SI Description of Item
Air-conditioning works
1.a Supply, Installation, Testing and Commissioning of accessories for the AHU ceiling suspended
AHU as under:
- Modular AHU panels with GI sheet of 0.60 mm thick for both inner & outer casing with
25 mm insulation sand witched in between. The outer panel shall have pre coating for
corrosion resistance as also to provide a very good finish.
- Blower section with forward curved centrifugal fan with TEFC motor (IP 55 and Class F
insulation).
- Drain section with 1.2mm SS drain pan.
- Coil section with 4/6 row chilled water coil, Slimseal BF valves at inlet/ outlet, drain and
purge connections.
a. Flexible connection the outlet.
b. AHU sub panel with isolator and starter (Star/ Delta) with lockable OFF pushbutton.
c. Fresh air cowl with screen and damper.
e. Power wiring with 3 C x 16 sqmm. PVC armoured copper cable with end terminations
and two runs of 6 SWG copper earth rods (approx length - 20 M)
f. Inlet and outlet isolating valves of 65 mm dia:
g. 3-way mixing valve with all connections and control wiring
h. Pressure gauges and thermometers at inlet and outlet
NOTE: This shall only include the accessories for the mentioned AHU capacity. The owner
shall be providing the AHU
2
Supply, Laying, Pressure testing and insulating of chilled water piping, complete with fittings,
supports and insulation. Insulation of 50 mm thick TF quality thermocole with 22 G
Aluminium cladding. Insulations shall be as under/as per IS 1239, Mild Steel heavy (Class C)
class pipe:
a. 65 mm dia:
b. 50 mm dia:
Drain piping from the AHU with PVC piping and insulated as required:
- 32 mm dia:
- 32 mm dia drain valve:
3.a
Supply and laying of galvanized sheet steel ducting with class VIII quality of zinc coating, complete
with anchor fasteners and MS supports, angle bracings as required, nut, bolt & gasket etc
etc.
a. 24 G ducting:
b. 22 G ducting:
c. 20 G ducting:
3.b Supply and laying of aluminium spiral ducting, complete with anchor fasteners and MS supports, angle
bracings as required, nut, bolt & gasket etc
22 G ducting:
20 G ducting:
4 Supply and installation of powder coated Al. Supply air grills and return air outlets:
a. Supply air grille with damper
b. Return air grille w/o damper.
c. Supply air diffuser with damper (circular/square)
d. Return air diffuser without damper (circular/square)
Acceptable makes: Air Master/ Air Breeze/System Air/AAF or equivalent.
6 Supply and laying of thermal insulation of ducting with 15 mm thick nitrile rubber, laminated with
Aluminium foil
TOTAL OF 1 TO 8
NOTE: All the above rates must be quoted inclusive of all applicable taxes, transport, scaffolding, and all n
Note:
Offer valid for 15days.
FCU,CSU,AHU Ducting related works not Considered
Electrical work done by Electrical Contractor
GST will Extra applicable
Any additional items/Qty required will be charged Extra.
WORKS:
RO sqM. 10325
RO sqM. 8500
1 sqM. 13500 13500
1.5 sqM. 12000 18000
459,325.00
2
3.a
3.b
3.c
3d,
4
5
10
SI
Air-conditioning works
1.a
AIR-CONDITIONING WORKS
Supply, Installation, Testing and Commissioning of AHU ceiling suspended AHU as under:
- Modular AHU panels with GI sheet of 0.60 mm thick for both inner & outer casing with 25 mm insulation
sand witched in between. The outer panel shall have pre coating for corrosion resistance as also to provide a
very good finish.
- Blower section with forward curved centrifugal fan with TEFC motor (IP 55 and Class F insulation).
- Drain section with 1.2mm SS drain pan.
- Coil section with 6 row chilled water coil, Slimseal BF valves at inlet/ outlet, drain and purge connections.
NOTE: The above AHU will be connected to terminal fan filter unit for HEPA filtration in the lab
Supply, Laying, Pressure testing and insulating of chilled water piping, complete with fittings, supports and
insulation. Insulation of 50 mm thick TF quality thermocole with 22 G Aluminium cladding. Insulations shall be
as under/as per IS 1239, Mild Steel heavy (Class C) class pipe:
a. 65 mm dia:
b. 50 mm dia:
Drain piping from the AHU with PVC piping and insulated as required:
- 50 mm dia:
- 32 mm dia:
- 50 mm dia drain valve:
- 32 mm dia drain valve:
Supply and laying of aluminium ducting, complete with anchor fasteners and MS supports, angle bracings as required,
nut, bolt & gasket etc
22 G ducting:
20 G ducting:
Supply and laying of galvanized sheet steel ducting with class VIII quality of zinc coating, complete with anchor fasteners
and MS supports, angle bracings as required, nut, bolt & gasket etc
etc.
a. 24 G ducting:
b. 22 G ducting:
c. 20 G ducting:
Supply and laying of aluminium spiral ducting, complete with anchor fasteners and MS supports, angle bracings as
required, nut, bolt & gasket etc
22 G ducting:
20 G ducting:
Supply and installation of powder coated Al. Supply air grills and return air outlets:
a. Supply air grille with damper
b. Return air grille w/o damper.
c. Supply air diffuser with damper (circular/square)
d. Return air diffuser without damper (circular/square)
e. Ceiling suspended laminar flow SS plenum for labs comprising as standard feature with HEPA filter
efficiency not less than 99.97% at 0.3 Microns (Factory DOP tested). with air flow at approx. 90-100 Fpm
velocity. Each HEPA filter - 2 ft x 2 ft. This is to be mounted only for the ceiling suspended units 12 TR for the
labs
f. Ceiling suspended fan filter unit of SS construction complete with independent fan with HEPA filter
efficiency not less than 99.97% at 0.3 Microns (Factory DOP tested). with air flow at approx. 90-100 Fpm
velocity. Each HEPA filter to take care of 750 CFM capacity. These units are only for the development lab and
MPCVD labs
Fan filter units, 750 CFM capacity
Acceptable makes: Air Master/ Air Breeze/System Air/AAF or equivalent.
g. Floor/wall mounted fan filter unit of SS construction complete with independent fan with HEPA filter
efficiency not less than 99.97% at 0.3 Microns (Factory DOP tested). with air flow at approx. 90-100 Fpm
velocity. Each HEPA filter to take care of 750 CFM capacity. These units are only for the development lab and
MPCVD labs
Fan filter units, 750 CFM capacity
Supply and laying of thermal insulation of ducting with 15 mm thick nitrile rubber, laminated with Aluminium
foil
Supplying and installation of acoustic insulation of ducting with 19 mm thick armasound or equivalent
material.
Supply and installation of acoustic insulation for the walls of the AHU room with 25 mm thick armasound or
equivalent material.
SITC of chilled water compact cassette unit (1 TR capacity) complete with all fittings and accessories for the
UPS and server room with a 24 hour auto timer
Description of Item
Air-conditioning works
Supply, Installation, Testing and Commissioning of accessories for the AHU ceiling suspended AHU as under:
- Modular AHU panels with GI sheet of 0.60 mm thick for both inner & outer casing with 25 mm insulation
sand witched in between. The outer panel shall have pre coating for corrosion resistance as also to provide a
very good finish.
- Blower section with forward curved centrifugal fan with TEFC motor (IP 55 and Class F insulation).
- Drain section with 1.2mm SS drain pan.
- Coil section with 4/6 row chilled water coil, Slimseal BF valves at inlet/ outlet, drain and purge
connections.
a. Flexible connection the outlet.
b. AHU sub panel with isolator and starter (Star/ Delta) with lockable OFF pushbutton.
c. Fresh air cowl with screen and damper.
e. Power wiring with 3 C x 16 sqmm. PVC armoured copper cable with end terminations and two runs of 6
SWG copper earth rods (approx length - 20 M)
f. Inlet and outlet isolating valves of 65 mm dia:
g. 3-way mixing valve with all connections and control wiring
h. Pressure gauges and thermometers at inlet and outlet
Note:
Offer valid for 15days.
Scaffolding, Civil Works , Duct Paint, Duct Torpolin sheet done by Customer
FCU,CSU,AHU Ducting related works not Considered
Electrical work done by Electrical Contractor
GST will Extra applicable
Any additional items/Qty required will be charged Extra.
Note:
Offer valid for 15days.
Scaffolding, Civil Works , Duct Paint, Duct Torpolin sheet done by Customer
FCU,CSU,AHU Valve Package Not Consider
Electrical work done by Electrical Contractor
GST will Extra applicable
Any additional items/Qty required will be charged Extra.
1.00 no. 342,500.00 342,500.00
1.00 no. 86,000.00 86,000.00
1,598,025.00
1 no.