Atlasga18 37vsdmanual 2 PDF
Atlasga18 37vsdmanual 2 PDF
Atlasga18 37vsdmanual 2 PDF
Instruction book
Atlas Copco
Oil-injected rotary screw compressors
Instruction book
Original instructions
Copyright notice
Any unauthorized use or copying of the contents or any part thereof is prohibited.
This applies in particular to trademarks, model denominations, part numbers and drawings.
This instruction book is valid for CE as well as non-CE labelled machines. It meets the
requirements for instructions specified by the applicable European directives as identified
in the Declaration of Conformity.
2013 - 10
No. 2920 7110 00
www.atlascopco.com
Instruction book
Table of contents
1 Safety precautions..........................................................................................................5
2 General description......................................................................................................10
2.1 INTRODUCTION.................................................................................................................................10
3.8 COUNTERS......................................................................................................................................38
2 2920 7110 00
Instruction book
4 Installation.....................................................................................................................75
4.4 PICTOGRAPHS.................................................................................................................................84
5 Operating instructions.................................................................................................85
6 Maintenance..................................................................................................................90
6.6 COOLERS.......................................................................................................................................97
7 Problem solving..........................................................................................................101
2920 7110 00 3
Instruction book
8 Technical data.............................................................................................................106
12 Declaration of conformity..........................................................................................122
4 2920 7110 00
Instruction book
1 Safety precautions
Explanation
Warning
Important note
General precautions
1. The operator must employ safe working practices and observe all related work safety requirements and
regulations.
2. If any of the following statements does not comply with the applicable legislation, the stricter of the two
shall apply.
3. Installation, operation, maintenance and repair work must only be performed by authorized, trained,
specialized personnel.
4. The compressor is not considered capable of producing air of breathing quality. For air of breathing quality,
the compressed air must be adequately purified according to the applicable legislation and standards.
5. Before any maintenance, repair work, adjustment or any other non-routine checks, stop the compressor,
press the emergency stop button, switch off the voltage and depressurize the compressor. In addition, the
power isolating switch must be opened and locked.
The units are powered by a frequency converter, wait 10 minutes before starting any electrical repair.
In a domestic environment, this product may cause radio interference in which case
supplementary mitigation measures are required.
If the machine is equipped with an automatic restart after voltage failure function and if this
function is active, be aware that the machine will restart automatically when the power is
restored if it was running when the power was interrupted!
6. Never play with compressed air. Do not apply the air to your skin or direct an air stream at people. Never
use the air to clean dirt from your clothes. When using the air to clean equipment, do so with extreme
caution and wear eye protection.
7. The owner is responsible for maintaining the unit in safe operating condition. Parts and accessories shall
be replaced if unsuitable for safe operation.
8. It is not allowed to walk or stand on the unit or on its components.
2920 7110 00 5
Instruction book
6 2920 7110 00
Instruction book
16. Piping or other parts with a temperature in excess of 70˚C (158˚F) and which may be accidentally touched
by personnel in normal operation must be guarded or insulated. Other high temperature piping must be
clearly marked.
17. For water-cooled machines, the cooling water system installed outside the machine has to be protected by
a safety device with set pressure according to the maximum cooling water inlet pressure.
18. If the ground is not level or can be subject to variable inclination, consult the manufacturer.
19. If the device is a dryer and no free extinguishing system is present in the air net close to the dryer, safety
valves must be installed in the vessels of the dryer.
Also consult following safety precautions: Safety precautions during operation and Safety
precautions during maintenance.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the application
which are not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.
2920 7110 00 7
Instruction book
Also consult following safety precautions: Safety precautions during installation and Safety
precautions during maintenance.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the application
which are not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.
8 2920 7110 00
Instruction book
12. Whenever there is an indication or any suspicion that an internal part of a machine is overheated, the
machine shall be stopped but no inspection covers shall be opened before sufficient cooling time has
elapsed; this to avoid the risk of spontaneous ignition of the oil vapour when air is admitted.
13. Never use a light source with open flame for inspecting the interior of a machine, pressure vessel, etc.
14. Make sure that no tools, loose parts or rags are left in or on the machine.
15. All regulating and safety devices shall be maintained with due care to ensure that they function properly.
They may not be put out of action.
16. Before clearing the machine for use after maintenance or overhaul, check that operating pressures,
temperatures and time settings are correct. Check that all control and shut-down devices are fitted and that
they function correctly. If removed, check that the coupling guard of the compressor drive shaft has been
reinstalled.
17. Every time the separator element is renewed, examine the discharge pipe and the inside of the oil separator
vessel for carbon deposits; if excessive, the deposits should be removed.
18. Protect the motor, air filter, electrical and regulating components, etc. to prevent moisture from entering
them, e.g. when steam cleaning.
19. Make sure that all sound-damping material and vibration dampers, e.g. damping material on the bodywork
and in the air inlet and outlet systems of the compressor, is in good condition. If damaged, replace it by
genuine material from the manufacturer to prevent the sound pressure level from increasing.
20. Never use caustic solvents which can damage materials of the air net, e.g. polycarbonate bowls.
21. The following safety precautions are stressed when handling refrigerant:
• Never inhale refrigerant vapours. Check that the working area is adequately ventilated; if required, use
breathing protection.
• Always wear special gloves. In case of refrigerant contact with the skin, rinse the skin with water. If
liquid refrigerant contacts the skin through clothing, never tear off or remove the latter; flush
abundantly with fresh water over the clothing until all refrigerant is flushed away; then seek medical
first aid.
Also consult following safety precautions: Safety precautions during installation and Safety
precautions during operation.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the application
which are not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.
2920 7110 00 9
Instruction book
2 General description
2.1 Introduction
Introduction
GA 18 VSD+ up to GA 37 VSD+ are single-stage, oil-injected screw compressors driven by an interior
permanent magnet motor (IPM).
The compressors are controlled by the Atlas Copco Elektronikon® Graphic regulator (ER).
The regulator is fitted to the front panel. An electric cabinet (1) comprising fuses, transformers, relays, etc.
is located behind this panel.
The compressors use VSD (Variable Speed Drive) technology. This means: automatic adjustment of the motor
speed, depending on the compressed air demand.
The compressors are air-cooled and are enclosed in a sound-insulated bodywork.
GA Workplace
10 2920 7110 00
Instruction book
GA Workplace Full-Feature
The Workplace Full Feature compressors have an air dryer which is integrated in the sound-insulated
bodywork. The dryer removes condensate from the compressed air by cooling the air to near freezing point.
2920 7110 00 11
Instruction book
Reference Name
AF Air filter
AR Air receiver
AV Air outlet
Ca Air cooler
12 2920 7110 00
Instruction book
Reference Name
Co Oil cooler
Da Automatic condensate outlet
Dm Manual condensate outlet
DR Refrigerant dryer
E Compressor element
ED Electronic water drain
ER Elektronikon® Graphic controller
FN Cooling fan
IPM Drive motor
OF Oil filter
OS Oil separator
S3 Emergency stop button
1 Electric cabinet
2920 7110 00 13
Instruction book
14 2920 7110 00
Instruction book
Reference Description
A Air inlet
B Air/oil mixture
C Oil
D Wet compressed air
E Condensate
2920 7110 00 15
Instruction book
Reference Description
F Dry compressed air (Full-Feature)
Air flow
Air comes in through filter (AF) and inlet valve (IV) and is compressed in the compressor element (E).
A mixture of compressed air and oil flows into the air receiver/oil separator (AR).
The air flows through the minimum pressure valve (Vp), the air cooler (Ca) and the condensate trap (MT) to
the outlet valve (AV).
Minimum pressure valve (Vp) prevents the receiver pressure from dropping below a minimum pressure and
includes a check valve which prevents blow-back of compressed air from the net.
Full-Feature compressors have a dryer (DR) after the air cooler.
Oil circuit
The air receiver (AR) removes most of the oil from the air/oil mixture by centrifugal action. The oil separator
(OS) removes the remaining oil. The oil collects in the lower part of the air receiver (AR) which serves as oil
tank.
The oil system has a thermostatic bypass valve (BV).
When the oil temperature is below 71 ˚C (160 ˚F), the bypass valve shuts off the oil supply to the oil cooler
(Co).
Air pressure forces the oil from air receiver (AR) through the oil filter (OF). The oil cooler (Co) is bypassed.
When the oil temperature has increased up to 71˚C (160 ˚F), bypass valve (BV) starts opening the supply to
the oil cooler (Co). At approx. 85˚C (185 ˚F), all the oil flows through the oil cooler.
The filtered oil flows through the cooling channels of the permanent magnetic motor (IPM) into the compressor
element (E).
Cooling
The cooling system has an air cooler (Ca) and an oil cooler (Co).
The fan (FN) blows air over the coolers. This fan is set on and off, depending on the operating conditions,
according to a specific algorithm.
Drain connections
The compressors have an electronic water drain (ED).
16 2920 7110 00
Instruction book
The water in the air condenses in the collector of the air cooler. When the condensate comes to a certain level,
it drains through the automatic drain outlet (Da).
On a GA Workplace Full-Feature, the water in the air also condenses in the separator of the heat exchanger/
evaporator. When the condensate comes to a certain level, it drains through the automatic drain outlet (Da).
2920 7110 00 17
Instruction book
Reference Designation
Da Automatic drain connection
Dm Manual drain connection
Test the electronic water drain. Press the test button (2) on top of the device.
Description
If the air consumption is less than the air output of the compressor, the net pressure increases.
When the net pressure is higher than the set-point (desired net pressure), the regulator decreases the motor
speed.
If the net pressure increases and the motor operates at minimum speed, the regulator stops the motor.
When the motor is stopped automatically and the net pressure comes to the set-point, the regulator starts the
motor again.
18 2920 7110 00
Instruction book
Electric components
The electrical system has following components:
Reference Designation
T1 Transformer
Q15 Circuit breaker
Q1 Circuit breaker
K15 Contactor
Z1 EMC filter
U1 Frequency converter
Electrical diagrams
You find the complete electrical diagram inside the electric cabinet.
2920 7110 00 19
Instruction book
Flow diagram
Air dryer
Reference Name
AI Air inlet
AO Air outlet
1 Air/air heat exchanger
2 Air/refrigerant heat exchanger/evaporator
3 Condensate separator
4 Automatic drain / condensate outlet
5 Refrigerant compressor
6 Refrigerant condenser
7 Liquid refrigerant dryer/filter
8 Capillary
9 Bypass valve
10 Condenser cooling fan
11 Pressure switch, fan control
12 Liquid separator
20 2920 7110 00
Instruction book
This causes the air to cool further close to the evaporating temperature of the refrigerant. More water in the
air condenses.
The cold air flows through the separator (3) where all the condensate gets out of the air.
The condensate is automatically drained through the outlet (4).
The outgoing, cold, dried air flows through the heat exchanger (1) where it is warmed up by the incoming
compressed air.
Refrigerant circuit
Refrigeration dryers of ID type contain high efficient refrigerant R410a of the HFC group.
The refrigerant compressor (5) delivers hot, high-pressure refrigerant gas which flows through the refrigerant
condenser (6).
Most of the refrigerant condenses.
The liquid refrigerant flows through the liquid refrigerant dryer/filter (7) to the capillary tube (8).
The refrigerant leaves the capillary tube at about evaporating pressure.
The refrigerant enters the evaporator (2) where it gets heat from the compressed air by further evaporation at
about constant pressure.
The heated refrigerant leaves the evaporator and gets into the compressor (5) through a liquid separator (12).
A by-pass valve (9) regulates the refrigerant flow.
The fan (10) blows cool air over the refrigerant condenser (6)
The switch (11) sets the fan (10) to on or off, depending on the pressure degree of the condensate.
2920 7110 00 21
Instruction book
Control panel
Introduction
The Elektronikon® controller has following functions:
• Controlling the compressor
• Protecting the compressor
• Monitoring components subject to service
• Automatic restart after voltage failure (made inactive)
A number of time based automatic start/stop commands may be programmed. Take into
account that a start command will be executed (if programmed and activated), even after
manually stopping the compressor.
22 2920 7110 00
Instruction book
Shut-down warning
A shut-down warning level is a programmable level below the shut-down level.
If one of the measured signals exceeds the programmed shut-down warning level, a message will appear on
display (1) and general alarm LED (2) will light up to warn the operator that the shut-down warning level is
exceeded.
The message disappears as soon as the warning condition disappears.
Warning
A warning message will appear if, on Full-Feature compressors, the dew point temperature is too high in
relation to the ambient temperature.
Service warning
A number of service operations are grouped (called Service Plans). Each Service Plan has a programmed time
interval. If a time interval is exceeded, a message will appear on display (1) to warn the operator to carry out
the service actions belonging to that Service Plan.
If the function is activated and provided the regulator was in the automatic operation mode,
the compressor will automatically restart if the supply voltage to the module is restored.
2920 7110 00 23
Instruction book
Elektronikon regulator
Control panel
24 2920 7110 00
Instruction book
Status icons
Running unloaded
Running loaded
or
Network control
Automatic restart after voltage Automatic restart after voltage failure is active
failure
2920 7110 00 25
Instruction book
Shutdown
Warning
Not valid
Input icons
Icon Description
Pressure
Temperature
Digital input
Special protection
26 2920 7110 00
Instruction book
System icons
Icon Description
Compressor element (LP, HP, ...)
Dryer
Fan
Frequency converter
Drain
Filter
Motor
Network problem
General alarm
Menu icons
Icon Description
Inputs
Outputs
Counters
Test
or
2920 7110 00 27
Instruction book
Icon Description
Settings
Service
Network
Setpoint
Info
Navigation arrows
Icon Description
Up
Down
28 2920 7110 00
Instruction book
Control panel
Function
The Main screen is the screen that is shown automatically when the voltage is switched on and one of the
keys is pushed. It is switched off automatically after a few minutes when no keys are pushed.
Typically, 5 different main screen views can be chosen:
1. Two value lines
2. Four value lines
3. Chart (High resolution)
4. Chart (Medium resolution)
5. Chart (Low resolution)
2920 7110 00 29
Instruction book
Text on figures
Text on figures
• Section A shows information regarding the compressor operation (e.g. the outlet pressure or the
temperature at the compressor outlet). On compressors with a frequency converter, the load degree (flow)
is given in % of the maximum flow.
• Section B shows Status icons. Following icon types are shown in this field:
• Fixed icons
These icons are always shown in the main screen and cannot be selected by the cursor (e.g. Compressor
stopped or running, Compressor status (running, running unloaded or motor stopped).
• Optional icons
These icons are only shown if their corresponding function is activated (e.g. week timer, automatic
restart after voltage failure , etc.)
• Pop up icons
These icons pop up if an abnormal condition occurs (warnings, shutdowns, service,...)
To call up more information about the icons shown, select the icon concerned using the scroll keys and
press the enter key.
• Section C is called the Status bar
This bar shows the text that corresponds to the selected icon.
30 2920 7110 00
Instruction book
Designation Function
Menu To go to the menu
Modify To modify programmable settings
Reset To reset a timer or message
To activate an action button, highlight the button by using the Scroll keys and press the Enter key.
To go back to the previous menu, press the Escape key.
Chart views
Instead of viewing values, it is also possible to view a graph of one of the input signals (see section Inputs
menu) in function of the time.
When Chart (High Resolution) is selected, the chart shows the variation of the selected input (in this case the
pressure) per minute. Also the instantaneous value is displayed. The screen shows the last 4 minutes.
The switch button (icon) for selecting other screens is changed into a small Chart and is highlighted (active).
When the Chart (Medium Resolution) is selected, the chart shows the variation of the selected input per
hour. The screen shows the last 4 hours.
2920 7110 00 31
Instruction book
When the Chart (Low Resolution) is selected, the chart shows the variation of the selected input per day. The
screen shows the evolution over the last 10 days.
Select the layout required and press the Enter key. See also section Inputs menu.
32 2920 7110 00
Instruction book
Control panel
Control panel
Description
When the voltage is switched on, the main screen is shown automatically (see section Main screen):
• To go to the Menu screen, select <Menu> (3), using the Scroll keys.
• Press the Enter key to select the menu. Following screen appears:
2920 7110 00 33
Instruction book
• The screen shows a number of icons. Each icon indicates a menu item. By default, the Pressure Settings
(Regulation) icon is selected. The status bar shows the name of the menu that corresponds with the selected
icon.
• Use the Scroll keys to select an icon.
• Press the Escape key to return to the Main screen.
Control panel
Function
• To display the actual value of the measured data (analog inputs) and the status of the digital inputs (e.g.
emergency stop contact, motor overload relay, etc.).
• To select the digital input to be shown on the chart in the main screen.
34 2920 7110 00
Instruction book
Procedure
Starting from the main screen,
• Move the cursor to the action button Menu and press the Enter key. Following screen appears:
Text on image
(1) Menu
(2) Regulation
• Using the Scroll keys, move the cursor to the Inputs icon (see above, section Menu icon).
• Press the Enter key. A screen similar to the one below appears:
Text on image
(1) Inputs
(2) Compressor outlet
(3) Element outlet
(4) Ambient air
(5) Emergency stop
• The screen shows a list of all inputs with their corresponding icons and readings.
• If an input is in warning or shutdown, the original icon is replaced by the warning or shutdown icon
respectively (i.c. the Stop icon and the Warning icon in the screen shown above).
A small chart icon, shown below an item in the list means this input signal is shown on the chart at the main
screen. Any analog input can be selected.
2920 7110 00 35
Instruction book
The first item in the list is highlighted. In this example, the Net Pressure is selected (chart icon).
To change, press the Enter button again: a pop-up window opens:
Press Enter again to remove this input from the chart. Another confirmation pop-up opens:
36 2920 7110 00
Instruction book
Control panel
Function
To call up information regarding the actual status of some outputs such as the condition of the Fan overload
contact (on air cooled compressors), the Emergency stop contact, etc.
Procedure
Starting from the Main screen,
• Move the cursor to the action button Menu and press the Enter key. Following screen appears:
Text on figure
2920 7110 00 37
Instruction book
(1) Menu
(2) Regulation
• Move the cursor to the Outputs icon (see above, section Menu icon, using the Scroll keys.
• Press the Enter key. A screen similar to the one below appears:
Text on image
(1) Outputs
(2) Fan motor contact
(3) Blow-off contact
(4) General shutdown
(5) Automatic operation
• The screen shows a list of all outputs with their corresponding icons and readings.
If an output is in warning or shutdown, the original icon is replaced by the warning or shutdown icon
respectively.
3.8 Counters
Control panel
38 2920 7110 00
Instruction book
Function
To call up:
• The running hours
• The loaded hours
• The number of motor starts
• The number of hours that the regulator has been powered
• The number of load cycles
• The number of recirculation cycles
• The number of recirculation cycle failures
Procedure
Starting from the Main screen (see Main screen),
• Move the cursor to the action button Menu and press the Enter key. Following screen appears:
Text on figure
(1) Menu
(2) Regulation
• Using the Scroll keys, move the cursor to the Counters icon (see above, section Menu icon)
• Press the Enter key. Following screen appears:
Text on figure
2920 7110 00 39
Instruction book
(1) Counters
(2) Running Hours
(3) Motor Starts
(4) Load Relay
(5) VSD 1-20 % rpm in % (the percentage of the time during which the motor speed
was between 1 and 20 %)
(6) Recirculation Cycles
(7) Recirculation Failures
The screen shows a list of all counters with their actual readings.
Control panel
Function
To select the control mode, i.e. whether the compressor is in local control, remote control or controlled via a
local area network (LAN).
Procedure
Starting from the main screen, make sure the button Menu (1) is selected:
40 2920 7110 00
Instruction book
Next, use the scroll buttons to go to the regulation icon (2) and press the enter button:
After selecting the required regulation mode, press the enter button on the controller to confirm your selection.
The new setting is now visible on the main screen. See section Icons used for the meaning of the icons.
2920 7110 00 41
Instruction book
Control panel
Function
• To reset the service plans which are carried out.
• To check when the next service plans are to be carried out.
• To find out which service plans were carried out in the past.
• To modify the programmed service intervals.
Procedure
Starting from the Main screen,
• Move the cursor to the action button Menu and press the Enter key. Following screen appears:
• Using the Scroll keys, move the cursor to the Service icon (see above, section Menu icon).
42 2920 7110 00
Instruction book
Text on image
(1) Service
(2) Overview
(3) Service plan
(4) Next service
(5) History
• Scroll through the items to select the desired item and press the Enter key to see the details as explained
below.
Overview
Text on image
(1) Overview
(2) Running Hours
(3) Real Time hours
(4) Reset
2920 7110 00 43
Instruction book
The figures within the bars are the number of hours to go till the next service intervention. In the example
above, the compressor was just started up, which means it still has 4000 running hours or 8280 hours to go
before the next Service intervention.
Service plans
A number of service operations are grouped (called Level A, Level B, etc...). Each level stands for a number
of service actions to be carried out at the time intervals programmed in the Elektronikon® controller.
When a service plan interval is reached, a message will appear on the screen.
After carrying out the service actions related to the indicated levels, the timers must be reset.
From the Service menu above, select Service plan (3) and press Enter. Following screen appears:
Text on image
44 2920 7110 00
Instruction book
Modify the value as required using the ↑ or ↓ scroll key and press the Enter key to confirm.
Note: Running hours can be modified in steps of 100 hours, real time hours can be modified in steps of 1
hour.
Next Service
Text on image
In the example above, the A Service level is programmed at 4000 running hours, of which 0 hours have passed.
History
The History screen shows a list of all service actions done in the past, sorted by date. The date at the top is
the most recent service action. To see the details of a completed service action (e.g. Service level, Running
hours or Real time hours), use the Scroll keys to select the desired action and press the Enter key.
2920 7110 00 45
Instruction book
Control panel
Function
On compressors with a frequency converter driven main motor, it is possible to program two different
setpoints. This menu is also used to select the active setpoint.
Procedure
Starting from the Main screen,
• Highlight the action key Menu using the Scroll keys and press the Enter key. Following screen appears:
Text on image
46 2920 7110 00
Instruction book
(1) Menu
(2) Regulation
• Activate the menu by pressing the enter key. A screen similar to the one below appears:
Text on image
(1) Regulation
(2) Setpoint 1
(3) Indirect stop level 1
(4) Direct stop level 1
(5) Setpoint 2
(6) Modify
• The first line of the screen is highlighted. Use the Scroll keys (1) to highlight the setting to be modified
and press the Enter key (2). Following screen appears:
The upper and lower limit of the setting is shown in grey, the actual setting is shown in black. Use the ↑
or ↓ key of the Scroll keys to modify the settings as required and press the Enter key to accept.
2920 7110 00 47
Instruction book
If necessary, change the other settings as required in the same way as described above.
Indirect stop: occurs when the pressure rises to the pre-set Indirect stop setpoint (= setpoint plus Indirect stop
level). The motor will decelerate to minimum speed and the compressor will switch to unloaded condition.
Direct stop: occurs when the compressor runs at a speed between minimum and maximum and the net pressure
rises above the direct stop setpoint (= setpoint plus Direct stop level).
Both settings (Indirect stop level and Direct stop level) are programmable, see section Programmable settings.
Control panel
Function
To call up the last shut-down and last emergency stop data.
Procedure
Starting from the Main screen,
• Move the cursor to the action button Menu and press the Enter key. Following screen appears:
48 2920 7110 00
Instruction book
• Using the Scroll keys, move the cursor to the Event History icon (see above, section Menu icon)
• The list of last shut-down and emergency stop cases is shown.
• Scroll through the items to select the desired shut-down or emergency stop event.
• Press the Enter key to find the date, time and other data reflecting the status of the compressor when that
shut-down or emergency stop occurred.
Control panel
2920 7110 00 49
Instruction book
Function
To display and modify a number of settings.
Procedure
Starting from the Main screen,
• Move the cursor to the action button Menu and press the Enter key. Following screen appears:
• Next, move the cursor to the Settings icon (see above, section menu icon).using the Scroll keys.
• Press the Enter key. Following screen appears:
This screen shows again a number of icons. By default, the User Password icon is selected. The status bar
shows the description that corresponds with the selected icon. Each icon covers one or more items , such
as
• Access level
• Elements
• Dryer
• Fan
• Converter(s)
• Filter(s)
• Motor/Starter
• General
• Automatic restart after voltage failure (ARAF)
• Network
• Regulation
• Remote
For adapting certain parameters, a password may be necessary.
Example: Selecting the General Settings icon gives the possibility to change e.g. the language, the date,
the date format, etc.:
50 2920 7110 00
Instruction book
Text on image
(1) General
(2) Language used
(3) Time
(4) Date
(5) Date format
(6) Modify
• To modify, select the Modify button using the Scroll keys and press the Enter key.
• A screen similar to the one above is shown, the first item (Language) is highlighted. Use the ↓ key of the
Scroll keys to select the setting to be modified and press the Enter key.
• A pop-up screen appears. Use the ↑ or ↓ key to select the required value and press the Enter key to confirm.
Control panel
2920 7110 00 51
Instruction book
Function
To show the Atlas Copco internet address.
Procedure
Starting from the Main screen,
• Move the cursor to the action button Menu and press the Enter key. Following screen appears:
• Using the Scroll keys, move the cursor to the Info icon (see above, section Menu icon).
• Press the Enter key. The Atlas Copco internet address appears on the screen.
Control panel
52 2920 7110 00
Instruction book
Function
• To program time-based start/stop commands for the compressor
• To program time-based change-over commands for the net pressure band
• Four different week schemes can be programmed.
• A week cycle can be programmed, a week cycle is a sequence of 10 weeks. For each week in the cycle,
one of the four programmed week schemes can be chosen.
Important remark:
In the Elektronikon you can select different timers on one day.(up to 8 actions). It is
however not possible to program 2 actions at the same time. The solution: leave at least
1 minute in between 2 actions.
Example: Start Compressor: 5.00 AM, Pressure Setpoint 2: 5.01 AM (or later).
Procedure
Starting from the Main screen (see Main screen),
• Move the cursor to the action button Menu and press the Enter key. Use the Scroll buttons to select the
Timer icon.
Text on figure
(1) Menu
(2) Week Timer
2920 7110 00 53
Instruction book
The first item in this list is highlighted in red. Select the item requested and press the Enter key on the
controller to modify.
• A weekly list is shown. Monday is automatically selected and highlighted in red. Press the Enter key on
the controller to set an action for this day.
54 2920 7110 00
Instruction book
(6) Friday
(7) Saturday
(8) Sunday
• A new window opens. The Modify action button is selected. Press the enter button on the controller to
create an action.
(1) Monday
(2) Modify
• A new pop-up window opens. Select an action from this list by using the Scroll keys on the controller.
When ready press the Enter key to confirm.
(1) Monday
(2) Actions
(3) Remove
(4) Start
(5) Stop
(6) Pressure Setpoint 1
(7) Modify
• A new window opens. The action is now visible in the first day of the week.
2920 7110 00 55
Instruction book
(1) Monday
(2) Start
(3) Save
(4) Modify
• To adjust the time, use the Scroll keys on the controller and press the Enter key to confirm.
(1) Monday
(2) Start
(3) Save
(4) Modify
• A pop-up window opens. Use the ↑ or ↓ key of Scroll keys to modify the values of the hours. Use the ←
or → Scroll keys to go to the minutes.
(1) Monday
(2) Time
(3) Save
(4) Modify
56 2920 7110 00
Instruction book
• Press the Escape key on the controller. The action button Modify is selected. Use the Scroll keys to select
the action Save.
(1) Monday
(2) Start
(3) Save
(4) Modify
• A new pop-up window opens. Use the Scroll keys on the controller to select the correct actions. Press the
Enter key to confirm.
(1) Monday
(3) Are you sure?
(4) No
(5) Yes
(6) Save
(7) Modify
2920 7110 00 57
Instruction book
58 2920 7110 00
Instruction book
(3) Week 2
(4) Week 3
(5) Week 4
(6) Modify
Press twice the Enter key on the controller to modify the first week.
• A new window opens. Select the action, example: Week Action Scheme 1
• A new window opens. Select Week 1 to set the Week Timer active.
2920 7110 00 59
Instruction book
• Press the Escape key on the controller to leave this window. The status shows that week 1 is active.
• Press the Escape key on the controller to go to the main Week Timer menu. Select Remaining Running
Time from the list and press the Enter key on the controller to Modify.
60 2920 7110 00
Instruction book
• This timer is used when the week timer is set and for certain reasons the compressor must continue working,
for example, 1 hour, it can be set in this screen. This timer is prior to the Week Timer action.
Control panel
2920 7110 00 61
Instruction book
or
Function
• To carry out a display test, i.e. to check whether the display and LEDs are still intact.
Procedure
Starting from the Main screen,
• Move the cursor to the action button Menu and press the enter key (2), following screen appears:
• Using the scroll keys (1), move the cursor to the test icon (see above, section Menu icon)
• Press the enter key (2), following screen appears:
• The safety valve test can only be performed by authorized personnel and is protected by a security code.
• Select the item display test and press the enter key. A screen is shown to inspect the display, at the same
time all LED's are lit.
62 2920 7110 00
Instruction book
Control panel
Function
If the password option is activated, it is impossible for not authorized persons to modify any setting.
Procedure
Starting from the Main screen (see Main screen),
• Move the cursor to <Menu> and press the Enter key (2). Following screen appears:
• Using the Scroll keys, select the <Settings> icon (see section Modifying general settings)
• Press the Enter key. Following screen appears:
2920 7110 00 63
Instruction book
• Move the cursor to the Password icon (see above, section Menu icon)
• Select <Modify> using the Scroll keys and press the Enter key. Next, modify the password as required.
Getting started
• Use a UTP cable (CAT 5e) to connect to the controller (see picture below).
64 2920 7110 00
Instruction book
• Select the Local Area connection (1), which is connected to the controller.
2920 7110 00 65
Instruction book
• Use the check box Internet Protocol (TCP/IP) (1) (see picture). To avoid conflicts, uncheck other properties
if they are checked. After selecting TCP/IP, click on the Properties button (2) to change the settings.
The internal web server is designed and tested for Microsoft® Internet Explorer 6, 7 and
8. Other web browsers like Opera and Firefox do not support this internal web server.
When using Opera or Firefox, a redirect page opens. Click on the hyperlink to connect to
the download server from Microsoft® to download the latest version of Internet Explorer,
and install this software.
66 2920 7110 00
Instruction book
• Click on the Connections tab (1) and then click on the LAN settings button (2).
• In the Proxy server Group box, click on the Advanced button (1).
2920 7110 00 67
Instruction book
• In the Exceptions Group box, enter the IP address of your controller. Multiple IP addresses can be given
but they must be separated with semicolons (;).
Example: Suppose that you already added two IP addresses (192.168.100.1 and 192.168.100.2). Now you
add 192.168.100.100 and separate the 3 IP addresses by putting semicolons between them (1) (see picture).
Click OK (2) to close the window.
68 2920 7110 00
Instruction book
All screen shots are indicative. The number of displayed fields depends on the selected
options.
• Open your browser and type the IP address of the controller you want to view in your browser (in this
example http://192.168.100.100). The interface opens:
• On the left side of the interface you can find the navigation menu (see picture below).
If a license for ESi is foreseen, the menu contains 3 buttons.
• Compressor (or machine): shows all compressor settings.
• Es: shows the ESi status (if a license is provided).
• Preferences: allows to change temperature and pressure units.
2920 7110 00 69
Instruction book
Compressor settings
All compressor settings can be displayed or hidden. Put a check mark in front of each point of interest and it
will be displayed. Only the machine status is fixed and can not be removed from the main screen.
Analog inputs
Lists all current analog input values. The measurement units can be changed in the preference button from
the navigation menu.
Counters
Lists all current counter values from controller and compressor.
Info status
Machine status is always shown on the web interface.
Digital inputs
Lists all Digital inputs and their status.
70 2920 7110 00
Instruction book
Digital outputs
Lists all Digital outputs and their status.
Special protections
Lists all special protections of the compressor.
Service plan
Displays all levels of the service plan and their status. This screen shot underneath only shows the running
hours. It is also possible to show the current status of the service interval.
ES screen controller
If an ESi license is provided, the ES button is displayed in the navigation menu. At the left all compressors
in the ES are shown. At the right the ES status is shown.
2920 7110 00 71
Instruction book
Compressor/motor
Parameters
72 2920 7110 00
Instruction book
Protections
Service plan
The built-in service timers will give a Service warning message after their respective preprogrammed time
interval has elapsed.
For specific data, see section Preventive Maintenance.
Consult Atlas Copco if a timer setting needs to be changed. The intervals must not exceed the nominal intervals
and must coincide logically. See section Modifying general settings.
Terminology
Term Explanation
ARAVF Automatic Restart After Voltage Failure. See section Elektronikon regulator.
Power recovery Is the period within which the voltage must be restored to have an automatic restart. Is
time accessible if the automatic restart is activated. To activate the automatic restart function,
consult Atlas Copco.
Restart delay This parameter allows to programme that not all compressors are restarted at the same
time after a power failure (ARAVF active).
Compressor The recommended minimum setting is 70 ˚C (158 ˚F). For testing the temperature sensor
element outlet the setting can be decreased to 50 ˚C (122 ˚F). Reset the value after testing.
The regulator does not accept inconsistent settings, e.g. if the warning level is programmed
at 95 ˚C (203 ˚F), the minimum limit for the shut-down level changes to 96 ˚C (204 ˚F). The
recommended difference between the warning level and shut-down level is 10 ˚C (18 ˚F).
Delay at signal Is the time period during which the warning signal must exist before the warning message
appears.
Delay at start Is the time period after starting which must expire before generating a warning. The setting
should be less than the setting for the delay at signal.
Minimum stop Once the compressor has automatically stopped, it will remain stopped for the minimum
time stop time, whatever happens with the net air pressure.
2920 7110 00 73
Instruction book
Term Explanation
Proportional band The settings for the Proportional band and integration time are determined by experiment.
and integration Altering these settings may damage the compressor. Consult Atlas Copco.
time
74 2920 7110 00
Instruction book
4 Installation
2920 7110 00 75
Instruction book
Type L B H Weight
(mm) (mm) (mm) (kg)
GA 18 VSD+ 380-460V 380 390 760 367
GA 22 VSD+ 380-460V 380 390 760 363
GA 26 VSD+ 380-460V 380 390 765 373
GA 30 VSD+ 380-460V 380 390 765 376
GA 37 VSD+ 380-460V 380 390 765 376
76 2920 7110 00
Instruction book
Type L B H Weight
(mm) (mm) (mm) (kg)
GA 18 VSD+ FF 380-460V 580 390 330 480
GA 18 VSD+ FF with trafo 200-230V 690 360 310 635
GA 18 VSD+ FF with trafo 500-575V 635 375 310 545
GA 18 VSD+ with trafo 200-230V 640 355 300 570
GA 18 VSD+ with trafo 500-575V 565 370 300 480
GA 22 VSD+ FF 380-460V 580 390 330 485
GA 22 VSD+ FF with trafo 200-230V 705 355 310 670
GA 22 VSD+ FF with trafo 500-575V 640 375 310 550
GA 22 VSD+ with trafo 200-230V 660 350 295 610
GA 22 VSD+ with trafo 500-575V 575 370 300 490
GA 26 VSD+ FF 380-460V 580 390 330 490
GA 26 VSD+ FF with trafo 200-230V 710 355 300 700
GA 26 VSD+ FF with trafo 500-575V 645 375 310 570
GA 26 VSD+ with trafo 200-230V 670 350 295 630
GA 26 VSD+ with trafo 500-575V 585 365 300 500
GA 30 VSD+ FF 380-460V 580 390 335 500
GA 30 VSD+ FF with trafo 200-230V 740 350 305 755
GA 30 VSD+ FF with trafo 500-575V 670 370 315 590
GA 30 VSD+ with trafo 200-230V 690 340 290 680
GA 30 VSD+ with trafo 500-575V 595 365 300 520
GA 37 VSD+ FF 380-460V 580 390 335 500
GA 37 VSD+ FF with trafo 200-230V 740 350 305 735
GA 37 VSD+ FF with trafo 500-575V 670 370 315 630
GA 37 VSD+ with trafo 200-230V 690 340 290 655
GA 37 VSD+ with trafo 500-575V 595 365 300 560
Dimensions +/- 10 mm
Weights (oil included) +/- 10 kg
Reference Designation
1 Electric cable entry
for 380 V - 460 V
(use the cable tray inside the bottom of the frame)
2 Cooling air outlet
3 Compressor air outlet
4 Compressor cooling air inlet
5 Manual drain
6 Automatic drain
7 Cubicle and converter cooling air inlet
8 Oil level indicator
9 Dryer cooling air inlet
10 Electric cable entry for 200 - 230 V and 500 - 575 V
11 Compressor air inlet
* Bottom view
2920 7110 00 77
Instruction book
Text on figure
1 Ventilation proposals
2 Minimum free area to be reserved for the compressor installation
Description
1 Compressor unit:
Install the compressor unit on a solid, level floor suitable for taking the weight.
2 Position of the compressed air outlet valve.
78 2920 7110 00
Instruction book
3 Delivery pipe:
The pressure drop over the air delivery pipe can be calculated as follows:
Δp = (L x 450 x Qc1.85) / (d5 x P), with
d = inner diameter of the pipe in mm
Δp = pressure drop (recommended maximum: 0.1 bar (1.5 psi)
L = length of the pipe in m
P = absolute pressure at the compressor outlet in bar(a)
Qc = free air delivery of the compressor in l/s
Connect air outlet pipe of the compressor on top of the main air net pipe. In this way, there is a
minimum carry-over of condensate residue.
4 Ventilation:
When you install the inlet grids and ventilation fan, make sure that no re-circulation of cooling air
into the compressor or into the dryer is possible.
The maximum air velocity through the grids is 5 m/s (16.5 ft/s).
The maximum air temperature at the compressor intake is 46 ˚C (115 ˚F).
The minimum air temperature at the compressor intake is 0 ˚C (32 ˚F).
Alternatives 1 and 3: the required ventilation to limit the compressor room temperature is
calculated as follows:
• Qv = 1.24 N/ΔT (for units without dryer)
• Qv = 1.29 N/ΔT (for units with dryer)
Qv = Required ventilation capacity in m3/s
N = Shaft input of compressor in kW
ΔT = Temperature increase in compressor room in °C
Alternatives 2 and 4:
Make sure that the cooling air duct of the air/oil cooler is separated from the cooling air duct of the
dryer.
The maximum pressure drop over the additional air/oil ducts is limited to 20 Pa for the standard fans.
5 Drain pipes:
Make sure that the drain pipes to the drain collector do not dip into the water of the drain collector.
Atlas Copco has oil/water separators (type OSD or OSCi) to separate the major part of the oil from
the condensate to ensure that the condensate meets the requirements of the environmental codes.
6 Control module with monitoring panel.
7 Power supply cable:
Have the power supply cable installed by a qualified electrician.
In case of an IT network, consult Atlas Copco.
To preserve the protection degree of the electric cubicle and to protect its components from dust
from the environment, it is mandatory to use a proper cable gland when connecting the supply cable
to the compressor.
8 Filter, type DD for general purposes
The filter traps solid particles down to 1 micron with a max. oil carry-over of 0.5 mg/m3.
A high-efficiency filter, type PD, may be installed downstream of a DD filter. This filter traps solid
particles down to 0.01 micron with a max. oil carry-over of 0.01 mg/m3.
If oil vapours and odours are undesirable, install a QD type filter downstream of the PD filter.
Install bypass pipes over each filter together with ball valves. This ensures that service operations
do not disturb the compressed air delivery .
9 Air tank:
Install the air tank (optional) in a frost free room, on a solid level floor suitable for taking the weight.
Install a safety valve on the air tank.
10 Outlet cooling air grating of the air cooler and the oil cooler.
11 Outlet cooling air grating of the dryer.
2920 7110 00 79
Instruction book
Safety
Apply all relevant safety precautions, including those mentioned in this book.
Outdoor/altitude operation
The compressors are not designed for outdoor use.
The compressors can only be used in temperatures above 0 °C (+32 °F). If frost might occur, the appropriate
measures should be taken to avoid damage to the machine and its ancillary equipment. In this case, consult
Atlas Copco.
Also if operating above 1000 m (3300 ft), consult Atlas Copco.
Moving/lifting
The compressor can be moved by a lift truck using the slots in the frame. Take care not to damage the bodywork
during lifting or transport. Before lifting, reinstall the transport securing bolts. Make sure that the forks
protrude from the other side of the frame. The compressor can also be lifted after inserting beams in the slots.
Make sure that the beams cannot slide and that they protrude from the frame equally. The chains must be held
parallel to the bodywork by chain spreaders in order not to damage the compressor. The lifting equipment
must be placed in such a way that the compressor is lifted perpendicularly. Lift gently and avoid twisting.
In case of units equipped with the Lifting Device Option, it is not allowed to lift the
compressor if the canopy parts or lifting supports are not completely installed. When the
compressor is being lifted, it is also forbidden to come under the load or to perform
maintenance activities to it.
Acclimatization
When moving the compressor into an installation room, forming of condense can occur
on some components.
To avoid dew harming of electrical components, ensure at least 2 hours of acclimatization
before switch on the compressor.
Most compressors are designed for use in TT/TN networks and are intended for industrial
environments where the electrical supply is separated from the residential/commercial
supply network.
To use the machine in light industrial, commercial or residential environments with a
shared supply network or in an IT network, extra measures can be required: contact Atlas
Copco.
80 2920 7110 00
Instruction book
2920 7110 00 81
Instruction book
Reference Designation
(1) Customer’s installation
(2) Power circuit
(3) Motor
(4) Dryer
Note
The complete electrical diagram can be found in the electrical cubicle.
Description
You find the correct position for the electrical connection on the Dimension drawings.
82 2920 7110 00
Instruction book
To preserve the protection degree of the electric cubicle and to protect its components
from dust from the environment, it is mandatory to use a proper cable gland when
connecting the supply cable to the compressor.
• LAN control: The compressor is controlled via a local network. Consult Atlas Copco.
2920 7110 00 83
Instruction book
4.4 Pictographs
Pictographs
Reference Designation
1 Switch off the voltage and depressurize the compressor before starting maintenance or
repairs
2 Automatic condensate drain
3 Manual condensate drain
4 Lightly oil the gasket of the oil filter, screw it on and tighten by hand (approx. half a turn)
5 Warning, hot surface
6 Stop the compressor before cleaning the coolers
7 Warning, voltage
8 Switch off the voltage and wait at least 10 minutes before maintenance
9 Compressor remains pressurized for 180 seconds after switching off the voltage
10 If the rotation direction is wrong, open the isolating switch in the voltage supply line and
reverse two incoming electric lines
84 2920 7110 00
Instruction book
5 Operating instructions
Initial start-up
The operator must apply all relevant Safety precautions. Also consult section Problem
solving.
For the location of the air outlet valve and the drain connections, see sections Introduction
and Condensate system.
- Remove the canopy panel(s) in order to get access to the internal components.
Remove the red transport spacers and the related bolts under motor (1).
- Check that the electrical connections correspond to the local codes and that all wires are clamped tight
to their terminals.
The installation must be earthed and protected against short circuits by fuses of the inert type in all
phases. An isolating switch must be installed near the compressor.
- Check the voltage selecting wires at the primary side of transformer T1.
- Fit air outlet valve (AV); see section Introduction for the position of the valve.
Close the valve.
Connect the air net to the valve.
- Fit the manual condensate drain valve (Dm).
Close the valve.
- Connect the condensate drain outlets to a drain collector. See section Condensate system for the
position of the valves.
The drain pipes to the drain collector must not dip into the water. For draining of pure condensate water,
install an oil/water separator which is available from Atlas Copco as an option. If the pipes have been
fitted outside the room where freezing is possible, they must be insulated.
2920 7110 00 85
Instruction book
- Check the oil level, the oil level should reach the bottom of the oil filler neck (FC).
Minimum level should reach the oil sight glass (GI) when the compressor is stopped.
If needed, top up the oil.
Take care that no dirt drops into the oil system.
Refit and tighten the filler plug (FC).
- Provide labels, warning the operator that:
• The compressor may automatically restart after voltage failure (if activated, consult Atlas Copco).
• The compressor is automatically controlled and may be restarted automatically.
• The compressor may be remotely controlled.
- Check the rotation direction of the axial fan motor. If the rotation direction is wrong, open the isolating
switch in the voltage supply line and reverse two incoming electric lines.
- Check the programmed settings. Consult section Programmable settings.
- Open the air outlet valve.
Start and run the compressor for a few minutes. Check that the compressor operates normally.
86 2920 7110 00
Instruction book
Starting
Step Action
- Open the air outlet valve.
- Switch on the voltage. Check that voltage on LED (6) lights up.
- Press start button (1) on the control panel. The compressor starts running and the automatic
operation LED (8) lights up.
During operation
When the motors are stopped and LED (8) (automatic operation) is alight, the motors may
start automatically.
When the automatic operation LED (8) is lit, the regulator is automatically controlling the
compressor, i.e. loading, unloading, stopping of the motors and restarting!
2920 7110 00 87
Instruction book
A few minutes after stopping, the oil level should reach the bottom of the oil filler neck (FC).
If the oil level is too low, wait until the compressor has depressurized. Push the emergency stop button (10)
to avoid the compressor to start unexpectedly. Next, close the air outlet valve and open the manual drain valve
(Dm) until the air system between oil separator/air receiver vessel and outlet valve is fully depressurized. See
section Condensate system for location of the outlet valve and water drain.
Unscrew oil filler plug (FC) one turn to permit any pressure left in the system to escape. Wait a few minutes.
Remove the plug and add oil until the level reaches the filler opening. Fit and tighten the plug (FC).
On compressors with an Elektronikon® Graphic controller, unlock the emergency stop button (10), select the
STOP icon on the display and press reset before restarting.
Regularly check that condensate is discharged during operation. See section Condensate system. The amount
of condensate depends on environmental and working conditions.
Check the display (2) regularly for readings and messages. The display normally shows the compressor outlet
pressure, while the status of the compressor is indicated by means of a number of icons. Remedy the trouble
if alarm LED (7) is lit or flashes, see section Icons used. The display (2) will show a service message if a
service plan interval has been exceeded or if a service level for a monitored component has been exceeded.
Carry out the service actions of the indicated plans or replace the component and reset the relevant timer, see
section Service menu.
Stopping
- Press stop button (9). Automatic operation LED (8) goes out and the compressor stops.
- To stop the compressor in the event of an emergency, press emergency stop button (10).
Alarm LED flashes (7).
• Remedy the problem cause, unlock the button by pulling it out.
• Navigate to the Stop icon on the display by means of the navigation keys (3/4) and press the
Select key.
Press Reset.
Do not use emergency stop button (10) for normal stopping!
- Close the air outlet valve.
- Press the test button on top of the electronic water drain(s) to the depressurize the piping between
air receiver and outlet valve, next open the manual drain valve (Dm). See section Condensate
system.
Switch off the voltage.
88 2920 7110 00
Instruction book
2920 7110 00 89
Instruction book
6 Maintenance
Control panel
Warning
Service kits
For overhauling or carrying out preventive maintenance, service kits are available (see section Service kits).
Service contracts
Atlas Copco offers several types of service contracts, relieving you of all preventive maintenance work.
Consult your Atlas Copco Customer Centre.
General
When servicing, replace all removed O-rings and washers.
Intervals
The local Atlas Copco Customer Centre may overrule the maintenance schedule, especially the service
intervals, depending on the environmental and working conditions of the compressor.
The longer interval checks must also include the shorter interval checks.
90 2920 7110 00
Instruction book
Each plan has a programmed time interval at which all service actions belonging to that plan are to be carried
out. When reaching the interval, a message will appear on the screen indicating which service plans are to be
carried out. After servicing, the intervals must be reset, see section Service menu.
Period Operation
Daily Check oil level. If needed, top up the oil (see section Operations instructions / During
operation)
Check readings on display.
Check that condensate is discharged during operation.
Drain condensate.
monthly Check that condensate is discharged when pressing the test button on top of the electronic
water drain.
3-monthly (1) Check coolers, clean if necessary.
Remove the air filter element and inspect. Replace damaged or heavily contaminated
elements.
Check the filter elements of the electric cabinet. Replace if necessary
Period Operation
Daily Check that condensate is discharged during operation.
Monthly (1) Drain inspection: Check that condensate is discharged when pressing the test button on
top of the electronic water drain(s).
Condenser cleaning:
• Stop the compressor, close the air outlet valve and switch off the voltage.
• Remove any dirt on the condenser inlet with a vacuum cleaner.
• Next, clean with an air jet in the reverse direction to normal flow. Use low pressure air.
Keep the compressed air nozzle more than 30 cm away from the condenser to avoid
damaging the of condenser fins.
• Remove dust from inside the dryer, e.g. with a vacuum cleaner.
Do not use water or solvents to clean the condenser.
2920 7110 00 91
Instruction book
Roto-Foodgrade Fluid
92 2920 7110 00
Instruction book
Important
Avoid mixing lubricants of different brands or types as they may not be compatible and the
oil mix may have inferior properties. A label, indicating the type of oil filled ex factory, is
stuck on the air receiver/oil tank.
Roto-Inject Fluid
Atlas Copco's Roto-Inject Fluid is a specially developed lubricant for use in single stage oil-injected screw
compressors. Its specific composition keeps the compressor in excellent condition. Roto-Inject Fluid can be
used for compressors operating at ambient temperatures between 0 ˚C (32 ˚F) and 40 ˚C (104 ˚F). If the
compressor is regularly operating in ambient temperatures above 35 °C (95 °F), oil lifetime is reduced
significantly. In such case use Roto-Xtend Duty Fluid for a longer interval for oil exchange.
If the compressor is regularly operating in ambient temperatures above 35 °C (95 °F), oil lifetime is reduced
(see table oil lifetime Preventive maintenance schedule).
Roto-Foodgrade Fluid
Special oil, delivered as an option.
2920 7110 00 93
Instruction book
Atlas Copco's Roto-Foodgrade Fluid is a unique high quality synthetic lubricant, specially created for oil-
injected screw compressors that provide air for the food industry. This lubricant keeps the compressor in
excellent condition. Roto-Foodgrade Fluid can be used for compressors operating at ambient temperatures
between 0 ˚C (32 ˚F) and 40 ˚C (104 ˚F).
If the compressor is regularly operating in ambient temperatures above 35 °C (95 °F), oil lifetime is reduced
(see table oil lifetime Preventive maintenance schedule).
Bearing maintenance
The motor bearing is lubricated by oil injection. Re-greasing in not necessary.
Procedure
1. Stop the compressor. Switch off the voltage.
2. Remove the cover of the air filter (AF) by turning it anti clockwise. Remove the filter element.
3. Fit the new element and the cover.
4. Reset the air filter service warning.
For compressors equipped with an Elektronikon® Graphic regulator, see section Service menu.
94 2920 7110 00
Instruction book
Warning
Procedure
1. • Run the compressor until warm and stop the compressor.
• Close the air outlet valve and switch off the voltage.
• Wait 3 minutes for the compressor to depressurise the vessel.
• Open the condensate drain valve to depressurise the cooler. (see condensate system) and close again.
• Unscrew the oil filler plug (FC) just one turn to permit any remaining pressure in the system to escape.
• Cover the duct of the heat sink on the electric cabinet.
2. Remove the vent plug (VP) of the oil cooler.
2920 7110 00 95
Instruction book
Take care that no dirt drops into the system. Refit and tighten filler plug (FC).
8. Run the compressor loaded for a few minutes. Stop the compressor.
9. • Close the air outlet valve and switch off the voltage.
• Wait 3 minutes for the compressor to depressurise the vessel.
96 2920 7110 00
Instruction book
• Open the condensate drain valve (Dm) to depressurise the cooler. (see Condensate system) and close
again.
• Unscrew the oil filler plug (FC) just one turn to permit any remaining pressure in the system to escape.
10. • Fill the air receiver (AR) with oil until the level reaches the filler neck. (see Operating instructions /
During operation)
• Refit and tighten filler plug (FC).
When the oil level is too low, go back to step 7.
6.6 Coolers
General
Keep the coolers clean to maintain their efficiency.
Procedure
• Stop the compressor, close the air outlet valve and switch off the voltage.
• Cover all parts under the coolers.
• Remove the service plate (1) at the fan compartment.
• Remove dirt from the coolers with a fibre brush. Brush in the direction of the cooling fins.
Remove dirt from the fan with a fibre brush.
• Clean with an air jet in the reverse direction to normal flow.
• If it is necessary to wash the coolers with a cleaning agent, consult Atlas Copco.
2920 7110 00 97
Instruction book
• Remove dirt on the inlet of the condenser (6) with a fibre brush.
• Clean with an air jet in the reverse direction to normal flow.
• Clean the condenser area with a fibre brush.
Safety precautions
Refrigeration dryers of ID type contain refrigerant HFC.
When handling refrigerant, all applicable safety precautions must be observed. Please be specifically
aware of the following points:
• Contact of refrigerant with the skin will cause freezing. Special gloves must be worn. If contacted with
the skin, the skin should be rinsed with water. On no account may clothing be removed.
• Fluid refrigerant will also cause freezing of the eyes; always wear safety glasses.
• Refrigerant is harmful. Do not inhale refrigerant vapours. Check that the working area is adequately
ventilated.
Be aware that certain components such as the refrigerant compressor and the discharge pipe can become quite
hot (up to 110 °C - 230 °F). Therefore, wait until the dryer has cooled down before removing the panels.
Before starting any maintenance or repair work, switch off the voltage and close the air inlet and outlet valves.
Local legislation
Local legislation may stipulate that:
• Work on the refrigerant circuit of the cooling dryer or on any equipment which influences its function
must be undertaken by an authorised control body.
• The installation should be checked once a year by an authorised control body.
98 2920 7110 00
Instruction book
Testing
The safety valve (SV) test can only be performed by authorized personnel and is protected
by a security code.
Refer to Elektronikon® Graphic controller, Test menu
If the safety valve does not open at the set pressure stamped on the valve, it needs to be replaced.
Warning
No adjustments are allowed. Never run the compressor without safety valve.
Service kits
For overhauling and for preventive maintenance, a wide range of service kits is available. Service kits comprise
all parts required for servicing the component and offer the benefits of genuine Atlas Copco parts while
keeping the maintenance budget low.
Also a full range of extensively tested lubricants, suitable for your specific needs is available to keep the
compressor in excellent condition.
Consult the Spare Parts List for part numbers.
Procedure
Run the compressor regularly, e.g. twice a week, until warm.
2920 7110 00 99
Instruction book
If the compressor is going to be stored without running from time to time, protective
measures must be taken. Consult your supplier.
Used filters or any other used material (e.g. desiccant, lubricants, cleaning rags, machine parts, etc.) must be
disposed of in an environmentally friendly and safe manner, and in line with the local recommendations and
environmental legislation.
Be careful when removing the electric motor. The rotor contains magnetic parts.
7 Problem solving
Warning
Before carrying out any maintenance, repair work or adjustment, stop compressor, wait 3
minutes and close the air outlet valve.
Press the test button on top of the electronic water drain until the air system between the
air receiver and outlet valve is fully depressurized.
Press the emergency stop button and switch off the voltage.
Depressurise the compressor by opening the oil filler plug one turn.
For location of components, see sections:
• Introduction.
• Condensate system.
• Operation instructions
• Maintenance.
Open and lock the isolating switch.
Lock the air outlet valve during maintenance or repair as follows:
• Close the valve.
• Remove the screw fixing the handle with the wrench delivered with the compressor.
• Lift the handle and turn it until the slot of the handle fits over the blocking edge on the
valve body.
• Fit the screw.
The operator must apply all relevant Safety precautions.
Wait for at least 10 minutes before starting any electrical repairs as dangerous high voltage
remains on the capacitors of the start and speed regulation unit during some minutes after
switching off the voltage.
(1) Shutdown
Navigate to the Stop icon or to the Protections icon and press Enter.
(1) Protections
(1) General
The display shows the problem (Main Motor Converter Alarm) and a fault code (31 in this case).
8 Technical data
Important
The readings mentioned below are valid under the reference conditions (see section
Reference conditions and limtations).
Reference Reading
Air outlet pressure Depends on the setpoint (desired net pressure).
Compressor element Approx. 80 ˚C (176 ˚F) (ambient temperature 20 °C + 60 °C)
outlet temperature
Dewpoint temperature Approx. 4 ˚C (39 ˚F).
(on Full-Feature
compressors
Important
• The voltage on the compressor terminals must not deviate more than 10% of the
nominal voltage.
It is however highly recommended to keep the voltage drop over the supply cables at
nominal current below 5% of the nominal voltage (IEC 60204-1).
• If cables are grouped together with other power cables, it may be necessary to use
cables of a larger size than those calculated for the standard operating conditions.
• Use the original cable entry. See section Dimension drawings.
To preserve the IP protection degree of the electric cubicle and to protect its
components from dust from the environment, it is mandatory to use a proper
cable gland when connecting the supply cable to the compressor.
• Local regulations remain applicable if they are stricter than the values proposed below.
• Caution:
• Always double-check the fuse size versus the calculated cable size. If required,
reduce fuse size or enlarge cable size.
• Cable length should not exceed the maximum length according to IEC60204 table
10
Compressor type Imax (1) Max fuse (1) Imax (2) Max fuse (2)
gL/gG gL/gG
V A A A A
GA 18 VSD+ 200 88.1 100 94.2 100
GA 18 VSD+ 230 88.9 100 94.9 100
GA 18 VSD+ 380 44.5 50 49.1 50
GA 18 VSD+ 400 44.1 50 48.6 50
GA 18 VSD+ 400+N 44.1 50 48.6 50
GA 18 VSD+ 460 44.4 50 49 50
GA 18 VSD+ 500 35.2 40 37.2 40
Compressor type Imax (1) Max fuse (1) Imax (2) Max fuse (2)
gL/gG gL/gG
V A A A A
GA 22 VSD+ 200 118.1 125 124.3 125
GA 22 VSD+ 230 118.7 125 125 125
GA 22 VSD+ 380 59.5 63 64.2 80
GA 22 VSD+ 400 59 63 63.7 80
Compressor type Imax (1) Max fuse (1) Imax (2) Max fuse (2)
gL/gG gL/gG
V A A A A
GA 22 VSD+ 400+N 59 63 63.7 80
GA 22 VSD+ 460 59.4 63 64.1 80
GA 22 VSD+ 500 47.2 50 49.7 50
Compressor type Imax (1) Max fuse (1) Imax (2) Max fuse (2)
gL/gG gL/gG
V A A A A
GA 26 VSD+ 200 118.8 125 125.1 125
GA 26 VSD+ 230 118.7 125 125 125
GA 26 VSD+ 380 59.5 63 64.2 80
GA 26 VSD+ 400 59.4 63 64.1 80
GA 26 VSD+ 400 + N 59.4 63 64.1 80
GA 26 VSD+ 460 59.4 63 64.1 80
GA 26 VSD+ 500 47.5 50 50 50
Compressor type Imax (1) Max fuse (1) Imax (2) Max fuse (2)
gL/gG gL/gG
V A A A A
GA 30 VSD+ 200 144.9 160 152.5 160
GA 30 VSD+ 230 144.8 160 152.4 160
GA 30 VSD+ 380 72.5 80 78.2 80
GA 30 VSD+ 400 72.5 80 78.2 80
GA 30 VSD+ 400 + N 72.5 80 78.2 80
GA 30 VSD+ 460 72.4 80 78.1 80
GA 30 VSD+ 500 57.9 63 60.9 63
Compressor type Imax (1) Max fuse (1) Imax (2) Max fuse (2)
gL/gG gL/gG
V A A A A
GA 37 VSD+ 200 174.5 200 183.1 200
GA 37 VSD+ 230 174.5 200 183.1 200
GA 37 VSD+ 380 87.7 100 93.4 100
GA 37 VSD+ 400 87.7 100 93.4 100
GA 37 VSD+ 400 + N 87.7 100 93.4 100
GA 37 VSD+ 460 87.7 100 93.4 100
GA 37 VSD+ 500 70.2 80 73.2 100
UL/cUL approval
Compressor type Imax (1) Max fuse (1) Imax (2) Max fuse (2)
K5/ K5/
HRC form II HRC form II
V A A A A
GA 18 VSD+ 200 88.1 90 94.2 100
GA 18 VSD+ 230 88.9 90 94.9 100
GA 18 VSD+ 460 44.4 50 49 50
GA 18 VSD+ 575 35.5 40 37.9 40
Compressor type Imax (1) Max fuse (1) Imax (2) Max fuse (2)
K5/ K5/
HRC form II HRC form II
V A A A A
GA 22 VSD+ 200 118.1 125 124.3 125
GA 22 VSD+ 230 118.7 125 125 125
GA 22 VSD+ 460 59.4 60 64.1 70
GA 22 VSD+ 575 47.5 50 50 50
Compressor type Imax (1) Max fuse (1) Imax (2) Max fuse (2)
K5/ K5/
HRC form II HRC form II
V A A A A
GA 26 VSD+ 200 118.8 125 125.1 125
GA 26 VSD+ 230 118.7 125 125 125
GA 26 VSD+ 460 59.4 60 64.1 70
GA 26 VSD+ 575 47.5 50 50 50
Compressor type Imax (1) Max fuse (1) Imax (2) Max fuse (2)
K5/ K5/
HRC form II HRC form II
V A A A A
GA 30 VSD+ 200 144.9 175 152.5 175
GA 30 VSD+ 230 144.8 175 152.4 175
GA 30 VSD+ 460 72.4 80 78.1 80
GA 30 VSD+ 575 57.9 70 60.9 70
Compressor type Imax (1) Max fuse (1) Imax (2) Max fuse (2)
K5/ K5/
HRC form II HRC form II
V A A A A
GA 37 VSD+ 200 175.4 175 183.1 200
GA 37 VSD+ 230 175.4 175 183.1 200
GA 37 VSD+ 460 87.7 90 93.4 100
GA 37 VSD+ 575 70.2 70 73.2 80
Q1 1A
Q15 0.5 A
Fuse calculations for IEC are done according to 60364-4-43 electrical installations of buildings, part 4:
protection for safety- section 43: protection against overcurrent. Fuse sizes are calculated in order to protect
the cable against short circuit.
Fuse calculations for cUL and UL: The indicated fuse size is the maximum fuse size in order to protect the
motor against short circuit. For cUL fuse HRC form II, for UL fuse class K5
Earthing
The earthing cable connected to the compressor (PE) should be minimum 10 mm2 (according to EN 60204-1
section 828).
Maximum allowed current in function of the ambient temperature for installation method B2
Ambient temperature
Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
4 mm² < 27 A < 23 A < 21 A < 19 A < 16 A
Ambient temperature
Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
6 mm² < 34 A < 30 A < 27 A < 24 A < 21 A
10 mm² < 46 A < 40 A < 36 A < 33 A < 28 A
16 mm² < 62 A < 54 A < 49 A < 44 A < 38 A
25 mm² < 80 A < 70 A < 63 A < 57 A < 49 A
35 mm² < 99 A < 86 A < 78 A < 70 A < 60 A
50 mm² < 118 A < 103 A < 93 A < 84 A < 72 A
70 mm² < 149 A < 130 A < 118 A < 106 A < 91 A
95 mm² < 179 A < 156 A < 141 A < 127 A < 109 A
120 mm² < 206 A < 179 A < 163 A < 146 A < 126 A
Maximum allowed current in function of the ambient temperature for installation method C
Ambient temperature
Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
4 mm² < 32 A < 28 A < 25 A < 23 A < 20 A
6 mm² < 41 A < 36 A < 32 A < 29 A < 25 A
10 mm² < 57 A < 50 A < 45 A < 40 A < 35 A
16 mm² < 76 A < 66 A < 60 A < 54 A < 46 A
25 mm² < 96 A < 84 A < 76 A < 68 A < 59 A
35 mm² < 119 A < 104 A < 94 A < 84 A < 73 A
50 mm² < 144 A < 125 A < 114 A < 102 A < 88 A
70 mm² < 184 A < 160 A < 145 A < 131 A < 112 A
95 mm² < 223 A < 194 A < 176 A < 158 A < 136 A
120 mm² < 259 A < 225 A < 205 A < 184 A < 158 A
Maximum allowed current in function of the ambient temperature for installation method F
Ambient temperature
Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
25 mm² < 110 A < 96 A < 87 A < 78 A < 67 A
35 mm² < 137 A < 119 A < 108 A < 97 A < 84 A
Ambient temperature
Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
50 mm² < 167 A < 145 A < 132 A < 119 A < 102 A
70 mm² < 216 A < 188 A < 171 A < 153 A < 132 A
95 mm² < 264 A < 230 A < 209 A < 187 A < 161 A
120 mm² < 308 A < 268 A < 243 A < 219 A < 188 A
Always check the voltage drop over the cable (less than 5 % of the nominal voltage is recommended).
Example of supply cable calculation: Itot = 128 A, maximum ambient temperature is 45 °C, recommended
fuse = 150 A
• Single supply cables (3 phases + 1 PE - configuration (1)):
• I = 128 A + 25 % = 128 x 1.25 = 160 A
• For AWG2/0, the maximum current is 175 A, which is sufficient => use AWG2/0
• Install the prescribed maximum fuse (150 A) on each cable
• Parallel supply cable (2 x 3 phases + 2 PE - configuration (2)):
• I = (128 A + 25%)/2 = (128 x 1.25)/2 = 80 A
• For a AWG4, the maximum current is 85 A x 0.8 = 68 A, which is insufficient. For an AWG3, the
maximum current is 100 x 0.8 = 80 A. So 2 parallel cables of 3 x AWG3 + 2 x AWG8 are sufficient.
• Install 80 A fuses on each cable.
Reference conditions
Limitations
Reference conditions
All data specified below apply under reference conditions, see section Reference
conditions and limitations.
Unit
Number of compression stages 1
Temperature of the air leaving the outlet valve (approx.), Workplace ˚C 30
Temperature of the air leaving the outlet valve (approx.), Workplace ˚F 86
Temperature of the air leaving the outlet valve (approx.), Workplace Full-Feature ˚C 30
Temperature of the air leaving the outlet valve (approx.), Workplace Full-Feature ˚F 86
Refrigerant type, Workplace Full-Feature R410a
GA 18 VSD+
GA 22 VSD+
GA 26 VSD+
GA 30 VSD+
GA 37 VSD+
General
Digital outputs
Number of outputs 9 (Elektronikon® Graphic controller - p.n. 1900 5200 10 …. 1900 5200 19)
Type Relay (voltage free contacts)
Rated voltage AC 250 V AC / 10 A max.
Rated voltage DC 30 V DC / 10 A max.
Digital inputs
Number of inputs 10 (Elektronikon® Graphic controller - p.n. 1900 5200 10 …. 1900 5200 19)
Supply by controller 24 V DC
Supply protection Short circuit protected to ground
Input protection Not isolated
Analog inputs
Number of pressure inputs 2 (Elektronikon® Graphic controller - p.n. 1900 5200 10 …. 1900 5200 19)
Number of temperature inputs 5 (Elektronikon® Graphic controller - p.n. 1900 5200 10 …. 1900 5200 19)
- This vessel can contain pressurised air; this can be potentially dangerous if the equipment is
misused.
- This vessel must only be used as a compressed air/oil separator and must be operated within
the limits specified on the data plate.
- No alterations must be made to this vessel by welding, drilling or any other mechanical
methods without the written permission of the manufacturer.
- The safety valve must correspond with pressure surges of 1.1 times the maximum allowable
operating pressure. It should guarantee that the pressure will not permanently exceed the
maximum allowable operating pressure of the vessel.
- Use only oil as specified by the manufacturer.
- This vessel has been designed and built to guarantee an operational lifetime in excess of 20
years.
The vessel needs a yearly visual inspection.
National legislation may require in service inspection.
Guidelines
On the Declaration of Conformity / Declaration by the Manufacturer, the harmonised and/or other standards
that have been used for the design are shown and/or referred to.
The Declaration of Conformity / Declaration by the Manufacturer is part of the documentation that is supplied
with this compressor.
Local legal requirements and/or use outside the limits and/or conditions as specified by the manufacturer may
require other inspection periods as mentioned below.
12 Declaration of conformity
On the Declaration of Conformity / Declaration by the Manufacturer, the harmonised and/or other standards
that have been used for the design are shown and/or referred to.
The Declaration of Conformity / Declaration by the Manufacturer is part of the documentation that is supplied
with this device.
www.atlascopco.com