Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

PMF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

PMF range

TECHNICAL CHARACTERISTICS
Positive tubular plates with special
alloy to reduce frequency of topping-
up intervals
Negative plates are of pasted grid type
with lead calcium alloy
Electrolyte: high purity sulphuric acid
solution with a specific gravity of 1.25
at 20°C
Separators are made of high quality
microporous material
Containers are of translucent plastic
material
FIAMM's PMF battery range can be used in Handles: many sizes have rope
handles which facilitates ease of
standby mode for long discharge rates or for
handling, installation and removal of
cycling applications. Its tubular positive plates
the batteries
with low antimony together with lead-calcium
negative plates guarantee an unsurpassed
cycle life and a long life even in the worst
operating conditions.
FIAMM has a program of continuous
improvement investing in manufacturing
processes, equipment and technology.
FIAMM's Standby Battery manufacture is in
compliance with ISO 9001 and ISO 14001
quality assurance standards. Our continuous
investment in battery technology is reflected
PRODUCT PLUS
by means of premium products that are of the
highest quality and reliability.
Safe
FIAMM's PMF tubular vented lead acid Reliability
Long life
batteries are the ideal energy source for many
Reduced maintenance
different standby applications. Design life > 15 years
PMF range 2007
10.06

TYPE NOMINAL NOMINAL CAPACITY WEIGHT WEIGHT DIMENSIONS (mm)


VOLTAGE in Ah at 20°C without with
electrolyte electrolyte
10 hours to 3 hours to 1 hour to
(Volt) 1.80 VPC 1.70 VPC 1.65 VPC (kg) (kg) L W H

12 PMF 25 12 25 20 15 7.5 14.5 260 175 240


12 PMF 50 12 50 40 30 14.5 22.5 310 178 240
12 PMF 75 12 75 60 45 20.0 32.5 510 175 245
12 PMF 100 12 100 80 60 28.0 44.0 510 216 245
12 PMF 125 12 125 100 75 34.0 53.5 510 278 256

FIAMM reserves the right to change or revise without notice any information or detail given in this pubblication
12 PMF 150 12 150 120 90 39.5 58.0 510 278 256
6 PMF 200 6 200 160 120 26.0 42.5 510 216 245
6 PMF 250 6 250 200 150 34.0 53.0 510 278 256
6 PMF 300 6 300 240 180 40.0 58.5 510 278 256

ELECTRICAL CHARACTERISTICS

FLOAT VOLTAGE PER CELL: 2.23 Volts


RECHARGE VOLTAGE PER CELL: 2.4 Volts
SELF DISCHARGE AT 20°C: < 2% a month at 20°C
MAXIMUM SHORT CIRCUIT CURRENT: 10 x C (Amperes) 10

INTERNAL RESISTANCE PER CELL: 0.16/C (Ohm) 10

www.fiamm.com