Isolating Switch for maintenance is located
before the equipment directly for maintenance
20
Isolator
Description
23
(2) Split unit:
ICB=2.25xIload due to starting current
Ex: 3 hp AC split :
Sload =3KVA
ICB=2.25xIload=2.25x4.5x3=30.35
Standard 32A but wire 3x4 mm2
24
(3) Fire pump & jockey pump:
Fire pump : ICB= 3xIn (IEC)
ICB=4xIn (EG)
Ex: 50 hp fire pump: ICB=1.5x3x50=225Amp
Standard cable : 250A MCCB fixed
jockey pump:
ICB=2.25xIload due to starting current (MCB)
ICB=1.25xIload due to starting current (MCCB)
Ex: 6 hp AC split :
Sload =6KVA
ICB=2.25xIload=2.25x1.5x6=20.5
Standard 25A MCB but 5x4mm2
25
(4) Fan coil unit (FCU) 1ph:
FCU load= max 330watt/0.8=400 VA
CB=16A,
wire 3x3mm2,
no of FCU per linea=2000/400=5
One FCU per linea is preferred