Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Sinamics G S Profinet Connection With Labview 20150904 v20 en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 30

Application description  01/2015

SINAMICS G/S: PROFINET


connection with LabVIEW
Application to connect SINAMICS converters with LabVIEW via a
standard Ethernet interface

http://support.automation.siemens.com/WW/view/en/99684399
Warranty and liability

Warranty and liability


Note The application examples are not binding and do not claim to be complete
regarding the circuits shown, equipping and any eventuality. These application
examples do not represent specific customer solutions, but are only intended to
provide support when it comes to typical tasks. You are responsible for the
proper operation of the described products. These application examples do not
relieve you of the responsibility in safely and professionally using, installing,
operating and servicing equipment. By using these application examples, you
agree that Siemens cannot be made liable for possible damage beyond the
liability clause described. We reserve the right to make changes to these
application examples at any time and without prior notice. If there are any
differences between the suggestions made in these application examples and
other Siemens publications, such as catalogs, the contents of the other
document(s) take priority.

We give no guarantee that the information contained in this document is complete,


accurate, or up-to-date.
We accept no liability for any damage or loss caused by the examples, information,
programs, planning data, or performance data described in this application
example, irrespective of the legal basis for claims arising from such damage or
loss, unless liability is mandatory. For example, according to the product liability
law, in cases of malfeasance, gross negligence, due to endangerment of life, body
or health, due to assumption of a guarantee for the properties of a product, due to
 Siemens AG 2015 All rights reserved

malicious concealment of a defect or due to violation of basic contractual


obligations. However, claims for indemnification based on breach of contract shall
be limited to liability for damages to the contract-specific, foreseeable damages,
provided there is no mandatory liability for intent, acts of gross negligence, harm to
the life, body and health of human beings. Any change to the burden of proof to
your disadvantage is not covered hereby.
Any form of duplication of these application examples or excerpts hereof is not
permitted without the express consent of Siemens Industry Sector.

Security Siemens provides products and solutions with industrial security functions that
informati support the secure operation of plants, solutions, machines, devices, and/or
on networks. They are important components in a holistic industrial security
concept. With this in mind, Siemens products and solutions undergo continuous
development. Siemens recommends strongly that you regularly check for
product updates.
For the secure operation of Siemens products and solutions, it is necessary to
take suitable preventive action (e.g. cell protection concept) and integrate each
component into a holistic, state-of-the-art industrial security concept. Any third-
party products that may be in use must also be taken into account. For more
information about industrial security, visit
http://www.siemens.com/industrialsecurity
To receive information about product updates on a regular basis, register for our
product newsletter. For more information, visit
http://support.automation.siemens.com.

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 2
List of contents

List of contents
Warranty and liability................................................................................................... 2
1 Task ..................................................................................................................... 4
1.1 Overview............................................................................................... 4
2 Solution............................................................................................................... 6
2.1 Overview............................................................................................... 6
2.2 Hardware and software components ................................................... 7
2.2.1 Validity .................................................................................................. 7
2.2.2 Components used ................................................................................ 7
3 Principle of operation ........................................................................................ 9
3.1 General overview ................................................................................. 9
3.2 Functionality of the basic functions ...................................................... 9
3.2.1 Program details about the block Start.vi .............................................. 9
3.2.2 Program details about the block Stop.vi ............................................... 9
3.2.3 Program details about the block PNIO_STD_TG1.vi ......................... 10
3.2.4 Program details about block PNIO_STD_TG111.vi ........................... 10
3.2.5 Program details about block PNIO_FREE_TG.vi .............................. 11
3.2.6 Program details about block PNIO_READ.vi ..................................... 11
3.2.7 Program details about block PNIO_WRITE.vi.................................... 12
3.2.8 Program details about the block DESCALE_SGL.vi .......................... 12
3.2.9 Program details about the block DESCALE_DBL.vi .......................... 12
 Siemens AG 2015 All rights reserved

3.2.10 Program details about the block SCALE_SGL.vi ............................... 13


3.2.11 Configuring information ...................................................................... 13
3.3 Functionality of the application example ............................................ 13
3.3.1 Program details about the block Example_S120_ET200S.vi ............ 13
3.4 Functionality of the acyclic communication ........................................ 13
4 Installation and commissioning ..................................................................... 15
4.1 Installing the hardware ....................................................................... 15
4.2 Installing the software (download) ...................................................... 16
4.3 Commissioning ................................................................................... 17
5 Using the application ...................................................................................... 21
5.1 Overview............................................................................................. 21
5.2 Starting the PROFINET controller ...................................................... 22
5.3 Operating the basic positioner of the upper drive .............................. 23
5.4 Operating the speed setpoint of the lower drive ................................ 24
6 Acyclically reading and writing parameters ................................................. 25
6.1 Overview............................................................................................. 25
6.2 Starting the DPV1 task ....................................................................... 26
7 Error codes ....................................................................................................... 27
8 References ....................................................................................................... 30
9 Contact person ................................................................................................ 30
10 History............................................................................................................... 30

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 3
1 Task
1.1 Overview

1 Task
1.1 Overview
Introduction
The application supports you when connecting SINAMICS converters with
PROFINET interface to the LabVIEW software from National Instruments.
This facilitates cyclic I/O communication via any network interface of the PC being
used. LabVIEW operates in this case as PROFINET controller.
Non-cyclic communication via DPV1 is also possible.

Note All of the PROFINET I/O devices available in the hardware catalog of the TIA
Portal can be Incorporated.
The application is primarily intended to control SINAMICS converters.

Overview of the automation task


The following diagram provides an overview of the connection.
 Siemens AG 2015 All rights reserved

Fig. 1-1: Labview as PROFINET controller

PG/PC

PROFINET

I/O

SINAMICS G/S

Description of the automation task


LabVIEW is a graphic programming system from National Instruments. LabVIEW
programs are called Virtual Instruments or simply VIs. They comprise two
components: The front panel accommodates the user interface, the block diagram
shows the graphic program code.
LabVIEW is frequently used as calculation and simulation tool for tests stands. In
order to integrate real hardware (e.g. converters) into the simulation or
measurement, it is necessary that this hardware is directly connected to LabVIEW.

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 4
1 Task
1.1 Overview

Frequency, it is sufficient to operate the SINAMICS drive with closed-loop speed or


torque control – or to use the integrated basic positioner without placing any real-
time demands on the communication.
PROFINET is one of the options available for establishing a connection between
SINAMICS converters and LabVIEW via a standard Ethernet interface.
This application allows this communication path to be used.
 Siemens AG 2015 All rights reserved

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 5
2 Solution
2.1 Overview

2 Solution
2.1 Overview
Schematic
The application comprises a DLL, which is integrated in LabVIEW and which is
executed there. This provides functions for communication with PROFINET I/O
devices directly from LabVIEW.

Design
The DLL provided by the application is essentially based on the Siemens
PROFINET driver for controllers.
An interface to the LabVIEW has been created via the IO base user programming
interface.
For simpler handling, the application example VIs are provided for standard
Siemens telegrams
• Standard telegram 1 (closed-loop speed control)
• Standard telegram 111 (EPOS operation)
• Free telegram configuration
their interface emulates 1:1 the SINAMICS telegram interface.
 Siemens AG 2015 All rights reserved

For non-cyclic communication, example VI is provided to read/write parameters;


this can be expanded when required.

Advantages
The application described here offers you the following advantages
• Shorter time and lower costs when implementing the solution
• Simple integration of the communication driver
• Simple control of SINAMICS drives from LabVIEW
• Integration of additional PROFINET IO devices in LabVIEW
• Connection via standard Ethernet interface

Restriction
This application does not contain a description of:
• how to use LabVIEW
• commissioning SINAMICS drive systems
• using STEP 7 in the TIA Portal
• DPV1 parameter request and response

Knowledge required
It is assumed that readers have basic knowledge about LabVIEW. Examples
showing the integration into LabVIEW are provided; however, the user is
responsible for the integration in his particular application.
Further, it is assumed that readers are knowledgeable about configuring
PROFINET nodes in the TIA Portal, as well as commissioning SINAMICS
converters and STARTER / SCOUT.

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 6
2 Solution
2.2 Hardware and software components

2.2 Hardware and software components


2.2.1 Validity

This application is valid for


• LabVIEW from version 2013 and higher
• SINAMICS drives
 S120 CU320-2 PN, CU310-2 PN from firmware V4.5 and higher
 S120 CU320-2 DP with CBE20 from firmware V4.5 and higher
 S110 CU305 PN from firmware V4.4 and higher
 G120 CU250S-2 PN, CU240E-2 PN, CU240E-2 PN-F
from firmware V4.5 and higher
 G120P CU230P-2 PN from firmware V4.5 and higher
 G120C PN from firmware V4.5 and higher
• Step7 Professional from V12 (a license is not required)

2.2.2 Components used

The application was created with the following components:


 Siemens AG 2015 All rights reserved

Hardware components
Table 2-1
Component Qty. Article number Note
SINAMICS 1 6ZB2480-0CN00 The demonstration case
demonstration case comprises the following
components:
6SL3040-1MA01-0AA0
6SL3054-0EG01-1BA0
6SL3130-6AE15-0AB1
6SL3120-2TE13-0AA4
6SL3055-0AA00-5BA3
1FK7022-5AK71-1LG0
1FK7022-5AK71-1AG3
ET200S 1 Any distributed I/O can be
optionally integrated

Software components
Table 2-2
Component Qty. Article number Note
LabVIEW 2013 1
Siemens PROFINET 1 6ES7195-3AA05-0XA0 Runtime license must be
driver runtime purchased
WinPCap v4.1.3 1 Freely available
VC++ 2010 SP1 1 Freely available
redistributable
STEP 7 Professional 1 A license is not required

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 7
2 Solution
2.2 Hardware and software components

Component Qty. Article number Note


V12 Download
Sinamics STARTER 1 Download
v4.4
PN driver HSP for 1
TIA Portal V12

Sample files and projects


The list below contains all the files and projects used in this example.

Table 2-3
Component Note
99684399_PNIO_BIB_v20_EN.zip This zipped file contains the LabVIEW
library.
99684399_PN-Driver_HSP.zip This zipped file contains the HSP for
the TIA Portal V12.
99684399_TIA_Project.zip This zipped file contains the TIA V12
project.
 Siemens AG 2015 All rights reserved

99684399_Starter_Project.zip This zipped file contains the Starter


project.
99684399_DOKU_v20_EN.pdf This document.

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 8
3 Principle of operation
3.1 General overview

3 Principle of operation
3.1 General overview
Fig. 3-1: Flowchart

User program Communication PROFINET IO


driver device

LabVIEW DLL Drive

The DLL serves as the interface between the LabVIEW user program and the
PROFINET IO devices. It provides functions, which control the communication and
allow cyclic IO data to be transferred.

3.2 Functionality of the basic functions


 Siemens AG 2015 All rights reserved

The complete functionality of the application is provided by the DLL, which is


integrated into LabVIEW. The functions contained in the DLL control the
initialization of the IO controller and the data transfer.
To use these functions, preconfigured VIs are available for LabVIEW; they correctly
call the DLL functions, and can be integrated in the actual LabVIEW user program.
The function and interface of each VI are described in the following sections.

3.2.1 Program details about the block Start.vi

This function initializes the PROFINET controller. The Ethernet interface to be used
is selected using the MAC address of the interface.

Table 3-1 - Interface of the VI:


Name Type Data Function
type

MAC address Input char[ ] MAC address of the Ethernet interface

error_code Output uint_32 Error number

3.2.2 Program details about the block Stop.vi

This function stops the execution of the PROFINET controller. The Ethernet
interface to be used is selected using the MAC address of the interface.

Table 3-2 - Interface of the VI:


Name Type Data Function
type

error_code Output uint_32 Error number

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 9
3 Principle of operation
3.2 Functionality of the basic functions

3.2.3 Program details about the block PNIO_STD_TG1.vi

This function is used for communication based on "Standard telegram 1".

Table 3-3 – Interface of the VI:


Name Type Data Function
type

input_address Input uint_32 Start address of the input memory area

output_address Input uint_32 Start address of the output memory area

STW1 Input uint_16 Control word 1

NSOLL_A Input uint_16 Setpoint speed

ZSW1 Output uint_16 Status word 1

NIST_A Output uint_16 Actual speed

state Output bool Read/write status

error_read Output uint_32 Error has occurred when reading

error_write Output uint_32 Error has occurred when writing


 Siemens AG 2015 All rights reserved

3.2.4 Program details about block PNIO_STD_TG111.vi

This function is used for communication based on "Standard telegram 111".

Table 3-4 - Interface


Name Type Data Function
type

input_address Input uint_32 Start address of the input memory area

output_address Input uint_32 Start address of the output memory area

STW1 Input uint_16 Control word 1

POS_STW1 Input uint_16 Pos. control word 1

POS_STW2 Input uint_16 Pos. control word 2

STW2 Input uint_16 Control word 2

OVERRIDE Input uint_16 Scaling factor (100% = 0x4000h)

MDI_TARPOS Input uint_32 Setpoint position

MDI Input uint_32 Set velocity


VELOCITY

MDI_ACC Input uint_16 Acceleration

MDI_DEC Input uint_16 Delay

user_write Input uint_16 Freely assignable word, user defined

ZSW1 Output uint_16 Status word 1

POS_ZSW1 Output uint_16 Pos. status word 1

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 10
3 Principle of operation
3.2 Functionality of the basic functions

Name Type Data Function


type

POS_ZSW2 Output uint_16 Pos. status word 2

ZSW2 Output uint_16 Status word 2

MELDW Output uint_16 Message word

XIST_A Output uint_32 Actual position

NIST_B Output uint_32 Actual speed

FAULT_CODE Output uint _16 Error code

WARN_CODE Output uint_16 Alarm code

user_read Output uint_16 Freely assignable word, user defined

state Output bool Read/write status

error_read Output uint_32 Error has occurred when reading

error_write Output uint_32 Error has occurred when writing

3.2.5 Program details about block PNIO_FREE_TG.vi


 Siemens AG 2015 All rights reserved

This function is used for communication based on "Free telegram configuration


with BICO".

Table 3-5 – Interface of the VI:


Name Type Data Function
type

input_address Input uint_32 Start address of the input memory area

output_address Input uint_32 Start address of the output memory area

number_bytes Input uint_32 Number of bytes to be written

data_write Input uint_8 [ ] Data to be written

data_read Output uint_8 [ ] Read data

state Output bool Read/write status

error_read Output uint_32 Error has occurred when reading

error_write Output uint_32 Error has occurred when writing

3.2.6 Program details about block PNIO_READ.vi

This function is used to read from a PROFINET IO device.

Table 3-6 – Interface of the VI:


Name Type Data Function
type

input_address Input uint_32 Start address of the input memory area

number_bytes Input uint_32 Number of bytes to be read

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 11
3 Principle of operation
3.2 Functionality of the basic functions

Name Type Data Function


type

data_read Output uint_8 [ ] Read data

state Output bool Read status

error_write Output uint_32 Error has occurred when reading

3.2.7 Program details about block PNIO_WRITE.vi

This function is used to write to a PROFINET IO device.

Table 3-7 – Interface of the VI:


Name Type Data Function
type

output_address Input uint_32 Start address of the output memory area

number_bytes Input uint_32 Number of bytes to be written

data_write Input uint_8 [ ] Data to be written

state Output bool Write status


 Siemens AG 2015 All rights reserved

error_write Output uint_32 Error has occurred when writing

3.2.8 Program details about the block DESCALE_SGL.vi

This VI descales a word value (e.g. speed) to 0x4000h.

Table 3-8 - Interface of the VI:


Name Type Data Function
type

Input Input int16 Scaled value

Reference Input float Reference value, used as basis for scaling


value

Output Output float Descaled value

3.2.9 Program details about the block DESCALE_DBL.vi

This VI descales a double word value (e.g. speed) to 0x40000000h.

Table 3-9 - Interface of the VI:


Name Type Data Function
type

Input Input int32 Scaled value

Reference Input double Reference value, used as basis for scaling


value

Output Output double Descaled value

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 12
3 Principle of operation
3.3 Functionality of the application example

3.2.10 Program details about the block SCALE_SGL.vi

This VI scales a word value (e.g. speed) to 0x4000h.

Table 3-10 - Interface of the VI:


Name Type Data Function
type

Input Input uint_16 Unscaled value

Reference Input float Reference value, used as basis for scaling


value

Output Output uint_16 Scaled value

3.2.11 Configuring information

When compiling the communication VIs for the complete PROFINET network, it
must be ensured that the PROFINET controller is first started, and this must be
executed again before closing the application.
In between opening and closing the PROFINET controller, the communication VIs
must be cyclically called (e.g. in a loop).
 Siemens AG 2015 All rights reserved

3.3 Functionality of the application example


The functionality and the interface of the application example are described in the
following sections.

3.3.1 Program details about the block Example_S120_ET200S.vi

In the VI that is associated with the application example, communication is cyclic.


As a first step, the PROFINET controller is initialized, then the communication
functions cyclically run in a "while" loop until the user stops the execution. The
PROFINET controller is terminated before exiting the VIs.

Communication is established to the following nodes/stations:


- S120 demonstration case – axis 1:
communication using standard telegram 111 (control of EPOS)
- S120 demonstration case – axis 2:
communication using standard telegram 1 (speed setpoint)
- ET200S – 1 input module and 1 output module (each 1 byte):
communication via the VIs PNIO_READ.vi and PNIO_WRITE.vi

3.4 Functionality of the acyclic communication


In addition to cyclic PNIO communication, there is the option of reading and writing
the parameter values of the SINAMICS converter.
Just the same as when communicating with a SIMATIC S7, a request block is
required, that must be transferred to the SINAMICS drive.
The evaluation of the response is realized using a user event returned in LabVIEW.

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 13
3 Principle of operation
3.4 Functionality of the acyclic communication

Additional details regarding the structure of the DPV1 parameter task and the
DPV1 parameter response can be reviewed in the "Function Manual Drive
Functions".
The attached example VI is used to read or write a parameter. The data type of the
read parameter is automatically identified, and the read value is converted into a
32-bit floating point number.
 Siemens AG 2015 All rights reserved

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 14
4 Installation and commissioning
4.1 Installing the hardware

4 Installation and commissioning


The prerequisites and steps necessary to run the application are explained in this
section.

4.1 Installing the hardware


The following diagram shows the hardware configuration of the application. The
PC, SINAMICS S120 and ET200S (optional) components belonging to the
application must be connected to via PROFINET.

Fig. 4-1

PROFINET
 Siemens AG 2015 All rights reserved

Optiona

Table 4-1
No. Action
1. Connect the PC that you are using with any PROFINET interface of the CU320-2 PN of the
SINAMICS demonstration case. Any Ethernet interface of the PC can be used.
2. Connect the ET200S with any PROFINET interface of the CU320-2 of the SINAMICS
demonstration case. Connecting the ET200S is optional, and is not required to operate the
converter. This is not a component of the application example in LabVIEW.
3. You require STEP7 Professional V13 on your engineering PC in order to configure the PC
station. This should not correspond to the LabVIEW-PC, and must be connected in the
PROFINET network in addition to the components mentioned above.
There are 2 options here:
- If an ET200S is being used, then connect the engineering PC with the free PROFINET
interface of the ET200s
- If an ET200S is not being used, then connect the engineering PC with the free
PROFINET interface of the CU320-2 PN of the SINAMICS demonstration case.
If you want to use one single PC station for the engineering and LabVIEW, then this PC station
must have 2 Ethernet interfaces. In this case, connect the two interfaces with the PROFINET
network.

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 15
4 Installation and commissioning
4.2 Installing the software (download)

4.2 Installing the software (download)


This chapter describes the steps required to install the code example.

Note At the present time, the hardware support package required for the application is
not available for STEP7 V13. STEP 7 Professional V12 is required to configure
the PROFINET network.

Table 4-2
No. Action
4. Install LabVIEW in a version >2013 on the PC you are using.
5. Install WinPCap with version 4.1.3 on the PC you are using.
WinPCap can be downloaded from here:
http://www.winpcap.org/
6. Install Microsoft Visual C++ 2010 SP1 Redistributable Package (x86) on the PC you are using.
This can be downloaded here:
http://www.microsoft.com/en-US/download/details.aspx?id=8328
7. Install STEP 7 Professional V12 on your engineering PC.
This can be downloaded here:
http://support.automation.siemens.com/WW/view/en/78793685
 Siemens AG 2015 All rights reserved

8. Unzip the content of the 99684399_PN-Driver_HSP.zip to a temporary folder.


To install the HSP, proceed as described in the following FAQ:
http://support.automation.siemens.com/WW/view/en/57424910
9. Unzip the content of the 99684399_PNIO_BIB_v20.zip to folder "user.lib" in the LabVIEW
installation directory.
As default, this is as follows:
„C:/Program Files/National Instruments/LabVIEW 2013/user.lib/“

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 16
4 Installation and commissioning
4.3 Commissioning

4.3 Commissioning
Table 4-3
No. Action
10. In the first step, the MAC address of the Ethernet interface selected for PROFINET
communication must be obtained. To do this, the PC must be connected to the CU320-2 and the
operating voltage connected to the SINAMICS Control Unit.
The MAC address of the interface can be identified as follows:
- Right-click on the network symbol in the taskbar and you go to the Network and Sharing
Center

- Click on change adapter settings


 Siemens AG 2015 All rights reserved

- Right-click on the network connection and then open the network connection status.

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 17
4 Installation and commissioning
4.3 Commissioning

No. Action
- On the status page, click on the Details button

- The MAC address of the interface can be taken from the window that then opens. This is
 Siemens AG 2015 All rights reserved

subsequently required for communication with the PROFINET I/O devices from
LabVIEW.

11. Please deactivate all of the elements used by the network connection. To do this, proceed as
follows:
- As described in the previous step, return to network connections.
- Right-click on the network connection and then open the network connection properties.

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 18
4 Installation and commissioning
4.3 Commissioning

No. Action
- Deactivate all elements:
 Siemens AG 2015 All rights reserved

12. Set the IP address of the Ethernet interface of the engineering PC as follows:
- Go to the properties of the Ethernet interface of the engineering PC analogously to the
previous description.
- Select element "Internet protocol Version 4 (TCP/Ipv4)“ and open the properties.
- Here, enter the following addresses:
IP address: 192.168.0.100
Subnet mask: 255.255.255.0
- Save the changes.
13. Unzip the archive that has been made available [Entry-ID]_TIA_Project.zip.
Start the TIA Portal and open the project. The components required for the example are already
preconfigured in the project.
The following settings are relevant for the communication:
- IP addresses:

LabVIEW PC: 192.168.0.1


SINAMICS S120: 192.168.0.10

- PROFINET name:

LabVIEW PC: labview


SINAMICS S120: s120

After the configuration has been completed, the LabVIEW PC station must be compiled. In the
"Devices & networks" view, select the station and in the Edit menu, select the Compile function.
After compilation has been completed, the configuration XML required for LabVIEW is provided
in the following directory:
"<Project directory>/AdditionalFiles/PNDriver/"
Please copy the .XML file generated in this directory to directory ".../user.lib/PNIO/" inserted
under Point 9.
14. Then assign the PROFINET IO devices their PROFINET names and IP addresses.

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 19
4 Installation and commissioning
4.3 Commissioning

No. Action
15. Unzip the 99684399_Starter_Project.zip archive provided.
Start STARTER / SCOUT and open the project.
Then transfer the project to the SINAMICS converter.

After these points have been completed, the components have been setup and the application
can be used in LabVIEW. In the next chapter we will tell you how the supplied LabVIEW library
is structured and how the application can be used.
 Siemens AG 2015 All rights reserved

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 20
5 Using the application
5.1 Overview

5 Using the application


5.1 Overview
The structure of the application example is explained in this section and you are shown how
to operate the LabVIEW user-interface.

Overview and description of the user interface

Fig. 5-1 - User interface of the application example


 Siemens AG 2015 All rights reserved

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 21
5 Using the application
5.2 Starting the PROFINET controller

As shown in the diagram, the user interface comprises 3 components:


- The first component is used to operate the PROFINET controller.
- The second component is used to operate the basic positioner via direct
setpoint input/MDI (upper axis of the S120 demonstration case).
- The third component is used to operate the speed-controlled axis (lower axis of
the S120 demonstration case)
A section of the program code behind the user interface – the LabVIEW block
diagram – is shown in the following figure:

Fig. 5-2 – Section of the LabVIEW block diagram of the application example
 Siemens AG 2015 All rights reserved

The calls of the two VIs "PNIO_STD_TG111.vi" and "PNIO_STD_TG111.vi" can be


identified in the block diagram. These make up the composition of the telegram and
transfer the data to the DLL. The entry fields with a red border are used to enter the
I/O addresses, set in the TIA Portal for the I/O devices. These do not have to be
changed to use the application example.
The individual steps that are required to use the application example are described
in the following sections.

5.2 Starting the PROFINET controller


The following steps are required to activate the PROFINET controller (corresponds
to the RUN state of an S7-PLC):

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 22
5 Using the application
5.3 Operating the basic positioner of the upper drive

Table 7-1
No. Action Remark
1. Enter the MAC address of the network The MAC address must be entered in the
interface, read out under Point 4.3, Step 10, following format:
which should be used for the PROFINET 00:ab:00:ab:00:ab
communication, in the field MAC address of The individual groups are separated by a
the 1st component of the LabVIEW user colon, lowercase letters are used.
interface of the application exampleVIs
2. Set switch "Start" of the 1st component of the
LabVIEW user interface to "ON"
3. Start the execution of the VIs If all of the components have been correctly
connected and commissioned, a value of 0 is
displayed in field "start_error". The status
fields "state" and "state2" of the drives are
green, and the fault fields of the drives also
indicate a value of 0x0h.
(It can take some time to establish
communications to the drive device. During
this time, fault 0x301h may be displayed. This
disappears as soon as the connection has
been established to the IO device).
 Siemens AG 2015 All rights reserved

5.3 Operating the basic positioner of the upper drive


The application example involves operating the basic positioner with the most
necessary operating functions via direct setpoint input/MDI. Other functions can
also be used; however, in this case, a dedicated virtual instrument must be
programmed.
The following table lists the various ways in which the application example can be
operated:

Table 7-2
No. Action Remark
1. Press the "ON/OFF" button Switch on and switch off the drive object using
OFF1.
2. Press the "Acknowledge" button Acknowledge active faults in the drive object
3. Press the "Jog 1" button Jogging in direction 1 with the jog velocity set
in the drive object
4. Press the "Jog 2" button Jogging in direction 2 with the jog velocity set
in the drive object
5. Press the "Positioning type" button Changing the positioning type
"ON" = absolute positioning
6. Press the "Activate traversing task" button Starting a traversing task
7. "OVERRIDE" entry field Setting the velocity override
8. "Acceleration" entry field Scaling factor of the acceleration set in the
drive object
9. "Deceleration" entry field Scaling factor of the deceleration set in the
drive object
10. "Target position" entry field Entry of the target position in LU
11. "Velocity" entry field Enter the required traversing velocity in 1000
LU/min

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 23
5 Using the application
5.4 Operating the speed setpoint of the lower drive

5.4 Operating the speed setpoint of the lower drive


The application example involves operating the lower drive by entering a speed
setpoint. The following table lists the various ways in which the application example
can be operated:

Table 7-3
No. Action Remark
1. Press the "ON/OFF" button Switch on and switch off the drive object using
OFF1.
2. Press the "Acknowledge" button Acknowledge active faults in the drive object
3. "Setpoint speed" entry field Enter the required setpoint speed in rpm
 Siemens AG 2015 All rights reserved

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 24
6 Acyclically reading and writing parameters
6.1 Overview

6 Acyclically reading and writing parameters


6.1 Overview
The structure of the VI example "PNIO_DPV1.vi" for acyclic communication is shown in this
section, and its operation explained.

Overview and description of the user interface

Fig. 6-1 - User interface of the application example


 Siemens AG 2015 All rights reserved

As shown in the diagram, the following information is required for acyclically


reading and writing parameters.
- HW identifier
The HW identifier is used to identify the drive object. The HW identifier of the
ModulAccessPoints of the drive object to be addressed is required here.
- Drive object number
Number assigned in the drive for the drive object.
- Write length
The data block length for the parameter task must be specified here
- Function selection
Selection whether to be read or written
- Parameter number
Number of the parameter to be accessed

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 25
6 Acyclically reading and writing parameters
6.2 Starting the DPV1 task

- Value to be written
Value to be written to the parameter

A section of the program code behind the user interface – the LabVIEW block
diagram – is shown in the following figure:

Fig. 6-2 – Section of the LabVIEW block diagram in the VI example


 Siemens AG 2015 All rights reserved

6.2 Starting the DPV1 task


The read/write task is started with the specified data by executing the VI example.
The read data are evaluated and displayed.
All of the data required for assembling the data block and the data types used can
be taken from the "Sinamics S120 Function Manual Drive Functions"
documentation that was mentioned previously.

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 26
7 Error codes

7 Error codes
The possible error codes of the communication driver are listed in the following
table.
Table 6-1
Error name Error code Remark
PNIO_OK 0x00000000 success
PNIO_WARN_IRT_INCONSISTENT 0x00000010 IRT Data may be inconsistent
PNIO_WARN_NO_SUBMODULES 0x00000011 no submodules to be updated
PNIO_WARN_LOCAL_STATE_BAD 0x00000012 data was written with local state
PNIO_S_BAD, because not all
components of splitted module have
local state PNIO_S_GOOD
PNIO_ERR_PRM_HND 0x00000101 parameter Handle is illegal
PNIO_ERR_PRM_BUF 0x00000102 parameter buffer is NULL-Ptr
PNIO_ERR_PRM_LEN 0x00000103 parameter length is wrong
PNIO_ERR_PRM_ADD 0x00000104 parameter address is wrong
PNIO_ERR_PRM_RSTATE 0x00000105 parameter remote state is NULL-Ptr
PNIO_ERR_PRM_CALLBACK 0x00000106 parameter cbf is illegal
 Siemens AG 2015 All rights reserved

PNIO_ERR_PRM_TYPE 0x00000107 parameter type has no valid value


PNIO_ERR_PRM_EXT_PAR 0x00000108 parameter ExtPar has no valid value
PNIO_ERR_PRM_IO_TYPE 0x00000109 parameter PNIO_ADDR::IODataType
is wrong
PNIO_ERR_PRM_CP_ID 0x0000010A parameter CpIndex is wrong,
probably driver is not loaded
PNIO_ERR_PRM_LOC_STATE 0x0000010B parameter IOlocState has no valid
value
PNIO_ERR_PRM_REC_INDEX 0x0000010C parameter RecordIndex has no valid
value
PNIO_ERR_PRM_TIMEOUT 0x0000010D parameter timeout has no valid
value
PNIO_ERR_PRM_DEV_ANNOTATION 0x0000010E parameter annotation has no valid
value
PNIO_ERR_PRM_DEV_STATE 0x0000010F parameter state has no valid value
PNIO_ERR_PRM_PCBF 0x00000110 parameter pCbf has no valid value
PNIO_ERR_PRM_MAX_AR_VALUE 0x00000111 parameter MaxAR has no valid value
PNIO_ERR_PRM_ACCESS_TYPE 0x00000112 parameter AccessType has no valid
value
PNIO_ERR_PRM_POINTER 0x00000113 an invalid pointer was passed
PNIO_ERR_PRM_INVALIDARG 0x00000114 an invalid argument was passed
PNIO_ERR_PRM_MEASURE_NUMBER 0x00000115 wrong Measure No in cycle statistics,
must be -1 (actual measure) up to 49
PNIO_ERR_PRM_CYCLE_OFFSET 0x00000116 wrong Offset for cycle info buffer
(must be 0 to 19)
PNIO_ERR_PRM_ROUTER_ADD 0x00000117 address used by io router

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 27
7 Error codes

PNIO_ERR_WRONG_HND 0x00000201 unknown handle


PNIO_ERR_MAX_REACHED 0x00000202 maximal number of opens reached;
close unused applications
PNIO_ERR_CREATE_INSTANCE 0x00000203 fatal error, reboot your system
PNIO_ERR_MODE_VALUE 0x00000204 parameter mode has no valid value
PNIO_ERR_OPFAULT_NOT_REG 0x00000205 register OPFAULT callback before
register STARTOP callback
PNIO_ERR_NEWCYCLE_SEQUENCE_REG 0x00000206 register NEWCYCLE callback before
register STARTOP callback
PNIO_ERR_NETWORK_PROT_NOT_AVAI 0x00000207 network protocol not available,
LABLE check card configuration

PNIO_ERR_NO_CONNECTION 0x00000301 device data not available, because


device is not connected to controller
PNIO_ERR_OS_RES 0x00000302 fatal error, no more operation
system resources available
PNIO_ERR_ALREADY_DONE 0x00000303 action was already performed
PNIO_ERR_ALLREADY_DONE
PNIO_ERR_NO_CONFIG 0x00000304 no configuration for this index
available
 Siemens AG 2015 All rights reserved

PNIO_ERR_SET_MODE_NOT_ALLOWED 0x00000305 PNIO_set_mode not allowed, use


PNIO_CEP_MODE_CTRL by
PNIO_controller_open
PNIO_ERR_DEV_ACT_NOT_ALLOWED 0x00000306 PNIO_device_activate not allowed,
use PNIO_CEP_MODE_CTRL by
PNIO_controller_open
PNIO_ERR_NO_LIC_SERVER 0x00000307 license server not running, check
your installation
PNIO_ERR_VALUE_LEN 0x00000308 wrong length value
PNIO_ERR_SEQUENCE 0x00000309 wrong calling sequence
PNIO_ERR_INVALID_CONFIG 0x0000030A invalid configuration, check your
configuration
PNIO_ERR_UNKNOWN_ADDR 0x0000030B address unknown in configuration,
check your configuration
PNIO_ERR_NO_RESOURCE 0x0000030C no resource too many requests been
processed
PNIO_ERR_CONFIG_IN_UPDATE 0x0000030D configuration update is in progress
or CP is in STOP state, try again later
PNIO_ERR_NO_FW_COMMUNICATION 0x0000030E no communication with firmware,
reset cp or try again later
PNIO_ERR_STARTOP_NOT_REGISTERED 0x0000030F no synchronous function allowed,
use PNIO_CEP_SYNC_MODE by
PNIO_controller_open or
PNIO_device_open
PNIO_ERR_OWNED 0x00000310 interface-submodule cannot be
removed because it is owned by an
AR

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 28
7 Error codes

PNIO_ERR_START_THREAD_FAILED 0x00000311 failed to start thread, probably by


lack of pthread resources
PNIO_ERR_START_RT_THREAD_FAILED 0x00000312 failed to start realtime thread,
probably you need root capability to
do it
PNIO_ERR_DRIVER_IOCTL_FAILED 0x00000313 failed to ioctl driver, probably API
version mismatch
PNIO_ERR_AFTER_EXCEPTION 0x00000314 exception occurred, save exception
info (see manual) and reset cp
PNIO_ERR_NO_CYCLE_INFO_DATA 0x00000315 no cycle data available
PNIO_ERR_SESSION 0x00000316 request belongs to an old session
PNIO_ERR_ALARM_DATA_FORMAT 0x00000317 wrong format of alarm data
PNIO_ERR_ABORT 0x00000318 operation was aborted
PNIO_ERR_CORRUPTED_DATA 0x00000319 data are corrupter or have wrong
format
PNIO_ERR_FLASH_ACCESS 0x0000031A error by flash operations
PNIO_ERR_WRONG_RQB_LEN 0x0000031B wrong length of request block at
firmware interface, firmware not
compatible to host sw
PNIO_ERR_NO_RESET_VERIFICATION 0x0000031C reset request was sent to firmware,
 Siemens AG 2015 All rights reserved

but firmware rut up can't be verified


PNIO_ERR_INTERNAL 0x000003FF fatal error, contact SIEMENS hotline
PNIO_ERR_MAC_ADRESS_NOT_FOUND 0x00000401 the entered mac-address could not
be found
PNIO_ERR_XML_NOT_FOUND 0x00000402 the XML-File can not be opened

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 29
8 References

8 References
Table 9-1
Topic Title
\1\ Siemens Industry http://support.automation.siemens.com
Online Support
\2\ SINAMICS S120 http://support.automation.siemens.com/WW/view/en/49084671
Function Manual
Drive Functions
\3\ Download page of http://support.automation.siemens.com/WW/view/en/99684399
the article
\4\ SINAMICS http://siemens.com/sinamics-applications
application
examples

9 Contact person
Siemens AG
Industry Sector
I DT MC PMA APC
Frauenauracher Strasse 80
D - 91056 Erlangen, Germany
 Siemens AG 2015 All rights reserved

E-mail: tech.team.motioncontrol@siemens.com

10 History
Table 11-1
Version Date Revision
V1.0 08/2014 First Edition
V2.0 01/2015 Examples of acyclic communication

SINAMICS G/S: Control with LabVIEW via PROFINET


Entry ID: 99684399, V2.0, 01/2015 30

You might also like