The document provides technical specifications and details for a 300REOZD 4-Cycle Diesel generator set including its ratings, features, available controllers, and accessories.

The generator set has standby ratings of 300 kW at 60 Hz and 252 kVA at 50 Hz and prime power ratings of 255 kW at 60 Hz and 228 kVA at 50 Hz for various voltages.

The generator set has features such as an electronic governor for precise frequency regulation, brushless rotating-field generator, EPA-compliant engine, vibration isolation, one-year limited warranty, and more.

Model: 300REOZD

4-Cycle
190--600 V Diesel

Standard Features
D Kohler Co. provides one-source responsibility for the
generating system and accessories.
D The generator set and its components are prototype-tested,
Ratings Range factory-built, and production-tested.
60 Hz 50 Hz D The 60 Hz generator set offers a UL-2200 listing.
Standby: kW 280--300 252 D The generator set complies with ISO 8528-5, Class G2
kVA 350--375 315 requirements for transient performance in all generator set
Prime: kW 255--270 228 configurations. Select the Decision-Makert550 controller
kVA 319--338 285 for improved voltage regulation and ISO 8528-5, Class G3
compliance.
D The generator set accepts rated load in one step.
D The 60 Hz generator set engine is certified by the
Environmental Protection Agency (EPA) to conform to Tier 2
nonroad emissions regulations.
D A one-year limited warranty covers all systems and
components. Two-, five-, and ten-year extended warranties
are also available.
D Generator features:
d Kohler’s unique Fast-Responset excitation system
delivers the fastest voltage response in the industry.
d The brushless, rotating-field generator has broadrange
reconnectability.
d Kohler’s permanent magnet-excited generator (PMG)
provides superior short-circuit capability.
D Other features:
d Controllers are available for all applications. See
controller features inside.
d The low coolant level shutdown prevents overheating.
(Standard on radiator models only.)
d Integral vibration isolation eliminates the need for
under-unit vibration spring isolators.
d An electronic, isochronous governor delivers precise
Generator Ratings frequency regulation.
130_C Rise 105_C Rise d Electronic engine controls and a generator
Standby Rating Prime Rating microprocessor controller combine to deliver one of the
Generator Voltage Ph Hz kW/kVA Amps kW/kVA Amps
most advanced control systems in today’s generator
market.
120/208 3 60 300/375 1041 270/338 937
120/240 3 60 300/375 902 270/338 812
127/220 3 60 300/375 984 270/338 886
139/240 3 60 300/375 902 270/338 812
220/380 3 60 280/350 532 255/319 484
240/416 3 60 300/375 520 270/338 468
277/480 3 60 300/375 451 270/338 406
4UA13 347/600 3 60 300/375 361 270/338 325 RATINGS: All three-phase units are rated at 0.8 power factor. Standby Ratings: Standby ratings
apply to installations served by a reliable utility source. The standby rating is applicable to varying
110/190 3 50 252/315 957 228/285 866 loads for the duration of a power outage. There is no overload capability for this rating. Ratings are
in accordance with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. Prime Power Ratings: Prime
110/220 3 50 252/315 827 228/285 748 power ratings apply to installations where utility power is unavailable or unreliable. At varying load,
the number of generator set operating hours is unlimited. A 10% overload capacity is available for
115/200 3 50 252/315 909 228/285 823 one hour in twelve. Ratings are in accordance with ISO-8528/1, overload power in accordance with
ISO-3046/1, BS 5514, AS 2789, and DIN 6271. For limited running time and base load ratings,
120/208 3 50 252/315 874 228/285 791 consult the factory. Obtain the technical information bulletin (TIB-101) on ratings guidelines for the
complete ratings definitions. The generator set manufacturer reserves the right to change the design
220/380 3 50 252/315 479 228/285 433 or specifications without notice and without any obligation or liability whatsoever. NOTE: Order
separate generator set specs for 50 or 60 Hz as this model cannot change frequency. GENERAL
230/400 3 50 252/315 455 228/285 411 GUIDELINES FOR DERATION: Altitude: Derate 0.5% per 305 m (1000 ft.) elevation above 1525 m
(5000 ft.) up to a maximum elevation of 3660 m (12000 ft.). Temperature: Derate 1.0% per 5.5_C
240/416 3 50 252/315 437 228/285 396 (10_F) temperature above 40_C (104_F). For radiator cooling system capacity, derate 1.4_C
(2.5_F) per 305 m (1000 ft.) elevation above 183 m (600 ft.).
G5-143 (300REOZD) 8/02f
Alternator Specifications
Specifications Generator D NEMA MG1, IEEE, and ANSI standards compliance for
temperature rise and motor starting.
Manufacturer Kohler
Type 4-Pole, Rotating Field D Sustained short-circuit current of up to 300% of the rated
Exciter type Brushless, Permanent- current for up to 10 seconds.
Magnet, Fast-Responset
D Sustained short-circuit current enabling downstream circuit
Leads: quantity, type 12, Reconnectable breakers to trip without collapsing the generator field.
Voltage regulator Solid State, Volts/Hz
D Self-ventilated and dripproof construction.
Insulation: NEMA MG1
Material . . . . . . . . . . . . . . . . . . . . . . . . . . Class H D Vacuum-impregnated windings with fungus-resistant epoxy
Temperature rise . . . . . . . . . . . . . . . . . . 130_C, Standby varnish for dependability and long life.
Bearing: quantity, type 1, Sealed D Superior voltage waveform from a two-thirds pitch stator
Coupling Flexible Disc and skewed rotor.
Amortisseur windings Full
D Solid-state, volts-per-hertz voltage regulator with ±2%
Voltage regulation, no-load to full-load no-load to full-load regulation.
Standard . . . . . . . . . . . . . . . . . . . . . . . . . ±2%
Decision-Makert 550 controller D Fast-Responset brushless alternator with brushless
(with 0.5% drift due to temp. variation) 3-Phase Sensing, ±0.25% exciter for excellent load response.
One-step load acceptance 100% of Rating
Unbalanced load capability 100% of Rated Standby
Current
Peak motor starting kVA: (35% dip for voltages below)
480 V, 380 V 4UA13 . . . . . . . . . . . . . 980 (60Hz), 600 (50Hz)

Application Data
Engine Engine Electrical
Engine Specifications 60 Hz 50 Hz Engine Electrical System 60 Hz 50 Hz
Manufacturer Detroit Diesel Battery charging alternator:
Engine: model, type S60, 4-Cycle Ground (negative/positive) . . . . . . . Negative
Turbocharged, Aftercooled Volts (DC) . . . . . . . . . . . . . . . . . . . . . 24
Cylinder arrangement 6, Inline
Ampere rating . . . . . . . . . . . . . . . . . 40
Displacement, L (cu. in.) 12.7 (778)
Starter motor rated voltage (DC) 24
Bore and stroke, mm (in.) 130 x 160 (5.12 x 6.30)
Battery, recommended cold cranking
Compression ratio 15.0:1 amps (CCA):
Piston speed, m/min. (ft./min.) 576 (1890) 480 (1575) Qty., CCA rating . . . . . . . . . . . . . . . 2, 950
Main bearings: quantity, type 7, Precision Half-Shell Battery voltage (DC) 12
Rated rpm 1800 1500
Max. power at rated rpm, kWm (BHP) 366 (490) 321 (430) Fuel
Cylinder head material Cast Iron
Fuel System 60 Hz 50 Hz
Piston: type, material Crosshead, Malleable Iron
Fuel supply line, min. ID, mm (in.) 13 (0.50)
Crankshaft material Forged Steel
Fuel return line, min. ID, mm (in.) 8 (0.31)
Valve material:
Max. lift, engine-driven fuel pump, m (ft.) 2.1 (6.8)
Intake . . . . . . . . . . . . . . . . . . . . . . . Iron Based Seat
Max. fuel flow, Lph (gph) 329 (86.8)
Exhaust . . . . . . . . . . . . . . . . . . . . . Nickel Based Seat
Fuel prime pump N/A
Governor: type, make/model DDEC Electronic Control
Fuel filter: quantity, type 2, Primary/Secondary
Frequency regulation, no-load to
full-load Isochronous Recommended fuel #2 Diesel
Frequency regulation, steady state ±0.25%
Frequency Fixed Lubrication
Air cleaner type, all models Dry Lubricating System 60 Hz 50 Hz
Type Full Pressure
Exhaust Oil pan capacity, L (qt.) 30 (32)
Exhaust System 60 Hz 50 Hz Oil pan capacity with filter, L (qt.) 36 (38)
Exhaust flow at rated kW, m3/min. (cfm) 71.6 (2530) 60.9 (2150) Oil filter: quantity, type 2, Cartridge
Exhaust temperature at rated kW, dry Oil cooler Water-Cooled
exhaust, _C (_F) 416 (780) 443 (830)
Maximum allowable back pressure,
kPa (in. Hg) 10.2 (3.0)
Engine exhaust outlet size, mm (in.) See ADV Drawing

G5-143 (300REOZD) 8/02f


Application Data Controllers
Cooling (Standard Radiator)
Cooling System 60 Hz 50 Hz
Ambient temperature, _C (_F) * 50 (122)
Engine jacket water capacity, L (gal.) 22.7 (6.0)
Radiator system capacity, including
engine, L (gal.) 45.4 (12)
Engine jacket water flow, Lpm (gpm) 363 (96) 300 (80)
Available Controllers
Decision-Makert 550 Controller
Heat rejected to cooling water at rated
kW, dry exhaust, kW (Btu/min.) 136 (7746) 121 (6871) Audiovisual annunciation with NFPA 110 Level 1 capability.
Programmable microprocessor logic and digital display features.
Heat rejected to air charge cooler at Generator safeguard circuit protection.
rated kW, dry exhaust, kW (Btu/min.) 87.8 (4997) 64.5 (3667)
12- or 24-volt engine electrical system capability.
Water pump type Centrifugal Remote start, remote annunciation, and remote communication options.
Fan diameter, including blades, mm (in.) 991 (39) Refer to G6-46 for additional controller features and accessories.
Fan, kWm (HP) 22 (30) 13 (18) Decision-Makert 3+, 16-Light Controller
Max. restriction of cooling air, intake and Audiovisual annunciation with NFPA 110 Level 1 capability.
discharge side of radiator, kPa (in. H2O) 0.125 (0.5) Microprocessor logic, AC meters, and engine gauge features.
12- or 24-volt engine electrical system capability.
* Weather housing reduces ambient temperature capability by
Remote start, prime power, and remote annunciation options.
6_C (10_F).
Refer to G6-30 for additional controller features and accessories.
Operation Requirements
Air Requirements 60 Hz 50 Hz
Radiator-cooled cooling air,
m3/min. (scfm)[ 561 (19800) 467 (16500)
Combustion air, m3/min. (cfm) 30 (1070) 25 (875)
Heat rejected to ambient air:
Engine, kW (Btu/min.) . . . . . . . . . . 51.8 (2949) 44.1 (2511)
Generator, kW (Btu/min.) . . . . . . . . 24.3 (1382) 21.9 (1245)
[ Air density = 1.20 kg/m3 (0.075 lbm/ft3)

Fuel Consumption 60 Hz 50 Hz
Diesel, Lph (gph) at % load Standby Rating
100% 82.5 (21.8) 70.8 (18.7)
75% 61.7 (16.3) 53.8 (14.2)
50% 42.0 (11.1) 36.7 (9.7)
25% 22.7 (6.0) 20.4 (5.4)
Diesel, Lph (gph) at % load Prime Rating
100% 74.9 (19.8) 64.6 (17.1)
75% 56.3 (14.9) 49.1 (13.0)
50% 38.5 (10.2) 33.7 (8.9)
25% 20.9 (5.5) 18.9 (5.0)

G5-143 (300REOZD) 8/02f


KOHLER CO., Kohler, Wisconsin 53044 USA Kohler Power Systems
Phone 920-565-3381, Fax 920-459-1646 Asia Pacific Headquarters
For the nearest sales and service outlet in the 7 Jurong Pier Road
US and Canada, phone 1-800-544-2444 Singapore 619159
KohlerPowerSystems.com Phone (65)264-6422, Fax (65)264-6455

Standard Features and Accessories


Standard Features Paralleling System
D Alternator Protection (standard with Decision-Makert 550) - Load-Sharing Module
D Battery Rack and Cables - Reactive Droop Compensator
D Electronic, Isochronous Governor - Voltage Regulator Relocation Kit
D Oil Drain Extension
Maintenance and Literature
D Operation and Installation Literature
- General Maintenance Literature Kit
Accessories - Maintenance Kit (includes air, oil, and fuel filters)
- NFPA 110 Literature
Enclosed Unit
- Overhaul Literature Kit
- Exhaust Silencer, Critical (kit: PA-354258)
- Production Literature Kit
- Exhaust Silencer, Residential (kit: PA-354257)
- Silencer Mounting Kit for Weather Housing Controller
- Tail Pipe and Rain Cap Kit - Common Failure Relay Kit
- Weather Housing (with skid end caps) - Communications Products and PC Software
(Decision-Makert 550 controller only)
Open Unit
- Customer Connection Kit
- Exhaust Silencer, Hospital (kits: PA-354903, PA-354905)
- Dry Contact Kit (isolated alarm)
- Exhaust Silencer, Critical (kits: PA-354880, PA-354881)
- Engine Prealarm Sender Kit
- Exhaust Silencer, Residential (kits: PA-354882, PA-354883)
- Remote Annunciator Panel
- Exhaust Silencer, Industrial (kits: PA-354904, PA-354906)
- Remote Audiovisual Alarm Panel
- Flexible Exhaust Connector, Stainless Steel
- Remote Emergency Stop Kit
Cooling System - Remote Mounting Cable
- Block Heater - Run Relay Kit
- Radiator Duct Flange Miscellaneous Accessories
Fuel System - _______________________________________________
- Flexible Fuel Lines - _______________________________________________
- Fuel Pressure Gauge - _______________________________________________
- Fuel/Water Separator with Prime Feature - _______________________________________________
- Hand Primer Pump
- Subbase Fuel Tanks Dimensions and Weights
- Subbase Fuel Tank with Day Tank
Overall Size, L x W x H, mm (in.): 3416 x 1270 x 1953
Electrical System (134.5 x 50.0 x 76.9)
- Battery Weight (radiator model), wet, kg (lb.): 3032 (6684)
- Battery Charger, Equalize/Float Type
- Battery Heater
Engine and Generator
- Air Cleaner, Heavy Duty H
- Air Cleaner Restriction Indicator
- Bus Bar Kits
- Crankcase Emission Canister
- CSA Certification
W L
- Generator Strip Heater
- Line Circuit Breaker (NEMA1 enclosure) NOTE: This drawing is provided for reference only and should not be used for planning
installation. Contact your local distributor for more detailed information.
- Line Circuit Breaker with Shunt Trip (NEMA1 enclosure)
- Optional Generators DISTRIBUTED BY:
- Rated Power Factor Testing
- Rodent Guards
- Safeguard Breaker (not available with Decision-Makert 550)
- Skid End Caps
- Voltage Regulation, 1%
- Voltage Regulator Sensing, Three-Phase

E 1998, 1999, 2000, 2001, 2002 by Kohler Co. All rights reserved.
G5-143 (300REOZD) 8/02f

You might also like