Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

SYS600 Operation Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 198

MicroSCADA Pro SYS600 9.

4
Operation Manual
Trace back information:
Workspace Main version a50
Checked in 2015-06-08
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Contents

1 Copyrights ............................................................................................. 7

2 Introduction ........................................................................................... 9
2.1 This manual .................................................................................. 9
2.2 Use of symbols ............................................................................. 9
2.3 Intended audience ........................................................................ 9
2.4 Related documents ....................................................................... 10
2.5 Document conventions ................................................................. 10
2.6 Document revisions ...................................................................... 10

3 Overview ................................................................................................ 11
3.1 Getting started .............................................................................. 11
3.1.1 Login ............................................................................... 11
3.1.2 Logout ............................................................................. 12
3.1.3 Time based logout .......................................................... 12
3.1.4 Time-based logout after inactivity ................................... 12
3.2 Application displays ...................................................................... 13
3.3 Process Displays .......................................................................... 14
3.3.1 Controlling the process ................................................... 15
3.3.2 Adding Process Display Notes ....................................... 16
3.3.3 Adding a comment to an object ...................................... 19
3.3.4 Renaming Process Display ............................................. 21
3.4 Monitor Pro layout ......................................................................... 21
3.4.1 Specifying toolbars ......................................................... 22
3.4.2 Changing application layout ............................................ 23
3.4.3 Resetting Layout ............................................................. 31
3.5 Using process lists ........................................................................ 31
3.6 Using reports and trends .............................................................. 32

4 Process controlling .............................................................................. 33


4.1 Navigating ..................................................................................... 33
4.2 Zooming ........................................................................................ 34
4.3 Find ............................................................................................... 37
4.4 Station Local/Remote control ........................................................ 38
4.5 Bay Local/Remote control ............................................................. 41
4.6 Switch control ............................................................................... 44
4.6.1 Blockings ........................................................................ 45
4.6.2 Forced operations ........................................................... 46
4.6.3 Simulation ....................................................................... 49
4.6.4 Alarms ............................................................................. 50
4.6.5 Auto-reclose .................................................................... 51
4.6.6 Operation counters ......................................................... 52

3
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

4.6.7 Dial-up ............................................................................ 54


4.6.8 Tagout ............................................................................. 57
4.6.9 Operator Place ................................................................ 60
4.7 Transformer voltage control .......................................................... 61
4.8 Measurement control .................................................................... 67
4.9 Alarm indicator control .................................................................. 75
4.10 Color Setting Tool ......................................................................... 77
4.11 Network topology coloring ............................................................ 78

5 Event Display ........................................................................................ 81


5.1 Event Rows ................................................................................... 84
5.2 The Event Display User Interface ................................................. 85
5.2.1 Using the Event Display User Interface .......................... 85
5.2.2 Using Filters .................................................................... 85
5.2.3 Locating Signals ............................................................. 87
5.2.4 Blocking Signals ............................................................. 88
5.2.5 Customizing the column layout ....................................... 89
5.2.6 Color Settings ................................................................. 90
5.2.7 Exporting Data ................................................................ 94
5.2.8 Indicating Daylight Saving Time ..................................... 94
5.3 Handling events ............................................................................ 94
5.3.1 Event Display Settings .................................................... 94
5.3.2 Event Comments ............................................................ 96

6 Alarm Display ........................................................................................ 99


6.1 Alarm rows ....................................................................................101
6.2 The Alarm Display User Interface .................................................103
6.3 Handling alarms ............................................................................103
6.3.1 Alarm Display Settings ....................................................105
6.3.2 Acknowledging alarms .................................................... 106

7 Blocking Display ................................................................................... 107


7.1 Blocking Rows .............................................................................. 109
7.2 The Blocking Display User Interface ............................................ 109
7.3 Handling Blockings ....................................................................... 109
7.3.1 Blocking Display Settings ............................................... 110

8 User Activity Log Display .....................................................................113

9 Trends Display ...................................................................................... 115


9.1 Starting Trends Display ................................................................ 116
9.2 The Trend Basket ......................................................................... 116
9.2.1 Add and remove Trends ................................................. 117
9.2.2 Trend settings ................................................................. 118
9.2.3 Clearing Trend data ........................................................ 119

4
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

9.3 The user interface .........................................................................119


9.3.1 Trends Display toolbars .................................................. 119
9.3.2 Trends Display menus .................................................... 120
9.3.3 Using Trend curves .........................................................122
9.3.4 Time range ......................................................................123
9.4 Graphical view .............................................................................. 123
9.5 Tabular view ..................................................................................134
9.6 Preconfigurations ..........................................................................138
9.7 Exporting Trends .......................................................................... 139
9.8 Printing Trends ..............................................................................140
9.9 Authorizing ....................................................................................140

10 Measurement Reports .......................................................................... 141


10.1 Starting Measurement Reports Display ........................................ 141
10.2 The user interface .........................................................................142
10.2.1 Measurement Reports Display toolbars ..........................142
10.2.2 Measurement Reports Display menus ............................145
10.2.3 Measurement Reports Display header ........................... 147
10.3 Graphical view .............................................................................. 147
10.4 Tabular view ..................................................................................149
10.5 Preconfigurations ..........................................................................155
10.6 Exporting Reports ......................................................................... 156
10.7 Printing Reports ............................................................................ 156
10.8 Authorizing ....................................................................................156
10.9 Quick Reports ............................................................................... 156

11 System Self Supervision ...................................................................... 159


11.1 Supervision application objects .................................................... 160
11.2 Supervision monitoring symbols and control dialogs ....................160
11.2.1 Supervision symbols ....................................................... 160
11.2.2 Symbol appearance ........................................................ 160
11.2.3 Supervision control dialogs ............................................. 162
11.2.3.1 Common characteristics ............................... 162
11.2.3.2 Application supervision ................................. 164
11.2.3.3 Communication Node supervision ................ 165
11.2.3.4 Communication Line supervision .................. 166
11.2.3.5 SNMP supervision .........................................167
11.3 Supervision events and alarms .................................................... 168
11.4 Supervision logging ...................................................................... 170
11.5 Supervision Log Viewer ................................................................ 170

12 Sequence Executor ...............................................................................173


12.1 Launching the tool ........................................................................ 173
12.2 User Interface ............................................................................... 174
12.2.1 Menu bar .........................................................................175
12.2.2 Toolbar ............................................................................ 175

5
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

12.3 User Authorizations ...................................................................... 176


12.4 Executing a Sequence ..................................................................176
12.5 Statuses and Outputs ................................................................... 177
12.6 Sequence Queue ..........................................................................178
12.7 Controllablity Check ......................................................................179

13 Using Calendar ......................................................................................181


13.1 Opening Calendar .........................................................................181
13.2 Making selections ......................................................................... 182
13.3 Adding day type to group of days ................................................. 183
13.4 Setting day type attributes ............................................................ 183
13.5 Saving attributes ........................................................................... 183
13.6 Changing current time .................................................................. 183
13.7 Setting day attributes .................................................................... 184
13.8 Changing calendar properties ...................................................... 186

14 Terminology ...........................................................................................191

15 Abbreviations ........................................................................................ 193


Index .......................................................................................................195

6
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

1 Copyrights

The information in this document is subject to change without notice and should not be
construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for any
errors that may appear in this document.
In no event shall ABB Oy be liable for direct, indirect, special, incidental or consequential
damages of any nature or kind arising from the use of this document, nor shall ABB Oy
be liable for incidental or consequential damages arising from the use of any software
or hardware described in this document.
This document and parts thereof must not be reproduced or copied without written
permission from ABB Oy, and the contents thereof must not be imparted to a third party
nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license.
Copyright © 2015 ABB Oy. All rights reserved.
Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their respective
holders.
Guarantee
Please inquire about the terms of guarantee from your nearest ABB representative.
Third Party Copyright Notices
List of Third Party Copyright notices are documented in "3rd party licenses.txt" and
included in SYS600 and DMS600 installation packages.

7
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

2 Introduction

2.1 This manual


This manual describes how to supervise and control the power process with the SYS600
Monitor Pro user interface. The supervision and control is done by means of Process
Displays, event/alarm displays, trends, measurement reports and so on. The manual also
describes the basic customizing possibilities of the user interface.

2.2 Use of symbols


This publication includes warning, caution and information symbols where appropriate
to point out safety-related or other important information. It also includes tips to point
out useful hints to the reader. The corresponding symbols should be interpreted as follows:

Warning icon indicates the presence of a hazard which could


! result in personal injury.

Caution icon indicates important information or a warning


related to the concept discussed in the text. It might indicate
the presence of a hazard, which could result in corruption of
software or damage to equipment/property.

Information icon alerts the reader to relevant factors and


conditions.

Tip icon indicates advice on, for example, how to design a


project or how to use a certain function.

Although warning hazards are related to personal injury, and caution hazards are
associated with equipment or property damage, it should be understood that operation
of damaged equipment could, under certain operational conditions, result in degraded
process performance leading to personal injury or death. Therefore, comply fully with
all warnings and caution notices.

2.3 Intended audience


This manual is intended for installation personnel, administrators and skilled operators
to support installation of the software.

9
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

2.4 Related documents


Name of the manual Document ID
DMS600 4.4 Operation Manual 1MRS757319
SYS600 9.4 Application Design 1MRS758122
SYS600 9.4 Process Display Design 1MRS758088
SYS600 9.4 Installation and Administration Manual 1MRS758086

2.5 Document conventions


The following conventions are used for the presentation of material:
• The words in names of screen elements (for example, the title in the title bar of a
dialog, the label for a field of a dialog box) are initially capitalized.
• Capital letters are used for file names.
• Capital letters are used for the name of a keyboard key if it is labeled on the keyboard.
For example, press the CTRL key. Although the Enter and Shift keys are not labeled
they are written in capital letters, e.g. press ENTER.
• Lowercase letters are used for the name of a keyboard key that is not labeled on the
keyboard. For example, the space bar, comma key and so on.
• Press CTRL+C indicates that the user must hold down the CTRL key while pressing
the C key (in this case, to copy a selected object).
• Press ALT E C indicates that the user presses and releases each key in sequence (in
this case, to copy a selected object).
• The names of push and toggle buttons are boldfaced. For example, click OK.
• The names of menus and menu items are boldfaced. For example, the File menu.
- The following convention is used for menu operations: Menu Name > Menu
Item > Cascaded Menu Item. For example: select File > Open > New Project.
- The Start menu name always refers to the Start menu on the Windows Task
Bar.
• System prompts/messages and user responses/input are shown in the Courier font.
For example, if the user enters a value that is out of range, the following message
is displayed: Entered value is not valid.
The user may be told to enter the string MIF349 in a field. The string is shown as
follows in the procedure: MIF349
• Variables are shown using lowercase letters: sequence name

2.6 Document revisions


Version Software revision Date History
number
A 9.4 16.5.2014 New document
B 9.4 FP1 3.6.2015 Document updated

10
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

3 Overview

This chapter introduces the SYS600 user interface functions. All application areas and
functions described in this manual are not necessarily covered by every customer's
application. Likewise, this manual may not describe every application functionalty a
customer may have, because the functionality of individual applications is designed
according to the needs of each customer.

3.1 Getting started


Start a Monitor Pro session by launching the SYS600 Monitor Pro program. The Login
dialog is displayed when Monitor Pro is started, see Figure 3.1.

Figure 3.1: Monitor Pro login dialog

Clicking Close in the Login dialog closes the Login dialog, but leaves the Monitor Pro
still running.

3.1.1 Login

To login, select an application from the Application drop-down list or click on the Process
Display view if Monitor Pro is running. Type the user name and password into the
corresponding fields and click Login.
Each user is associated with a certain user profile defined by the system manager. For
more information, see SYS600 Application Design.

11
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

If the user name and the password do not match or the user name does not exist, the
Login dialog is displayed again and login may be attempted again. Each attempt to login
is registered by the system, even those that fail.
If login is successful, the first display is shown on the screen (if one has been defined in
the Application Settings dialog). All the operations subsequently performed on the
Monitor Pro are related to the authority profile associated with the user name. The user
name is also included as an identifier in the event register when certain manual operations
are performed.

In order to prevent unauthorized usage of a user name and


authority profile, always logout when leaving the control room.

3.1.2 Logout

In Monitor Pro, logout means that the current user name and user authority are cleared.
The options for logout are:
• Selecting Main > Logout.
• Closing the Monitor Pro by selecting Main > Exit.
• Automatic time based logout executed by Monitor Pro.
• Changinh the SYS600 application state from HOT to WARM or COLD.
• The SYS600 OPC DA server or service is stopped.

3.1.3 Time based logout

An automatic logout is done after a certain time period (for example 8 hours). The logout
duration is defined in the User Account Management tool. The values are application
specific. After time based logout, the user must login again via the Login dialog.

3.1.4 Time-based logout after inactivity

Users with appropriate permissions can set a timeout threshold for idle sessions. If there
is no interaction between the user and the product on application level (no user activity
or commands) for the configured time, the session is discarded and the user must
re-authenticate before the next interaction.
Logout duration after inactivity can be configured in the User Account Management
tool.

12
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 3.2: The User Account Management timeouts tab

The same definitions are available for logout duration after inactivity as for logout
duration (notify messages/closing Monitor Pro when logout occurs).

3.2 Application displays


There are many different types of application displays: Process Displays, System
Supervision Displays, Alarm Display, Event and Blocking Displays, Measurement
Reports Display and Trends Displays. Figure 3.3 illustrates an example of application
display.

13
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 3.3: Example of Trends display

3.3 Process Displays


The Process Displays contain information on objects with dynamic behavior on the
system process in graphical form, see Figure 3.4. Process Displays contain functions for
zooming, panning and de-cluttering displays.
The display name, the application's name and number as well as the login user are
presented on the title bar of the Process Display.

14
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 3.4: Station Process Display

3.3.1 Controlling the process

Figure 3.4 is an example of a station Process Display in a single line diagram form. The
power processes can generally be shown in the Process Display in different presentations.
The presentation to be used is selected when the Process Displays are configured. For
more information about the colors used in Process Display, see Section 4.10 Color Setting
Tool and Section 4.11 Network topology coloring.
The primary devices can be interacted through the control dialogs accessed from the
Process Display, see Figure 3.5. Only users in certain user groups are allowed to execute
control operations.

15
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 3.5: Main display of a Control dialog

The user can switch between the main view and the advanced
view by clicking the >> and << buttons in the upper right hand
corner of a Control dialog.

3.3.2 Adding Process Display Notes

A Process Display Note can be added to a Process Display to point out important
information, for example a line that is under construction. The Process Display Note
comments can be freely edited (i.e. added, deleted, moved) without it affecting the actual
process.
To add a Process Display Note, select Tools > Notes and select the color for the comment.
The colors should be used according to the importance of the comment.

16
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 3.6: Process Display Note

The available colors are:


• Symbol 1 (Yellow)
• Symbol 2 (Red)
• Symbol 3 (Green)
• Symbol 4 (Magenta)
• Symbol 5 (Cyan)
To change the color of the Process Display Note, click Color in the Process Display
Note dialog. The Process Display Note Color dialog opens, see Figure 3.7. Select a color
for the Process Display Note and click OK.

Figure 3.7: Changing the Process Display Note color

17
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

The Process Display Note object is created on the center of the visible display. It can be
moved into the right place with the mouse.
To write a comment:
1. Click the Process Display Note object. A Process Display Note dialog is displayed.
2. Type a comment to the Note box.
3. Click OK.

Deleting Process Display Note


Delete a Process Display Note object by opening the Process Display Note dialog and
selecting Delete. Monitor Pro confirms the operation by displaying a warning dialog.
The comment information is removed and the Process Display Note object is deleted
from the display.

Moving Process Display Note


Move the Process Display Note by dragging it with the mouse.

Resizing Process Display Note


Resize Process Display Notes by holding down the right mouse button and moving the
cursor up or down. Moving up the cursor increases the Process Display Note and moving
down decreases the Process Display Note.

Adding Process Display Note links


Create links to files on the server or on a local computer by selecting Links from the
Process Display Note dialog. A Process Display Note Links dialog is displayed.

18
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 3.8: Process Display Note Links

Add new links by browsing the file should be linked to the comment. Click Open to
open the linked file. For example, if the linked file is a .txt file, it is opened from the
Process Display Note Links dialog in Windows Notepad.
Remove the links by selecting the corresponding link and clicking Remove....

3.3.3 Adding a comment to an object

A comment can be written for an object, for example a circuit breaker. The comment is
displayed for all users who open the control dialog of the same object. The comment is
independent of the display file where the object is presented. User name and edit time
are also stored for the comment.
If a comment has been added to an object, it is displayed when the control dialog is
opened, see Figure 3.9.

19
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 3.9: Comment in the control dialog

To add a comment:
1. Click the information symbol ( ) in the control dialog to open the dialog, see
Figure 3.10.

Figure 3.10: Adding comment to control dialog

2. Write the comment.


3. Click OK.

20
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

3.3.4 Renaming Process Display

A Process Display can be renamed through the Customize dialog:


1. From the main menu, select Settings > Customize to open the Customize dialog.
2. Right-click the Process Display name.
3. Select Name and enter a new name for the Process Display Figure 3.11.

Figure 3.11: Renaming the Process Display

The Customize dialog can also be opened by right-clicking the Process Display name,
and selecting Customize from the context menu.

3.4 Monitor Pro layout


Default Monitor Pro layout contains the following components:
1. Process Display name, application number, application name, user name
2. Main menu bar
3. View Info
4. Latest unacknowledged alarms
5. Shortcut to displays
6. Network Topology Coloring toolbar
7. Process Displays

21
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

8. Application display area


9. Status bar
10. Customization tool
11. Handle for moving toolbars

Figure 3.12: Monitor Pro default layout after the login

3.4.1 Specifying toolbars

Toolbars can be added and removed by right-clicking the existing toolbar, docking area
or standard menu, and selecting or clearing the checked commands from the context
menu.
By default, Monitor Pro has just a small set of visible prebuilt toolbars. Each user can
modify the layout of Monitor Pro to correspond to their requirements. The layout
modifications are saved at logout. At the next login, the user's default layout is loaded
in the application. By default, Monitor Pro loads and hides some of the toolbars and
menus depending on the current display. For example, if the Event Display is displayed,
both the Event Display menu and Event Display toolbars are loaded.

22
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Toolbar visibility and position are display specific. For example, if the user moves the
alarm row to a certain position in Process Display, it will not affect the alarm row position
in Event Display.

Reset Toolbars Resets the toolbar positions. User-specific


customizations are not lost. Shortcut key:
CTRL+ALT+SHIFT+T.

3.4.2 Changing application layout

Display the Customize dialog by double-clicking any empty space on the toolbar area
of Monitor Pro. The little arrows in the toolbars can also be used to customize toolbars,
commands or options. The Customize dialog can also be selected in Settings > Customize
(see Figure 3.13).
The Customize dialog can be used to:
• Add, reset, rename and delete custom toolbars. Old menu items can be deleted and
renamed, but new ones cannot be added. Some menu items (for example the ones
in Process Display menu) and some toolbars (for example the buttons in application
specific toolbar) are not customizable because their contents is dynamic. For example,
the contents of Process Display Toolbar are generated based on the files found in a
certain folder.
• Change the Command Context menu's caption and style. The Command Context
menu is another way to customize. It is displayed when the Customize dialog is
open and the toolbar is right-clicked. The styles can be changed to:
- Default Style: Contains both text and icon, if available
- Text Only: Only text (caption of tool) is shown
- Image Only: Only the icon is displayed, if available
- Image and Text: Contains both text and icon, if available
• Categorize the action tools and drag-and-drop commands to any toolbar, menu or
submenu.
• Change the icon size in Monitor Pro.
• Create keyboard shortcuts.

23
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 3.13: Command context menu while the Customize dialog is open.

When the Customize dialog is open, the toolbar buttons and menu items can be moved
around. If the CTRL key is held down while moving the tool, the tool is copied.
The last button on the right of each toolbar is a little arrow button. This quick
customization shortcut allows the user to show or hide tools from the toolbar without
opening the Customize dialog (see Figure 3.14).

24
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 3.14: Adding and removing tool

The buttons can also be moved between toolbars without opening the Customize dialog.
This can be done by holding down the ALT key and dragging the buttons to another
location. Buttons can be deleted by dragging them away from the toolbar. Pressing
CTRL+ALT while moving the button copies the button. This function is not possible
for menu items without the Customize dialog.
All the toolbars and menus can be shown or hidden without the Customize dialog by
right-clicking the main menu bar and selecting or deselecting the toolbars (see
Figure 3.15). The user has access to different toolbars according to the display in use
(see Table 3.1). For the Process Display, Alarm Display, Event Display, Blocking Display
or Trends Display and full screen mode there are different configurations depending on
which toolbars are shown.

25
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 3.15: Showing and hiding toolbars

Table 3.1: Toolbars according to different displays


Display Toolbars
Process Menu Bar
Alarm Row
Network Topology Coloring
Navigate
Zoom
Event Menu Bar
Alarm Row
Event Display
Navigate
Process Displays
Main
Alarm
Template 1 Menu Bar
Alarm Row
Alarm Display Template 1
Navigate
Process Displays
Main
Template 2 Menu Barr
Alarm Row
Alarm Display Template 2
Navigate
Process Displays
Main
Blocking Menu Bar
Alarm Row
Blocking Display
Navigate
Process Displays
Main
Trend

26
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Display Toolbars
Graphical View Menu Bar
Alarm Row
Trends Display
Trends Graphical Mode
Navigate
Process Displays
Zoom
Main
Tabular View Menu Bar
Alarm Row
Trends Display
Trends Tabular View
Navigate
Process Displays
Main
Measurement Reports
Graphical View Menu Bar
Alarm Row
Measurement Reports Display
Measurement Reports Graphical View
Navigate
Process Displays
Zoom
Main
Tabular View Menu Bar
Alarm Row
Measurement Reports Display
Measurement Reports Tabular View
Navigate
Process Displays
Main

To create a new toolbar:


1. Select New from the Customize dialog.
2. Type a new name for the toolbar.
3. Click OK. A new toolbar is shown in the Toolbars tab.

Figure 3.16: New Toolbar dialog

When the user selects a toolbar they have created, the Rename and Delete buttons
become active. The created toolbar can be renamed or deleted. Clicking the Undo button
loads the last saved layout.

27
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

By clicking Keyboard in the Toolbars tab a Keyboard dialog is displayed (see


Figure 3.17).

Figure 3.17: The Customize Keyboard dialog

New keyboard shortcuts can be added for menu items and toolbars seen in the Categories
section.
Categories:
• Built-in Menus: All the top-level menus
• Start with characters mi: All menus that have sub-menus
• Start with characters tb: All toolbars (except the user defined toolbars created with
Customize dialog)
Commands:
• Sub menu items and buttons of the selected category
To assign a new value to the tool (menu item, button in the toolbar):
1. In the Categories section, select the category in which the menu item or toolbar
buttons are located.
2. In the Commands section, select the command (menu item, buttons in the toolbar).
3. Click the New shortcut key box so that the mouse cursor blinks in it and press the
new shortcut key combination. The key combination is displayed in the box.
4. Click Assign, and the shortcut key appears in the Current Keys section.

28
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

The shortcut key can be deleted by clicking Remove.... Clicking Reset All resets the
shortcut keys.
In the Commands tab of the Customize dialog, categories and commands are the same
as in Toolbars tab (see Figure 3.18).

Figure 3.18: Commands tab of Customize dialog

The Commands can be moved around the same way as on the Toolbars tab. Clicking
Modify Selection corresponds to the function when a toolbar button or menu item is
right-clicked (when the Customize dialog is open) and a similar context menu is displayed.
The Modify Selection button becomes active when a tool is selected either from the
menu or from the toolbar.
Personalized menus can be selected into use in the Options tab (see Figure 3.19).

29
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 3.19: Option tab of Customize dialog

Only the most recently used menus are visible. The memory of the menu usage can be
cleared by clicking Reset usage data. Menu animations can be selected or the size of
icons changed in the Other field.

If another option than None is selected in the Menu


animations box, automatic menu command activations can
occur when the pointer is moved over the menus.

Alarm row
The Alarm row provides a quick notification of an alarming event in the system. The
advantage is that it can be noticed easily, and it also instantly tells the operator what has
happened and where. With the alarm row the alarms can easily be acknowledged. Display
the alarm row by selecting it on the Toolbar tab.

Figure 3.20: Alarm row

The alarm row shows all the unacknowledged active and inactive alarms in the system.
The latest alarm is shown on the top of the list. Any of the alarms shown on the list can
be selected to be acknowledged.

30
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

The user authorization level has to be at least Control (1) before alarms can be
acknowledged (the Alarm row uses authorization group ALARM_HANDLING). For
more information, see SYS600 Application Design.
On the Alarm row, active and inactive alarms are separated by showing the alarm text
in parentheses (Alarm) if the alarm is inactive. Thereafter, the date and time of the alarm
and the object text of the alarming object are presented.

Status bar
The Status bar shows the SYS600 version number, Base system Node Name, (system
name) and the current date and time.

3.4.3 Resetting Layout

To reset the layout, select Settings > Reset Layout. This action restores the layout from
either the previously saved layout or the installation default layout, see Figure 3.21.

Figure 3.21: The Layout Reset Confirmation dialog

3.5 Using process lists


There are three types of process lists:
• Alarm Display, presents the actual alarm state in the process data base.
• Event Display, presents all events reported to the system.
• Blocking Display, presents the blocking situation in the process data base. Some
typical blockings are alarm, event and control blocking.
These lists are all described in separate chapters, see Chapers Chapter 5 Event Display,
Chapter 6 Alarm Display and Chapter 7 Blocking Display.

31
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

3.6 Using reports and trends


Reports can be used for analyzing sampled measurements. Collected data can be presented
in a graphical or numerical form.
Typical reports are energy, currents, process disturbance reports (for example trippings,
earth-faults, overcurrents, auto-reclosures). These reports can be used for analyzing fault
situations, for improving service and maintenance, as well as for normal supervision.
Trends can be used for trend analyses and showing measured values in a graphical or
numerical form.
The reports and trends are described in separate chapters, see Chapter 10 Measurement
Reports and Chapter 9 Trends Display.

32
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

4 Process controlling

This chapter describes the generic control dialogs in SYS600 Power Process Library.
These dialogs provide fast and easy access to the device status and to the single devices
in a substation. The Control dialog combines different kinds of information, depending
on the object.
Control dialogs interact with standard objects created with Object Navigator by using
the Power Process Library (SA_LIB) standard functions. Control dialogs are generic
and they have the same user-interface appearance, independent on the IED and the
communication protocol defined in standard object configuration. The available
functionality and access rights for a user can be limited using authorization levels.

4.1 Navigating
The user can flexibly navigate between the Process Displays and within a Process Display.
Navigate between the different Process Displays by:
• selecting Main > Open
• clicking a shortcut on the Process Displays toolbar.
• clicking Go to Previous Display or Go to Next Display in the View Info toolbar.
• clicking elements in a Process Display.
When a certain element in a Process Display is clicked, a predefined area of a
different Process Display is shown.
• using menu commands and toolbar buttons.
Define the needed menu commands and toolbar buttons for navigating to a predefined
area of a different Process Display.
• locating an object in the Event, Alarm or Blocking display.
To locate the object, right-click on a selected line to open a shortcut menu and select
Locate object in Monitor Pro or Locate object in Monitor Pro - new window.
Navigate within displays by:
• using the Save/Restore Zoom dialog.
Use this dialog for zooming to predefined locations.
• clicking elements in a Process Display.
When a certain element in a Process Display is clicked, a predefined area of the
same Process Display is shown.
• using menu commands and toolbar buttons.
Define the needed menu commands and toolbar buttons for navigating to a predefined
area of the same Process Display.
• using the mouse to grab and pan the view by clicking Select Panning button on the
Zoom toolbar.
• using Flicks with touch screen.
By default with Back and Forward Flicks the navigation of Displays occurs. The
defaults can be changed in Windows Control Panel – Pen and Touch.

33
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

The Navigate menu shows 5 of the previously used displays (with a preconfiguration).
This information is stored to the user-specific ini-file and is available on next login.

4.2 Zooming
Zoom Monitor Pro by selecting Navigate > Zoom... The zooming options are displayed
as a submenu of the Zoom command, see Figure 4.1.

Figure 4.1: Zoom submenu

Table 4.1: Zoom commands


Command Shortcut key Description
Save/Restore - Opens the Save/Restore
Zoom Zoom dialog.
Normal size CTRL + ALT + space Zooms to the normal size.
Zoom Previous - Returns to the previous
Zoom level.
Zoom in Rotate the mouse wheel forward or press CTRL Zooms in.
and click the left mouse button.
Zooming in with touch screen is handled by en-
tering two fingers in contact with the screen at
the same time and moving fingers together along
an axis.

34
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Command Shortcut key Description


Zoom out Rotate the mouse wheel backward or press Zooms out.
CTRL + SHIFT and click the left mouse button.
Zooming out with touch screen is handled by
entering two fingers in contact with the screen at
the same time and moving fingers apart along
an axis.
Zoom to Selec- Press CTRL, click the left mouse button and se- Zooms in the selected area.
tion lect the zoom area.
Pan Click the mouse wheel and move the mouse. Moves the graphic with the
Panning in touch screen is handled by entering mouse.
one or two fingers in contact with the screen and
dragging while keeping the fingers in the same
position relative to each other.
Step Left Press arrow left key on the keyboard Moves the zoomed area to
the left.
Step Right Press arrow right key on the keyboard Moves the zoomed area to
the right.
Step Up Press arrow up key on the keyboard Moves the zoomed area up.
Step Down Press arrow down key on the keyboard Moves the zoomed area
down.

It is possible to save application and user specific zoom areas with the Save/Restore
Zoom dialog, see Figure 4.3. Open the Save/Restore Zoom dialog either by clicking
the icon in the Zoom tool bar, see Figure 4.2 or from the main tool bar, select Navigate
> Zoom > Save/Restore Zoom, see Figure 4.1.

Figure 4.2: Save/Restore Zoom icon

Open the Save/Restore Zoom dialog, enter a name for the zoom in the Save zoom field,
select either the Application or User radio button and click Save.
The user can also:
• create a new folder in the tree structure
• delete a folder in the tree structure
• rename items in the tree structure
• drag and drop items in the tree structure
• define filters for specific items to be displayed

35
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 4.3: Save / Restore Zoom dialog

The saved zoom can be seen in the Restore zoom field. The list of saved zooms can be
filtered using the All, Application and User radio buttons.
To restore a saved zoom, select the zoom name the Restore zoom field, and click Restore.
To delete a zoom, select the zoom name the Restore zoom field, and click Delete.
To save zoomed views for the current session, select the Temporary tab, at the top of
the Save/Restore Zoom dialog. All zooms saved here will be lost on closing the current
session.

36
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

4.3 Find
Objects within the display can be found and zoomed in on using the Find function on
the toolbar, see Figure 4.4.

Figure 4.4: Find tool

Searches can be made using the Object name, or part of it, the Logical name (LN) or
Index (IX). Select the required object from the search result and click Show to display.
To change the zoom level, select the value from Zoom level, then click Show to display
the object, see Figure 4.5.

Figure 4.5: Find process objects

37
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

4.4 Station Local/Remote control


The station control shows the operator location information of the substation, that is,
whether the control is authorized from the station locally or from an external control
center. The state can be set to Station or Remote in the Station L/R Switch dialog.

Figure 4.6: The Main tab of the Station Local/Remote switch dialog

The Main tab of the dialog shows the object name and the selection for operator location.
Select the operator location by selecting the right option button. The available options
depend on the object configuration. Unavailable options are dimmed.
Select the corresponding option for operator location (for example Remote). Close the
control dialog by clicking the Exit button.
The Messages tab (Figure 4.7) shows different messages concerning the object. A message
is shown, for example, if the object is simulated or the information of the physical
local/remote key position is unknown.

38
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 4.7: The Messages tab of the Station L/R switch dialog

Different blockings concerning the process object that belong to the station are shown
and controlled in the Blocking tab, see Figure 4.8.

Figure 4.8: The Blocking tab of the Station L/R switch dialog

After selection (multiple selections allowed), click Apply for making the changes. Click
Cancel to discard the changes made in this dialog. Click Refresh to update the blocking
status in case it has been changed elsewhere in the system.

39
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

The alarms are shown on the Alarms tab, see Figure 4.9. To acknowledge alarms click
Ack. All or Ack. selected. Click Refresh to update the alarm status.

Figure 4.9: The Alarms tab of the Station L/R switch dialog

The Update data tab is aimed for updating the database from the actual process within
the selected station, see Figure 4.10. The Update Process Data... button can be used to
initialize the substation after a system restart, or to verify database consistency.

Figure 4.10: The Update data tab of the Station L/R switch dialog

40
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

4.5 Bay Local/Remote control


The Bay L/R control shows the operator location information of a bay in a substation,
that is, whether the control is authorized from the bay unit locally or remotely over a
communication link (for example station HSI).
If the Bay L/R switch is remotely controllable, it is possible to change the switch state
from the control dialog.
The Main tab of the Bay L/R Switch dialog (Figure 4.11) shows the object name and the
selection for the operator location. Select the operator location by selecting the
corresponding option. The available options depend on the object configuration,
unavailable options are dimmed.
Select the corresponding option for operator location (for example Remote). Close the
control dialog by clicking Exit.

Figure 4.11: The Main tab of the Bay L/R switch dialog

In Operator place tab (Figure 4.12) it is possible to set the authorized control location
for each bay separately.
For operator place handling the are two different principles
1. MicroSCADA Internal model
2. IEC 61850 model

MicroSCADa Internal model


The operator place switch has meaning, if the IED L/R switch is in remote position. In
this case the operator place can be the following

41
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

• None, control is prevented both from Station and NCC


• Station, control is allowed from station level if system is defined as Substation
Control System (SCS).
• Remote, control is allowed from remote level if system is defined as Network Control
Center (NCC).
• Station/Remote control is allowed both from SCS and NCC
System location (SCS/NCC) is defined in Application Settings Dialog. If process object
for Operator place switch does not exist in process database, this tab is not shown.

Figure 4.12: The Operator place tab of the Bay L/R switch dialog

IEC 61850 model


IEC 61850 model is the same for bay as for device level objects, like breaker. For more
information Section 4.6.9 Operator Place
The Messages tab shows the different messages concerning the selected object. A message
is shown, for example, if the object is simulated or the information of the physical
local/remote key position is unknown.
Different blockings concerning the process objects that belong to the bay are shown and
controlled in the Blocking tab, see Figure 4.13.

42
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 4.13: The Blocking tab of the Bay L/R switch dialog

After selection (multiple selection allowed) click Apply to make the changes. Click
Cancel to restore the changes made. Click Refresh to update the status of the blocking
in case it has been changed elsewhere in the system.
The alarms are shown on the Alarms tab, see Figure 4.14. To acknowledge alarms click
Ack. All or Ack. selected. Click Refresh to update the alarm status.

Figure 4.14: The Alarms tab of the Bay L/R switch dialog

43
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

The Update Data tab is aimed for updating the database from the actual process within
the selected bay.

Figure 4.15: The Update data tab of the Bay L/R switch dialog

4.6 Switch control


Switch Control dialog can be used to show current state and status of a switch device
object. It is also used for operating the switch device. Open the Switch Control dialog
by clicking the objects. The same dialog operates with breakers, disconnectors and
earthing disconnectors. The available functions are based on the configuration definition
of the corresponding Power Process Library standard object.
There are several tab pages on this dialog. The object identification (station, bay and the
object) are located above the tab pages. The tab pages in the Switch Control dialog are
divided into the main display and the advanced display. In the main display, it is only
possible to open and close the switch. Open the advanced display by clicking the >>
button in the upper right corner of the Switch Control dialog.
Object status is shown on the Main tab. The object status can be, for example,
authorization, blocking information and reservation information, as well as potential
problems on the communication link acquiring the correct status. Possible errors during
the operation appear in the Object Status field of the Main tab. Close the dialog by
clicking Exit, pressing ESC key on keyboard or clicking the button on the upper-right
corner of the dialog.

44
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 4.16: The Main tab of the Switch control dialog

If the switch device is opened or closed, the text "Object is selected for operation" is
displayed in the Object Status field and the program asks the user to verify the control
operation. In case of an error in selection, the error message is shown in the Object Status
field.
If controlling is possible, the Open Disconnector or Close Disconnector buttons are
active. Note that once the selection of the control command is done, it may include
several steps on the process to be controlled (for example interlocking conditions are
checked). These depend on the actual configuration of the process devices.
In the advanced display, there are tabbed pages for blockings, forced operation, simulation,
alarms and operation counters.

4.6.1 Blockings

In the Blocking tab of the Switch Control dialog (Figure 4.17), the different blockings
concerning the process objects that hold information about switch state are shown and
controlled. After selection (multiple selection allowed), click Apply to make the changes.
Clicking Cancel discards the made changes. To update the status of the blocking (in
case it has been changed elsewhere in the system), click Refresh.

45
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 4.17: The Blocking tab of the Switch Control dialog

4.6.2 Forced operations

On Forced operation tab (Figure 4.18), the internal blockings of SYS600 and Power
Process Library control blockings can be bypassed. The user can force objects to operate
on their command even if another user is connected to them or the function is normally
not permitted. However, this does not disable any interlockings or other IED measures,
that is, no special bypass messages are sent to the IEDs.

46
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 4.18: The Forced operation tab of the Switch Control dialog

If an object is selected on another display or it is under command and the user wants to
have the control, click Release device reservation. When this is done, Control dialogs
disappear from other operators. Releasing of command reservation is possible only if
the process object for switch device command event is simulated in the MicroSCADA
process database.
Open Disconnector and Close Disconnector buttons may be inactive for various reasons,
for example, the switch is in the middle position. The Forced open/close control button
can be used for enabling the buttons for actual control. In this case the controlling is as
normal control without bypassing options.
There are two different device level overrides available in the control dialog. When the
controlling is done with interlocking bypass/synchrocheck bypass option, the bypass
command is sent/and handled in actual IED.

The interlocking and synchrocheck bypass functions can only


be used with IEC 61850 protocol.

If the switch device is interlocked or synchrocheck inhibits the control, select the
corresponding check box and control the switch device in a normal way with the Open
Disconnector and Close Disconnector buttons. The Event Display shows that controlling
was done with the bypass option.
The following table presents the control type for the switch device:

47
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Table 4.2: ABBCommandBitmask


Name Type Value/Value M/O/C OPC Data Type
range
NormalControl 1bit FALSE (0) I TRUE M 0
NormalControl: true = (1)
normal operation, false
= inverse operation (for
example On/Off)

InterlockOverride 1bit FALSE (0) I TRUE M 1


InterlockOverride: true (1)
= interlockcheck > false

Synchrocheck- 1bit FALSE (0) I TRUE M 2


Override (1)
SychrocheckOverride:
true = syncrocheck >
false

TestCommand 1bit FALSE (0) I TRUE M 3


TestCommand: true = (1)
test command

Originator Originator: 4bit not-supported (0) M 4-7


Command originator (= I bay-control (1) I
Originator.orCat) station-control (2)
I remote-control
(3) I automatic-
bay (4) I automat-
ic-station (5) I
automatic-remote
(6) I maintenance
(7) I process (8)
ControlValue nbit M 8-31

1. NormalControl: true = normal operation, false = inverse operation (for example


On/Off)
2. InterlockOverride: true = interlockcheck > false
3. SychrocheckOverride: true = syncrocheck > false
4. TestCommand: true = test command
5. Originator: Command originator (= Originator.orCat)

48
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

4.6.3 Simulation

The state of the switch object can be simulated on the Simulation tab (Figure 4.19). The
state is then indicated on Process Displays with blue color and appropriate messages on
control dialogs. Simulation cannot be deactivated if there is no process communication
for the corresponding process object.

Figure 4.19: Simulation tab of the Switch Control dialog

After the selection, click Apply to apply the changes. Clicking Cancel discards the made
changes. By clicking Refresh, the status of the simulation is updated in case it has been
changed elsewhere in the system.

49
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

4.6.4 Alarms

The alarms are shown on the Alarms tab (Figure 4.20). To acknowledge alarms click
Ack. All or Ack. selected. Click Refresh to update the alarm status.

Figure 4.20: The Alarms tab of the Switch Control dialog

50
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

4.6.5 Auto-reclose

In case auto-reclose function is configured for the switch object, the messages from the
function is shown in the Object Status box of the Reclosing tab (Figure 4.21). Interrupt
an ongoing sequence by clicking Interrupt AR sequence. This button is dimmed if the
corresponding function is not available.

Figure 4.21: The Reclosing tab of the Switch Control dialog

51
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

4.6.6 Operation counters

When the switch is closed with the Close Disconnector button in the Switch Control
dialog, the number in the Operation counter value field is incremented.

Figure 4.22: The Operation counters tab of the Switch Control dialog

When the operation counter value reaches the limit defined in the Operation counter
limit field, a message "Operation counter limit reached" is displayed on the Operation
counters tabbed page.

52
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 4.23: The Operation counter limit reached

To reset the operation counter value, click the Reset button next to the Operation counter
value field. To reset the operation counter limit value, click the Set button next to the
Operation counter limit field and enter a new value.
To switch off the operation counter, clear the Operation counter in use check box.
When the operation counter is not in use, the counter value is not increased when the
switch device is closed.

53
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

4.6.7 Dial-up

If a switch device is connected to the system via an autocaller line (a modem with
functions for automatic dial-up), Control dialog detects this configuration. When the
Control dialog is opened, the autocaller state is displayed in the Object Status field of
the Dial up tab. Autocaller can have the following states:
• IDLE: ready to make a call
• CONNECTED: transmission is activated
• BUSY: for example dialling
• INITIAL: uninitialized
• CONFIGURE: the IU attribute of the line is set to 0

Figure 4.24: The Dial up tab

If the autocaller state is idle, the Dial up tab is automatically displayed. Depending on
the configuration, the following options are available in the Dial up tab:
• Dial opens the connection to the device. When making a call to the device, the
Object Status field indicates the progress of the call with the autocaller state and a
raising counter.

54
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 4.25: The Autocaller state is busy

When the object is configured so that Synchronize and/or Update Data commands are
automatically send to the device, it is also shown in the status field.

Figure 4.26: The Synchronize command is sent to the device

Figure 4.27: The Update Data command is sent to the device

Control buttons are available after the connections are ready:

55
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 4.28: The autocaller state is connected

• Hang Up closes the connection.


• Synchronize sends the time synchronization command to the device. An object can
be configured so that the Synchronize command is automatically sent to the device
when the connection is ready.
• Update Data updates the process data from the device. An object can be configured
so that Update Data command is automatically sent to the device when the connection
is ready.
• Settings opens the Dial-up settings dialog.

Dial-up settings

Figure 4.29: Dial-up settings

The Settings dialog can be opened if an object is not yet configured for dial-up and/or
the user has engineering privileges for process control.
The Settings dialog has the following options:

56
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

• Automatically call: automatically opens the connection when the control dialog is
opened.
• Automatically synchronize: automatically sends the time synchronization command
when the connection is ready.
• Automatically update data: automatically sends the update process data command
when the connection (and time synchronization) is ready.
• Automatically Hang up: automatically closes the connection when the control
dialog is closed.

The indication process object has to be connected to process


(UN>0, OA>0), in order to have the Dial-up functionality in
the Control dialog.

4.6.8 Tagout

If the Tagout function is configured for the switch device, the status of the function is
shown in the Tagout tab (Figure 4.30).
The Tagout tab position depends on the active Tagout class. If the class contains also
the blocking functionality, the Blocking tab will be replaced with the Tagout tab. If the
active Tagout class does not contain the blocking functionality, the Tagout tab appears
last in the dialog Figure 4.31.

Figure 4.30: The Tagout tab with blockings of the Switch Control dialog

57
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 4.31: The Tagout tab without blockings of the Switch Control dialog

The properties and the view of the Tagout tab can be adjusted with the Tagout Class
Editor.
To add a tagout, click Add. The Add/Edit Tagout dialog opens.

Figure 4.32: The Add/Edit Tagout dialog

The Add/Edit Tagout dialog contains several tabs. The title and the position of the tabs
can be adjusted with the Tagout Class Editor.

58
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Only the owner of the tagout can edit and remove active
tagouts.

To remove a tagout:
1. Select a tagout from the list of active tagouts
2. Click Remove...
3. The Remove Tagout confirmation dialog opens

Figure 4.33: The Remove Tagout confirmation dialog

To edit a tagout:
1. Select a tagout from the list of active tagouts
2. Click Edit or double-click the tagout
3. The Add/Edit Tagout dialog opens

59
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 4.34: The Add/Edit Tagout dialog

4.6.9 Operator Place

When the operator place checking is configured to an object, The Operator Place tab
indicating the current state switches appears.

Multilevel switching authority allows control


Indication only. When this option is enabled, both Station level and NCC level are
authorized operator places for the object

Device Level Control


Indication only. The state of the device level L/R switch. Local means that control
authority is in the front panel of the device. Remote means that control can be done via
remote communication.

System Level Control


This option is enabled if Device Level control is in Remote position. The control authority
of the device can be switched between Station and NCC

60
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 4.35: The Operator Place tab of the Switch Control Dialog

The view in the Operator Place tab is dynamic depending on


the object configuration. If the indication does not exist in the
process database, also the functionality is hidden in the tab.

4.7 Transformer voltage control


Tap changer control dialog shows the current state of the transformer voltage controller,
and can be used for operating it as well. The available functions are based on the
configuration definition of the corresponding Power Process Library standard object.
The identification information (station, bay, object) is shown in the box on the Main tab,
see (Figure 4.36). Set the control operation mode by clicking the corresponding option
under the Operation mode. The options are available depending on object configuration,
the unavailable options are dimmed. Confirm the selection by clicking the Execute
button. Cancel the selection by clicking Cancel. The symbol buttons are presented in
the beginning of Chapter 4 Process controlling.

61
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 4.36: The Main tab of the Tap changer control dialog

Voltage or tap positions can be controlled if the configuration and status allow it. Control
the voltage and tap values by using the Lower and Raise buttons. In the Main tab, the
current tap position and voltage values can be set as well.
To set Reference voltage:
1. Click Set and the Reference voltage setting dialog opens
2. Type a new value in kilovolts to the New reference voltage box
3. Click OK

Figure 4.37: The Reference voltage setting dialog

The unit changes dynamically according to the unit defined in the ST attribute of the
reference voltage process object.
Reference voltage setting requires the following:
• Process object to set reference voltage value (command object)
• Process object for indication of reference voltage
• User interface support for setting the reference value
To set Tap value:

62
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

1. Click Set and the Tap value setting dialog opens

Figure 4.38: The Tap value setting dialog

2. Type a new value in kilovolts to the Tap value settings box


3. Click OK
Tap value setting requires the following:
• Process object to set reference tap value (command object).
• Process object for indication of tap value.
• User interface support for setting the tap value. This can be implemented in control
dialog by adding a text box where numerical tap value can be written.
The Set is not visible if numerical command object does not exist.
The Messages tab shows different messages concerning the object, for example if the
object is simulated, or the information of the voltage controller is unknown.
On the Operation tab the operation mode can be selected (Figure 4.39).

Figure 4.39: The Operation mode tab of the Tap changer control dialog

63
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Different blockings concerning the process objects holding information about the voltage
controller are shown and controlled in Blocking tab (Figure 4.40). After selection (multiple
selections allowed), click OK to apply the changes. Clicking Cancel discards the made
changes. Click Refresh to update the status of the blocking in case it has been changed
elsewhere in the system.

Figure 4.40: The Blocking tab of the Tap changer control dialog

If an object is selected on the current or on another monitor, clicking Release device


reservation resets the selection and the user has the authority for controlling the object.

64
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 4.41: The Forced operation tab of the Tap changer control dialog

When a control operation, that is a change the tap position either with Raise or Lower
buttons is made in the Tap changer control dialog box, or with direct setting of the tap
value with the Set button in the Switch Control dialog box, the number in the Operation
counter value field is incremented.
The Operation counter value field can be found in the Operation counters tab of the Tap
changer control dialog box.

65
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 4.42: The Operation counters tab of the Tap changer control dialog

When the operation counter value reaches the limit defined in the Operation counter
limit field, a message Operation counter limit reached is displayed on the Operation
counters tab.

Figure 4.43: Operation counter limit reached

66
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

To reset the operation counter value, click the Reset button next to the Operation counter
value field. To reset the operation counter limit value, click the Set button next to the
Operation counter limit field and enter a new value.
To switch off the operation counter, clear the check box Operation counter in use. When
the operation counter is not in use, the counter value is not increased when the tap value
is changed.

4.8 Measurement control


View the measured values in numeric and bar graph presentations in the Measurement
dialog. The values and bar graphs are colored based on the state and status of the measured
signal.

Show and hide the bar graph presentation by clicking the button in the Measurement
dialog (Figure 4.44).
Open the advanced display by clicking the >> button in the upper right corner of the
Measurement dialog. The number of shown measurands depends on the configuration
of the measurement object (Figure 4.45).

Figure 4.44: Normal display with bar graphs

In the Measurement dialog the following can be monitored:


• 1 to 4 measurement values including measured values and unit information
• 1 to 4 state and/or status indicators (text and coloring)

67
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

• 1 to 4 alarm acknowledgement buttons (blinking button, visible if the measurement


has an unacknowledged alarm, confirmation dialog for acknowledgement of the
alarm)
• 1 to 4 optional bar graphs (The bar graph is not shown, if a measurement does not
have alarm or warning limits, for example, it is a pulse counter)
• The advanced display includes tabbed pages for measured values, limits, zero
deadband supervision, blocking, object messages and alarms.
If the information on the tab is related to only one measurand, the option buttons to select
the measurand become visible (Figure 4.45). Otherwise the option buttons are hidden.
The different colors on the dialog are based on definitions made for the used color scheme.
The reserved space for the maximum value of the bar graph is high alarm limit + 10%
of the difference between high and low alarm limits. The reserved space for the minimum
value of the bar graph is low alarm limit - 10% of the difference between high and low
alarm limits. If the measured value is above high alarm limit or below low alarm limit,
the 10% space reservation is added to or subtracted from the measured value.
If the limit supervision is handled by IED or if the limit supervision is not in use (all
alarm and warning limits have been set to same value), the bar graph does not display
limit lines.
In the Measured Values tab of the Measurement dialog it is possible to:
• See the selected measured value and timestamp
• Reset the min value and timestamp
• Reset the max value and timestamp
• Reset the frozen value and timestamp
• Simulate a value
• Check that the simulated value is valid

68
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 4.45: Advanced display with measured value and simulation

The simulated value entered is validated at first. If the simulated value is not valid, the
Value box is displayed in red color (Figure 4.46).

Figure 4.46: Invalid simulated value

On the Limits tab it is possible to:


• Set the high and low alarm and warning limit values. The maximum and minimum
values are calculated like in the bar graphs (the limits cannot be set, for example,
for pulse counters).
• Copy and paste the limit values by right-clicking on the limits frame.
A warning message will be shown if the limits in the process have been changed during
the edition of the new limits in the Measurement dialog.

69
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 4.47: The Limits tab of the Measurement dialog

The limit values entered are validated at first. If, for example, the high warning limit is
bigger than the high alarm limit, the inappropriate limits are shown in red color (see
Figure 4.48).

Figure 4.48: Inappropriate limits

70
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

If a limit is not a number, the invalid limit is shown in red color (see Figure 4.49).

Figure 4.49: Invalid limit value

The zero deadband supervision can be set on the Deadband tab.


A warning message is shown if the deadband value in the process is changed during the
edition of the new setting value in the Measurement dialog.

71
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 4.50: The Deadband tab of the Measurement dialog

The deadband limit value entered is validated at first. If an invalid deadband value is set,
the invalid limit is shown in red color (see Figure 4.51).

Figure 4.51: Invalid deadband setting value

On the Blocking tab the measurements can be blocked.

72
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 4.52: The Blocking tab of the Measurement dialog

The condition of the Blocking check box shows its status:


• checked, respective measurements are blocked (Alarm in Figure 4.53).
• unchecked, respective measurements are not blocked, (Event, Printout and Action
in Figure 4.53).
• grayed out, some but not all measurements are blocked (Update in Figure 4.53).
• disabled, blocking cannot be applied to the function in question (Control in
Figure 4.53).

Figure 4.53: Example of condition on Blocking check boxes

When Apply to selected is checked, the blocking will affect only to the single
measurement selected by the radio button to the left of the dialog.

73
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

On the Messages tab the object messages of a selected measurand can be seen.

Figure 4.54: The Messages tab of the Measurement dialog

On the Alarms tab the alarms of the measurand can be seen.

Figure 4.55: Extended display with alarms

74
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

4.9 Alarm indicator control


The Alarm Indicator control is used to monitor the alarm state of input signals. The status
of each signal is indicated in the Alarm indicator control dialog shown in Figure 4.57.

Figure 4.56: The Alarm indicator control dialog

The Alarm indicator symbols and their meaning are explained in Table 4.3.
Table 4.3: Alarm indicators
Symbol Meaning
Not sampled or uncertain

Alarm, active unacknowledged

Alarm, fleeting unacknowledged

Alarm, active acknowledged

Substituted

Blocked

Manually entered

Normal

75
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

In addition to the symbols above, the alarm state is also shown in textual form. In the
Alarm state column, each signal can have the following explanation:
• Persisting
• Fleeting
• Acknowledged
• Not sampled
• Not alarming
Different blockings concerning the process object that belong to the alarm indicator are
shown and controlled in the Blocking tab, seeFigure 4.57.

Figure 4.57: The Alarm indicator control dialog, the Blocking tab

The blocking can be done to either all signals or to one signal only. To block all signals
related to alarm indicator, select Blockings and click Apply.
In order to block only one signal, select the signal from the list, check
"Apply to selected" and click Apply.

76
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

4.10 Color Setting Tool


Color Setting Tool is used to change the RGB values of logical colors. The tool contains
tabs for status colors, network topology colors and miscellaneous colors, which are
related to the Process display. There are also dedicated tab sheets for the rest of the
displays (Alarm / Event / Blocking / Trends / Measurement Reports display).

Figure 4.58: Color Setting Tool

77
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

4.11 Network topology coloring


The network topology coloring in SYS600 Monitor Pro can be used to indicate the status
of line segments in several different ways. It can indicate which line segments are
powered, unpowered or in certain other states, or more accurately which voltage level
each line segment has. Alternatively, each voltage source type can have a color that is
used for line segments they are connected to. Network topology coloring may also be
used to indicate situations where two or more voltage sources form a loop.
To define the network topology coloring settings, select Settings > Network Topology
Coloring... The Network Topology coloring dialog is displayed in
Figure 4.59 shows how the network topology coloring settings can be used in the current
monitor. Save the settings to be used as default by clicking OK. Restore the factory
settings by clicking Factory defaults.
When the coloring is disabled, static coloring is used for line segments. When Use status
colors setting is enabled, objects are colored using only their status color.
The user can also specify what kind of color is to be used for the powered network
objects, for example, line segments and switching devices. There are three modes:
• One color mode
• Voltage level mode
• Voltage source mode
One color mode uses the same color for all powered network objects. In Voltage level
mode, the color is specified for the voltage source (generator, transformer, line indicator)
according to voltage level. In Voltage source mode, the same color is used for all network
objects that are fed by some voltage source type.
Different voltage source types can be prioritized in the Colors tab. The colors used for
the voltage levels and voltage source types can be set using the Color Setting Tool.
There are two modes to color sources (line indicators). In Adjacent line segment color,
the color is taken from the line segment connected to the source. External color handling
uses a color from some external origin, for example DMS 600.

78
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 4.59: Network Topology Coloring Settings dialog

The priority of the voltage source colors can be ordered with the Colors tab. The device
of the highest priority is on top of the list. To change the priority order, select a device
from the list and click the arrow buttons on the right to change the order. Priority setting
is only applicable if the user has selected to color powered line segments according to
voltage source type in Coloring modes tab.

79
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

5 Event Display

With the Event Display, the information about events occurring in the system can be
monitored. Thus, the user can make the right decisions and verify that taken measures
have been successfully performed. The user can also receive information about activities
carried out by other users, operations of objects, acknowledging of alarms, editing of
limit values, logging in, and all other type of events which can occur.

Figure 5.1: Event Display main view

The Event Display presents the data in a structured way for the user's convenience. Each
event is one row in the display. With default settings, Event Display rows consist of a
time stamp, object identification, a signal text and a text indicating the status.
The Event Display contains the following features and options:
• Configurable layout: columns, fonts, toolbars, coloring, and so on
• Configurable coloring of events
• Configurable modes: log/event order, latest at top/bottom

81
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

• Updating/Frozen modes
• Easy navigation through scrolling, go to date, time filters, and so on
• Extensive filtering that can be stored and easily called up later
• Find
• Sorting by column
• Copy/Paste of events to other applications
• Printouts
• Commenting of events
The event activation and consequential actions are defined in the process database
separately for each individual object.
Typical examples on events are:
• Changes in or updating of an object value
• Changes of an alarm and a warning state
• Changes of the alarm definition, alarm blocking, acknowledgement, and so on
When an event occurs in the system, the operator wants to receive an answer to the
following questions (answers provided below each question):
1. What happened?
• A change in the state of the object or an executed operation.
2. Where did it happen?
• A descriptive text (object identification, OI and object text, OX) comprising
of, for example, a device notation and the type of object or operation.
3. When did it happen?
• The point of time when the event occurred. If the event originates from a station
providing a time stamp, this time stamp will be used. Depending on the station,
the time is on a second or a millisecond level. In other cases, the time stamp is
the SYS600 system time with an accuracy of 10 milliseconds.
The following functions can be activated by an event:
• Automatic printout. Like alarms, events can cause automatic printouts on the event
and alarm printer.
• Activation in the report database, for example automatic control operations,
registration, report printout, and so on.
Depending on how crucial an object is, the following events in the object may activate
an event printout, a registration in the history buffer, or an activity in the report database
(from the least crucial to the most crucial object):
• No activation
• An alarm is activated and deactivated
• The alarm or warning state changes
• The object value changes
• The object value is updated, although it is not changed
There are two ways to access the Event Display: selecting Navigate > Event or by
clicking Event Display on the toolbar.

82
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

The Event menu contains the following commands:


Filters: Opens a Filter Settings dialog, where filters can be selected and edited.
Reset Filter: Resets filters.
Comment: Opens a Comments dialog, which is used for writing comments to
events.
Keep Updating: Sets the Event Display to the updating mode. When changing
to Event Display, the mode is by default set to updating mode, provided there is
a user logged in.
Stop Updating: Sets the Event Display to the frozen mode. When changing to
Event Display, the mode is by default set to frozen mode if no user is logged in.
Show Info Fields: Displays/hides the info fields.
Show Headers: Displays/hides the list headers.
Previous Event Set: Displays the list of previous events.
Next event set: Displays the list of next events.
Last Event: Displays the list of last events.
Select Day: Opens a Day select dialog.
Export: Exports the current view in CSV file format.
The toolbar is a shortcut that can be used in parallel with the drop-down menu.

Figure 5.2: Event Display toolbar

The buttons in the toolbar from left to right are:


• Show Filters
• Reset Filter
• Switch to Updating or Frozen Mode
• Go to Previous Event Set
• Go to Next Event Set
• Go to Last Event
• Go to Selected Day
The toolbar buttons can be added or removed in the same way as in applications in
general, see Section 3.4.2 Changing application layout.
If the Event Display is in updating mode, the list will be updated when a new event
occurs in the system. When the list is in frozen mode (non-updating), a message will be

83
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

displayed informing the user to proceed to the last events and to change the mode to the
updating mode.

5.1 Event Rows


With default settings an event row contains the following information:
• Status sign
• Time stamp
• Object identification
• Signal name
• Event text
The first column always shows the row number in the list. With default settings, the next
three columns are status columns. The Date and Time columns present the time stamp
of the event. The Station, Bay and Device columns present the Object Identifier (OI),
and the following column the Object Text (OX). The Event Text (MX) column present
the event message information.
It is also possible to use only one column to show the object identification. In that case
station, bay and device names are shown in one column. The column is labeled as Object
Identifier.

Alarm symbol
The alarm symbol is the first status column shown in the beginning of the event row. If
the object is alarming, the symbol * is displayed.

Object status symbol


The second status column shows the signal status. If the object status differs from normal,
the status symbol is displayed as follows:
Table 5.1: Object status symbols
Status Color Symbol
Faulty value Magenta F
Obsolete value Red <
Faulty time Red T
Not sampled Magenta ?

Object comment symbol


The object comment symbol is the third status column shown in the beginning of the
event row. When a comment is added, the exclamation point (!) is displayed.

84
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

5.2 The Event Display User Interface


The information presented on the screen consists of several elements, which will be
described in the following section.

5.2.1 Using the Event Display User Interface

Sorting Rows
Rows can be sorted by clicking a column header. If the same column is clicked twice,
the sorting order is reversed.

Finding
Rows can be searched for using the Find function by going to Main > Find or by clicking

the icon.

The Find dialog box searches the list from start to end. If an event row contains the
desired text, it is selected. A message appears when the end point of the search has been
reached or when the searched text is not found.

Printing

List can be printed (Main > Print or the icon). The user can print either all rows,
selected rows, or a page range. The font size in the print is automatically adjusted so that
all the data fits into the page. If the text does not fit into the page, the rest of the columns
are printed to following pages.

Copying List Rows


Selected rows from the list can be copied. Rows are copied as tab separated values. Time
attributes are copied in standard format.

5.2.2 Using Filters

A list can be filtered. Only the rows that match the filter are shown.

85
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Filters are defined by selecting Filters from the menu bar. The Filter dialog contains
standard filters that can be selected by the user. The Filter dialog provides at least the
following standard filters: all events, event time, per substation, per bay and per device.
It is possible to change the existing filters or to add new filters that can be stored and
reused by other operators. The Filter dialog contains a specification form where new
filters can be created or the existing filters can be changed.

The filter can also be defined by right-clicking on a row in a


list, and by selecting Use as Filter. This uses a part of the rows
OI as the filter.

In Alarm Display and Event Display on the upper part of the Filter dialog, there are two
options that specify whether the Lower Time Limit or Upper Time Limit is used. If the
Lower Time Limit is not in use (off), the alarms or events will be presented from the
latest backwards. If the Upper Time Limit is not in use, the alarms or events will be
presented up to the latest. Only when a time limit is in use, the corresponding date and
time limits can be defined. Clicking the drop-down menu in the time limit field opens
the date selector, by which the time limit can be defined (Figure 5.3). Whether the Lower
Time Limit or Upper Time Limit is defined, the date selector opens the related time limit
below indicating which time limit is edited.

Figure 5.3: Edit Upper Time Limit

To save the active filter settings, select Preconfigurations... in the Filter Settings dialog.
The Preconfigurations dialog is opened, in which the name for the preconfiguration can

86
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

be defined. Define the location of the preconfiguration in the Visibility field. When
selecting the Application option, the preconfiguration becomes accessible for all the
users of the application, see Figure 5.4. Click Save to save the preconfiguration file.
Click Close to close the dialog without saving.

Figure 5.4: Visibility definition

To load preconfigured filter settings, select Preconfigurations... in the Filter Settings


dialog. Sort preconfigurations by name, visibility setting or modification time. When
clicking Open, the preconfiguration file is loaded and set as an active filter. Clicking
Close closes the dialog without opening any files. To activate the filter, click OK in the
main filter dialog.

5.2.3 Locating Signals

Right-click a line row to open a context menu. In this menu, Locate object in DMS ,
Locate object in Monitor Pro, or Locate object in Monitor Pro - new window can
be selected.

87
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 5.5: Locating object

Locate object in DMS displays the process point according to the logical node and the
index (LN and IX) attributes. This function is provided together with DMS 600. For
more information, see DMS 600 Operation Manual.
Locate object in Monitor Pro opens a Process Display and zooms into the symbol that
presents the same object that produced the row, and marks it with a highlighted symbol.
Locate object in Monitor Pro - new window opens a Process Display in a new window,
zooms into the symbol that presents the same object that produced the row, and marks
it with a highlighted symbol.

Figure 5.6: Highlighted symbol

5.2.4 Blocking Signals

Signal blocking states for each signal in the list can be viewed and modified. For more
information on blockings see Section 7.3 Handling Blockings.
Signal blocking state dialog is accessed through a context menu that appears by
right-clicking a row, see Figure 5.7.

88
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 5.7: An access to Blockings

Blockings can be set with option buttons, see Figure 5.8. If some of the blockings are
not allowed to a signal, the option button is disabled.

Figure 5.8: Signal Blocking State dialog

5.2.5 Customizing the column layout

The layout settings can be configured by selecting Settings > Display Settings... >
Layout Settings. The dialog in shown in Figure 5.9.

89
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 5.9: Layout settings

All the available attributes are shown in the Attributes box. Selected Columns is a list
of currently selected columns. Add attributes to Selected Columns list by clicking >.
Clicking >> adds all the attributes to Selected columns list.
Remove selected attributes from the Selected Columns list by clicking < or remove all
attributes from Selected columns list by clicking <<.
Change the order of the columns by selecting a column and clicking Up or Down buttons.
Default Settings restores the settings to an installation defaults for specific display type.

Renaming the Columns


The column headers can be defined. Select the column from the list of selected columns.

Enter the new name to the column name field and click the icon.
In Event Display, there is a special STATUS column, which is displayed as three
consequtive columns in the list. Names for these can be given separated by a comma, as
shown in the Figure 5.9.

5.2.6 Color Settings

It is possible to configure certain events to use different colors in the list display. This
improves the possibility to locate certain system events. For example, important events,
which cause alarms in the system, can be defined to use the red color in the Event Display.
For more information, see SYS600 Application Design.

90
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

To use the color settings, the authorization level Control (1) is required. The Color Setting
tool is in the read-only mode, if the authorization level is lower than Engineering (2) in
the TOOLS authorization group. If the TOOLS authorization group is not found, the
authorization group GENERAL is used.
The Color Settings dialog is used when the list display is customized with different colors
for rows on the list display. The coloring of a row in a list is defined with one or multiple
conditions defined in the Color Settings dialog, see Figure 5.10.

Figure 5.10: The Color Settings dialog.

To add a new coloring rule to the list, click Add. Remove the selected coloring rule from
the list by clicking Remove.... The position of the selected row can be changed by clicking
the Up or Down buttons. Coloring rules are prioritized according to their order in the
list and the first rule matching the criteria is used.

91
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

The background color of every display can be changed. The Color settings dialog has
Edit buttons to open the Color dialog, where the color selection is done. The selected
color is displayed as a colored box.
Default Settings button reverts the color settings.
There are some predefined color rules. A predefined color rule can be added to the list
by selecting it from the drop down list and clicking the Add button. Unused predefinitions
are shown in the drop-down list. When a preconfigure color rule is removed, it is returned
to the drop down list.
User Activity Log Display uses Event Display color settings definitions. Only color rules
can be defined specific to the User Activity Log Display.
Frozen mode color and Filter in use color are used in markers in the Monitor Pro
application window to highlight that the appropriate mode is used.

Figure 5.11: Frozen mode color

Day Break color is used on event display. When events are sorted by the time column,
every other day uses day break color as background color.

Color conditions
The condition of when a coloring rule is applied is defined with edit condition dialog.
Conditions can be entered either by using conditions rows or by hand in the filter field.
The condition is a simple logical expression such as AL = 1 AND AR = 0. Conditions
can also contain parenthesis. A name can be given to each condition.

92
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 5.12: Edit Condition dialog

The available operators for the conditions are described in Table 5.2.
Table 5.2: Condition operators
Operator Function
== or = Equal than
< Less than
> Greater than
<= Less or equal than
>= Greater or equal than
<> Not equal to

The Value field contains the value that is compared to the selected attribute by using the
selected comparison operator. It is possible to use the wildcard characters % and * when
defining the value of the Value field, but, in that case, the only allowed operators are =
and <>. For example, a value 5* means that the first character in the value must be 5 but
the rest of the value can contain any number of arbitrary characters. Character % means
any character.

93
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

5.2.7 Exporting Data

It is possible to save the data shown in event, alarm and bloking lists to a file in CSV
format. The separator between the columns is the List Seprator character defined in
operating systems Regional Settings. If the List Separator is defined to be '.' (full stop),
it is replaced with ';' (semicolon) character.
To export data:
1. Select Export... from list specific menu. The Save As dialog opens.
2. Specify the folder and the file name for CSV export file.
3. Click Save button to export the data.
The exported text file contains the header information, the export creation time, and the
events data. To open the export file with e.g. Microsoft Excel, select Format > Cells >
Text in the Category list to display the format correctly.

5.2.8 Indicating Daylight Saving Time

Lists have a setting for Daylight Saving visualization. The setting is accessed via the
lists' General Settings dialog. If the setting is enabled, lists will indicate Daylight Saving
times in each list column having timestamp information. Daylight Saving timestamps
are suffixed with '*' (asterix) character.

5.3 Handling events


Events in SYS600 system are stored in the history database (HDB). There are two types
of events: process events and internal events. Process events are events that belong to
supervised processes such as indications, protecting events, alarm limits for measurements,
tripped breakers, and so on. Internal events are events that indicate disturbances in the
supervision system. They are normally initialized by the system.
When an event occurs in the system, it is instantly printed on the event printer and stored
in the history database. The history database consists of history database files, of which
each contains the events for one day. The files are named according to the date as
APL_yymmdd.PHD. For example, the file APL_040630.phd contains the events logged
on 30-Jun-2004. The files are stored in the directory /SC/APL/nnn/APL_, where nnn is
the name of the application.

5.3.1 Event Display Settings

To configure Event Display settings (see Figure 5.13), the authorization level Control is
required. The Settings dialog is used when customizing the list.

94
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 5.13: Settings dialog

To configure the Event Display, the following settings can be specified:


• In the Max nr. of days / event set drop-down list the maximum number of days that
will be included in one event set can be set.
• In the Max nr. of events drop-down list the maximum number of events that will be
included in one event set can be selected.
• In the Scroll order drop-down list the sorting order of the events in the frozen mode
can be defined.
• In the Timeout drop-down list the maximum amount of time for the history database
query can be specified.
• Selecting the Day break option the user can define if a light blue background will
be presented between the events that have time stamps from different days.
• Selecting the Latest event on bottom option the user can specify the location of the
latest event on the list.
• Selecting the Show Grid lines option shows the gridlines in the events list.
• Under the Font Settings the font style and size can be defined.

95
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

The following items can be selected to be shown in the Context Menu:


• Comment
• Locate object in Monitor Pro
• Locate object in Monitor Pro - new window
• Locate object in DMS
• Blockings...
• Use as Filter...
• Export...
Locate object in DMS option is available only if DMS 600 is installed.
The scroll order setting defines the time attribute used in the list. If the setting is LOG
the registration time (RT) is used. If the setting is event, the event time (ET) is used.

5.3.2 Event Comments

Comments can be used for making remarks to events. The comments are available to all
Event Display users. Comments can also be removed.
The Comments dialog can be opened by right-clicking an event row with or without the
comment marker and selecting Comment in the context menu. Events with comment
markers are shown in Figure 5.14.

Figure 5.14: Comments dialog

To add a comment:
1. Open the Comments dialog.
2. Write the comment to the dialog and click OK.

96
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

3. Press Enter after each line. If no comment text is given, no comment mark will be
displayed in the Event Display.
Open the Comment dialog to read the comment. To remove the comment, click Remove
Comment. The Last Edit by User and Modification date fields show the name of the
user that last edited the comment, and the time and date of the modification.
The length of the comment is limited. If the comment is too long, the OK button is
disabled.

97
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

6 Alarm Display

The Alarm Display shows a summary of the present alarm situation of the supervised
process. Each alarm is normally presented as an alarm text row, which describes the
cause of the alarm in the process. With default settings the alarm text row normally has
a time stamp, an object identification, an object text and text indicating the alarm status.
See Figure 6.1 for Alarm Display Template 1 and Figure 6.2 for Alarm Display Template
2.

Figure 6.1: Alarm Display Template 1

Figure 6.2: Alarm Display Template 2

The Alarm Display contains the following features and options:

99
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

• Two types of Alarm Display templates


• Filters
• Alarm Display setting tool for colors and text layout
• Updating/Frozen modes
• Alarm acknowledgement
• Alarm reset function
• Authorization support
• Help in all dialogs (The complete manual will be opened from Help)
• Visible Alarm Class
• Locate object in DMS
• Locate object in Monitor Pro
• Column sort
• Find
Template 1 and Template 2 also have other features than those described above.
These templates include:
• Fields indicating the number of active and unacknowledged alarms
• A field indicating the use of filters
• A field indicating the current mode
• Alarm count indication on both lists.
The Alarm Display is started by selecting Navigate > Alarm. By default, the two
templates are included in the Alarm menu.
When the filters are defined, only those alarms matching the filter configuration are
displayed. When the filter is defined, the text "Filters:Used" is displayed on the Monitor
Pro application window. By default, the filters are not used.
An alarm is activated in the following situations:
• An incoming binary signal (BI type process object) changes to an alarming state.
• A double indication (DB type process object) changes to an alarming state, for
example a breaker middle state due to a faulty operation.
• An analog measured value (AI type process object) exceeds the alarm limits (the
preset upper and lower limits).
• An object is marked faulty by a process device.
• A system error or communication failure occurs.
If the process object has an alarm function and the alarm is not blocked, information on
the alarming process object will be displayed in the alarm list.
The Alarm Display Template 1 and 2 menus contain the following commands:
Filters: Opens a dialog, where filters can be selected and edited.
Reset Filter: Resets filters back to the default settings.
Keep Updating: Sets the Alarm Display to the updating mode. When changing to Alarm
Display, the mode is by default set to updating mode if a user is logged in.
Stop Updating: Sets the Alarm Display to the frozen mode. When changing to Alarm
Display, the mode is by default set to frozen mode if no user is logged in.

100
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Acknowledge…:
All: Acknowledges all the alarms on the list. A confirmation dialog is opened to confirm
the operation.
Page: Acknowledges all the alarms on the current pages (both lists). A confirmation
dialog is opened to confirm the operation.
Show Info Fields: Displays/hides the info fields.
Show Headers: Displays/hides the list headers.
Last Alarm: Scrolls the list to show the latest alarm and sets the mode to updating.
Export: Exports the current view in CSV file format.
The toolbar provides a shortcut to the commands in the menus. The toolbars in the Alarm
Display Template 1 and Alarm Display Template 2 can be modified separately.

Figure 6.3: Toolbar of Alarm Display

The buttons in the toolbar of Alarm Display are from left to right:
• Show Filters
• Reset Filter
• Switch to Updating or Frozen Mode
• Acknowledge All
• Acknowledge Page
• Acknowledge Selected Alarm
• Go to Last Alarm
Add or remove buttons on the toolbar the same way as in applications in general, refer
to Section 3.4.2 Changing application layout.
The list can be set to two different modes: frozen and updating. When the list is in the
frozen mode, it is not updated, and the alarm information can be read easily. If alarms
are changed while the Alarm Display is in the frozen mode, the operator is notified with
an informative text on the display area. When in the updating mode, the Alarm Display
is updated when alarms are changed. The current mode is indicated in the Monitor Pro
application window.

6.1 Alarm rows


Each alarm is presented as a single alarm row.
Different alarm templates list alarms in different states. The states are show in Figure 6.4.
With default settings, the different states are colored differently. The default colors are
the background colors in the figure.

101
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Acknowledge
Unacknowledged Acknowledged Persisting
Alarm Alarm Alarms

Non alarming Non alarming

Acknowledge
Fleeting alarm Non alarming

Figure 6.4: Alarm states

When a new alarm is created, it can either be unacknowledged or already acknowledged.


On Template 1, these are shown in the upper list. If a signal leaves the alarming state
but the alarm was unacknowledged, the alarm becomes a fleeting alarm. Fleeting alarms
are show on the lower list on Template 1. When a fleeting alarm is acknowledged, the
signal enters non-alarming state. Template 1 does not show non-alarming signals.
On Template 2, unacknowledged, acknowledged, and fleeting alarms are always shown.
With default settings, non-alarming signals are shown in the list, if the state of the alarm
is changed when the list is visible. When the list is refreshed, the non-alarming signals
are removed. If Remove fleeting alarm is set, non-alarming signals are not show on the
list at all.
The values for status column and default colors are explained in Table 6.1.
Table 6.1: Default colors and status texts of the alarm types
Alarm type Default color Status text Explanation
Active unacknow- Red Alarm An alarm has been re-
ledgeda High alarmb ported, but it has not
Low alarmb been acknowledged.
Active acknowledgeda Blue Ack An alarm has been re-
High alarm Ackb ported, and it has been
Low alarm Ackb acknowledged.
Inactive unacknow- Black Normal The state has been
ledgeda alarming, but it is no
longer alarming.

a. included in persisting alarms


b. shown with analog values
c. included in fleeting alarms

102
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

In the Alarm Display Template 2, the inactive acknowledged alarms can also be kept on
the list. Due to this, Template 2 functions as a sort of alarm log. The inactive
acknowledged alarms are erased from the list when the Alarm Display is closed. The
same can be done by selecting Alarm Display Template 2 > Refresh from the menu.
All alarms are displayed on a single list. A flashing character * indicates all
unacknowledged alarms, both active and inactive. Template 2 is presented in Figure 6.2.
Table 6.2 provides an explanation for the different alarm types.
Table 6.2: Alarm types
Alarm Type Explanation
Active unacknowledged An alarm has been reported, but it has not been
acknowledged.
Active acknowledged The alarm has been inactivated (the state is
normal again).
Inactive unacknowledged The state has been alarming, but it is no longer
alarming.
Inactive acknowledged An alarm has been reported, and it has been
acknowledged.

6.2 The Alarm Display User Interface


The alarm display works in the same way as the event display, see Section 5.2 The Event
Display User Interface. In the alarm display Template 1, there are two separate lists in
the display. All configurations on the list affect both of the lists.

6.3 Handling alarms


The process database is the part of the base system where all the registration of incoming
and outgoing process data takes place. The process database also supervises the current
alarm situation of the various process objects by storing information of process objects
with an alarm generating state into a special alarm buffer. The interface for alarm handling
is the application process database, which is project specific, but the main functionality
of the process database is always the same.

Process alarms
Process alarms are alarms that are related to the supervised process, for example,
measurement values exceeding or going below the preset alarm limits, breakers tripping
or getting into a faulty position and so on.

Internal alarms
Internal alarms are alarms caused by the network control system itself. Reasons for these
alarms contain communication problems between a communication unit and substation,
printer device errors, substation getting suspended, and so on. These kinds of erroneous

103
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

states are detected and converted from internal system messages to alarms by the System
Self Supervision function of SYS600.

System alarm
A system alarm is an alarm generated by an external module supervising the Base System.
The external module is working as a Watch Dog for the base system and it generates an
external alarm if the base system stops. It is not possible to include this alarm in the
Alarm Display.

Alarm activation time


An activation time shows the time when the alarm was activated. The Time (AT attribute)
and Activation time (YT attribute) columns are the same for active alarms. The column
shows the time when the alarm was activated. For fleeting alarms, the Time (AT attribute)
column shows the time when the object is changed back to normal state. The Activation
time (YT attribute) column shows the time the alarm was activated.

Alarm acknowledgement
An acknowledgement of an alarm is a way to show that the operator has registered and
identified the alarm. Generally, acknowledging an alarm does not affect the alarm state.
An unacknowledged alarm remains in the alarm buffer until it is acknowledged, even if
the alarm state has passed. A required acknowledgement can be set individually for each
process object (RC attribute).

Alarm blocking
Alarm blocking blocks a signal in such a way that it cannot generate an alarm. (The same
applies to history blocking, printout blocking and action blocking). Since the alarm is
blocked, it is not registered in the process database when the process object gets into an
alarm generating state. The other types of blocking are history blocking, printout blocking
and action blocking.
It is not possible to block features that has not been activated, for example alarms, history,
printouts and action features. Alarm blocking is set individually for each process object
(AB attribute).

Alarm classes
The term alarm class means that the alarms can be grouped into seven equally significant
alarm classes. This feature can be used when the user wants to group alarms caused by
process objects with common properties, for example object location. From the base
system's point of view, there is no internal priority between the different alarm classes.
The alarm classes can also be used when searching alarms from the alarm buffer. By
setting the alarm class to 0, the alarm function of a process object is set off. The use of
alarm classes is user-defined.

104
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Function and alarm class lists differ from the object lists in that they are not editable.
This is to simplify modifications. The number of the selected alarm class refers directly
to the alarm class of the alarms to be shown in the Alarm Display. Any combination
between these two lists is possible.

6.3.1 Alarm Display Settings

Figure 6.5: Settings dialog

The Settings dialog (see Figure 6.5) includes general settings, Font Settings, Visibility
settings and context menu settings. The Latest alarm on bottom specifies whether the
latest alarm is presented in the Alarm.
Display on the top or at bottom of the list. By default, the latest alarm is on the top. In
the font settings the font size, name and style can be specified. The visibility settings
include the options Application specific and User specific. The following items can be
selected to be shown in the context menu:
• Acknowledge…
• Locate object in Monitor Pro
• Locate object in Monitor Pro - new window

105
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

• Locate object in DMS


• Blockings...
• Use as Filter...
• Export...

6.3.2 Acknowledging alarms

Acknowledge a single alarm by selecting the alarm row from the Latest Alarms dialog,
see Figure 6.6.

Figure 6.6: Latest Alarms dialog

If the selected alarm is unacknowledged, the Acknowledgement dialog in Figure 6.7 can
be opened by selecting Acknowledge All from the context menu. The same can be
achieved by double-clicking an unacknowledged alarm row in the list.

Figure 6.7: Acknowledge alarm dialog

In the dialog, the alarm text row (except for the status text) is shown to ensure that the
right alarm is acknowledged. If OK is clicked, the alarm will be acknowledged, the
dialog closed, and the Alarm Display will be updated. Clicking Cancel closes the dialog
and returns the Alarm Display. All alarms on the list can be acknowledged at the same
time by selecting Alarm Display Template 2> Acknowledge All from the menu or by
clicking the appropriate button on the toolbar. The alarms currently visible on the list
can be acknowledged by selecting Alarm Display Template 2 > Acknowledge Page
or by clicking the appropriate button on the toolbar.

106
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

7 Blocking Display

The Blocking Display summarizes the present blocking situation of signals in the
supervised process. Each signal is presented as a signal row, which describes the signal
in the process. The signal text row normally consists of a signal text and a group of check
boxes indicating the blocking state. Figure 7.1 shows the Blocking Display main view.

Figure 7.1: The Blocking Display main view

The Blocking Display contains the following features and options:


• Selection of signal(s) for blocking/deblocking
• Blocking Display setting tool for the view layout
• Printout of blocking situation
• Event and printout enabling/disabling
• Authorization support
• Possibility to copy contents on the clipboard of the operating system
• Help in all dialogs (the complete Operation Manual will be opened)
• Locate object in DMS
• Locate object in Monitor Pro
• Column sort
• Find
The Blocking Display can be started by selecting Navigate > Blocking (see Figure 7.2).

107
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 7.2: Starting the Blocking Display

All the tools can be used either by clicking the shortcuts on the toolbar or by selecting
the corresponding items in the Blocking menu.
The Blocking menu contains the following commands:
Filters: Opens a Filter Settings dialog, where filters can be selected and edited.
Reset Filter: Resets filters.
Refresh: Updates the blocking information.
Show All Signals: Loads all signals to the display despite of their blocking status.
Show Info Fields: Displays/hides the info fields.
Show Headers: Displays/hides the list headers.
First Blocking: Shows the first blocking.
Last Blocking: Shows the last blocking.
Export: Exports the current view in CSV file format.
The toolbar is a shortcut that can be used in parallel with the drop-down menu.

Figure 7.3: Toolbar of the Blocking Display

The buttons in the toolbar from left to right are:


• Filters
• Reset Filters
• Show All Signals
• Refresh

108
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

• First Blocking
• Last Blocking

7.1 Blocking Rows


There are six different types of blockings: alarm, update, control, event, printout, and
action blocking. Each blocking type has a condition that is defined when the particular
blocking can be used. Alarm blocking can be done only if the signal has a defined alarm
class. Update blocking is only applicable for input signals and control blocking is only
applicable for output signals. Event blocking can be done if events are enabled for the
signal. Printout blocking can be used if the signal has a printer defined. Action blocking
is available if actions are enabled for the signal. Different blocking types are described
in Table 7.1.
Table 7.1: Blocking types and their attribute values
Blocking type Header in printout Attribute values Condition
Alarm blocked AB AB = 1 AC > 0
Update blocked UB UB = 1 Input signal
Control blocked CB UB = 1 Output signal
Event blocked EB HB = 1 HE = 1
Printout blocked PB PB = 1 LD > 0
Action blocked XB XB = 1 AE = 1

7.2 The Blocking Display User Interface


The blocking display works in the same way as the event display. See Section 5.2 The
Event Display User Interface. By default, the list contains only signals that are blocked.
By selecting Blocking > All Signals all the signals can be seen.

7.3 Handling Blockings


The SYS600 provides a wide range of blocking attributes, which are included in the
Blocking Display. To provide a blocking handling mechanism in a more clear and rational
way, the following blocking types are provided by the Blocking Display:
Alarm blocking: alarms are not raised, regardless of the object state.
Update blocking: indications are not updated by the process.
Control blocking: operation commands are not sent to the process.
Event blocking: event registrations are not made, events are not shown in the
Event Display.
Printout blocking: events are not sent to the printer.

109
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Action blocking: event channel activation is blocked.


The blocking activity must be expanded to the signal level. The reason for this is that,
for example, in case of an oscillating signal, the user must be able to block it but leave
the other signals (related to the device in question) unblocked to minimize the information
loss. Blocking is possible either by setting the blocking state for each signal presented
on the list or by fetching any signal from the database and setting its blocking.
When a signal is update-deblocked, its state in the database is not necessarily up to date,
since the state of the process device may have changed while the signal has been
update-blocked. Therefore, the state of each signal must be updated from the process
when the signal is update-deblocked.
Blocking Display is not automatically updated when a blocking signal has changed. A
Refresh function is provided to enable updating of the blocking information. The Blocking
Display is refreshed by selecting Blocking > Refresh or by clicking the appropriate
toolbar button.

Setting signal blocking state


The blocking state of the signal can be set by clicking the selection box for the signal in
question. Since a signal can be either of indication or of control type, the selection boxes
corresponding to either one of the blocking types is unset and unavailable, depending
on the signal.
An alternative way to set the blocking states for the signals is to use the copy-paste
function. The selected signal's blocking states are copied by pressing CTRL-C and the
blocking states can be set to another signal by pressing CTRL-V. Multiple signals can
be blocked or deblocked by selecting multiple rows and selection Block/Deblock from
the context menu.

If all the blockings are deblocked, the signal will be removed


from the Blocking Display after next view refresh. If a
non-internal signal is in the update-deblocked mode and it is
connected to a process, its state will be updated.

7.3.1 Blocking Display Settings

The settings part of the Blocking Display functions consists of two main parts: view and
event/printout settings. The user can concentrate on one or more blocking types by
excluding the other blocking types from the list with the view part of the Blocking Display
Settings dialog (shown in Figure 7.4).
There are settings for enabling event generation and printout on a change of blocking.
Events and printouts are enabled/disabled regardless of the attributes (HE and PB) of
the target signal.

110
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 7.4: The Blocking Display General Settings dialog

111
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

8 User Activity Log Display

With the User Activity Log Display the information about all user activity related events
can be monitored and analyzed. Typical user activity related events are user login and
logout events.

Figure 8.1: The User Activity Log Display main view

Each user activity event is one row in the display. With default settings, User Activity
Log Display rows consist of event identifier, a time stamp, event text, user name, severity
of the event and the source application of the event.
The User Activity Log Display contains the following features and options:
• Configurable layout: columns, fonts, toolbars, coloring, and so on
• Configurable coloring of user activity events
• Configurable mode for presenting latest event at top/bottom
• Easy navigation through scrolling, go to date, time filters, and so on
• Extensive filtering that can be stored and easily called up later using preconfigurations
• Find
• Sorting by column
• Printouts
The User Activity Log Display is accessed by selecting Navigate > User Activity Log.
The User Activity Log menu contains the following commands:
Filters: Opens a Filter Settings dialog, where filters can be selected and edited.
Reset Filter: Resets filters.
Refresh: Updates the User Activity Log information.

113
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Show Info Fields: Displays/hides the info fields.


Show Headers: Displays/hides the list headers.
Go to First: Shows the first user activity event.
Go to Last: Shows the last user activity event.
Select Day: Opens a Day select dialog.
Export: Exports the current view into CSV file format.
The toolbar is a shortcut that can be used in parallel with the drop-down menu.

Figure 8.2: User Activity Log Display toolbar

The buttons in the toolbar from left to right are:


• Show Filters
• Reset Filter
• Refresh User Activity Log
• Go to First User activity
• Go to Last User activity
• Go to Selected Day
The toolbar buttons can be added or removed in the same way as in applications in
general, see Section 3.4.2 Changing application layout.
The User Activity Log Display is not automatically updated when new user activity
events occure in the application. New user activity events can be fetched by Refreshing
the display or by pressing F5.

114
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

9 Trends Display

The Trends Display is used for trend analyses and for showing measured values in the
form of a curve or a table.
A trend is a time related follow-up of process data. All types of process objects, for
example in and out data and binary, analog and digital data can be illustrated as trends.

Figure 9.1: The Trends Display

The Trends Display contains the following features:


• Graphical or tabular view
• Zooming mode
• Scrolling with scroll bars and panning

115
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

• Configurable axes and line properties


• Using legend
• Using hairline
• Update interval options from 10 seconds to 10 minutes
• Calculation formulas; direct, mean, sum, integral and difference
• Clearing trend data by the user
• Save, Open and Delete preconfigurations
• Printout option
• Update/Frozen modes
• Authorization support
• Copy to clipboard
• Export to CSV file
Trend display configuration includes a set of parameters such as colors, fonts, and so
on, which are called trend preconfigurations. For more information on preconfigurations,
see Section 9.6 Preconfigurations.

9.1 Starting Trends Display


The Trends Display can be started by selecting Navigate > Trends (see Figure 9.2).
To open the basic Trends Display, select Navigate > Trends > No Preconfiguration.
For more information about saving the preconfiguration, see Section 9.6 Preconfigurations.

Figure 9.2: Trends navigation menu

9.2 The Trend Basket


The Trend Basket is a link between the process data and the Trend display. With the
Trend Basket dialog the user can select data from the process database to be logged and
shown in the Trend display.

116
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

The Trend Basket dialog can be opened by selecting Trends > Trend Basket, or by

clicking the corresponding button in the toolbar. The Trend Basket dialog lists the
system objects and lets the user pick the objects to be shown in the trend.

Figure 9.3: The Trend Basket dialog

By default, only measurement objects are shown. If the All Objects (not only
measurements) option is selected, the Trend Basket object tree displays all the objects
from the process database.

9.2.1 Add and remove Trends

The available objects are presented on the left side of the dialog. In the object tree's
lowest level objects which will be included into the Trend Basket list can be selected
one at a time.
There are three ways to add objects to the Trend Basket from the object list:
1. right-click the object and select the Add to Trend Basket command from the context
menu. Added objects are shown on the right side in the Trend Basket.
2. drag an object from the available object list and drop it into the Trend Basket list
on the right side.
3. double-click the object to add it to the Trend Basket list.
To remove selected object from the Trend Basket:
1. right-click the object in the Trend Basket list and select Remove Log from the
context menu.
2. press the Delete key from the keyboard.
3. click Delete button in the dialog.

117
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Check from the Show/Hide Trend curves dialog that the


related trend items are included in the active preconfiguration.

9.2.2 Trend settings

The Trend Basket dialog will also be used to configure individual trend parameters. The
Trend Setting dialog for the selected trend can be opened by double-clicking an object,
selecting the corresponding Log Settings... item from the context menu or by clicking
the Edit... button.

Figure 9.4: The Trend Settings dialog

The following Trend properties can be changed:


• Time channel (10, 30 seconds; 1, 2, 5 or 10 minutes)
• Logging function (Direct, Sum, Mean, Integral or Difference), see Table 9.1.

Change the Log function will cause the lost of all existing data
for the selected Trend.

Table 9.1: Log functions


Log function
Log time Data Direct Sum Mean Intergral Difference
T-1 0 0 0 0 0 0
T0 1 1 1 1 0 1
T+1 min 2 2 3 1.5 60 1
T+2 min 3 3 6 2 180 1
T+3 min 5 5 10 2.75 360 2
T+4 min 4 4 14 3 660 -1

118
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

9.2.3 Clearing Trend data

Clearing the Trend data for the selected Trend can be done by right-clicking an item in
the Trend Basket and selecting Clear log data from the context menu, or by clicking

the corresponding button from the Trends tabular view toolbar.

Access to this functionality requires at least ENGINEERING


level (2) access rights. Otherwise, the appropriate functions
are unavailable.

9.3 The user interface


The Trend data can be presented in a tabular or in a graphical view. These two views
share the same Trend database.
Both views also share some of the toolbars and the Trends Display menu.

9.3.1 Trends Display toolbars

The Trends Display has four toolbars. Three are used for both views and one dedicated
for the graphical view.
When the Trends Display is started for the first time, all the three toolbars are visible.
Show or hide the toolbars by selecting Settings > Customize. Add or remove buttons
on the toolbars the same way as described in Section 3.4.2 Changing application layout.

Figure 9.5: Main toolbar

Table 9.2: Main toolbar functions


Function Description
Open Preconfiguration Opens the Open Preconfiguration dialog.
Save Preconfiguration Opens the Save Preconfiguration dialog.
Print Prints the selected report to a network printer or a specified
output file.
Copy to Clipboard Copies the selected visible trend data to the operating system
clipboard.
Find This function is disabled for the Trends display.

119
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Function Description
Display Settings Opens a sub-menu with the following items:
• General Legend Settings...
• Graph Settings...
• Legend layout Settings...
Help Opens the Help dialog

The Trends Display toolbar buttons and drop-down lists from left to right are as follows:
• Switch updating/frozen mode
• Refresh
• Open Trend Basket
• Show or hide trend curves
• Switch tabular/graphical view

Figure 9.6: Display toolbar

Table 9.3: Display toolbar functions


Function Description
Switch between updating and frozen mode
indicates the update mode as active
mode. Clicking this button will change to the
frozen mode.

indicates the frozen mode as active


mode. Clicking this button will change to the
update mode.
Refresh Forces a display refresh.
Show/hide trend curves Open the Show/Hide dialog, where the user can
select which curves to show in the current view.
Switch tabular/graphical view

The graphical view is active. Clicking


this button will change to the tabular view.

The tabular view is active. Clicking this


button will change to the graphical view.

9.3.2 Trends Display menus

The toolbar commands can also be selected from the Trends menu (see Figure 9.7 and
Figure 9.8). Some of the menu items are active for graphical view only.

120
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 9.7: Trends Display menu for tabular view

Figure 9.8: Trends Display menu for graphical view

In addition to the toolbars the following functions are available from the menu:
• Show/Hide Hairline
• Show/Hide Legend
• Export...

121
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

9.3.3 Using Trend curves

Show and hide the trend curves by selecting Trends > Select Curves, or by clicking the

corresponding button in the Trends Display toolbar. The Show/Hide Trend curves
dialog displays the items the Trend Basket contains. These items can be included in or
excluded from the selected preconfiguration by selecting or clearing the corresponding
checkbox. It is also possible to select all or clear all of the items by using the appropriate
commands from the context menu, or by using the command buttons.

Figure 9.9: Show/Hide Trend Curves dialog

By default, all the added items in the Trend Basket are automatically included and
displayed in the trend curves as well. View the detailed information about the trended
items in preconfiguration in the Show/Hide Trend curves dialog.
With the Show All Curves check-box all Trend curves not used for the selected
preconfiguration can be hidden.
To change the Trend curve position within the preconfiguration, select one curve and
use the corresponding Down or Up button. This will also change the position in the curve
legend. After changing the position, the preconfiguration must be saved to keep the
position change.

Up to 20 Trend curves can be viewed for the graphical and


tabular view.

122
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

9.3.4 Time range

The time period used in tabular and graphical view can be changed with the Select Time

Period dialog, which can be opened from the navigation toolbar .

Figure 9.10: Select Time Period dialog

By default, the Full registration period is applied. This means that all the samples are
shown on the graphical view, and the accuracy of the registration time is scaled
accordingly. When Custom period is selected, it is possible to select a start date and time
for the detailed information. The first registration time is shown on the X axis.
Additionally, the length of the period is defined to one of the following alternatives: 30
days, 5 days, 1 day, 1 hour, 10 minutes or 1 minute.

9.4 Graphical view


In the graphical view, up to twenty measurements can be presented on a two-dimensional
coordinate system that consists of a horizontal time (X) axis and a vertical value (Y)
axis. The curves can be panned both in the X and Y directions and the parameters of the
Y axis can be changed. All the curves can be hidden from the view with the dialog.
The horizontal (X) axis of the graphical view represents the registration time of the
measurement, and the vertical (Y) axis represents the value of the measurement. The X
axis is divided into intervals specific to the selected time range. The time of every interval
point is labeled below the X axis. The amount of the shown interval points depends on
the zooming level.
The Y axis is automatically divided into intervals according to the registered values.
Note that the graphical view does not recognize any units or scales, only the values
registered in the trends database.

123
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 9.11: Graphical view of Trends

The graphical view has the following functional areas:


• The plot area where the trended data will be shown.
• The legend area shows selected curve properties, hairline values and summary
information.
For the plot area, the following curve types can be chosen:
1. Plot (default)
2. Area (fills the area between two selected curves or between a curve and the X or Y
axis)
3. Bar or group of bars
4. Stacked bar
The curve type can be configured with the dialog.

Not all data are always available for the curve type Bar and
Stacked bar. The amount of displayed bars or groups of bars
depends on the zooming level.

The legend position can be changed with the dialog or the Legend Control context menu.
The legend show up can be disabled with the dialog or from the Trends menu.

Navigation
The Navigation toolbar buttons from left to right are as follows:

124
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

• Go to First Period
• Go to Previous Period
• Go to Next Period
• Go to Last Period
• Select Period

Figure 9.12: Navigation toolbar

Table 9.4: Navigation toolbar functions


Function Description
Go to First Period Shows the data for the first time period in the
selected time range.
Go to Previous Period Shows the data for the previous time period in
the selected time range.
Go to Next Period Shows the data for the next time period in the
selected time range.
Go to Last Period Shows the data for the last time period in the
selected time range.
Select Period Opens the dialog to enter the start time and the
time range.

Scrolling, panning and zooming


Select the zooming mode to outline the area that needs to br zoomed in the graphical
view. Scroll to the zoomed curve by using the scroll bars.
By selecting the panning mode the user can drag the curve with the mouse. Panning is
only possible after zooming in.
For more information about zooming, see Section 4.2 Zooming.
The Trends Display Zoom toolbar buttons from left to right are as follows:
• Save/Restore Zoom, disabled for Trends display graphical view
• Reset zoom to normal
• Zoom Previous, disabled for Trends display graphical view
• Zoom In, disabled for Trends display graphical view
• Zoom Out, disabled for Trends display graphical view
• Select zooming mode
• Select panning mode
• Select selection area for copy selected area data to the clipboard

125
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 9.13: Zoom toolbar

The Save/Restore Zoom…, Zoom Previous, Zoom in and Zoom out buttons can be
removed, because they are not used for the graphical view of the Trends Display.

Figure 9.14: Removed buttons from the zoom toolbar

The Hairline function


Hairline provides more accurate information on the graphical view. It is related to certain
time and it is relating values for Trend data in the configuration.
To view the hairline on the graphical view, select Show Hairline from the Trends menu.
Place the hairline into another location by dragging it horizontally. New time information
is displayed above the hairline.
By using the left or right arrow key the hairline will be snapped to the previous
respectively next valid curve value.
The values for the Trend curve items are displayed in the legends hairline value column.
Instead of placing the hairline by dragging, any point in the plot area can be selected.
Select the Show Hairline Here item from the context menu. The hairline will be placed
at that point.

Graph Settings

The dialog can be opened either by clicking the appropriate Main toolbar button or
by right-clicking inside the plot area and selecting the Graph Settings... item.
Authorization level has to be at least Control (1) to be able to change these properties.
After modifying the settings in the dialog, save it as a preconfiguration if the changes
need to be permanent.
1. Common Settings

126
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 9.15: The Graph Settings dialog, Common Settings

Table 9.5: Graph Settings, Common Settings


Setting Description
background color If "Use color scheme" is enabled, the background color from the
active color scheme will be used. If not, the user can freely choose
any color with the color chooser.
Grid color If "Use color scheme" is enabled, the background color from the
active color scheme will be used. If not, the user can freely choose
any color with the color chooser.
Mouse mode If the Mouse mode "Selection" is active, area selection with the mouse
can be used to copy the data from the selected area to the clipboard.

127
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

2. Axis properties

Figure 9.16: The Graph Settings dialog, Axis Properties

Table 9.6: Graph Settings, Axis Properties


Setting Description
Font Font for the Axis annotation
Color (all Y axes) Axis line color
Y axes common for all pages If checked the current Y axes configuration will be used
for all existing report pages. If not checked different Y
axes properties can be defined for every selected page.
This option is disabled for reports having only a single
page configured.
Select (Y2 .. Y4 axes) Show/hide selected Y axis (By default it will be hidden)
Auto scale (Y1 axis) The scaling is based on the minimum and maximum
values for the complete time range, not only for the
selected time range.

128
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Setting Description
Use Grid color (all Y axes) If enabled, the dedicated Y axis gridline color will be
used. Otherwise the gridline color from global color
setting tool will be used.
Left or right selection (all Y axes) Y axis placement
Enable gridline (all Y axes) If enabled, horizontal gridline corresponding with Y
axis will be shown.
Unit name (all Y axes) Display unit name of Y axis, default value is Y1, Y2,
Y3, Y4.

3. Curve properties
The Curve Properties tab can be used to change individual curve settings. First
the correct report curve must be selected from the drop-down list.
The Curve Properties dialog can be also opened via the curve right mouse click
context menu in the graphical area or the legend.
Selecting the All Curves option helps to change the curve type for all available
curves.

Figure 9.17: The Graph Settings dialog, Curve Properties

129
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Table 9.7: Graph Settings, Curve Properties


Setting Description
Curve type The curve types plot, area and bar can be chosen for each indi-
vidual trend. The stacked bar type can only be used for all en-
abled trend curves.
Bar width selection Either the automatic bar width calculation or manually entered
value can be chosen. This setting is only available for the curve
type Bar or Stacked bar.
Select Y axes Maps Curve to selected Y axis.
Marker color If the curve data has a none normal status the corresponding
color from the color setting tool will be used as marker color.
Use curve settings as If this option is selected the current curve settings wil be stored
global as global settings. Every time the same curve object will be ad-
ded to some preconfiguration this global settings will be used.
To be able to use different settings this option needs to get un-
checked. In case use as global is checked and the current
properties will be changed, e.g. new line color selected, the
stored global settings will be overwritten.
Curve settings defined as beeing global will be stored in a sep-
arate file and not in the selected preconfiguration.
Changed global curve settings will be saved with OK or Apply
button selection.

Configuring and mapping Multiple Y-axes


It’s possible to use 4 different Y axes to accumulate four different ranges of curve values.
Curves from Trends display can be mapped with any Y axis.
The following steps are required to configure and map Y axes:
1. Open Graph Settings... > Axes Properties
2. Select (Enable) particular Y-axes
3. Provide Min. and Max. value for selected axes
4. Set the axes color
5. Select Enable/Disable gridline
6. Select Curve Properties tab
7. Select curve
8. Map enabled Y-axes with selected curve
9. Apply Changes

The Legend
The Legend shows selected curves attributes, the hairline values and summary information
in a tabular form.

130
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 9.18: Legend area

Main Legend features are:


• Show curve properties, identifier, current, calculated and hairline values
• Show/hide all or selected curves
• Locate function via context menu
• Configurable legend position and column layout
• Highlight the selected curve if enabled

Legend show up and position


The legend can be shown/hidden by selecting the appropriate item from the Trends menu
or in the Common settings tab from the dialog.
The legend position can be changed either from the legend context menu or in the
Common settings tab from the dialog.

Figure 9.19: Legend context menu

Legend layout settings


The Legend layout settings can be configured by selecting Settings > Display Settings
> Legend layout Settings... or from the Legend context menu.
The Attributes box shows all available attributes which can be added to the layout. The
Selected columns box shows the list of already selected attributes.

131
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Clicking > adds the selected attributes to the Selected columns list. Clicking >> adds all
attributes to Selected columns list. Clicking < removes the selected attributes from the
Selected columns list. Clicking << removes all attributes from the Selected columns list.
The column position within the Legend table can be changed by moving the selected
column upwards or downwards using the Up/Down buttons.

Figure 9.20: Legend layout settings dialog

• Default Settings restores the default installation settings.


• OK applies all the pending changes and closes the dialog.
• Cancel discards all the pending changes and closes the dialog but does not cancel
or undo changes that have already been applied.
• Apply applies all the pending changes but leaves the dialog open.
• Help opens the help window.
Renaming the column header
Select the column from the list of selected columns. Enter the new name to the column

name field and click the icon.


Select the OK or Apply button do activate all modifications.

General Legend settings


The general Legend settings can be configured by selecting Settings > Display Settings
> Legend General Settings or from the Legend context menu.

132
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 9.21: General Legend settings dialog

Table 9.8: General Legend settings


Settings Description
Show gridlines Enable/Disable gridlines for Legend area
Highlight time The time a selected curve gets highlighted. Selectable options
are: never, forever or defined time in steps of 5 seconds in the
range from 5 to 60 seconds.
Set Font Font style and size used for the Legend area
Context menu items Configure the context menu items for the legend area
Visibility Visibility is configured to be either Application or User specific

Copying selected data to clipboard


Selected Trend data from the graphical view can be copied to the clipboard of the
operating system.

Activate the selection mode from the Zoom toolbar.


Select the desired Trend data area with the mouse. After the mouse button is released,
a dialog confirms that the data has been copied to the clipboard.

133
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 9.22: Copy to clipboard confirmation

If an empty area is selected, the following dialog is shown.

Figure 9.23: No data available for copy to clipboard

When the selection is pasted to the clipboard, the data is divided into several sections,
where each section has a header and contents of each selected Trend data.

9.5 Tabular view


Up to twenty Trends can be presented in the tabular view at the same time.
Each Trend is shown in a separate page.
The tabular view contains the following columns:
• Index column
• Time column
• Value column
• Status column

134
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 9.24: Tabular view of Trends

Trend values, registration time and status are shown on the list. Other Trend parameters,
for example object text, time interval, logging function and statistics, are shown on the
right side.
The Status column provides a clear text description for the status of the trended data.
Table 9.9: Tabular view, status column
Status Description
column
OK The Trend data has been registered under good conditions.
Suspicious The source of the Trend data has been marked as suspicious, e.g. if the input
card has some failure.
Obsolete The source of the Trend data has been marked as obsolete (not up to date), e.g.
if the connection to the data collection device has been lost.
Faulty time The source of the Trend data has an inaccurate time stamp because of time syn-
chronization.
Man. This Trend data has been manually entered by an operator.
Entered

135
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Status Description
column
Not sampled The source of the Trend data never had a valid value, e.g. after system start before
the connection with data collection device is established.

General settings
The General Settings dialog can be opened either by clicking the appropriate Main

toolbar button or by selecting Settings > Display Settings.

Figure 9.25: General Settings

Table 9.10: Tabular view, General Settings


Settings Description
Show gridlines Enable/Disable gridlines for tabular data area
Background shading Enable/Disable the row shading effect
Set Font Font style and size used for the tabular data area
Context menu items Configure the context menu items for the tabular data area
Visibility Visibility is configured to be either Application or User specific

Navigation
The Navigation toolbar buttons from left to right are:

136
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

• Clear Current Trend Log


• Shift to First
• Shift to Previous
• Shift to Next
• Shift to Last
• Select Day Period

Figure 9.26: Navigation toolbar

Table 9.11: Navigation toolbar functions


Function Description
Clear Current Trend Log Removes all data from the selected Trend. The sampling of new
values restarts.
Shift to First Shows the data for the first Trend.
Shift to Previous Shows the data for the previous Trend.
Shift to Next Shows the data for the next Trend.
Shift to Last Shows the data for the last Trend.
Select Day Period Opens the dialog to enter the start time and the time range.

Editing values
When the tabular view is active, it is possible to enter a specified Trend value manually.
To enter the value manually:
1. Right-click the specified value and select Edit value from the context menu or
double-click the value that needs to be edited. The Edit Value dialog is displayed.

Figure 9.27: Edit value dialog

2. The text fields of this dialog show the index, registration time, status and current
value of the selected registration. Type a new value into the Value field.
3. Click OK to change the new value to the Trend. To leave the value unchanged, click
Cancel.

137
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

The Status column text is changed to "Man. Entered".

Copying selected data to the clipboard


The data selection can be done by using one of the three methods:
1. To select the successive values, click the first row of the reported item to be selected,
press the SHIFT key down and click the last row of the reported item.
2. To select the specific values, click the first row of the reported item to be selected,
press the CTRL key down and click more specific rows of the reported items.
3. To select all, press CTRL+A.

When the selection is done, select the appropriate button from the Main toolbar or
press CTRL+C.

When pasting the selection to the clipboard, the data is divided into several sections,
where each section has a header and contents of each selected report item.

9.6 Preconfigurations
The current Trend settings can be saved in a preconfiguration (see Figure 9.28). The
following properties will be saved:
• Background color of the graphical form
• Colors and styles of the X and Y axes
• Text fonts of the axes
• Trend curve colors and styles
• Trend curve marker colors and styles
• Trend curve title fonts
• Visibility and position of the legend in the graphical view
• Visibility of the Trend curves
• Auto scaling of Y axes
• Type of the curves in the graphical view
• Legend settings
• Curve properties from global settings selection
Saving the current Trend settings can be done by selecting Main > Save, or by clicking

the appropriate Main toolbar button . The Save Preconfiguration dialog is displayed,
see Figure 9.28.
To create a new preconfiguration, a new name must be entered in the Name field and it
must be saved.
To replace an existing preconfiguration with the current Trend settings, the existing
preconfiguration name must be selected and Save button clicked.

138
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 9.28: Save Preconfiguration dialog

All the saved application specific preconfigurations are available for all users working
with a certain application. Each user can save individual preconfigurations by selecting
the User specific preconfiguration visibility checkbox.
The Monitor Pro Menubar item Navigate > Trends shows all available preconfigurations.
All the application and user specific preconfigurations are displayed as a submenu of
this command. User specific preconfigurations are only visible for the creator of the
preconfiguration.
Additionally, it is also possible to open preconfigurations using the appropriate button

from the Main toolbar. The Open Preconfiguration dialog is displayed. On


appropriate preconfiguration name selection and clicking the Open button the
preconfiguration is loaded and all the parameters are applied to the Trends Display.
To delete an existing preconfiguration the name must be selected in the Save
Preconfiguration or Open Preconfiguration dialog. Clicking the Delete button will
remove the preconfiguration.

9.7 Exporting Trends


It is possible to save the selected Trend data to a file in .CSV format. In .CSV format,
the separator between the columns is retrieved from the system settings. It can be changed
in Windows control panel > Region and Language > Additional settings... > Customize
Format numbers tab > List separator.
To export data:

139
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

1. Select Export item from the Trends menu or from the right-click context menu.
The Save As dialog opens.
2. Select a folder and file name for the selection.
3. Click the Save button to export the data.
The exported text file contains the header information, curve statistics and curve values.
A curve value includes an index, the time, value, and status.
To open the export file with e.g. Microsoft Excel, select Format > Cells > Text (in the
Category list) to display the format correctly.

9.8 Printing Trends


Printing the Trend data either in the tabular view or in the graphic view can be done by
selecting Main > Print from the menubar or by clicking the appropriate button from the
Main toolbar. The current Trend registration values are printed as shown on the left
side list of the tabular form. The Trend information from the right side of the tabular
form will be printed on the last page.
When printing from the graphic view, the printout is exactly the same as shown in the
graphical view at that moment. The legend information will be printed on the last page.

9.9 Authorizing
Trends Display follows the authorization concept of MicroSCADA Pro. The authorization
level is checked from the authorization group TrendS. If this authorization group does
not exist, the authorization level of the group GENERAL is used.
The following functions in the Trend views require at least Control (1) authorization
level:
• Changing Graph Settings
• Manually entering values

To be able to clear the Trend data, the Engineering level (2)


is required.

140
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

10 Measurement Reports

Measurement Reports provide an interface for showing measured values for further data
analysis in the application. It can be used for monitoring time related follow ups of the
process as well as measured or calculated data. It shows the history of these values and
the entering values. The reports are meant for various types of time related reports, for
example hourly, daily, weekly, monthly and yearly reports.
Generally, all types of data can be illustrated as reports. All data for the reports is
calculated and stored in real time. The report data is collected and calculated cyclically.
The most common method is to collect raw data from the process, refine it and store it
in the report database. Measurement Reports can be used, for instance, in reporting the
following:
• Energy (active, reactive)
• Current (for example bay level)
• Voltage (for example bay level)
• Frequency
• Temperature
• District heating
All data values in the report can be presented either in tabular (numerical) or in a graphical
view. The contents and the reprocessing of data has been defined during the configuration
of the Measurement Reports, which is described in the Application Design manual.
During runtime, the collected data may be updated due to the following reasons in the
application:
• At predefined time intervals
• As a calculation result
Measurement Reports contain the following features:
• All types of process objects illustrated as reports
• All types of process objects illustrated as reports- demo
• Graphical or tabular view modes
• Zooming mode
• Scrolling with scroll bars and panning
• Configurable axes and line properties
• Using legend and hairline
• Report types with different time resolution (hourly, daily, weekly, monthly, yearly)
• Quick report type with different time resolution (hourly, daily weekly, monthly,
yearly)
• Load duration curves
• User specific and application specific preconfigurations

10.1 Starting Measurement Reports Display


Start Measurement Reports by selecting Navigate > Measurement Reports and select
the appropriate report type (see Figure 10.1).

141
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 10.1: Default opening of the Measurement Reports displays

The Measurement Reports menu structure is dynamic and application/customer specific.


It may differ from the example shown in Figure 10.1.

10.2 The user interface


The report data can be presented in a tabular or in a graphical view. These two views
share the same report database. Both views also share some of the toolbars and the
Measurement Reports menu. In addition, some basic information about the selected
Measurement Report display will be shown in both views.

10.2.1 Measurement Reports Display toolbars

Measurement Reports has four toolbars. Three toolbars are used for both views and one
is dedicated for the graphical view.
With the first Measurement Reports start all toolbars are visible. Toolbars can be shown
or hidden through the Settings > Customize mode. It is possible to add or remove buttons
on the toolbars the same way as described in Section 3.4.2 Changing application layout.
The Measurement Reports Main toolbar buttons from left to right are as follows:
• Open Preconfiguration
• Save Preconfiguration
• Print Display
• Copy to Clipboard from Selected Display
• Find in Selected Display

142
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

• Show Display Settings


• Show Help

Figure 10.2: Main Toolbar

Table 10.1: Main Toolbar functions


Function Description
Open Display Preconfiguration Opens the Open Preconfiguration dialog.
Save Preconfiguration Opens the Save Preconfiguration dialog.
Print Prints the selected report to a network printer or a specified
output file.
Copy to Clipboard Copies the selected visible report data to the operating system
clipboard.
Find This function is disabled for the Measurement Reports views.
Display Settings Opens a sub-menu with the following items:
- General Legend Settings...
- Graph Settings...
- Legend layout Settings...
Help Opens the Help dialog.

The Measurement Reports display toolbar buttons and drop-down lists from left to right
are as follows:
• Switch updating/frozen mode
• Refresh
• Show/hide report data
• Switch tabular/graphical view
• Select report page
• Select time interval

Figure 10.3: Display Toolbar

143
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Table 10.2: Display Toolbar functions


Function Description
Switch between updating and frozen mode
indicates the update mode as active
mode. Clicking this button will change to the
frozen mode.

indicates the frozen mode as active


mode. Clicking this button will change to the
update mode.
Refresh Forces a display refresh.
Show/hide report data (curves) Open the show/hide dialog, where the user can
select which data to show in the current view.
Switch tabular/graphical view

The graphical view is active. Clicking


this button will change to the tabular view.

The tabular view is active. Clicking this


button will change to the graphical view.
Select report page The items to select with this drop-down list are
different depending on the selected Report dis-
play type.
For configured standard Report pages:
contains all existing and configured pages for
the selected Measurement Report display.
For Quick-Reports pages:
contains all existing Quick-Report preconfigura-
tions for the selected Quick Report display.
The * character indicates the default configura-
tion used in the selected Quick Report display.
Select time interval This drop-down list is only enabled for the hourly
base Quick Report display. It contains a list of
all used sampling time intervals.

The Measurement report Navigation toolbar buttons from left to right are as follows:
• Go to first available period
• Go to previous period
• Go to next period
• Go to last available period
• Select period

Figure 10.4: Navigation toolbar

144
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Table 10.3: Navigation toolbar functions


Function Description
Go to first available period Navigates to the first available period in the re-
port. If the current period is already the first, the
button will be dimmed.
Go to previous period Navigates to the previous period in the report.
If the previous period is outside the history area,
the previous period button will be dimmed.
Go to next period Navigates to the next period in the report. If the
next period is outside the history area, the next
period button will be dimmed.
Go to last available period Navigates to the last available period in the re-
port. If the current period is already the last, the
button will be dimmed.
Select period Opens the Select Date dialog from which the
target period for the report can be selected.

Browse backwards and forwards in time by one hour, day, month or year at a time. The
browsing interval is related to the time relation of the report type. To browse backwards,
click the previous hour/day/week/month (arrow left). To browse forward, click the next
hour/day/week/month (arrow right). The same selections can be made from the menu
bar. The values from the previous or next interval are fetched and displayed.
Select a specific hour, day, month or year in the Select Period dialog. The selection is
related to the time relation of the report type. To open the Select Period dialog, click the
date sheet symbol.

10.2.2 Measurement Reports Display menus

The toolbar commands can be selected from the Measurement Reports menu (see
Figure 10.5 and Figure 10.6). Some of the menu items are active only for the graphical
view.

145
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 10.5: Measurement Reports menu for the tabular view

The menu for the tabular view contains the same commands as the toolbars.

Figure 10.6: The Measurement Reports menu for the graphical view

In addition to the toolbars, the following functions are available from the menu:
• Show/Hide Hairline
• Load duration curves
• Export...
For more information about the commands, see Section 10.3 Graphical view.

146
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

10.2.3 Measurement Reports Display header

The header contains the following information fields from left to right:
• Period field
• Measurement Unit information

Figure 10.7: Measurement Reports header

The Period field gives information about the date/time range for the current visible data.
The field content depends on the current active report type:
• For hourly and daily reports the current active day, as shown in Figure 10.7.
• For weekly reports the current active week.

• For monthly reports the current active month.

• For yearly reports the current active year.

10.3 Graphical view


In the graphical view, up to twenty measurements can be presented on a two dimensional
coordinate system that consists of a horizontal time (X) axis and a vertical value (Y)
axis. The curves can be panned both in the X and Y directions and the parameters of the
Y axis can be changed. All the curves can be hidden from the view with the dialog.
The horizontal (X) axis of the graphical view represents the time of the measurement,
and the vertical (Y) axis represents the value of the measurement. The X axis is divided
into intervals specific to the related period. The time of every interval point is labeled
below the X axis. The amount of the shown interval points depends on the zooming
level.
The Y axis is automatically divided into intervals according to the registered values. The
quarter point values of the Y axis are marked on the left side of the Y axis.

147
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

The graphical view does not recognize any units or scales, only
the values registered in the report database. To avoid confusion,
curves with different units should use different Y axes.

Figure 10.8: Graphical view

The graphical view has the following functional areas:


• The plot area where the report data will be shown.
• The legend area shows part of the visible curve properties (optional, can be hidden
with the dialog).
For the plot area, the following curve typesFigure 10.8 can be chosen:
1. Plot (default)
2. Area (fills the area between two selected curves or between a curve and the X or Y
axis)
3. Bar
4. Stacked bar

148
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

The curve type can be configured with the dialog.


The legend show up can be disabled with the dialog or from the Measurement Report
menu. The legend area shows for all visible curves the following default information:
• Column title (Report object name)
• Line color
• Marker shape
• Registration time and value for the last available from the selected view
• Hairline value
• Selected Y axis for enabled curves
• Summary information as e.g. minimum and maximum value.
The legend position can be changed with the dialog or in Help of the legend context
menu.
The graphical view has the same main functionality as used for the Trends Display.
Information about:
• Scrolling, panning and zooming
• The Hairline function
• The Graph settings
• The Legend
can be found in Section 9.4 Graphical view.

Load duration curves


It is possible to toggle between load curves and load duration curves in the graphical
form. The Load Duration Curves mode can be enabled from the Measurement Reports
menu.

10.4 Tabular view


In the tabular view, up to fifty measurements can be presented at the same time.
Recommendation is to not use more than twenty. Each measurement is shown in an
individually configured report column.
The tabular view contains the following columns:
• Comment column
• Time column
• A set of report data columns
• A set of summary information columns
The default accuracy of the report columns is two decimals, but it may be individually
set for each column during the report configuration.
If a measurement data registration has an uncertain or an obsolete status, the corresponding
cell is represented with the character "?" (see 1. in Figure 10.9). Manually entered values
are indicated with the character "m" (see 2. in Figure 10.9).

149
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

If a measurement data registration is not sampled or has an erroneous status, there is no


value available (see 3. in Figure 10.9).

Figure 10.9: The Tabular view

The measured column shows the report data as defined in the Report Page Configuration.
The measurements can be based on the measurements of the process, manually entered
or calculated values.

150
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

General settings
The General Settings dialog can be opened either by clicking the appropriate Main

toolbar button or by selecting Settings > Display Settings.

Figure 10.10: General Settings

Table 10.4: Tabular view, General Settings


Settings Description
Show gridlines Enable/Disable gridlines for tabular data area
Time range If selected the period start and end time will be shown in the
time column else only the period start time
Background shading Enable/Disable the row shading effect
Set Font Font style and size used for the tabular data area
Context menu items Configure the context menu items for the tabular data area
Visibility Visibility is configured to be either Application or User specific

Daylight saving leap hour data


All data sampled and calculated during the one hour transition from daylight saving time
to standard time will be stored on a separate location and made available in all DAY
reports as shown in below figure.

151
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 10.11: Leap hour data presentation

The data from that extra hour are also included in the summary information calculation.

152
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Time column
The following figures show and explain the different time column formats based on the
selected Report Display base type.
Hour report, time interval 3 minutes
The indication in the time column is shown as time, for example
11:03 or 11:06.
The time indicates the period begin.
In the example to the left, "11:00 -" indicates the period from
11:00 to 11:03.
The sampling time for this period was at 11:03.

Day report, 15 minutes period


In the daily reports, the time resolution is 15, 30 or 60 minutes.
The indication in the time column is shown as time, for example
00:00 or 00:15.
The time indicates the period begin.
In the example to the left, "00:00 -" indicates the period from
00:00 to 00:15.
The sampling or calculation time for this period value was at
00:15.

Week report
In the weekly reports, the indication in the time column is the
day of the week, for example Monday or Tuesday.

Month report
In the monthly reports, the indication in the time column is the
day of the month, for example 1, 2 or 3.

153
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Year report
In the yearly reports, the indication in the time column is the
name of the month, for example January or February.

For hour and day reports, the time column can be configured in a way that the start and
the end time of each period will be shown. This can be done in help of the "Time Range"
parameter in the General Settings dialog.

Editing values
Data included in the measurement reports can be edited in the tabular view with the Edit
Value dialog, if an appropriate command is accessible in the user's authorization.
Manually edit value is only possible in Day report displays where the interval is equal
to the Report Object base period. If, for example, Report Object base period is 15 min,
then editing is only enabled in Day report displays with a 15-minute interval time.
The edited values are stored into the report database, and other values, for example
calculated values that depend on it, are automatically recalculated using the new value.
To enter the data registration manually:
1. Right-click the item in the report column and select Edit value from the context
menu. The Edit Value dialog is displayed.

2. The text fields of this dialog show the registration time and status, and the existing
value of the selected registration. Type a new value in the Value field.

3. Click OK to change the new value to the measurement report. To leave the value
unchanged, click Cancel.

The color of the measurement and status field is changed


to indicate that the data registration has been manually
entered.

154
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Adding comments
A comment can be added or removed with the Comment dialog. The comment is attached
to one row.
To open the Comment dialog, click the time column in the tabular format. The comment
is saved to a file and the note is indicated with an exclamation mark next to the time
column.

Figure 10.12: The Comment dialog

Copying selected data to the clipboard


See Copying selected data to the clipboard, on page 138.

10.5 Preconfigurations
The current Measurement Report settings can be saved in a preconfiguration. The
following properties will be saved:
• Background color of the graphical view
• Colors and styles of the X and Y axes
• Colors and styles of the measurement curves
• Visibility of the legend in the graphical view
• Visibility of the measurement curves
• Auto scaling of the Y axes
• Type of the measurement curves in the graphical view
• Column widths of the tabular view
• Legend settings
Clicking the Default button in the Open Preconfiguration/Save Preconfiguration dialog
will load the default graph, legend and legend layout settings.
Otherwise the preconfiguration handling for Measurement Reports works in a same way
as for Trends, see Section 9.6 Preconfigurations.

155
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

10.6 Exporting Reports


The selected report page can be saved to a file in .CSV format.
It is possible to save the selected Trend data to a file in .CSV format. In .CSV format,
the separator between the columns is retrieved from the system settings. It can be changed
in Windows control panel > Region and Language > Additional settings... > Customize
Format numbers tab > List separator.
1. Select Export from the Measurement Reports menu. The Save As dialog is opened.
2. Specify the folder and the file name.
3. Click Save to export the data.
The exported text file contains the header information, the report time period, the unit
information and the report data. When opening the export file with Microsoft Excel,
select Format > Cells > Text (in the Category list).
This way the time format will be displayed correctly.

10.7 Printing Reports


Printing the Report data either in the tabular view or in the graphic view can be done by
selecting Main > Print from the menu bar or by clicking the appropriate button from
the Main toolbar. The summary information from the bottom of the tabular form will
be printed on the last page.
When printing from the graphic view, the printout is exactly the same as shown in the
graphical view at that moment. The legend information will be printed on the last page.

10.8 Authorizing
Measurement reports follow the authorization concept of MicroSCADA Pro. The
authorization level is checked from the authorization group REPORTS. If this
authorization group does not exist, the authorization level of the group GENERAL is
used.
The following functions in the Report views require at least authorization level 1:
• Add, remove or edit comments
• Manually enter values

10.9 Quick Reports


Quick Report is essentially a report browser, which is able to show all the report objects
defined within the report application. The objects to be shown at a time can be selected
through the Show/Hide Curve dialog.

156
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

The current Quick Report configuration can be saved with a unique name and is available
from the report page selection box.
Quick Reports are available on hourly, daily, weekly, monthly and yearly basis. The
report data can be viewed both in tabular and in graphical form.

157
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

11 System Self Supervision

System Self Supervision (SSS) is used in MicroSCADA Pro systems for supervising
and monitoring the system. It provides status information of hardware and software using
the supervision symbols of SYS600.
The System Self Supervision consists of:
• supervision application objects
• supervision monitoring symbols and control dialogs
• supervision events and alarms
• supervision logging
The supervision application objects provide the source for supervision state and status
information. The supervision information is shown in the Event and Alarm lists. Typically,
additional system supervision display has been designed for MicroSCADA Pro system
supervision purposes. Figure 11.1 shows the System Self Supervision dedicated symbols
and statuses, which can be found from such a system supervision display. The supervision
information is displayed in the supervision display by supervision monitoring.

Figure 11.1: An example of a typical system supervision display

159
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

11.1 Supervision application objects


The main function of the supervision application objects is to provide the information
source for the objects to be supervised. These application objects provide information
for supervision monitoring symbols, appearance of information as events and alarms in
the appropriate lists. Additionally, these application objects are involved in supervision
logging.

11.2 Supervision monitoring symbols and control dialogs


The main function of supervision monitoring is to provide the visual information about
the supervised objects in a user friendly way. Supervision symbols are reflecting the
states and statuses based on usage of coloring. For example, green color typically indicates
a good object status, whereas red color indicates a failure status. The alarming supervision
symbols are indicated by a blinking red color.

11.2.1 Supervision symbols

About 50 symbols have been designed for system supervision purposes. These symbols
are updated either as event based or time based manners by the runtime logic of
supervision application objects. This way, the supervised object gets visualized by the
real world object state and status in the system.
For example the following supervision symbol categories are available:
• System server
• Application
• Communication unit
• Station (IED)
• Workplace
• Computer accessories
• Network equipment
• Status
These supervision symbols are installed into the system supervision display using Display
Builder. For information on the characteristics of all supervision symbols, see SYS600
Process Display design manual.

11.2.2 Symbol appearance

Principles for supervision symbol visual design are general and used for all supervision
monitoring symbols. Some supervision symbols have both the dynamic and static
appearance as indicated in Figure 11.2.

160
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 11.2: Dynamic and static appearance of supervision symbols

A supervision symbol contains these appearances:


1. Dynamic state (circle) and status (rectangle) color indicators.
2. Static identification drawing of an object.
3. Dynamic identification text of an object.
The dynamic appearance contains both the state and status indicator of an object.
Supervision state is indicated by a green or red circle. The rectangle part of the dynamic
indicator shows the status of the supervision symbol. For example, a blinking red color
indicates an alarm, which has not yet been acknowledged by the operator. The following
table lists the typical states and statuses that may appear for supervision symbols.
Table 11.1: States and statuses for supervision symbols
State and Status Indic- Description
ator
Good status
In good status the symbol is static green.

Failure status with non-alarming


In failure status the symbol background is blinking red.
The cause for the failure status should be analyzed and corrective
actions should be taken.
Good status with Invalid Time
In good status the symbol is static green.

Unknown status
In unknown status the symbol is static magenta.
The cause for the unknown status should be analyzed and corrective
actions should be taken.
Warning status (warning limit has been exceeded)
In warning status the symbol is static yellow.
The cause for the warning status should be analyzed, because over
time this object may change to failure status.
Good status with unacknowledged alarm
Symbol has been in the alarming state, but not anymore. Acknowledge-
ment of alarm will change the symbol to Good status.

161
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Failure status with unacknowledged alarm


Symbol is generating an alarming state, which is still active. Acknow-
ledgement of alarm will not change the symbol to good status. The
cause for the failure status should be analyzed and corrective actions
should be taken.
Failure status with acknowledged alarm
Symbol is generating an alarming state, which is still active. Alarm has
already been acknowledged, but the cause for the failure status should
be analyzed and corrective actions should be taken.

Association to the real world object is achieved with the static part of symbol. For
example, for Station supervision, there is a variety of IED products available. Additionally,
it is possible to include a Station symbol, if needed. The available supervision symbols
for IED products are shown in Figure 11.3.

Figure 11.3: Supervision symbols for IED products

11.2.3 Supervision control dialogs

Supervision control dialogs are opened when the appropriate symbol in the supervision
display is clicked. These dialogs have been designed to provide more information about
the selected supervision object. Additionally, it is possible to perform the supervision
related control operations, for example, sending general interrogation command to Station
(IED) or activating the take over in HSB system. Supervision control dialog contents
and authority handling for control operations can be configured.
For example, the following control dialogs are available:
• Base System Supervision
• Application Supervision
• Communication Node Supervision
• Communication Line Supervision
• Station Supervision
• SNMP Supervision

11.2.3.1 Common characteristics

Supervision control dialogs have common characteristics, such as the Power Process
control dialogs. An example of Station Supervision is shown in Figure 11.4. By default,
dialog shows the Main tab. The selected supervision object is indicated in the dialog

162
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

title and the Object Identification field. Detailed attribute information is shown in
Attribute and Value columns. The dialog can be expanded by using the >> button.

Figure 11.4: An example of a supervision control dialog

When the dialog is expanded, additional tabs appear, see Figure 11.5. By using the tabs,
it is possible to perform supervision control operations, especially in the Control tab.
The supervision alarms for the selected object are listed in the Alarms tab. In this tab,
it is possible to acknowledge selected or all alarms. Also other tabs may exist, for example
Diagnostics, where typical operations are resetting the counter values with the appropriate
buttons.

163
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 11.5: Expanded station supervision control dialog

11.2.3.2 Application supervision

The appearance of the control dialog for application supervision depends on the type of
system. The Main and Diagnostics tabs are shown only for the single system, whereas
the Shadowing and Forced Takeover tabs appear for a redundant system.
The Diagnostics and Shadowing tabs provide more detailed information about the
application counters. In the Forced Takeover tab it is possible to activate the forced
takeover.

164
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 11.6: Application supervision control dialog

11.2.3.3 Communication Node supervision

There are control dialogs available for both PC-NET and IEC 61850 nodes. By default,
the same attribute information is shown in the Main tab. Additionally, for PC-NET
communication nodes, it is possible to expand the dialog to get details of each
communication line.

Figure 11.7: Communication node supervision control dialog

165
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

11.2.3.4 Communication Line supervision

Communication lines for PC-NET are shown when the PC-NET Node Supervision
control dialog is expanded. Attributes for communication lines configured for selected
PC-NET node are shown in separate tabs with attribute and value descriptions (for
example, the Line 5 tab).

Figure 11.8: Communication line attributes

Communication line diagnostics can be monitored on the dedicated tabs, for example
the Diagnostics 5 tab. This tab shows Index, Diagnostic Counter and Value information
for the selected communication line. Clicking Reset or Reset All clears the value
information either for the selected diagnostic counter or all counters at the same time.
Clear to Send and Carrier Detect items indicate the communication status for serial
communication lines. These items are not visible to the TCP/IP communication lines.
All information shown in this tab is cyclically updated.

166
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 11.9: Communication line diagnostics

In the Control tab it is possible to set communication lines either out of use or in use.
It is also possible to stop or start the PC-NET Node communication from that tab, too.
See Figure 11.10 for details.

Figure 11.10: Communication line control

11.2.3.5 SNMP supervision

The appearance for SNMP supervision control dialog depends on the type of the SNMP
device. Simple Network Management Protocol devices are able to provide information
about them in the internet protocol network via network management protocol. Such

167
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

devices are: servers, printers, hubs, switches and routers. An example of Network Switch
with 8 ports is shown in Figure 11.11. When the dialog is expanded, the alarms for the
device are shown and control operations can be performed by using the Ack. selected
and Ack. All buttons.

Figure 11.11: Network switch supervision control dialog

The appearance of attributes shown for the SNMP device is configured via device
templates. For more information, see SYS600 Application Design manual. By default,
the following device templates are found:
• Network switch
• GPS
• Computer
• Printer

11.3 Supervision events and alarms


System Self Supervision events and alarms in the system can be monitored in the Event
and Alarm Displays. Events and alarms of each supervised object are generated according
to the supervision event filtering specified during the configuration. For more information
about the filtering, see SYS600 Application Design manual.

168
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Figure 11.12: Supervision events and alarms

In case of an alarm, the supervised object causing an alarm can be found from the Alarm
Display. This alarm indicates the existing state of the supervised object and it gets changed
to the normal value as the supervised object receives the normalized event. The reason
for causing the alarm in system can be found from the Event Display, for example Device
stopped [13918].

Filtering supervision events and alarms


It is possible to define a filter condition that filters out all other events and alarms except
the supervision related events and alarms shown in Alarm and Event Displays. In Event
Display, selecting Event > Filters opens the Filter Settings dialog. Define the settings
as shown in Figure 11.13. Click OK to apply the filter definition and close the dialog
window.

169
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 11.13: Filter Settings for Supervision information

11.4 Supervision logging


In addition to the supervision information appearance in the Event and Alarm Displays,
each supervision object event can be logged into the supervision log file. These events
are collected according to the supervision event filtering configuration and stored in the
file system. For more information about the configuration for supervision event filtering
and logging parameters, see SYS600 Application Design manual.
In addition to the Event and Alarm Displays, the supervision information can also be
found from Supervision Log Viewer, when configured accordingly in MicroSCADA
Pro system.

11.5 Supervision Log Viewer


Supervision Log Viewer is used for monitoring the supervision information logged into
different log files. These files contain information about the supervision events related
to the system software and hardware.
Supervision Log Viewer contains the following features:
• viewing common system messages of MicroSCADA Pro system
• viewing unknown process object messages of MicroSCADA Pro system
• viewing Windows Operating System events

170
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Starting tool
Supervision Log Viewer can be started from the menu bar by selecting Tools >
Supervision Log. When the tool gets started, it shows the contents of logged information
at that moment. To update the view, select View > Refresh to get the tool reflected by
the latest collected information. An example of the Supervision Log Viewer main view
is shown in Figure 11.14.

Figure 11.14: Main view

171
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

12 Sequence Executor

SYS600 Sequencer offers creation, execution and monitoring of switching device


command sequences in MicroSCADA Pro. Sequencer has two separate tools one for
creation and configuration of sequences (Sequence Configurator) and another tool for
execution of sequences (Sequence Executor). This chapter describes sequence execution
and monitoring using Sequence Executor. More details regarding Sequence Configurator
tool can be found from SYS600 Application Design Manual.
A sequence is a collection of one or more steps (commands) for switching devices.
Currently, the supported commands for sequence executions are switching device open
or close commands and a custom message to display. For instance, opening a circuit
breaker can be considered as one step in a sequence.

12.1 Launching the tool


Sequence Executor can be launched directly from Monitor Pro by selecting Tools >
Sequencer as shown in Figure 12.1

Figure 12.1: Launching Sequence Execution Tool in Monitor Pro

Note! Sequencer menu item is not shown in the menu if the sequencer is missing or not
enabled in the applied license or the sequencer package is not installed.

173
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

12.2 User Interface


By default, Sequence Executor shows an empty view with no sequence selected. A
pre-configured sequence can be selected from the Sequence drop down menu to view
the sequence steps and execute a sequence.

Figure 12.2: Sequence Executor showing the tool’s layout and an opened sequence

Description of the tool layout shown in Figure 12.2 are described in Table 12.1
Table 12.1: Description of Sequence Executor Tool layout
Or- Item Name Description
der
1 Menu bar Contains the tool menus
2 Toolbar Contains the toolbar buttons of sequence executor
3 Step numbers Shows the step numbers in order
4 Descriptions of steps Describes the steps as configurd using Sequence Configurator
tool
5 RC (Require Confirma- Checkboxes for selecting or deselecting user confirmation during
tion) step executions
6 Operation buttons sec- Contains buttons that are used for sequence execution, step se-
tion lection, skipping a running step and aborting a sequence
7 Status bar Contains buttons that are used for sequence execution, step se-
lection, skipping a running step and aborting a sequence
8 State of steps Shows the states of the step executions using the symbols de-
scribed in Figure 12.5

174
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

12.2.1 Menu bar

The menu bar in Sequence Executor consists of different menus including the
commands/functions in the toolbar. The menus are shown in Figure 12.3 below and the
menu and menu items are described in detail in Table 12.2

Figure 12.3: Sequence Executor’s Menu bar

Table 12.2: Sequence Execution Tool’s menu bar functions


Menu Function Description
File Exit Exits Sequence Configurator Tool
Sequence Controllability Check Executes controllability check to make sure
that each switching device included in the
sequence can be controlled (See Controllab-
ility Check Section)
Execution Log Shows detailed log or report of the last se-
quence execution (See Status and Outputs
Section)
Queue Queue State Opens Queue State dialog that shows the
tabular summary of sequences running or
waiting in the execution queue
Stop All Aborts the running sequence and removes all
waiting sequences from the execution queue.
If aborted by an INT user, all sequences
triggered by other triggers will also be stopped
Help About Information about the tool and system

12.2.2 Toolbar

Sequence Executor toolbar, shown in Figure 12.4, consists of three different functions.
The descriptions of the toolbar functions are described in Table 12.3 below.

Figure 12.4: Toolbar in Sequence Executor

Table 12.3: Sequence Execution Tool’s Toolbar functions


Function Description
Queue State Opens Queue State dialog that shows the tabu-
lar summary of sequences running or waiting in
the execution queue

175
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Function Description
Queue/Stop All Aborts the running sequence and removes all
waiting sequences from the execution queue.
If aborted by an INT user, all sequences
triggered by other triggers will also be stopped.
Sequence Selection Enables users to select a sequence from a list
of configured sequences. After selecting a se-
quence from the drop down list, the following
information is shown on the text field:
<OI of the bay>/<The name of the se-
quence>/<Sequence number>
If the sequence consists of steps from different
bays, <OI of the bay> will be substituted by <*>.

12.3 User Authorizations


Execution of sequences requires at least Level 2 Authorization Level. However Level 1
is enough for View Only rights for a running sequence.

12.4 Executing a Sequence


Sequences execution may require user confirmation. If the sequence steps are configured
to require user confirmation the user has the possibility to choose one of the following
actions after each step:
• Continue Sequence from next step
• Skip step
• Go to step to continue the execution from specified step
• Abort Sequence
To execute a sequence:
1. Select a sequence from Sequence drop down list in the toolbar.
The sequence opens with a list of steps having sequence number, description and
RC (Require Confirmation) checkboxes. An empty Sequence drop down list shows
that there is no sequence to execute.
2. Select/Clear the checkboxes in RC column (Optional)
By default the RC checkboxes are set according the sequence configuration. To
toggle whether the user confirmation is required for the step, select/clear the
checkboxes in RC column. You can also select/clear all the checkboxes in the column
by selecting/clearing the RC checkbox in the column header.
Steps are executed without user confirmation when the checkboxes are clear. A
selected checkbox shows that the step requires an interactive user confirmation.
3. Click on Start Sequence button to start sequence execution from the beginning/from
the first step.
4. To start from a step other than the first step, click on GOTO STEP button and select
a step to begin with. Press START SEQUENCE to start sequence execution from
the selected step.

176
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

After sequence execution starts, the active step (the step under execution) is
highlighted in yellow
5. Click on Abort Sequence button to abort/cancel sequence execution
Note! In addition to an interactive user, sequences can be started from internal and
external triggers. Internal triggers include event channel and Schedule function of the
MicroSCADA Pro Calendar. Using external triggers, the sequences can be started from
an NCC via COM500i functionality or from DMS600.

12.5 Statuses and Outputs


Sequence states are shown in the status bar indicated by number 7 in Figure 12.2
The tool shows the following sequence status information:
• Number of sequences in the execution queue
• State of sequence execution in status bar: Disabled, Ready, Running, Paused
• Current selected sequence with their ID (ID_APL) and name
• Description for every sequence step
The states of each step during sequence execution are indicated with different symbols.
These symbols are located in front of each step (see section 8, State of steps, in
Figure 12.2).
The description of the state of steps and the corresponding symbols are shown in
Figure 12.5

Figure 12.5: State of Step and corresponding symbols

Sequence Execution Log


Sequence Execution Log dialog shows the detailed log or report of the last sequence
execution. The log includes the following information regarding the sequence:
• Time stamps
• Step number
• Step names
• Event texts for each step
• User Type

177
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

• User names
• Execution result (E.g. successful/unsuccessful completion of sequence execution
or error)
Select Sequence>Execution Log from the tool's menu to open the Figure 12.6 as shown
below

Figure 12.6: Sequence Execution Log

12.6 Sequence Queue


Only one sequence can be executed at a time. The maximum numbers of sequences that
are allowed to be in a queue for execution are five. See Figure 12.7 Queue State Dialog
Note! Only the non-interactive execution of sequences are queued. It is not possible to
queue interactive user sequence execution.

Figure 12.7: Queue State Dialog showing three pending sequences

To view the queued sequences:

178
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

1. Click on Queue State button in the tool bar or Select Queue > Show State from
the menu to open the Queue State dialog.
The queue state dialog shows all sequences in the queue with their number , user
name and user type..
2. Click on Stop All button to abort all the active and pending sequences in queue.

12.7 Controllablity Check


Every step in a sequence must be controllable beforehand. Before any sequence execution
is started, the sequencer function executes controllability check to make sure that each
switching device included in the sequence can be controlled. The controllability check
is repeated for each particular step command of the sequence. The progress of the
sequence execution can be monitored and controlled in Sequence Executor. Controllability
of steps is also checked when opening a new sequence. The Sequence Controllability
Check dialog opens if one or more steps are not possible to be executed/controlled. See
Figure 12.8
Sequence Controllability Check dialog can also be launched by selecting Sequence >
Controllability Check from the main menu.

Figure 12.8: Controllability Check Dialog showing a failure due to station local/remote switch
inhibition of control

179
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

13 Using Calendar

Calendar is a tool for defining features or activities that depend on time.


Time periods can be applied, for instance, to define day and night tariffs, to specify
contracts that are in force, general holidays, and so on. Calendar data can then be utilized
by other functions, for example by the measurement reports.
It is possible to use the Calendar to define command procedures which are to be run on
a defined day or on all days that are marked as a certain type of day. Default day settings
are available either for all days or for workdays and Sundays separately.
Settings that determine the operations or properties which will take place at a certain
moment of time, are defined in a day specific graphical attribute list. The attribute list
is maintained by using an attribute tool that is integrated into the calendar. Each attribute
has a graphical user interface of its own on the list.
Individual days can be configured independently with the attribute tool to have day
specific attributes. The attribute list can also be defined for the day type. The day type
is a logical name that can be used for connecting an attribute list to a day. All attributes
defined for a day type are then applied to all days that have a link to the day type. Fast
modifications can be performed simultaneously for several days by using the predefined
day types. New day types can be created freely.

13.1 Opening Calendar


Calendar can be started in the application main picture. Select Calendar in the Tools
menu.
The main calendar view is used for browsing general calendar information. The calendar
is divided into 12 months, one in every tabbed page. A month can be selected by clicking
the corresponding tab. The current day is marked with a red box (see Figure 13.1).

181
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 13.1: The Calendar tool

There are shortcuts in the toolbar for the most used commands. The commands are from
left to right:
• Previous Year
• Next Year
• Go to Today
• Go to Year X
• Select Day of the Week
• Select Week
• Select Month
• Add Day Type

13.2 Making selections


Multiple selections can be made when the Attribute dialog is not open. Close it before
making a multiple selection.
• Click a day in the Calendar to add the day into the selection.
• To deselect days, single-click the day label again. The current label state can also
be changed by pressing the Space bar. Opening the Attribute dialog by

182
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

double-clicking a day label also removes all other days selected except the current
day.
• Selection can be expanded by using the selection buttons in the toolbar.
• Any day type can be added to the selection.
• Any day type setting can be removed from the selection.

13.3 Adding day type to group of days


When a selection is made, a day type can be added to the day group. Select a day type
on the day type list and click Set. When the button is clicked, all the selection marks
disappear and the number fonts of the selected day change to bold to indicate that they
are provided with the relevant settings. If the day color is set on the day type attribute
list, all the days are marked with that color.
To remove a day type setting from a day, make a multiple selection, select the day type
to be removed and click Remove.... Another way to remove a day type setting is to open
the Edit day attributes dialog and to delete the corresponding day type block from the
attribute list.

13.4 Setting day type attributes


To set a day type attribute, double-click the day type item on the list containing the day
type names. This opens the Attribute dialog.
The day type attributes are defined in a similar way as the day attributes. The only
difference is the text box in the upper part of the dialog where the type name is displayed.
This name is also visible on the list of the main calendar view.
Changes made in the day type attributes are applied to all the days defined as that day
type.

13.5 Saving attributes


Save the attributes by clicking Apply. Not clicking Apply before selecting another day
will delete all the blocks containing invalid data. It is recommended to click Apply to
check the data validity before moving to another day or closing the dialog.
Saving is also done when Go to Today is clicked. This is the most recommended way
to save changes to the day or to day type attributes. When the Attribute dialog is closed,
data validity is checked and valid data is saved.

13.6 Changing current time


To step one year forward, click Next Year on the toolbar. Similarly, to move to the
previous year, click Previous Year. To move to any year between the years 1978–2045,
click the Go To Year and type the year into the Input dialog.

183
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

13.7 Setting day attributes


Set the day and the day type attributes by double-clicking the day label (day number).
The Edit day attributes dialog is then displayed (see Figure 13.2).
To add a new day attribute:
1. Click Outage New from the Edit day attributes dialog. A new block is added to the
attribute list.
2. New attributes can be added into the day profile by clicking Outage New. In the
subsequent dialog box, the type of the new attribute can be selected.
3. Click Apply after having edited the day attributes. The program checks the validity
of the data and saves the changes. If data is not valid, an error message will be
displayed.
Delete removes all the marked blocks. After having saved the attributes, the dialog can
be closed by clicking Close.
Help displays the attribute tool help text.

Figure 13.2: The Edit day type attributes dialog

A maximum of 10 attributes per day (or per day type) is allowed.

184
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Available attributes
The following attributes are used in the attribute tool. Some of the blocks are available
only for the day attribute list. Every block has a check box in the upper right corner. It
is used for selecting the block.
1. Assign type: Inserting this block into the attribute list of a day connects the day to
a day type. All the settings made for the named day type are then applied to the
current day. This block is available only for a day, not for a day type. All the day
types that are defined in the Options tool are visible in the drop-down list.

Figure 13.3: The Assign type dialog

2. Day name: A day is named with a given text string. The day color in the main
calendar view is selected with the help of the drop-down list. The block is available
both for days and day types.

Figure 13.4: The Day name dialog

3. Run command procedure: It executes a command procedure at a given time of


day. The running time is given with the time resolution of 1 minute. This block is
available both for days and for day types.

Figure 13.5: The Run command procedure dialog

4. Time period start/stop: This block is used to define periods which are in effect for
several days. The block is available only for days.

185
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Figure 13.6: The Time period start/stop dialog

5. In-day period: The block defines a period that starts and ends during the current
day 0:00-23:59. Time resolution is 1 minute. This block is available both for days
and day types.

Figure 13.7: The In-day period dialog

13.8 Changing calendar properties


Open the Calendar Properties dialog from the Options > Tool Properties... menu. The
dialog consists of three tabbed pages:
• General options
• Procedures
• Day types

186
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

General calendar options

Figure 13.8: General calendar options

Table 13.1: Available default day types


No Type
1 No default types
2 One default type which is applied to all days
3 Default types for Sundays and other days separately. Default types are selected from
the drop-down list where all the available day types are visible. The default type of an
individual workday can be overridden by assigning it to Sunday type. Likewise, Sunday
settings can be overridden with the day type of workday. If the default type of an indi-
vidual day is to be overridden, select the day from the calendar’s main view and assign
it to an appropriate day type.

To add more day types into the combo box, select the Day types tab and add new types
on the list.

187
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Procedures

Figure 13.9: Allowed procedures

Allowed procedures can be defined in the Procedures tab of the Calendar Options dialog.
On the right side of the Procedures tab are all the command procedures that exist in the
system, on the left side are the command procedures that are allowed in the calendar.
To add new procedures to the list of allowed procedures, select a procedure from the All
procedures list and click the << button. To remove a procedure from the list of allowed
procedures, select a procedure and click the >> button.
Allowed procedures are used by the Run command procedure calendar attribute. Only
allowed procedures are included in the combo box of the attribute (see Figure 13.5).
At least Engineering authorization level (2) is required to be able to modify the list of
allowed procedures. The list is initially empty but it will be filled according to the user's
above mentioned actions.

188
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Day types

Figure 13.10: Day type tab

To add a new day type:


1. Click the Add button.
2. Type a name for the day type. The day type is displayed on the list.
3. Save the changes by clicking OK.
To remove a day type, select a day type from the list and click Remove....

If a day type is removed, all references to that day type are


deleted from the calendar database.

189
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

14 Terminology

Term Description
Application All the processes and views included in an application. Normally an application
consists of an overview or a login dialog and several Process Displays and
application views.
Application dis- An application display gives the user an overview of the application. A Process
play Display is a picture, which shows a specific process in a station. In a very small
application they can all be the same.
Attribute Attributes contain the settings and definitions for the properties of the picture
functions. They are stored in the process data base.
Authorization Different users can have different access rights to the same picture functions
and processes.
Authorization Picture functions and application pictures can be grouped into authorization
group groups and thereby require a certain user authorization level.
Authorization Different levels of authorization give the users different types of access (view,
level control operations, system manager and so on.).
LIB 500 LIB 500 contains the needed base functionality for installing support packages
like LIB 510, LIB 5xx... LIB 500 also provides functions like Event Display, Alarm
Display, and Network topology coloring.
LIB 510 LIB 510 is a support package, which contains the library functions for using for
example MV process functions, Trends Displays, SPACOM Relay Setting Tool,
RED Relay Setting Tool, DR-Collector Tool.
Library function A library function is a function in a software package that is ready made and
only needs configuration of the attributes.
Menu item The available options that are listed when opening a drop-down menu.
MicroSCADA The whole operation from starting up the system, performing login, running the
session system with its customer application to ending the session.
MV process Medium Voltage functions like Circuit breaker, Transformer, Three state switch,
Station, Bay, and so on. Used as picture functions in the Process Displays.
Picture function The functionality is built in with the application picture presented on the monitor.
However, the application picture can contain one or several different picture
functions, as well as several similar ones (disconnectors, transformers, and so
on.).
Process Display An area where process specific functions are presented.
Specific area
Process data- A database, which contains the individual process objects and related attributes.
base
Process object One signal in the Process database (for example a disconnector position indic-
ation).
Process Display A type of an application picture containing process objects (for example MV
Process Display functions), which are connected to the processes. In the Pro-
cess Display, for example measurements, the states of disconnectors and
breakers are normally updated and switching devices can be operated.

191
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Representation The symbol used for a picture function, for example a circuit breaker, trans-
symbol former, measurement, and relay. The representation symbol is selected during
the configuration of the picture function.
Switching Devices in the MV process that can be operated (for example circuit breakers,
device three-state switches, and transformers).

192
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

15 Abbreviations

The following is a list of abbreviations the user should be familiar with. See also the
terminology table.
Abbrevi- Description
ation
Clut Color LookUp Table: a file where Display Builder saves the RGB (Red, Green,
Blue) values for each color in color palette.
DMS Distribution Management System
HDB History Database
HSI Human System Interface
IED Intelligent Electronic Device
MV Medium Voltage
NCC Network Control Center
SA Substation Automation
SCS Substation Control System
SSS System Self Supervision

193
1MRS758087 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2015 Operation Manual
Version: B/3.6.2015

Index

A
E
Acknowledge
All ................................................................... 101 Event activation .................................................... 82
Current page .................................................. 101 Event Display line ................................................. 81
Acknowledgement Dialog ................................... 106
Activation .............................................................. 82 F
Active acknowledged alarms .............................. 102
AI type process object ........................................ 100 Filters ............................................................ 85, 101
Alarm blocking .................................................... 104 settings ............................................................. 87
Alarm buffer ................................................ 103–104
Alarm classes ..................................................... 104
Alarm row ............................................................. 30
G
Alarm text line ....................................................... 99 Graphical view .................................................... 147
Allowed procedures ............................................ 188 Graphic view mode ............................................. 123
Analog measured value ...................................... 100
Assign type ......................................................... 185
Attribute list ......................................................... 181
H
Authorization level .............................................. 156 History Database (HDB) ....................................... 94
Available attributes ............................................. 185
I
B Incoming binary signal ........................................ 100
BI type process object ........................................ 100 Incoming process data ....................................... 103
Blocking Display toolbar ..................................... 108 In-day period ...................................................... 186
Internal events ...................................................... 94
C
Calendar ............................................................. 181
L
Color settings ........................................................ 90 Latest Alarm ....................................................... 101
Command procedures ........................................ 181 Logout ................................................................... 12
Communication failure ........................................ 100 automatic logout after inactivity ........................ 12
Current alarm situation ....................................... 103 time based logout ............................................. 12

D M
Day color .................................................... 183, 185 Measurement Reports ........................................ 141
Day name ........................................................... 185 Display Toolbar functions ....................... 120, 143
Day type ............................................. 182, 187, 189 Main Toolbar functions ................................... 142
Day type setting .................................................. 183 menu .............................................................. 145
DB type process object ...................................... 100 toolbars ........................................................... 142
Default day settings ............................................ 181 Measurements Reports
Defining filters ....................................................... 86 display header ................................................ 145
dialog Multiple selection ................................................ 182
Color Setting Tool ............................................. 77
DMS .................................................................... 193 N
Double indication ................................................ 100
Navigation toolbar .............................................. 145

195
SYS600 9.4 MicroSCADA Pro 1MRS758087

Operation Manual

Navigation toolbar functions ............................... 125 Signal .................................................................. 107


Network topology coloring .................................... 78 Starting
Alarm Display ................................................. 100
O Station (process) picture ................................ 14–15
Status bar ............................................................. 31
Outgoing process data ....................................... 103 SYS600
Monitor Pro ....................................................... 78
P System error ....................................................... 100

Persisting alarms ................................................ 102


Preconfigurations ............................................... 155
T
Printout ................................................................ 82 Tabs
Process database ............................................... 103 Colors tab ......................................................... 79
Process events ..................................................... 94 Tabular view ........................................................ 149
Process list types ................................................. 31 Add comments ............................................... 155
Process object .................................................... 100 Edit value ........................................................ 154
Time column ................................................... 153
Q Tagout ................................................................... 57
adding ............................................................... 58
Quick Reports ..................................................... 156 editing ............................................................... 59
removing ........................................................... 59
R Template 1 .......................................................... 100
The Day type list ................................................. 189
Registration .......................................................... 82 time based logout ................................................. 12
Report data Time period start/stop ......................................... 185
exporting ......................................................... 156 Trends Display .................................................... 115
Run command procedure ................................... 185
U
S Unacknowledged alarms .................................... 104
Setting Calendar options .................................... 186

196
Contact us

1MRS758087 B/3.6.2015 © Copyright 2015 ABB. All rights reserved.


ABB Oy
Substation Automation Products
P.O. Box 614
FI-65101 Vaasa
FINLAND
Tel. +358 10 22 11
Fax. +358 10 224 1094

www.abb.com/substationautomation

You might also like