• A switchyard is a part of an electrical Generation, Transmission,
and Distribution system. Substations transform voltage from high to
low, or the reverse, or perform any of several other important
functions.
• Switchyards generally have Breakers, Isolators , CTs ,PTs , Bus bars,
protection and control equipments, transformers ,grounding wires
and switches, disconnects and metering devices, etc.
3
132 KV Switchyard
• Constructional Overview
• Testing
• Operation & Maintenance
• Protection
• Conclusion
4
Constructional Overview
• Two main Bus-1& 2 bars – ACSR TWIN MOOSE Conductor.
Both are used to energize any abnormality with Bus-coupler for un
interruption Operation.
• Current rating 2000A,Fault Level 40KA for 3 Sec.
• Bay Equipment to Equipment Connection-ACSR Moose
Conductor.
• CTs are connected in Series , PTs are connected across supply.
• STG Generator Transformer Bay -01 No.
• Start-up S.A.T. Bay -01 No.
• 132 KV overhead line circuit Bay -02 No.s
• 132 KV Transfer Bus coupler Bay - 01 No.s
• Fully Equipped Bus PT Bay -02 No.s
5
TRNSFER BUS
COUPLER BAY
6
Constructional Overview
• Total no. of Towers- 28 (A/B/C/D/E)
• Total no. of SF6 CB- 5
• Total no. of PT-12
• Total no. of CT-12
• Total no. of LA-12
• Total no. of Wave Trap -2
• Total no. of Isolators- 22
• Total no. of CVT- 6
• Total no. of BPI- 18
• Total no. of EMPT -6 7
GEN BAY SAT BAY
8
Line# 1 & 2
BAY
B/C BAY
9
Bus Bar
Protection Scheme
10
• Rated Voltage 145 KV
• Rated Current 1250 A Frequency 50 Hz
• Breaking Capacity 40 KA
• Making Capacity 100 KVP
• Short Time Rating 40 KA for 3 sec
• Operating sequence
O-0.3 sec - CO- 3 MIN- CO
• Trip and Closing Coil Voltage 110V DC
• Motor Supply 240 V
Testing for SF6:-
Applied Volt 5KV DC
•IR Value
> 20 GΩ CB ON
[R(Y+B+E),Y(R+B+E),B(R+Y+E)]
> 50 GΩ CB OFF
[R-R’,Y-Y’,B-B’]
•Applied current 100 A DC
Contact Resistance test: R-ø ,Y-ø B-ø < 34 μΩ
•SF6 Gas pressure setting 5.4 bar.
•Breaker , Closing Time 72 ms
Opening Time -29 ms Each Phase
These are used to operate on the fault on line or X-mer depending upon where it is
connected. This isolates the faulty line or equipments from the live portion of the sub
station by opening automatically through protective relays; control cables etc. in
11
definite time.
Make CGL
No of Core 2
Ratio 132KV/√3/110V/√3/110V/√3
Class 0.2/3P
Burden 100 VA/100 VA
a) Measurement of voltage
b) Provide secondary voltage for
protection.
Make CGL
Type Outdoor
No of Core 2 Core
Ratio 400-800/1-1A
Class 0.25/0.25
Burden 30 VA
ISF <= 5
a) Measurement of current
b) Protection current circuits when currents
passed through protective relays like
Distance protection, Backup protection. 12
Common Testing's Required for CT & PT:-
•IR Test :
Applied Volt 5KV DC
> 10 GΩ [Prim – Earth, Prim – Core]
Applied Volt 1KV DC
> 500 MΩ [Core-Earth]
•Winding Resistance Test:
< 5-6 Ω [Ex: R-ø ,1s1-1s2,1s1-1s3]
•Ratio Test :
[Prim current 400-800]/ [Sec. current 1-1A]
[Ex: R-ø ,1s1-1s2,2s1-2s2]
•Polarity Test :
[Ex: R-ø ,1s1-1s2,2s1-2s2] Press
P1 P2
S1 S2
Press Back
14
Make
OBLUM ELECTRICAL
Type METAL OXIDE
LD DISCHARGE CLASS Class-3
Rated Voltage 60 KV
Rated Frequency 48-62 HZ
Maximum continuous Operating
102 KV
Voltage
Nominal Discharge Current 10 KA
MFD 2010
Make
OBLUM ELECTRICAL
Clamp
Tension
Suspension
17
OPERATIONAL MODES
• Normal Operation :
Synchronization Press
Start Up / Import Press
18
Move Next
OUTGOING OHL #1 BAY OUTGOING OHL #2 BAY
DS-5 DS-5
DS-4 DS-4
CB CB
DS-3 DS-3
DS-2 DS-1 DS-2 DS-1
MAIN -2 CUM TRANSFER BUS <--- GT BAY <--- STN. TRFO BAY
MAIN -1 BUS
CB
CB CB
DS-4 DS-4
STN. TRFO
G. TRFO
Gen CB
G GENERATOR
U.A.TRFO LOAD 19
OUTGOING OHL #1 BAY OUTGOING OHL #2 BAY
DS-5 DS-5
DS-4 DS-4
CB CB
DS-3 DS-3
DS-2 DS-1 DS-2 DS-1
MAIN -2 CUM TRANSFER BUS <--- GT BAY <--- STN. TRFO BAY
MAIN -1 BUS
CB
CB CB
DS-4 DS-4
STN. TRFO
G. TRFO
G GENERATOR
U.A.TRFO
LOAD
LOAD 20
Press Back
OUTGOING OHL #1 BAY OUTGOING OHL #2 BAY
DS-5 DS-5
DS-4 DS-4
CB CB
DS-3 DS-3
DS-2 DS-1 DS-2 DS-1
MAIN -2 CUM TRANSFER BUS <--- GT BAY <--- STN. TRFO BAY
MAIN -1 BUS
CB
CB CB
DS-4 DS-4
STN. TRFO
G. TRFO
G GENERATOR
U.A.TRFO
LOAD
LOAD 21
Press Back
MAIN -2 CUM TRANSFER BUS
MAIN -1 BUS
CB
CB Tripping Prt.
DS-4
1. Close DS-3
BUS COUPLER CUM 2. Open DS-3 & DS4
TRNSFER BREAKERS
Close DS-3
OUTGOING OHL #1 BAY
22
MAIN -2 CUM TRANSFER BUS
MAIN -1 BUS
DS-2
DS-1
DS-3
CB Tripping Prt.
DS-1 DS-2
CB
DS-4
23
Press Back
MAIN -2 CUM TRANSFER BUS
MAIN -1 BUS
CB
Protection
Tripping fuse Out
CB Tripping Prt.
DS-4
1. Open DS-1
BUS COUPLER CUM 2. Close DS-1
TRNSFER BREAKERS
24
Press Back
Maintenance
• CTs, PTs ,all auxiliaries terminal tightness.
• SF6 Breaker Gas pressure monitoring &
maintain.
• Stone,metnal layer maintain across the area.
• Monitoring & diagnosis using Hotspot detector
or temperature scanner .
• Isolator & contact cleaning on scheduled.
25
Thermal Sensor / Hot Spot Detector
26
27
Protection
28
29
30
Protection System
• A series of devices whose main purpose is to
protect persons and primary electric power
equipment from the effects of faults.
Why A System Needs Protection?
Protected
Control Equipment
Relay
VTs
How Do Relays Detect Faults?
• When a fault takes place, the
current, voltage, frequency, and other electrical variables
behave in a peculiar way. For example:
– Current suddenly increases
– Voltage suddenly decreases
• Relays can measure the currents and the voltages and
detect that there is an overcurrent, or an undervoltage, or
a combination of both
• Many other detection principles determine the design of
protective relays
Main Protection Requirements
• Reliability
• Selectivity
• Speed
• Sensitivity
Typical Short-Circuit Type Distribution
Single-Phase-Ground: 70–80%
Phase-Phase-Ground: 17–10%
Phase-Phase: 10–08%
Three-Phase: 03–02%
Following type of Protection Curve
used in our plant
1. INSTANTANEOUS/High Speed
2. DMT: (Definite Mean Time-I>>/high set)
3. IDMT: (Inverse Definite Minimum Time)
a. SI - Standard Inverse (I>)
b. VI - Very Inverse
c. EI - Extreme Inverse
d. LTI - Long Time Inverse
Formula for Relay Operating Time
calculation
Operating Time:
= A X TMS
Ir C - 1
o A=0.14 & C=0.02 for SI
o A=0.13.5 & C=1.0 for VI
o A= 80 & C= 2.0 for EI
o A=120 & C=1.0 for LTI
o Ir= I(multiple of fault current) / Iset
Example:
• If FLC=100A, % setting =105,
• Operate time = 10sec Then TMS=?
If CTR =150/1A, In=150, Isec=1A
51