Circuit Breaker Time / Current Curves (Earth Current) : With Without With

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Digitrip 1150Vi Earth Curve

with Zero Sequence Sensor 69C3016G02 (50A Tap)

30

40

60
50

70
20
10
5
6

9
8
3

7
2
1
10000
9000
2 HOURS

8000 Circuit Breaker Time / Current Curves (Earth Current)


7000
VCP-T, VCP-TR, T-VAC, and T-VACR Medium Voltage Circuit Breakers
6000 Response: Earth (Gnd) Trip using Zero Sequence
2
(FLAT & I T)
5000 This curve is for 50Hz or 60Hz applications.
1 HOUR

4000 Notes:

3000 1. The Zero Sequence scheme requires that sensor be wired to breaker terminals
B-4 and B-5 and also requires a jumper on terminals B-6 to B-7 to enable the Zero
Sequence functionality. Also required is the programming of Digitrip 1150Vi setting
“EXT GND CT RATIO” be set to 50/1.
2000
2. For phase current time/current curves, see curves 5721B01 through 5721B06 and
5721B08 through 5721B11.

3. The curve is shown using 50/1 Sensor and is shown in Amperes.


1000
900 4. The Earth Fault settings have conventional 100% ± 10% as their pick up points.
800
700
5. With zone interlocking on ground fault utilized and no restraining signal, the
600 minimum time band (FLAT) applies regardless of setting.
500
6. The dotted line shows the worst case response of the minimum setting, 0.1x, when
400 Trip unit’s external power is not available.

300 7. Earth Slope: FLAT


Tolerance is +0 / -80 ms except
0.10s setting band is 0.06 to 0.13
200 0.15s setting band is 0.08 to 0.17
0.20s setting band is 0.15 to 0.22

2
8. Earth Slope: I T
2
I T slope flattens out at 0.625x In (50 x .625 =31.2A) for top of band with FLAT
100
90 time minimum value prevailing for bottom of band.
2
80 Curve Trip Equation: Trip = (Earth TIME) x 0.39 / In (top)
1 MINUTE

70 2
60 Curve Trip Equation: Trip = ((Earth TIME) x 0.39 / In ) * 0.70 (bottom)
50
The above equations indicate tolerance is +0 / -30% for all settings except
40
0.10s is +30% -25%
0.15s is +20% -25%
30
0.20s is +10% -25%

0.1x setting
20 0.1x setting without
20
with 0.1x setting
Aux Power with 0.1x setting
Aux Power available
available Aux Power without
See Note 6 available Aux Power
10 available 10
9 9
8 See Note 6 8
7 7
6 6
5 5

4 4

Available EARTH PU
3 3
settings 0.1 to 1.0x
CLEARING TIME IN SECONDS

“EXT EARTH CT RATIO”


2 with steps of 0.01. 2
See Note 4

CLEARING TIME IN SECONDS


Break point
1 @ 31.2A 1
.9 to FLAT .9
.8 .8
.7 .7
.6 .6
0.50s
.5 0.50s .5

.4 .4
2
Available I T
.3 Response .3
Available FLAT response
EARTH TIME
EARTH TIME 0.1 to 0.5 seconds
.2 0.1 to 0.5 seconds .2
with
with 0.05 s increments 0.05 s increments See Notes 7,8
See Note 7

.1 .1
.09 .09
.08 .08
.07 .07
.06 0.10s 0.10s .06

.05 .05

.04 Minimum .04


Minimum
Clearing Time Clearing Time
.03 for 0.10 s setting .03
for 0.10 s setting

.02 .02

.01 .01
1

40
2

7
100
40

30
50

80

4
10

20

9
10
30

70

100
2

7
8

20
6

70
90
4

60

90
5

60
50

80
6
3

Current in Amperes

Dwg. No: 5721B17


September 2006