automatic Equalize feature.
When the Automatic Equalize feature is enabled, if system voltage drops to less than the BOD alarm setpoint, the MCA initiates a timing
cycle to measure the discharge time period. The MCA requires at least 15 minutes of continuous BOD alarm in order to prevent nuisance
equalization cycles. When system voltage rises to above the BOD alarm setpoint, the MCA ends the discharge timing cycle and
(assuming a minimum of 15 minutes has elapsed) places the Rectifier Modules into the equalize mode for a customer selectable multiple
of the discharge time period (the discharge time period includes the initial 15 minutes).
The equalize time period can be set for 0 to 15 times the discharge time period, up to a maximum of 300 hours. A zero (0) setting
disables the feature.
When the Automatic Equalize feature is enabled, the MCA prevents a user from setting the equalize value lower than the float setpoint. If
the equalize value is set first, the MCA automatically sets the Automatic Equalize Multiplier to zero (0), disabling the feature.
Manually setting the system to float or equalize mode cancels the automatic function, if active.
Note: Equalization is only effective if the correct multiplier is entered to allow the battery to charge to capacity. It makes no sense to
end the equalize cycle before battery capacity has been restored. To determine the multiplier, load current and system capacity
must be known. For example, consider a system with 200 amps of Rectifier Module capacity and 150 amps of load. If there is a
2 hour outage of AC power, 300 amp-hours (150 x 2) will be drained from the battery. When AC power is restored, the battery
charge current will be 50 amps (200-150), and it will take at least 6 hours (300/50) to replace the battery capacity. In this
scenario, the multiplier must be set greater than 3 for the Automatic Equalize feature to have any effect.
Enabling and Disabling the Automatic Equalize Feature: To enable, set the "AUTO EQ MUL = ##" menu item in the MCA Configure Menu
to a value between 0 and 15. To disable, set the "AUTO EQ MUL = ##" menu item in the MCA Configure Menu to 0. A step-by-step
procedure is provided next.
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE MENU" is displayed.
4. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "AUTO EQ MUL = ##" or "AUTO EQ
DISABLED" is displayed.
Note: If "AUTO EQ MUL = ##" is displayed, the system is already set for Automatic Equalize. In this case, you can proceed with
steps 5) through 8) to change the current setting, or proceed with step 9) if no changes are required.
Note: If "END AUTO ##.##HR" is displayed, the system is already set for Automatic Equalize, and an Automatic Equalize is in
progress. In this case, you can proceed with steps 5) through 8) to cancel the Automatic Equalize in progress and
change the current setting, or proceed with step 9) to proceed with the Automatic Equalize in progress and make no
changes.
5. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "AUTO EQ MUL =" portion of
the display flashes.
6. Press the FUNCTION SET YES (+) or FUNCTION SET NO (-) pushbutton until the desired value is displayed, then release the
pushbutton. Note that as you scroll below 1, "AUTO EQ DISABLED" is displayed. Scroll back up to redisplay "AUTO EQ MUL =".
7. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
8. “ARE YOU SURE? +_” is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
9. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
Placing the System into Test/Equalize Mode: The MCA automatically does this for the conditions as previously described.
Returning to Float Mode: The MCA automatically does this for the conditions as previously described.
Note: Navigating to "END AUTO ##.##HR" of the MCA Configure Menu displays the hours remaining in an automatic equalize period, if
active.
Note: Auto Equalize is canceled and the system is placed in the float mode if any of the following occurs.
1) Manually placing the system in the float mode by navigating to and activating "SET FLOAT MODE" menu item in the MCA
Function Menu.
2) Resetting the "AUTO EQ MUL = ##" value in the MCA Configure Menu when "END AUTO ##.##HR" is being displayed, as
described in the previous procedure.
In this method, a user (or external equipment) places the system in the test/equalize mode by applying an external signal to the system.
The system returns to the float mode when the external signal is removed. This method overrides the other three methods.
Placing the System into Test/Equalize Mode: Apply system ground to the system's external test/equalize terminal.
Returning to Float Mode: Remove system ground from the test/equalize terminal.
Note: If a manual test/equalize, manually initiated timed test/equalize, or automatic equalize is in process; it is canceled and the
system returns to float mode when system ground is removed from the test/equalize terminal.
Restarting Procedures when Rectifier Module (PCU) is Automatically or Manually Inhibited, Shut down, or
Locked Out
RECTIFIER MODULE HIGH VOLTAGE SHUTDOWN AND LOCKOUT
Turn AC power to the Rectifier Module off or remove the Rectifier Module, wait 5 seconds or more, then turn AC power to the Rectifier
Module on or re-insert the Rectifier Module. Refer to the "Troubleshooting" section for a Rectifier Module removal procedure.
Remove the emergency shutdown and fire alarm disconnect signal. Turn AC power to the Rectifier Modules off then on, or remove and
re-insert the Rectifier Modules. Refer to the "Troubleshooting" section for a Rectifier Module removal procedure.
Remove the remote on/off (TR) signal from the respective Rectifier Module. The signal can originate from the LMS1000 (if furnished), or
via the local MCA Interface Pad.
Low Voltage Disconnect Reconnect Procedure (when furnished and set for manual reconnect)
If the low voltage disconnect circuit(s) is set for manual reconnect, the battery and system output have to be manually reconnected to
the controlled load(s) when the low voltage disconnect circuit activates. (Battery voltage must be above the upper setting of the low
voltage disconnect circuit.) Perform the following procedure to reconnect the low voltage disconnect circuits.
Procedure
2. With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
3. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "ALARM LVD ACTIVE".
5. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until the low voltage disconnect circuit to be
reconnected is displayed ("RECONNECT LVD**", **=the designation of the low voltage disconnect circuit).
6. To reconnect the low voltage disconnect circuit being displayed, press and release the ALARM CUTOFF and FUNCTION SET
ENTER pushbuttons simultaneously.
7. "ARE YOU SURE? +-" is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The low voltage disconnect circuit
reconnects.
8. If the system contains additional low voltage disconnect circuits, separately reconnect these by repeating steps 5) through 7).
9. When done, press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously. You are returned to the
beginning of the MCA menu tree.
The low voltage disconnect circuit is set for manual reconnect when "MANUAL RECONNECT" is selected as the Low Voltage Disconnect
"Reconnect" value, as outlined below.
Procedure
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
4. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUST LVD" is displayed.
6. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "LVRECON = ##.##V" is displayed.
Note: If "MANUAL RECONNECT" is displayed, low voltage disconnect is already set for manual reconnect. In this case,
proceed with step 11).
7. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "LVRECON =" portion of the
display flashes.
8. Observe the value displayed. Press and hold the FUNCTION SET NO (-) pushbutton until "MANUAL RECONNECT" is displayed.
Release the pushbutton.
9. With "MANUAL RECONNECT" being displayed, press and release the FUNCTION SET ENTER pushbutton.
10. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The reconnect value will not be changed and the adjustment mode will be exited if the FUNCTION SET YES (+)
pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
11. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
This feature requires battery current Shunt PODs to be installed in compatible Battery Stand(s) and connected to the power system. The
battery recharge current limit function depends on measurements supplied by the system and by the battery current shunts. It is critical
that the output current of all Rectifier Modules is monitored either by battery current or system load shunts connected to the MCA via
Shunt PODs.
DESCRIPTION
A Battery Recharge Current Limit value can be set. When set, the maximum current delivered to the batteries is limited to this value. This
value can be set from 10% of total system current capacity to the system current limit setting (MCA prevents the user from adjusting this
value above the system current limit setting).
When battery recharge current approaches the battery recharge current limit setting, the MCA automatically adjusts the current limit
circuit on each Rectifier Module so that this value is not exceeded. The MCA also displays "BAT CHGCL #####A" in the measurement
menu.
The MCA will not adjust Rectifier Module current limits to less than the actual measured system load current plus half of the battery
recharge current limit setpoint. The MCA will stop adjusting Rectifier Module current limits when battery current falls to half of the
battery recharge current limit setpoint or when adjusted Rectifier Module current limits are greater than the actual Rectifier Module
output currents by more than half of the battery recharge current limit setpoint.
If a Rectifier Module fails, the MCA automatically resets each remaining Rectifier Modules current limit point to maintain this value. The
MCA also insures that the current limit circuit on any Rectifier Module is not set above 105% of its capacity.
Refer to "Enabling, Disabling, and Adjusting the Battery Recharge Current Limit Setting" in "MCA System Adjustments" for a procedure.
The Battery Charge Current Alarm is adjustable from 0 to 60000 amperes. Factory set at 2000, unless otherwise specified.
This feature requires battery current Shunt PODs to be installed in compatible Battery Stand(s) and connected to the power system.
Refer to "Setting the Battery Charge Current Alarm Value" in "MCA System Adjustments for a procedure".
The MCA displays total battery current (charge or discharge) and individual battery currents (charge or discharge) from up to sixteen
shunts. Total of system, subsystem, and battery shunts cannot exceed sixteen.
Procedure
The Measurement Menu displays either "BAT CHG #####A" for total battery charge current, "BAT CHGCL #####A" if the battery charge is
in current limit, or "BAT DIS #####A" for total battery discharge current. You can step the display to indicate the current measured
through each battery Shunt POD installed in the system.
Procedure
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE MENU" is displayed.
4. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "RELAYTEST = ###SEC" is displayed.
5. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "RELAYTEST =" portion of the
display flashes.
6. Observe the value displayed. Press and hold the FUNCTION SET YES (+) or NO (-) pushbutton until the desired value is displayed.
Release the pushbutton.
7. With the desired value being displayed, press and release the FUNCTION SET ENTER pushbutton.
8. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The relay test period will not be changed and the adjustment mode will be exited if the FUNCTION SET YES (+)
pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
9. To return to the beginning of the MCA Logic Tree, press and release the FUNCTION SET YES (+) and NO (-) pushbuttons
simultaneously.
Procedure
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
4. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "ADJUST ALARMS".
6. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "TEST ALM RELAYS" is displayed.
7. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
8. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
9. The display changes to "TESTING RELAY 1". Relay 1 is set to the alarm state and should turn in an alarm for the time period
previously set. Each relay is consecutively tested in this manner.
Note: You can view your system's MCA Configuration Number by navigating to "SPECNO#########" in the MCA "Inventory
Menu".
List 10 MCA
(MCA Configuration Spec. No. 534876):
Relay #1 = Major Alarm
Relay #2 = Minor Alarm
Relay #3 = High Voltage 1 Alarm
Relay #4 = High Voltage 2 Alarm
Relay #5 = Battery On Discharge Alarm
Relay #6 = 50% Battery On Discharge Alarm
Relay #7 = AC Fail Alarm
Relay #8 = MCA Audible Alarm
Relay #9 = Test/Equalize Indication
List 11 MCA
(MCA Configuration Spec. No. 534877):
Relay #1 = Major Alarm
Relay #2 = Minor Alarm
Relay #3 = High Voltage 1 Alarm
Relay #4 = Rectifier Module Fail Major Alarm
Relay #5 = Battery On Discharge Alarm
Relay #6 = Rectifier Module Fail Minor Alarm
Relay #7 = AC Fail Alarm
Relay #8 = MCA Audible Alarm
Relay #9 = Fuse Alarm / Circuit Breaker Alarm
List 12 MCA
(MCA Configuration Spec. No. 534878):
Relay #1 = Major Alarm
Relay #2 = Minor Alarm
Relay #3 = High Voltage 1 Alarm
Relay #4 = MCA Fail Alarm
Relay #5 = Battery On Discharge Alarm
A programmable audible alarm cutoff reset feature is provided. Once an audible alarm has been cutoff, it automatically resets (and
sounds if the alarm condition is still present) after the time period programmed expires. If the audible alarm is again cutoff while the
same alarm condition is still present, the reset feature is inoperable, and the audible alarm remains silenced. If another alarm condition
occurs, the audible alarm again sounds.
Note: The audible alarm feature is not available when power system is equipped with a List 12 or List 13 MCA.
The MCA Audible Alarm Cutoff Reset feature is active when a "NAG MINUTES" value is selected.
The MCA Audible Alarm Cutoff Reset feature is inactive when "AUDIBLE NAG OFF" is selected.
Procedure
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE MENU" is displayed.
4. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "NAG MINUTES = ##" or "AUDIBLE NAG OFF"
is displayed.
5. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "NAG MINUTES =" portion of
the display flashes.
6. Observe the value displayed. Press and hold the FUNCTION SET YES (+) or NO (-) pushbutton until the desired value or "AUDIBLE
NAG OFF" is displayed. Release the pushbutton.
7. With the desired value or "AUDIBLE NAG OFF" being displayed, press and release the FUNCTION SET ENTER pushbutton.
8. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The audible alarm cutoff reset time period will not be changed and the adjustment mode will be exited if the
FUNCTION SET YES (+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
9. To return to the beginning of the MCA Logic Tree, press and release the FUNCTION SET YES (+) and NO (-) pushbuttons
simultaneously.
Setting Rectifier Module Fan Speed Control (Normal and Variable Speed) Feature
DESCRIPTION
The Rectifier Modules contain a variable-speed fan control circuit. When ambient temperature drops below a preset non-adjustable
value, fan speed is reduced. When the ambient temperature rises above this preset non-adjustable value, normal fan speed is resumed.
This allows audible noise to be lowered if thermal conditions permit.
This feature can be enabled or disabled by a user via the MCA. The default state is disabled.
When the variable-speed fan feature is enabled by the MCA, the Rectifier Modules individually use their internal temperatures to control
fan speed. It is therefore possible that, in a system with many Rectifier Modules and under certain conditions, some fans will be operating
at higher speed than others.
Procedure
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE MENU" is displayed.
4. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "LO SPEED FAN OFF" or "LO SPEED FAN ON"
is displayed. This is the current setting for this feature. To toggle this setting, perform steps 5) through 7). To keep this setting,
proceed with step 7).
5. To toggle this setting, press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
6. "ARE YOU SURE? +_" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
7. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
Procedure
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE MENU" is displayed.
4. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "DISPLAY ROLL OFF" or "DISPLAY ROLL ON" is
displayed. This is the current setting for this feature. To toggle this setting, perform steps 5) through 7). To keep this setting,
proceed with step 7).
5. To toggle this setting, press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
6. "ARE YOU SURE? +_" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
7. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
Procedure
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE MENU" is displayed.
4. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "SHARE ALARM OFF" or "SHARE ALARM ON"
is displayed. This is the current setting for this feature. To toggle this setting, perform steps 5) through 7). To keep this setting,
proceed with step 7).
5. To toggle this setting, press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
6. "ARE YOU SURE? +_" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
7. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
Procedure
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE MENU" is displayed.
4. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "EMERG STOP ON" or " EMERG STOP OFF" is
displayed. This is the current setting for this feature. To toggle this setting, perform steps 5) through 7). To keep this setting,
proceed with step 7).
5. To toggle this setting, press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
6. "ARE YOU SURE? +_" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
7. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
ENABLING OR DISABLING THE ' REMOTE HIGH VOLTAGE SHUTDOWN ' FEATURE
Procedure
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE MENU" is displayed.
4. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until " REMOTE HVS ON" or " REMOTE HVS OFF" is
displayed. This is the current setting for this feature. To toggle this setting, perform steps 5) through 7). To keep this setting,
proceed with step 7).
5. To toggle this setting, press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
6. "ARE YOU SURE? +_" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
7. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
• When accessing the MCA using the modem port of the RS-232/Modem assembly, it is suggested to use the 19200 bits/s setting
in WinLink for the MCA's modem port.
• When using the RS-232/Modem MCA Interface Option, the modem port has precedence over the RS-232 port. If someone is
using the local port and the modem detects a ring, the local user is automatically logged off. When the call is terminated, the
RS-232 port becomes active again and the RS-232 device will have to log back on.
Refer to Section 5982 for User instructions. Section 5982 can be accessed from the CD (Electronic Documentation Package) furnished
with your system.
If you installed an MCA Ethernet card that supports SNMP, you will also set the SNMP parameters when you perform the procedure in
"Installing the Rectifier Modules and Initially Starting the System" of the separate INSTALLATION INSTRUCTIONS (SECTION 5974).
• an Ethernet port for system connection into a TCP/IP network and support for SNMP V2 (Simple Network Management
Protocol). Communications to and from the system is accomplished via a MIB (Management Information Browser).
• SNMP Traps for alarms listed on the MCA Menu Tree under the "Alarms Menu".
Local Procedure
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE MENU" is displayed.
4. "VERIFY INVENTORY" is displayed. Press and release the FUNCTION SET ENTER pushbutton.
5. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "REMOTE INSTALLED" or "REMOTE ACTIVE" is
displayed.
6. With "REMOTE INSTALLED" or "REMOTE ACTIVE" being displayed, press and release the ALARM CUTOFF, FUNCTION SELECT UP,
and FUNCTION SELECT DOWN pushbuttons simultaneously.
The display automatically times out, or press the FUNCTION SELECT UP or FUNCTION SELECT DOWN arrow pushbutton to
return to the previous display.
Remote Procedure
None
1. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously.
1. With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Refer to the ALARM MENUS in "Navigating the MCA" for additional information.
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. "MEASUREMENT MENU" is displayed. Press and release the FUNCTION SET ENTER pushbutton. Refer to the MEASUREMENT
MENUS in "Navigating the MCA" for additional information.
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
4. "ADJUST SYSTEM" is displayed. Press and release the FUNCTION SET ENTER pushbutton.
5. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "100% Curr: ####A" is displayed. This is the
current capacity of the system derived from the combined current capacities of all installed Rectifier Modules.
6. To return to the beginning of the MCA Logic Tree, press and release the FUNCTION SET YES (+) and NO (-) pushbuttons
simultaneously.
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE MENU" is displayed.
4. "VERIFY INVENTORY" is displayed. Press and release the FUNCTION SET ENTER pushbutton.
5. Press and release the FUNCTION SELECT DOWN and UP arrow pushbuttons to view the various inventory items.
6. To return to the beginning of the MCA Logic Tree, press and release the FUNCTION SET YES (+) and NO (-) pushbuttons
simultaneously.
To temporarily view system parameters when the MCA is in the "Power Down" mode, press any keypad button. This reactivates the
display and communications.
The MCA resumes "Power Down" mode after the MCA is returned to the "Normal Display" position (beginning of MCA Menu Tree).
These adjustments can also be done via WinLink software (if furnished) or via LMS1000 Monitoring System (if furnished). Refer to the
online Help Files accessed within the WinLink program for User Instructions. Refer to the LMS1000 User Instructions (Section 5847) for
LMS1000 operating procedures. Section 5847 can be accessed from the CD (Electronic Documentation Package) furnished with the
LMS1000.
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
8. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "FLOAT =" portion of the
display flashes.
9. Observe the value displayed. This is the float voltage setting for all Rectifier Modules, assuming 50% load. If the system is used
with a battery charge digital temperature compensation probe, this value is the float voltage setting at 25°C. To change this
value, press and hold the FUNCTION SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is
displayed.
Note: The float voltage value is prevented from being adjusted higher than 1V below the high voltage shutdown setting.
When used with a Battery Charge Digital Temperature Compensation Probe, float voltage is prevented from being
adjusted higher than 2.75V below the high voltage shutdown setting. When used with a Battery Charge Digital
Temperature Compensation Probe, float voltage is prevented from being adjusted higher than the Maximum Voltage
with Temperature Compensation setting, or lower than the Minimum Voltage with Temperature Compensation
setting.
The MCA is used in various applications, float voltage cannot be adjusted beyond the limits of the Rectifier Module.
10. With the desired float voltage value being displayed, press and release the FUNCTION SET ENTER pushbutton.
11. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The Rectifier Modules will assume the new value at their prevailing load current.
Note: The float voltage will not be changed and the adjustment mode will be exited if the FUNCTION SET YES (+) pushbutton
is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
12. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
7. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "TEST/EQ = ##.##V".
8. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "TEST/EQ =" portion of the
display flashes.
9. Observe the value displayed. This is the test/equalize voltage setting for all Rectifier Modules, assuming 50% load. To change
this value, press and hold the FUNCTION SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is
displayed.
Note: The test/equalize voltage value is prevented from being adjusted higher than 1V below the high voltage shutdown
setting. When used with a Battery Charge Digital Temperature Compensation Probe, test/equalize voltage is
prevented from being adjusted higher than the Maximum Voltage with Temperature Compensation setting, or lower
than the Minimum Voltage with Temperature Compensation setting.
The MCA is used in various applications, equalize voltage cannot be adjusted beyond the limits of the Rectifier Module.
10. With the desired test/equalize voltage value being displayed, press and release the FUNCTION SET ENTER pushbutton.
11. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The Rectifier Modules will assume the new value at their prevailing load current.
Note: The test/equalize voltage will not be changed and the adjustment mode will be exited if the FUNCTION SET YES (+)
pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
12. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
7. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "SET HVS = ##.##V" is displayed.
8. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "SET HVS =" portion of the
display flashes.
9. Observe the value displayed. This is the high voltage shutdown setting for all Rectifier Modules. To change this value, press and
hold the FUNCTION SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
Note: The system will not allow a value higher than 59.5 to be entered. Also, the high voltage shutdown value is prevented
from being adjusted lower than 1V above the higher of the float or test/equalize setting. When used with a Battery
Charge Digital Temperature Compensation Probe, high voltage shutdown is prevented from being adjusted lower
than 1V above the Maximum Voltage with Temperature Compensation setting.
The MCA is used in various applications, high voltage shutdown cannot be adjusted beyond the limits of the Rectifier
Module.
10. With the desired high voltage shutdown value being displayed, press and release the FUNCTION SET ENTER pushbutton.
11. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The high voltage shutdown value will not be changed and the adjustment mode will be exited if the FUNCTION SET
YES (+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
12. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
7. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CURR LIM = ####A" is displayed.
8. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "CURR LIM =" portion of the
display flashes.
9. Observe the value displayed. This is the system current limit setting. Each Rectifier Module’s current limit circuit will be
automatically adjusted to ensure that system current does not exceed this value. To change this value, press and hold the
FUNCTION SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
Note: "CURRLIM = ####MAX indicates the sum of the maximum capabilities of all Rectifier Modules installed in the system.
10. With the desired current limiting value being displayed, press and release the FUNCTION SET ENTER pushbutton.
11. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The system current limit value will not be changed and the adjustment mode will be exited if the FUNCTION SET YES
(+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
12. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
5. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "ADJUST ALARMS".
8. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "SYS HV1 =" portion of the
display flashes.
9. Observe the value displayed. This is the high voltage alarm 1 setting. To change this value, press and hold the FUNCTION SET
YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
10. With the desired high voltage alarm 1 value being displayed, press and release the FUNCTION SET ENTER pushbutton.
11. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The high voltage alarm 1 value will not be changed and the adjustment mode will be exited if the FUNCTION SET YES
(+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
12. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
5. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "ADJUST ALARMS".
7. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "SYS HV2 = ##.##V".
8. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "SYS HV2 =" portion of the
display flashes.
9. Observe the value displayed. This is the high voltage alarm 2 setting. To change this value, press and hold the FUNCTION SET
YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
10. With the desired high voltage alarm 2 value being displayed, press and release the FUNCTION SET ENTER pushbutton.
11. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The high voltage alarm 2 value will not be changed and the adjustment mode will be exited if the FUNCTION SET YES
(+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
12. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
5. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "ADJUST ALARMS".
7. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "SYS BOD = ##.##V" is displayed.
8. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "SYS BOD =" portion of the
display flashes.
9. Observe the value displayed. This is the battery on discharge alarm setting. To change this value, press and hold the FUNCTION
SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
10. With the desired battery on discharge alarm value being displayed, press and release the FUNCTION SET ENTER pushbutton.
11. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The battery on discharge value will not be changed and the adjustment mode will be exited if the FUNCTION SET YES
(+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
12. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
5. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "ADJUST ALARMS".
7. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "SYS 50% = ##.##V (VERYLOVOLT =
##.##V)" is displayed.
8. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "SYS 50% = (VERYLOVOLT =)"
portion of the display flashes.
9. Observe the value displayed. This is the 50% battery on discharge (very low voltage) alarm setting. To change this value, press
and hold the FUNCTION SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
10. With the desired 50% battery on discharge (very low voltage) alarm value being displayed, press and release the FUNCTION SET
ENTER pushbutton.
11. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The 50% battery on discharge (very low voltage) alarm value will not be changed and the adjustment mode will be
exited if the FUNCTION SET YES (+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
12. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
5. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "ADJUST ALARMS".
7. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "SYS CURR = ####A" is displayed.
8. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "SYS CURR =" portion of the
display flashes.
9. Observe the value displayed. This is the system current alarm setting. To change this value, press and hold the FUNCTION SET
YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
10. With the desired system current alarm value being displayed, press and release the FUNCTION SET ENTER pushbutton.
11. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The system current alarm value will not be changed and the adjustment mode will be exited if the FUNCTION SET YES
(+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
12. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
5. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "ADJUST ALARMS".
7. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "SUB HV = ##.##V" is displayed.
8. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "SUB HV =" portion of the
display flashes.
9. Observe the value displayed. This is the subsystem high voltage alarm setting. To change this value, press and hold the
FUNCTION SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
10. With the desired subsystem high voltage alarm value being displayed, press and release the FUNCTION SET ENTER pushbutton.
11. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The subsystem high voltage alarm value will not be changed and the adjustment mode will be exited if the FUNCTION
SET YES (+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
12. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
5. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "ADJUST ALARMS".
7. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "SUB LV = ##.##V" is displayed.
8. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "SUB LV =" portion of the
display flashes.
9. Observe the value displayed. This is the subsystem low voltage alarm setting. To change this value, press and hold the
FUNCTION SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
10. With the desired subsystem low voltage alarm value being displayed, press and release the FUNCTION SET ENTER pushbutton.
11. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The subsystem low voltage alarm value will not be changed and the adjustment mode will be exited if the FUNCTION
SET YES (+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
12. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
5. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "ADJUST ALARMS".
7. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "SUB CURR = ####A" is displayed.
8. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "SUB CURR =" portion of the
display flashes.
9. Observe the value displayed. This is the subsystem current alarm setting. To change this value, press and hold the FUNCTION
SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
10. With the desired subsystem current alarm value being displayed, press and release the FUNCTION SET ENTER pushbutton.
11. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The subsystem current alarm value will not be changed and the adjustment mode will be exited if the FUNCTION SET
YES (+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
12. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
1. All controls are located on the MCA Interface Pad, unless otherwise stated. Refer to Figure 1.
Warning: Performing the next step inhibits the operation of the low voltage disconnect circuit, and if a load
contactor is furnished, prevents disconnection of battery and system output from the controlled load(s) if
a low battery voltage condition occurs. Also, if low voltage disconnect battery contactor is furnished,
prevents disconnection of battery from the system if a low battery voltage condition occurs.
2. Place the NOR/INH switch to the INH position. This switch is located inside the Distribution Cabinet. The low voltage
disconnect INHIBIT indicator illuminates. This prevents accidental disconnection of battery and system output from the
controlled load(s) if a load contactor is furnished and accidental disconnection of battery from the system if a low voltage
disconnect battery contactor is furnished while performing this procedure.
3. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
4. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
6. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUST LVD" is displayed.
8. "LVD1A = ##.##V" is displayed (if installed). If you are adjusting the other low voltage disconnect circuits, repeatedly press and
release the FUNCTION SELECT DOWN arrow pushbutton until the respective low voltage disconnect circuit name is displayed
(LVD1B, LVD2A, LVD2B, LVD3A, or LVD3B).
9. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. Portion of the display flashes.
10. Observe the value displayed. This is the low voltage disconnect setting for the circuit being adjusted. To change this value,
press and hold the FUNCTION SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
Note: The low voltage disconnect circuit is prevented from being adjusted higher than 1.0V below the reconnect voltage
setting. If you attempt to do this, a WARNING message is displayed.
11. With the desired low voltage disconnect value being displayed, press and release the FUNCTION SET ENTER pushbutton.
12. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The low voltage disconnect value will not be changed and the adjustment mode will be exited if the FUNCTION SET YES (+)
pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
13. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
14. Repeat this procedure to set the disconnect value for the other low voltage disconnect circuits installed.
Caution: DO NOT perform the next step until you verify that there are NO low voltage disconnect alarms active. If
the next step is performed when low voltage disconnect alarms are active, battery and system output will
disconnect from the controlled load(s) if a load contactor is furnished, and/or battery will disconnect from
the system if a low voltage disconnect battery contactor is furnished.
15. Return the NOR/INH switch to the NOR position. The low voltage disconnect INHIBIT indicator extinguishes.
16. Perform the next procedure to set the reconnect value for all low voltage disconnect circuits installed.
Adjusting the Reconnect Value for All Low Voltage Disconnect Circuits Installed
Local MCA Control Panel Adjustment Procedure
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
5. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUST LVD" is displayed.
7. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "LVRECON = ##.##V" or "MANUAL
RECONNECT" is displayed.
8. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "LVRECON =" portion of the
display flashes.
9. Observe the value displayed. This is the reconnect setting for all low voltage disconnect circuits installed. To change this value,
press and hold the FUNCTION SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
Note: The reconnect setting is prevented from being adjusted less than 1.0V above the highest of the disconnect values. If
you attempt to do this, a WARNING message is displayed.
Note: For manual reconnect, select "MANUAL RECONNECT". For automatic reconnect, select a value.
10. With the desired reconnect value being displayed, press and release the FUNCTION SET ENTER pushbutton.
11. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The reconnect value will not be changed and the adjustment mode will be exited if the FUNCTION SET YES (+)
pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
12. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CALIBRATION MENU" is displayed.
6. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "CAL SYS =" portion of the
display flashes.
7. Observe the value displayed. This is the system output voltage reading calibration setting. To change this value, press and hold
the FUNCTION SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
8. With the desired calibration value being displayed, press and release the FUNCTION SET ENTER pushbutton.
9. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The system output voltage reading calibration value will not be changed and the calibration mode will be exited if the
FUNCTION SET YES (+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
10. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CALIBRATION MENU" is displayed.
5. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "CAL SUB = ##.##V".
6. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The CAL SUB =" portion of the
display flashes.
7. Observe the value displayed. This is the subsystem output voltage reading calibration setting. To change this value, press and
hold the FUNCTION SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
8. With the desired calibration value being displayed, press and release the FUNCTION SET ENTER pushbutton.
9. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The subsystem output voltage reading calibration value will not be changed and the calibration mode will be exited if
the FUNCTION SET YES (+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
10. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
Returning System and Subsystem Output Voltage Reading Calibrations to their Default Values
Local MCA Control Panel Adjustment Procedure
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CALIBRATION MENU" is displayed.
5. Press and release the FUNCTION SELECT DOWN arrow pushbutton until "SET FACTORY CAL." is displayed.
Note: If the calibration values are at their defaults, this option is not displayed.
6. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
7. "ARE YOU SURE? + -" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
Note: The system and subsystem output voltage reading calibration values will not change to their defaults and the
calibration mode will be exited if the FUNCTION SET YES (+) pushbutton is not pressed within 10 seconds of the “ARE
YOU SURE? + -” prompt.
8. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CALIBRATION MENU" is displayed.
5. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "DIGITAL TC OFF” or “SLOPE = .### V/°C" is
displayed.
6. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The “DIGITAL TC OFF” or "SLOPE
=" portion of the display flashes.
7. Observe the value displayed. This is the Battery Charge Digital Temperature Compensation slope setting. To change this value,
press and hold the FUNCTION SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
Note: Refer to Battery and Equipment Manufacturers’ recommendations or site requirements for the value. Note that this is
the compensation for the entire battery string, not per battery cell.
8. With the desired slope value being displayed, press and release the FUNCTION SET ENTER pushbutton.
9. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The slope value will not be changed and the adjustment mode will be exited if the FUNCTION SET YES (+) pushbutton
is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
10. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CALIBRATION MENU" is displayed.
5. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "MAX W/T = ##.## V" is displayed.
6. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The “MAX W/T =" portion of the
display flashes.
7. Observe the value displayed. This is the Battery Charge Digital Temperature Compensation maximum voltage setting. To
change this value, press and hold the FUNCTION SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired
value is displayed.
Note: Refer to Battery and Equipment Manufacturers’ recommendations or site requirements for the value.
Note: Maximum Voltage with Temperature Compensation is prevented from being adjusted higher than 1V below the High
Voltage Shutdown setting, or lower than the float voltage setting.
The MCA is used in various applications, this setting cannot be adjusted beyond the limits of the Rectifier Module.
8. With the desired maximum voltage with temperature compensation value being displayed, press and release the FUNCTION
SET ENTER pushbutton.
9. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The maximum voltage with temperature compensation value will not be changed and the adjustment mode will be
exited if the FUNCTION SET YES (+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
10. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CALIBRATION MENU" is displayed.
5. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "MIN W/T = ##.## V" is displayed.
6. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The “MIN W/T =" portion of the
display flashes.
7. Observe the value displayed. This is the Battery Charge Digital Temperature Compensation minimum voltage setting. To
change this value, press and hold the FUNCTION SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired
value is displayed.
Note: Refer to Battery and Equipment Manufacturers’ recommendations or site requirements for the value.
Note: Minimum Voltage with Temperature Compensation is prevented from being adjusted lower than 1V above the Low
Voltage Disconnect Reconnect Value setting, or higher than the float voltage setting.
8. With the desired minimum voltage with temperature compensation value being displayed, press and release the FUNCTION
SET ENTER pushbutton.
9. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The minimum voltage with temperature compensation value will not be changed and the adjustment mode will be
exited if the FUNCTION SET YES (+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
10. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CALIBRATION MENU" is displayed.
5. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "TCOMP ON SENSOR1" or "TCOMP ON
AVERAGE" or "TCOMP ON HIGHEST" is displayed.
6. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The display flashes.
7. Observe the value displayed. This is the Battery Charge Temperature Compensation Source setting. To change this value, press
and hold the FUNCTION SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
8. With the desired value being displayed, press and release the FUNCTION SET ENTER pushbutton.
9. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The Temperature Compensation Source will not be changed and the adjustment mode will be exited if the FUNCTION
SET YES (+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
10. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
Adjusting Battery Ambient High Temperature Alarm (if Battery Charge Digital Temperature Compensation
Probe is installed)
Local MCA Control Panel Adjustment Procedure
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
5. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "ADJUST ALARMS".
7. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "HI TEMP ** IS OFF” or “HI TEMP ** =
###°C" is displayed.
8. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The “HI TEMP ** IS OFF” or "HI
TEMP ** =" portion of the display flashes.
9. Observe the value displayed. This is the high temperature alarm setting. To change this value, press and hold the FUNCTION
SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
10. With the desired high temperature alarm value being displayed, press and release the FUNCTION SET ENTER pushbutton.
11. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The high temperature alarm value will not be changed and the adjustment mode will be exited if the FUNCTION SET
YES (+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
12. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
Adjusting Battery Ambient Low Temperature Alarm (if Battery Charge Digital Temperature Compensation
Probe is installed)
Local MCA Control Panel Adjustment Procedure
1. All controls are located on the MCA Interface Pad. Refer to Figure 1.
2. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
3. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
5. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "ADJUST ALARMS".
7. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "LO TEMP ** IS OFF” or “LO TEMP ** =
###°C" is displayed.
8. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The “LO TEMP ** IS OFF” or "LO
TEMP ** =" portion of the display flashes.
9. Observe the value displayed. This is the low temperature alarm setting. To change this value, press and hold the FUNCTION SET
YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
10. With the desired low temperature alarm value being displayed, press and release the FUNCTION SET ENTER pushbutton.
11. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The low temperature alarm value will not be changed and the adjustment mode will be exited if the FUNCTION SET
YES (+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
12. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
Enabling, Disabling, and Adjusting the Battery Recharge Current Limit Setting
Note: The Battery Recharge Current Limit feature is active when a "BATTLIM" value is selected, as described in this procedure.
The Battery Recharge Current Limit feature is inactive when "BATTLIM DISABLED" is selected, as described in this procedure.
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
6. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "BATTLIM = #####A" or "BATTLIM DISABLED"
is displayed.
7. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "BATTLIM =" portion of the
display flashes.
8. Observe the value displayed. This is the battery recharge current limit setting. Each Rectifier Modules current limit circuit will be
automatically adjusted to ensure that battery current does not exceed this value, as described in the System Operating
Procedures section. To change this value, press and hold the FUNCTION SET YES (+) or NO (-) pushbutton. Release the
pushbutton when the desired value is displayed. Note that as you scroll above the system current limit setting, "BATTLIM
DISABLED" is displayed. Scroll back down to redisplay "BATTLIM =".
9. With the desired battery recharge current limit value being displayed, press and release the FUNCTION SET ENTER pushbutton.
10. “ARE YOU SURE? + - “ is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The battery recharge current limit value will not be changed and the adjustment mode will be exited if the FUNCTION
SET YES (+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
11. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT MENU" is displayed.
4. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "ADJUST ALARMS".
6. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "BAT CHG = #####A" is displayed.
7. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "BAT CHG =" portion of the
display flashes.
8. Observe the value displayed. This is the battery charge current alarm setting. To change this value, press and hold the
FUNCTION SET YES (+) or NO (-) pushbutton. Release the pushbutton when the desired value is displayed.
9. With the desired battery charge current alarm value being displayed, press and release the FUNCTION SET ENTER pushbutton.
10. “ARE YOU SURE? + - “ is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
Note: The battery charge current alarm value will not be changed and the adjustment mode will be exited if the FUNCTION
SET YES (+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? + -” prompt.
11. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
System Maintenance
Admonishments
GENERAL SAFETY
Performing the following procedures may expose service personnel to hazards. These procedures should be
performed by qualified service personnel familiar with the hazards associated with this type of equipment.
These hazards may include shock, energy, and/or burns. To avoid these hazards:
a) The tasks should be performed in the order indicated.
b) Remove watches, rings, and other jewelry.
c) Prior to contacting any uninsulated surface or termination, use a voltmeter to verify that no voltage or the
expected voltage is present.
d) Wear eye protection, and use recommended tools.
e) Use insulated tools.
(To avoid danger to the installer or damage to the equipment, the tools used in this procedure should have
insulated grips. All exposed metal shafts, extensions, handles, etc. should be completely insulated with a
minimum of three half-lapped layers of electrical tape. Ensure that wrenches with more than one working
end have only one end exposed.)
VOLTAGES
AC Input Voltages
Danger: This system operates from AC voltage capable of producing fatal electrical shock.
DC Input/Output Voltages
Danger: This system produces DC Power and may require battery to be connected to it. Although the DC voltage is not
hazardously high, the rectifier Modules and/or battery can deliver large amounts of current. Exercise extreme
caution not to inadvertently contact or have any tool inadvertently contact a battery terminal or exposed wire
connected to a battery terminal. NEVER allow a metal object, such as a tool, to contact more than one
termination at a time, or to simultaneously contact a termination and a grounded object. Even a momentary
short circuit can cause explosion and injury.
Caution: Performing the following procedures may interrupt power to the loads, if battery reserve is not sufficient.
Table 5. Procedures which May be Performed at 12-Month Intervals to Track System Operation
Measure and Record Total System Section 5975, Navigating the MCA.
Current (Line #62)
Measure and Record Total Rectifier Section 5975, Navigating the MCA.
Module Current (Line #63)
Measure and Record Subsystem (if Section 5975, Navigating the MCA.
connected) Output Voltage (Line #64)
Measure and Record Total Subsystem Section 5975, Navigating the MCA.
(if connected) Output Current (Line #65)
#1
#2
#3
#4
#5
#6
#7
#8
Measure and Record Output Current Section 5975, Navigating the MCA.
of Each Individual System Load Shunt (Line #86)
#9
#10
#11
#12
#13
#14
#15
#16
#1
#2
#3
#4
#5
#6
#7
#8
#9
#10
#11
#14
#15
#16
#17
#18
#19
#20
#21
#22
#23
#24
#25
#26
#27
#28
#29
#30
#31
#32
#33
#34
#35
#38
#39
#40
#41
#42
#43
#44
#45
#46
#47
#48
#49
#50
#51
#52
#53
#54
#55
#56
#57
#58
#59
#62
#63
#64
#65
#66
#67
#68
#69
#70
#71
#72
#1
#2
#3
#4
#5
#6
#7
#10
#11
#12
#13
#14
#15
#16
#1
#2
#3
#4
#5
#6
#7
#10
#11
#12
#13
#14
#15
#16
Record Battery Recharge Current Limit Section 5975, Navigating the MCA.
Value (Line #99A)
#1 =
#2 =
#3 =
Measure and Record Temperature Section 5975, Navigating the MCA. #4 =
Sensor (if installed) Temperature (Line #65B) #5 =
#6 =
#7 =
#8 =
#1 =
#2 =
#3 =
Record High Temperature Alarm
Section 5975, Navigating the MCA. #4 =
Value (if temperature compensation
(Line #110B) #5 =
probe installed)
#6 =
#7 =
#8 =
#1 =
#2 =
#3 =
Record Low Temperature Alarm
Section 5975, Navigating the MCA. #4 =
Value (if temperature compensation
(Line #110C) #5 =
probe installed)
#6 =
#7 =
#8 =
Record Slope Value (if temperature Section 5975, Navigating the MCA.
compensation probe installed) (Line #83A)
Rectifier Modules can be inserted or removed with power applied (hot swappable).
Note: Each Rectifier Module locks into the Rectifier Module Mounting Shelf through a latch located on the underside of the Rectifier
Module. The latch and Rectifier Module handle are interactive. Push the handle into the Rectifier Module’s front panel, and the
latch will pop out from the Rectifier Module bottom. Click the handle to pop it out from the Rectifier Module’s front panel, and
the latch will retract back into the Rectifier Module. See Figure 2 for handle operation.
Warning: To prevent damage to the latching mechanism, ensure the handle is in the open position when installing or
removing a module. NEVER hold the handle in the closed position when installing a module into a shelf.
Procedure
2. If present, remove blank cover panel from the mounting position into which Rectifier Module is to be installed.
3. Place the Rectifier Module into the unoccupied mounting slot without sliding it in completely.
4. Click the Rectifier Module handle in order to pop it forwards out of the Rectifier Module’s front panel (this will also retract the
latch mechanism located on the underside of the Rectifier Module).
6. Push the handle into the front panel of the Rectifier Module. This will lock the module securely to the shelf.
7. After the Rectifier Module is physically installed in the mounting shelf, it is ready for operation immediately after power is
supplied to it.
Adding an Additional Rectifier Module Mounting Shelf to a System in the Field (Using Output Busbar Kit P/N
529139)
Note: Apply anti-oxide compound to all mechanical connections.
Procedure
Danger: Observe the admonishments located at the beginning of this section.
1. On the rear of the new Rectifier Module Mounting Shelf and the shelf installed directly above it, remove the rear shield that
covers the output busbars.
2. Install the new Rectifier Module Mounting Shelf directly below the bottom Rectifier Module Mounting Shelf in the rack. Use the
mounting hardware provided in Kit P/N 529139.
Hardware build-up is: 12-24 x 3/4" screw and flat washer, (1) set per side.
12-24 x 3/4" screw and ground washer, (1) set per side.
Install the ground washers so the teeth dig into the paint on the mounting angles. Torque all screws to 65 in-lbs.
3. Install the kit-furnished output busbars as shown in Figure 3. Apply electrical anti-oxidizing compound to all busbar mating
surfaces.
Install the Belleville lock washer so the concave side is towards the busbar. Torque all bolts and nuts to 60 in-lbs.
4. Plug the connector on the cable exiting the top of the new shelf with the mating connector exiting the bottom of the shelf
above it.
5. If more shelves are being added, repeat Steps 1) through 4) for each of the additional shelves.
6. Replace the output busbar shield on the rear of all Rectifier Module Mounting Shelves.
7. Refer to the Installation Instructions (Section 5974) and connect AC input power to the new shelf(s).
8. Refer to the previous procedure and install Rectifier Modules into the new shelf.
Figure 3. Installing Kit P/N 529139 Output Busbars (cont'd on next page)
Figure 3. Installing Kit P/N 529139 Output Busbars (cont'd from previous page)
To increase subsystem current capacity, an additional Converter Module can easily be added to an existing Converter Mounting Shelf that
contains an empty mounting position. Follow the procedure detailed below.
Procedure
1. If not already done, remove blank modules from any mounting position into which a Converter Module is to be installed.
2. Ensure that the ON/STANDBY switch on the new Converter Module is in the STANDBY ( ) position.
3. Slide the Converter Module into its mounting position in the shelf. Secure by tightening the captive fastener located on the
front panel.
4. Ensure that all mounting positions are occupied, by either a Converter Module or a blank module.
5. Place the ON/STANDBY switch on the new Converter Module to the ON ( I ) position.
6. Ensure that there are no local or remote alarms active on the system.
If the power system is equipped with a List 63 Converter Mounting Shelf in the Main Bay, subsystem current capacity may be increased,
by installing an additional Converter Mounting Shelf (List 64).
Danger: If the PCU Mounting Shelf is operating or connected to battery during this procedure, -48VDC power will be
present on the exposed output busbars on the rear of the Power System. While this voltage is not hazardously
high, the PCUs and/or battery can deliver large amounts of current. Use extreme caution not to allow any
conductive object to contact these busbars. Remove watches, rings, and other jewelry before performing this
procedure.
Refer to the separate Installation Manual (Section 5974) for procedures detailing mounting and wiring of List 63 and 64 DC-DC Converter
Mounting Frames.
Perform the following procedure to install the LVD bypass busbar. Refer to Figure 4 as the procedure is performed.
Procedure
Danger: Observe the admonishments located at the beginning of this section.
1. Open the Distribution Cabinet's front door by turning and holding the captive fastener in the counterclockwise position.
2. Remove the four bolts and washers indicated in Figure 4. Retain the washers for reuse. The bolts may be discarded.
Danger: Perform the next step to avoid arcing when the busbar is installed.
3. Verify that the LVD contactor is energized (contacts are closed); otherwise arcing may occur when the bypass busbar is
installed. As an alternative, remove all loads from the contactor by turning off all circuit breakers or removing all fuses in the
distribution row.
Note: In the next step, apply electrical anti-oxidizing compound to busbar mating surfaces.
4. Place the kit-furnished busbar as shown in Figure 4. Secure by installing four kit-furnished bolts (1/4-20 x 1”) and the washers
that were removed in a previous step. Recommended torque is 84 inch pounds for the standard (split) lock washers, and 60
inch pounds for the Belleville washers.
5. Ensure all circuit breakers are turned on or fuses installed in the distribution row.
6. Close the Distribution Cabinet's front door. The door can be shut without turning the captive fastener.
REMOVE THESE
4 BOLTS
P/N 514909
BYPASS
BUSBAR
TORQUE TO
84 IN. LBS. TORQUE TO
60 IN. LBS.
Perform the following procedure to replace the LVD contactor with the bypass busbar. Refer to Figure 5 as the procedure is performed.
Procedure
Danger: Observe the admonishments located at the beginning of this section.
Danger: All sources of AC and DC power must be completely disconnected from this power system before performing
this procedure. Use a meter to verify no DC voltage is present on the system busbars and contactor before
proceeding.
1. Open the Distribution Cabinet's front door by turning and holding the captive fastener in the counterclockwise position.
2. On the side of the contactor body, disconnect the lug that terminates two 22 AWG violet wires. Cut and remove the plastic
cable tie that secures these two violet wires to a red/white wire.
3. Use kit-furnished sleeving to insulate the lug that was disconnected in the last step. Secure the sleeving to the wires by applying
kit-furnished plastic cable ties. Tie back the wires using kit-furnished plastic cable ties.
4. Remove the seven bolts and washers indicated in Figure 5. Remove the contactor. Retain all hardware for reuse.
Note: In the next step, apply electrical anti-oxidizing compound to busbar mating surfaces.
5. Place the kit-furnished busbar as shown in Figure 5. Secure by installing and tightening the seven bolts and 14 washers that
were removed in a previous step. Recommended torque is 84 inch pounds for the standard (split) lock washers, and 60 inch
pounds for the Belleville washers.
6. Close the Distribution Cabinet's front door. The door can be shut without turning the captive fastener.
REMOVE THESE
3 BOLTS REMOVE THESE
4 BOLTS
P/N 514911
BUSBAR
TORQUE TO
84 IN. LBS. TORQUE TO
60 IN. LBS.
DISCONNECT
LUG WITH 2
VIOLET WIRES
Admonishments
GENERAL SAFETY
Performing the following procedures may expose service personnel to hazards. These procedures should be
performed by qualified service personnel familiar with the hazards associated with this type of equipment.
These hazards may include shock, energy, and/or burns. To avoid these hazards:
a) The tasks should be performed in the order indicated.
b) Remove watches, rings, and other jewelry.
c) Prior to contacting any uninsulated surface or termination, use a voltmeter to verify that no voltage or the
expected voltage is present.
d) Wear eye protection, and use recommended tools.
e) Use insulated tools.
(To avoid danger to the installer or damage to the equipment, the tools used in this procedure should have
insulated grips. All exposed metal shafts, extensions, handles, etc. should be completely insulated with a
minimum of three half-lapped layers of electrical tape. Ensure that wrenches with more than one working
end have only one end exposed.)
VOLTAGES
AC Input Voltages
Danger: This system operates from AC voltage capable of producing fatal electrical shock.
DC Input/Output Voltages
Danger: This system produces DC Power and may require battery to be connected to it. Although the DC voltage is not
hazardously high, the Rectifier Modules and/or battery can deliver large amounts of current. Exercise extreme
caution not to inadvertently contact or have any tool inadvertently contact a battery terminal or exposed wire
connected to a battery terminal. NEVER allow a metal object, such as a tool, to contact more than one
termination at a time, or to simultaneously contact a termination and a grounded object. Even a momentary
short circuit can cause explosion and injury.
Caution: Performing the following procedures may interrupt power to the loads, if battery reserve is not sufficient.
CIRCUIT CARDS
Warning: Installation or removal of the circuit cards requires careful handling. Before handling any circuit card, read
and follow the instructions contained on the Static Warning Page located at the beginning of this document.
To avoid possibility of circuit card damage from static discharge, a static wrist strap grounded through a one
megohm resistor should always be worn when handling the circuit cards.
Troubleshooting Information
GENERAL
This system is designed for ease in troubleshooting and repair. The various indicators as described in "System Operating Procedures", are
designed to isolate failure to a specific element. Once the faulty element has been identified, refer to the next sections, “REPLACEMENT
INFORMATION” and "REPLACEMENT PROCEDURES".
The procedures listed in "System Maintenance", can also be used by servicing personnel in identification and/or prevention of trouble
symptoms in the system.
ADJUSTMENTS
If the suspected cause of a trouble symptom is an out of adjustment condition, that particular adjustment setting should be checked or
reset using the appropriate adjustment procedure detailed in "MCA System Adjustments". If a failed Rectifier Module, MCA, or Low
Voltage Disconnect circuit card is suspected, the adjustment procedures can also be used to verify the setpoints as well as the operation
of the Rectifier Module, MCA, or Low Voltage Disconnect circuit card.
MCA MESSAGES
An MCA Menu Tree is provided in the separate Installation Manual (and on the CD furnished with your system). Each line in the MCA Menu
Tree contains a number. This number is referenced in a chart provided in "Navigating the MCA". This chart provides a description of each
line listed on the MCA Menu Tree.
If the MCA displays a system or subsystem alarm message, find the line in the MCA Menu Tree showing this message. For an explanation
of this alarm, locate the corresponding MCA Menu Tree Line Number in the chart provided in section.
Note: If the MCA is replaced with an MCA previously used in another power system, the MCA may reflect inventory items not in the
current power system and may display alarms. In this case, update the inventory as detailed in this section. Also, if you remove
an inventory item (a component) from the power system, you must update the inventory to clear alarms.
Note: If you remove a Battery Charge Temperature Compensation Probe, alarms are displayed. Manually set the Battery Charge
Temperature Compensation feature to off as described in "MCA System Adjustments" to clear the alarms.
The following provides a list and descriptions of additional messages the MCA may display.
ARE YOU SURE? +-: MCA presents this query before changing an operating parameter.
TempCmp Hardware: The user tried to set the TC CAL value (line 83 on MCA Menu Tree Section 6022) to a value when a temperature
compensation module was not present, or to ANALOG TC OFF when a module was present.
or
The user tried to set the temperature compensation probe's SLOPE value (line 83A on MCA Menu Tree Section 6022) to a value when a
temperature compensation probe was not present, or to DIGITAL TC OFF when a probe was present.
NOT RUNNING YET!: This is the normal display (instead of line 1 or 0 on MCA Menu Tree Section 6022) when no Rectifier Modules are
talking to the MCA.
PASSWORD: $$$$$$: Pressing ALARM CUTOFF, FUNCTION SELECT UP, and FUNCTION SELECT DOWN at the same time while viewing
REMOTE INSTALLED or REMOTE ACTIVE (line 123 on MCA Menu Tree Section 6022) allows the user to view the remote access password.
TestEq Switch On: The user tried to set Float mode (line 42 on MCA Menu Tree Section 6022) while the external test/equalize input
switch was on.
Local Lockout On: The user tried to change an operating parameter while the local lockout jumper was in place.
NO PCUs FOUND: Displayed instead of line 15 or 118 (on MCA Menu Tree Section 6022) when no Rectifier Modules are talking to the
MCA.
NO SHUNTS FOUND: Displayed instead of line 120 (on MCA Menu Tree Section 6022) when no shunt A/D's are talking to the MCA.
NO LVDs FOUND: Displayed instead of line 121 (on the MCA Menu Tree Section 6022) when no LVDs are talking to the MCA.
NO TEMP SENSORS FOUND: Displayed instead of line 121A (on MCA Menu Tree Section 6022) when no Temperature Sensors are talking
to the MCA.
Alarm(s) Active: The user tried to enter TEST ALM RELAYS mode (line 111 on MCA Menu Tree Section 6022) when external alarms were
active.
A Bypass Circuit Card (P/N 513737) must be installed in every unused Quad Shunt POD Circuit Card or Quad Low Voltage Disconnect
Circuit Card Mounting Position in every Distribution Cabinet in the Power System. Otherwise the power system will not operate
normally.
UPDATING THE INVENTORY AFTER CHANGES TO THE SYSTEM HAVE BEEN MADE
When an inventory item is removed from the system, an alarm will be reported until the following procedure is performed.
Example, if a Rectifier Module (PCU) is removed from the system, "PCU** TYPE ###A" will change to reflect this but the Rectifier Module
will not be removed from the MCA's inventory until "VERIFY INVENTORY" is entered and the "UPDATE INVENTORY" operation is
completed.
Procedure
1. With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "FUNCTION MENU" is displayed. Press and
release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE MENU" is displayed.
4. "VERIFY INVENTORY" is displayed. Press and release the FUNCTION SET ENTER pushbutton.
5. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "UPDATE INVENTORY" is displayed.
6. With "UPDATE INVENTORY" being displayed, press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons
simultaneously.
7. “ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
8. To return to the beginning of the MCA Logic Tree, press and release the FUNCTION SET YES (+) and NO (-) pushbuttons
simultaneously.
Replacement Information
REPLACEMENT ASSEMBLIES
When a trouble symptom is localized to a faulty Rectifier Module or circuit card, that particular Rectifier Module or circuit card should be
replaced in its entirety. Other than a Rectifier Module fan replacement, no attempt should be made to troubleshoot or repair individual
components on any Rectifier Module or circuit card.
Refer to SAG582126000 (System Application Guide) for replacement part numbers. The SAG can be accessed from the CD (Electronic
Documentation Package) furnished with your system.
REPLACEMENT CABLES
Refer to SAG582126000 (System Application Guide) for replacement part numbers. The SAG can be accessed from the CD (Electronic
Documentation Package) furnished with your system.
Replacement Procedures
REPLACING A RECTIFIER MODULE (PCU)
Refer to the Rectifier User Instructions (UM1R483500e) for a Rectifier Module replacement procedure. Before replacing any Rectifier
Module, note the following.
Note: If a Rectifier Module (PCU) is removed without being replaced, perform the UPDATE INVENTORY procedure found in this section
under TROUBLESHOOTING INFORMATION to clear alarms.
If a Rectifier Module (PCU) is removed and replaced with a different module, alarms are activated for 2 minutes after inserting
the new Rectifier Module. The MCA automatically removes the old Rectifier Module from inventory and adds the new Rectifier
Module to the inventory. Refer to the following note for further explanation.
Note: The "REPLACE ## PCUs" message is automatically displayed when a new Rectifier Module (PCU) is detected and a PCU no reply
alarm is active, or becomes active within two minutes. The message is displayed for 2 minutes and the message timer is
restarted every time a new Rectifier Module (PCU) is detected or a new PCU no reply alarm becomes active.
The timer is terminated and the ALM ## PCUs FAIL message is displayed if the NO (-) pushbutton is pressed.
Rectifier Modules (PCUs) equal to the number of new Rectifier Modules (PCUs) or the number of PCU no reply alarms, whichever
is less, are removed from the inventory if the YES (+) pushbutton is pressed or if the timer expires without a pushbutton being
pressed. The MCA displays the PLEASE WAIT message while it updates the Rectifier Modules (PCUs) in its permanent inventory,
and then displays the CURRLIM = #####A message.
Note: Only applies if system is equipped with List 63 or 64 Converter Mounting Shelf.
A failed Converter Module can be replaced without interrupting operation of other Converter Modules present in the Converter
Mounting Shelf.
Warning: Each Converter Module contains static-sensitive devices. Read the Static Statement at the front of this manual
before performing this procedure.
Procedure
1. Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these
alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system.
2. On the Converter Module to be removed, place the ON/STANDBY (I / ) switch to the STANDBY ( ) position.
3. Loosen the captive fastener on the front of the Converter Module to be removed. Using the handle provided on the front of the
module, pull the module from the DC-DC Converter Mounting Shelf.
4. Ensure that the ON/STANDBY (I / ) switch on the replacement Converter Module is in the STANDBY ( ) position.
5. Slide the replacement Converter Module into its mounting position in the Converter Mounting Shelf. Secure it to the shelf by
tightening the captive fastener located on the front panel.
7. Ensure that all mounting positions are occupied, by either a Converter Module or a blank module.
8. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
9. Ensure that there are no local or remote alarms active on the system.
OUTPUT
ON
OK
ON / STANDBY
SWITCH
Note: Only applies if system is equipped with List 63 or 64 Converter Mounting Shelf.
A failed alarm circuit card can be replaced without interrupting operation of the converters present in the Converter Shelf.
A No. 2 Phillips screwdriver is required to perform this procedure.
Procedure
1. Remove two screws that secure the alarm circuit card assembly to the converter shelf. Refer to Figure 7.
2. Carefully slide the alarm circuit card assembly out of the shelf until the ribbon cable connection on the circuit card is accessible.
3. Disconnect the ribbon cable from its mating plug (P6) on the alarm circuit card. To do so, depress the locking tab on the side of
the connector until it can be separated from the plug.
4. Remove two screws and lock washers that secure the alarm circuit card to its mounting bracket. Remove the circuit card. Refer
to Figure 8.
5. Install the replacement circuit card on the mounting bracket. Secure with two previously removed screws and lock washers.
6. Connect the ribbon cable to its mating plug (P6) on the replacement circuit card. Insert fully to ensure the connector locks in
place.
7. Carefully slide the alarm circuit card assembly into of the Converter Shelf. Ensure the tab at the rear of the mounting bracket
engages the mating slot at the rear of the shelf.
8. Reinstall the two screws that secure the alarm circuit card assembly to the converter shelf.
9. Ensure that there are no local or remote alarms active in the system.
Figure 7. Removing the Alarm Circuit Card Assembly from List 63, 64 Converter Shelf
FASTENING
SCREW NOTE:
MODULES IN
POSITIONS 3 AND 7 MUST
BE REMOVED TO
REPLACE ALARM CIRCUIT
INPUT
CARD ASSEMBLY.
OK
INPUT
OK
ALARM
MINOR
MAJOR
ALARM
FASTENING
SCREW
Figure 8. Replacing the Converter Shelf Alarm Circuit Card in List 63, 64
ALARM CIRCUIT
CARD
MOUNTING
BRACKET
MCA REPLACEMENT
The MCA includes three separate circuit cards: the MCA Main Controller, the MCA Power Supply, and the MCA Keypad/Display. The MCA
is removed from the Distribution Cabinet as a complete assembly prior to replacing any of these circuit cards. A procedure for removing
the MCA assembly for service is provided here. Procedures for replacing each of the circuit cards are also provided.
Caution: When performing any step in this procedure that requires removal or installation of hardware, use caution to
ensure no hardware is dropped and left inside the cabinet; otherwise service interruption or equipment damage
may occur.
Warning: Circuit cards used in this equipment contain static-sensitive devices. Read the Static Warning page at the
front of this document before performing the following procedure.
Note: When performing any step in this procedure that requires removal of existing hardware, retain all hardware for use in
subsequent steps.
Note: A flat-blade screwdriver, No. 2 Phillips screwdriver, and 5/16” nut driver are required to perform all the following procedures.
Preparation
1. Observe the admonishments presented at the beginning of this section, and those encountered in this procedure.
2. Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these
alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system.
Replacing the MCA Main Controller circuit card WILL result in all MCA settings being returned to their factory default values.
1. If you are replacing the MCA Main Controller circuit card, in Table 6 and Table 7, either manually record all existing MCA settings
or record the required settings for your site from your company's DC Plant Set Points specifications (standards).
Note: The MCA configuration can be saved by downloading the configuration using the WinLink software program (if
available).
BASIC SETTINGS
Factory
Factory
Default Setting
Default Setting Required
Setting MCA Config.
MCA Config. Site Setting
534876, 534878,
534877
and 534879
Float Voltage 54.48V 54.00V
Test/Equalize Voltage 54.48V 55.20V
High Voltage Shutdown 57.50V 56.00V
100% of Rated Full 100% of Rated Full
System Current Limit
Load Load
System HV1 55.50V 55.40V
System HV2 56.50V 56.00V
System BOD 48.00V 47.00V
System 50%BOD 46.00V 44.50V
System Current Alarm 2000A 2000A
Subsystem HV 25.00V 28.00V
Subsystem LV 23.00V 23.00V
Subsystem Current Alarm 2000A 2000A
LVD 1A 42.0V 43.5V
LVD 1B 42.0V 43.5V
LVD 2A 42.0V 43.5V
LVD 2B 42.0V 43.5V
LVD 3A 42.0V 43.5V
LVD 3B 42.0V 43.5V
LVD Reconnect 49.0V 50.5V
Digital Temperature
Off (0V/°C) Off (0V/°C)
Compensation (Slope)
Digital Temperature
56.50V 55.00V
Compensation (MAX W/T)
Digital Temperature
50.00V 51.50V
Compensation (MIN W/T)
TCOMP ON TCOMP ON
Temperature Compensation Source
SENSOR1 SENSOR1
High Battery Ambient
Off Off
Temperature Alarm
Low Battery Ambient
Off Off
Temperature Alarm
Number of Available
- -
Rectifier Module Mounting Positions
ADVANCED SETTINGS
Factory
Factory
Default Setting
Default Setting Required
Setting MCA Config.
MCA Config. Site Setting
534876, 534878,
534877
and 534879
Alternating Display Feature Disabled Disabled
Rectifier Module Fan
Disabled Disabled
Speed Control Feature
MCA Audible Alarm
15 Minutes 15 Minutes
Cutoff Reset Time Period
Manually Initiated Timed Test/Equalize
1 Hour 1 Hour
Feature
Automatic Test/Equalize Feature Disabled Disabled
Alarm Relay Test Feature 45 Seconds 45 Seconds
1. Open the Distribution Cabinet's front door by turning and holding the captive fastener in the counterclockwise position.
Danger: Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
2. Remove the clear plastic panel that covers the circuit cards at the bottom of the cabinet. To do so, loosen but do not remove
the two screws that secure the cover. Slide the cover to the front until the screw heads clear the keyhole slots in the cover.
Then lift the cover out of the cabinet.
Warning: Damage to the MCA may result if the next step is not followed.
3. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
Note: If distribution Row A (bottom row) in the Distribution Cabinet is equipped with a GJ/218 type circuit breaker in the bottom
mounting position, it may be necessary to turn off and remove the circuit breaker to access connector J15 in the next step.
If so, reinstall and turn on the circuit breaker after completing all MCA replacement procedures.
4. Disconnect the locking-type plug from connector J15 at the rear of the MCA Main Controller circuit card. This removes input
power to the MCA.
5. With an external voltmeter, verify plant voltage is correct (MCA is powered down at this point).
2. Remove the following cables from the MCA Interface Option circuit card (if installed).
a. Various MCA Interface Options are available, remove any cable(s) connected to the circuit card.
3. Remove the following cables from the Rectifier Shelf Interface circuit card.
a. Separate the cable connected to the pigtail cable permanently connected to the circuit card.
b. Disconnect the cable from connector J2.
c. Disconnect the cable from connector J4.
4. Remove the following cables from the MCA Main Controller circuit card.
a. Disconnect the cable from connector J8.
b. Disconnect the cable from connector J9. To do so, grasp the ejector tabs at each end of the connector and pivot outward,
forcing the plug out of the connector.
c. If a Battery Ambient Temperature Probe or TXM is installed, remove the connector from J4.
5. Using a 5/16” nut driver, remove the two hex nuts and ground washers that secure the MCA assembly to the floor of the
Distribution Cabinet.
6. Lift the front of the MCA assembly and pull straight out of the Distribution Cabinet. Remove the MCA Assembly to a static-safe
work surface.
1. Remove the MCA assembly to a static-safe work surface as describe in the “Removing the MCA Assembly for Service” procedure.
Warning: Damage to the MCA may result if the next step is not followed.
2. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
3. Locate the metal bracket that is under the Rectifier Shelf Interface circuit card. Loosen but do not remove the four Phillips
screws that secure the metal bracket. Remove the metal bracket with the Rectifier Shelf Interface circuit card by sliding toward
the rear of the MCA assembly until the screw heads clear the slots in the bracket. Lift the bracket and circuit card from the MCA
assembly, and set aside.
4. Remove the ribbon cable permanently connected to the MCA Power Supply circuit card from connector J2 on the rear edge of
the MCA Main Controller circuit card.
5. Remove the two Phillips head screws and two hex spacers that secure the MCA Power Supply circuit card to the MCA Main
Controller circuit card. Remove the Power Supply circuit card.
6. Position the replacement MCA Power Supply circuit card over its mounting position. Secure by installing and tightening the two
Phillips head screws (front) and two hex spacers (rear) previously removed.
7. Connect the ribbon cable permanently connected to the MCA Power Supply circuit card to connector J2 on the rear edge of the
MCA Main Controller circuit card.
8. Reinstall the previously removed metal bracket and Rectifier Shelf Interface circuit card. To do so, place the bracket on its four
mounting posts so that the mounting screw heads pass through the slots in the bracket. Slide the bracket toward the front of
the MCA assembly. Tighten the four screws.
9. STOP. If no other circuit cards in the MCA assembly are being replaced, continue with the “Reinstalling the MCA Assembly
Following Service” procedure found later in this section.
Note: Refer to Figure 9, Figure 10, and Figure 11 as this procedure is performed.
1. Remove the MCA assembly to a static-safe work surface as describe in the “Removing the MCA Assembly for Service” procedure.
Warning: Damage to the MCA may result if the next step is not followed.
2. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
3. Refer to Figure 10, and locate the metal bracket that is under the Rectifier Shelf Interface circuit card. Loosen but do not
remove the four Phillips screws that secure the metal bracket. Remove the metal bracket with the Rectifier Shelf Interface
circuit card by sliding toward the rear of the MCA assembly until the screw heads clear the slots in the bracket. Lift the bracket
and circuit card from the MCA assembly, and set aside.
4. Remove the ribbon cable permanently connected to the MCA Power Supply circuit card from connector J2 on the rear edge of
the MCA Main Controller circuit card.
5. Refer to Figure 10, and remove the two Phillips head screws and two hex spacers that secure the MCA Power Supply circuit card
to the MCA Main Controller circuit card. Remove the Power Supply circuit card, and set aside.
6. If an MCA Interface Option Assembly (modem, combination modem/RS-232, or RS-485) is present, remove as follows:
a. Refer to Figure 9, and remove the one Phillips head screw that secures the MCA Interface Option Assembly mounting
bracket.
b. Slide the MCA Interface Option Assembly toward the rear of the MCA assembly until connector and plug separate and the
mounting stud clears the keyhole slot in the mounting bracket.
c. For the Combination Modem/RS-232 Interface Assembly only: A ribbon cable extends from the assembly to a front panel-
mounted RS-232 connector. Disconnect this cable from the Interface Assembly.
d. Lift the MCA Interface Option Assembly away from the MCA assembly.
7. Locate the ribbon cable that extends from the MCA Main Controller circuit card to the MCA Keypad/Display circuit card.
Disconnect the cable plug from connector J1 on the Keypad/Display circuit card.
8. Remove the five screws and two hex spacers securing the MCA Main Controller circuit card to the MCA assembly. Remove the
circuit card.
9. Position the replacement MCA Main Controller circuit card over its mounting position, as shown in Figure 11. Secure by
installing and tightening the five screws and two hex spacers previously removed.
10. If an MCA Interface Option Assembly (modem, combination modem/RS-232, or RS-485) was installed, reinstall as follows:
a. Position the MCA Interface Option Assembly over the MCA assembly so that the mounting stud on the MCA assembly
passes through the keyhole in the MCA Interface Option Assembly mounting bracket.
b. Slide the MCA Interface Option Assembly toward the front of the MCA assembly until connector and plug mate. Ensure
that the mounting engages the keyhole slot in the mounting bracket.
c. Reinstall the one Phillips head screw that secures the MCA Interface Option Assembly mounting bracket.
d. For the Combination Modem/RS-232 Interface Assembly only: Reconnect the ribbon cable that extends from the front
panel-mounted RS-232 connector to its mating connector on the MCA Interface Option Assembly.
11. Position the MCA Power Supply circuit card over its mounting position, as shown in Figure 10. Secure by installing and
tightening the two Phillips head screws (front) and two hex spacers (rear) previously removed.
12. Connect the ribbon cable permanently connected to the MCA Power Supply circuit card to connector J2 on the rear edge of the
MCA Main Controller circuit card.
13. Reconnect the ribbon cable that extends from the MCA Main Controller circuit card to connector J1 on the MCA Keypad/Display
circuit card.
14. Reinstall the previously removed metal bracket and Rectifier Shelf Interface circuit card. To do so, place the bracket on its four
mounting posts so that the mounting screw heads pass through the slots in the bracket. Slide the bracket toward the front of
the MCA assembly. Tighten the four screws.
15. STOP. If no other circuit cards in the MCA assembly are being replaced, continue with the “Reinstalling the MCA Assembly
Following Service” procedure found later in this section.
Note: A No. 2 Phillips screwdriver having a minimum shaft length of 10 inches is required for this procedure. If such a screwdriver is
not available, you should remove the MCA Main Controller circuit card as describe under “MCA Main Controller Circuit Card
Assembly Replacement Procedure” before removing the MCA Keypad/Display circuit card.
1. Remove the MCA assembly to a static-safe work surface as describe in the “Removing the MCA Assembly for Service” procedure.
Warning: Damage to the MCA may result if the next step is not followed.
2. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
3. Locate the metal bracket that is under the Rectifier Shelf Interface circuit card. Loosen but do not remove the four Phillips
screws that secure the metal bracket. Remove the metal bracket with the Rectifier Shelf Interface circuit card by sliding toward
the rear of the MCA assembly until the screw heads clear the slots in the bracket. Lift the bracket and circuit card from the MCA
assembly, and set aside.
4. Remove the two (2) hex spacers that secure the FRONT of the MCA Main Controller circuit card.
5. Loosen but do not remove the three (3) Phillips screws that secure a metal shield over the Keypad/Display circuit card. Slide the
shield to the side until the screw heads clear the keyhole slots. Remove the metal shield.
6. Remove the five (5) screws securing the Keypad/Display circuit card. Carefully slide the Keypad/Display circuit card out of the
MCA assembly until the ribbon cable connection on the circuit card is accessible.
7. Locate the ribbon cable that extends from the MCA Main Controller circuit card to the MCA Keypad/Display circuit card.
Disconnect the cable plug from connector J1 on the Keypad/Display circuit card.
8. Connect the ribbon cable that extends from the MCA Main Controller circuit card to connector J1 on the replacement
Keypad/Display circuit card.
9. Position the replacement MCA Keypad/Display circuit card on the MCA assembly. Secure by installing the five (5) previously
removed Phillips head screws.
10. Reinstall the previously removed metal shield that covers the Keypad/Display circuit card. Secure by tightening the three Phillip
screws.
11. Reinstall the two (2) hex spacers that secure the front of the MCA Main Controller circuit card.
12. Reinstall the previously removed metal bracket and Rectifier Shelf Interface circuit card. To do so, place the bracket on its four
mounting posts so that the mounting screw heads pass through the slots in the bracket. Slide the bracket toward the front of
the MCA assembly. Tighten the four screws.
13. STOP. If no other circuit cards in the MCA assembly are being replaced, continue with the “Reinstalling the MCA Assembly
Following Service” procedure found later in this section.
Danger: Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
Warning: Damage to the MCA may result if the next step is not followed.
1. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
3. Install and tighten the two hex nuts and ground washers that secure the MCA assembly to the floor of the Distribution Cabinet.
4. Reconnect the following cables to the MCA Main Controller circuit card.
a. Reconnect the cable to connector J8.
b. Reconnect the ribbon cable extending from the “Interconnect/LVD Inhibit” circuit card to connector J9 on the MCA Main
Controller circuit card. Insert fully so that the ejector tabs at each end of the connector pivot inward fully.
c. If a Battery Ambient Temperature Probe or TXM is installed, reconnect the connector to J4.
5. Reconnect the following cables to the Rectifier Shelf Interface circuit card.
a. Reconnect the cable to the pigtail cable that is permanently connected to the circuit card.
b. Reconnect the cable from connector J2.
c. Reconnect the cable from connector J4.
6. Reconnect the following cables to the MCA Interface Option circuit card (if installed).
a. Various MCA Interface Options are available, reconnect any cable(s) removed from the circuit card.
7. DO NOT CONNECT THE POWER INPUT PLUG TO J15 AT THIS TIME. Continue with the next procedure to restart the system.
Note: The MCA is powered by the DC output (either by operating Rectifier Modules or from battery) on the power system busbars.
Reconnecting the input power plug to connector J15 will initiate the MCA startup sequence.
Note: During MCA startup, one of three scenarios may occur. Be prepared to view the MCA Display. Different user actions are
required depending on which scenario occurs.
Scenario One: On initial MCA startup, the display will briefly show the proper value for the MCA Configuration Spec. No. and
System Voltage for two seconds, then continue on.
Scenario Two: On initial MCA startup, the display will immediately pause at "MUST SET SPEC NO.".
Scenario Three: On initial MCA startup, the display will briefly show an MCA Configuration Spec. No. and System Voltage for
two seconds other than the proper value, then continue on.
Note: After power-up, you can also view the MCA Configuration Spec. No. Refer to Line Item "Spec. No." in the MCA INVENTORY
MENU. Another option if you miss the displayed MCA Configuration Spec. No., is to simply remove and reapply MCA input
power to restart the MCA initialization process.
1. Note the possible MCA Configuration Spec. Nos. for your power system in the following table.
Note: On MCA startup, be prepared to view the MCA Display. Different user actions are required depending on what is displayed.
2. Connect the power input plug to connector J15 on the MCA Main Controller circuit card. Observe and record the MCA
Configuration Spec. No. briefly displayed as the MCA starts.
3. Perform the "MCA INITIALIZATION AND BASIC SETTINGS" and "MCA ADVANCED SETTINGS" procedures detailed later in this
document.
In lieu of manually entering new MCA settings, if the old MCA configuration was downloaded via WinLink, upload the
configuration.
Final Steps
1. Reinstall the clear plastic cover in the bottom of the cabinet. To do so, place the cover on its two mounting posts so that the
mounting screw heads pass through the keyhole slots in the cover. Slide the cover towards the rear. Tighten the two screws.
3. Close the Distribution Cabinet's front door by turning and holding the captive fastener in the counterclockwise position.
4. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
5. Ensure that there are no local or remote alarms active on the system.
J4
J4
J8 J9
J2
Assembled View
Ribbon Cable
MCA
Main Controller
Circuit Card
Connector J2
Assembled View
Ribbon Cable
J1 on
Keypad/Display
Circuit Card
Ribbon Cable
MCA
Main Controller
Circuit Card
J1 on
Keypad/Display
Circuit Card
When power is applied to the MCA (by reconnecting the input power plug to connector J15), the MCA initializes. The MCA may…
• briefly display the proper value for the MCA Configuration Spec. No. and System Voltage for two seconds, then continue on.
• briefly display an MCA Configuration Spec. No. and System Voltage for two seconds other than the proper value, then continue
on.
Note: After power-up, you can also view the MCA Configuration Spec. No. Refer to Line Item "Spec. No." in the MCA INVENTORY
MENU. Another option if you miss the displayed MCA Configuration Spec. No., is to simply remove and reapply MCA input
power to restart the MCA initialization process.
Procedure 1
(The Proper MCA Configuration Spec. No.
and System Voltage was Briefly Displayed)
1. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
2. At the "ARE YOU SURE? +-" prompt, press the FUNCTION SET YES (+) pushbutton.
3. The MCA displays "INITIALIZING..." along with the maximum remaining initialization time in seconds while it is resetting the
variables, followed by "CHECK SETPOINTS".
4. As you press the FUNCTION SELECT UP and DOWN arrow pushbuttons, each value listed later in this procedure under "CHECK
SETPOINTS ADJUSTABLE VALUES" is displayed.
a. Change these settings to the values recorded in Table 6 at the beginning of this document.
b. To change the setting of the currently displayed entry, press and release the ALARM CUTOFF and FUNCTION SET ENTER
pushbuttons simultaneously.
c. The portion of the display before the equal sign (=) flashes.
d. Use the FUNCTION SET YES (+) or NO (-) pushbutton to increase or decrease, respectively, the setting.
e. Press the FUNCTION SET ENTER pushbutton.
f. At the "ARE YOU SURE? +-" prompt, press the FUNCTION SET YES (+) pushbutton to store the new value, or the FUNCTION
SET NO (-) pushbutton to cancel this operation without changing the setting.
g. Display the next or previous entry using the FUNCTION SELECT UP or DOWN arrow pushbutton.
h. Repeat this procedure for each entry presented.
5. When all the adjustable values have been properly set, press the FUNCTION SELECT DOWN arrow pushbutton until "START THE
SYSTEM" is displayed.
6. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
7. At the "ARE YOU SURE? +-" prompt, press the FUNCTION SET YES (+) pushbutton.
8. The MCA briefly displays " INITIALIZING..." along with the maximum remaining initialization time in seconds while it is starting
the system.
1. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
2. At the "ARE YOU SURE? +-" prompt, press the FUNCTION SET YES (+) pushbutton.
3. The MCA displays "INITIALIZING..." along with the maximum remaining initialization time in seconds while it reconfigures itself
for proper voltage operation, and then displays "CHECK SETPOINTS".
4. As you press the FUNCTION SELECT UP and DOWN arrow pushbuttons, each value listed later in this procedure under "CHECK
SETPOINTS Adjustable Values" is displayed.
a. Change these settings to the values recorded in Table 6 at the beginning of this document.
b. To change the setting of the currently displayed entry, press and release the ALARM CUTOFF and FUNCTION SET ENTER
pushbuttons simultaneously.
c. The portion of the display before the equal sign (=) flashes.
d. Use the FUNCTION SET YES (+) or NO (-) pushbutton to increase or decrease, respectively, the setting.
e. Press the FUNCTION SET ENTER pushbutton.
f. At the "ARE YOU SURE? +-" prompt, press the FUNCTION SET YES (+) pushbutton to store the new value, or the FUNCTION
SET NO (-) pushbutton to cancel this operation without changing the setting.
g. Display the next or previous entry using the FUNCTION SELECT UP or DOWN arrow pushbutton.
h. Repeat this procedure for each entry presented.
5. When all the adjustable values have been properly set, press the FUNCTION SELECT DOWN arrow pushbutton until "START THE
SYSTEM" is displayed.
6. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
7. At the "ARE YOU SURE? +-" prompt, press the FUNCTION SET YES (+) pushbutton.
8. The MCA briefly displays " INITIALIZING..." along with the maximum remaining initialization time in seconds while it is starting
the system.
"CHECK SETPOINTS" Displayed
Description: If some serial numbers match, MCA starts the system using the MCA's existing setpoints. The MCA displays "CHECK
SETPOINTS" during and after system startup.
1. Press the FUNCTION SELECT UP or DOWN pushbutton to move to the "System Adjustment Menu". Check all MCA settings per
Table 6.
"SYSTEM OK" or "## ALARMS ACTIVE" Displayed
Description: If all serial numbers match, the MCA starts the system using its existing setpoints. After the system is started, the MCA
displays "SYSTEM OK" or "## ALARMS ACTIVE".
1. Go to the "System Adjustment Menu", and check all MCA settings per Table 6.
Procedure 2
(MCA Displays "MUST SET SPEC NO.")
1. Press and release the FUNCTION SELECT UP and DOWN arrow pushbuttons until the proper MCA Configuration Spec. No. and
System Voltage are shown.
Note: Selecting an MCA Configuration Spec. No. or System Voltage different from your system's original will alter system
performance, and is not recommended. Refer to the System Application Guide (SAG) to determine the proper MCA
Configuration (Spec. No.) and system voltage.
2. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
3. At the "ARE YOU SURE? +-" prompt, press the FUNCTION SET YES (+) pushbutton.
4. The MCA displays “CHANGING SPEC” then "INITIALIZING..." along with the maximum remaining initialization time in seconds
while it reconfigures itself for proper operation, and then displays "CHECK SETPOINTS".
5. As you press the FUNCTION SELECT UP and DOWN arrow pushbuttons, each value listed later in this procedure under "CHECK
SETPOINTS ADJUSTABLE VALUES" is displayed.
a. Change these settings to the values recorded in Table 6 at the beginning of this document.
b. To change the setting of the currently displayed entry, press and release the ALARM CUTOFF and FUNCTION SET ENTER
pushbuttons simultaneously.
c. The portion of the display before the equal sign (=) flashes.
d. Use the FUNCTION SET YES (+) or NO (-) pushbutton to increase or decrease, respectively, the setting.
e. Press the FUNCTION SET ENTER pushbutton.
f. At the "ARE YOU SURE? +-" prompt, press the FUNCTION SET YES (+) pushbutton to store the new value, or the FUNCTION
SET NO (-) pushbutton to cancel this operation without changing the setting.
g. Display the next or previous entry using the FUNCTION SELECT UP or DOWN arrow pushbutton.
h. Repeat this procedure for each entry presented.
6. When all the adjustable values have been properly set, press the FUNCTION SELECT DOWN arrow pushbutton until "START THE
SYSTEM" is displayed.
7. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
8. At the "ARE YOU SURE? +-" prompt, press the FUNCTION SET YES (+) pushbutton.
9. The MCA briefly displays "INITIALIZING..." along with the maximum remaining initialization time in seconds while it is starting
the system.
Procedure 3
(An MCA Configuration Spec. No. and System Voltage
other than the Proper Value was Briefly Displayed)
1. Immediately depress and hold the ALARM CUTOFF, FUNCTION SELECT UP, and FUNCTION SELECT DOWN pushbuttons at the
same time while the display is showing the MCA "SPEC" number and then the "MCA SW ##.##.## " version number. Only after
the "MCA SW ##.##.##" version number goes off, release the three buttons.
Note: The pushbuttons must be depressed before "INITIALIZING ##" appears on the display. Remove and re-apply MCA input
power to restart this step, if necessary.
2. Press and release the FUNCTION SELECT UP and DOWN arrow pushbuttons until the proper MCA Configuration Spec. No. and
System Voltage are shown.
Note: Selecting an MCA Configuration Spec. No. or System Voltage different from your system's original will alter system
performance, and is not recommended. Refer to the System Application Guide (SAG) to determine the proper MCA
Configuration (Spec. No.) and system voltage.
3. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
4. At the "ARE YOU SURE? +-" prompt, press the FUNCTION SET YES (+) pushbutton.
5. The MCA displays “CHANGING SPEC” then "INITIALIZING..." along with the maximum remaining initialization time in seconds
while it reconfigures itself for proper operation, and then displays "CHECK SETPOINTS".
6. As you press the FUNCTION SELECT UP and DOWN arrow pushbuttons, each value listed later in this procedure under "CHECK
SETPOINTS ADJUSTABLE VALUES" is displayed.
a. Change these settings to the values recorded in Table 6 at the beginning of this document.
b. To change the setting of the currently displayed entry, press and release the ALARM CUTOFF and FUNCTION SET ENTER
pushbuttons simultaneously.
c. The portion of the display before the equal sign (=) flashes.
d. Use the FUNCTION SET YES (+) or NO (-) pushbutton to increase or decrease, respectively, the setting.
e. Press the FUNCTION SET ENTER pushbutton.
f. At the "ARE YOU SURE? +-" prompt, press the FUNCTION SET YES (+) pushbutton to store the new value, or the FUNCTION
SET NO (-) pushbutton to cancel this operation without changing the setting.
g. Display the next or previous entry using the FUNCTION SELECT UP or DOWN arrow pushbutton.
h. Repeat this procedure for each entry presented.
7. When all the adjustable values have been properly set, press the FUNCTION SELECT DOWN arrow pushbutton until "START THE
SYSTEM" is displayed.
8. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
9. At the "ARE YOU SURE? +-" prompt, press the FUNCTION SET YES (+) pushbutton.
10. The MCA briefly displays "INITIALIZING..." along with the maximum remaining initialization time in seconds while it is starting
the system.
1) FLOAT = ##.##V ##.##V = float voltage setting for all Rectifier Modules
2) TEST/EQ = ##.##V ##.##V = test equalize voltage setting for all Rectifier Modules
3) SET HVS = ##.##V ##.##V = high voltage shutdown setting for all Rectifier Modules
4) CURRLIM = #####A #####A = system current limit setting, current limit circuit on all Rectifier Modules are
automatically adjusted to ensure system current does not exceed this value
CURRLIM = #####MAX #####MAX = the sum of the maximum capabilities of all Rectifier Modules installed in the system
5) SYS HV1 = ##.##V ##.##V = system high voltage alarm 1 setting
6) SYS HV2 = ##.##V ##.##V = system high voltage alarm 2 setting
7) SYS BOD = ##.##V ##.##V = system battery on discharge alarm setting
8) SYS 50% (VERYLOVOLT) = ##.##V ##.##V = system 50% battery on discharge (very low voltage) alarm setting
9) SYSCURR = #####A ####A = system current alarm setting
10) SUB HV = ##.##V ##.##V = subsystem high voltage alarm setting
11) SUB LV = ##.##V ##.##V = subsystem low voltage alarm setting
12) SUBCURR = #####A ####A = subsystem current alarm setting
13) LVD ** = ##.#V LVD** = number assigned to the low voltage disconnect circuit detected, each low voltage
disconnect circuit detected in the system is displayed separately
##.#V = respective low voltage disconnect circuit "disconnect" setting
14) LV RECON = ##.#V ##.#V = reconnect setting for all low voltage
MANUAL RECONNECT disconnect circuits detected, or manual reconnect
15) TC CAL = ##.##V ##.##V = calibration voltage value written on
ANALOG TC OFF battery charge temperature
TempCmp Hardware compensation module, or off
16) DIGITAL TC OFF digital temperature compensation off, or
SLOPE = .###V/ºC slope parameter setting
TempCmp Hardware
17) MAX W/T = ##.##V ##.##V = maximum voltage with temperature compensation setting
18) MIN W/T = ##.##V ##.##V = minimum voltage with temperature compensation setting
19) HI TEMP 1 = ###ºC ###ºC = high temperature 1 alarm setting, or
HI TEMP 1 IS OFF high temperature 1 alarm off
20) LO TEMP 1 = ###ºC ###ºC = low temperature 1 alarm setting, or
LO TEMP 1 IS OFF low temperature 1 alarm off
21) ****A PLACES = ## ****A = amperage of each type of Rectifier Module, each type of Rectifier Module is displayed
separately
## = number of total (filled and empty) shelf positions available for this amperage Rectifier Module
22) START THE SYSTEM Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. At
the "ARE YOU SURE? + -" prompt, press the FUNCTION SET YES (+) pushbutton to start system.
Press the FUNCTION SET NO (-) pushbutton to go back and change more setpoints before starting
the system. Use the FUNCTION SELECT UP and DOWN arrow pushbuttons to scroll through the list
of adjustable values as previously described.
Advanced Settings
Procedure
1. With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET ENTER pushbutton.
2. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE MENU" is displayed.
4. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "DISPLAY ROLL OFF" or "DISPLAY ROLL ON" is
displayed. This is the current setting for this feature. To toggle this setting, perform steps 5) and 6). To keep this setting,
proceed with step 7).
5. To toggle this setting, press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
6. "ARE YOU SURE? + -" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
7. Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "LO SPEED FAN OFF" or "LO SPEED FAN ON"
is displayed. This is the current setting for this feature. To toggle this setting, perform steps 8) and 9). To keep this setting,
proceed with step 10).
8. To toggle this setting, press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
9. "ARE YOU SURE? + -" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
10. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "NAG MINUTES = ##" or "AUDIBLE NAG OFF".
11. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "NAG MINUTES =" portion of
the display flashes.
12. Press the FUNCTION SET YES (+) or NO (-) pushbutton until the value displayed equals the desired audible alarm cutoff reset
time period or "AUDIBLE NAG OFF", then release the pushbutton.
14. "ARE YOU SURE? + -" is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
15. Press and release the FUNCTION SET DOWN arrow pushbutton to display "TEST/EQ HRS = ##".
16. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "TEST/EQ HRS =" portion of
the display flashes.
17. Press the FUNCTION SET YES (+) or NO (-) pushbutton until the value displayed equals the desired timed test/equalize period.
Note: To disable the manually initiated timed test/equalize feature, press the FUNCTION SET YES (+) pushbutton until the
value goes above 99. "TEST/EQ MAN STOP" is then displayed.
19. "ARE YOU SURE? + -" is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
20. Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "AUTO EQ MUL = ##" or "AUTO EQ DISABLED".
21. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "AUTO EQ MUL =" portion of
the display flashes.
22. Press the FUNCTION SET YES (+) or NO (-) pushbutton until the desired value is displayed, then release the pushbutton. Note
that as you scroll below 1, "AUTO EQ DISABLED" is displayed. Scroll back up to redisplay "AUTO EQ MUL =".
24. "ARE YOU SURE? + -" is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
25. Press and release the FUNCTION SET DOWN arrow pushbutton to display "RELAYTEST = ###SEC".
26. Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The "RELAYTEST =" portion of the
display flashes.
27. Press the FUNCTION SET YES (+) or NO (-) pushbutton until the value displayed equals the desired timed period for the Alarm
Relay Test feature.
29. "ARE YOU SURE? + -" is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The display stops flashing.
30. Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the beginning of the MCA
menu tree.
A Rectifier Shelf Interface circuit card is installed in each bay. To replace the circuit card perform the following procedure.
Procedure
1. Observe the admonishments presented at the beginning of this section, and those encountered in this procedure.
2. Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these
alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system.
3. Open the Distribution Cabinet's front door by turning and holding the captive fastener in the counterclockwise position.
Danger: Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
4. Remove the clear plastic panel that covers the circuit cards at the bottom of the cabinet. To do so, loosen but do not remove
the two screws that secure the cover. Slide the cover to the front until the screw heads clear the keyhole slots in the cover.
Then lift the cover out of the cabinet.
Warning: Damage to the MCA may result if the next step is not followed.
5. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
6. Remove the following cables from the Rectifier Shelf Interface circuit card.
a. Separate the cable connected to the pigtail cable permanently connected to the circuit card.
b. Disconnect the cable from connector J2.
c. Disconnect the cable from connector J4.
7. Refer to Figure 13 or Figure 14 and locate the Rectifier Shelf Interface circuit card. Remove the four screws securing the circuit
card. Remove the circuit card.
8. Set switches S1 and S2 on the replacement circuit card to the same settings as the circuit card just removed.
9. Position the replacement circuit card over its mounting position, and secure with the screws previously removed.
10. Reconnect the following cables to the Rectifier Shelf Interface circuit card.
a. Reconnect the cable to the pigtail cable that is permanently connected to the circuit card.
b. Reconnect the cable from connector J2.
c. Reconnect the cable from connector J4.
11. Reinstall the clear plastic cover in the bottom of the cabinet. To do so, place the cover on its two mounting posts so that the
mounting screw heads pass through the keyhole slots in the cover. Slide the cover towards the rear. Tighten the two screws.
13. Close the Distribution Cabinet's front door by turning and holding the captive fastener in the counterclockwise position.
14. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
15. Ensure that there are no local or remote alarms active on the system.
Figure 13. Replacing the Rectifier Shelf Interface Circuit Card in the Main Bay Panel
Rectifier Shelf
Interface
Circuit Card
Figure 14. Replacing the Rectifier Shelf Interface Circuit Card in the Supplemental Bay Panel
Rectifier Shelf
Interface
Circuit Card
Procedure
1. Observe the admonishments presented at the beginning of this section, and those encountered in this procedure.
2. Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these
alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system.
3. Open the Distribution Cabinet's front door by turning and holding the captive fastener in the counterclockwise position.
4. Remove the clear plastic panel that covers the circuit cards at the bottom of the cabinet. To do so, loosen but do not remove
the two screws that secure the cover. Slide the cover to the front until the screw heads clear the keyhole slots in the cover.
Then lift the cover out of the cabinet.
Warning: Performing the next step inhibits the operation of the low voltage disconnect circuit, and prevents
disconnection of battery and system output from the controlled load(s) if a low battery voltage condition
occurs.
5. Place the low voltage disconnect NOR/INH switch to the INH position. This switch is located on Interconnect/LVD Inhibit Circuit
Card A1. Refer to Figure 15 for circuit card and switch location. The low voltage disconnect INHIBIT indicator will illuminate.
This step prevents accidental disconnection of battery and system output from the controlled load(s) while performing this
procedure.
6. Remove fuses D (F4) and E (F5) from the fuseholders located on Interconnect/LVD Inhibit Circuit Card A1. Refer to Figure 20 for
circuit card and fuse location.
Warning: Damage to the circuit card may result if the next step is not followed.
7. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
Danger: Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
8. Remove the two screws that secure the front edge of the circuit card. Pull the circuit card forward out of the edge connector at
the back of the card, and remove from the cabinet.
9. Set "Low Voltage Disconnect Circuit Card Identification Switches" S1-S4 on the replacement circuit card to match the setting on
the existing circuit card. You can refer to "Setting Wiring Options" in the separate INSTALLATION INSTRUCTIONS (SECTION
5974) for details.
10. Insert the replacement circuit card into the edge connector previously vacated. Fully seat the card in the connector so that the
mounting holes at the front of the card line up with the mounting posts beneath. Install and tighten the two mounting screws
at the front edge of the card.
13. Check the MCA for the presence of low voltage disconnect alarms. If alarms are active, use the MCA to reconnect the low
voltage disconnect circuits. DO NOT perform the next step until you verify that there are NO Low Voltage Disconnect alarms
active.
Caution: If the next step is performed when low voltage disconnect alarms are active, battery and system output will
disconnect from the controlled load(s).
14. Return the low voltage disconnect NOR/INH switch to the NOR position. The low voltage disconnect INHIBIT indicator
extinguishes.
15. Reinstall the clear plastic cover in the bottom of the cabinet. To do so, place the cover on its two mounting posts so that the
mounting screw heads pass through the keyhole slots in the cover. Slide the cover towards the rear. Tighten the two screws.
16. Close the Distribution Cabinet's front door. The door can be shut without turning the captive fastener.
17. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
18. Ensure that there are no local or remote alarms active on the system.
NOR-INH INH
REMOVE SWITCH INDICATOR
SCREWS
INTERCONNECT/LVD
INHIBIT CIRCUIT CARD A1
One Quad Shunt POD Circuit Card, designated A3, (system distribution current monitoring) is located in each Distribution Cabinet. If the
Power System includes a subsystem, a second Shunt A/D circuit card, designated A4, (subsystem distribution current monitoring) will
also be mounted in the main Distribution Cabinet. To replace either circuit card perform the following procedure.
Refer to Figure 16 as this procedure is performed.
Caution: When performing any step in this procedure that requires removal or installation of hardware, use caution to
ensure no hardware is dropped and left inside the cabinet; otherwise service interruption or equipment
damage may occur.
Warning: Circuit cards used in this equipment contain static-sensitive devices. Read the Static Warning page at the
front of this document before performing the following procedure.
Note: When performing any step in this procedure that requires removal of existing hardware, retain all hardware for use in
subsequent steps.
Procedure
1. Observe the admonishments presented at the beginning of this section, and those encountered in this procedure.
2. Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these
alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system.
3. Open the Distribution Cabinet's front door by turning and holding the captive fastener in the counterclockwise position.
Warning: Damage to the circuit card may result if the next step is not followed.
4. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
Danger: Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
5. Remove the clear plastic panel that covers the circuit cards at the bottom of the cabinet. To do so, loosen but do not remove
the two screws that secure the cover. Slide the cover to the front until the screw heads clear the keyhole slots in the cover. Then
lift the cover out of the cabinet.
6. If you are replacing a System Distribution Quad Shunt POD circuit card and the optional System Load Shunt Test Point Kit is
installed, remove the ribbon cable from the J2 connector on the Quad Shunt Pod circuit card.
7. Remove the two screws that secure the front edge of the circuit card. Pull the circuit card forward out of the edge connector at
the back of the card, and remove from the cabinet.
9. Insert the replacement circuit card into the edge connector previously vacated. Fully seat the card in the connector so that the
mounting holes at the front of the card line up with the mounting posts beneath. Install and tighten the two mounting screws
at the front edge of the card.
10. If you are replacing a System Distribution Quad Shunt POD circuit card and the optional System Load Shunt Test Point Kit is
installed, replace the ribbon cable to the J2 connector on the Quad Shunt Pod circuit card.
Note: Before performing the next step, ensure that both Quad Shunt POD Circuit Card mounting positions are occupied; either
by a Quad Shunt POD Circuit Card or by a Bypass Circuit Card.
12. Reinstall the clear plastic cover in the bottom of the cabinet. To do so, place the cover on its two mounting posts so that the
mounting screw heads pass through the keyhole slots in the cover. Slide the cover towards the rear. Tighten the two screws.
13. Close the Distribution Cabinet front door. The door can be shut without turning the captive fastener.
14. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
15. Ensure that there are no local or remote alarms active on the system.
Figure 16. System Quad Shunt POD Circuit Card Replacement (Subsystem Circuit Card Replacement Similar)
To Optional
SYSTEM System Load
BYPASS QUAD SHUNT Shunt Test
VIEW WITH DOOR OPEN, LOOKING
DOWN AT BOTTOM OF CABINET CIRCUIT CARD, POD CIRCUIT Point Kit,
P/N 117086 CARD, P/N 507431 if furnished.
J2
REMOVE
SCREWS
Note: Applies only if power system is equipped with List 71. Applies only to Main Bay.
Note: When performing any step in this procedure that requires removal of existing hardware, retain all hardware for use in
subsequent steps.
Procedure
1. Observe the admonishments presented at the beginning of this section, and those encountered in this procedure.
2. Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these
alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system.
3. Open the Distribution Cabinet's front door by turning and holding the captive fastener in the counterclockwise position.
Danger: Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
4. Remove the clear plastic panel that covers the circuit cards at the bottom of the cabinet. To do so, loosen but do not remove
the two screws that secure the cover. Slide the cover to the front until the screw heads clear the keyhole slots in the cover. Then
lift the cover out of the cabinet.
5. Carefully identify the wires connected to external alarm connectors J1 through J4. These wires must be connected to the same
terminals on the replacement circuit card.
Danger: In the next step, external alarm wiring may be energized from an external source. DO NOT allow bare wire
ends to contact any grounded or energized object.
6. READ THIS ENTIRE STEP AND UNDERSTAND BEFORE PROCEEDING. Remove external alarm wiring from connectors J1 through
J4. To do so, for each wire, insert a small flat-blade screwdriver into the square cavity directly behind the wire. Depress the
screwdriver until the wire is released and can be pulled out of the terminal block. DO NOT allow bare wire end to contact any
grounded or energized object. Isolate the wire end with electrical tape. Repeat for each wire.
8. Disconnect the ribbon cable plug from connector J8. To do so, grasp the ejector tabs at each end of the connector and pivot
outward, forcing the plug out of the connector.
Warning: Damage to the circuit card may result if the next step is not followed.
9. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
Danger: Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
10. Remove the two screws that secure the front edge of the circuit card. Pull the circuit card forward out of the edge connector at
the back of the card, and remove from the cabinet.
11. Set the J10 and J11 (local audible alarm enable/disable) wiring options on the replacement circuit card to match the settings on
the existing circuit card. You can refer to "Setting Wiring Options" in the separate INSTALLATION INSTRUCTIONS (SECTION
5974) for details.
12. Insert the replacement circuit card into the edge connector previously vacated. Fully seat the card in the connector so that the
mounting holes at the front of the card line up with the mounting posts beneath. Install and tighten the two mounting screws
at the front edge of the card.
14. Reconnect the ribbon cable plug to connector J8. Insert fully so that the ejector tabs at each end of the connector pivot inward
fully.
16. READ THIS ENTIRE STEP AND UNDERSTAND BEFORE PROCEEDING. Reconnect the external alarm wiring, removed in step 6, to
the correct terminals of connectors J1 through J4 as recorded in step 5. To do so, for each wire, remove the electrical tape that
was applied to the wire end in a previous step. DO NOT allow bare wire end to contact any grounded or energized object. Fully
insert the bare wire end into the rectangular opening in the terminal block. Gently tug on the wire to ensure that it cannot be
pulled out of the terminal block. Repeat for each wire.
17. Reinstall the clear plastic cover in the bottom of the cabinet. To do so, place the cover on its two mounting posts so that the
mounting screw heads pass through the keyhole slots in the cover. Slide the cover towards the rear. Tighten the two screws.
18. Close the Distribution Cabinet's front door. The door can be shut without turning the captive fastener.
19. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
20. Ensure that there are no local or remote alarms active on the system.
ALARM TERMINATION/
AUDIBLE ALARM
CIRCUIT CARD,
P/N 509539 VIEW WITH DOOR OPEN, LOOKING
DOWN AT BOTTOM OF CABINET
J4 J5 J3
J8
J1 J2
DISCONNECT
WIRING REMOVE DISCONNECT CABLE
REMOVE
FROM CONNECTOR J8
SCREWS SCREWS
Procedure
1. Observe the admonishments presented at the beginning of this section, and those encountered in this procedure.
2. Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these
alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system.
3. Open the Distribution Cabinet's front door by turning and holding the captive fastener in the counterclockwise position.
Danger: Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
4. Remove the clear plastic panel that covers the circuit cards at the bottom of the cabinet. To do so, loosen but do not remove
the two screws that secure the cover. Slide the cover to the front until the screw heads clear the keyhole slots in the cover. Then
lift the cover out of the cabinet.
5. Carefully identify the wires connected to external control terminal block TB1. These wires must be connected to the same
terminals on the replacement circuit card.
Danger: In the next step, control wiring may be energized from an external source. DO NOT allow bare wire ends to
contact any grounded or energized object.
6. READ THIS ENTIRE STEP AND UNDERSTAND BEFORE PROCEEDING. Remove control wiring from terminal block TB1. To do so,
for each wire, insert a small flat-blade screwdriver into the square cavity directly behind the wire. Depress the screwdriver until
the wire is released and can be pulled out of the terminal block. DO NOT allow bare wire end to contact any grounded or
energized object. Isolate the wire end with electrical tape. Repeat for each wire.
7. Carefully identify the cables connected to connectors J1, J2, J8, J9 and J10. These cables must be connected to the same
connectors on the replacement circuit card.
8. Disconnect the cables from connectors J1, J2, J8, J9 and J10.
9. Disconnect the ribbon cable plug from connector J13. To do so, grasp the ejector tabs at each end of the connector and pivot
outward, forcing the plug out of the connector.
Warning: Damage to the circuit card may result if the next step is not followed.
10. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
Danger: Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
11. Remove the four screws that secure the circuit card. Pull the circuit card forward out of the edge connector at the back of the
card, and remove from the cabinet.
12. Set the following wiring options on the replacement circuit card to match the settings on the existing circuit card:
• J5 – LVD Jumper
You can refer to "Setting Wiring Options" in the separate INSTALLATION INSTRUCTIONS (SECTION 5974) for details.
13. Insert the replacement circuit card into the edge connector previously vacated. Fully seat the card in the connector so that the
mounting holes at the front of the card line up with the mounting posts beneath. Install and tighten the two mounting screws
at the front edge of the card.
14. Reconnect the cables removed in step 8 to the appropriate connectors J1, J2, J8, J9 and J10 as recorded in step 7.
15. Reconnect the ribbon cable plug to connector J13. Insert fully so that the ejector tabs at each end of the connector pivot inward
fully.
17. READ THIS ENTIRE STEP AND UNDERSTAND BEFORE PROCEEDING. Reconnect the control wiring, removed in step 6, to the
appropriate terminals of TB1as recorded in step 5. To do so, for each wire, remove the electrical tape that was applied to the
wire end in a previous step. DO NOT allow bare wire end to contact any grounded or energized object. Fully insert the bare wire
end into the rectangular opening in the terminal block. Gently tug on the wire to ensure that it cannot be pulled out of the
terminal block. Repeat for each wire.
18. Reinstall the clear plastic cover in the bottom of the cabinet. To do so, place the cover on its two mounting posts so that the
mounting screw heads pass through the keyhole slots in the cover. Slide the cover towards the rear. Tighten the two screws.
19. Close the Distribution Cabinet's front door. The door can be shut without turning the captive fastener.
20. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
21. Ensure that there are no local or remote alarms active on the system.
J8 J9 J10
J12 J7
J4
J5 J6
J1 J2
TB1
DISCONNECT
WIRING
DISCONNECT CABLE
FROM J12
REMOVE
SCREWS
One Shunt POD Circuit Card (battery current monitoring) is located within the List RD and RE assembly, which is located on the rear of the
Distribution Cabinet. To replace this circuit card perform the following procedure.
Note: When performing any step in this procedure that requires removal of existing hardware, retain all hardware for use in
subsequent steps.
Procedure
1. Observe the admonishments presented at the beginning of this section, and those encountered in this procedure.
2. Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these
alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system.
4. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
Danger: Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
7. Set "Shunt Capacity Selection” and “Shunt POD Identification” Switches S1 and S2 on the replacement circuit card to match the
setting on the existing circuit card. You can refer to "Setting Wiring Options" in the separate INSTALLATION INSTRUCTIONS
(SECTION 5974) for details.
8. Place the circuit card over its mounting posts and carefully press down at each post until fully seated. Install and tighten the one
mounting screw.
11. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
12. Ensure that there are no local or remote alarms active on the system.
Connector J1
3 4
2
1
If an alarm, reference, or control fuse opens; replace with the same type and rating, or equivalent. Refer to SAG582126000 for fuse
replacement part numbers. Refer to Figure 20 and Figure 21 for the location of these fuses. Refer also to the following replacement
procedures.
Fuses are located on the Part No. 509532 Interconnect/LVD Inhibit circuit card as shown in Figure 20. This circuit card is located in the
Main Bay Distribution Cabinet.
Note: A Part No. 509532 circuit card is located in each Distribution Cabinet. Fuses have a function only on the circuit card located in
the main Distribution Cabinet.
Figure 20. Location of Replaceable Fuses on Interconnect/LVD Inhibit Circuit Card Part No. 509532
1 2 3 4 5 6 7 8 9
5A
1-1/3A
NOR INH
INTERCONNECT/LVD
INHIBIT CIRCUIT SELECT INHIBIT BEFORE REPLACING LVD CONTROL
CARD, P/N 509532 CARD. SWITCH INHIBITS THIS BAY ONLY.
In addition to distribution fuses, an input fuse and associated alarm fuse are located on each optional Part No. 509128 GMT-type
distribution fuse circuit card as shown in Figure 21. See SAG582126000 for fuse part numbers. An open alarm fuse F11 indicates that
input fuse F12 is open. Replace F12 before replacing F11. Recommended torque for input fuse fastening screws is 10 inch pounds.
Danger: Hazardous energy is present at input fuse terminals. Use caution not to short either terminal to ground.
Figure 21. Location of Replaceable Fuses on Optional GMT-Type Distribution Fuse Circuit Card Part No. 509128
GMT DISTRIBUTION
FUSE CIRCUIT CARD
ASSEMBLY, P/N 509128
(TYPICAL LOCATION)
1A 10A
F11
F12
Note: If a TPH-type fuse opens, the associated alarm fuse opens. Replace the TPH-type fuse before replacing the alarm fuse. Likewise,
if a TPS/TLS-type fuse opens, the associated alarm fuse opens. Replace the TPS/TLS-type fuse before replacing the alarm fuse.
1. An alarm, reference, or control fuse can be removed by pulling it straight out of the fuseholder.
2. Safety fuse covers are provided for all Bussmann GMT type fuses installed in the system. These covers snap onto the fuses and
provide protection from exposed electrical terminations when a fuse opens. Insure that the safety fuse cover is installed after
replacing a fuse. Refer to Figure 22 for installation details.
BUSSMANN BUSSMANN
GMT GMT
Each Rectifier Module contains an input and output fuse. These fuses are not customer replaceable. If a fuse opens, replace the entire
Rectifier Module. An open fuse causes the unit’s Rectifier Module FAIL alarm circuit to activate. The input fuse has a higher amperage
rating than the recommended external branch circuit protection.
A defective TPS/TLS-type fuse is replaced by removing the fuse carrier from the bullet nose-type fuseholder, and replacing the defective
fuse.
If required, pre-charge any load capacitors before installing a replacement fuse. If the List 79 Pre-charge Assembly is provided, use the
furnished clip cord lead to connect to the fuseholder terminals. Then refer to the Pre-Charge Assembly instructions (Section 5823). This
document is provided in the document set furnished with your system.
Procedure
1. Open the Distribution Cabinet's front door by turning and holding the captive fastener in the counterclockwise position.
2. Remove the fuse carrier from the mounted fuseholder body by pulling it straight out.
3. Replace the open fuse with the same type and rating, or equivalent.
4. Replace the alarm fuse located in the front of the fuse carrier. Replace only with a fuse of the same type and rating. Ensure that
a plastic safety cover is installed on the alarm fuse.
5. When done, push the fuse carrier back into the fuseholder body. Note that a polarizing key on the bottom of the carrier
prevents the carrier from being inserted upside down.
7. Close the cabinet's front door. The door can be shut without turning the captive fastener.
Figure 23. Replacement Details for TPS/TLS-Type Fuse in a Bullet Nose Type Fuseholder
Insert These Terminals
in Corresponding Sockets
in Distribution Assembly.
Distribution Fuse
Fuse Carrier
Safety
Cover
Polarizing Keyway
Matches Key on
Bottom of Fuse Carrier Fuseholder Body
Alarm Fuse
Procedure
1. Open the Distribution Cabinet's front door by turning and holding the captive fastener in the counterclockwise position.
2. Remove the fuse carrier from the mounted fuseholder body by pulling it straight out.
3. Gently rock the defective fuse holder up and down while pulling firmly outward until the fuse holder is free from the distribution
assembly.
Warning: If the following procedure is not followed, the fuseholder may be damaged.
4. Orient the fuseholder so the LOAD designation found on the fuseholder side is at the top, and the LINE designation is at the
bottom. Insert the terminals on the rear of the fuseholder into their corresponding sockets on the distribution assembly. Push
fuseholder in firmly until fully seated.
5. Push the fuse carrier back into the fuseholder body. Note that a polarizing key on the bottom of the carrier prevents the carrier
from being inserted upside down.
7. Close the Distribution Cabinet's front door. The door can be shut without turning the captive fasteners.
Defective TPH-type fuses are replaced by opening the fuseholder and replacing the defective fuse.
Replace also the alarm fuse associated to this fuse as previously explained.
When required, use the List 79 capacitor Pre-charge Assembly to initially charge DC load capacitors prior to installing a distribution fuse.
A clip cord is provided for connecting to the circuit breaker or fuseholder terminals. For operating information, refer to the Pre-Charge
Assembly instructions (Section 5823). These instructions are provided in the document set furnished with your system.
Procedure
1. Remove the fuse carrier from the fuseholder body by grasping its handle and pulling straight out.
3. Replace the open fuse with the same type and rating, or equivalent. Install the fuse into the fuse carrier. When done, push the
fuse carrier securely back into the fuseholder body.
4. On the distribution row, locate the open alarm fuse associated with the TPH-type fuse being replaced. Replace the alarm fuse
with a Bussmann GMT 1/4 ampere alarm fuse. Emerson Network Power Part No. 248610200.
5. Safety fuse covers are provided for all Bussmann GMT type fuses. These covers snap onto the fuses and provide protection from
exposed live contacts when a fuse opens. Re-install the safety fuse cover after replacing any GMT type fuse. Refer to Figure 22
for safety fuse cover installation details.
Figure 24. Replacing a TPH-Type Fuse
Fuse
Fuseholder Body
Fuse Carrier
Note: Applies only if power system is equipped with Bullet Nose type circuit breakers.
Procedure
1. Open the Distribution Cabinet's front door by turning and holding the captive fastener in the counterclockwise position.
3. Gently rock the defective circuit breaker up and down while pulling outward until the breaker is free.
4. Ensure that the circuit breaker is in the OFF position, and is of the correct rating.
Caution: In the next step, the circuit breaker alarm will operate incorrectly if the circuit breaker is installed upside
down.
5. Orient the circuit breaker so the OFF and ON labeling on the handle is right side up. Insert the terminals on the rear of the circuit
breaker into their corresponding sockets on the distribution assembly. Push circuit breaker in firmly until fully seated in the
distribution assembly.
8. Close the front door of the Distribution Cabinet. The door can be shut without turning the captive fastener.
Lettering on Handle
Must Be Right Side Up.
Turn Off Before Installing.
When performing the following procedure, refer to the appropriate detail of Figure 26 for your distribution bus assembly as shown in
Table 8.
Table 8.
1. For 2-, 3-, and 4-row Distribution Cabinets Only: Remove the access cover(s) from the rear of the Distribution Cabinet, if
present.
2. For Lists EA, GB, NA, NB, ND Only: Disconnect link busbar from system busbar (1 bolt for List EA—2 bolts each for Lists GB, NA,
NB, ND).
3. For 2-, 3-, and 4-row Distribution Cabinets Only: Disconnect the 9-pin alarm and control harness connector from the mating
plug on the main system wire harness (two connectors on Lists AD, AE, CE, and CF).
From Front:
1. Open the Distribution Cabinet's front door by turning and holding the captive fastener in the counterclockwise position.
2. For all lists equipped with a plastic shield over the circuit breakers or fuseholders (all bullet nose assemblies), loosen (2) screws
holding the shield, slide shield upwards and remove.
3. Disconnect all load wiring from the circuit breaker or fuse positions. If necessary, refer to the separate INSTALLATION
INSTRUCTIONS (SECTION 5974) for connection locations.
4. On assemblies equipped with a ground busbar, remove all load return wiring from the ground busbar. If necessary, refer to the
separate INSTALLATION INSTRUCTIONS (SECTION 5974) for connection locations.
5. For Lists JA, JB, JC, JD, KA, LB, and LC Only: Disconnect Subsystem Input wiring (+ and –) from distribution bus assembly as
shown at SUBSYSTEM INPUT JUMPERS in the appropriate detail of Figure 26.
6. For All Bullet Nose Assemblies: Remove circuit breakers and fuseholders from distribution bus assembly.
7. For Each GJ/218 Circuit Breaker Present: Remove circuit breaker far enough to reach alarm and control wiring on back. Note
the connection order of alarm and control wires so they can be reconnected correctly later in the procedure. Disconnect alarm
wires and, if present, shunt wires, from back of circuit breakers. Then remove circuit breaker.
8. For List AJ or CJ Only: Follow shunt leads from the rear of the distribution assembly to their point of termination. Note the order
in which leads are connected. Disconnect the leads at that end. Leads will be removed with the Distribution Buss Assembly.
9. For Each TPH Fuse Present: If not replacing the fuse, remove fuse carrier from the fuseholder. Remove the fuse from the fuse
carrier.
10. Disconnect the distribution assembly input busbar from the system busbar (two busbars on Lists AD, AE, CE, and CF) as shown
at SYSTEM BUSBAR CONNECTION in the appropriate detail of Figure 26. For List ND only, remove the link busbar from the
cabinet.
11. On assemblies equipped with a ground busbar, disconnect the distribution assembly ground busbar from the system ground
busbar (two busbars on Lists AD, AE, AL, CE, and CF) as shown at GROUND BUSBAR CONNECTION in the appropriate detail of
Figure 26.
12. For 1-Row Cabinets Only: Remove 4 screws that secure distribution assembly to cabinet. Carefully pull distribution assembly
from cabinet until the 9-pin alarm and control harness connector and mating plug on the main system wire harness are
accessible. Disconnect the connector from the plug. Remove distribution assembly from the cabinet.
13. For 2-, 3-, and 4-row Distribution Cabinets Only: Remove 4 screws that secure distribution assembly to cabinet. Remove
distribution assembly.
Note: In the following procedure, before making busbar-to-busbar connections, apply a thin coating of electrical anti-oxidizing
compound to the mating surfaces of the busbars.
From Front:
1. For 1-Row Cabinets Only: Install assembly into cabinet until the 9-pin alarm and control harness connector and mating plug on
the main system wire harness can be connected. Connect the mating plug and connector. Position the distribution assembly,
and secure to the Distribution Cabinet with 4 screws. Check to ensure no wires are pinched.
2. For 2-, 3-, and 4-row Distribution Cabinets Only: Install assembly into cabinet and secure with 4 screws. Check to ensure no
wires are pinched.
3. For All Except List ND: Connect distribution assembly input busbar to system busbar (two busbars on Lists AD, AE, CE, and CF)
as shown at SYSTEM BUSBAR CONNECTION in the appropriate detail of Figure 26.
4. For List ND Only: Install the linking busbar previously removed, and connect to system busbar as shown at SYSTEM BUSBAR
CONNECTION in the appropriate detail of Figure 26.
5. On assemblies equipped with a ground busbar, connect distribution assembly ground busbar to system ground busbar (two
busbars on Lists AD, AE, AL, CE, and CF) as shown at GROUND BUSBAR CONNECTION in the appropriate detail of Figure 26.
Warning: In the next step, observe correct polarity; otherwise equipment damage will result.
6. For Lists JA, JB, JC, JD, KA, LB, and LC Only: Reconnect Subsystem Input wiring (+ and –) to distribution bus assembly as shown at
SUBSYSTEM INPUT JUMPERS in the appropriate detail of Figure 26.
7. On assemblies equipped with a ground busbar, reconnect all load return wiring to the ground busbar. Refer to the separate
INSTALLATION INSTRUCTIONS (SECTION 5974) for recommended torque.
8. Reconnect all load wiring to the circuit breaker or fuse positions. Refer to the separate INSTALLATION INSTRUCTIONS (SECTION
5974) for recommended torque.
9. For All Bullet Nose Assemblies: Install circuit breakers and fuseholders into distribution bus assembly.
10. For all lists equipped with a shield over the circuit breakers or fuseholders (all bullet nose assemblies), position the shield and
slide downwards on screws. Tighten screws.
11. For All GJ/218 Circuit Breakers: Connect alarm wires and, if present, shunt wires, to back of circuit breaker. Then mount circuit
breaker to its busbars. Recommended torque is 84 inch pounds.
12. For List AJ or CJ Only: Route shunt lead from the rear of the Distribution Bus Assembly to the intended point of termination.
Connect shunt leads in the order previously noted. Form leads for best fit, and secure with plastic cable ties as required.
13. For All TPH Fuses Only: Install the fuse. See Replacing a TPH-Type Fuse in this section.
1. For 2-, 3-, and 4-row Distribution Cabinets Only: Connect the 9-pin alarm and control connector to the mating plug on the main
system wire harness (two connectors on Lists AD, AE, CE, and CF).
2. For Lists EA, GB, NA, NB, ND Only: Connect link busbar to the distribution assembly busbar (1 bolt for List EA—2 bolts each for
Lists GB, NA, NB, ND). Torque bolts to 180 in lbs.
3. For 2-, 3-, and 4-row Distribution Cabinets Only: If access cover(s) were removed from the rear of the Distribution Cabinet,
install covers.
2. Start the Power System. Refer to "Installing Rectifier Modules and Initially Starting the System" in the separate INSTALLATION
INSTRUCTIONS (SECTION 5974) for a startup procedure.
4. Close the Distribution Cabinet's front door. The door can be shut without turning the captive fasteners.
Figure 26. (Detail A) Replacing List JA (Lists AA, AM, JB, JC, JD, KA Similar)
GROUND SYSTEM
BUSBAR CONNECTION BUSBAR CONNECTION
Remove / Install Remove / Install
1/4-20 X 7/8" Bolt 1/4-20 X 7/8" Bolt
1/4" Belleville Washer 1/4" Belleville Washer
1/4" Flat Washer 1/4" Flat Washer
(4) Places. (4) Places.
Torque to 60 In. Lbs. Torque to 60 In. Lbs.
FRONT
VIEW
- JUMPERS + JUMPERS
Remove / Install Remove / Install
Remove / Install Remove / Install
10-32 X 5/8" Screw 10-32 X 5/8" Screw
1/4-20 Hex Nut 1/4-20 x 5/8" Bolt
No. 10 Flat Washer No. 10 Flat Washer
1/4" Lock Washer 1/4" Lock Washer
(2) Places. (2) Places
1/4" Flat Washer 1/4" Flat Washer
(2) Places Per Jumper (2) Places Per Jumper
Torque to 84 In. Lbs. Torque to 84 In. Lbs.
SYSTEM
GROUND BUSBAR CONNECTION
BUSBAR CONNECTION Remove / Install
Remove / Install 1/4-20 X 7/8" Bolt
1/4-20 X 7/8" Bolt 1/4" Belleville Washer
1/4" Belleville Washer 1/4" Flat Washer
1/4" Flat Washer (4) Places.
(4) Places. Torque to 60 In. Lbs.
Torque to 60 In. Lbs.
GROUND
BUSBAR CONNECTION
Remove / Install
1/4-20 X 7/8" Bolt
1/4" Belleville Washer
1/4" Flat Washer
(4) Places.
Torque to 60 In. Lbs.
SYSTEM
GROUND BUSBAR CONNECTION
BUSBAR CONNECTION Remove / Install
Remove / Install 1/4-20 X 7/8" Bolt
1/4-20 X 7/8" Bolt (or 1/4-20 X 1" Bolt List BA only)
1/4" Belleville Washer 1/4" Belleville Washer
1/4" Flat Washer 1/4" Flat Washer
(4) Places. (4) Places.
Torque to 60 In. Lbs. Torque to 60 In. Lbs.
+ JUMPERS - JUMPERS
Remove / Install Remove / Install Remove / Install Remove / Install
10-32 X 5/8" Screw 1/4-20 x 5/8" Bolt 1/4-20 Hex Nut 10-32 X 5/8" Screw
No. 10 Flat Washer 1/4" Lock Washer 1/4" Lock Washer No. 10 Flat Washer
(2) Places. 1/4" Flat Washer 1/4" Flat Washer (2) Places
(2) Places Per Jumper (2) Places Per Jumper
Torque to 84 In. Lbs. Torque to 84 In. Lbs.
Figure 26. (Detail E) Replacing List CB (Lists AB, AC, and CD Similar)
GROUND SYSTEM
BUSBAR CONNECTION BUSBAR CONNECTION
Remove / Install Remove / Install
1/4-20 X 7/8" Bolt 1/4-20 X 7/8" Bolt
1/4" Belleville Washer 1/4" Belleville Washer
1/4" Flat Washer 1/4" Flat Washer
(4) Places. (4) Places.
Torque to 60 In. Lbs. Torque to 60 In. Lbs.
Figure 26. (Detail F) Replacing List CE (Lists AD, AE, and CF Similar)
GROUND SYSTEM
BUSBAR CONNECTION BUSBAR CONNECTION
Remove / Install Remove / Install
1/4-20 X 7/8" Bolt 1/4-20 X 7/8" Bolt
1/4" Belleville Washer 1/4" Belleville Washer
1/4" Flat Washer 1/4" Flat Washer
(8) Places. (8) Places.
Torque to 60 In. Lbs. Torque to 60 In. Lbs.
LVD
CONTACTORS
(LISTS CE &
CF ONLY)
Figure 26. (Detail H) Replacing List CG (List AG, AJ, AP, and CJ Similar)
SYSTEM
BUSBAR CONNECTION
Remove / Install
1/4-20 X 7/8" Bolt
1/4" Belleville Washer
1/4" Flat Washer
(4) Places.
Torque to 60 In. Lbs.
SYSTEM
GROUND BUSBAR CONNECTION
BUSBAR CONNECTION Remove / Install
Remove / Install 1/4-20 X 7/8" Bolt
1/4-20 X 7/8" Bolt 1/4" Belleville Washer
1/4" Belleville Washer 1/4" Flat Washer
1/4" Flat Washer (4) Places.
(4) Places. Torque to 60 In. Lbs.
Torque to 60 In. Lbs.
SYSTEM
GROUND BUSBAR CONNECTION
BUSBAR CONNECTION Remove / Install
Remove / Install 1/4-20 X 7/8" Bolt
1/4-20 X 7/8" Bolt 1/4" Belleville Washer
1/4" Belleville Washer 1/4" Flat Washer
1/4" Flat Washer (4) Places.
(4) Places. Torque to 60 In. Lbs.
Torque to 60 In. Lbs.
NOTE SYSTEM
IF LIST AL GROUND BAR IS BUSBAR CONNECTION
MOUNTED ABOVE LIST AK, Remove / Install
REMOVE LIST AL PRIOR 1/4-20 X 7/8" Bolt
TO REMOVING LIST AK. 1/4" Belleville Washer
1/4" Flat Washer
(4) Places.
Torque to 60 In. Lbs.
GROUND
BUSBAR CONNECTION
Remove / Install Remove / Install
1/4-20 X 7/8" Bolt 1/4-20 X 7/8" Bolt
1/4" Belleville Washer 1/4" Lock Washer
1/4" Flat Washer 1/4" Flat Washer
(4) Places. (4) Places.
Torque to 60 In. Lbs. Torque to 60 In. Lbs.
FRONT VIEW
Danger: All sources of AC and DC power must be completely disconnected from this power system before performing
this procedure. Use a voltmeter to verify no DC voltage is present on the system busbars before proceeding.
1. Open the Distribution Cabinet's front door by turning and holding the captive fastener in the counterclockwise position.
2. Disconnect all battery wiring from the Contactor Assembly input busbar. If necessary, refer to the separate INSTALLATION
INSTRUCTIONS (SECTION 5974) for connection locations.
3. Disconnect the Contactor Assembly linking busbar from the system busbar as shown at SYSTEM BUSBAR CONNECTION in
Figure 27.
4. Loosen but do not remove (1) 12-24 x 1/2" mounting screw at bottom of contactor mounting plate, as shown in Figure 27.
5. Remove (2) 12-24 x 1/2" mounting screws at top of contactor mounting plate, as shown in Figure 27.
6. Lift the Contactor Assembly up off bottom mounting screw. Remove the assembly far enough to access the terminals on the
side of the coil body. Note the positions of the wire connections so that they can be correctly reconnected later in the
procedure. Disconnect the lug that terminates (1) Violet and (1) Violet/White wire. Remove the Contactor Assembly to a work
surface.
7. Disconnect from the coil body the lug that terminates (1) Red/White wire.
8. Note the orientation of the contactor with respect to the input and linking busbars. Remove the hardware that secures the
input and linking busbars to the contactor.
Note: In the following procedure, before making busbar-to-busbar connections, apply a thin coating of electrical anti-oxidizing
compound to the mating surfaces of the busbars.
1. Install the linking and input busbars on the new contactor. First, apply a thin coating of electrical anti-oxidizing compound to
the mating surfaces of the busbars. Tighten the bolts as specified in Figure 27.
2. Connect to the coil body the lug that terminates (1) Red/White wire.
3. Install the Contactor Assembly into the Distribution Cabinet far enough for the (1) Violet and (1) Violet/White wire removed in
Step 6 to reach the terminals on the coil body. Connect the lug that terminates the two wires to the terminal on the coil body.
4. Position the Contactor Assembly on its mounting plate, and lower over the bottom mounting screw.
5. Install (2) 12-24 x 1/2" mounting screws at top of contactor mounting plate, as shown in Figure 27.
7. Reconnect the Contactor Assembly linking busbar to the system busbar as shown at SYSTEM BUSBAR CONNECTION in Figure
27. Tighten the bolts as specified in the figure.
8. Reconnect all battery wiring to the Contactor Assembly input busbar. Refer to the separate INSTALLATION INSTRUCTIONS
(SECTION 5974) for connection locations and recommended torque.
2. Start the Power System. Refer to "Installing Rectifier Modules and Initially Starting the System" in the separate INSTALLATION
INSTRUCTIONS (SECTION 5974) for a startup procedure.
4. Close the Distribution Cabinet's front door. The door can be shut without turning the captive fasteners.
(Cutaway View)
Remove / Install
IN 12-24 x 1/2" Screw MOUNTING
DISTRIBUTION No. 12 Flat Washer PLATE
CABINET (2) Places
SYSTEM
BUSBAR CONNECTION
Remove / Install
3/8-16 x 1-1/4" Bolt
3/8" Belleville Washer
3/8" Flat Washer
(2) Places
Torque to 180 In. Lbs.
(Cutaway View)
INPUT Loosen / Tighten LINKING
BUSBAR Screw. BUSBAR
Do Not Remove.
Remove / Install
1/2-13 x 1-1/2" Bolt
1/2" Belleville Washer
Remove / Install 1/2" Flat Washer
1/2-13 x 1-1/2" Bolt (2) Places
1/2" Belleville Washer Finger Tight Until SYSTEM
1/2" Flat Washer BUSBAR CONNECTION
(2) Places is Made. Then
Torque to 200 In. Lbs. Torque to 200 In. Lbs.
REMOVED
FROM
DISTRIBUTION
CABINET
Disconnect / Reconnect
INPUT Red/White Wire at LINKING
BUSBAR Contactor Coil Body BUSBAR
Danger: All sources of AC and DC power must be completely disconnected from this power system before performing
this procedure. Use a voltmeter to verify no DC voltage is present on the system busbars before proceeding.
1. Remove the contactor rear access cover. To do so, loosen but do not remove the four screws that secure the cover. Slide the
cover up and remove. Refer to Figure 28 for screw location.
2. Remove the four (4) 3/8-16 x 1-1/4” bolts and associated washers from the contactor. Slide contactor back until wiring on
contactor is accessible. Refer to Figure 28.
3. Disconnect the four (4) wires on the auxiliary switch, and the two (2) wires on the coil body. Refer to Figure 29. Remove the
contactor.
Note: In the following procedure, before making busbar-to-busbar connections, apply a thin coating of electrical anti-oxidizing
compound to the mating surfaces of the busbars.
1. Connect the six (6) wires to the replacement contactor as shown in Figure 29.
2. Place the contactor in position, and secure by installing the 3/8” hardware as shown in Figure 28. Torque as shown in the figure.
3. Reinstall the contactor rear access cover. Tighten the four screws.
2. Start the Power System. Refer to "Installing Rectifier Modules and Initially Starting the System" in the separate INSTALLATION
INSTRUCTIONS (SECTION 5974) for a startup procedure.
4. Close the Distribution Cabinet's front door. The door can be shut without turning the captive fasteners.
TOP OF
DISTRIBUTION
CABINET
REAR VIEW
Remove / Install
3/8-16 x 1-1/4" Bolt
3/8" Belleville Washer
3/8" Flat Washer
(4) Places
Torque to 180 In. Lbs.
VIOLET
BLUE
WHITE
RED
(2) VIOLET
SLATE
Adding a Battery Charge Digital Temperature Compensation Probe to a Previously Operated System
This procedure details the steps to add a Battery Charge Digital Temperature Compensation Probe to a system that has been previously
started, configured, and checked.
Procedure
1. Refer to “Installing System Components” of the separate INSTALLATION INSTRUCTIONS (SECTION 5974), and mount the
Battery Charge Digital Temperature Compensation Probe near the batteries.
2. Refer to “Making Electrical Connections” of the separate INSTALLATION INSTRUCTIONS (SECTION 5974), and connect the
Battery Charge Digital Temperature Compensation Probe to connector J4 located on the MCA Main Controller circuit card in the
Main Bay Distribution Cabinet. The MCA automatically detects the probe and adds it to the inventory without any alarms. The
default slope setting is DIGITAL TC OFF.
3. Refer to “MCA System Adjustments”, and set the following digital battery charge temperature compensation parameters:
SLOPE, MAX W/T, and MIN W/T.
4. Refer to “MCA System Adjustments”, and set the following alarm parameters: HI TEMP and LO TEMP.
5. Verify that battery charge temperature compensation has begun by comparing the SYSTEM voltage reading versus the FLOAT
setting. Depending on the battery ambient temperature, the SYSTEM voltage should be higher or lower than the FLOAT setting
by the amount of slope V/ºC (note that SYSTEM voltage will also vary from the FLOAT setpoint depending on the load).
Note: At 25ºC, the battery charge temperature compensated SYSTEM voltage equals the FLOAT voltage setting.
Note: If the probe is disconnected or fails, a major alarm (local and extended) activates and the system returns to the FLOAT
voltage setting.
Removing a Battery Charge Digital Temperature Compensation Probe from a Previously Operated System
This procedure details the steps to remove a Battery Charge Digital Temperature Compensation Probe to a system that has been
previously started, configured, and checked.
Procedure
1. In the Calibration menu, set the SLOPE = .### V/°C to DIGITAL TC OFF. Temperature Compensation stops and the System
returns to the FLOAT voltage setting.
2. Remove the probe. The Major Alarm activates. Update inventory to clear this alarm, as described in this section.
Account Management
Email AccountManagement.ESNA@Emerson.com Provides quotes and bid responses for custom configured [2] DC power
systems and outside plant enclosures for customers and channel partners
Phone 1.800.800.1280 option 2 (Reps, VARs & Distributors).
Spare Parts
DCpower.Spares@Emerson.com Pricing and purchase orders for spare parts, including but not limited to
Email
OSP.Spares@Emerson.com breakers, cables, fuses, rectifier fans, misc. breaker and fuse panels,
Phone 1.800.800.1280 option 5 enclosure fans, doors and switches, etc.
Email DCpower.Repair@Emerson.com Creates and processes RMAs for depot repair and refurbishment.
Determines repair and refurbishment lead times and pricing based on
warranties/contractual agreements. Provides repair shipping information
Phone 1.800.800.1280 option 6 and status.
Technical Support
DCpower.TAC@Emerson.com
Email Answers technical product and system questions; determines status of
OSP.TAC@Emerson.com
warranties and contractual agreements for repair.
Phone 1.800.800.5260
Email DCpowerReps.ESNA@Emerson.com Provide quotes and bid responses for application specific configured DC
Phone 1.440.240.0639 power systems for Liebert DC power sales reps.
The information contained in this document is subject to change without notice and may
not be suitable for all applications. While every precaution has been taken to ensure the
accuracy and completeness of this document, Emerson Network Power, Energy Systems,
North America, Inc. assumes no responsibility and disclaims all liability for damages result-
ing from use of this information or for any errors or omissions. Refer to other local
practices or building codes as applicable for the correct methods, tools, and materials to
be used in performing procedures not specifically described in this document.
The products covered by this instruction manual are manufactured and/or sold by Emerson
Network Power, Energy Systems, North America, Inc. This document is the property of
Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and
proprietary information owned by Emerson Network Power, Energy Systems, North
America, Inc. Any copying, use or disclosure of it without the written permission of Emerson
Network Power, Energy Systems, North America, Inc. is strictly prohibited.