Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Kinco VFD Cv100

Download as pdf or txt
Download as pdf or txt
You are on page 1of 119

Preface

Thank you for using CV100 series Variable Frequency Drive made by Kinco Automation.
CV100 satisfies the high performance requirements by using a unique control method to achieve high torque, high
accuracy and wide speed-adjusting range. Its anti-tripping function and capabilities of adapting to severe power
network, temperature, humidity and dusty environment exceed those of similar product made by other companies,
which improves the product’s reliability noticeably;Without PG connector, strong speed control, flexiable input/output
terminal, pulse frequency setting, saving parameters at power outage and stop, frequency setting channel, master and
slave frequency control and so on, all these satisfy various of high accuracy and complex drive command, at the same
time we provide the OEM customer high integration total solution, it values highly in system cost saving and
improving the system reliability.
CV100 can satisfy the customers’ requirements on low noise and EMI by using optimized PWM technology and
EMC design.
This manual provides information on installation, wiring, parameters setting, trouble-shooting, and daily
maintenance. To ensure the correct installation and operation of CV100, please read this manual carefully before
starting the drive and keep it in a proper place and to the right person.

Unpacking Inspection Note


Upon unpacking, please check for:
z Any damage occurred during transportation;
z Check whether the rated values on the nameplate of the drive are in accordance with your order.
Our product is manufactured and packed at factory with great care. If there is any error, please contact us or
distributors.
The user manual is subject to change without notifying the customers due to the continuous process of product
improvements
VFD model rule
CV 1 00 – 4 T– XXXX G–U–000
VFD code
CV: Mini type
Reserved

Customize hardware:
The first gerneration
U:None

00:Standard model

G: Constant torque
Power supply L: Constant power
2: 200V
4: 400V
Power
0002: 200w
S: signal phase 0004: 400w
T: 3-phase ……
Content
Chapter 1 Safety................................................................................................................................................................... 1

1.1 Safety...................................................................................................................................................................... 1
1.2 Notes for Installations.............................................................................................................................................1
1.3 Notes for Using CV100.......................................................................................................................................... 1
1.3.1 About Motor and Load................................................................................................................................1
1.3.2 About Variable Frequency Drive...............................................................................................................2
1.4 Disposing Unwanted Driver................................................................................................................................... 3
Chapter 2 Product introduction......................................................................................................................................... 4

2.1 Genernal sepcifications...........................................................................................................................................4


2.2 Introduction of product series.................................................................................................................................5
2.3 Structure of VFD.................................................................................................................................................... 6
2.4 External dimension and weight.............................................................................................................................. 6
2.4.1 External dimension and weight..................................................................................................................6
2.4.2 Operation panel and installation box......................................................................................................... 7
Chapter 3 Installation Environment.................................................................................................................................. 8

Chapter 4 Wiring Guide of VFD.......................................................................................................................................9

4.1 Wiring and Configuration of Main circuit terminal............................................................................................... 9


4.1.1 Terminal Type of Main Loop’s Input and Output...................................................................................... 9
4.1.2 Wiring of VFD for Basic Operation......................................................................................................... 10
4.2 Wiring and configuration of control circuit......................................................................................................... 11
4.2.1 Wiring of control circuit termial............................................................................................................... 11
Chapter 5 Operation Instructions of Kinco VFD............................................................................................................16

5.1 Using Operation Panel....................................................................................................................................16


5.1.1 Operation panel appearance and keys’ function description.................................................................... 16
5.1.2 Function Descriptions of LED and Indicators.......................................................................................... 17
5.1.3 Display status of operation panel..............................................................................................................17
5.1.4 Panel Operation.........................................................................................................................................17
5.2 Operation mode of VFD................................................................................................................................. 19
5.2.1 Control mode of VFD............................................................................................................................... 19
5.2.2 Operating Status........................................................................................................................................ 19
5.2.3 Control mode and operation mode of Kinco VFD................................................................................... 19
5.2.4 The channels to set the VFD frequency....................................................................................................20
5.3 Power on the Drive for the first time..............................................................................................................20
5.3.1 Checking before power on........................................................................................................................ 20
5.3.2 Operations when start up the first time.....................................................................................................20
Chapter 6 Parameter Introductions................................................................................................................................. 22

6.1 Group A0.............................................................................................................................................................. 22


6.2 Group A1.............................................................................................................................................................. 24
6.3 Group A2.............................................................................................................................................................. 27
6.4 Group A3.............................................................................................................................................................. 28
6.5 Group A4.............................................................................................................................................................. 30
6.6 Group A5.............................................................................................................................................................. 31
6.7 Group A6.............................................................................................................................................................. 33
6.8 Group A7.............................................................................................................................................................. 42
6.9 Group A8.............................................................................................................................................................. 42
6.10 Group b0............................................................................................................................................................. 43
6.11 Group b1............................................................................................................................................................. 45
6.12 Group b2............................................................................................................................................................. 46
6.13 Group b3............................................................................................................................................................. 48
6.14 Group b4............................................................................................................................................................. 48
6.15 Group C0.............................................................................................................................................................49
6.16 Group C1.............................................................................................................................................................50
6.17 Group C2.............................................................................................................................................................54
6.18 Group C3.............................................................................................................................................................57
6.19 Group d0............................................................................................................................................................. 58
6.20 Group d1............................................................................................................................................................. 60
6.21 Group d2............................................................................................................................................................. 60
Chapter 7 Troubleshooting.................................................................................................................................................61

Chapter 8 Maintenance.......................................................................................................................................................67

8.1 Daily Maintenance................................................................................................................................................67


8.2 Periodical Maintenance........................................................................................................................................ 67
8.3 Replacing Wearing Parts...................................................................................................................................... 68
8.4 Storage.................................................................................................................................................................. 69
Chapter 9 List of Parameters..............................................................................................................................................70

Communication Protocol..................................................................................................................................................105

1. Networking Mode.................................................................................................................................................105
2. Interfaces...............................................................................................................................................................105
3. Communication Modes.........................................................................................................................................105
4. Protocol Format.................................................................................................................................................... 105
1. RTU mode.................................................................................................................................................... 106
2. ASCII mode..................................................................................................................................................106
5. Protocol Function..................................................................................................................................................107
6.Control parameters and status parameters of VFD............................................................................................... 108
Chapter 1 Safety

1.1 Safety
Operations without following instructions
Danger can cause personal injury or death.

Operations without following instructions

! Attention can cause personal injury or damage to ! Attention


product or other equments
· Don’t carry the drive by its cover. The cover can not
support the weight of the drive and may drop.
1.2 Notes for Installations · Please install the drive on a strong support, or the
drive may fall off.
Danger · Don’t install the drive in places where water pipes

· Please install the drive on fire-retardant material like may leak onto it.

metal, or it may cause fire. · Don't allow screws, washers and other metal foreign

· Keep the drive away from combustible material and matters to fall inside the drive, otherwise there is a

explosive gas, or it may cause fire. danger of fire or damage;

· Only qualified personnel shall wire the drive, or it · Don't operate the drive if parts are damaned or not

may cause electric shock., complete,otherwise there is a danger of a fire or human

· Never wire the drive unless the input AC supply is injury;

totally disconnected, or it may cause electric shock., · Don't install the drive under direct sunshine,

· The drive must be properly earthed to reduce otherwise it may be damaged;

electrical accident · Don’t short circuit +//B1 and terminal (-), otherwise

· Install the cover before switching on the drive, to there is a danger of fire or the drive may be damaged.

reduce the danger of electric shock and explosion. · Cable lugs must be connected to main terminals

· For drives that have been stored for longer than 2 firmly

years, increase its input voltage gradually before · Don’t apply supply voltage (AC 220V or higher) to

supplying full rated input voltage to it, in order to control terminals except terminals R1a, R1b and R1c.

avoid electric shock and explosion ·B1 and B2 are used to connect the brake resistor, do

· Don't touch the live control terminals with bare not shortcut them, or the brake unit may be damaged

hands
parts inside the drive so as to avoid the risk of fire.
· Don’t operate the drive with wet hands
· Parameter settings of the control panel that has been
· Perform the maintenance job after confirming that
changed must be revised, otherwise accidents may
the charging LED is off or the DC Bus voltage is occur.
below 36V, or it may cause electric shock.,
· The bare portions of the power cables must be bound
· Only trained professionals can change the
with insulation tape
components, it is prohibited to leave wires or metal

1
Braking Torque
1.3 Notes for Using CV100 Braking torque is developed in the machine when the
Pay attention to the following issues when using CV100. drive is hoisting a load down. The drive will trip when it
cannot cope with dissipating the regenerative energy of
1.3.1 About Motor and Load
the load. Therefore, a braking unit with proper
Compared to the power frequency operation parameters setting in the drive is required.
CV100 series drives are voltage type variable frequency The mechanical resonance point of load
drive. The output voltage is in PWM wave with some The drive system may encounter mechanical resonance
harmonics. Therefore, temperature rise, noise and with the load when operating within certain band of
vibration of motor are higher compared to the rated output frequency. Skip frequencies have been set to
frequency. avoid it.

Low Speed operation with Constant Torque Start and stop frequntly
Driving a common motor at low speed for a long time, The drive should be started and stopped via its control
the drive’s rated output torque will be reduced terminals. It is prohibited to start and stop the drive
considering the deteriorating heat dissipation effect, so a directly through input line contactors, which may
special variable frequency motor is needed if operation damage the drive with frequent operations.
at low speed with constant torque for a long term.
Insulation of Motors
Motor’s over-temperature protecting threshold Before using the drive, the insulation of the motors must
When the motor and driver are matched, the drive can be checked, especially, if it is used for the first time or if
protect the motor from over-temperature. If the rated it has been stored for a long time. This is to reduce the
capacity of the driven motor is not in compliance with risk of the Drive from being damaged by the poor
the drive, be sure to adjust the protective threshold or insulation of the motor. Wiring diagram is shown in Fig.
take other protective measures so that the motor is 1-1. Please use 500V insulation tester to measure the
properly protected. insulating resistance. It should not be less than 5MΩ.

Operation above 50Hz


When running the motor above 50Hz, there will be
increase in vibration and noise. The rate at which the
torque is available from the motor is inversely
proportional to its increase in running speed. Ensure that
the motor can still provide sufficient torque to the load. Fig. 1-1 checking the insulation of motor

Lubrication of mechanical devices


Over time, the lubricants in mechanical devices, such as 1.3.2 About Variable Frequency Drive

gear box, geared motor, etc. when running at low speed, Varistors or Capacitors Used to Improve the Power
will deteriorate. Frequent maintenance is recommended. Factor

2
Considering the drive output PWM pulse wave, please
don't connect any varistor or capacitor to the output
terminals of the drive, , otherwise tripping or damaging
of components may occur; as shown in fig 1.2

U
CV100 M
V
W

Fig. 1-3 Derating Drive's output current with altitude

1.4 Disposing Unwanted Driver


Fig. 1-2 Capacitors are prohibited to be used.
When disposing the VFD, pay attention to the following
issues:
Circuit breakers connected to the output of VFD
The electrolytic capacitors in the driver may explode
If circuit breaker or contactor needs to be connected
when they are burnt.
between the drive and the motor, be sure to operate these
Poisonous gas may be generated when the plastic parts
circuit breakers or contactor when the drive has no
like front covers are burnt.
output, to avoid damaging of the drive.
Please dispose the drive as industrial waste.
Using VFD beyond the range of rated voltage
The drive is not suitable to be used out of the
specified range of operation voltage. If needed, please
use suitable voltage regulation device.
Protection from lightning
There is lightingstrike overcurrent device inside the
Drive which protects it against lighting.
Derating due to altitude
Derating must be considered when the drive is
installed at high altitude, greater than 1000m. This is
because the cooling effect of drive is deteriorated due to
the thin air, as shown in Fig.1-3 that indicates the
relationship between the altitude and rated current of the
driver.

3
4
Chapter 2 Product introduction

In this chapter we introduce the basic product information of specifications, model, and structure and so on.

2.1 General specifications


Table 2-1 General specifications
Item Description
Rated voltage and 4T: 3-phase,380V~440V AC; 50Hz/60Hz;
frequency 2S: Single-phase,200V~240V;50Hz/60Hz
Input
Allowable voltage
4T: 320V~460V AC; 2S:180V~260V;Voltage tolerance<3%; Frequency: ±5%
range
Rated voltage 0~Rated input voltage
Frequency 0Hz~300Hz(Customed 0Hz~1000Hz)
Output
G type : 150% rated current for 1 minute, 180% rated current for 10 seconds;
Overload capacity
L type :110% rated current for 1 minute, 150% rated current for 1 second
Control mode V/F control
Modulation mode Space vector PWM modulation
Frequency accuracy Digital setting:Max frequency ×±0.01%;Analog setting:Max. frequency ×±0.2%
Frequency
Digital setting: 0.01Hz;Analog setting: Max frequency×0.05%
Control resolution
Characteristi Torque boost Manual torque boost :0%~30.0%
cs 4 pattens: 1 V/F curve mode set by user and 3 kinds of torque-derating modes (2.0
V/F pattern
order, 1.7 order, and 1.2 order)
Acc/Dec curve Linear acceleration/deceleration, Four kinds of acceleration/deceleration time
Limit current during the operation automatically to prevent frequent overcurrent
Auto current limit
trip
Range of jog frequency:0.00Hz~50.00Hz; Acc/Dec time of Jog
Jog
Customized operation:0.1~60.0s, Interval of Jog operation is also settable.
function Multiple speed
Implement multiple speed operation by digital inputs
operation
Operation command Keypad setting, terminal setting, communication setting.
Frequency
Keypad setting, Analog input, Communication setting
Operation command setting
function Auxiliary frequency
Implement flexible auxiliary frequency trim and frequency synthesis.
setting
Pulse output 0~100KHz pulse output.

5
Analog output 2 channels analog output(0/4~20mA or 0/2~10V).
Display setting frequency, output frequency , output voltage, output current and so
LED Display
on, about 20 parameters.
Operation
Parameters copy Copy parameters by operation panel.
panel
Keys lock and
Lock part of keys or all the keys. Define the function of part of keys
function selection
Open phase protection (optional), overcurrent protection, overvoltage protection,
Protection function
undervoltage protection, overheat protection, overload protection and so on.
Indoor , installed in the environment free from direct sunlight, dust, corrosive gas,
Operating site
combustible gas, oil mist, steam and drip.
Derated above 1000m, the rated output current shall be decreased by 10% for
Altitude
every rise of 1000m
Ambient
Environment -10℃~40℃, derated at 40℃~ 50℃
temperature
Humidity 5%~95%RH, non-condensing
Vibration Less than 5.9m/s2 (0.6g)
Storage
-40℃~+70℃
temperature
Protection class IP20
Structure
Cooling method Air cooling, with fan control.
Installation method Wall-mounted
Efficiency ≥90%

2.2 Introduction of product series


Table 2-1 Series of Kinco VFD
Rated capacity Rated input current Rated output current Motor power
Model of VFD
(kVA) (A) (A) (kW)
CV100-2S-0002G 0.5 2.3 1.3 0.2
CV100-2S-0004G 1.0 5.3 2.5 0.4
CV100-2S-0007G 1.5 8.2 4.0 0.75
CV100-2S-0015G 3.0 14 7.5 1.5
CV100-2S-0022G 4.0 23 10 2.2
CV100-4T-0007G 1.5 3.4 2.3 0.75
CV100-4T-0015G 3.0 5.0 3.7 1.5
CV100-4T-0022G 4.0 5.8 5.5 2.2

6
2.3 Structure of VFD
The structure of VFD is as following figure.

Fig.2-1 Structure chart of VFD

2.4 External dimension and weight

2.4.1 External dimension and weight

External dimension and weight is as following figure.

Fig 2-2 CV100-2S-0002G~ CV100-4T-0022G

7
Tabble 2-2 Mechanical parameters
VFD model External dimension and (mm)
(G:Constant torque
Weight
load; Installation
W H D W1 H1 D1 T1 (kg)
L: Draught fan and hole(d)
water pump load)
CV100-2S-0002G
CV100-2S-0004G
127
CV100-2S-0007G 85 142 73 130 117 10 5 0.8
CV100-2S-0015G
CV100-2S-0022G
CV100-4T-0007G
CV100-4T-0015G 101 152 127 89 140 117 10 5 1
CV100-4T-0022G

2.4.2 Operation panel and installation box

50.00
R UN Hz A V

MENU ENTER

SHIFT M

RUN

STOP
RST

Fig 2-3 Operation panel dimension

8
Chapter 3 Installation Environment

In this chapter we introduce the installation environment of VFD


Please mount the drive vertically inside a well-ventilated location.
When considering mounting environment, the following issues should be taken into account:
z Ambient temperature should be within the range of-10℃~40℃. If the temperature is higher than 40 ℃, the drive
should be derated and forced ventilation is required;
z Humidity should be lower than 95%,non-condensing
z Install in the location where vibration is less than 5.9m/s2 (0.6G);
z Install in the location free of direct sunlight.
z Install in the location free of dust, metal powder.
z Install in the location free of corrosive gas or combustible gas.
If there are any special requirements for installation, please contact us for clarifications.
The requirements on mounting space and clearance are shown in Fig. 3-1 and Fig. 3-2.

Fan airflow >10cm

>5cm >5cm

>10cm

Fig 3-1 Installation interval (Power below 45kW) Fig 3-2 Installation interval(Power above 55kW)
When two VFD are mounted one on top the other, an air flow diverting plate should be fixed in between them as
shown in Fig. 3-3.

Fig 3-3 Installation of servial VFD

9
Chapter 4 Wiring Guide of VFD

In this chapter we introduce the wiring of VFD

Danger
·Wiring can only be done after the drive’s AC power is disconnected, all the LEDs on the operation panel are off
and waiting for at least 5 minutes. Then, you can remove the panel.
·Wiring job can only be done after confirming the charge indicator on the right bottom is off and the voltage
between main circuit power terminals + and - is below DC36V.
·Wire connections can only be done by trained and authorized person
·Check the wiring carefully before connecting emergency stop or safety circuits.
·Check the drive’s voltage level before supplying power to it, otherwise human injuries or equipment damage
may happen.

! Attention
·Check whether the Variable Speed Drive’s rated input voltage is in compliant with the AC supply voltage
before using.
·Dielectric strength test of the drive has been done in factory, so you need not do it again.
·Refer to chapter 2 on connected braking resistor or braking kit.
·It is prohibited to connect the AC supply cables to the drive’s terminals U, V and W.
·Grounding cables should be copper cables with section area bigger than 3.5mm2, and the grounding resistance
should be less than 10Ω.
·There is leakage current inside the drive. The total leakage current is greater than 3.5mA, depending on the
usage conditions. To ensure safety, both the drive and the motor should be grounded, and a leakage current
protector (RCD) should be installed. It is recommended to choose B type RCD and set the leakage current at
300mA.
·The drive should be connected to the AC supply via a circuit breaker or fuse to provide convenience to input
over-current protection and maintainance.

4.1 Wiring and Configuration of Main circuit terminal

4.1.1 Terminal Type of Main Loop’s Input and Output

Terminal Type
Applicable Model: CV100-2S-0002G~CV100-4T-0022G

10
Table 4-1 Description of main loop terminal

Terminal
Function description
name

Single phase 220VAC input


L,N
terminal

R,S,T 3-phase 380VAC input termianl

+/B1、B2 Braking resistor terminal

U,V,W 3-phase AC output terminal

PE Shield PE terminal

RS+ RS485+

RS- RS485-

4.1.2 Wiring of VFD for Basic Operation

Applicable model: CV100-4T-0007G/0022G

11
Fig.4-1 Basic wiring chart

4.2 Wiring and configuration of control circuit

4.2.1 Wiring of control circuit termial.

Wire the terminals correctly before using the Drive. Refer to the table 4-2 for control circuit terminal function
Note
It is recommended to use cables bigger than 1mm2 to connect to the terminals.
Arrangement of control circuit terminals is as follows

Fig.4-2 Arrangement of control terminals

Refer to table 4-2 for description of each terminal


Table 4-2 function list of each terminal
Category Terminals Name Function description Specification
Shield PE Shielded PE PE terminal connected to shielding Connected to circuit PE inside the

12
Category Terminals Name Function description Specification
layer.Analog singal, 485 drive
communication,motor power cable
shield can be connected here
Power +10V Power
+10 Provide +10V power supply Maximum output current is 5mA
supply supply
Can accept analog voltage/current
Signal-ended input, jumper AI1 can select voltage or Input voltage range: -10V ~ 10V
AI1
input AI1 current input mode. (Reference ground: ( Input impedance 45KΩ )
Analog GND) Resolution: 1/4000
input Can accept analog voltage/current Input current range : 0mA ~ 20
Signal-ended input, jumper AI2 can select voltage or mA, Resolution: 1/2000(Need
AI2
input AI2 current input mode. (Reference ground: jumper)
GND)

Providing analog voltage or current


output, they are selected by the jumper Voltage output range: 0V~10V
AO1 Analog output 1 AO1. The default setting is output Current output range:
voltage, refer to the function code 0/4~20mA

Analog A6.28(Reference ground: GND)

output Providing analog voltage or current


output, they are selected by the jumper Voltage output range: 0V~10V
AO2 Analog output 2 AO2. The default setting is output Current output range:
voltage, refer to the function code 0/4~20mA
A6.29(Reference ground: GND)

Multi-function Optocoupler isolation input


X1
input terminal 1 Input resistor: R=3.3kΩ
Multi-function Maximum input frequency of
X2
Multi-fun input terminal 2 Can be defined as multi-function digital X1~X5: 200Hz
ction Multi-function input terminal.(Refer to the A6 group, Input voltage range:20~30v
X3
input input terminal 3 from A6.00 to A6.04) 24V
+24V

PLC +3.3V
terminal Multi-function
X4
input terminal 4 R

X1、。。。X5
Multi-function
X5 COM

input terminal 5
Multi-fun
Bi-direction Can be defined as multi-function digital Optocoupler isolation output
ction
Y1 open-collector output terminal , refer to the A6.14 Maximum working voltage: 30v
output
output desctription (Com port: COM) Maximum output current: 50mA
terminal

13
Category Terminals Name Function description Specification
Common port of
Common Three common ports in all, cooperate
COM 24V power
port with other terminals
supply
R1a-R1b:Normally closed,
RA
R1a-R1c:normally open

RB Contact capacity :
Relay Can be defined as multi-function relay AC250V/2A(COSΦ=1)
output Relay output output terminal(Refer to the A6.16 for AC250V/1A(COSΦ=0.4)
terminal 1 function description)
DC30V/1A
RC
Input voltage of relay output
terminal 's overvoltage class is
overvoltage class II

Arrangement of control circuit terminals is as follows


24V PLC

J606

RA RB RC AI1 AI2 +10V X1 X2 X3 X4 X5 Y1 AO1 AO2 OP COM PE

Wiring of OP
24V PLC

1:When: J606 Use internal +24V power supply


Wirings of multiple function input terminal and operation terminal

RA RB RC AI1 AI2 +10V X1 X2 X3 X4 X5 Y1 AO1 AO2 OP COM PE

24V PLC

2:When: J606 Use external power supply


Wirings of multiple function input terminal and operation terminal

RA RB RC AI1 AI2 +10V X1 X2 X3 X4 X5 Y1 AO1 AO2 OP COM PE

+
-

Wiring of analog input


1)AI1, AI2 can be connected to analog voltage or current single-ended input. Voltage or current mode can be seleted
by AI1and AI2. The wiring is as follows:

14
CV100

+10

AI1,AI2

GND
-10~+10V PE
Or0~20mA Shield cable connect
to PE

Fig 4-3 AI1,AI2 terminal wiring

Wiring of analog output terminal


If the analog output terminals AO1,AO2 are connected to analog meters, then various kinds of physical values can be
measured. The jumper can select current output (0~20mA) or voltage output (0~10V). The wiring is as follows:

Analog meters
AO1
CV100

GND

Fig.4-4 Wiring of analog output


Notes:
1.When using analog input, a common mode inductor can be installed between input signal and COM.
2.The analog input voltage is better under 15v.
3.Analog input and output signals are easily disturbed by noise, so shielded cables must be used to transmit these
signals and the cable length should be as short as possible.
4.The analog output terminal can stand the voltage under 15v

Wirings of Multi-function output terminal wiring 2. Multi-function output terminal Y1 can use the external
1. Multi-function output terminal Y1 can use the internal 24 power supply too, the wiring is as shown in Fig.4-12.
24 power supply, the wiring is as shown in Fig.4-11 +24V
24V
+5V DC
+24V Y1
24V + -
Relay
+5V COM
Relay
Y1

CV100
COM

CV100
Fig 4-12 Wiring method 2 of multi-function output
terminal
Fig 4-11 Wiring method 1 of multi-function
output terminal
Wiring of relay output terminals Ra, Rb and Rc

15
If the drive drives an inductive load (such as
electromagnetic relays and contactor), then a surge
suppressing circuit should be added, such as RC
snubbing circuit (Notice that the leakage current must be
smaller than the holding current of the controlled relay
or contactor) and varistor or a free-wheeling diode (Used
in the DC electric-magnetic circuit and pay attention to
the polarity when installing). Snubbing components
should be as close to the coils of relay or contactor as
possible.
Note
1. Don’t short circuit terminals 24V and COM,
otherwise the control board may be damaged.
2. Please use multi-core shielded cable or multi-stranded
cable(above 1mm) to connect the control terminals.3.
When using a shielded cable, the shielded layer’s end
that is nearer to the drive should be connected to PE.
4. The control cables should be as far away(at least
20cm) from the main circuits and high voltage cables as
possible (including power supply cables, motor cables,
relay cables and contactor cables and so on). The cables
should be vertical to each other to reduce the disturbance
to minimum.
5. The resistors R in Fig. 4-11 and Fig.4-12 should be
removed for 24V input relays, and the resistance of R
should be selected according the parameters of relay for
non-24V relay.
6. Digital output terminal can not stand the voltage
higher than 30V

16
Chapter 5 Operation Instructions of Kinco VFD

In this chapter we introduce the necessary knowledge of Kinco VFD and related operations.

5.1 Using Operation Panel

5.1.1 Operation panel appearance and keys’ function description

Operation panel is used to setup the drive and display parameters, it is LED display . As shown in Fig.5-1

Fig.5-1 Illustration of operation panel


There are 9 keys on the operation panel and functions of each key are shown in Table 4-1.
Table 5-1 Function list of operation panel
Key Name Function
MENU Program/ exit key Enter or exit programming status
ENTER Function/ data key Enter next level menu or confirm data
∧ Increase key Increase data or parameter
∨ Decrease key Decrease data or parameter
In editing status, pressing this key select the Bit to be modified. In other
SHIFT Shift key
status, this key is used to switch parameters.
M Multi-function key Use the b4.02 to cofigure thw function of this key

17
Key Name Function
RUN Run key In panel control mode, press this key to run the drive.
STOP/RST Stop/reset key Press this key to stop or reset the drive.
Frequency setting
Rotary knob Rotate it to set the frequency.
rotary knob

control terminal or communication command to reset


5.1.2 Function Descriptions of LED and Indicators
the error. If the error still exists, then the panel keeps
The operation panel consists of a 4-digits eight
displaying the error code.
segments LED display, 3 unit indicators and 1 status
4. Parameter editing status
indicator as shown in Fig.5-1. The LED display can
When the drive is in stop, running or error state, press
display the status parameters, function codes and error
MENU can enter edit status(If password needed,
codes of the drive. 1 status indicator,its description is
please refer to description of A0.00),. Edit state
shown in table 5-2
displays in 2-level menu, they are: function codegroup
Table 5-2
or function code number→function code parameter
Indicator Status Current status of drive
value. You can press ENTER to enter parameter
Running Off Stop displayed status. In function parameter displayed
indicator(RUN) On Running sttatus, press ENTER to save the settings, and press
MENU to exit the menu.
5.1.3 Display status of operation panel
5.1.4 Panel Operation
CV100 operation panel can display the parameters in
Various operations can be done on the operation
stopping status, running status, parameters editing
panel,follows are 5 common examples. Refer to
status..
parameter list in chapter 9 for detail function code
1. Parameters displayed in stopping status
description.
When the drive is in stop status, the operation panel
displays the stopping staus parameter. Pressing the Example 1:Set parameters

SHIFT key can display different stop status parameters Example: Change the value in A0.03 from 50.00Hz to
(Defined by function code b4.05) 30Hz
2. Parameters displayed in running status 1. In the stop parameter displaying state, press MENU
When the drive receives operating command, it starts to enter the fiest level A0.00;
running and its panel will display the running status 2. Press ∧ to change A0.00 to A0.03;
parameters, the RUN indicator turns on.The unit 3. Press ENTER to enter the second level menu
indicator display the unit of the parameter, by pressing 4. Press the SHIFT to change the marker to the highest
the SHIFT key can display different operation bit
parameters (Defined by function code b4.05) 5. Press the ∨ to change the 50.00 to 30.00
3. Parameters displayed in error status 6. Press the ENTER to confirm above change and back
When the drive detects a fault signal, the panel will to the fist level menu. Then the parameter is changed
display the flashing fault code.. successfully.
Press the SHIFT key to display the stop staus The above operations are shown in following picture.
parametere and error code. By pressing the STOP/RST,

18
Fig 5-3 Modify the setting frequency
Fig 5-2 Example of setting parameter
After modification, if there are no operations in 5
In function parameter displaying status, if there is no
seconds. The LED back to display the voltage, it is the
bit flashing. It means that this function code can not be
display status before modification.
changed, the possible reason are:
Example 3: Set the password
1. This function code is unchangeable parameter. Like
To protect parameters, the VFD provides the password
actual detected parameter, operation log parameter and
protection function. The user needs to input the right
so on
password to edit the parameters if the VFD been set
2. This parameter can not be changed when operating;
password. For some manufacturer parameters, the
you need stop the VFD to edit the parameter
manufacturer password is needed.
3. The parameters are protected. When the b4.02 is 1,
function code can not be changed. It is to protect the Note:

VFD from wrong operatingon. If you want to edit this Do not try to change the manufacturer parameters, if

parameter, you need set function code b4.02 to 0. they are not set probably, the VFD may can not work
or be damanged.

Example 2: Regulate the setting frequency Function code A0.00 is to set user password. Refer to
Chapter 6.1 A0 group for more information
Press the ∧ ∨ or rotary knob to change the setting
Suppose the user’s password is set as 1234, then the
frequency directly when power on VFD
VFD is locked, and you can not do any operation to
Note:
VFD. Then you can follow the following steps to
When the Operating Speed, Setting Speed, Operating
unlock the VFD.
Line Speed, and Setting Line Speed is displayed on the
1 when the VFD is locked, press MENU. The LED
panel. Press ∧ or ∨ is to modify the value of
enter the password display status: 0000;
Setting Speed and Setting Line Speed.
2 Change 0000 to 1234;
3 Press ENTER to confirm. Then the LED displays
Example: changing the setting frequency from A0.01. So the VFD is unlocked
50.00Hz to 40.00Hz.
Note:
After the VFD power on (in this example the LED is in
After unlock the password, if there is no operation in 5
voltage display status AI1), Press ∨ to modify the
minutes, VFD will be locked again.
setting frequency (Holding ∨ can speed up the
modification) from 50.00Hz to 40.00Hz. So the setting Example 4: Lock the operation panel
frequency is modified. The b4.00 is used to lock the operation board. Refere
The above steps are as the following figure: to chapter 6.1 A0 group for more information

19
Example: Lock all the keys of the operation panel The control modes can be selected by function code
Undrer stop parameter displaying status. A0.04, multi-function input terminal (Function No.
1 press MENU to enter A.00 15~17 are selected by A6.00~A6.04 )
2 Press ∧ to choose the function code b4.00 Note:
3 Press ENTER to entere the second level menu Before you change the control mode, make sure that
4 Press ∧ to change the hundreds place from 0 to 1 the mode suitable for the application. Wrong selection

5 Press ENTER to confirm of control mode may cause damage to equipment or

6 Press MENU to back the stop parameter displaying human injury!

status;
5.2.2 Operating Status
7 Press ENTER and hold, then press MENU, so the
There are 3 operating status: stop, motor parameters
key board is locked
auto-tuning, and operating.
Example 5: Unlock the keys of the operation panel
1.Stop status: After the drive is switched on and
When the operation panel is locked, follow the follow
initialized, if no operating command is accepted or the
operations to unlock it:
stop command is executed, then the drive in stop
Press the ENTER and hold , then press the ∨ three
status.
times
2.Running status: The drive enters running status after
Note:
it receives the operating command.
Whatever setting is in b4.00, after the VFD power on,
3.Motor parameters auto-tuning status: If there is an
the operation board is in unlock status.
operating command after b0.11 is set to 1 or 2, the
drive enters motor parameters auto-tuning status, and
then enters stopping status after auto-tuning process
5.2 Operation mode of VFD
finishes.
In the follow-up sections, you may encounter the terms
describing the control, running and status of drive 5.2.3 Control mode and operation mode of Kinco

many times. Please read this section carefully. It will VFD

help you to understand and use the functions discussed Control mode
in the follow chapters correctly. CV100 VFD has three control methods, it is set by
A0.01:
5.2.1 Control mode of VFD
0. Vector control without PG: it is vector control
It defines the physical channels by which drive without speed sensor, need not to install the PG, at the
receives operating commands like START, STOP, JOG same time it has very high control performance, it can
and others, there are two channels: control the speed and torque of motor accurately. It has
1 Operation panel control: The drive is controlled by the characteristics like low frequency with high torque
RUN, STOP and M keys on the operation panel; and steady speed with high accuracy. It is often used in
2 Terminal control: The drive is controlled by the applications that the V/F control mode can not
terminals Xi 、 Xj and COM (2-wire mode), or by stisfy, but requires high robustness.
terminal Xk (3-wire mode); 1. Reserved

20
2. V/F control: It is used in the applications that do not frequency to stacking and adjusting (except Jog mode),
require very high performance, such as one VFD the descriptions of each mode are as follows:
controls multiple motors. 1) JOG operation:
Operation mode When the drive is in STOP state, and receives the JOG
Speed control: Control the speed of motor accurately, command (for example the M key on the panel is
related function codes in group A5 should be set. pressed), then the drive jogs at the JOG frequency
Torque control: Control the torque of motor accurately, (refer to A2.04 and A2.05)
related function codes in group A5 should be set. 2) Close-loop process operation:
If the close-loop operating function is enabled
5.2.4 The channels to set the VFD frequency
(C1.00=1), the drive will select the close-loop
CV100 supports 5 kinds of operating modes in speed operation mode, that is, it will perform closed-loop
control mode which can be sequenced according to the regulation according to the given and feedback value
priority: Jog>Close loop process operation>PLC (refere to Group C1). This mode can be deactived by
operation>Multiple speed operation>simple operation. the multi-function terminals, and switch to the lower
It is shown as follows: priority mode.
3) PLC operation
This function is customized, description is omitted.
4) Multi-step (MS) speed operation:
Select Multiple frequency 1~15(C0.00~C0.14)to
start Mulitple speed operation by the ON/OFF
combinations of the multi-function terminals (No.27,
28, 29 and 30 function). If all the terminals are
“OFF”,it is in simple operation.

Note:
About the frequency setting channel under speed mode,
please refer to the chapter 6 for detail information

5.3 Power on the Drive for the first


time

5.3.1 Checking before power on

Please wire the drive correctly according to chapter 4

5.3.2 Operations when start up the first time

After checking the wiring and AC supply, switch on


Fig 5-4 Operating mode in speed control mode the circuit breaker of the drive to supply AC power to
The three operating modes provide three basic it. The drive’s panel will display “8.8.8.8.” at first, and
frequency sourse.Two of them can use the auxiliary then the contactor closes. If the LED displays the

21
setting frequency,that is to say the initialization of the
drive is completed.
Procedures of first-time start-up are as follows:

Start

Properly wiring

N
Check wiring

Y
N Check input
voltage

Y
Power on

Display N
.
8.8.8.8?

Y
N
Contactor closed?

N
Display frequency?

Y Failed

Successful
Cut off the power

Check the reason

Fig.5-5 Procedures of first-time start-up

22
A0.02 Main reference
0~4【0】
frequency selector
Chapter 6 Parameter Introductions 0: Digital setting.
The initial reference frequency is the value of A0.03.
Note :
It can be adjusted via ▲ and ▼ key,or via terminal
XX.XX YYYYYYYY N1~N2【D】
UP/DOWN.
Parameter Parameter Default
1: Set via AI1 terminal.
No. Name Range value
The reference frequency is set by analog input via
terminal AI1 and the voltage range is -10V~10V. The
6.1 Group A0 relationship between voltage and reference frequency
can be set in Group A3.
00000~65535
A0.00 User password 2: Set via AI2 terminal.
【00000】
This function is used to prevent the irrelevant personnel The reference frequency is set by analog input via
from inquiring and changing the parameter as to protect terminal AI2 and the voltage range is -10V~10V. The
the safety of the inverter parameters. relationship between voltage and reference frequency
0000: No password protection. can be set in Group A3.
Set password: 3:Set via potentiometer.
Input four digits as user password, and press ENTER
key for confirmation. After 5 minutes without any other Range: Lower limit of
A0.03 Set the operating
operation,the password will be effective automatically. frequency ~upper limit
frequency in digital mode
Change password: of frequency【50.00Hz】

Press MENU key to enter the password verification When the reference frequency is set in digital

status. Input correct password and it enters parameter mode(A0.02 = 0), this setting of this parameter is the

editing status. Select A0.00 (parameter A0.00 displayed drive’s initial frequency value.
as 00000).Input new password and press ENTER key for
confirmation. After 5 minutes without any other A0.04 Methods of inputting
0~2【1】
operation, the password will be effective automatically. operating commands
CV100 has two control modes.
Note:
0: Panel control: Input operating commands via panel
Please safekeeping the user password.
Start and stop the drive by pressing RUN, STOP and M
on the panel.
A0.01 Control mode 0~2【0】 1: Terminal control: Input operating commands via
0: Vector control without PG (Open loop vector control) terminals.
It is a vector control mode without speed sensor Use external terminals Xi(Set function code
feedback.It is applicable to most applications. A6.00~A6.04 to 1 and 2),M Forward, M Reverse to start
1: Reserved and stop the drive.
2:V/F control 2:Modbus communication.
It is used to control voltage/frequence constantly.It is
applicable to most application, especially for the A0.05 Set running direction 0~1【0】
application of one drive driving multiple motors.
This function is active in panel control mode and serial

23
port control mode, and inactive in terminal control Max output voltage is the highest permissible output
mode. voltage of the drive, as shown in Fig. 6-1 as Vmax
0: Forward Upper limit of frequency is the highest permissible
1: Reverse operating frequency of the user setting, as shown in Fig.
6-1 as FH.
0.0~6000.0s Lower limit of frequency is the lowest permissible
A0.06 Acc time 1
【6.0s】 operating frequency of the user setting,as shown in

0.0~6000.0s Fig.6-1 as FL.


A0.07 Dec time 1 Basic operating frequency is the Min. frequency when
【6.0s】
the drive outputs the max voltage in V/F mode, as shown
Default value of Acc/Dec time 1:
in Fig. 6-1 as Fb
2KW or below:6.0S
Output
30KW~45KW:20.0S Voltage

45KW or above:30.0S Vmax


Acc time is the time taken for the motor to accelerate
from 0Hz to the maximum frequency (as set in A0.08).
Dec time is the time taken for the motor to decelerate
from maximum frequency (A0.08) to 0Hz.
FL FH Fb Fmax Output frequency
CV100 series VFD has defined 4 kinds of Acc/Dec
time.(Here only Acc/Dec time 1 is defined, and Acc/Dec Fig.6-1 Characteristic parameters
time 2~4 will be defined in A4.01~A4.06),and the Note:
Acc/Dec time 1~4 can be selected via the combination 1 . Please set Fmax, FH and FL carefully according to
of multiple function input terminals,please refer to motor
A6.00~A6.04. Parameters and operating states.
2 . FH and FL is invalid for JOG mode and auto tuning
Max{50.00,A0.11 upper mode.
A0.08 Max. output
limit of frequency}~300.00Hz 3.Besides the upper limit of frequency and lower limit
frequency
【50.00】
of frequency,the drive is limited by the setting value of
A0.09 Max. output 0~480V【VFD’s rating frequency of starting,starting frequency of DC braking
voltage values】 and hopping frequency.
A0.10 Upper limit 4.The Max. output frequency,upper limit frequency and
A0.12~A0.09【50.00】
of frequency lower limit frequency is as shown in Fig.6-1.
A0.11 Lower limit 5.The upper/lower limit of frequency are used to limit
0.00~A0.11【00.00】
of frequency the actual output frequency.If the preset frequency is
A0.12 Basic 0.00~Max. output frequency higher than upper limit of frequency,then it will run in
operating frequency A0.08【50.00】 upper limit of frequency.If the preset frequency is lower
Max output frequency is the highest permissible output than the lower limit of frequency,then it will run in lower
frequency of the drive, as shown in Fig. 6-1 as Fmax; limit of frequency.If the preset frequency is lower than
starting frequency,then it will run in 0Hz.

24
A0.13 Torque boost of motor 1 0.0~30.0%【0.0%】 0.00 ~ 60.00Hz
A1.01 Starting frequency
In order to compensate the torque drop at low frequency, 【0.00Hz】
the drive can boost the voltage so as to boost the torque. A1.02 Holding time of starting
0.00~10.00s【0.00s】
If A0.13 is set to 0, auto torque boost is enabled and if frequency
A0.13 is set non-zero, manual torque boost is enabled, Starting frequency is the initial frequency when the drive
as shown in Fig. 6-2. starts, as shown in Fig. 6-3 as FS.Holding time of
Output
voltage starting frequency is the time during which the drive
Vmax operates at the starting frequency, as shown in Fig. 6-3
as t1

Vb

Fz Fb Output frequency

Vb:Manual torque boost Vmax:Max. output voltage


Fz:Cut-off frequency for torque boost Fb:Basic operating frequency

Fig.6-2 Torque boost(shadow area is the boostedvalue)

Note:
1. Wrong parameter setting can cause overheat or
over-current protection of the motor. Fig.6-3 Starting frequency and starting time
2. Refer to b1.07 for definition of Fz.

Note:
6.2 Group A1
Starting frequency is not restricted by the lower limit of
frequency.
A1.00 Starting mode 0、1、2【0】
A1.03 DC injection braking
0. Start from the starting frequency 0.0~100.0%【0.0%】
current at start
Start at the preset starting frequency (A1.01) within the
A1.04 DC injection braking
holding time of starting frequency (A1.02). 0.00~30.00s【0.00s】
time at start
1.Brake first and then start
Brake first(refer to A1.03 and A1.04), and then start in A1.03 and A1.04 are only active when A1.00 is set to 1
(starting mode 1 is selected), as shown in Fig. 6-4.
mode 0.
2.Speed tracking DC injection braking current at start is a percentage
value of drive’s rated current. There is no DC injection
braking when the braking time is 0.0s.
Notes:
Starting mode 1 is suitable for starting the motor that is
running forward or reverse with small inertia load when
the drive stops. For the motor with big inertial load, it is
not recommended to use starting mode 1.

25
Output
o injection braking initial frequency(A1.06) to the time
Frequency
when the DC injection braking is applied.
The drive has no output during the waiting time. By
setting waiting time, the current overshoot in the initial
stage of braking can be reduced when the drive drives a
Time
high power motor.
DC Braking
Output energy DC injection braking current at stop is a percentage of
Voltage
(effective drive’s rated current. There is no DC injection braking
Value) Time when the braking time is 0.0s.

Output
DC injection Freqency
Braking time
Runing
Initial Frequency
command of braking

Waiting time
Fig.6-4 Starting mode 1 Output
Voltage
(RMS value) Braking
energy

A1.05 Stopping mode 0、1、2【0】


Braking time
0: Dec-to-stop
Operating
After receiving the stopping command, the drive reduces command

its output frequency according to the Dec time, and stops


when the frequency decreases to 0. Fig.6-5 Dec-to-stop + DC injection braking
1: Coast-to-stop
After receiving the stopping command, the drive stops Note:
outputting power immediately and the motor stops under DC injection braking current at stop(A1.08) is a
the effects of mechanical inertia. percentage
2: Dec-to-stop+DC injection braking value of drive’s rated current.
After receiving the STOP command, the drive reduces
its output frequency according to the Dec time and starts
A1.10 Restart after power
DC injection braking when its output frequency reaches 0、1【0】
failure
the initial frequency of braking process.
A1.11 Delay time for restart
Refer to the introductions of A1.06~A1.09 for the 0.0~10.0s【0.0s】
after power failure
functions of DC injection braking.
A1.10 and A1.11 decide whether the drive starts
A1.06 DC injection braking 0.00~60.00Hz
initial frequency at stop automatically and the delay time for restart when the
【0.00Hz】
A1.07 Injection braking drive is switched off and then switched on in different
0.00~10.00s【0.00s】
waiting time at stop control modes.
A1.08 DC injection braking If A1.10 is set to 0, the drive will not run automatically
0.0~100.0%【0.0%】
current at stop after restarted.
A1.09 DC injection braking
0.00~30.00s【0.00s】 If A1.10 is set to 1, when the drive is powered on after
time at stop
power failure, it will wait certain time defined by A1.11
DC injection braking waiting time at stop: The duration
from the time when operating frequency reaches the DC and then start automatically depending on the current

26
control mode and the drive’s status before power failure. in Fig. 6-6 as t1.
See Table 6-1. Output
frequency
Table 6-1 Restarting conditions
3-wire
Status 2-wire
Settin Serial modes Time
before Panel modes 1
g of port 1 and
power and 2
A1.10 2 t1
off
Without control command With
Fig.6-6 Delay time from reverse running to forward
Stop 0 0 0 0 0
0 running or from forward running to reverse running
Run 0 0 0 0 0
Stop 0 0 0 0 1
1 A1.14 Switch mode of run
Run 1 1 1 0 1 0、1【0】
reverse/forward
Table 6-1 shows the drive’s action under different
0:Switch when pass 0Hz
conditions. “0” means the drive enter ready status and
1:Switch when pass starting frequency
“1” means the drive start operation automatically.
Note:
A1.15 Detecting frequency of
1.When using the panel or serial port or 3-wire mode 1 0.00~150.00Hz
stop
and 2 to start or stop the drive, the command signal is in
A1.16 Action voltage of
pulse mode and there is no operating command when the 650~750【700】
braking unit
drive is switched on.
A1.17 Dynamic braking 0、1【0】
2.If there is a stopping command, the drive will stop
0:Dynamic braking is disabled
first. 3.When the function of restart after power failure is
enabled, the drive will start on the fly after power on if it 1:Dynamic braking is enabled

is not switched off totally (that is, the motor still runs Note:
and drive’s LED displays “P.OFF”). It will start in the This parameter must be set correctly according to the
starting mode defined in A1.00 after power on if it is actual
switched off totally (LED turns off). conditions, otherwise the control performance may be
affected.

A1.12 Anti-reverse running


0、1【0】
function A1.18 Ratio of working time

0: Disabled of braking unit to drive’s total 0.0~100.0%【80.0%】

1: Enabled working time

Note: This function is effective for the drive with built-in

This function is effective in all control modes. braking


resistor.

A1.13 Delay time of run reverse/ Note:


0~3600s【0.0s】 Resistance and power of the braking resistor must be
forward
taken into consideration when setting this parameters.
The delay time is the transition time at zero frequency
when the drive switching its running direction as shown

27
6.3 Group A2 A2.02 is used to define the change rate of reference
frequency that is changed by terminal UP/DN or ▲/▼
A2.00 Auxiliary
key.
reference 0~5【0】
A2.03 UP/DN regulating
frequency selector 0~11H【00】
control
0: No auxiliary reference frequency
Preset frequency only determined by main reference
frequency, auxiliary reference frequency is 0Hz by
default.
1: Set by AI1 terminal
The auxiliary frequency is set by AI1 terminal.
2: Set by AI2 terminal
The auxiliary frequency is set by AI2 terminal.
3: Reserved
4: Set by DI terminal(PULSE)
5: Set by output frequency of process PID.

A2.01 Main and auxiliary


Note:
reference frequency 0~3【0】
In this manual,there are many .Their
calculation
meanings are as following:
0:”+” A means the thousand’s place of LED display.
Preset frequency=Main+auxiliary. B means the hundred’s place of LED display.
1:”-” C means the ten’s place of LED display.
Preset frequency=Main-auxiliary. D means the unit’s place of LED display.
2:MAX
Set the max. absolute value between Main and auxiliary A2.04 Jog operating 0.01 ~ 50.00Hz
reference frequency as preset frequency. frequency 【5.00Hz】
Set Main reference frequency as preset frequency when
A2.04 is used to set the jog operating frequency.
the polarity of auxiliary frequency is opposite to main
Note:
frequency.
Jog operation can be controlled by panel(M key),
3:MIN
terminals.
Set the min. absolute value between Main and auxiliary
reference frequency as preset frequency.
A2.05 Interval of Jog operation 0.0~100.0s【0.0】
Set preset frequency as 0Hz when the polarity of
Interval of Jog operation (A2.05) is the interval from the
auxiliary frequency is opposite to main frequency.
time when the last Jog operation command is ended to
the time when the next Jog operation command is
A2.02 UP/DN rate 0.01~99.99Hz/s【1.00】
executed.
The jog command sent during the interval will not be
executed. If this command exists until the end of the

28
interval, it will be executed. 【100.0%】
A3.06 Actual value
0.0% ~ 100.0%
A2.06 Skip frequency 1 0.00~300.0Hz【0.00Hz】 corresponding to the Max
【100.0%】
A2.07 Range of skip reference of curve 2
0.00~30.00Hz【0.00Hz】
frequency 1 A3.07 Min reference of curve 2 0.0%~A3. 05【0.0%】
A2.08 Skip frequency 2 0.00~300.0Hz【0.00Hz】 A3.08 Actual value
0.0% ~ 100.0 %
A2.09 Range of skip corresponding to the Min
0.00~30.00Hz【0.00Hz】 【0.0%】
frequency 2 reference of curve 2
A2.10 Skip frequency 3 0.00~300.0Hz【0.00Hz】 A3.11 ~ 110.0%
A3.09 Max reference of curve 3
A2.11 Range of skip 【100.0%】
0.00~30.00Hz【0.00Hz】
frequency 3 A3.10 Actual value
0.0% ~ 100.0%
A2.06 ~ A2.11 define the output frequency that will corresponding to the Max
【100.0%】
cause reference of curve 3
resonant with the load, which should be avoided. A3.11 Min reference of curve 3 0.0%~A3. 09【0.0%】
Therefore, the drive will skip the above frequency as A3.12 Actual value
0.0% ~ 100.0 %
shown in Fig. 6-7. Up to 3 skip frequencies can be set. corresponding to the Min
【0.0%】
Adjusted preset
frequency
reference of curve 3

Skip
A3.15 ~ 110.0%
frequency 3 Skip range 3 A3.13 Max reference of curve 4
【100.0%】
Skip Skip range 2
Frequency 2 A3.14 Actual value
0.0% ~ 100.0%
Skip Skip range 1 Preset corresponding to the Max
Frequency 1 frequency 【100.0%】
reference of curve 4

Fig.6-7 Skip frequency and skip range A3.15 Reference of inflection A3.17 ~ A3.13
point 2 of curve 4 【100.0%】
6.4 Group A3 A3.16 Actual value

A3.00 Reference frequency corresponding to the Min 0.0% ~ 100.0%


0000~3333H【0000】
curve selection reference of inflection point 2 【100.0%】

A3.03 ~ 110.0% of curve 4


A3.01 Max reference of curve 1
【100.0%】 A3.17 Reference of inflection A3.19 ~ A3.15
point 1 of curve 4 【0.0%】
A3.02 Actual value
0.0% ~ 100.0%
corresponding to the Max A3.18 Actual value
【100.0%】 corresponding to the Min 0.0% ~ 100.0%
reference of curve 1
A3.03 Min reference of curve 1 0.0%~A3.01【0.0%】 reference of inflection point 1 【0.0%】
of curve 4
A3.04 Actual value
0.0% ~ 100.0%
corresponding to the Min A3.19 Min reference of curve 4 0.0%~A3. 17【0.0%】
【0.0%】
reference of curve 1 A3.20 Actual value 0.0% ~ 100.0%

A3.05 Max reference of curve 2 A3.07 ~ 110.0% corresponding to the Min 【0.0%】

29
reference of curve 4
A B C D

Reference frequency signal is filtered and amplified, and AI1 Curve selection
0:Curve 1 1:Curve 2
then its relationship with the preset frequency is 2:Curve 3 3:Curve 4

determined by Curve 1,2,3 or 4. Curve 1 is defined by AI2 Curve selection


0:Curve 1 1:Curve 2
A3.01 ~ A3.04.Curve 2 is defined by A3.05 ~ 2:Curve 3 3:Curve 4

A3.08.Curve 3 is defined by A3.09 ~ A3.12.Curve 4 is Reserved

defined by A3.13 ~ A3.20. Take preset frequency as


example, positive and negative characteristics are shown Reserved

in Fig.6-8.In Fig.6-8,the inflection points are set the


same as the corresponding relationship of Min. or Max Fig.6-9 Frequency curve selection

reference. For example, the requirements are:

Preset frequency Preset frequency


1.Use the analog signal(AI1) input to set the
reference frequency;
Fmax 2.Input signal: 0V~10V;
Fmax
3 . 0.5V input signal corresponds to 50Hz reference
frequency, and 4V input signal corresponds to 10Hz
Fmin Fmin
reference frequency, 6V input signal corresponds to
40Hz reference frequency, 10V input signal corresponds
Pmin Pmax P Pmin Pmax P
Amin Amax A Amin Amax A to 5Hz reference frequency.
(1) Positive (2) Negative
P:Pulse terminal input A:AI1~AI3 terminal input
According to the above requirements, the parameter
Pmin、Amin:Min. reference Pmax、Amax:Max. reference settings are:
Fmin:Freq. coreesponding Fmax:Freq. coreesponding
To Min. frequency To Max. frequency 1 ) A0.02 = 1, select AI1 input to set the reference
frequency.
Fig.6-8 Freq. coreesponding to Min. frequency
3)A3.00=0003, select curve 4.
Analog input value(A) is a percentage without unit, and
4)A0.08=50.0kHz,set the Max output frequency to 50
100% corresponds to 10V or 20mA. Pulse frequency (P)
Hz.
is also a percentage without unit, and 100% corresponds
to the Max pulse frequency defined by A6.10. 5)A3.13=10÷10×100%=100.0%, set the percentage

The time constant of the filter used by the reference that the Max reference (10V) corresponds to 10V

selector is defined in Group A6. 6)A3.14=5.00Hz÷A0.08*100%, set the percentage that

A3.00 is used to select the analog input curve and pulse the max input signal corresponds to the the reference
input curve,as show in Fig.6-9. frequency
7)A3.15=6÷10×100%=60.0%,the percentage that
inflection2 reference(6V) of curve 4 corresponds to the
10V.
8)A3.16=40.00Hz÷A0.08*100%,set the percentage
that inflection2 reference (6V) corresponds to the
reference frequency.

30
9)A3.17=4÷10×100%=40.0%,the percentage that Note:
inflection1 refererece (4V) of curve 4 corresponds to the 1.If user set the reference of inflection point 2 of curve
10V 4the same as Max. reference(A3.15=A3.13),then the
10)A3.18=10.00Hz÷A0.08*100%,set the percentage drive will force A3.16=A3.14,means the setting of
that inflection1 reference (4V) of curve 4 corresponds inflection point 2 is invalid.If reference of inflection
to the reference frequency. point 2 is the same as reference of inflection point
11)A3.19=0.5÷10×100%=5.0%,set the percentage 1(A3.17 = A3.15),then the drive will force
that the Minimum reference(0.5V) of curve 4 A3.18=A3.16,means the setting of inflection point is
corresponds to the 10V invalid.If reference of inflection point 1 is the same as
12)A3.20=50.00Hz÷A0.08*100%,set the percentage Min. reference(A3.19 =A3.17),then the drive will force
that the minimum reference(0.5V) corresponds to the A3.20=A3.18,means the setting of Min. reference is
reference frequency. invalid.The setting of curve 1 is in the same manner.
Output frequency(%) 2.The range of the actual value that corresponds to the
A3.20=100%
. reference of curve 1,2,3 and 4 is 0.0 % ~ 100.0
A3.16=80% % ,corresponds to torque is 0.0 % ~ 300.0 % ,and
corresponds to frequency,its range is 0.0%~100.0%。
A3.18=20%
A3.14=10% Pulse signal input
5% 40% 60% 100%
A3.19 A3.17 A3.15 A3.13
6.5 Group A4
Fig.6-10 Pulse signal input 1
A4.00 Acc/Dec mode 0~1【0】
If there is no setting of inflection point in the 3rd
0:Linear Acc/Dec mode
requirement,means to change the requirement as 0.5V
Output frequency increases or decreases according to a
input signal corresponds to 50Hz reference frequency,
constant rate, as shown in Fig. 6-12.
and 10V input signal corresponds to 5Hz reference
Frequency
frequency.Then we can set the inflection point 1 the
same as Min. reference(A3.17=A3.19,A3.18=A3.20) Fmax

and inflection point 2 the same as Max. reference(A3.13


Time
=A3.15,A3.14=A3.16).As shown in Fig.6-11. t1 t 2

Fig.6-12 Linear Acc/Dec


1:S curve Acc/Dec mode.
The output frequency accelerates and decelerates
according to S curve,as shown in Fig.6-13.

Fig.6-11 Pulse signal input 2

31
A4.07+A4.08≤90%, A4.09+ A4.10≤90%,as shown in
Fig.6-14.

Fig.6-13 S curve Acc/Dec


S curve Acc/Dec mode can smooth acceleration and
deceleration,suitable for application like lift,conveyer Fig.6-14 Acc/Dec starting time and ending time

belt.
A4.01 Acc time 2 0.1~6000.0s【6.0s】 A4.11 Quick start-stop selctor 0~3【0】

A4.02 Dec time 2 0.1~6000.0s【6.0s】 0:Disable

A4.03 Acc time 3 0.1~6000.0s【6.0s】 1:Quick start,normal stop


2:Normal start,quick stop
A4.04 Dec time 3 0.1~6000.0s【6.0s】
3:Quick start,quick stop
A4.05 Acc time 4 0.1~6000.0s【6.0s】
A4.12 Start ACR-P 0.1~200.0【20.0】
A4.06 Dec time 4 0.1~6000.0s【6.0s】
A4.13 Start ACR-I 0.000~10.000s【0.200s】
Acc time is the time taken for the motor to accelerate
from 0Hz to the maximum frequency (as set in A0.08), A4.14 Start AVR-P 0.1~200.0【20.0】
see t2 in Fig.6-12. Dec time is the time taken for the A4.15 Start AVR-I 0.000~10.000s【0.200s】
motor to decelerate from maximum frequency (A0.08) A4.16 Stop ACR-P 0.1~200.0【20.0】
to 0Hz, see t2 in Fig.6-12.
A4.17 Stop ACR-I 0.000~10.000s【0.200s】
CV100 define three kinds of Acc/Dec time,and the
A4.18 Stop AVR-P 0.1~200.0【20.0】
drive’s Acc/Dec time 1~4 can be selected by different
A4.19 Stop AVR-I 0.000~10.000s【0.200s】
combinations of control terminals, refer to the
introductions of A6.00~A6.04 for the definitions of
6.6 Group A5
terminals used to select Acc/Dec time.
A4.07 S curve acceleration 10.0%~50.0% A5.00:Reserved
starting time (Acc time)【20.0%】 A5.01 ASR1-P 0.1~200.0【20.0】

A4.08 S curve acceleration 10.0%~70.0% A5.02 ASR1-I 0.000~10.000s【0.200s】


ending time (Acc time)【20.0%】 A5.03 ASR1 output filter 0~8【0】
A4.09 S curve deceleration 10.0%~50.0% A5.04 ASR2-P 0.1~200.0【20】
starting time (Dec time)【20.0%】
A5.05 ASR2-I 0.000~10.000s【0.200s】
A4.10 S curve deceleration 10.0%~70.0%
A5.06 ASR2 output filter 0~8【0】
ending time (Dec time)【20.0%】
A5.07 ASR1/2 switching
A4.07~A4.10 is only valid when A4.00 is set as 1 (S 0~100.0%【10.0Hz】
frequency
curve Acc/Dec mode),and it must make sure

32
The parameters A5.00~A5.07 are only valid for vector When decreasing integral time I,it can speed up the
control mode. system’s dynamic response.But if I is too small,the
Under vector control mode,it can change the speed sysem will become overshoot and easily oscillating.
response character of vector control through adjusting Generally, to adjust proportional gain P firstly.The value
the proportional gain P and integral time I for speed of P can be increased as big as possible if the system
regulator. don’t become oscillating.Then adjust integral time to
1.The structure of speed regulator (ASR) is shown in make the system with fast response but small
Fig.6-15.In the figure, KP is proportional gain P. TI is overshoot.The speed step response curve of speed,when
integral time I. set a better value to P and I parameters,is shown in
Fig.6-17.(The speed response curve can be observed by
analog output terminal AO1,please refer to Group A6)

A6.10, A6.11
Speed
Fig.6-15 Speed regulator Command

When integral time is set to 0 (A5.02 = 0 , A5.05 =


0),then the integral is invalid and the speed loop is just a
proportional regulator.
Fig.6-17 The step response with better dynamic
2.Tuning of proportional gain P and integral time I for
performance
speed regulator(ASR).
Note:
Proportional gain
is bigger If the PI parameters are set incorrectly,it will cause
Speed
command
Proportional gain over-voltage fault when the system is accelerated to high
is smaller
speed quickly(If the system doesn’t connect external
braking resistor or braking unit),that is because the
energy return under the system’s regenerative braking
(a) when the system is dropping after speed overshoot.It can

Integral time is smaller be avoided by adjusting PI parameters


Speed
command
Integral time is bigger
3 . The PI parameters’ adjustment for speed
regulator(ASR) in the high/low speed running occasion
To set the switching frequency of ASR (A5.07) if the
system requires fast response in high and low speed
(b)
running with load.Generally when the system is running
at a low frequency,user can increase proportional gain P
Fig.6-16 The relationship between step response and PI
and decrease integral time I if user wants to enhance the
parameters of speed regulator(ASR)
dynamic response.The sequence for adjusting the
When increasing proportional gain P,it can speed up the
parameters of speed regulator is as following:
system’s dynamic response.But if P is too big,the system
1)Select a suitable switching frequency( A5.07).
will become oscillating.
2 ) Adjust the proportional gain (A5.01) and integral
time(A5.02) when running at high speed,ensure the

33
system doesn’t become oscillating and the dynamic 6.7 Group A6
response is good.
A6.00 Multi-function terminal X1 0~41【0】
3 ) Adjust the proportional gain (A5.04) and integral
A6.01 Multi-function terminal X2 0~41【0】
time(A5.05) when running at low speed, ensure the
system doesn’t become oscillating and the dynamic A6.02 Multi-function terminal X3 0~41【0】
response is good. A6.03 Multi-function terminal X4 0~41【0】
4.Get the reference torque current through a delay filter A6.04 Multi-function terminal X5 0~41【0】
for the output of speed regulator.A5.03 and A5.06 are A6.05 Reserved
the time constant of output filter for ASR1 and ASR2. A6.06 Reserved
A6.07: Reserved
A5.08~A5.09 Reserved The functions of multi-function input terminal X1~X5
Reserved function are extensive. You can select functions of X1~X5
according to your application by setting A6.00~A6.04.
A5.10 Driving torque limit 0.0%~+300.0%【180.0%】 Refer to Table 6-2.
A5.11 Braking torque limit 0.0%~+300.0%【180.0%】 Table 6-2 Multi-function selection
Driving torque limit is the torque limit in motoring Setting Function Setting Function
condition. 0 No function 1 Forward
Braking torque limit is the torque limit in Forward jog
2 Reverse 3
generating condition operation
In setting value, 100% is corresponding to drive’s Reverse jog 3-wire operation
4 5
rated torque. operation control
External RESET External fault
6 7
A5.12 ~A5.16 Reserved signal input signal input
Reserved function External interrupt Drive operation
8 9
signal input prohibit
A5.17 ACR-P 1~5000【1000】 DC injection
External stop
A5.18 ACR-I 0.5~100.0mS【8.0ms】 10 11 braking
command
command
Frequency ramp
A5.17 and A5.18 are the parameters for PI regulator of 12 Coast to stop 13
up (UP)
current loop.Increasing P or decreasing I of current loop
Frequency ramp Switch to panel
can speed up the dynamic response of torque.Decreasing 14 15
down (DN) control
P or increasing I can enhance the system’s stability.
Switch to terminal
Note: 16 17 Reserved
control
For most applications, there is no need to adjust the PI
Main reference
parameters of current loop, so the users are suggested to Main reference
18 19 frequency via
change these parameters carefully. frequency via AI1
AI2
20 Reserved 21 Main reference

34
Setting Function Setting Function Acc/Dec time are defined by A2.04~A2.05,A4.05~A
frequency via DI 4.06.
Auxiliary 6: External RESET signal input.

22 reference 23 Reserved The drive can be reset via this terminal when the drive
frequency invalid has a fault. The function of this terminal is the same with

24 Reserved 25 Reserved that of RST on the panel.


Preset frequency 7: External fault signal input.
26 Reserved 27
1 If the setting is 7, the fault signal of external equipment

Preset frequency can be input via the terminal, which is convenient for the
28 Preset frequency 2 29
3 drive to monitor the external equipment. Once the drive

30 Preset frequency 4 31 Acc/Dec time 1 receives the fault signal, it will display “E015”.

Multi-closed 8. External interrupt signal input


32 Acc/Dec time 2 33 If the setting is 8, the terminal is used to cut off the
loop reference 1
Multi-closed loop Multi-closed output and the drive operates at zero frequency when the
34 35 terminal is enabled. If the terminal is disabled, the drive
reference 2 loop reference 3
Multi-closed loop will start on automatically and continue the operation.
36 37 Forward prohibit 9: Drive operation prohibits.
reference 4
If terminal is enabled, the drive that is operating will
Acc/Dec
38 Reverse prohibit 39 coast to stop and is prohibited to restart. This function is
prohibit
mainly used in application with requirements of safety
Switch speed
Process closed protection.
40 41 control and
loop prohibit 10: External stop command.
torque control
This stopping command is active in all control
Main frequency
modes.When terminal 35 is enabled; the drive will stop
switch to digital
42 43 PLC pause in the mode defined in A1.05.
setting
11: DC injection braking command.
If the setting is 11, the terminal can be used to perform
PLC stop
44 PLC prohibit 45 DC injection braking to the motor that is running so as to
memory clear
realize the emergent stop and accurate location of the
46 Swing input 47 Swing reset
motor. Initial braking frequency, braking delay time and
48~49 Reserved 50 Timer 1 start
braking current are defined by A1.06~A1.08. Braking
51 Timer 2 start 53 Counter input
time is the greater value between A1.09 and the effective
54 Counter clear
continuous time defined by this control terminal.
Introductions to functions listed in Table 6-2:
12: Coast to stop.
1: Forward. 2: Reverse. 5: 3-wire operation control
If the setting is 12, the function of the terminal is the
These are used for terminal control mode.More details
same with that defined by A1.05. It is convenient for
please refer to descriptions of A6.09.
remote control.
3~4: Forward/reverse jog operation.
13~14: Frequency ramp UP/DN.
They are used to jog control of terminal control mo
If the setting is 13~14, the terminal can be used to
de.The jog operation frequency,jog interval and jog
increase or decrease frequency. Its function is the same

35
with ▲ and ▼ keys on the panel, which enables remote
K4 K3 K2 K1 Frequency setting
control. This terminal is enabled when A0.02=0 or
Common operating
A0.04=1. Increase or decrease rate is determined by OFF OFF OFF OFF
frequency
A2.02 and A2.03.
OFF OFF OFF ON Preset frequency1
15: Switch to panel control.
OFF OFF ON OFF Preset frequency 2
It is used to set the control mode as panel control.
OFF OFF ON ON Preset frequency 3
16: Switch to terminal control
OFF ON OFF OFF Preset frequency 4
It is used to set the control mode as terminal control
OFF ON OFF ON Preset frequency 5
17: Reserved.
OFF ON ON OFF Preset frequency 6
18: Main reference frequency via AI1
OFF ON ON ON Preset frequency 7
19: Main reference frequency via AI2
ON OFF OFF OFF Preset frequency 8
20: Reseved
21: Main reference frequency via DI ON OFF OFF ON Preset frequency 9

These functions are used to set the main reference ON OFF ON OFF Preset frequency 10

frequency controlled by AI1,AI2 or DI. ON OFF ON ON Preset frequency 11

22: Auxiliary reference frequency invalid. ON ON OFF OFF Preset frequency 12


Auxiliary reference frequency is invalid when the ON ON OFF ON Preset frequency 13
terminal activate ON ON ON OFF Preset frequency 14
23~26: Reserved. ON ON ON ON Preset frequency 15
27~30: Preset frequency selection. The frequency references will be used in multiple speed
Up to 15 speed references can be set through different operation. Following is an example: Definitions of
ON/OFF combinations of these terminals K4, K3, K2 terminals X1, X2, X3and X4 as following:
and K1. After setting A6.00 to 27, A6.01 to 28 and A6.03 to 30,
Table 6-3 On/Off combinations of terminals terminals X1~X4 can be used in multiple speed
operation, as shown in Fig. 6-18.
Speed 15
Output frequency

Common
Speed 1
Operating
frequency
Common
command Time

K
K2
K3
K4

Fig.6-18 Multi-step speed operation

31~32:Acc/Dec time selection


Table 6-4 Acc/Dec time selection

36
Terminal 2 Terminal1 Acc/Dec time selection When this signal is valid,it will clear swing status
OFF OFF Acc time 1/Dec time 1 information.When this signal is invalid,the drive will
OFF ON Acc time 2/Dec time 2 start swing function again.

ON OFF Acc time 3/Dec time 3


ON ON Acc time 4/Dec time 4 A6.08 Terminal filter 0~500ms【10ms】

Through the On/Off combinations of terminal 1 and 2, A6.08 is used to set the time of filter for input
Acc/Dec time 1~4 can be selected. terminals.When the state of input terminals change,it
33~36: Reserved. must keep the state for the filter time,or the new state

37: Forward prohibit. won’t be valid.

The drive will coast to stop if the terminal activate when A6.09 Terminal control mode
0~3【0】
running forward.If the terminal activate before the drive selection
run forward,the drive will run in 0Hz. This parameter defines four operating modes controlled
38: Reverse prohibits. by external terminals.
The drive will coast to stop if the terminal activate when 0: 2-wire operating mode 1
running reverse.If the terminal activate before the drive
run reverse,the drive will run in 0Hz.
39: Acc/Dec prohibit
Keep the mortor from the controlling of external signal
(except the STOP command), so the the motor can runs
at the current speed.
Fig.6-19 2-wire operating mode 1
40:Process closed loop prohibit
1:2-wire operating mode 2
Forbid process closed loop control.
41:Reseverd
42:Main frequency switch to digital setting
Switch the main frequency selector to digital setting.
43:PLC pause
Pause PLC function control.
44:PLC prohibit Fig.6-20 2-wire operating mode 2
Forbid PLC function running. 2:3-wire operating mode 1
45:PLC stop memory clear
CV100
Clear the memory which store the steps before PLC
function stop.
46:Swing input
When this signal is valid,the drive will start swing
operation.This function is only valid when the swing
operation mode is set as 1.
Fig.6-21 3-wire operating mode 1
47:Swing reset
Where:
SB1: Stop button
SB2: Run forward button

37
SB3: Run reverse button If X1~X4 are required to be positive logic, and X5 is
Terminal Xi is the multi-function input terminal of required to be negative logic,then the settings are as
X1~X5.At this time, the function of this terminal should following:
be defined as No.5 function of “3-wire operation”. Logic status of X4~X1 is 0000, and the hex value is 0.
3:3-wire operation mode 2 Logic status of X5 is 001, and the hex value is 1. The
display on LED decade is 1; so the value in A6.13
should be set as 10..
Table 6-5 Conversion of binary code and hex value
Binary settings Hex value
BIT3 BIT2 BIT1 BIT0 (Displaying of LED)
Fig.6-22 3-wire operation mode 2 0 0 0 0 0
0 0 0 1 1
Where: 0 0 1 0 2
SB1: Stop button 0 0 1 1 3
SB2: Run button 0 1 0 0 4
Terminal Xi is the multi-function input terminal of
0 1 0 1 5
X1~X5.At this time, the function of this terminal should
0 1 1 0 6
be defined as No.5 function of “3-wire operation”.
0 1 1 1 7
1 0 0 0 8
A6.10 Reserved
1 0 0 1 9
A6.11 Reserved
1 0 1 0 A
A6.12 Reserved
1 0 1 1 B
A6.13 Input terminal’s
00~FFH【00H】 1 1 0 0 C
positive and negative logic
1 1 0 1 D
1 1 1 0 E
1 1 1 1 F

Note:
Factory setting of all the terminals is positive logic.
Fig.6-23 terminal’s positive and negative logic
A6.13 defines the input terminal’s positive and negative A6.14 Bi-direction pen-collector
0~20【0】
logic output terminal Y1
Positive logic: Terminal Xi is enabled if it is connected A6.15 Reserved
to the common terminal; A6.16 Output functions of relay R1 0~20【0】
Negative logic: Terminal Xi is disabled if it is connected A6.17 Reserved
to the common terminal; Refer to chapter 3 for the output characteristics of Y1
If the bit is set at 0, it means positive logic; if set at 1, it that are bi-direction open-collector output terminal and
means negative logic. the relay’s output terminal. Table 6-6 shows the
For example:

38
functions of the above 2 terminals. One function can be See A6.20~A6.21.
selected repeatedly. 3: Frequency detection threshold (FDT2)
Table 6-6 Functions of output terminals See A6.22~A6.23.
Setting Function Setting Function 4: Reserved.
Drive running Frequency arriving 5: Low voltage lock-up signal (LU)
0 1
signal (RUN) signal (FAR) The terminal outputs the indicating signal if the DC bus
Frequency voltage is lower than the low voltage limit, and the LED
detection Frequency detection displays “P.oFF”.
2 3
threshold threshold (FDT2) 6: External stopping command (EXT)
(FDT1) The terminal outputs the indicating signal if the drive
Low voltage outputs tripping signal caused by external fault (E015).
4 Reserved 5
lock-up signal (LU) 7: High limit of frequency (FHL)
External The terminal outputs the indicating signal if the preset
stopping High limit of frequency is higher than upper limit of frequency and the
6 7
command frequency (FHL) operating frequency reaches the upper limit of
(EXT) frequency.

Lower limit of 8: Lower limit of frequency (FLL)

8 frequency 9 Zero-speed running The terminal outputs the indicating signal if the preset

(FLL) frequency is higher than lower limit of frequency and the

10 Reserved 11 Reserved operating frequency reaches the lower limit of

PLC running frequency.


PLC running cycle 9: Zero-speed running
12 step finish 13
finish signal The terminal outputs the indicating signal if the drive’s
signal
14 Swing limit 15 Drive ready (RDY) output frequency is 0 and the drive is in operating status.

16 Drive fails 17 Reserved 10~14:Reserved.


15: drive ready (RDY)
18 Reserved 19 Torque limiting
If RDY signal is output, it means the drive has no fault,
Drive running
20 21 Timer 1 reach its DC bus voltage is normal and it can receive starting
forward/reverse
command.
22 Timer 2 reach 23 Counter reach
16: Drive fails
Intermediate
24 The terminal outputs the indicating signal if the drive
counter reach
has faults.
The instructions of the functions in Table 6-6 as
17~18: Reserved.
following:
19: Torque limiting
0: Drive running signal (RUN)
The terminal outputs the indicating signal if the torque
When the drive is in operating status, there will be
reach drive torque limit or brake torque limit.
running indication signal output by this terminal.
20: Drive running forward/reverse
1: Frequency arriving signal (FAR)
The terminal outputs the indicating signal according to
See A6.19.
the drive’s current running direction.
2: Frequency detection threshold (FDT1)
21:Timer 1 reach

39
22:Timer 2 reach
When timer reach the setting value(A6.37,A6.38),this A6.20 FDT1 level 0.00~300.0Hz【50.00Hz】
output will enable.When timer reset,then the output will A6.21 FDT1 lag 0.00~300.0Hz【1.00Hz】
disable.
A6.22 FDT2 level 0.00~300.0Hz【25.00Hz】
23:Counter reach
A6.23 FDT2 lag 0.00~300.0Hz【1.00Hz】
When the counter reach the target value(A6.39),this
output will enable. A6.20~A6.21 is a complement to the No.2 function in

24:Intermediate counter reach Table 6-6. A6.22 ~ A6.23 is a complement to the No.3
When the counter reach middle value(A6.40),then this function in Table 6-6. Their functions are the same.Take
output will enable. A6.20~A6.21 for example:
When the drive’s output frequency reaches a certain
A6.18 Ouput terminal’s
00~1FH【00H】 preset frequency (FDT1 level), it outputs an indicating
positive and negative logic
signal until its output frequency drops below a certain
frequency of FDT1 level (FDT1 level-FDT1 lag), as
shown in Fig. 6-26

Fig.6-24 Ouput terminal’s positive and negative logic


A6.18 defines the output terminal’s positive and
negative logic.
Positive logic: Terminal is enabled if it is connected to
the common terminal;
Negative logic: Terminal is disabled if it is connected to
Fig.6-26 FDT level
the common terminal;
A6.24 Virtual terminal setting 0~007FH【00h】
If the bit is set at 0, it means positive logic; if set at 1, it
means negative logic.

A6.19 Frequency arriving


0.00~300.0Hz【2.50Hz】
signal (FAR)
As shown in Fig. 6-25, if the drive’s output frequency is
within the detecting range of preset frequency, a pulse
signal will be output.

A6.25 Y2 terminal output 0~88【0】

0~50:Y2 is used as Y terminal output; its function is the


same as Table 6-6.
51~88:Y2 function.
Fig.6-25 Frequency arriving signal

40
Pulse frequency frequency of Y2:0 ~ Max pulse output This parameter defines different centre point mode of Y2
frequency(Defined in A6.26). pulse output.
The linear relationship between the displaying range and 0:No centre point.Shown as following figure:
the output values of Y2 is shown as Table 6-7. Corresponding
value

Table 6-7 Displaying range of Analog output


Setting Function Range
0 No function No function 0 A6.26 Frequency

1 Output frequency 0~Max. output frequency


Fig.6-27 No centre point mode
2 Preset frequency 0~Max. output frequency
All the corresponding value of pulse output frequency
Preset frequency are positive.
3 0~Max. output frequency
(After Acc/Dec) 1: Centre point mode 1.Shown as following figure.
4 Motor speed 0~Max. speed Corresponding
value
0~2 times of drive’s
5 Output current
rated current
0 A6 . 26 A6.26
0~2 times of motor’s Frequency
2
6 Output current
rated current
0~3 times of motor’s
7 Output torque Fig.6-28 Centre point mode 1
rated torque
There is a centre point in pulse output.The value of the
Output torque 0 ~ 3 times of motor’s
8 centre point is a half of max. output pulse frequency
current rated torque
(A6.26).The corresponding value is positive when the
0~1.2 times of drive’s output pulse frequency is less than centre point.
9 Output voltage
rated voltage 2:Centre point mode 2
10 Bus voltage 0~800V There is a centre point in pulse output.The value of the
11 AI1 0~Max. analog input centre point is a half of max. output pulse frequency
12 AI2 0~Max. analog input (A6.26).The corresponding value is positive when the

64 DI Pulse input 0-Max.pulse input input pulse frequency is greater than centre point.
Corresponding
Others Reserved Reserved value

A6.26 Max. output pulse


0.1~100kHz【10.0】 0 A6 . 26 A 6.26
frequency Frequency
2
This parameter defines the permissible maximum pulse
frequency of Y2.
Fig.6-29 Centre point mode 2

A6.27 Centre point of A6.28 Functions of terminal


0~2【0】 0~36【0】
pulse output selection AO1
A6.29 Functions of terminal 0~36【0】

41
AO2 100% of zero offset of analog output is corresponding to
Refer to section 4.2 for the output characteristics of AO1 the maximum output (10V or 20Ma).Take output voltage
The relationship between the displaying range and the for example,the relationship between the value before
output values of AO1 is shown as Table 6-8 adjustment and with after adjustment is as following:
Table 6-8 Displaying range of Analog output AO output value = (Gain of AO)×(value before
Setting Function Range adjustment)+(Zero offset calibration)×10V
0 No function No function The relationship curve between analog output and gain
1 Output frequency 0~Max. output frequency and between analog output and zero offset calibration
2 Preset frequency 0~Max. output frequency are as Fig.6-30 and Fig.6-31.
Value after adjustment(V)
Preset frequency
3 0~Max. output frequency 10
(After Acc/Dec) A 6.30=200%
A 6.30=100%
4 Motor speed 0~Max. speed
0~2 times of drive’s -10 -5 5 10
5 Output current 0 Value before adjustment(V)
rated current
0~2 times of motor’s
6 Output current
rated current -10

0~3 times of motor’s


7 Output torque Fig.6-30 Relationship curve between analog
rated torque
output and gain
Output torque 0 ~ 3 times of motor’s
8 Value after adjustment(V)
current rated torque 10
A6.31=50%
0~1.2 times of drive’s A6.31=0
9 Output voltage 5
rated voltage
-10 5 10
10 Bus voltage 0~800V 0
Value before adjustment(V)
11 AI1 0~Max. analog input

12 AI2 0~Max. analog input


-10
Others Reserved Reserved
Fig.6-31 The relationship curve between analog
output and zero offset
Note:
The external resistor is advised to be lower than 400Ω
Note:
when AO output current signal.
The parameters of gain and zero offset calibration affect
the
A6.30 Gain of AO1 0.0~200.0%【100.0%】
analog output all the time when it is chaning.
A6.31 Zero offset calibration
-100.0~100.0%【0.0%】
of AO1
A6.32 Reserved
For the analog output AO1,adjust the gain if user need to
A6.33 Reserved
change the display range or calibrate the gauge outfit
A6.34 AI1 filter 0.01~10.00s【0.05】
error.

42
A6.35 AI2 filter 0.01~10.00s【0.05】
A6.36 Reserved
A6.34 ~ A6.36 define the time constant of AI filter.The
longer the filter time,the stronger the anti-interference
ability,but the response will become slower.The shorter
the filter time,the faster the response,but the ! Attention
Please set the fault masking selection
anti-interference ability will become weaker. function carefully,or it may cause worse accident,bodily
injury and property damage.
A6.37 Setting value of timer 1 0.0~10.0s【0】
A8.03 Motor overload protection
A6.38 Setting value of timer 2 0~100s【0】 0、1、2【1】
mode selection
A6.39 Counter target value 0~65535【100】
0: Disabled
A6.40 Counter intermediate 0~65535【50】
The overload protection is disabled. Be careful to use
value
this function because the drive will not protect the motor
when overload occurs.
1:Common motor (with low speed compensation)
6.8 Group A7
Since the cooling effects of common motor deteriorates
The parameters in this group are reserved at low speed (below 30Hz), the motor’s overheat
protecting threshold should be lowered, which is called
6.9 Group A8
low speed compensation.
A8.00 Protective action of relay 0~1111H【0000】 2: Variable frequency motor (without low speed
compensation)
The cooling effects of variable frequency motor is not
affected by the motor’s speed, so low speed
compensation is not necessary.

A8.04 Auto reset times 0~100【0】

A8.05 Reset interval 2.0~20.0s【5.0s】


Auto reset function can reset the fault in preset times and
A8.01 Fault masking selection 1 0~2222H【0000】 interval. When A8.04 is set to 0, it means “auto reset” is
disabled and the protective device will be activated in
case of fault.
Note:
The IGBT protection (E010) and external equipment
fault (E015) cannot be reset automatically.

A8.06 Fault locking


0~1【0】
function selection.
A8.02 Fault masking selection 2 0~22H【00】
0:Disable.

43
1:Enable. See Fig. 6-32 for the above parameters.
jX11 R2 jX21
R1

I1 I2
6.10 Group b0
1-S R
U1 2
S
0.4~999.9kW【dependent on
b0.00 Rated power I0 Xm
drive’s model】
0~rated volotage of drive
Fig. 6-32 Motor’s equivalent circuit
b0.01Rated voltage 【 dependent on drive’s
In Fig. 6-32, R1, X1l, R2, X2l, Xm and I0 represent
model】 stator’s
0.1 ~ 999.9A 【 dependent on resistance, stator’s leakage inductance, rotor’s resistance,
b0.02 Rated current
drive’s model】 rotor’s leakage inductance, exciting inductance and

1.00 ~ 300.00Hz 【 dependent current without load respectively. The setting of b0.07 is
b0.03 Rated frequency the sum of stator’s leakage inductance and rotor’s
on drive’s model】
inductance.
b0.04 Number of
2~24【4】 The settings of b0.06 ~b0.09 are all percentage values
polarities of motor
calculated by the formula below:
b0.05 Rated speed 0~60000RPM【1440RPM】
R
%R = × 100 %
These parameters are used to set the motor’s parameters. V /( 3 × I)
(1)
In order to ensure the control performance, please set
R: Stator’s resistance or rotor’s resistance that is
b0.00~b0.05 with reference to the values on the motor’s
converted to the rotor’s side;
nameplate.
V: Rated voltage;
Note:
I: Motor’s rated current
The motor’s power should match that of the
Formula used for calculating inducatance (leakage
drive.Generally the motor’s power is allowed to be inductance or exciting inductance):
lower than that of the drive by 20% or bigger by 10%, X
%X = × 100 %
otherwise the control performance cannot be ensured. V /( 3 × I) (2)
X: sum of rotor’s leakage inductance and stator’s
b0.06 Resistance of stator 0.00~50.00%【dependent leakage inductance (converted to stator’s side)or the
%R1 on drive’s model】 exciting inductance based on base frequency.

b0.07 Leakage 0.00~50.00%【dependent V: Rated voltage;

inductance %Xl on drive’s model】 I: Motor’s rated current


If motor’s parameters are available, please set
b0.08 Resistance of 0.00~50.00%【dependent
b0.06~b0.09 to the values calculated according to the
rotor %R2 on drive’s model】
above formula. b0.10 is the motor current without
b0.09 Exciting 0.0~2000.0%【dependent load,the user can set this parameter directly.
inductance %Xm on drive’s model】 If the drive performs auto-tuning of motor’s
b0.10 Current without 0.1~999.9A【dependent parameters,the results will be written to b0.06~b0.10
load I0 on drive’s model】 automatically.After motor power (b0.00) is changed, the
drive will change b0.02~b0.10 accordingly(b0.01 is the

44
rated voltage of motor,user need to set this parameter by auto-tuning is over.
manual according to the value on the motor’s 3:Reserved.
nameplate.) Note:
1.When setting b0.11 to 2, Acc/Dec time can be
b0.11 Auto-tuning 0~3【0】 increased if over-current or over-voltage fault occurs in
0: Auto-tuning is disabled the auto-tuning process;
1: Stationary auto-tuning (Start auto-tuning to a 2.When setting b0.11 to 2, the motor’s load must be
standstill motor) removed
Values on the motor’s nameplate must be input correctly first before starting rotating auto-tuning;
before starting auto-tuning ( b0.00 ~ b0.05 ) .When 3.The motor must be in standstill status before starting

starting auto-tuning to a standstill motor, the stator’s the

resistance (%R1), rotor’s resistance (%R2) and the auto-tuning, otherwise the auto-tuning cannot be

leakage inductance (%X1) will be detected and written executed

into b0.06、b0.07 and b0.08 automatically. normally;


4.In some applications, for example, the motor cannot
2: Rotating auto-tuning
break
Values on the motor’s nameplate must be input correctly
away from the load or if you have no special
before starting auto-tuning ( b0.00 ~ b0.05 ) .When
requirement on motor’s control performance, you can
starting a rotating auto-tuning, the motor is in standstill
select stationary auto-tuning. You can also give up the
status at first, and the stator’s resistance (%R1), rotor’s
auto-tuning. At this time, please input the values on the
resistance (%R2) and the leakage inductance (%X1) will
motor’s nameplate correctly .
be detected, and then the motor will start rotating,
5.If the auto-tuning cannot be applied and the correct
exciting inductance (%Xm and I0 will be detected. All
motor’s
the above parameters will be saved in b0.06 、 b0.07 、
parameters are available, the user should input the values
b0.08、b0.09 and b0.10 automatically.After auto-tuning,
on the motor’s nameplate correctly (b0.00~b0.05), and
b0.05 will be set to 0 automatically. then input the calculated values (b0.06~b0.10). Be sure
Auto-tuning procedures: to set the parameters correctly.
1). A0.13(Torque boost of motor 1) is suggested to set as 6.If auto-tuning is not successful, the drive will alarm
0. and display fault code E024.
2). Set the parameters b0.00(Rated power),b0.01(Rated
voltage),b0.02(Rated current),b0.03(Rated
b0.12 Motor’s overload 20.0% ~ 110.0%
frequency),b0.04 (Number of polarities of motor ) and
protection coefficient 【100.0%】
b0.05(Rated speed) correctly;
In order to apply effective overload protection to
3). Set the parameter A0.10 correctly.The setting value
different
of A0.10 can’t be lower than rated frequency.
kinds of motors, the Max. output current of the drive
4). Remove the load from the motor and check the
should be adjusted as shown in Fig. 6-33.
Safety when set the parameter b0.11 as 2.
5). Set b0.11 to 1 or 2, press ENTER, and then press
RUN to start auto-tuning;
6). When the operating LED turns off, that means the

45
b1.06 V/F voltage value V1
0.0~b1.04【0.0%】
of motor 1
This group of parameters define the V/F setting modes
of CV100 so as to satisfy the requirements of different
loads. 3 preset curves and one user-defined curve can
be selected according to the setting of b1.00.
If b1.00 is set to 1, a 2-order curve is selected, as shown
in Fig. 6-34 as curve 1;
If b1.00 is set to 2, a 1.7-order curve is selected, as
Fig.6-33 Motor’s overload protection coefficient shown in Fig. 6-34 as curve 2;
This parameter can be set according to the user’s If b1.00 is set to 3, a 1.2-order curve is selected, as
requirement.In the same condition,set b0.12 to a lower shown in Fig. 6-34 as curve 3;
value if the user need fast protection for overload of The above curves are suitable for the variable-torque
motor,or set it to a bigger value. loads such as fan & pumps. You can select the curves
Note: according to the actual load so as to achieve best
If the motor’s rated current does not match that of the energy-saving effects.
drive,
motor’s overload protection can be realized by setting
b0.12.

b0.13 Oscillation inhibition


0~255【10】
coefficient
Adjust this parameter can prevent motor oscillation
when drive using V/F control.

Fig.6-34 Torque-reducing curve


6.11 Group b1
If b1.00 is set to 0, you can define V/F curve via
b1.00 V/F curve setting 0~3【0】 b1.01~b1.06, as shown in Fig. 6-30. The V/F curve can
b1.01 V/F frequency value be defined by connecting 3 points of (V1,F1), (V2,F2)
b1.03~A0.08【0.00Hz】
F3 of motor 1 and (V3, F3), to adapt to special load characteristics.
b1.02 V/F voltage value V3 Default V/F curve set by factory is a direct line as show
b1.04~100.0%【0.0%】
of motor 1 in Fig. 6-35 as curve 0.

b1.03 V/F frequency value


b1.05~b1.01【0.00Hz】
F2 of motor 1
b1.04 V/F voltage value V2
b1.06~b1.02【0.0%】
of motor 1
b1.05 V/F frequency value
0.00~b1.03【0.00Hz】
F1 of motor 1

46
Set a value(not zero) to b1.09 to select a analog input to
control the output voltage.
This function can be only valid in V/F control mode,the
output voltage VO is separated from output
frequency.The output voltage is not controlled by the
curve of V/F but controlled by analog input as shown in
Fig.6-36.

V1~V3: Voltage of sections 1~3


F1~F3: Freq of sections 1~3
Fb:Basic operating frequency of A0.12

Fig.6-35 V/F curve defined by user

b1.07 Cut-off point used


0.0%~50.0%【10.0%】
for manual torque boost
b1.07 defines the ratio of the cut-off frequency used for Fig.6-36 Curve of output voltage
manual torque boost to the basic operating frequency
Example 2:The output voltage in V/F mode is adjusted
(defined by A0.12), as shown in Fig. 6-2 as Fz.This by AI.
cut-off frequency adapts to any V/F curve defined by Set a value(not zero) to b1.10 to select a adjustment for
b1.00. output voltage.As shown in Fig.6-37

b1.08 AVR function 0~2【1】

0:Disable
1:Enable all the time
2:Disabled in Dec process
Fig.6-37 Offset of output voltage
AVR means automatic voltage regulation.
The relationship between analog input and offse voltage
The function can regulate the output voltage and make it
is as follows:
constant. Therefore, generally AVR function should be -10V~0V/4mA of VAI is corresponding to offset voltage
enabled, especially when the input voltage is higher than –V/F.
the rated voltage. 10V/20mA of VAI is corresponding to offset voltage
In Dec-to-stop process, if AVR function is disabled, the V/F.
Dec time is short but the operating current is big. If AVR Output voltage VO=V/F+Vb.

function is enabled all the time, the motor decelerates Note


steadily, the operating current is small but the Dec time Output offset voltage of AI can be only valid in V/F
control mode.
is prolonged.
Example 1:The output voltage in V/F mode is controlled 6.12 Group b2
by AI.
b2.00 Carrier wave frequency 2.0~15.0kHz【8kHz】
Drive’s type and carrier wave frequency(CWF)

47
Drives power Default CWF value defined by b2.03. If the bus voltage exceeds the stall
2.2~5.5 kW 10kHz overvoltage point, the drive will stop reducing its output
frequency. When the bus voltage become lower than the
7.5~55 kW 8kHz
point, the deceleration continues, as shown in Fig.6-36.
55~250 kW 2kHz
The hundred’s place is used to set overmodulation
function of V/F control.For vector control,the
Note:
overmodulation function will be always
1.The carrier wave frequency will affect the noise when
enable.Overmodulation means when the voltage of
motor running,generally the carrier wave frequency is
power grid is low for long term(Lower than 15% of
supposed to set as 3~5KHz.For some special situation
rated voltage),or is overload working for long term,then
where require operating mutely,the carrier wave
the drives will increase the use ratio of its own bus
frequency is supposed to set as 6~8KHz.
voltage to increase output voltage.
2 . When set the carrier wave frequency larger than
defaultvalue,then the power of drive need to derate 5%
by every increase of 1KHz.

b2.01Auto adjusting of CWF 0~1【0】

0:Disable
1:Enable
b2.02 Voltage adjustment
000~111H【001H】
selection Fig.6-38 Over-voltage at stall
b2.03 Overvoltage point at
120~150%【140.0%】
stall b2.04: Reserved
b2.05 Auto current limiting
20.0~200.0%【150.0%】
threshold
b2.06 Frequency decrease rate 0.00~99.99Hz/s
when current limiting 【10.00Hz/s】
b2.07 Auto current limiting
0~1【1】
selection
Auto current limiting function is used to limit the load
current smaller than the value defined by b2.05 in real
During deceleration, the motor’s decelerate rate may be
time. Therefore the drive will not trip due to surge
lower than that of drive’s output frequency due to the
over-current. This function is especially useful for the
load inertia. At this time, the motor will feed the energy
applications with big load inertia or big change of load.
back to the drive, resulting in the voltage rise on the
b2.05 defines the threshold of auto current limiting. It is
drive's DC bus. If no measures taken, the drive will trip
a percentage of the drive’s rated current.
due to over voltage.
b2.06 defines the decrease rate of output frequency when
During the deceleration, the drive detects the bus voltage
the drive is in auto current limiting status.
and compares it with the over voltage point at stall

48
If b2.06 is set too small, overload fault may occur. If it is program will be activated to stop the fan or let the fan
set too big, the frequency will change too sharply and continue to run according to the IGBT’s temperature.
therefore, the drive may be in generating status for long The drive will activate the internal temperature detecting
time, which may result in overvoltage protection. program automatically when it is operating,and run or
Auto current limiting function is always active in Acc or stop the fan according to the IGBT’s temperature.If the
Dec process. Whether the function is active in constant fan is still running before the drive stop,then the fan will
speed operating process is decided by b2.07. continue running for three minutes after the drive stops
b2.07 = 0, Auto current limiting function is disabled in and then activate the internal temperature detecting
constant speed operating process; program.

b2.07 = 1, Auto current limiting function is enabled in 1:The fan operates continuously.

constant speed operating process; The fan operates continuously after the drive is switched
In auto current limiting process, the drive’s output on.
frequency may change; therefore, it is recommended not Note:This function is only valid in power above 7.5KW.
to enable the function when the drive’s output frequency
6.13 Group b3
is required stable.
When the auto current limiting function is enabled, if Details please refer to the Group b3 of function list in
b2.05 is set too low, the output overload capacity will be chapter 9.
impaired.
b2.08 Gain of slip
0.0~300.0%【100%】 6.14 Group b4
compensation
b2.09 Limit of slip b4.00 Key-lock function selection 0~4【0】
0.0~250.0%【200%】
compensation 0: The keys on the operation panel are not locked, and
b2.10 Slip compensation all the keys are usable.
0.1~25.0s【2】
time constant 1: The keys on the operation panel are locked, and all the
b2.11 Energy-saving function 0:Disable. 1:Enable. 【0】 keys are unusable.
b2.12 Frequency decrease 0.00~99.99Hz 2: All the keys except for the multi-functional key are
rate at voltage compensation 【10.00 Hz/s】 unusable.
3: All the keys except for the SHIFT key are unusable.

0.00~300.00Hz 4:All the keys except for the RUN AND STOP keys are
b2.13Threshold of
unusable.
zero-frequency operation 【0.50 Hz/s】
This parameter is used together with No.9 function of
b4.01 Multi-functional key
digital output terminal. 0~3【0】
function
0: Jog
b2.14 Reserved
1: Coast to stop
b2.15 Fan control 0~1【0】
2: Quick stop
0:Auto operating mode.
3: Operating commands switchover
The fan runs all the time when the drive is operating.
After the drive stops, its internal temperature detecting

49
b4.02 Parameter protection 0~2【0】 6.15 Group C0
0: All parameters are allowed modifying;
Lower limit of
1: Only A0.03 and b4.02 can be modified;
C0.00 Preset frequency 1 frequency~upper limit of
2: Only b4.02 can be modified.
frequency【5.00Hz】
Lower limit of
b4.03 Parameter initialization 0~2【0】
C0.01 Preset frequency 2 frequency~upper limit of
0: No operation
frequency【10.00Hz】
1: Clear falt information in memory
Lower limit of
2: Restore to factory settings
C0.02 Preset frequency 3 frequency~upper limit of
frequency【20.00Hz】
b4.04 Parameter copy 0~3【0】
Lower limit of
0: No action
C0.03 Preset frequency 4 frequency~upper limit of
1: parameters upload
frequency【30.00Hz】
2: parameters download
Lower limit of
3: parameters download (except the parameters related
C0.04 Preset frequency 5 frequency~upper limit of
to drive type)
frequency【40.00Hz】

b4.05 Display parameters Lower limit of


0~7FFFH【1007H】
selection C0.05 Preset frequency 6 frequency~upper limit of

B4.05 defines the parameters that can be displayed by frequency【45.00Hz】

LED in operating status. Lower limit of


If Bit is 0, the parameter will not be displayed; C0.06 Preset frequency 7 frequency~upper limit of
If Bit is 1, the parameter will be displayed. frequency【50.00Hz】
Lower limit of
C0.07 Preset frequency 8 frequency~upper limit of
frequency【5.00Hz】
Lower limit of
C0.08 Preset frequency 9 frequency~upper limit of
frequency【10.00Hz】
Lower limit of
C0.09 Preset frequency 10 frequency~upper limit of
frequency【20.00Hz】
Lower limit of
C0.10 Preset frequency 11 frequency~upper limit of
Note: If all the BITs are 0, the drive will display setting
frequency【30.00Hz】
frequency at stop and display output frequency at
Lower limit of
operating.
C0.11 Preset frequency 12 frequency~upper limit of
frequency【40.00Hz】

50
Lower limit of Analog feedback control system:
C0.12 Preset frequency 13 frequency~upper limit of An analog feedback control system uses a pressure
frequency【45.00Hz】 transmitter as the feedback sensor of the internal
Lower limit of
close-loop.As shown in Fig. 6-37, pressure reference
C0.13 Preset frequency 14 frequency~upper limit of
(voltage signal) is input via terminal AI2, while the
frequency【50.00Hz】
feedback pressure value is input into terminal AI1 in the
Lower limit of
C0.14 Preset frequency 15 frequency~upper limit of form of 0(4)~20mA current signal. The reference signal
frequency【50.00Hz】 and feedback signal are detected by the analog
These frequencies will be used in multi-step speed channel.The start and stop of the drive can be controlled
operation, refer to the introductions of No.27,28,29 and by terminal Xi.
30 function of A6.00~A6.04. The above system can also use a TG (speed measuring
generator) in close speed-loop control.
6.16 Group C1 Note:
Process close-loop control The reference can also be input via panel or serial port.
The process closed-loop control type of CV100 is analog
close-loop control. Fig.6-39 shows the typical wiring of Operating principles of internal process close-loop of
analog close-loop control. CV100 is shown in the Fig. 6-38.

QF R
In the above Fig., KP: proportional gain; Ki: integral
U
AC S
CV10 V Output gain
M P
input T W
PE Pressure In Fig. 6-40, refer to C1.00~C1.14 for the definitions of
transmitter close-loop reference, feedback, error limit and
Xi
+10V
proportional and Integral parameters.
AI1
COM
+10V
AI2
GND
-10V

Fig.6-39 Analog feedback control system with


internal process close-loop

KP× ε
Reference ( C1.09) +
regulation
+ ε Error limit Regulation Output
Reference
(C 1.14 ) (C1.15 )
(C 1.05、 C1.07 ) - ∑Ki× ε +
( C1.10)
Feedback regulation
Feedback
( C1.06、C 1.08)

Fig.6-40 Principle diagram of process close-loop control


the signal of pressure sensor is 4~20mA, then the
There are two features of internal close-loop of CV100: relationship between reference and feedback is shown
The relationship between reference and feedback can be in Fig. 6-41.
defined by C1.05~C1.08
For example: In Fig. 6-38, if the reference is analog
signal of -10~10V, the controlled value is 0~1MP, and

51
Feedbac 5:Max{ AI1,AI2}
20mA
6:DI (Pulse)
Settings of AI are the same as above.

4mA
C1.03 Digital setting of
-10.00~10.00V【0.00】
reference
-10V 10V Referenc
This function can realize digital setting of reference via
Fig.6-41 Reference and feedback
panel or serial port.
After the control type is determined, follow the
procedures below to set close loop parameters.
C1.04 Close-loop speed
1)Determine the close-loop reference and feedback 0~39000rpm
reference
channel (C1.01 and C1.02);
C1.05 Min reference 0.0%~C1.08【0.0%】
2)The relationship between close-loop reference and
C1.06 Feedback value
feedback value (C1.05~C1.08) should be defined for
corresponding to the Min 0.0~100.0%【0.0%】
analog close-loop control;
reference
3)Determine the close-loop regulation characteristic, if
C1.06 ~ 100.0%
the relationship between motor speed and the reference C1.07 Max reference
【100.0%】
is opposite,then set the close-loop regulation
characteristic as negative characteristic(C1.15=1). C1.08 Feedback value

4)Set up the integral regulation function and close-loop corresponding to the Max 0.0~100.0%【100.0%】

frequency presetting function (C1.16~C1.18); reference


The regulation relationship between C1.05,C1.07 and
5)Adjust the close-loop filtering time, sampling cycle,
reference is shown in Fig.6-42.When the analog input
error limit and gain(C1.09~C1.14).
6V,if C1.05=0% and C1.07=100%,then adjusted value
C1.00 Close-loop control function 0、1【0】
is 60%.If C1.05 = 25% and C1.07 = 100% , then the
0:Disable.
adjusted value is 46.6%.
1:Enable.
Adjusted value

100%
C1.01 Reference channel selection 0、1、2、3【1】
0: digital input(Take the value of C1.03). 60%
46.6%
1: AI1 analog input.
2: AI2 analog input
25% 50%
0% 80% 100%
C1.02 Feedback channel selection 0~5【1】 (6V)
Analog input

0:AI1 analog input


C1.05=0%
1:AI2 analog input C1.07=100%
2:AI1+ AI2 C1.05=25%
-100% C1.07=100%
3:AI1-AI2
4:Min{ AI1,AI2} Fig.6-42 Regulation curve of reference

52
Note: This parameter defines the max. deviation of the output
1 . Fig.6-42,0% ~ 100% in X axis is corresponding to from the reference, as shown in Fig. 6-43. Close-loop

analog input - 10V ~ 10V,10V of analog input is regulator stops operation when the feedback value is
within this range.Setting this parameter correctly is
corresponding to 100%,and - 10V is corresponding to
helpful to improve the system output accuracy and
0%,6V is corresponding to 80%.
stability.
2 . If the analog type is current input,because the
Feedback value
Error limit
currentinput range is 4~20mA,then the range of X axis
Reference
is 50%~100%.
3.The adjusted value can be observed in d0.24.
Ooutput Time
The regulation relationship between C1.06,C1.08 and frequency

feedback is similar to reference regulation.Its adjusted


value can be observed in d0.25.

Time
C1.09 Proportional gain
0.000~10.000【2.000】 Fig.6-43 Error limit
KP
C1.10 Integral gain Ki 0.000~10.000【0.100】
C1.15 Close-loop regulation characteristic 0、1【0】
C1.11 Differential gain
0.000~10.000【0.100】 0: Positive
Kd
Set C1.15 to 0 if the motor speed is required to be
C1.12 Sampling cycle T 0.01~50.00s【0.50s】
increased with the increase of the reference.
The bigger the proportional gain of KP, the faster the
1: Negative
response, but oscillation may easily occur.
Set C1.15 to 1 if the motor speed is required to decrease
If only proportional gain KP is used in regulation, the
with the increase of the reference.
error cannot be eliminated completely. To eliminate the
error, please use the integral gain Ki to form a PI control
C1.16 Integral regulation
system. The bigger the Ki, the faster the response, but 0、1【0】
selection
oscillation may easily occur if Ki is too big.
0: Stop integral regulation when the frequency reaches
The sampling cycle T refers to the sampling cycle of
the upper and lower limits
feedback value. The PI regulator calculates once in each
1: Continue the integral regulation when the frequency
sampling cycle. The bigger the sampling cycle the
reaches the upper and lower limits
slower the response.
It is recommended to disable the integral regulation for
the system that requires fast response.
C1.13 Output filter 0.01~10.00【0.05】
This parameter defines the filter time of the close-loop
C1.17 Preset close-loop
output (Frequency or torque).The bigger the output 0.00~1000.0Hz【0.00Hz】
frequency
filter,the slower the response.
C1.18 Holding time of
preset close-loop 0.0~3600.0s【0.0s】
C1.14 Error limit 0.0~20%【2.0%】
frequency

53
This function can make the close-loop regulation enter C1.29 Preset close-loop
-10.00~10.00V【0.00V】
stable status quickly. reference 11
When the close-loop function is enabled, the frequency C1.30 Preset close-loop
-10.00~10.00V【0.00V】
will ramp up to the preset close-loop frequency (C1.17) reference 12
within the Acc time, and then the drive will start C1.31 Preset close-loop
-10.00~10.00V【0.00V】
close-loop operation after operating at the preset reference 13
frequency for certain time(defined by C1.18). C1.32 Preset close-loop
-10.00~10.00V【0.00V】
Output frequency reference 14
Preset frequency C1.33 Preset close-loop
-10.00~10.00V【0.00V】
reference 15
Among the close-loop reference selectors, besides the 3
T(time)
selectors defined by C1.01, the voltage value defined by
Holding time of
C1.19~C1.33 can also be used as the close-loop
Preset frequency
reference.
Fig.6-44 Preset frequency of close-loop operation
Voltage of preset close-loop reference 1~15 can be
Note: selected by terminals, refer to introductions to
You can disable the function by set both C1.17 and A6.00~A6.04 for details.
C1.18 to 0. The priority preset close-loop reference control is higher
than the reference selectors defined by C1.01
C1.19 Preset close-loop
-10.00~10.00V【0.00V】
reference 1
C1.34 Close-loop output reversal
C1.20 Preset close-loop 0、1【0】
-10.00~10.00V【0.00V】 selection
reference 2
0 : The close-loop output is negative,the drive will
C1.21 Preset close-loop
-10.00~10.00V【0.00V】 operate
reference 3
at zero frequency.
C1.22 Preset close-loop
-10.00~10.00V【0.00V】 1 : The close-loop output is negative,and the drive
reference 4
operate reverse.If the anti-reverse function is
C1.23 Preset close-loop
-10.00~10.00V【0.00V】 activated,then the drive will operate at zero
reference 5
frequency.Refer to the instructions of A1.12.
C1.24 Preset close-loop
-10.00~10.00V【0.00V】
reference 6
C1.35 Sleep function selection 0,1【0】
C1.25 Preset close-loop
-10.00~10.00V【0.00V】
reference 7 0:Disable

C1.26 Preset close-loop 1:Enable.


-10.00~10.00V【0.00V】
reference 8
C1.27 Preset close-loop C1.36 Sleep level 0.0~100.0%【50.0%】
-10.00~10.00V【0.00V】
reference 9 C1.37 Sleep latency 0.0~6000.0s【30.0s】
C1.28 Preset close-loop C1.38 Wake-up level 0.0~100%【50.0%】
-10.00~10.00V【0.00V】
reference 10

54
As shown in Fig.6-43,when the output frequency is
lower than the sleep level(C1.36),timer for sleep latency
will start.When the output frequency is larger than the
sleep level,the timer for sleep latency will stop and
clear.If the time of the situation that the output frequency
is lower than the sleep level is longer than sleep
latency(C1.37),then the driver will stop.When the actual
feedback value is higher than wake-up level(C1.38),the
driver will start again.
In Sleep level(C1.36),100% is corresponding to the Fig.6-46 Simple PLC function
frequency in A0.08. In Fig.6-46,a1~a15 and d1~d15 are the acceleration and
In Wake-up level(C1.38),100% is corresponding to 10V deceleration of the steps.f1~f15 and T1~T15 are the
or 20mA. setting frequency and operating time of the steps.There
parameters are defined in group C2.
PLC step finish signal and PLC cycle finish signal can
be defined in open collector output Y1,
Detected
value C2.00 Simple PLC operation
0~1123H【0000】
mode selector

A B C D

0: No function
1: Stop after single cycle
2: Keep final states after single cycle
3: Continuous cycle

Start mode
0: Start from first step
1: Start from the step before stop
(or alarm).
Fig.6-45 Sleep Function 2: Start from the step and frequency
before stop(or alarm)

6.17 Group C2 Storage after power off


0: Disable
1: Save the segment,frequency when
Simple PLC function power off

Simple PLC function is used to run different frequency Time unit selector for each step
0: Second
1: Minute
and direction in different time automatically,as shown in
Fig.6-46
The unit’s place of LED:PLC function running mode
0:No function.
Simple PLC function is invalid.
1:Stop after single cycle.
As shown in Fig.6-47,the drive will stop automatically
after finishing one cycle running,the wait for another
start signal to startup.

55
The ten’s place of LED:Start modes
0:Start from first step
If the drive stop while it was running(Caused by stop
command,fault or power failure), then it will start from
first step when it restart.
1:Start from the step before stop(or alarm)
If the drive stop while it was running(Caused by stop
command or fault), then it will record the operating time
of current step,and start from this step and continue the

Fig.6-47 Stop after single cycle left operating time when it restart,as shown in Fig.6-50.

2.Keep final states after single cycle


As shown in Fig.6-48,the drive will keep running at the
frequency and direction in last step after finishing single
cycle.

Fig.6-50 Start mode 1 of PLC function


2.Start from the step,frequency before stop(or alarm)
If the drive stop while it was running(Caused by stop
command or fault),it will record the operating time of
current step and also record the operating frequency,then
when it restart,it will return to the operating frequency
Fig.6-48 Keep final states after single cycle
before stop and continue the left operating time,as
3.Continuous cycle
shown in Fig.6-51.
As shown in Fig.6-49,the drive will continue next cycle
after finishing one cycle,and stop when there is stop
command.

Fig.6-51 Start mode 2 of PLC function


Hundred’s place of LED:Save after power off
0:Not save
Fig.6-49 Continuous cycle

56
The drive will not save the PLC operating status after C2.16 Step 8 operating time 0.0~6500.0【20.0】
power off.It will start from first step after power on C2.17 Step 9 setting mode
Same as C2.01
again. selector
1:Save the segment frequency after power off
C2.18 Step 9 operating time 0.0~6500.0【20.0】
It will save the PLC operating status including
C2.19 Step 10 setting mode
step,operating frequency and operating time,then it will Same as C2.01
selector
restart according the the setting in ten’s place of LED
C2.20 Step 10 operating time 0.0~6500.0【20.0】
when power on again.
C2.21 Step 11 setting mode
Thousand’s place of LED:Time unit selector of each step Same as C2.01
selector
0:Second
Each steps will use second as the unit of operating time. C2.22 Step 11 operating time 0.0~6500.0【20.0】

1:Minute C2.23 Step 12 setting mode


Same as C2.01
Each steps will use minute as the unit of operating time. selector
This unit selector is only valid for PLC operating time. C2.24 Step 12 operating time 0.0~6500.0【20.0】
C2.25 Step 13 setting mode
Same as C2.01
C2.01 Step 1 setting mode selector
0~323H【0000】
selector C2.26 Step 13 operating time 0.0~6500.0【20.0】
C2.02 Step 1 operating time 0.0~6500.0【20.0】 C2.27 Step 14 setting mode
Same as C2.01
C2.03 Step 2 setting mode selector
Same as C2.01
selector C2.28 Step 14 operating time 0.0~6500.0【20.0】
C2.04 Step 2 operating time 0.0~6500.0【20.0】 C2.29 Step 15 setting mode
Same as C2.01
C2.05 Step 3 setting mode selector
Same as C2.01
selector C2.30 Step 15 operating time 0.0~6500.0【20.0】
C2.06 Step 3 operating time 0.0~6500.0【20.0】 C2.01~C2.30 are used to set the operating frequency,direction,
C2.07 Step 4 setting mode Acc/Dec time and operating time for PLC function.Here takes
Same as C2.01 C2.01 as example,as shown in Fig.6-52.
selector
A B C D
C2.08 Step 4 operating time 0.0~6500.0【20.0】
C2.09 Step 5 setting mode 0: Multiple frequency N(N:
Same as C2.01 corresponding to current step)
selector 1: Defined by A0.02cycle
2: Multiple closed-loop reference N
(N:corresponding to current step)
C2.10 Step 5 operating time 0.0~6500.0【20.0】
3: Defined by C1.01
C2.11 Step 6 setting mode
Same as C2.01 0: Forward
selector 1: Reverse
2: Defined by operation command
C2.12 Step 6 operating time 0.0~6500.0【20.0】
0: Acc/Dec time 1
C2.13 Step 7 setting mode
Same as C2.01 1: Acc/Dec time 2
selector 2: Acc/Dec time 3
3: Acc/Dec time 4
C2.14 Step 7 operating time 0.0~6500.0【20.0】
C2.15 Step 8 setting mode
Same as C2.01
selector Fig.6-52 PLC steps setting

57
The unit’s place of LED:
0:Multiple frequency N(N:corresponding to current step)
The frequency of current step depends on the multiple
frequency N.About the details of multiple frequency
setting,please refer to Group C0.
1:Defined by A0.02.
Use A0.02 to set the frequency of current step.
2.Multiple closed loop reference N(N:corresponding to
current step)
The frequency of current step depends on the multiple
closed loop reference N.About multiple closed loop
setting,please refer to C1.19~C1.33.
Fig.6-53 Swing operation
3:Defined by C1.01.
The process of swing control:Firstly the drive accelerate
PLC runs in process closed loop mode,the closed loop
to preset swing frequency(Set in C3.02),and wait for
reference is defined by C1.01.
some time(Set in C3.03),then accelerate to centre
Ten’s place of LED:
frequency,and run cyclic according to the swing
0:Forward amplitude(C3.04),Jump frequency(C3.05),Swing
Set the direction of current step as forward cycle(C3.06) and Triangle wave rising time(C3.07),and
1:Reverse then stop in dec time when there is stop command.
Set the direction of current step as reverse C3.00 Swing function
2:Defined by operation command 0~1【0】
selector
The direction of current step is defined by the operation
0:Disable
command of terminals.
Note: 1:Enable
If the operation direction of current step can not be
confirmed,then it will continue the previous direction. C3.01 Swing Operation
0~1111H【0000】
mode

6.18 Group C3 A B C D

Startup method
Swing function is suitable for application like spinning 0: Auto mode
which requires winding and swing function.Its typical 1: By terminal

operation is as shown in Fig.6-53.


Swing control
0: Reference centre frequency
1: Reference max.frequency

Swing states storage


0: Save after stop
1: Not save after stop

Swing states storage after power failure


0: Save
1: Not save

C3.02 Main reference


-300.0~300.0Hz【0.00】
frequency
C3.03 Waiting time for 0.0~3600.0s【0.0s】

58
preset swing frequency This parameter is used to monitor the frequency

C3.02 is used to set the operating frequency of swing combined by main reference frequency and auxiliary
operation.C3.03 is used to set the continuous time of reference frequency.Positive indicates running forwards,
preset swing frequency,C3.03 is invalid when swing negative indicates running reverse.
operation mode is set as 1.
C3.04 Swing amplitude 0.0%~50.0%【0.0%】
d0.03 Frequency after
Swing amplitude setting value is the percentage corresponding to
-300.0~300.0Hz【0.00】
Acc/Dec
centre frequency or max. frequency.
For centre frequency: Swing amplitude frequency=centre This parameter is used to monitor the drive’s output
frequency * C3.04. frequency(include direction) after the drive accelerating
For max. frequency: Swing amplitude frequency=Max. frequency
or decelerating.
* C3.04.
C3.05 Jump frequency 0.0%~50.0%【0.0%】
d0.04 Output frequency -300.0~300.0Hz【0.00】
As shown in Fig.6-53,when C3.05 is set to 0,then there is no
jumping frequency. This parameter is used to monitor the drive’s output
C3.06 Swing cycle 0.1~999.9s【0.1s】 frequency(include direction).
Swing cycle is the time from rising and falling of swing
frequency. 0~480V【0】
d0.05 Output voltage
C3.07 Triangle wave rising 0.0%~100.0%(Swing
This parameter is used to monitor the drive’s output
time cycle) 【50.0%】
voltage.
C3.07 is the percentage corresponding to swing cycle,as shown in
Fig.6-53.
Note: d0.06 Output current 0.0~3Ie【0】
Centre frequency:It is the setting value of main reference This parameter is used to monitor the drive’s output
frequency.
current.
Max. frequency:It is the setting value of A0.08.

-300.0%~300.0%【0.0
6.19 Group d0 d0.07 Torque current
%】
The parameters of Group d0 are used to monitor some This parameter is used to monitor the percentage of
states of drives and motors. drive’s torque current that corresponding to the motor’s
d0.00 Main reference rated current.
-300.0~300.0Hz【0.00】
frequency
This parameter is used to monitor main reference d0.08 Magnetic flux current 0.0%~100.0%【0.0】
frequency at normal operation mode. This parameter is used to monitor the percentage of
drive’s magnetic flux current that corresponding to the
d0.01 Auxiliary reference motor’s rated current.
-300.0~300.0Hz【0.00】
frequency
This parameter is used to monitor the auxiliary reference d0.09 Motor power 0.0%~200.0%【0.0】
frequency at normal operation mode.
This parameter is used to monitor the percentage of
drive’s output power that corresponding to the motor’s
d0.02 Preset frequency -300.0~300.0Hz【0.00】
rated power.

59
C D

d0.10 Motor estimated - 300.00 ~ 300.00Hz


BIT0:X1terminal status
frequency 【0.00】 BIT1:X2terminal status
BIT2:X3terminal status
This parameters is used to monitor the estimated motor BIT3:X4terminal status

rotor frequency under the condition of open-loop vector


BIT0:X5terminal status
BIT1
control. BIT2: Reserved
BIT3:

d0.11 Motor actual - 300.00 ~ 300.00Hz Fig.6-39 Input terminals status


frequency 【0.00】 This parameter is used to display the status of X1~X5.
This parameter is used to monitor the actual motor rotor 0 indicates OFF status,1 indicates ON status.
frequency measured by encoder under the condition of
close-loop vector control. d0.15 Output terminals status 0~1FH【0】

D
d0.12 Bus voltage 0~800V【0】
This parameter is used to monitor the drive’s bus BIT0:Y1 terminal status
BIT1:Reserved
voltage. BIT2:R01 relay status
BIT3:Reserved

d0.13 Drive operation


0000~FFFFH【0000】
status
Fig.6-40 Output terminal status
A B C D This parameter is used to display the status of output
terminals.When there is signal output,the corresponding
BIT0:0:Stop. 1:Run
BIT1:0:Forward. 1:Reverse bit will be set as 1.
BIT2:Operating at zero frequecy
BIT3:Accelerating

BIT0:Decelerating -10.00~10.00V【0.00】
BIT1:Operating at constant speed
d0.16 AI1 input
BIT2:Pre-commutation
BIT3:Tuning d0.17 AI2 input -10.00~10.00V【0.00】

BIT0:Over-current limiting d0.18 AI3 input -10.00~10.00V【0.00】


BIT1:DC over-voltage limiting
BIT2:Torque limiting d0.16~d0.18 are used to display the analog input value
BIT3 Reversed
before regulation.
BIT0:Drive fault
BIT1:Speed control
BIT2:Reserved
BIT3:Reserved
d0.19 Percentage of AI1 after
-100.0%~100.0%【0.0】
regulation
Fig.6-38 The drive’s operation status
d0.20 Percentage of AI2 after
-100.0%~100.0%【0.0】
regulation
d0.14 Input terminals status 00~FFH【00】
d0.21 Reserved
d0.19 ~ d0.21 are used to display the percentage of
analog input after regulation.

60
d0.22 AO1 output 0.0%~100.0%【0.0】 6.20 Group d1
d0.23 Reserved
d1.00 Fault record 1 0~50【0】
d0.22、d0.23 are used to diplay the percentage of analog
d1.01 Bus voltage of the latest
output that corresponding to the full range. 0~999V【0】
failure
d1.02 Actual current of the latest
d0.24 Process close-loop 0.0~999.9A【0】
-100.0%~100.0%【0.0】 failure
reference
d1.03 Operation frequency of the
d0.25 Process close-loop 0.00~300.0Hz【0.00】
-100.0%~100.0%【0.0】 latest failure
feedback
d1.04 Operation status of the
d0.26 Process close-loop 0~FFFFH【0000】
-100.0%~100.0%【0.0】 latest failure
error
d1.05 Fault record 2 0~50【0】
d0.27 Process close-loop
-100.0%~100.0%【0.0】 d1.06 Fault record 3 0~50【0】
output
CV100 support 50 kinds of protection alarm and can
record the latest three fault code (d1.00,d1.05,d1.06) and
d0.28 Temperature of heatsink 1 0.0~150.0℃【0.0】
bus voltage, current,operation frequency and operation
d0.29 Temperature of heatsink 2 0.0~150.0℃【0.0】
status of the latest fault.
Temperature of heatsink 1 is the temperature of IGBT
Fault record 1 is the latest fault record.
modules. Different IGBT modules have different
See Chapter 7 of failure and alarm information during
over-temperature threshold.
failures recently occurred for the ease of Trouble
Temperature of heatsink 2 is the temperature of rectifier.
Shooting and repair.
The drive of 30kW or below does not detect this
temperature. 6.21 Group d2
Temperature display range:0~100℃.Accuracy:5%
d2.00 Serial number 0~FFFF【100】
d2.01 Software version
d0.30 Total conduction time 0~65535 hours【0】 0.00~99.99【1.00】
number
d0.31 Total operating time 0~65535 hours【0】 d2.02 Custom-made version
0~9999【0】
d0.32 Total fan’s operating time 0~65535 hours【0】 number
d0.30 ~ d0.32 define the drive’s total conduction d2.03 Rated capacity 0~999.9KVA【Factory】
time,operating time and fan’s operating time after d2.04 Rated voltage 0~999V【Factory】
production. 0~999.9A【Factory 】
d2.05 Rated current
This group of parameters can be changed by user.
d0.33 ASR controller output -300.0~300.0%
(Corresponding to
rated torque of motor
d0.34 Reference torque -300.0~300.0%
(Corresponding to
rated torque of motor

61
Chapter 7 Troubleshooting

Table 7-1 list the possible faults of CV100, the fault code varies from E001 to E050. Once a fault occurs, you may
check it against the table and record the detailed phenomena before seeking service from your supplier.
Table 7-1 Faults and actions
Fault code Fault categories Possible reasons for fault Actions
Acc time is too short Prolong the Acc time
Atuo-tune the parameters of
Parameters of motor are wrong
motor
Over-current
Check the coded disc and the
E001 during Coded disc breaks down, when PG is running
connection
accerleration
Drive power is too small Select a higher power drive
Check and adjust V/F curve,
V/F curve is not suitable
adjust torque boost
Deceleration time is too short Prolong the Dec time
Over-current The load generates energy or the load inertial is too big Connect suitable braking kit
E002 during Check the coded disc and the
Coded disc breaks down, when PG is running
deceleration connection
Drive power is too small Select a higher power drive
Prolong Acceleration/
Acceleration /Deceleration time is too short
Deceleration time
Over-current in Sudden change of load or Abnormal load Check the load
E003 constant speed Low AC supply voltage Check the AC supply voltage
operation Check the coded disc and the
Coded disc breaks down, when PG is running
connection
Drive power is too small Select a higher power drive
E004 Over voltage Abnormal AC supply voltage Check the power supply
during Too short acceleration time Prolong accerlation time
acceleration
E005 Over voltage Too short Deceleration time (with reference to Prolong the deceleration time
during generated energy)
deceleration The load generates energy or the load inertial Connect suitable braking kit
is too big
Over voltage in Wrong ASR parameters, when drive run in the vector Refer to A5. ASR parameter
constant-speed control mode seting
operating Prolong Acceleration/
Acceleration /Deceleration time is too short
E006 process Deceleration time
Abnormal AC supply voltage Check the power supply
Abnormal change of input voltage Install input reactor
Too big load inertia Connect suitable braking kit

62
Fault code Fault categories Possible reasons for fault Actions
E007 Drive’s control Abnormal AC supply voltage Check the AC supply voltage
power supply or seek service
over voltage
E008 Input phase Any of phase R, S and T cannot be detected Check the wiring and
loss installation
Check the AC supply voltage
Check the drive’s output
Output phase wiring
E009 Any of Phase U, V and W cannot be detected
loss Check the cable and the
motor
Rewiring, please make sure
Short-circuit among 3-phase output or
the insulation of motor is
line-to-ground short circuit
good
Instantaneous over-current Refer to E001~E003
Clean the vent or replace the
Vent is obstructed or fan does not work
fan
Lower the ambient
Protections of Over-temperature
E010 temperature
IGBT act
Wires or connectors of control board are loose Check and rewiring
Current waveform distorted due to output
Check the wiring
phase loss
Auxiliary power supply is damaged or IGBT
Seek service
driving voltage is too low
Short-circuit of IGBT bridge Seek service
Control board is abnormal Seek service
Lower the ambient
Ambient over-temperature
IGBT module’s temperature
E011 heatsink Vent is obstructed Clean the vent
overheat Fan does not work Replace the fan
IGBT module is abnormal Seek service
Lower the ambient
Rectifier’s Ambient over-temperature
temperature
E012 heatsink
Vent is obstructed Clean the vent
overheat
Fan does not work Replace the fan
Atuo-tune the parameters of
Parameters of motor are wrong
motor
Select the drive with bigger
E013 Drive overload Too heavy load
power
Reduce the DC injection
DC injection braking current is too big
braking current and prolong

63
Fault code Fault categories Possible reasons for fault Actions
the braking time
Too short acceleration time Prolong accerlation time
Low AC supply voltage Check the AC supply voltage
Adjust V/F curve or torque
Improper V/F curve
boost value
Modify the motor’s overload
Improper motor’s overload protection threshold
protection threshold.
Motor is locked or load suddenly become too big Check the load
Use a special motor if the
Motor Common motor has operated with heavy load
E014 motor is required to operate
over-load at low speed for a long time.
for a long time.
Low AC supply voltage Check the AC supply voltage
Set V/F curve and torque
Improper V/F curve
boost value correctly
external Terminal used for stopping the drive in Disconnect the terminal if the
E015
equipment fails emergent status is closed external fault is cleared
EEPROM R/W Press STOP/RST to reset,
E016 R/W fault of control parameters
fault seek service
E017 reserved reserved reserved
Low AC supply voltage Check the AC supply voltage
Replace the contactor in main
Contactor damaged
circuit and seek service
Contactor not
E018 Replace the soft start resistor
closed Soft start resistor is damaged
and seek service
Control circuit is damaged Seek service
Input phase loss Check the wiring of R, S, T.

Current Wires or connectors of control board are loose Check and re-wire

detection Auxiliary power supply is damaged Seek service


E019
circuit Hall sensor is damaged Seek service
fails Amplifying circuit is abnormal Seek service
Press STOP/RST key to reset
Terrible interference or add a power filter in front of
System
E020 power supply input
interference
Press STOP/RST key or seek
DSP in control board read/write by mistake
service.
Update the panel’s
Panel’s parameters are not complete or the parameters and version again.
Parameter copy
E023 version of the parameters are not the same First set b4.04 to 1 to upload
error
as that of the main control board the parameters and then set
b4.04 to 2 or 3 to download

64
the parameters.
Panel’s EEPROM is damaged Seek service
Auto-tuning Improper settings of parameters on the Set the parameters correctly
E024
fault nameplate according to the nameplate
Fault code Fault categories Possible reasons for fault Actions
Prohibiting contrarotation Auto-tuing during rollback Cancel prohibiting rollback
Check the motor’s wiring
Check the set value of
A0.10(upper limiting
Overtime of auto-tuning
frequency), make sure if it is
lower than the rated
frequency or not
Check the wiring of the
E025 PG fails With PG vector control, the signal of encoder is lost
encoder, and re-wiring
The load of Check the situation of the
E026 The load is lost or reduced
drive is lost load
E027 Brake unit fault Brake tube is broken Seek service
E028~E0 Reserved
50

Note:
The short circuit of the brake resistance can lead to the damage of brake unit fault.

Table 7-2 Abnormal phenomena and handling methods


Phenomena Conditions Possible reasons of fault Actions
In stopping status, first press ENTER and
hold on, then press ∨ 3 times
Panel is locked up continuously to unlock the panel
No response Part of the keys or
Power-on the drive after it shuts down
of operation all the keys are
completely
panel disabled
Panel’s cables are not well
Check the wiring
connected.
Panel’s keys are damaged. Replace operation panel or seek service
Parameters are not allowed
Operating status
Settings of changing during Change the parameters at STOP status
cannot be changed
parameters operation
cannot be Part of parameters b4.02 is set to 1 or 2 Set b4.02 to 0
changed cannot be Parameters are actually detected, Do not try to change these parameters,
changed. not allowed changing users are not allowed to chaged these
MENU is disabled Panel is locked up See “No response of operation panel”

65
Phenomena Conditions Possible reasons of fault Actions

Parameter not
displayed when User’s password is required Input correct user’s password
pressing MENU.

Instead, “0.0.0.0.”
Seek service
is displayed

The drive stops Fault alarm occurs Find the fault reason and reset the drive

and its “RUN” AC supply is interrupted Check the AC supply condition


LED is off, while Check the setting of relevant
Control mode is changed
there is no parameters
“STOP” command
Logic of control terminal changes Check the settings of A6.13
Auto-reset upon a fault Check the setting of auto-reset
The drive Stopping command is input from Check the setting of this external
stops during Motor stops when
external terminal terminal
operating there is no
Preset frequency is 0 Check the frequency setting
process stopping
Start frequency is larger than
command, while Check the start frequency
preset frequency
the drive’s “RUN”
Skip frequency is set incorrectly Check the setting of skip frequency
LED illuminates
and operates at Enable “ Ban forwarding” when
Check the set of terminal funtion
zero frequency run forward
Enable “Ban revesing” when run
Check the set of terminal function
reversely
Terminal used for coasting to stop Check the terminal used for coasting to
is enabled stop
Terminal used for prohibiting
Check the terminal used for prohibiting
running
running of the drive is enabled.
of the drive is enabled.
The drive does not
Terminal used for stopping the Check the terminal used for stopping the
work and its
The drive drive is enabled drive
“RUN” LED is off
does not work In 3-wire control mode, the
when the “RUN”
key is pressed. terminal used to control the 3-wire Set and close the terminal
operation is not closed.
Fault alarm occurs C Clear the fault
Positive and negative logic of
input Check the setting of A6.13
terminal are not set correctly
“P.oFF” Since the transistor or contactor is
Transistor or
is reported disconnected, the bus voltage
contactor Run the drive until the transistor or
when the drive drops at heavy load, therefore, the
disconnected and contactor is connected.
begin to run drive
overload
immediately displays P.Off, not E018

66
Phenomena Conditions Possible reasons of fault Actions
after message
power-on.

67
Chapter 8 Maintenance

Many factors such as ambient temperature, humidity, dust, vibration, internal component aging, wear and tear will give
rise to the occurrence of potential faults. Therefore, it is necessary to conduct routine maintenance to the drives.
Notes:
As safety precautions, before carrying out check and maintenance of the drive, please ensure that :
The drive has been switched off;
The charging LED lamp inside the drive is off.
Use a volt-meter to test the voltage between terminals (+) and (-) and the voltage should be below 36V.

8.1 Daily Maintenance


The drive must be operated in the environment specified in the Section 2.1. Besides, some unexpected accidents may
occur during operation. You should maintain the drive conditions according to the table below, record the operation
data, and find out problems in the early stage.
Table 8-1 Daily checking items
Instructions
Items Criterion
Items Cycle Checking methods
Temperature and Thermometer and
-10℃~+40℃,
Operating humidity hygrometer
Any time derating at 40℃~50
environment Dust and water dripping Visual inspection

Gas olfactometry
Stable vibration and
Vibration and heating Touch the case proper
Drive Any time
temperature
Noise Listen No abnormal sound
Heating Touch by hand No overheat
Motor Any time Low and regular
Noise Listen
noise
Output current Current meter Within rated range
Operating
Output voltage Volt-meter Within rated range
status Any time
Temperature rise is
parameters Internal temperature Thermometer
less than 35℃

8.2 Periodical Maintenance


Customer should check the drive every 3 months or 6 months according to the actual environment.
Notes:
1. Only trained personnel can dismantle the drive to replace or repair components;
2. Don't leave metal parts like screws or pads inside the drive; otherwise the equipment may be damaged.

68
General Inspection:

1. Check whether the screws of control terminals are loose. If so, tighten them with a screwdriver;
2. Check whether the main circuit terminals are properly connected; whether the mains cables are over heated;
3. Check whether the power cables and control cables are damaged, check especially for any wear on the cable tube;
4. Check whether the insulating tapes around the cable lugs are stripped;
5. Clean the dust on PCBs and air ducts with a vacuum cleaner;
6. For drives that have been stored for a long time, it must be powered on every 2 years. When supplying AC
power to the drive, use a voltage regulator to raise the input voltage to rated input voltage gradually. The drive
should be powered for 5 hours without load.
7. Before performing insulation tests, all main circuit input/output terminals should be short-circuited with conductors.
Then proceed insulation test to the ground. Insulation test of single main circuit terminal to ground is forbidden;
otherwise the drive might be damaged.
Please use a 500V Mega-Ohm-Meter.
8. Before the insulation test of the motor, disconnect the motor from the drive to avoid damaging it.
Note:
Dielectric Strength test of the drive has already been conducted in the factory. Do not do the test again, otherwise, the
internal components might be damaged.
Using different component to substitute the original component may damage the dirver.

8.3 Replacing Wearing Parts


The components that are easily damaged are: cooling fan and electrolytic capacitors of filters. Their lifetime depends
largely on their application environment and preservation. Normally, lifetime is shown in following table.
Table 8-2 Lifetime of components
Components Lifetime
Fan 3~40,000 hours
electrolytic capacitor 4~50,000 hours
Relay About 10,000 times
You can decide the time when the components should be replaced according to their service time.

1.Cooling fan
Possible cause of damages: wear of the bearing, aging of the fan vanes.
Criteria:After the drive is switched off, check whether abnormal conditions such as crack exists on fan vanes and other
parts. When the drive is switched on, check whether drive running is normal, and check whether there is any abnormal
vibration.
2. Electrolytic capacitors
Possible cause of damages: high ambient temperature, aging of electrolyte and large pulse current caused by rapid
changing loads.
Criteria: Check if there is any leakage of liquids. Check if the safety valve protrudes. Measure static capacitance and
insulation resistance.
3.Relay
Possible cause of damages: corrosion, frequent-switching.
Criteria: Check whether the relay has open and shut failure.

69
8.4 Storage
The following points must be followed for the temporary and long-term storage of drive:
1. Store in locations free of high temperature, humidity, dust, metal powder, and with good ventilation.
2. Long-term storage will cause the deterioration of electrolytic capacitors. Therefore, the drive must be switched on
for a test within 2 years at least for 5 hours. The input voltage must be boosted gradually by the voltage regulator to the
rated value.

70
Chapter 9 List of Parameters

CV100 series VFD’s parameters are organized in groups. Each group has several parameters that are identified by
“Group No.+ Function Code. There are AX,YZ letters in other content in this manual,it indicate the YZ function code
in group X.For example,“A6.08” belongs to group A6 and its function code is 8.
The parameter descriptions are listed in the tables below.
Table 9-1 Descriptions of Function Code Parameter Structure Table
No. Name Description
1 Function code The number of function code
2 Name The name of function code
3 Setting range The setting range of parameters.
4 Unit The minimum unit of the setting value of parameters.
5 Factory setting The setting value of parameters after the product is delivered
The “modification” column in the parameter table means whether the parameter can be
modified.
“○”:Denotes the parameters can be modified during operation or at STOP state;
“×”:Denotes the parameters cannot be modified during operating;
6 Modification
“* ”:Denotes the parameters are actually detected and cannot be revised;
“—”:Denotes the parameters are defaulted by factory and cannot be modified ;
( When you try to modify some parameters, the system will check their modification
property automatically to avoid mis-modification.)
Note:
1 . Parameter settings are expressed in decimal (DEC) and hexadecimal (HEX). If the parameter is expressed in
hexadecimal, the bits are independent to each other.The value of the bits can be 0~F.
2.“Factory settings” means the default value of the parameter. When the parameters are initialized, they will resume
to the factory settings. But the actual detected or recorded parameters cannot be initialized;

It is defaulted that no parameters except A0.03 are allowed changing. If you need change them, please
first set b4.02(parameter write-in protection) from 1 to 0.

Table 9-2 List of Parameters


Function Factory Setting
Name Descriptions Unit Modif.
code setting range
Group A0:Basic operating parameters
A0.00 User password 0:No password protection. 1 0 ○ 0~FFFF
Others:Password protection.
A0.01 Control mode 0:Vector control without PG 1 0 × 0~2
1:Vector control with PG

71
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
2: V/F control
A0.02 Main reference 0:Digital setting 1 0 ○ 0~5
frequency selector 1:AI1
2:AI2
3:Potentiometer

A0.03 Set the operating A0.11~A0.10 0.01Hz 50.00 ○ 0~30000


frequency in
digital mode
A0.04 Methods of 0:Panel control 1 1 ○ 0~2
inputting operating 1:Terminal control
commands
2:Communication control
A0.05 Set running 0:Forward 1:Reverse 1 0 ○ 0~1
direction
A0.06 Acc time 1 0.0~6000.0 0.1S 2KW or ○ 0~60000
below:6.
0S
30KW~
45KW:2
0.0S
45KW
or
above:30
.0S
A0.07 Dec time 1 0.0~6000.0 0.1S 2KW or ○ 0~60000
below:6.
0S
30KW~
45KW:2
0.0S
45KW
or
above:30
.0S
A0.08 Max. output upper limit of frequency A0.11~ 0.01Hz 50.00 × 0~30000
frequency 300.00Hz

72
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
A0.09 Max. output 0~480 1V VFD’s × 0~480
voltage rated
values
A0.10 Upper limit of A0.12~A0.08 0.01Hz 50.00 ○ 0~30000
frequency
A0.11 Lower limit of 0.00~A0.11 0.01Hz 0.00 ○ 0~30000
frequency
A0.12 Basic operating 0.00~Max.output frequency 0.01Hz 50.00 ○ 0~30000
frequency A0.08
A0.13 Torque boost 0.0%(Auto)
,0.1%~30.0% 0.1% 0.0% ○ 0~300

Group A1:Start and stop parameters


A1.00 Starting mode 0 Start from the starting frequency 1 0 × 0~2
1 Brake first and then start
2 Start on the fly(including
direction judgement), start at
starting frequency

A1.01 Starting frequency 0.00~60.00Hz 0.01Hz 0.00Hz ○ 0~6000


A1.02 Holding time of 0.00~10.00s 0.01s 0.00s ○ 0~1000
starting frequency
A1.03 DC injection 0.0%~100.0% drive’s rated current 0.1% 0.0% ○ 0~1000
braking current at
start
A1.04 DC injection 0.00(No action) 0.01s 0.00s ○ 0~3000
braking 0.01~30.00s
time at start
A1.05 Stopping mode 0:Dec-to-stop 1 0 × 0~2

1:Coast-to-stop
2 : Dec-to-stop+DC injection
braking
A1.06 DC injection 0.00~60.00Hz 0.01Hz 0.00Hz ○ 0~6000
braking initial
frequency at stop
A1.07 Injection braking 0.00~10.00s 0.01s 0.00s ○ 0~1000
waiting time at
stop

73
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
A1.08 DC injection 0.0%~100.0% drive’s rated current 0.1% 0.0% ○ 0~1000
braking current at
stop
A1.09 DC injection 0.0(No action) 0.01s 0.00s ○ 0~3000
braking time at 0.01~30.00s
stop
A1.10 Restart after power 0:Disable 1 0 × 0~1
failure 1:Enable
A1.11 Delay time for 0.0~10.0s 0.1s 0.0s ○ 0~100
restart after power
failure
A1.12 Anti-reverse 0:Disabled 1 0 × 0~1
running function 1:Enabled (It will operate at zero
frequency when input a reverse
command)
A1.13 Delay time of run 0.00~360.00s 0.01s 0.00s ○ 0~36000
reverse/forward
A1.14 Switch mode of 0:Switch when pass 0Hz 1 0 × 0~1
run 1 : Switch when pass starting
reverse/forward frequency
(Reserved)
A1.15 Detecting 0.00~150.00Hz 0.01Hz 0.10Hz × 0~15000
frequency of stop
A1.16 Action voltage of 650~750V 1 720 × 650~750
braking unit
A1.17 Dynamic braking 0:Disable 1 0 × 0~1

1:Enable
A1.18 Ratio of working 0.0~100.0% 0.1% 80.0% ○ 0~1000
time of braking
unit to drive’s total
working time
Group A2:Frequency setting
A2.00 Auxiliary 0:No auxiliary reference frequency 1 0 ○ 0~5
reference 1:AI1
frequency selector
2:AI2
3:Reserved

74
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
4:Reserved
5:Output by PID process
A2.01 Main and auxiliary 0:+ 1 0 ○ 0~3
reference 1:-
frequency
2:MAX(Main reference,Auxiliary
calculation
reference)
3:MIN(Main reference,Auxiliary
reference)
A2.02 UP/DN rate 0.01~99.99Hz/s 0.01 1.00 ○ 1~9999
A2.03 UP/DN regulating Unit’s place of LED: 1 00 ○ 0~11H
control 0 : Save reference frequency upon
power outage
1 : Not save reference frequency
upon power outage.
Ten’s place of LED:
0 : Hold reference frequency at
stop
1:Clear reference frequency at stop
Hundred’s place of LED:
0:UP/DN integral time valid
1:UP/DN speed value
A2.04 Jog operating 0.10~50.00Hz 0.01Hz 5.00 ○ 10~5000
frequency
A2.05 Interval of Jog 0.0~100.0s 0.1s 0.0 ○ 0~1000
operation
A2.06 Skip frequency 1 0.00~300.00Hz 0.01Hz 0.00 × 0~30000
A2.07 Range of skip 0.00~30.00Hz 0.01Hz 0.00 × 0~3000
frequency 1
A2.08 Skip frequency 2 0.00~300.00Hz 0.01Hz 0.00 × 0~30000
A2.09 Range of skip 0.00~30.00Hz 0.01Hz 0.00 × 0~3000
frequency
A2.10 Skip frequency 3 0.00~300.00Hz 0.01Hz 0.00 × 0~30000
A2.11 Range of skip 0.00~30.00Hz 0.01Hz 0.00 × 0~3000
frequency 3
Group A3:Setting curve

75
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
A3.00 Reference LED unit’s place : AI1 curve 1 0000 ○ 0~3333H
frequency selection
curve selection 0:Curve 1
1:Curve 2
2:Curve 3
3:Curve 4
LED ten’s place : AI2 curve
selection
0:Curve 1
1:Curve 2
2:Curve 3
3:Curve 4
LED hundred’s place:Reserved
LED thousand’s place:Reserved
A3.01 Max reference of A3.03~110.00% 0.01% 100.00% ○ 0~11000
curve 1
A3.02 Actual value Reference frequency: 0.01% 100.00% ○ 0~10000
corresponding to 0.0~100.00%Fmax
the Max reference Torque:0.0~300.00%Te
of curve 1
A3.03 Min reference of 0.0%~A3.01 0.01% 0.00% ○ 0~11000
curve 1
A3.04 Actual value The same as A3.02 0.01% 0.00% ○ 0~10000
corresponding to
the Min reference
of curve 1
A3.05 Max reference of A3.07~110.00% 0.01% 100.00% ○ 0~11000
curve 2
A3.06 Actual value The same as A3.02 0.01% 100.00% ○ 0~10000
corresponding to
the Max reference
of curve 2
A3.07 Min reference of 0.0%~A3.05 0.01% 0.00% ○ 0~11000
curve 2
A3.08 Actual value The same as A3.02 0.01% 0.00% ○ 0~10000
corresponding to

76
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
the Min reference
of curve 2
A3.09 Max reference of A3.11~110.00% 0.01% 100.00% ○ 0~11000
curve 3
A3.10 Actual value The same as A3.02 0.01% 100.00% ○ 0~10000
corresponding to
the Max reference
of curve 3
A3.11 Min reference of 0.0%~A3.09 0.01% 0.00% ○ 0~11000
curve 3
A3.12 Actual value The same as A3.02 0.01% 0.00% ○ 0~10000
corresponding to
the Min reference
of curve 3
A3.13 Max reference of A3.15~110.00% 0.01% 100.00% ○ 0~11000
curve 4
A3.14 Actual value The same as A3.02 0.01% 100.00% ○ 0~10000
corresponding to
the Max reference
of curve 4
A3.15 Reference of A3.17~A3.13 0.01% 100.00% ○ 0~11000
inflection point 2
of curve 4
A3.16 Actual value The same as A3.02 0.01% 100.00% ○ 0~10000
corresponding to
the Min reference
of inflection point
2 of curve 4
A3.17 Reference of A3.19~A3.15 0.01% 0.00% ○ 0~11000
inflection point 1
of curve 4
A3.18 Actual value The same as A3.02 0.01% 0.00% ○ 0~10000
corresponding to
the Min reference
of inflection point
1 of curve 4
A3.19 Min reference of 0.0%~A3.17 0.01% 0.00% ○ 0~11000

77
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
curve 4
A3.20 Actual value The same as A3.02 0.01% 0.00% ○ 0~10000
corresponding to
the Min reference
of curve 4
Group A4:Acc/Dec parameters
A4.00 Acc/Dec mode 0:Linear Acc/Dec 1 0 × 0~1

1:S Curve
A4.01 Acc time 2 0.0~6000.0 0.1S 20.0S ○ 0~60000
A4.02 Dec time 2 0.0~6000.0 0.1S 20.0S ○ 0~60000
A4.03 Acc time 3 0.0~6000.0 0.1S 20.0S ○ 0~60000
A4.04 Dec time 3 0.0~6000.0 0.1S 20.0S ○ 0~60000
A4.05 Acc time 4 0.0~6000.0 0.1S 20.0S ○ 0~60000
A4.06 Dec time 4 0.0~6000.0 0.1S 20.0S ○ 0~60000
A4.07 S curve acceleration 10.0%~50.0%(Acc time) 0.1% 20.0% ○ 100~500
starting time A4.07+ A4.08≤90%
A4.08 S curve acceleration 10.0%~70.0%(Acc time) 0.1% 20.0% ○ 100~800
ending time A4.07+ A4.08≤90%
A4.09 S curve deceleration 10.0%~50.0%(Dec time) 0.1% 20.0% ○ 100~500
starting time A4.09+ A4.10≤90%
A4.10 S curve deceleration 10.0%~70.0%(Dec time) 0.1% 20.0% ○ 100~800
ending time A4.09+ A4.10≤90%
A4.11 Quick start-stop 0:Disable 1 0 × 0~3
selctor 1:Quick start,normal stop
2:Normal start,quick stop
3:Quick start,quick stop
A4.12 Start ACR-P 0.1~200.0 0.1 20.0 ○ 1~2000
A4.13 Start ACR-I 0.000~10.000S 0.001S 0.200s ○ 0~10000
A4.14 Start AVR-P 0.1~200.0 0.1 20.0 ○ 1~2000
A4.15 Start AVR-I 0.000~10.000S 0.001S 0.200s ○ 0~10000
A4.16 Stop ACR-P 0.1~200.0 0.1 20.0 ○ 1~2000
A4.17 Stop ACR-I 0.000~10.000S 0.001S 0.200s ○ 0~10000
A4.18 Stop AVR-P 0.1~200.0 0.1 20.0 ○ 1~2000
A4.19 Stop AVR-I 0.000~10.000S 0.001S 0.200s ○ 0~10000
Group A5:Control parameters

78
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
A5.00 Speed/torque 0:Speed control mode 1 0 × 0~1
control mode 1:Torque control mode
A5.01 ASR1-P 0.1~200.0 0.1 20.0 ○ 1~2000
A5.02 ASR1-I 0.000~10.000S 0.001S 0.200s ○ 0~10000
A5.03 ASR1 output filter 0~8(Corresponding to 1 0 ○ 0~8
0~2^8/10ms)
A5.04 ASR2-P 0.1~200.0 0.1 20.0 ○ 1~2000
A5.05 ASR2-I 0.000~10.000S 0.001S 0.200s ○ 0~10000
A5.06 ASR2 output filter 0~8(Corresponding to 1 0 ○ 0~8

0~2^8/12.5ms)
A5.07 ASR1/2 switching 0.0%~100.0% 0.1 10.0% ○ 0~1000
frequency
A5.08 Maximum speed 0.0%~+100.0% 0.1% 100.0% ○ 0~1000
limit for forward
running when
torque control
A5.09 Maximum speed 0.0%~+100.0% 0.1% 100.0% ○ 0~1000
limit for reverse
running when
torque control
A5.10 Driving torque 0.0%~+300.0% 0.1% 180.0% ○ 0~3000
limit
A5.11 Braking torque 0.0%~+300.0% 0.1% 180.0% ○ 0~3000
limit
A5.12 Reserved
A5.13 Reserved
A5.14 Reserved
A5.15 Reserved
A5.16 Reserved
A5.17 ACR-P 1~5000 1 1000 ○ 1~5000
A5.18 ACR-I 0.5~100.0mS 0.1 8.0 ○ 5~1000
Group A6:Control terminals parameters
A6.00~A Multi-function 0:No function 1 0 × 0~41
6.04 terminal X1~X5 1:Forward
2:Reverse

79
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
3:Forward jog operation
4:Reverse jog operation
5:3-wire operation control
6:External RESET signal input
7:External fault signal input
8:External interrupt signal input
9:Drive operation prohibit
10:External stop command
11:DC injection braking command
12:Coast to stop
13:Frequency ramp up (UP)
14:Frequency ramp down (DN)
15:Switch to panel control
16:Switch to terminal control
17 : Switch to communication
control mode
18 : Main reference frequency via
AI1
19 : Main reference frequency via
AI2
20:Reserved
21 : Main reference frequency via
DI
22 : Auxiliary reference frequency
invalid
23 : Auxiliary reference frequency
via AI1 (Reserved)
24 : Auxiliary reference frequency
via AI2 (Reserved)
25:(Reserved)
26 : Auxiliary reference frequency
via DI (Reserved)
27:Preset frequency 1
28:Preset frequency 2

80
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
29:Preset frequency 3
30:Preset frequency 4
31:Acc/Dec time 1
32:Acc/Dec time 2
33 : Multiple close-loop reference
selection 1
34:Multiple close-loop
reference selection 2
35:Multiple close-loop
reference selection 3
36:Multiple close-loop
reference selection 4
37:Forward prohibit
38:Reverse prohibit
39:Acc/Dec prohibit
40:Process close-loop prohibit
41:Reserved
42 : Main frequency switch to
digital setting
43:PLC pause
44:PLC prohibit
45:PLC stop memory clear
46:Swing input
47:Swing reset
48~49:Reserved
50:Timer 1 start
51:Timer 2 start
53:Counter input
54:Counter clear
Others:Reserved
A6.08 Terminal filter 0~500ms 1 10 ○ 0~500
A6.09 Terminal control 0:2-wire operating mode 1 1 0 × 0~3
mode selection 1:2-wire operating mode 2
2:3-wire operating mode 1

81
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
3:3-wire operation mode 2
A6.10 Reserved
A6.11 Reserved
A6.12 Reserved
A6.13 Input terminal’s Binary setting 1 00 ○ 0~FFH
positive and 0 : Positive logic: Terminal Xi is
negative logic enabled if it is connected to
corresponding common terminal,
and disabled if it is disconnected.
1 : Negative logic: Terminal Xi is
disabled if it is connected to
corresponding common terminal,
and enabled is it is disconnected.
Unit’s place of LED:BIT0~BIT3 :
X1~X4
Ten’s place of LED:BIT0~BIT2 :
X5
6.14 Bi-direction 0:Running signal(RUN) 1 0 × 0~50
pen-collector 1:frequency arriving signal(FAR)
output terminal Y1
2:frequency detection threshold
(FDT1)
3:frequency detection threshold
(FDT2)
4:overload signal(OL)
5:low voltage signal(LU)
6:external fault signal(EXT)
7:frequency high limit(FHL)
8:frequency low limit(FLL)
9:zero-speed running
10:Terminal X1(Reserved)
11:Terminal X2(Reserved)
12 : PLC running step complete
signal
13 : PLC running cycle complete
signal

82
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
14:Swing limit
15:Drive ready (RDY)
16:Drive fault
17:Switching signal of host
18:Reserved
19:Torque limiting
20: Drive running forward/reverse
21: Timer 1 reach
22: Timer 2 reach
23: Preset counter reach
24: Intermediate counter reach
Others:Reserved
A6.15 Bi-direction Same as A6.14 1 1 × 0~50
pen-collector
output terminal Y2
A6.16 Output functions The same as A6.14 1 15 × 0~50
of relay R1
A6.17 Reserved 1 16 × 0~20
A6.18 Ouput terminal’s Binary setting: 1 0 ○ 0~1FH
positive and 0: Terminal is enabled if it is
negative logic connected to
corresponding common terminal,
and disabled if it is disconnected.
1: Terminal is disabled if it is
connected to
corresponding common terminal,
and
enabled is it is disconnected.
Unit’s place of LED:
BIT0~BIT3:Y1、R1
Ten’s place of LED:
BIT0:
A6.19 Frequency arriving 0.00~300.00Hz 0.01Hz 2.50Hz ○ 0~30000
signal (FAR)
A6.20 FDT1 level 0.00~300.00Hz 0.01Hz 50.00Hz ○ 0~30000
A6.21 FDT1 lag 0.00~300.00Hz 0.01Hz 1.00Hz ○ 0~30000

83
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
A6.22 FDT2 level 0.00~300.00Hz 0.01Hz 25.00Hz ○ 0~30000
A6.23 FDT2 lag 0.00~300.00Hz 0.01Hz 1.00Hz ○ 0~30000
A6.24 Virtual terminal Binary setting 1 00 ○ 0~FFH
setting 0:Disable
1:Enable
Unit’s place of LED:
BIT0~BIT3:X1~X4
Ten’s place of LED:
BIT0~BIT2:X5
A6.25 Reserved
A6.25 Reserved

A6.26 Reserved
A6.27 Reserved
A6.28 Functions of 0:No function 1 0 ○ 0~36
terminal AO1 1 : Output frequency ( 0~ Max.
output frequency)
2:Preset frequency(0~ Max. output
frequency)
3:Preset frequency(After Acc/Dec)
(0~ Max. output frequency)
4:Motor speed(0~ Max. speed)
5:Output current(0~2*Iei)
6:Output current(0~2*Iem)
7:Output torque(0~3*Tem)
8:Output power(0~2*Pe)
9:Output voltage(0~1.2*Ve)
10:Bus voltage(0~800V)
11:AI1
12:AI2
13:Reserved
14:Reserved
15:Percentage of host(0~4095)
16~36:Reserved

84
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
A6.29 Functions of Same as A6.28 1 0 ○ 0~36
terminal AO2
A6.30 Gain of AO1 0.0%~200.0% 0.1% 100.0% ○ 0~2000
A6.31 Zero offset -100.0%~100.0% 0.1% 0.0 ○ 0~2000
calibration of AO1
A6.32 Reserved
A6.33 Reserved
A6.34 AI1 filter 0.01~10.00s 0.01s 0.05 ○ 1~1000
A6.35 AI2 filter 0.01~10.00s 0.01s 0.05 ○ 1~1000
A6.36 Reserved
A6.37 Setting value of 0.0~10.0s 0.1s 0.0 ○ 1~100
timer 1
A6.38 Setting value of 0~100s 1s 0 ○ 1~100
timer 2
A6.39 Target value of 0~65535 1 100 ○ 0~65535
counter
A6.40 Intermediate value 0~65535 1 50 ○ 0~65535
of counter
Group A7:Reserved
Group A8:Fault parameters
A8.00 Protective action Unit’s place of LED: 1 0000 × 0~1111H
of relay Action selection for under-voltage
fault indication.
0:Disable
1:Enable
Ten’s place of LED:
Action selection for auto reset
interval fault indication.
0:Disable
1:Enable
Hundred’s place of LED:
Selection for fault locked function.
0:Disable
1:Enable
Thousand’place of LED:
Reserved

85
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
A8.01 Fault masking Unit’s place of LED: 1 0000 × 0~2222H
selection 1 Communication fault masking
selection
Ten’s place of LED:
Relay faultmasking selection
Hundred’s place of LED:
EEPROMfault masking selection
Thousand’s place of LED:
Reserved
0:Disable.Stop when fault
happen
1:Disable.Continue operating
when fault happen
2:Enable
A8.02 Fault masking Unit’s place of LED: 1 00 × 0~22H
selection 2 Open phase fault masking selection
for input
Ten’s place of LED:
Open phase fault masking selection
for output
0:Disable.Stop when fault happen
1:Disable.Continue operating when
fault happen
2:Enable
A8.03 Motor overload 0: Disabled 1 1 × 0~2
protection mode 1:Common mode (with low speed
selection compensation)
2: Variable frequency motor
(without low speed compensation)
A8.04 Auto reset times 0:No function 1 0 × 0~100

1~100:Auto reset times


Note: The IGBT protection (E010)
and external equipment fault (E015)
cannot be reset automatically.
A8.05 Reset interval 2.0~20.0s/time 0.1s 5.0s × 20~200
A8.06 Fault locking 0:Disable. 1 0 × 0~1
function selection. 1:Enable.

86
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
Group b0:Motor parameters
b0.00 Rated power 0.4~999.9KW 0.1 0 × 4~9999
b0.01 Rated voltage 0~ rated volotage of drive 1 0 × 0~999
b0.02 Rated current 0.1~999.9A 0.1A Depende × 1~9999
nt
on
drive’s
model
b0.03 Rated frequency 1.00~1000.00Hz 0.01Hz Depende × 100~3000
nt 0
on
drive’s
model
b0.04 Number of 2~24 1 4 × 2~24
polarities of motor
b0.05 Rated speed 0~60000RPM 1RPM 1440RP × 0~60000
M
b0.06 Resistance of 0.00%~50.00% 0.01% Depende × 0~5000
stator %R1 nt
on
drive’s
model
b0.07 Leakage 0.00%~50.00% 0.01% Depende × 0~5000
inductance %Xl nt
on
drive’s
model
b0.08 Resistance of rotor 0.00%~50.00% 0.01% Depende × 0~5000
%R2 nt
on
drive’s
model
b0.09 Exciting 0.0%~2000.0% 0.1% Depende × 0~20000
inductance %Xm nt
on
drive’s
model

87
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
b0.10 Current without 0.1~999.9A 0.1A Depende × 1~9999
load I0 nt on
drive’s
model
b0.11 Auto-tuning 0: Auto-tuning is disabled 1 0 × 0~3
1: Stationary auto-tuning (Start
auto-tuning to a standstill motor)
2: Rotating auto-tuning
3:Reserved.
b0.12 Motor’s overload 20.0%~110.0% 0.1% 100.0% × 200~1100
protection
coefficient
b0.13 Oscillation 0~255 1 10 ○ 0~255
inhibition
coefficient
Group b1:V/F parameters
b1.00 V/F curve setting 0:V/F curve is defined by user 1 0 × 0~3

1:2-order curve
2:1.7-order curve
3:1.2-order curve
b1.01 V/F frequency B1.03~A0.08 0.01Hz 0.00Hz × 0~30000
value F3
b1.02 V/F voltage value B1.04~100.0% 0.1% 0.0% × 0~1000
V3
b1.03 V/F frequency B1.05 ~B1.01 0.01Hz 0.00Hz × 0~30000
value F2
b1.04 V/F voltage value B1.06~B1.02 0.1% 0.0% × 0~1000
V2
b1.05 V/F frequency 0.00~B1.03 0.01Hz 0.00Hz × 0~30000
value F1
b1.06 V/F voltage value 0~B1.04 0.1% 0.0% × 0~1000
V1
b1.07 Cut-off point used 0.0%~50.0%( Corresonding to 0.1% 10.0% ○ 0~500
for manual torque A0.12)
boost
b1.08 AVR function 0:Disable 1 2 × 0~2

88
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
1:Enable all the time
2:Disabled in Dec process
Group b2:Enhanced parameters
b2.00 Carrier wave 2.0~15.0KHz 0.1 8.0 ○ 20~150
frequency
b2.01 Auto adjusting of 0:Disable 1 1 ○ 0~1
CWF 1:Enable
b2.02 Voltage adjustment Unit’s place of LED: 1 001 × 0~111H
selection Over-voltage at stall Selection
0:Disable(When install brake
resistor)
1:Enable
Ten’s place of LED:
Not stop when instantaneous stop
function selection
0:Disable
1:Enable(Low voltage
compensation)
Hundred’s place of LED:
Overmodulation selection
0:Disable
1:Enable
b2.03 Overvoltage point 120.0%~150.0%Udce 0.1% 140.0% × 1200~150
at 0
stall
b2.04 Droop control 0:Disable,0.01~10.00Hz 0.01 0.00Hz ○ 0~1000
b2.05 Auto current 20.0%~200.0%Ie 0.1% 150.0% × 200~2000
limiting threshold
b2.06 Frequency 0.00~99.99Hz/s 0.01Hz/ 10.00 ○ 0~9999
decrease S Hz/s
rate when current
limiting
b2.07 Auto current 0:Invalid at constant speed 1 1 × 0~1
limiting 1:Valid at constant speed
selection Note:It is valid all the time at
Acc/Dec

89
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
b2.08 Gain of Slip 0.0~300.0% 0.1% 100.0% ○ 0~3000
compensation
b2.09 Slip compensation 0.0~250.0% 0.1% 200.0% ○ 0~2500
limit
b2.10 Slip compensation 0.1~25.0s 0.1s 2.0s ○ 0~250
time constant
b2.11 auto energy-saving 0:Disable 1 0 × 0~1
function 1:Enable
b2.12 Frequency 0.00~99.99Hz/s 0.01Hz/ 10.00 ○ 0~9999
decrease S Hz/s
rate at voltage
compensation

b2.13 Zero-frequency 0.00~300.00Hz 0.01Hz 0.50Hz ○ 0~30000


operation
threshold
b2.14 Zero-frequency 0.00~300.00Hz 0.01Hz 0.00Hz ○ 0~30000
Hysteresis
(Reserved)
b2.15 Fan control 0:Auto operation mode 1 0 × 0~1
1:Fan operate continuously when
power is on
Note: 1.Continue to operate for 3
minutes .
2.This parameter is only valid for
drive of power above 7.5KW.
Group b3:Communication parameter
b3.00 Communication Unit’s place of LED: 1 001 × 0~155H
configuration Baud rate selection
0:4800BPS
1:9600BPS
2:19200BPS
3:38400BPS
4:115200BPS
5:125000BPS
Ten’s place of LED:

90
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
Data format
0:1-8-2-N format,RTU
1:1-8-1-E format,RTU
2:1-8-1-O format, RTU
3:1-8-2-N format,ASCII
4:1-8-1-E format,ASCII
5:1-8-1-O format,ASCII
Hundred’s place of LED:
wiring mode
0:Direct connection via cable
(RS232/485)
1: MODEM (RS232)
b3.01 Local address 0~127 , 0 is the broadcasting 1 5 × 0~127
address
b3.02 Time threshold for 0.0~1000.0S 0.1 0.0S × 0~10000
judging
the communication
status
b3.03 Delay for 0~1000mS 1 5mS × 0~1000
responding to
control PC
Group b4:Keyboard parameters
b4.00 Key-lock function 0: The keys on the operation panel 1 0 ○ 0~4
selection are not locked, and all the keys are
usable.
1: The keys on the operation panel
are locked, and all the keys are
unusable.
2: All the keys except for the
multi-functional key are unusable.
3: All the keys except for the SHIFT
key are unusable.
4:All the keys except for the RUN
AND STOP keys are unusable.
b4.01 Multi-function key 0: Jog function 1 0 ○ 0~3
definition 1: Coast-to-stop
2: Quick stop

91
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
3: Switch of operating command
4:Switch of forward and
reverse(Save after power failure)
5:Switch of forward and
reverse(Not save after power
failure)
b4.02 Parameter 0: All parameters are allowed 1 1 ○ 0~2
protection modifying;
1: Only A0.03 and b4.02 can be
modified;
2: Only b4.02 can be modified.
b4.03 Parameter 0: No operation 1 0 × 0~2
initialization 1: Clear falt information in memory
2: Restore to factory settings
b4.04 Parameter copy 0: No action 1 0 × 0~3
1: parameters upload
2: parameters download
3: parameters download (except the
parameters related
to drive type)
Note:Not to upload/download
drive’s parameters.
b4.05 Display Binary setting: 1 1007H ○ 0~7FFFH
parameters BIT1:Operating
selection 0:No display;1:Display
Unit’s place of LED:
BIT0:Output frequency(No
display at stop.Display power
frequency at energy feedback
mode)
BIT1:Setting frequency
(Flicking.No display at energy
feedback mode)
BIT2:Output current(No display
at stop.Display power frequency
at energy feedback mode)
BIT3:Output voltage(No display at

92
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
stop.Display power frequency at
energy feedback mode)
Ten’s place of LED:
BIT0:AI1
BIT1:AI2
BIT2:Reserved
BIT3:Reserved
Hundred’s place of LED:
BIT0:Output power(No display
at stop and energy feedback
mode)
BIT1:Output torque(No display
at stop and energy feedback
mode)
BIT2:Analog close-loop feedback
(%)(No display at feedback mode)
BIT3:Analog close-loop setting
(%)(Flicking, no display at
feedback mode)
Thousand’s place of LED:
BIT0:Bus voltage
BIT1:Speed(R/MIN)(No display at
feedback mode)
BIT2:Setting speed(R/MIN)
(Flicking, no display at feedback
mode)
Note:If all the BITs are 0,the drive
will display setting frequency at
stop,display output frequency at
operating and display bus voltage at
energy feedback mode.
Group C0:Multi-section parameters
C0.00 Preset frequency 1 A0.12(Lower limit of frequency) 0.01Hz 5.00Hz ○ 0~30000

~A0.11(upper limit of frequency)


C0.01 Preset frequency 2 Same as above 0.01Hz 10.00Hz ○ 0~30000
C0.02 Preset frequency 3 Same as above 0.01Hz 20.00Hz ○ 0~30000

93
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
C0.03 Preset frequency 4 Same as above 0.01Hz 30.00Hz ○ 0~30000
C0.04 Preset frequency 5 Same as above 0.01Hz 40.00Hz ○ 0~30000
C0.05 Preset frequency 6 Same as above 0.01Hz 45.00Hz ○ 0~30000
C0.06 Preset frequency 7 Same as above 0.01Hz 50.00Hz ○ 0~30000
C0.07 Preset frequency 8 Same as above 0.01Hz 5.00Hz ○ 0~30000
C0.08 Preset frequency 9 Same as above 0.01Hz 10.00Hz ○ 0~30000
C0.09 Preset frequency Same as above 0.01Hz 20.00Hz ○ 0~30000
10
C0.10 Preset frequency Same as above 0.01Hz 30.00Hz ○ 0~30000
11
C0.11 Preset frequency Same as above 0.01Hz 40.00Hz ○ 0~30000
12
C0.12 Preset frequency Same as above 0.01Hz 45.00Hz ○ 0~30000
13
C0.13 Preset frequency Same as above 0.01Hz 50.00Hz ○ 0~30000
14
C0.14 Preset frequency Same as above 0.01Hz 50.00Hz ○ 0~30000
15
Group C1:Process PID parameters
C1.00 Close-loop control 0:Disable 1 0 × 0~1
function 1:Enable
C1.01 Reference channel 0:Digital input 1 1 ○ 0~3
selection 1:AI1;
2:AI2;
3:Reserved;
C1.02 Feedback channel 0:AI1; 1 1 ○ 0~6
selection 1:AI2;
2:AI1+AI2;
3:AI1-AI2;
4:MIN(AI1,AI2);
5:MAX(AI1,AI2)

6: DI
C1.03 Digital setting of -10.00V~10.00V 0.01 0.00 ○ 0~2000
reference
C1.04 Close-loop speed 0~39000rpm 1rpm 0 ○ 0~39000

94
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
reference
C1.05 Min reference 0.0%~(C1.07) 0.1% 0.0% ○ 0~1000
(Ratio of Min reference to base
value of 10V/20mA))
C1.06 Feedback value 0.0~100.0% 0.1% 0.0% ○ 0~1000
corresponding to (Ratio of Min reference to base
the Min reference value of 10V/20mA)
C1.07 Max reference (C1.05)~100.0% 0.1% 100.0% ○ 0~1000
(Ratio of Max reference to base
value of 10V/20mA)
C1.08 Feedback value 0.0~100% 0.1% 100.0% ○ 0~1000
corresponding to (Ratio of Max reference to base
the Max reference value of 10V/20mA)
C1.09 Proportional gain 0.000~10.000 0.001 2.000 ○ 0~10000
KP
C1.10 Integral gain Ki 0.000~10.000 0.001 0.100 ○ 0~10000
C1.11 Differential gain 0.000~10.000 0.001 0.100 ○ 0~10000
Kd
C1.12 Sampling cycle T 0.01~50.00s 0.01s 0.50s ○ 1~5000
C1.13 Output filter 0.01~10.00s 0.01s 0.05 ○ 1~1000
C1.14 Error limit 0.0~20.0% 0.1% 2.0% ○ 0~200
(Corresponding to close-loop
reference)
C1.15 Close-loop 0:Positive 1 0 × 0~1
regulation 1:Negative
characteristic
C1.16 Integral regulation 0: Stop integral regulation when the 1 0 × 0~1
selection frequency reaches the upper and
lower limits
1: Continue the integral regulation
when the frequency reaches the
upper and lower limits

C1.17 Preset close-loop 0.00~300.00Hz 0.01Hz 0.00Hz ○ 0~30000


frequency
C1.18 Holding time of 0.0~3600.0S 0.1S 0.0S × 0~36000
preset close-loop

95
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
frequency
C1.19 Preset close-loop -10.00V ~10.00V 0.01V 0.00V ○ 0~2000
reference 1
C1.20 Preset close-loop -10.00V ~10.00V 0.01V 0.00V ○ 0~2000
reference 2
C1.21 Preset close-loop -10.00V ~10.00V 0.01V 0.00V ○ 0~2000
reference 3
C1.22 Preset close-loop -10.00V ~10.00V 0.01V 0.00V ○ 0~2000
reference 4
C1.23 Preset close-loop -10.00V ~10.00V 0.01V 0.00V ○ 0~2000
reference 5
C1.24 Preset close-loop -10.00V ~10.00V 0.01V 0.00V ○ 0~2000
reference 6
C1.25 Preset close-loop -10.00V ~10.00V 0.01V 0.00V ○ 0~2000
reference 7
C1.26 Preset close-loop -10.00V ~10.00V 0.01V 0.00V ○ 0~2000
reference 8
C1.27 Preset close-loop -10.00V ~10.00V 0.01V 0.00V ○ 0~2000
reference 9
C1.28 Preset close-loop -10.00V ~10.00V 0.01V 0.00V ○ 0~2000
reference 10
C1.29 Preset close-loop -10.00V ~10.00V 0.01V 0.00V ○ 0~2000
reference 11
C1.30 Preset close-loop -10.00V ~10.00V 0.01V 0.00V ○ 0~2000
reference 12
C1.31 Preset close-loop -10.00V ~10.00V 0.01V 0.00V ○ 0~2000
reference 13
C1.32 Preset close-loop -10.00V ~10.00V 0.01V 0.00V ○ 0~2000
reference 14
C1.33 Preset close-loop -10.00V ~10.00V 0.01V 0.00V ○ 0~2000
reference 15
C1.34 Close-loop output 0 : The close-loop output is 1 0 ○ 0~1
reversal selection negative,
the drive will operate at zero
frequency.
1 : The close-loop output is

96
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
negative,
and the drive operate reverse.

C1.35 Sleep function 0:Disable 1 0 ○ 0~1


selection 1:Enable.
C1.36 Sleep level 0.0~100.0% 0.1% 50.0% ○ 0~1000
C1.37 Sleep latency 0.0~6000.0s 0.1s 30.0s ○ 0~60000
C1.38 Wake-up level 0.0~100.0% 0.1% 50.0% ○ 0~1000

C2:Simple PLC
C2.00 Simple PLC Unit’s place of LED: 1 0000 × 0~1123H
operation PLC operation mode
mode selector 0:No function
1:Stop after single cycle
2:Keep final states after single
cycle
3:Continuous cycle
Ten’s place of LED:
Start mode
0:Start from first step
1:Start from the step before
stop(or alarm).
2 : Start from the step and
frequency before stop(or alarm)
Hundred’s place of LED:
Storage after power off
0:Disable
1:Save the segment,frequency
when power off
Thousand’s place of LED:
Time unit selector for each step
0:Second
1:Minute
C2.01 Step 1 setting Unit’s of LED: 1 000 ○ 0~323H

0 : Multiple frequency
N(N:corresponding to current step)

97
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
1:Defined by A0.02
2 : Multiple closed-loop
reference N(N:corresponding to
current step)
3:Defined by C1.01
Ten’s place of LED:
0:Forward
1:Reverse
2 : Defined by operation
command
Hundred’s place of LED:
0:Acc/Dec time 1
1:Acc/Dec time 2
2:Acc/Dec time 3
3:Acc/Dec time 4
C2.02 Step 1 operating 0.1 20.0 ○
0.0~6500.0 0~65000
time
C2.03 Step 2 setting Same as C2.01 1 000 ○ 0~323H
C2.04 Step 2 operating 0.1 20.0 ○
0.0~6500.0 0~65000
time
C2.05 Step 3 setting Same as C2.01 1 000 ○ 0~323H
C2.06 Step 3 operating 0.1 20.0 ○
0.0~6500.0 0~65000
time
C2.07 Step 4setting Same as C2.01 1 000 ○ 0~323H
C2.08 Step 4 operating 0.1 20.0 ○
0.0~6500.0 0~65000
time
C2.09 Step 5 setting Same as C2.01 1 000 ○ 0~323H
C2.10 Step 5 operating 0.1 20.0 ○
0.0~6500.0 0~65000
time
C2.11 Step 6 setting Same as C2.01 1 000 ○ 0~323H
C2.12 Step 6 operating 0.1 20.0 ○
0.0~6500.0 0~65000
time
C2.13 Step 7 setting Same as C2.01 1 000 ○ 0~323H
C2.14 Step 7 operating 0.1 20.0 ○
0.0~6500.0 0~65000
time

98
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
C2.15 Step 8 setting Same as C2.01 1 000 ○ 0~323H
C2.16 Step 8 operating 0.1 20.0 ○
0.0~6500.0 0~65000
time
C2.17 Step 9 setting Same as C2.01 1 000 ○ 0~323H
C2.18 Step 9 operating 0.1 20.0 ○
0.0~6500.0 0~65000
time
C2.19 Step 10 setting Same as C2.01 1 000 ○ 0~323H
C2.20 Step 10 operating 0.1 20.0 ○
0.0~6500.0 0~65000
time
C2.21 Step 11 setting Same as C2.01 1 000 ○ 0~323H
C2.22 Step 11 operating 0.1 20.0 ○
0.0~6500.0 0~65000
time
C2.23 Step 12 setting Same as C2.01 1 000 ○ 0~323H
C2.24 Step 12 operating 0.1 20.0 ○
0.0~6500.0 0~65000
time
C2.25 Step 13 setting Same as C2.01 1 000 ○ 0~323H
C2.26 Step 13 operating 0.1 20.0 ○
0.0~6500.0 0~65000
time
C2.27 Step 14 setting Same as C2.01 1 000 ○ 0~323H
C2.28 Step 14 operating 0.1 20.0 ○
0.0~6500.0 0~65000
time
C2.29 Step 15 setting Same as C2.01 1 000 ○ 0~323H
C2.30 Step 15 operating 0.1 20.0 ○
0.0~6500.0 0~65000
time
Group C3:Swing parameters
C3.00 Swing function 0:Disable 1 0 × 0~1
selector 1:Enable
C3.01 Swing Operation Unit’s place of LED : Startup 1 0000 × 0~1111H
mode method
0:Auto mode
1:By terminal
Ten’s place of LED:Swing control
0:Reference centre frequency
1:Reference max. frequency
Hundred’s place of LED : Swing

99
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
states storage
0:Save after stop
1:Not save after stop
Thousand’s place of LED : Swing
states
storage after power failure
0:Save
1:Not save
C3.02 Preset swing 0.00Hz~Max. frequency 0.01Hz 0.00Hz ○ 0~100000
frequency
C3.03 Waiting time for 0.0~3600.0s 0.1s 0.0s ○ 0~36000
preset swing
frequency
C3.04 Swing amplitude 0.0%~50.0% 0.1% 0.0% ○ 0~500
C3.05 Jump frequency 0.0%~50.0% 0.1% 0.0% ○ 0~500
C3.06 Swing cycle 0.1~999.9s 0.1s 10.0s ○ 1~9999
C3.07 Triangle wave 0.0%~100.0%(Swing cycle) 0.1% 50.0% ○ 0~1000
rising time
Group d0:Status display
d0.00 Main reference -300.00~300.00Hz 0.01Hz 0.00 * 0~60000
frequency
d0.01 Auxiliary -300.00~300.00Hz 0.01Hz 0.00 * 0~60000
reference
frequency
d0.02 Preset frequency -300.00~300.00Hz 0.01Hz 0.00 * 0~60000
d0.03 Frequency after -300.00~300.00Hz 0.01Hz 0.00 * 0~60000
Acc/Dec
d0.04 Output frequency -300.00~300.00Hz 0.01Hz 0.00 * 0~60000
d0.05 Output voltage 0~480V 1V 0 * 0~480
d0.06 Output current 0.0~3Ie 0.1A 0.0 * 0~65535
d0.07 Torque current -300.0~+300.0% 0.1% 0.0% * 0~6000
d0.08 Magnetic flux 0~+100.0% 0.1% 0.0% * 0~1000
current
d0.09 Motor power 0.0~200.0%(Corresponding to the 0.1% 0.0% * 0~2000

motor’s rated power)


d0.10 Motor estimated -300.00~300.00Hz 0.01 0.00 * 0~60000

100
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
frequency
d0.11 Motor actual -300.00~300.00Hz 0.01 0.00 * 0~60000
frequency
d0.12 Bus voltage 0~800V 1V 0 * 0~800
d0.13 Drive operation 0~FFFH 1 0 * 0~FFFFH
status bit0:Run/Stop
bit1:Reverse/Forward
bit2:Operating at zero
frequency
bit3:Accelerating
bit4:Decelerating
bit5:Operating at constant speed
bit6:Pre-commutation
bit7:Tuning
bit8:Over-current limiting
bit9:DC over-voltage limiting
bit10:Torque limiting
bit11:Speed limiting
bit12:Drive fault
bit13:Speed control
bit14:Torque control
bit15:Position control(Reserved)
d0.14 Input terminals 0~FFH,0:OFF;1:ON 1 00 * 0~FFH
status
d0.15 Output terminals 0~1FH,0:OFF;1:ON 1 0 * 0~1FH
status
d0.16 AI1 input -10.00~10.00V 0.01V 0.00 * 0~2000
d0.17 AI2 input -10.00~10.00V 0.01V 0.00 * 0~2000
d0.18 Reserved
d0.19 Percentage of AI1 -100.00%~110.00% 0.01% 0.00 * 0~20000
after regulation
d0.20 Percentage of AI2 -100.00%~110.00% 0.01% 0.00 * 0~20000
after regulation
d0.21 Reserved -100.00%~110.00% 0.01% 0.00 * 0~20000
d0.22 AO1 output 0.0~100.0% (Ratio of the full 0.1% 0.0% * 0~1000

101
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
range)
d0.23 Reserved
d0.24 Process close-loop -100.0~100.0% (Ratio of the full 0.1% 0.0% * 0~2000
reference range)
d0.25 Process close-loop -100.0~100.0% (Ratio of the full 0.1% 0.05% * 0~2000
feedback range)
d0.26 Process close-loop -100.0~100.0% (Ratio of the full 0.1% 0.0% * 0~2000
error range)
d0.27 Process close-loop -100.0~100.0% (Ratio of the full 0.1% 0.0% * 0~2000
range)
d0.28 Temperature of 0.0~150.0℃ 0.1℃ 0.0 * 0~1500
heatsink 1
d0.29 Temperature of 0.0~150.0℃ 0.1℃ 0.0 * 0~1500
heatsink 2
d0.30 Total conduction 0~65535 hours 1 hours 0 * 0~65535
time
d0.31 Total operating 0~65535 hours 1 hours 0 * 0~65535
time
d0.32 Total fan’s 0~ 65535 hours 1 hours 0 * 0~65535
operating time
d0.33 ASR controller -300.0~300.0% (Corresponding to 0.1% 0.0% * 0~6000
output drive’s rated torque)
d0.34 Reference torque -300.0~300.0% ( Corresponding to 0.1% 0.0% * 0~6000

drive’s rated torque)


Group d1:Fault record
d1.00 Fault record 1 0:No fault records 1 0 * 0~50

1:Over-current during acceleration


(E001)
2:Over-current during deceleration
(E002)
3:Over-current in constant speed
operation (E003)
4:Over voltage during acceleration
(E004)
5:Over voltage during deceleration
(E005)

102
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
6:Over voltage in constant-speed
operating process (E006)
7 : Drive’s control power supply
over voltage (E007)
8:Input phase loss (E008)
9:Output phase failure (E009)
10:Protections of IGBT act (E010)
11 : IGBT module’s heatsink
overheat (E011)
12 : Rectifier’s heatsink overheat
(E012)
13:Drive overload (E013)
14:Motor over-load (E014)
15:External equipment fails (E015)
16:EEPROM R/W fault (E016)
17:RS232/RS485 communication
failure (E017)
18:Contactor not closed (E018)
19 : Current detection circuit has
fault,Hall sensor or amplifying
circuit(E019 )
20:Reserved
21:Reserved
22:Reserved
23:Parameter copy error(E023)
24:Auto-tuning fails(E024)
25:Reserved
26:Reserved
27:Brake unit failure(E027)
Note:
1 E007 is not detected if the the
model is 18.5G/22G or blow.
2 Fault E010 can’t be reset until
delaying 10 seconds.

103
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
3 The over-current fault can’tbe
reset until delaying 6 seconds.
4 The keypad will diplay fault
A××× when fault warning
appears.(For example,when
contactor failure,the keypad
will display E018 if it is action
protection,and the keypad will
display A018 if it is warning
and continue to run).
d1.01 Bus voltage of the 0~999V 1V 0V * 0~999
latest failure
d1.02 Actual current of 0.0~999.9A 0.1A 0.0A * 0~9999
the latest failure
d1.03 Operation 0.00Hz~300.00Hz 0.01Hz 0.00Hz * 0~30000
frequency of the
latest failure
d1.04 Operation status of 0~FFFFH 1 0000 * 0~FFFFH
the latestfailure
d1.05 Fault record 2 0~55 1 0 * 0~50
d1.06 Fault record 3 0~55 1 0 * 0~50
Group d2:Product Identity Parameters
d2.00 Serial number 0~FFFF 1 100 * 0~65535
d2.01 Software version 0.00~99.99 1 1.00 * 0~9999
number
d2.02 Custom-made 0~9999 1 0 * 0~9999
version number
d2.03 Rated capacity Output power ,0~999.9KVA 0.1KVA Factory * 0~9999
(Dependent on drive’s model) setting
d2.04 Rated voltage 0~999V (Dependent on drive’s 1V Factory * 0~999
model) setting
d2.05 Rated current 0~999.9A (Dependent on drive’s 0.1A Factory * 0~9999
model) setting
Group U0:Factory parameters
U0.00 Factory password **** 1 Factory - 0~FFFF
Note:Other parameters in this group setting
can’t display until entering the right

104
Function Factory Setting
Name Descriptions Unit Modif.
code setting range
password.
Note:○:Can be modified during operation;
×:Cannot be modified during operating;
*:Actually detected and cannot be revised;
-:Defaulted by factory and cannot be modified.

105
Communication Protocol

1. Networking Mode
According to the following pic 10-1, there are two networking modes: Single master and multi-slave, Single master
and single slave.

Pic 10-1

2. Interfaces
RS485 or RS232: asynchronous, semi-duplex
Default: 8-N-1, 9600bps, RTU. Refer to Group b3 for parameter settings.

3. Communication Modes
1. The commnication protocol for the drive is Modbus. It support normal reading and writing of the registers, also
supports managing the funtion code.
2. The drive is a slave in the network. It communicates in “point to point” mode.
3. When there is multi-station communication or the communication distance is long, please connect a 100~200 ohm
resistance to the positive and minus terminal of the master’s signal wire in parallel.
4. FV 100 normally provides RS485 interface, if you need RS232, please choose to add a RS232/RS485 conversion
equipment.

4. Protocol Format
CV100 support Modbus RTU and ASCII,its frame format is shown in Fig.10-2.

106
RTU Format

Modbus Mode

Start(The space of End(The space of


Slave Function Check sum
the frame is 3.5 Data frame is 3.5
address code
characters at least) characters at least)

ASCII Mode

Modbus Frame

Start Slave Function End


Data Check sum
( 0x3A ) address code (0x0D,ETX bytes)

Fig.10-2 Modbus protocol format

Modbus use “Big Endian” of encoder mode, which means sending data with high byte in front and low byte behind.

1. RTU mode

In RTU mode,there must be a idle of at least 3.5 characters between two frames.It use CRC-16 for data check.
Following is an example for read the parameter of internal register 0101(A1.01) from No.5 slave.
Request frame:
Slave Function Data
Checksum
address code Register address Length
0x05 0x03 0x01 0x01 0x00 0x01 0xD5 0xB2
Response frame:
Data
Slave Function
Response Register Checksum
address code
length content
0x05 0x03 0x02 0x13 0x88 0x44 0xD2
Therein, checksum is CRC value.

2.ASCII mode

In ASCII mode, characters are used to start and end a frame. The colon “0x3A” is used to flag the start of a message
and each message is ended with a “0x0D,0x0A” combination. Except frame header and end of frame,all other
messages are coded in hexadecimal values, represented with readable ASCII characters. Only the characters 0...9 and
A...F are used for coding. Herein the data use LRC as error checksum.
Following is an example for writing value 0003(0x0003) into the parameter of internal register 0201(A2.01) from No.5
slave.
Request frame:
Frame Slave Function Data Check
Frame trail
header address code Register address Setting value code
Character : 0 5 0 6 0 2 0 1 0 0 0 3 E F CR LF
ASCII 3A 30 35 30 36 30 32 30 31 30 30 30 33 45 46 0D 0A
Therein,the check code is LRC checksum,which value is equal to the complement of (05+06+02+01+0x00+0x03).
Response frame:
Frame Slave Function Data Check
Frame trail
header address code Register address Setting value code

107
Character : 0 5 0 6 0 2 0 1 0 0 0 3 E F CR LF
ASCII 3A 30 35 30 36 30 32 30 31 30 30 30 33 45 46 0D 0A
VFD can set different delay time for response according to different application.For RTU mode,the actual delay time
for response is 3.5 characters interval at least.For ASCII mode,the actual delay time for response is 1 ms at least.

5. Protocol Function
The main functions of Modbus are read and write parameters.Different function codes need different operation
request.The modbus protocol of VFD support the operations in the following table.
Function code Meaning
Read parameters of VFD,including function code parameters,control parameters and status
0x03
parameters.

Rewrite single function code or control parameter with 16bit length,the value of the
0x06
parameter can’t be saved after VFD power off.

0x08 Diagnosis.

Rewrite multiple function code or control parameters,the vaule of the parameters can’t be
0x10
saved after VFD power off.

Rewrite single function code or control parameter with 16bit length,the value
0x41
can be saved after VFD power off.

0x42 Manage function code of VFD.

Rewrite multiple function code or control parameters,the vaule of the parameters can be
0x43
saved after VFD power off.
All the function code, control parameters and status parametes of VFD are mapping to the read/write register of
Modbus.The group number of function code is mapping to the high byte of register address and the index address in
the group is mapping to the low byte of register address.The corresponding relationship between group number and
register address is shown in following table.
Group No. High bye of mapping Group No. High bye of mapping
address address
Group A0 0x00 Group B2 0x0C
Group A1 0x01 Group B3 0x0D
Group A2 0x02 Group B4 0x0E
Group A3 0x03 Group C0 0x14
Group A4 0x04 Group C1 0x15
Group A5 0x05 Group D0 0x1E
Group A6 0x06 Group D1 0x1F
Group A7 0x07 Group D2 0x20
Group A8 0x08 Group U0 0x5A
Group B0 0x0A Control parameter 0x32
Group B1 0x0B Status parameter 0x33
For example, the register address of function code A3.02 is 0x0302, and the register address of the first control
parameter (Control command 1) is 0x3200.

108
6.Control parameters and status parameters of VFD
The control parameters of VFD can achieve the function such as startup, stop,setting operating frequency and so
on.Retrieving the status parameters of VFD can obtain the parameters such as operating frequency,output
current,output torque and so on.
1.Control parameter

The control parameters of VFD are shown in following table.


Register Parameter Name Saved after powered off Note
0X3200 Control word 1 No
0x3201 Main setting No The main setting
frequency: In the common
operation mode, the
channel of main setting is
serial communication, it
tack effects if the bit8 of
control word 1 is set on.
Wether it saves or not
depends on the setting in
A2.03
0x3202 Operation frequency setting No Same as above
0x3203 Digital closed loop setting yes Takes effects after the
closed loop is enabled
0x3204 Pulse closed loop setting / Do not support
0x3205 Analog outprut AO1 setting No Enable when A6.28=15
0x3206 Reserved
0x3207 Digital output DO setting No Enable when A6.25=65
0x3208 Frequency Proportion Do not support
setting
0x3209 Virtual terminal control No Bit0~bit4: X1~X5.
setting Corresponding to on state
of the bits in A6.24
Bit10~bit13: Y1
/RO1/RO2, They are
enabled when
A6.14~A6.17=17
0x320A Set the acceleration time Yes
0x320B Set the deceleration time Yes
Ox3212 Control command word 2 No

Note:
(1)When read control parameters,it will return the value which is rewrote in the previous communication.
(2)In control parameters,the preset value,range of input/output setting value and decimal point scaling should
refer to the corresponding function code.

109
The bits for the control command word 1 are defined as follows:

Bit Value Function Note


bit2~bit0 111B Running command Start VFD(enable when jog is disable)

110B Stop mode 0 Stop according to the preset deceleration


time(enable when jog is disable)

101B Stop mode 1 Coast to stop

100B Stop by external fault Coast to stop and VFD display external
fNotltsupport
011B Stop mode 2
Others Reserved
bit3 1 Reverse Set the operating direction when run

0 Forward command is enable

bit4 1 Jog forward


No action when bits for jog forward and
0 Jog forward disable
reverse are enable at the same time,and jog
bit5 1 Jog reverse
stop when both are disable at the same time.
0 Jog reverse disable
bit6 1 Enable Acc/Dec The bit5~bit0 of control word 1 are enable

0 Disable Acc/Dec when this bit is enable.

bit7 1 Host computer control word 1


enable Selection bit of host computer control word
0 Host computer control word 1 1
disable
bit8 1 Main reference enable
Selection bit of main reference
0 Main reference disable
bit9 1 Fault reset enable
Selection bit of fault reset
0 Fault reset disable
bit15~bit10 000000B Reserved
Note:
(1)The host computer control word(control word1 and control word 2) is enable when set “Methods of inputting
operating commands” to “communication control”.The control word 1 is enabled when the bit7 of control word 1 is
enable.And bit5~bit0 are enable when the bit6 of control word 1 is enable.
( 2 ) Processing of fault and alarm in host computer:when VFD is failure,all the command of control word 1 and
control word 2,except fault reset command,are disable,it need to reset fault firstly before sending other
commands.When the alarm happens,the control words is still enable.
The bits definitions of control word 2 are shown as follows:
Bit Value Function Note

110
bit0 1 VFD operation disable Selection bit for VFD operation
0 VFD operation enable enable/disable

bit1 1 Running(The direction refer to

function code)
Running direction
0 Other operation status(Refer to
control word 1)

bit2 1 Auxiliary reference enable The selection bit for auxiliary

0 Auxiliary reference disable reference frequency.

bit3 1 The control word 2 enable The selection bit for control word

0 The control word 2 disable 2.

bit15~bit4 Reserved
Note: control word 2 is enabling when the bit3 of control word 2 is enable.

2.Status parameters
Register address Parameters name Note
0x3300 VFD operation status word 1
0x3301 Current main reference value Current operating
frequency
0x3302 Slave model
0x3303 VFD model
0x3304 Software version
0x3305 Current operating frequency
0x3306 Output current
0x3307 Output voltage
0x3308 Output power
0x3309 Operating rotary speed
0x330A Operating line speed
0x330B Analog close-loop feedback
0x330C Bus voltage
0x330D External counter Not support
0x330E Output torque
0x330F Digital input/output terminal status bit0~bit4:
X1~X5;
bit10~bit12:
Y1 /RO1。
0x3310 Actual length Not support
0x3311 Operating frequency after compensation Not support
0x3312 The first operating fault
0x3313 The second operating fault
0x3314 The latest operating fault
0x3315 Operating frequency setting
0x3316 Rotary speed setting
0x3317 Analog close-loop setting
0x3318 Line speed setting

111
Register address Parameters name Note
0x3319 AI1
0x331A AI2
0x331B Length setting Not support
0x331C Acceleration time 1 setting
0x331D Deceleration time 1 setting
0x331E Methods of inputting
operating commands
0:Panel control
1:Terminal control
2:Communication control
0x331F VFD operating status word 2
0x3320 Main reference frequency selector
0:Digital setting 1(Keypad ∧∨ setting)
1:Digital setting 2(Terminal UP/DN setting)
2:Digital setting 3 (Serial port)
3:AI analog setting
4:DI pulse setting
5:Expansion card.

0x3321 Accumulated length Not support


Note:
(1)Status parameters don’t support write operation.
(2)The encoding rules of slave model is as follows:the range of slave model is 0~999.
The bit definitions of VFD operating status word 1 are shown in following table:
Bit Value Function Note
bit0 1 VFD running
0 VFD stop
bit1 1 VFD reverse rotation
0 VFD forward rotation
bit2 1 Reach main reference
0 Not reach main reference
bit3 1 Serial port control enable
0 Serial port control disable
bit4 1 Serial port setting enable
0 Serial port setting disable
bit5~bit6 Reserved
bit7 1 Alarm When this bit is 0,the bit15~8 of control word
0 Fault or normal 1show the status.If bit15~8 are 0,means
normal.If not,means failure.
bit15~ bit8 0x00~0xFF Fault/alarm code 0: normal.
Not 0: fault/alarm.

The bit definitions of VFD operating status word 2 are shown in following table:
Bit Value Function Note
bit0 1 Jog running
0 Non-jog running
bit1 1 Close loop running
0 Non-close loop running

112
bit2 1 PLC running
0 Non-PLC running
bit3 1 Multi-section frequency
operation
0 Non multi-section
frequency operation.
bit4 1 Common operation
0 Non-common operation
bit5 1 Swing frequency
0 Non-swing frequency
bit6 1 Under voltage
0 Normal voltage
bit7 Reserved
bit8 Servo operation
bit9 Customized operation
bit10 Synchronous speed
operation
Others Reserved

The bit definitions of VFD operating status word 3 are shown as following table:
Bit Value Function Note
bit0~bit1 Reserved
bit2 Zero speed operation
bit3 Accelerating
bit4 Decelerating
bit5 Constant speed running
bit6 Pre-excitation
bit7 Tuning
bit8 Over-current limiting
bit9 DC over-voltage
limiting
bit10 Torque limiting
bit11 Speed limiting
bit12 VFD failure
bit13 Speed control
bit14 Torque control
bit15 Position control

1. Some instructions
1.For function code 0x10 and 0x43,when rewrite multiple continous function codes,if any one of the function
codes is invalid for write operation,then it will return error information and all of the parameters can’t be
rewritten.When rewrite multiple continuous control parameters,if any one of the parameters is invalid for write
operation, then it will return error information and this parameter and others behind can’t be rewritten,but other
parameters before this parameter can be rewritten normally.
2 . For some special function code,Using 0x06 and 0x41 or 0x10 and 0x43 are the same function,in write
operation,the parameters can be saved after power failure.
Function code Description

113
B4.02 Parameters protection setting

A6.00~A6.04 Selection of input terminal X1~X5

A2.03 Main reference frequency control

A2.03 Auxiliary reference frequency control

C2.00 PLC operation mode

C3.00 Swing frequency operation mode

B0.00 Motor rated power

U0.01 Machine model setting(Factory parameter)

U0.09 VFD series selection(Factory parameter)


3.Some control parameters can’t save in EEPROM,so for these parameters,using function code 0x41 and 0x06 or
0x43and 0x10 are the same,mean parameters can be saved after power failure.
4.Some internal parameters of VFD are reserved and can’t be changed via communication, refer to following
table:
Function code Description
B4.04 Parameters copy

B0.11 Motor parameters auto-tuning


5.The operation of user password and factory password in host computer
(1)User password
1)Protection of user password:Read/write function code, function code management (except “read address of
displaydata” and”switch display data”)
2)If you set user password(A0.00!=0),then you must enter the right password to A0.00 when you want to visit
function code,but control parameters and status parameters are not protected by user password.
3)User password can’t be set,change or cancel by host computer,it can only operated by keypad. To A0.00 of
write operation, only effective in two situations: one is in the password decryption; Second,write 0 is in the situation of
no password.It will return invalid operation information in other situations.
4)The operation of host computer and keypad to user password is independent. Even if the keyboard completes
decryption, but host computer still need to decrypt when it want to access function codes, and vice versa.
5)After host computer acquire the access right of parameters,when reading user password,it will return “0000”
instead of actual user password.
6)The host computer will acquire the access right of function code after decryption,if there is no communication
for 5minutes,then the access right will disable.And if it want to access function code,it need to enter user password
again.
7 ) When host computer has acquired access right(no user password or has decryption),if the user password is
rewritten by keypad at this moment,the host computer has still the current access right and no need to decryption
again.
(2)Factory password
1)Protection range of factory password:Read/write parameters of Group U0, function code management of Group
U0.

114
2)Host computer can only access function code of Group U0 after decryption(write correct factory password into
U0.00).If there is no communication for 5 minutes after acquiring access right,the right will disable automatically,and
it need to enter password again to access Group U0.
3)After acquiring the access right of Group U0,if host computer read U0.00,it will return 0000 instead of actual
factory password.
4)The operation of host computer and keypad to user password is independent. They need to enter the correct
password separately to acquire the access right.
5 ) Host computer has no right to modify factory password.When host computer write data into U0.00, it will
return invalid operation unless the data is correct password.
2. Application example
CV100 only support 16bit access.
Start No.5 VFD to perform forward rotation.
Data frame Address Function code Register address Register content Checksum
Request 0x05 0x06 0x3200 0x00C7 0xC764

Response 0x05 0x06 0x3200 0x00C7 0xC764


No.5 VFD stops in mode 0.
Data frame Address Function code Register address Register content Checksum
Request 0x05 0x06 0x3200 0x00C6 0x06A4

Response 0x05 0x06 0x3200 0x00C6 0x06A4


No.5 VFD jogs forward.
Data frame Address Function code Register address Register content Checksum
Request 0x05 0x06 0x3200 0x00D0 0x876A

Response 0x05 0x06 0x3200 0x00D0 0x876A


No.5 VFD stop jogging.
Data frame Address Function code Register address Register content Checksum
Request 0x05 0x06 0x3200 0x00C0 0x86A6

Response 0x05 0x06 0x3200 0x00C0 0x86A6


No.5 VFD reset fault:
Data frame Address Function code Register address Register content Checksum
Request 0x05 0x06 0x3200 0x0280 0x8636

Response 0x05 0x06 0x3200 0x0280 0x8636


Read the operating frequency of No.5 VFD and the response operating frequency of the VFD is 50.00Hz:
Data frame Address Function code Register Number of Register Checksum
address registers or content
bytes
Request 0x05 0x03 0x3301 0x0001 None 0xDB0A

Response 0x05 0x03 None 0x02 0x1388 0x44D2

115
Rewrite the acceleration time 1(Function code A0.06) of No.5 VFD to 10.0s and can’t save after power failure.
Data frame Address Function code Register address Register content Checksum
Request 0x05 0x06 0x0006 0x0064 0x69A4

Response 0x05 0x06 0x0006 0x0064 0x69A4


Read the output current of No.5 VFD and the response output current of the VFD is 30.0A.
Data frame Address Function code Register Number of Register Checksum
address registers or content
bytes
Request 0x05 0x03 0x3306 0x0001 None 0x6ACB

Response 0x05 0x03 None 0x02 0x012C 0x49C9


Read the deceleration time 1(Function code A0.07) of No.5 VFD and the response deceleration time of the VFD
is 6.0s.
Data frame Address Function code Register Number of Register Checksum
address registers or content
bytes
Request 0x05 0x03 0x0007 0x0001 None 0x344F

Response 0x05 0x03 None 0x02 0x003C 0x344F

Scaling relationship of VFD:


A)Scaling of frequency C is 1:100.
If you want to make the VFD run at 50Hz,then the main reference should be set as 0x1388(5000).
B)Scaling of time is 1:10
If you want to set the acceleration time of the VFD as 30s,then the function code should be set as 0x012C(300).
C)Scaling of current is 1:10
If the response current of VFD is 0x012C(300),then current of the VFD is 30A.
D)Output power is the absolute value.
E)Other (such as the input and output terminals, etc.) please reference inverter user manual

116

You might also like