TEST REPORT
Table Of Contents
Report No.
Page 2 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
Voltage Ratio ......................................................................................................................................3
Winding Resistance ............................................................................................................................4
No Load Losses ..................................................................................................................................5
Load Losses ........................................................................................................................................6
Efficiency...........................................................................................................................................7
Regulation...........................................................................................................................................8
Applied Voltage ..................................................................................................................................9
Induced Voltage ................................................................................................................................ 10
Insulation Resistance ........................................................................................................................ 11
Insulation Capacitance...................................................................................................................... 12
Lightning Impulse ............................................................................................................................ 13
Current Transformer Test ................................................................................................................. 15
ABB
TEST REPORT
Asea Brown Boveri Ltda.
Report No.
Page 1 of 15
Factory: Asea Brown Boveri Ltda. Test Department:
Calle16 # 15-124 La Popa Dosquebradas
(Risaralda-Colombia)
ISO 9001 - ISO 14001 – OHSAS 18001 Date of Issue:
Issued by:
Signature: ___________________________________
Approved by:
Signature: _________________________________
Tests Room Engineer Quality Manager
Customer: Test Object: Serial No.:
Customer Ref.:
Customer Specification:
Highest Rated Power:
Voltage:
Highest Rated Current:
BIL:
Connection:
Phase Displacement:
Frequency:
Cooling Condition(s):
Oil Temp. Rise:
Winding Temp. Rise:
ABB Reference:
Product Reference:
Order No.:
Name Plate No.:
Inspection and Test Plan:
Performed and Approved Tests:
Voltage Ratio
Winding Resistance
No Load Losses
Load Losses
Efficiency
Regulation
Applied Voltage
Induced Voltage
Insulation Resistance
Insulation Capacitance
Temperature Rise
Current Transformer Test
Applied Standards:
Witnessed by:
Comments:
ABB
TEST REPORT
Voltage Ratio
Report No.
Page 3 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
First Terminals:
Second Terminals:
Phase Displacement:
Tap Position Rated Voltage (kV) Measured Ratio
First
Terminals
Second
Terminals
First
Terminals
Second
Terminals
U-PN
x-z
V-PN
y-x
W-PN
z-y
Calculated
Ratio
(with
Multiplier)
Maximum
Difference
(%)
Remarks: Was checked the polarity and phase deviation.
ABB
TEST REPORT
Winding Resistance
Report No.
Page 4 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
Reference Temperature:
Tested Terminal Names:
Average Oil Temperature:
Tap Resistance Between Terminals (W )
Positions U-PN V-PN W-PN
Average
Resistance
(W /Phase)
Resistance at
Reference Temp.
(W /Phase)
1
2
3
4
5
Reference Temperature:
Tested Terminal Names:
Average Oil Temperature:
Tap Resistance Between Terminals (W )
Positions x-y y-z z-x
Average
Resistance
(W /Phase)
Resistance at
Reference Temp.
(W /Phase)
-
ABB
TEST REPORT
No Load Losses
Report No.
Page 5 of 15
Serial No.:
1 Corrected to Sinusoidal Wave
Test Date: Test Engineer: Test Department:
Supplied Terminals: Tap:
1st O pen Terminals: Tap:
2nd Open Terminals: Tap:
Power Base: Rated Power:
Average Oil Temperature:
Measured Values Guaranteed
Vappl.
. xVmean
Vrms
1 11
1.11xVmean
(kV)
Vrms
(kV)
IA
(A)
IB
(A)
IC
(A)
Losses
(kW)
Losses1
(kW)
Current Losses
(kW)
Current
ABB
TEST REPORT
Load Losses
Report No.
Page 6 of 15
Serial No.:
1 Corrected to Reference Temperature
2 Corrected to Instrument Error
Test Date: Test Engineer: Test Department:
Supplied Terminals: Reference Temperature:
1st Shorted Terminals: Power Base:
2nd Shorted Terminals:
Connection Measured Corrected1 Guaranteed
Tap Positions
Supplied 1st
Shorted
2nd
Shorted
Supplied
Winding
Vrated
(kV)
Temp.
(°C)
Voltage
(kV)
Current
(A)
Losses
(kW)
Imp.
(%)
Losses
(kW)
Imp.
(%)
ABB
TEST REPORT
Efficiency
Report No.
Page 7 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
Test Condition:
1st Terminals:
2nd Terminals:
Power Base:
Tap Positions Power Factor
0.80 0.80 0.80 0.80
1st Load Factor
Terminals
2nd
Terminals 25 % 50 % 75 % 100 %
Test Condition:
1st Terminals:
2nd Terminals:
Power Base:
Tap Positions Power Factor
0.90 0.90 0.90 0.90
1st Load Factor
Terminals
2nd
Terminals 25 % 50 % 75 % 100 %
Test Condition:
1st Terminals:
2nd Terminals:
Power Base:
Tap Positions Power Factor
1.00 1.00 1.00 1.00
1st Load Factor
Terminals
2nd
Terminals 25 % 50 % 75 % 100 %
ABB
TEST REPORT
Regulation
Report No.
Page 8 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
1st Terminals:
2nd Terminals:
Power Base:
Tap Positions Power Factor
1st
Terminals
2nd
Terminals
1.00 0.90 0.80
ABB
TEST REPORT
Applied Voltage
Report No.
Page 9 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
Frequency (Hz):
Supplied Terminals Voltage (kV) Duration (s)
ABB
TEST REPORT
Induced Voltage
Report No.
Page 10 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
Tap Position For HV Terminals:
Supplied Terminals:
Frequency (Hz):
Tested Terminals Grounded Terminals Voltage (kV) Duration (s) P.D. Measured
ABB
TEST REPORT
Insulation Resistance
Report No.
Page 11 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
Test Condition:
Applied Voltage:
Terminals Time
Tested Grounded Guard
Temp.
(°C)
Measured
Ratio 15s 30s 45s
Time
1m 0s 2m 0s 3m 0s 4m 0s 5m 0s 6m 0s 7m 0s 8m 0s 9m 0s
Tiempo
10m 0s
Remarks: Values in M -ohm
Test Condition:
Applied Voltage:
Terminals Time
Tested Grounded Guard
Temp.
(°C)
Measured
Ratio 15s 30s 45s
Time
1m 0s
Remarks: Values in M -ohm
ABB
TEST REPORT
Insulation Capacitance
Report No.
Page 12 of 15
Serial No.:
Fp(20) = Fp(T) / K
Doble:
Fp(20) = Power Factor corrected to 20C
Fp(T) = Power Factor measured at T degrees
K = Correction Factor (from Table below)
T (C) 10 15 20 25 30 35 40 45 50 55 60 65 70
K: BIL < 750 kV 0.8 0.9 1.0 1.12 1.25 1.4 1.55 1.75 1.95 2.18 2.42 2.7 3.0
K: BIL >= 750 kV 1.01 0.99 1.00 1.02 1.05 1.08 1.12 1.17 1.23 1.31 1.41 - -
ANSI:
T (C) 10 15 20 25 30 35 40 45 50 55 60 65 70
K 0.8 0.9 1.0 1.12 1.25 1.4 1.55 1.75 1.95 2.18 2.42 2.7 3.0
Test Date: Test Engineer: Test Department:
Applied Voltage for Capacitance:
Applied Voltage for Power Factor:
Equipment Type:
No Test Tested Grounded Guard (UST) Capacitance
[ pF ]
Power Factor
at 20 C (%)
ABB
TEST REPORT
Lightning Impulse
Report No.
Page 13 of 15
Serial No.:
1 Legend:
ANSI: Reduced Full-Wave RFW IEC: Reduced Full-Impulse RFI
Full-Wave FW Full-Impulse FI
Reduced Chopped Wave RCW Reduced Chopped Impulse RCI
Chopped Wave CW Chopped Impulse CI
Reduced Front-of-Wave RFoW
Front-of-Wave FoW
Test Date: Test Engineer: Test Department:
Test
Type 1
Tested
Terminal
Required
Voltage
(kV)
Test Voltage
(kV)
Tap
Position
Impulse
Shape
(m s)
Oscillogram
Number
ABB
TEST REPORT
Lightning Impulse
Report No.
Page 14 of 15
Serial No.:
1 Legend:
ANSI: Reduced Full-Wave RFW IEC: Reduced Full-Impulse RFI
Full-Wave FW Full-Impulse FI
Reduced Chopped Wave RCW Reduced Chopped Impulse RCI
Chopped Wave CW Chopped Impulse CI
Reduced Front-of-Wave RFoW
Front-of-Wave FoW
Test Date: Test Engineer: Test Department:
ABB
TEST REPORT
Current Transformer Test
Report No.
Page 15 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
Checkup
Position Name Taps Measured Ratio Power
(VA)
Class Measured
Ratio
Measured
RatioPower system protection philosophy
TEST REPORT
Table Of Contents
Report No.
Page 2 of 15
Serial No.:
Test Date: Test Engineer: Test Department:
Voltage Ratio ......................................................................................................................................3
Winding Resistance ............................................................................................................................4
No Load Losses ..................................................................................................................................5
Load Losses ........................................................................................................................................6
Efficiency...........................................................................................................................................7
Regulation...........................................................................................................................................8
Applied Voltage ..................................................................................................................................9
Induced Voltage ................................................................................................................................ 10
Insulation Resistance ........................................................................................................................ 11
Insulation Capacitance...................................................................................................................... 12
Lightning Impulse ............................................................................................................................ 13
Current Transformer Test ................................................................................................................. 15
ABB
TEST REPORT
Asea Brown Boveri Ltda.
Report No.
Page 1 of 15
Factory: Asea Brown Boveri Ltda. Test Department:
Calle16 # 15-124 La Popa Dosquebradas
(Risaralda-Colombia)
ISO 9001 - ISO 14001 – OHSAS 18001 Date of Issue:
Issued by:
Signature: ___________________________________
Approved by:
Signature: