Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

HT Panel

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 9

BILL OF MATERIAL OF HT PANEL FOR

S. NO DESCRIPTION RATING

Voltage - 33kV
Current - 1250A,
1 VACUUM CIRCUIT BREAKER (VCB)
Capacity - 31.5kA
Type - Indoor Type

Current - 1250 A
2 BUSBAR Area = 80x10
Type - Aluminium

RATIO: 100-50/5-
3 CURRENT TRANSFORMER 5A
CLASS : 0.5

4 POTENTIAL TRANSFORMER RATIO:


33KV/√3/110V/√3

Voltage - 33kV
5 PT FUSE LINKS
Current - 3.15A

6 DIGITAL AMMETER WITH ASS N/A


7 DIGITAL VOLTMETER WITH VSS N/A

3OC+1EF
8 IDMT RELAY
NUMERICAL

9 MASTER TRIP RELAY N/A


10 AUX RELAY FOR TRF PROTECTION N/A

ANTIPUMPING RELAY AUX. CONTACTOR CONTACTOR


11
2NO+2NC 2NO+2NC

12 INDICATING LAMP 24V DC {Red, Green, Red,


Blue, Amber,
Green }=6 lamp
13 INDICATING LAMP 63.5V AC {Red, Yellow,
Blue }=3 lamp

Current - 6A,
14 MCB Capacity - 10kA
Type - Single pole

Current - 6A,
15 MCB Capacity - 10kA
Type - Double pole

16 230V AC/24V DC
POWER PACK (7AH)
17
ANNUNCIATOR WITH PUSH BUTTON Power - 8W
18 Voltage - 24V DC
HOOTER

19 TNC SWITCH BREAKER


CONTROL SWITCH
20 2P 2W WITH OFF
SELECTOR SWITCH 6A
21 STRIP HEATER Power - 100W
Voltage 240V AC
Temp - 0-60ºC
22 THERMOSTATE
Voltage 240V AC
23 EMERGENCY STOP PUSH BUTTON PUSH BUTTON

24 3 PIN POWER SOCKET Current - 5A

25 LED BULB N/A

26 DOOR LIMIT SWITCH N/A

27 TOGGLE SWITCH N/A

28 NEUTRAL LINK 32 A

29 C.T. TERMINAL 6mm WITH 2 END POINT 6mm

30 P.T. TERMINAL 6mm WITH 2 END POINT 6mm


BILL OF MATERIAL OF HT PANEL FOR 33KV
TECHNICAL SPECIFICATIONS PURPOSE QTY
230V AC SPRING CHARGING MOTOR
24V DC CLOSING COIL
24V DC SHUNT TRIP COIL Vacuum circuit breakers (VCBs) are used in high
AUX. CONTACT: 6NO+6NC transmission (HT) panels because they are more
1
MECHANICAL ON/OFF PUSH BUTTONS efficient and suitable for high voltage and high
power transmission systems.

The obvious and easy way to identify


the busbar capacity rating on an
electrical panel is to look at the main The primary function of a bus bar is to transport
breakers. If the main breakers are and distribute electricity, contributing to the 1
1250A, the bus bars are rated for at efficiency of systems.
least 1250A.

CORE-1: 15VA CLASS : 0.5, METERING


CORE-2: 15VA, 5P10-PROTECTION
Use for metering and Protection 3
INDOOR SINGLE PHASE RESIN CAST

Burden - 100VA, CLASS: 0.5


Use for metering voltage 3
INDOOR SINGLE PHASE RESIN CAST
A PT Fuse is a medium voltage,,
current limiting, fuse with a high
interrupting rating,. The PT fuse is Protects potential transformers by limiting
used to protect the primary windings current and interrupting circuits before they're 3
of a potential transformer or control exposed to the full impact of an overcurrent
power transformers

For measuring value of current For measuring value of current 1


For measuring value of current For measuring value of current 1

a relay can be stated as the actuation to protect power systems from faults and
DC voltage/current of the coil and the abnormalities by isolating the faulty component 1
voltage and current carrying capacity from the healthy system
of the output contact. The output
switches are usually double throw
(with NO and NC contacts) and the
number of poles can be specified.

The purpose of a master trip relay is to provide


It is operates only on protection trip insulation between the protection relay and the 1
command given by some other breaker tripping coil, and to reduce the cost of
protection relays like motor protection wiring
relay or feeder protection relay.
Electromechanical relays are An auxiliary relay is used for trip protection to
common, known for their reliability continuously monitor the trip circuit of a circuit 2
and ability to handle high currents. breaker and to provide alarms when faults occur.
Solid-state relays, on the other
hand, offer faster switching times
and longer lifespan due to the
absence of moving parts.

Electromechanical relays are to prevent the breaker from closing unexpectedly


common, known for their reliability after tripping. If the TNC switch fails (Trip normal
and ability to handle high currents. close) or there is any problem with the CB (circuit 1
breakers) closing circuit, the continuous CB
Solid-state relays, on the other (circuit breakers) close command can be
hand, offer faster switching times extended to the closing coil.
and longer lifespan due to the
absence of moving parts.

for indicating whether function is ON o for indicating whether function is ON or OFF 1

for indicating whether function is ON o for indicating whether function is ON or OFF 1

protect electrical circuits and


protect electrical circuits and equipment from
equipment from short circuits and 10
short circuits and overloads
overloads

protect electrical circuits and


protect electrical circuits and equipment from
equipment from short circuits and 2
short circuits and overloads
overloads

supply DC axillary supply to the Trip / used to supply DC axillary supply to the Trip /
Close coil of the Circuit breakers when Close coil of the Circuit breakers when AC input is 1
AC input is not available. not available.
to monitor the machine functions and alert
1
for alarm function operators to abnormal conditions or events

for alarming whenever fault occurs 1


use as alarm if there is any fault occurs

ON or OFF device 1
Trip to neutral or trip to close
ON or OFF device ON or OFF device 1

They are used for both forced and natural


1
Heating purpose convection air heating.

for sensing temperature 1


temperature sensing element
To stop machinery quickly to reduce the risk of
Emergency switch injury or to stop a dangerous interruption in 1
workflow

operate class III electrical appliances operate class III electrical appliances such as
such as refrigerators, microwave refrigerators, microwave ovens, and other metal 1
ovens, and other metal body body appliances.
appliances.
whether light is ON or OFF Indicating purpose 1
A door limit switch is a switch that
is used for automatic detection and
for sensing the opening and closing A door limit switch is a mechanical device that
of a door or the presence of an senses when a door is opened or closed and 1
object. interrupts the electrical current in a panel.

A toggle switch is a mechanical switch


that controls the flow of electricity in
electronic devices by allowing or allows users to turn things on or off, or to switch
interrupting the current. 1
between two states or options

A 32A neutral link is used to terminate


neutral wires in electrical circuits. A 32A neutral link is used to terminate neutral
2
wires in electrical circuits.

6 sq.mm Feed Through Terminal


Blocks are the most Versatile CT connectors are a miniature wire-to-board and
terminals for control, Automation, wire-to-wire interconnect solution and has
Instrumentation and Power 10
proven performance in its harness making
Distribution applications. capability.

Feed-through terminal block


CT connectors are a miniature wire-to-board and
nominal voltage: 1000 V
wire-to-wire interconnect solution and has
nominal current: 41 A number 10
proven performance in its harness making
of connections- 2 number of
capability.
positions: 1
MAKE