DCD Material Test Standards - September - 2018
DCD Material Test Standards - September - 2018
DCD Material Test Standards - September - 2018
4.1.2. The weather protection of buildings is not the scope or intention of this section.
Thermal and Weather protection aspect of the building façade, such as protection
from temperature, wind, water, pressure etc., shall comply with Municipality regula-
tions, assembly tests and requirements.
4.1.3. The intention of this section is to ensure that flame spread on exterior façade is re-
stricted.
4.1.4. This section applies only to non load bearing exterior walls.
4.1.5. Where exterior walls are required to be loadbearing, such walls shall comply with
relevant sections of this Chapter.
4.2.2. Where “Assembly Tests” are mandated by Section 4.2.1., the tests shall be conduct-
ed for the entire system assembly, that is intended for use on building façade, in-
cluding wall panels, cavities, insulation, panel rails, joints, sealants, seams, fasteners,
barriers and other construction details. Laboratories testing assembly tests shall en-
sure that the test specimen is duplicated as per intended final installation specifica-
tions, including dimensions, cavities, joints and sealants. Laboratories shall ensure
that façade assembly tests are not ‘over engineered’ purely to pass test criteria.
4.2.3. The tests shall clearly indicate “Pass” or “Fail” criteria and such results shall be clear-
ly noted on the Test Certificates (and CoC, Certificate of Compliance), in evaluation
of the following minimum requirements.
a. The wall assembly shall resist flame propagation over the face of the exterior wall.
b. The wall assembly shall resist flame propagation over the face of the interior of
the wall assembly and cavity.
c. The wall assembly shall resist flame propagation from one story to the next.
d. The wall assembly shall resist flame propagation from compartment of fire origin
to the adjacent compartment.
4.3.2. Interior fires are intervened and controlled by automatic sprinkler system or by fire
fighters. However, when the fire outgrows fire fighter’s efforts or the sprinkler sys-
tem and reaches flash over stage, it leaps out from the openings onto the exterior
façade or cavities behind the façade of the building causing “leap frog” effect.
4.3.3. At this stage, if the façade material delaminates, exposing the core, if the core of the
facade material is combustible, if the cladding system components such as sealants,
linings, insulation are combustible, the flames start consuming the combustible ma-
terial on the façade, spreading along the surface of the façade and along the cavities
behind the façade.
4.3.4. If the floor slab fire stopping is absent or fire stop material is not approved and not
installed as per standards, if the curtainwall is not listed, the flames penetrate
through the gaps and reach for the upper floors. Flames can even propagate down-
wards if the material on façade is flammable.
4.3.5. Such propagated flames find the other openings of the building from exterior and
enter back into the buildings, feeding on the interior fire loads. This “Reverse leap
frog” effect continues along the building from floor to floor, to height and width,
consuming the building façade swiftly.
4.3.6. Cavity can be part of the façade system by design or cavity can be created by com-
bustible materials on façade system or poor integrity of the façade panels or poor
performance of perimeter joint systems and fire stopping systems or combinations
of these factors. As flame propagates and enters this cavity behind façade system, it
can elongate ten times its length in its search for oxygen in the confined space of
such cavity, thus burning behind the façade system unnoticed from outside for many
floors above the fire origin.
4.3.7. As the intense heat develops behind the façade and flames continue to grow, fa-
çade panels delaminate, exposing more core material to the flame, resulting in a
sudden engulfing of vast area and multiple stories of the building façade under fire.
4.3.8. Apart from combustible façade materials, poor installation, poor joint detailing, poor
mechanical detailing in fixing insulation and façade panels and poor railing system
installations contribute to the rapid façade flame spread and collapse of façade pan-
els and frames, making external fire fighting extremely difficult.
4.3.10. The initial ignition of the fire can be attributed to human behavior as well. See Chap-
ter 18., Section 2.21. Responsibilities of Residents.
Following 10 approaches have been adopted by UAE Civil Defence to tackle the caus-
es of Façade flame spread, pointed out in Section 4.3.9.
4.4.1.1. Core of the Façade material shall be tested in exposed form as per test
requirements of this code.
4.4.1.2. Façade panel as a product shall be tested as per test requirements of this
code.
4.4.1.3. Façade system as wall assembly shall be tested or listed as per test re-
quirements of this code.
4.4.1.4. Curtainwall, Perimeter joints and fire stopping shall be a listed system.
4.4.1.5. Cavity Fire Barrier bands shall be provided in concealed cavities between
façade and primary substrate, at every slab.
4.4.1.7. Exterior Sprinklers should be considered for the balconies having com-
bustible facade. Interior window sprinklers should be considered for the
glazing. See Chapter 9.
4.4.1.8. Consultants shall have competent and qualified façade specialists in-
house or shall hire Civil Defence approved house of expertise who have
experience and expertise in façade consultancy for Façade design, system
selection and supervision of the façade contractor.
4.4.1.9. Façade contractor and fabricator shall be approved by Civil Defence, with
valid Civil Defence License.
4.4.3.2. Where manufacturer or supplier undertakes both tests, TEST 1, as pre Sec-
tion 4.4.2.1. as well as TEST 2, as per Section 4.4.3.1., and produces the
“system” test certificates, the Civil Defence registration and certificate shall
be for the product including full system and permission to be installed on
exterior façade of any building, provided that the façade fabricator under-
takes that project façade arrangement matches the tested and certified
wall assembly arrangement.
4.4.3.3. The system manufacturer or supplier and the fabricators shall provide a
formal submittal to the Municipality and Civil Defence material approval
department for the product registration, that shall consist of the following.
4.4.3.4. Where the building envelope is uniquely shaped and designed, or there is no clear dis-
tinction between vertical façade and horizontal roofing, or where a single envelope is
installed as roofing as well as façade envelope, such materials and system assembly
shall be tested for both façade as well as roofing requirements in accordance with Sec-
tion 4, Section 5 and Section 6 of this chapter.
4.4.4.2. Consultant’s façade design submittal to Civil Defence shall be during project
design NOC application, along with architecture, fire alarm, fire fighting and
smoke control proposals. See Annexure 1. Drawing Submission Require-
ments.
4.4.4.3. Consultant’s façade design shall be complete with system listings, material
approval certifications, drawings, sections, illustrations specifying installa-
tion methods as per manufacturer’s guide-lines, insulations, thermal barri-
ers, panel railing, cavity fire barrier locations/specifications, primary sub-
strate details and fixing details.
4.4.4.4. Engineering Judgments (EJ), if any, shall be permitted where Civil Defence
has no objections. Such Engineering Judgment submissions to Civil Defence
shall be site specific, prepared and stamped jointly by main consultant,
House of expertise, Cladding contractor, façade system manufacturers and
façade installers.
4.4.4.5. Where the building envelope is uniquely shaped and designed, or there is
no clear distinction between façade and roofing, or where a single envelope
is installed as roofing as well as façade envelope, such materials and system
assembly shall satisfy both façade and roofing test requirements and shall
be subjected to “mock-up” tests, if Civil Defence initiates such a require-
ment based on the proposal reviews.
4.4.5. Installation
4.4.6.1. Installer specializing in façade and cladding system shall be trained as per
manufacturer’s standards and guidelines and certified by the system manu-
facturer.
4.6.6.2. The trained and experienced installer shall be qualified and licensed by Civil
Defence. The Civil Defence written examinations and license shall be based
on the training and certification provided by the system manufacturer to
install manufacturer’s products as per specified listed system requirements.
4.4.7.1. Special inspections shall be required for all façade and cladding systems.
Inspection shall take place in successive stages as installation proceeds.
Such successive stages shall be at every 20% intervals of the total building
height.
4.4.7.4. Main consultant or house of expertise, who inspect the installation, shall
certify and signoff the façade and cladding installations undertaken during
progressive inspections at each successive stage of installations in report
which shall be part of the documentation required by Civil Defence during
final inspection and handing over.
4.5.2.1. Façade materials, exterior wall systems, claddings and insulation installed
on any building shall not reduce the fire resistance rating of the exterior
wall where required by other sections of this Chapter.
4.5.3.1. Façade Cladding Materials such as MCM and ACP shall be completely sepa-
rated from the building interior and plenum by a thermal barrier, complying
to test standards of Section 7.1.11. of this chapter.
4.5.3.2. Required thermal barriers shall not be installed on the walls or frames with
adhesives alone. Thermal barriers shall be fixed mechanically on primary
substrate, structural frame or the wall or on rails as appropriate.
4.5.3.3. Thermal barrier is not mandatory only when MCM or ACP or cladding mate-
rials are used on balconies and minor architectural appendages on exterior
wall.
4.5.3.4. In all cases the Building Exterior Base wall must be imperforate and provide
a nominal 15 minutes fire resistance ( Insulation and integrity).
4.5.4.1. Cavity Fire Barriers shall be incorporated into façade designs, including ar-
chitectural features with uninterrupted vertical columns (e.g. High Rise
‘Fins’), at every floor horizontally around window openings on all sides to
limit fire breakout from a room into the adjacent cavity. This cavity barrier
shall not be a thermal bridge.
4.5.4.2. Cavity Fire Barriers shall be incorporated into façade design at every floor
vertically to restrict flame within continuous cavities or where cavities
bridge the perimeter firestopping. Perimeter Firestopping systems shall
be installed as per Section 3 of this chapter.
4.5.4.4. The cavity fire barrier shall be 100 mm high and, where the thermal insula-
tion is not of equivalent fire resistance to the cavity barrier, shall run
through insulation horizontally at each floor level and vertically on each
face of façade as required by Section 4.5.4.2.
4.5.4.6. The cavity fire barrier shall be mechanically bonded to the primary sub-
strate or structural frame and extended or compressed behind the finish
façade panel to ensure that no fire path are created between the barrier
and substrate or external façade panel.
4.5.4.7. Where cavity is necessary part of ventilated façade design and cavity needs
to be maintained, an intumescent system, approved and listed for the pur-
pose shall be fixed as cavity fire barrier band. These intumescent bands
serve as fire barriers when exposed to flames and shall expand to seal the
gaps.
4.5.6.1. Use of flammable silicon or fillers or non rated groove sealants, materials
in between panel joints is not permitted unless these joint fillers are test-
ed as per Section 7.1.45 and part of their full wall assembly and were used
in achieving “pass criteria” as the Wall Assembly “Large Scale Tests”. See
figures 1.19.a and figure 1.19.b.
4.5.6.2. Vapour Barrier systems (VBS) and membranes are generally provided to
resist water vapour and are often an essential part of the façade system.
Vapour barriers, particularly rubber, bituminous based materials, maybe
combustible by their nature and may affect the overall performance of
the façade system in respect of fire development and spread. Therefore
the VBS product should be checked against the MSDS for base content
(See Section 4.5.1.1). VBS products must be registered and Licensed by
the Civil Defence and must achieve EN13501-1 Class A as per Section
7.1.45.
4.5.6.3. EPDM products, Rubber sheeting and architectural carpets are creating
new design possibilities as building skins. EPDM rubber (ethylene propyl-
ene diene monomer rubber) and similar rubber products must not be
used as a full VBS/Façade Liner. However it is acceptable in other dis-
crete locations, such as Curtain Wall Gaskets or window waterproofing
provided the fire performance achieves a minimum of EN 13501-1 C,
S2,d0., as per Section 7.1.45.
4.5.6.4. Artificial turf has been typically used for sports grounds or indoor solu-
tions, but now this surface covering is being used in the design of indoor
and outdoor spaces in horizontal and vertical applications. Where such
applications are used as floor coverings they shall be tested to EN 13501
-1 and achieve a minimum of Cfl,S1 where the premises are provided
with a sprinkler system or, with the exception of areas being used for
Assembly, where the installation is completely out doors. Where the
material is being used as an internal wall covering it must comply with
Section 7.1.4. or when proposed as an External wall covering, it shall
comply with the requirements of chapter 1 Section 4, achieve ASTM E84
class A and EN13501-1 Class A2 minimum. The Façade system which the
material forms a part must also be tested to NFPA 285 and NFPA 268
( ‘no ignition at 12.5 kw/m2 at 20 minutes)
4.5.8.1. Architectural features shall comply to all the relevant requirements of Sec-
tion 4.
4.5.9.3. Fire safing forming the perimeter edge protection must ensure the same
performance as the structural floor slab in respect of F and T ratings.
4.5.10.1. Façade lighting fixtures have high intensity light and heat. When over heat-
ed or poorly installed, these fixtures emit intense heat and can be cause of
fire ignition source when in contact with readily combustible materials.
4.5.10.2. Flood Lighting fixtures shall not be installed directly on façade surface,
wood, plastic, insulation, façade cavity with combustible material etc. Flood
lighting fixtures shall be installed such that lighting fixture heat is not dissi-
pated directly onto the façade surface. Appropriate steel framing and non
combustible thermal insulation shall separate the lighting fixtures from fa-
çade surface.
4.5.11.2. Poor installation, poor wiring and overheating of such electrical equipment
and its contact with combustible insulation or façade material shall be
avoided. Electrical equipment shall be separated from façade surface with
proper steel frames, steel lining, metal conduit for wiring and non combus-
tible insulation coverings.
4.5.11.3. Façade cavity shall not be used for routing electrical cabling, LPG or natural
gas piping and hot water piping.
4.5.12.2. Sign boards, billboards, advertising banners shall comply with Table 1.9.56.
4.5.12.2. Flammable, Combustible, Plastic and Foam materials shall not be used for
advertising or billboard on façade envelope.
4.5.13. Housekeeping
4.5.13.1. Competent house keeping shall be ensured in every building to keep exteri-
or façade surface clean and free from flammable and combustible materials
within the vicinity. Trash accumulation near façade surface shall be avoid-
ed. Trash cans shall not be placed adjacent to exterior façade surface.
4.6.2. Definition
4.6.2.1. A factory manufactured panel consisting of metal skins bonded to both fac-
es of a “core”. All MCM’s shall be tested and approved at the maximum
thickness intended for use and intended assemblies. However, MCM’s
(Such as ACP’s) shall have a minimum exterior skin thickness of 0.019 in.
(0.5 mm), a minimum interior skin thickness of 0.010 in. (0.25 mm) and a
maximum panel thickness of ¼ in. (6.3 mm) where installed on facades and
exterior walls.
4.6.3.3. MCM/ACP Core shall not be of foam plastic insulation or LDPE (Low Density
Polyethylene) or any such expanded plastic having density less than 320 kg/
m3).
4.6.3.4. MCM/ACP Core shall be tested and evaluated separately. Core (exposed
without skin) used in Cladding and façade Panels can be of plastic or miner-
al or combination of such material having flame and smoke spread charac-
teristics as per TEST 1 in accordance with Table 1.14.a. and Table 1.14.b.
test requirements.
4.6.3.5. The fire resistance performance of Fire Rated façade system is a function of
the base exterior wall when tested to ASTM E119 (or equivalent) and NOT
only the MCM/ACP panel element. It must be made clear by the MCM/ACP
manufacturer that their products have no Resistance to Fire qualities when
tested as a system in accordance with Table 1.14.b. unless the MCM/ACP
panel has been tested as an individual component product to ASTM E119.
4.6.4.1. MCM/ACP panels and facade systems on non-fire resistance rated and non
load bearing exterior wall coverings shall comply with Table 1.14.a.
4.6.4.2. MCM/ACP panels and facade systems on fire resistance rated exterior and
non-load bearing wall assembly coverings shall comply with Table 1.14.b.
4.6.5. Application
4.6.6.1. The occupancies and type of buildings that are allowed to have MCM or
ACP shall be in accordance with Table 1.14.a. and Table 1.14.b.
AND OR
OR
viii. EN 1362-4
With pass criteria
“1 Hr or 2 Hr OR 3 Hr as
per required fire rating of
the wall.
4.7.2. Definition
4.7.2.1. Exterior insulation and finish systems (EIFS) are materials, assemblies made up of
layers of foam plastic insulation or expanded polystyrene or mineral insulation
with adhesives and fiber reinforcement, used in exterior non load bearing walls as
wall coverings and exterior cladding systems
4.7.3.1. EIFS and ETICS shall be constructed such that it meets the performance
characteristics required as per ASTM E 2568.
4.7.3.2. EIFS and ETICS shall be certified and listed by a third party independent
testing and Certification body, approved by Civil Defence.
4.7.3.3. EIFS and ETICS shall be Marked/labeled to verify its certification mark from
accredited certification body.
4.7.3.4. The layers and core materials shall be tested separately and entire assem-
bly including ornaments, trims and moldings’ with intended thickness,
joints, seams, fasteners and wall arrangement shall be tested in accordance
with Table 1.15.a.
4.7.3.5. Where EIFS or ETICS is installed on Fire rated or load bearing walls, the wall
arrangement shall be tested in accordance with Table 1.15.b.
4.7.3.6. EIFS shall be specified in accordance with ANSI/EIMA 99-A (Latest Edition)
‘American National Standard for EIFS’. ETICS shall meet the performance
requirements as per ETAG 004 (Latest Edition) ‘Guidelines for European
Technical Approval of ETICS with Rendering’
4.7.3.7. Requirements of the ANSI/EIMA 99-A or ETAG 004 guidelines shall be fol-
lowed independently. Using parts from each of the guidelines is not per-
mitted.
4.7.4.1. EIFS and ETICS panels and facade systems on non-fire resistance rated and
non load bearing exterior wall coverings shall comply with Table 1.15.a.
4.7.4.2. EIFS and ETICS panels and facade systems on fire resistance rated exterior
wall assembly coverings shall comply with Table 1.15.b.
4.7.5. Application
4.6.6.1. The occupancies and type of buildings that are allowed to have EIFS and
ETICS shall be in accordance with Table 1.15.a. and Table 1.15.b.
Points to Ponder
Governments all over the world advocate usage of green building products,
which contribute to high energy efficient performances of buildings and
reduce the carbon footprints.
AND OR
v. EN 1362-3
With pass criteria
“1 Hr or 2 Hr OR 3 Hr as
per required fire rating of
the wall.
OR
vi. EN 1362-4
With pass criteria
“1 Hr or 2 Hr OR 3 Hr as
per required fire rating of
the wall.
4.8.2. Definition
4.8.3.1. PEWFS shall be certified and listed by a third party independent Testing and
Certification body, approved by Civil Defence.
4.8.3.2. PEWFS shall be Marked/labeled to verify its certification mark from accred-
ited certification body.
4.8.3.3. The entire assembly including ornaments, trims and moldings with intended
thickness, joints, seams, fasteners and wall arrangement shall be tested in
accordance with Table 1.16.a.
4.8.4.1. PEWFS panels and facade systems on non-fire resistance rated and non
load bearing exterior wall coverings shall comply with Table 1.16.a.
4.8.4.2. EIFS and ETICS panels and facade systems on fire resistance rated exterior
wall assembly coverings shall comply with Table 1.16.b.
4.8.5. Application
4.8.5.1. The occupancies and type of buildings that are allowed to have PEWFS shall
be in accordance with Table 1.16.a. and Table 1.16.b.
3. MALLS AND OR
OR
v. FM 4881
With pass criteria
“Pass”
OR
OR
v. EN 1362-3
With pass criteria
“1 Hr or 2 Hr OR 3 Hr as
per required fire rating of
the wall.
OR
vi. EN 1362-4
With pass criteria
“1 Hr or 2 Hr OR 3 Hr as
per required fire rating of
the wall.
4.9.2. Sandwich Panels used in other applications such as internal partitions, cold storage
or roofing shall comply with the specific requirements of Section 4.9.
4.9.3. Sandwich panels shall be tested for the intended applications such as external, inter-
nal, roofing or cold storages and shall not be interchanged in their end applications.
4.9.4. Definition
4.9.4.1. Sandwich panels are foam plastic insulated sandwich panels (FISP) or mineral
core insulated panels or self supporting double skin metal faced insulating
panels.
4.9.4.3. Sandwich panels are generally used as external wall systems in low rise
building such as warehouses and roofing. As internal partitions and ceiling
applications, sandwich panels are used in, cold storages, food industries,
warehouses and industries.
4.9.5.1. Where Sandwich panels are installed on the exterior walls, they shall not
reduce the fire resistance rating of the wall.
4.9.5.4. Thermal barrier shall not be required in masonry or concrete wall, floor or
roof constructions where the sandwich panel is covered on each face by
concrete or masonry with a minimum thickness of 25 mm.
4.9.5.5. Thermal barrier shall not be required in fully Sprinkler protected cooler or
freezer or cold rooms and the rooms they are located in, when sandwich
panel is minimum 4 inch thick and has Class A rating as per UL 723 or ASTM
E 84 (FSI-25, SDI-450 or less), when tested both core and panel. Moreover,
sandwich panel shall have self ignition temperature, not less than 4270C in
accordance with ASTM D 1929.
4.9.5.6. Thermal barrier shall not be required in roof assemblies where sandwich
panels are separated from the interior of the building by wood structural
sheathing not less than 12 mm in thickness. And the sandwich panel is part
of roof covering assembly tested and passes with FM 4450 or UL 1256 or
FM 4471.
4.9.5.7. Foam plastic insulation, exterior facings an coatings shall be tested sepa-
rately in the thickness of intended use as per Table 1.17.c.
4.9.6.2. Sandwich panels as fire resistance rated exterior wall assembly coverings
shall comply with both Table 1.17.a. and Table 1.17.b.
4.9.6.3. Sandwich panels used in applications other than as exterior walls shall com-
ply with test requirements in accordance with Table 1.17.c.
4.9.7. Application
4.9.7.1. The occupancies and type of buildings that are allowed to have sandwich
panels in their exterior wall facades shall be in accordance with Table
1.17.a. and Table 1.17.b.
OR viii. FM 4881
With pass criteria
iv. FM 4880 “Class 1”
With pass criteria
“Non-combustible core” OR
iv. FM 4880 OR
With pass criteria
“Non-combustible core” viii. EN 1362-3
With pass criteria
AND “1 Hr or 2 Hr OR 3 Hr as
per required fire rating of
v. ASTM D1929 the wall.
Shall have self ignition
temperature of not less OR
than 3430C.
ix. EN 1362-4
With pass criteria
“1 Hr or 2 Hr OR 3 Hr as
per required fire rating of
the wall.
i. BS 476 Part 7
With pass criteria
“Class 1”
OR
i. FM 4880
With pass criteria
“Non-combustible core”
AND
i. ASTM D1929
Shall have self ignition
temperature of not less
than 3430C.
ii. FM 4880
With pass criteria
“Non-combustible core”
AND
v. UL 790
With pass criteria
“Class B”
OR
OR
v. UL 790
With pass criteria
“Class A”
OR
4.10.2. GRP/GRFC and GRP systems may be used in a variety of building exterior envelope
and Façade systems, many of which may be project based and of a specific design.
However Manufacturers, Consultants, Design Teams, Contractors and Testing labor-
atories must ensure that these systems comply in the first instance with the Reac-
tion to Fire, Surface Spread of Flame and Resistance to Fire performance require-
ments and intent of the UAE Fire and Life Safety Code of Practice. This also includes
selection of non-combustible formers, appropriate Fire Stopping and buildability of
the tested system against the field application.
4.10.3. Definition
4.10.3.1. Glass fiber reinforced concrete or GFRC is a type of fiber-reinforced concrete. The
product is also known as glass fiber reinforced concrete or GRC. Glass fiber con-
cretes are mainly used in exterior building façade panels and as architectural pre-
cast concrete.
4.10.4.1. GRP(GRFP) shall be constructed such that it meets the performance char-
acteristics required as per ASTM D3841.
4.10.4.2. GRC/GRFC and GRP systems shall be certified and listed by a third party
independent testing and Certification body, approved by Civil Defence.
4.10.4.3. GRC/GRFC and GRP systems shall be Marked/labeled to verify its certification
mark from accredited certification laboratory.
4.10.4.4. The Base layers and core materials shall be tested separately and entire as-
sembly including ornaments, trims and moldings’ with intended thickness,
joints, seams, fasteners and wall arrangement shall be tested in accordance
with Table 1.18.a.
4.10.4.5. Where GRC/GRFC and GRP systems are installed on Fire rated or load
bearing walls, the wall arrangement shall be tested in accordance with
Table 1.18.b.
4.10.5.1. GRC/GRFC and GRP panels and facade systems on non-fire resistance rated
and non load bearing exterior wall coverings shall comply with Table 1.18.a.
4.10.5.2. GRC/GRFC and GRP panels and facade systems on fire resistance rated exteri-
or wall assembly coverings shall comply with Table 1.18b.
4.10.6. Application
4.10.6.1. The occupancies and type of buildings that are allowed to have GRC/GRFC
and GRP shall be in accordance with Table 1.18.a. and Table 1.18.b.
3. MALLS WITH OR
OR
10. WAREHOUSE OR OR
ii. EN 13823 OR
ix. EN 1362-4
With pass criteria “1 Hr or
2 Hr or 3 Hr as per re-
quired fire ratings of the
wall.
5.1. Intention
5.1.1. The provisions of this document shall specify the minimum requirements for the
certification and listing, design, installation, inspection and maintenance of glazing
systems to achieve acceptable levels of Fire resistance, Reaction to fire, Perime-
ter fire protection, Safety of people from impact with glass.
5.1.2. The weather protection of buildings is not within the scope or intention of this sec-
tion. Weather protection aspect to buildings, such as protection from wind and
water, seismic pressure etc., shall comply with Municipality regulations and re-
quirements.
5.1.3. The intention of this section is to ensure that flame spread on exterior glazed fa-
çade, or glazed room radiation or radiation from glazed fire doors is restricted to
ensure safety of people.
Photo Caption
b. The duration of fire resistance required (30 min, 45 min, 60 min, 90 min, 120
min etc.)
5.3.2. The Glazing shall comply with the relevant general requirements of Section 4.5.,
Table 1.18: Glazing Test requirements.
GLAZING APPLICATION IN TEST A TEST B
THE BUILDING WHERE FIRE RESISTANCE RATING SAFETY GLAZING TESTS
IS REQUIRED (Resistance to impact either without
breaking, or breaking in way such
that persons may not sustain pierc-
ing or cutting injuries.)
1. NON LOAD BEARING TESTED WITH ANY OF THE FOLLOWING, EN 12600
CURTAINWALL WITH WHERE FIRE RESISTANCE RATING IS OR
GLAZING, REQUIRED ANY OF THE FOLLOWING
Pass as assembly with NFPA 251 ANSI Z97.1, A FOR < 0.9 m2 ,
Pass as assembly with EN 1364-3 B FOR > 0.9 m2
Pass as assembly with UL 263 CPSC 16 CR 1202, I FOR < 0.9 m2 ,
Pass as assembly with ASTM E119 II FOR > 0.9 m2
2. NON LOAD BEARING TESTED WITH ANY OF THE FOLLOWING, EN 12600
WALLS WHERE FIRE RESISTANCE RATING IS OR
REQUIRED ANY OF THE FOLLOWING
5.4.1.3. In addition to the fire strategy Approved by Civil Defence, the following
points shall be addressed by the glazing installer to ensure they are con-
sistent with the fire strategy and overall intent of the proposed glazing
system:
5.4.2.1. The Safety Glazing is required in critical locations (2,3,4,5,6,7,8 and 11)
described in doors, side panels and low level glazing as shown in the
Figure 1.21 and 1.22.
Figure 1.21.: Safety Glazing at Door and adjacent areas Figure 1.22.: Safety Glazing at Windows
5.4.2.3. Where glazing is only accessible from one side (3.a, 4.a), the testing and
classification can be from only that side.
4 mm 1(C)2
6 mm 1(C)2
8 mm 1(C)2
10 mm 1(C)1
12 mm 1(C)1
5.4.3.2. If the presence of such glazing is not sufficiently well indicated by mulli-
ons, transoms, door frames, large door handles, stall risers or other
components of the glazing system, it shall be made apparent by some
form of manifestation.
5.4.3.4. It shall take the form of broken or solid lines, patterns or company logos
or similar, positioned between 600 mm and 1500 mm above floor level
at appropriate horizontal intervals. The manifestation should preferably
be permanent, e.g. etching of the glazing, but alternatively, if applied
materials are used they should be durable and not easily removed.
5.4.4.5. Injury from objects falling through the glass are not considered in these
requirements. A specific risk assessment should be conducted to evalu-
ate this. However, consideration at design stage may enable selection of
suitable glazing materials / measures to mitigate this situation.
5.4.4.6. This section does not consider the risk of injury to persons who may fall
onto the non-vertical (sloping) overhead glazing.
5.4.4.7. CWCT TN66 shall be used to evaluate the safety and fragility of glazed
roofing.
5.4.5.1. The use of glass in floors or staircases shall be limited to pedestrian foot
traffic only. (see GGF data sheet 7.3: Guidelines for the use of glass in
floors and stairs)
5.4.5.2. For the specification of the design floor loads for the specific use of the
building the following standard shall be used.
c. BS 5395-1: 2010 Stairs. Code of practice for the design of stairs with
straight flights and winders.
5.4.5.4. Consideration shall be given to the complete design process. The follow-
ing list comprises a number of topics that shall be considered alongside
the regulatory requirements. The list is not exhaustive but relates to the
common considerations:
a. Frequency of use
b. Potential for exposure to water and slipping
c. Potential for glazing breakage from impacts
d. Consequences of glazing failure, i.e. Post-breakage behavior of the
glazing material.
5.4.5.6. The ability of a broken pane to remain in situ is dependent upon the
loads being applied, the glass type, the temperature, the number of frac-
tured plies and the type of interlayer considered in the construction.
5.4.6.1. The installation shall be carried out by an Civil Defence and Municipality
approved installer or fabricator as per system manufacturer's installation
instructions and shall comply with local regulations and the construction
documents.
5.4.7.2. The installer and fabricator license shall be based on the training and
certification by the system manufacturer to install manufacturer’s prod-
ucts as per specified listed system requirements.
5.4.8. Inspection
5.4.8.1. Special inspection shall be required for all Glazing system. Inspection
shall take place in successive stages as installation progresses.
5.4.8.2. The manufacturer’s guidelines shall be available to and used by the glaz-
ing specialist.
5.4.10.1. The main consultant and his hired façade consultant or house of expertise
shall be responsible for the glazing design specifications, material selec-
tion, fabricator selection, initiation of laboratory tests, verification of test
results, progressive inspection during construction and commissioning.
5.4.10.2. The main consultant, the Glazing system manufacturer, glazing system
installer, glazing system fabricator, glazing specialist and the house of ex-
pertise shall jointly sign off the installation and provide final inspection
report for Civil Defence’ acceptance as evidence of compliance.
5.4.11.1. The glazing processor shall be responsible for glazing tests as required by
Table 1.18., TEST B., Safety and impact tests. The glazing processor
shall be registered with Civil Defence along with his tested materials.
5.4.11.2. The glazing fabricator shall be responsible for glazing tests as required by
Table 1.18., TEST A., Fire rating of the glazing assembly. The glazing
fabricator shall be registered with Civil Defence along with his tested as-
semblies.
6.1. Intention
6.1.1. The provisions of this document shall specify the minimum requirements for the
certification and listing, design, installation, inspection and maintenance of Roofing
System to achieve acceptable levels of Fire safety of buildings.
6.1.2. The weather protection of buildings is not the scope or intention of this section.
Weather protection aspect to buildings, such as protection from wind, water, seis-
mic impact etc., shall comply with Municipality regulations and requirements.
6.1.3. The intention of this section is to ensure that flame spread on roofing is restricted.
6.2.1. Roofing systems are composed of varying types of components such as Roof cover-
ings, Organic or Glass Fiber, Asphalt felts, Metal Composite panels, Sandwich Pan-
els, Photovoltaic Panels, Single Ply Membrane, Insulation, Support System etc.
6.3.2. The performance requirements of roofing systems shall be classified based on the
following criteria.
6.3.3. The roofing systems shall be certified and listed by a third party independent Test-
ing and Certification body, approved by Civil Defense.
6.3.4. Parties seeking approval for roof assemblies or rooftop structures shall furnish the
test certificates, approval certification numbers for the system as an assembly and
not for the individual components.
6.3.5. Only companies with a valid commercial license will be eligible for Civil Defence
approval if products are tested and certified according to specifications and re-
quirements of this code.
6.3.6. The entire roofing system including ornaments, trims and moldings’ with intended
thickness, involved core, insulation, joints, seams, fasteners and wall arrangement
shall be tested in accordance with any of the following standards:
6.3.7. Only Private Villas, Commercial Villas and Agricultural buildings are exempted from
having fire rated/ listed roof assemblies or rooftop structures.
6.3.8. Roof coverings with following materials shall be allowed without testing and certi-
fication.
6.4.1. Design/Specification/Submittals
6.4.1.2. Consultant’s roofing submittal to Civil Defence shall be during project de-
sign NOC application, along with architecture, fire alarm, fire fighting and
smoke control proposals..
6.4.1.3. Roofing System shall be specified in accordance with their test certifica-
tions as an assembly as per Table 1.22.
1. NON SPRINKLERED ANY OF THE FOLLOWING ANY OF THE FOLLOWING ANY OF THE FOLLOWING
BUILDINGS,
2. BUILDINGS WITHOUT Class A with ASTM E 108 CLASS I rating with FM 4450 Class A with FM 4431
FIRE SUPPRESSION Class AA with BS 476 -3 Pass as assembly with Class A with ASTM E 84
SYSTEMS, Class Broof t4 with UL 1256 Class A with UL 723
3. BUILDINGS, LESS EN 13501-5: +A1 Class 1 with BS 476 –7
THAN 6 M FROM Class A with UL 790 Structural Metal panel Roof Class A with EN 13501-1
NEIGHBORING
Class 1 with NFPA 276 systems shall be tested with
BUILDING,
Pass with FM 4470 or FM 4471 FM 4471
4. MALLS,
5. ASSEMBLY,
6. HOSPITAL, Roof systems with modified
7. EDUCATIONAL, bitumen and other types of
membrane roof
systems shall be tested with
FM 4470
8. OTHER BUILDINGS ANY OF THE FOLLOWING ANY OF THE FOLLOWING
AND OCCUPAN-
CIES, NOT MEN- Class B with NFPA 256 Class B with FM 4431
TIONED ABOVE Class B with ASTM E 108 Class B with ASTM E 84
9. BUILDINGS WITH Class BB with BS 476 -3 Class B with UL 723
SPRINKLER Class Broof t4 with Class 2 with BS 476 –7
PROTECTION EN 13501-5: +A1 Class B with EN 13501-1
10. BUILDINGS WITH
Class B with UL 790
FIRE
SUPPRESSION
SYSTEMS
6.4.1.4. For Roof recovering situations, where covering an existing roofing system with a new
roofing system or Roof Replacement situations where removing an existing roof system
and replacing it with a new system, the following methods shall apply.
a. Certified insulated systems may be installed over existing certified insulated sys-
tems when:
i. The new system is certified for use with the existing roof insulation type (glass
fiber, perlite, wood fiber, foamed plastic, etc.
ii. The total thickness of insulation in both systems does not exceed the maxi-
mum specified for the new system being applied.
b. For installation over noncombustible decks, any certified insulated system utilizing
minimum 1-in.-thick insulation (glass fiber, polyisocyanurate or perlite) may be
used over any existing insulated system regardless of the type, provided the insula-
tion in both systems does not exceed the maximum specified for the new system
being applied.
6.4.1.5. Roofing shall be designed by a roofing specialist designer and shall specify in accord-
ance with their test certifications, as an assembly as per Table 1.22. and manufacturer’s
recommendations.
6.4.1.6. The system manufacturer shall provide a formal submittal to the Munci palty and
Civil Defence for product registration, that will consist of the following.
6.4.2. Installation
6.4.2.1. The installation shall be carried out by Civil Defence and Municipality approved
installer as per system manufacturer's installation instructions and shall comply
with local regulations and the construction documents.
6.4.3.1. Installer specializing in Roofing system installation and certified by the system
manufacturer shall be listed with Municipality and Civil Defence Authority.
6.4.3.2. The installer license shall be based on the training and certification by the system
manufacturer to install manufacturer’s products as per specified listed system
requirements.
6.4.4. Inspection
6.4.4.1. The manufacturer’s guidelines shall be available to and used by the inspection
personnel.
6.4.4.2. The consultant shall be responsible for progressive inspection and shall sign off
the inspection report.
6.4.5.1. The main consultant, the roofing system manufacturer, roofing system
installer shall jointly sign off the installation and provide final inspection
report for Civil Defence’ acceptance as evidence of compliance.
7.1.1. All the Materials, Components, Systems, Assemblies, equipment, Products and Ac-
cessories, referred to in this chapter with respect to construction and Life Safety,
Fire Safety and Emergency Services shall be Listed, Approved and Registered by the
Civil Defence Material Approval Department.
7.1.2. There is no year of edition mentioned against any test standards. It is the intent of
Civil Defence to convey to the customers seeking material tests and the test labor-
atories to follow the “LATEST EDITION OF THE TEST STANDARD, AS AND WHEN
THEY ARE UPGRADED/REVISED/AMENDED, TO THE DATE.”
i. ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and
Materials
ii. UL 723, Standard for Test of Surface Burning Characteristics of Building Materi-
als
iii. FM 4880, Approval Standard for Class 1 Insulated Wall or Wall and Roof/
Ceiling Panels; Plastic Interior Finish Materials; Plastic Exterior Building Panels;
Wall/Ceiling Coating Systems; Interior or Exterior Finish Systems.
iv. NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall
and Ceiling Interior Finish to Room Fire Growth.
v. EN 13823: Reaction to fire tests for building products - Building products ex-
cluding floorings exposed to the thermal attack by a single burning item.
vi. EN-ISO 11925-2: Reaction to fire tests - Ignitability of products subjected to
direct impingement of flame - Part 2: Single-flame source test.
vii. EN-ISO 1182: Reaction to fire tests for products - Non-combustibility test
viii. EN-ISO 1716: Reaction to fire tests for products - Determination of the gross
heat of combustion (calorific value)
ix. EN 13501-1: Fire classification of construction products and building elements -
Part 1: Classification using data from reaction to fire tests.
x. BS 476 Part 7: Fire Tests on Building materials and structures; method of test
to determine the classification of the surface spread of flame of products
xi. BS 476 Part 6: Fire Tests on Building materials and structures; method of test
for fire propagation for products
xii. EN 1364-2, Fire resistance tests for non-loadbearing elements. Ceilings.
xiii. UL 1715, Standard for Fire Test of Interior Finish Material.
i. NFPA 286, Standard methods of fire tests for evaluating contribution of wall
and ceiling interior finish to room fire growth
ii. ASTM E 84, Standard Test Method of Surface Burning Characteristics of Build-
ing Materials
iii. UL 723, Standard for Test of Surface Burning Characteristics of Building Materi-
als.
iv. EN 1364-2: Fire resistance tests for non loadbearing elements. Ceilings.
v. EN 13823: Reaction to fire tests for building products - Building products ex-
cluding floorings exposed to the thermal attack by a single burning item.
vi. EN-ISO 11925-2: Reaction to fire tests - Ignitability of products subjected to
direct impingement of flame - Part 2: Single-flame source test.
vii. EN-ISO 1182: Reaction to fire tests for products - Non-combustibility test
viii. EN-ISO 1716: Reaction to fire tests for products - Determination of the gross
heat of combustion (calorific value)
ix. EN 13501-1: Fire classification of construction products and building elements -
Part 1: Classification using data from reaction to fire tests.
ix. BS 476 Part 7: Fire Tests on Building materials and structures; method of test
to determine the classification of the surface spread of flame of products
x. BS 476 Part 6: Fire Tests on Building materials and structures; method of test
for fire propagation for products
7.1.11. Thermal Barriers (Temperature rise shall not exceed 2500 C on unexposed surface)
i. The average temperature rise of the unexposed surface shall not rise more
than 250°C after 15 minutes of fire exposure as per ASTM E 119 or UL 263.
The thermal barrier shall remain in place for not less than 15 minutes as per
UL 1040 or UL 1715.
ii. NFPA 275, Standard Method of Fire Tests for the Evaluation of Thermal Barriers
Used Over Foam Plastic Insulation
iii. EN 1364-1 Fire resistance tests for non-loadbearing elements. Walls
i. ASTM E 814, Standard Test Method for Fire Tests of Through-Penetration Fire
Stops
ii. UL 1479, Standard for Safety for Fire Tests of Through-Penetration Fire Stop
iii. EN 1366-3: Fire resistance tests for penetration seals
iv. UL 263, Standard for Fire Tests of Building Construction and Materials.
v. FM 4990, Approval standard for firestopping.
i. ASTM E 814, Standard Test Method for Fire Tests of Through-Penetration Fire
Stops
ii. UL 1479, Standard for Safety for Fire Tests of Through-Penetration Fire Stop
iii. EN 1366-3: Fire resistance tests for penetration seals
iv. UL 263, Standard for Fire Tests of Building Construction and Materials.
v. FM 4990, Approval standard for firestopping.
vi. EN 1366-4: Fire resistance tests for service installations. Linear joint seals
i. ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and
Materials
ii. UL 263, Standard for Fire Tests of Building Construction and Materials.
iii. EN 1364-1, Fire resistance tests for non-loadbearing elements - Part 1: Walls;
iv. EN 1634 - 1, Fire resistance test for door and shutter assemblies and openable
windows
v. EN 15254-4: Extended application of results from fire resistance tests - Non-
loadbearing walls - Part 4: Glazed constructions
vi. BS 476-22: Fire tests on building materials and structures - part 22: Methods
for the determination of the fire resistance of non-loadbearing elements of
construction.
vii. UL 10B, Standard for Fire Tests of Door Assemblies
i. ASTM E 276, Standard Test Method for Extended Duration Surface Burning
Characteristics of Building Materials.
ii. EN 13381-4, Test methods for determining the contribution to the fire re-
sistance of structural members - Part 4: Applied passive protection to steel
members
iii. EN 13381-8, Test methods for determining the contribution to the fire re-
sistance of structural members - Part 8: Applied reactive protection to steel
members
i. ASTM E 2307, Standard Test Method for Determining Fire Resistance of Perim-
eter Fire Barriers Using Intermediate-Scale, Multi-story Test Apparatus
ii. UL 2079, Standard Test Method for Determining Fire Resistance of Perimeter
Fire Barrier Systems Using Intermediate-Scale, Multi-Story Test Apparatus,
iii. EN 1364-4 Fire resistance tests for non-loadbearing elements. Curtain walling.
Part configuration
iv. EN 1364-3, Fire resistance tests for non-loadbearing elements. Curtain walling.
Full configuration (complete assembly)
7.1.20. Roof Assemblies (Exterior fire exposure, See classification requirements in Table
1.22.)
7.1.21. Roof Assemblies (Interior fire exposure, See classification requirements in Table
1.22.)
i. FM 4450, Approval standard for Class 1 insulated steel roof deck roofs.
ii. UL1256, Standard for Fire Test of Roof Deck Constructions.
iii. FM 4471, Approval standard for Class 1 panel roofs.
i. FM 4470, Approval standard for single ply, polymer modified bitumen sheet,
built-up roof (BUR) and liquid applied roof assemblies for use in Class 1 and
non combustible roof construction.
ii. ANSI/UL 790, Standard Test Methods for Fire Tests of Roof Covering.
iii. ASTM E 108, Standard Test Methods for Fire Tests of Roof Coverings.
iv. UL1256, Standard for Fire Test of Roof Deck Constructions.
v. NFPA 256, Standard methods of fire tests of roof coverings
vi. BS 476-3: Standard Test Methods for Fire Tests of Roof Coverings.
vii. CEN/TS 1187: Test methods for external fire exposure to roofs
viii. EN 13501-5: Fire classification of construction products and building elements -
Part 5: Classification using data from external fire exposure to roofs tests
ix. LPS 1505 Requirements and tests for the LPCB approval and listing of roofing
systems - protection against fire from outside the building.
7.1.24. Factory manufactured or prefabricated panels with foam plastic insulation. (See
Sandwich panels, Table 1.17.a,b,c for specific details)
7.1.27. EIFS/ETICS
i. UL 10B/10C, Standard for Fire Tests of Door Assemblies/ Standard for Positive
Pressure Fire Tests of Door Assemblies
ii. NFPA 252, Standard methods of fire tests of door assemblies
iii. EN 1634-1: Fire resistance and smoke control tests for door, shutter and, open-
able window assemblies and elements of building hardware. Fire resistance
tests for doors, shutters and openable windows
iv. BS 476: Part 22, Methods of determination of fire resistance of non load bear-
ing elements of construction.
v. EN 1364-1: Fire resistance tests for non-loadbearing elements: Part 1 - Walls
7.1.34. Combination (Fire/Smoke) Damper (90 minutes and 3 hour fire rated )
i. ANSI/UL 555, Standard for Fire Dampers, and ANSI/UL 555S, Standard for
Smoke Dampers.
ii. EN 1366-10 Fire resistance tests for service installations. Smoke control damp-
ers.
iii. EN 13501-3: Fire classification of construction products and building elements -
Part 3: Classification using data from fire resistance tests on products and ele-
ments used in building service installations: fire resisting ducts and fire dampers
i. ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and
Materials.
ii. EN 1364-3, Fire resistance tests for non-loadbearing elements. Curtain walling.
Full configuration (complete assembly)
iii. UL 263, Standard for Fire Tests of Building Construction and Materials.
iv. NFPA 251, Standard methods of tests of fire resistance of building construction
and materials.
v. EN 1364-1: fire resistance tests for non-loadbearing elements. part 1: walls.
vi. BS 476: Part 22, Methods of determination of fire resistance of non load
bearing elements of construction.
7.1.36. Glazing System on load bearing floor/roof shall satisfy any of the following
i. ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and
Materials.
ii. UL 263, Standard for Fire Tests of Building Construction and Materials.
iii. NFPA 251, Standard methods of tests of fire resistance of building construction
and materials.
iv. EN 1365-2: Fire resistance tests for loadbearing floor/roof.
v. BS 476-21: Fire tests on building materials and structures - part 21:
Methods for the determination of the fire resistance of loadbearing elements of
construction
i. EN 12600, Glass in building - Pendulum test - Impact test method and classifica-
tion for flat glass.
ii. ANSI Z97, American National Standard for Safety Glazing Materials Used in
Buildings -Safety Performance Specifications and Methods of Test
iii. CPSC 16 CR 1202
iv. For shower enclosures: EN 14428, Shower enclosures - Functional requirements
and test methods
i. Particleboard conforming to Type PBU of ANSI A208.1., not less than 6.4 mm
thick.
ii. Foamed plastics having a maximum heat release rate not greater than 100 kW
when tested in accordance with UL1975 or in accordance with NFPA289,
Standard Method of Fire Test for Individual Fuel Packages, using the 20 kW
ignition source.
iii. Textile confirming to NFPA 701, Standard Methods of Fire Tests for Flame
Propagation of Textiles and Films or section 7.1.10. of this chapter.
iv. Metal Composite Panels confirming to Section 7.1.24. of this chapter.
i. NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles
and Films.
ii. EN 13501-1 Fire classification of construction products and building elements.
Classification using test data from reaction to fire tests
iii. ASTM E 84, Standard Test Method of Surface Burning Characteristics of Build-
ing Materials
iv. UL 723, Standard for Test of Surface Burning Characteristics of Building Materi-
als.
iv. BS 476 Part 7: Fire Tests on Building materials and structures; method of test
to determine the classification of the surface spread of flame of products
i. Shall be designed and operated in accordance with ASCE/SEI 17, Air Supported
Structures.
i. NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles
and Films.
i. ASTM E 84, Standard Test Method of Surface Burning Characteristics of Build-
ing Materials
ii. UL 723, Standard for Test of Surface Burning Characteristics of Building Materi-
als
iii. NFPA 265., Standard methods of fire tests for evaluating room fire growth con-
tribution of textile or expanded vinyl wall coverings on full height panels and
walls.
7.1.45. Non-Combustible Material for Cavity Fire Barrier (Groove sealants, Gaskets, Back-
er Rod and vapour barrier systems)
i. Class B, with ASTM E-84, Standard Test for Surface Burning Characters
i. Class B with UL 723, Standard Test for Surface Burning Characters
ii. Limited Combustible, with FM 4880, Standard test for insulated wall panels
3.1.1.1. Many projects in UAE are on marinas with water front and without compli-
ant Fire Access Road. Civil Defence has included Fire Boats in its fleet to ad-
dress fires in water front buildings, marinas and creek boats.
3.1.1.2. The requirements of this section shall provide the guidelines for docking fa-
cilities, dimensions and the access of Civil Defence from water front.
3.2.2. A dedicated Berth measuring 15 m long and 5 m wide shall be provided for the Fire
Boat for docking during emergencies.
3.2.3. There shall be Mooring facility complete with approved ropes, fixed fittings on the
deck and platform.
3.2.4. The mooring bitt or cleats shall be corrosion resistant and secured to a foundation that
is tied into an underdeck structure and is of adequate strength to carry the mooring
loads.
Length 5500 mm
Width 2000 mm
Height 2000 mm
Weight 2700 kg
Wheel Base 3300 mm
Length 7500 mm
Width 2400 mm
Height 2400 mm
Weight 8500 kg
Wheel Base 4500 mm
Length 7200 mm
Width 2500 mm
Height 3800 mm
Weight 15000 kg
Front Axial Load 6100 kg
Rear Axial Load 10500 kg
Length 6800 mm
Width 2500 mm
Height 3500 mm
Weight 14,100 kg
Front Axial Load 6200 kg
Rear Axial Load 8500 kg
Length 9000 mm
Width 2500 mm
Height 3800 mm
Weight 30,000 kg
Front Axial Load 9000 kg
Rear Axial Load 26,000 kg
4.1.6. Pulling Tractor (6x4)
Length 6800 mm
Width 2500 mm
Height 3500 mm
Permitted Weight 38,000 kg
Wheel Base 3300 mm
Length 12,500 mm
Width 2500 mm
Height 3500 mm
Weight 36,000 kg
Length 10,160 mm
Width 2500 mm
Height 3700 mm
Weight 26,000 kg
Front Axial Load 8000 kg
Rear Axial Load 18,000 kg
Length 12,000 mm
Width 2500 mm
Height 4000 mm
Weight 40,000 kg
Front Axial Load 15,000 Kg
Rear Axial Load 2x13,000 kg
Length 10,000 mm
Width 2500 mm
Height 3500 mm
Weight 19,000 kg
Front Axial Load 8000 kg
Rear Axial Load 11,000 kg
Length 6500 mm
Width 2000 mm
Height 3700 mm
Weight 7,500 kg
Length 6200 mm
Width 2050 mm
Height 2500 mm
Weight 4000 kg
4.2. Fireboats
Photo Caption
Length 10,360 mm
Width 3206 mm
Height 5000 mm
Length 14,016 mm
Width 4372 mm
Height 5000 mm
MEANS OF EGRESS
7.1.2. There is no year of edition mentioned against any test standards. It is the intent of
Civil Defence to convey to the customers seeking laboratory tests and the test la-
boratories to follow the “LATEST EDITION OF THE TEST STANDARD, AS AND WHEN
THEY ARE UPGRADED/REVISED/AMENDED, TO THE DATE”
7.1.3. Fire resistance rated Door Assemblies shall satisfy any of the following tests as per
specifications required by the code.
i. UL 10B/10C, Standard for Fire Tests of Door Assemblies/ Standard for Positive
Pressure Fire Tests of Door Assemblies.
ii. UL 1784, Standard for Air Leakage Tests of Door Assemblies and Other Opening
Protectives
iii. NFPA 252, Standard methods of fire tests of door assemblies.
iv. EN 1634-1: Fire resistance and smoke control tests for door, shutter and, open-
able window assemblies and elements of building hardware. Fire resistance
tests for doors, shutters and openable windows.
v. EN 1634-2: Fire resistance and smoke control tests for door, shutter and open-
able window assemblies and elements of building hardware - Part 2: Fire re-
sistance characterization test for elements of building hardware
vi. EN 1634-3: Fire resistance and smoke control tests for door and shutter assem-
blies, openable windows and elements of building hardware - Part 3: Smoke
control test for door and shutter assemblies
vii. EN 14600: Doorsets and openable windows with fire resisting and/or smoke
control characteristics - Requirements and classification
viii. EN 15269-1: Extended application of test results for fire resistance and/or
smoke control for door, shutter and openable window assemblies, including
their elements of building hardware - Part 1: General requirements
ix. EN 15269-2: EXAP – Part 2: Fire resistance of hinged and pivoted steel doorsets
and openable windows
x. EN 15269-3: EXAP – Part 3: Fire resistance of hinged and pivoted timber
doorsets and openable timber framed windows
xi. prEN 15269-4: EXAP – Part 4: Fire resistance of hinged and pivoted glazed
doorsets and shutter assemblies.
xii. prEN 15269-5: EXAP – Part 5: Fire resistance of hinged and pivoted metal
framed glazed doorsets and openable windows
xiii. prEN 15269-6: EXAP – Part 6: Fire resistance of timber sliding doors
xiv. EN 15269-7: EXAP – Part 7: Fire resistance for steel sliding doorsets
xv. prEN 15269-8: EXAP – Part 8: Fire resistance of timber horizontally folding
doors.
i. BHMA/ANSI A156.19, American National Standard for Power Assist and Low
Energy Power Operated Doors.
7.1.7. Fire resistance rated Window Assemblies shall satisfy any of the following
7.1.8. Fire resistance rated Glazing in Doors and Walls is acceptable with any of the fol-
lowing
i. ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and
Materials
ii. UL 263, Standard for Fire Tests of Building Construction and Materials.
iii. EN 1364-1, Fire resistance tests for non-loadbearing elements - Part 1: Walls;
iv. EN 1634 - 1, Fire resistance test for door and shutter assemblies and openable
windows.
v. EN 15254-4: Extended application of results from fire resistance tests - Non-
loadbearing walls - Part 4: Glazed constructions.
vi. BS 476-22: Fire tests on building materials and structures - part 22: Methods
for the determination of the fire resistance of non-loadbearing elements of
construction.
vii. UL 10B/10C, Standard for Fire Tests of Door Assemblies.
i. EN 12600, Glass in building - Pendulum test - Impact test method and classifica-
tion for flat glass.
ii. ANSI Z97, American National Standard for Safety Glazing Materials Used in
Buildings -Safety Performance Specifications and Methods of Test
iii. CPSC 16 CR 1202
iv. For shower enclosures: EN 14428, Shower enclosures - Functional requirements
and test methods
v. BS EN ISO 12543-2, Glass in building. Laminated glass and laminated safety
glass. Laminated safety glass.
7.1.13. Carpets and Textile floor finish is acceptable with any of the following
i. Particleboard conforming to Type PBU of ANSI A208.1., not less than 6.4 mm
thick.
ii. Foamed plastics having a maximum heat release rate not greater than 100 kW
when tested in accordance with UL1975 or in accordance with NFPA289,
Standard Method of Fire Test for Individual Fuel Packages, using the 20 kW
ignition source.
iii. Textile confirming to NFPA 701, Standard Methods of Fire Tests for Flame
Propagation of Textiles and Films or Chapter 1, section 7.1.10.
iv. Metal Composite Panels confirming to Chapter 1, Section 7.1.24.
v. BS EN 16755, Durability of reaction to fire performance. Classes of fire-
retardant treated wood products in interior and exterior use applications.
i. 16 CFR 1632, “Standard for the Flammability of Mattresses and Mattress Pads”
ii. 650°F (343°C) or greater when tested in accordance with ASTM D 1929, Stand-
ard Test Method for Determining Ignition Temperatures of Plastic.
iii. Class B, ASTM E 84, Standard Test Method for Surface Burning Characteristics of
Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Char-
acteristics of Building Materials.
iv. BS 6807, Methods of test for the ignitability of mattresses with primary and sec-
ondary sources of ignition.
v. BS 6807, Methods of test for assessment of ignitability of mattresses, uphol-
stered divans and upholstered bed bases with flaming types of primary and sec-
ondary sources of ignition.
vi. BS 7175, Methods of test for the ignitability of bedcovers and pillows by smoul-
dering and flaming ignition sources.
vii. BS 7177, Specification for resistance to ignition of mattresses, mattress pads,
divans and bed bases.
viii. BS EN ISO 12952-1, Textiles. Assessment of the ignitability of bedding items.
Ignition source. Smouldering cigarette.
ix. BS EN ISO 12952-2, Textiles. Assessment of the ignitability of bedding items.
Ignition source. Match-flame equivalent.
x. BS EN 579-1, Furniture. Assessment of the ignitability of mattresses and uphol-
stered bed bases. Ignition source: smouldering cigarette.
xi. BS EN 579-2, Furniture. Assessment of the ignitability of mattresses and uphol-
stered bed bases. Ignition source: match flame equivalent.
xii. EN 13501-1: Fire classification of construction products and building elements -
Part 1: Classification using data from reaction to fire tests.
xiii. ASTM E1590, Standard test method for fire testing mattresses.
7.1.18. Elevators
FIRE EXTINGUISHERS
4.1.2. There is no year of edition mentioned against any test standards. It is the intent of
Civil Defence to convey to the customers seeking laboratory tests and the test la-
boratories to follow the “LATEST EDITION OF THE TEST STANDARD, AS AND WHEN
THEY ARE UPGRADED/REVISED/AMENDED, TO THE DATE.”
i. ANSI/UL 711, Standard for Rating and Fire Testing of Fire Extinguishers
ii. ANSI/NFPA 10, Portable Fire Extinguishers
iii. CAN/ULC-S508-M90, Standard for Rating and Fire Testing of Fire Extinguishers
and Class D Extinguishing Media
iv. EN 3-7 +A1, EN 3-8, EN 3-9, Portable fire extinguishers. Characteristics, perfor-
mance requirements and test methods.
EXIT SIGNS
5.1.2. There is no year of edition mentioned against any test standards. It is the intent of
Civil Defence to convey to the customers seeking laboratory tests and the test la-
boratories to follow the “LATEST EDITION OF THE TEST STANDARD, AS AND WHEN
THEY ARE UPGRADED/REVISED/AMENDED, TO THE DATE.”
EMERGENCY LIGHTING
8.1.2. There is no year of edition mentioned against any test standards. It is the intent of
Civil Defence to convey to the customers seeking laboratory tests and the test la-
boratories to follow the “LATEST EDITION OF THE TEST STANDARD, AS AND WHEN
THEY ARE UPGRADED/REVISED/AMENDED, TO THE DATE.”
i. EN 50200, Method of test for resistance to fire of unprotected small cables for
use in emergency circuits
ii. UL 2196, Standard for Fire Test for Circuit Integrity of Fire-Resistive Power,
Instrumentation, Control, and Data Cables
iii. BS 8434-2, Methods of test for assessment of the fire integrity of electric ca-
bles. Test for unprotected small cables for use in emergency circuits. BS EN
50200 with a 930° flame and with water spray .
iv. BS 7629-1, Electric cables. Specification for 300/500 V fire resistant screened
cables having low emission of smoke and corrosive gases when affected by
fire. Multicore and multipair cables.
v. BS 6387, Test method for resistance to fire of cables required to maintain
circuit integrity under fire conditions.
vi. IEC 60331-1, Tests for electric cables under fire conditions.
vii. IEC 60331-2, Tests for electric cables under fire conditions.
viii. IEC 60332-2-2, Tests on electric and optical fibre cables under fire conditions.
ix. IEC 60332-3-10, Tests on electric and optical fibre cables under fire condi-
tions.
x. IEC 60331-2, Tests for electric cables under fire conditions.
xi. UL 1724, Outline of Investigation for Fire Tests for Electrical Circuit Protective
Systems.
xii. UL 1685, Standard for Vertical-Tray Fire-Propagation and Smoke-Release Test
for Electrical and Optical-Fiber Cables.
xiii. UL 1666, UL 1666 Test for Flame Propagation Height of Electrical and Optical-
Fiber Cables Installed Vertically in Shafts.
EMERGENCY VOICE
EVACUATION SYSTEMS
6.1.2. There is no year of edition mentioned against any test standards. It is the intent of
Civil Defence to convey to the customers seeking laboratory tests and the test la-
boratories to follow the “LATEST EDITION OF THE TEST STANDARD, AS AND WHEN
THEY ARE UPGRADED/REVISED/AMENDED, TO THE DATE.”
6.1.4. Speakers
6.1.5. Amplifiers
i. UL 864, Standard for Control Units and Accessories for Fire Alarm Systems
ii. UL 1711, Amplifiers for Fire Protective Signaling Systems
iii. EN 54-16, Voice Alarm Control and indicating equipment
i. UL 864, Standard for Control Units and Accessories for Fire Alarm Systems
ii. EN 54-21, Alarm Transmission and fault warning routing equipment
i. EN 50200, Method of test for resistance to fire of unprotected small cables for
use in emergency circuits
ii. UL 2196, Standard for Fire Test for Circuit Integrity of Fire-Resistive Power, In-
strumentation, Control, and Data Cables
iii. BS 8434-2, Methods of test for assessment of the fire integrity of electric ca-
bles. Test for unprotected small cables for use in emergency circuits. BS EN
50200 with a 930° flame and with water spray .
iv. BS 7629-1, Electric cables. Specification for 300/500 V fire resistant screened
cables having low emission of smoke and corrosive gases when affected by fire.
Multicore and multipair cables.
v. BS 6387, Test method for resistance to fire of cables required to maintain cir-
cuit integrity under fire conditions.
vi. IEC 60331-1, Tests for electric cables under fire conditions.
vii. IEC 60331-2, Tests for electric cables under fire conditions.
viii. IEC 60332-2-2, Tests on electric and optical fibre cables under fire conditions.
ix. IEC 60332-3-10, Tests on electric and optical fibre cables under fire conditions.
x. IEC 60331-2, Tests for electric cables under fire conditions.
xi. UL 1724, Outline of Investigation for Fire Tests for Electrical Circuit Protective
Systems.
xii. UL 1685, Standard for Vertical-Tray Fire-Propagation and Smoke-Release Test
for Electrical and Optical-Fiber Cables.
xiii. UL 1666, UL 1666 Test for Flame Propagation Height of Electrical and Optical-
Fiber Cables Installed Vertically in Shafts.
FIRE DETECTION
AND ALARM SYSTEM
7.1.2. There is no year of edition mentioned against any test standards. It is the intent of
Civil Defence to convey to the customers seeking laboratory tests and the test la-
boratories to follow the “LATEST EDITION OF THE TEST STANDARD, AS AND WHEN
THEY ARE UPGRADED/REVISED/AMENDED, TO THE DATE”
i. FM3230, Approval standard for Smoke Actuated Detectors for automatic alarm
signaling.
ii. UL 268, Standard for Smoke Detectors for Fire Alarm Systems.
iii. EN 54-7, Fire detection and fire alarm systems. Smoke detectors. Point detec-
tors using scattered light, transmitted light or ionization.
iv. EN 14604, Smoke alarm devices (Domestic)
v. ISO7240-7, Fire detection and alarm systems -- Part 7: Point-type smoke detec-
tors using scattered light, transmitted light or ionization.
vi. EN 54-12, Smoke detectors - Line detectors using a transmitted optical beam
vii. ISO 7240-12, Smoke detectors - Line detectors using a transmitted optical
beam
i. UL 521, Standard for Heat Detectors for Fire Protective Signaling Systems.
ii. FM 3210, Heat Detectors for Automatic Fire Alarm Signaling.
iii. EN 54-5, Fire detection and fire alarm systems. Heat detectors. Point detectors
iv. ISO 7240-5, Fire detection and alarm systems. Point-type heat detectors
i. EN 54-20, Fire detection and fire alarm systems. Aspirating smoke detectors
ii. FM3230, Approval standard for Smoke Actuated Detectors for automatic alarm
signaling
i. FM 3260, Radiant Energy-Sensing Fire Detectors for Automatic Fire Alarm Sig-
naling.
ii. EN 54-10, Flame detectors - Point detectors
iii. ISO 7240-10 - Flame detectors - Point detectors
iv. BS ISO 19292, Ships and marine technology. Lifesaving and fire protection.
Point-type resettable flame detectors for ships
i. ISO 7240-15, Point type fire detectors using scattered light, transmitted light or
ionization sensors in combination with a heat sensor
ii. EN 54-29, Multi-sensor fire detectors - Point detectors using a combination of
smoke and heat sensors
iii. EN 54-30, Multi-sensor fire detectors - Point detectors using a combination of
carbon monoxide and heat sensors
iv. EN 54-31, Multi-sensor fire detectors - Point detectors using a combination of
smoke, carbon monoxide and optionally heat sensors
i. UL 38, Standard for Manual Signaling Boxes for Fire Alarm Systems.
ii. EN 54-11, Manual call points
iii. ISO 7240-11, Manual call points
iv. FM-3010, Approval Standard for Fire Alarm Signaling Systems
i. UL 464, Audible Signaling Devices for Fire Alarm and Signaling devices, includ-
ing accessories.
ii. UL 1480, Speakers for Fire Alarm and Signaling Systems, including Accessories.
iii. FM 3150, Audible Notification Appliances for Automatic Fire Alarm Signaling.
iv. EN 54-3, Sounders
i. UL 1638, Visible Signaling Devices for Fire Alarm and Signaling Systems, includ-
ing accessories.
ii. EN 54-23, Fire alarm devices. Visual alarm devices
iii. UL 1971, Standard for Signaling Devices for the Hearing Impaired
i. UL 864, Standard for Control Units and Accessories for Fire Alarm Systems.
ii. FM 3010, Fire Alarm Signaling Systems
iii. FM 3011, Central Station Service for Fire Alarms and Protective Equipment Su-
pervision.
iv. EN 54-2, Control and indicating equipment
v. ISO 7240-2, Control and indicating equipment
i. EN 50200, Method of test for resistance to fire of unprotected small cables for
use in emergency circuits
ii. UL 2196, Standard for Fire Test for Circuit Integrity of Fire-Resistive Power,
Instrumentation, Control, and Data Cables
iii. BS 8434-2, Methods of test for assessment of the fire integrity of electric ca-
bles. Test for unprotected small cables for use in emergency circuits. BS EN
50200 with a 930° flame and with water spray .
iv. BS 7629-1, Electric cables. Specification for 300/500 V fire resistant screened
cables having low emission of smoke and corrosive gases when affected by fire.
Multicore and multipair cables.
v. BS 6387, Test method for resistance to fire of cables required to maintain cir-
cuit integrity under fire conditions.
vi. IEC 60331-1, Tests for electric cables under fire conditions.
vii. IEC 60331-2, Tests for electric cables under fire conditions.
viii. IEC 60332-2-2, Tests on electric and optical fibre cables under fire conditions.
ix. IEC 60332-3-10, Tests on electric and optical fibre cables under fire conditions.
x. IEC 60331-2, Tests for electric cables under fire conditions.
xi. UL 1724, Outline of Investigation for Fire Tests for Electrical Circuit Protective
Systems.
xii. UL 1685, Standard for Vertical-Tray Fire-Propagation and Smoke-Release Test
for Electrical and Optical-Fiber Cables.
xiii. UL 1666, UL 1666 Test for Flame Propagation Height of Electrical and Optical-
Fiber Cables Installed Vertically in Shafts.
6.1.2. There is no year of edition mentioned against any test standards. It is the intent of
Civil Defence to invite the customers seeking laboratory tests and the test labora-
tories to follow the “LATEST EDITION OF THE TEST STANDARD, AS AND WHEN
THEY ARE UPGRADED/REVISED/AMENDED, TO THE DATE”
i. UL 1247, Standard for Diesel Engines for Driving Stationary Fire Pumps.
ii. FM 1333, Diesel Engine Fire Pump Drivers
iii. LPS 1239, Requirements and testing procedures for the LPCB approval and
listing of diesel engines for sprinkler pump sets
6.1.7. Sprinkler
i. FM 5511 - Firefighting Nozzles for Use with Hose, Monitor Assemblies and oth-
er Firefighting Equipment.
ii. UL 401, Portable Spray Hose Nozzles for Fire-Protection Service
i. FM 1613, Approval Standard for Polyethylene (PE) Pipe and Fittings for under-
ground fire protection service, in accordance with NFPA 24 and AWWA C906,
minimum DR-9 with temperature and pressure rating not less than the system
working pressure.
ii. FM 1614, Approval Standard for Fiber Reinforced Composite (FRC) Pipes and
Fittings for underground fire protection service.
iii. FM 1620, Approval Standard for Pipe joints and anchor fittings for under-
ground fire protection service.
iv. UL 1285 Pipe and Couplings, Polyvinyl Chloride (PVC), and Oriented Polyvinyl
Chloride (PVCO) for Underground Fire Service
v. UL 1713 Pressure Pipe and Couplings, Glass Fiber-Reinforced, for Underground
Fire Service
vi. UL 194 Gasketed Joints for Ductile-Iron Pipe and Fittings for Fire Protection
Service
i. FM 1920, Approval Standard for Pipe coupling and fittings for aboveground fire
protection service.
ii. ANSI/UL 852, Metallic Sprinkler Pipe for Fire Protection Service
iii. ANSI/UL 1821, Thermoplastic Sprinkler Pipe and Fittings for Fire Protection
Service
iv. FM 1637, Flexible Sprinkler Hose with Fittings
v. FM 1630, Steel Pipe for Automatic Fire Sprinkler Systems
vi. UL 852, Metallic Sprinkler Pipe for Fire Protection Service
vii. UL 1821, Thermoplastic Sprinkler Pipe and Fittings for Fire Protection Service
viii. ASTM A53, Galvanized Steel ERW Pipe, sch 40.
ix. ASTM A53, Galvanized Steel Seamless Pipe, sch 40.
6.1.16. Hangers
6.1.17. Fittings
i. Fittings ANSI/UL 213, Rubber Gasketed Fittings for Fire Protection Service
ii. FM 1920, Pipe Couplings and Fittings for Fire Protection Systems
iii. UL 1474, Adjustable Drop Nipples for Sprinkler Systems
iv. FM 1631, Adjustable and Fixed Sprinkler Fittings 1⁄2 Inch through 1 Inch Nomi-
nal Size
v. ANSI/UL 2443, Flexible Sprinkler Hose with Fittings for Fire Protection Service
vi. LPS 1219, Requirements and testing procedures for the LPCB approval and
listing of pipe couplings
vii. LPS 1261, Requirements for Testing Flexible Hoses for Sprinkler Systems
i. UL 2127, Standard for Inert Gas Clean Agent Extinguishing System Units.
ii. FM 5600 - Clean Agent Extinguishing Systems
i. LPS 1276, Requirements for the LPCB Certification and Listing of above ground
Suction Tanks for Sprinkler Systems.
i. EN 50200, Method of test for resistance to fire of unprotected small cables for
use in emergency circuits
ii. UL 2196, Standard for Fire Test for Circuit Integrity of Fire-Resistive Power,
Instrumentation, Control, and Data Cables
iii. BS 8434-2, Methods of test for assessment of the fire integrity of electric ca-
bles. Test for unprotected small cables for use in emergency circuits. BS EN
50200 with a 930° flame and with water spray .
iv. BS 7629-1, Electric cables. Specification for 300/500 V fire resistant screened
cables having low emission of smoke and corrosive gases when affected by
fire. Multicore and multipair cables.
v. BS 6387, Test method for resistance to fire of cables required to maintain cir-
cuit integrity under fire conditions.
vi. IEC 60331-1, Tests for electric cables under fire conditions.
vii. IEC 60331-2, Tests for electric cables under fire conditions.
viii. IEC 60332-2-2, Tests on electric and optical fibre cables under fire conditions.
ix. IEC 60332-3-10, Tests on electric and optical fibre cables under fire conditions.
x. IEC 60331-2, Tests for electric cables under fire conditions.
xi. UL 1724, Outline of Investigation for Fire Tests for Electrical Circuit Protective
Systems.
xii. UL 1685, Standard for Vertical-Tray Fire-Propagation and Smoke-Release Test
for Electrical and Optical-Fiber Cables.
xiii. UL 1666, UL 1666 Test for Flame Propagation Height of Electrical and Optical-
Fiber Cables Installed Vertically in Shafts.
i. UL 448 D, Outline of Investigation for Fire Pump, Driver and Controller Assem-
bly Rating Compatibility
6.1.2. There is no year of edition mentioned against any test standards. It is the intent of
Civil Defence to invite the customers seeking laboratory tests and the test laborato-
ries to follow the “LATEST EDITION OF THE TEST STANDARD, AS AND WHEN THEY
ARE UPGRADED/REVISED/AMENDED, TO THE DATE.”
6.1.4. Fire Damper (90 minutes and 3 hour fire rated with 1.2 mm galvanized steel
frame)
6.1.5. Combination (Fire/Smoke) Damper (90 minutes and 3 hour fire rated with 1.5 mm
galvanized steel frame)
i. ANSI/UL 555, Standard for Fire Dampers, and ANSI/UL 555S, Standard for Smoke
Dampers.
ii. EN 1366-2 Fire resistance tests for service installations. Fire dampers.
iii. EN 1366-10 Fire resistance tests for service installations. Smoke control damp-
ers.
iv. EN 13501-3: Fire classification of construction products and building elements -
Part 3: Classification using data from fire resistance tests on products and ele-
ments used in building service installations: fire resisting ducts and fire dampers.
i. ANSI/UL 864, Standard for Control Units and Accessories for Fire Alarm Systems,
category UUKL, for their intended purpose.
ii. ISO 21927-9:Smoke and heat control systems — Specification for control equip-
ment.
iii. ISO 21927-10: Smoke and heat control systems — Specification for power output
devices.
iv. EN 12101-10: Smoke and heat control systems. Power supplies.
i. ISO 21927-1: Smoke and heat control systems, Specification for smoke barriers.
ii. EN 12101-1: Smoke and heat control systems. Specification for smoke barriers.
6.1.9. Natural Smoke and Heat Vents (Rated at 3000 for 30 minutes)
i. ISO 21927-2: Smoke and heat control systems — Specification for natural smoke
and heat exhaust ventilators.
ii. FM 4430, Heat and Smoke Vents.
iii. UL 793, Standard for Automatically Operated Roof Vents for Smoke and Heat
iv. EN 12101-2: Smoke and heat control systems. Specification for natural smoke
and heat exhaust ventilators.
6.1.10. Mechanical Extract Fans and Jet Fans (Rated at 4000 for 2 hours)
i. EN-12101-3: Smoke and heat control systems. Specification for powered smoke
and heat exhaust ventilators.
ii. UL 705, Standard for Power Ventilators.
iii. EN 13501-4: Fire classification of construction products and building elements -
Part 4: Classification using data from fire resistance tests on components of
smoke control systems.
6.1.11. Powered Smoke and Heat Exhaust Ventilators (Rated at 4000 for 2 hours)
i. EN 12101-3: Smoke and heat control systems. Specification for powered smoke
and heat exhaust ventilators.
ii EN ISO 13350: Industrial fans. Performance testing of jet fans.
iii. EN 13501-4: Fire classification of construction products and building elements -
Part 4: Classification using data from fire resistance tests on components of
smoke control systems
iv. UL 705, Standard for power ventilators
i. BS 476, Part 24, Fire tests on building materials and structures. Method for
determination of the fire resistance of ventilation ducts.
ii. ISO 21927-7: Smoke and heat control systems—Smoke control Ducts.
iii. Class 0 or Class 1 in accordance with ANSI/UL 181.
iv. ASTM E2816-12: HVAC ducts fire resistance
v. EN 1366-1: Fire resistance test for service installations. PART 1: DUCTS.
vi. EN 1366-8: Fire resistance tests for service installations - Part 8: Smoke extrac-
tion ducts
vii. UNE-EN 1366-9: Fire resistance tests for service installations - Part 9: Single
compartment smoke extraction ducts
viii. EN 13501-4: Fire classification of construction products and building elements -
Part 4: Classification using data from fire resistance tests on components of
smoke control systems.
ix. EN 12101-7: Smoke and Heat control Systems. Smoke duct sections.
6.1.13. Duct and Pipe Insulation as assembly including Pipe and Duct insulation, cover-
ings, linings fasteners, adhesives.
i. EN 50200, Method of test for resistance to fire of unprotected small cables for
use in emergency circuits
ii. UL 2196, Standard for Fire Test for Circuit Integrity of Fire-Resistive Power,
Instrumentation, Control, and Data Cables
iii. BS 8434-2, Methods of test for assessment of the fire integrity of electric ca-
bles. Test for unprotected small cables for use in emergency circuits. BS EN
50200 with a 930° flame and with water spray .
iv. BS 7629-1, Electric cables. Specification for 300/500 V fire resistant screened
cables having low emission of smoke and corrosive gases when affected by
fire. Multicore and multipair cables.
v. BS 6387, Test method for resistance to fire of cables required to maintain cir-
cuit integrity under fire conditions.
vi. IEC 60331-1, Tests for electric cables under fire conditions.
vii. IEC 60331-2, Tests for electric cables under fire conditions.
viii. IEC 60332-2-2, Tests on electric and optical fibre cables under fire conditions.
ix. IEC 60332-3-10, Tests on electric and optical fibre cables under fire conditions.
x. IEC 60331-2, Tests for electric cables under fire conditions.
xi. UL 1724, Outline of Investigation for Fire Tests for Electrical Circuit Protective
Systems.
xii. UL 1685, Standard for Vertical-Tray Fire-Propagation and Smoke-Release Test
for Electrical and Optical-Fiber Cables.
xiii. UL 1666, UL 1666 Test for Flame Propagation Height of Electrical and Optical-
Fiber Cables Installed Vertically in Shafts.
LIQUEFIED PETROLEUM
GAS CODE OF PRACTICE
6.1.1. All the Materials, Systems, Assemblies, Cylinders, Tanks, Pipes and fittings, equip-
ment, Controls, Devices, Products and Accessories, referred to in this chapter shall
be Listed, Approved and Registered by the Civil Defence Material Approval Depart-
ment.
6.1.2. There is no year of edition mentioned against any test standards. It is the intent of
Civil Defence to convey to the customers seeking laboratory tests and the test la-
boratories to follow the “LATEST EDITION OF THE TEST STANDARD, AS AND WHEN
THEY ARE UPGRADED/REVISED/AMENDED, TO THE DATE.”
6.1.3. LPG Cylinders *Working pressure should not be less than 250 psi (17.57 Kg/Sq. cm)
and design storage temperature shall be –420C to 550C.+
i. ASME Boiler and Pressure Vessel Code, Section VIII, “Rules for the Construction
of Unfired Pressure Vessels,” or the API-ASME Code for Unfired Pressure Ves-
sels for Petroleum Liquids and Gases.
ii. EN 12245, Transportable gas cylinders. Fully wrapped composite cylinders.
iii. EN 14427, LPG equipment and accessories. Transportable refillable fully
wrapped composite cylinders for LPG. Design and construction.
iv. EN 1442 - LPG equipment and accessories. Transportable refillable welded
steel cylinders for LPG. Design and construction.
v. EN 12807 - LPG equipment and accessories. Transportable refillable brazed
steel cylinders for liquefied petroleum gas (LPG). Design and construction.
vi. EN 13110 - LPG equipment and accessories. Transportable refillable welded
aluminum cylinders for liquefied petroleum gas (LPG). Design and construc-
tion.
vii. EN 14140 - LPG equipment and accessories. Transportable refillable welded
steel cylinders for LPG. Alternative design and construction.
viii. ISO 4706 - Gas cylinders. Refillable welded steel cylinders. Test pressure 60 bar
and below.
ix. ISO 22991 - Gas cylinders. Transportable refillable welded steel cylinders for
liquefied petroleum gas (LPG). Design and construction.
x. ISO 20703 - Gas cylinders. Refillable welded aluminum-alloy cylinders. Design,
construction and testing.
xi. EN 14893 - LPG equipment and accessories. Transportable Liquefied Petroleum
Gas (LPG) welded steel pressure drums with a capacity between 150 liters and
1 000 liters.
xii. ISO 10460 Gas cylinders -- Welded carbon-steel gas cylinders Periodic inspec-
tion and testing.
xiii. ISO 11119-2 Gas cylinders of composite construction. Specification and test
methods. Part 2. Fully wrapped fiber reinforced composite gas cylinders and
tubes with load-sharing metal liners.
xiv. UL 2003 Outline for LP-Gas Cylinder Assemblies.
xv. ANSI/UL 147A, Standard For Safety For Nonrefillable (Disposable) Type Fuel
Gas Cylinder Assemblies.
xvi. ANSI/UL 147B Nonrefillable (Disposable) Type Metal Container for Butane.
xvii. UAE S/GSO ISO 22991, Gas Cylinders. Transportable refillable welded steel cyl-
inders for liquefied petroleum gas (LPG). Design and construction.
i. EN 1439, LPG equipment and accessories. Procedure for checking LPG cylin-
ders before, during and after filling.
i. EN 16119, Sealing caps and plugs for LPG cylinder and pressure vessel valves.
Specification and testing.
6.1.7. LPG Tanks *Working pressure should not be less than 250 psi (17.57 Kg/Sq. cm)
and design storage temperature shall be –420C to 550C.+
i. Regulations of the U.S Department of Transportation (DOT), the “Rules for the
Construction of Unfired Pressure Vessels”, Section VIII, Division 1
ii. ASME Boiler and Pressure Vessel Code.
iii. API-ASME Code for Unfired Pressure Vessels for Petroleum Liquids and Gases.
iv. PD 5500 -Specification for unfired fusion welded pressure vessels
v. EN 14075, Static welded steel cylindrical tanks, serially produced for the stor-
age of liquefied petroleum gas (LPG) having a volume not greater than 13 m3
and for installation underground. Design and manufacture
vi. EN 12542, LPG equipment and accessories. Static welded steel cylindrical
tanks, serially produced for the storage of liquefied petroleum gas (LPG) hav-
ing a volume not greater than 13 m3. Design and manufacture
vii. EN 14570, LPG equipment and accessories. Equipping of overground and un-
derground LPG vessels.
viii. UL 644, Container assemblies for LP Gas.
ix. EN 12493, LPG equipment and accessories. Welded steel pressure vessels for
LPG road tankers. Design and manufacture.
x. EN 13445 Unfired Pressure vessel codes
i. EN 14334, LPG equipment and accessories. Inspection and testing of LPG road
tankers.
ii. EN 12493, LPG equipment and accessories. Welded steel pressure vessels for
LPG road tankers. Design and manufacture.
iii. EN 12805, Automotive LPG components. Containers.
iv. ISO 20826, Automotive LPG components. Containers.
v. EN 13776 LPG equipment and accessories. Filling and discharge procedures for
LPG road tankers.
i. UL 132, Standard on Safety Relief Valves for Anhydrous Ammonia and LP-Gas.
ii. EN 16631, LPG equipment and accessories. Pressure relief valves for LPG pres-
sure vessels. Reconditioning requirements.
iii. EN 13953, LPG equipment and accessories. Pressure relief valves for trans-
portable refillable cylinders for Liquefied Petroleum Gas (LPG).
iv. EN 14071, LPG equipment and accessories. Pressure relief valves for LPG pres-
sure vessels. Ancillary equipment.
v. EN 14129, LPG Equipment and accessories. Pressure relief valves for LPG pres-
sure vessels.
vi. EN 13175 - LPG Equipment and accessories. Specification and testing for Lique-
fied Petroleum Gas (LPG) pressure vessel valves and fittings.
i. Wrought iron — ASME B 36.10M, Welded and Seamless Wrought Steel Pipe.
ii. Steel pipe — ASTM A 53, Standard Specification for Pipe, Steel, Black and Hot-
Dipped, Zinc-Coated Welded and Seamless.
iii. Steel pipe — ASTM A 106, Standard Specification for Seamless Carbon Steel
Pipe for High-Temperature Service.
iv. Brass pipe — ASTM B 43, Standard Specification for Seamless Red Brass Pipe,
Standard Sizes.
v. Copper pipe — ASTM B 42, Standard Specification for Seamless Copper Pipe,
Standard Sizes.
vi. Polyamide and polyethylene pipe — ASTM D 2513, Standard Specification for
Thermoplastic Gas Pressure Pipe, Tubing and Fittings, and shall be recom-
mended by the manufacturer for use with LP-Gas.
vii. ASTM 1387, Specification for screwed and socketed steel tubes and tubulars
and for plain end steel tubes suitable for welding or for screwing to BS 21 pipe
threads.
viii. EN 16125. LPG equipment and accessories. Pipework systems and supports.
LPG liquid phase and vapour pressure phase.
ix. EN ISO 16440. Petroleum and natural gas industries. Pipeline transportation
systems. Design, construction and maintenance of steel cased pipelines.
x. EN 682 - Elastomeric seals. Materials requirements for seals used in pipes and
fittings carrying gas and hydrocarbon fluids.
xi. ISO 17484-1 - Plastics piping systems. Multilayer pipe systems for indoor gas
installations with a maximum operating pressure up to and including 5 bar
(500 kPa). Specifications for systems.
xii. ISO 18225 - Plastics piping systems. Multilayer piping systems for outdoor gas
installations. Specifications for systems.
6.1.13. Tubing
6.1.14. PE Pipes
i. BS ISO 4437-3, Plastics piping systems for the supply of gaseous fuels. Polyeth-
ylene (PE). Fittings.
ii. EN 1555-3, Plastics piping systems for the supply of gaseous fuels. Polyeth-
ylene (PE). Fittings.
iii. GIS/PL2-2, Polyethylene pipes and fittings for natural gas and suitable manu-
factured gas Part 2: Pipes for use at pressures up to 5.5 bar.
iv. GIS/PL2-4, Polyethylene pipes and fittings for natural gas and suitable manu-
factured gas Part 4: Fusion fittings with integral heating element(s).
v. GIS/PL2-6, Polyethylene pipes and fittings for natural gas and suitable manu-
factured gas Part 6: Spigot end fittings for electrofusion and/or butt fusion pur-
poses.
vi. GIS/PL2-8, Polyethylene pipes and fittings for natural gas and suitable manu-
factured gas Part 8: Pipes for use at pressures up to 7 bar.
vii. ASTM D 2683, Standard Specification for Socket-Type Polyethylene (PE)
Fittings for Outside Diameter Controlled Polyethylene Pipe.
viii. ASTM D 3261, Standard Specification for Butt Heat Fusion Polyethylene (PE)
Plastic Fittings for Polyethylene (PE) Plastic Pipe and Tubing.
ix. ASTM F 1055, Standard Specification for electrofusion Type Polyethylene
Fittings for Outside Diameter Controlled Polyethylene Pipe and Tubing.
x. ASTM F 1733, Standard Specification for Butt Heat Fusion Polyamide (PA) Plas-
tic Fitting for Polyamide (PA) Plastic Pipe and Tubing.
i. BS 4089 Specification for metallic hose assemblies for liquid petroleum gases
and liquefied natural gases.
ii. BS 3212 type 1 flexible tubing for applications not exceeding 50 mbar
working pressure.
iii. BS 669 part 1, part 2 for metallic flexible hose.
iv. EN 14800 Corrugated safety metal hose assemblies for the connection of do-
mestic appliances using gaseous fuels.
v. ISO 2928 - Rubber hoses and hose assemblies for liquefied petroleum gas, LPG
(liquid or gaseous phase) and natural gas up to 25 bar (2,5 MPa). Specification.
vi. ISO 11759 - Rubber hoses and hose assemblies for dispensing liquefied petro-
leum gas (LPG). Specification.
vii. ISO 8789. Rubber hoses and hose assemblies for liquefied petroleum gas in
motor vehicles.
viii. EN 13766 - Thermoplastic multilayer (non-vulcanized) hoses and hose assem-
blies for the transfer of liquid petroleum gas and liquefied natural gas. Specifi-
cation.
ix. EN 1762 - Rubber hoses and hose assemblies for liquefied petroleum gas, LPG
(liquid or gaseous phase), and natural gas up to 25 bar (2,5 MPa). Specification.
x. ISO 27127 - Thermoplastic multi-layer (non-vulcanized) hoses and hose assem-
blies for the transfer of liquid petroleum gas and liquefied natural gas.
xi. UL 21 LP-Gas Hose, LP-Gas Hose Assemblies.
xii. UL 569 Pigtails and Flexible Hose Connectors.
enclosures "d""
xi. IEC 60079-11, Explosive atmospheres Equipment protection by intrinsic safety
II
"i""
i. EN 50200, Method of test for resistance to fire of unprotected small cables for
use in emergency circuits
ii. UL 2196, Standard for Fire Test for Circuit Integrity of Fire-Resistive Power,
Instrumentation, Control, and Data Cables
iii. BS 8434-2, Methods of test for assessment of the fire integrity of electric ca-
bles. Test for unprotected small cables for use in emergency circuits. BS EN
50200 with a 930° flame and with water spray .
iv. BS 7629-1, Electric cables. Specification for 300/500 V fire resistant screened
cables having low emission of smoke and corrosive gases when affected by
fire. Multicore and multipair cables.
v. BS 6387, Test method for resistance to fire of cables required to maintain cir-
cuit integrity under fire conditions.
vi. IEC 60331-1, Tests for electric cables under fire conditions.
vii. IEC 60331-2, Tests for electric cables under fire conditions.
viii. IEC 60332-2-2, Tests on electric and optical fibre cables under fire conditions.
ix. IEC 60332-3-10, Tests on electric and optical fibre cables under fire conditions.
x. IEC 60331-2, Tests for electric cables under fire conditions.
xi. UL 1724, Outline of Investigation for Fire Tests for Electrical Circuit Protective
Systems.
xii. UL 1685, Standard for Vertical-Tray Fire-Propagation and Smoke-Release Test
for Electrical and Optical-Fiber Cables.
xiii. UL 1666, UL 1666 Test for Flame Propagation Height of Electrical and Optical-
Fiber Cables Installed Vertically in Shafts.
6.1.1. All the Materials, Systems, Assemblies, wiring, fittings, equipment, Products and
Accessories, referred to in this chapter shall be Listed, Approved and Registered by
the Civil Defence Material Approval Department.
6.1.2. There is no year of edition mentioned against any test standards. It is the intent of
Civil Defence to convey to the customers seeking laboratory tests and the test la-
boratories to follow the “LATEST EDITION OF THE TEST STANDARD, AS AND WHEN
THEY ARE UPGRADED/REVISED/AMENDED, TO THE DATE.”
i. API Specification 620, Recommended Rule for the design and construction of
Large, Welded, Low-Pressure Storage Tanks
ii. ASME, Code for Unified Pressure Vessels, Section VIII, Division 1.
6.1.6. Vaults
i. UL 2245, Standard for below grade vaults for flammable liquid storage tanks
i. UL 558, Standard for Safety Industrial Trucks, internal combustion Engine pow-
ered.
ii. UL 583, Standard for Safety Electric– Battery powered Trucks.
UTILITY OCCUPANCIES
2.2.4.1.1. All the Materials, Systems, Assemblies, Pipes and fittings, equipment,
Products and Accessories, referred to in this chapter shall be Listed, Ap-
proved and Registered by the Civil Defence Material Approval Depart-
ment.
i. IEC 62109 –1, Safety of power converters for use in photovoltaic power sys-
tems, and IEC 62109 –2, Particular requirements for inverters OR
ii. UL 1741, Standard for Inverters, Converters, Controllers and Interconnection
System Equipment for Use With Distributed Energy Resources
ITEMS REQUIREMENTS
1. SIGNALS FROM 1. ALARMS
BUILDING
i. As a minimum, the following “Alarm” signals from a building shall be annunci-
ated to Civil Defence through Smart monitoring System.
a. ‘Fire Alarm’ from Fire Detection and Alarm Control Panel (FACP)
b. ‘Low Water level’ alarm from building Fire Water Tank
c. ‘LP Gas or Natural Gas leakage’ alarm from building gas detection system
d. ‘Fire Pump in operation’ annunciation from building fire pump controller
e. ‘Diesel Fuel Low’ signal from Diesel Fire Pump controller
f. ‘Pressure Low’ signal from fire water line
g. ‘Passenger Alarm’ signal from Lift control panel
2. FAULTS
ITEMS REQUIREMENTS
2. PROVISIONS 3. HIGHRISE AND SUPERHIGH RISE BUILDINGS
REQUIRED IN
THE BUILDING 3.a. SMART BUILDINGS WITH OPEN PROTOCOLS
i. Where buildings are provided with FACP’s, Smoke control panel, Gas detection
panel, Fire pump controllers and elevator control panels with state of the art In-
ternet or things (IoT) features OR building has ‘Smart’ features OR building has
BMS (Building Management Systems), open protocols shall be made available to
achieve the required signal annunciation and communication as per Table 16.1.1.
ii. The acceptable open protocols shall be such as following
a. BACnet IP
b. BACnet MSTP
c. Modbus TCP
d. Modbust RTU with RS485 ports
e. Lonworks
i. Dedicated volt free contacts (VFC) in the FACP shall be available. The state of the
VFC should ideally be normally closed (NC) during normal condition and open
(NO) during alarm condition, for
a. Common fire alarm from FACP
b. Common fire alarm system fault from FACP
ii. Dedicated volt free contacts (VFC) in the Fire Pump Controller shall be available.
The state of the VFC should ideally be normally closed (NC) during normal condi-
tion and open (NO) during alarm condition, for
a. Fire Pump in operation
b. Common fire pump system fault from controller
c. System Pressure Low
d. Diesel fuel low
e. Water tank level low
iii. Dedicated volt free contacts (VFC) in the Gas control panel shall be available. The
state of the VFC should ideally be normally closed (NC) during normal condition
and open (NO) during alarm condition, for
a. Gas leak detection
b. Common gas detection system fault from control panel
iv. Dedicated volt free contacts (VFC) in the Smoke control panel shall be available.
The state of the VFC should ideally be normally closed (NC) during normal condi-
tion and open (NO) during fault condition, for
a. Common system fault from control panel
v. Dedicated volt free contacts (VFC) in the Elevator control panel shall be available.
The state of the VFC should ideally be normally closed (NC) during normal condi-
tion and open (NO) during fault condition, for
a. Common elevator fault from control panel
b. Passenger Alarm from elevator control panel
vi. Dedicated volt free contacts (VFC) in the Emergency lighting control panel shall
be available. The state of the VFC should ideally be normally closed (NC) during
normal condition and open (NO) during fault condition, for
a. Common system fault from control panel