240 126260252
240 126260252
240 126260252
Revision: 1
Total Pages: 37
Supported by SCOT/SC
Riaz Asmal
SCOT/SC Chairperson
Date:2018/03/01
Content
Page
Executive Summary ............................................................................................................................................ 4
1. Introduction .................................................................................................................................................. 5
2. Supporting clauses ...................................................................................................................................... 5
2.1 Scope ................................................................................................................................................. 5
2.1.1 Purpose .................................................................................................................................. 5
2.1.2 Applicability ............................................................................................................................ 6
2.2 Normative/informative references ...................................................................................................... 6
2.2.1 Normative ............................................................................................................................... 6
2.3 Definitions ........................................................................................................................................... 6
2.3.1 General .................................................................................................................................. 6
2.4 Abbreviations ...................................................................................................................................... 7
3. Technical documentation requirement for the connection of an EG to a shared LV feeder ....................... 7
4. DGSL Type Testing and conformance assurance ...................................................................................... 8
4.1 DGSL Type Test Certificate requirements ......................................................................................... 8
4.2 ISO 9001 Certification of the DGSL manufacturer. ............................................................................ 8
Manufacturers of DGSL devices must have valid ISO 9001 certification at all times during the
design and manufacture of DGSLs. ................................................................................................... 8
4.3 DGSL Conformance Certificate .......................................................................................................... 8
4.4 Registration of DGSL models with the Eskom Technology Division .................................................. 8
5. Maintaining the integrity of the DGSL through its life .................................................................................. 8
5.1 Preservation of harware settings and firmware versions changes .................................................... 8
5.2 Tamper sealing of the DGSL .............................................................................................................. 8
5.3 Maintenance and repair of DGSL, certification and sealing ............................................................... 8
6. DGSL Requirements ................................................................................................................................... 9
6.1 DGSL components ............................................................................................................................. 9
6.2 General requirements.......................................................................................................................10
6.2.1 Load current rating and design ............................................................................................11
6.2.2 Fault current rating and design ............................................................................................11
6.2.3 Standard ratings for shared feeder DGSL ...........................................................................11
6.3 Detail specification ...........................................................................................................................11
6.3.1 Assembly housing ................................................................................................................11
6.3.2 Terminals of the DGSL ........................................................................................................11
6.3.3 Switch-disconnector (and circuit breaker where applicable) ...............................................12
6.3.4 AC arresters Specification ...................................................................................................14
6.3.5 The Functional Relay ...........................................................................................................14
6.3.6 Auxiliary components short circuit protection ......................................................................16
6.3.7 Contactor specification .........................................................................................................16
6.3.8 Residual current disconnecting (RCD) device .....................................................................17
6.3.9 Busbar and interconnection conductor requirements ..........................................................17
6.3.10 Earth Continuity Conductor dimension ................................................................................17
6.4 Labelling ...........................................................................................................................................18
6.4.1 Main identity label ................................................................................................................18
6.4.2 Generator side pigtail or terminal label ................................................................................19
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 3 of 37
Figures
Tables
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 4 of 37
Executive Summary
This specification lays down the requirements for the Dead-Grid Safety Lock (DGSL). The DGSL is a device
that ensures the safety of utility staff in the presence of EG on LV feeders in concert with the normal safety
procedures for working on installations dead. When these procedures are followed in the normal way, the
DGSL will ensure that it is not possible for EG’s that accidentally become live, to be a hazard to the workers
on the network between the locked out isolation point and the Embedded Generator.
It is envisaged that the DGSL will in the future become a SANS standard.
The document also contains the minimum safety requirements for a photovoltaic driven embedded generator
connected at low voltage. (As and Eskom standard)
It is envisaged that the minimum safety requirements will be moved to the inter utility standard - NRS 097-2-1
in future revisions of the NRS document. The requirements will eventually be incorporated into SANS
10142-3 when that standard is written and approved.
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 5 of 37
1. Introduction
This standard applies to the connection of PV EG connections done by LV connected customers of Eskom.
It ensures the safety of operating staff working dead on the LV network.
2. Supporting clauses
2.1 Scope
This specification lays down the requirements for the Dead-Grid Safety Lock (DGSL). The DGSL is a device
that ensures the safety of utility staff in the presence of EG on LV feeders in concert with the normal safety
procedures for working on installations dead. When these procedures are followed in the normal way, the
DGSL will ensure that it is not possible for EG’s that accidentally become live, to be a hazard to the workers
on the network between the locked out isolation point and the Embedded Generator.
This specification is for 230V single phase and 400V three phase systems.
The schematic diagram of a single phase Dead-Grid Safety Lock ( DGSL) is shown in figure 1.
The DGSL include isolators, auxiliary circuit protection (for the relay circuit and the surge arresters as and
when required), surge arresters, protective earths, these are part of the minimum installation that will ensure
that the life critical elements retain their functions for in excess of 20 years as the minimum design life target.
The RCD is an element that is only required in the case where the EG uses transformerless inverter
technology, and the inverter does not include this function already. (It would therefore rarely be required.)
DGSL specifications for different applications such as inverter based EGs, rotating machine EG, multi- EG
networks differs. These different applications cause different environments in which the DGSL has to
operate including fault level, risk of faults and more.
The initial focus of the DGSL development will be on inverter based (PV driven) EGs on shared LV
feeders as. For this reason rated current is selected in accordance with NRS 097-2-3, as 20A / 4.6 kVA
single phase and 50A /34.5 kVA three phase.
DGSL specifications for other applications will follow and may include:
Larger capacity units for dedicated feeder installations
Rotating machine generators,
Hybrid systems where the EG switches from a current to a voltage control mode.
2.1.1 Purpose
Design objective: The long term durability and reliability of the DGSL is the cornerstone objective. The
document should be the minimum requirements that ensure safety of the device over a life of at least 20
years.
Sustainability: Consideration should be given for how the device would be maintained in a sustainable way
over the life of the associated Embedded Generator. This pertains to the initial certification, periodical
inspection and failure-maintenance events.
Functions of the Dead-Grid Safety Lock:
Provide a secure means that prevent EG’s to feed energy back into the grid, once it was declared
safe to work on. (Protecting utility staff working on a LV network with the LV dead work method,
from re-energization from the EG.)
Safety and quality assurance through type testing and unit certification.
Isolation point for working safely beyond this point on the installation.
Lightning protection of both the DGSL and the inverter
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 6 of 37
2.1.2 Applicability
This document shall apply throughout Eskom Holdings Limited Divisions.
2.2.1 Normative
[1] ISO 9001, Quality Management Systems.
[2] SANS 10142-1 the wiring of premises Part 1: Low-voltage installations.
[3] GRID CONNECTION CODE FOR RENEWABLE POWER PLANTS (RPPs) CONNECTED TO THE
ELECTRICITY TRANSMISSION SYSTEM (TS) OR THE DISTRIBUTION SYSTEM (DS) IN SOUTH
AFRICA. (Referred to in the text as the Grid Code).
[4] NRS 097-2-1GRID INTERCONNECTION OF EMBEDDED GENERATION Part 2: Small-scale
embedded generation Section 1: Utility interface.
[5] NRS 097-2-3 GRID INTERCONNECTION OF EMBEDDED GENERATION Part 2: Small-scale
embedded generation Section 3: Simplified utility connection criteria for low-voltage connected
generators.
[6] SANS 61439-1:2012 Low voltage switchgear and controlgear assemblies. Part 1 General rules.
[7] IEC 60947-2 Low-voltage switchgear and controlgear Part 2: Circuit-breakers.
[8] IEC 60947-3 Low-voltage switchgear and controlgear Part 3: Switches, disconnectors, switch-
disconnectors and fuser-combination units
[9] SANS 61117/IEC 61117, A method for assessing the short-circuit withstand strength of partially
type-tested assemblies (PTTA).
[10] IEC 60947-4-1:2010+A1:2012. Low-voltage switchgear and controlgear Part 4-1: Contactors and
motor-starters — Electromechanical contactors and motor-starters.
[11] IEC 60255-6:1995 Electrical relays — Part 6: Measuring relays and protection equipment.
[12] IEC 60255-1:2010 Measuring relays and protection equipment — Part 1: Common requirements.
[13] SANS 60947-2:2007/IEC 60947-2:2006, Low-voltage switchgear and controlgear – Part 2: Circuit
breakers.
2.3 Definitions
2.3.1 General
Definition Description
Feed-in tariff metering This is metering for a tariff where all the energy generated by the EG is
measured separately from the energy consumed by the customer and a tariff is
applied to the energy so metered.
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 7 of 37
Definition Description
Net-billing-metering This is metering (normally a single meter) for a tariff where the net-energy at
the Point of Supply are measured. Energy consumed or energy generated
could be accumulated in separate registers and different energy rates could be
applied to generated or consumed energy.
2.4 Abbreviations
Abbreviation Description
DGSL Dead-Grid Safety Lock
AC alternating current
CB circuit-breaker
COC certificate of compliance
DB distribution board
DC direct current
EG embedded generator
FIT feed-in tariff
Isc short-circuit current
POC point of connection
PV photovoltaic
RCD residual current device
r.m.s. root mean square
SPD Surge Protection Device
ST Sjunt trip
NO Normally open
NC Normally closed
Ir
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 8 of 37
*Valid: Here mean a DGSL model and rating for which the Manufacturer of the DGSL has registered the
DGSL model and rating with Eskom’s Grid Access Department via the appropriate process, and Eskom have
accepted the validity of the documentation. (The DGSL Conformance Certificate contains a direct reference
to the DGSL Type Test Certificate.)
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 9 of 37
6. DGSL Requirements
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 10 of 37
Figure 2: A typical embodiment of the DGSL. The salient features are the enclosure with relevant
labelling. The AC Disconnector with the ability to lock it in the off position as required by SANS
10142-1. Sealing of the enclosure. Cable trunking or conduit terminations for the grid and a pigtail
cable for the embedded generator connection
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 11 of 37
Ir Vr Isc VA
10A single phase 10A 230V 5 kA 2.3 kVA
10A three phase 10A 230V 5 kA 6.9 kVA
20A single phase 20A 230V 5 kA 4.6 kVA
20A three phase 20A 400V 5 kA 13.8 kVA
50A three phase 50A 400V 5 kA 34.5 kVA
IP 65
Painted metal or sutably rated plastic enclosure suitable to last 20 years
The switch disconnector must have a mechanism that allows operating, locking and tagging from
outside of the DGSL enclosure of the disconnection function.
Assembly housing temperature rise:
The maximum steady state temperature rise (of air) inside the enclosure may not exceed 20 degrees celcius
at the rated current of the DGSL. One hour continous operation at rated current is deembed to be steady
state.
The test is to be done at both Vnominal + 10% and Vnominal – 10%.
The temperature rise determination is to be done through SANS/IEC 61439-1. (SANS 60890 is a very useful
design aid).
A termination point should be provided; in compliance of SANS 10142-1 and its associated standards for
cable terminations and/or other means such as trunking and conduit.
2
The terminals should at least provide for standard cable size termination equal or greater than 3A/mm (up to
2
Ir ≤100A) and 2A/mm (above Ir >100A) at the rated current of the DGSL (Ir).
The EG side connection should preferably be a 800mm long pig tail for connection directly into the EG
terninals. The current carrying conductors should be copper and the cross section should be such that it
2 2
does not exceed 3A/mm (up to Ir ≤100A) and 2A/mm (above Ir >100A) at the rated current of the DGSL
(Ir).
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 12 of 37
(At the time of writing this document it is anticipated that net-billing will apply to most Eskom customer
installations.)
For net-billing installations, only switch-disconnection functionality is required.
This switched-disconnector fulfils the functions as required by SANS 10142-1 clause 6.9.3 Disconnecting
devices for equipment.
Product standard: IEC 60947-3 Low-voltage switchgear and controlgear Part 3: Switches, disconnectors,
switch-disconnectors and fuser-combination units.
It has to be lockable and it should be possible to attach safety tags to it as part of the construction of the
DGSL housing.
Rating of the switch-disconnector:
Rated operational voltage (Ue) > 415V
Rated insulation voltage (Ui) >= 690V
Rated impulse withstand voltage (Uimp) >= 6 kV
Rated AC-21 operational current (Ie) Must be larger than the rated current of the DGSDL.
Rated making capacity > 3x Must be larger than the rated current of the DGSDL
Rated breaking capacity > 3x Must be larger than the rated current of the DGSDL
[Note: The DGSL for net-billing instllations does not require fault protection, the fault protection function will be resident on the
upstream distribution board.]
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 13 of 37
The switched-disconnector have to be compliant to the requirements of SANS 10142-1 6.8.1 (Circuit
breakers used as main or local switch-disconnectors) read along with clause 3.79.2 pertaining to the
applicable standards for “circuit-breakers used as switched-disconnectors.
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 14 of 37
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 15 of 37
Under voltage Must-Remain-Closed, voltage-dip-time response, within the limits of E1, where it
is possible, safety requirements will always take priority over the Grid Code requirements.*
Under voltage Must-Open, voltage dip- time response, must be prevent contactor chatter of the
contactors chosen for the particular DGSL.
Under voltage Must-Open-voltage-trip-setting, under voltage trip setting must be between 65%
and 75% of the nominal phase to neutral voltage (230V phase to ground).
Under voltage Must-open-delay-time, may not exceed 2 seconds.
Under voltage Re-close level, the close operation should have a hysteresis of no less than 2%
above the under voltage open level. The desired value would be greater than 5%.
Over-voltage trip functionality is not required in this device. However should it have such
capability it should be compatible to the Grid Code and NRS 097-2-1 see E1. [It should be
considered to be a requirement. The argument for this is that over voltage presents a safety risk.
If this is accepted a value of tripping at 120% of the phase to ground voltage is suggested, with an
operating time slower than 3 seconds and faster than 30 seconds.]
Over and under frequency trip response is not required in this device. However it is permitted
to have it and should be compatible to the Grid Code and NRS 097-2-1 limits. Ie. Lower and higher
than the respective low and high frequency limits.
Note # NRS 097-2-1 only allows the generator to switch back on after 60 seconds. (And any other similar requirements.) It
should be noted that these are requirements of the total EG system, not a requirement for the DGSL.
General Requirements
Nominal LN voltage 230 V
Nominal LL voltage 400 V
Maximum continuous LL voltage 550 V
Maximum continuous LN voltage 440 V
Measuring method True RMS or Average
Casing IP 50
Terminals IP 20
Environmental requirement
Operating temperature range -20 to 65 degrees Celsius
Climate category IEC 60721-3-1
Vibration IEC 60255-21-2 Class 2
Shock 60255-21-2 Class 2
Isolation requirement
Input-output
Output 1 to output 2
Test voltage between all isolated circuits 2.5 kV rms
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 16 of 37
General Requirements
Basic isulation level 500V
Pollution degree 3
Electromagnetic compatibility
Electrostatic discharge 61000-4-2
Fast transient 61000-4-4 Level 3 (2kV 5kHz )
Surge 61000-4-5 Level 4 (2kV L-L, L-N)
Harmonics and interharmonics 61000-4-13 Class 3
Larger DGSL with current ratings 100A and above and Isc > 10 kA are candidates that may require separate
protection for the auxiliary circuits.
It is up to the designer to determine this requirement.
Both circuit breakers and fuses could be used as auxiliary circuit protectors.
Note further that the DGSL auxiliary circuits are not subjected to fault currents caused by faults external to the DGSL. Only
faults inside the DGSL auxiliary circuits would subject it to fault current.
As this is a PI 65 sealed unit it is very unlikely that internal faults should occur. Only internal auxiliary circuit
faults can cause this. If the DGSL is suitably designed and rated, this probability will be very low.
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 17 of 37
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 18 of 37
Table 2: Copy of SANS 10142 6.24(a) Cross sectional area of protective conductors proportional to
the cross sectional area of the phase conductors
6.4 Labelling
Labelling must comply with SANS 1186-1. The labels must have a life expectancy of 20 year.
The DGSL must have the following labels which is permanently fixed to the DGSL:
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 19 of 37
7. Authorization
This document has been seen and accepted by:
8. Revisions
Date Rev Compiler Remarks
April 2018 1 H Geldenhuys First issue
9. Development team
The following people were involved in the development of this document:
Johan Beukes
Koos Kraft
Dumisani Mtolo
10. Acknowledgements
The assistance of many persons form industry is acknowledged. The document is an outcome of
deliberations that took place at the NRS 097-2-1 meetings.
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 20 of 37
Annex A – Pro forma Type Test and Conformance Certificate for the DGSL
(Normative)
Address ______________________________________
DGSL Rating
Rated current Ie A
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 21 of 37
Balance of components…………… Allowed if it equal or exceeds the specified requirements as per the
standard and well as the short circuit capability of the DGSL. . [Must be declared in the device certificate as
an appendix.]
Substitution testing rules
Thermal testing- the combination of alternative components which have the highest losses should
be used in temperature test.
Voltage and time response compliance should be demonstrated with all the combinations of
components considered as alternative designs.
2) Component compliance
(Where applicable, alternative components should be duplicated in the form below.)
Functional relay
Make
Model no
Requirement Detail Confirmation:
Actual value and Y/N
Product standard IEC 60255-2: 1995 or
Y/N
IEC 60255-1:2010
Y/N
Rated operational voltage > 252 Vrms P-G, 440 Vrms P-P Y/N
Rated Insulation voltage > 252 P-G, 440 Vrms P-P Y/N
Accuracy of voltage limits +/- 1% Y/N
Power consumption < 3 watt Y/N
Energy storage and latching No electrical charge storage or
magnetic latching effective for Y/N
more than 1 sec
Contactor
Make
Model no
Requirement Detail Confirmation:
Actual value and Y/N
Product standard SANS/ IEC 60947-4-1 Y/N
Rated operational voltage > 252 VrmsP-G, 440 Vrms P-P Y/N
Rated Insulation voltage > 252 P-G, 440 Vrms P-P Y/N
Rated impulse withstand > 6kV peak Y/N
AC-1 rated current > 1.5 x DGSL rated current Y/N
Mechanical operations > 1 000 000 Y/N
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 22 of 37
Switch-disconnector
Make
Model no
Requirement Detail Confirmation:
Actual value and Y/N
Product standard SANS/IEC 60 947-1 and
IEC 60 947-3 (isolator) OR Y/N
SANS 60 947-2(Circuit breaker)
Rated operational voltage > 252 Vrms P-G, 440 Vrms P-P Y/N
Rated Insulation voltage > 252 P-G, 440 Vrms P-P Y/N
Rated impulse withstand > 6kV peak Y/N
Rated current > 1.5 x DGSL rated current Y/N
Surge Arresters
Make
Model no
Requirement Detail Confirmation:
Actual value and Y/N
Product standard SANS/ IEC 61643-1 Y/N
MCOV 260 Vrms < MCOV < 280Vrms Y/N
Voltage protection level < 1500V Y/N
Nominal discharge current 20 kA Y/N
Maximum discharge current 40 kA Y/N
Short circuit fault withstand (Isc Rating of DGSL) Y/N
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 23 of 37
3) Circuit conformance
Requirement Detail Confirmation Y/N
Single phase wiring arrangement Figure 1 Y/N
Three phase wiring topology Annex E Y/N
2
Cross sectional area of primary 4 A / mm Ir ≤ 100A
current circuit and copper 2 Y/N
3A / mm Ir > 100 A
conductor
2
Earth continuity conductor and > 6mm And
its connection terminals’
Compliant to Table 2
equivalent continuously rated Y/N
capacity Continuously capable of carrying
DGSL rated current.
4) Functional Compliance
System MUST OPEN and MUST REMAIN CLOSE with no contact chatter
Voltage change Duration to trip Requirement
Phase 1 Phase 2 Phase 3
1 PU to 0.40 PU in less than 1 3 sec maximum Trip in Trip in Trip in
second time time time
[1+2]
Start 1 PU lower voltage to No contactor No No No
0.6PU in 10 seconds chatter and contactor contactor contactor
must open chatter chatter chatter
contactors and open and open and open
5) Labelling
Main label Clause 3.4.1
Grid side cable terminal label Clause 3.4.3
Inverter side cable terminal label Clause 3.4.2
Isolation switch label Clause 3.4.4
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 24 of 37
This Dead Grid Safety Lock complies with all the requirements of SANS 1973-1or3 and the design
requirements of the Dead Grid Safety Lock Standard.
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 25 of 37
DGSL model:_______No___________________
Date :_____________
DGSL serial No:______________________
DGSL Rating
Single phase or three phase 1/3 Phase
Rated operating voltage Ue V
Rated current Ie A
Maximum power rating of EG kVA
Short circuit withstand capacity kA
Identical to all the requirements of the original type test design (Y/N)
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 26 of 37
N: m-Ohm
ECC: m-Ohm
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 27 of 37
Figure C.1: Schematic layout of the essential safety requirements for a PV inverter EG installation
for upstream safe work and network protection
The salient apparatus required to ensure the safety of upstream network equipment and staff is shown in B1.
[The consumer installation also has other safety requirements, not dealt with here.]
It comprises of the following elements:
Earth Continuity Conductor (ECC) which is connected all the way through from the PV panel frame
earth, the PV structural lightning protection (if applicable), through to the AC installation ECC and
the utility earth conductor.
Dead-Grid Safety Lock DGSL
DC Isolator before the inverter
DC surge arresters before the inverter.
Structural lightning protection, if required.
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 28 of 37
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 29 of 37
Table C.1: Maximum protection levels for DC arresters, for inverter system voltage
600V ≤ 2 500V
1000V ≤ 4 000V
1200V ≤ 4 500V
The arresters must be mounted in a suitable housing, in accordance with the requirements of SANS 10142-1.
B6 Fault Current protection for the EG circuit including the DGSL
Cascading of fault current protection devices in accordance with IEC 60947-2 can be applied. This has to be
documented in the COC for the installation.
Ensuring that the DGSL and other EG components are adequitely fault current protected, is the
accountability of the installation designer in accordance with SAN !0142-1.
B6 Structural lightning protection of the PV-DC panel installation
The structural protection is to be done in accordance of SANS / IEC 62305-3 Protection against lightning
Part 3: Physical damage to structures and life hazards.
Comprising of the following:
B6.1) Earth electrode(s)
B6.2) Down conductors
B6.3) Air terminals as and when required
The installation of a lightning earth electrode system and suitable down conductors is the primary
compulsory requirement.
Where the risk of a strike to the PV installation exceeds a frequency of once in 20 years (calculated via
SANS 62305-2), a lighting protection system which is insulated from the PV-DC is required. If the risk is not
calculated it must be applied to all installations exceeding 12.8 kVA.
In the case where a separate insulated lightning protection system is used the only connection between the
lighting earth-bonding conductor and the power protective earth is to be done at the consumer’s (power)
earth terminal (CET) per chapter 6.11 of SANS 10142-1.
B7 Protection associated with utility tariff structure and supply options
Supply tariff options have consequences for the installation with respect to the electrical regulations and
standards including SANS 10142-1. There are three known possible contractual options:
No compensation.
Net metering.
Feed in tariffs.
It can have effect on the utility supply point and design as well as on the customer installation.
ESKOM COPYRIGHT PROTECTED
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 30 of 37
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 31 of 37
Figure C.2: The DGSL to the DC side arresters, maximum distance requirement
B8 Disconnector requirements
The DGSL should be installed in accordance with SANS 10142-1 clause 6.9.3 as it is acts as the
disconnecting device for the inverter.
B9 Cooling of the DGSL
The DGSL enclosure may not be built into a wall. It has to be surface-mounted to assist in cooling.
A 70mm clearance has to be maintained to all sides to ensure adequate cooling. See B2.
It should not be mounted in direct sunlight. (To avoid additional heating.)
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 32 of 37
Figure D.1: DGSL main breaker maximum current clearing time in terms of the rated current of the
DGSL breaker
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 33 of 37
Figure E.1: Functional relay single phase application schematic connection diagram
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 34 of 37
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 35 of 37
Figure G.1: The Renewables Grid Code voltage-time requirements for embedded generators to
remain connected or have to disconnect. [Changes that will only be published in 2017 are already
reflected here.]
One of the primary functions of the undervoltage relay is to prevent chattering of the contactors. For this the
under voltage relay has to consider the levels at which chattering of contactors occur, which is depicted in
F2.
From these requirements, the under voltage operating voltage-time relationship is derived.
ESKOM COPYRIGHT PROTECTED
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 36 of 37
Eskom will allow LV connected EG up to 75% of 500 kVA which is 375 kVA. Some other municipalities has
indicated that they will allow LV connected EG up to 75% of 2 MVA which is 1 500 kVA.
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.
Document Classification: Public
THE DEAD-GRID SAFETY LOCK SPECIFICATION AND Unique Identifier: 240-126260252
MINIMUM SAFETY REQUIREMENTS FOR LV
CONNECTED PHOTOVOLTAIC EMBEDDED Revision: 1
GENERATORS Page: 37 of 37
*Possible “same cause” could be fault current behind the ADD or lighting current through it.
However the probability of this, is not the average failure rate.
When downloaded from the WEB, this document is uncontrolled and the responsibility rests with the user
to ensure it is in line with the authorized version on the WEB.