XQ2000 Auto Paralleling - Quick Start v1.3 PDF
XQ2000 Auto Paralleling - Quick Start v1.3 PDF
XQ2000 Auto Paralleling - Quick Start v1.3 PDF
v1.3
Running: Running:
See ‘Common Start/Stop Instructions’ lower RH corner See ‘Common Start/Stop Instructions’ lower RH corner
Application Notes: Application Notes:
In single unit mode, the paralleling controller and In island mode, GPC (paralleling controller)
utility protective relay can be switched off if desired. performs real (kW) and reactive (kVar) load sharing
The unit will operate similar to a standard genset. with like units using independent load sharing
This switch is located behind the EMCP3 near the analog signals. GPC is backwards compatible with
terminal strip. legacy units for real power (kW) sharing.
Reactive (kVar) load sharing should be disabled
when paralleling with legacy units. The factory
default setting in the GPC is set to ‘disabled’.
4 9
5 8
6
7
1. “AUTO” lamp – This LED is lit when any of the conditions below are present:
Controller is performing auto synchronization (breaker is open). EMCP3.3 must be in AUTO mode and V&F built up
to normal.
Gen breaker is closed in either SINGLE UNIT or ISLAND MODE
Gen breaker is closed with request to run active in UTILITY PARALLEL MODE
Note: lamp goes off during ramp-down when unit is stopping
2. “ACTIVE” lamp – This LED is lit when not in setpoint programming mode using the keypad.
Note: does not indicate whether or not setpoint programming is in use by the PC interface.
3. “CB CLOSE CMD” lamp – This LED is lit when the controller is issuing a circuit breaker close signal.
Note: this will occur only when the LED SYNCHROSCOPE has the green LED lit (center position).
4. “Hz-, Hz+” lamps – These two lamps indicate when the controller is actively biasing the speed signal to the engine
control (Hz- is decreasing speed, Hz+ is increasing speed). When paralleled with other sources, indicates decreasing or
increasing generator real load (kW) contribution.
“V-, V+” lamps – These two lamps indicate when the controller is actively biasing the voltage regulator (V- is decreasing
voltage, V+ is increasing voltage). When paralleled with other sources, indicates decreasing or increasing generator
reactive (VAR) contribution.
5. “LED SYNCHROSCOPE” row of lamps – When the lights are moving left to right, the generator is moving faster than the
bus. When the lights are moving right to left, the generator is moving slower than the bus. The synchroscope is only
active when voltage is within 50%-125% rated and frequency is within +/- 2Hz. When the green LED (center position) is
lit then the gen is “in sync” with the bus.
6. “GEN CB CLOSED” lamp – This LED is lit when the generator breaker is closed.
8. “DIGIT” pushbutton – This button is used only when programming setpoints (ACTIVE lamp off). When pressing this
button, the number at which the cursor is currently located is increased by one digit.
Press “DIGIT” and “CLEAR | CURSOR” pushbuttons simultaneously to enter/exit setpoint programming mode.
Press “DISPLAY | SELECT” and “CLEAR | CURSOR” pushbuttons simultaneously to move back in the setpoints menu.
XQ2000 Auto Paralleling - Quick Start v1.3.doc Page 3 of 15
5
1
2 6
7
3
Potentiometer Baseload
(10 turn) Level
8 0, 0 400 kW
1, 0 460 kW
2, 0 525 kW
3, 0 600 kW
4, 0 690 kW
5, 0 795 kW
6, 0 920 kW
6, 55 1000 kW
9 7, 0 1075 kW
4 8, 0 1265 kW
9, 0 1515 kW
10, 0 1825 kW
1. “Utility Transfer Trip” lamp – This LED is lit when the customer’s utility transfer trip signal is present.
2. “Utility Breaker” lamp – This LED is lit when the utility breaker is closed.
Note: when this LED is lit and the Red LED on the breaker control switch (item #4) is lit then the generator is operating in
parallel with the utility source.
3. 86 Lockout Relay – This device performs fast response fault clearance by opening the generator breaker directly and
placing the engine in cooldown when a fault occurs as detected by the on-package utility protective relay or customer’s
utility transfer trip signal.
Note: the EMCP3 must be in STOP mode to allow the manual reset of the 86 lockout relay (this also resets fault alarms
in the UMR utility protective relay).
4. Circuit Breaker Switch – For automatic paralleling modes, this switch must be in the center position (red or green flag).
For manual paralleling modes, the generator breaker is signaled to close when this switch is held in the “close” position
and paralleling conditions are satisfied. This switch also provides a “pull-to-lock” feature that gives a constant trip signal
to the breaker to lockout operation. Breaker status is indicated by LED’s on the switch (green=open, red=closed).
Single Unit Mode: lamp is ON when the lead unit jumper is installed and goes OFF when the breaker closes.
Island Mode: lamp is ON when all units are in standby and at least one unit has the lead unit jumper installed
(NOTE: if all are not ON then inspect the interconnect wiring). When units are started this lamp turns OFF on all
except the unit with the lead unit jumper. If that unit fails to close, the permissive signal will transfer to the next unit
and this lamp will come ON in that unit. This lamp goes OFF when any unit is closed to the bus.
Utility Parallel Mode: this lamp should never be ON in this mode. If it is, then remove the lead unit jumper.
6. “Auto Start” lamp – This LED is lit when either a remote run request is present or the unit has been started using the
local start/stop switch.
IMPORTANT: verify the status of this lamp before placing the EMCP3 in auto mode. If this lamp is ON then the unit will
start once the EMCP3 is placed in auto.
7. Baseload potentiometer – This potentiometer is used to manually adjust the generator kW output (range of 400kW to
1825kW) when in parallel with the utility. This potentiometer is enabled by the left position of the switch below it (item
#8).
8. Baseload Select Switch – With this switch in the left position, the potentiometer (item #7) is used for baseload level
reference. In the right position, the setpoint in the GPC “Power Controller P set1” provides the baseload level reference.
9. Local Start/Stop Switch – This switch is used to locally run the unit in an auto paralleling mode. Requires EMCP3 in
AUTO mode.
XQ2000 Auto Paralleling - Quick Start v1.3.doc Page 4 of 15
Doghouse & Wall-Mount Components Layout
A1 A2 A3 A4 A5 A6
GPC:
Generator
Paralleling
Controller
UMR:
Utility
Multifunction
Relay
B2
B1
LOAD
Single Unit Mode - Manual Operation
Setup:
Switch OFF paralleling controls (B1)
Install ‘lead unit jumper’ (C)
¾ Configurations: CDVR (‘load compensation mode’=OFF)
Startup:
Press RUN on EMCP3 (A1) (engine will start immediately)
After engine is running at normal speed, observe generator voltage and frequency on EMCP3 screen
Adjust voltage and/or frequency, if necessary, using operator controls (A2)
Close generator breaker, when desired, using circuit breaker switch (A3)
Running:
Observe engine and generator parameters on EMCP3 screen to verify normal operating conditions
Shutdown:
Press STOP on EMCP3 (A1) (generator breaker will open immediately, engine will continue to run in cooldown mode
until cooldown time is elapsed)
LOAD
Single Unit Mode - Automatic Operation
Setup:
Switch OFF paralleling controls (B1)
Install ‘lead unit jumper’ (C)
Install wiring (C) to remote run request contact (i.e. Automatic Transfer Switch)
¾ Configurations: CDVR (‘load compensation mode’=OFF)
Startup:
Press AUTO on EMCP3 (A1)
Start engine by either:
a) Closing the remote run request contact
b) Switch local start/stop switch to ON (A4)
After engine is running at normal speed, generator breaker will close automatically to a dead bus
Running:
Observe engine and generator parameters on EMCP3 screen to verify normal operating conditions
Adjust voltage and/or frequency, if necessary, using operator controls (A2)
Shutdown:
Shutdown, by any means, will cause generator breaker to open immediately, engine will continue to run in cooldown
mode until cooldown time is elapsed:
a) Open the remote run request contact
b) Switch local start/stop switch to OFF (A4)
c) Press STOP on EMCP3 (A1)
LOAD
CAUTION: Verify phase rotation of generator matches that of the bus connection prior to paralleling units. Failure to
do so may result in damage to equipment.
Setup A: All paralleling units equipped with GPC Auto Paralleling controls:
Switch ON paralleling controls (B1)
Install ‘lead unit jumper’ in only one unit – the one closing to a dead bus (C)
Install kW (real) and kVAR (reactive) load share lines interconnected between units (C)
¾Configurations (all units): CDVR (‘load compensation mode’=OFF), GPC (‘Reactive Power Load Share’=ON)
Setup B: One or more paralleling units equipped with GPC Auto Paralleling controls and one or more paralleling units equipped with
LSM (Load Share Module):
Switch ON paralleling controls (B1)
Install ‘lead unit jumper’ in only one unit – the one closing to a dead bus (C)
Install kW (real) load share lines interconnected between units (C)
¾ Configurations (all units with LSM**): CDVR (‘load compensation mode’=DROOP),
LSM load share lines: 0-3V (0-2000kW)
¾ Configurations (all units with GPC): CDVR (‘load compensation mode’=DROOP), GPC (‘Reactive Power Load
Share’=OFF)
** Units equipped with touch-screen based swgr must have LSM enabled by installed ‘Rev Compatibility Mode’ jumper.
** NOTE: allows only passive freq. and phase synchronization in manual mode.
Running:
Observe engine and generator parameters on EMCP3 screen to verify normal operating conditions
Observe load sharing between units (operating in Setup A). If load balancing adjustment is desired, adjust the
following parameters in the GPC: ‘Active Load Share Factor’ (lower % puts more emphasis on kW sharing vs. desired
freq.) and/or ‘Reactive Load Share Factor’ (lower % puts more emphasis on VAR sharing vs. desired kVA)
Observe load sharing between units (operating in Setup B). If load balancing adjustment is desired, adjust the gain on
the LSM(s). Do not adjust parameters in the GPC. Verify LSM is setup correctly – see above!
Shutdown:
At each unit, press STOP on EMCP3 (A1) (generator breaker will open immediately, engine will continue to run in
cooldown mode until cooldown time is elapsed)
LOAD
CAUTION: Verify phase rotation of generator matches that of the bus connection prior to paralleling units. Failure to
do so may result in damage to equipment.
Setup A: All paralleling units equipped with GPC Auto Paralleling controls:
Switch ON paralleling controls (B1)
Install ‘lead unit jumper’ in only one unit – the one closing to a dead bus (C)
Install kW (real) and kVAR (reactive) load share lines interconnected between units (C)
Install lead-unit-select wiring interconnected between units (C) (for automatic transfer of dead-bus-close-permissive
signal from unit to unit upon occurrence of fail to parallel)
¾Configurations (all units): CDVR (‘load compensation mode’=OFF), GPC (‘Reactive Power Load Share’=ON)
Setup B: One or more paralleling units equipped with GPC Auto Paralleling controls and one or more paralleling units equipped with
LSM (Load Share Module):
Switch ON paralleling controls (B1)
Install ‘lead unit jumper’ in only one unit – the one closing to a dead bus (C)
Install kW (real) load share lines interconnected between units (C)
Install lead-unit-select wiring interconnected between units (C) (for automatic transfer of dead-bus-close-permissive
signal from unit to unit upon occurrence of fail to parallel)
¾ Configurations (all units with LSM**): CDVR (‘load compensation mode’=DROOP),
LSM load share lines: 0-3V (0-2000kW)
¾ Configurations (all units with GPC): CDVR (‘load compensation mode’=DROOP), GPC (‘Reactive Power Load
Share’=OFF)
** Units equipped with touch-screen based swgr must have LSM enabled by installed ‘Rev Compatibility Mode’ jumper.
Startup:
At each unit, press AUTO on EMCP3 (A1)
Start each engine by either:
a) Closing the remote run request contact
b) Switch local start/stop switch to ON (A4)
After lead unit is running at normal speed, generator breaker will close automatically to a dead bus**
All other units will auto-sync and close to the live bus
** If lead unit takes more than 45 sec. to close its breaker, the fail-to-parallel timer (FPT) will cause a shutdown and the permissive signal
will be transferred to the next unit allowing it to close to the dead bus. FPT is adjustable and is located inside the doghouse (RH side) (B2).
Running:
Observe engine and generator parameters on EMCP3 screen to verify normal operating conditions
Observe load sharing between units (operating in Setup A). If load balancing adjustment is desired, adjust the
following parameters in the GPC: ‘Active Load Share Factor’ (lower % puts more emphasis on kW sharing vs. desired
freq.) and/or ‘Reactive Load Share Factor’ (lower % puts more emphasis on VAR sharing vs. desired kVA)
Observe load sharing between units (operating in Setup B). If load balancing adjustment is desired, adjust the gain on
the LSM(s). Do not adjust parameters in the GPC. Verify LSM is setup correctly – see above!
Shutdown:
Shutdown, by any means, will cause generator breaker to open immediately, engine will continue to run in cooldown
mode until cooldown time is elapsed:
a) Open the remote run request contact
b) Switch local start/stop switch to OFF (A4)
c) Press STOP on EMCP3 (A1)
CAUTION: Verify phase rotation of generator matches that of the bus connection prior to paralleling units. Failure to
do so may result in damage to equipment.
Setup:
Switch ON paralleling controls (B1)
Verify GPC setpoint ‘Power controller P set1’ (default=1825kW) is set to desired baseload level
Verify GPC ‘Pow.fact.control Set point’ (default=i0.95) is set to desired power factor level**
Verify GPC ‘Power controller Ramp’ (default=10 kW/s) is set to desired (shared setpoint for soft load & soft unload)
Use 2-position switch to select either potentiometer or GPC setpoint control for baseload level reference (A5)***
Install wiring to ‘utility breaker aux’ contact (C) (intertie breaker, form a)
(Opt.) install wiring to utility equipment for ‘utility transfer trip’ contact (C) (form a)
¾ Configurations: CDVR (‘load compensation mode’=DROOP), GPC (‘Reactive Power Load Share’=OFF)
¾ Verify on-board utility protective relay (UMR) settings per site-specific requirements
** If VAR setpoint control is desired, make the following settings: GPC (‘Power Factor Control’=OFF), CDVR (‘VAR setpoint’=set to
desired, and ‘Operating Mode’=set to VAR.) No other changes are required.
*** If desired to disable the potentiometer, make the following settings: GPC (‘External setp. 4mA’=desired kW,
‘External setp. 20mA’=desired kW, and ‘Power controller P set1’=desired kW,) where ‘desired kW’ are all the same value. Verify GPC
settings are password protected.
** NOTE: allows only passive freq. and phase synchronization in manual mode.
Running:
Observe proper soft load to desired baseload level and then steady state PF and baseload control
Switch to potentiometer baseload level control is allowed at any time (A5) (soft ramp occurs between selections)
Shutdown:
Press STOP on EMCP3 (A1)
Generator will soft unload to 10% of rated (200kW), generator breaker will then trip open, and engine will continue to
run in cooldown mode until cooldown time is elapsed (‘pre-cooldown’ will be displayed on the EMCP3 engine overview
screen during soft unload)
CAUTION: Verify phase rotation of generator matches that of the bus connection prior to paralleling units. Failure to
do so may result in damage to equipment.
Setup:
Switch ON paralleling controls (B1)
Verify GPC setpoint ‘Power controller P set1’ (default=1825kW) is set to desired baseload level
Verify GPC ‘Pow.fact.control Set point’ (default=i0.95) is set to desired power factor level**
Verify GPC ‘Power controller Ramp’ (default=10 kW/s) is set to desired (shared setpoint for soft load & soft unload)
Use 2-position switch to select either potentiometer or GPC setpoint control for baseload level reference (A5)***
Install wiring to ‘utility breaker aux’ contact (C) (intertie breaker, form a)
(Opt.) install wiring to utility equipment for ‘utility transfer trip’ contact (C) (form a)
¾ Configurations: CDVR (‘load compensation mode’=DROOP), GPC (‘Reactive Power Load Share’=OFF)
¾ Verify on-board utility protective relay (UMR) settings per site-specific requirements
** If VAR setpoint control is desired, make the following settings: GPC (‘Power Factor Control’=OFF), CDVR (‘VAR setpoint’=set to
desired, and ‘Operating Mode’=set to VAR.) No other changes are required.
*** If desired to disable the potentiometer, make the following settings: GPC (‘External setp. 4mA’=desired kW,
‘External setp. 20mA’=desired kW, and ‘Power controller P set1’=desired kW,) where ‘desired kW’ are all the same value. Verify GPC
settings are password protected.
** If the unit takes more than 45 sec. to close its breaker, the fail-to-parallel timer (FPT) will cause a shutdown
Running:
Observe proper soft load to desired baseload level and then steady state PF and baseload control
Switch to potentiometer baseload level control is allowed at any time (A5) (soft ramp occurs between selections)
Shutdown:
Shutdown, by any means, will cause the generator to soft unload to 10% of rated (200kW), generator breaker will then
trip open, and engine will continue to run in cooldown mode until cooldown time is elapsed (‘pre-cooldown’ will be
displayed on the EMCP3 engine overview screen during soft unload):
a) Open the remote run request contact
b) Switch local start/stop switch to OFF (A4)
c) Press STOP on EMCP3 (A1)