Operator's Manual: Power Systems, Inc
Operator's Manual: Power Systems, Inc
Operator's Manual: Power Systems, Inc
Operator’s Manual
“E” Option Control Panels
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe
! operation be copied and posted in potential hazard areas. Safety should be stressed to all
operators and potential operators of this equipment. !
Study these SAFETY RULES carefully before • Do not handle any kind of electrical device while
installing, operating or servicing this equipment. standing in water, while barefoot, or while hands or
Become familiar with this manual and all literature feet are wet. DANGEROUS ELECTRICAL SHOCK
pertaining to your generator set and related equip- MAY RESULT.
ment. This equipment can operate safely, efficiently • If people must stand on metal or concrete while
and reliably only if it is properly installed, operated installing, operating, servicing, adjusting or repairing
and maintained. Many accidents are caused by failing this equipment, place insulative mats over a dry
to follow simple and fundamental rules or precau- wooden platform. Work on the equipment only while
tions. standing on such insulative mats.
Generac cannot possibly anticipate every possible cir- • Wire gauge sizes of electrical wiring, cables and cord
sets must be adequate to handle the maximum elec-
cumstance that might involve a hazard. The warn-
trical current (ampacity) to which they will be sub-
ings in this manual, and on tags and decals
jected.
affixed to your equipment are, therefore, not
all-inclusive. If you use a procedure, work method or • Before installing or servicing this equipment, make
operating technique Generac does not specifically rec- sure that all power voltage supplies are positively
TURNED OFF at their source. Failure to do so will
ommend, you must satisfy yourself that it is safe for you
result in hazardous and possibly fatal electrical
and others. You also must make sure the procedure,
shock.
work method or operating technique that you choose
does not render the equipment unsafe. • When installed with an automatic transfer switch, the
generator may crank and start anytime without
! GENERAL HAZARDS ! warning. To prevent injuries caused by sudden start-
up, disable the generator’s automatic start circuit
• For safety reasons, Generac recommends that this before working on or around the unit. Then, place a
equipment be installed and serviced by a Generac “Do Not Operate” tag on the generator control panel
Authorized Service Dealer or other competent, quali- and on the transfer switch.
fied electrician or installation technician who is famil- • In case of accident caused by electric shock, imme-
iar with applicable codes, standards and regulations. diately shut down the source of electrical power. If
The operator also must comply with all such codes, this is not possible, attempt to free the victim from
standards and regulations. the live conductor. AVOID DIRECT CONTACT WITH
THE VICTIM. Use a nonconducting implement,
• When working on this equipment, remain alert at all
such as a rope or board, to free the victim from the
times. Never work on the equipment when you are
live conductor. If the victim is unconscious, apply
physically or mentally fatigued.
first aid and get immediate medical help.
• Inspect the equipment regularly, and promptly repair
• Never wear jewelry when working on this equipment.
or replace all worn, damaged or defective parts using
Jewelry can conduct electricity resulting in electric
only factory-approved parts.
shock, or may get caught in moving components
• Before performing any maintenance on the generator causing injury.
or any related equipment, disable the generator to
prevent accidental start-up. Remove the control
panel fuse and then disconnect the battery cables by FIRE HAZARDS
removing the one indicated by a NEGATIVE, NEG or
(–) first. To re-enable the generator, reconnect the • For fire safety, the generator and related equipment
battery cables connecting the one indicated by a must be installed and maintained properly.
NEGATIVE, NEG or (–) last, then re-install the con- Installation always must comply with applicable
trol panel fuse. codes, standards, laws and regulations. Adhere
strictly to local, state and national electrical and
building codes. Comply with regulations the
ELECTRICAL HAZARDS Occupational Safety and Health Administration
(OSHA) has established. Also, ensure that the
• Generators produce dangerous electrical voltages equipment is installed in accordance with the man-
and can cause fatal electrical shock. Avoid contact ufacturer’s instructions and recommendations.
with bare wires, terminals, connections, etc., while Following proper installation, do nothing that
the generator and related equipment are running. might alter a safe installation and render the unit
Ensure all appropriate covers, guards and barriers in noncompliance with the aforementioned codes,
are in place before operating the equipment. If you standards, laws and regulations.
must work around an operating unit, stand on an
insulated, dry surface to reduce shock hazard.
Generac® Power Systems, Inc.
Table of Contents
E Option Control Panels
1-800-333-1322
DEALER LOCATION INFORMATION
CAN BE OBTAINED AT THIS NUMBER.
OVERVIEW The user can program the length of time that the starter
The “E” option control panel is a programmable motor is engaged during a start attempt. After the first
engine control and monitoring system. It allows the attempt, the generator will pause for a programmable
user to customize the generator starting and running length of time before the next attempt. The number of
sequence, monitor engine parameters and configure attempts also is programmable, after which the failed
the alarms. This can be done either through its own to start alarm is activated.
control module, featuring liquid-crystal display The user can program a warm-up time that is active
(LCD) and keypad, or using a PC and RS232 serial after the generator has started. This could be used in
communications. The module includes user pro- conjunction with a programmable relay output to
grammable inputs and outputs that allow it to be tai- inhibit the transfer switch from applying load until
lored to a vast range of applications. All of the setup the generator is ready. The warm-up time can be set
information is stored in nonvolatile (permanent) to zero if this function is not required. This timer is
memory. separate from the alarm hold off timer, which allows
the generator to run for a time before certain alarms
ENGINE CONTROL (such as low oil pressure) are active.
The module has a three-position selector switch that If the generator is in the AUTO mode and a stop com-
selects between “Auto” mode, “Off” and “Manual” start mand is received, a programmable cool-down timer
mode. When the switch is in the OFF position, the can be used to keep the generator running with no
generator will not start, and it will stop if it is running. load for a fixed time. This also can work in conjunc-
When the switch is turned to MANUAL, the generator tion with a relay output to inhibit the transfer switch.
will start immediately and will continue to run until If the timer is set to zero, this function is disabled. If
the switch is turned to the OFF position or a shut- the selector switch is turned to OFF, then the genera-
down alarm is activated. With the switch in the AUTO tor will stop immediately without waiting for the cool-
position, the generator will wait for either the remote down time.
start contacts to close or for a start command to be
sent from the serial link. The generator will run until Certain alarm functions are designated as shutdown
the remote start contacts open, a stop command is alarms. These alarms will stop the generator and
sent down the serial link, a shutdown alarm is acti- inhibit it from starting until the alarm condition has
vated or the switch is turned to the OFF position. The cleared and the alarm has been reset.
remote start contacts always will have priority over
the serial link commands so that the serial link can- E OPTION CONTROL MODULE
not stop the generator if the remote start contacts are
closed. When GenLink® software, which may be OVERVIEW
obtained from a Generac Authorized Service Dealer, is
connected to the E panel via modem, the panel will The LCD on the front of the module (Figure 1.1) fea-
monitor the connection to ensure that the line has not tures a 24-character by two-line display screen that will
dropped. If the E panel detects that the line has been show one of seven pages. There is a keypad with six
dropped, it will disconnect the modem so that it is keys that are used for operating the display and select-
ready for another incoming call. If the generator had ing the various pages. A key-activated switch allows the
been started via the modem connection, then it will be user to select whether the generator is in the “Auto”
stopped immediately unless the remote start contacts mode, “Off” mode or “Manual” run mode. Four LEDs
are closed or the generator is in manual. However, if indicate the following conditions:
the GenLink® software disconnected cleanly (as a • “Power” – Battery power is OK.
result of a user command) with the generator running,
then the generator will continue to run for a another • “Not Auto” – The generator is not in the automatic
three hours unless it receives a stop command. mode.
• “Com Alarm” – A common alarm condition has
When a start command is received, the engine preheat occurred.
will be engaged, if it is selected. The user can program • “Gen Run” – The generator is running.
the preheat to engage for a programmable time before
engaging the starter motor, to engage while the engine is NOTE:
attempting to start, or to do both. In order to protect The “Power” LED will go out immediately if the
the engine from trying to start while it is already run- battery voltage dips below the alarm limit, but the
ning (if the rpm sensor is damaged), an alarm is gener- alarm will not be triggered unless the voltage is
ated if there is oil pressure when the start command is low for more than five minutes.
sent. An alarm also is generated if there is a voltage
output from the generator but the rpm sensor detects
zero engine speed.
Figure 1.1 – Control Module Layout When the display is showing certain pages, the user
is able to scroll between relevant items within the
page using the up and down arrow keys. For example,
if the display is showing the “Alarm Log Page,” the
user can use the up and down arrow keys to scroll
between the entries on the alarm log. A description of
each page is given below.
If an alarm becomes active, the display will switch to If an alarm condition occurs when the user is enter-
this page and display the highest priority alarm mes- ing data, the data will be ignored, and the display will
sage. The back light and alarm LED will flash, and the show the alarm screen. If a status condition occurs
audible alarm will be activated. The user must press when data is being entered, the display will not
the enter key to accept the alarm, at which time the change.
back light will be on continuously. If the alarm is non- Once the user has finished entering data by pressing
latching, the alarm message will clear as soon as the the Enter key, pressing the Reset key will allow the
condition is cleared. If the alarm is a latching alarm, user to select other pages using the left and right
then the user must press the reset key to clear the mes- arrow keys.
sage. Once a message has cleared, the display will show
the next priority alarm message.
After an alarm has been accepted, the user is able to
ALARMS
All analog channels have alarms associated with
scroll through other active alarm and message them. There is also a coolant level alarm, an emer-
screens using the up and down arrow keys. gency stop alarm and eight user definable inputs that
Alarm Log Page can be used to generate alarms. Alarms can be status
messages, non-latching alarms, latching alarms or
This page displays the last 50 alarm messages. When shutdown alarms. When a new alarm condition
the user selects this page, it displays the latest alarm occurs, the alarm LED and the display back light will
message. Pressing the up or down arrow keys will flash. Also, the alarm relay contacts will close (oper-
allow the user to scroll up and down the list of mes- ating the audible alarm), and the display will show
sages. the alarm message. The user will be able to accept the
alarm (turn off the audible alarm) from the keypad,
Instrumentation Page and if the alarm condition has cleared, he or she also
This page displays one of the analog signal values. will be able to clear the alarm. Non-latching alarms
Pressing the up or down arrow keys will scroll to will clear themselves if the alarm condition is no
other analog display screens. longer present. Latching alarms require the user to
clear the alarm from the keypad even if the alarm
Parameter Entry Page condition is no longer present. Shutdown alarms are
This page allows the user to modify the various set similar to latched alarms, but they also cause the
points and programmable options. See the generator to stop and will not allow it to start again
“Programmable Parameters” section of this manual until the key-switch has been turned to the OFF posi-
for more specific option information. The user must tion to reset the alarm. Status messages are similar
press the Enter key when this page is displayed and to non-latching alarms except that they do not acti-
will then be prompted for a password. The password vate the alarm relay or the alarm LED and are not
is a six-digit number and the default value is 000000. recorded on the alarm log.
However, the user will be able to change the pass- Alarms can be always active, immediately active when
word. Digits will be selected using up and down the generator is commanded to run, or active after
arrow keys, and the cursor will be moved by the left the hold off timer has expired. This timer delays the
and right arrow keys. When the user presses the operation of certain alarms until a programmable
Enter key, the password will be checked. If the pass- time after the engine has started. Some alarms allow
word is correct, the display will show one of the data the user to define the type of alarm and when it is
entry screens. active.
There are four parameter entry menus: “Engine The following chart is a summary of the alarms and
Parameter,” “System Alarm,” “Digital I/O” and “Analog the programmable options:
Input.” The user will be able to scroll through the vari-
ous parameters in each menu using the up and down
arrow keys. The left and right arrow keys are used to
switch between the four menus. When a parameter that
requires changing is displayed, the user presses the
Enter key to enable data entry. A cursor will appear at
the first character that can be altered. The user can
then change the character using the up and down arrow
keys. The user can move to the next character or previ-
ous character using the left and right arrow keys.
Pressing the Enter key will accept the new setting.
Pressing the Reset key will ignore the new setting.
NOTE:
The modem is not intended to be mounted inside
the control panel. It should be mounted inside the
enclosure (no vibration) or inside a nearby build-
E PANEL RS232 CABLES ing or shelter if the generator does not have an
enclosure.
The “E” panel can communicate via its RS232 port to
a remote PC. The connection is made either directly NOTE:
to the serial port on a PC, or via a modem and tele-
Use shielded cable, 100 feet maximum in length.
phone line.
Connect the shield drain wire to Pin 1 on the E
The “E” panel has a 9-pin male “D” type connector, panel end only.
and is configured as DTE (Data Terminal
Equipment). The serial ports on most PCs also have SERIAL COMMUNICATIONS
a DTE configuration, and are usually 9-pin “D” type
male connectors. Most modems have a DCE configu- Serial Communication Via Modem
ration (Data Communication Equipment) and a 25-
pin female connector. (Also refer to the appropriate Genlink Manual)
Connecting an “E” panel directly to a PC requires a The control panel has the ability to communicate to a
“Null Modem” connection. This can be achieved with PC via an RS232 serial port. The PC software will be
either a null modem cable, or a standard serial cable able to interrogate the module. The user also will be
with a null modem adapter. Figure 1.3 shows the able to program the parameters on the PC and down-
required pin connections between the two cables for load them to the module if using the Pro version. The
a 9-pin serial connector on the PC. user will be able to start and stop the generator if it is
in AUTO mode.
Figure 1.3 — “E” Panel to PC Cable The module does not have a built-in modem.
Configuration However, software will include the ability to interface
with an external modem. The user can initialize the
modem from the panel. Generac offers a remote
annunciator (models #’s 004391-0, 004392-0 and
004391-1, 004392-1) which allows the E panel to
communicate with both a modem and a remote
annunciator. See the Remote Annunciator Panel man-
ual (part number 0A7450) for a complete description
of these panels.
Figure 1.5 – E Panel Serial Communications Figure 1.6 – E Option Panel Components
Setup Modification
VOLTAGE ADJUST POTENTIOMETER 4. Using a multimeter (e.g., Fluke 87) set to the diode
range, measure between pins 1 (BAT+) and 2 (BAT-
This potentiometer permits the operator to “fine ) of connector CON4 on the module.
adjust” the generator’s AC output voltage on units • With the positive meter lead connected to pin
rated below 400 kW. Adjustment range is plus or 2 and the negative lead to pin 1, the meter
minus five percent. Turn the knob clockwise to should read between 0.4 and 0.6 volts, which
increase voltage, counterclockwise to decrease voltage. indicates that the internal fuse is OK.
ALARM HORN • Reversing the meter leads would give a slowly
increasing voltage reading on the meter, which
This horn sounds an audible warning when an alarm also indicates a good fuse.
condition exists. See the “Alarms” section for further
• An open circuit fuse will give an open circuit
information.
meter reading (.OL on Fluke 87).
DC PANEL FUSE If the meter reads open circuit:
This 15-amp fuse protects the panel components. 5. Remove the four phillips head screws retaining the
This fuse is not to be confused with the control mod- rear cover of the control module.
ule internal fuse discussed in “Checking/Replacing 3. Open the back of the control module.
the E Panel Control Module Internal Fuse.” 4. Locate the internal printed-circuit board mounted
fuse, which is behind and to the left of CON4.
EMERGENCY STOP SWITCH 5. Remove the white plastic cover from the fuse hold-
When pressed, this switch will automatically shut er and remove the fuse.
down the entire generator set. The operator must pull 6. If the fuse has blown, replace the fuse (part
the switch out to its original position to reset it and #0A5705), reassemble the control module, and
allow for generator operation. reinstall the control module and its connections.
7. Reconnect the generator start battery and check if
CHECKING/REPLACING THE E PANEL the control module now functions.
If the fuse blows again, or was not blown when the
CONTROL MODULE INTERNAL FUSE module was opened, or the module still does not
Typically, the main indication of fuse failure is the function, the E panel control module must be
absence of any illuminated front panel LEDs (even replaced.
with the key in the OFF position, the “Power” LED
will be illuminated) and no text visible on the module
display. It should be noted however, that these condi- USER PROGRAMMABLE INPUTS
tions can exist if either: The E panel has eight (8) user programmable inputs.
These inputs can be used for annunciation, pre-
a. The generator start battery is dead (less than five alarm, or shutdown alarms. Four of the inputs,
volts) or disconnected. Battery Charge Fail, Gen Power, Line Power, and
b. The main panel fuse (15 amp) is blown. Programmable Input 4 are set up to annunciate on
c. The battery supply wires (#13 and #0) to the the control panel display and at the optional 20 Light
panel control module are open circuit (discon- Remote Annunciator (Programmable Input 4 will
nected). light the unlabeled “spare” LED). These four inputs
d. The “Power” connector (CON4) is disconnected can be used for other connections if a remote annun-
from the rear of the control module. ciator is not used. The other four inputs, if utilized,
e. The generator start battery connections have been will annunciate at the control panel only.
reversed. Reversal of the battery connections The user programmable input connection points are
WILL blow the internal fuse and is the most like- located inside the E option control panel on a 12-
ly reason for its failure. position strip labeled TB3 (refer to Figures 1.7 and
Before removing or disconnecting the E panel control 1.8 on page 12.). The first four terminals are labeled
module, check that none of the above conditions (a- “prog input gnd”. These are the common ground con-
e) exist. nection points for the user supplied switch devices to
If you are satisfied that the problem lies with the be used for the programmable annunciation.
control module: NOTE:
1. Disconnect the generator start battery. These ground terminals are for user programma-
2. Unplug all four wire harnesses from the back of ble input use only. The are not to be used for
the control module. grounding any other circuits.
3. Loosen, then detach, the two retaining clips secur-
ing the control module and remove the module.
Generac® Power Systems, Inc. 11
Section 1 — General Information
E Option Control Panels
Figure 1.7 — TB3 Units Up to 400 kW The remaining eight terminals on TB3 are for the “pos-
itive” side of each user programmable input switch cir-
cuit. These eight terminals have a five VDC potential
available in an open-circuit condition (whether the
control panel key switch is in the off, manual, or auto
position). The inputs can be programmed to annunci-
ate upon either an open circuit condition (five VDC
potential at the terminal) or a grounded condition
(zero VDC potential at the terminal). This voltage state
is determined by the user supplied switch either open-
ing or closing to cause an annunciation.
Program set-up for the user programmable inputs is
carried out in the Digital I/O Menu of the E module
(please refer to the Display Map on pages 18-19). Each
of the eight inputs has four parameters in which spe-
cific options must be selected to make the annuncia-
tion function properly. These four parameters are
labeled Input Channel Message, Input Channel Setting,
Input Channel Alarm Enable, and Input Channel
Alarm Type. Following is a brief description of each:
• Input Channel Message — for selecting letters and
numbers to spell out what the display will read
upon activation of that specific input.
• Input Channel Setting — for selecting whether
annunciation should activate upon that specific
circuit opening or closing to ground.
• Input Channel Alarm Enable — for enabling or dis-
abling annunciation function of that specific input.
Figure 1.8 — TB3 Units Over 400 kW Also, if enabled, for selecting when annunciation
will be active. The choices are: Disabled, Always,
Immediate and Hold-off. See E Control Panel
Definitions on page 38.
• Input Channel Alarm Type — for selecting the type
of alarm annunciation and the effect it has on the
generators control system. The four choices are:
Status, Non-latched, Latched and Shutdown. See
E Control Panel Definitions on page 14.
WIRING EXAMPLES
◆ USER PROGRAMMABLE INPUT NUMBER 1
On units rated below 400 kW, input number 1 is pro-
grammed for “Battery Charge Fail” annunciation at
the control panel display, and the LED on the 20 Light
Remote Annunciator (if used). A user supplied AC
relay is wired in to be powered up by AC voltage that
supplies the unit Battery Charger (see Figure 1.9).
Figure 1.9 — Battery Charge Fail Wiring
Upon loss of this AC supply voltage, the relay will de- 2. Use the LEFT or RIGHT arrow keys to scroll over
energize. The normally closed contacts on the relay to the PARAMETER ENTRY column.
are to be connected to TB3 in the control panel. One 3. Once at the PARAMETER ENTRY column, press
wire connects to any of the four “Prog Input Gnd” ENTER. Enter the password (if different from the
terminals, the other wire connects to terminal num- factory set password 000000) and press ENTER.
ber 5 (B/C Fail). With the relay de-energized, terminal From the ENGINE PARAMETER MENU, press the
5 will be grounded, signaling the E module to activate RIGHT arrow to get to the DIGITAL I/O MENU.
on Programmable Input 1. 4. Using the UP or DOWN arrows (the column is a
continuous loop), scroll to INPUT CHANNEL 1
◆ USER PROGRAMMABLE INPUTS NUMBERS MESSAGE and press ENTER. Up to 24 letters,
2 AND 3 numbers and other characters can be entered to
spell out what will be displayed upon this input
On units rated below 400 kW, input numbers 2 and 3 becoming active. In this case, enter Battery Charge
are programmed for “Gen Power” and “Line Power” Fail. After entering the message, press ENTER.
respectively, indicating the transfer switch position
5. Press the UP arrow to display INPUT CHANNEL 1
(Standby or Utility). Annunciation will occur at the
SETTING. Press ENTER, the display will read
control panel display and at the Remote Annunciator
Input Function, OPEN=ALARM. The Battery
(if used). These signals will come from a set of spare
Charge Fail annunciation should occur upon the
auxiliary contacts located on the main contactor
user supplied relay de-energizing and its normal-
assembly in the transfer switch. The auxiliary contact
ly-closed contact closing, therefore, select
switch is a set of dry contacts with three terminals:
CLOSED=ALARM by pressing the UP or DOWN
Common, Normally Open, and Normally Closed.
arrow. Press ENTER, the display will read Input
Wires must be connected to these three terminals and
Channel 1 Setting, CLOSED=ALARM.
routed to the generator control panel. These three
wires must not be run in the same conduit as the gen- 6. Press the UP arrow, the display will read Input 1
erator’s main output conductors. The wire connected Alarm Enable, DISABLED, press ENTER. The
to the Common terminal on the auxiliary contacts choices are DISABLED, ALWAYS, IMMEDIATE,
will connect to any of the Prog Input Gnd terminals and HOLD OFF. This alarm should always be
on TB3. The wire connected to the Normally Open active, therefore, scroll up or down and select
terminal on the auxiliary contacts will connect to ter- ALWAYS, and press ENTER.
minal 6 (Gen Power) on TB3. The wire connected to 7. Press the UP arrow, the display will read Input
the Normally Closed terminal on the auxiliary con- Channel 1 Alarm Type, STATUS MESSAGE, press
tacts will connect to terminal 7 (Line Power) on TB3. ENTER. The choices are STATUS MESSAGE,
NON LATCHING ALARM, LATCHING ALARM and
◆ ALL USER PROGRAMMABLE INPUTS SHUTDOWN ALARM. This annunciation for
Battery Charge Fail should be a STATUS message,
On units rated below 400 kW, input numbers 4 therefore, scroll up or down and select STATUS
through 8, and units rated over 400 kW, input num- MESSAGE by pressing ENTER.
bers 1 through 8 can be used for virtually any kind of
annunciation the user wishes to set up, within the Programming for User Input Channel 1, Battery
parameters previously described, via an opened or Charge Fail is now complete. The E module has been
closed switch device. Proper wiring consists of two programmed for a STATUS alarm message that is
wires from the user supplied switch: one wire con- ALWAYS active. Upon loss of AC supply voltage to the
nects to one of the “Prg Inpt Gnd” terminals (1 generators battery charger, the user supplied relay
through 4 on TB3), the other wire connects to a will de-energize, its normally closed contacts will
Programmable Input terminal on TB3. close, grounding TB3 terminal 5 to Prg Input Gnd.
The E module will display BATTERY CHARGE FAIL.
Because it was programmed as a STATUS alarm and
PROGRAMMING EXAMPLES not a LATCHING or SHUTDOWN alarm, the status
message will clear when AC power is restored to the
◆ USER PROGRAMMABLE INPUT NUMBER 1 battery charger.
To be used for Battery Charge Fail annunciation. NOTE:
After properly wiring the circuit as described in
Wiring Examples, program as follows: The Battery Charger Fail LED on the 20 Light
Remote Annunciator (if connected) will also turn
1. Power up the E panel by connecting unit battery on when Input Channel 1 is activated.
(ies) and inserting control panel fuse. The module
will run through a self-test mode. Once it has com-
pleted its self-test, it will display the generator sta-
tus (Stopped, ready to run).
Generac® Power Systems, Inc. 13
Section 2 — Operation
E Option Control Panels
*1 Assigned if used with 20 light Remote Annunciator or Remote Relay Panel Otherwise available for any
customer options.
*2 Factory wired if unit is equipped with these options. Otherwise these inputs are available for any
customer requirements.
TABLE A
Dip Switch Setting
1 Up
2 Down
3 Down
4 Down
5 Up
6 Up
7 Up
8 Down
TABLE B
“E” Panel Pin Modem Pin
1 8
2 3
3 2
4 20
5 7
GENERATOR
ALARM STATUS ALARM LOG INSTRUMENTATION PARAMETER ENTRY SOFTWARE VERSION GENERATOR COMMAND
STATUS
Stopped ready to run No active messages * Logged Alarm Number 1 Generator Voltage Parameter entry Generac digital panel Generator switch off
XXX Volts Press Enter to Continue Software version X.XX Generator switch off
Or Or * this is true as long as Or or Or or Or Enter Or Enter * Or Turn key to auto mode: Or
there are no messages Generator in auto mode
X.X Enter
or
Analog Input 1 Engine Parameter Menu Or System Alarm Menu Or Digital I/O Menu Or Analog Input menu
X.X
or or or or
or
Fuel Level Low Fuel Shutdown Enable Input Ch 8 Alarm Type Analog Ch 2 Low Type
X RS485 Port
or Direct Connection only or or or
or
Battery Voltage RS 232 Port Low Fuel Shutdown Setpt Input Ch 8 Alarm enable Analog Ch 2 High Type
XX.X Volts Direct conection XX %
or or or or or
RS 232 Port
Oil Pressure Modem connection Fuel Level Low Enable Input Channel 8 Setting Analog Ch 2 Low Enable
XXX p.s.I or
or RS 232 Port or or or
Modem connection & Setup
Oil Temperature or Fuel Level Low Setpoint Input Channel 8 Message Analog Ch 2 High Enable
XXX deg F XX%
or Restore all values or or or
to default settings
Coolant Temperature or Fuel Level High Enable Input Ch 7 Alarm Type Analog Ch 2 low Setpoint
XXX deg. F X.X
or Voltage Scaling Factor or or or
XXX.XX
Engine Speed or Fuel Level High Setpoint Input Ch 7 Alarm Enable Analog Ch 2 High Setpoint
XXXX Rpm XX% X.X
or Flywheel Teeth or or or
XXX
Generator Frequency or Under Freq Alarm Type Input Channel 7 Setting Analog 2 Low Alarm Msg
XX.XHz
Panel I.D. or or or
XXXXXX
or Under Freq Setpoint Input Channel 7 Message Analog Ch 2 High Alarm Msg
XX.X Hz
User Password or or or
XXXXXX
or Over Freq Alarm Type Input Ch 6 Alarm Type Analog Channel 2 Title
Preheat Option or or or
Coolant Temp Shutdn Setpt. Input Ch 3 Alarm Type Analog Ch 1 Value at 10V
XXX Deg F X.X
or or or
or or
or or
or
or
or
or
or
Output 3 Function
or
Output 2 Function
E Option Control Panels
Section 2 — Operation
or
Output 1 Function
OIL PRESSURE SENSING (Refer to Figure 3.1) TESTING THE CONTROL PANEL
It is relatively easy to do a thorough test of the E
OVERVIEW Panel's Oil Pressure input.
An analog Oil Pressure Sender (OPS) is used for Place the Auto/Off/Manual switch to the Off position
monitoring the engine oil pressure. This sender during this testing.
allows the E panel to measure and display the Engine
oil pressure. Open circuit testing
Refer to the owners manual for the OPS part number This test checks the high end of the oil pressure input
and mounting location. of the E Panel.
Wire number 69 is used to connect the OPS to the E 1. Remove the 69 wire from the control panel termi-
Panel. The Ground for the OPS is made through the nal strip. This simulates a sender open circuit
engine block. condition.
The OPS is a resistive device, whose resistance 2. Look for the following response from the E Panel:
changes based on engine oil pressure. The resistance The back light will flash, the Com Alarm LED will
of the sender results in a voltage being developed flash, and the display will read as follows:
across the sender. As the oil pressure increases, the OIL PRESS SENSE FAULT
resistance will decrease, causing the voltage to PRESS ENTER TO ACCEPT
decrease. This changing voltage is read by the E Panel
and converted into the engine Oil Pressure. 3. Press enter to accept the alarm.
The E Panel will monitor and display oil pressure Short circuit testing
anytime the DC input to the E Panel is present. This test checks the low end of the oil pressure input
of the E Panel.
TROUBLESHOOTING
1. Reconnect the 69 wire to the control panel termi-
Prior to any troubleshooting, the oil pressure param- nal strip.
eters programmed into the E Panel should be Connect a jumper wire between the 69 and 0
checked and verified. The oil pressure input has two positions on the control panel terminal strip. This
different set points associated with it. They are: simulates a sender short circuit condition
Pre-Low Oil Pressure Warning: This is the warning 2. Look for the following response from the E Panel
set point. The generator's alarm will sound, but the 2.1 For units with software version V1.11 and
generator will continue to run. earlier: The back light will flash, the Com
Critical Low Oil Pressure Alarm: This is the alarm Alarm LED will flash, and the display will
set point. The generator will shut down and sound read as follows:
the alarm. OIL PRESS SENSE FAULT
It is important to verify that these parameters are set PRESS ENTER TO ACCEPT
correctly for the specific unit. Check the E Panel set- Press enter to accept the alarm.
tings against the Generator setup sheet. If the gener- 2.2 For units with software version V1.12 and
ator setup sheet is not available, contact Generac's later:
service department for the recommended settings. Use the arrow keys to go to the Oil pressure
display screen.
Figure 3.1 — Oil Pressure Sender Connections The screen should display oil pressure as
Oil Pressure Sender Connections 125 p.s.i.
Refer to the unit's Wiring Diagram for specific connector locations
Control panel testing complete
E Panel E Panel 1. Remove the jumper between the 69 and 0 loca-
CON 2-5
+5V
Set Screw tions on the control panel terminal strip.
Connector
2. If any E Panel alarms are present, press enter to
accept.
Test Results
69 69 69
Oil Pressure
Sender 1. Tests 1and 2 Pass:
69 Location on the (OPS)
69 Location in the
Control Panel Deutsch Connector Move on to the next test "Testing the Oil Pressure
terminal strip ("Sealed Connector" This Ground (0)
Control Panels only) connection is Sender".
made through the
Engine Block
2. If either test 1 or 2 failed: 1.2 Check to see if the sender nut is tightened
2.1 Repeat the open and short circuit testing securely. Be careful not to over tighten the
directly at the back of the E Panel as follows: nut. If the nut is over tightened, the stud will
Open: The 69 wire should be removed from break free and cause incorrect sender read-
CON2-5 ings. This nut should be tightened to 14 to 18
Short: With the 69 wire still removed, insert inch pounds.
a jumper wire into CON2-5. Connect 1.3 Check for any environmental corrosion on
the other end of the jumper to ground the lug or the sender terminal. Generac rec-
(0). ommends the following actions if corrosion is
After testing, remove the jumper wire from found:
CON2-5 and insert the 69 wire back into 1.3.1 Replace the lug.
CON2-5 1.3.2 Replace the sender if possible. If not
2.2 Test results: possible, thoroughly remove all of the
2.2.1 If these tests fail again directly at the corrosion from the sender terminal.
back of the E Panel, then the E Panel 1.3.3 Protect the lug and sender terminal
has failed and should be replaced. with an approved automotive dielectric
2.2.2 If these tests pass at the back of the E grease.
Panel, but failed at the terminal strip, 2. Check the 69 wire in the Deutsch connector (only
then there is a wiring error between the used on the "water tight connector" panels.)
E Panel and the terminal strip. Check 2.1 Refer to appendix A for information on the
this wiring carefully. Deutsch connectors used.
2.2 Refer to the unit's wire diagram for the 69
TESTING THE OIL PRESSURE SENDER location in the Deutsch plug.
The resistance of the OPS can be checked in a power 3. Check the 69 wire on the control panel terminal
down state as follows: strip.
3.1 Check for a proper crimp on both lugs.
1. Remove the control panel fuse to power down the
E panel. 3.2 Check to see if both screws are tightened
securely. These screws should be tightened to
2. Unplug CON2 from the E Panel. 12 inch pounds.
3. Measure the resistance of the oil pressure sender. 4. Check the 69 wire going into CON2 on the back of
This measurement should be made between the the E Panel.
sender terminal and the sender body.
4.1 Check to see if the wire is stripped properly
The sender resistance should measure between 225 inside the green plug. The wire conductor
and 260 Ohms at 0 PSI. should be trapped inside the metal wire
NOTE: clamp. The wire insulation should not be
trapped inside the metal wire clamp.
If the engine has just been stopped, allow suffi-
cient time for the oil pressure to drop to zero 4.2 Check to see if the set screw is tightened
before making this measurement. securely, but do not over tighten. This screw
should be set to 2 to 4 inch pounds.
If the resistance measurement is not in this range, the 5. Check for any wire damage along the entire run
sender has failed. Replace the sender. between the E Panel and the sender.
If the resistance measurement is in this range, move 5.1 Check for any areas along the wire with miss-
on to the next test. ing insulation. This could allow the 69 line to
momentarily come into contact with ground
TESTING THE OIL PRESSURE SENDER causing a false shut down.
CONNECTIONS 5.2 Check to see if the wire is pinched anywhere
along the run. A wire that is pinched between
Visual Inspection the sheet metal can cause the 69 wire to
momentarily come into contact with ground
Carefully check the wiring between the oil pressure resulting in a shut down fault. A pinched wire
sender and the E Panel. may also cause the wire to break inside the
1. Check the 69 wire connection to the OPS. insulation. This could cause the 69 line to
1.1 Check for a proper crimp on the lug. monetarily "open" while running. This will
also result in a shut down fault.
Check the OPS mounting 4.1.2.2 Remove the OPS and check the
conditions of the threads.
The ground return (0) connection for the OPS is Check for an excessive amount
made by the physical connection of the sender to the of pipe sealant on the threads.
engine block. This connection may be made directly, Ensure there is no pipe sealant
or through a series of adapters or fittings. on the end of the sender cover-
Check for the following at each junction point: ing the oil inlet hole. Repeat
step D, measuring the resist-
1. Check for a tight mechanical connection.
ance between the 69 and 0
2. Check for a good electrical connection. locations on the control panel
Resistance measurement terminal strip and comparing
it to the earlier reading.
The resistance of the OPS was measured in "Testing
the Oil Pressure Sender." 4.2 If this measurement is less than 2-3 Ohms
greater than the one taken directly across the
In that test, the resistance was measured directly OPS, and a thorough visual inspection was
across the OPS. This test will now measure that same performed, the wiring is OK.
resistance inside the control panel. This will provide
an additional test of the wiring and connections used LOW COOLANT LEVEL (Refer to Figure 3.2)
to connect the sender to the control panel.
1. Remove the control panel fuse to power down the OVERVIEW
E Panel. A Low Coolant Level (LCL) sensor is placed in the
2. Unplug CON2 from the E Panel. generator's coolant system. This sensor allows the E
3. Measure the resistance between the 69 and 0 loca- Panel to detect a Low Coolant Level condition.
tions on the control panel terminal strip. Wire number 85 is used to connect the LCL to the E
4. Compare this measurement to the measurement Panel. The Ground for the LCL is made through the
taken directly across the OPS. radiator frame or engine block (depending on where
4.1 If this measurement is more than 2-3 Ohms the LCL is located). The LCL is a resistive device
greater than the one taken directly across the whose resistance changes based on the temperature
OPS, there is a problem with the sender con- of the LCL.
nections. You can determine if the problem is The resistance of the LCL results in a voltage being
the 69 connection or the 0 connection as fol- developed across the LCL. This voltage changes as
lows: the resistance changes. This changing voltage is read
4.1.1 Measure the resistance between the by the E Panel.
OPS stud and the 69 wire inside the The LCL is supplied with current from the E Panel.
control panel. If this measurement is This current will cause the LCL to generate heat. If
greater than 2-3 Ohms, replace the the LCL is in coolant, the coolant will keep the LCL
entire wire running between the control from heating up. If the LCL is in air, it will heat up
panel and the OPS stud. telling the E panel there is a low coolant condition.
Repeat step D, measuring the resist- In most systems, a back up High Water Temperature
ance between the 69 and 0 locations on (HWT) switch is wired in parallel with the LCL. This
the control panel terminal strip and switch is a normally open switch whose contacts will
comparing it to the earlier reading. close at a predetermined temperature setting. If this
4.1.2 Measure the resistance between the HWT switch closes, it will result in the E Panel shut-
body of the sender and the 0 location ting down with a "Low Coolant Level" display.
on the control panel terminal strip. If Refer to owners manual for the LCL and HWT part
this measurement is greater than 2-3 numbers and mounting locations.
Ohms, go back and carefully check the
following: The E Panel checks for low coolant level as follows:
4.1.2.1 OPS mounting, including all Software version V1.03 and earlier: Will check for
fittings and adapters. a low coolant level anytime the DC input to the E
Panel is present.
Software version V1.04 and later: Will only check
for a low coolant level once the engine has started and
the hold off timer has expired.
There are no user-definable parameters for the Low
Coolant Level.
22 Generac® Power Systems, Inc.
Section 3 — Troubleshooting and Diagnosis
E Option Control Panels
CHECK THE WIRING BETWEEN THE E PANEL 6. Check the 85 wire on the control panel terminal
strip.
AND THE LCL/HWT 6.1 Check for a proper crimp on both lugs.
The Low coolant level input is active low. This means 6.2 Check to see that both screws are tightened
that a short to ground on the 85 line will cause the E securely. These screws should be tightened to
Panel to shut down for Low coolant level. 12 inch pounds.
Very carefully check the 85 wire from the back of the 7. Check the 85 wire going into CON2 on the back of
E Panel out to the LCL and HWT. Check for the fol- the E Panel.
lowing: 7.1 Check to see the wire is stripped correctly.
The wire conductor should be trapped inside
1. Check for any areas along the wire with missing the metal wire clamp. The wire insulation
insulation. This could allow the 85 line to momen- should not be inside the metal wire clamp.
tarily come into contact with ground causing a 7.2 Check to see if the set screw is tightened
shut down. securely. This screw should be set to 2 to 4
2. Check to see if the wire is pinched anywhere along inch pounds.
the run. A wire that is pinched against sheet metal 8. Check the LCL and the HWT mounting. The
can cause the 85 wire to momentarily come into ground return (0) connection for these devices is
contact with ground resulting in a shut down. made by the physical connection of the device
A pinched wire may also cause the wire to break body to the engine block/radiator frame. These
inside the insulation. This could cause the 85 line connections can be made directly or through a
to momentarily "open" while running. This "open" series of adapters or fittings. Check for a good
condition would not result in a false shutdown, mechanical and electrical connection at each junc-
but it could prevent the E Panel from shutting tion point.
down the generator in the event of a true failure.
TESTING THE LCL/HWT
3. Check the 85 wire connection to the LCL
3.1. Check for a proper crimp on the lug. 1. Check the devices while the generator is not run-
3.2 Check for any environmental corrosion on ning.
the lug or the switch terminal. Generac rec- 1.1 Test the resistance of the LCL.
ommends the following actions if corrosion is 1.1.1 Remove the front panel fuse to power
found: down the E Panel.
3.2.1 Replace the lug. 1.1.2 Unplug CON2 from the E Panel.
3.2.2 Replace the sender if possible. If not 1.1.3 Disconnect the 85 wire from the LCL.
possible, thoroughly remove all of the 1.1.4 Measure the resistance of the LCL. This
corrosion from the sender terminal. measurement should be taken from the
3.3.3 Protect the lug and sender terminal sender terminal to the sender body.
with an approved automotive dielectric The sender should measure between
40 and 65 ohms. This resistance will
grease.
vary with temperature. It will be closer
4. Check the 85 wire connection to the HWT switch. to 40 ohms at 30F, and closer to 65
4.1 Check for a proper crimp on the lug. ohms at 120F.
4.2 Check for any environmental corrosion on If the resistance measurement is not in
the lug or the switch terminal. We recommend this range, the sender has failed and
the following actions if corrosion is found: needs to be replaced.
4.2.1 Replace the lug. 1.1.5 Reconnect the 85 wire to the LCL.
4.2.2 Replace the switch if possible. If not 1.2 Test the HWT switch.
possible, thoroughly remove all of the 1.2.1 Disconnect the 85 wire from the HWT
corrosion from the sender terminal. switch.
4.2.3 Protect the lug and switch terminal 1.2.2 Measure the resistance of the HWT
with an approved automotive dielectric switch. This resistance should be taken
grease. from the switch terminal to the switch
5. Check the 85 wire in the Deutsch connector (only body.
used on "water tight connector" panels.) 1.2.3 This resistance should measure "infini-
5.1 Refer appendix A for information on the ty" or "open circuit". If not, the switch
Deutsch connectors used. has failed and needs to be replaced.
5.2 Refer to the unit's wiring diagram for the spe- 1.2.4 Reconnect the 85 wire to the HWT
cific wire location. switch. Plug CON2 back into the E
Panel. Replace the front panel fuse.
24 Generac® Power Systems, Inc.
Section 3 — Troubleshooting and Diagnosis
E Option Control Panels
2. Check the devices while the generator is running. The WTS is a resistive device whose resistance
If the E Panel is still shutting down on low coolant changes based on coolant temperature. The resist-
level, and both devices check good in the power ance of the sender results in a voltage being devel-
down state, the devices can be checked while the oped across the sender. As the Coolant temperature
engine is running. The following tests will isolate increases, the resistance will decrease, causing the
the two different senders and determine which voltage to decrease. This changing voltage is read by
sender is causing the shutdown. the E Panel and converted into coolant temperature.
NOTE: The E Panel will monitor and display the coolant
It is very important that the wiring between the E temperature anytime the DC input to the E Panel is
Panel and the LCL/HWT was carefully checked as present.
described above. Incorrect wiring or damage to
any of the wiring can result in false test results. TROUBLESHOOTING
2.1 Test the HWT switch. Prior to any troubleshooting, the Coolant
2.1.1 Disconnect the 85 wire connected to Temperature parameters programmed into the E
the LCL. Position the wire such that the Panel should be checked and verified. The coolant
lug will not come into contact with any temperature has three different set points associated
metal surface. with it. They are:
2.2.2 Start and run the generator. If the gen- • Low Coolant Temp Warning: This is a warning set
erator shuts down with a low coolant point. The generator's alarm will sound, but the
level alarm, the HWT switch is the unit will continue to run.
cause. Replace the HWT switch. • Pre-High Coolant Temp Warning: This is a warn-
If the generator does not shut down on ing set point. The generator's alarm will sound, but
alarm, stop the generator and proceed the unit will continue to run.
to the next test. • High Coolant Temp Alarm: This is the alarm set
2.2 Test the LCL sender. point. The generator will shut down and sound the
2.2.1 Reconnect the 85 wire to the LCL. alarm.
It is important to verify that these parameters are set
2.2.2 Disconnect the 85 wire connected to
correctly for the specific unit. Check the E Panel set-
the HWT switch. Position the wire such
tings against the generator setup sheet. If the genera-
that the lug will not come into contact
tor setup sheet is not available, contact Generac's
with any metal surface.
service department for the recommended settings.
2.2.3 Start and run the generator. If the gen-
erator shuts down with a low coolant Figure 3.3 — Water Temperature Sender
level alarm, the LCL is the cause. Connections
Replace the LCL.
If the generator does not shut down on Water Temperature Sender Connections
Refer to the unit's Wiring Diagram for specific connector locations
alarm, stop the generator manually.
2.2.4 Reconnect the 85 wire to the HWT. E Panel E Panel The Sender may
CON 2-6 be located in the
+5V
COOLANT TEMPERATURE SENSING Set Screw
Connector
Radiator or
Engine Block
Open circuit testing After testing, remove the jumper wire from
CON2-6 and insert the 68 wire back into CON2-
This test checks the high end of the coolant tempera- 6.
ture input of the E Panel. 2.2 Test results:
1. Remove the 68 wire from the control panel termi- 2.2.1 If these tests fail again directly at the
nal strip. This simulates a sender open circuit back of the E Panel, then the E Panel
condition. has failed and should be replaced.
2. Look for the following response from the E Panel. 2.2.2 If these test pass at the back of the E
The E Panel should respond in either one of the Panel, but failed at the terminal strip,
following ways: then there is a wiring error between the
2.1 The Coolant temperature display will read E Panel and the terminal strip. Check
less than 20 F. this wiring carefully.
OR
2.2 The back light will flash, the com alarm LED TESTING THE COOLANT TEMPERATURE
will flash, and the display will read as follows: SENDER CONNECTIONS
OIL TEMP SENSE FAULT
Visual Inspection
PRESS ENTER TO ACCEPT
Carefully check the wiring between the coolant tem-
Short circuit testing perature sender and the E Panel.
This test checks the low end of the coolant tempera- 1. Check the 68 wire connection to the WTS.
ture input of the E Panel. 1.1 Check for a proper crimp on the lug.
1.2 Check to see if the sender nut it tightened
1. If any E Panel alarms are present, press enter to
securely. Be careful not to over tighten the
accept. nut. If the nut is over tightened the stud will
2. Reconnect the 68 wire to the control panel termi- break free and cause incorrect sender read-
nal strip. ings. This nut should be tightened to 6 to 7
3. Connect a jumper wire between the 68 and 0 posi- inch pounds.
tions on the control panel terminal strip. This 1.3 Check for any environmental corrosion on
simulates a sender short circuit condition. the lug or sender terminal. Generac recom-
4. Look for the following response from the E Panel. mends the following actions if corrosion is
The back light will flash, the Com Alarm LED will found:
flash, and the display will read as follows: 1.3.1 Replace the lug.
COOLANT TEMP SENSE FAULT 1.3.2 Replace the sender if possible. If not
PRESS ENTER TO ACCEPT possible, thoroughly remove all of the
corrosion from the sender terminal.
Press enter to accept the alarm. 1.3.3 Protect the lug and sender terminal
Control panel testing complete with an approved automotive dielectric
grease.
1. Remove the jumper between the 68 and 0 loca- 2. Check the 68 wire in the Deutsch connector (only
tions. used on the "water tight connector" panels.)
2. If any E Panel alarms are present, press enter to 2.1 Refer to appendix A for information on the
accept. Deutsch connectors used.
Test Results 2.2 Refer to the units wiring diagram for the 68
location in the Deutsch plug.
1. Tests 1 and 2 pass:
3. Check the 68 wire on the control panel terminal
Move on to the next test "Testing the coolant tem- strip.
perature sender connections". 3.1 Check for a proper crimp on both lugs.
2. If either Test 1 or 2 failed: 3.2 Check to see if both screws are tightened
2.1 Repeat the open and short circuit testing at securely. These screws should be tightened to
the back of the E Panel as follows: 12 inch pounds.
Open: The 68 wire should be removed from 4. Check the 68 wire going into CON2 on the back of
CON2-6. the E Panel.
Short: With the 68 wire still removed, insert 4.1 Check to see if the wire is stripped properly
a jumper wire into CON2-6. Connect inside the green plug. The wire conductor
the other end of the jumper to ground should be trapped inside the metal wire
(0). clamp. The wire insulation should not be
trapped inside the metal wire clamp.
26 Generac® Power Systems, Inc.
Section 3 — Troubleshooting and Diagnosis
E Option Control Panels
4.2 Check to see if the set screw is tightened The OTS is a resistive device, whose resistance
securely, but do not over tighten. This screw changes based on oil temperature. The resistance of
should be set to 2 to 4 inch pounds. the sender results in a voltage being developed across
5. Check for any wire damage along the entire run the sender. As the oil temperature increases, the
between the E Panel and the sender. resistance will decrease, causing the voltage to
5.1 Check for any areas along the wire with miss- decrease. This changing voltage is read by the E Panel
ing insulation. This could allow the 68 line to and converted to oil temperature.
momentarily come into contact with ground
causing a false shut down. TROUBLESHOOTING
5.2 Check to see if the wire is pinched anywhere
along the run. A wire that is pinched between Prior to any troubleshooting, verify the following:
the sheet metal can cause the 68 wire to 1. Verify the oil temperature option has been ordered
momentarily come into contact with ground and installed on the generator.
causing a false shut down. A pinched wire
may also cause the wire to break inside the 2. Check and verify the Oil Temperature parameters
insulation, this could cause the 68 line to programmed into the E Panel. The oil temperature
momentarily "open" while running. This will has two different set points associated with it.
also result in a false shut down. Pre-High Oil Temp Warning: This is a warning
set point. The generator's alarm will sound but the
Check the WTS mounting generator will continue to run. This parameter
The ground return (0) connection for the WTS is should be Disabled if no sender was fitted.
made by the physical connection of the sender to the High Oil Temp Alarm: This is an alarm set point.
engine block. This connection may be made directly, The generator will shut down and sound the
or through a series of adapters or fittings. alarm. This parameter should be Disabled if no
Check for the following at each junction point: sender was fitted.
It is important to verify that these parameters are set
1. Check for a tight mechanical connection. correctly for the specific unit. Check the E Panel set-
2. Check for a good electrical connection. tings against the Generator setup sheet. If the gener-
Resistance measurements ator setup sheet is not available, contact Generac's
service department for the recommended settings.
Power down the E Panel by removing the front panel
fuse. Figure 3.4 — Optional Oil Temperature Sender
Remove CON2 from the back of the E Panel. Connections
1. Measure the resistance between the WTS stud and
OptionalOil Temperature Sender Connections
the 68 wire inside the control panel. If this meas- Refer to the unit's Wiring Diagram for specific connector locations
Short circuit testing 1. Check the 523 wire connection to the OTS.
1.1 Check for a proper crimp on the lug.
This test checks the low end of the oil temperature
1.2 Check to see if the sender nut is tightened
input of the E Panel.
securely. Be careful not to over tighten the
1. Reconnect the 523 wire to the control panel ter- nut. If the nut is over tightened the stud will
minal strip. break free and cause incorrect sender read-
2. Connect a jumper wire between the 523 and 0 ings. This nut should be tightened to 6 to 7
locations on the control panel terminal strip. This inch pounds.
simulates a sender short circuit condition. 1.3 Check for any environmental corrosion on
3. Look for the following response from the E Panel. the lug or sender terminal. Generac recom-
The back light will flash, the Com Alarm LED will mends the following actions if corrosion is
flash, and the display will read as follows: found:
OIL TEMP SENSE FAULT 1.3.1 Replace the lug.
PRESS ENTER TO ACCEPT 1.3.2 Replace the sender if possible. If not
possible, thoroughly remove all of the
Press enter to accept the alarm. corrosion from the sender terminal.
Control Panel testing complete 1.3.3 Protect the lug and sender terminal
1. Remove the jumper between the 523 and the 0 with an approved automotive dielectric
locations on the control panel terminal strip. grease.
2. If any E Panel alarms are present, press enter to 2. Check the 523 wire in the Deutsch connector (only
accept. used on the "water tight connector" panels.)
2.1 Refer to appendix A for information on the
Test results Deutsch connectors used.
1. Tests 1 and 2 pass: 2.2 Refer to the unit's wiring diagram for the 523
Move on to the next test "testing the oil tempera- location in the Deutsch plug.
ture sender connections". 3. Check the 523 wire on the control panel terminal
2. If either test 1 or test 2 failed: strip.
2.1 Repeat the open and short circuit testing 3.1 Check for a proper crimp on both lugs.
directly at the back of the E Panel as follows: 3.2 Check to see if both screws are tightened
Open: The 523 wire should be removed from securely. These screws should be tightened to
CON2-4. 12 inch pounds.
Short: With the 523 wire still removed, insert 4. Check the 523 wire going into CON2 on the back
a jumper wire into CON2-4. Connect the of the E Panel.
other end of the jumper to ground (0). 4.1 Check to see if the wire is stripped properly
After testing, remove the jumper wire from inside the green plug. The wire conductor
CON2-4 and insert the 523 wire back into should be trapped inside the metal wire
CON2-4. clamp. The wire insulation should not be
trapped inside the metal wire clamp.
4.2 Check to see if the set screw is tightened The voltage displayed on the E Panel, and the
securely, but do not over tighten. This screw over/under voltage set points are all based on the gen-
should be set to 2 to 4 inch pounds. erators full line to line output voltage. However, in
5. Check for any wire damage along the entire run most cases full line to line voltage is not connected to
between the E Panel and the sender. the E Panel. (Please refer to the unit's wiring diagram
5.1 Check for any areas along the wire with miss- and schematic for complete wiring details.)
ing insulation. This could allow the 523 line The E Panel has a programmable voltage scaling fac-
to momentarily come into contact with tor that is used to scale the sensing voltage applied to
ground causing a false shut down. CON4-4 and CON4-6. This allows the E Panel to dis-
5.2 Check to see if the wire is pinched anywhere play full line to line voltage.
along the run. A wire that is pinched between The scaling factor should be checked if the E Panel is
the sheet metal can cause the 523 wire to not displaying the line to line voltage correctly.
momentarily come into ground causing a false
shut down. A pinched wire may also cause the Check the scaling factor against the generators set up
wire to break inside the insulation, this could sheet. If the set up sheet is not available, contact
cause the 523 line to momentarily "open" Generac's service department for the recommended
while running. This will also result in a false setting.
shut down. The voltage scaling factor can also be used to "cali-
brate" the voltage display.
Check the OTS mounting
The ground return (0) connection for the OTS is Example:
made by the physical connection of the sender to the A 480 volt unit has 240 volts sensing voltage applied
engine block. This connection may be made directly, to E Panel CON4-4 and CON4-6.
or through a series of adapters or fittings.
The E Panels scaling factor should be set to 2.0 to
Check for the following at each junction point: provide a proper line to line display voltage.
1. Check for a tight mechanical connection. If, however, the E Panel displays 490 volts with a scal-
2. Check for a good electrical connection. ing factor of 2.0, the scale factor may be adjusted
slightly to "calibrate" the voltage display. In this case,
Resistance measurements the displayed voltage is roughly 2% high, so the scal-
Power down the E Panel by removing the front panel ing factor should be reduced by 2% to 1.96. Change
fuse. the scaling factor and recheck the voltage display. If
Remove CON2 from the back of the E Panel. necessary, readjust the scaling factor until the voltage
display is properly "calibrated".
1. Measure the resistance between the OTS stud and
the 523 wire inside the control panel. If this meas- Please note the following:
urement is greater than 2-3 Ohms, replace the 1. Software versions V1.07 and earlier had a one
entire wire running between the control panel and decimal point scale factor.
the OTS stud. Software versions V1.08 and later have a two dec-
2. Measure the resistance between the body of the imal point scale factor.
sender and the 0 location on the control panel ter- 2. The E Panel displayed voltage is not used in any
minal strip. If this measurement is greater than 2 way to regulate the generators output voltage. The
-3 Ohms, go back and carefully check the OTS voltage regulator is responsible for regulating gen-
mounting and the star ground connections on the erator voltage.
engine block.
RPM SENSOR AND ENGINE SPEED
AC VOLTAGE DISPLAY ALARMS (Refer to Figures 3.5, 3.6 & 3.7)
The E Panel monitors the generator's AC output volt-
age. This voltage can be viewed locally on the E OVERVIEW
Panel's display, or remotely using Genlink.
The E Panel uses an RPM sensor to monitor engine
There are two user programmable set points for the speed. The RPM sensor is mounted in the blower
Generator output voltage: over voltage and under housing and positioned so the tip of the sensor is
voltage. Both parameters are active after the hold off directly above the engine flywheel teeth. As the fly-
timer has expired. They can be programmed to be a wheel rotates, the sensor will send an electrical pulse
status message, non-latched alarm, latched alarm, or to the E Panel each time a tooth passes the sensor.
shut down alarm. The E Panel will count these pulses and convert them
into engine speed.
Generac® Power Systems, Inc. 29
Section 3 — Troubleshooting and Diagnosis
E Option Control Panels
TROUBLESHOOTING
1. Verify that all the following parameters have been
correctly programmed into the E Panel.
1.1 Number of flywheel teeth. The number of fly-
RPM Sensor wheel teeth is used by the E Panel to convert
Gap - 1/2 to 3/4 (Magnetic Pick Up) the electrical pulses from the RPM sensor,
into engine speed. If this parameter is not
of a turn
Ring Gear programmed correctly, the E Panel will not be
able to monitor engine speed correctly. Verify
If the magnetic pickup is removed for any reason, it the number of flywheel teeth against the gen-
must be installed properly. erator setup sheet. If the generator setup
sheet is not available, contact Generac's serv-
INSTALLATION ice department for the REQUIRED setting.
1.2 Over speed and under speed settings. Verify
1. Rotate the ring gear until a gear tooth face is these settings against the generator setup
directly in the center of the tapped hole on the sheet. If the generator setup sheet is not avail-
blower housing. able, contact Generac's service department
NOTE: for the recommended settings.
Do NOT use the alternator fan to rotate the engine. 2. Check the RPM sensor wiring. A two conductor
shielded cable is used to connect the RPM sensor
2. Gently turn the magnetic pick up clockwise into to the E Panel. It is important to very carefully
the tapped hole until it bottoms on the gear tooth. check this wiring and all connections, including
3. Use a marker to mark a line on the magnetic pick the shield connections.
up threads and blower housing. 2.1 Cable description:
4. Using the lines marked in Step 3 as a guide, turn
the magnetic pick up 1/2 to 3/4 of a turn counter- 2.1.1 Red wire (wire 79). The red wire inside
clockwise. the cable is wire number 79. This wire
is used to connect the RPM signal from
5. Tighten the jam nut securely. the sender to the E Panel.
RELATED ALARMS 2.1.2 Black wire (wire 0). The black wire
inside the cable is the 0 wire that con-
RPM Sensor Loss nects the RPM sensor to the E Panel.
RPM sensor loss is a shut down alarm. There are two Figure 3.6 — Control Panel RPM Sensor
conditions that will result in RPM sensor loss. Connections
1. No RPM signal at crank. The E Panel will monitor Control Panel RPM Sensor Connections
the RPM sensor during the crank cycle. If no sig-
nal is detected within a few seconds of cranking,
the E Panel will display RPM Sensor Failure and Shielded Cable
engine.
Engine Under Speed
Engine under speed is a hold off alarm with a pro-
grammable set point. The alarm type is programma-
0 Wire
ble as shutdown, latched, non-latched or status. Locations
79 Wire
Location
2.1.3 Shield/Drain wire. The shield is an alu- 3. RPM sensor voltage measurement. The RPM sen-
minum foil shield that surrounds the sor voltage can be measured at the control panel's
two conductors and runs the entire main terminal strip. This voltage should be meas-
length of the cable. The foil shield will ured during crank and run.
be cut even with the cable jacket.
The drain wire is a non insulated wire
that is in physical contact with the Once the engine has started, there will be high
shield and also runs the entire length of voltage inside the generators control panel.
the cable. The drain wire is used to
make the shield connections. 3.1 Using an AC volt meter, measure the voltage
at terminal positions 79 and 0.
The drain wire MUST be connected to This voltage should measure as follows:
system ground to shield the sensitive
During crank: 150 milli volts or greater
RPM sensor signal from noise. This (0.150V)
ground connection is typically made at
During run: 500 milli volts or greater
the control panel main terminal strip.
(0.500V)
Refer to Figure 3.6.
3.2 If the voltages measured are lower than what
2.2 Check the cable at the RPM sensor. Look for is listed above do the following:
breaks, signs of over stress, excessive ten-
sion, etc. 3.2.1 Reset the RPM sensor. Refer to Figure
3.5 for the proper setting.
2.3 Check all of the connection points along the
entire cable run (refer to the unit's wiring dia- NOTE:
grams.) At each connection point, check for The RPM sensor will have to be removed in order
proper wire stripping, lugging, etc. to be set properly. Do not strain (twist) the sender
2.4 Drain wire connections. Carefully check the cable during this process. Units that have a con-
drain wire connections at each connection nector at the sender can simply be disconnected.
point. Figure 3.7 shows the different methods If a connector is not available, the cable will have
that may be used for connecting the drain to be removed from the wire harness and discon-
wire. Note that the drain can be connected to nected at the control panel.
the 0 wire at a connection point, or it can be 3.2.2 Retake the voltage measurements. If
run separately. the voltages are still low, then the RPM
Figure 3.7 — RPM Sensor Engine Connections sender is faulty and should be
replaced.
4. Preheat option. Check to see how the Preheat 4.1 "Preheating": The E Panel is preheating the
option is set. If it is set as either "before start" or engine. (Only occurs if preheat is enabled.)
"before and during start" the preheat timer The start output will not be active during this
becomes active. time, and the engine should not be cranking.
5. Preheat timer. This number (in seconds) defines 4.2 "Attempting to start": The E Panel is activat-
the length of time the E Panel will preheat prior to ing all the following outputs:
cranking. 4.2.1 Start solenoid output at CON3-2.
Example: 4.2.2 Fuel solenoid output at CON3-1.
Preheat options: the preheat option is set to before 4.2.3 Preheat output at CON3-4 and 3-3
start, and the preheat timer is set to 10. (Only if preheat is enabled.)
Result: When a start signal is given, the E Panel will 4.3 "Pausing before start": This indicates the E
activate the preheat output for 10 seconds. Once that Panel is in a rest cycle between start attempts.
10 seconds is over, it will activate the start and fuel 4.3.1 The start solenoid output will not be
outputs. active.
4.3.2 The fuel solenoid output will not be
TEST THE E PANEL KEY SWITCH active.
NOTE: 4.3.3 The Preheat output will be active (Only
Leave the key switch in each position for a few if preheat is enabled).
seconds. Turning the key too quickly may cause 4.4 The start sequence will now begin cycling
false test results. between "attempting to start" and "pause
before start". This cycling will continue for the
programmed number of cycles.
If the engine has not started by the end of the
The following steps will signal the generator to final cycle, the display will read "failed to
! start and run. start" and issue a shutdown alarm. This fault
1. Place the key switch in the off position. condition is referred to as over crank.
2. Use the left and right arrow keys to go to the 5. TEST RESULTS: Did the E Panel display
Generator Command page. "attempting to start" during the start cycle?
With the key switch in the off position, the display 5.1 NO.
should read "Generator switch off". 5.1.1 Go back and carefully check the start
3. Turn the key switch to the Auto position. The top settings programmed into the E Panel.
line of the display should read "Generator in auto 5.1.2 Is there an alarm condition present
mode". which is preventing the E Panel from
4. Turn the key switch to the manual position. In the initiating the start sequence? If yes,
manual position, the E Panel should begin the they must be cleared before the E Panel
engine starting sequence. The display will contin- will attempt to start.
ue updating to show the user the progress. This is 5.1.3 If all of the programmable start param-
discussed in detail in the next test. eters are correct, and there are no
If however, the E Panel display shows the key alarms present, then the E Panel has
switch is in either the off or auto positions, the E failed and needs to be replaced.
Panel has failed and needs to be replaced. 5.2 YES. — If the E Panel displayed "attempting
WATCH THE E PANEL DISPLAY DURING THE to start" but the engine did not crank, move
on to the next test.
START ATTEMPT
MEASURE THE START SIGNAL IN THE
CONTROL PANEL (REFER TO FIGURE 3.8)
Warning: the following steps will signal the CON3-2 is the start output from the E Panel and
! generator to start and run. should be at +battery (+12V or +24V) whenever the
1. Set the key switch to the off mode. E Panel display reads "attempting to start."
2. Use the left and right arrow keys to go to the Wire #56 is used to connect CON3-2 from the E Panel
screen "Generator switch off". to the starter contactor.
3. Turn the key switch to the manual position.
All measurements in this test are DC volts with
4. The E Panel display will begin displaying the start respect to ground (0) unless otherwise noted.
sequence as follows:
32 Generac® Power Systems, Inc.
Section 3 — Troubleshooting and Diagnosis
E Option Control Panels
1. Measure the start output directly at CON3-2 on the 1.3 Protect the lugs and terminals with an
back of the E Panel. This should read +12/24V approved automotive dielectric grease.
whenever the E Panel display reads "attempting to 2. Check to see if the terminal nuts are tightened
start." securely, but be careful not to over tighten them.
1.1 If it does not, then the E Panel has failed and 2.1 Coil terminals (10-32 studs and nuts). These
needs to be replaced. nuts should be tightened to 12 to 15 inch
pounds.
Figure 3.8 — Starter Contactor Connections 2.2 Contact terminals (5/16-24 studs and nuts).
Starter Contactor Connections
These nuts should be tightened to 30 to 36
inch pounds.
5.2 If it does read +12/24V, but the engine does Check the fuel output from the E Panel
not crank, then test the starter solenoid and
the starter motor as outlined in the appropri- CON3-1 is the fuel output from the E Panel and
ate engine service manual. should be high (+12 or +24V DC) whenever the E
Panel is displaying "attempting to start."
OVERCRANK Wire number 14/219 is used to connect CON3-1 from
the E Panel to the fuel solenoid. (Wire #14 used in a
FAILED TO START 12 volt system, wire #219 used in a 24 volt system.)
When the E Panel receives a start signal, it initiates All measurements in this test are DC volts with
the programmed starting sequence. The start respect to ground (0) unless otherwise noted.
sequence consists of the number of crank attempts, 1. Measure the fuel output directly at CON3-1 on the
the length of each crank attempt, and the rest time back of the E Panel. This should read +12/24V
between each crank attempt. If the engine has not whenever the E Panel display reads "attempting to
started by the end of the final crank attempt, an start." (crank cycle). This will not read +12/24V
Overcrank alarm is generated, the E Panel will sound when the E Panel display reads "Pausing before
the alarm and display the message "Failed to start". start." (rest cycle).
1.1 If it does not, then the E Panel has failed and
Check the E Panel start settings needs to be replaced.
All of the following start related parameters will be 1.2 If it does, then there is nothing wrong with the
found in the Engine Parameters Menu. E Panel, proceed to the next test.
These settings should be checked against the 2. Measure the 14/219 location on the control panels
Generator setup sheet. If the generator setup sheet is main terminal strip. This measurement should be
not available, contact Generac's service department the same as in step 1.
for the recommended settings. 2.1 If it is not, then carefully check the wiring
1. Number of start attempts: This number defines between the E Panel and the terminal strip.
the maximum number of times the E Panel will There are two basic methods for the 14/219
engage the starter. Verify this number is not set to wiring between the E Panel and the terminal
zero. strip. Refer to the unit's wiring diagram for
the method used.
2. Start timer: This number (in seconds) defines the
length of time the E Panel will keep the starter 2.1.1 Direct wiring: In this method, a wire is
energized during a start attempt. Verify this num- run from CON3-1 on the back of the E
ber is not set to zero. Panel directly to the 14/219 location on
3. Start attempt pause time: This number (in sec- the terminal strip.
onds) defines the length of time the E Panel will 2.1.2 Secondary relay: In this method, a sec-
pause between start attempts. ondary relay is used between the E
4. Preheat option: Check to see how the Preheat Panel and the terminal strip. Refer to
option is set. If it is set as either "before start" or Figure 3.9 for a typical wiring schemat-
"before and during start" the preheat timer ic.
becomes active. 2.2 If it does read correctly: If the 14/219 loca-
5. Preheat timer: This number (in seconds) defines tion on the control panel terminal strip reads
the length of time the E Panel will preheat prior to correctly, there is nothing wrong with the con-
cranking. trol system.
Example: This means the problem is external to the
control panel and may include the fuel sup-
Preheat options: The preheat option is set to before ply, fuel solenoid/injector pump, ignition sys-
and during, and the preheat timer is set to 5. tem, or the wiring connecting these compo-
Result: When a start signal is given, the E Panel will nents.
activate the preheat output for 5 seconds. Once that Refer to the appropriate engine service manu-
5 seconds is over, it will activate the start, fuel and al for further troubleshooting techniques.
preheat outputs.
Figure 3.9 is a typical wiring schematic using a sec- Figure 3.9 — Typical Wiring Schematic Using a
ondary relay for the E Panel fuel output. Refer to the Secondary Fuel Relay
unit’s wiring schematics and diagrams to determine
if a secondary relay is used and for specific connec-
E Panel
tions. CON 3-1
Set Screw
Connector
When the E Panel supplies + battery voltage (12 or This Point is
connected to a +
14/219 14/219
Ø
This Point is
connected to 0 on the
Control Panel
Terminal Strip
The screws
should be set to 2
to 4 inch pounds
HD30 Type
Step 1: Contact Removal Step 2: Wire Stripping
Solid Contacts
Contact Part Wire Gauge Strip Length
1. With rear insert toward Number Range (inches)
you, snap appropriate size
extractor tool over the wire 0460-202-20141 20 AWG .156-.218
of contact to be removed. 0462-201-20141 20 AWG .156-.218
DT Type
Step 1: Contact Removal Step 2: Wire Stripping
Solid Contacts
E CONTROL PANEL DEFINITIONS • LOW: A low signal to a digital input is a contact clo-
Please refer to the following list for an explanation of sure to ground.
terms used in various charts throughout the manual:
• NON-LATCHED: This type of warning will activate
the audible alarm, and flash the alarm LED and
• ALWAYS: With this option selected, the alarm is display back light. The associated message will be
active regardless of the state of the generator. displayed on the screen. When the user accepts the
warning (by pressing the Enter key), the back light
• ANALOG INPUT: An analog input to the E control will stop flashing, and the alarm LED will be on
panel is a voltage sourced input with a zero volt to continuously. The message will be displayed on the
10-volt range. alarm screen, but the user will be able to scroll
through other screens. The LED and message will
• DIGITAL INPUT: A digital input to the E control clear when the warning condition clears. This type
panel is NOT a voltage sourced input, but a dry of warning is logged.
contact closure to ground. Voltage should never be
sourced to a digital input. • SHUTDOWN: This type of alarm will act similar to
the latched alarm, but it also will stop the engine
• DISABLED: If this option is selected, the alarm is when the alarm condition occurs. It can be reset
disabled and has no effect. only by turning the key-switch to the OFF position.
All shutdown alarms are latching, and this type of
alarm is logged.
• HIGH: A high signal to a digital input is
open circuit.
• STATUS: This type of alarm will display a message
on the screen. The message will not be logged. This
• HOLD OFF: This option waits until a preset time is the lowest priority of alarm types.
after the generator is running before becoming
active. The hold off time can be set by the user.
Note that the hold off time is common to • USER INPUT: Any of the eight digital or two ana-
all alarms. log inputs reserved for customer options.
Manufacture Prior to 2nd 2nd Qtr. 2000 Starting 3rd Prior to 3rd Starting 3rd Prior to 2nd Starting 2nd Starting 1st
Date Qtr. 2000 thru 3rd Qtr. Qtr. 2002** Qtr. 2002 Qtr. 2002** Qtr. 2000 Qtr. 2000* *** Qtr. 2003
2002*
Watertight
Connectors No No No Yes Yes No No Yes Yes
Alt. Type Generac Generac Generac Generac Generac Marathon Marathon Marathon Marathon
kW Range <400 kW <400 kW <400 kW <400 kW <400 kW >400 kW >400 kW >400 kW 400 kW Only
0A5502-D (Pg. 52)
0A5501 (Pg. 51) XXX
0A6325-N (Pg. 68)
0C8319-E (Pg. 48)
0C8318 (Pg. 50) XXX
0C8459-J (Pg. 72)
0C8319-E (Pg. 48)
0C8318 (Pg. 50) XXX
0D8765-G (Pg. 66)
0D2378-C (Pg. 44)
0D2379 (Pg. 46) XXX
0D2383-J (Pg. 60)
0D2378-C (Pg. 44)
0D2379 (Pg. 46) XXX
0D8764-H (Pg. 64)
0C1376-D (Pg. 56)
0C1375-C (Pg. 54) XXX
0C3879-B (Pg. 70)
0C8327-C (Pg. 58)
0C8326-B (Pg. 55) XXX
0C8460-G (Pg. 74)
0D4267-A (Pg. 42)
0D4267A-A (Pg. 40) XXX
0D4267C (Pg. 41)
0D4267B-H (Pg. 62)
0D2378-C (Pg. 44)
0D2379 (Pg. 46) XXX
E Option Control Panels
Section 5 — Electrical Data
567 R
589 T
591 V
NOTES:
ALL WIRING 18 AWG UNLESS NOTED. 590 U
REQUIRED WIRING.
OPTIONAL WIRING A
CABLE SHIELDED CABLE 12 AWG
0 G
L
12 AWG
12 AWG
218 E BC3
CABLE B X H
575 S W J
C G B K
68 F
V
A C
For units manufactured with a watertight connector.
H L
573
U F D
P
M
573
N E
T
P
0
86 K
S N
219
85 J
20 354
R SOC
A M
219
C3207 49 W
TB1
ENGINE ON
A
FUSED 15A
D2
FUEL LEVEL
LEVEL SIG.
BATTERY
BATTERY
COOLENT
PROBE
C3208
SPEED
R1 TB3 OPEN D A
(+DC)
(+DC)
(+DC)
START
GND
TB1
SIG.
SIG.
(-)
220 X
PRG INPT GND 1
573
79
0
0
PRG INPT GND
49
PRG INPT GND
0 L
GND A
0 M
TEMP.
523
USED(+)
DEC
T DOWN
OPEN N
TB5 20) 6
C3206
TB4
GRAM
OPEN P
7
C2688
0
GRAM
OPEN R
Section 5 — Electrical Data
GND
8
BC2
485+ 1 PRG RLY 1 NO UT 2
(-)
0 OPEN S
GRAM
485-
219 PRG RLY 1 NC
OPEN T
SCREEN
219 PRG RLY 2 COM
86
OPEN U
X H
85 W J
0V
PRG RLY 2 NO
EMP.
OPEN V
+12/24V
5
IL FILTER
LOCKED 12 354
OPEN W G B K
PRG RLY 2 NC V
7 X A C
PRG RLY 3 COM
TB3 0A K L
F
589
589 8
U D
TB5
C2688
485-
C3207
ENGINE ON
FUSED 15A
SCREEN
OIL PRESS.
LEVEL SIG.
BATTERY
BATTERY
TEMP. SIG.
CONTACT
COOLENT
COOLENT
PROBE
SPEED
(+DC)
(+DC)
(+DC)
START
GND
0
TB1
SIG.
0V
(-)
219
220
220
220
573
5 220
79
56
68
69
0
0
+12/24V
1 2 3 4 5 6 13 14 15 16 17 18 19 20
TB1
220
220
220
220
220
218
218
219
219
219
575
573
79
56
68
69
0
0
0
0
0
0
0
0
0
0
0
LOCATED ON BACK OF PANEL
12 AWG
12 AWG
0
RR
87 218 12 AWG
86 30
85
219A
0 CABLE CABLE
219
0
BC1
C3208
C3206
TB4 TB3
TB1
A6577
TB2
S1 1 183
BATTERY
0 1 0 BAT GND (-) 0 1 178 1 PRG INPT GND
S2 2 11 178 GND 0
S3 3 10 0 (-)
0 2 BAT GND (-) 0 2 0 A0 2 PRG INPT GND
S15 5 8 58
219 3 219 DC FUSED (+) 3 220 3 PRG INPT GND
ENGINE ON (15/220)
(+DC) 220
S16 6 7 57 219 4 PRG RLY 1 COM 4 R1 A0 4 PRG INPT GND
PROGRAM
7 PRG RLY 2 COM 7 R4 A1 7 A1
INPUT 1
BACK-UP
PRG RLY 3 COM 10 R7 A4 10 (A4)
LOW OIL
PRESS.
BACK-UP
85
PRG RLY 3 NO 11 590 A5 11 (A5)
TEMP.
TB2 TB3
NOTE:
THESE TERMINALS ARE
INTENDED ONLY TO BE
USED FOR "DRY CONTACTS"
ASSOCIATED WITH THE
PROGRAMMABLE INPUTS.
CON1 CON3
219B
R15
56A
0
#?-A #?-A
515
#?-B #?-B
CABLE
FERRITE
BEAD
#?-A = #0 OR #S15
#?-B = #220 OR #S16
219
0
S1
S3
S2
57
58
59
0
0
1
20
18
16
14
AM LEGEND
SW1
15
19
AA - AUDIBLE ALARM
67 AM - AMMETER
BC1 - BULKHEAD CONNECTOR (LOWER PANEL)
L1
65
64
67
0
S16 VM - VOLTMETER
S16 65
8
0 7 575 WHITE NEUTRAL 0,1,R15,591
7
567 RED NON-FUSED DC
6
0 ORANGE FUSED DC 14,15,219,220
509 4 5 502
5
0 56,56A,57-59,67,89
591
590
509
502
575
567
BROWN CONTROL
0
0
BC2 162,178,183,S1-3,590
2,49,150,A1-8,R1-9
0 79 BLUE SIGNAL/SENSING
1
S15,S16,64,65
0 85
2
BLACK AC/MISC 6
0 523
3
68,69,85,502,509,
0 68 YELLOW UNIT STATUS
4
515,523,567,575,589
0 69
5
13/218
6
49
575
567
14/219
LEGEND
150
56 AVR = AUTOMATIC VOLTAGE REGULATOR
13/218
0 BC1 = BULKHEAD CONNECTOR [LOWER PANEL]
13/218
0
BC3 = BULKHEAD CONNECTOR [ENGINE2]
13/218
14/219
14/219
49
COOLNT TEMP
15/220
13/218
14/219
14/219
150
523
567
COOLNT LVL
79
49
56
68
85
1 12 13/218
0
0
RUPT TANK
12
OIL P SEND
1
PRE-HEAT
C ALT W/L
CB1 = AVR CIRCUIT BREAKER
MLCB SW
FUEL LVL
OIL TEMP
2 11
11
0
2
14/219
8
20
12
13
14
15
16
17
18
19
2
3
4
6
7
8
6 7 0
7
6
15/220
15/220
15/220
15/220
13/218
14/219
14/219
14/219
BC3
150
523
575
567
TB2 = TERMINAL BLOCK [14 POS.]
49
56
68
69
85
1
1
0
0
0
0
0
15/220
0
0
0
0V 1 0
0
0V 2 0 14/219
0 49
0V 3 0 0
0V 4 0
0
0 0
+12/24V 15/220
0
SCREEN 1
SCREEN 6 0 13/218
485- 7 CLEAR
485+ 8 BLACK CABLE
TB4 0 15/220
0
178 CB1 15/220
14/219
0
591
590
567
89
K W
183
178
1
0 1
0
B/C FAIL
R2
P R PRG RLY 1 COM R1
A2 6 GEN POWER
D2
SOC 0
PRG RLY 1 NO 5 R2
A3 7 LINE POWER
A
B
0
183
PRG RLY 1 NC 6 R3
A4 8 PRG INPT 4
R1
C 4 PRG RLY 2 COM
R4 502
D 1 A5 9 PRG INPT 5 29 14/219
E 2 PRG RLY 2 NO 8 R5
F 6 A6 10
0 PRG INPT 6
G S16 PRG RLY 2 NC 9 R6
H A7 11 MLCB
J 178 PRG RLY 3 COM 10
0 R7
D1
162
89
2
K S1 A8 12 RUPT TANK
L S2 PRG RLY 3 NO R8
S15
S16
1
0
4
2
6
M S3
N 57
58
PRG RLY 3 NC
12 R9
TB3 4
O
P 59 590
FUEL +
1
13 590
567 4 AVR
Q NOT USED FUEL- 14 591 589
R 589 591
1
590
6
5
3
2
4
4
4
59
58
57
2 2
1 1
589
0 0 0
ES MC1
0 R15
14/219 14A
CON1
56 56A A1 1 PRG INPT 1 SNDR RLY N/C 16
A2 2 PRG INPT 2 SNDR RLY N/O 515
A3 3 PRG INPT 3 SNDR RLY COM 14 15/220
A4 4 PRG INPT 4 PRG RLY 3 NC R9
A5 5 PRG INPT 5 PRG RLY 3 NO 12 R8
A6 6 PRG INPT 6 PRG RLY 3 COM R7
A7 7 PRG INPT 7 PRG RLY 2 NC 10 R6
F1 A8 8 PRG INPT 8 PRG RLY 2 NO 9 R5
0 9 GND PRG RLY 2 COM 8 R4
13/218
0 10 GND PRG RLY 1 NC 7 R3
15/220 PRG RLY 1 NO 6 R2
1 USER INPT 1 PRG RLY 1 COM 5 R1
575 2 FUEL LVL PRE-HEAT N/O 150
3 USER INPT 2 PRE-HEAT COM 3 15/220
S16
523 4 OIL TEMP STARTER SOL 56A
69 5 OIL PRES FUEL SOL 1 14A
68 6 COOL TEMP
85 7 COOL LVL
79
CON4
8 SPD SNSR +
VR1 0
183
9
10
SPD SNSR -
REMOTE STRT
ALT LINE 2 6 S16
0
R15 11 EMRG STOP ALT LINE 1 4
12 SPR INPT 1
BAT - 2
15/220
590
14/219
13/218
13 FUEL SNDR +
BAT + 1
R15
S16
56A
14A
CON2
S15
S16
0
15/220
AA
515
0
0
0
0
0
0
0
L1 FERRITE
0
13/218 14/219 BEADS
15/220
PFG
S15
S16
CABLE 0
15/220
S15
S16
15/220 15/220
14/219 14/219
89
WIRE COLOR
LEGEND FUNCTION WIRE #'s LEGEND
WHITE NEUTRAL 0,1,R15,591 AA = AUDIBLE ALARM
RED NON-FUSED DC
ORANGE FUSED DC 14,15,219,220 AM = AMMETER
56,56A,57-59,67,89 ES = EMERGENCY STOP SWITCH
BROWN CONTROL
162,178,183,S1-3,590 F1 = 15 AMP AGC TYPE FUSE
2,49,150,A1-8,R1-9
BLUE SIGNAL/SENSING
S15,S16,64,65 HZ = FREQUENCY METER
BLACK AC/MISC 6 L1 = PANEL LAMP
68,69,85,502,509, MC1 = E-PANEL CONTROL ASSEMBLY
YELLOW UNIT STATUS
515,523,567,575,589
PFG = PANEL FRONT GROUND STUD
SW1 = VOLT/AMMETER SWITCH
S16
S16
S16
S15
S15
S15
VM = VOLT METER
S1
S3
S2
57
58
59
18
16
14
3
S16 64 67
SW1 S16
HZ VM AM
64
19
15
12
2
S15
S15 65 0
S15 0
64
65
67
0
65
67
0
0
64
67
0
0 0
BC1-R
MLCB OPEN 589
BC1-S
GROUND RETURN 0
BC1-A
CT COMMON 0
BC1-N 2
L1 CT 57 3
CB1
CODE P/N: DESCRIPTION
AA 061286 AUDIBLE ALARM
AM VARIOUS AMMETER
AVR 067680 AUTOMATIC VOLTAGE REGULATOR 50Hz
092952 AUTOMATIC VOLTAGE REGULATOR 60Hz
1
4
5
CB1 VARIOUS AVR CIRCUIT BREAKER POWER
D1 049939 FIELD BOOST DIODE
SENSING
FIELD
F1
CON4-4
CON4-6
CON1-2
15A
CON2-10
BC3-6 A3 PROG. INPUT 3
GROUND FROM ENGINE 0 CON4-2 CON1-3 733 LINE POWER
BC4-5
GROUND FROM ENGINE CON1-4
BC4-4
CON3-14 CON1-5 A5 PROG. INPUT 5
L1
CON1-6 A6 PROG. INPUT 6
BC3-9
FUEL SOLENOID 14 CON3-1 CON1-7 589 MLCB OPEN
BC3-3 ES-3 BC4-6
STARTER SOLENOID 56 A8 PROG. INPUT 8
ES-2 CON3-2 CON1-8
BC4-2
CON3-3 CON1-9 0 GROUND RETURN
BC4-3
PRE-HEAT SOLENOID CON3-4 CON1-10 0 GROUND RETURN
BC2-9
COOLANT TEMP. SENSOR CON2-6
BC2-8
OIL PRESSURE SENSOR 69 CON2-5
OIL TEMP. SENSOR CON2-4 CON3-5 R1
BC4-7 COM
FUEL LEVEL SENSOR CON2-2 CON3-6 PROG. RELAY 1
N/O
MC1
BC4-8
'E' PANEL
FUEL SENDER + CON2-13 CON3-7 R3
N/C
FUEL SENDER - CON2-14
BC2-11
CONTROL BOX
COOLANT LEVEL DETECTOR 85 CON2-7 CON3-8 R4
COM
CON3-9 R5 PROG. RELAY 2
N/O
BC2-12 CON3-10 R6
79 CON2-8 N/C
MAGNETIC RPM SENSOR
0 CON2-9
BC2-2 CON3-11 R7
AA
DSUB-5
DSUB-4
DSUB-3
DSUB-2
DSUB-1
RS232 (DSR)
TB4-8
TB4-7
RS232 (Tx)/RS485-
TB4-6
COMMON
For units manufactured with a watertight connector.
Section 5 — Electrical Data
Schematic Diagram (For Use With Generac Alternator) – Drawing No. 0D2379
Standard diagram. Please refer to the Owner’s Manual of the unit for specific details.
TB4
13A
C2688
TB4
485+ 1
FUEL
+ BAT
FUSED DC
COOLNT TEMP
A3392
COOLNT LVL
PROBE
SPEED
RUPT TANK
GND (-)
PRE-HEAT
OIL P SEND
OIL TEMP
BAT
FUEL LVL
C ALT W/L
13A
13A/15/220
13A/15/220
485- 2
13/218
14/219
14/219
0
523
150
575
567
49
68
69
85
SCREEN 3 0
0V 4 0 TB1
11
20
12
14
15
16
18
19
6
7
+12/24V 5 13A
1
1
0
0
0
0
0
69
79
13
14
14
14
15
15
15
49
56
68
85
150
523
589
575
567
13
15
0
89
CABLE
15
0
183
S15
S16
14
14 14
49 49
CB1
S16
S15
178
89
A6577
1
1
0
TB1
TB3
C8229
TB1
TB2
49
14
BAT GND (-) 0
1 1
183 BAT GND (-) 0
2 0 0 2 PRG INPT GND
162
DC FUSED (+)
3 15 PRG INPT GND 2
(15/220)
15
49
PRG RLY 1 COM R1 0 PRG INPT GND
178
S16
PRG RLY 1 NO 5 R2 A1 5 B/C FAIL
R2
PRG RLY 1 NC
6 R3 A2 6 GEN POWER
D2
15
12
6
9
1
8
589
567
R5
PRG RLY 2 NO
A4 PRG INPT 4
R1
10
13
4
7
SH
S1
S3
58
4
2
TB2 AVR
4
1
6
5
3
2
4
S1
58
59
57
89
1
4
2
6
162
S15
89
1
6
6
S15
4
2
0 0
1
ES
0 R15 MC1
14 14A
56 56A
CON1 CON3
A1 1) PRG INPT 1 16) SNDR RLY N/C
A2 515 15) SNDR RLY N/O
A3 15 14) SNDR RLY COM
A4 R9 13) PRG RLY 3 NC
F1 A5 R8 12) PRG RLY 3 NO
13
A6 R7 11) PRG RLY 3 COM
A7 R6 10) PRG RLY 2 NC
15 A8 R5 9) PRG RLY 2 NO
0 R4 8) PRG RLY 2 COM
0 R3 7) PRG RLY 1 NC
S16 R2 6) PRG RLY 1 NO
R1 5) PRG RLY 1 COM
575 150 4) PRE-HEAT N/O
15 3) PRE-HEAT COM
523 56A 2) STARTER SOL
VR1 69
68
14A 1) FUEL SOL
85 CON4
13 79
15 0 S16 6) ALT LINE 2
0 183
4) ALT LINE 1
89
AA 590
591 14) FUEL SNDR -
0
15
2) BAT -
1) BAT +
0 0
515 CON2
CABLE
15
0
#?-A #?-A
#?-B #?-B
S15 FERRITE
BEAD
S16
#?-A = #0 or #S15
14
#?-B = #15 OR #S16
S1
S3
S2
57
58
59
11
67
18
16
14
3
SW1 AM
L1
19
15
12
2
S16
S16
S15
S15
S16
WIRE COLOR
FUNCTION WIRE #'s
LEGEND
0
162,178,183,S1-3
64
14
2,49,150,A1-8,R1-9
BLUE SIGNAL/SENSING
BLACK AC/MISC 6
64
65
68,69,85,515,523
YELLOW UNIT STATUS
567,575,589
LEGEND
AA - AUDIBLE ALARM
AVR - AUTOMATIC VOLTAGE REGULATOR
HZ VM AM - AMMETER
CB1 - AVR CIRCUIT BREAKER
CON1- PLUG 3.5 10 POS
CON2- PLUG 3.5 14 POS
CON3- PLUG 3.5 16 POS
CON4- PLUG 3.5 6 POS
14 D1 - FIELD BOOST DIODE
D2 - C/A EXCITER DIODE
ES - EMERGENCY STOP SWITCH
F1 - 15 AMP FUSE
HZ - FREQUENCY METER
L1 - PANEL LAMP
S15 MC1 - E-PANEL CONTROLLER ASSEMBLY
R1 - FIELD BOOST RESISTOR
R2 - C/A EXCITER RESISTOR
0 0
SH - SOCKET HOUSING(MALE/15 CKT)
SW1 - VOLT/AMMETER SWITCH
TB1 - TERMINAL BLOCK 1 (20 POS)
TB2 - TERMINAL BLOCK 2 (14 POS)
TB3 - TERMINAL BLOCK 3 (12 POS)
TB4 - TERMINAL BLOCK 4 (5 POS)
VM - VOLTMETER
VR1 - VOLTS TRIM POTENTIOMETER
CT COMMON
CODE
ES1-3
L3 VOLTS
L2 VOLTS
SENSING
L1 VOLTS
2-WIRE
MC1
SW1
SIGNAL
AM
AA
VM
HZ
RR
D3
SH
ES
START
F1
L1
FREQ.
L3 CT
L2 CT
L1 CT
S15
178
S16
57
S1
QTY
0
3
2
1
PIN #
SH
14
15
10
7
5
9
1
PART NO.
VARIOUS
VARIOUS
VARIOUS
98426A
98426C
94261E
A4087
86035
70202
32300
55089
61945
61286
S3
S2
58
57
59
S1
E-PANEL CONTROLLER ASSEMBLY
HZ
NORMALLY CLOSED CONTACTS
18
16
14
1
FREQUENCY METER
SW1
RUN RELAY (70A)
SOCKET HOUSING
DESCRIPTION
AUDIBLE ALARM
PANEL LAMP
15
19
VOLTMETER
2
AMMETER
64
65
67
0
AM
VM
RR
0
85
86
219A
183
S15
S16
CON3-1
CON2-10
CON4-4
CON4-6
15A
F1
218
CON1-1
GROUND FROM ENGINE 0 0 CON4-2
CON1-2
CON1-3
RR
30
0 219
L1
CON1-4
87
11 12 CON1-5
FUEL STOP SOLENOID 219 219B
ES-3
11 12 CON1-6
CON3-2
'E' PANEL CONTROL BOX
ES-2
AUX. FUSED DC SUPPLY 220 CON3-3
CON1-7
SHUT DOWN ALARM RELAY
CON1-8
GND 0
CON1-10 PRG INPT GND
FUEL LEVEL SENDER +VDC 220
11 12 CON3-11
0 R15 CON2-11
ES-1
DSUB-4
DSUB-5
DSUB-3
DSUB-2
DSUB-1
CON3-13
AA
RS232 (DTR)
RS232 (Tx)/RS485-
RS232 (Rx)/RS485+
RS232 (DSR)
NOTES:
ALL WIRING 18 AWG UNLESS NOTED.
REQUIRED WIRING.
OPTIONAL WIRING C3207
ENGINE ON
FUSED 15A
LOW FUEL
LEVEL SIG.
BATTERY
BATTERY
TEMP. SIG.
SHIELDED CABLE
COOLENT
COOLENT
CABLE
PROBE
SPEED
(+DC)
(+DC)
GND
TB1
SIG.
(-)
218
218
218
219
219
219
220
220
220
573
79
68
69
0
0
1 2 3 4 6 7 8 9 10 12 13 14 15 16 17 18 20
TB1
219
219
219
218
218
220
220
220
220
575
573
79
56
69
68
0
0
0
0
0
0
LOCATED ON BACK OF PANEL
12 AWG
12 AWG
219B 12 AWG
RR
87 218 12 AWG
86 30
85
219A
0 CABLE
SH
178
C3206
C3208
59 13 15 183
TB1
TB4 TB3
A6577
TB2
S3
57 10 12 58 BATTERY
0 1 0 BAT GND (-) 0 1 178 1 PRG INPT GND
S2 GND 0 C B
(-)
S15 7 9 S16 0 2 BAT GND (-) 0 2 0 0 2 PRG INPT GND
S1 NOTE:
4 5 6 219 3 219 DC FUSED (+) 3 220 C PRG INPT GND THESE TERMINALS ARE
ENGINE ON (15/220) INTENDED ONLY TO BE
(+DC) 220
0 1 2 3 4 PRG RLY 1 COM 4 R1 0 4 PRG INPT GND
ASSOCIATED WITH THE
OIL TEMP.
5 AI1 PRG RLY 1 NO 5 R2 523 5 523
SIG.
PROGRAMMABLE INPUTS.
INPUT 1
SHUT DOWN
AI2 6 AI2 PRG RLY 1 NC 6 R3 190 6 190
ALARM RLY
INPUT 2
LEGEND
PROGRAM
PRG RLY 2 COM 7 R4 A1 A1
INPUT 1
354
HZ - FREQUENCY METER PRG RLY 3 NC 12 R9 A6 12 (A6)
OIL FILTER
BLOCKED
L1 - PANEL LAMP
TB2 TB3
RR - RUN RELAY
SH - SOCKET HOUSING(MALE/15 CKT)
SW1 - VOLT/AMMETER SWITCH
TB1 - TERMINAL BLOCK 1(20 POS)
TB2 - TERMINAL BLOCK 2(12 POS)
TB3 - TERMINAL BLOCK 3(12 POS)
TB4 - TERMINAL BLOCK 4(9 POS)
VM - VOLTMETER
56A
PRG RLY 3 NC R9
PRG RLY 3 NO R8
PRG RLY 3 COM R7
PRG RLY 2 NC R6
PRG RLY 2 NO R5
PRG RLY 2 COM R4
PRG RLY 1 NC R3
ES D PRG RLY 1 NO R2
219
56
220
ALT LINE 2 6 S2
F1 ALT LINE 1 S1
218
CABLE
BAT - 0
BAT + 220
0
AA
515
L1
219
S1
S1
S3
S2
S2
59
57
58
0
0
1
16
5
18
14
20
AM
SW1
15
19
67
65
67
64
S15 64
HZ VM
S16 65
34
VIEW A DETAIL 1
HINGE ASSEMBLY
RECTIFIER ASSEMBLY
54 56 SCALE: NONE MIC
SCALE: NONE
68 13
3
11
60
63 63
59 60 59 60 2 E
17 43
22 23
20 21 21 87
50 52
14
64 65
66 67 6
A3392
BAT
1 36
24
35 29
25
26
61
37 46
D3153
27
75 71 31 32
37 76
44 28 83
64
18
66
16
A A
54 56 68
50 52 50 52
x4 x4 84
45 15
59 60 60
63 63 58 59 33 59 60
60 63 62
86
55 56
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
1 0D2370 1 BOTTOM E PANEL W/SEALED CONS 45 0D3471 2 DECAL COVER DEUTSCH (RECT)
2 0A6324 1 PANEL FRNT E W/SLKSCRN (ELECTRONIC GOVERNOR HARNESS
3 0A6322 1 PANEL RIGHT SIDE E IF EQUIPPED)
4 0A6321 1 PANEL LEFT SIDE E 46 0C5141 2 CONN DEUTSCH GASKET 8/12POS
5 0E3550 1 CHASSIS, UNIVERSAL DT
6 0D2382 1 HARNESS E-PANEL W/SEALED CONS 50 022155 14 WASHER LOCK #6
7 044213 1 RES 10R 5% 12W 51 0C2428 14 SCREW TAPTITE PH 6-32 X 1/2 Z/YC
8 025192 1 RECTIFIER MSC 2A 600V 1N5062 52 0C2323 10 SCREW TAPTITE PH 6-32 X 5/8 ZYC
9 070370 2 WASHER MICA .203 53 022471 4 NUT HEX #8-32 STEEL
10 023762 1 WASHER SHAKEPROOF EXT #10 STL 54 022264 8 WASHER LOCK M4
11 055444 1 HEATSINK 13.3L 55 038150 4 WASHER FLAT #8 ZINC
12 030468 1 WASHER STEP NYLON .20 56 036918 8 SCREW PPHM #8-32 X 1/2
13 049939 1 RECTIFIER MSC 12A 600V 1N1206R 57 0A2284 4 SCREW SWAGE 8-32 X 1/2 Z/YC
14 0A3392 1 DECAL TERMINAL BLOCK 58 022158 2 NUT HEX #10-32 STEEL
15 0C8229 1 DCL-E PNL TS#2 (W/FS) 59 022152 14 WASHER LOCK #10
16 0A6577 1 DECAL T STRIP 3 E PNL 60 023897 15 WASHER FLAT #10 ZINC
17 0D3153 1 DECAL T STRIP TB4 W/SEALED CON 61 024469 2 SCREW TAPTITE #10-32 X 3/8 BP
18 0A2273 1 HINGE RAM PANEL 62 033120 1 SCREW HHC #10-32 X 3/8
19 0C1229 1 DECAL CUST CONN BOX 63 033121 13 SCREW HHC #10-32 X 1/2
20 0E2693A 1 SWITCH MUSHRM HEAD/ARROWS 64 022507 4 SCREW HHC 1/4-20 X 1/2 G5
40MM 65 022097 4 WASHER LOCK M6-1/4
21 0E2693C 3 CONTACT BLOCK D5-3 X 01 W/2 1417 66 022473 4 WASHER FLAT 1/4 ZINC
22 032300 1 HOLDER FUSE 67 040479 4 VIB MNT 1.0 X 1.0 X 1/4-20
23 022676 1 FUSE 15A X AGC15 68 036261 4 RIVET POP .125 X .129-.133/#30
24 055349 1 INSULATOR 69 0C8243 1 WASHER LOCK HDPDEUTSCH
25 071361 1 POT 5K 10% 2.25W PNL 70 0C8244 1 NUT HDP DEUTSCH
26 050123 1 KNOB PLASTIC .25 SHAFT
27 061286 1 SOUNALERT BUZZER ADDITIONAL PARTS (BASE TANK UNITS)
28 061945 1 SWITCH SELECTOR 6A AMP/V 71 074908 4 SCREW HHTT M-5-0. 8 X 10 BP
29 0A4087 1 MASTER CTRL BOX E-PNL 75 0D3306 1 HARNESS BASETANK FOR E-PANEL
30 0E3703 1 LIGHT PANEL WITH LUG 76 0C5141 1 CONN DEUTSCH GASKET 8/12 POS
31 0C8481 1 BULB-PANEL LIGHT-12V DT
083288 1 LIGHT 28VDC .17A MIN BAYNT MNT
32 070082 1 BLOCKER LIGHT PANEL SPECIAL PARTS
33 0A2275 1 DOOR-STOP RAM PANEL 80 064733 2 BRACKET RESISTOR MNTNG FOR
34 030809 1 GROMMET 11/16 X 1/8 X 7/16 25W
35 028739 2 TIE WRAP 3.9" X .10" NAT'L UL 81 SEE TABLE A 1 RESISTOR #2
36 0A2400A 1 TRUNKING 180MM 82 SEE TABLE B 1 FIELD CIRCUIT BREAKER
37 074908 8 SCREW HHTT M5-0.8 X 10 BP 83 SEE TABLE C 1 AMMETER
38 0A1441B 1 COVER PLATE, AVR 84 SEE TABLE D 1 VOLTMETER AC
39 0C1127 1 DECAL AVR COVER 85 070042 1 METER FREQUENCY 55-65HZ
40 0A1441C 1 COVER PLATE EGOV 070042A 1 FREQUENCY METER 240V 45-55HZ
41 0A3394 1 DECAL ELEC GOVERNOR 86 067680 1 ASSY VOLTAGE REGULATOR 60HZ
42 0A5705 REF. FUSE 5A X LTTL215005 (NOT 092952 1 ASSY VOLTAGE REGULATOR 50HZ
SHOWN) 87 0E3783 1 DECAL WARNING REMOVE FUSE
43 0D3243 1 CBL ASSY-RS485 E PNL W/SEALED
44 0D3471 2 DECAL COVER DEUTSCH (RECT)
36 3
52 53 54
43 44 45
33
52 53 54
14 56 57 41
18 58 59
43 44 45 21 22
7
37 28 29
12 13 20 63
64 65 66 43 45 46
6
19
25 26 27 38
20 60 61 62 63 11
23 24
45
64 65 66 68 72
43 44 45
8
65 68 43 44 45
73
9
74
42 43
2
1 16 VIEW A
17 43 44 45
10
43 44 45 15
51 53 54
31
5 52 53 54 55
52 53 54 55 75
47 48 49 50
30
52 53 54
47 48 49
41 32
35
42 43
GOVERNOR CONTROL
BEHIND COVER
42 43
34
39 4
VIEW A
CONTROL PANEL LEFT SIDE
HINGE ASSEMBLY
OUTSIDE VIEW
SCALE: NONE
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
34
VIEW A DETAIL 1
HINGE ASSEMBLY
RECTIFIER ASSEMBLY
SCALE: NONE MICA
SCALE: NONE
12
9 9
68 13
58
11
10
63 63 D
59 60 59 60 2
17 43
22 23 47
20 21 21 21
50 52 50 52
64 65 14
64 65
67
66 67 6
FUEL
+ BAT
FUSE
A3392
BAT
1 36
24
35 29
50
25
52
26
61
46 87
D3153
0V 82
0V
27 30
75 0V
32
87 0V
76 +12/24V
37 37
SCREE
81
44
485-
28 83
485+
64 65
64
67 18
PRG RLY 3 NO
66 67 52 PRG RLY 3 NC
FUEL + 8
FUEL -
EE
ETAIL
1
4
16
A A
68
50 52 50 52 51
84
45 15 85
59 60 59 60
63 63 58 59 33 59 60
60 63 62
TSUJDA EGATLOV
53 54 86
55 56
50 51 41 40 38 39 50 51
19
ALL DIRECTLY EXCITED MACHINES 7A
19 TO 45KW P/N: 048467
ALL BRUSHLESS & PME MACHINES 5.5A
19 TO 26KW P/N: 054450
ALL BRUSHLESS & PME MACHINES 6.0A
21 TO 41KW P/N: 048505
ALL BRUSHLESS & PME MACHINES 7A CONTROL PANEL LEFT SIDE
45 TO 100KW P/N: 048476
ALL BRUSHLESS & PME MACHINES 4.5A
OVER 100KW P/N: 048476
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
1 0D8756 1 BOTTOM, E PANEL W/SEALED CONS 43 0D3243 1 CBL ASSY-RS485 E PNL W/SEALED
2 0D8754 1 "E" PANEL FRONT W/SILK SCREEN 44 0D3471 2 DECAL COVER DEUTSCH (RECT)
3 0A6322 1 PANEL RIGHT SIDE E 45 0D3471 2 DECAL COVER DEUTSCH (RECT)
4 0A6321 1 PANEL LEFT SIDE E (ELECTRONIC GOVERNOR HARNESS
5 0E3550 1 CHASSIS, UNIVERSAL IF EQUIPPED)
6 0D2382 1 HARNESS E-PANEL W/SEALED CONS 46 0C5141 2 CONN DEUTSCH GASKET 8/12POS
7 044213 1 RES 10R 5% 12W DT
8 025192 1 RECTIFIER MSC 2A 600V 1N5062 47 0E3783 1 DECAL, WARNING REMOVE FUSE
9 070370 2 WASHER MICA .203 50 022155 14 WASHER LOCK #6
10 023762 1 WASHER SHAKEPROOF EXT #10 STL 51 0C2428 14 SCREW TAPTITE PH 6-32X1/2 Z/YC
11 055444 1 HEATSINK 13.3L 52 0C2323 10 SCREW TAPTITE PH 6-32X5/8 ZYC
12 030468 1 WASHER STEP NYLON .20 53 022471 4 NUT HEX #8-32 STEEL
13 049939 1 RECTIFIER MSC 12A 600V 1N1206R 54 022264 8 WASHER LOCK M4
14 0A3392 1 DECAL TERMINAL BLOCK 55 038150 4 WASHER FLAT #8 ZINC
15 0C8229 1 DCL-E PNL TS#2 (W/FS) 56 036918 4 SCREW PPHM #8-32 X 1/2
16 0A6577 1 DECAL T STRIP 3 E PNL 57 0A2284 4 SCREW SWAGE 8-32 X 1/2 Z/YC
17 0D3153 1 DECAL T STRIP TB4 W/SEALED CON 58 022158 2 NUT HEX #10-32 STEEL
18 0D6947 1 HINGE CONTINUOUS 59 022152 14 WASHER LOCK #10
19 0C1229 1 DECAL CUST CONN BOX 60 023897 15 WASHER FLAT #10 ZINC
20 0E2693A 1 SWITCH MUSHRM HEAD/ARROWS 61 024469 2 SCREW TAPTITE #10-32 X 3/8 BP
40MM 62 033120 1 SCREW HHC #10-32 X 3/8
21 0E2693C 3 CONTACT BLOCK D5-3 X 01 W/2 1417 63 033121 13 SCREW HHC #10-32 X 1/2
22 032300 1 HOLDER FUSE 64 022507 4 SCREW HHC 1/4-20 X 1/2 G5
23 022676 1 FUSE 15A X AGC15 65 022097 4 WASHER LOCK M6-1/4
24 055349 1 INSULATOR 66 022473 4 WASHER FLAT 1/4 ZINC
25 071361 1 POT 5K 10% 2.25W PNL 67 040479 4 VIB MNT 1.0 X 1.0 X 1/4-20
26 050123 1 KNOB PLASTIC .25 SHAFT 68 036261 6 RIVET POP .125 X .129-.133/#30
27 061286 1 SOUNALERT BUZZER 69 0C8243 1 WASHER LOCK HDPDEUTSCH
28 061945 1 SWITCH SELECTOR 6A AMP/V 70 0C8244 1 NUT, HDP DEUTSCH
29 0A4087 1 MASTER CTRL BOX E-PNL
30 0E3703 1 LIGHT PANEL WITH LUG ADDITIONAL PARTS (BASE TANK UNITS)
31 0C8481 1 BULB-PANEL LIGHT-12V 75 0D3306 1 HARNESS BASETANK FOR E-PANEL
083288 1 LIGHT 28VDC .17A MIN BAYNT MNT 76 0C5141 1 CONN DEUTSCH GASKET 8/12 POS
32 070082 1 BLOCKER LIGHT DT
33 0A2275 1 DOOR-STOP RAM PANEL
34 030809 1 GROMMET 11/16 X 1/8 X 7/16 PANEL SPECIAL PARTS
35 028739 2 TIE WRAP 3.9" X .10" NAT'L UL 81 SEE TABLE A 1 RESISTOR #2
36 0A2400A 1 TRUNKING 180MM 82 SEE TABLE B 1 FIELD CIRCUIT BREAKER
37 064733 2 RES MTG BRACKET 83 SEE TABLE C 1 AMMETER
38 0A1441B 1 COVER PLATE, AVR 84 SEE TABLE D 1 VOLTMETER AC
39 0C1127 1 DECAL AVR COVER 85 070042 1 METER FREQUENCY 55-65HZ
40 0A1441C 1 COVER PLATE EGOV 070042A 1 FREQUENCY METER 240V 45-55HZ
41 0A3394 1 DECAL ELEC GOVERNOR 86 067680 1 ASSY VOLTAGE REGULATOR 60HZ
42 0A5705 REF. FUSE 5A X LTTL215005 (NOT 092952 1 ASSY VOLTAGE REGULATOR 50HZ
SHOWN) 87 074908 12 SCREW HHTT M5-0.8 X 10 BP
46
56 59 60
32 33
C
14 72 29
16 24 25
86
26
78 81
20
27
48 50
6
85
19
28
41 47
48 75 22
48 50 30 31 62
75
1
85
9
34
82 83
10
68 69 70 71
2
17
67
75
VIEW A
79 80 2 37 36 35
40
38
55 59 60
56 59 60 61
5
52 58
56 59 60
51 52 53 54
MICA
12
64 64
63
42
13 61
45
10
13
49 50
AVR BEHIND COVER
11 GOVERNOR CONTROL
BEHIND COVER ALIGNMENT
TAB
49 50
43 23
65
44 DETAIL 1
60 VIEW A
HINGE ASSEMBLY FOR LOWER PANEL
SCALE: NONE HOUSING SOCKET
SCALE: NONE
4
DETAIL 2
RECTIFIER ASSEMBLY
SCALE: NONE
CONTROL PANEL LEFT SIDE 84
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
1 0D8759 1 PANEL BOTTOM/BACK (E-PANEL) 37 061945 1 SWITCH 6A AMP/V SELECTOR
2 0D8754 1 "E" PANEL FRONT W/SILK SCREEN 38 067680 1 ASSY VOLTAGE REGULATOR 60HZ
3 0A6322 1 CONTROL PANEL RIGHT SIDE 092952 1 ASSY VOLTAGE REGULATOR 50HZ
4 0A6321 1 CONTROL PANEL LEFT SIDE 40 0A2275 1 DOOR-STOP RAM PANEL
5 0E3550 1 CHASSIS UNIVERSAL 41 0A2400A 1 TRUNKING 180MM
6 0C8320 1 HARNESS E PNL. WAUK (W/FS) 42 0A1441B 1 COVER PLATE AVR
7 SEE TABLE B 1 CIRCUIT BREAKER 43 0C1127 1 DECAL AVR COVER
8 044213 1 RESIST MISC 10R X 12W 44 0A1441C 1 COVER PLATE E-GOV
9 025192 1 RECTIFIER MSC 2A 600V 1N5062 45 0A3394 1 DECAL E-GOV COVER
10 SEE TABLE A 1 RESISTOR 2 46 030809 1 GROMMET 11/16 X 1/8 X 7/16
11 055444 1 HEAT SINK 47 028739 2 TIE WRAP 4" WHITE
12 030468 1 WASHER STEP NYLON .20 48 0C2323 10 SCREW PHM SWAGE 6-32 X 5/8 Z/YC
13 049939 1 RECTIFIER MSC 12A 600V 1N1206R 49 036901 4 SCREW PPHM #6-32 X 3/8
14 039271 1 FITTING 90 DEGREE 3/4 50 022155 7 WASHER LOCK #6
15 034616 1 FITTING STRAIGHT 3/4 51 036918 8 SCREW PPHM #8-32 X 1/2
16 0A3392 1 DECAL TERMINAL STRIP 52 022264 8 WASHER LOCK M4
17 0C8229 1 DECAL E PNL TS#2 (W/FS) 53 038150 4 WASHER FLAT #8 ZINC
18 0A6577 1 DECAL TERMINAL STRIP TB3 54 022471 4 NUT HEX #8-32 STEEL
19 0C2688 1 DECAL TERMINAL STRIP TB4 55 033120 1 SCREW HHM 10-32 X 3/8
20 048850 REF. BLOCK TERM 20A 5 X 6 X 1100V 56 033121 9 SCREW HHM 10-32 X 1/2
22 061286 1 AUDIBLE ALARM 58 0A2284 4 SCREW SWAGE 8-32 X 1/2 Z/YC
23 055089 1 CONN ELEC AMP M-N-L 15PLUG PNL 59 022152 10 WASHER LOCK #10
24 0E2693A 1 SWITCH MUSHRM HEAD/ARROWS 60 023897 11 WASHER FLAT #10 ZINC
40MM 61 022158 2 NUT HEX #10-32 STEEL
25 0E2693C 3 CONTACT BLOCK D5-3 X 01 W/2 1417 62 074130 1 LUG DIS SN-PLG I-T 22-18 CU
26 071361 1 POTENTIOMETER PNL 5K +/-10% 63 036261 6 RIVET POP .125 X .129-.133/#30
2.25W 64 070370 2 WASHER MICA .203
27 050123 1 KNOB PLASTIC .25 SHAFT 65 023762 1 WASHER SHAKEPROOF EXT #10 STL
28 055349 1 INSULATOR 67 040479 4 MOUNT VIBR 1.0 X 1.0 X 1/4-20
29 0A4087 1 MASTER CONTROL BOX 68 022287 4 SCREW HHC 1/4-20 X 3/4 G5
30 0C8481 REF. BULB-PANEL LIGHT-12V 69 022097 4 WASHER LOCK M6-1/4
0E3703 REF. LIGHT PANEL WITH LUG 70 022473 4 WASHER FLAT M6-1/4 ZINC
083288 REF. LIGHT 28VDC .17A MIN BAYNT MNT 71 047246 4 WASHER FLAT 1/4 SPECIAL
31 070082 1 LIGHT BLOCKER 72 0D6947 1 HINGE CONTINUOUS
32 032300 1 FUSE HOLDER 74 022188 2 NUT HEX #6-32 STEEL
33 022676 1 FUSE 15A X AGC15 75 0C2428 8 SCREW TAPTITE PH #6-32 X 1/2 ZYC
34 070054 1 AMMETER AC 0-50 * 0A5705 1 FUSE 5A X LTTL215005 HLDRA4017
070055 1 AMMETER AC 0-100 (NOT SHOWN)
070056 1 AMMETER AC 0-150 78 057335 REF. BLOCK TERM 20A 20 X 6 X 1100V
070057 1 AMMETER AC 0-300 79 0C4167 REF. BLOCK TERM 20A 14 X 6 X 1100V
070058 1 AMMETER AC 0-400 80 055911 REF. BLOCK TERM 20A 12 X 6 X 1100V
070059 1 AMMETER AC 0-600 81 0441140156 REF. WIRE ASSEMBLY
070060 1 AMMETER AC 0-800 82 084717 1 ASSY TIME DELAY (13.3L GAS ONLY)
075323 1 AMMETER AC 0-1000 83 036908 1 SCREW PPHM #6-32 X 1-1/4 (13.3L
075324 1 AMMETER AC 0-1600 GAS ONLY)
075325 1 AMMETER AC 0-2000 84 0C1229 1 DECAL WARNING
35 070043 1 METER VOLT AC 0-300 85 024469 2 SCREW HHTT #10-32 X 3/8 CZ_
070044 1 METER VOLT AC 0-600 86 0F3783 1 DECAL WARNING REMOVE FUSE
36 070042 1 METER FREQUENCY 55-65HZ
070042A 1 METER FREQUENCY 240V 45-55HZ
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
36 3
52 53 54
12 14 40 56 57 41
58 59
52 53 54 43 44 45 21 22
7
18 37 28 29
43 45 46
6
19
25 26 27 38
11
23 45
43 44 8
13 9
1
2
16 VIEW A
17 43 44 45
10
43 44 45 15
51 53 54
31
5 52 53 54 55
52 53 54 55
47 48 49 50
30
53 54
47 48 49
32
35
41
42 43
AVR BEHIND COVER
GOVERNOR CONTROL
BEHIND COVER
42 43
33
34
39
CONTROL PANEL LEFT SIDE
OUTSIDE VIEW VIEW A
HINGE ASSEMBLY
SCALE: NONE
SLOT WIRE 20
# #
1 0
2 1
15
12
3 2
11
14
4 4
5 S1
13
10
1
7
6 6
7 S15
ALIGNMENT
8
TAB
9 S16
DETAIL 1
11 S3 WIRE NUMBERS/LOCATIONS
12 58 FOR LOWER PANEL
13 59 HOUSING SOCKET
14 178 SCALE: NONE
15 183 REAR VIEW
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
46
F
56 59 60
32 33
14 72 29
16 24
26
78 81
2
27
48
6
48
19
28
47
48
22
48 50 30 31 62
1
48
34
82 83
68 69 70 71
2
17
67
VIEW A
79 80
37 36 35
40
38
55 59 60
56 59 60 61
5
52 58
56 59 60
51 52 53 54
MICA
5
6 SLOT
63
42 # #
13 61
45 1 0
2
49 50 4
AVR BEHIND COVER S1
11 GOVERNOR CONTROL
BEHIND COVER ALIGNMENT
S15 TAB
49 50 S2
43 S16 23
65
44 DETAIL 1
60 VIEW A
HINGE ASSEMBLY FOR LOWER PANEL
SCALE: NONE HOUSING SOCKET
15 183
SCALE: NONE
4
DETAIL 2
RECTIFIER ASSEMBLY
SCALE: NONE
CONTROL PANEL LEFT SIDE 84
48 81 74
81 OVER 100KW WITH 12 OR 24V DC SYSTEMS P/N: 086266
50
74
7A
P/N: 048467
5.5A
P/N: 054450
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
1 0A6320 1 CONTROL PANEL BOTTOM 37 061945 1 SWITCH 6A AMP/V SELECTOR
2 0A6324 1 CONTROL PANEL FRONT 38 067680 1 ASSY VOLTAGE REGULATOR 60HZ
3 0A6322 1 CONTROL PANEL RIGHT SIDE 092952 1 ASSY VOLTAGE REGULATOR 50HZ
4 0A6321 1 CONTROL PANEL LEFT SIDE 40 0A2275 1 DOOR-STOP RAM PANEL
5 0E3550 1 CHASSIS, UNIVERSAL 41 0A2400A 1 TRUNKING 180MM
6 0C8320 1 HARNESS E PNL. WAUK (W/FS) 42 0A1441B 1 COVER PLATE AVR
7 SEE TABLE B 1 CIRCUIT BREAKER 43 0C1127 1 DECAL AVR COVER
8 044213 1 RESIST MISC 10RX12W 44 0A1441C 1 COVER PLATE E-GOV
9 025192 1 RECTIFIER MSC 2A 600V 1N5062 45 0A3394 1 DECAL E-GOV COVER
10 SEE TABLE A 1 RESISTOR 2 46 030809 1 GROMMET 11/16 X 1/8 X 7/16
11 055444 1 HEAT SINK 47 028739 2 TIE WRAP 4" WHITE
12 030468 1 WASHER STEP NYLON .20 48 0C2323 12 SCREW PHM SWAGE 6-32 X 5/8 Z/YC
13 049939 1 RECTIFIER MSC 12A 600V 1N1206R 49 036901 4 SCREW PPHM #6-32 X 3/8
14 039271 1 FITTING 90DEGREE 3/4 50 022155 7 WASHER LOCK #6
15 034616 1 FITTING STRAIGHT 3/4 51 036918 8 SCREW PPHM #8-32 X 1/2
16 0A3392 1 DECAL TERMINAL STRIP 52 022264 8 WASHER LOCK M4
17 0C8229 1 DECAL E PNL TS#2 (W/FS) 53 038150 4 WASHER FLAT #8 ZINC
18 0A6577 1 DECAL TERMINAL STRIP TB3 54 022471 4 NUT HEX #8-32 STEEL
19 0C2688 1 DECAL TERMINAL STRIP TB4 55 033120 1 SCREW HHM 10-32 X 3/8
20 048850 REF. BLOCK TERM 20A 5 X 6 X 1100V 56 033121 13 SCREW HHM 10-32 X 1/2
22 061286 1 AUDIBLE ALARM 58 0A2284 4 SCREW SWAGE 8-32 X 1/2 Z/YC
23 055089 1 CONN ELEC AMP M-N-L 15PLUG PNL 59 022152 14 WASHER LOCK #10
24 0E2693A 1 SWITCH MUSHRM HEAD/ARROWS 60 023897 15 WASHER FLAT #10 ZINC
40MM 61 022158 2 NUT HEX #10-32 STEEL
25 0E2693C 3 CONTACT BLOCK D5-3 X 01 W/2 1417 62 074130 1 LUG DIS SN-PLG I-T 22-18 CU
26 071361 1 POTENTIOMETER PNL 5K +/-10% 63 036261 4 RIVET POP .125 X .129-.133/#30
2.25W 64 070370 2 WASHER MICA .203
27 050123 1 KNOB PLASTIC .25 SHAFT 65 023762 1 WASHER SHAKEPROOF EXT #10 STL
28 055349 1 INSULATOR 67 040479 4 MOUNT VIBR 1.0 X 1.0 X 1/4-20
29 0A4087 1 MASTER CONTROL BOX 68 022287 4 SCREW HHC 1/4-20 X 3/4 G5
30 0C8481 REF. BULB-PANEL LIGHT-12V 69 022097 4 WASHER LOCK M6-1/4
0E3703 REF. LIGHT PANEL WITH LUG 70 022473 4 WASHER FLAT M6-1/4 ZINC
083288 REF. LIGHT 28VDC .17A MIN BAYNT MNT 71 047246 4 WASHER FLAT 1/4 SPECIAL
31 070082 1 LIGHT BLOCKER 72 0A2273 1 HINGE RAM PANEL
32 032300 1 FUSE HOLDER 74 022188 2 NUT HEX #6-32 STEEL
33 022676 1 FUSE 15A X AGC15 75 0C2428 8 SCREW TAPTITE PH #6-32 X 1/2 ZYC
34 070054 1 AMMETER AC 0-50 * 0A5705 1 FUSE 5A X LTTL215005 HLDRA4017
070055 1 AMMETER AC 0-100 (NOT SHOWN)
070056 1 AMMETER AC 0-150 78 057335 REF. BLOCK TERM 20A 20 X 6 X 1100V
070057 1 AMMETER AC 0-300 79 0C4167 REF. BLOCK TERM 20A 14 X 6 X 1100V
070058 1 AMMETER AC 0-400 80 055911 REF. BLOCK TERM 20A 12 X 6 X 1100V
070059 1 AMMETER AC 0-600 81 0441140156 REF. WIRE ASSEMBLY
070060 1 AMMETER AC 0-800 82 084717 1 ASSY TIME DELAY (13.3L GAS ONLY)
075323 1 AMMETER AC 0-1000 83 036908 1 SCREW PPHM #6-32 X 1-1/4 (13.3L
075324 1 AMMETER AC 0-1600 GAS ONLY)
075325 1 AMMETER AC 0-2000 84 0C1229 1 DECAL WARNING
35 070043 1 METER VOLT AC 0-300 85 0E3783 1 DECAL WARNING REMOVE FUSE
070044 1 METER VOLT AC 0-600
36 070042 1 METER FREQUENCY 55-65HZ
070042A 1 METER FREQUENCY 240V 45-55HZ
45
64
43
36 3
52 53 54
64 65
68 65
12 14 40 56 57 41
59
55 53 43 45 60 67 21 22
7
37 28 29
45
6
19
25 26 27 38
11
23 45
43 8
16
9
2
1 VIEW A
17 67 63 45 15 45 61 67 45 62 67 10
51 53 54
31
5 52 53 54 55
52 53 54 55
48 49 50
30
52 53 54
47 48 49
SLOT 20
# #
1 0
2 1
15
12
3 2 41
11
14
5 S1
10
13
1
7
6
7
ALIGNMENT
8 S2
TAB
9 S16
10 57 DETAIL 1
11 S3 WIRE NUMBERS/LOCATIONS 39
12 58 FOR LOWER PANEL
59 HOUSING SOCKET VIEW A
14 SCALE: NONE HINGE ASSEMBLY
15 REAR VIEW SCALE: NONE
32
35
42 43
AVR BEHIND COVER
GOVERNOR CONTROL
BEHIND COVER
(IF SO EQUIPPED)
42 43
33
34
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
1 0C2616 1 CONTROL PANEL BOTTOM 35 0A3394 1 DECAL ELECTRONIC GOVERNOR
2 0C3872 1 CONTROL PANEL FRONT 36 030809 1 GROMMET 11/16 X 1/8 X 7/16
3 0A6322 1 CONTROL PANEL RIGHT SIDE 37 029333 1 TIE WRAP 7" WHITE
4 0A6321 1 CONTROL PANEL LEFT SIDE 38 074130 1 LUG DIS SN-PLG I-T 22-18 CU
5 0E3550 1 CHASSIS, UNIVERSAL 39 036261 4 RIVET POP .125 X .129-.133/#30
6 0C8328 1 HARNESS E PANEL MAIN 40 040479 4 MOUNT VIBR 1.00 X 1.00 X 1/4-20
7 0A4087 1 MASTER CONTROL BOX 41 0A2273 1 HINGE RAM PANEL
8 SEE NOTE 1 AMMETER 42 036901 4 SCREW PPHM #6-32 X 3/8
9 SEE NOTE 1 VOLT METER AC 43 022155 7 WASHER LOCK #6
10 SEE NOTE 1 FREQUENCY METER 45 0C2323 12 SCREW TAPTITE PH 6-32 X 5/8 ZYC
11 074386 1 SWITCH VOLT/AMP 47 036918 4 SCREW PPHM #8-32 X 1/2
12 0A9234 CONNECTOR 90 DEGREE ELBOW 48 022264 8 WASHER LOCK M4
13 034616 1 FITTING STRAIGHT 3/4 49 038150 4 WASHER FLAT M4
14 0C3207 1 DECAL TERM STRIP TB1 50 0A2284 4 SCREW SWAGE 8-32 X 1/2 Z/YC
15 0C8229 1 DECAL TERM STRIP TB2 51 033120 1 SCREW HHM 10-32 X 3/8
16 0C3208 1 DECAL TERM STRIP TB3 52 033121 17 SCREW HHM 10-32 X 1/2
17 0C3206 1 DECAL TERM STRIP TB4 53 022152 20 WASHER LOCK #10
18 0C4110 1 RELAY 24V 50A W/DIODE 54 023897 20 WASHER FLAT #10 ZINC
19 061286 1 ALARM AUDIBLE 55 022158 6 NUT HEX #10-32 STEEL
20 055089 1 CONN ELEC AMP M-N-L 15PLUG PNL 56 022287 4 SCREW HHC 1/4-20 X 3/4 G5
21 098426A 1 SWITCH EMERGENCY STOP 57 022097 4 WASHER LOCK M6-1/4
22 098426C 3 CONTACT EMERGENCY STOP 58 022473 4 WASHER FLAT M6-1/4 ZINC
SWITCH 59 047246 4 WASHER FLAT 1/4 SPECIAL
23 091472 9.5" WIRE DUCT1 X 1.5 60 057335 1 BLOCK TERM 20 POS TB1
24 091472A 9.5" WIRE DUCT COVER 1" 61 0C4167 1 BLOCK TERM 20A 14 X 6 X 1100V
25 0E3703 1 LIGHT PANEL WITH LUG 62 055911 1 BLOCK TERM 20A 12 X 6 X 1100V
26 083288 1 LIGHT 28VDC .17A MIN BAYNT MNT 63 061520 1 BLOCK TERM 20A 9 X 6 X 1100V
27 070082 1 LIGHT BLOCKER 64 0441140156 1 WIRE ASSY 18AWG #0
28 032300 1 FUSE HOLDER 65 022188 2 NUT HEX #6-32 STEEL
29 022676 1 FUSE 15A X AGC15 66 0C1229 1 DECAL WARNING
30 067710 1 CONTROLLER ELECTRONIC 67 046669 17 BLOCK TERM JUMPER
GOVERNOR 68 0E3783 1 DECAL, WARNING REMOVE FUSE
31 0A2275 1 DOOR-STOP RAM PANEL
32 0A1441B 1 COVER PLATE AVR NOTE: CONTACT GENERAC SERVICE FOR CORRECT PART NUMBER
33 0C1127 1 DECAL AVR COVER FOR TOUR UNIT.
34 0A1441C 1 COVER PLATE ELECTRONIC
GOVERNOR