Ac Boq
Ac Boq
Ac Boq
B CAMPUS
SUMMARY
SR. NO. ITEM DESCRIPTION AMOUNT
II FINISHING WORK 0
V ELECTRICAL WORK 0
VI HVAC WORK 0
TOTAL OF (I+II+III+IV+V+VI) 0
ITEMWISE SUMMARY
II FINISHING WORK
V ELECTRICAL WORK
VI HVAC WORK 0
1 In addition to Clause 3.5.2 of Special Conditions of Contract Rate quoted for the items shall also be in
a) The tenderer shall provide barricade consisting of MS angle/pipe posts runners, bracing & corruga
separate the working area, maintaining the barricade in good condition including removing the same
any cost to IITB.
b) Statutory traffic regulations inforce shall be considered for transporting material, labour etc and no
account of the restrictions imposed by the local statuary authorities. Royalty charges for excavation a
other materials
c) Transporting of material ,labour , machinery etc to all heights & including locations of where direc
including arranging own arrangement
e) Security Regulations & rules of I.I.T, and its constituent units shall be strictly followed while movem
work forces and Cost arising due to security regulations.
h) Safety of Labours working at site shall be as per safety code enclosed in the specifications and to
safety engineer.
2 Cement for structural works shall be OPC/PPC ISI marked and duly approved by the Engineer-in-ch
3
PPC/blended cement of ISI marked shall only be used for finishing works on prior approval of Engin
4 The approach road should be kept clean & free from obstructions for smooth functioning of existing tr
be made good without any extra cost to the IITB.
5 Tenderer's are advised to acquaint themselves with access to site, location of work, local labour prob
to availability and carriage of construction materials.
Signature of tend
1.1 Depth not exceeding 1.50 m. from ground level. Cum 80.00
2 Disposing off the surplus excavated materials by mechanical transport lead up to
2 KM to the nearby dumping pits/ dumping areas with in IITB campus identified
by Engineer in charge , including all lifts, loading, unloading, stacking etc.
complete as per specifications & as directed by the EIC.
The contractor shall have to furnish ten years guarantee in the prescribed Sqmt 15.00
Performa (Appendix 'E') to maintain the anti-termite treated area /structure free
from termite.
5 Providing and laying dry rubble stone hard core soling of 230mm consolidated
thickness in sub base to floor and in plinth protection to required levels and lines
with first quality rubble, hand set, well packed including filling the interstices with
smaller stone chips, supplying & finishing/blinding the surfaces with approved
blinding quality murrum including watering, consolidation etc. complete as per
specifications, drawings & as directed by EIC.
7.1 For RCC work for all structural Members such as Raft , foundations , all types of Cum 12.00
Walls, Columns, Beams , Waffle beams, Slabs, Staircases , Pardis, drop pardis ,
parapets, chajjas, niches etc of any shapes, sizes , thickness and depths etc.
Grade of concrete :- M20
(Note :- Rate inclusive of all shapes, sizes, curves, slopes, thickness and depths
at all heights etc and No extra payment for shall be payable.)
8.3 Lintels, beams, girders, bressumers and cantilevers etc complete. Sqm. 15.00
8.4 Suspended floors, roofs, landings, balconies and access platform. Sqm. 35.00
II FINISHING WORK
General Notes
b) The contractor shall provide at their own cost temporary tarpaulin screens for
the entire duration of the contract to cover the works under execution to avoid
spreading / flying of dust to the adjoining buildings/ areas.
d) The materials required for the following works shall be sorted out as per the
manufacturing dates & batches, approved samples & shades. Prestacking,
handling, rehandling, transporting within the site, stacking & protection of
materials approved and rejected materials (rejected materials shall be replaced),
confirming the net quantities selected for use. No extras shall be paid for all above
and the contractor shall allow for all such eventualities in the construction time
period. No material/ samples including their makes/ brands shall be procured/
appointed/ subcontracted for mock up or for execution as the schedule of
quantities without the prior approval of the client / Architect.
10 For Deck slab, roof extension including cols trusses purlins, extension of existing MT 6.75
members , site welding etc
13 Providing & fixing STUD type shear connector 12mm dia Thermomechanically each 50.00
fixed,
14 Providing & fixing in position 12mm thk. of Shalitex board at various joints such as Sqm. 5.00
isolation joints at wall edge, and column junctions and sealing with Winsil-20
neutral base sealent manufactured by GE Silicon , as per manufacturer's
requirements ,etc. complete,
15 Providing and fixing in position Bare Galvalume sheets for Roof & Colour Coated Sqm. 300.00
Galvalume Sheet for Cladding, including providing necessary laps, Flashing
pieces, self tapping screws , EPDM washers, seam bolts, stitch rivets at overlap
and all other hardware, scaffolding Etc.Complete.
16 Same as item 15 above above using j hooks Sqm. 25.00
17 Providing and fixing in position GI gutter made from 1.22mm thick a GI Rmt. 35.00
sheet,moulded to shape as per detail drawing approximately 300mm wide and
average 300mm deep laid to slope all as per design. Including treating the joints
with rubber & watrerproofing compound etc. complete.
18 Providing & fixing in position flashing at the junction of roof sheet and existing wall Rmt. 32.00
21 Providing & Laying Non shrink grout of FOSROCK / Sunanda / Krishna / MYK Cum 1.00
Laticrete / Ardex Endura Make GP 2, under side of base plates etc at all locations
and heights
TOTAL OF STEEL & ROOFING WORK
B DEMOLITION WORK
22 Dismantling, Demolishing, Cutting, Breaking, Removing & Cleaning Existing Items
Carefully and Stacking the Materials at site or as Instructed including necessary
tool, tackles, machineries, requisite scaffolding, carting away debris from site time
to time or disposing the material as directed and specified by the Architect / Client
for the following Items. (The rate shall include all leads, lift and height)
22.1 Removing of existing Flooring in Green rooms, and Prefunction area etc. Sqm. 190.00
including bedding materials. (Refer Drw. No. I-200, I-201, I-202)
22.2 Removing of existing windows including window frames (Refer Drw. No. I-200, Sqm. 45.00
I-201, I-202)
22.3 Removing of existing Doors including door frames (Refer Drw. No. I-200, I- Sqm. 45.00
201, I-202)
22.4 Remove and salvage door for refurbishment & refixing (Refer Drw. No. I-200, I- Sqm. 10.00
201, I-202)
22.5 Removing of existing partitions on stage (Refer Drw. No. I-200, I-201, I-202) Sqm. 50.00
22.6 Removing existing internal plaster with racking out the masonry joints. (Refer Sqm. 585.00
Drw. No. I-200, I-201, I-202)
22.7 Removing of existing Ms Grill,ventilators,aluminium frame ,glass with fixtures etc Sqm. 15.00
(Refer Drw. No. I-200, I-201, I-202)
22.8 Providing and doing core cutting in RCC slab at given location as per architectural Sqm. 5.00
instructions inluding necessary tools and machinaries, scaffolding, watering, rate
also included carting away the debris from site time to time or disposing the
material as directed and specified by the Architect / Client (Refer Drw. No. A-
200)
22.9 Removing of existing internal 100 mm thick brick work for green room partion. Sqm. 40.00
(Refer Drw. No. I-200, I-201, I-202)
22.10 Removing of existing internal 150 mm thick brick work for green room partion. Sqm. 10.00
(Refer Drw. No. I-200, I-201, I-202)
22.11 Removing of existing internal 230 mm thick brick work for green room partion. Sqm. 5.00
(Refer Drw. No. I-200, I-201, I-202)
22.12 Removing of existing wooden box for Duct in post Function (Refer Drw. No. I- Sqm. 15.00
200, I-201, I-202)
22.13 Removing of existing counter pre function area (Refer Drw. No. I-200, I-201, I- Rmt. 5.00
202)
22.14 Removing of existing curtains with pelmet in Auditorium (Refer Drw. No. I-200, Sqm. 125.00
I-201, I-202)
22.15 Removing of existing foundation stone and salvage with extreme care in pre each 2.00
function and post function area (Refer Drw. No. I-200, I-201, I-202)
22.17 Removing of existing screen with accessories & fittings (Refer Drw. No. I-200, Sqm. 50.00
I-201, I-202)
22.18 Removing of existing grid false ceiling with supports, framings, light fittings etc. Sqm. 375.00
(Refer Drw. No. I-200, I-201, I-202)
22.19 Removing of existing push back chairs (Refer Drw. No. I-200, I-201, I-202) each 399.00
22.20 Removing of existing roof with structural memebers in post function area. (Refer Sqm. 205.00
Drw. No. I-200, I-201, I-202)
22.21 Removing of existing corrugated sheet in post function area (Refer Drw. No. I- Sqm 370.00
200, I-201, I-202)
22.22 Removing of existing electical wirings, cables, fittings, boards, switches etc. Job 1.00
(Refer Drw. No. I-200, I-201, I-202)
22.23 Making cut outs in RC wall, with supporting steel frame etc Edge prepation to Cum 5.00
receive steel frame etc.. (str.steel frame qty, & anchor bolts, item will be paid
separetly in respective items (Refer Drw. No. A-200)
22.24 Removing of existing mosaic flooring in Auditorium (Refer Drw. No. I-200, I- Sqm. 155.00
201, I-202)
22.25 Removing of Wash basin with tap,bottle trap with all fixtures & supports. (Refer each 2.00
Drw. No. I-200, I-201, I-202)
22.26 Removing of existing Storage with all fixtures in Green room. (Refer Drw. No. I- Sqm. 10.00
200, I-201, I-202)
22.27 Removing of panel in post function area (Refer Drw. No. I-200, I-201, I-202)
Sqm. 20.00
22.28 Removing the existing stage flooring & sub base for flooring to place subwoofers
of approximate size 650mm x 650mm x 450mm and making good the same after
placing the subwoofers with capping using hard wood floor matching to the
Nos. 2.00
existing stage flooring etc complete as per the drawings and instructions of
Engineer - In - Charge
26 Providing and applying avg. 8mm thk. (avg.) single coat internal plaster in Sqm. 10.00
cement sand mortar (1:4) for all plain / curved Ceiling surfaces and finishing the
same (smooth or broom) in correct line & level, making of edges, corners, sill,
jambs, soffits, grooves, pattas etc. as per drawings & relevant specifications
including all necessary surface preparation, scaffolding, hacking of concrete
surface to receive plaster, watering, curing, cleaning etc. complete at all levels
and heights. (Refer Drw. No. I-210, I-211, I-213, I-600A, I-600B, I-601,I-
602A, I-602, I-603A, I-603B, I-604A, I-604B, I-604C, I-604D, I-604E,I-
605A, I-605B, I-606, I-607A, I-607B, I-701,I-702, I-703, I-705A, I-705B, I-
706, I-830)
28 Providing and applying avg. 6mm thk. (avg.) POP to ceiling using approved Sqm. 10.00
quality pop as per IS 2547,1976 for all plain / curved surfaces, pattas finished
smooth in correct line & level including all necessary surface preparation, making
level pads (Dada), scaffolding, hacking of surface to receive plaster, cleaning etc.
complete as per relevant working drawings & specifications at all levels and
heights. (Refer Drw. No. I-210, I-211, I-213, I-600A, I-600B, I-601,I-602A,
I-602, I-603A, I-603B, I-604A, I-604B, I-604C, I-604D, I-604E,I-605A, I-
605B, I-606, I-607A, I-607B, I-701,I-702, I-703, I-705A, I-705B, I-706, I-
830)
29 Providing & laying POP of sufficient thickness over plastic sheets as a protective Sqm. 45.00
layer for flooring during the work including all maintenance, p/l plastic sheets,
removing & disposing POP after the use, cleaning, etc. complete at all floors & as
directed by the EIC. (Refer Drw. No. I-210, I-211, I-213, I-600A, I-600B, I-
601,I-602A, I-602, I-603A, I-603B, I-604A, I-604B, I-604C, I-604D, I-
604E,I-605A, I-605B, I-606, I-607A, I-607B, I-701,I-702, I-703, I-705A, I-
705B, I-706, I-709, I-830)
30 Providing and making Grooves of approved shape and size in POP at various 0.00
locations viz.above skirting, around the door & window frame,above dado or
wherever required as per the
drawing including finishing of groove in correct line and level, making of moulds
(farmas), cleaning, scaffolding etc. complete at all heights & floors. (Refer Drw.
No. I-210, I-211, I-213, I-600A, I-600B, I-601,I-602A, I-602, I-603A, I-
603B, I-604A, I-604B, I-604C, I-604D, I-604E,I-605A, I-605B, I-606, I-
607A, I-607B, I-701,I-702, I-703, I-705A, I-705B, I-706, I-830)
31 Providing & fixing suspended false ceiling using 12.5mm thick Gypsum boards Sqm. 55.00
confirming to IS 2095-1982 and GI framework of Gyp steel or approved equivalent
as per architectural drawing and instructions comprising of following.
1. GI perimeter channel of 0.55mm thick having one flange of 20mm, another
of 30mm and web of 27mm fixed to brick wall partition along periphery of ceiling
with the help of nylon sleeves and screws at 610mm c/c
2. GI intermediate channel of size, 45mm web, two flanges each of 15mm &
thickness 0.9mm ) suspended from the soffit / ceiling at 600mm c/ c spacing.
3. GI ceiling sections of 0.55mm thick having knurled web of 51.5mm and two
flanges each of 26mm with leaves of 10.5mm fixed to intermediate channel with
the help of connecting clip at direction perpendicular to the intermediate channel
at spacing of 600 mm c/c,
4. GI suspender angle of 25mmx10mm and thk.0.55mm at spacing of 600mm
c/c, fixed to the ceiling / soffit using GI cleat angle 25mm x 25mm, 0.55mm thk.
Cleat angle to be fixed to the ceiling / soffit using 6mm dia anchor fastener.
Gyp boards with tapered edges to be screwed to the framework with 25mm long
GI screws at 230 mm c/c. Screw fixing shall be done mechanically. Gyp boards
are to be joined and finished so as to have a flush look which includes filling and
finishing the tapered and square edge of the boards with gypsum roller net tape &
approved quality joining compounds. The work also includes vertical drops,
curvature, providing & making farma cutting of gyp boards & frame work and
providing cutouts / openings and additional supports wherever required for the
fixing of ceiling fixtures like, lights, A.C grills, sprinklers, smoke detectors etc.
Refer Drw. No. I-210, I-211, I-213 I-300A, I-602A, I-602B, I-603A, I-603B,
I-703, A-202, A-501, A-502, I-830
(Mode of measurements : Only plan are of ceiling shall be measured for
payment)
32 Do as per item No.31 but for Gypsum patta in various sizes for ceiling. 0.00
Refer Drw. No. I-210, I-211, I-213, I-300A, I-602A, I-602B, I-603A, I-
603B, I-703, I-830
Mode of measurements : Only running length of patta shall be measured
for payment)
34 Do as per item No. 33 but for CNBM MgO board patta in various sizes for ceiling. 0.00
Refer Drw. No. I-210,I-211, I-213, I-300A, I-600B, I-700, I-830 (Mode of
measurements : Only running length of patta shall be measured for
payment)
36 Providing and fixing 20mm thick Black Straw board of Anutone or any other Sqm. 210.00
approved make. ( Strand square edge magnesite bonded wood fiber panels of
size 600x600x20mm having density 400kg/m3, weight 8kg.) for auditorium celing.
The panels shall be fixed directly to existing rcc ceiling with screw properly as per
architectural drawing and instruction. including necessary hardware, scaffolding,
drilling, cuting, filling the screw holes with putty or any other filler material and
finish the holes with paint matching to straw board andcleaning etc. completed at
at all levels and heights and as specified by EIC/ Architect Refer Drw. No. I-
210,I-211, I-213, 1-300A, I-300B, I-604A, I-604B, I-604C, I-604D,I-604E,
I-704, I-830 (Mode of measurements : Only plan are of ceiling shall be
measured for payment)
37 Providing and making Grooves of approved shape and size in Gypsum/ MGO 0.00
Ceiling at various locations viz. above skirting, around the door & window frame,
above dado or wherever required as per the drawing including finishing of groove
in correct line and level, making of moulds (farmas), cleaning, scaffolding etc.
complete at all heights & floors. (Refer Drw. No.I-210, I-211, I-213 1-300A, I-
300B, I-604A, I-604B, I-604C, I-604D,I-604E, I-704, I-830)
39 Providing & Laying in position 32 mm thick machine cut Rough finished Kota Sqm. 20.00
Stone of approved size, quality, type & colour as per the approved sample for
Fire exit Ramp Flooring in approved shape and pattern in true line and level / to
required slope over average 50mm thick bedding of cement mortar (1:4) floated
with neat cement slurry / paste (cement @ 4.5 kg/sqm) including cutting to the
required sizes (up to 570mm x 570mm), surface preparation, providing & laying ,
filling & finishing the joints with neat cement slurry & approved colour pigments,
watering curing, cleaning etc complete at all floors & levels as per the instructions
of the EIC. Refer Drw No.-I-210, I-213, I-605A, I-605B, I-606,I-706, I-830,
A-201, A-501, A-502, A-503, A-800 (Mode of measurements : Only plan
are of flooring shall be measured for payment)
40 Doing mirror polishing to existing Kota Stone flooring Post function/Ramp/ Sqm. 245.00
pantry Flooring including all machinaries, kits, cleaning etc complete at all floors &
levels as per the instructions of the EIC. Refer Drw No.--I-210, I-211, I-213, I-
605A, I-605B, I-606,I-706, I-830, A-201, A-501, A-502, A-503, A-800
(Mode of measurements : Only plan are of flooring shall be measured for
payment)
42 Providing & Laying in position 19 mm thick machine cut Telephone Black Sand Sqm. 20.00
Blasted Granite slab of approved size, quality, type & colour as per the
approved sample for Pre- Function Flooring/ Mid landing in approved shape
and pattern in true line and level / to required slope over average 50mm thick
bedding of cement mortar (1:4) floated with neat cement slurry / paste (cement @
4.5 kg/sqm) including cutting to the required sizes, surface preparation, providing
& laying , filling & finishing the joints with neat cement slurry & approved colour
pigments, watering curing, cleaning etc complete at all floors & levels as per the
instructions of the EIC. Refer Drw No.I-210, I-211 I-213, I-600A, I-601, I-
701, I-702, I-606, I-707, I-830 (Mode of measurements : Only plan are of
flooring shall be measured for payment)
43 Providing & Laying in position full body Vitrified tiles of different sizes 0.00
(thickness to be specified by the manufacturers) of approved size, quality,
type & colour as per the approved sample for Flooring (conforming to IS 15622)
in approved shape and pattern in true line and level to required slope over
average 20mm thick bedding of cement mortar 1:4 (1 cement : 4 coarse sand)
floated with neat cement slurry / paste (cement @ 4.5 kg/sqm) including
chamfering of tiles wherever required, cutting to the required sizes, surface
preparation, providing & laying, grouting the joints with white cement & matching
pigments, watering, curing, cleaning etc complete at all floors & levels as per the
instructions of the EIC.
Refer Drw No.I-210, I-211 I-213, I-602A, I-602B, I-603A, I-603B, I-703, I-
830
(Mode of measurements : Only plan area of flooring shall be measured
for payment)
43.1 600mm x 600mm in size Vitrified tile for Green room VT 01) (Code No. SCPL- Sqm. 55.00
5286 Make - Sameer Ceramics/ Mirage- Vision Charcoal /).
44.1 10mm thick Vitrified tile skirting (Code No. SCPL-5286 Make - Sameer Rmt. 60.00
Ceramics/ Mirage- Vision Charcoal /).
44.2 19 mm thk. Telephone Black flamed Granite skirting with top edge polish Rmt. 125.00
44.3 19 mm thk. Telephone Black sandblasted Granite skirting with top edge Rmt. 35.00
polish
44.4 19mm thk. Kota stone skirting with top edge polish. Rmt. 55.00
45 Providing and laying 1st quality Ceramic tiles for Dado at all heights and location 0.00
(CR 01) (thickness to be specified by the manufacturer) conforming to IS :
15622 of approved make and colour and pattern, in dado laid over 12mm thick
backing coat of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with
grey cement slurry @ 3.3kg per sqm including cost of backing coat pointing in
white cement and matching pigment, staging if required etc. complete all as per
specifications and drawings and as directed by Engineer In Charge.
Ref Drg no. I-210, I-211, I-213, I-606, I-707, I-830
45.1 600mm x 600mm in size Ceramic tile for Pantry/Green room Dado in (CR 01) Sqm. 45.00
(Crema Dun Make - Nitco/ RAK/ Kajaria)
45a Providing and laying 2nd quality ceramic matt finished wall tiles (SQT 01) at all Sqm. 8.00
heights and location behind storage i.e below pantry platform (thickness to be
specified by the manufacturer) conforming to IS : 15622 of approved make and
colour and pattern, in dado laid over 12mm thick backing coat of cement mortar
1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per
sqm including cost of backing coat pointing in white cement and matching
pigment, staging if required etc. complete all as per specifications and drawings
and as directed by Engineer In Charge.
Ref Drg no. I - 606
47 Providing & Fixing in position 150mm wide 19mm thick machine cut, Second Rmt. 65.00
quality marble as per the approved sample for Door/ window sils, jambs etc.
as per the drawing laid to the required level & line including cutting of stone to the
required size & shape, edge polishing / chamferred edges, surface preparation
including cement backing with 1:1 cement grout, filling & finishing the joints with
cement & approved colour pigments, cutting, mirror polishing to moulding &
exposed edges, curing, cleaning etc complete as per the instructions of the EIC.
(Mode of measurements : Running length of individual marble patti shall
be measured for payment)
Refer Drw. No I-210, I-211, I-213, I-800, I-801, I-820, I-830
48 Providing & Fixing in position 19mm thick machine cut,Telephone Black Flamed 0.00
Granite as per the approved sample for Door/ window cills, jambs or any
other specified in the drawing etc. as per the drawing laid to the required level
& line including cutting of stone to the required size & shape, edge polishing /
chamfered edges, surface preparation including cement backing with 1:1 cement
grout, filling & finishing the joints with cement & approved colour pigments,
cutting, mirror polishing, curing, cleaning etc complete as per the instructions of
the EIC. (Mode of measurements : Running length of individual marble
patti shall be measured for payment).
Refer Drw. No.I-210, I-211, I-213, I-800, I-801, I-820, I-830
52 Providing & laying IPS flooring (as base for Vinyle flooring) or any other location 0.00
as specified by EIC of various thickness with cement concrete nominal mix of
proportion 1:2:4 (cement : Sand : Aggregate) in correct level / slope at all levels as
per architectural drawings including mixing of concrete in mixer, lifting, shifting to
the work location, compacting / vibrating, finishing smooth to the satisfaction of
the EIC, curing, and cleaning the surface etc. complete. (Mode of
measurements :Plan area of Flooring shall be measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-709, I-830
56.1 Fenomastic gold 007 to wall in green room and projector room Sqm. 150.00
56.2 Fenomastic matt 003 to ceiling green room and projector room Sqm. 70.00
56.3 Do as per item no.56.2 but spray painting (217-4000 B-G) for ceiling straw Sqm. 210.00
boards/ AC ducts and any other location as directed by EIC/ Architects.
57 Providing & applying 1st quality synthetic enamel paint ( Conforming IS 2932- Sqm. 200.00
1994) (for service areas) of approved make & shade in 3 coats over a coat of
approved quality primer to the wooden surface / MS railings & grills including
providing, erecting & dismantling scaffolding, preparation of surface, appying hard
putty, sanding, etc. complete as diected by the EIC at all lheights & levels. (Mode
of measurement- Only painting area shall be measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-605A, A-201, A-501, A-502, A-503, A-
800, I-830
58 Providing & applying 1st quality Water cut enamal paint ( Conforming IS 2932- Sqm. 5.00
1994) of approved make & shade for wooden surface / MS railings & grills to be
applied as per manufacturer's instructions & methodology as directed by Architect
including preparing the surface, p/a one coat of water base metalic primer of
Estee or equivalent make and two coat of water base acrylic putty, sanding with
water, light sanding with water, scaffolding, work platform, painting equipment /
apparatus, dismantling scaffolding and cleaning etc. required to complete interior
grade finish with 3 coats of approved shade colour etc. complete as directed by
the EIC at all heights & levels. (Mode of measurement- Only painting area
shall be measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-605A, A-201, A-501, A-502, A-503, A-
800, I-830
59.1 For Auditorium wall paneling (Make - OIKOS- Antique effect-811/ Asian paints- Sqm. 165.00
Royale play Dune Silver Streak M609) Range - Special Products)
59.2 For Green room wall paneling (Make - OIKOS-Antique effect-812 / Asian paints- Sqm. 10.00
Royale play Dune Silver Streak M609 Dark ) Range - Special Products
59.3 For Prefunction and Post Function area.External texture paint (Make - Jotun- Sqm. 75.00
Texotile- B-G-213-4502B / Asian Paints - Pebble Tex Head cut- steel 6142)
Range - Special Products
59.4 For Prefunction and Post Function area.External texture paint (Make - Jotun- Sqm. 135.00
Texotile- B-G-213- 7502B / Asian Paints - Pebble Tex Head cut- Charcoal Shadow
8286) Range - Special Products
59.5 For Prefunction area (Make- Asian Silver metalic paint-Shade code 135- 30 % Sqm. 15.00
dark) Range - Special Products .
59.6 For Prefunction and Post Function area External paint (Make - Sherwin Williams- Sqm. 40.00
Beige Assorted Paino / Aisan Paints - Swirl Tex with top coat of Apex)
61 Providing & applying Natural / French polish ( Conforming IS 348-1968) in 3 or Sqm. 10.00
more coats of approved shade to the wooden / Plywood / veneer surface,
mouldings pattas, grooves etc. including surface preparation, applying filler /
hardener / putty, sanding, cleaning of furniture after completion of job etc.
complete as directed by the EIC. (Mode of measurement- Only polishing
area shall be measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-830, I-602A , I-602B, I-603A, I-603B,
I-606, I-703, I-707
62 Providing and applying Melamine polish for exposed wooden surfaces Sqm. 65.00
wherever directed by the architects. including surface preparation, applying filler /
hardener / putty, sanding, cleaning of furniture, required smooth finishing after
completion of job etc. complete as directed by the EIC. (Mode of measurement-
Only polishing area shall be measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-830, I-602A , I-602B, I-603A, I-603B,
I-606, I-703, I-707
66 Providing & exchanging 1mm thick laminate (Laminate to be approved by each 1.00
architect before commencement of work) of existing door (D4) for Green
room Ladies internal door. including removing old laminate providing all necessary
consumables viz. adhesive, necessary hardware, necessary beads moulding,
lipping,fastenings, cleaning etc. completed at all floors & heights as per
architectural drawings and instructions.
Refer Drw. No. I-210, I-211, I-213, I-800, I-801, I-830
80 Providing & fixing 6mm thick frosted glass of modi or equivalent for Green Sqm. 2.00
Room as per approved shape, size and as per architectral rawing and instruction
fixed with 25mm dia SS Studs properly. Rate also included providing all
necessary consumables viz., necessary hardware etc. complete at all heights as
per architectural drawings and instructions.
Refer Drw. No. I-210, I-211, I-213, I-830, I-602A, I-602B,
I-603A, I-603B, I-703
81 Providing & fixing in positions 12 mm thick commercial ply and 12 mm thick 0.00
calicium silicate board paneling as per architectural drawing and instructions.
The system shall be comprising following. Ply frame work -Providing, making
and fixing 18mm thick marine ply frame work as architectural drawing and
instruction at all shapes and sides.
Panelling- providing and fixing 12mm thick commercial ply fix on the frame and
finish the ply with 12mm thick calcium silicate board as per architectural drawing,
including cutting, necessary hardware, drilling, The work also includes vertical
drops, sides, curvature, cutting of ply/veneer & frame work and providing cutouts /
openings for switch boards, fd and cleaning etc. completed at all floors and
heights as specified and directed by Architects/ EIC.
Ref Drw. No. I-210, I-211, I-213, I-830, I-600A, I-600B, I-601, I-700, I-701,
I-706
(Front elevational area shall be measured for Billing)
89 Providing and fixing 300mm wide and 25mm thick commercial ply shelves for Rmt. 5.00
Changing Room fixed in partitions at given loction properly as per architectural
drawing and instructions and finish the shelves with 1mm thick approved make
and colour laminate(Laminate to be approved by architect before commencement
of work) including providing all necessary consumables viz. adhesive, necessary
hardware, necessary beads moulding, lipping, fastenings etc. complete at all
floors & heights as specified and as directed by EIC. (Mode of measurement-
Only running length of shelves shall be measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-830, I-602A, I-602B, I-603A, I-603B,
I-703
90 Providing & fixing 12mm thick & 75mm high approved quality Wooden skirting Rmt. 15.00
finished with approved melamine polish as per the pattern given to correct line,
level & plumb including chasing of wall wherever required, surface preparation,
joints should be proper, cutting, mitring at edges, screwing, necessary hardware,
lipping, commercial ply backing as per site condition, adhesives, cleaning . etc
complete as per the Architectural drawings & instructions. (Mode of
measurement- running length of skirting shall be measured for payment)
Refer Drw. No. I-210, I-211, I-213, I-830, I-604A, I-604B, I-604C, I-604D,
I-604E, I-705A, I-705B
92 Providing, making and errecting 500 mm wide and 750mm high Green room Rmt. 10.00
Dressing counter with wash basin made out of 19mm commercial ply as per
architectural drawing and instructions. Including 12mm thick marine ply facia,
drawers, p/f approved washbasin, providing all necessary consumables viz.
adhesive, necessary hardware, necessary beads moulding, lipping, fastenings,
fittings and finish the ply with approve laminate (Laminate to be approved by
architect before commencement of work) at visible side and french polish at
drawer inner side and whereever is required and cleaning etc. complete as
directed and as specified by EIC.
Refer Drw. No. I-210, I-211, I-213, I-830, I-602A, I-602B, I-603A, I-603B,
I-703
93 Providing & fixing 38 mm thick Glass Shutter (1350 X 950) for TV in each 1.00
Postfunction area comprising with 12mm thick Toghened clear glass fixed in 50 x
38mm teak wood frame finished with approved water cut enamel paint as per
architectural drawings and instructions including providing & fixing 12 mm thk TW
lipping all around finished with approved water cut enamel paint. Rate also
included providing and fixing teak wood shutter of size 50 x 38mme of size finish
with approved water cut enamel paint including providing all necessary
consumables viz. adhesive, necessary hardware, necessary beads moulding,
lipping,fastenings, L & Key locking system & cleaning etc. completed at all floors
& heights as per architectural drawings and instructions.
Refer Drw. No. I-210, I-211, I-213, I-830, I-605A, I-605B, I-607A, I-607B,
I-706
95 Providing & fixing aluminium louvered grill for return air duct with approved colour Sqm. 20.00
power coated matching to the wall texture paint and 50 mm X 65 mm aluminium
box frame as per architectural detailed drawing including louvers, brass fixtures,
fastenings & fittings, necessary back packing, cutting, griding, drilling and
cleaning etc. complete. as specified and as directed by EIC / Architect.
Refer Drw. No. I-210, I-211, I-213, I-830, I-604A, I-604B, I-604C, I-604D,
I-604E, I-705A, I-705B
96 Providing and doing laminated wooden hardwood flooring of approved make and Sqm. 10.00
pattern and as per architectural drawing and instructions. The system shall be
comprise with following.
Wooden Flooring- Providing and fixing 150mm to 200mm and 19mm thick
interlocking wooden planks matching to the existing wooden flooring for stage
fixed on existing base properly as per architectural drwaing and instructions.
including necessary hardware, lipping, moulding, approved quality foam below the
wooden strips, cutting, drilling, finish the strips with approved melamine polish
matching to the existing wooden flooring and cleaning etc. completed as
directed and specified by EIC.
i) The contractor shall submit 6 copies of shop drawings for each windows,
ventilators showing dimension details of construction etc. for approval of the
Engineer - in - charge. And according to the approved shop drawing a sample of
each of windows with all fittings and fixtures with locking arrangement including
glass panes etc. complete as per schedule of quantities, specifications and
drawings, shop drawing should be submitted for preliminary inspection for
approval. After preliminary inspection , the sample should be fixed at site to
ascertain its performance. Large scale manufacturing should be taken up only
after rectification of defects in samples as directed to the full satisfaction of the
department and after obtaining formal approval.
ii) All doors, windows, ventilators section shall be anodized extruded section of
M/s Jindal / M/s Indal or or any other makes specified in the list of approved
makes.
iii) All fittings / fixtures shall be of approved make / quality and as approved
by Architect.
xi) Shall furnish guarantee of one year on a stamp paper for performance of
smooth operation and leakage.
97
Supply & fixing in position at all floors integrated Champagne color anodized matt
finished alluminium work work for door, window, ventilator, louver with extruded
builtup standard sections of Jindal / Aluminax or other approved make conforming
IS: 733 & IS: 1285 fixing with dash fastners of required size, including filling up the
gaps at junctions i.e. top, bottom & sides with required EPDM rubber / neoprene /
polysulphide sealant etc. Alluminium section shall be smooth, rust free, straight
and jointed mechanically wherever required, including cleat angle, alluminium
snap beading for glazing / paneling, stainless steel screws all complete.
- All fitting and fixtures such as lever locks, handles, hinges, concealed tower
bolts, door closer etc. shall be suited to sections and be of approved make. They
shall be finished in matching coating or as approved.
- Supply and fixing of aluminum work shall be carried out from 'approved agency.
- Prior to start of work supplier shall submit detailed full scale
Shop drawings including plan, elevation and detail of fixing with structure for
approval of the EIC. Samples of each item on full
scale or smaller scale as directed by the EIC shall be submitted for approval.
98.1 With 5.0 mm thick clear glass of approved make (fixed panel of windows) Sqm. 5.00
99 Vision Glass - 5mm Solar Low E Refl HS +12mm air Gap + 6mm clear float HS. Sqm. 20.00
The glass spectrophotometric properties shall be as follows : Glass appearance -
Light Grey , VLT- 46% , Solar factor - 0.45 max , shading coefficient - 0.51 max ,
U value - 2.8 W/m2K.
Refer Drw. No. I-210, I-211, I-213, I-820, I-830
102 Providing and doing conbond chemical treatment to damaged RCC portion with Sqm. 10.00
rich concrete and using sunanda or equivalent bonding chemical as per
manufacturar's specifications & instructions.including removing damaged RCC
portion,form-work, compacting, finishing the exposed faces, curing & rate also
included P/d chemical treatment to Reainforcement etc. completed as specified
and as directed by EIC. (Mode of measurements : Only damaged area shall
be measured for payment)
Refer Drw. No. A-200, A-201, A-202, A-502, A-503, A-800
103 Providing, making and fixing Roller Blinds as per architectural drawing and 0.00
instructions made out of approved make and quality fabrics shall be made from
high quality texturised and spun yarn. It should has excellent textile appearance of
translucency, 100% polyster fabric, acrylic coating on both side of fabric, fabric
fixed to the proper location.including necessary hardware, drilling, cutting, powder
coate aluminum clips, rods and pulling rope. two blinds should be over lap to each
other by 150mm. etc. cpmpleted as required as specified by EIC. (Area of the
fabric shall be measured for billing)
Refer Drw. No. I-210, I-211, I-213, I-830, I-604A, I-604B, I-604C, I-604D,
I-604E, I-705A, I-705B
103.1 2) Providing and fixing Blackout Blinds ( Make- Galeecha -CB-04/ NL- 1511 W - Sqm. 25.00
2.4 MT)
104 Providing and fixing of Wall 25 mm dia SS Curtain Rod with approved Sqm. 10.00
Curtains (- Make -Gujarat furnishing -Mooshy collection design No. 22/ Pride- PR
- DS 1004) for Green room of approved colour fixed to the wall properly and SS
pipe shall be fixed to the wall by 50 mm ss flange including necessary hardware,
runners and accessiories, drilling, scaffolding, distance between two folds of
curtain shall not be more than 25mm, and cleaning etc..complete as required as
specified by EIC. (Elevational area of the opening shall be measured for
billing)
Refer Drw. No. I-210, I-211, I-213, I-830, I-602A, I-602B, I-603A, I-603B,
I-703
106 Providing, making & errecting False Floor system as per architectural Sqm. 15.00
drawings & instruction. System consisting of concore steel panels, bare steel
panels of size 60cm x 60cm with following details. The floor panels made out of
hard cold rolled steel top sheet welded to a formed draw quality steel bottom pan
at assembly of each dome and multiple points along perimeter. The panels shall
be internally filled with lightweight cementitious product (Concore). The floor
panels shall be protected from corrosion by powder coat epoxy paint finish. The
understructure shall be with stringer system with finish floor height (FFH) of
200mm. The system shall be stringer system provide a range of adjustment upto
35mm total. The understructure supporting the panel shall be as follows
Refer Drw. No. I-210, I-211, I-213, I-830, I-607A, I-607B, I-706
Pedestal Heads : Consist of solid steel stud roll formed and press fitted into
head. Pedestal heads shall incorporate tabs, which accurately align the head with
the panel. The stud shall provide an anti rotation feature and vibration proof
locking device when engaged with the pedestal base assembly.
Pedestal Bases :Fabricated of a square base with not less than 100 cm sq.
assembled to a stud or tube, which is designed to engage the pedestal assembly,
secured to sub floor with adhesive or with screws. The tube shall be 2.22 Sq. Cm.
108 Providing, making and fixing in position custom made SS Signages as per 0.00
arcthitectural drawings and instructions with approved SS fixtures, approved base
including necessary hardware, farmas etc. complete as per detail drawing, as
specified and as directed by Architect.
108.1 Embossed sign with black paint (230mm x 230mm high in size) 0.00
109.1.3 Green Room Ladies- (600mm x 150mm height in size) each 1.00
109.1.4 Green Room Gents- (600mm x 150mm height in size) each 1.00
110 Providing & fixing following size, approved quality CP brass Waste coupling with each 3.00
brass check nuts conforming to IS 2963, including jointing with white zinc and
spun yarn and testing the joints for leak proofness all complete.
111 Providing & fixing following size approved quality CP brass Bottle trap with 32 each 3.00
mm size & connection pipe upto the wall and wall flanges including jointing with
white zinc and spun yarn & testing the joints for leak proofness etc. complete.
112 Providing & fixing 15 mm dia. CP brass Basin Tap, fixing the cock in position each 2.00
with inlet connection using white zinc and spun yarn testing the joints to a
hydraulic pressure of 10 kg / Sq.cm for leak proof joints etc. all complete as per
specifications.
113 Providing, fixing, testing and commissioning of C.P. brass angle valve with each 3.00
C.P. wall flange, Nut and Washer etc. complete as required.
114 Fixing, testing and commissioning of sink including providing & fixing C.I./M.S. each 1.00
Brackets (duly painted with 2 coats of paint over a coat of primer) C.P. cast brass
bottle trap with extension piece, rubber adaptor, wall flange, union, C.P. brass
chainrubber plug & making good. (wiithout drain board)For pantry area
115 Fixing, testing & commissioning of C.P. brass eurometic self closing pillar tap. each 1.00
116 Fixing push type liquid soap dispenser with PVC rawl plug & C.P. brass screw each 3.00
complete as required.
TOTAL OF SANITARYWARES & CP APPURTENANCES
122 Providing and fixing Heavy class SS grating with Cockroach proof SS strainer of
approved design including setting in floor with cement motor to match with floor
finish as per architect requirement & suitable for waste and FD.
123.2 Adressable Control modules For Fans, AHU Tripping & Fire Exhaust /smoke each 3.00
Extractas activation per specification
123.7 Addressable type manual Break glass (Pull station) unit as per specifications each 2.00
123.8 Surface mounted addressable type fully solid state circuitory dual tone Electronic each 2.00
loud speaker type hooters with strobe lights of 110 Cd intensity as per
specifications
123.9 Addressable Fault Isolation Module as per specifications each 1.00
124.10 Response Indicator as per Specification each 1.00
TOTAL OF FIRE ALARM SYSTEM
124 Supplying, terminating, testing and commissioning of cabling for fire detection Per Device 25.00
and alarm system with 2C x 1.5 sq mm annealed tinned copper conductor Red
coloured PVC sheathed FRLS armoured cables as per specifications. FR grade
and ISI marked as per relavent IS standards and specifications. Cables shall be
estimated as per the drawings. Cabling for response indicator/ power
/communication cable shall not be considered seperatelyas device. The cost of
the same shall be included in the unit rate estimated for per device. Laying
supervision is under IBMS contractor scope. Cabling for response indicator/
power /communication cable shall not be considered seperatelyas device. The
cost of the same shall be included in the unit rate estimated for per
device(i.e.Cable from FACP panel to First Detector/device ,Last Detector/device
& return to Panel ,Detector to detector/device,Power from Hooter to Hooter and
FACP panel l)
V ELECTRICAL WORK
GENERAL NOTES
Required clearances from the concerned statutory authorities are in the scope of
this work.Statutory fees paid will be reimbursed on production of original receipts
in the name of IITB.
A POINT WIRING IN PVC CONDUIT, TELEPHONE WIRING, T.V WIRING
ETC.
125 Point wiring in PVC conduit (HMS variety)
Point wiring for light/ceiing fan/6A/ 16A/ socket outlet /6A outlet for exhaust fan,
bell point etc. with 1.1 KV grade FRLS PVC insulated multistranded copper
conductor wire(ISI marked), in 25 to 40 mm dia High mechanical stress (HMS)
rigid PVC conduit having ISI marked IS 9537 Part - 3, including fixing accessories
& hardware concealed /exposed in slab/wall or on 5mm. thick G.I. spacers fixed
with no. 10 nettle within the box piece fold wood screws with nylon plug complete
with all conduit accessories 20 SWG G.I. Saddles, ready made MS modular
switchboxes, socket outlet boxes of approved makes including termination inside
sw/sockets with using copper lugs ,zinc chromate passivated, brass earthing stud
1/2 nos, controlling modular switches, sockets with moulded front plate and inner
plate etc. including appropriate size of FRLS PVC insulated copper earth wire,
brass/bakelite (straight / angular) lamp holders, 3 plate ceiling rose,16 A,
connectors, painting etc. as per specifications and drawings and as directed by
E.I.C.and as detailed below : (sample switch Box etc. to be got approved before
fabrication)
NOTE:
1. Connections shall be done with crimped type tinned copper lugs & washers.
11. Light point wiring cost shall include connection of fixture from ceiling rose with
3 core 1.5sqmm copper flexible cable.
125.1 Ceiling Mounted Lights In Sitting Area
126.1.1 Primary Light point with 2 nos of 2.5 sq.mm wires alongwith 1 no of 2.5 sq.mm Pt. 18.00
insulated earth wires controlled by 10A SP MCB in the DB. Excluding cost of MCB
as per specification.
126.1.2 Secondary light point with 2 nos of 1.5 sq.mm wires alongwith 1 no of 2.5 sq.mm Pt 56.00
insulated earth wire looped to item above as per specification.
125.2 Step Lights On Chair
126.2.1 Primary Light point with 2 nos of 2.5 sq.mm wires alongwith 1 no of 2.5 sq.mm Pt. 6.00
insulated earth wires controlled by 10A SP MCB in the DB. Excluding cost of MCB
as per specification.
126.2.2 Secondary light point with 2 nos of 1.5 sq.mm wires alongwith 1 no of 2.5 sq.mm Pt 70.00
insulated earth wire looped to item above as per specification.
125.3 Color Lights On Stage
126.3.1 Primary Light point with 2 nos of 2.5 sq.mm wires alongwith 1 no of 2.5 sq.mm Pt. 2.00
insulated earth wires controlled by 10A SP MCB in the DB. Excluding cost of MCB
as per specification.
125.4 Auditorium Foot Lighting
126.4.1 Primary Light point with 2 nos of 2.5 sq.mm wires alongwith 1 no of 2.5 sq.mm Pt. 2.00
insulated earth wires controlled by 10A SP MCB in the DB. Excluding cost of MCB
as per specification.
126.4.2 Secondary light point with 2 nos of 1.5 sq.mm wires alongwith 1 no of 2.5 sq.mm Pt 10.00
insulated earth wire looped to item above as per specification.
125.5 Post Function Area Lighting
126.5.1 Primary Light point with 2 nos of 2.5 sq.mm wires alongwith 1 no of 2.5 sq.mm Pt. 1.00
insulated earth wires controlled by 10A SP MCB in the DB. Excluding cost of MCB
as per specification.
126.5.2 Secondary light point with 2 nos of 1.5 sq.mm wires alongwith 1 no of 2.5 sq.mm Pt 8.00
insulated earth wire looped to item above as per specification.
125.6 Room Lighting
126.6.1 Wiring with 25mm dia HMS FR PVC conduit embedded or surface mounted as Pt 5.00
including cost of junction boxes, bends, elbows, sockets, tees etc. laying in slab,
cutting chasis and making good wherever called for or surface mounted including
all fixing hardware along with 3 nos - 2.5 sq.mm PVC insulated multi stranded
flexible FRLS copper wires from DB to Switch board near the entrance of room
and necessary accesories required to complete the job in an approved manner as
per instruction of Engineer In Charge as per specification. (As per scheme &
layout)
126.6.3 Secondary light point with 2 nos of 1.5 sq.mm wires alongwith 1 no of 2.5 sq.mm Pt 12.00
insulated earth wire looped to item above as per specification.
125.7 Pre Function Area
126.7.1 Primary Light point with 2 nos of 2.5 sq.mm wires alongwith 1 no of 2.5 sq.mm Pt. 5.00
insulated earth wires controlled by 10A SP MCB in the DB. Excluding cost of MCB
as per specification.
126.7.2 Secondary light point with 2 nos of 1.5 sq.mm wires alongwith 1 no of 2.5 sq.mm Pt 25.00
insulated earth wire looped to item above as per specification.
125.8 Cove Lighting
126.8.1 Primary Light point with 2 nos of 2.5 sq.mm wires alongwith 1 no of 2.5 sq.mm Pt. 2.00
insulated earth wires controlled by 10A SP MCB in the DB. Excluding cost of MCB
as per specification.
126.8.2 Secondary light point with 2 nos of 1.5 sq.mm wires alongwith 1 no of 2.5 sq.mm Pt 6.00
insulated earth wire looped to item above as per specification.
TOTAL FOR POINT WIRING IN PVC CONDUIT, TELEPHONE WIRING,
T.V WIRING ETC.
Note:
1) Sample fixture/fittings shall be got approved from Department and Architects
with complete technical data.
2) The Cat No. indicated below is only indicative.
3) Cost of lamps to be included in installation rate.
4) All fixtures shall be with low loss electronic ballast
5) T5 High Efficiency Lamps control Gear with 10% Total harmonic distortion
(THD)
126.1 Philips Make 1X 70 W CDMT MSB 150 HF downlighter each 33.00
126.2 Philips Make 2X26 W PL-C/2P FBH225 downlighter (with dimmable ballast) each 37.00
126.3 Philips Make 1X28 W T5 V2 VECTOR TCH207 strip fitting each 30.00
126.5 Philips Make 1X11 W FOOT LIGHT BWG 150 each 12.00
126.6 Prolite Make 1 X 11 W PLE 111 E/NM emergency EXIT signage light with each 4.00
Maintainance free batteries for 3hrs Backup
126.7 Philips Make 1X3 W STEP LIGHT(Only lamp with ballast) each 72.00
126.8 Philips Make 1X18W PL Circular down lighting FBS 085 each 14.00
126.9 Philips Make Colorblast Powercore RGB Stage Light (Procenium Mounting) each 2.00
127.10 Philips Make white LED strip light with driver for cove lighting Rmt. 75.00
127.11 DIN Rail mount, 12-Channel Ballst Controller, suitable for 0- of Make- each 1.00
Philips.programmable. Input Power: 1-Phase, 220VAC, 50Hz. To be connected
dimming along with suitable type of dimmable ballst. All the 10VDC/DSI/DALI
Broadcast type (DDBC1200)
127.12 DIN Rail mount, 12-Channel Relay, suitable for 20 A (inductive) On/Off control per each 1.00
channel.Total 12 Chanel Relay capable of 180 A load. All the Channels are
independentlyprogrammable. Input Power: 1-Phase, 220VAC, 50Hz. To be
connected on Dynet network.Make-Philips.(DDRC1220FR-GL)
127.13 Smart switch location to be sujested by Architect / Client .Low-voltage, User each 3.00
interface keypad with 7 Buttons, Standard steel Finish.(DUS 804C)
127.14 Multi Sensor for IR Receiver, motion control.The operation of sensor is Subject to each 2.00
Height of False Celing. Ideally it is suitable for 2.5 Meter height.
129.1 S/I/T/C of Primary point 6A modular type switched socket outlet complete with each 10.00
flush mounting GI back box with earth terminal, civil works and making good to
rough finish plaster so that the box is lined and levelled including wiring as
expressed above complete in all respect.
129.2 S/I/T/C of Secondary Point 6A modular type switched socket outlet looped each 10.00
FRLSom above point complete with flush mounting GI back box with earth
terminal, civil works and making good to rough finish plaster so that the box is
lined and levelled.
129.3 S/I/T/C of Primary point of 6/16A modular type switched socket outlet complete each 15.00
with flush mounting GI back box with earth terminal, civil works and making good
to rough finish plaster so that the box is lined and levelled including wiring as
expressed above complete in all respect.
129.4 S/I/T/C of Secondary Point 6/16A modular type switched socket outlet looped each 26.00
FRLSom above point complete with flush mounting GI back box with earth
terminal, civil works and making good to rough finish plaster so that the box is
lined and levelled.
129.5 AC Points
130.5.1 S/I/T/C of Primary point of 20A modular type switched socket outlet complete each 4.00
with flush mounting GI back box with earth terminal, civil works and making good
to rough finish plaster so that the box is lined and levelled including wiring as
expressed above complete in all respect.(for AC)
130.6.2 S/I/T/C of the 6/16A modular type switched socket outlet looped FRLSom above each 29.00
point complete with flush mounting GI back box with earth terminal, civil works
and making good to rough finish plaster so that the box is lined and levelled. (ups
secondery point )
NOTE:
1. Point wiring means 4 pair 0.50 sq.mm wires from Telephone Tag Block in
Tel/LAN shaft to the assigned point including end termination of one pair at both
sides and other pairs should be kept spare.
2. G.A drawings & fabrications drawing are to be got approved from E-I.C.
3. Approved makes for Telephone wire : FINOLEX / ITL/ POLYCAB
130.7.2 Point wiring for telephone point with 4 pair 0.50 sqmm wire with RJ 11 jack type Pt. 4.00
socket with shutter in a box with connector as per specification.
Note:
1) Point distribution diagram shall put in side the DB with polythene protective
cover.
2) All fabrication drawings shall be got approved.
D UPS
130 Supply, installation,testing and commissioning of 10 KVA online UPS System each 1.00
(Three Phase In & Single Phase Out) with Inbuilt SMF batteries and 15 minutes of
battery backup.
131 Supply, installation,testing and commissioning of following MCB's in powder
coated enclosures.
131.1 32A 4P MCB 'C' curve each 1.00
131.2 63 A DP MCB 'C' each 1.00
132 Supply, installation,testing and commissioning of following sizes of stranded FRLS
copper wire inside flex.PVC conduits including termination at both the ends.
( MCB's mentioned in item no.2 & UPS terminal box.)
132.1 4 sq.mm. x 4 nos in 32 mm Flex. PVC conduit ( for incoming) Rmt. 2.00
132.2 10 sq.mm x 2 no's in 25 mm Flex.PVC conduit for Outgoing. Rmt. 2.00
TOTAL FOR UPS SYSTEM
E DISTRIBUTION BOARDS
READYMADE DISTRIBUTION BOARDS
Note:
1.MCBs shall be minimum 10 KA breaking capacity (Type –C)
2. Blanking Plates shall be included in scope of work.
3. DB shall be of standard readymade type as per catalouge No. from approved
manufacturers as indicated in preferred makes of material.
4. Wire way & cable end box also end & locking plates shall be provided.
5. Routine tests will be conducted at factory in presense of user as per relevant
IS.
All Electrical component should have IS mark
Note:
133.1 DB :(12way TPN DB) Set 2.00
a) 63 A 4P MCB as incomer -- 1 No.
b) 63 A, 2 pole RCCB with 30mA sensitivity - 3Nos.
c) 6 - 32 A SP MCB -- 36 nos
d) 12 way brass neutral links -- 4 Sets.
e) Brass earth links - 1 Sets
e) Brass earth links - 1 Sets
133.2 UPSDB (AV System) Set 1.00
16Way SPN Emergancy Lighting Distribution Boards comprising of:
Incomer:63A DP MCB
16 nos. of 10/16/32A SP MCB C curve, 10kA
Enclosure IP 43 double door PPI Kit
TOTAL OF DISTRIBUTION BOARDS
G EARTHING SYSTEM
136 Supply, installation, testing & commissioning of earthing system & associated
accessories, etc. complete all as per the instructions of E.I.C.
Note :
1) Measurements of resistance of each earth station & resistance of complete
scheme of earthing layout must be measured recorded & got approved by E.I.C.
2) Jointing of the earth strip shall be with brass nuts bolts and also with solder
joints.
3) Jointing of the earth wire shall be with solder joints with tinned cable sockets
136.1 Supply & making Tinned Cu. earth plate electrode 600 X 600 X 3.15 mm earth each 2.00
station 2.5 m below ground level conforming to IS 3043 including 2 nos of 50 x 6
mm Copper earth strips from earthing plate upto the ground level inside the
chamber with all required materials like coke /charcoal, salt, brass nut-bolt &
washers, watering arrangement, G.I. Pipe (B class) concrete chamber of 450mm
x 450mm x 450mm deep, thick chequered plate hinged cover with locking
arrengement mounted on 40x40x5 mm thick angle iron frame & excavation in all
types of soil in ground refilling & removal of excess earth within radius of 2 km.
within IITB campus etc.
VI HVAC WORK
137 Supply, Installation, Testing & Commissioning of Double Skin Air Handling Unit each 1.00
25mm thick panel as per Tech.specifications.
Outer Skin : GSS 0.63mm Preplasticised
Inner Skin : GSS 0.63mm Plain
6RD Dx. Cooling Coil with 3 independent circuits / 48TR Capacity
MERV 13 Filters
Plug type / Backward Curved Fan of 11200 CFM
TEFC Induction Motor EFF1
Insulated SS Drain Tray
138 Supply, Installation, Testing & Commissioning Prefabricated Rectangular 120GSM
GSS Ducting + Rolamate Flanges + Proper Supportiong arrangement
141 Supply, Installation, Testing & Commissioning Duct Acoustic Insulation using
25mm thick Open Cell Nitrile Rubber
141.1 ARMASOUND covered with 28G Al.Perforated Sheet Sqm. 360.00
ngineer-in-charge
oval of Engineer-in-charge
Rate Amount
0
0
Rate Amount
0
Rate Amount
Rate Amount
Rate Amount
Rate Amount
0
0
0
0
0
Rate Amount
Rate Amount
0
Rate Amount
0
Rate Amount
0
0
0
0
0
0
Rate Amount
0
0
0
0
0
0
Rate Amount
0
0
0
0
0
0
0
0
0
Rate Amount
0
Rate Amount
0
Rate Amount
0
Rate Amount
Rate Amount
0
0
0
0
0
Rate Amount
0
0
0
0
Rate Amount
0
0
0
0
0
Rate Amount
0
0
0
0
Rate Amount
0
0
0
Rate Amount
Rate Amount
0
Rate Amount
0
Rate Amount
0
Rate Amount
0
Rate Amount
0
Rate Amount
0
Rate Amount
0
Rate Amount
0
Rate Amount
0
Rate Amount
0
Rate Amount
Rate Amount
0
Rate Amount
0
0
Item Deleted
0
0
0
Rate Amount
0
0
0
0
Rate Amount
0
0
0
0
Rate Amount
Item deleted
Rate Amount
0
Rate Amount
0
Rate Amount
0
Rate Amount
Rate Amount
Rate Amount
0
0
0
0
Rate Amount
0
Rate Amount
0
Rate Amount
Rate Amount
0
0
0
Rate Amount
0
0
0
0
0
0
0
0
0
0
Rate Amount
Rate Amount
0
0
0
0
Rate Amount
Rate Amount
0
0
Rate Amount
0
0
0
Rate Amount
0
0
0
0
0
0
0
0
0
0
Rate Amount
0
Rate Amount
0
Rate Amount
0
0
0
0
0
Rate Amount
Rate Amount
0
0
0
0
0
Rate Amount
0
0
0
0
0
0
0
0
0
0
Rate Amount
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
A B C D E F G H=FXG I=EXH
C.P. & Sanitary Fittings & Accessories
17.2.1 W.C. pan with ISI marked white solid plastic seat and lid each 11.00 2152.50 1.39 2991.98 32,911.73
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
17.70 Providing and fixing PTMT Bottle Trap for Wash basin and sink.
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
Internal work
Providing & fixing G. I pipes complete with G. I. fitting and
18.11 clamps i/c making good the walls etc. concealed pipe including
6 painting with anticorrosive bitumastic paint, cutting chases and
making good the wall
18.11.1 15 mm dia nominal bore metre 100.00 144.75 1.39 201.20 20,120.25
External work
Providing & fixing G. I pipes complete with G. I. fittings
18.12
7 including trenching and refilling etc.
18.12.3 25 mm dia. Nominal bore metre 30.00 156.85 1.39 218.02 6,540.65
18.15 Provding & fixing brass bib cock of approved quality
8
18.15.1 15 mm nominal bore each 11.00 1.39 0.00 -
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
Providing and fixing C.P. brass angle valve for basin mixer and
18.53 geyser points of approved quality conforming to IS:8931 a)
10 15 mmnominal bore
18.53.1 15mm nominal bore each 347.65 each 11.00 347.65 1.39 483.23 5,315.57
18.74.2 15 mm nominal bore with 45 cm length. each 11.00 52.90 1.39 73.53 808.84
Total of Water Supply 47,380.30
Internal Drainage
17.35 Providing and fixing soil, waste and vent pipes :
17.35.1 100 mm dia
17.35.1.2 Centrifugally cast (spun) iron socketed pipe as per IS: 3989 metre 26.00 730.00 1.39 1014.70 26,382.20
12
17.35.2 75 mm diameter
17.35.2.2 Centrifugally cast (spun) iron socketed pipe as per IS: 3989 metre 79.00 629.85 1.39 875.49 69,163.83
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
19.7.1.1 With F.P.S. bricks with class designation 75 each 4.00 5383.70 1.39 7483.34 29,933.37
Total of External Sewage 109,914.39
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
Civil Work
8.10.1 White Agaria Marble Stone sqm 4.00 2274.45 1.39 3161.49 12,645.94
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
Total of Civil Work 46,882.89
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
Rain Water
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
A B C D E F G H=FXG I=EXH
Road work
15.2.1 1:3:6 or richer mix cum 5.00 368.45 1.39 512.15 2,560.73
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
2.8.1 All kinds of soil cum 1510.00 103.40 1.39 143.73 217,026.26
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
Extra for compaction of earth work in embankment under
8 16.2 optimum moisture conditions to give at least 95% of the cum 369.00 4.50 1.39 6.26 2,308.10
maximum dry density(proctor density).
16.3 Supplying and stacking at site.
16.3.1 90 mm to 45 mm size stone aggregate cum 248.00 742.30 1.39 1031.80 255,885.66
9
16.3.2 63 mm to 45 mm size stone aggregate cum 331.00 768.45 1.39 1068.15 353,556.16
16.3.10 Moorum. cum 369.00 421.85 1.39 586.37 216,371.08
16.30.1 On W.B.M. @ 0.75 Kg / sqm. sqm 1229.00 23.90 1.39 33.22 40,828.61
16.30.2 On bituminous surface @ 0.50 Kg / sqm sqm 2612.00 17.15 1.39 23.84 62,266.16
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
16.48.1 New work (Two or more coats). sqm 431.00 58.10 1.39 80.76 34,807.13
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
Scarifying the existing bituminous road surface to a depth of
19 16.77 50mm anddisposal of scarified material within all lifts and lead sqm 2612.00 2.60 1.39 3.61 9,439.77
upto 1000 metre (bymechanical means).
Total of Road work 4,169,407.96
Storm water Drain work
2.8.1 All kinds of soil cum 480.00 103.40 1.39 143.73 68,988.48
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
Coursed rubble masonry (second sort) with hard stone in
23 7.7.1 foundation and plinth with : cum 152.00 1913.1 1.39 2659.21 404,199.77
cement mortar 1:6 (1 cement : 6 coarse sand)
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
Compound wall
2.8.1 All kinds of soil cum 967.00 103.40 1.39 143.73 138,983.04
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
Providing and laying 230 mm. thick dry rubble soling in line and
level, hand packed and vertically set, including filling interstices
33 NON DSR with quarry spoils, stone chips, grit etc. finally spreading either Sq m 405.00 264.50 107,122.50
grit or shingle above it as directed, compaction by wooden/
metallic rammers, watering etc. complete.
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
Total of Compound wall 1,379,435.44
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
A B C D E F G H=FXG I=EXH
Soft Landscape
3 Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
2.33.2 Beyond 60 cm girth upto and including 120 cm girth each 5.00 359.80 1.39 500.12 2,500.61
2.33.3 Beyond 120 cm girth upto and including 240 cm girth each 10.00 1658.85 1.39 2305.80 23,058.02
Supplying and stacking of good earth at site including royalty
4 23.2 and carriage up to 1 km ( earth measured in stacks will be cum 204.00 144.05 1.39 200.23 40,846.82
reduced by 20% for payment).
23.4.3 Screened through sieve of I. S. designation 4.75mm cum 56.00 97.05 1.39 134.90 7,554.37
6 23.7 Fine dressing the ground 100 sqm 6.00 80.20 1.39 111.48 668.87
Spreading of sludge, dump manure or/and good earth in
7 23.8 required thickness (cost of sludge, dump manure or/ and good cum 204.00 11.60 1.39 16.12 3,289.30
earth to be paid separately)
Mixing earth and sludge or manure in proportion specified or
8 23.9 cum 260.00 7.85 1.39 10.91 2,836.99
directed.
23.10.3 In rows 5 cm apart in either direction. 100 sqm 6.00 384.85 1.39 534.94 3,209.65
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
A B C D E F G H=FXG I=EXH
Miscellaneous Items
Operative
SR.NO. DSR 2007 Description Unit Qty Rate Cost Index Amount
Rate
2mm thick corrugated (2.5" or 4.2" or 6") or step-down (2" or3"
12.47.1 sqm 33.00 785.35 1.39 1091.64 36,024.00
or 6" ) as specified.
S. DSR OPERATIVE
ITEM DESCRIPTION QTY UNIT RATE COST INDEX
NO. 2007 RATE
A B C D E F G H=FXG
Supply & fixing modular base & cover plate: Supply &
10 1.28 fixing following modular base nd cover plate for modular
switches in recess etc as required.
AMOUNT IN RS.
I=DXH
30,545.25
8,089.80
66,428.10
3,010.00
25,645.50
13,066.00
3,580.64
1,490.08
2,246.24
423.95
2,746.64
444.80
8,195.44
2,513.12
4,749.63
1,579.04
1,558.19
2,271.26
1,984.92
291.90
291.90
985.51
1,036.94
1,912.64
2,638.22
7,561.60
9,618.80
7,089.00
861.80
95.91
95.91
213,048.73
M.S.
S. OPERATIVE
PWD ITEM DESCRIPTION QTY UNIT RATE COST INDEX
NO. RATE
DSR NO
A B C D E F G H=FXG
Telephone wiring
Supplying & errecting telephone cable 1 pair with 0.5mm
1 1.10.1 dia laid in provided pvc casing / conduit as per 75.00 Metre 9.00 1.39 12.51
specification no. WG-TW
Supplying , errecting & commissioing junction box
2 1.11.12 1.00 Each 553.00 1.39 768.67
suitable for 10 pairs as per specification no. WG-TW
Supplying , errecting & commissioing crone module of 10
3 1.11.20 1.00 Each 339.00 1.39 471.21
pairs as per specification no. WG-TW
LAN cabling
AMOUNT IN RS.
I=DXH
938.25
768.67
471.21
3,440.25
166.80
4,345.14
9,798.11
17,167.89
33,682.48
4,481.36
12,776.88
1,451.16
7,005.60
7,005.60
17,743.35
15,595.80
136,838.55
S. COST OPERATIVE
CODE ITEM DESCRIPTION QTY UNIT RATE
NO. INDEX RATE
A B C D E F G H=FXG
DSR
COPPER WIRING IN PVC CONDUITS
2007
Point wiring in PVC conduit,with MODULAR type
switch :Wiring for light point/fan point/exhaust fan
point/call bell point with 1.5 sq.mm FR PVC insulated
copper conductor single core cables in surface/recessed
1.10
1 PVC conduit,with modular switch ,modular
plate,,suitable size G.I box and earthing the point with
1.5 sq.mm FR PVC insulated copper conductor single
core cables etc. as required.
AMOUNT IN RS.
I=DXH
30,545.25
8,089.80
66,428.10
3,010.00
25,645.50
13,066.00
3,580.64
1,490.08
2,246.24
423.95
2,746.64
444.80
8,195.44
2,513.12
4,749.63
1,579.04
1,558.19
2,271.26
1,984.92
291.90
291.90
985.51
1,036.94
1,912.64
2,638.22
7,561.60
9,618.80
7,089.00
861.80
95.91
95.91
213,048.73
AMOUNT IN RS.
I=DXH
938.25
768.67
471.21
3,440.25
166.80
4,345.14
9,798.11
17,167.89
33,682.48
4,481.36
12,776.88
1,451.16
7,005.60
7,005.60
17,743.35
15,595.80
136,838.55
S. COST OPERATIVE
CODE ITEM DESCRIPTION QTY UNIT RATE
NO. INDEX RATE
A B C D E F G H=FXG
DSR 2007 ITEM AS PER DSR 2007
Prewired MCB DB
S/F prewired MCB DB: Supplying and installation &
testing & commissioing of 4 way (4+4) , TPN , vertical
1791
1 type , prewired MCB DB with extended loose wire box ,
double door
2.43.5 4 way vertical double door 1.00 Each 5,830.00 1.39 8,103.70
MCB, RCCB, MCB DB's
2 1722 63 Amps rating , 4 pole RCCB 100mA / 300mA 1.00 Each 1,218.00 1.39 1,693.02
6 Amp to 32 Amp rating TP MCB 'C' series 10KA
3 1709 4.00 Each 1,218.00 1.39 1,693.02
breaking capacity
Steel tubular pole & strut
AMOUNT IN RS.
I=DXH
8,103.70
1,693.02
6,772.08
34,166.20
50735.00
AMOUNT IN RS.
I=DXH
12,176.40
86,736.00
57,546.00
627,473.80
16,652.20
12,982.60
83,122.00
15,957.20
7,089.00
8,701.40
928,436.60
5,610,000.00
5,610,000.00