2015 Product Catalogue

Q/S&M/Variable Speed Drive/Inverter & Transducer Cat/15/01

frequency inverter

pressure transducer
VSD Product Range

variable speed drive


VSD Product Range - Variable Speed Drive Frequency Inverter

variable speed drive frequency inverter


220V single phase/380V three phase/525V three phase

Plastic Frame

Plastic Frame

Hanging Steel Frame Standing Steel Frame

2 www.vegapumps.co.za
VSD Product Range - Variable Speed Drive Frequency Inverter

DIMENSIONS
POWER SIZE
SERIES CASE MODEL ADAPTER (MM)
(KW) A B H W D d
F2053F0030L21 3.0
F2053F0040L21 4.0
F2053F0030L23 3.0
F2053F0040L23 4.0
302 F2053F0055L23 5.5 158 236 247 147 170 5.4
F2053F0040L43 4.0
F2053F0055L43 5.5
F2053F0075L43 7.5
F2053F0075L53 7.5
F2053F0110L43 11.0
F2053F0150L43 15.0
317 F2053F0185L43 18.5 218 304 320 196 203 6.5
F2053F0110L53 11.0
F2053 F2053F0150L53 15.0
F2053F0220L43 22.0
F2053F0300L43 30.0
F2053F0370L43 37.0
030 F2053F0185L53 18.5 285 457 475 195 240 9
F2053F0220L53 22.0
F2053F0300L53 30.0
F2053F0370L53 37.0
F2053F0450L43 45.0
F2053F0550L43 55.0
045 315 620 645 230 310 11
F2053F0450L53 45.0
F2053F0550L53 55.0
F2053F0750L43 75.0
075 375 725 750 290 335 13
F2053F0930L43 93.0

www.vegapumps.co.za 3
VSD Product Range - Variable Speed Drive Frequency Inverter

MODEL NAME BREAKDOWN

1: Single phase output 3: Three phase output


Input voltage: 2-220V 4-380V
Freq. range: L: 0 - 400Hz
Applicable motor: 0007 is 7.5kW, 0015 is 1.5kW
Series: F - intelligent water pump controller
Series Name

SELECTION TABLE
Applicable Rated
Output power
voltage Model Motor Current
(kW)
(HP) (A)
F0007L21 0.75 1 5.3
(1PH - 1PH)
F0015L21 1.5 2 10
220V
F0022L21 2.2 3 13
F0007L43 0.75 1 2.5
F0015L43 1.5 2 3.7
F0022L43 2.2 3 5
F0030L43 3 4 6.5
F0040L43 4 5 9.5
F0055L43 5.5 7 12.5
(3PH - 3PH) F0075L43 7.5 10 17.5
380V F0110L43 11 15 24
F0150L43 15 20 33
F0185L43 18.5 25 40
F0220L43 22 30 46
F0300L43 30 40 58
F0370L43 37 50 80
F0450L43 45 60 91
F0075L53 7.5 10 14
F0110L53 11 15 19.2
F0150L53 15 20 26.4
(3PH - 3PH) F0185L53 18.5 25 32
525V F0220L53 22 30 36.8
F0300L53 30 40 46.4
F0370L53 37 50 64
F0450L53 45 60 72.8
1 www.vegapumps.co.za
VSD Product Range - Variable Speed Drive Frequency Inverter

TECHNICAL SPECIFICATIONS

item specifications

Control Model SPWM


Input 220V: 220±15%; 380V: 380±15%; 525V: 525±15%
Output Voltage 0~input voltage
5-Digit Display & Status This shows frequency, current, speed, voltage, set pressure,
Indicator light current pressure, fault and so on
Communication Control RS-485
Operating Temperature -10~400C
Ambient Humidity 0-95% relative humidity (non-condensing)
Vibration <0.5G
Range 0.10~400.0Hz
Setting Resolution Digital: 0.1Hz; Analogue: 1% maximum frequency
Frequency Control

Output Resolution 0.1Hz


Keyboard Setting
Set by up/down keys
Mode
Analogue Setting
External voltage 4-20mA, 2-10V
Mode
Frequency limits, running frequency, frequency stop, three
Other Functions
adjustable carrier frequencies can be set separately
Electronic relay protection motor drive
Overload
(for constant torque 150%/1min)
220V: DC Voltage<200V; 380V: DC Voltage<350V;
Low Voltage
525V: DC Voltage<472V
Protection Function

220V: DC Voltage>242V; 380V: DC Voltage>420V;


High Voltage
525V: DC Voltage >578V
Instant Stop and
Restarted by frequency track after instantaneous stop
Restart
Stall Prevention Anti-stall during acceleration/deceleration run
Output short circuit Electronic circuit protection
Fin over-heating protection, restriction of reverse running,
Other functions direct start after power on, fault reset, parameter lock PID,
one-drive-more, etc.

www.vegapumps.co.za 2
VSD Product Range - Variable Speed Drive Frequency Inverter

FUNCTIONING OF OPERATOR PANEL


Press the RUN/STOP button
- If the RUN and STOP buttons flash at the same time,
the VSD is in its stop state
- If the PUMP1 indicator is on and the RUN button
flashes, this is automatic state
- If the STOP indicator flashes, the VSD is in maual
mode

Use the up and down arrows to adjust the frequency.

power on,
flash
at the stop state

flash

3 www.vegapumps.co.za
VSD Product Range - Variable Speed Drive Frequency Inverter

BASIC ADJUSTMENT
SINGLE PUMP

1. Confirm the rated parameter of the pump motor:


F002=rated frequency (factory setting=50HZ)
F003=rated voltage (factory setting=380V/220V/525V)
F007=rated current (factory setting=controller’s rated current)

2. Confirm the maximum pressure range of the pressure transmitter:


10 bar - F006=10
16 bar - F006=16
25 bar - F006=25

3. Check the motor direction of rotation:


Press STOP/RUN to choose the Debug (manual) mode - the DEBUG indicator will be on.
Press “v” or “ʌ” to change the pump’s speed, and check and change the direction of rotation.

MULTI-PUMPS

1. Establishment of pump stations:


F011 = A B
B= current pump station/pump number (eg. Pump1 = 1)
A= total number of pump stations (eg. 2 pumps in system = 2)
Note: this must be set on each pump

2. On the master controller, confirm the parameters of the pump and rated pressure range of
pressure transmitter:
F002/003/006/007 - As section 1 for a single pump

3. Check each pump’s direction of rotation:


Press the STOP button of the master controller to choose the DEBUG mode (manual) - the
DEBUG indicator will be on
Press each pump’s “v” or “ʌ” buttons to change the pump’s speed, and check and change the
direction of rotation.

AUTO RUN

1. Single pumps run automatically.


Press STOP/RUN to choose the auto mode - AUTO indicator will be on.

2. Multi-pumps run automatically


Press the STOP button on the master controller to choose the auto mode - AUTO indicator
will be on.

www.vegapumps.co.za 4
VSD Product Range - Variable Speed Drive Frequency Inverter

PARAMETERS AND FUNCTIONS

5 www.vegapumps.co.za
VSD Product Range - Variable Speed Drive Frequency Inverter

www.vegapumps.co.za 6
VSD Product Range - Variable Speed Drive Frequency Inverter

7 www.vegapumps.co.za
VSD Product Range - Variable Speed Drive Frequency Inverter

www.vegapumps.co.za 8
VSD Product Range - Variable Speed Drive Frequency Inverter

WIRING

SWITCH DESCRIPTION ON MAIN BOARD:


V: 0-10V voltage signal
I: 4-20mA current signal

AVI: remote transmissible pressure gauge 0-10V

Input polarity optional switch


PNP: Multi-function input terminal (S1-S4), FWD/REV connect to common terminal DCM
NPN: Multi-function input terminal (S1-S4), FWD/REV connect to common terminal EV

WORKING SYSTEM

9 www.vegapumps.co.za
VSD Product Range - Variable Speed Drive Frequency Inverter

OPERATOR PANEL
The digital keypad includes two parts: the display panel and keypad.
The display panel displays the parameters and shows the operation status of the AC drive
and the keypad provides a programming and control interface.

LED Run indicator light Main pump indicator light

LED Indicator

Function button

www.vegapumps.co.za 10
VSD Product Range - Variable Speed Drive Frequency Inverter

FAULT FINDING
FAULT FINDING FOR CONTROLLER

Fault Codes:
H: At stop
Status D: At acceleration
Alarm messages P: At constant speed run
Fault B: At deceleration

11 www.vegapumps.co.za
VSD Product Range - Variable Speed Drive Frequency Inverter

FAULT FINDING FOR WATER SUPPLY CONTROLLER

E.1.P: Warning for PID break detection


Parameter: F027 - The standard of the feedback pressure (set range: 0-100%).
When the feedback is under the value of F027 for longer than the time of F028, the
E1P warning will appear. Please check the water inlet, connection of the pressure
sensor, the rotation of the pump motor and if any air is present in the pump.
Note: If F028=0, the warning will be invalid.

E.2.P: Warning for lack of water


Parameter: F038 - the water detection delay.
When the external terminal detects the lack of water and the time of F038 elapses,
the E29 warning will be released. The code for the external terminal is 31.
Note: If F038=0, the protection function is invalid.

E.H.P: High pressure warning.

E.L.P: Low pressure warning.


Parameter: F039 - The protection point of high pressure (0-100%).
F040 - The protection point of low pressure (0-100%).
The delay of water out protection of high pressure and recovery.
When the pressure is higher than F039 and keeps within the time of F041, warning
EHP will be released.
When the pressure is lower than F040 and keeps within the time of F041, warning
ELP will be released.
The normal working pressure is between F039 and F040. If it exceeds the time of
F041 the alarm will automatically be released.
Note: If F041=0, the protection of high/low pressure is invalid.

E.L.B: Warning of low water level/negative pressure


Parameter: F042 - The delay of low water level/negative pressure detection warning.
Parameter: F043 - The delay of low water level/negative pressure recovery
When the external terminal (S3) detects the low water level/negative pressure signal,
it delays the ELB warning for the time of F042.
When the external terminal (S3) detects the normal signal, it auto releases the alarm
after delaying the time of F043.
Note: if F042=0, the alarm function is invalid.

www.vegapumps.co.za 12
VSD Product Range - Pressure Transducer

PRESSURE TRANSDUCER

SPECIFICATIONS
Range 16 & 25 bar
Accuracy 0.5%FS; 1%FS
Nonlinearity Full span x 0.2%
Repeatability Full span x .05%
Output 4-20mA(two wire), 0-5V, 0-10V (Three wire); 2mV/V,
3.3mV/V (PTS-210)
Input voltage 24(12~36)VDC (Amplifying signal),
10(6~12)VDC (mV output)
Operating temperature -40~800C
Compensated temperature 0~700C
Overload pressure 150%FS
Medium material Stainless steel
Electric connector Hirschman (DIN), M12, 4 pin, Bendix connector,
grand cable (custom design)
Process connector G1/4, G1/2, 1/2NPT, 1/4NPT, M12*1.5 (custom design)

13 www.vegapumps.co.za