5) Why in a three pin plug the earth pin is thicker and longer than the other pins?
Answer: It depends upon R=rho l/a where area(a) is inversely proportional to
resistance (R), so if (a) increases, R decreases & if R is less the leakage current
will take low resistance path so the earth pin should be thicker. It is longer
because the First to make the connection and last to disconnect should be earth
Pin. This assures Safety for the person who uses the electrical instrument.
9) What is the difference between MCB & MCCB, Where it can be used?
Answer: MCB is miniature circuit breaker which is thermal operated and use for
short circuit protection in small current rating circuit. MCCB moulded case circuit
breaker and is thermal operated for over load current and magnetic operation for
instant trip in short circuit condition. under voltage and under frequency may be
inbuilt. Normally it is used where normal current is more than 100A.
18) how to calculate capacitor bank value to maintain unity power factor with some
suitable example?
Answer:KVAR= KW(TAN(COS(-1)#e)- TAN(COS(-1)#d) )
#e= EXISTING P.F.
#d= DESIRED P.F.
20) There are a Transformer and an induction machine. Those two have the
same supply. For which device the load current will be maximum? And why?
Answer: The motor has max load current compare to that of transformer bcoz
the motor consumes real power.. and the transformer is only producing the
working flux and its not consuming.. hence the load current in the transformer is
because of core loss so it is minimum.
is the ac generator whose field winding are stationary and armature rotates. initial
voltage is built up by residual magnetism gives the starting torque to the
generator.
31) Why use the VCB at High Transmission System? Why can't use ACB?
Answer: Actually the thing is vacuum has high arc quenching property compare
to air because in VCB ,the die electric strength is equal to 8 times of air . That
why always vacuum used as in HT breaker and air used as in LT.
32) What is the difference between surge arrestor and lightning arrestor?
Answer: LA is installed outside and the effect of lightning is grounded, where as
surge arrestor installed inside panels comprising of resistors which consumes the
energy and nullify the effect of surge.
33) Why syn. generators are used for the production of electricity?
Answer: synchronous machines have capability to work on different power factor
(or say different imaginary power varying the field emf. Hence syn. generators are
used to produce electricity.
43) What is the Polarization index value? (pi value) and simple definition of
polarization index?
Answer: Its ratio between insulation resistance (IR)i.e. megger value
for 10min to insulation resistance for 1 min. It ranges from 5-7 for new motors &
normally for motor to be in good condition it should be Greater than 2.5 .
44) What will happen when power factor is leading in distribution of power?
Answer: If there is high power factor, i.e if the power factor is close to one:
1) losses in form of heat will be reduced.
2) cable becomes less bulky and easy to carry, and very cheap to afford, &
it also reduces over heating of tranformers.
45) what is the one main difference between UPS & inverter ? And electrical
engineering & electronics engineering ?
Answer: uninterrupted power supply is mainly use for short time means
according to ups VA it gives backup. ups is also two types : on line and offline .
Prepared By K.P.N Subhash
Interview questions
online ups having high volt and amp for long time backup with with high dc
voltage. but ups start with 12v dc with 7 amp. but inverter is start with 12v,24,dc
to 36v dc and 120amp to 180amp battery with long time backup.
3. exact posiitoning
4. better protection for motor.
5.high/low speed selection.
6.reliability of break shoe.
7.programmable break control.
8.easy circutry
9.reduction in controls
10.increases motor life
49) Which type of A.C motor is used in the fan (ceiling fan, exhaust fan, padestal
fan, bracket fan etc) which are find in the houses ?
Answer:Its Single Phase induction motor which mostly squirrel cage rotor and
are capacitor start capacitor run.
50) why, when birds sit on transmission lines or current wires doesn't get shock?
Answer: Its true that if birds touch the single one line (phase or neutral) they
don't get electrical shock... if birds touch 2 lines than the circuit is closed and they
Prepared By K.P.N Subhash
Interview questions
get electrical shock.. so if a human touch single one line(phase) then he doesn't
get shock if he is in the air (not touching - standing on the ground if he is standing
on the ground then touching the line (phase) he will get a shock because the
ground on what we standing is like line (ground bed - like neutral) and in the
most of electric lines the neutral is grounded... so that means that human who
touch the line closes the circuit between phase and neutral.
52) what happen if we give 220 volts dc supply to d bulb r tube light?
Answer: Bulbs [devices] for AC are designed to operate such that it offers high
impedance to AC supply. Normally they have low resistance. When DC supply is
applied, due to low resistance, the current through lamp would be so high that it
may damage the bulb element.
53) Which motor has high Starting Torque and Staring current DC motor,
Induction motor or Synchronous motor?
Answer: DC Series motor has high starting torque. We can not start the
Induction motor and Synchronous motors on load, but can not start the DC series
motor without load.
55) What is vaccum currcuit breaker.define with cause and where be use it
Device?
Answer: A breaker is normally used to break a ciruit. while breaking the circuit,
the contact terminals will be separated. At the time of seperation an air gap is
formed in between the terminals. Due to existing current flow the air in the gap is
ionised and results in the arc. various mediums are used to quench this arc in
respective CB's. but in VCB the medium is vaccum gas. since the air in the CB is
having vaccum pressure the arc formation is interrupted. VCB's can be used upto
Prepared By K.P.N Subhash
Interview questions
11kv.
59) Why Human body feel Electric shock ?? n in an Electric train during running ,
We didnt feel any Shock ? why?
Answer: Unfortunately our body is a pretty good conductor of electricity, The
golden rule is Current takes the lowest resistant path if you have insulation to our
feet as the circuit is not complete (wearing rubber footwear which doing some
repairs is advisable as our footwear is a high resistance path not much current
flows through our body).The electric train is well insulated from its electrical
system.
62) How can you start-up the 40w tube lite with 230v AC/DC without using any
choke/Coil?
Answer: I t's possible by means of Electronic choke. Otherwise it's not possible
to ionise the particles in tube. Light, with normal voltage.
65) Why link is provided in neutral of an ac circuit and fuse in phase of ac circuit?
Answer: Link is provided at a Neutral common point in the circuit from which
various connection are taken for the individual control circuit and so it is given in
a link form to withstand high Amps. But in the case of Fuse in the Phase of AC
circuit it is designed such that the fuse rating is calculated for the particular circuit
(i.e load) only.So if any malfunction happens the fuse connected in the particular
control circuit alone will blow off.
66) what is the diff. btwn. electronic regulator and ordinary rheostat regulator for
fans?
Answer: The difference between the electronic and ordinary regulator is that in
electronic reg. power losses are lessi.e.for as we decrease the speed the
electronic reg. give the power needed for that particular speed but in case of
ordinary rh type reg. the power wastage is same for every speed and no power is
saved. In electronic regulator triac is employed for speed cntrl.by varying the
firing angle speed is controlled but in rheostat ctrl resistance is decreased by
steps to achieve speed control.